6K/10K Rack/Tower Online UPS User Manual
Contents
1. 5 Calibration 1 Batt Calibrate the battery voltage measurement Calibration range is from OV to 5 7V The default value is OV It is available on all operation modes gt Batt 2 30 40 4 Inv Adjust the inverter output voltage the adjustable range is Inv from OV to 6 4V the default value is OV It is only available inline battery converter mode Chg Adjust the Charger output voltage the adjustable value is from OV to 6 9V the default value is OV It is only available in bypass line ECO converter mode NOTE Before making charger output voltage adjustment be sure to disconnect all batteries first to get the accurate charger voltage Be careful that the adjustment should be suitable to battery specifications or the battery maybe destroyed 6 Other settings available on all operation modes Hihepe Hot standby Oe Enable Hot standby function is enabled It means that the current UPS is set to be host of hot standby system and it will automatically gt Hot Standby restart after AC recovery even without battery connected Disable Hot standby function is disabled The UPS is running at normal mode and can t restart without battery Disable is default setting Calibration Che Backup Time Hot Standby gt Status Disable Others Hot Standby gt Backup Time Backup Time gt Batt Groups Batt Cap Factor l QAH 1 0 Backup Time Parameters Setting Batt
2. edap POWERTRONIC User Manual 6K 10K Rack Tower Online UPS Uninterruptible Power Supply System Version gt 1 2 Please comply with all warnings and operating instructions in this manual strictly Save this manual properly and read carefully the following instructions before installing the unit Do not operate this unit before reading through all safety information and operating instructions carefully Table of Contents 1 Safety and EMC instructions svassuin eietetiniy teen ivatetinae uaentuctntin wehosnaeeieid 4 l 1 Transportation and Storage sixiscecasticastictintesacebeudastmceiianibenaasipeetant 4 ESA POD al E E E E A A E A E aaa 4 1 5 1MStallAUIO Ms minnin a a a 4 t4 Connection Warning S tesetswetstescauesandnsnoecbeneendeddeetehusmemenaiiwenaiab s N 25 Operaio sasona R 5 1 6 Standard Saser A 6 PARRE Eao a AE ET AE E AEE E E E 7 2 1 Unpacking and Inspection s esssnssnnnsnnnnnnnnnnnnnannnnnnnnnnnnnnnnnnnnnnanne 7 25A Real Paner VIO W ecann 7 2 3 Rack Tower Installation cccceccececeecvevseeeuevseeeuevaveeeeuaveneeuavanensenas 9 2A NJE UPS INSANO N anina 10 2 5 Parallel UPS Installation sisssissiscasaeiauinieadannavariauselaedvannrinauietindends 11 Die OD CVACIONS ranana tees aa ote tana taaaiensee a T 12 3 1 Operating Mode Status DESCTIPtiON cccececeeseeeeeeeeeeteeneeeeeeeeeaees 12 3 2 BUOM OPELA osaa S 12 5 52 LED INdICalOrS sperrir ear rar E E miter 13 BAU Gl DIG alar M
3. OHz Measurement Batt 273 0V 99 Load 100 Information Setting Alarm 1 After pressing the UP or DOWN button at the home page it will display five items in operation menu Control Measurement Information Setting Alarm 2 Press UP or DOWN button to select item 3 Press ON ENTER button to confirm the selection 4 Press OFF ESC button to return back to home page 3 7 2 2 Control Batt Test Mute Para Unlock NOTE 1 Para Unlock appears only when parallel communication failure happens NOTE 2 Turn On will be displayed if UPS is not turned on Turn Off will be displayed if UPS is turned on Generally speaking these two messages will not be displayed at the same time or in all operation modes 1 Turn On Turn Off This item is for turning on off the UPS a On Bypass mode it will display Turn On in control menu If it is selected and confirmed the UPS will transfer to AC mode or converter mode or ECO mode or battery mode according to the setting and input status ine Mode Turn On IP 208 OV 50 OHz Batt Test OP 208 0V 50 OHz ne Batt 273 0V 99 Para Unlock Load 100 NOTE You may simply turn on UPS by pressing ON ENTER button in home page It s not necessary to enter control menu to turn on the UPS b On AC mode or converter mode or ECO mode or battery mode it will display Turn Off in control menu If it is
4. 100 Backup Time 10M It s to allow UPS startup with parallel function It only appears when the LCD shows the warning of 3F Para Protect It means the parallel system is in protection and could not startup because of parallel communication failure Before restart the parallel system please confirm this selection first NOTE Before executing this action you must check if the system cables and connections areconnected correctly and safely Please read the related contents in the section of trouble shooting Control Turn On Batt Test Mute gt Para Unlock 3 7 2 3 Measurement Is single or parallel cable OK gt Yes No Bypass Mode Parallel Master IP 208 0V 50 OHz OP 208 OV 50 OHz Batt 273 0V 99 Load 0 Measurement displays the measurement value of the parameters such as voltage current frequency power capacity time etc Press UP or DOWN to explore the pages Output Volt 208 OV Curr 43 3A Freq 50 OHz Inv 208 OV Apparent Power 273 0V 100 00 00 00 Volt Charger Status 3 7 2 4 Information Information displays all parameter setting value and status Press UP or DOWN to explore the pages Bypass 6 ECO 2 6 Output Status Open Status Open Volt 208V Enable HighLoss V 232V Freq Auto HighLoss V 264V LowLoss V 184V CVCF Disable LowLoss V 110V HighLoss F 52Hz HighLoss E 54
5. UPS will cut off all power supply and there is no display shown on the panel 3 5 9 Changing battery quantity number The default battery 12V quantity of this UPS system is 20 for one series but 18 19 could also be applied in this system However before changing the battery quantity the UPS should be fully shutdown and the cabinet cover should be removed and the jumpers on the control board should be re set as below table Battery Number JP1 on control board one series pind amp pin2 pin3 amp pin4 Pind amp pin6 pin7 amp ping Xe Note 1 insert with jumper 0 no jumper x these pins are for other functions NOTE This operation should be done by professional technicians please contact the dealer for support 3 6 Parallel UPS Operation For parallel UPS operation please contact your dealer for more professional support 3 7 LCD Operation The entire LCD structure is demonstrated as diagram below Turn On Press button Enter Batt Test Control Press button Esc Mute Para Unlock Page 1 Input Page 2 Output Press button Enter Page 3 Battery Page 4 Bypass Page 5 Charger Page 1 Bypass Page 2 ECO Press either button UP or DOWN Press button Enter Main Interface Press button ESC Page 3 Output Information Pr
6. UPSs or there is an error in the parallel system 41 Over Temp The internal temperature is too Make sure the ambient high and reach the fault level temperature not over 40 C shutdown Make sure the fan is OK Maybe the environment is hot Make sure ventilation iswell Maybe the fan is blocked or Remove some loads if failed possible Maybe ventilation is blocked by the wall or other goods Load is too heavy between CPUs specification and the UPS shuts output and restart it down automatically Fault a Q C ct 5 Storage and Maintenance 5 1 Storage Before storing charge the UPS at least 7 hours Store the UPS covered and upright in a cool dry location During storage recharge the battery in accordance with the following table Storage Temperature Recharge Frequency Charging Duration 5 2 Maintenance A The UPS system operates with hazardous voltages Repairs may be carried out only by qualified maintenance personnel A Even after the unit is disconnected from the mains components inside the UPS system are still connected to the battery packs which are potentially dangerous Before carrying out any kind of service and or maintenance disconnect the batteries and verify that no current is present and no hazardous voltage exists in the terminals of high capability capacitor such as BUS capacitors A Only persons are adequately familiar with batteries and with the required precautionary measure
7. automatically soon Users could switch off some non critical loads to disable the shutdown alarm and 2 3 4 5 3 5 6 1 2 3 3 5 7 1 2 3 5 8 1 2 prolong the backup time If there is no more load to be taken off at that time you have to shut down all loads as soon as possible to protect the devices or save data Otherwise there is a risk of data loss or load failure In Battery mode if buzzer sounds annoying you could enter Control gt Mute on LCD to silence it Please refer to the section of LCD operation The backup time of the long run model depends on the external battery capacity The backup time may change under different environment temperature and load type The maximum backup time is limited by default 16 5 hours After discharging 16 5 hours UPS will shut down automatically to protect the battery The time could be modified through LCD panel or communication port Test the batteries If you need to check the battery status or performance when the UPS is running in Line Converter ECO mode you could enter Control gt Batt Test to instruct the UPS to do battery test Please refer to the section of LCD operation Users also can set battery test through monitoring software If the UPS is in battery testing Battery test mode will be displayed on LCD the buzzer indication will be the same as Battery mode but both line LED and battery LED will be lit Turn
8. laws and regulations A Warning e For standard battery pack there are one DC breaker to disconnect the battery pack and the UPS But for other external battery pack make sure a DC breaker or other protection device between UPS and external battery pack is installed If not please install it carefully Switch off the battery breaker before installation NOTE Set the battery pack breaker in OFF position and then install the battery pack e Pay highly attention to the rated battery voltage marked on the rear panel If you want to change the numbers of the battery pack please make sure you modify the setting simultaneously The connection with wrong battery voltage may cause permanent damage of the UPS Make sure the voltage of the battery pack is correct e Pay highly attention to the polarity marking on external battery connector and make sure the correct battery polarity is connected Wrong connection may cause permanent damage of the UPS e Make sure the protective earth ground wiring is correct The wire current spec color position connection and conductance reliability should be checked carefully e Make sure the utility input amp output wiring is correct The wire current spec color position connection and conductance reliability should be checked carefully Make sure the L N site is correct not reverse and short circuited 2 5 Parallel UPS Installation For parallel UPS installation please contact your dealer fo
9. of the nominal voltage LowLoss V 184V 3 LowLoss V Low voltage point in ECO mode The setting range is HighLoss F 52Hz from 5 to 10 of the nominal voltage LowLoss F 48Hz 4 HighLoss F Set low frequency point for ECO mode 50 Hz system Setting range is from 46Hz to 48Hz 60 Hz system Setting range is from 56Hz to 58Hz The default value is 48Hz 58Hz 5 LowLoss F Set high frequency point for ECO mode 50 Hz Setting range is from 52 0Hz to 54 0 Hz 60 Hz Setting range is from 62 0Hz to 64 0Hz The default value is 52 0Hz 62 0Hz 3 Output setting only available or effective on bypass mode Output gt Volt 208V Freq 50Hz CVCF Enable 1 Volt 208 Presenting the rated output voltage with 208Vac 220 Presenting the rated output voltage with 220Vac 230 Presenting the rated output voltage with 230Vac 240 Presenting the rated output voltage with 240Vac Freq 50Hz The output frequency is setting for 50Hz 60Hz The output frequency is setting for 60Hz ATO If selected output frequency will be decided according to the latest normal utility frequency If it is from 46Hz to 54Hz the output frequency will be 50 0Hz If it is from 56Hz to 64Hz the output frequency will be 60 0Hz ATO is default setting CVCF Enable or disable converter mode Enable The output frequency will be fixed at 50Hz or 60Hz according to setting of Freq The input frequency could be from 46Hz to 64Hz Disable The output fr
10. to fully disconnect the UPS system first press the OFF button and then disconnect the mains A Ensure that no liquid or other foreign objects can enter into the UPS system The UPS can be operated by any individuals with no previous experience 1 6 Standards Safety IEC EN 62040 1 EMI Category C3 Category C3 Warning This is a product for commercial and industrial application in the second environment installation restrictions or additional measures may be needed to prevent disturbances 2 Installation There are two types standard and long run models Please refer to the following model table Model Type 6KRT _ Standard model 6KRTL 10KRT_ Standard model LOKRTL 2 1 Unpacking and Inspection Unpack the package and check the package contents The shipping package contains e One UPS e One user manual e One monitoring software CD e One RS 232 cable option e One USB cable e One parallel cable and one share current cable option e One battery cable option e Two sets of tower stands including feet and extensions e Mounting ears NOTE Before installation please inspect the unit Be sure that nothing inside the package is damaged during transportation Do not turn on the unit and notify the carrier and dealer immediately if there is any damage or lacking of some parts Please keep the original package in a safe place for future use 2 2 Rear Panel View Diagram 2 6KRT L 10KRT L Inpu
11. transfer to Battery mode without interruption 3 5 2 Turn on the UPS without utility power supply to Battery mode 1 Make sure the battery is connected well and the battery pack breaker is at ON position 2 Press the ON ENTER button to start up the internal power the UPS will enter into bypass mode without output 3 When LCD is on home page press the ON ENTER button LCD will show a prompt page of Turn On Move the arrow to Yes by up or down button then press ON ENTER the UPS will be starting up with beeping once You could also enter the control menu to select the instruction Turn On to startup the UPS Please refer to the section of LCD operation 4 A few seconds later the UPS will enter into Battery mode Battery mode will be displayed on LCD In Battery mode it will shutdown automatically when battery is depleted If the utility power is restored it will auto restart to Line mode 3 5 3 Connect devices to UPS After the UPS is turned on you can connect devices load to the UPS 1 Turn on the UPS first and then switch on the devices one by one the LCD panel will display total load level 2 If inductive loads needed to be connected such as a printer the in rush current should be calculated carefully to see if capacity of the UPS can cover due to the huge starting power consumption of this kind of load 3 If the UPS is overload the buzzer will beep twice
12. Groups Set the number of battery group ranging from 1 to 6 The default value is 1 group Batt Cap Set the battery capacity such as 7AH 9AH 10AH 12AH 17AH 26AH 40AH 65AH 100AH and so on The default value is 9AH Factor Calibrate the displayed backup time by adjusting this multiplier factor The formulation is listed below Displayed backup time Original calculated backup time x Multiplier factor The value of default factor is 1 0 and it ranges from 0 5 to 2 These parameters are for the battery backup time calculation 3 7 2 6 Alarm page Alarm Info Fault 14 0utput Short Warning Ol Bat Open This page records and displays the faults or warning events happened in history 4 Trouble Shooting 4 1 Warning status When Fault LED flashes and the buzzer beeps once every second it means that there are some problems with UPS Users can see the warning code from LCD panel and refer to the trouble shooting table to check what problem probably happen 4 2 Fault mode 1 When Fault LED illuminates and the buzzer beeps continuously it means that there is a fatal error about UPS Users can get the fault code from LCD panel Please refer to the trouble shooting table to check what problems probably happen 2 Don t try to turn on the UPS again before the problem is clear If the problems can t be fixed please contact the distributor or service people immediately 3 For emergency case please cut off the connectio
13. Hz LowLoss F 48Hz LowLoss F 46Hz Battery 4 6 UPS Info 5 Others 6 6 Backup Time UPS Model 1OKL Hot Standby 990 Miniute DSP Ver 99 00 Disable Batt Test Type MCU Ver 97 00 Bypass Mute Short Time Unit Name Disable 10 Second XXXXXXXXX Batt Mute Manufacturer Disable XXXXXXXXX Fault Mute Disable 3 7 2 5 Setting This menu is used to configure the parameter settings or do the calibrations Setting gt Bypass ECO Output Battery Calibration Others NOTE Some settings will be only available in some operation modes If the setting is not available in current mode the LCD will show prompt message with Item can not be set in this mode Press any button or just wait for several seconds until this message fades 1 Bypass setting 1 Status only available in bypass AC mode 1 1 Open Forbid Open Bypass allowed When selected UPS will run at Bypass Bypass mode depending on bypass enabled disabled setting Forbid Bypass not allowed When selected it s not allowed for running in Bypass mode under any situations gt status Open 1 2 Enable Disable Enable This option appears only when Bypass status is set to Open HighLoss V 264V Enable Bypass enabled When selected Bypass mode is Lon ase Ve Vy activated ii labels Disable Bypass disabled When selected automatic bypass is HighLoss F 54Hz acceptable but manual bypass is not available Manual bypass Lo
14. d Please refer to chart 1 Step 2 Lift the UPS module and slide it into rack enclosure Attach the UPS module to the rack with screws nuts and washers user provided through its mounting ears and into the rack rails Please refer to chart 2 2 4 Single UPS Installation Installation and wiring must be performed in accordance with the local electric laws regulations and execute the following instructions by professional personnel 1 Make sure the mains wire and breakers in the building are enough for the rated capacity of UPS to avoid the hazards of electric shock or fire NOTE Do not use the wall receptacle as the input power source for the UPS as its rated current is less than the UPS s maximum input current Otherwise the receptacle may be burned and destroyed 2 Switch off the mains switch in the building before installation 3 Turn off all the connected devices before connecting to the UPS 4 Prepare wires based on the following table Model Wiring spec AWG Output Battery 6KRT L 10 10 10 10 10 loKRT L 8 8 8 amp 8 NOTE 1 The cable for 6KRT L should be able to withstand over 40A current It is recommended to use 10AWG or thicker wire for safety and efficiency NOTE 2 The cable for 1OKRT L should be able to withstand over 63A current It is recommended to use 8AWG or thicker wire for safety and efficiency NOTE 3 The selections for color of wires should be followed by the local electrical
15. equency will synchronize with the input frequency within 46 54 Hz for 50Hz system or within 56 64 Hz for 60Hz system NOTE CVCF means Constant Voltage and Constant Frequency it represents converter mode 4 Battery setting available on all operation modes Battery gt DisChge Protect Fnable 990 Minute Batt Test Type Short Time Till Batt Low Battery gt DisChg Protect Fnable 990 Minute Batt Test Type Short Time 10 Minute 1 Dischg Protect 1 1 Enable Battery discharge protection function is enabled When UPS have been continuously working in battery battery test mode the UPS will automatically shut down when the running time set by option 1 2 below is up Disable Battery discharge protection function is disabled 1 2 0000 1500 The maximum discharge time ranging from 0 to 1500mins UPS will shut down to protect battery after backup time arrives when the Dischg Protect is enabled If Dischg protect is disabled then this setting does not make sense whatever the setting is The default value for this setting is 990mins 2 Batt Test Type 2 1 Short Time Battery test will last for 10 seconds 2 2 Long Time Battery test could last for longer time which is able to be adjusted within 01 99 minutes 2 3 Till Batt Low Battery test will not stop until battery voltage is low Battery gt DisChg Protect Fnable 990 Minute Batt Test Type Short Time 10 Second
16. ess button Esc Page 4 Battery Page 5 UPS Info Page 6 Others Bypass ECO Press button Enter Output p Press button Esc Setting Battery Calibration Others Press button Enter Alarm _ IX Fault Info Press button Esc Warning Info 3 7 1 Main interface home page Bypass Mode Bypass Mode IP 208 OP 208 Batt 273 0V 99 Batt 273 0V 99 V 50 OHz IP 208 0V 50 OHz V 50 OHz OP 208 0V 50 OHz Load 0 Load 0 Warning 01 1 In the first line it will display the UPS running status mode 2 When alarms happen the warning or fault information will display below the load line 3 When the front panel is not operated for 10 minutes the display page will return back to home page 4 Press the UP or DOWN button to enter the operation menu see 3 7 2 1 5 When it displays home page in LCD if UPS is in bypass you could press the ON ENTER button to turn on the UPS to AC converter ECO battery mode according to the setting and input status in reverse you could press the OFF ESC button to allow UPS to bypass mode or shut down Refer to section of Single UPS Operation 3 7 2 Operation menu 3 7 2 1 Main menu Line Mode gt Control IP 208 0V 50 OHz OP 208 0V 50
17. every second 4 When the UPS is overload please remove some loads immediately It is recommended to have the total loads connected to the UPS less than 80 of its nominal power capacity for system safety 5 If the overload time is over duration listed in spec at Line mode the UPS will automatically transfer to Bypass mode After the overload is removed it will return to Line mode If the overload time is over duration listed in spec at Battery mode the UPS will become fault status At this time if bypass is enabled the UPS will power to the load via bypass If bypass function is disabled or the input power is not within bypass acceptable range it will cut off output directly 3 5 4 Charge the batteries 1 After the UPS is connected to the utility power the charger will charge the batteries automatically except in Battery mode or during battery test 2 Suggest to charge batteries at least 10 hours before use Otherwise the backup time may be shorter than expected 3 Make sure the battery numbers setting on the control board Please refer to the section of changing battery quantity is consistent with actual connection 3 5 5 Battery mode operation 1 When the UPS is in Battery mode the buzzer will beep according to different battery capacity Normally the buzzer will beep once every 4 seconds in battery mode but when the battery voltage drops to the alarm level the buzzer will beep once per second and the UPS will shut down
18. le and the connections If the parallel cable is not connected inthe parallel mode the UPS may be damaged Fault 01 Bus Start Fail The internal converter failed sothe Contact the dealer to repair DC bus voltage could not be boosted correctly Fault 02 Bus Over 1 DC bus voltage is too high 1 Shut down and restart the because of mains input or load system to see if it happens transient current again 2 The internal converter failed 2 Contact the dealer to repair Fault 03 Bus Under The internal converter failed sothe Contact the dealer to repair DC bus voltage is too low 04 Bus Unbalance 1 The load is special or abnormal Contact the dealer so the internal positive and negative DC bus voltages are unbalanced 2 The internal converter failed inverter voltage could not start up correctly inverter voltage is too high inverter voltage is too low output Fault 1A NegPower UPS output power is negative It Contact the dealer means there is energy feedback into the internal of UPS from output It may be caused by regenerative load or current control failure in the parallel system and short Fault 24 Inv Rly Short The internal inverter relay is stick to Contact the dealer to repair a Transfer Switch is short not connected well in the parallel system Fault 36 OP I Unbalance The output current is extremely Contact the dealer to repair unbalanced between the paralleled
19. ll the UPS system where it would be exposed to direct sunlight or nearby heater A Do not block ventilation holes in the UPS housing 1 3 Installation A Do not connect appliances or devices which would overload the UPS e g big motor type equipment Place cables in such a way that no one can step on or trip over them Do not block air vents in the housing of UPS The UPS must be installed in a location with good ventilation Ensure enough space on each side for ventilation A UPS has provided earthed terminal in the final installed system configuration equipotential earth bonding to the external UPS battery cabinets The UPS can be installed only by qualified maintenance personnel An appropriate disconnect device as short circuit backup protection should be provided inthe building wiring installation AA An integral single emergency switching device which prevents further supply to the load by the UPS in any mode of operation should be provided in the building wiring installation Connect the earth before connecting to the building wiring terminal A Installation and Wiring must be performed in accordance with the local electrical laws and regulations 1 4 AN connection Warnings e There is no standard backfeed protection inside please isolate the UPS before working according to this circuit The isolation device must be able to carry the UPS input current External Distribution Panel Coil Remote Switch Magneto Thermal In
20. n from utility external battery and output immediately to avoid more risk or danger 4 3 Trouble shooting table If the UPS system does not operate correctly please solve the problem by referring to the table below Alarm type LCD display Possible cause Possible cause Remedy Warning 01 Batt Open The battery is not connected Connect the battery well well Replace or restore the The battery protection device is protection device open Warning 07 Over Charge Battery numbers and setting Correct the battery number are not matching or its setting Charger voltage is too high or Disconnect the battery and charger failure check the charger output voltage Then contact the dealer to repair Warning 08 Batt Low Battery is discharged deeply to 1 Recharge the battery low level Correct the battery number Battery number is not correct Replace the battery Battery is in the end of life 09 Over load The load is too heavy Remove excess loads from UPS output Warning OA Fan Error 1 Fan is blocked 1 Make sure fan is 2 Fan is in the end of life blocked 3 Fan detection circuit failed 2 Contact the dealer to replace the fan 3 Contact the dealer to repair Warning OB EPO Enable EPO plug jumper is removed or Connect the EPO plug jumper the external EPO switch is off well or switch on the external EPO switch Make sure ambient temperature not over 40 C Make sure the fan is OK Make sure ventilation i
21. nabled through LCD or monitoring software the UPS will start Battery Test This operation is used to check the battery status Warning Status If some errors occur in the UPS but it is still running normally buzzer will alarm and warning code will appear in the LCD for trouble shooting Fault Mode When fatal error occurs in the UPS it will beep continuously and go to fault mode It will display fault codes in LCD 3 2 Button Operation OF E p Ky gt S Fai amp co D S O YO LED indicators 37 Buttons LD i v La Sy There are 4 buttons on front panel gt Press this button to turn on the UPS ON ENTER gt Or press it to confirm the selection in the menu gt Press this button to turn off the UPS OFF ESC gt Or press it to return to last menu oe gt Press this button to select the previous item in the menu UP gt Or press this button to jump to previous page in the screen gt Or press this button to increase the number in the setting pow gt Press this button to select the next item in the menu DOWN gt Or press this button to jump to next page in the screen gt Or press this button to decrease the number in the setting gt To allow LCD display to rotate 90 automatically press these two buttons at the same time This operation is used to configure the UPS in rack or tower display 3 3 LED Indicators There are 4 LEDs on front panel to show the UPS worki
22. ng status Medes Bypass Line Batey AC mode Converter mode er Battery test mode o oe ECO mode oOo e Note means LED is lit O means LED is faded means LED is flashing 3 4 Audible alarm UPS status Ci Buzzerstatus Muted Beeping continuously Warnings except overload Beeping once every second No 3 5 Single UPS Operation 3 5 1 Turn on the UPS with utility power supply to Line mode 1 Make sure mains input and battery are connected well and the battery pack breaker is at ON position Set the external mains input breaker to ON position then the fan will be running and the UPS supplies power to the loads via bypass The UPS is operating in Bypass mode NOTE When UPS is in Bypass mode the output voltage comes directly from utility so the load is not protected by UPS To protect the precious load the UPS should be turned on to Line mode 2 When LCD is on home page press the ON ENTER button LCD will show a prompt page of Turn On Move the arrow to Yes by up or down button then press ON ENTER the UPS will be starting up with beeping once You could also enter the control menu to select the instruction Turn On to startup the UPS Please refer to the section of LCD operation 3 A few seconds later the UPS will enter into Line mode Line mode will be displayed on LCD In line mode if the utility power is abnormal the UPS will
23. off the UPS with utility power supply in Line mode When LCD is on home page press the OFF ESC button LCD will show a prompt page of Turn Off Move the arrow to Yes by up or down button then press ON ENTER the UPS will be turning off to bypass mode with beeping once You could also enter the control menu to select the instruction Turn Off to turn off the UPS Please refer to the section of LCD operation NOTE Here Turn Off means that UPS is not working on line converter ECO battery battery test mode So even though the UPS is turned off if input or bypass voltage is normal the internal power supply will be still working and if bypass status has been set to enable the output voltage of the UPS will be still exist If you need to fully cut off the output please switch off the external input breaker A few seconds later there is no display shown on the panel and UPS is completely off Turn off the UPS without utility power supply in Battery mode When LCD is on home page press the OFF ESC button LCD will show a prompt page of Turn Off Move the arrow to Yes by up or down button then press ON ENTER the UPS will be turning off to bypass mode with beeping once You could also enter the control menu to select the instruction Turn Off to turn off the UPS Please refer to the section of LCD operation If there is no bypass input voltage the
24. out Main Switch AC Contactor as backfeed protection device Neutral L2 L1 Line Input e This UPS should be connected with TN earthing system e The power supply for this unit must be single phase rated in accordance with the equipment nameplate It also must be suitably grounded e Use of this equipment in life support applications where failure of this equipment can reasonably be expected to cause the failure of the life support equipment or to significantly affect its safety or effectiveness is not recommended Do not use this equipment in the presence of a flammable anesthetic mixture with air oxygen or nitrous oxide e Connect your UPS power module s grounding terminal to a grounding electrode conductor e The UPS is connected to a DC energy source battery The output terminals may be live when the UPS is not connected to an AC supply Before working on this circuit Isolate Uninterruptible Power System UPS Then check for Hazardous Voltage between all terminals including the protective earth AN Risk of Voltage Backfeed 1 5 Operation AA Do not disconnect the earth conductor cable on the UPS or the building wiring terminals in any time since this would cancel the protective earth of the UPS system and of all connected loads If the external battery cabinet is connected the UPS output Anderson connector may be electrically live even if the UPS system is not connected to the building wiring outlet AN In order
25. r more professional support 3 Operations 3 1 Operating Mode Status Description UPS Power On When UPS is powered on it will enter into this mode for a few seconds for initializing the CPU and system AC Mode When the input voltage is within acceptable range and the UPS is turned on the inverter is running the UPS will provide pure and stable sine wave AC voltage The UPS will also charge the battery in AC mode ECO Mode When the input voltage is within voltage regulation range and ECO mode is enabled the UPS will bypass voltage to output for energy saving If the input voltage is out of the regulation range but it is still within acceptable range of AC mode the UPS will transfer to inverter supplying the power to load similar as AC mode When input frequency is within 46 to 64Hz the UPS can be set with a constant output frequency 50 Hz or 60 Hz through the inverter The UPS will still charge battery at this mode There is no bypass at this mode Battery Mode When the input voltage is out of the acceptable range or power failure and the UPS is turned on the inverter is running the UPS will backup power from battery Bypass Mode When input voltage is within acceptable range and bypass is enabled and the UPS inverter is not turned on or the inverter can t support the load the UPS will supply power to the load through b Battery Test Mode When the UPS is in AC mode or Converter mode and the battery test command is e
26. s may replace batteries and supervise operations Unauthorized persons must be kept well away from the batteries AN Verify that no voltage between the battery terminals and the ground is present before maintenance or repair In this product the battery circuit is not isolated from the input voltage Hazardous voltages may occur between the battery terminals and the ground A Batteries may cause electric shock and have a high short circuit current Please remove all wristwatches rings and other metal personal objects before maintenance or repair and only use tools with insulated grips and handles for maintaining or repairing When replace the batteries install the same number and same type of batteries Do not attempt to dispose of batteries by burning them This could cause battery explosion The batteries must be rightly deposed according to local regulation A Do not open or destroy batteries Escaping electrolyte can cause injury to the skin and eyes Itmay be toxic A Please replace the fuse only with the same type and amperage in order to avoid fire hazards A Do not disassemble the UPS system 6 Specifications INPUT 110 VAC 3 at 50 Load Itage 176 VAC 3 at 100 Load i Low Line Loss Voltage 10V 300 VAC 3 High Line Loss Voltage 10V 46Hz 54 Hz 50Hz system 56Hz 64 Hz 60Hz system Single phase with ground 0 99 at 100 Load Frequency Range hase ower Factor OUTPUT Outp
27. s well Remove some loads if possible OE Charger Fail Charger failed Contact the dealer for repair board is burnt fuse Warning 33 Overload 3Times Locked in bypass after overload 3 Remove excess loads from UPS the UPS and restart it 3A Maintain Open EMBS port is open or the maintain If the EMBS port is short switch sensor connected to EMBS circuited the warning will port is trigged The UPS is disappear transferred to bypass Parallel cable is still not connected Warning OD Over Temp The internal temperature is too high and reach the warning level 1 Maybe the environment is hot 2 Maybe the fan is blocked or failed 3 Maybe ventilation is blocked by the wall or other goods 4 Load is too heavy 3F Para Protect 1 If the system is still needed well when restart after the parallel system is fault because of parallel communication failure When this warning appeared the UPS could not start up because it is system to be operated in parallel mode please connect the parallel cable well And choose Para Unlock in control menu to remove the protection for parallel system warning Then the UPS could start up If the UPSs in the system are separated to single UPS please disconnect the output to other UPSs and choose Para Unlock in control menu to remove _ the warning Then the UPS could start up NOTE Be careful to check the UPS operation mode parallel or sing
28. selected and confirmed the UPS will transfer to bypass mode or shut down Bypass Mode Turn Off IP 208 0V 50 OHz Batt Test OP 208 0V 50 OHz mute Batt 273 0V 99 Para Unlock Load 0 NOTE You may simply turn off UPS by pressing OFF ESC button in home page It s not necessary to enter control menu to turn off the UPS 2 Battery Test It is to check if the UPS could work well in battery mode and test the battery performance This selection will be displayed under all UPS modes However it couldn t execute this test in Battery Fault Eco mode and reminder will pop up in the screen When battery test is selected the screen will return back to home page with Battery Test Mode displayed on top If the test is completed the displayed status will change back to UPS current mode Turn On IP 208 0V 50 OHz gt Batt Test OP 208 0V 50 OHz Mute gt Yes Batt 245 0V 50 Para Unlock No Load 0 Backup Time 10H 3 Mute It is to mute the buzzer only when UPS is in battery bypass fault mode After the selection is confirmed it will return back to home page and mute icon will be displayed Although this selection will display in other modes it can t be mute alarm and reminder will pop up at the same time Control Turn On Batt Test gt Mute Para Unlock 4 Para Unlock Mute gt Yes No Battery Mode x IP 0 0V 0 OHz OP 208 0V 50 OHz Batt 245 0V 50 Load
29. sireenin nn a a 13 JS SNJICUPS OPSl AUlON srn 13 3 6 Parallel UPS Operation ccccsssssenssessenusessensossnenseesuensaeauensaeauensaras 16 S77 ER DO De MALO lvaasesssacaatrae eacieubtaceateisiorngieseeeiia anatase tans eran 17 As MOUDE SOONG cxisssiivetassiw evn tcahonmawnieais a a 27 PEP A es NVI SUI Siar is ate ats Severs as Seater tts Reece as ee eats Seeman haat Ramana ean 2 42 Fault MOGC sneonen a 27 4 3 Trouble shooting table cccscssececcecurseececcecursecceccucutsesseeaesursessaes 27 5 Storage and MAiINteMance cccsscecsecccsecceeececeececeececuecneuecneuesneursnearens 30 Dees SUONACessaaustansasueaseaasehiegs sousimee E E E E 30 532 MantenNa NCE unread a A Or A 30 o PECE AON S a nantes tertun nace aaa eatin eradineee maces etauens 31 1 Safety and EMC instructions Please read carefully the following user manual and the safety instructions before installing the unit or using the unit 1 1 Transportation and Storage A Please transport the UPS system only in the original package to protect against shock and impact The UPS must be stored in the room where it is ventilated and dry 1 2 Preparation A Condensation may occur if the UPS system is moved directly from cold to warm environment The UPS system must be absolutely dry before being installed Please allow at least two hours for the UPS system to acclimate the environment Do not install the UPS system near water or in moist environments Do not insta
30. t Output Terminal Diagram 3 Battery Pack Rear Panel RS 232 communication port USB communication port EPO Emergency Power Off connector Share current port for parallel function Parallel port for parallel function Intelligent slot EMBS External Maintain Bypass Switch port Cooling fan External battery connector Input circuit breaker Input Output terminal Input terminal Ground Output terminal Battery pack output circuit breaker 2 3 Rack Tower Installation 2 3 1 Tower Installation The UPS system is shipped with two sets of feet and 6 extensions 2 short extensions plus 4 long extensions that can be used to tower install the UPS module in 3U or UPS module with one battery bank in 6U Install UPS module in 3U Assemble two feet and one short extension as Short extension one tower stand shown in step 1 Align the two stands approximately 35cm apart in step 2 Then put UPS module in the stands as shown in step 3 Install UPS module and one battery bank in 6U Assemble two feet and two long extensions as one tower stand shown in step 1 Align the two stands approximately 35cm apart in step 2 Then put UPS module and battery bank in the stands as shown in step 3 2 3 2 Rack Installation Please follow below steps to mount UPS into 19 rack or rack enclosure Step 1 Attach mounting ears to the side mounting Chart 1 holes of UPS using the screws provided and the ears should face forwar
31. ut voltage 200V 208 220 230 240VAC 1 46Hz 54 Hz 50Hz system 56Hz 64 Hz 60Hz system 50 Hz 0 1 Hz or 60Hz 0 1 Hz 100 110 10min Line mode 110 130 imin gt 130 1sec 100 110 30sec Battery mode 110 130 10sec gt 130 1sec 3 1 max lt 2 100 Linear Load lt 4 100 Non linear Load AC Voltage Regulation Frequency Range Synchronized Range requency Range Battery Mode Overload i urrent Crest Ratio Harmonic Distortion marn oms ls 0 ms Inverter ECO lt 10 ms EFFICIENCY Dimension DXWXH mm UPS unit 580X438 X133 UPS unit 668X438 X133 Battery pack 580X438 X133 Battery pack 580X438 X133 UPS unit 20 UPS unit 23 5 Net WegAL Kgs Battery pack 57 Battery pack 63 ENVIRONMENT MANAGEMENT If the UPS is in converter mode the power capacity will be derated to 60 of full capacity Tf the battery number is 18 the power capacity will be derated to 90 if it is 19 the power capacity will be derated to 95 TF the UPS is installed or used in a place where the altitude is above than 1000m the output power must be derated one percent per 100m WProduct specifications are subject to change without further notice
32. wLoss F 46Hz means users manually operate UPS to Bypass mode for example in AC mode turning off the UPS to Bypass mode Then the UPS will go to bypass mode but without output if it is turned off in AC mode Bypass NOTE The following items are only available in bypass mode 7 HighLoss V Set the acceptable high voltage for bypass Setting Potatus Forbid range is from Rated Output Volt 11V to 276V and the default value is 264V HighLoss V 264V LowLoss V Set the acceptable low voltage for bypass Setting ee tee retin range is from 110V to Rated Output Volt 11V and the default LowLoss V 110 value is 110V HighLoss F 54Hz HighLoss F Set the acceptable high frequency for bypass LowLoss F 46Hz 50 Hz Setting range is from 51Hz to 54 Hz 60 Hz Setting range is from 61Hz to 64Hz The default value is 54 0Hz 64 0Hz LowLoss F Set the acceptable high frequency for bypass 50 Hz system Setting range is from 46 0Hz to 49 0Hz 60 Hz system Setting range is from 56 0Hz to 59 0Hz The default value is 46Hz 56Hz 2 ECO setting only available or effective on bypass mode 1 Status Enable Enable ECO Function Disable Disable ECO Function ECO If ECO function is disabled voltage range and frequency range for ECO mode still can be set but it is meaningless unless the ECO gt Status Disable Tae Prane MEA l an eee eae 2 HighLoss V High voltage point in ECO mode The setting range HighLoss V 232 is from 5 to 10