Home

PRODUCT MANUAL

image

Contents

1. RETURN TO TOC 5 if using a 16 30VDC mains charger then plug this into the socket shown in the picture below Alternatively the charger may be wired into the solar panel screw terminal block to the left of the socket 6 Once all your cables are plugged in you need to fully test the system When you are happy that everything is connected and working properly you need to fill the cable entry point with expanding space filler foam Fill down the first 5 to 10cm 2 to 4 of the conduit This is to prevent insects and or moisture damaging the system 1 Follow instructions on the previous page to drill out the cable entry point for routing cables through conduit 2 Use four M8 screws bolts or coach screws to secure the box to the wall Use flat washers between the screw head and the box Do not overtighten the wall mounting bolts as permanent damage may occur to the electronics enclosure 3 Follow instructions 3 6 on the previous page for routing the cables through conduit RETURN TO TOC MACE AGRIFLO SER ES3 PRODUCT MANUAL 25 12 0 Installing additional cards Users are advised to download data and stop the AgriFlo prior to installing additional cards See Chapter 24 and Chapter 27 for details 1 Open the Series3 enclosure and remove the three screws using a 2 Phillips screwdriver fastening the PCB clamping bracket Take care not to drop screws in the box as damage may occur to the ci
2. S EA E H HH H H Ha Charger Input 16 30VDC Centre of jack is positive G External Battery Input _ ae XT 12VDC z Charged by Series3 Device L E Doppler Sensor lll e i yA UE Serial Communications Port Solar Panel Charger Input 16 30VDC Use with Solar Panel or Mains Plug Pack Pole Cable Entry Point Conduit Cable Entry Point NOTE Door not shown ELECTRONICS MODULE UNDERSIDE RETURN TO TOC MACE AGRIFLO SER ES3 PRODUCT MANUAL 21 10 0 Installing the AgriFlo on a 2 pole The sensor and power cables can be routed either directly through the inside of the 2 mounting pole or through electrical conduit Installation directions for both are provided below MACE recommends that the AgriFlo Series 3 electronics module be mounted so that the LCD faces in a direction away from direct sunlight 10 1 Sensor and power cables routed inside the pole 1 Place the electronics module on a work bench and using a hammer and screwdriver carefully knock out the plastic cable entry point from the rear of the enclosure It is only thin plastic and is designed to break away at the edges so work your way around the edge of the oval shape until the cover is completely broken free of the unit IMPORTANT Apply NON ACIDIC cure silicon sealant to the back of the electronics module in the channel around the cable entry point This will stop water flowing down the po
3. MACE FloCom Plus main screen click Connect gt Direct and the Connect to device dialogue box will appear This counter code has a time limit on its validity typically three days It must be used to access the unit within this time or it will be void and a new one will need to be produced Enter the 16 digit authorisation counter code into the Password field and click continue You will now have super user access to the device A You should immediately change the super password to one that will not be forgotten see Chapter 18 3 for details RETURN TO TOC MACE AGRIFLO SER ES3 PRODUCT MANUAL 35 18 0 System information 36 SECTION A HARDWARE MANUAL From the main menu click System and the following drop down menu options will appear as listed below FlocomPlus IOl x Disconnect Start device Download view totals Settings Real time data System Clear stored data Set device date time i l j 7 Module check Change download password Change super password m The force in flow Site id Device type AgriFlo M5 Battery status 12 2 Y OK Serial No 19414 External power 0 3 W Firmware version 1 00 7 Device time on connection 10 05 2007 11 37 09 AM Local connection 57600 Stopped 5 System settings 18 1 Set device date time The device date and time must be set correctly x Current device time so that data can be accurately matched t
4. Velocity Sensor Undershot Gate Valve Looking up stream 2x D Before 6x D After 6x D Before 4 SECTION A HARDWARE MANUAL RETURN TO TOC RETURN TO TOC MACE AGRIFLO SER ES3 PRODUCT MANUAL 5 6 SECTION A HARDWARE MANUAL 3 0 Site selection continued SOHSHSHOSHEHSHEEHHEHSHHHHEHSHSHHHEHHEHHSHOHEHHEHHHSHHEHHHHHHHEHSHESHEHHEHEHHHEHHEHHHHHEHEHHHHHEHHSHHEHHHSHHEHHEHSHEHEHHOHHEHSHHEHEHHEHEHEHHEHEHEOHESOHEORESEOHEOLEOOE 6 Where is the best place to mount the sensor in a Full pipe The sensor should be mounted on the side wall of the pipe between the 2 and 5 o clock positions A ball valve should be used when mounting Insert type sensor to allow for easy maintenance SENSOR MOUNTING POSITION FULL PIPE V v_ IX X WARNING Don t mount the sensor at the top of the pipe as air pockets could give unreliable readings Don t mount the sensor at the bottom of the pipe as silt build up can cover the sensor Only mount the sensor between 2 and 5 o clock as shown above 7 Where is the best place to mount the sensor in a partially full pipe or channel The sensor must be mounted such that the depth sensor is always covered by water to a depth of at least 50mm 2 inches Refer diagram over page 8 Is there likely to be silt build up over the sensor If this is the case MACE recommends mounting the sensor on the side wall of the pipe instead of near the bottom of the pipe Refer diagram over page 9 Is there enough sunlig
5. Agrio Mace AgriFlo Series 3 Product Manual Product Support Should you experience difficulty in using this product please contact your supplier We also welcome feedback from customers who feel that their experience may provide an improvement to the product or may be beneficial to other users Please go to www macemeters com Disclaimer No warranties of any nature are extended by this document Measuring and Control Equipment Co Pty Ltd MACE will not accept any financial or other responsibility that may be the result of your use of this information including direct indirect special or consequential damages You must be careful to ensure that the use of this information complies with the laws rules and regulations of the jurisdictions with respect to which it is used MACE assumes no responsibility for personal or property damage caused by the misuse of this equipment Copyright Information in this document is subject to change without notice The software described in this document is furnished under a license agreement or nondisclosure agreement The software may be used or copied only in accordance with the terms of those agreements No part of this publication may be reproduced stored in a retrieval system or transmitted in any form or any means electronic or mechanical including photocopying and recording for any purpose other than the purchaser s personal use without the written permission of Measuring amp Co
6. Apply If one is present select the modem which will be used if remote communication will take place with the device The Flo device must also have a modem attached to it at the remote site Click Apply to save the settings MACE AGRIFLO SERIES3 PRODUCT MANUAL RETURN TO TOC 33 17 0 Connecting to the device 17 1 Connecting to the device using the serial port 1 Unscrew the cover from the communications port 2 Connect a MACE serial cable Part No 891 300 between the serial port of the computer and the serial port of the FloSeries3 device located on the underside of the electronics module Underside of Electronics Module 3 Click Connect gt direct Enter the password which has been set in the unit and select continue The default password is superid 4 The MACE FlocomPlus dialogue box appears featuring the main menu which includes the device status summary screen as shown below Fjmace FlocomPlus 4 mfe x File Connect FloCalc Help direct Mm The f H MACE FlocomPlus 15 x Disconnect Start device Download View totals Settings Real time data System gine one The force in flow Site id Device type AgriFlo M5 Battery status 12 2 V OK Serial No 19414 No connection External power 0 3 Firmware version 1 00 7 Device time on connection 10 05 2007 11 37 09 AM Local connection 57600 Stopped 5 A The dev
7. 16 18 19 20 22 d2 24 25 26 27 28 28 do 29 ag Section B Software Manual CHAPTER 15 0 Introduction to Flocom 16 0 Installing the software 17 0 Connecting to the device VA Connecting to the device using the serial port 17 2 What to do if the password is lost forgotten 18 0 System information 19 0 Configuring the device 20 0 Configure new channel 20 1 Flow calculation tab sheet 20 2 Sensor parameters tab sheet 21 0 Configuring FloS Card 21 1 Configuring a FloSI 21 2 Serial Interface Settings 22 0 About real time data 23 0 Realtime data 24 0 Start Stop device 25 0 Disconnect 26 0 View totals 27 0 Downloading stored data 28 0 View downloaded data file PAGE 31 32 34 34 35 36 38 39 40 44 52 52 53 57 61 62 62 63 64 64 Section A Hardware Manual Mace AgriFlo Series 3 1 0 Introduction to AgriFlo Series 3 This manual describes the installation use and maintenance of the AgriFlo Series 3 The AgriFlo Series 3 typically consists of four main components e The electronics module e The sensor s e The solar panel or power supply e Flocom software enabling you to configure and download your AgriFlo Series 3 Solar Panel Electronics Module Insert Velocity Sensor N oO Velocity Depth Sensor N vee O RETURN TO TOC MACE AGRIFLO SERIES3 PRODUCT MANUAL 1 2 SECTION A HARDWARE M
8. Configuration of the FloSI requires MACE Flocomt software and successful PC communications with a MACE Flo Series3 device The FloSI configuration settings are available from the settings menu of Flocom as detailed in the software section of this manual Installing the FloSi Card Install the FloSI card as per the procedure outlined in Chapter 12 0 Installing additional cards Wiring the FloSI After installing the card connect it to the remote device using either 1 The 9 pin d connector RS232 ASCII or RS232 ModBUS for RS232 2 The 4 way terminal block for RS485 ModBUS mode 3 The 3 way terminal block for SDI 12 mode Pin out details for the various connectors are printed on the back of the FloS card and below FloSI Card Diagram RS485 Pin 1 Ground Pin 2 D1 Pin 3 DO Pin 4 12V Out SDI 12 Tr Pin 1 Ground Pin 2 Data RS232 Pin 3 12V Out Pin 2 Transmit Data TxD Pin 3 Receive Data RxD Pin 5 Ground GND Pin 7 Ready to Send RTS Pin 8 Clear to Send CTS RETURN TO TOC MACE AGRIFLO SER ES3 PRODUCT MANUAL 27 14 0 Maintenance Depending on the physical location and the type of flow being monitored the AgriFlo Series 3 may require regular maintenance Should the instrument require servicing it must be returned to your vendor 14 1 Battery maintenance The AgriFlo Series 3 internal battery if kept fully charged should last many years However if the battery
9. available from the Settings menu of Flocom 21 1 Configuring a FloSI Establish communications with the device as per Chapter 17 Connecting to the device Ensure at least one Doppler card is configured as per Chapter 20 Configuring new channel Then check the FloS enabled box FJ aoriFlo settings Click FloSI and then click Change to select the output mode that you wish to use Site Id Test Measurement interval 30 sec v Logging interval 30 sec x V Event logging Channels v Edit channel New channel Remove channel Select output mode Select new mode sp1 12 v V Flasher enabled IV FloSI enabled R5232 ASCII Modbus R SDI 12 52 SECTION B SOFTWARE MANUAL RETURN TO TOC 21 2 Serial Interface Settings The FloSI can only be configured to use one serial protocol from the three available The parameter values are provided in the user configured units 21 2 1 RS 232 ASCII Mode The line transmission characteristics are as follows Baud rate 9600 Data bits 8 Parity None Stop bits 1 In this mode the FloSI is dormant while RTS is inactive On RTS going active the FloSI transmits the most current result string from the Flo Series3 device If RTS is active when a scheduled sample is made then the string is transmitted immediately on completion of the measurement The transmitted ASCII text string starts with the character asterix ends with a c
10. Channel 4 total Channel 5 Channel 6 total Channel 7 Channel 8 Channel 9 Channel 10 Channel 11 Channel 12 Channel 13 Channel 14 Channel 15 Channel 16 Channel 17 Channel 18 Channel 19 Channel 20 flow rate flow rate Notes 1 Register byte order is big endian 2 Float values are formatted according to IEEE 744 32 bit representation Type float float float float float float float float float float float float float float float float float float float float 3 Flow total has a range from 0 to 999999 9 4 Registers corresponding to parameters which are not configured to be measured or calculated contain random values Size bits Registers 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 Sub code dec 00 04 10 18 N NINININININININININIJINININININIJININIJNIJN Register s 40001 40002 40003 40004 40005 40006 40007 40008 40009 40010 40011 40012 40013 40014 40015 40016 40017 40018 40019 40020 40021 40022 40023 40024 40025 40026 40027 40028 40029 40030 40031 40032 40033 40034 40035 40036 40037 40038 40039 40040 5 AgriFlo channel outputs are in order of channel configuration as per AgriFlo settings SECTION B SOFTWARE MANUAL RETURN TO TOC 21 2 3 SDI 12 Mode The SDI 12 implementation complies with V1 3 of the SDI 12 specification Configurable parameters are e Address 0 9 A Z a 2 e
11. Strap mount with depth Type circular pipe Pipe diameter 0 45 m Range 4 0 mis Integration period 5 S Calculation method Pump method elocity Max measurement count g Peak threshold 100 2 point calibration Offset adjust Offset 10 0 Apply Close Velocity maximum Sensor orientation measurement count MACE AGRIFLO SER ES3 PRODUCT MANUAL 45 20 2 Sensor parameters tab sheet continued Velocity integration period The integration time is the period in which samples of the velocity spectrum are taken before an average velocity reading is calculated The minimum integration time is 4 sec and the maximum integration time is 180 seconds and may be reduced automatically by the measurement interval and the maximum measurement count depending upon the instrument configuration The integration time may be varied for several reasons e Under field conditions where the flow is fluctuating dramatically increasing the integration time will help to get a more accurate average velocity reading because more samples are available to calculate the average e Under field conditions where the flow has a low number of acoustically reflective particles increasing the integration time will help to get a more accurate average velocity reading because more reflective targets will be sampled to calculate the average The power consumption of the system is affected by the integration time The longer th
12. Where X depth of stream The co efficients are listed in order A B C D E F Import parameters from FloCalc The Mace utility program FloCalc download separately from www macemeters com can be used to draw regular and irregular channel shapes These shapes are then converted into a 5th order polynomial Their co efficients can be imported directly into the appropriate fields in Flocom by clicking Copy to clipboard and Exiting from FloCalc See separate user manual Depth limit When the cross sectional area of a stream is calculated using the polynomial co efficient method the user must set the depth limit at which the polynomial reaches a maximum For example if a channel has a maximum depth of 1 5m the depth limit should be set at 1 5m as well SECTION B SOFTWARE MANUAL RETURN TO TOC Polynomial coefficients mife fs Profile Designer Unit Converter 2 72063162522315E 14 B 0 300000000002602 C 5 84181845312908E 11 D 5 04093445803045E 10 E 1 84671865115328E 9 F 2 41626452295084E 9 Max height 0 3 Max area 0 09 Max area error 8 7941 7694221 729E 9 Max area eror 9 771390771357477E 6 Units m RETURN TO TOC MACE AGRIFLO SERIES3 PRODUCT MANUAL 43 44 SECTION B SOFTWARE MANUAL 20 2 Sensor parameters tab sheet Sensor Orientation Under usual field conditions the velocity sensor should be positioned so that the transmitted beam is faced upstream F
13. by the sensors This is useful if you think there may be irregularities in the flow at the site or you want to check the operation of the unit e Download data from the AgriFlo Series 3 FloComt is available for download at www macemeters com RETURN TO TOC MACE AGRIFLO SER ES3 PRODUCT MANUAL 7 4 0 Sensor types The AgriFlo Series 3 sensors measure the amount of water flowing in the pipe using one of two methods When the pipe is full only the velocity of the flow is measured as the cross sectional area of the flow is constant In partially full pipes or open channels the velocity and depth of the flow are measured in order to calculate flow rate A combination of up to three MACE velocity and or MACE velocity depth sensors may be installed and configured 4 1 Insertion sensors This type of sensor is used in full pipes where access into the pipe is impractical or when it may be necessary to remove the sensor in the future without stopping the flow or emptying the pipe Insertion sensors require access to the outside wall of the pipe in which the sensor is to be mounted The 2 insertion sensor should be used in pipes that have a diameter of greater than 100 mm 4 NOTE MACE recommends that a ball or gate valve is always used when installing insertion sensors so that sensor maintenance can occur without requiring the pipe to be emptied of liquid 4 2 Strap mount sensors Strap mount type This type of configu
14. exhausted they are light pink The crystals should be replaced when they first appear to be light pink The following procedure should be followed to change the crystals 1 Remove the large rubber stopper on the bottom of the filter housing This is the stopper without the tube attached 2 Empty the filter chamber of exhausted crystals 3 Add new crystals MACE Part No 590 009 to the filter chamber so that there is enough room for the rubber stopper to be replaced 4 Replace the rubber stopper Ensure that the reference filter tube is not crimped as a blockage will result in incorrect depth readings from the sensor The longevity of the silica gel crystals is dependent on the amount A of moisture in the atmosphere in which the instrument is mounted It is recommended that the crystals be checked at least ona monthly basis A Do not eat the crystals Wash hands after use RETURN TO TOC MACE AGRIFLO SER ES3 PRODUCT MANUAL 29 30 Section B Software Manual FloCom for Mace AgriFlo Series 3 SECTION B SOFTWARE MANUAL RETURN TO TOC 15 0 Introduction to FloCom This manual describes FloCom and way it is used to configure calibrate and extract data from MACE Flo Series3 devices System Requirements Minimum system requirements for PC are Windows XP e Serial port or USB to Serial Adapter e 4Mb available hard drive space Windows is a registered trademark of Microsoft Corporation in the United States and
15. parameters Flo wrate th resh old Flowrate threshold fo 1 Mifday Flowrate units m liday F l owrate un i ts elocity correction None Change Edit Polynomial coefficients amp 0 000000 Depth limit 0 300000 m B 0 300000 Ree Change Edit D 0 000000 E 0 000000 F 0 000000 Siltation depth o o m Siltation depth Flow volume units mi Flow volume units Apply Close Polynomial coefficients Velocity correction EjPolynomial coefficients Oj x Flow area A Bx Cx Dx fF velocity factors O x where x depth elocity Factors o o Depth limit fo 3 m eee a B fo 3 Zone Factor Upper depth limit o o i fi 0 Max depth D bo 8 J fi 0 o o m E o o 3 fi Oo o o m E o o 4 41 0 o o m RETURN TO TOC MACE AGRIFLO SERIES3 PRODUCT MANUAL 41 20 1 Flow calculation tab sheet continued Polynomial function Used if flow in partially full non circular shaped pipe or open channel A The polynomial function will ONLY be visible when other conduit type 42 is selected See Chapter 20 2 for details Polynomial co efficients When the stream flow is in an open channel non circular the user must determine the cross sectional area and relate it to depth via a polynomial equation MACE Flo series instruments can use 5th order polynomial equations The polynomial co efficients listed in FloCom are related to the following equation Cross Sectional Area A B X C X2 D X3 E X4 F X5
16. the depth sensor is displayed at the top of the window and is P y P Current raw value 14 642 updated approximately once per second mist point Rawvalue 1 625 Set To carry out a two point calibration prepare the measurement set up for the first calibration Depth 102 m point and when the current raw value has PE stabilised click on Set in the 1st point Rewvalue 14642 Set box The current raw value is copied to the Depth 1 985 m Raw value field and the Depth field is enabled Enter the actual depth value in the ay ome Depth field Now prepare the measurement set up for the second calibration point and repeat the procedure in the 2nd point box Click on Apply to calculate the new slope and offset parameter values for the associated depth channel Clicking on Cancel terminates the procedure without altering the parameter values RETURN TO TOC Offset adjust This function is used to fine tune the depth reading whenever the sensor is deployed or reading inaccurately For example the depth sensor may be sitting slightly off the bottom of the stream or the user has deployed it above a silt line on the side of a pipe The offset adjustment function is selected by clicking on Offset adjust The Depth Offset adjust dialogue box appears The depth value is displayed at the top of the window and updated approximately once per sec
17. the pump method should be used Surface wave rejection In severely turbulent open conduit flows such as encountered in a sewerage system it is common for standing waves to develop in the flow stream If situated closely these standing waves surface waves may confound a Doppler ultrasonic sensor because they typically result in reflections of a significantly slower velocity In the diagram a surface wave can be seen as a sharp peak on the real time graph at about the 0 2 m s mark 0 0 1 0 2 0 3 0 4 0 Velocity m s RETURN TO TOC MACE AGRIFLO SER ES3 PRODUCT MANUAL 47 20 2 Sensor parameters tab sheet continued In this case if the user selects the surface wave rejection calculation method a menu item called low end cutoff will be displayed This feature enables the user to force the Flo series instrument to ignore Doppler shifts that lie between zero and the low end cutoff The low end cutoff is a percentage of the range x axis of the real time graph In the diagram the low end cutoff would be configured to about 10 of the graph That is any data that are received between 0 and 0 4m s will be ignored when computing an average stream velocity greyed area not represented in actual real time graph Gravity method This method should be used wherever a stream is slow moving and or contains few acoustically reflective particles Because this calculation method is designed to enhance the velocity processing of slow movin
18. 12 Now tighten the M8 nuts on each side of the mounting bracket to secure 13 The cables from the solar panel charger to the electronics unit must be enclosed to minimise exposure to the elements The cable should be either routed through conduit or through the solar panel mounting pole You will need a hole drilled in the mounting pole at the top near the solar panel as well as a cut away where the electronics unit is to be mounted Refer to the pictures below RETURN TO TOC MACE AGRIFLO SER ES3 PRODUCT MANUAL 17 T NOTE The electronics module I MACE highly reccomends the use 8 1 Solar panel installation on a 2 pole continued 14 Ensure that the cable from the solar panel is terminated using the three pin connector provided in the electronics box and that the polarity is correct The photo below shows the location of the three pin connector inside the AgriFlo 15 The polarity is labelled on the circuit board near the connector NOTE When wiring the solar panel either of the ground ve terminals may be used should be installed before connecting the solar panel Refer to Chapters 10 amp 11 for more detail of Tri spikes on the top of the solar panel to reduce accumulation of bird droppings on the front face of the solar panel 8 2 Installing a MACE mains powered trickle charger In certain applications or where the use of a solar panel is impractical or undesirable the AgriFlo can be powered from any DC sou
19. 7 5 19 1 IChannels 3 INames Pipe 1 Pipe 2 Pipe 3 IUnits cuftis cuFtis cuFkjs IPoints 60 To file FloSenes 3 Manuals UserHelp prin eae Start download Cancel Status 2008 02 06 12 52 02 Note Unit started 2008 02 06 13 00 00 4 51 15 6 15 48 messages 2008 02 06 13 00 00 Note No external power 28 0 Vi ew d own loa d ed data fi le 2008 02 06 13 00 00 Flow start Pipe 1 0 1 2008 02 06 13 00 00 Flow start Pipe 2 0 3 2008 02 06 13 00 00 Flow start Pipe 3 0 3 2008 02 06 13 15 00 7 7 14 34 13 85 Time stamped a ye 2008 02 06 13 30 00 6 39 16 22 14 26 d This function is accessed via the File function on the Start up menu and sided aer ata Mf l 4 LA gt then selecting the View download file option aroomi aE Opening a file 2008 02 07 00 30 00 5 2 14 48 14 8 End of file data continued On entry an open file prompt window is displayed If downloaded data was saved during the current session the last downloaded data file appears as NOAOA DATAN A mera 2008 02 07 03 45 00 Note Unit stopped the default selection On selecting Open the selected file is loaded and if successful the data is displayed as a text file A different downloaded data file may be selected at any time by selecting the local File function and repeating the file selection procedure Time stamp tree view 64 SECTION A HARDWARE MANUAL RETURN TO TOC RETURN
20. ANUAL A 2 0 Warnings 2 1 Intrinsic Safety The AgriFlo Series 3 is NOT an intrinsically safe instrument and should not be installed in hazardous explosive environments Should an intrinsically safe instrument be required MACE can offer other instruments with this approval level 2 2 Floods MACE recommends that the AgriFlo Series 3 electronics module be mounted above known flood peak levels MACE will not be liable for damage caused by flooding The unit is weatherproof but NOT waterproof and should NOT be submerged 2 3 Sunlight MACE recommends that the AgriFlo Series 3 electronics module be mounted so that the LCD faces in a direction away from direct sunlight ie South in the Southern Hemisphere and North in the Northern Hemisphere 2 4 Cable damage MACE recommends that all cables be appropriately routed through electrical conduit or other similar mechanism MACE will not be liable for damage to cables especially if it is caused by vehicles digging implements animals or debris in the pipe or channel 2 5 Insects and moisture After the AgriFlo Series 3 system has been installed and fully tested MACE recommends the use of expanding space filler foam down the first 5 to 10cm 2 to 4 of the conduit or mounting pole to prevent insect moisture ingress 2 6 Battery life Care must be taken when a mains power supply is used to charge the internal battery instead of a solar panel If the mains power remains discon
21. ANUAL 11 RETURN TO TOC 6 0 Installing a sensor on a plastic strap These plastic polypropylene straps are typically used to mount the sensor in locations where temporary monitoring will take place or when it is undesirable to drill in to the pipe wall They allow for both very quick installation and removal of a strap mount sensor 1 Hold the sensor so that you can see the eyes of the sensor in front of you the sensor cable running to your left 2 Place the mounting strap on the ground or a bench so that you can see the chamfered edge of the strap in front of you Place the toe of the sensor into the front of the hole in the strap Press the body of the sensor down onto the strap 3 Turn the whole assembly over Make sure the cut out in the strap sits down around the foot on the sensor 4 You should see six countersunk holes in the strap Fit the six screws supplied M3 x 8 mm Phillips head countersunk 304 s s Use only a hand screwdriver Do not over tighten these screws as permanent damage to the thread may result 5 Tie the cable to the plastic strap using the holes and cable ties provided Make sure that the knob of the cable tie sits to the back of the assembly out of the flow DO NOT OVERTIGHTEN CABLE TIES 6 Place the strap so you are behind the sensor looking upstream Upstream is preferred due to better debris shedding characteristics A of the bevelled leading edge but not critical a
22. DOES NOT exceed the flow rate threshold see Chapter 20 1 Flow calculation tab sheet is calculated on all of the channels at the same time no data is logged for Data is logged in the data file that time stamp ONLY at the logging interval If a value that exceeds the flow rate threshold has been calculated on at least one of the configured channels at the defined logging interval then data is logged for that time stamp The measurement interval will always be shorter than or equal to the logging interval In the case of the measurement interval being shorter than the logging interval then the data logged will be the average of those values calculated per measurement interval Log totals 12 hourly When selected this function records the accumulated total of each channel in the data at midday and midnight If unselected the accumulated totals are logged ONLY at midnight RETURN TO TOC Ej AsgriFlo settings i O x Site Id Farm 123 Measurement interval 3 min Logging interval s min IV Event logging IV Log totals 12 hourly Flasher enabled This function activates the high intensity LED on the front face of the device The LED will flash if a value that exceeds the flow rate threshold has been measured on any of the configured channels Channels Edit channel New channel Remove channel Flasher enabled Apply Exit 20 0 Configure new channel 1 From the AgriF
23. Directory C MaceFlocomPlus BACKUP Browse 5 Selecting a Program EUN Manager Group Mace utilities is the default group and we suggest leaving this as is Enter the name of the Program Manager group to add Mace FlocomPlus icons to MACE utilities Accessories Administrative Tools Games Cancel RETURN TO TOC 6 Starting installation Click Next to begin installing FloCom 7 FloCom will now install Once the software installation is complete click Finish to exit the setup program FloCom is now ready to be used 8 Run FloCom using the shortcut provided on your desktop The startup menu will appear as shown below Click File gt Comms settings to configure FloCom for your computer aces The force in flow Hjmace FlocomPlus File Connect Help View download file View MYD file Comms settings Noconmection ff 9 Select the serial port of your computer which will be used to communicate with the Flo Series3 device Local Comms Pot com when a local connection will be made i e with a serial cable directly connected to the device Max response wait time 10000 ms Direct connect timeout 1000 ms Mode Conexant D480 MDC 92 Modem If using a USB to Serial adapter A please refer to the product product documentation supplied with the adapter to ensure the correct driver is installed Close
24. E AGRIFLO SERIES3 PRODUCT MANUAL 19 9 0 Electronics module 20 The electronics module is the central processing unit of the AgriFlo Series 3 It includes the enclosure battery and circuit boards that control the device On the front of the AgriFlo Series 3 a backlit liquid crystal display LCD allows the user to see an on site readout of channel information and status messages Pressing either membrane switch will turn on the LCD The flashing flow indicator is a high intensity LED that emits a flash every second when flow is sensed in any of the configured channels Do not look directly at the flashing rate indicator as permanent eye damage may occur The membrane switches can be used to scroll the display between the various parameters being measured A serial communications port is located on the bottom face of the main enclosure Using the MACE serial data cable Part No 891 300 between this port and a PC users can configure troubleshoot and download the device ELECTRONICS MODULE FRONT LCD Display Flashing Flow Indicator Secure Latch with Padlock Hole Agriflo Series F Membrane Switch scrolls the display up amp down SECTION A HARDWARE MANUAL RETURN TO TOC ELECTRONICS MODULE INSIDE 12v Battery Bracket Wd Doppler Module slot 1 lt gt ware was Controller Module slot 0 nie PR f o iii Module Slots 2 5 n IE o s s
25. N TO TOC MACE AGRIFLO SERIES3 PRODUCT MANUAL 61 24 0 Start Stop device Once the FloSeries3 device has been configured and tested it is ready to be started so that measuring and logging is initiated WARNING If the device is NOT started flow measurements will A not occur From the main menu click Start device and you will i i be asked Are you sure Click Yes and the device PI sues will start and you will be returned to the main menu You will notice that the Start Device has changed to No Stop device in the main menu To enable changing of settings access of real time data and resetting totals the AgriFlo must first be stopped From the main menu click Stop device and you will be asked Are you sure Click Yes and the device will stop and you will be returned to the main menu You will notice that the Stop Device has changed to Start device in the main menu FlocomPlus YD Stop device Are you sure 25 0 Disconnect From the main menu click Disconnect and you will be asked Are you sure Click Yes and the device will be disconnected and you will be returned the start up menu Click on File gt Exit to shut down FloCom Disconnect s 2 Disconnect From unit Are you sure lt a WARNING If FloCom is not disconnected from the device excesscurrent will be drawn from the main battery 62 SECTION B SOFTWARE MAN
26. R gt lt LF gt a lt CR gt lt LF gt a lt values gt lt CRC gt lt CR gt lt LF gt a lt CRC gt lt CR gt lt LF gt MACE AGRIFLO SER ES3 PRODUCT MANUAL 55 21 0 Configuring FloSI Card continued SCHHSHSHOHHSHSHSHSHSHHEHSHHEHHHHHEHHOHHHHSHHHHSHOHHHHSHHHHHSHHHHHHHEHHHHHHHHSHHHHHHHSHHHHSHHHHHSHHHHHHEHHHHHEHHHHHHEHHOHHEHSEHHHSHHHSHHSHEHSHHOHEHOHHOSESCHOTESSOEOOEOOE The number and order of channel values in the output string for SDI 12 or RS232 ASCII output can be configured using Flocom FloSI settings Current mode DI 12 Change Address jo Available channels Output channels Move the required channels from the Available channels table to the Output channels table by highlighting the desired channel in the Available channels table and clicking the Right arrow If a channel in the Output channels table is no longer required highlighting it and clicking the Left arrow will remove from the Output channels table The position of a channel in the Output channels table can be changed by highlighting the channel and clicking the Up arrow or the Down arrow The user must ensure that there are no two devices with the same address on the same bus In such a case the behaviour of the bus is unpredictable 56 SECTION B SOFTWARE MANUAL RETURN TO TOC 22 0 About real time data MACE Flo Series instruments measure average stream velocity using Doppler ultrasoni
27. TO TOC MACE AGRIFLO SER ES3 PRODUCT MANUAL 65 66 SECTION B SOFTWARE MANUAL 28 0 View downloaded data file continued Header information At the top of each data file the following information is displayed e Version of Flocom used to download the file e Time and date the data were downloaded to the PC e Device type ie AgriFlo FloPro or HydroMace 3000 e Serial number of the electronics module e Version of firmware installed in the electronics module e Time and date of the clock in the electronics module e Battery status and charge voltage of the electronics module e The units of measure used for the accumulated total of each channel e The current total for each channel at the time of data download e Number of channels being recorded e The names of each channel being recorded e The units of measure used for each channel being recorded e Points refers to the number of data lines in the dowloaded file e Interval refers to the time in seconds between each time stamp logging interval Status messages Status messages are defined by the use of an asterisk immediately following a time stamp For example in the download on the previous page the following message appears which tells the user the date and time the unit was started 2008 02 06 12 52 07 Mote Unit started NOTE Refer to the table over page for a full listing of status messages Time stamped data At each time stamp the
28. To overcome this problem MACE Flo series instruments include the maximum measurement count feature whereby if the instrument detects a state change i e flow has started or flow has stopped it stays on and takes X number of readings to confirm this situation If all X number of readings meet the criteria for a valid reading as set by peak threshold flow threshold minimum stream activity and stream activity percentage then the reading is accepted and the change of state confirmed If the readings do not all agree that there has been a change of state then the reading is discarded and the current flow state remains That is the unit continues to calculate zero flow or accepts the flow rate as calculated Furthermore the Flo series instrument also checks that the direction of flow has not changed within the X readings For example if there is zero flow and the unit detects a reading of positive flow and another of negative flow then the overall reading is discarded and the unit continues to register a zero flow The number of readings used for the maximum measurement count is configurable by the user Velocity calculation method Pump method Under normal conditions water flow that is provided by a pump is turbulent and contains a vast number of acoustically reflective particles particularly miniature air bubbles that are a result of cavitation events In monitoring sites that are pumped or where low signal strengths are uncommon
29. UAL RETURN TO TOC 26 0 View totals From the main menu click View totals and the Flow volume totals dialogue box will appear This dialogue box lists all the accumulated flow channels and their respective totals and units Flow volume totals Refresh Close If the AgriFlo has not been started the Set Reset button will be active and the totalised reading can be changed It is strongly advised to download the logged data PRIOR to A resetting the total value 1 Highlight the channel you wish to reset by clicking on it s name ane 2 Click Set Reset and the Set total value dialogue box will appear Set Reset Refresh Close Flow volume totals 3 Enter the New value into the Set total value field and click Set value The new Channet Pump i value will then be displayed in the Flow volume totals dialogue box Current value 123 0 New value 555 Set value Cancel A Double check that this value is CORRECT 4 If the AgriFlo has not been stopped the Set Reset button will be greyed out and the total s will not be re settable 5 To update the reading whilst flow is accumulating click Refresh RETURN TO TOC MACE AGRIFLO SER ES3 PRODUCT MANUAL 63 27 0 Downloading stored data Viewing a file From the Start up screen click Connect gt Direct to display the main menu Time stamp tree view Select Download to initiate the s
30. Which measurement results to provide On receiving an SDI 12 Measurement command the FIoSI replies with notification that the measurement results are immediately available Upon receiving a Send Data command the FloSI returns the currently available result data which it has been configured to provide THE FOLLOWING SDI 12 COMMANDS ARE SUPPORTED Name Acknowledge active Send Identification Address Query Start Measurement Start Measurement and Request CRC Send data Additional Measurements Additional Measurements and Request CRC Start Verification Start Concurrent Measurement Start Concurrent Measurement and Request CRC Additional Concurrent Measurements Continuous Measurement 0 Continuous Measurements 1 to 9 Continuous Measurement 0 and Request CRC Continuous Measurements 1 to 9 and Request CRC RETURN TO TOC Command a al aM aMC aDO to aD9 aM1 to aM9 aMC1 to aMC9g aV aC aCC aCC1 to aCC9 aRO aR1 to aR9 aRCO aRC1 to aRC9 Response a lt CR gt lt LF gt a13MACE P FloSI3100 nnnnn lt CR gt lt LF gt a lt CR gt lt LF gt a000n lt CR gt lt LF gt a000n lt CR gt lt LF gt a lt values gt lt CR gt lt LF gt or a lt values gt lt CRC gt lt CR gt lt LF gt a0000 lt CR gt lt LF gt a0000 lt CR gt lt LF gt a0000 lt CR gt lt LF gt a000n lt CR gt lt LF gt a000n lt CR gt lt LF gt a0000 lt CR gt lt LF gt a lt values gt lt C
31. an I get access to the outside wall of the pipe for mounting the sensor Yes Consider using an insert velocity sensor if the pipe runs full No Must use a strap mount sensor internally RETURN TO TOC MACE AGRIFLO SER ES3 PRODUCT MANUAL 3 3 0 Site selection continued 5 Does the proposed site have obstructions in the pipe which might cause MINIMUM STRAIGHT PIPE REQUIREMENTS BUTTERFLY VALVE irregularities in the flow eg elbows constrictions valves gates etc ee ai Butterfly Valve D Pipe Diameter Yes You will need to install the sensor at a point where there is at least 8 _ hernia pipe diameters of straight pipe with no obstructions MACE recommends that the sensor is mounted so that there is a distance of at least six pipe _ FLOW diameters of straight pipe in front of it and at least two pipe diameters of n w l l l l l l l l l l l l l l j l straight pipe behind it 15x D Before Straight Length 2x D After No Even when there are no obvious obstructions MACE recommends observing the instructions described above oanien Pua Looking up stream 6x D Before MINIMUM STRAIGHT PIPE REQUIREMENTS Looking up stream preferred Velocity Sensor D Pipe Diameter MINIMUM STRAIGHT PIPE REQUIREMENTS UNDERSHOT GATE VALVE D Pipe Diameter Undershot Gate Valve Velocity Sensor Looking up stream 6x D Before 2x D After Looking down stream 2x D After Velocity Sensor
32. arriage return and contains the configured number of channel values The number and order of channel values in the output string can be configured using Flocom Each channel value in the string always begins with either a plus sign or minus sign there are no spaces between values 21 2 2 MODBUS Mode The MODBUS implementation complies with the MODBUS over Serial Line Specification V1 0 and the MODBUS Application Protocol Specification V1 1 The external port is either a standard RS232 port or a two wire RS485 port depending on the selected MODBUS mode The MODBUS parameters are configurable by selecting the entering the appropriate Address selecting the correct baud rate from the drop down list and checking the required radar buttons FloS settings x A Current mode Modbus Change Address 1 1 247 NOTE The user must Ve Socal ol p Hardware mode ensure th at th ere are RTI C ASCII R5485 C R5232 o P he E A no two devices with the Baudrate Parity Stop bits C None Gi same address on the EE same bus In such a case the behaviour of the bus is unpredictable Apply Exit RETURN TO TOC MACE AGRIFLO SER ES3 PRODUCT MANUAL 53 54 21 2 Serial Interface Settings continued SUPPORTED FUNCTION CODES Command Code hex Read Input Registers 04 Diagnostics 08 REGISTER MAP Parameter AgriFlo Output Channel 1 flow rate Channel 2 total Channel 3
33. asher through the hole in left arm of the mounting bracket Ensure that the head of the bolt is on the INSIDE and the thread faces outward 2 On the OUTSIDE of the bracket place an M8 spring washer then an M8 nut DO NOT TIGHTEN THE NUT 3 Repeat these two steps on the right hand side of the bracket 4 Holding the solar panel carefully hold it above the two arms of the mounting bracket 5 Slide the solar panel down so that the head of each of the M8 bolts fits in the channel on either side of the solar panel Ensure that the gutter of the solar panel is positioned between the flat washer and the head of the M8 Bolt 7 Place the u bolt provided in the solar panel mounting kit around the pole 16 SECTION A HARDWARE MANUAL RETURN TO TOC 8 Place the solar panel mounting bracket onto the u bolt Ensure that the arms of the bracket face out from the pole and that the mounting hole on each arm is towards the top of each arm 9 Slide the bracket to the desired position on the pole taking care to place it at the desired height and so that the open face of the bracket faces towards the sun 10 Place the 3 s flat and spring washers on to the U bolt and tighten the two nuts so that the bracket is secured on the pole 11 Tilt the solar panel so that the active side faces towards the sun North in Southern hemisphere South in Northern hemisphere at an angle specified in the data sheet provided your latitude 15
34. ay contain a sediment load 2 Fit a full bore 2 gate or ball valve to the male nipple using thread sealant to ensure that it makes a water tight seal 3 You are now ready to insert the sensor but first you must determine how far into the pipe the sensor face needs to be inserted The sensor face must be the only thing that intrudes into the flow Accurate measurements must be taken to get the values x y and z as shown in the diagram over the page 4 Measure value z Measure from the top of the sensor head to the top of the sensor shaft Write the number as your z value RETURN TO TOC MACE AGRIFLO SER ES3 PRODUCT MANUAL 9 10 5 0 Installing an insertion sensor continued HOW TO CALCULATE INSERTION MEASURMENT FOR TRANSDUCER l 5 Measure value x Take a measurement from the top of the ball valve to the inside of the pipe wall NOTE You need the end of the tape measure to be level with the inside diameter of the pipe wall 6 Calculate value y Value y is the difference between value x and value z 7 Apply thread sealant onto the thread of the sensor to ensure that it makes a water tight joint with the valve Screw the sensor assembly into the valve 8 Make sure that the 2 4 gland nut is only finger tight This will allow the sensor head to be moved freely while the head is aligned into the flow 9 Open the valve fully and push the sensor head into the flow so it fully enters the stream without exposi
35. c technology Anything moving in the stream which is acoustically reflective may produce an echo and therefore a Doppler shift Acoustically reflective particles include e suspended solids e bubbles eddies and waves e larger particles such as sand leaves and pebbles When selected in FloCom the user can display a real time graph of the velocity spectrum received by the velocity sensor The histogram you see in real time data is a composite spectrum of the velocities of the stream flow as well as various other factors explained below e The graph is two dimensional X Y e The X axis is the velocity range set by user e The Y axis vertical is the strength of the signal received by the processing electronics from each velocity sensed in the spectrum e Several thousand data points are plotted to give the composite graph MACE Flo Series instruments measure several thousand data points and compute an average velocity The flow is then calculated using the formula Q VxA where Q Quantity V Stream velocity and A Cross sectional area Users of MACE Flo Series instruments can use the real time graph to determine the correct positioning of the velocity sensor by assessing the shape of the curve and the signal strength The following graph is an example of a spectrum that was received from a full pipe irrigation flow Under field conditions several factors can affect the spectrum without affecting the performance or accurac
36. city is zero along the wall of the pipe and increases to a maximum at or about the centre of the pipe MACE Flo series instruments receive reflected frequencies from particles moving at these different velocities The greater the area of flow moving at a particular velocity the greater the number of reflections with the respective frequency shift The average velocity of the stream is therefore calculated by averaging those frequency reflections received across the whole stream profile Section A Hardware Manual CHAPTER 1 0 Introduction to AgriFlo Series 3 2 0 Warnings 3 0 Site selection 4 0 Sensor types 4 1 Insertion sensors 4 2 Strap mount sensors 5 0 Installing an insertion sensor 6 0 Installing a sensor on a plastic strap 7 0 Installing a sensor using the mounting plate 8 0 Installing AgriFlo power options 8 1 Solar panel installation on a 2 pole 8 2 Installing a MACE mains powered trickle charger 8 3 Powering the AgriFlo with an external battery 9 0 Electronics module 10 0 Installing the AgriFlo on a 2 pole 10 1 Sensor and power cables routed inside the pole 10 2 Sensor and power cables routed through conduit 11 0 Installing the AgriFlo on a wall 12 0 Installing additional cards 13 0 Installing a Series3 FloSI card 14 0 Maintenance 14 1 Battery maintenance 14 2 Solar panel maintenance 14 3 Sensor maintenance 14 4 Depth sensor reference filter maintenance PAGE CO CO CO w N 12 15 16
37. date time and recorded channel values are shown In the example below the date and time are followed by the flow rate value recorded for each of the three configured channels 20080207 00 15 00 2 34 13 33 16 84 End of file The end of the data file is always delineated by a Download End followed by the date and time RETURN TO TOC Status message table Status message Unit started Unit stopped Flow start Flow stop Flow total No external power External power restored Low Battery Battery normal Flat battery condition Battery was flat Sensor not detected Sensor error Device reset 0 TOD clock error RETURN TO TOC Description AgriFlo was started AgriFlo was stopped Time at which the flow threshold was exceeded for a configured channel and the accumulated total at the start of the flow event Time at which the measured flowrate did not exceed the flow threshold for a configured channel and the accumulated total at the end of the flow event Accumulated total for a configured channel Recorded at midday and or midnight user configurable No external power is detected If a solar panel is used this will occur at sunset External power is detected If a solar panel is used this will occur at sunrise Time at which battery voltage fell below 11 5V Time at which battery voltage exceeded 11 5V Battery voltage at download time is less than 10V Battery was less than 10V MACE Doppler sensor n
38. e unit is on and physically sampling the shorter the battery life without charging The Flo Series3 internal battery has a 7 2 Ah capacity During an integration period each Doppler sensor will draw approximately 120 mA Velocity maximum measurement count Under certain flow or no flow conditions signal noise may disrupt the calculation of a true average velocity reading As described the peak threshold feature is designed to overcome this problem However unwanted velocity readings may be derived from other sources such as aquatic life which may give strong signal strengths Within all Flo series instruments one of two flow states can occur The stream can either be moving or stationary For example a Flo series sensor submerged in a river diversion pipe that is used to pump irrigation water may be full at times when no water is being pumped Under these conditions it is common for fish and aquatic invertebrates to inhabit the pipeline Unfortunately to a Doppler ultrasonic velocity sensor a fish swimming at 500 mm s is computed as a full pipe of water moving at 500 mm s This type of erroneous flow reading will result in an increase in the totalised flow Conversely in a slow moving stream or one that contains few acoustically reflective particles a velocity reading may be missed if there is insufficient data to analyse Under this circumstance the totaliser will not be incremented 46 SECTION B SOFTWARE MANUAL RETURN TO TOC
39. elocity range will often result in far more repeatable data because the instrument does not waste processing power gathering data outside of expected ranges To be safe the velocity range should be set larger than expected and the site monitored for several weeks under different flow conditions to determine the peak expected velocity After this period the user may find it prudent to increase the resolution by changing the velocity range The velocity range must be set so that ALL components of the stream velocity are captured when viewed on the real time graph Failure to do so will compromise the validity of the velocity calculation See Chapter 22 for further details RETURN TO TOC Sensor type This parameter defines the type of sensor which is connected to the device Conduit type This parameter defines the type of structure that the sensor is mounted within For example this can be set to circular pipe non circular pipe or other conduit type Edit channel configuration dialogue box Sensor parameters tab Sensor type Conduit type Velocity range Velocity integration period Velocity calculation method Velocity peak threshold RETURN TO TOC iol Doppler flowrate channel Channel name Pump 1 Decimal places 2 7 Flow calculation Sensor parameters Sensor id 1 ensor z rientation Type E Insert head upstream 2 Insert head C downstream Strap mount onduil
40. f the pipe off set to either side if there is a build up of debris the sensor will not get covered 13 Press out the Z in the hoop with the palm of your hand The strap will snap into place You won t be able to move the mounting strap up or down the pipe by hand if done properly 14 Carefully route the cable from the sensor back to where the electronics box will be mounted as described in installation of insertion sensors Particular care should be taken when routing cables to ensure that A moisture CANNOT enter the connector or the air reference line of the sensor cable as permanent damage may occur 15 To remove open the strap by wedging a screwdriver into the flattened z and bearing down on the strap 14 SECTION A HARDWARE MANUAL RETURN TO TOC 7 0 Installing a sensor using the mounting plate The mounting plate consists of a plastic plate with four 6mm clearance holes 1 Attach the sensor head securely to the mounting plate by the six 3mm screws supplied M3 x 8 mm Phillips head countersunk 304 s s A Use only a hand screwdriver Do not over tighten these screws as permanent damage to the thread may result 2 Tie the cable to the mounting plate using the holes and cable ties provided Make sure that the knob of the cable tie sits to the back of the assembly out of the flow DO NOT OVERTIGHTEN CABLE TIES 3 The cable from the sensor to the instrument should then be run inside the pipe and secu
41. g clean streams it may also result in erroneous velocity readings unless enabled correctly When enabled this method will display two new menu items Minimum stream activity Under conditions of zero flow within a conduit see maximum measurement count a single aquatic life form can produce large Doppler shifts The minimum stream activity parameter must be set to negate the effects of these aquatic life forms This parameter should be set to low values 2 10 in sites where extremely slow average velocities are expected lt 0 2 m s Values greater than 10 can be set where average velocities of gt 0 2 m s are expected The user MUST check that the value does not cause real velocity data to be ignored Stream activity percentage To be used in conjunction with the minimum stream activity parameter this parameter forces the Flo series instrument to utilise only those velocity spectrums that have a minimum stream activity value greater than set by the user Under good acoustic conditions typically 90 100 of the data received by the velocity sensor will be used to calculate an average velocity Under conditions where the data received by the velocity sensor has been caused by aquatic life typically lt 10 of the data will be used Therefore this parameter should be set to low values 2 10 in sites where extremely slow average velocities are expected lt 0 2 m s Values greater than 10 can be set where average velocities of gt 0 2
42. ht for the solar panel to work efficiently Yes Mount solar panel as per instructions see 8 1 Solar panel installation on a 2 pole No A mains powered trickle charger should be used to charge the internal battery RETURN TO TOC Users are advised to ascertain the suitability of solar panels for A their application by checking relevant solar radiation maps for their region for example those found at http rredc nrel gov solar old_data nsrdb redbook atlas As a guideline for an AgriFlo with 3 Doppler sensors and measuring every 5 minutes at least 3 hours sunlight per day DEPTH SENSOR MOUNTING POSITION PARTIALLY FULL PIPE V X Water level Water level 50mm 2 inches 50mm 2 inches DEPTH SENSOR MOUNTING POSITION OPEN CHANNEL Water level Water level NOTE Sensor should be mounted on the side of the channel when sediment or weed is present NOTE Straight run requirements for open channels are the same as for closed pipes The diameter to use when calculating your straight run should be the maximum depth 10 How far can the sensor be mounted from the electronics module A maximum of 50 metres 150ft of cable is available on any MACE sensor 11 How do I customise the AgriFlo Series 3 for my application Use the application software FloCom t to e Configure the unit for your site For example this includes setting the pipe diameter and logging interval e View the velocity profile measured
43. ice must be configured and started before the meter will record flow Once finished remove the MACE serial cable and screw the serial port cover back in place to maintain enviromental protection 34 SECTION B SOFTWARE MANUAL RETURN TO TOC 17 2 What to do if the password is lost forgotten In the event that you have forgotten or lost your password the following steps should be taken 1 From the MACE FloCom Plus p ET Pe main screen click Help gt Show device authorisation code 2 Click Connect gt Direct and the Connect to device dialogue box will appear Authorisation code THSW D PGS SNHL UKUR 3 In the Connect to device dialogue box the device s unique authorisation code is seen at the bottom A You MUST note this code EXACTLY to fulfil the next steps 4 The unique device serial number located on an adhesive label inside the box should also be noted This will be used to verify the history of the device 5 Once you have noted the code and serial number you must contact your local MACE dealer distributor and inform them of these details They will obtain a counter code for your device A You will be required to prove that you have the authority to access the device prior to a counter code being issued For a billing device only an official of the water distribution authority will be given the counter code No exemptions from this requirement will be given 6 From the
44. iod RETURN TO TOC MACE AGRIFLO SER ES3 PRODUCT MANUAL 59 22 0 About real time data continued CHHSHSHHHSHEHSHSHSHHEHSHSHHHHHHHHHEHHSHOHHSHSHOHHHHSHHHSHHSHHHSHHHHEHHHHHHHHHHHEHHHHHSHHHHSHHHHHSHHHSHHEHEHHHHHEHHHHHHSSHHHHHEHHHEHHHOHSHHHEHHHOHEHOHHOSESHOTOOSEEEOLEOOE A general rule of thumb if a spectrum has low signal strength but gives a consistent velocity reading then the measurements should be accurate However if the spectrum has low signal strength and gives inconsistent velocity readings or none at all the site may be unsuitable for flow measurement with Doppler ultrasonic flow devices Very distorted signals such as that described in the diagram on the previous page may result from interference to the velocity sensor by the build up of debris or siltation In sites where there is an expectation of sedimentation the velocity sensor should be mounted in a raised position In a full pipe application it is recommended that the sensor be mounted or inserted on the side of the pipe to avoid sedimentation Similarly in partially full pipes the sensor may be offset from the invert of the pipe In these instances the depth reading will need to be offset accordingly Covering the sensors with algae and other materials that are saturated generally does not affect the accuracy of velocity readings This is because saturated materials exhibit the same speed of sound as water MACE Flo Series instruments include several signal proce
45. le and into the electronics module 3 Hold the electronics module up against the pole so that the oval cut away on the pole matches the cable entry point Route the sensor and power cables through the cable entry point as shown A k Vin A N y f 22 SECTION A HARDWARE MANUAL RETURN TO TOC 4 Use the two U bolts s nuts and s washers provided to secure the electronics module to the pole Do not overtighten the pole mounting bolts as permanent damage may occur to the electronics enclosure 5 Plug in both the sensor cable and solar panel cable into the sockets as shown in the picture below to act as a form of strain relief Ensure that the sensor cable is securely attached by squeezing the slidelock and latching it in place f The Doppler sensor cable should be looped prior to connecting Ensure that the cable from the solar panel charger is terminated A using the three pin connector provided in the electronics box and that the polarity is correct The polarity is labelled on the circuit board near the connector 6 If using a 16 30VDC mains charger then plug this into the socket shown in the picture below Alternatively the charger may be wired into the solar panel screw terminal block to the left of the socket 7 Once all the cables are connected the system should be fully tested Assuming everything is connected and fully functional the cable entry point should be filled with expanding space fi
46. ller foam This is to prevent insects and or moisture damaging the system RETURN TO TOC MACE AGRIFLO SER ES3 PRODUCT MANUAL 23 24 SECTION A HARDWARE MANUAL 10 2 Sensor and power cables routed through conduit 1 Place the electronics module on a work bench Using a power drill and 2 holesaw carefully drill out the round plastic cable entry point at the base of the unit as shown below It is only thin plastic and is designed to break away Alternatively the round cable entry point may be removed using the hammer and screwdriver method described in Chapter 10 1 2 Use the two U bolts s nuts and s washers provided to secure the electronics module to the pole Do not overtighten the pole mounting bolts as permanent damage may occur to the electronics enclosure 3 Carefully attach an electrical conduit adaptor Clipsal 50mm or Carlon 1 2 to the electronics module 4 Plug in both the sensor cable and solar panel cable into the sockets as shown in the picture below The Doppler sensor cable should be looped prior to connecting to act as a form of strain relief Ensure that the sensor cable is securely attached by squeezing the slidelock and latching it in place Ensure that the cable from the solar panel charger is terminated using the three pin connector provided in the electronics box and that the polarity is correct The polarity is labelled on the circuit board near the connector
47. lo settings dialogue box click New channel and the Configure new channel dialogue box will appear Sensor slot id Ifa Doppler module is installed in Configure new channel the device it s slot id number will be Channehgame Pumpi shown Select the corresponding slot id Sensor slot id 1 v from the drop down for each channel nem Sew that requires configuring Channel name Type in a name for the channel that will be configured This channel name MUST be unique and will be displayed both on the AgriFlo s LCD display and in the logged data file 2 Click Continue and the Edit channel configuration dialogue box will appear as shown over page RETURN TO TOC MACE AGRIFLO SER ES3 PRODUCT MANUAL 39 SECTION B SOFTWARE MANUAL 20 1 Flow calculation tab sheet Decimal places This parameter defines the number of decimal places to which the flow rate for the particular channel is recorded and displayed Flowrate threshold The flow rate threshold defines the trigger point at which flow rate data for the channel is event logged If the threshold is not reached the flow rate is not logged but IS used to update the totaliser channels Flow units The flow rate volume units can be selected by the user at this point and define how the data is calculated and logged See Chapter 18 4 System settings to switch between metric and U S units Velocity correction Unfortunately ideal h
48. m s are expected The user MUST check that the value does not cause real velocity data to be ignored 48 SECTION B SOFTWARE MANUAL RETURN TO TOC Velocity peak threshold Doppler shifts that are unrelated to the measurement of velocities in a stream are often called signal noise This noise can be a result of several different factors including e electromagnetic interference e reflections of signals from other echoes In some situations background noise may interfere with the calculation of correct average velocity readings Flo series instruments feature a noise filter called a peak threshold 100 50 Amplitude 0 0 1 0 2 0 3 0 4 0 Velocity m s In the figure above signal noise can be seen on the velocity spectrum graph as low signal strength echoes In the graph above you can see that the signal noise has an approximate amplitude value of 75 Therefore by setting a threshold of say 100 this noise will be ignored in the computation of average velocity The user should be careful however at sites where signal strength is inherently lower a peak threshold that is set too high could mean that true velocity readings are discarded This feature is particularly useful at sites where the sensor may be submerged for periods where no flow is occurring For example signal noise encountered in a submerged 1 m diameter pipeline that gives a false average velocity of 1 m s will still increase a totalisi
49. nected for an extended period of time the internal battery may be permanently damaged 2 7 Electromagnetic compatibility EMC This is a Class A product In a domestic environment this product may cause radio interference in which case the user may be required to take adequate measures RETURN TO TOC 3 0 Site selection When selecting a suitable site to measure flow and mount the instrument you must consider the following 1 Does the stream flow that wish to measure contain sufficient acoustically reflective particles such as sand silt dirt leaves or air bubbles The stream that you wish to measure must contain at least 100 parts per million of acoustically reflective particles that are greater than 75 microns in size Yes The stream flow is suitable for Doppler ultrasonic flow measurement No The stream flow is unsuitable for Doppler ultrasonic flow measurement 2 Does the pipe in which am measuring run full or partially full Full A velocity only sensor can be used Partial A combined depth velocity sensor will be required 3 If the pipe flows full is the internal pressure of the pipe within the range 0 25 m 0 253kPa 0 37 psi Yes The stream flow is suitable for Doppler ultrasonic flow measurement No The stream flow is suitable for Doppler ultrasonic flow measurement only if it contains at least 100 parts per million of suspended solids that are greater than 75 microns in size 4 C
50. ng any shaft To get the sensor in exactly the right position you need to make the distance between the top of the ball valve to the top of the sensor shaft the same as value y Refer to the photos over page RETURN TO TOC SECTION A HARDWARE MANUAL 10 Now that the insertion depth is correct rotate the sensor so that the grub screw at the top of the sensor shaft is accurately pointing in the direction of the longest straight section of pipe Remember you must have a distance of at least six pipe diameters of straight pipe in front of the sensor and two pipe diameters of distance behind the sensor NOTE The grub screw indicates the velocity sensing face 11 Tighten the 3 4 gland nut to lock the sensor in place A Do not use thread sealant on the 3 4 gland nut 12 When the installation is complete the sensor shaft should be pointing directly towards the centre of the pipe in all planes 13 Carefully route the cable from the sensor back to where the electronics box will be mounted Particular care should be taken when routing cables to ensure A that moisture CANNOT enter the connector of the sensor cable as permanent damage may occur electrical conduit or other similar mechanism MACE will not be liable for damage to cables especially that caused by vehicles digging implements animals or debris in the pipe or channel I MACE recommends that all cables be appropriately routed through MACE AGRIFLO SERIES3 PRODUCT M
51. ng counter by 785 litres per second even though no true flow existed By watching several real time graphs of no flow conditions and monitoring the extent of signal noise apparent a peak threshold may be set so that signal noise is not computed as real flow RETURN TO TOC MACE AGRIFLO SER ES3 PRODUCT MANUAL 49 50 SECTION B SOFTWARE MANUAL 20 2 Sensor parameters tab sheet continued Depth parameters Depth slope and offset If the user has a sensor with known slope and offset characteristics they may be entered directly into the unit configuration For example the MACE Ceramic Pressure Transducer is supplied with a factory calibration tag indicating the sensor s slope and offset values Alternatively the user should perform a 2 point calibration to determine the slope and offset characteristics of the sensor The factory calibration tag includes slope offset values for both metres m and inches in Be sure to enter the correct values for the selected depth units 2 point calibration To correctly calibrate a depth sensor it is important to calibrate it over its useful range For example if a sensor has a range of 0 2 metres but you only wish to use it to measure the range 0 1 metres to 1 2 metres you should recalibrate it across the reduced range The two point calibration function is selected by clicking 2 point calibration The Depth 2 point calibration dialogue box appears The measured raw value from
52. ntrol Equipment P L Copyright 1996 2009 MACE PYL All rights reserved This is an interactive PDF This user manual is setup as an interactive PDF The user can click on any of the Chapters in the Table of contents to navigate directly to the corresponding page To return to the Table of contents click on the Return to TOC button at the bottom of each page References to chapters in the body text are hyperlinks Part No 825 302 Rev 2 0 Code 090209 About Doppler ultrasonics MACE Flo series instruments utilise the Doppler Effect to measure velocity of stream flows The Doppler Effect after C J Doppler 1803 53 is defined as the apparent change in the frequency of sound or electromagnetic radiation due to relative motion between the source and the observer Uvarov amp Isaacs 1986 Dictionary of Science The MACE Flo Series instruments transmit an ultrasonic sound wave into the flow This sound wave is reflected by acoustically reflective particles e g air bubbles suspended solids and the instrument detects the reflected frequencies The difference between the transmitted frequency and the received frequencies is directly proportional to the velocity of the stream flow Flow direction Velocity gt yj O i Ta By In full or partially full pipes the velocity of the stream flow varies markedly across the cross section of the pipe Typically velo
53. o 145461 Thu 10 05 2007 known time intervals New time e The date and time can be set by manual entry f 22735P 10 05 2007 use daylight saving time or by synchronizing with the computer time 7 use computer time e The time is held in 24 hour time e Allowance can be made for daylight savings time Synchronize 18 2 Change download password The download password allows low level access to the device When this password is used for xj entry to the device channel totals may be Nin paaa viewed and data can be downloaded sex Cancel Many irrigation districts give this password to irrigators to allow them to use the data for water management operations RETURN TO TOC 18 3 Change super password The super password allows high level access to the device When this password is used for entry to the device all editing functions including data downloading are allowed Most irrigation districts set this password to prevent non authorized access to the device T Both the super and download passwords are case sensitive 18 4 System settings The system settings function allows the user to change the measurement units from metric to U S and vice versa 18 5 Clear stored data This function should only be used by high level users It clears all stored data from the device including all time stamped flow rate data 18 6 Module check This function provides the user with a simple method
54. of identifying the FloSeries3 modules which are currently installed in the device RETURN TO TOC Super password x New password Confirm p Cancel System Settings x Parameter unit metric C us x T All stored data will be lost T Are you sure Cancel Module check x Modules Slot Sensor type Doppler module Doppler module Doppler module MACE AGRIFLO SER ES3 PRODUCT MANUAL 37 19 0 Configuring the device 38 SECTION B SOFTWARE MANUAL 1 From the main menu click Settings and the AgriFlo settings dialogue box will appear Site I D Ej AsgriFlo settings The site i d is a text field used to steta Fam 123 identify the location of the device Measurement interval z min Logging interval s min When data is retrieved from the V Event loggifg 30 se device it will be identified by this do A Channels RALAS name rg Eg Edit channel For example the site I D might ian be the name of the farm or water T licence number 1O x I Flasher enabled Apply Exit Measurement and Logging Interval The measurement interval is the time at which the device wakes up to calculate the flow rate readings on each of the configured flow channels Each totaliser channel is also updated after each measurement interval Event logging This function is designed to save memory inside the device If a value that
55. ond To adjust the depth offset value Curent depth 0 033 m enter the actual depth value in the Corrected sia tail value field and click on Apply Clicking on Cancel terminates the procedure without altering the offset value Corrected value fo 038 Cancel Depth measurements should always be carried out from the BOTTOM of the channel pipe to the top of the water level RETURN TO TOC MACE AGRIFLO SER ES3 PRODUCT MANUAL 51 21 0 Configuring FloSI Card The Flo Series Serial Interface FloSI is an optional upgrade module for Flo Series3 devices The FloS provides unconditional polling access to the most recent user configured measurement results of Flo Series3 devices NOTE Only one FIoSI per Series3 device is supported RS 232 RS 485 and SDI 12 interfaces are available from Flo Series3 devices with the use of a FloSI The FloSI enables users to request the last measurement from Flo Series3 devices without the complexity of communicating via the host communications port The FloSI cannot be used to download or configure a Flo Series3 device and only one serial protocol may be used at one time The FloSI requires no routine maintenance and has no user serviceable components Configuration of the FloSI requires MACE Flocom Version 1 0 1 5 or later software and successful PC communications with a MACE Flo Series3 device Firmware Version 1 01 0 or later The FloSI configuration settings are
56. or example MACE recommends that the velocity sensor is positioned so that there are six pipe diameters of straight flow before the sensor and two pipe diameters of straight flow behind the sensor In practice this may not always be possible However these conditions may also be met by positioning the sensor to face downstream for 6 pipe diameters At poor signal sites turning the sensor around may help to increase signal strengths The Sensor Orientation feature allows the user to tell the processing electronics that although the velocities received are negative when the sensor is facing downstream you wish to totalise this flow as positive flow NOTE When receiving data from a sensor facing downstream the real time velocity graph will show a spectrum that appears upside down Velocity range This parameter sets the range of expected velocities that are to be analysed MACE Flo series instruments pigeon hole velocity readings into 128 positions over the velocity range set by the user For example each hole in a range of 0 4 m s is 03125 m s wide whereas in a 0 1 m s range each hole is 078 m s wide For example in a stream in which the user knows that the peak velocity will never exceed say 0 6 m s a velocity range of 1 m s may be set In this way the resolution of the final average velocity is increased Furthermore in slow moving streams or ones that contain few acoustically reflective particles a smaller v
57. ot detected MACE Doppler module not detected Power up reset occurred Error reading Time of day clock MACE AGRIFLO SERIES3 PRODUCT MANUAL 67 Mace USA LLC PO Box 7144 Overland Park KS 66207 United States of America Ph 888 440 4215 Fax 888 440 6999 Email sales maceusa com www maceusa com Measuring amp Control Equipment MACE P L PO Box 911 Pennant Hills NSW 1715 Australia Ph 02 9658 1234 Fax 02 9651 7989 Email sales macemeters com www macemeters com R mace Water Monitoring Solutions Part No 825 302 Rev2 0
58. other countries MACE Software End User License Agreement EULA Users should read and accept the terms of the MACE EULA before installing FloCom on their PC The EULA can be found on the downloads page of the MACE website www macemeters com RETURN TO TOC MACE AGRIFLO SER ES3 PRODUCT MANUAL 31 16 0 Installing the software 32 SECTION B SOFTWARE MANUAL Download FloCom from our website www macemeters com 1 Run the FlocomPlus_ version number exe file to start the installation process 2 Follow the instructions on the welcome screen then click Next to move to the next screen 3 Choose a location on your computer to install Flocom FloCom will setup a folder in your program files called Mace FlocomPlus This is the default option Click Next to continue 4 Backing up replaced ERTIY x files FloCom will ask if you wish to create backups of replaced files We advise you to click Yes and then click Next This installation program can create backup copies of all files replaced during the installation These files will be used when the software is uninstalled and a rollback is requested If backup copies are not created you will only be able to uninstall the software and not roll the system back to a previous state Do you want to create backups of the replaced files Yes C No Please select the directory where the replaced files will be copied Backup File Destination
59. ration is used in full pipes when access to the pipe is available and the pipe can be emptied when installation or maintenance is required Strap mount velocity depth type This type of sensor must be used in pipes that run partially full or in open channels There are several different types of straps used to hold the strap mount sensors in pipes e Plastic expandable mounting straps polypropylene e Mounting plate polypropylene A plastic expandable mounting strap can be used to secure the sensor in place These straps are made from polypropylene and come in five lengths to suit different pipe diameters e 225 300mm 12 max e 450 625mm 25 max e 700 810mm 32 max Single mounting plates are normally used in large pipes where a cost effective solution is required The sensor is attached to the plate which is then bolted to the inside surface of the pipe This plate is supplied in polypropylene e 300 450mm 18 max e 600 725mm 29 max 8 SECTION A HARDWARE MANUAL RETURN TO TOC 5 0 Installing an insertion sensor 1 Attach a male 2 BSP or NPT nipple to the pipe in a manner suitable for the pipe material This fitting must e Be at right angles to the flow e Provide for a clean join inside the pipe no burring etc e Be watertight WARNING DO NOT mount this fitting e In the centre at the top of the pipe may contain trapped air e In the centre on the bottom of the pipe m
60. rce of 16 30 Volts 2Amps 1 When the ambient temperature is less than 10 C 14F the battery 18 should be removed to avoid permanent damage to the battery The AgriFlo should be powered by an external power source 1 The charger available from MACE Part No 850 323 comes complete with a circular barrel connector that plugs directly into the electronics module See photos over page RETURN TO TOC SECTION A HARDWARE MANUAL The barrel connector for the 16 30VDC charger input is centre positive BI KPLANE 1 880 099 REU 2 0 J5 CHARGER 16 30UC 2 Alternatively if a DC source other than a MACE charger is used this is terminated using the same three pin connector as for the solar panel described above 8 3 Powering the AgriFlo with an external battery In certain applications it may be desireable to power the AgriFlo with an external battery 1 The Series 3 AgriFlo can be powered by an external 12V battery through the dedicated External Battery 12V terminal See photos below 1B GI 57 al 2 If a solar panel is connected to the AgriFlo as in Chapter 8 1 the internal charging circuit of the AgriFlo will also charge the external battery The charging circuitry of the AgriFlo has a 20 Watt capacity If the external battery is charged via its own solar panel and NOT A through the AgriFlo charging circuit the internal AgriFlo battery will discharge competely RETURN TO TOC MAC
61. rcuitry IMPORTANT Before removing card from packaging you MUST earth yourself by touching one of the screws on the display module as shown 3 Remove the MACE Series3 card from its packaging Position the new card in your hand such that the large cream 48 pin connector is facing down and aligned with the mating connector on the backplane PCB A 4 Earth yourself again Your finger must remain earthed on the screw whilst carefully inserting the card into any spare slot Take care to align the pins of the two connectors together There is a slot at the top of the card area that helps the alignment process Ensure that the card is contained within this slot and press down firmly to ensure that it is seated fully 5 Replace the PCB clamping bracket ensuring that the slots in the underside of the bracket are aligned with the tops of all the cards Fix the bracket into place with the 3 screws DO NOT over tighten the screws 6 Connect to the instrument with a PC and configure the card using Flocom as detailed in the software section of this manual 26 SECTION A HARDWARE MANUAL RETURN TO TOC 13 0 Installing a Series3 FloSI card The Flo Series Serial Interface FloSI is an optional upgrade module for Flo Series3 devices The FloSI provides unconditional polling access to the most recent user configured measurement results of Flo Series3 devices The FloSI requires no routine maintenance and has no user serviceable components
62. red to the pipe in such a manner as to prevent damage by debris in the pipe For example in most cases the cable should be routed through electrical conduit 4 Using a fixing method that is suitable for the pipe material the sensor plate should be attached to the pipe or channel in a position such that the sensor is always facing parallel with the pipe WARNING Take care to ensure no gap exists between the plate and the pipe wall This will stop the collection of debris 5 Carefully route the cable from the sensor back to where the electronics box will be mounted as described in installation of insertion sensors Particular care should be taken when routing cables to ensure moisture CANNOT enter the connector or the air reference line of the sensor cable as permanent damage may occur RETURN TO TOC MACE AGRIFLO SER ES3 PRODUCT MANUAL 15 8 0 Installing AgriFlo power options 8 1 Solar panel installation on a 2 pole The solar panel is used to charge the internal battery of the AgriFlo Series 3 where mains power is unavailable Users are advised to ascertain the suitability of solar panels for their A application by checking relevant solar radiation maps for their region for example those found at http rredc nrel gov solar old_data nsrdb redbook atlas As a guideline for an AgriFlo with 3 Doppler sensors and measuring every 5 minutes at least 3 hours sunlight is required per day 1 Place an M8 bolt with M8 flat w
63. remains flat for an extended time it may be damaged and should be replaced Contact your vendor for a replacement battery 14 1 1 Removing the damaged flat battery 1 Disconnect the battery cable assembly from the backplane board 2 Carefully hold the battery in position 3 Use a Phillips head screwdriver to remove the 3 screws which fasten the battery bracket to the main enclosure 4 Carefully remove the battery from the main enclosure 5 Disconnect the battery cable from the battery terminals 14 1 2 Installing the new battery 1 Connect the battery cable to the new battery with the red lead to the positive terminal of the battery and the black lead to the negative terminal 2 Place the battery in the main enclosure and hold it in place 3 Secure the new battery in place using the battery bracket and three screws 4 Tighten all three screws 5 Reconnect the battery cable assembly to the backplane board Damage to the AgriFlo Series 3 caused by incorrect battery replacement will void the warranty Using a battery that is not approved MAY damage the AgriFlo Series 3 and void the warranty gt gt 14 2 Solar panel maintenance The solar panel should be checked regularly for build up of solids such as dust and bird droppings These type of build ups can affect the performance of the solar panel and result in a decrease of the charge that is received by the internal battery The solar panel should be cleaned with a wet b
64. rush or rag Do not use steel bristle brushes that may cause damage to the glass of the solar panel 28 SECTION A HARDWARE MANUAL RETURN TO TOC 14 3 Sensor maintenance To ensure trouble free data collection sensors mounted in the flow should be kept free of built up debris silt or grease This is done by using a stiff bristle brush and carefully cleaning the sensor head and surrounding area This process should be repeated as often as necessary in order to keep the sensors clean Also check the sensor cable for physical damage Do not use steel bristle brushes that may cause damage to either A the velocity or depth sensors 14 4 Depth sensor reference filter maintenance The ceramic depth sensor used by the AgriFlo Series 3 measures the hydrostatic pressure of the stream depth This sensor is vented to atmospheric pressure via a vent tube inside the sensor cable which passes through a filter before entering the silica gel canister that is attached to the sensor connector and housed within the AgriFlo Series 3 In order to keep the depth sensor working properly this vent tube must always remain free from moisture The silica gel crystals contained within the reference filter effectively entrap atmospheric moisture However these crystals require changing regularly to ensure that they are still effective The silica gel crystals used in the AgriFlo Series 3 are an indicator type When fresh they are a deep blue in colour and when
65. s this can be reversed in FloCom software Ensure that minimum straight pipe requirements are still met 12 SECTION A HARDWARE MANUAL RETURN TO TOC 7 A stainless steel buckle is provided Slide the buckle onto the mounting strap as shown 8 The left side of the strap will simply run through the buckle The position of the buckle on the left side of the strap determines the diameter of the hoop Therefore the largest diameter occurs when you first place the buckle on the strap The right side of the strap curves around inside the left and tucks into the buckle Pick up the left side of the mounting strap and curve it over to form a semi circle 9 Bring the right side of the strap up inside the left and tuck into the mounting strap The strap should now form a complete hoop 10 Position the buckle so that the whole assembly is slightly too large to comfortably fit in the pipe 11 Now form a Z at the creases in the strap as shown below RETURN TO TOC MACE AGRIFLO SER ES3 PRODUCT MANUAL 13 6 0 Installing a sensor on a plastic strap continued CHHOSHSHHSHSHSHSHEHHESHEHSHHEHHEHEHHHHHHSHOHHHSHOHHSHHSHHHHHHHEHHHHHEHHHHHHOHHHHHSHHHHHSHOHHHHSHHHHHSHHOHHHHEHSHHHEHHHHHEHSHHOHHEHSEHHHHHHHOHHHEHHHOHEHOHHSESOHOLOSCEEOLEOLEEOE 12 Hold the Z with one hand the sensor with the other and place the assembly into the pipe reaching as far as is comfortable Ensure that the sensor is parallel to the flow and in the bottom part o
66. sensor may be moved slightly to try to overcome the distortion Furthermore the operator should inspect the positioning of the sensor to ensure that there is not a build up of debris or other matter close to the sensor head If no obstruction is observed and re positioning the sensor does not improve the data you can be assured that the sensor is operating effectively and that the displayed data is a site induced phenomenon Amplitude 2 0 Velocity m s Velocity 0 675 m s Measurement YW If data such as that seen above is received the operator should ensure that the sensor is positioned correctly and monitor the site for any obstructions close to the sensor If no obstructions are located close to the sensor the site may be unsuitable to flow measurement with Doppler ultrasonic flow devices The signal strength of received echoes on the real time histograms is a measure of the number of reflective particles moving in the stream Therefore low signal strengths do not necessarily equate to poor velocity readings Relatively few particles may provide enough echoes for an accurate average velocity reading Furthermore a histogram with a broad base will generally tend to have a peak with a lower signal strength In sites where it is Suspected that there are relatively few reflective particles in the flow the period in which the MACE Flo Series instrument takes readings may require extending see Velocity integration per
67. ssing features specifically designed to overcome anomalous data produced by such phenomena as aquatic life fish weeds small invertebrates surface waves produced by turbulence and wind and background noise It should always be remembered when examining real time graphical data that settings within the unit itself can have a marked effect on the data displayed The configuration of the instrument should always be checked thoroughly before viewing real time data 60 SECTION B SOFTWARE MANUAL RETURN TO TOC 23 0 Real time data From the main menu click Real time data and the following drop down menu options will appear as listed below FlocomPlus The force in flow Site id Device type AgriFlo M5 Battery status 12 2 W OK Serial No 19414 External power 0 3 Firmware version 1 00 7 Device time on connection 10 05 2007 11 37 09 4M Local connection 57600 Stopped 5 Doppler sensor check Click Doppler sensor check and the MACE Doppler real time data dialogue box will open Select the channel that you wish to xj observe Click Display and the Real Select channel time display will open JTY Display Open Channel 1 Click Start to begin measurements Click Stop then Exit to return to the main menu Exit Measure and display Click Measure and display then Start to observe the current flow rate values RETUR
68. tored data download procedure This pane enables the user to quickly navigate the data file by date and A save file dialogue box will appear The default file name is the unit ID The time Expand the tree on the date of interest by clicking the to reveal the default target directory is the directory into which the previous download file various time stamps Click the time stamp you wish to view and the data file was stored will automatically scroll to it Click OK once you are ready to download the device The download dialogue box will appear which shows the amount of stored data in the device and the date of the earliest available record If the download end time is left unchanged or set to a time earlier than the earliest record all stored records will be downloaded Otherwise only those data stored after the Header Program FlocomPlus 1 0 1 10 chosen Download from date will be downloaded 2008 02 06 Download Start 2008 02 06 11 09 41 12 52 02 IDevice AqriFlo 18 00 00 SerialNo 21263 2008 02 07 Ident 90 56 Header 00 00 00 lYersion 1 01 5 IDevice Time 2008 02 07 04 08 32 information IBattery OK 17 26 File I Mathew Help files 90 56_a prn Click Start download to complete the download procedure Download Stored data 141 8 K Earliest data 13 15 01 on 08 02 2008 Download fram 72 00 00 H on 8 02 2008 ITotal flow units acft acft acFt ICurrent total 6 9 1
69. y of the velocity sensor Armed with an understanding of these factors and some field experience the operator can vary the position of the sensor and the system settings to correct site induced errors in the velocity readings RETURN TO TOC MACE AGRIFLO SER ES3 PRODUCT MANUAL 57 22 0 About real time data continued SPOHHSHSHEHSHHSSEHEHEHSEHHSHEHEHSHHHHHEHHSHHEHHHSHHEHHHSHHOHHEHHOHHHHHHHHHEHHHHEHHHHHSHHHHHHHEHHHOHHEHSHHHHHSHEHHHHSHHEHEHHHHOEHEHHEHESHHOHESHHOHEHSSOHEOHEOHEOHEEEEOHEREOEE EjReal time display Pump 1 Module 1 x Velocity m s Velocity 0 826 m s Measurement A Factors affecting the velocity sensor This section is designed to give the operator a brief understanding of some of the factors affecting the performance of the MACE Flo Series velocity sensor In flowing streams there are always a range of different velocities present particularly in turbulent water where the effects of eddies and boundary layers can cause the velocity histogram to appear distorted in the diagram below Although distorted MACE Flo Series instruments have powerful signal processing algorithms which determine the average stream velocity from these signals EjReal time display Pump 1 Module 1 x a tot Ext Ss ee 2 0 Velocity m s Velocity 0 587 m s Measurement h 58 SECTION B SOFTWARE MANUAL RETURN TO TOC If the operator is receiving data such as displayed in the diagram above the
70. ydraulic conditions cannot be achieved at every site that requires monitoring In locations where hydraulic conditions are such that velocity calibrations at various flow regimes are required then the velocity factors function may help Under abnormal hydraulic conditions the average velocity of the stream must be calculated using traditional means that comply with Australian refer to AS3778 series or International Standards The velocity correction parameter can be set to scale the calculated velocity result and should only be used with extreme care In full pipe applications it allows a single multiplication factor to be applied to the calculated velocity readings In partially full pipes or channels up to 4 factors can be applied to the calculated velocity reading depending on the depth of the stream To edit the velocity click Change Edit on the Velocity correction panel as shown A Velocity Factors dialogue box will appear as shown to the left Siltation depth This parameter can be used to correct the calculated flow rate if a known amount of silt is inside the pipe The depth of silt will be subtracted from the area calculation in order to calculate the corrected flow rate RETURN TO TOC Edit channel configuration dialogue box Flow calculation tab ioixi Doppler flowrate channel Decimal places Channel name Open Channel 1 Decimal places 2 gt Sensor id 3 Flow calculation Sensor

Download Pdf Manuals

image

Related Search

Related Contents

Modular 4K MOD44 User Manual  EDC Client 5.13 User Manual    Samsung E958 用户手册  EN DE Original-Montage- und Betriebsanleitung Original assembly  Sony VPCSB11FX/B Replacement Instructions  Worldwide Lighting W83101C25-CL Installation Guide  Instructions de service  

Copyright © All rights reserved.
Failed to retrieve file