Home
DIGITRAcE
Contents
1. 80 to Max 700 C High Temp Alarm Enter in this field the value at which when exceeded you want the DigiTrace NGC 20 control unit to generate a high a temperature alarm This High Temperature condition will be monitored by Temperature sensor T1 only Low Tern Alarm ts Low Temp Alarm Min 80 to Max 700 C Temperature Alarm Filter Enter in this field the value at which when exceeded you S00 sec want the NGC 20 control unit to generate a Low Temperature Alarm This Low Temperature condition will be monitored by Temperature sensor T1 only z 2 Temperature Alarm Filter Min 0 to Max 59940 seconds Can be seen as an alarm delay This means that when the Back i Fig 17 1 Temperature Setup screen 1 temperature drops below the Low Alarm Set point the DigiTrace NGC 20 Control unit will only trigger an alarm when the value entered in the Low Alarm Filter is timed out This means that if immediate action of the alarm output is required that the Low Alarm Filter value should be set at 0 sec Any other value will result in a delay The operation of the High Alarm Filter is the same Tap on Apply to confirm your new settings Tap Back when ready 00 21 2 Fail Safe mode and High Limit Cut Out Set point The Fail safe mode defines the output of the DigiTrace NGC 20 output switch in case of a sensor failure Tap on the entry field behind Fail Safe mode for more options Temperature Settings
2. Limiter Normal operation Tripped Latch Temporarily Disabled Safety Limiter Temperature Shows the temperature actually being measured by the Limiter RTD Ifthis value exceeds the Safety Limiter set point the Safety Limiter will trip open Once the Safety Limiter has tripped a manual intervention will be required to Reset Rearm the Safety Temperature Limiter Resetting the safety Temperature limiter will only be possible once all process conditions have returned to a safe state The Limiter Temperature has dropped below the Limiter Temperature Set point Safety Limiter Temperature Set point This field holds the Safety Limiter set point This value should be chosen in accordance with the Temperature Class of the area in which the heating application is installed T class T4 T3 T2 or the maximum surface temperature allowed for the heating device assuming this is a lower temperature Since the Safety Temperature Limiter is a safety device it requires a special procedure to write a new set point to the Temperature limiter Tap in the Safety Limiter Setpoint field to start the write procedure This will open a new screen 04 23 1 Safety Limiter Setpoint Safety limiter setpoint Safety Limiter Cut Out Enter the new set point by tapping on the numeric pad Hit a Enter to confirm the new Limiter Cut Out set point This will g open a new screen called Safety Limiter Cut Out Man l piis a 789 456m 1
3. Should you have any questions concerning this Agreement or if you want to contact Pentair Thermal Management for any reason please write to HOUSTON 7433 Harwin Drive Houston TX 77036 Tel 1 713 868 4800 Fax 1 713 868 2333 pentairthermal com 1 4 User Responsibilities The performance reliability and safety of your heat tracing system depend on proper design selection and installation The DigilTrace NGC 20 CMA will help you to configure and monitor a system that meets your requirements but it is only a tool It assumes that your input is accurate that you are familiar with heat tracing system design and configuration and that you will ensure that all components of the heat tracing system are installed maintained and used as intended The configuration of the Digilrace NGC 20 handheld should be reviewed by a knowledgeable engineer to ensure it is appropriate for your application Additional information relating to safety design and installation is contained in Design Guides Installation Manuals Data Sheets and other literature available from Pentair Thermal Management Be sure to consult these documents as needed 1 5 Safety Warnings There are important safety warnings which are shipped with Pentair Thermal Management products and that are also printed in DigiTrace NGC 30 Installation Manual INSTALL 112 and NGC 20 installation manual INSTALL 130 Be sure to read understand and follow these safety warnings to reduce the r
4. Temperature Fall Mode Fail Off Last Yo Cancel Figure 9 9 Temperature Settings Temperature Fail Mode screen The different Fail modes supported by the DigiTrace NGC 20 are Fail Off meaning that if the control sensor s of this DigiTrace NGC 20 unit should fail the output switch will open Use this for all circuits where keeping the heating cables permanently powered could cause overheating Fail On meaning that if the control sensor s of this DigiTrace NGC 20 unit should fail the output switch will be permanently close This is the preferred option for freeze protection lines and most self regulating heating systems Last this Fail Mode is only applicable to the control mode PASC or Proportional Ambient sensing The Fail Safe mode Last will control the output in a similar manner as it was doing before the sensor s failed This Alternate ON OFF switching will be time based only there will be no relation to temperature Fixed The Fail Mode Fixed will alternate the control output ON and OFF at a certain interval Choose the desired fail safe mode from the list by tapping on that field Cancel will bring you back to the previous screen as shown in Figure 9 8 22 9 7 Setting the High Limit Cut Out Set point Tap in the field of the High Limit Cut Out This will open the numeric key pad Enter the new High Limit Cut Out set point and confirm the new set point by tapping Enter
5. Temperature Settings Temperature Settings Fall Mode Fall Off Fail Mode o Sou High Limit Cut Out AASE Latch Temperature Alarms No Yes Latch High Temperature Cut Out Alarm w No Yes Control Tags Other Back Apply Figure 9 10 Temperature Settings Temperature Fail Mode screen The High Limit Cut Out actually works as a temperature limiter which can be configured to operate as either a latching or non latching type When the Latching button is set to YES than each time an alarm has occurred the Alarm needs to be manually reset When set to NO than the alarms will be self healing and will disappear when the alarm condition is no longer present Confirm your new settings by tapping the Apply button After that tap on Back to return to Figure 9 1 NGC 20 Configuration screen 9 8 Configuring the Digifrace NGC 20 Temperature Sources DigiTrace NGC 20 units can be configured to read from various types of temperature sources temperature sensors Use the following screens to configure the DigiTrace NGC 20 control unit Tap on Temp Source Settings Figure 9 1 NGC 20 Configuration screen NGC 20 Configuration NGC 20 Configuration Temperature Settings Temp Source Settings Electrical Settings Safety Limiter Alarm Masks k Controller Settings Figure 9 11 NGC 20 Configuration screen This will open a new screen as is shown on Figure 9 12 Temper
6. The following pages will focus on the features supported in mixed mode only DigiTrace NGC 20 units will automatically detect in which mode they are operated stand alone in a network with DigiTrace Supervisor or in a mixed mode system together with an NGC UIT the general operation and use of the NGC CMA remains unchanged 17 1 Initial Setup of the unit in Mixed Mode After the program is started the start up screen will be visualised The start up screen allows users to configure the unit to their personal needs and process requirements DigiTrace Configuration Utility Main screen The Tab Configure initiates the Bluetooth device discovery i process Configuration and Monitoring Assistant The tab Settings allows setting the Language Temperature units and About shows the software revision The tab Exit closes the application Begin the initial configuration by tapping on Settings on the start up screen This will open the Setup screen as shown in Figure 17 1 Figure 17 1 Startup screen 18 CHANGING MAIN SETTINGS OF THE USER INTERFACE SCREENS Setup Setup About shows the software version of the DigiTrace _ _ _ Configuration Utility Software Languages Allows selecting a convenient language of the user interface software Temperature Units Sets the temperature units of the Digilrace Languages NGC CMA Supported are degrees Celcius and degrees Fahrenheit The
7. 20 Tag Figure 8 11 Temp Set point Numeric Screen Enter the desired Tag by using the onscreen keyboard Tap OK when finished For this example the new tag will be Pipe 1 8 5 Changing the NGC 20 console units Tap on the field Console units to change the readout of the DigiTrace NGC 20 Control units display Console Units Console Units Fahran heit Cancel Figure 8 12 NGC 20 Console Units screen Tap on the desired console units ie 8 6 Load Shed Temperature Source Communications time out Load shedding is a control mode that can be programmed and initiated only by an external communicating device which overrides temperature control and forces the output of the controller OFF until the override is removed When using an external device DigiTrace Supervisor Software or a DCS a load shedding command is continually broadcast over the communications network When power Is applied the controller delays energising its trace by x number of seconds where x is equal to the last digit in its network address If the load shed function is enabled the controller will go into load shed mode before it turns its output on It will then look for the broadcasted load shed command If the controller receives the load shed command before it times out it will remain in load shed mode and the output will remain off as long as the module receives a regular broadcast of the
8. Bluetooth Discovery Please walt Discovering devices B 8 Back Continue Figure 7 2 Bluetooth Discovery screen Searching for devices In background the device will scan for all DigiTrace NGC 20 controllers which are within range of the Bluetooth communications Ensure that all DigiTrace NGC 20 units are powered up Bluetooth Discovery Process building the device inventory list Bluetooth Discovery Please select the device you Wish to connect to Scan for Devices Back Continue Figure 7 3 Bluetooth Discovery screen one device found When searching is complete all devices in range will be listed on the screen Example For this example the only device that is found is NGC 20 1 If more than one DigiTrace NGC 20 control unit is in range all units will be listed on the screen as is shown on Figure 7 4 Bluetooth Discovery Process selecting device Bluetooth Discovery Please select the device you wish to connect to a ee Figure 7 4 Bluetooth Discovery screen finding 2 devices Now select the device you want to connect to by tapping on the device name When a device is selected the background color will be black see NGC 20 1 Next tap on Continue to go on to the Main configuration screen If devices are not showing up repeat the device discovery process by simply tapping on Scan for Devices once more 10 8 CONFIGURING DIGITRA
9. It will then look for the broadcasted load shed command If the controller receives the load shed command before it times out it will remain in load shed mode and the output will remain off as long as the module receives a regular broadcast of the command If the controller does not receive the load shed command within the timeout period it will energise its output and resume normal operation The timing of this broadcast and the timeout value can vary between 30 seconds and 10 minutes A total of 16 different Load shedding zones can be defined 48 Load Shedding 1 Figure 20 1 Coftrofier Settings L Shedding Fnabled Shedding Fail Safe Goabled C fone 1 Shedding Enabled _J Zone 2 Shedding Enabled L Zone 3 Shedding Fnabled _ Zone 4 Shedding Enabled fone 5 Shedding Enabled _ Zone 6 Shedding Enabled L Zone 7 Shedding Enabled Load Shedding 1 Load Pee e Controller Settings Load Shedding 1 If a load shedding command is present the controller will continue to hold the output OFF until one of two conditions occurs 1 The zone definition flags of an external communicating device which initiated load shedding clears and the command to terminate load shedding mode is issued 2 Communications are interrupted between the controller and its communicating device as in the case of a damaged communications wire If communication ceases for a specified timeout value the controller will ret
10. Palle 5 Cancel Figure 23 6 Limiter cut out temperature updated successfully After the new set point has been successfully updated a pop up message as shown in Figure 23 6 confirming the new set point has been successfully updated Note that the new set point may differ 1 or 2 degrees from the selected values This is caused by rounding up or rounding down the set point while it is been converted by the internal electronics 23 2 Resetting Safety Temperature Limiter Once the safety Temperature limiter has tripped it will need to be reset in order to restore normal operation Resetting the Safety Temperature limiter will only be possible after safe operating conditions have returned Look at Fig 7 4 in order to find see where the RESET button is located inside the enclosure Reset protection Password Enter 547 to continue Figure 23 7 Resetting rearming the Safety temperature Limiter Resetting the safety temperature limiter is a safety Function therefore the Reset operation is protected by a password in order to prevent the safety temperature limiter form being reset unintentionally The safety temperature limiter can be reset from the Digilrace NGC CMA In order to do so tap on Reset Tripped Limiter This will open a new screen as is shown in Figure 23 7 Use the numeric Key pad to enter the number shown in blue on the top of the screen and tap enter Successfully Reset Tripped Lim
11. REP RESENTATIVES BE LIABLE FOR DAMAGES OF ANY KIND INCLUDING WITHOUT LIMITA TION ANY LOSS DAMAGE OR DELAY OR FOR ANY LOST PROFITS LOSS OF USE INTERRUPTION OF BUSINESS OR FOR ANY COMPENSATORY SPECIAL INCIDENTAL CONSEQUENTIAL INDIRECT DAMAGES HOWEVER ARISING INCLUDING NEGLIGENCE OF ANY KIND ARISING OUT OF OR IN CONNECTION WITH THE USE OF OR THE INABILITY TO USE THE SOFTWARE OR THIS AGREEMENT EVEN IF PENTAIR THERMAL MANAGEMENT HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES FURTHER IN NO EVENT SHALL PENTAIR THERMAL MANAGEMENT ITS AFFILIATES DIRECTORS OFFICERS SHAREHOLDERS EMPLOYEES OR OTHER REPRESENTATIVES BE LIABLE TO YOU IN AN AMOUNT GREATER THAN THE AMOUNT ACTUALLY PAID BY YOU IF ANY FOR THE SOFTWARE YOU FURTHER AGREE THAT REGARDLESS OF ANY STATUTE OR LAW TO THE CON TRARY ANY CLAIM OR CAUSE OF ACTION ARISING OUT OF OR RELATED TO USE OF THE SOFTWARE OR THE TERMS AND CONDITIONS MUST BE FILED WITHIN ONE 1 YEAR AFTER SUCH CLAIM OR CAUSE OF ACTION AROSE OR BE FOREVER BARRED INDEMNITY To the extent allowed under federal and state law you agree to indemnify and hold Pentair Thermal Management its parents subsidiaries affiliates officers employees spon sors and partners harmless from any claim loss cost expense demand or damage including reasonable attorneys fees arising directly or indirectly out of a your use of or inability to use the Software b your activities in connection therewith or c your
12. Tracing Start Reporting Disabled caga We Test Tracing tapping on the Start Stop field will open the numeric key pad Enter here a number x After tapping on Enter the output of the DigiTrace NGC 20 will close turning the connecter heater on for x amount of seconds Voltage this shows the actual voltage and the highest lowest voltage that the unit has recorded since the last reset For resetting these values go to the Maintenance screens as explained elsewhere in this manual Load Current this field shows the actual load current and the highest current the unit has ever seen since the last reset To reset these values go to the Maintenance screens Tracing Resistance this field shows the actual calculated tracing resistance Calculated by dividing the measured supply voltage by the measured current a value of 8000 Ohms means there is no load connected Monitoring Screen 4 NGC 20 Monitoring Control Temperature Reporting 15 Max 17 e Min 13 Last On 15 c Sensor 1 lermperalure Reporting 15 C Max 37 C Min s i a Sensor A Temperaire Reporting 13 haw 18e Miri 13 C Figure 14 4 NGC 20 Monitoring Control Temperature This is the temperature used by the DigiTrace NGC 20 controller to steer the output switch This can be the either the temperate measured by Temperature sensor 1 temperature sensor 2 the average or the lowest of both readings Max Min are
13. Trip Current field holds the value at which a ground fault signal will trip the output permanently OFF Typically GF Trip is set at a slightly higher value than the Ground Fault Alarm setpoint Typical value is between 20 and 30 mA Ground Fault Trip Enable Disable This selection activates or deactivates the Ground fault Trip Function Selecting Disable here will deactivate the ground Fault Trip function so that in case of ground fault current only an alarm will appear Confirm the new settings by tapping on the Apply button Back will return to Figure 22 1 03 23 SIL 2 SAFETY TEMPERATURE LIMITER SETTINGS This paragraph shows you how to configure the DigiTrace NGC 20 SIL 2 approved Safety Temperature Limiter Electrical Settings Alarm Set points screen 2 NGC 20 Configuration Temperature Settings Electrical Settings Safety Limiter Maintenance Figure 23 1 NGC 20 Configuration screen Tap on Safety Limiter to open the Limiter configuration screen Limiter Parameters Saety i imiter Parameters Fintinerares 20 Safety Limiter Status Tripped Safety Limiter Temperature 117 C Satety Limiter Setpolnt 457 C Trip Safety Limiter Figure 23 2 Safety Limiter Parameters Firmware This field shows the actual firmware revision of the Safety Temperature Limiter Safety Limiter Status This field shows the actual status of the Safety Temperature
14. and for each of these the highest and lowest value ever measured is stored in the DigiTrace NGC 20 controllers memory The Maintenance screens of the NGC CMA enable to visualise and to reset this data Note Maintenance data is stored until it is manually reset After resetting the measuring process starts new and stores new Min Max values until the next reset Tap Maintenance Data In order to continue NGC 20 Configuration Tamperature Limiter Alarm Masks Masks Figure 12 1 NGC 20 Configuration Screen In total there are 6 screens showing maintenance data The last option in Maintenance Screen 6 Forces the Factory defaults to be loaded in the DigiTrace NGC 20 control Unit Reset Maintenance 1 Reset Maintenance Control Min Temp 13a blax Tenn s7 C AC Voltage Min Vollage 127 v Max Vollage 233 v Figure 12 2 Maintenance data screen 1 Records are kept of Control Temperature AC Voltage Reset Maintenance 2 Reset Maintenance sensor 1 Min Temp iac Mas Verp 14 C Sensor 2 Mil Ten 15 e Max Ten 325 Figure 12 3 Maintenance data screen 2 Sensor 1 Temperature Sensor 2 Temperature 31 Reset Maintenance 3 Reset Maintenance Highest Instantaneous Ground Fault Reporting O mA Reset Highest Grownd Fault Highest Instantaneous Load Current Reporting n 0 A Reset Highest Lead Current Figure 12 3 Mainten
15. application requirements If FAIL SAFE MODE is enabled then at least one LOW TS ALARM of a TS used in the TS CONTROL MODE must be enabled If the alarm temperature exceeds the CONTROL SETPOINT temperature fail safe mode will be disabled 3 The zone definition flags of an external communicating device that are to be associated with the load shedding action for the controller must be defined The NGC40O controller will support up to 16 different zones These parameters can only be configured using an external communicating device connected to the bridge or DigiTrace UIT Notes e Fail safe mode Is always disabled if the SWITCHCONTROL MODE is set to either of the two proportional ambient control modes or the TS CONTROL MODE EXT INPUT FAIL OFF ON The HTC will turn on its output switch when the control temperature becomes less than the highest LOW TS ALARM temperature if the following conditions are met Fail safe mode is enabled Load shedding is active The TS CONTROL MODE uses both TS 1 and TS 2 Both TS 1 and TS 2 have their LOW TS ALARMS enabled e A FORCE ON override signal has higher priority than a load shedding signal An INHIBIT signal has higher priority than fail safe mode Tapping the Back button brings you back to the NGC 20 configuration screen Figure 8 2 NGC 20 Configuration screen 9 CHANGING DIGITRACE NGC 20 TEMPERAT URE SETTINGS AND TEMPERATURE ALARMS On the DigiTrace NGC 20 Configurati
16. breach of this Agreement or violation of the rights of any other party TERMINATION The license granted herein will automatically terminate without notice from Pentair Thermal Management if you fail to comply with any term or condition of this Agreement You agree upon such termination to remove the DigiTrace NGC 20 handheld Software from any memory and or storage media or device and to return the DigiTrace NGC 20 handheld Software including all media and written materials or destroy the same and certify such destruction to Pentair Thermal Management along with any backup or other copies in your possession COMPLETE AGREEMENT MODIFICATION IN WRITING This Agreement constitutes the sole and complete understanding between the parties with respect to the DigiTrace NGC 20 handheld Software and its use and may not be varied except by a writing signed by an officer of Pentair Thermal Management You agree that you may not rely on any representations concerning the DigilTrace NGC 20 handheld Software to the extent they vary from this Agreement and such repre sentations If any will neither add to nor vary the terms of this Agreement CHOICE OF LAWS This Agreement is governed by the laws of the State of California and the United States including U S Copyright Laws EXPORT LAWS The Digilrace NGC 20 handheld Software may require a license from the U S Department of Commerce or other governmental agency before it may be exported The term
17. command If the controller does not receive the load shed command within the timeout period it will energise its output and resume normal operation The timing of this broadcast and the timeout value can vary between 30 seconds and 10 minutes A total of 16 different load shedding zones can be defined Enter confirms the new settings and returns to Figure 8 10 Controller Settings Settings 2 screen Controller Settings PESC 20 Tay Comeole Unitas Celsius Load Shed Temperature Source Communications inne j0 ilir Settings 1 Settings 2 4 gt pack Figure 8 10 8 7 Setting the Auto Cycle Interval Tap on Settings 3 on the bottom of the controller settings screen of Figure 8 6 till Figure 8 10 Controller Settings 3 Controller Settings This screen allows you to change the NGC 20 device tag Tags Sutotvceinteval _ can be 39 characters in length and may contain all numeric characters Enter the desired Tag for the NGC 20 device by tapping in the actual device tag or elsewhere in that field NGC Alarm Output Mode 20 1 Console Units field allows changing the way temperature Alarm Output Toggle Time units are shown on the DigiTrace NGC 20 control units display Temperature can be shown in degrees Fahrenheit or Celsius Load Shed Temperature Source Communications Timeout l Settings 2 KID Apply Figure 8 13 Controller settings Settings 3 screen 16 8 8 Alar
18. dead band the device tag and load shedding Tap Temperature Settings to alter High and Low Temperature alarm values the temperature alarm filter fail safe mode and to enable and preset the high limit Cut Out Tap Temp Source Settings to define the temperature sources used by this DigiTrace NGC 20 unit Tap Electrical Settings in order to set the high and low load current and voltage alarm values The second screen offers the possibility to load the relay cycles time counter and to adjust the ground fault alarm warning and trip level Tap Temperature Limiter use this entry in order to control the Safety temperature limiter set point trip and reset the Safety temperature limiter after it has tripped Tap Maintenance to get information about the minimum and maximum values ever seen by the unit Of the following variables the minimum and maximum are stored Control temperature AC Voltage Ground fault current Load current Relay cycle count Heater hours in use Time and the Safety Limiter temperatures Tap Alarm Masks to specify for which variables an alarm will be generated Tab Back brings you to the Configuration screen 11 8 2 Changing the Temperature set point of a Digifrace NGC 20 control unit Tap on Controller Settings This will open a next screen showing the actual Controller settings In order to change any of the values tap on the field holding the actual variable Controller Settings Controller
19. default is Celsius Back Return to previous screen Figure 18 1 Setup Screen 42 18 1 Languages Setup English Fran ais Deutsch Cancel d 3 b Figure 18 2 Language Selection Screen Tap on Languages in Figure 18 1 to select your language Supported languages are English default French Fran ais German Deutsch After tapping on the desired language the Application will close and will need to be restarted manually Remark selecting a different language will cause the unit to reboot Allow enough time for the unit to reboot and then revert back to step 1 in order to restart the application The application will now run in the selected language 18 2 Temperature units Temperature Units Temperature Units Celsius Fahrenheit Figure 18 3 Temperature Units Screen From the Setup Screen as shown in Fig 1 3 tap on Temperature Units to change the way in which temperatures will be displayed on the NGC CMA screens The factory default setting is C Tap on the desired units of measure degrees Celsius or degrees Fahrenheit The screen will return automatically when the new unit has been selected Tap on Cancel to return to the Startup Screen 19 ESTABLISHING CONNECTION BETWEEN THE DIGITRACE NGC CMA AND DIGITRACE NGC 20 CONTROL UNITS The following pages will explain how to configure DigilTrace NGC 20 units from the NGC CMA hand
20. gt PENTAIR DIGITRACE NGC CMA THERMAL MANAGEMENT SOLUTIONS EN DigitraceNGCCMA IM INSTALL147 R1 CONTENTS Ba Product OVGIVI OW cusina aiana Eiaa a ia aaa EE p BaN 4 1 1 Digilrace NGC CMA configuration and monitoring SOTWAN esq s dencirsccessceasasensedsccowaseesdeaicesncdesed jhailacctapdeddeaddoandsaceneiceses 4 lite Digilrace NGC CMA Frogramming GUO srsicetsasgirceeiedertsaquinsetecesaaeelanieaniaancins aw reine EEEE a aaas 5 1 3 DigiTrace NGC 20 HANDHELD Software License Agreement sssssssnseerrrrrtrrrrrrtesssssestrrrttttnnnnnnnnttttttnntrtetrtrenseeent 5 1 4 User IRESDOMSIDIING Sc cracscxsnccaizoscsnasasmeocsmastaonasnascsibeaionsainsotedsetusbusisnmsatensaseshauiessansdessabesteasadates acnsasesiucaabecutassieessinnanchaotasiels 7 ede SUEY VY cI MING e A E A E E E E E E E E A E E iiautaaies J How to Run the DigiTrace NGC CMA Program c cescesceseeeseeensensenseneeseecnscneensensessasensonsonsonsensessnssasonsoees 8 Gla Setup ofthe UNIT siisii naa AAAA ARA ANANA ARAA 8 Using the DigiTrace NGC CMA in Standard Mode cceccsceseeecenceneneenscnscneensonsnsensensonsonsonsensessassnsonsnsoess 8 Ml Initial Seu Or The unit in Standard ModE sasise neiaa a A TE RAE iE ETOS AS 8 Changing the Language of the user interface ScreenS s sssssssnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnn nnmnnn mnnn 9 Temperature units ui penntiycankenatunmnnnnnneinediaaishnanaarnbeaaasnsdnnenneeiiddns aslinandeii
21. in Figure 20 5 The different control modes supported are gt ON OFF gt PASC gt Always ON gt Always Off gt Cancel Note that depending on the selected control mode the input fields in the previous and next screens will vary Cancel will return to the Controller Settings screen 46 Controller Settings 1 Deadband Controller Settings Temperature Setpoint Loot Mioch lon ott Deadhancd ec ack avoy Figure 20 6 Controller Settings 1 ON OFF is a simple set point dead band operation Set in the Dead band Field the desired dead band Note that the Dead band will be above set point Example a set point of 40 C and dead band of 5 will turn the heating off at 45 C and on at 39 C Controller Settings 1 PASC Controller Settings Temperature Setpoint 10 C I Mode PASC PASC Min Ambient Teng PASC Min Pipe Size 1 3cm Power Adjust 100 Vn Figure 20 7 Controller Settings 1 PASC takes advantage of the fact that the heat loss from a pipe is proportional to the temperature difference between the pipe and the ambient air This is true regardless of heater type insulation type or pipe size Once the heat tracing and insulation on a pipe has been designed to balance heat input with heat loss and maintain a particular temperature the main variable in controlling the pipe temperature becomes the ambient air temperature The DigiTrace NGC
22. the use of optional MONI RMM2 and NGC UIT units Refer to the operating manual of the DigiTrace NGC 30 for more details Tapping on Remote will require that you enter the Gateway ModBus Address Gateway Port Number and the ModBus address of the MONI RMM2 device to which the temperature Source is physically connected Refer to the operating manual of the DigiTrace NGC 30 UIT for more details Confirm your settings by tapping on Apply Cancel will bring you back to the previous screen 9 9 Temperature Sensor Configuration The next screens allow you to configure the use of the temperature sensors Temperature Configuration 24 Tamnperalure Con fauration Not Used Used For Control High Limit Cut Out High Limit And Control Cancel Figure 9 15 Temperature Configuration The different options are Not Used tap on this field in case the temperature sensor is not used Used for Control tap on the field Used For Control if you want this temperature input to be used as primary input for control drives the control logic of the DigiTrace NGC 20 High Limit Cut Out tap on this field if you want to configure this temperature source as an Input for the high temperature cut out function of the DigiTrace NGC 20 The High Limit Cut Out function prevents the heated surface from overheating When the High Cut Out Temperature Setpoint is reached the NGC 20 Output will be turne
23. 0800 0224993 salesnl pentair com NORGE Tel 47 66 81 79 90 Fax 47 66 80 83 92 salesno pentair com OSTERREICH Tel 0800 297410 Fax 0800 297409 info ptm at pentair com POLSKA Tel 48 22 331 29 50 Fax 48 22 331 29 51 salespl pentair com REPUBLIC OF KAZAKHSTAN Tel 7 495 926 18 85 Fax 7 495 926 18 86 saleskz pentair com POCCHA Ten 7 495 926 18 85 Maxkc 7 495 926 18 86 salesru pentair com SERBIA AND MONTENEGRO Tel 381 230 401 770 Fax 381 230 401 770 salesee pentair com SCHWEIZ SUISSE Tel 0800 551308 Fax 0800 551309 info ptm ch pentair com SUOMI Puh 0800 11 67 99 Telekopio 0800 11 86 74 salesfi pentair com SVERIGE Tel 46 31 335 58 00 Fax 46 31 335 58 99 salesse pentair com TURKIYE Tel 90 530 977 64 67 Fax 32 16 21 36 04 ptm sales tr pentair com UNITED KINGDOM Tel 0800 969013 Fax 0800 968624 salesthermaluk pentair com WWW PENTAIRTHERMAL COM All Pentair trademarks and logos are owned by Pentair or its global affiliates Pentair reserves the right to change specifications without prior notice 2013 Pentair THERMAL MANAGEMENT SOLUTIONS EN DigitraceNGCCMA IM INSTALL147 R1
24. 2 Temperature Setup Power Off High Lirnit Cut hut qa High Limit Cut Caut Disabled 4 E j T Figure 21 2 Temperature Setup screen 2 Fail Safe In order to choose a Fail Safe mode tap on the field currently showing Power Off The different Fail modes supported by the DigiTrace NGC 20 are Power Off or Power On Fail Safe Fail Safe Figure 21 3 Temperature Setup Fail Safe Mode Power Off meaning that should the control sensor or control sensors of this DigiTrace NGC 20 unit fail the output switch will open Use this for all circuits where keeping the heating cables permanently powered could cause overheating Power On meaning that should the control sensor or control sensors of this DigiTrace NGC 20 unit fail the output switch will be permanently close This is the preferred option for freeze protection lines and most self regulating heating systems Choose the desired fail safe mode from the list by tapping on that field Cancel will bring you back to the previous screen as shown In Figure 21 2 Temperature Setup Screen 2 Temperature Setup Power Off High Lirnit Cut Chut M High Limit Cut Out Disabled iF i ck Apply Figure 21 4 Temperature Setup screen 2 The High Limit Cut Out actually works as a temperature limiter which can be configured to operate as either a latching or non latching type When the Latching button is set to Enabled each time a
25. 2 device Tap on Back to return to the NGC 20 Configuration Screen 26 DIGITRACE NGC 20 ALARM SCREENS Tap on the View Alarms screen in order to investigate and eventually reset actual alarms In the Active Alarms field all alarms are shown NGC 20 Alarms NGC 20 Alarms Active Alaris contra Temperature High Figure 26 1 NGC 20 Alarms Screen In order to reset an alarm select the alarm by tapping on that specific alarm in the Active alarms window and then hit Reset Selected Alarm The Reset All Alarms button resets all actual alarms in a single operation Note that Alarms can only be reset after the event causing the alarm has been resolved or the measured value has changed such that the actual reading is within the alarm boundaries Tap on Back when done and to return to the NGC 20 Configuration Screen 60 Example a low temperature alarm can only be reset when the temperature has increased to a value above the low temperature alarm set point Firrmware 3 12 9 Firmware Settings Figure 26 2 NGC 20 Main screen 27 UPGRADING FIRMWARE OF THE DIGITRACE NGC 20 CONTROL UNIT Remark the Firmware Settings menu items are identical with the Standard Mode menu items Therefore most items will not be repeated See for more details Chapter 16 The Update Firmware function allows installing new revisions of DigiTrace NGC 20 firmware in the controller via the DigiTrace NGC CMA
26. 20 has a control algorithm that uses the measured ambient temperature desired maintain temperature minimum ambient temperature assumption used during the design stage and size of the smallest pipe diameter to calculate how long the heater should be on or off to maintain a near constant pipe temperature PASC Min Ambient Temp this is the minimum expected ambient temperature which is expected for this area This information is part of the design information and is country and region specific PASC Min Pip Size this is the diameter of the smallest diameter of any pipe controlled by the heating circuit DigiTrace NGC 20 control unit The Power Adjust min 10 to Max 200 The Power adjustment factor can be used to influence or override the calculated ON OFF ratio Values in excess of 100 will lead to more heat values below 100 will reduce the temperature Apply confirms new settings Controller Settings 1 Force ON Force OFF Controller Settings Temperature Setpoint LOA Mloda Always Of Load Sheddid 4 gt Laem Figure 20 8 Controller Settings 1 Always On The relay output is permanently switched on user override turns on the power to the heater and leaves it on Always OFF The relay output is permanently switched off user override turns off the power to the heater and leaves it off Note consider to monitor the pipe temperatures for Low High temperature alarms when selectin
27. 23 o 1 Figure 23 3 Safety Limiter Cut Out Limiter Set point Safety Limiter Setpoint From this point onward the NGC CMA device will be sending S the new set point at regular intervals to the DigiTrace NGC 20 hardware Polling The polling process will be repeated until the process is cancelled or until the Safety Limiter Set button inside the unit is pressed Press and hold the button for 3 Current Safety seconds Limiter Setpoint 457 C The Display of the DigiTrace NGC 20 will flash briefly and show Desired Safety actual and new safety limiter setpoint Press Satety Limiter Set Button Tin MiGC 20 Hardware Limiter Setpoint 457 C The Safety Limiter Temperature Set button is the Black Push button on the left hand side of the DigiTrace NGC 20 hardware as is shown in Figure 235 Number at Polls 3 Figure 23 4 writing a new Safety LimiterSetpoint LIMITER RESET BUTTON REARM THE LMITER AFTER IT HAS TRIPPED LIMITER TEMPERATURE SET BUTTON TO BE PRESSED AFTER THE POLLING PROCESS HAS BEEN INITIATED SSA a a C NO oe r A Figure 23 5 Location of limiter temperature set button and Limiter Reset button inside the DigiTrace NGC 20 control unit enclosure JJ Safety limiter setpoint Safety Limiter Setpoint Press Satety Limiter Set Button Tin NGC 20 Hardware Notite y Sakety Limiter Cut Out Temperature Petpoiae hae been updated aucecaaful ly Number at
28. CE NGC 20 CONTROL UNITS In order to configure the connected Digilrace NGC 20 control unit tap on continue DigiTrace NGC 20 Main Configuration Screen NGC 20 NiGC 20 I Firmware 3 14 13 Configure Monitor View Alarms i Firmware Settings Back Figure 8 1 Main screen 8 1 Changing the DigiTrace NGC 20 controller settings The main screen supports different options as is shown on Figure 8 1 Tap Configure to configure the selected unit Tap Monitor to look at all process variables as currently active on this unit All measured sensor temperatures control temperature load current supply voltage ground fault current and the status of the safety limiter Tap View Alarms in order to get an overview of all active alarms and to reset alarms Tap Firmware Settings in order to install a new version of firmware in the selected controller Tap Back to go back to the Bluetooth discovery screen as shown on Figure 7 4 Tap on Configure in the NGC 20 Main screen As a result of this the NGC 20 Configuration screen will be shown The NGC 20 configuration screen supports different options DigiTrace NGC 20 Configuration Screen NGC 20 Configuration Controller Settings Temperature Settings Temp Source Settings Electrical Settings Safety Limiter Maintenance Alarm Masks Figure 8 2 NGC 20 Configuration screen Tap Controller Settings to alter set points control mode
29. D INDEXES CONTROL MODE DEFINITIONS On Off The NGC 20 monitors the control temperature and compares it to the setpoint If the control temperature is above the setpoint by more than the Deadband value the relay output is turned off If the control temperature falls below the setpoint temperature the output is turned on The control temperature is defined as the lowest RTD temperature input value Additional Entry Fields Deadband Ifthe control temperature is above the Setpoint temperature plus Deadband the relay output is turned off If the control temperature is below the Setpoint temperature the output is turned on Range 1 C 2 F to 50 C 90 C Default 3 C 5 F PASC Proportional Ambient Sensing Control PASC takes advantage of the fact that the heat loss from a pipe is proportional to the temperature difference between the pipe and the ambient air This is true regardless of heater type insulation type or pipe size Once the heat tracing and insulation on a pipe has been designed to balance heat input with heat loss and maintain a particular temperature the main variable in controlling the pipe temperature becomes the ambient air temperature The NGC 20 has a control algorithm that uses the measured ambient temperature desired maintain temperature minimum ambient temperature assumption used during design and size of the smallest pipe diameter to calculate how long the heater should be on or off to maintain a near constan
30. DigiTrace NGC 20 handheld Software by any government shall be governed solely by the terms of this Agreement and shall be prohibited except to the extent expressly permitted by the terms of this Agreement and no license to the DigiIrace NGC 20 handheld Software is granted to any government requiring different terms ASSIGNMENT You may neither assign any right nor delegate any obligation under this Agreement and attempted assignment or delegation shall be void Pentair Thermal Management may freely assign this agreement and its rights and obligations there under to any third party INVALID PROVISIONS If any of the provisions of this provisions Agreement are invalid under any applicable statute or rule of law they are to that extent deemed omitted WAIVER No failure or delay of Pentair Thermal Management in exercising or enforcing any right or provision of this Agreement shall constitute a waiver of such right or provision or any other right or provision hereunder Furthermore any waiver by Pentair Thermal Management of any right or provision of this Agreement shall not be construed as or constitute a continuing waiver of such right or provision or waiver of any other right or provision of this Agreement HEADINGS The section titles in this Agreement are for convenience only SURVIVABILITY You agree that the terms and conditions of this Agreement shall survive any termination of this Agreement and your rights to use the Software
31. F until one of two conditions occurs 1 The zone definition flags of an external communicating device which initiated load shedding clears and the command to terminate load shedding mode is issued 2 Communications are interrupted between the controller and its communicating device as in the case of a damaged communications wire If communication ceases for a specified timeout value the controller will return to normal operation The value for this timeout is programmable within the controller 30 seconds to 600 seconds Note The controller will return to normal operation if communications between the external communicating device and the controller are disrupted in any way This will return temperature control to the HTC Also the HTC does not perform a periodic autocycle test while operating in load shed mode 17 Load Shedding 2 controller Settings _ Zone amp Shedding Enabled Zone 9 Shedding Enabled Zone 10 Shedding Enabled Zone 11 Shedding Enabled O Zone 12 Shedding Enabled _ Zone 13 Shedding Enabled O Zone 14 Shedding Enabled LUI Zone 15 Shedding Enabled C Zone 16 Shedding Enabled Load Shedding 2 a Figure 8 16 Controller Settings Load Shedding 2 18 Three parameters must be set in the controller to configure it for load shedding operation 1 The load shedding feature must be enabled 2 The FAIL SAFE MODE parameter must be enabled or disabled depending on the
32. Figure 14 6 NGC 20 Monitoring Limiter Status This field shows the actual state of the Safety temperature limiter of DigiTrace NGC 20 CL E units Limiter Temperature These fields are showing temperature information measured by the limiter temperature sensor RTD 3 Reporting actual measured temperature Max maximum temperature ever measured since last reset Min minimum temperature ever measured since last reset Number of hours Since Reset This feature indicates the total hours of use of the controller since the last reset power cycle The number of hours since last reset hours accumulator can only be reset by cycling the controller s power Note The Number of hours since last reset will roll over to zero when the upper limit of 65 535 hours has been exceeded In Use The purpose of this feature is to indicate the total hours of use of the controller since its initial operation Note The Hours in use accumulator value will roll over to zero when the upper limit of the accumulator has been exceeded This limit is 4 294 967 295 hours Heater Time Total time the heater has been energised since it was last reset power cycle Tap on the Back button when done This will bring you back to the NGC 20 Main Screen NGC 20 Taq BEG Firmware 3 14 13 Configure Firmware Settings Back Figure 14 7 NGC 20 Main screen 37 15 DIGITRACE NGC 20 ALARM SCREENS Tap on the View Ala
33. MA Tap on the monitoring field to continue This will open the first of a total of 6 available monitoring screens You can use the Left Right buttons on the bottom of the screen to cycle through the different screens The following parameters are permanently monitored Monitoring Screen 1 NGC 20 Monitoring Control Temperature Shows the actual temperature used by EOT E E the DigiTrace NGC 20 for control Based on this temperature the e Tempera output will be switched ON OFF eparting 22 C Load Current Load Current current uptake of the load s connected to the Reporting U U A control output of the DigiTrace NGC 20 control Unit Voltage Reporting 235 V Note that the load connected to the daisy chain terminals will Ground Fault Current not be monitored Instantaneous mA Safety Limiter Status Voltage actual power supply voltage Latch Temporarily Dis Satety Limiter Temperature Reporting 46 C Limiter Status shows actual limiter status Ground Fault Current instantaneous ground fault current Rack gt Limiter Temperature Reporting this field shows the actual limiter temperature measured by the Limiter RTD Figure 14 1 NGC 20 Monitoring 3d Monitoring Screen 2 Voltage Load Current Hepar ting Miar Mini L st Ore Hepar ting Highest Pver oe Ps Bs 184 ne Tracing Mesislanec Reporting ROOD Figure 14 2 NGC 20 Monitoring NGC 20 Monitoring Test
34. NT EEAS 42 17 Using the DigiTrace NGC CMA in Mixed MOde ccsccsccseesceeseseneenscnsceseeseesnscnsonsenseesesensonsonsonseesnssnsonsonees 43 17 1 Initial Setup of the unit in Mixed MOOG vcnsisascxdsccisntananinamnimianninennrersnsmnenestaataaaad shantardpaaasantantusminseeasesareaonantaaasanaesainantaanctass 43 18 Changing main settings of the user interface SCreenS sssssssnsnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnn nnmnnn 44 18 1 Languages as aemenenectesezasaanassiannyaaansiatestencetraceaasataaee aaaetayasiasenas sesuseveanmimcsecasaqaanasaantaaaorasedus saqusnim qatsastaseatnnnaemnsonersstadansaeotess 44 Pece TTS Ii MU aes ethene cee gad ince ETA E EE AEE A A A EE E EEA E EEES 44 19 Establishing connection between the DigiTrace NGC CMA and DigiTrace NGC 20 control units 45 20 Configuring DigiTrace NGC 20 control units ccceeeeeceeceeeeeeeecneceeeeseesesensenscnsonseesenscnsoaseasessnssnesanensoes 46 20 1 Changing the NGC 20 controller SQtUINOS 2icscadoxccontsnenmnasedionccnse canncsadetaonednanscontiiuulbiohgeadnccnba sesh dhwuanubntcdwaseuatinaiadadiacendeaemacans 47 20 2 Changing the Temperature set point of a DigiTrace NGC 20 Control UNIt ccecccccsssssseeeeeeeeeeeaeesseeeeeeeeeesaaaasseneeeeess 47 20 Ghanding the Switch Cantr INGE soraan notarii Rianne arrira denia ari adeaaniaadia da Aiansxsmunuaerasdantwobointistavees 48 204 Changing Digiirace NOC 20 device Tag NaMe nenscc
35. RE MENTS OR THAT THE OPERATION OF THE SOFTWARE WILL BE UNINTERRUPTED OR ERROR FREE OR THAT PROGRAM DEFECTS WILL BE CORRECTED LIMITED WARRANTY MEDIA THE MEDIUM ON WHICH THE PROGRAM IS ENCODED IS WARRANTED TO BE FREE FROM DEFECTS IN MATERIAL AND WORKMANSHIP UNDER NORMAL USE FOR A PERIOD OF SIXTY 60 DAYS FROM THE DATE OF DELIVERY TO YOU AS EVIDENCED BY A COPY OF YOUR RECEIPT ALTHOUGH PENTAIR THERMAL MANAGEMENT BELIEVES THE MEDIA AND THE PROGRAM TO BE FREE OF VIRUSES THE MEDIUM AND THE PROGRAM ARE NOT WARRANTED TO BE VIRUS FREE PENTAIR THERMAL MANAGEMENT LIABILITY AND YOUR EXCLUSIVE REMEDY IF THE MEDIUM IS DEFECTIVE OR INCLUDES ANY VIRUS SHALL BE PROMPT REPLACEMENT OF THE MEDIUM WITH A NEW DIGI TRACE NGC 20 HANDHELD SOFTWARE PRE ENCODED DISC EXCLUSION OF ALL OTHER WARRANTIES EXCEPT AS EXPRESSLY PROVIDED ABOVE PENTAIR THERMAL MANAGEMENT DISCLAIMS ALL WARRANTIES EITHER EXPRESS IMPLIED OR STATUTORY INCLUDING BUT NOT LIMITED TO ANY WARRANTY OF MERCHANTABIL ITY OR FITNESS FOR A PARTICULAR PURPOSE EVEN IF PENTAIR THERMAL MANAGEMENT HAS BEEN ADVISED OF SUCH PURPOSE THIS AGREEMENT GIVES YOU SPECIFIC LEGAL RIGHTS SOME STATES OR COUNTRIES DO NOT ALLOW THE EXCLUSION OF WARRANGTIES SO THE ABOVE EXCLUSION MAY NOT APPLY TO YOU LIMITATION OF LIABILITY THE ENTIRE RISK AS TO THE RESULTS AND PERFORMANCE OF THE SOFTWARE IS ASSUMED BY YOU IN NO EVENT SHALL PENTAIR THERMAL MANAGEMENT ITS AFFILIATES DIRECTORS OFFICERS SHAREHOLDERS EMPLOYEES OR OTHER
36. Select the device to be connected by tapping on the device name When a device is selected the background colour will become black See NGC 20 1 Tap on Continue to go on to the Main Screen If devices are not showing up move closer to the DigiTrace NGC 20 unit and repeat the scanning process by tapping on Scan for Devices once more This will re launch the device discovery process 44 20 CONFIGURING DIGITRACE NGC 20 CONTROL UNITS In order to configure the connected Digilrace NGC 20 control unit tap on Continue DigiTrace NGC 20 Main Configuration Screen NGC 20 The NGC 20 main screen supports different options as shown in Figure 20 1 Tag P l Configure to configure the selected unit Monitor to monitor all process variables as currently active Firmware 3 14 14 on this unit All measured sensor temperatures control Configure temperature load current supply voltage ground fault current and the status of the safety limiter View Alarms shows an overview of all active alarms and to 7 Firmware Settings to install a new version of firmware in the Firmware Settings selected controller Back Back to go back to the Bluetooth discovery screen From here a different DigiTrace NGC 20 unit can be selected for Figure 20 1 NGC 20 Main screen configuration 20 1 Changing the NGC 20 controller settings Tap on Configure in the NGC 20 Main screen As a result of this the NGC 20 Configur
37. Sergent EE E EAE A E EEA AEEA E O EO E A A 17 8 9 Setting up Load Shedding acccnccanacansnaadacomeicn siaamncen daceniacsnanentecdocauhlaaunsnemtadmpecmsercmalPadiontabecutesdes ddcdiaccendeaepnemntinenetadoaeaednadensees 17 9 Changing DigiTrace NGC 20 Temperature Settings and Temperature AlarmMS ssnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnn 19 9 1 Changing NGC 20 Temperature Sensor Type Sensor 1 cccccccessccesseceesseeecseceescecceseecccsseeecsuesersseeenseececsesecssesensaeeenas 19 9 2 Setting High and Low Temperature Alarm Set Points Sensor 1 siccssssssissisies iver ves enesviienncsiawvenimvedeenienuvensereeenvens 19 To Wigh and Low Alarm Filter Sensor 1 scsascssseccaansencpscswmcsidiennnenaaonnaeiveiasuetsnvadaniedineiinsueandendaceaaienuudbemueedinearmeeiastactuaes 20 9 4 Defining which temperature input is used TOF COMTI Ol sicccosccssressaesscaadeooncsccedrSaucaencdeecsoerseianciseacsqdsduedetmdetencsessensevaeeenets 21 Tic Assigning Temperature SENSOR Tag MANIC sissrisiesrmerseinn ier iei eea eee a EETA ETa niai e a 22 9 6 setting up Fail Safe mode and High Limit Cu t Qut Set point issssiiissisarresesiinsisiinrereni sanai ia anaa a T Seng The Aan Linn Cut Qut Ser DOIN sossen aiaei aieiaiee U S E aae 23 7 8 Configuring the Digilrace NGC 20 Temperature SOUL CES iscsi sieaa iraire iinunsiannd acd ninniesersademisiinlnaeeay es 23 U7 Temperature Sensor Conngu raosna a ai a araar aiin 24 19 Electrical Settings oreren ernari
38. Settings Temperature Setpoint Switch Control Mork Deadband Settings 1 Settings 2 4 gt Pack J Figure 8 3 Controller Settings Settings 1 screen Tap on the field holding the actual value 35 C A numeric key pad as shown in Figure 8 4 will pop up Numeric Input Screen Temperature Setpoint Temp Sefpoint 40 c Min a Maa rog 7 89 456 ol Figure 8 4 Temp Set point Numeric Screen Enter the desired temperature set point by tapping on the screen and press Enter to complete For this example we will be using a Setpoint of 10 C As soon as you tap the enter button you will be brought back to the Controller Settings screen REMARK The numeric screen is used at various places throughout this manual everywhere where numeric values are to be changed or entered 12 8 3 Changing the Switch control mode When returned to the Controller Setting screen of Figure 8 3 on the input field under Switch Control Mode Switch Control Mode Prop Ambient Contactor Force On Cancel Figure 8 5 Control Mode settings Screen The switch control mode defines in which manner the output switch will be operated in order to maintain the desired temperature Tap on the desired Switch Control Mode The NGC 20 supports a number of different control modes as shown on Figure 8 5 The different control modes supported are gt On Off Prop Ambient Con
39. Temperature Sensor 2 Fallure Temperature Sensor 2 High _ Temperature Sensor z Low Heather Tine Figure 13 2 Alarm Masks Screen 1 Alarm Masks 2 Alarm Masks _ Temperature Source 1 Faure _ Temperature Source 2 Failure C Tongro Soniri 3 Famhiri Temperature Source 4 Failure Temperature Source 5 Failure Temperature Source Failure _ Temperature Source 7 Failure Temperature Source A Faire C High Loved Gurreret Low Load Current Figure 13 3 Alarm Masks Screen 34 Alarm Masks 3 Alarm Masks _ High Voltage _ iow valini C High Tracing Resistance L Low Tracing Resistance C Device Reset User Conflquration Lost je Low Shed Source Fadure Groured Fault Trip Ground Fault CT Failure el High Ground Fault Gurrert Figure 13 4 Alarm Masks Screen 3 Alarm Masks 4 Alarm Masks Tap on the Back button when done This will bring you back to Switch Failure Figure 13 1 NGC 20 Configuration Screen je High Lint Temperature Cut Contactor Cycle Caiit Figure 13 5 Alarm Masks Screen 4 14 DIGITRACE NGC 20 MONITORING SCREENS Besides its function as a programming and configuration interface the DigiTrace NGC CMA can also be used to monitor DigiTrace NGC 20 units while they are in operation When used in monitoring mode all process variables measured by the Digilrace NGC 20 control units can be visualised on the DigiTrace NGC C
40. a EEE NENNE EENEN EENEN EEE 25 11 SIL 2 Safety Temperature Limiter SettingS ccccccceeceececeeseseneenscneoeeeesesenscnsensosseesessnscnsonsensessessnsonsonees 28 11 1 Resetting the Safety Temperature LIMItED c cc cccceeeee cece cece eeeeeeeeenee ee eeaeaeeaaaaaaeeeeeeeeeeeeeeeeeeeeeeeeesaeaeeeeaaaeaeaeseeeeeeeeeeeees 30 11 2 Trip Limiter Test function for SIL approved Safety Temperature limiter cccccceeeeeeeeceeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeees 31 12 MUAIMUCM ANCES dalee emus r EEE a 32 l amp k Force UcerConnigurahon Detali Sesiidae A a EOE AE OO CaS 34 TAGMA RS a a 35 14 DigiTrace NGC 20 Monitoring screens cccceccesceeesecnecneeeseesessesensonsceecesesensensoasonseesesoesonsonsensessnssassnsonees 36 15 DigiTrace NGC 20 Alarm screensS ssssssssnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnn nnmnnn nnmnnn nnmnnn nnmnnn 39 2 16 Firmware Settings communication settings ccscccssssecsscsssseeeeceeseseeeeceeueseeeeeeuagseeeeeueaseeseeeuaeeeessneas 40 16 1 Upgrading firmware of the Digilrace NGC 20 control unit ecccecsssceceinzivacsdieiasieancorcdecdenessmiedeiensnsesanielaueorarencccsensateuassivee 40 16 2 Changing the serial interface settings of the DigiTrace NGC 20 Control Unit eceeecccccceccssseeeeeeeeeeeeceeaaeeeeeeeeeeeeeeaaas 42 lOve DIG race NGC 20 Display IESi acssesories amy EER 42 TG OIG race NGC 20 Mode SUNG S cesses anire E ERSE NEA e Eea aN E
41. age Setting the Temperature Control to Average means SSE es that the output of the DigiTrace NGC 20 will be controlled based on the average temperature measured by all the Temperature sensors connected to the DigilTrace NGC 20 either direct to the Temperature sensor inputs TS 1 and TS 2 and any other sensor connected via MONI RMM2 E and DigiTrace NGC UIT Temperature Control Figure 9 6 Temperature Settings Control screen 21 9 5 Assigning Temperature sensor Tag name The third screen of the Temperature settings enables an easy recognisable Tag name to be assigned to each individual Temperature Sensor Sensor 1 Tag Sensor 1 lag NGC20 RTD1 Demo 03 Figure 9 7 Temperature Settings Sensor Tag screen Sensor Tags fields can contain a maximum of 39 characters and may contain numeric and alpha numeric values Confirm the new sensor tag by tapping on the OK button When appropriate also edit the Temperature Sensor 2 Tag name 9 6 Setting up Fail Safe mode and High Limit Cut Out Set point The Fail safe mode defines the output of the DigiTrace NGC 20 output switch in case of a sensor failure Tap on the entry field behind Fail mode for more options Sensor 1 Tag Temperature Settings Fail Mode Fixed Yo Fail Mode a High Limit Cut Out FOODS C Latch Temperature Alarms O No Ves Latch High Temperature Cut Out Alarm No C Yes Figure 9 8 Temperature Settings Other screen
42. ance data screen 2 Highest Ground Fault Highest Load Current Reset Maintenance 4 Reset Maintenance Contactor Cycle Count Keporting 0 Cycles Reset Contactor Cycle Count umber of Hours In Wee Heporting 0 hes Reset Number of Hours In Use Figure 12 5 Maintenance data screen 4 Contactor Cycle count Number of hours in use Reset Maintenance 5 Reset Maintenance Heater On Time Reporting 0 hra Reset Heber On Time Power Accumulator Meper ting 0 kW r 2 Te a 1 amp oh Figure 12 6 Maintenance data screen 5 Heater On Time Power Accumulator 32 Reset Maintenance 6 Reset Maintenance Temperature Limiter Plin Temp 15e Max lemp 103 e Reset Limiter Max Min Temps Figure 12 7 Maintenance data screen Safety Limiter Min Max temperatures Forces the Factory defaults to be loaded in the connected DigiTrace NGC 20 control Unit Tap on Back when done This will bring you back to the NGC 20 Configuration Screen Figure 12 1 12 1 Force User Configuration Defaults Tapping on this field will force the factory defaults to be loaded in the connected DigiTrace NGC 20 control Unit Reset Maintenance Forcing Factory Default settings Reset Maintenance Temperature Limiter Plin Temp 15c Max lemp 103 e Figure 12 7 Maintenance data screen Tapping on the field Force User Config Defaults will force t
43. and the wireless Bluetooth interface This procedure can be performed on units while they are in operation During the firmware upload process the Digilrace NGC 20 unit will be out of service for about 2 minutes For safety reasons the output of the controller will be off during the entire upgrade process Click on Firmware Settings in the main screen Select Update Firmware button to initiate the process This will open the Firmware update screen Firmware Update Firmware Update Taq Mit Denic Ot Current Firmware 4 14 13 Selected Firrmvare Firmware File el Lo h sc Figure 27 1 Installing new Firmware Current Firmware shows the revision number of the Firmware currently installed Firmware File tap on the blue field showing the three dots in order to brows to the location where the new firmware file is installed Firmware files are binary files and are having the extension bin 61 Select Firmware File Select Firmware File Figure 27 2 Selection new Firmware Tapping on this field will open a new screen On this screen all available versions of DigiTrace NGC 20 firmware currently present on the NGC CMA firmware folder will be listed Note the DigiTrace firmware files are binary files New configuration files need to be placed in the folder Application Data DigiTrace NGC CMA NGC20 Firmware This folder will be automatically installed while installing the application Se
44. ation screen will be shown The NGC 20 configuration screen supports different options DigiTrace NGC 20 Configuration Screen NGC 20 Configuration Use Controller Settings to alter set points control mode dead mMM band the device tag and load shedding Controller Settings Use Temperature Settings to alter High and Low Temperature SS aT EOE alarm values the temperature alarm filter fail safe mode and to Temperature Settings enable and preset the high limit Cut Out Electrical Settings Use Electrical Settings in order to set the high and low load current and voltage alarm values The second screen offers the F m possibility to load the relay cycles time counter and to adjust the Safety Limiter ground fault alarm warning and trip level Use Safety Limiter use this entry in order to control the Safety temperature limiter setpoint trip and reset the Safety temperature limiter after it has tripped Use Maintenance to get information about the minimum Figure 20 2 NGC 20 Configuration screen and maximum values recorded by the unit Of the following variables the minimum and maximum are stored control temperature AC Voltage ground fault current load current relay cycle count heater hours in use time and the safety limiter temperatures Back returns to the Main Screen Figure 20 1 45 20 2 Changing the Temperature set point of a Digifrace NGC 20 control unit Tap on Controller Settings Th
45. ature Sources Temperature Source 1 Temperature Source 2 Temperature Source 3 Temperature Source 4 Temperature Source 5 Temperature Source 6 Temperature Source Temperature Source 8 Back Figure 9 12 Temperature Sources MAE Select the Temperature source you want to configure by tapping on the field One Digilrace NGC 20 Control unit can be configured with up to 8 Temperature Sources 2 of these sources are local hardwired to the NGC 20 unit the remaining inputs can be configured through optional MONI RMM2 E and NGC UIT modules 23 Temperature Source Mode i Temperature Source Mode Local Temperature Configuration Used For Control Temperature Input 1 O Temperature Input 2 Back ay Figure 9 13 Temperature Source mode 1 Temperature Source Figure 9 14 Temperature Source mode 1 Temperature Source Mode in this first field the installation method of the temperature source needs to be specified The different options are Not Used means that this temperature sensor is not being used Local means that the temperature source is hard wired to the input terminals of the DigiTrace NGC 20 control unit This can be either to the terminals labelled with TS 1 or the one labelled as TS 2 Tapping on the field of your choice will bring you back to the previous screen Figure 9 13 Remote this means that this particular temperate Source is imported through
46. d OFF regardless of whether or not the maintain temperature is reached Use this function for instance to prevent the cable surface temperature exceeding a certain level High Limit And Control this combines the function Used for Control and High Limit Cut Out This function only applies where multiple sensors are being used to control one circuit for instance on by passes Confirm your settings by tapping on Apply Back will return to the screen Figure 9 12 10 ELECTRICAL SETTINGS To set up the electrical Settings in the Configuration menu tap on Electrical Settings in Figure 10 1 NGC 20 Configuration screen NGC 20 Configuration Controller Settings Temperature Settings Temp Source Settings Maintenance Back Figure 10 1 NGC 20 Configuration screen Electrical Settings Alarm Set points 1 Electrical Settings High Load Current 30 0 A Low Load Current Dc A High Yoltage Low Voltage ea m Alarm Setpolnts 1 Alan 4 Back i Figure 10 2 Electrical Settings Alarm Setpoints 1 screen The Electrical Settings Alarm Set points Screen 1 allows the following variables to be adjusted High Low Load Current Range Min 0 3 Max 30A The Load Current alarm will generate an alarm each time the Load Current supplied to the heating cable exceeds the defined band The load current is the same as the heater current High and Low Voltage Range Min 50 Max 305 VAC Th
47. describe in detail how the DigiTrace NGC 20 can be configured and be monitored via the NGC CMA 4 1 Initial Setup of the unit in Standard Mode After the program is started the start up screen will be visualised The start up screen allows users to configure the unit to their personal needs and process requirements DigiTrace Configuration Utility Main screen DigiTrace NGC Configuration and Monitoring Assistant Figure 4 1 Startup screen The Tab Configure initiates the Bluetooth device discovery process The tab Settings allows setting the Language Temperature units and shows the software revision The tab Exit closes the application Begin the initial configuration by tapping on Settings on the start up screen This will open the Setup screen as shown in 5 CHANGING THE LANGUAGE OF THE USER INTERFACE SCREENS DigiTrace Configuration Utility Main screen E tup About Languages Temperature Units Back Figure 5 1 Setup Screen About shows the software version of the DigiTrace Configuration Utility Software Languages Allows selecting a convenient language of the user interface software Temperature Units Sets the temperature units of the DigiTrace NGC CMA Supported are Degrees Celsius and degrees Fahrenheit The default value is degrees Celsius Back Brings you back to the previous screen Figure 4 1 Tap on Languages to continue Se
48. e field NGC UIT as central User DigiTrace Supervisor software DTS as central User Interface MONI RMM Units are optional Interface wa ZA SD AE Ne NGC UIT NGC 20 Pt100 RTD Pt100 RTO Heating cable Heating cable Figure 1 1 DigiTrace NGC 20 system overview Configuration and Monitoring The NGC CMA can be used to configure the DigiTrace NGC 20 Besides its function as programming interface the DigiTrace NGC 20 CMA can also be used to monitor DigilTrace NGC 20 units while they are in operation When used in monitoring mode all process variables used by the NGC 20 control units can be visualised on the screen of the DigiTrace NGC CMA Installation Please refer to the User Manual INSTALL 131 for guidelines about unpacking and basic use of the DigiTrace NGC CMA devices Communications DigiTrace NG CMA devices support various types of communications interfaces Refer to the User Manual INSTALL 131 or product datasheet for complete details about all communication options 1 2 Digifrace NGC CMA Programming Guide Vital Information This manual is a guide for the setup and operation of the DigiTrace NGC 20 CMA handheld programming devices Important All information including illustrations is believed to be reliable Users however should independently evaluate the suitability of each product for their particular application Pentair Thermal Managemen
49. e only under the terms of this Agreement and Pentair Thermal Management reserves any rights not expressly granted to you Subject to the terms and conditions of this Agreement Pentair Thermal Management grants to you a non exclusive nontransferable lim ited license without the right to sublicense others to use the one copy including written materials if any of the Software on a single computer at the location company and address to which Pentair Thermal Management issued this copy of the DigiTrace NGC 20 handheld Soft ware The Software is owned by Pentair Thermal Management LLC and is protected by United States copyright laws and international treaty provisions All copies made by you are sub ject to the terms and conditions of this Agreement The structure organisation and code of the Software are valuable trade secrets and confidential information of Pentair Thermal Management You agree not to modify alter merge adapt duplicate distribute translate decom pile disassemble reverse engineer create derivative works copy for use on any other computer or at any other location or otherwise make this software available to any person or entity outside this location The Software is licensed only to you In no event may you transfer sell sublicense rent assign or transfer rights lease or otherwise dispose of the Software on a temporary or permanent basis without the prior written consent of Pentair Thermal Management You agree to use reaso
50. e voltage alarm will generate an alarm each time the power supply voltage supplying the NGC 20 control unit and the heating cables exceeds the defined band 29 Electrical Settings Alarm Set points 1 Electrical Settings High GF Current L0 mA Ground Fault Trip Current 2 mA Contactor Cycle Count Limit AOOOO00 Cycles Heater On Time LODODO hrs i Alarm Setpoints 2 Al Back il Figure 10 3 Electrical Settings Alarm Setpoints 2 screen Electrical Settings High Voltage Low Voltage High GF Current High Load Current Low Load Current Alarm Filters Other 4 gt Figure 10 4 Electrical Settings Alarm Filters screen The Electrical Settings Alarm Set points Screen 2 allows the following variables to be adjusted High GF Current Range Min 10 Max 250 mA This field holds the value at which an early warning will be generated in the form of a High GF alarm Typical value between 15 and 20 mA Ground Fault Trip Current Range Min 10 Max 250 mA The GF Trip Current field holds the value at which a ground fault signal will trip the output permanently OFF Typically GF Trip is set at a slightly higher value than the High GF Current Set point Typical value is between 20 and 30 mA Ground Fault Trip Enable Disable setting the Ground Fault Trip to Disabled disables the Ground Fault Trip function The High GF Alarm would still be generated when the leakage curren
51. ed Limiter Trip Limiter 24 MAINTENANCE DATA The Maintenance data screens provide the possibility to look at Minimum and Maximum values of recorded data The DigiTrace NGC 20 control unit measures many variables such as voltage current temperature ground fault etc and for each of these the highest and lowest value ever measured is stored in the DigiTrace NGC 20 memory The Maintenance screens of the NGC CMA enable to visualise and to reset this data Note Maintenance data Is stored until it will be manually reset After resetting the measuring process will start again and stores new Min Max values until the next reset Tap on Maintenance to go to the Maintenance menu NGC 20 Configuration Controller Settings Temperature Settings Electrical Settings Temperature Limiter Maintenance il Back Figure 24 1 NGC 20 Configuration Screen In total there are 4 screens showing NGC 20 control units maintenance data 0 7 Reset Maintenance 1 Reset Maintenance Contral Min Temp ete Max Temp 26 C AG Voltage Min Voltage 219 wv Max Voltage 238 v Reset AC Voltage Mine Min Back Figure 24 2 Maintenance data screen 1 Records are kept of Control Temperature AC Voltage Tap on the blue field Reset in order to reset the actual values This will bring up a screen as shown in Figure 24 3 Resetting values Confirm Are you sure you want to reset the Con
52. eeeseneensceseeeessesenscneonseeseeseesneonsens 64 Appendices and Indexes scensicivannvnsaawycnnnennnieneasnnnnsicnnssnsondasnie ean snsavicansnlivnaiihiuaswdnwaneduliyehwanlesinasviunpnewanainueviadsianieenini 66 1 PRODUCT OVERVIEW This document describes the use and the capabilities of the DigiTrace NGC CMA handheld device and software For more information about the correct use and handling of the device we refer to DigiTrace NGC CMA Getting Started INSTALL 131 manual 1 1 Digifrace NGC CMA configuration and monitoring software The DigiTrace NGC CMA software is developed for Windows Mobile 5 The software enables DigiTrace NGC 20 control units to be configured and monitored via a Wireless Bluetooth interface The exact use of this software is described in this manual Note For hazardous area Zone 1 21 and Zone 2 22 use the DigiTrace NGC CMA EX only The DigiTrace NGC 20 can be configured in either Standard mode or Mixed mode The Mixed mode meets situations where DigiTrace NGC 20 is communicating with a DigiTrace NGC UIT otherwise the DigiTrace NGC 20 will be configured in Standard mode In both circumstances a different set of parameters Is available for configuration Standard Mode with optional DigiTrace Mixed Mode with optional DigiTrace NGC UIT used as central Supervisor Software used as central user user interface interface Digilrace NGC 20 as local controller in the field DigilTrace NGC 20 as local controller in th
53. elow the Limiter Temperature Set point Safety Limiter Temperature Set point This field holds the Safety Limiter set point This value should be chosen in accordance with the Temperature Class of the area in which the heating application is installed T class T4 T3 T2 or the maximum surface temperature allowed for the heating device assuming this is a lower temperature Since the Safety Temperature Limiter is a safety device it requires a special procedure to write a new set point to the Temperature limiter Tap in the Limiter Temperature Set point field to start the write procedure This will open a new screen Limiter Setpoint Safety Limiter Cut Out C Man dl a TERE 112 3 o 1 Figure 11 3 Safety Limiter Cut Out Frotesr Enter the new set point via the numeric pad Hit Enter to confirm the new Limiter Cut Out set point This will open a new screen Figure 11 4 writing a new Safety Limiter Cut Out Limiter Set point Figure 11 Safety Limiter Setpoint Press Satety Limiter Set Button In NiGC 20 Hardware Current Safety Limiter Setpolnt 1230C Desired Satety Limiter Setpoint 120 C Number at Polls 7 Cancel 4 writing a new Safety Limiter Cut Out From this point onward the NGC CMA device will send the new set point at regular intervals to the DigiTrace NGC 20 hardware Polling The poll
54. ens Use the Left Right buttons on the bottom of the screen to cycle through the different screens The following parameters are permanently monitored Monitoring Screen 1 NGC 20 Monitoring Control Temperature Reporting 24 c Load Current Reporting Oo 0 A Voltage Reporting 231 W Ground Fault Current Instantareous i mA Safety Limitler Status Latch Temporarily Dis Satety Limiter Temperature Reporting 121 c Back ae Figure 25 1 NGC 20 Monitoring Screen Control Temperature Shows the actual temperature used by the DigiTrace NGC 20 for control Based on this temperature the output will be switched ON OFF Load Current current uptake of the load s connected to the control output of the DigiTrace NGC 20 control Unit Note that the load connected to the daisy chain terminals will not be monitored Voltage actual power supply voltage Ground Fault Current instantaneous ground fault current Limiter Status shows actual limiter status Limiter Temperature Reporting this field shows the actual limiter temperature measured by the Limiter RTD Monitoring Screen 2 NGC 20 Monitoring Source emperaires l 74 C IHot Used z Hot Used Not Umed Back Figure 25 2 NGC 20 Monitoring Screen 2 Source Temperatures This field shows the Temperatures measured by all temperatures presently connected Temperature sources 3 and 4 require the use of an optional NGC UIT and MONI RMM
55. erature the main variable in controlling the pipe temperature becomes the ambient air temperature The DigiTrace NGC 20 has a control algorithm that uses the measured ambient temperature desired maintain temperature minimum ambient temperature assumption used during the design stage and size of the smallest pipe diameter to calculate how long the heater should be on or off to maintain a near constant pipe temperature Proportional Band is the delta between the desired temperature set point and the minimum expected ambient temperature The Prop Ambient Cycle Time defines the total time cycle Sum of the ON OFF cycle in minutes The cycle time can be adjusted between minimum 10 and Maximum 255 minutes The ON OFF ratio will be calculated based on the measured ambient temperature 13 Controller Settings Temperature Setpoint Switch Canbral thocke PASC Contactor PASC Min Ambient Tern 40 PASC hin Pipe Size 1 tem Power Adj 1009 Settings 1 Settings 2 4 gt Ds Figure 8 8 Controller Settings The Power Adjustment factor min 10 to Max 200 The Power adjustment factor can be used to influence or override the calculated ON OFF ration values in excess of 100 will lead to more heat values below 100 will reduce the temperature Tap Apply to confirm your new settings Controller Settings 1 Force ON Force OFF Controller Settings Temperature Setpolnt 20 C Switch Con
56. ereneucdsnenpeniiniiernsnieanninisidlaxwhanenaneiedekoetennns 9 Establishing a Bluetooth connection between the DigiTrace NGC CMA and ccseceseeeenecnceeseneeeeeeeneeneees DigiTrace DigiTrace NGC 20 control UNItS cccceeeeeeeceneeneeeseeensensensensoeeeesesensonscesesseseesonsensensensessnesesonees 10 8 Configuring DigiTrace NGC 20 control units ccccceceeeeeceeeeeeneeesenseeeeesesensensensonseeensensenecnseasenseeeesonseneons 11 6 1 Changing the Digiirace NGC 20 controller Settings casce cacescriseterinnsdaiewasecedentcunedmantandeseeesceacswrwstexcsesniseacnentandensedandetonaeiae t 8 2 Changing the Temperature set point of a DigiTrace NGC 20 control unit essssssssussssssssssnrrrrreesssrrrrrrrrnsssrnrrrrrrrrenerrnnn f2 8o Changing the SiC Control ModE csn e R a SEER E eE a Si 13 84 Changing Vidi trace NGC 20 device tag Name sacs axsicnresatcesanasadinnurishavinntninsdvnariennvaraiies ash catasuitasaTaianiupeinatadertads SSES 1D 8 9 Changing the NGC 20 Console UNITS cccenosdrascsascnsaaainaaniaratarneinannnsaminassinnsaneny annhinn SEAE SES SS N inasinoneaansdnesnienoneasedass 12 8 6 Load Shed Temperature Source COMMUNICATIONS time OUt cececcccccsssceccsseccsssecceseececseeeccsseecsssecessueeesseeecctsesensaneesas 16 8 7 Setting the Auto Cycle Interval 20 0 ccccseccceccccceesssseceeeececceeessseeeeeceecseceusseceeeececseseeaseeeeeeeesseseeeaseeeeeeesssaeeaasseeeeeeessaaaes 16 cs POUT TIO
57. eters allows configuring the ModBus and serial interface settings NGC 20 Display Test forces the DigiTrace NGC 20 unit to execute a display test NGT zt Display Test Back Figure 16 1 Firmware and general settings 16 1 Upgrading firmware of the DigiTrace NGC 20 control unit The Firmware Settings function allows you to install new revisions of DigiTrace NGC 20 firmware in the controller via the NGC CMA and the wireless Bluetooth interface This procedure can be performed on units while they are in operation During the firmware upload process the DigilTrace NGC 20 unit will be out of service for about 2 minutes For safety reasons the output of the controller will be off during the entire upgrade process In the screen of Figure 16 1 tap on the Update Firmware button to initiate the process This will open the Firmware update screen Firmware Update Firmware Update Update Firmware enables new revisions of firmware to be Tag installed in the DigiTrace MGC D Denio UF NGC 20 controller via the NGC CMA Current Firmware 4 14 14 Selected Firmware Com Parameters allows configuring the ModBus and serial interface settings NGC 20 Display Test forces the DigiTrace NGC 20 unit to execute a display test H Firnmware File Back Upload Figure 162 Installing new Firmware Select Firmware File Safect Airmware File Tapping on this field will open a new screen On this sc
58. export includes many acts such as transferring the DigiTrace NGC 20 handheld Software to a foreign citizen within the United States in addition to sending or taking the DigiTrace NGC 20 handheld Software outside the United States You agree to ascertain the necessary licensing pro cedures and obtain any required licenses before exporting the DigiITrace NGC 20 handheld Software You also agree to indemnify Pentair Thermal Management and assume all financial responsibility for any losses it may suffer if you do not comply with this paragraph GOVERNMENT RESTRICTED RIGHTS User acknowledges that the DigiTrace NGC 20 handheld Soft ware has been developed at private expense and is provided with Restricted Rights Use duplication or disclosure by the Government is subject to restrictions as set forth in sub paragraph b 3 and paragraph c of the Rights in Technical Data clause at 48 C F R 252 227 7013 or subparagraphs c 1 and 2 of the Commercial Computer Software Restricted Rights clause at 48 C F R 52 227 19 as applicable This provision applies to the DigiTrace NGC 20 handheld Software acquired directly or indirectly by or on behalf of any governament The DigiTrace NGC 20 handheld Software is a commercial product licensed on the open mar ket at market prices and was developed entirely at private expense and without the use of any government funds Any use modification reproduction release performance display or disclosure of the
59. g Force ON or Force OFF control mode Tap Apply after the desired control mode has been selected 47 20 4 Changing DigiTrace NGC 20 device tag name Controller Settings 2 DigiTrace NGC 20 Tag Controller Settings This screen allows you to change the DigiTrace NGC 20 device TP tag Tags can be 39 characters in length and may contain all M lag numeric characters Enter the desired Tag for the DigiTrace TO 1 NGC 20 device by tapping in the actual device tag or elsewhere in that field NGC 20 1 Back Figure 20 9 Controller Settings Settings 2 screen NGC 20 Tag NGC 20 Tag Enter the desired Tag by using the onscreen keyboard Tap OK when finished For this example the new tag will be Pipe 1 Figure 20 10 NGC 20 Tag 20 5 Load Shedding Load shedding is a control mode that can be programmed and initiated only by an external communicating device which overrides temperature control and forces the output of the controller OFF until the override is removed When using an external device DigiTrace Supervisor Software or a DCS a load shedding command is continually broadcast over the communications network When power is applied the controller delays energising its trace by x number of seconds where x is equal to the last digit in its network address If the load shed function is enabled the controller will go into load shed mode before it turns its output on
60. g the Safety Temperature Limiter Once the safety Temperature limiter has tripped it will need to be reset in order to restore normal operation Resetting the Safety Temperature limiter will only be possible after safe operating conditions have returned See Figure 11 5 in order to locate the RESET button Reset protection Password Enter 547 to continue Resetting the Safety Temperature Limiter is a safety Function therefore the Reset operation is protected by a password in order to prevent the Safety Temperature limiter form being reset unintentionally l 3 5 z Ls wlan Le The Safety temperature Limiter can be reset from the DigiTrace NGC CMA In order to do so tap on Reset Tripped Limiter doing this will open a new Screen as is shown in Figure 11 7 Use the numeric Key pad to enter the number shown in blue on the top of the screen and tap enter elele Nao Figure 11 7 Resetting rearming the Safety temperature Limiter 27 Successfully Reset Tripped Limiter Seavety i imiter Parameters Firre 1 9 Safety Limiter Status Notite Guccessiully Tripped safety Limiter Figure 11 8 Resetting rearming the Safety temperature Limiter If the number entered was correct than the Safety Limiter will Reset and a pop up screen will appear The pop up screen confirms the Safety temperature Limiter has been successfully reset Tap OK when done 11 2 Trip L
61. gure the second temperature input connected to the DigiTrace NGC 20 control unit Hit Apply when done The Back button will bring you back to the NGC 20 Configuration screen of Figure 8 2 20 9 4 Defining which temperature input is used for control The third screen of the Temperature Settings menu defines the Temperature Control Mode Temperature Settings Temperature Settings Use the Temperature Control Screen to define which n Z temperature input is chosen for control Of all the temperature Temperature Control Mode i i input options one input needs to be selected for control Temperature Source 1 Alternatively the control temperature can be based on the High Alarm Setpoint average or the lowest temperature of all temperature inputs lesee currently connected and enabled Low Alarm Setpolnt 3 High Temperature Alarm Set point hoe i range from min 80 to Max 700 C High Alarm Filter 5 sec Enter in this field the value at which when surpassed you Low Al Filter want the NGC 20 control unit to generate a high temperature iali alarm This high temperature condition will be monitored by the temperature sensor or group of temperature sensors selected for control Low Temperature Alarm Set point Figure 9 5 Temperature Settings Control screen range from min 80 to Max 700 C Enter in this field the value at which when surpassed you want the DigiTrace NGC 20 control unit to generate a low tempe
62. he factory defaults to be loaded in the connected DigiTrace NGC 20 control Unit Force User Defaults Force User Defaults Are you sure you want to Force User Config Defaults This will reset setpoints and other user settings back to their default configuration Fig 8 8 Reset Maintenance Confirm to load factory defaults Tap Yes or No Note that this function will override all customised settings and that they will be lost After tapping Yes the field will briefly colour green as confirmation that the factory defaults are being loaded 33 13 ALARM MASKS The Alarm Mask defines which alarms will be enabled and which Alarms will be disabled In order to enable an alarm just check the checkbox in on the left side of the screen Before alarms will be generated they need to be enabled NGC 20 Configuration Temperature Limiter Figure 13 1 NGC 20 Configuration Screen In total there are 4 screens with Alarm Masks Alarms preceded by the V checkmark are enabled Alarm Masks 1 Alarm Masks Tap Yes or No e Control Terpaerseteore Fiia Note that this function will override all customised settings _ Control Temperature High and that they will be lost After tapping Yes the field will briefly v Control Temperature Low colour green as confirmation that the factory defaults are being _ Temperature Sensor 1 Failure loaded Demperature Sensor 1 High Temperature Serer 1 Love
63. held programmer DigiTrace Configuration Utility Main Screen Bigitrace NGG Configuration and Monitoring Assistant Figure 19 1 Main Screen Tap on Configure Figure 19 1 The display will now show the Bluetooth discovery screen and the device discovery process will be started 43 Bluetooth Discovery Process Bluetooth Discovery Please walt Discovering devices B 8 Back Continue Figure 19 2 Bluetooth Discovery screen Searching for devices In background the device will scan for all DigiTrace NGC 20 controllers which are within range of the Bluetooth communications Ensure that all NGC 20 units are powered up Bluetooth Discovery Process device inventory Bluetooth Discovery Please select the device you Wish to connect to 20 1 Scan for Devices Back Continue Figure 19 3 Bluetooth Discovery screen one device found When searching is complete devices in range will be listed on the screen Example For this example the only device that is found is NGC 20 1 If more than one DigiTrace NGC 20 control unit is in range all units will be listed on the screen as shown in Figure 19 4 Bluetooth Discovery Process selecting device Bluetooth Discovery Please select the device you wish to connect to eee ne C 20 2 Scan for Devices Figure 19 4 Bluetooth Discovery screen finding multiple devices
64. imiter Test function for SIL approved Safety Temperature limiter This is the test function of the SIL 2 approved Safety Temperature limiter Limiter Parameters Trip Limiter Safely Limiter Parameters Firmware 2 Safety Limiter Status Tripped Safety Limiter Temperature 117 C Safety Limiter Setpoint 45 790 Reset Tripped Safety Limiter Trip Safety Limiter Figure 11 9 Limiter cut out temperature updated successfully Limiter Parameters Firmware 1 9 Limiter Stals otite haccesstully Trigped Limiter Trip Limiter Figure 11 10 Successfully tripped safety temperature limiter This is the test function of the SIL 2 approved Safety Temperature limiter Hit this field in order to Test the safety Temperature limiter at regular intervals at least once every year When tripped a screen will pop up confirming that the Safety Temperature Limiter has tripped successfully In order to rearm the safety temperature limiter follow the procedure as explained in paragraph 11 1 Resetting the Safety Temperature Limiter Tap on Back when done This will bring you back to the NGC 20 Configuration Screen Figure 11 1 30 12 MAINTENANCE DATA The Maintenance data screens provide the possibility to look at Minimum and Maximum values of recorded data While controlling the DigiTrace NGC 20 control unit measures many variables such as voltage current temperature ground fault etc
65. ing process will be repeated until the process is cancelled or until the Safety Limiter Set button inside the unit is pressed Press and hold the button for 3 seconds The Display of the DigiTrace NGC 20 will flash briefly and show actual and new limiter cut out temperature The Safety Limiter Temperature Set button is the Black Push button on the left hand side of the DigiTrace NGC 20 hardware as Is shown on Figure 11 5 below 28 r f IO j LIMITER RESET BUTTON REARM THE LMITER AFTER IT HAS TRIPPED LIMITER TEMPERATURE SET BUTTON TO BE PRESSED AFTER THE POLLING PROCESS HAS HEEM INITIATED JO Figure 115 location of limiter temperature set button and Limiter Reset button inside the DigiTrace NGC 20 control unit enclosure Limiter Set point Safety Limiter Setpoint After the new set point has been successfully updated a pop up l message as shown in Figure 11 6 will appear confirming the Press Satety Limiter new set point has been successfully updated Set Button Tin WGC 20 Hardware Note that the new set point may differ 1 or 2 degrees from the Netion selected values This is caused by rounding up or rounding Satecy Miniter Cue cur down the set point while it is been converted by the internal J Temperature setpoint electronics P had been updated aucecaaful ly Number at Palle 5 Cancel Figure 11 6 Limiter cut out temperature updated successfully 11 1 Resettin
66. ining the desired value is tapped then the screen will close and you will be brought back to Figure 10 4 When all filter times are entered than tap Apply to confirm the new settings Click on Back to return to previous screen Figure 11 1 NGC 20 Configuration Screen 26 Electrical Settings Other Electrical Settings The Electrical Settings Other allows the following variables to be adjusted Nominal Tracing Resistance 6 0 0 Nominal Tracing Resistance this field contains the calculated High Tracing Deviation value of the tracing resistance Ohmic Enter the nominal tracing resistance via the numeric pad and confirm the new 500 settings by tapping Enter Low Tracing Deviation i o l High Tracing Deviation if the calculated tracing resistance deviates more than x an alarm will be generated Use the numeric keypad to enter the desired value and confirm new settings by tapping Enter KOU me Low Tracing Deviation if the calculated tracing resistance Al Filters Other amikin El deviates more than x an alarm will be generated Use the Back Apply numeric keypad to enter the desired value and confirm new settings by tapping Enter Figure 10 6 Electrical Settings Other Tap Apply to confirm Tap on Back to go to the NGC 20 Configuration screen 11 SIL 2 SAFETY TEMPERATURE LIMITER SETTINGS The next section shows how to configure the DigiTrace NGC 20 SIL 2 app
67. is will open a next screen showing the actual Controller settings In order to change any of the values tap on the field holding the actual variable Controller Settings Controller Settings Temperature Setpoint ht Mioch lon ott Deadhand Back 7 Apply 7 Figure 20 3 Controller Settings Settings 1 screen Tap on the field holding the actual value 10 C A numeric key pad as shown in Figure 20 4 will pop up Numeric Input Screen Temperature Set point Temp Sefpoint 40 c Mn lt a Mas rog 7 89 ol Figure 20 4 Temp Set point Numeric Screen Enter the desired temperature set point by tapping on the screen and press Enter to complete This example shows a Temp Set point of 10 C By pressing enter the screen will return to the Controller Settings screen Figure 20 3 REMARK The numeric screen is used at various places throughout this manual everywhere where numeric values are to be changed or entered 20 3 Changing the Switch control mode To change the control mode select the Mode on the Controller settings page Figure 21 2 Switch Control Mode Switeh Control Mode Figure 20 5 Control Mode settings Screen The switch control mode defines how the output switch will be operated in order to maintain the desired temperature Tap on the desired Switch Control Mode The DigiTrace NGC 20 supports a number of different control modes as shown
68. isk of fire shock or personal injury If you have any questions contact your local representative or contact Pentair Thermal Management directly Warning Error and Alarm Messages Under certain conditions the DigiTrace NGC 20 CMA will alert the user with a warning an alarm or an error message These are typically either because the program cannot find an acceptable answer based on user input or because the user may need to take some additional action to ensure the design requirements are completely met These warnings and error messages are detailed in chapter 9 of this manual For questions please contact Pentair Thermal Management Technical Support Technical Support For technical support contact your local representative or contact Pentair Thermal Management directly HOUSTON BELGIUM 7433 Harwin Drive Romeinse straat 14 Houston TX 77036 3001 Leuven Tel 1 713 868 4800 Tel 32 16 213 511 Fax 1 713 868 2333 Fax 32 16 213 603 pentairthermal com pentairthermal be 2 HOWTO RUN THE DIGITRACE NGC CMA PROGRAM Tarski Seateberr 3 INITIAL SETUP OF THE UNIT After the program is started the start up screen will be visualised The start up screen allows users to configure the unit to their personal needs and process requirements 4 USING THE DIGITRACE NGC CMA IN STANDARD MODE When operated in the Standard Mode the maximum set of parameters are available for configuration and monitoring The following chapters will
69. iter Saety i imiter Parameters Firre 20 Safety Limiter Status Notite guccessiully Reset Teipped safety Limiter Trip Safety Limiter Figure 23 8 Resetting rearming the safety temperature limiter If the number entered was correct than the safety temperature limiter will reset and a pop up screen will appear The pop up screen confirms the safety temperature limiter has been successfully reset Tap OK when done 06 23 3 Trip Limiter The trip safety limiter is a test function of the SIL 2 approved safety temperature limiter Limiter Parameters Trip Limiter Safety Limiter Parameters This is the test function of the SIL 2 approved safety a temperature limiter Hit this field in order to Test the safety Fintinerncares ee 50 temperature limiter at regular intervals at least once every year Safety Limiter Status Tripped Safety Limiter Temperature 117 C Satety Limiter Setpolnt 457 C Reset Tripped Safety Limiter Trip Safety Limiter Figure 23 9 Limiter cut out temperature updated successfully When tripped a screen will pop up confirming that the safety Limiter Parameters a i temperature limiter has tripped successfully Firmware 1 9 In order to rearm the Safety temperature Limiter follow the Limiter Status procedure as explained in paragraph 23 2 Notice Back will return to the NGC 20 Configuration Screen heceestully Trigp
70. l unit to generate a high temperature alarm This High Temperature condition will be monitored by Temperature sensor T1 only Low Alarm Setpoint Enter in this field the value at which when exceeded you want the NGC 20 control unit to generate a Low Temperature Alarm This Low Temperature condition will be monitored by Temperature sensor T1 only 1 9 3 High and Low Alarm Filter Sensor 1 High and Low Alarm Filter Sensor 1 Alarm filters can be seen as an alarm delay This means that Temperature Settings E when the temperature drops below the Low Alarm Set point the Temperature Sensor 1 Type DigiTrace NGC 20 Control unit will only trigger an alarm when 2 Wire 100 Platinum the value entered in the Low Alarm Filter is timed out This means that If immediate action of the alarm output is required the Low Alarm Filter value should be set at 0 sec Any other value will result in a delay The operation of the High Alarm High Alarm Setpoint Filter is the same Min 0 to Max 59940 seconds Low Alarm Setpoint High Alarm Filter lo CEM Low Alarm Filter Figure 9 4 Temperature Settings Sensor 1 screen Repeat Steps from Temperature Sensor 1 Type 3 Wire 100 Platinum High Alarm Setpoint 65 Low Alarm Setpoalnt 10 C High Alarm Filter Low Alarm Filter Fsec Sensor 1 Sensor 2 Cont pack J Figure 9 2 for Sensor 2 in order to confi
71. lect Language Supported languages are English default English French Francais German Deutsch After tapping on the desired language you will be returned to the Startup screen Remark selecting a different language will cause the unit to reboot Allow enough time for the unit to completely Deutsch reboot When ready revert back to step 1 in order to restart the application The application will now run in the selected language Figure 5 1 Setup Screen 6 TEMPERATURE UNITS From the Setup Screen tap on Temperature Units to change the Temperature Units l l way in which temperatures will be displayed on the NGC CMA Celsius screens The factory default setting is C Tapping on the desired field will select the units of measure Celsius or Fahrenheit and will return you to the Setup Screen while the new units of measure will be selected Fahrenheit Tap on Back to return to the Startup Screen Cancel Figure 6 1 Temperature Units Screen 7 ESTABLISHING A BLUETOOTH CONNECTION BETWEEN THE DIGITRACE NGC CMA AND DIGITRACE NGC 20 CONTROL UNITS DigiTrace Configuration Utility Main Screen From the Startup screen tap on Configure The display will now iaia show the Bluetooth discovery screen and the device discovery Configuration and process will be started Monitoring Assistant Figure 7 1 Main Screen Bluetooth Discovery Process
72. lect the new file by tapping on it and hit OK Warning don t try to upload files other than original files provided by Pentair Thermal Management Any attempt to try to upload false or incomplete files may damage the DigiTrace NGC 20 Control unit Firmware Update Firmware Update Taq BECA U ci OS Current Finmeare J 1na Selected Firmware 3 16 23 Finmmware File NGC 20_V3 16 bin Current Task Sending Index 167207 Progress E Back Figure 27 3 Updating Firmware After the new file is selected hit Upload to start the upload process The existing Firmware version as well as the new Firmware are shown on the DigiTrace NGC CMA screen The installation procedure will remove the existing version and install new software in the DigiTrace NGC 20 control unit The installation progress can be followed on the Progress bar and on the installation progress timer Once the upload process is complete the DigiTrace NGC 20 control unit will briefly show the Firmware version number on the display and return to normal operation Firmware Update Complete Firmware Update Tag wat O Deno 03S Current Firmware 3 0 0 d Notice Fitewace update i Cinished succesfully TOJ ESS Stop Figure 27 4 Successful update firmware If the installation was successful a pop up window will appear confirming the firmware update was successful 62 APPENDICES AN
73. m Output Mode The Alarm Output Mode defines the way the alarm relay will act in case of alarms The different options are Normal Operation Toggle Flash or cancel Alarm Output Mode Alarm Output Mode Normal Operation Toggle iy zl my i a Cancel Figure 8 14 Alarm Output Mode Normal operation Selecting this will result in the alarm relay changing state in case of an alarm General alarm This means the open contact will close and the closed contact of the SPDT alarm relay will open Toggle selecting toggle will cause the Alarm relay to change state each time a new alarm comes up Flash selecting to Flash the Alarm relay will alternatively open and close the Alarm relay The interval itself can be user defined in the Alarm Output Toggle Time Cancel will take you back to the previous screen without any of the changes made 8 9 Setting up Load Shedding A total of 16 different load shedding zones can be defined Load Shedding 1 Cofttrolier Settings L Shedding Fnabled Shedding Fail Safe Grable C fone 1 Shedding Enabled _ Zone 2 Shedding Enabled L Zone 3 Shedding Fnabled Zone 4 Shedding Enabled fone 5 Shedding Enabled _J Zone 6 Shedding Enabled L Zone 7 Shedding Enabled Load Shedding 1 Load mea Loot Figure 8 15 Controller Settings Load Shedding 1 If a load shedding command is present the controller will continue to hold the output OF
74. n alarm has occurred the Alarm needs to be manually reset When set to Disabled the alarms will be self healing and will disappear when the alarm condition is no longer present Confirm your new settings by tapping the Apply button Tap Back when ready doing this will bring you back to screen Figure 211 51 22 ELECTRICAL SETTINGS To set up electrical settings click on Electrical Settings in the NGC 20 Configuration screen Figure 21 1 NGC 20 Configuration Controller Settings Temperature Settings Electrical Settings Temperature Limiter Maintenance il Back Figure 22 1 NGC 20 Configuration screen Electrical Settings Alarm Set points screen 2 Electrical Settings High Load Current 30 0 A Low Load Current High Voltage 270 Y Low Voltage 90 V Heater Tire Alarrre 100000 hrs Figure 22 2 Electrical Settings screen 1 The Electrical Settings Alarm Set points Screen 1 allows the following variables to be adjusted High Load Current Range Min 0 3 Max 30A The Load Current alarm will generate an alarm each time the Load Current supplied to the heating cable exceeds the defined band The load current is the same as the heater current Low Load Current Range Min 0 3 Max 30A The Load Current alarm will generate an alarm each time the Load Current supplied to the heating cable exceeds the defined band The load current is the same as the heater current High and Low V
75. nable efforts to protect against the unauthorised copying and use of the Software by others You agree not to remove disable or circumvent any proprietary notices or labels contained on or within the Software OTHER RESTRICTIONS You may not sublicense rent or lease the DigiTrace NGC 20 handheld Software to anyone You agree to notify Pentair Thermal Management promptly if bugs or seemingly incorrect or anomalous behaviour is discovered when using the Software You agree that the DigiTrace NGC 20 handheld Software including written materials if any and all copies in whole or in part will be destroyed or returned to Pentair Thermal Management at the written request of the Pentair Thermal Management Product Manager By installing or otherwise accessing the DigiTrace NGC 20 handheld Software you acknowledge that you have read and understood Pentair Thermal Management Disclaimer of Warranty and Limitation of Liability set forth below You agree to use reasonable efforts to protect against the unauthorised copying and use the Digilrace NGC 20 handheld Software by others DISCLAIMER OF WARRANTY THE DIGITRACE NGC 20 HANDHELD SOFTWARE AND ACCOMPANYING WRITTEN MATERIALS ARE PROVIDED AS IS WITHOUT WARRANTY OF ANY KIND THE ENTIRE RISK AS TO THE RESULTS AND PERFORMANCE OF THE DIGITRACE NGC 20 HANDHELD SOFTWARE IS ASSUMED BY YOU PENTAIR THERMAL MANAGEMENT DOES NOT WARRANT THAT THE FUNCTIONS CONTAINED IN THE SOFTWARE WILL MEET YOUR REQUI
76. nits which can be connected to one RS 485 serial communications port Baud Rate This field allows you to select the baud rate of the external communication port Selections 2400 4800 9600 19200 38400 57600 Default 9600 Transmit Delay Entry Window TX Delay This field sets the time the NGC UIT will wait after it receives a message before it replies Range 0 1000 milliseconds Default 20 ms Other defaults are Frame Type RTU 8 Data bits No Parity and 2 stop bits These settings may have to be adjusted in order to set up communication between Digilrace NGC 20 control units and non Pentair Thermal Management Host systems like PLC s Tap on the Back button in order to leave this screen and to go back to figure 12 1 16 3 DigiTlrace NGC 20 Display Test The field NGC 20 Display Test will initiate a display test of the DigiTrace NGC 20 Control unit s display Tap on the Back button when done 16 4 Digifrace NGC 20 Mode settings The field NGC 20 Mode will offer the option to switch the mode of the NGC 20 controller If the controller is used in combination with an UIT select Mixed Mode In all other cases select Standard Mode 41 17 USING THE DIGITRACE NGC CMA IN MIXED MODE When operated in mixed mode the feature set of the NGC CMA is adapted to the level of the NGC UIT This means that a number of features as shown in the first part of the operation manual will be hidden in mixed mode
77. oltage Range Min 50 Max 305 V AC The voltage alarm will generate an alarm each time the power supply voltage supplying the NGC 20 control unit and the heating cables exceeds the defined band Heater Time Alarm Range Min 1 Max 1 000 000 hrs The Heater Time Alarm is an hour counter which record the actual time the output is closed and the heating cables are used since the last reset Confirm the new settings by tapping on the Apply button Back will return to Figure 22 1 02 Electrical Settings Alarm Set points screen 2 Electrical Settings Relay Cycle Alar 500000 Cycles Ground Fault Alarm om SSCS Ground Fault Trip 30 mA Ground Fault Trip Disabled i Back Apply Figure 22 3 Electrical Settings screen 2 The Electrical Settings Alarm Set points Screen 2 allows the following variables to be adjusted Relay Cycle Alarm Range Min 0 Max 2 000 000 The Relay Cycle Count counts the number of switch operations the Control output of the NGC 20 has made since the last reset Each switch operation will subtract one 1 from the value entered in the counter When the counter runs empty an alarm will be generated Ground Fault Alarm Range Min 10 Max 250 mA This field holds the value at which an early warning will be generated in the form of a High GF alarm Typical value between 15 and 20 mA Ground Fault Trip Range Min 10 Max 250 mA The Ground Fault
78. on screen Figure 9 1 tap on Temperature Settings NGC 20 Configuration Controller Settings Temperature Settings Temp Source Settings Electrical Settings safety miter Maintenance Alarm Macks Back Figure 9 1 NGC 20 Configuration screen 9 1 Changing NGC 20 Temperature Sensor Type Sensor 1 The first screen of the temperature settings screen enables configuration of the sensors The DigiTrace NGC 20 control unit supports only one type of temperature control input Pt 100 3 wire Temperature Settings Sensor 1 Temperature Sensor 1 Type E Wire 100 Platinunt High Alarmi Setpoint esc Low Alarm Setpalnt 10 C High Alarm Filter Low Alarm Filter sec i B ave Figure 9 2 Temperature Settings Sensor 1 screen The first field Temperature sensor 1 Type offers only two options either 3 wire 100 Ohm Platinum or Not Used only use Not used when there is no temperature sensor connected to this input 9 2 Setting High and Low Temperature Alarm Set Points Sensor 1 High Low Alarm Set point Sensor 1 Temperature Sensor 1 Type 3 Wire 100 Platinum High Alarmi Setpoint esc Low Alarm Setpoalnt 10 C High Alarm Filter Low Alarm Filter 7 sec Figure 9 3 Temperature Settings Sensor 1 screen High Alarm Set point Enter in this field the value at which when exceeded you want the DigiTrace NGC 20 contro
79. rature alarm This low temperature condition will be monitored by the temperature sensor or group of temperature sensors selected for control High and Low Temperature Alarm Filter Range from Min 0 to Max 59940 seconds Alarm filters can be seen as an alarm delay This means that when the temperature drops below the Low Alarm Set point the DigilTrace NGC 20 Control unit will only trigger an alarm when the value entered in the Low Alarm Filter is timed out This means that If immediate action of the alarm output is required that the Low Alarm Filter value should be set at 0 sec Any other value will result in a delay The operation of the High Alarm Filter is the same Hit Apply when done Note that TS 1 and TS 2 are inputs directly connected to the input terminals of the DigiTrace NGC 20 unit whereas the temperature inputs TS 3 to TS 8 are optional through the use TS 1 TS 2 T53 of MONI RMM2 E temperature multiplexing units and an NGC 30 UIT Please refer to the installation instructions of these TS 4 TSS Tse products for more details Lowest Setting the Temperature Control to Lowest means that N A the output of the DigiTrace NGC 20 will be controlled based on the lowest temperature measured by any of the temperature sensors connected to the DigiTrace NGC 20 either direct to the Temperature sensor inputs TS 1 or TS 2 or any other sensor Average connected via MONI RMM2 E and DigiTrace NGC UIT Cancel Aver
80. reen l all available versions of DigiTrace NGC 20 firmware currently present on the NGC CMA firmware folder will be listed Note the Digilrace firmware files are binary files New configuration files need to be placed in the folder Application Data DigiTrace NGC CMA NGC20 Firmware This folder will be automatically installed while installing the application Select the new file by tapping on it and hit OK Warning don t try to upload files other than original files provided by Pentair Thermal Management Any attempt to try to upload false or incomplete files may damage the DigiTrace NGC 20 Control unit Cancel OK Figure 16 3 Selecting Firmware 37 Firmware Update Firmware Update Taq Pst O Derno OFS Current Pintmnvrare A lma Selected Firmware 3 16 23 Finmmware File ss NiO 20 V4 16 bin Current Task Sending Indes 167207 Progress ae Figure 16 4 Uploading Firmware After the new file is selected hit Upload to start the upload process The old Firmware version as well the as the new Firmware are shown on the DigiTrace NGC CMA screen The installation procedure will remove the existing version and install new software in the DigiTrace NGC 20 control unit The installation progress can be followed on the Progress bar and on the installation progress timer Once the upload process is complete the DigiTrace NGC 20 control unit will briefly show the Firmware ve
81. rms screen in order to investigate and eventually reset actual alarms In the Active Alarms field all alarms are shown In the example below only one Limiter Trip Alarm is present NGC 20 Alarms NGC 20 Alarms In order to reset an alarm select the alarm by tapping on that ae aa specific alarm in the Active alarms window and then hit Reset a Selected Alarm The Reset All Alarms button resets all actual safety Limiter Trip Alarm alarms in a single operation Note that Alarms can only be reset after the event causing the alarm has been resolved or the measured value has changed such that the actual reading is within the alarm boundaries Reset All Alarms Back Figure 15 1 NGC 20 Alarms Screen Example a low temperature alarm can only be reset when the temperature has increased to a value above the low temperature alarm set point as shown in Figure 9 5 Temperature Settings Control screen Figure 9 5 Temperature Settings Control screenAfter the alarms are reset than hit the Back button to go back to the main screen NGc 20 Taq BG A Firmware 3 14 13 Back Figure 15 2 NGC 20 Main screen 38 16 FIRMWARE SETTINGS COMMUNICATION SETTINGS Tap on the Firmware Settings button as presented on Figure 8 2 Firmware Settings Firmware Settings Update Firmware enables new revisions of firmware to be EE installed in the DigiTrace Update Fi are NGC 20 controller via the NGC CMA Com Param
82. roved Safety Temperature Limiter Use this limiter to prevent heating applications from overheating The NGC 20 Safety Temperature Limiter is approved for use in Hazardous area Zone 1 Zone 21 Zone 2 and Zone 22 NGC 20 Configuration Tap on Temperature Limiter to open the Limiter configuration N screen Controller Settings Temperature Settings Temp Source Settings Electrical Settings Figure 11 1 NGC 20 Configuration Screen Zi Limiter Parameters Saety i imiter Parameters Fintinerares 20 Safety Limiter Status Tripped Safety Limiter Temperature 117 C Satety Limiter Setpolnt 457 C Reset Tripped Safety Limiter Trip Safety Limiter md Figure 11 2 Limiter Parameters Firmware This field shows the actual firmware revision of the Safety Temperature Limiter Safety Limiter Status This field shows the actual status of the Safety Temperature Limiter Normal operation Tripped Latch Temporarily Disabled Safety Limiter Temperature Shows the temperature actually being measured by the Limiter RTD If this value surpasses the Safety Limiter set point the Safety Limiter Will Trip Open Once the Safety Limiter has tripped a manual intervention will be required to Reset Rearm the Safety Temperature Limiter Resetting the safety Temperature limiter will be only possible after all process conditions have returned to a safe state The Limiter Temperature has dropped b
83. rsion number on the display and return to normal operation Firmware Update Complete Firmware Update Tag Abe O Deno 0S Current Firmware 3 0 0 Notice Pr Fitewace update Cinished succesfully rog ess pc ltl Back Stop Figure 16 5 Firmware update complete If the installation was successful a pop up window will appear confirming the firmware update was successful Confirm this pop up by tapping OK This will close the Firmware upload process and return to the screen of Figure 16 4 Tap Back to close this window Doing this will bring you back to Figure 16 iP 16 2 Changing the serial interface settings of the DigiTrace NGC 20 control unit Firmware Update Complete Firmware Settings Figure 16 6 Firmware Settings screen Tap on Com Parameters to open the Communication Parameters screen 40 Com Parameters Baud Rate TX Delay Frame Type RTU C Frame Type ASCII 6 Data Bits 7 Data Bits No Parity O Ode Parity C Even Parity 1 StopRit gt Stop Bits Back rooy Figure 16 7 Communication Parameters The Com Parameters screen allows users to configure the communication settings of DigiTrace NGC 20 control units Modbus Address the Modbus address needs to be unique on the DigiTrace NGC 20 network The Modbus address can have any value from 1 to 247 247 is the maximum number of DigilTrace NGC 20 u
84. showing the highest and lowest reading recorded since the last reset The value last on was the control temperature of the DigiTrace NGC 20 when the output was switched ON the last time Sensor 1 Temperature This field shows the actual temperature measured by temperature sensor 1 Max Min are showing the highest and lowest reading recorded since the last reset Sensor 2 temperature This field shows the actual temperature measured by temperature sensor 2 Max Min are showing the highest and lowest reading recorded since the last reset Monitoring Screen 5 36 a5 NGC 20 Monitoring Source Temperatures li gt Hot HoE 4 Not e HoE amp Not fi NoE E Not Contactor Cycle Court Reporting 9665 Beck gt Figure 145 NGC 20 Monitoring e Used Trec Used Treci Used Trec Used Source Temperatures This field shows all actual tensor temperatures presently connected Temperature sources 3 to 8 require the use of an optional NGC UIT and MONI RMM2 device Contactor Cycle Count This filed gives the actual number of switch operations the output switch has performed since the last reset Monitoring Screen 6 NGC 20 Monitoring Satety Limiter Status Latch Temporarily Dis Safety Limiter Temperature Heporling 447c Max 2oo c Miiri 19 c Highest Fver 2oo c Lowest Ewer 13 c Number of Hours Since Reset 3 In Use 147 Heater lime Reporting 95 hrs
85. t exceeds the alarm value Contactor Cycle Count Limit Range Min 0 Max 2000000 The Contactor Cycle Count counts the number of switch operations the Control output of the NGC 20 has made since the last reset Each switch operation will subtract one 1 from the value entered in the counter When the counter runs empty an alarm will be generated Heater On Time Range Min 1 Max 1000000 hrs The Heater On Time Alarm is an hour counter which record the actual time the output is closed and the heating cables are used since the last reset Confirm your new settings by tapping on the Apply button Click on Back to return to NGC 20 Configuration screen The Electrical Settings Alarm filters The use of Alarm filters minimizes nuisance alarms by forcing the NGC 20 to verify that the Alarm condition continually exists over the selected period of time before the alarm is being indicated and the alarm relay acts Alarm filters are provided for high and low voltage alarms high and low heater current alarms high ground fault current alarms high and low tracing resistance There is no alarm filter provided for ground fault tip alarms since this sort of alarm requires immediate action Tapping on the field after the Alarm filter name will open a selection screen Only filter times as shown on the screen can be selected High Voltage a jL2 js A Figure 10 5 Electrical Settings Alarm Filters values Once the field conta
86. t makes no warranties as to the accuracy or completeness of the information and disclaims any Liability regarding its use Pentair Thermal Management only obligations are those in the Pentair Thermal Management Standard Terms and Conditions of Sale for this product and in no case will Pentair Thermal Management or its distributors be liable for any incidental indirect or consequential damages arising from the sale resale use or misuse of the product Specifications are subject to change without notice In addition Pentair Thermal Management reserves the right to make changes without notification to Buyer to processing or materials that do not affect compliance with any applicable specification 1 3 Digifrace NGC 20 HANDHELD Software License Agreement This agreement is a legal agreement between you the end user and Pentair Thermal Management LLC Pentair Thermal Management BY INSTALLING OR OTHERWISE ACCESSING THIS PROGRAM YOU ARE AGREEING TO BECOME BOUND BY THE TERMS OF THIS AGREEMENT IF YOU DO NOT AGREE TO THE TERMS OF THIS AGREEMENT DO NOT INSTALL OR ACCESS THIS PROGRAM IF INSTALLING OR OTHERWISE ACCESSING THIS PROGRAM BY OPENING A SEALED DISK PACKAGE PROMPTLY RETURN THE UNOPENED DISK PACKAGE AND THE OTHER ITEMS INCLUDING WRITTEN MATERIALS OR OTHER CONTAINERS TO THE PLACE WHERE YOU OBTAINED THEM GRANT OF LICENSE The DigiTrace NGC 20 handheld Software the Software is licensed not sold to you for us
87. t pipe temperature Additional Entry Fields PASC Min Ambient Temp The Min Ambient Temp is the lowest ambient temperature that was used when the heat tracing system was designed The entered value should agree with the value used by the design engineer to ensure that the heat tracing system was sized correctly Range 73 C 99 F to 51 C 125 F Default 40 C 40 F PASC Min Pipe Size Min Pipe Size is the diameter of the smallest heat traced pipe in the group controlled by this circuit Small diameter pipes heat up and cool down more rapidly than larger diameter pipes therefore the PASC duty cycle is calculated over a shorter time base Larger diameter pipes heat and cool less rapidly the on off periods for the heater system can be stretched over a longer period If electromechanical contactors are being used to control the heater circuit the longer the time base reduces the number of contactor on off cycles and extends the contactor life List 1 27cm 0 5in 2 54cm lin 5 08cm 2in Default 1 27cm 0 5in Power Adjust This allows the PASC control to be adjusted when the heating cable output is greater than the design assumption or if the pipe insulation proves to be more efficient than assumed Pipe temperature may run higher or lower than desired if the heating cable has a different output than required to offset the heat loss The Power Adjust parameter enables a reduction or an increase in the heat tracing effective po
88. tactor PASC contactor Force On Force OFF Cancel gt gt gt gt y Note that depending on the selected control mode the input fields in the previous and next screens will vary Cancel will bring you back to the Controller Settings screen Figure 8 3 Controller Settings 1 On Off controller Settings Temperature Setpolnt asec Switch Control Mode lon Orr Deadharid jire Sett Figure 8 6 Controller Settings 1 On Off is a simple set point on off operation Set in the Dead band Field the desired dead band Note that the Dead band will be above set point Example a set point of 40 C and dead band of 5 will turn the heating off at 45 C and on at 39 C Controller Settings 1 Prop Ambient Contactor Controller Settings Temperature Setpoint orc Switch Control Modhe Prop Ambient Contactor Proportional Bari 27 Prop Ambient Cycle Time 10 min Settings Settings 2 4 gt Back Apply Figure 8 7 Controller Settings Prop Ambient Contactor see PASC below PASC Contactor takes advantage of the fact that the heat loss from a pipe is proportional to the temperature difference between the pipe and the ambient air This is true regardless of heater type insulation type or pipe size Once the heat tracing and insulation on a pipe has been designed to balance heat input with heat loss and maintain a particular temp
89. trol Max Min Temperatures Figure 24 3 Reset Maintenance data Confirm that you want to clear actual maintenance data Tap No to Abort or Tap Yes to clear the actual values A similar screen will be used for other variables as well Reset Maintenance 2 Reset Maintenance Highest Instantaneous Ground Fault Heporling U mA Highest Instantaneous Load Current Reporting 0 4 A Figure 24 4 Maintenance data screen 2 Highest Instantaneous Ground Fault Highest instantaneous Load Current 08 Reset Maintenance 3 Reset Maintenance Relay Cycle Count Reporting 1566 cycles Heater Time Reporting 95 hes Back Figure 24 5 Maintenance data screen 3 Contactor Cycle count Heater Time Reset Maintenance 4 Reset Maintenance Safety Limiter Min Temp ae i Max Temp 180e Reset Safety Limiter hin Mir Figure 24 6 Maintenance data screen 4 Safety Limiter Min Max temperatures Tap on Back when done 97 25 DIGITRACE NGC 20 MONITORING SCREENS Besides its function as a programming and configuration interface the DigiTrace NGC CMA can also be used to monitor Digilrace NGC 20 units while they are in operation When used in monitoring mode all process variables measured by the NGC 20 control units can be visualised on the NGC CMA Tap on the monitoring field to continue This will open the first of a total of 6 available monitoring scre
90. trol Moche i orce On Settings J Slee Figure 8 9 Controller Settings 8 4 Changing DigiTrace NGC 20 device tag name Force On The relay output is permanently switched on user override turns on the power to the heater and leaves it on Force OFF The relay output is permanently switched off user override turns off the power to the heater and leaves it off Note Remember to monitor the pipe temperatures for Low High temperature alarms when selecting Force ON or Force OFF control mode Tap Apply after the desired control mode has been selected Tap on Settings 2 on the bottom of the controller settings screen Figure 8 6 till Figure 8 9 Controller Settings 2 Controller Settings MisC 20 Tag Comeole Unitas Celsius Load Shed Temperature Source Communications inne 10 iir Settings 1 Settings 2 Back Apply Figure 8 10 Controller Settings Settings 2 screen This screen allows you to change the NGC 20 device tag Tags can be 39 characters in length and may contain all numeric characters Enter the desired Tag for the NGC 20 device by tapping in the actual device tag or elsewhere in that field NGC 20 1 Console Units field allows changing the way temperature units are shown on the DigilTrace NGC 20 control units display Temperature can be shown in degrees Fahrenheit or Celsius Load Shed Temperature Source Communications Timeout 14 NGC
91. upport up to 16 different zones These parameters can only be configured using an external communicating device connected to the bridge or DigiTrace UIT Notes e Fail safe mode is always disabled if the SWITCH CONTROL MODE is set to either of the two proportional ambient control modes or the TS CONTROL MODE EXT INPUT FAIL OFF ON The HTC will turn on its output switch when the control temperature becomes less than the highest LOW TS ALARM temperature if the following conditions are met Fail safe mode is enabled Load shedding is active The TS CONTROL MODE uses both TS 1 and TS 2 Both TS 1 and TS 2 have their LOW TS ALARMS enabled A FORCE ON override signal has higher priority than a load shedding signal An INHIBIT signal has higher priority than fail safe mode Back button returns to the NGC 20 configuration screen 49 21 DIGITRACE NGC 20 TEMPERATURE SETTINGS AND TEMPERATURE ALARMS On the DigiTrace NGC 20 Configuration screen Figure 21 1 tap on Temperature Settings NGC 20 Configuration Controller Settings Temperature Settings k Figure 21 1 NGC 20 Configuration screen 21 1 Changing NGC 20 Temperature sensor type Sensor 1 The first screen of the temperature settings screen enables configuration of the sensors The DigiTrace NGC 20 control unit supports only one type of temperature control input Pt 100 3 wire Temperature Settings 1 Temperature Setup High Temp Alarm Min
92. urivnriienencimnanime n ES E EEEE aeneee 50 Dyas Gad Neddi zeree aari a a S E o Sea E Tai 51 21 DigiTrace NGC 20 Temperature settings and temperature alarms ccsesceecenceeeeesescnscnseneeseeeseeenseneens 53 21 1 Changing NGC 20 Temperature sensor type Sensor 1 oo cccceccccsscesssceeseeecseccsseeeseeccseccssecessesesseccsseeesseecseesesseeesseeens J3 21 2 Fal sate mode and Aigh Limit Cut Out Set POM sesiis sr ana a are ea Ea aa n EEEa ESR A an J4 22 Electrical Se CLINGS nenni AEE 55 23 SIL 2 Safety Temperature Limiter SettingS cscceccsececeeceseeeeescnscnscnsessnsensensonsoeeesessnssnsoaseesessneensonsensegs 56 Zale Daly Limiter SCUD OMI srnusivssausiantcantotuantacstnnwsaduiiesusnnstatustntianananad siren tonmianseasaehtesintsnuteiedstantauttoxsireseatiiwiaderatered bitepuusexsexs al 23 2 Resetting Safety Temperature LIMItCr cccccccececeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeaaaaaaaaaaaaaaaaaaaaaaaaeeeeeeeeeeeeeeeeeeeeeeeeseeaaeaeaaaaaas 37 Le LE CE ar e A T E E E A E E TE TA eres eneieeeeesks 397 LA E E e e E E A E E A EA E E E E E EET 60 25 DigiTrace NGC 20 Monitoring screenS c ccccceeeeseeeenecncenseseneenecnscnseesensnsenseesonsoneoesessnsensonsoaseeeessnssnsensaes 62 26 DigiTrace NGC 20 Alarm screens 02cccceecesceneeseeecnsenecnsonseneneeescnsonsensessesssensonsonsossssasensensensessessnesasensses 63 27 Upgrading firmware of the DigiTrace NGC 20 control UMit ccccccceeeese
93. urn to normal operation The value for this timeout is programmable within the controller 30 seconds to 600 seconds Note The controller will return to normal operation if communications between the external communicating device and the controller are disrupted in any way This will return temperature control to the HTC Also the HTC does not perform a periodic autocycle test while operating in load shed mode Load Shedding 2 controller Settings C Zone 8 Shedding Enabled Ul Zone 9 Shedding Enabled Zone 10 Shedding Enabled _ Zone 11 Shedding Enabled C Zone 12 Shedding Enable O Zone 13 Shedding Enabled Zone 14 Shedding Enabled _ Zone LS Shedding Enabled Zone 16 Shedding Enabled Load Shedding 2 Back Figure 20 12 Controller Settings Load Shedding 2 Three parameters must be set in the controller to configure it for load shedding operation 1 The load shedding feature must be enabled 2 The FAIL SAFE MODE parameter must be enabled or disabled depending on the application requirements If FAIL SAFE MODE is enabled then at least one LOW TS ALARM of a TS used in the TS CONTROL MODE must be enabled If the alarm temperature exceeds the CONTROL SETPOINT temperature fail safe mode will be disabled 3 The zone definition flags of an external communicating device that are to be associated with the load shedding action for the controller must be defined The NGC4O controller will s
94. wer by entering a value less or greater than 100 IMPORTANT If improperly used the Power Adjust parameter can cause the piping to get too cold or too hot If unsure leave at 100 Do not change this value unless an engineer calculates the temperature impact on the system and determines that it is safe to do so Be particularly cautious if the circuit has more than one diameter of pipe or type of heat tracing Contact a Pentair Thermal Management representative for assistance with this factor Range 10 200 Default 100 63 BELGIE BELGIQUE Tel 32 16 21 35 02 Fax 32 16 21 36 04 salesbelux pentair com BULGARIA Tel fax 359 56 86 68 86 fax 359 56 86 68 86 salesee pentair com CESKA REPUBLIKA Tel 420 241 009 215 Fax 420 241 009 219 czechinfo pentair com DANMARK Tel 45 70 11 04 00 Fax 45 70 11 04 01 salesdk pentair com DEUTSCHLAND Tel 0800 1818205 Fax 0800 1818204 salesde pentair com ESPANA Tel 34 902 125 307 Fax 34 91 640 29 90 ptm sales es pentair com FRANCE Tel 0800 906045 Fax 0800 906003 salesfr pentair com HRVATSKA Tel 385 1 605 01 88 Fax 385 1 605 01 88 salesee pentair com gt PENTAIR ITALIA Tel 39 02 577 61 51 Fax 39 02 577 61 55 28 salesit pentair com LIETUVA LATVIJA EESTI Tel 370 5 2136633 Fax 370 5 2330084 info baltic pentair com MAGYARORSZAG Tel 36 1 253 7617 Fax 36 1 253 7618 saleshu pentair com NEDERLAND Tel 0800 0224978 Fax
Download Pdf Manuals
Related Search
DIGITRAcE digitrace digitrace 920 digitrace forensics digitrace heat trace digitrace 910 digitrace wayland mi digitrace 910 manual digitrace 920ss3 digitrace raystat-control-10 digitrace michigan digitrace machine works ltd digitrace raystat-eco-10 digitrace 910 series heat trace controller digitrace 920 manual digitrace grand rapids
Related Contents
Avanity TRIBECA-VSB36-CG-C Instructions / Assembly Fiche technique régulateur radio MR24 Galaxy Flex V3 TS1 ThermoShaker user manual (English) PAC1 PRE User guide Change codes.pub Curtis PLED4616A 46" Full HD Black LED TV A300 Service Manual Component Level Supplement Superchips Inc. Video Gaming Accessories 1825 User's Manual Weider CTS 2000 CLUB SERIES SYSTEM 70393 User's Manual User Manual Copyright © All rights reserved.
Failed to retrieve file