SurgeX Axess Elite User Manual
Contents
1. 001238 IU S pa Miu Aux 2 Detar n Soc Slats as al TOOTS 124841 Sequence Control 2 11 Device View tem 3 Description O Overall System Indicates that the surge protection rack temperature line voltage and current draw are at acceptable levels Surge Protection Indicates that the surge protection is fully functional Rack Displays the temperature of the sensor that is connected to the rear terminal Temperature block If the temperature sensor is not connected the display will read NC for Not Connected Line Voltage Displays the true RMS AC voltage Displays the total current draw of all 8 receptacles in true RMS Amps Displays the total power draw of all 8 receptacles in Watts Energy Used Displays the total energy consumption of the equipment plugged into the IN unit in KW Hours since the last counter reset Pressing Reset Energy Usage will reset the KW Hours count Reboot Turns the selected outlets off for the length of the Reboot Time and then back on History Log Displays the internal history log if enabled Global View The Global View page displays the current outlet states and system status for the Axess Elite and expansion units Up to 15 expansion units may be set up on the Links Setup page Device Name 4 8 Aux 1 Aux 2 Sys Stat
2. Table of Contents IX SDXP PROTOCOL 26 OVERVIEW eee 26 HELLO HANDSHAKE o nar n2SSana 4uuznnnnnnnnnnr ran 26 SDXP PACKET eee 27 TYPES LLL LLL eee vsv O P 28 LLL LLLLLLLLLLLL LL LIL L 29 PAYLOADS LLL 31 X FIRMWARE UPGRADES 34 SYSLOG 34 XII REAR PANEL RESET BUTTON 34 XIII SPECIFICATIONS 35 SUR GE e Axess Elite User Manual Pages L Introduction The SurgeX Axess Elite is a single rack space 120V 15 20 AC power conditioner that can be controlled over a network or the internet through a direct serial connection or through a contact closure input The simple web server structure allows basic control of the outlets and viewing of status information all from the home page The extensive programming and setup capabilities are accessed in seven other pages or through a Command Line Interface CLI The Axess Elite incorporates SurgeX Advanced Series Mode power conditioning and surge elimination SurgeX Impedance Tolerant EMI RFI filtering and SurgeX ICE Inrush Current Elimination circuitry on receptacles 1 and 2 SurgeX ICE eliminates problems associated with inrush currents from large loads such as amplifiers With SurgeX ICE it is not necessary to take inrush currents into account when designing the AC power for a system Special time delay circuit breakers are not required it is necessary only to ensure that the average currents of all products plugged into the Axess
3. set current lt 1 8 all gt offset lt 20 20 gt Zeroes the individual outlet current calibration Amps Yes 0 sei power lt 1 8 all gt calibration lt 1 2400 gt Sets the individual outlet power calibration AC Watts Yes set power lt 1 8 gt offset lt 20 20 gt Zeroes the individual outlet power calibration Watts Yes o0 SURGEN Axess Elite User Manual energy intelligence Vil Email Notification Email can be automatically sent for System Triggers and User Triggers Emails generated by the Axess Elite will display the device name and information related to the system Trigger or User Trigger Examples Subject Axess ELITE Cabinet_1 Date Sat 7 Jul 2012 09 41 00 0500 From lt AxessElite surgex com gt TO networkadmin yourco com Axess ELITE Cabinet 1 at 192 168 1 199 oystem Trigger Over Temperature at 115 degrees Alarm Subject Axess ELITE Cabinet 3 Date Sat 7 Jul 2012 09 46 00 0500 From lt AxessElite surgex com gt lt networkadmin yourco com gt Axess ELITE Cabinet_3 at 192 168 1 199 schedule1 processed at 09 46 on 07 07 2012 SNMP Axess Elite Setup and Control functions can be linked to any SNMP v2c manager Up to four SNMP managers may be set Each manager can perform all Setup and Control functions and may receive Trap notifications for System Triggers User Triggers and Manual outlet control Th
4. Axess ELITE mr Nr Nr Outlets and Aux Relays commanded to turn On Off or Reboot for up to 16 Axess Elite units 1 master and 15 expansions In order to have rights to control expansion unit outlets the user s identical user name and password must be programmed into each expansion Axess Elite to be managed SUR GEX Axess Elite User Manual Page 12 energy intelligence Setup Complete setup and configuration of the Axess Elite is provided via 7 Setup web pages Each setup page is described in the following sections Setup Page Configure basic device parameters ce network settings including the network adapter email and time Network Reporting Configure SNMP SDxP and Syslog reporting Configure user accounts Configure System Triggers Create and modify User Triggers Create and modify custom Sequences Create and modify Expansion units and Favorite links Triggers SURGE Axess Elite User Manual Page 13 energy intelligence SS V Web Server continued Device Setup The Device Setup page allows for the specification of basic device parameters Saving any change which requires a reboot to take effect will result in the addition of a Reboot Required button at the bottom of the page Device Setup 2 JDescipio 0 Specifies the name label to be associated with the Axess Elite Power Up Delay Specifies the amount of time in se
5. SURGEX energy intelligence AXESS ELITE Hardware Installation Guide SS 55 AXE pz AXE SX AX15E 5 20 Web Enabled Power Conditioning Energy Management System FIRMWARE VERSION 1 02 222 SurgeX 517 North Industrial Drive Zebulon NC 27597 Customer Service 800 645 9721 Technical Support 800 645 9721 Fax 919 269 0454 www surgex com Table of Contents INTRODUCTION 4 Il INITIAL SET UP 6 COMMAND LINE INTERFACE CLI 55 EE ee ed n 7 SETTING THE IP ADDRESS 9 9 9 9 9 9 9 9 9h 9 9 9h LLL 7 lll INSTALLATION 9 120 VOLT CONNECTIONS ssa 9 ETHERNET CONNECTION eee 9 5232 SERIAL PORT CONNECTION LLL 9 TEMPERATURE SENSOR eee 9 CONTACT CLOSURE NPUT see 9 AUXILIARY RELAY OUTPUTS U 222 fI 9 IV LEDINDICATORS B L 10 V WEB SERVER 1f 11 DEVICE LL LLL 11 GLOBAL VIEW 12 SETUP oe 13 DEVICE SETUP ss eee 14 NETWORKSETUP 2 222 15 NETWORK REPORTING SETUP 16 USERS SETUP eee 17 TRIGGERS SETUP 2 9 9 9h LLL LLL LL LLL 18 USER DEFINED TRIGGERS eee 19 SEQUENCES SETUP eee 20 LINKS SETUP eee 21 Vi COMMAND LINE INTERFACE CLI PROTOCOL 22 PROMPTS U eee 22 SYNTAX 22 RESPONSES ss ee 22 CLI DOCUMENTATION NOTATION LLL 22 DEVICE COMMANDS 0 23 NETWORK COMMANDS 5 5 5 9 9 5 9 9 9 9h LLL 24 CALIBRATION COMMANDS LLL 24 VII EMAIL NOTIFICATION 25 VIII SNMP 25 SUR GE Axess Elite User Manual
6. password uChar desc uChar param uint16 seq T Header Variable type Enumerated type that tells the SDxP server what type of packet is being sent See the Types subsection for a full list of packet types uName password desc This variable is the type descriptor that describes the type of data that is being sent By extension it lets the server know what the payload is There is a different set of descriptors for each type class See the Descriptors subsection for a full list of descriptors by type param Reserved for future use Optional parameter that may be passed to the server in addition to the descriptor packet s sequence number Used as part of the security scheme Payload The payload is determined by a combination of the type class and the descriptor The payloads are described by the descriptor see the Descriptors subsection for details Page 27 SUR GE Axess Elite User Manual energy intelligence IX SDxP Protocol continued Types There are currently 2 types All classes are defined in the C programming enumerated type definition below typedef enum null elype inform elype commands eCmnd Command Description O jelype null 1 This is a null command and should not be sent to the server inform Informs are similar to SNMP traps They are sent from the managed device to the manager on a periodic basis Used to co
7. Description get all get outlets get status get outlet lt 1 10 gt Returns the status of the specified outlet AC outlets are numbers 1 8 Aux Relays A and B are numbers 9 and 10 Sets the selected outlet to the selected state The user must have rights to the selected outlet AC outlets are numbers 1 8 Aux Relays A and B are numbers 9 and 10 get devicename set outlet 1 10 lt on off reboot gt Returns the status of all AC outlets and the following system level measurements Device Name Line Voltage Total Current Draw Total Power Draw Total Energy Used Reboot Time currently in use Delay Time currently in use Temperature On Off status of each outlet Current draw of each outlet Power Draw of each outlet Current Firmware Version Returns the device name Axess set devicename lt devicename gt Sets the device name get reboot Returns the Reboot Time 3 getdelay jRetumstheDelay Time Nf get console 7 Retumsthecurentconsoletimeoutandbaudrate setautologout lt 0 99 gt 7 Setsthe automatic logout timeout of web and CLI minutes 0 no timeout Yes 2 clear shutdown clear shutdown Clears a persistent shutdown state 9600 No C set clear shutdown by user yes no Sets the ability of a user account to clear a persistent shutdown state Yes Yes get upload enable Returns the status of the ability to accep
8. Elite are within the 15 20 Amp product rating Telnet and serial access use the same Command Line Interface CLI structure and syntax to configure monitor and control the Axess Elite The Axess Elite may also be monitored and controlled via SNMP and or the SDxP API and may be configured to report to a Syslog server The internal web server may be secured with Secure Sockets Layer SSL encryption Two Auxiliary Relay outputs are provided for simple control of other equipment Connection terminals are provided for each relay s Common Normally Open and Normally Closed connections Up to 16 Axess Elites can be linked together and controlled from a single web interface One master Axess Elite provides the communication to the users and receives status information from the rest of the Axess Elites in the cluster Up to 128 outlets can be controlled in this manner from one IP address Up to 16 users can be assigned administrator or user only rights plus access to specific outlets The extensive programming capabilities of the Axess Elite allow sequencing and scheduling to be set up User Triggers can be programmed to activate on an if X then do Y then do Z when no longer X basis Triggers include AC line voltage total unit current draw individual receptacle current draw temperature Net Test and Contact Closure Input Actions include turning receptacles on and off cycling a receptacle executing previously defined sequences and sending e
9. RelayStatus ee k i s eCommands getLineVoltage This command is used to get the line None elnforms_LineVoltage eCommands_getLineCurrent This command is used to get the total None elnforms_LineCurrent eCommands getLinePower This command is used to get the total None elnforms LinePower eCommands getSysStatus This command is used to get the None elnforms sysStatus C eCommands poll This command is used to poll None elnforms poll HUN SUR GEX Axess Elite User Manual Page 30 energy intelligence IX SDxP Protocol continued Payloads Payload typedef struct eOutletStatus status 8 tOutletStatus tOutletStatus typedef enum eOutletStatus null eOutletStatus on eOutletStatus off tOutletStatus tAuxStatus typedef struct eAuxStatus status 2 tAuxStatus typedef enum eAuxStatus null eAuxStatus energized eAuxStatus deenergized tAuxStatus tLineVoltage typedef struct float lineVoltage tLineVoltage tLineCurrent typedef struct float lineCurrent tLineCurrent tPoll typedef struct u8 outletStatus 8 u8 auxStatus 2 float lineVoltage float lineCurrent float linePower float outletCurrent 8 float outletPower 8 u8 statusFlags tExpansionUser users 8 tPoll tLinePower typedef struct float linePower tLinePower tOutletCurrent typedef struct float outletCurrent 8 tOutletCurrent Payload EE SUR GEX Axe
10. a temperature reading the external temperature sensor must be connected to the first far left terminal block The sensor has two wires red and black Connect the red wire to pin 1 and the black wire to pin 2 The sensor can be positioned to read air temperature at any location in the rack although the top of the rack would be optimal since heat rises it can also be placed in contact with the chassis of a particular piece of equipment that you want to monitor Contact Closure Input Connect a contact closure control input if any to the 2 pins of the second terminal block Relays switches and push buttons are all suitable input types The actions to be executed upon closing or opening of the contact closure input may be defined as various User Triggers on the Triggers Setup web page Auxiliary Relay Outputs Two auxiliary relay outputs are provided at the third Aux Relay A and fourth Aux Relay B terminal blocks Access to the Common Normally Open and Normally Closed positions is provided for each relay The auxiliary relays are controlled in the same manner as the AC outlets and may be controlled by Sequences Schedules and User Triggers SUR GEX Axess Elite User Manual Page 9 energy intelligen IV LED Indicators There are thirteen LED indicators located on the front panel Their function is as follows I 2 3 4 5 6 7 8 BA BR Self Test BUM m 79 LED Indicators Outlets When illuminated the correspon
11. as been saved it will be available at the bottom of the Device View page and when creating or editing a User Trigger when a sequence is selected as an action Time delay is specified from the previous sequence item not from the initial starting point For example creating a sequence with Step 1 1 second Outlet 1 On and Step 2 1 second Outlet 2 will turn on Outlet 1 after 1 second and Outlet 2 on 1 second after Outlet 1 has turned on This sequence will not turn on both Outlets 1 and 2 at the same time SUR GEX Axess Elite User Manual energy intelligence Page 20 Links Setup The Links Setup page allows for the setup of Axess Elite Expansion units and Favorites Expansion units are other Axess Elite units which will be available for monitoring and control on the Global View page of the master unit Up to 15 Expansion units be defined Favorites may be any internet address Use Favorites to set up shortcuts to earlier versions of the Axess Elite Favorite Name product other equipment web servers or Internet web pages Addresses may be specified with a port number in this format htto IPADDRESS PORTNUMBER for example http 192 168 1 199 72 oaved Expansions and Favorites are available in the Links subsection of the Device View page SURGEN Axess Elite User Manual k E energy intelligence Vi Command Line Interface CLI Protoco
12. conds by which to stagger the manual Reboot Time Specifies the amount of time an outlet is to remain off during a Reboot User Accounts Specifies whether or not a non administrative user account is allowed to Serial Port Requires Specifies whether or not a serial CLI session requires login Login Auto Logout Specifies the web and telnet security timeout in minutes Use History Logging Specifies whether or not to keep an internal log file Allow Firmware Specifies whether or not the Axess Elite is in an upgradeable state Upgrade Outlet Name Allows for the specification of name labels for each outlet Initial State Specifies the state the outlet will take following a loss of power or the clearing of a shutdown event Specifies whether or not to activate Inrush Current Elimination for outlets 1 and 2 SUR GEX Axess Elite User Manual Page 14 energy intelligence TE R Network Setup The Network Setup page allows for the specification of network settings including the network adapter email and time keeping rr ml Saving any change which requires a reboot to take effect si will result in the addition of a Reboot Required button at zm Luar NNNM the bottom of the page Description IP Setup Specifies whether to use Static or DHCP mode Specifies the address to be used when in Static mode and displays the assigned address when
13. d On Off or Rebooted in a predetermined way with specified delay time between each step Using sequences avoids manually turning each outlet on or off individually A sequence as defined for this product is purely a one way sequence That is you do not Modify Edit Delete Run use the same sequence to turn outlets on as you use to turn the same outlets off in reverse Action order One sequence must be created for the Pause Outlet Action EDS Outlet turn on function and then a second sequence b None None gt None gt must be created for the turn off function ES sme None E To create a new sequence press the New Ss None B Sequence button The new sequence must be 1 None gt given a unique name This name should clearly indicate what the sequence will do such as All r or Stage Equipment On There s be up to 16 steps a single sequence eee Select the time delay from the Pause column Select the outlet from the Outlet column Select whether the outlet is to turn off turn on or reboot from the Action column Press the Save button to save the sequence To run a sequence to test it press Run To edit an existing sequence press Edit To delete a sequence press Delete After a sequence h
14. define the protective shutdown IEE See PH points for the AC outlets and take precedence over all other actions including User Triggers See tee tee Triggers Setup 0 Hem Description 0 Hysteresis Specifies the amount by which the associated parameter must return closer to nominal following the activation of a System Trigger for the shutdown to be considered clear For example using an over voltage shutdown point of 150V and a hysteresis of 7 The Axess Elite will enter a shutdown state when the line voltage exceeds 150V and will not leave the shutdown state until the line voltage drops below 150 7 143V Over Voltage Immediately shuts off all outlets if the AC line voltage rises above the set value May Auto Shutdown not be disabled Under Voltage Shuts off all outlets if the AC line voltage falls below the set value May be disabled Auto Shutdown Over Current Shuts off all outlets if the total current draw exceeds the set value Once this has been Auto Shutdown triggered the unit will stay a persistent shutdown state until manually cleared by pressing Clear Shutdown on the Device View page or by issuing the CLI command clear shutdown The over current shutdown point should not be set too close to the anticipated normal operating current draw as this could cause an inadvertent shutdown May be disabled Over Shuts off all outlets if the temperature sensed by the external temperature sensor T
15. ding AC outlet is on Aux Relays When illuminated the corresponding auxiliary relay is latched Self Test Green When illuminated the surge suppression circuitry is functioning correctly Shutdown Amber When illuminated the Axess Elite is in shutdown mode due to out of range line voltage current or temperature Mains When illuminated the Axess Elite is connected to a live wall or CW eS Ble ts connected 1 a Ivo walor SUR GEX Axess Elite User Manual Page 10 energy intelligence The web server is built around 4 pages Login Device View Global View and Setup Each page is discussed in detail below Login The Login page is the first page displayed when a web browser makes a connection to the Axess Elite Enter a valid user name and password in the User and Password fields and press Login to log in to the Axess Elite Device View The Device View page provides information and status for the whole unit and individual outlets as well as basic control of outlets The top left section of the page provides system status To refresh the Status information click the Refresh button For each outlet the Outlet Name Present State Current Draw Power Draw and Energy Usage are displayed OO i k SURGEX Axess Elite User Manual energy intelligence Current itaw Power Draw Energy Usage m op 001027 n 001183
16. e float lineCurrent float linePower float outletCurrent 8 float outletPower 8 U8 picFlags U8 outletRights U8 relayRights tSystemStatus typedef struct U8 outlet eOutletStatus status tOutletCommand typedef struct char relay eAuxStatus tAuxCommand typedef struct unsigned char outlet unsigned char status tInformManualControl typedef struct float voltage tInformOverVoltage typedef struct float voltage MInformUnderVoltage typedef struct float current tInformOverCurrent AorB IIN or F id of outlet to change the state to change to tInformOverTemperature typedef struct int temperature tInformOverTemperature SUR GEX Axess Elite User Manual energy intelligence Page 33 XII Firmware Upgrades To Be Determined Syslog The Axess Elite contains a built in Syslog client When enabled it will send Syslog formatted UDP messages on port 514 Messages will be sent for the following System Triggers Over Voltage Auto Shutdown Trigger Over Voltage Auto Shutdown Clear Under Voltage Auto Shutdown Trigger Under Voltage Auto Shutdown Clear Over Current Auto Shutdown Trigger Over Current Auto Shutdown Clear Over Temperature Auto Shutdown Trigger Over Temperature Auto Shutdown Clear Self Test Failure Auto Shutdown Trigger Self Test Failure Auto Shutdown Clear Example 02 24 2012 13 55 14 System4 Alert 10 1 2 69 02 24 2012 13 55 15 Cabinet_1 System Trigg
17. e Axess Elite MIB is available at surgex com Page 25 SUR Axess Elite User Manual energy intelligence IX SDxP Protocol Overview The SDxP Protocol is a packet based protocol designed to be extensible This protocol is transmitted over TCP on a user defined port The factory default SDxP port is 9100 The protocol uses a Hello handshake to establish unique sequence numbers to allow for advanced security when AES encryption is used With AES enabled all messages must be encrypted with the AES Passphrase set in the device After the Hello a Command and Response sequence follows Any number of Command Response sequences are permitted after Hello Hello Handshake The client sends a Hello message in the form of a text string hello 000 The SDxP enabled Axess Elite will respond with a packet containing the unsigned 16 bit sequence number This sequence number is incremented by the client and server with each correct packet sent Example Cin Sever nello 000 _ 1234 es qM S j j Response Command seq 1237 SUR GEX Axess Elite User Manual Page 26 energy intelligence IX SDxP Protocol continued SDxP Packet The packet is broken up into 2 parts the Header and the Payload Header The header is used to carry general information such as is shown in the C programming structure below typedef struct type char 21 uName char 21
18. e following tools will be required 1 A computer with a web browser Internet Explorer 8 is preferred 2 Network crossover cable supplied in the Axess Elite box 3 The Axess Elite hardware includes the latest firmware pre installed Initial set up steps 1 Disconnect your computer from the current network connection and set the computer to a temporary IP address of 192 168 1 1 Make a note of your computer s original IP settings 2 Connect a network crossover cable between the computer and the Axess Elite hardware the Axess Elite must also be connected to ac power Open a web browser and type the following address in the address bar http 192 168 1 199 4 Login to the web interface by entering user name admin and password admin Navigate to the Setup menu and select Network 6 Change the network information to something suitable for your facility and press Save After saving a Reboot Required button will be available Press this button to reboot the Axess Elite with the updated network settings If it does not perform a manual reboot by briefly pressing the rear panel reset button 7 Disconnect the network cables Restore your computer s original IP settings 9 Connect the Axess Elite to the network it will be installed on If manual static network settings were used you may navigate to the specified IP address to access the web pages If automatic DHCP network settings were chosen you may locate
19. emperature exceeds the set value Once this has been triggered the unit will stay in a persistent Auto Shutdown shutdown state until manually cleared by pressing Clear Shutdown on the Device View page or by issuing the CLI command clear shutdown May be disabled Self Test Failure Shuts off all outlets in the unlikely event that the internal surge protection circuitry fails Auto Shutdown Once this has been triggered the unit will stay in a persistent shutdown state until manually cleared by pressing Clear Shutdown on the Device View page or by issuing the CLI command clear shutdown May be disabled Persistent The Axess Elite will enter a Persistent Shutdown State upon registering an Over Shutdown State Current Over Temperature or Self Test Failure event While in this state all 8 receptacles will be turned Off and the front panel amber LED labeled Shutdown will be illuminated Outlet control will not be restored until the shutdown is manually cleared by pressing one of the Clear Shutdown buttons located on the Device View page or by issuing the CLI command clear shutdown Before clearing the shutdown state it is advised to verify that the combined current requirement of all equipment powered by the Axess Elite is less than the value specified by the Over Current System Trigger and that the measured temperature is less than the value specified by the Over Temperature System Trigger Note that Over Voltage and Under Voltage
20. er Over Temperature Alarm Rear Pane Reset Button The recessed reset pushbutton located on the rear panel to the right of the Network connection performs three functions Reboot Password Reset and Factory Default Reset Pressing the reset button once quickly will reboot the Axess Elite The outlets will be set to the states specified by their Initial State parameters This operation will also clear a Persistent Shutdown State Holding the reset button for 5 seconds or longer will initiate a recovery mode Once the reset button is released the user has 30 seconds to log in to the CLI using the username admin and password admin While in this mode the red Mains LED will flash 0 5 seconds on off Holding the reset button for 5 seconds or longer while powering up the unit will enter factory default reset mode When the button is released the unit will be reset to factory defaults including Network Settings SUR GE Axess Elite User Manual Page 34 energy intelligence Specifications Load Rating 15 20 Amps at 120 Volts SX AX15E SX AX20E Power Requirement no load 5 Watts Surge Let through Voltage 6000 Volt 0 Volts Surge ae 1000 Surges 6000 Volts 3000 Amps B3 pulse measured suppressed voltage UL 1449 Adjunct Classification Test Results 170 Volts no failures Maximum Applied Surge Voltage 6000 Volts Maximum Applied Surge Current Unlimited due to current limiting Maximum Applied Surge Energy Unlimited d
21. in DHCP IP Address inode Subnet Mask the subnet mask to be used when Static mode and displays the assigned mask when DHCP GateWa Specifies the gateway address to be used when in Static mode and displays the assigned gateway address y when in DHCP mode DNS1 Specifies the first DNS server address to be used when in Static mode and displays the acquired address when in DHCP mode DNS2 Specifies the second DNS server address to be used when in Static mode and displays the acquired address when in DHCP mode Specifies the port that the web server will communicate on If the port number is changed from the default value of 80 the Axess Elite s web pages be accessed by navigating to http IPADDRESS PORTNUMBER for Web HTTP Port example http 192 168 1 199 72 SUR GEX Axess Elite User Manual Page 15 energy intelligence V Web Server continued Network Reporting Setup The Network Reporting Setup page allows for the configuration of SNMP SDxP and Syslog reporting Saving any change which requires a reboot to take effect will result in the addition of Reboot Required button at the bottom of the page Network Reporting Setup mm gem _ Desorption SDxP Port Specifies the port to be used with the SDxP exchange protocol The SDxP protocol is the means of communication between master and expansion units all of which must use the same SDxP port and is a
22. l The Command Line Interface provides complete setup of all functions of the Axess Elite The CLI may be accessed either via the network interface using Telnet or via the serial port using a terminal emulator program Some commands of the CLI require administrative rights these are indicated in the following tables Prompts Description Prompt to enter a valid User Name Not case sensitive Prompt to enter the Password associated with the User Name Case sensitive Axess ELITE gt Standard prompt while logged in Axess ELITE Reboot Required gt Prompt after making a change which requires a reboot to take effect Syntax Standard Syntax This command is used to change a parameter set variable lt specifier gt value This command is used to return the value of a parameter get variable This command adds an entry row to any array of variables add array newentry This command renames an entry in an array ren array lt oldname gt lt newname gt DD This command deletes an entry from an array del lt array gt lt entryname gt Responses 0 CLI Documentation Notation Notation jDescipion 0 22 Hyphen Range of acceptable numeric values Vertical Bar Separator for mutually exclusive items choose one Page 22 SURGEN Axess Elite User Manual energy intelligence Vi Line Interface CLI Protocol continued Device Commands
23. lso the API to be used with the Axess Elite SDxP Status Broadcast Specifies whether or not to enable a status broadcast and the SES requenoy otino broadcast messages mies o SDxP Encryption Specifies whether or not to use AES encryption with a shared passphrase Syslog Port Specifies the port to be used with a Syslog server Syslog Server Specifies the IP address of a Syslog server SUR GE Axess Elite User Manual Page 16 energy intelligence Users Setup The Users Setup page allows for the creation deletion and editing of up to 8 user accounts Each user will have a unique user name password and email address and may be assigned access to specific outlet s User accounts may be of the Administrator or Tee i User type Administrators have access to all functions Users do not have access to Setup functions User authentication is supported for Web Serial Telnet and SDxP interfaces New User Allows for the creation of a new user account Save oaves the updated user information Save Closes the edit dialogue without saving any changes SURGEX energy intelligence Axess Elite User Manual Page 17 V Web Server continued Triggers Setup The Triggers Setup page allows for the modification EN of System Triggers and creation of User Triggers Vim Sein Enable yer geAoShudowm Gramer Than m F E 1 1 ep k E System Triggers
24. m proper operation SUR Axess Elite User Manual Page 8 energy intelligance Installation SurgeX Axess Elite is designed to be installed 19 inch equipment rack and requires unit 1 U of rack space Use the four screws provided with the product to secure the rack ears to the rack rails These screws can be tightened by hand and do not require tools Connect power to the unit by plugging the cord into a 120V AC 15 20 amp wall or floor receptacle Do not plug the unit into a relocatable power tap 120 Volt Connections The Axess Elite has a total of 8 receptacles Each receptacle is rated for a maximum load of 15 amps but the total load of the Axess Elite must not exceed 15 20 amps Plug the equipment cords into the receptacles as needed The receptacles are numbered 1 through 8 This same numbering is used in the control interface Ethernet Connection The RJ45 connector for Ethernet is situated on the rear panel beside the Serial connector The default IP Address is 192 168 1 199 RS232 Serial Port Connection The Axess Elite has a 9 pin D subminiature connector for RS 232 serial control The connector is configured as DCE for direct connection to a laptop or other terminal device Default serial parameters are 115 200 bps 8 data no parity 1 stop bit 9600 8 n 1 Contact Closure Auxiliary Relay Auxiliary Relay B Temperature Sensor In order to obtain
25. mails For example an action can be created to send an email if the rack temperature exceeds 95 F The eight rear mounted receptacles can each be individually controlled and the current power and energy consumption of each receptacle can be obtained through the web page interface and CLI The metering includes the AC line voltage and current draw and all measurements voltage current and power are true RMS readings Thus the current draw and energy consumption of non linear electronic loads which have a power factor of less than unity will be correctly reported SUR GEX Axess Elite User Manual Page 4 energy intelligence mm Introduction continued Located on the rear panel are the input power cord circuit breaker 15A or 20A 8 NEMA 5 15 AC outlets Serial connection DCE 9 pin D subminiature Network connection RJ 45 Temperature Sensor input Contact Closure input Auxiliary Relay A B output connections and recessed Reset button Temperature Sensor Closure Auxiliary Relay A Auxiliary Relay B Black _ _ 2 COM NC NO COM NC The thirteen front panel LEDs provide indications for eight AC outlet On Off status green two Auxiliary Relay Latched Unlatched status green surge protection status green Shutdown status amber and AC mains power red 121345678 Shutdown SUR GEX Axess Elite User Manual Page 5 energy intelligence IL Initial Set Up Th
26. ntrol and query the managed device Descriptors Descriptors are used to describe the individual commands within a command class and the payload that the packet contains All of the descriptors and their payloads are outlined by command class below elype Informs Informs are similar to SNMP traps They are sent from the managed device to the manager on a periodic basis typedef enum elnform null elnform outletStatus elnform_auxRelayStatus elnform_lineVoltage elnform_lineCurrent elnform_linePower elnform ouletCurrent elnform outletPower elnform sysStatus elnform poll elnform overVoltager elnform underVoltage elnform overCurrent elnform overTemperature elnform selfTestFail elnform userTriggerClear elnform userTriggerFail elnform manualControl jelnform SUR GE Axess Elite User Manual Page 28 energy intelligence DE S MS LO IX SDxP Protocol continued Descriptors Description 7 Payload Inform elnform_outletStatus This inform is used to tell the manager the status of tOutletStatus all 8 outlets It is also the response to the getOutletStatus and setOutletStatus commands elnform_auxRelayStatus This inform is used to tell the manager the status of tAuxStatus the 2 auxiliary relays It is also the response to the getAuxRelayStatus and setAuxRelayStatus commands elnform_lineVoltage This inform is used to tell the manager the line tLineVoltage voltage It i
27. parameters After setting these parameters the Axess Elite will need to be rebooted for the settings to take effect Any command that requires rebooting of the Axess Elite will provide a prompt to do so All commands may be entered as required before rebooting Example Telnet to default IP address 192 168 1 199 on Port 23 Axess ELITE Connected to Telnet Session 1 User gt admin Password Axess ELITE gt set ipaddress 192 168 1 3 OK Axess ELITE Reboot Required gt set subnet 255 255 255 0 OK Axess ELITE Reboot Required set gateway 192 168 1 7 OK Axess ELITE Reboot Required gt reboot Once the IP address is set the following command can be used to prevent DHCP from altering it set ipmode static Setting the IP address from a DHCP Server A DHCP server will automatically assign an IP address dynamic address as well as Subnet Mask and Gateway to the Axess Elite To enable this feature configure the Axess Elite with the command set ipmode dhcp Then reboot the Axess Elite or enter the command reboot To find the IP address of the Axess Elite you will need to query your DHCP server and locate the MAC address of the Axess Elite in the DHCP server s IP MAC table You can also access the CLI via serial and use the get network command Unix Linux MAC and others Consult your systems administrator for information on how to set an IP Address The unit should be pinged after the IP Address has been set to confir
28. riggerFail elnform manualControl This inform is sent whenever a manual outlet state tinformManualControl change is made SUR GEX Axess Elite User Manual Page 29 energy intelligence IX SDxP Protocol continued el ype Commands Commands are used to control and query the managed device typedef enum eCommands_ null eCommands setOutletStatus eCommands getOutletStatus eCommands getOutletCurrent eCommands getOutletPower eCommands setAuxHRelayStatus eCommands_getAuxRelayStatus eCommands getLineVoltage eCommands getLineCurrent eCommands getLinePower eCommands getSysStatus eCommands poll eCommands Payload eCommands_ null This is a null command and should None None not be used eCommands setOutletStatus This command is used to control an tOutletCommand elnforms OutletStatus individual outlet Note The inform returned as a result of the command will reflect the current outlet state and will not reflect the requested change eCommands getOutletStatus This command is used to get the None elnforms OutletStatus s eCommands getOutletCurrent This command is used to get the None elnforms OutletCurrent eCommands getOutletPower This command is used to n e None elnforms OutletPower eCommands setAuxRelayStatus This command is used to set the tOutletCommand elnforms_AuxRelayStatus Und ptm eCommands_getAuxRelayStatus This command is used to get the None elnforms Auxh
29. s also the response to the getLineVoltage command elnform_lineCurrent This inform is used to tell the manager the total line tLineCurrent current It is also the response to the getLineCurrent command elnform_linePower This inform is used to tell the manager the total line tLinePower power It is also the response to the getLinePower command elnform outletCurrent This inform is used to tell the manager the current tOutletCurrent draw of each of the individual outlets It is also the response to the getOutletCurrent command This inform is used to tell the manager the power draw of each of the individual outlets It is also the response to the getOutletPower command elnform sysStatus This inform is used to tell the manager the entire tSysStatus system status all above metrics It is sent every X minutes by the managed device to keep the manager in sync It is also the response to the getSysStatus command elnform poll This inform is used as the response to the Poll tPoll command The Poll command is used by the Axess Elite to poll Expansion units System Trigger Over Voltage occurs System Trigger Under Voltage occurs System Trigger Over Current occurs System Trigger Over Temperature occurs System Trigger Self Test Failure occurs elnform userTriggerClear This inform is sent whenever any User Trigger clears tlnformUserTriggerClear elnform userTriggerFail This inform is sent whenever any User Trigger fails tinformUserT
30. shutdown events will clear automatically when the line voltage returns to an acceptable level SUR GEX Axess Elite User Manual Page 18 energy intelligence V Web Server continued User Defined Triggers User defined triggers that have previously been created are displayed in a list The name of the trigger is the name that was given to the trigger when it was created Pressing Test Alarm will activate the trigger alarm action and pressing Test Clear will activate the trigger clear action use these test functions to verify that the trigger will operate as intended Pressing Edit will open the trigger for editing and pressing Delete will delete the trigger New triggers may be created by pressing the New Trigger button Trigger Hama Tngger Alarm Action Z None Threshold Temperature High Temp 0 Deg F Target Clear Action rene Ej Target Trigger Executes When Trigger Clears When Temperature High Temperature gt Set Point Temp Set Hysteresis Threshold Alarm Clear Actions Outlet On Outlet Off Outlet Reboot SUR GEX Axess Elite User Manual energy intelligence Page 19 Sequences Setup The Sequences Setup page allows for the creation and modification sequences A sequence is a list of outlets including Auxiliary Relays that Sequence Name will be turne
31. ss Elite User Manual energy intelligence Page 31 IX SDxP Protocol continued Continue p SSS SSS S S tOutletPower tSystemStatus tOutletCommand tAuxCommand tInformManualControl tInformOverVoltage tInformUnderVoltage tInformOverCurrent tInformOverTemperature SUR GEX Axess Elite User Manual energy intelligence typedef struct float outletPower 8 tOutletPower typedef struct eOutletStatus outletStatus 8 eAuxStatus auxStatus 2 float lineVoltage float lineCurrent float linePower float outletCurrent 8 float outletPower 8 U8 picFlags U8 outletRights U8 relayRights tSystemStatus typedef struct U8 outlet 1 8 eOutletStatus status tOutletCommand typedef struct char relay eAuxStatus tAuxCommand typedef struct unsigned char outlet of outlet to change unsigned char status the state to change to tInformManualControl typedef struct float voltage tInformOverVoltage typedef struct float voltage tInformUnderVoltage typedef struct float current tInformOverCurrent typedef struct int temperature tInformOverTemperature AorB N or F Page 32 IX SDxP Protocol continued Payload Continued tSystemStatus tOutletCommand tAuxCommand tInformManualControl tInformOverVoltage tInformUnderVoltage tlnformOverCurrent typedef struct eOutletStatus outletStatus 8 eAuxStatus auxStatus 2 float lineVoltag
32. t a firmware upload No set upload enable yes no Sets the ability to accept a firmware upload Yes N Clears history text log file ves s C Resets all parameters except Network Settings to their factory default settings set factory defaults Axess Elite User Manual SURGEN energy intelligence Confirmation is required Note This command may take up to 30 seconds to execute Ends the session Reboots the unit Will not affect the status of the outlets SI Page 23 Vi Command Line Interface CLI Protocol Network Commands Command _ JjDescripio FactDef get network Retmmthenetworksetinp CS getmc MAC address of the network adapter set ipaddress dotted decimal gt Sets the IP Address in dotted decimal 192 168 1 199 set subnet lt dotted decimal gt Sets the subnet mask in dotted decimal 255 255 255 0 set gateway lt dotted decimal gt Sets the gateway in dotted decimal 0 0 0 0 setdns2 dotted decimal 7 Sets the DNS server 2 address 0 setwebhttpport 1 65535 7 Setsthewebseverpot 0 90 Calibration Commands 777 set voltage offset lt 0 130 Zeroes the voltage calibration AC Vots o _ set current lt 1 8 all gt calibration 1 20 Sets the individual outlet current calibration AG Amps Yes
33. the Axess Elite in your servers DHCP table e p Alternatively the command line serial interface may be used to perform the initial network set up Default user name and password admin admin SUR GEX Axess Elite User Manual Page 6 energy intelligence I Initial Set Up continued Command Line Interface CLI Many configuration parameters may be set using the Command Line Interface CLI The CLI is accessed through the network using a telnet client or through the serial port Open telnet client and point it to the current IP Address of the Axess Elite Factory Default is 192 168 1 199 telnet Port 23 Connect to the Serial port Factory Default is 9600 8 n 1 Upon connection press Enter and then enter the username and password when prompted Factory Default for username and password is admin Setting the IP Address Axess Elite units come with factory default static IP address 192 168 1 199 There are three techniques to setting the IP address of the Axess Elite 1 Terminal Client software via Telnet or Serial 2 Web page 3 Automatically from a DHCP Server To configure the mode to set the IP address access the Axess Elites command line interface CLI and use the set ipmode command as indicated below SUR GE e Axess Elite User Manual Page 7 energy intelligence I Initial Set Up continued Setting the IP address using CLI These are the basic commands to set the network
34. ue to current limiting C62 41 1991 category 1 KV gt 500 000 3 KV gt 10 000 6 KV gt 1000 pulses MM 40 dB 100 KHz 50dB 300 KHz 50 MHz 50 MHz load EMI RFI Filter Mode 90 1 KHz 30 dB 1 MHz 50 dB 5 MHz 50 dB 20 MHz Under Voltage Auto Shutdown Adjustable from 80V to 110V or disabled Over Voltage Auto Shutdown Adjustable from 130V to 160V Over Current Auto Shutdown Adjustable from 1A to 20A or disabled Over Temperature Auto Shutdown Adjustable from 70 to 100 F or disabled Voltage 1 from 90 160 1 from 0 1 20 Arms Resistive Measurement Accuracy 5 trom 0 1 2400 Waws Resistive 10 100 Ethernet connection on Female RJ 45 Auto Negotiating with 10 100 1000 network connections with Link and Activity LEDs 19 W x 12 25 D x 1 75 H Single Rack Space 0 to 95 R H Non condensing ESU i i i l l i i i l i C l l i l l l i l li lil il ll l lD l lD qq Dll lili i 1 2 x 50 microsecond industry standard combination wave surge as per IEEE C62 41 CAUTION Do not install this device if there is not at least 10 meters 30 feet or more between the electrical outlet and Network Port the electrical service panel SUR GEX Axess Elite User Manual Page 35 energy intelligence