Home
User Manual Bulletin 2705 RediPANEL Keypad Modules
Contents
1. ji The program example in Figure 7 2 illustrates how the function key FI may be used just like a push button or other similar input type device In this instance F1 is used to increment the accumulative value of count up counter C5 1 and initiate a MOVE instruction Each time the FI function key is pressed the accumulated value of the counter increases by one and the MOVE instruction moves the new value to the right hand side of the Keypad display The Destination address of the MOVE instruction is 0 021 which for this configuration is the word in the output image table where integer data is sent to the Keypad Module See Figure 7 1 Input and Output Image Tables Any integer number sent to this word address will be displayed on the Keypad Module display Move instructions aren t the only instructions that may be used to display data on a Keypad Module Logical Arithmetic and some File type instructions may also be used Any method of moving data is acceptable 7 4 Triggering a Stored Message to Describe Data Rung 2 0 Function m Rung 2 1 Key I 020 I F1 Function Chapter 7 Programming The Keypad Module is not only capable of displaying numeric data but also alphanumeric messages to describe that data These messages may be stored in the programmable controller and sent to the Keypad Module via ASCII code or store up to 120 messages in the Keypad Module and trigger t
2. Chapter 7 Programming SLC 5 02 Programming In the following example a Bulletin 2705 RediPANEL displays stored Example messages An alarm connected to an output module signals when communications with the RediPANEL are lost The system consists of e SLC 5 02 Processor Catalog No 1747 L524 in slot 0 e Remote I O Scanner Catalog No 1747 SN in slot 1 e Output Module Catalog No 1746 OB8 in slot 2 e An alarm connected to the output module e Bulletin 2705 RediPANEL SLC 5 02 RediPANEL SLC 5 02 Programming As shown in G file below the RediPANEL is configured as a 1 2 rack device Examples beginning at rack 0 group 0 G FILE RIO Rack 3 RIO Rack 2 RIO Rack 1 RIO Rack 0 Starting Group Starting Group Starting Group Starting Group 6 4 2 Device Address Word 1 0 0 Device Size Word 2 0 0 0 Chapter 7 Programming The scanner input file is shown below The output file is similar it is addressed O 1 0 to O 1 3 BitNumber 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Input File Rack 0 Group 0 EEHEEHE 1 1 0 Rack 0 Group 1 P gl B 1 1 1 Rack 0 Group 2 P L I 1 2 Rack 0 Rack 0 Group 3 a ees ON A 1 1 3 Rack 0 Group 4 1 1 4 Rack 0 Group 5 1 1 5 Rack 0 Group 6 1 1 6 Rack 0 Group 7 1 1 7 Rack 1 Group 0 1 1 8 Rack 1 Group 1 1 1 9 Rack 1 Group 2 1 1 10 Rack 1 Rack 1 Group 3 1 1 11 Rack 1 Group 4 1 1 12 Rack 1 Group 5 13 13 Rack 1 Group 6 1 1 14 Rack 1 Group 7 111 15 Rack 2 Group
3. 00 16 310 Gl l 16 600 540 1E 1I Rung 7 The input signal function key F2 is being latched on Rung 8 The input signal 540 00 is retrieving the preset 137 of counter 037 and displaying it on the Keypad Module output 412 Rung 10 The existing preset value is now being displayed on the Keypad Module To enter a new preset depress the appropriate number keys followed by the ENTER key 310 16 Rung 11 This rung verifies what was entered to show us the new preset When the ENTER key was depressed 310 16 the new preset 137 was then displayed on the Keypad Module 412 Rung 12 Output word 540 is unlatched when ENTER key is pressed 7 22 Chapter 7 Programming Part C Displaving a Rungs 13 17 retrieve and display a message 6 Character Message for HLC 2 310 0511 13 L I G Rung 13 When function key F6 is depressed a number is retrieved from word 511 and put in the output image table location 413 reserved for a stored message number Refer to output image table Shown above message number 1 is being moved to word 413 Rung 14 In order for the message to continually be displayed the Display Message bit 410 16 of the output image table must be on Rung 14 latches this bit on 310 16 a 14 000 310 0477 17 G 14 00 Rung 15 When function key F5 is depressed the display Rung 16 message bit
4. e Any momentary push button function e Acknowledging alarm messages Each function key features an independent LED A terminal block is provided for hardwiring a security keyswitch When the Normally Open contact is closed it locks out the functionality of the numeric keypad but allows the use of the function keys 1 through 6 and destination value functions The RediPANEL Keypad Module features a sixteen character alphanumeric vacuum fluorescent display It can display input information from the keypad ASCII and numeric data from the PLC and messages that are stored in the module The module can display any one of the following combinations of information at any one time 1 All ASCII data This can consist of either a A single line 16 character message stored inside the module Up to 120 single line messages can be stored in the EEPROM inside the module To create and edit messages the modules feature a built in message editor The editor is accessed by plugging an IBM XT AT keyboard or compatible into the receptacle located on the back of the module b Up to 12 ASCII characters from the PLC In this manner the Keypad Module can display text to inform and prompt operators It can also be used to display alarm messages that are stored on the kevpad s EEPROM inside the module 2 3 Chapter 2 Product Introduction Remote I O Communications 2 4 2 A combination of ASCII and numeric data Up to 8 charac
5. wy Allen Bradley Bulletin 2705 User RediPANEL Keypad Manual Modules Cat Nos 2705 K11C1 K11C2 K12C2 K12C3 K12C4 Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment Safety Guidelines for the Application Installation and Maintenance of Solid State Controls Publication SGI 1 1 describes some important differences between solid state equipment and hard wired electromechanical devices Because of this difference and also because of the wide variety of uses for solid state equipment all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable In no event will the Allen Bradley Company be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment The examples and diagrams in this manual are included solely for illustrative purposes Because of the many variables and requirements associated with any particular installation the Allen Bradley Company cannot assume responsibility or liability for actual use based on the examples and diagrams No patent liability is assumed by Allen Bradley Company with respect to use of information circuits equipment or software described in this manual Reproduction of the contents of this manual in whole or in part without written permissio
6. Maintenance and Troubleshooting Power Up Sequence Error Message Display Basic Troubleshooting Questions 8 2 The COMM Indicator Anv communication faults or errors are indicated bv the green LED labeled COMM The LED can be in one of three states 1 OFF 2 ON 3 Blinking COMM OFF When COMM indicator is OFF 1 The module is not receiving input power 2 The module is operating correctiv but no communications is occurring at this time Check the Remote I O Link wiring 3 The module is the last rack but the DIP switch indicating this state is not in the OFF position COMM ON When COMM indicator is ON 1 The module is operating correctly and no communications faults have been found COMM Blinking When COMM indicator is blinking The COMM indicator blinks if the PLC is in the program or test mode If you receive an error message during power up clear the error and recycle power to the module Since error conditions may stack up you may have to repeat the power up clear error power up cycle several times to clear all errors Since the Keypad Module is part of an integrated system you must evaluate the entire system when a fault is detected Start your troubleshooting by asking these basic questions 9 Is the rack address set properly Refer to Chapter 5 9 Are the baud rates of the Keypad Module and the Scanner Module the same Refer to Chapter 5 9 Is the Keypad Module the last module in
7. Publication 1747 NM005 PLC Processors Logical Physical Logical Physical Mini PLC s 2 05 2 15 16 Devices 7 Racks 2 16 2 17 PLC 5 12 16 Devices 7 Racks tJ tJ PLC 5 25 16 Devices 7 Racks 3 1 PLC 5 250 32 Devices 8 16 Devices 7 Racks Scanner 4 Racks Scanner O Scanners 4 Scanners Processor Processor PLC 2 30 16 Devices 7 Racks total 16 Devices 7 Racks channel 2 Channels scanner PLC 3 16 Devices 32 Racks 16 Devices 7 Racks channel 64 using 4 Channels complimentarv scanner 1 0 PLC 5 15 12 Devices 3 Racks 2 7 Racks 7 Racks PLC 3 10 16 Devices 16 Racks total 16 Devices 7 Racks channel 4 Channels scanner 1 Two of these may be Bulletin 1771 chassis 2 PLC 5 15 Series B Revision H or later have partial rack addressing Earlier versions were limited to 3 full rack devices PLC 5 25 Series A Revision D or later have partial rack addressing Earlier versions were limited to 7 full rack devices e Chapter Objectives DIP Switches Chapter Selecting Options This chapter describes DIP switch location and functions on the Bulletin 2705 RediPANEL Kevpad Module Italso lists the switch bank settings for selecting function and configuration options See Figure 5 1 to identifv the Kevpad Module switch banks Figure 5 1 Switch Bank Location and Functions on Bulletin 2705
8. l 2 To get maximum benefit from this manual and the best use of the Bulletin 2705 Kevpad Module in vour svstem vou must be able to operate and program an Allen Bradley Programmable Logic Controller PLC or Small Logic Controller SLO We make reference in this manual to several other publications Thev are e Allen Bradley Publication 1770 4 1 for grounding and wiring guidelines e National Electrical Code published by the National Fire Protection Association of Boston Massachusetts wire sizes and tvpes for grounding electrical equipment e Programmable Controller and scanner module literature Refer to page 4 6 for publication numbers e Bulletin 2705 Keypad Programming Software User s Manual We use the following terms and acronyms in this manual Keypad Module Allen Bradley Bulletin 2705 RediPANEL Keypad Modules Catalog Numbers 2705 K11C1 K11C2 K12C2 K12C3 K12C4 PLC Programmable Logic Controller SLC Small Logic Controller Chapter Objectives Features Functions Chapter Product Introduction This chapter describes the features functions and operation of the Bulletin 2705 RediPANEL Kevpad Module The Bulletin 2705 RediPANEL Kevpad Module is an operator module that connects directly to an Allen Bradley PLC via the remote I O link It provides the capabilitv for operators to input data to and retrieve data from the PLC It also functions as a single line message display The Keypad Modu
9. this method is called Bidirectional Block Transfers The block transfer read instruction reads input data from the sub I O scanner and transfers that data to integer files in the PLC The block transfer write instruction writes output data to files of the PLC then transfers that data to the sub I O scanner What this means is that instead of input addresses starting with I and output addresses starting with O both input and output addresses will begin with N7 or greater The rest of the input addresses will depend on the specific integer file that is designated as the DATA FILE in the block transfer read instruction The rest of the output addresses will depend on the specific integer file that is designated as the DATA FILE in the block transfer write instruction The Keypad Module must have Bank 1 DIP Switch settings set for PLC 2 even though a 1771 SN scanner is used with a PLC 5 Refer to Page 5 2 for additional information Chapter 7 Programming The ladder diagram in Figure 7 6 is a simple programming example showing Bidirectional Block Transfers between a sub I O scanner and PLC 5 Figure 7 6 PLC 5 Block Transfer BTR BTW Read from Sub Scanner Enable Bit Enable Bit to the PLC 5 N10 0 N10 5 4 d H a m BLOCK TRNSFR READ L gN 15 15 RACK ol l GROUP MODULE 1 CONTROL BLOCK N1004 ER DATA FILE LENGTH BTR BIW Write to the Sub Scanner Enable B
10. 14 11 DOC 5 l Output Image Table ag Mode 17 16 15 14 11 10 7 ECEDEDEDBERRID Dec Pos DC SDP Displayed data has 3 SDP is Entered data has 1 places to the right Enabled place to the right 1 27 Chapter 7 Programming When to Use the Handshake RediPANEL Modules have a standard TIMED feature that holds all push Mode button depressions for a minimum of 100 milliseconds to allow the PLC controller to read the depression during its scan cycle No special programming is needed for this function Most svstem configurations can use this feature to help insure data capture of a push button depression As a general guideline handshaking is not required The few cases where it 1s required would be 1 Very lengthy scan times Lengthy scan times can occur when the block transfer instruction is used numerous times in the ladder program Lengthy scan times can also occur when the ladder program is very large 2 When the remote I O link is approaching its physical limitation of 16 devices RediPANEL push button modules keypad modules remote I O racks To select the Handshake feature enable set ON the module s DIP switch 7 on switch bank 2 Setting this switch OFF gives you the TIMED feature which is the default setting Chapter 5 discusses switch settings for mode configuration Figure 5 5 refers to Handshake enable and disable settings To use the Handshake feature the PLC program must have a rung that
11. 20 Chapter 7 Programming Part A Changing and Examining Rungs 1 5 show a procedure for monitoring the accumulated value of Accumulated Value of Counter counter 037 using the Keypad Module for PLC 2 Rung 1 The input signal function key Fl is programmed to increment counter 037 Rung 2 The counter value cannot be sent directly to the output image table of the Keypad Module because the counter is a 3 digit BCD and word 412 of the keypad output table is designed for a 4 digit BCD value So we must first put the counter value in a buffer location and make sure the upper 4 bits of counter 037 are zero before being sent to Keypad Module output image table Rung 3 These rungs guarantee that no number will appear Rung 4 in the fourth digit of the Keypad Module Input signal 477 on both rungs will put a zero into the done bit 500 15 and CTU enable 500 17 bit of the buffer word 500 Rung 5 When function key Fl is depressed the accumulated value of the counter will be displayed on the right hand side of the Keypad Module 7 21 Chapter 7 Programming Part B Changing and Examining Rungs 7 12 show a programming procedure that will allow you to change preset Value of Counter for the preset values of the counter that was being monitored in rungs l 5 PLC 2 Rung 6 and Rung 9 are for message recording and will be explained later 540 0137 G 00 500 540 310 0312 fil jres fal
12. 511 0413 e SS E PUT 4 15 001 003 0 310 fi L 16 15 ig 410 SS A u 14 16 310 0477 0413 SS E SS SS SS a PUT 14 000 003 310 0477 0412 81 PUT 14 00 214 END 01107 The explanation of the example program begins on the next page 16 Chapter 7 Programming Program Set up Rungs A B and C set the program up i BLOCK XFER READ DATA ADDR 0030 MODULE ADDR 111 BLOCK LENGTH 14 FILE 0200 0215 BLOCK XFER WRITE 4 EN 4 DATA ADDR 0031 l 16 MODULE ADDR 111 BLOCK LENGTH 14 FILE 0400 0415 FILE TO FILE MOVE COUNTER ADDR 0031 POSITION 014 FILELENGTH 014 FILE A 0200 0215 PILE B 0300 0315 RATE PER SCAN 014 The block transfers and the file to file move allow for communications from the sub scanner to the programmable controller The block length of 14 allows for 8 utility words needed by the sub scanner and 6 words or 4 rack for the Keypad Module The resulting input output image tables in Figure 7 9 on the following page go along with this programming example for Keypad Module Chapter 7 Programming Figure 7 9 I O Table for Sample Program BCD Mode 3 4 Rack Input Image Table 17 16 15 14 13 6 5 4 3 2 1 0 Output Image Table 17 16 15 14 13 12 6 5 4 2 1 0 The symbols and abbreviations for the bits in these tables are explained on pages 7 25 and 7 26 7
13. 5cm from outside edge of mounting flange Depth of enclosure 8 20cm or more Mechanical Installation Mounting tabs are built into the module After vou slide the module into the enclosure the tabs secure the module to the enclosure See Figure 3 2 The installation procedure is listed on the following page 3 3 Chapter 3 Installing the Bulletin 2705 Keypad Module To install the module follow these guidelines Step 1 Cut an opening in the panel approximately 5 86 149mm H x 8 61 219mm W See Figure 3 3 Figure 3 3 Mounting Dimensions of the Module 9 50 241 30 7 375 d 187 33 dls Panel Cut Out 5 86 x 8 61 148 84 x 218 69 Front View Panel Outline 12 Max Thkns Panel Cutout Dimensions Step 2 Drill six 0 312 7 6mm diameter holes for the top and bottom mounting brackets A template is provided with the module to assist in this operation Step 3 Slide the module through the opening The mounting tabs will help seat the module tightly against an 062 1 6mm to 125 3 2mm thick enclosure 3 4 y k l l Connecting to a Remote I O Link Chapter 3 Installing the Bulletin 2705 Kevpad Module Step 4 To complete the mechanical installation apply the mounting brackets and tighten all the captive knurled thumbscrews to 5 in lbs only A torque screwdriver is recommended for this operation Figure 3 4 shows the location of t
14. I O link Enable HANDSHAKE to allow the use of the handshake bit which holds an input signal on until the PLC acknowledges data receipt If you disable HANDSHAKE the module uses a timed mode 100 millisecond delay to make sure the PLC reads the input signal Handshaking is explained in detail in Chapter 7 Enable LAST STATE to lock the module up hold the display in its last state if communication with the PLC is lost If you disable LAST STATE the display will clear instead of locking up When communication is reestablished the module updates itself and resumes operation 5 4 Chapter 5 Selecting Options Setting Switch Bank 3 rib Se SUPR gives the switch functions and settings for Switch Bank 3 These itc in dank FB settings are for all PLC s Figure 5 6 Setting Switch Bank 3 RACK SIZE 1 4 1 ON 2 ON 1 2 1 ON 2 OFF 3 4 1 OFF 2 ON Full 1 OFF 2 OFF STORED MESSAGE DISABLED 3 OFF ENABLED 3 ON ON Example SPLIT DISPALY ENABLED 4 OFF DISABLED 4 ON KEVBOARD STVLE XT 5 OFF AT 5 ON SMD DEST FORMAT TRACKING 6 OFF BCD 6 ON NOT USED SWITCHES 788 Enable STORED MESSAGE to be able to store and retrieve messages on the EEPROM inside the keypad module If STORED MESSAGE is disabled messages can only be retrieved from PLC memory Enable SPLIT DISPLAY to control what is displayed during operator entry Refer to page 6 4 for more information The DEST and SMD FORMAT contr
15. Kevpad Module Switch bank 1 SW 1 sets the rack address Switch bank 2 SW 2 controls format and communication parameters baud rate data format and the modes for Destination Bits Last Rack Keyswitch Handshake and Last State Switch bank 3 SW 3 establishes rack size and the modes for Stored Message Display Split Display and Keyboard type IMPORTANT NOTE Remove power from the module before setting DIP switches Switch settings are scanned only on power up 5 1 Chapter 5 Selecting Options Typical Switch Settings The following figures show examples of DIP switch settings Figure 5 2 illustrates the ON and OFF positions of the DIP switches Figure 5 2 Setting DIP Switches FRONT SIDE ON ON and OFF position examples The switch setting is indicated by shading Setting Switch Bank 1 Figure 5 3 gives functions and settings for Switch Bank 1 Notice that the rack address settings apply only to PLC 2 or any other PLC usung a 1771 SN Sub I O Scanner Module Rack address settings for PLC 3 PLC 5 15 and PLC 5 25 are listed in Figure 5 4 on the following page Figure 5 3 Setting Switch Bank 1 for PLC 2 or any other PLC using a 1771 SN Specifying Rack Address for PLC 2 family or any other PLC using a 1771 SN sub I O Scanner Module 1 0 Rack Rack address MSB Address Rack address Rack address Rack address Rack address Rack address LSB First I O group MSB First I
16. O group LSB mn Example PLC 2 First I O I O rack Group number 5 First I O group 6 T Chapter 5 Selecting Options Figure 5 4 lists the rack address settings on Switch Bank 1 for PLC 3 PLC 5 15 PLC 5 25 and SLC 5 02 controllers Figure 5 4 Setting Switch Bank 1 for PLC 3 PLC 5 15 PLC 5 25 and SLC 5 02 Specifying Rack Address for PLC 3 or PLC 5 1 0 Rack Switch Settings 1 0 Rack jk Aa S GRIS on on on on on on Rack 00 not valid with PLC 5s First I O Group 0 2 4 6 Chapter 5 Selecting Options Setting Switch Bank 2 Figure i 8re 5 5 gives the switch functions and settings for switch bank 2 Seiting Switch Bank 2 Figure 5 5 Setting Switch Bank 2 BAUD RATE 57 6K 1 ON 115 2K 1 OFF 230 4K 1 ON N A 1 OFF DATA TYPE BINARY 3 ON 4 ON ON Example PLC 5 15 INTEGERS ON 4 OFF BCD 3 OFF 4 ON A Baud Rate 57 6K N A 3 OFF 4 OFF LAST DEVICE ENABLED 5 OFF DISABLED 5 ON Integer Datatype Last Device DISABLED Keyswitch DISABLED Handshake DISABLED Last State DISABLED DISABLED 6 OFF ENABLED 6 ON DESTINATION BITS HANDSHAKE DISABLED 7 OFF ENABLED 7 ON LAST STATE DISABLED 8 OFF ENABLED 8 ON Set BAUD RATE to 57 6K for PLC 5 15 and 5 25 or the module will not communicate with the PLC Set LAST DEVICE to OFF position to tell the scanner module that the Keypad module is the last device of that logical rack not necessarily the last device on the
17. Programming be reflected in this file Therefore all vour input or output addresses for these remote devices will be elements of this file e LENGTH is the number of words the sub I O scanner is transferring The number entered will be equal to 8 words reserved for sub I O scanner utilitv functions plus 2 words for each 1 4 rack of I O the sub I O scanner will be communicating with For example If you are connecting 4 RediPANELs configured for 1 4 rack plus 1 RediPANEL configured for 1 2 rack to the sub I O scanner the number vou would enter here would be 20 8 words for sub I O scanner utility functions 48 words 2 words for each 1 4 rack RediPANEL 4 words for the one 1 2 rack RediPANEL 20 words e CONTINUOUS determines the mode of instruction execution Enter N for no It is important to note that all block transfer read and write instructions should be programmed in the first rungs of the program Each instruction may transfer a maximum of 64 words at a time between the processor and the sub I O scanner 8 words for the sub I O scanner utility functions and 8 words for each of the 7 logical racks of RediPANELs the sub I O scanner is capable of communicating to Programming Example In this programming example we are using block transfer read and write instructions to communicate between a PLC 5 15 and sub I O scanner The sub I O scanner is located in slot 1 module group 7 of the local I O rack The sub I O sca
18. a physical rack and has it been identified as the last rack Refer to Chapter 5 e Is the communication connector securely plugged in at both the Keypad Module end and the Scanner Module end Chapter 8 Maintenance and Troubleshooting e Have you changed the settings of any of the DIP switches New DIP switch settings will not be acknowledged until power is recycled Refer to Chapter 5 e If you do not have the communications LED ON and all of your DIP switches seem correct check the remote I O link wiring You may need to reverse the blue and clear wires e f your 120 Volt AC is intermittent be sure your 120 240 Volt AC selectable switch is set properly 8 3 Chapter Objectives Specifications Chapter Specifications This chapter lists the specifications for the Bulletin 2705 Kevpad Module FUNCTION Provides kevpad interface for data entrv and displav in Remote I O Serial Data Link POWER AND ENVIRONMENTAL Power Supplv Integral power supplv in each module Operating ranges Series A B C D Series E 90 132 Volts AC 47 63Hz 90 265 Volts AC 47 63Hz 180 265 Volts AC 47 63Hz 18 30 Volts DC 18 30 Volts DC Input Current and Power Ratings 24 Volts DC 15VA 625 milliamperes 120 Volts AC 15VA 125 milliamperes Temperature Range Operating 0 C to 60 C Storage 40 C to 85 C Humiditv 5 95 non condensing Note Operating temperature at 0 C is based on the absence of freezing moistu
19. accepts the handshake bit and allows communication to continue Refer to Figure 7 11 for an example of this rung If you have selected the Handshake feature then your PLC program must contain this rung or the module will not operate Figure 7 11 Ladder Logic Handshake Rung Input Handshake Bit Output Handshake Bit F lt 7 28 Chapter 7 Programming With the handshake feature enabled and the handshake rung in the user s program the RediPANEL module holds all function kev input signals high for a minimum of one complete PLC program scan It keeps the signal s high for one complete cycle of the handshake input bit The handshake input and output signals will continuously toggle independent of any function key closures This ensures that the handshake function is operational even if no function keys have been pressed The timing diagrams Figure 7 12 further explain how this is accomplished IMPORTANT The following diagrams are used for illustrative purposes only and are not intended to be precise timing diagrams Exact timing diagrams vary from application to application and are dependent upon the number of remote I O nodes program scan time etc Figure 7 12 Handshake Timing Diagrams PLC Scan Cvcle Handshake Input Bit 17 Handshake Output Bit 17 Read Inputs Write to Outputs Program Scan Function Kev Contact Function Kev Input Handshake holds the function kev input high even if the function k
20. is released Rung 16 and 17 put zeros Rung 17 in the data table words 412 and 413 so that the display is cleared when F5 is depressed Chapter 7 Programming Part D Displaying Message and Tn Part A and B we learned how to examine information from the PLC by Variable Data Simultaneously for using the Keypad In order to have an 8 character message work with the PLC 2 variable data a message number must be put into the stored message word of the output image table at the same time the variables appear on the keypad display Therefore the following rung is all that is required for a message to be displayed 310 0513 G 10 003 Rung 6 This rung says that when function key F1 is depressed message number 3 will be put into the stored message number location Part E Using Destination Bits to Destination bits allow for the retrieval of data from an existing area in the Retrieve or Change Data for data table where information is known to reside PLC 2 310 0137 6 12 313 0510 19 6 00 500 Rung 18 When function key F3 is depressed the preset 137 value from counter 037 will be displayed on the Keypad Module Rung 19 Input signal 313 00 is a destination bit To enable this destination bit depress the ENTER key The keypad will display gt gt gt gt Now you enter a 1 for the first bit of destination bits available which is 313 00 in
21. messages This error can be eliminated by entering a Control E and responding X to the ERROR FIX prompt when it the Message Editor It also is corrected by editing a message Note Fixing the error does not mean that the cause of the error has been corrected MESSAGE ERROR This error message is displayed whenever an invalid message number is called up for edit BAD MSG NUMBER This error is displayed when the PLC attempts to display a message that cannot be entered in the EEPROM i e a message greater than 120 WATCHDOG FAILURE This error indicates that the power up diagnostics detected an error with the watchdog circuitry Appendix A Displav Characters Figure A 1 shows the 14 segment character set for the module display The numbers next to each figure are the hexadecimal values for the characters Figure A 1 14 Segment Display Characters FTA TTIE AIR FIFA Bul AZ KRI L T V EM LU Il PNV al EEE A Address Rack 5 1 5 2 Applicable PLCs and Scanners 4 2 Applications Kevpad Module 2 2 Architecture Remote I O 4 2 ASCII Data 2 3 6 2 ASCII Message Displav 6 2 B BAD MSG NUMBER A 2 Basic Troubleshooting 8 3 Baud Rate 3 5 544 BCD Datatype 2 4 5 4 Binary Datatype 2 4 5 4 Bulletin 2705 RediPANEl Keypad Modules 2 1 C Calculating Rack Size 4 7 COMM Communications Blinking 8 2 Indicator 8 2 OFF 8 2 ON 8 2 COMM SETUP ERR A 1 COMM START ERROR A 1 COMM 1 Fau
22. the requirements of NEMA Type 4 Within the NEMA enclosure the Keypad Module or modules needs enough room to allow for convection cooling If the ambient temperature around the enclosure is below 40 C you may use an unvented enclosure To mount several modules in the same enclosure follow these guidelines see Figure 3 1 on the following page e Vertical stacking of modules The lower edge of the top cutout must be at least 6 inches 15cm from the top edge of the lower cutout The enclosure must be at least 8 inches 20cm deep e Horizontal mounting You can mount modules as close together as physically possible The enclosure must be at least 8 inches 20cm deep In some applications you may also have to deal with heat produced by other equipment inside or outside the enclosure In such a case you may place blower fans inside the enclosure to assist in circulating air to reduce hot spots near the components Do not bring in unfiltered outside air it could contain contaminants or dirt harmful to the components In extreme cases you may have to use air conditioning to protect against heat buildup within the enclosure Chapter 3 Installing the Bulletin 2705 Kevpad Module Figure 3 1 shows recommended spacing for modules inside the NEMA enclosure Figure 3 1 Spacing for Modules inside the NEMA Enclosure Recommended spacing A 6 15cm from lower edge of top cutout to upper edge of lower cutout 1 2
23. wiring and power wiring in the same conduit Where wire paths must cross make their intersection perpendicular With solid state systems grounding helps to limit the effects of noise due to electromagnetic interference EMI To avoid problems caused by EMI use shielded cables Before connecting the Keypad Module to the incoming power verify that the power source and module type AC or DC are in agreement The Keypad Module will operate from these sources e 90 265 Volts AC switch selectable 47 63Hz e 18 30 Volts DC 3 1 Chapter 3 Installing the Bulletin 2705 Keypad Module Grounding NEMA Enclosures 3 2 Grounding is an important safetv measure in electrical installations With solid state svstems as we mentioned before grounding also helps to limit the effect of noise due to EMI electromagnetic interference An authoritative source on grounding requirements is the National Electrical Code published by the National Fire Protection Association of Boston Massachusetts An article of the Code discusses the types and sizes of wire conductors and safe methods of grounding electrical equipment and components You must use a NEMA enclosure to protect the electronics of the Keypad Module from atmospheric contamination Standards established by the National Electrical Manufacturer s Association NEMA define enclosure types based on the degree of protection an enclosure will provide Select an enclosure that meets
24. with the keypad data must be moved from the Input Image table of the Kevpad Module to the PLC 5 Figure 7 5 below shows one example of the ladder logic required to change a PLC 5 counter preset value 1 7 Chapter 7 Programming Figure 7 5 Rung 2 5 Enter Key 1 020 TTII 16 Rung 2 6 F2 Function In the example shown in Figure 7 5 rung 2 5 is used to move the value from the input image table 1 021 to counter C5 1 preset each time the Enter key is pressed Rung 2 6 in Figure 7 5 shows how the function key F2 or the Enter key are used to display stored message 2 C5 1 PRE on the left side of the kevpad and the current or new preset value of counter C5 1 on the right This rung is used strictly to allow the operator to view the value that is about to be changed To actually change the preset the new value must first be entered into the input image table This is accomplished by first punching in the desired preset value using the numeric keys on the Keypad Module then pressing the ENTER key The new value is then placed in the input image table or in the case of this particular configuration word I 021 Placing rung 2 5 before rung 2 6 ensures the new updated preset value will be displayed 7 8 Using the Destination Function to Load Multiple Timer Presets 1 020 1 023 1 024 1 020 Rung 17 ll Ill Chapter 7 Programming The kevpad destination function c
25. your system design See Chapter 5 on DIP switch settings IMPORTANT NOTE For stored messages you must configure for 1 rack or larger Vou cannot use stored messages with 1 4 rack Note Stored message display requires 3 4 rack to use the BCD mode BCD mode can only be configured for 4 or 1 rack if message storage is disabled Table 4 D shows the functional characteristics of the Keypad Module configured in the available rack sizes Table 4 D 2705 Keypad Module Functions by Rack Size Binary or Integer Mode 8 Digits Number of Number of Rack Size Stored Message Number of Capability Destination Bits Number of BCD ASCII ASCII Digits Characters from Characters from PLC PLC 1 4 Rack E 6 DOCTOR ICO 37 0 0 0 1 BCD 32 3 4 Rack Others 48 BCD 64 Full Rack Others 80 4 7 Chapter 4 Configuring the Bulletin 2705 Kevpad Modules with PLC Controllers Remote I O Configuration 4 8 Once vou have selected the appropriate scanner for the PLC controller Table 4 E below lists how manv separate chassis the scanner can support and how much I O it can address For anv given application the total of all the I O used bv each device I O rack drive svstem or RediPANEL Module connected to the cable gives the amount of full racks of I O being supported by the scanner or sub scanner for that application For SLC 5 02 applications using the 1747 SN Remote I O Scanner refer to
26. 0 Word 16 1 1 16 Rack 2Group1 Word 17 1 1 17 Rack 2 Group 2 Word 18 1 1 18 Rack 2 Rack 2 Group 3 Word 19 I 1 19 Rack2Group4 Word 20 1 1 20 Rack 2 Group 5 Word 21 1121 Rack2Group6 Word22 1 1 22 Rack 2 Group 7 Word 23 1 1 23 Rack 3 Group 0 Word 24 1 1 24 Rack 3 Group 1 Word 25 1 1 25 Rack 3 Group 2 Word 26 1 1 26 Rack 3 Rack 3 Group 3 Word 27 1 1 27 Rack 3 Group 4 Word 28 1 1 28 Rack 3 Group 5 Word 29 1 1 29 Rack 3 Group 6 Word 30 1 1 30 Rack 3 Group 7 Word 31 1 1 31 octal Bit Number 47 16g 15 14s 133 12 11s 10 7s 6 5s 4s 3s 2s 1s Os 7 40 Chapter 7 Programming Address Conversion The addresses for the Input and Output files are provided in an octal format You must convert the bit addresses to decimal to accommodate the SLC 5 02 Refer to the following Bit Address Decimal 1 2 3 4 5 e 7 8 9 10 12 13 14 15 sLe 5102 octal 1 2 3 4 5 6 7 10 11 12 13 14 15 6 17 PLC 5 Scanner Configuration The BAUD rate is 115 2K DIP switch 1 should be in the OFF position DIP switch 2 should be ON The G file size is set to 3 using the Speciality I O Configuration function The MO and MI file sizes are set to 32 in the Advanced Set Up function Since only the first four words of the input and output files contain valid information the scanned input and output words can be set to 4 Reducing the number of scanned input and output words decreases your SLC scan time 7 41 Cha
27. 2 17 1772 2 25 1772 LN Mini PLC 2 1772 6 8 4 1785 LT3 PLC 5 12 1785 6 8 2 The 1771 SN sub I O scanner can be used with any PLC 2 or PLC 5 familv processor Table 4 BA Applicable Programmable Controllers Requiring 1747 SN Sub scanner Catalog ne Number Description Related Pub No 1747 SN SLC 5 02 1747 NM005 Table 4 C Applicable Scanners Catalog Number Description iie Pub 1772 SD SD2 Remote scanner distribution panel for PLC 2 family 1772 2 18 1771 SN Sub I O scanner module for PLC 2 and PLC 5 families 1771 2 91 1775 SR SR5 O Scanner Communication Adapter Module for PLC 3 10 family 1775 6 5 5 1775 S4A 1775 6 5 2 1775 S4B I O scanner programmer interface module for PLC 3 family 1775 6 5 3 1775 S5 1775 6 5 5 1785 I O scanner message handling module for PLC 5 15 4 5 25 1785 6 6 1 1785 6 8 1 5250 RS Remote scanner for PLC 5 250 5000 2 17 6008 SI IBM PC I O Scanner Module 6008 6 5 3 6008 SV VME Bus l O Scanner Module 6008 6 5 2 1747 SN Remote l O Scanner 1747 NMoo5 Scanner 1772 SD2 Revision 3 or later 4 6 Chapter 4 Configuring the Bulletin 2705 Kevpad Module with PLC Controllers Calculating Rack Size The 2705 Kevpad Module can be configured for anv of four rack sizes 1 4 1 5 3 4 and a full rack Rack sizes relate to the amount of I O accessible to each rack 32 I O bits or points for 1 4 rack 64 for 1 rack 96 for 3 4 rack and 128 for a full rack Xou set DIP switches for the rack size vou want in
28. 4 13 1 15 2 11 10 7 6 5 4 3 2 1 0 o a 1 4 Rack Using Stored Messages Stored message displav cannot be used with 1 4 rack configurations 1 32 Chapter 7 Programming Input and Output Image Tables Integer Data With Stored Message 1 3 4 and Full Rack Figure 7 16 Integer Mode 1 2 3 4 and Full Rack Input Image Table Integer Mode 17 16 15 14 13 12 11 10 7 3 A Ja Output Image Table Integer Mode 17 16 15 14 13 12 11 10 7 6 5 4 3 2 1 0 CODO 7 33 Chapter 7 Programming Input and Output Image Tables Integer Data With Stored Message 1 4 Rack Figure 7 17 Integer Mode 1 4 Rack Input Image Table 17 16 15 14 1 3 12 11 10 7 6 5 4 3 2 1 0 Integer Data Output Image Table 17 16 15 14 13 12 11 10 7 6 5 4 3 2 1 Integer Data 7 34 Chapter 7 Programming Input and Output Image Tables Binarv Data With Stored Message 3 and Full Rack Figure 7 18 BCD Mode 3 4 and Full Rack Input Image Table BCD Mode 17 16 15 14 PEPTIDES T m Output Image Table BCD Mode 17 16 15 14 11 olle pd Two Alphanumeric Characters Two Alphanumeric Characters Two Alphanumeric Characters Two Alphanumeric Characters Two Alphanumeric Characters ATTENTION If an invalid BCD number is entered in the least significant digit location in the Output Image Table an error will occur To clear this error a valid number must be placed in the Output Image Table a
29. N when the keypad operator enters destination number 17 All other destination bits are OFF The ENTER bit 1 020 16 prevents data from being moved until the keypad operator enters a new preset for T4 16 The MOVE instruction takes the integer data in 1 021 and transfers it to T4 16 PRE The PLC 5 15 example program could be expanded to display the timer preset along with an 8 character message that identifies each timer preset The following rungs could be added for each timer Rung 18 When destination bit 1 023 00 is ON the T4 0 PRE value is displayed on the right hand side of the keypad module Rung 19 When destination bit 1 023 00 is ON the constant 4 is moved to the SMD word triggering message number 4 T4 0 PRE will be displayed on the left hand side identifying the data in the right hand side Using PLC 5 Controllers and a Sub I O Scanner with Keypad Modules Chapter 7 Programming A 1771 SN Sub I O scanner may be used with a PLC 5 family processor when the application requires more remote devices than that processor can accommodate The sub I O scanner module may be used to communicate to as many as 16 additional remote I O devices The 1771 SN Sub I O scanner may be located in the same rack as the PLC 5 the local rack or in any space of the remote racks supported by the processor The PLC 5 communicates to the sub I O scanner using block transfer read and write instructions
30. NTER keystroke After the second ENTER the new destination is mapped directly into the destination word When the destination number is entered its corresponding destination bit will be ON and all other destination bits are OFF If destination 5 is entered then the 5th destination bit is on and all others off The PLC program can utilize that ON bit to MOV GET or PUT data to from the appropriate timer counter memory location etc The DELETE key and Minus key can be used during destination entry Depress the DELETE key to delete one character at a time Depress the MINUS key to abort destination entry A programming example of the destination function is presented in Chapter 7 Page 7 9 The Keypad Module stores up to 120 16 character messages in EEPROM Refer to Page 6 2 for ASCII Message information Xou create store and edit the messages with an external kevboard A message is displaved when the program calls the storage identification number assigned to the message Refer to Page 7 1 for more information There are two methods of entering messages e IBX XT AT style keyboard e IBM PC or compatible with Keypad Programming Software Catalog Number 2705 ND1 The user s manual provided with the software describes how to enter messages using this method Keyboard You enter messages into the module with an IBM XT AT or compatible keyboard The keyboard plugs into a round 5 pin DIN receptacle on back
31. Sub I O Scanner with Keypad Modules 11 7 9 7 11 Maintenance and Troubleshooting Specifications Appendix Table of Contents RediPANEL Kevpad Module User Manual Instruction Parameters Programming Example Programming Example PLC 2 Programming Example PLC 2 Example Program Program Set up Part A Changing and Examining Accumulated Value of Counter for PLC 2 Part B Changing and Examining Preset Value of Counter for PLC 2 Part C Displaying a 16 Character Message for PLC 2 Part D Displaving Message and Variable Data Simultaneously for PLC 2 Part E Using Destination Bits to Retrieve or Change Data for PLC 2 Symbols and Abbreviations for I O Image Tables Decimal Point Control When to Use the Handshake Mode Input and Output Image Tables Integer Data With Stored Message BCD Data With Stored Message Binary Data With Stored Message Integer Data No Stored Message BCD Data No Stored Message Binary Data No Stored Message Chapter 8 Chapter Objectives Using the Comm Fault LED Indicators Power up Sequence Error Message Display Basic Troubleshooting Questions Chapter 9 Chapter Objectives Specifications A Error Messages Display Characters 7 24 7 25 7 26 7 28 7 30 7 30 7 31 7 32 7 33 7 35 7 37 NUN qo We Mo ue N o2 Chapter Objectives What this Manual Contains Chapter Using this Manual This chapter describes the manual s organization inten
32. age Display number This is the output word location for the message number which is being displayed on the Keypad When SMD 0 then ASCII data will be displayed ATTENTION Any SMD value greater than 120 will cause a lock up condition To protect against this condition a boundary check should be used in the PLC program to help insure a valid MSG is sent Chapter 7 Programming Decimal Point Control 7 26 Dec Pos DECimal POSition The decimal position field holds a binary value 1 7 that is the number of positions to the right of the decimal point Input Image table Indicates the number of places to the right of the decimal point as numeric data is being entered Output Image table Controls the number of places to the right of the decimal point when the Keypad Module is displaying variable data DC Decimal point Control Decimal point control enables SDP See Table 7 A SDP Scratchpad Decimal point Position The binary value of these bits will control the number of places 1 7 to the right of the decimal point as numeric data is being entered When this value is 0 the decimal point button in the keypad module will be active DC SDP Decimal Point Scratchpad Decimal Decimal Enable Bit Point Position Point Mode Output Image Output Image 1 0 Variable 0 don t care Disabled Chapter 7 Programming Figure 7 10 Example of Decimal Point Control Input Image Table pin Mode 17 16 15
33. ains the power up sequence error message display plus addresses basic troubleshooting questions on the RediPANEL Keypad Module Two LED indicators are located on the right top corner of the module a green LED labeled COMM and a red LED labeled FAULT The FAULT Indicator Any software or hardware faults not related to communications are indicted by the red LED labeled FAULT The LED can be in one of three states 1 OFF 2 ON 3 Blinking FAULT OFF When FAULT indicator is OFF 1 Module is operating correctly and no faults have been found 2 The module is not receiving input power FAULT ON When FAULT indicator is ON 1 The module has just been powered up The FAULT indicator momentarily 1s ON during the power up sequence 2 A fault has been detected Such a fault would be internal to the module there is no way to clear this fault condition Keypad Module power should be recycled FAULT Blinking When FAULT indicator is blinking 1 DIP switch fault 9 Check for valid data type e Make sure you have programmed the PLC for handshaking before enabling the handshake bit on the Keypad Module 2 The calculated size and rack address combination is not valid For example the module is addressed for the last module group group 3 of a logical rack and its size was calculated to be a half rack The functional configurations which result in a size of two quarter racks are indicated in Chapter 5 8 1 Chapter 8
34. an be used to load data values into multiple timer counter presets or other PLC memorv locations The example program listed below can be used to load preset values into 17 consecutive timer presets beginning with T4 0 PRE and ending with T4 16 PRE Rungs 3 through 16 have been omitted to simplify the example The keypad is configured for 3 4 Rack instead of 1 2 Rack as in the previous examples otherwise all DIP switch settings remain the same Refer to page 7 30 for an example of a 3 4 rack I O Image table Rungs 1 17 provides a PLC 5 15 example program using the Destination Function Source Rung 1 Destination bit 1 023 00 is ON when the keypad operator enters destination number 1 All other destination bits are OFF The ENTER bit 1 020 16 prevents data from being moved until the keypad operator enters a new preset for T4 0 The MOVE instruction takes the integer data in 1 021 and transfers it to T4 0 PRE Rung 2 Destination bit 1 023 01 is ON when the keypad operator enters destination number 2 All other destination bits are OFF The ENTER bit 1 020 16 prevents data from being moved until the keypad operator enters a new preset for T4 1 The MOVE instruction takes the integer data in I 021 and transfers it to T4 1 PRE 7 9 Chapter 7 Programming Rung 19 Rungs 3 16 Would appear the same but with different timer destination bit addresses Rung 17 Destination bit 1 024 00 is O
35. bleshooting 8 3 Typical Switch Settings 5 2 U Using PLC 5s and a Sub I O Scanner 7 11 Continuous 7 13 Control Block 7 13 Data File 7 13 Group 7 12 Instruction Parameters 7 12 Length 7 13 Module 7 12 Programming Example 7 13 7 15 Rack 7 12 Using the Destination Function 7 9 W WATCHDOG FAILURE A 2 Wiring 3 1 AN Rockwell Automation Rockwell Automation helps its customers receive a superior return on their investment by bringing together leading brands in industrial automation creating a broad spectrum of easy to integrate products These are supported by local technical resources available worldwide a global network of system solutions providers and the advanced technology resources of Rockwell a AA Worldwide representation el Argentina e Australia e Austria e Bahrain e Belgium e Bolivia e Brazil e Bulgaria e Canada e Chile e China People s Republic of e Colombia e Costa Rica e Croatia e Cyprus Czech Republic e Denmark e Dominican Republic e Ecuador e Egypt e El Salvador e Finland e France e Germany e Ghana e Greece e Guatemala e Honduras e Hong Kong Hungary e Iceland e India e Indonesia e Iran e Ireland e Israel Italy eJ amaica eJ apan e ordan e Korea e Kuwait e Lebanon e Macau e Malaysia e Malta e Mexico e Morocco The Netherlands e New Zealand e Nigeria e Norway e Oman e Pakistan e Panama e Peru e Philippines e Poland e Portugal e Puerto Rico e Qatar e Romania e Russia e Saudi Arabia
36. ck with Stored Message Display Input Image Table MODULE 44 INPUT RACK 4 GROUP Bits 16 15 14 13 12 10 WORD 17 7 6 5 4 TT li O ee SR Destination Bits Output Image Table MODULE ji OUTPUT RACK 2 GROUP Bits 17 16 15 14 13 12 10 7 6 5 4 3 WORD IeTepepepepepep e 9 e CARA MESAS Stored Message Display Number SMD Two Alphanumeric Characters EXAMPLE The address for the function key F1 in this example would be 1 020 10 The I O image table shown in Figure 7 1 reflects the Integer data type that the Keypad Module has been configured for Setting the DIP switches for Integer data type is particularly useful when using the Keypad Module with the PLC 5 because the PLC 5 timer and counter data is stored in an Integer format To display the Preset or Accumulated values of these instructions requires only a MOVE instruction See Displaying Numeric Data example 1 If the Keypad Module had been configured for a Binary or BCD data type a conversion instruction would have been needed to convert the ACCUM value of the counter to that data type format prior to displaying it on the Keypad Module Note The input image table will only momentarily indicate a state change if F1 F6 is pressed This change of state may not be displayed in all instances 7 3 Chapter 7 Programming Displaving Numeric Data Figure 7 2 Rung 2 0 FI COUNT UP Counter Preset C5 1 ACC 0 021 b 50 l
37. ded audience and special terminologv This manual describes the equipment communication protocol command structure installation operation troubleshooting and specifications for the Allen Bradley Bulletin 2705 RediPANEL Keypad Modules Catalog Numbers 2705 K11C1 K11C2 K12C2 K12C3 K12C4 You will want to study this manual before installing interconnecting or operating the Keypad Module Table 1 A shows the manual s organization Chapter Purpose 1 Using this Manual Gives guidance on how to use this manual properly 2 Product Introduction Describes Keypad features and functions 3 Describes electrical power and Installing the grounding requirements gives Keypad Module procedures for connecting to remote I O links and scanners Configuring the Provides communication and 4 Keypad Module configuration parameters as well with PLC s as application considerations 5 Selecting Options Describes DIP switch settings Explains data input and display 6 Operating Modes modes and message entering editing and storing 7 Programming Describes programming explains sample program and lists input output image tables Maintenance and Covers basic troubleshooting 8 Troubleshooting questions LED displays and power up sequence 9 Specifications Lists the design and operating specifications for the Module 1 1 Chapter 1 Using this Manual Audience Reference Materials Definition of Major Terms
38. e Singapore e Slovakia e Slovenia e South Africa Republic of e Spain e Sweden e Switzerland e Taiwan e Thailand e Trinidad e Tunisia e Turkey e United Arab Emirates United Kingdom e United States e Uruguay e Venezuela Rockwell Automation Headquarters 1201 South Second Street Milwaukee WI 53204 2496 USA Tel 1 414 382 2000 Fax 1 414 382 4444 Rockwell Automation European Headquarters Avenue Hermann Debroux 46 1160 Brussels Belgium Tel 32 2 663 06 00 Fax 32 2 663 06 40 Rockwell Automation Asia Pacific Headquarters 27 F Citicorp Centre 18 Whitfield Road Causeway Bay Hong Kong Tel 852 2887 4788 Fax 852 2508 1846 World Wide Web http www ab com Publication 2705 ND002 Series A 40061 144 01 A Supersedes Publication 2705 801 Dated November 1987 Copyright 1993 Allen Bradley Company Inc Printed in USA
39. ed message What is shown on the display is controlled by the DM bit in the Output Image table When DM 0 only the first eight ASCII characters show up on the left hand side of the display and the right most positions of the display show the numeric data When DM 1 all 16 ASCII characters are displayed and no numeric data is displayed ASCII Message Display The ASCII message is stored in the PLC and moved to the Output Image table of the Keypad Module to display the message Each word defined in the Output Image table as alphanumeric characters can hold a numbered code for two characters The PLC program can also be used to send up to 12 ASCII characters to the display Note Refer to the Appendix for the alphanumeric sub set that the Keypad Module can support The first word of alphanumeric characters in the Output Image table represents position one and two of the Keypad Module display when looking left to right The rest of the Output Image table words assigned to the alphanumeric characters follow the same pattern Word 2 positions 3 and 4 etc When the DM 1 more than eight ASCII characters can be displayed on the Keypad Module See chapter 7 for an example of an I O Image table Data Entrv Chapter 6 Operating Modes The Kevpad Module offers a standard numeric kevpad interface with a polaritv minus sign kev and a decimal point as shown in Figure 6 2 Additional features are DELETE and ENTER keys and six pro
40. error while testing the EPROM memory of the Numeric Keypad Node Module INTERNAL RAM ERR This error indicates that the power up diagnostics have detected an error in the RAM contained on the module s CPU processor EXTERNAL RAM ERROR This error indicates that the power up diagnostics have detected an error in the RAM that is external to the module s CPU processor INT TIMER1 ERROR This error indicates that the power up diagnostics have detected an error with the interrupt timer circuitry DATA TYPE ERROR This error indicates that the data type set up is incompatible with the other DIP switch selections RACK CONFIG ERR This error indicates a rack configuration error i e address switches data type SMD enabled This is caused by incorrect setting of DIP switches on the module COMM SETUP ERR This error indicates that there was an error during the setup of communications COMM START ERROR This error indicates that an error was detected when the Numeric Keypad Module attempted to start communications A 1 Appendix A OVERFLOW This error indicates that the user attempted to enter a number that was larger than what the module s configuration could handle PLC SENT NON BCD This error indicates that the PLC sent a non BCD digit when one was expected This is generally a programming error on the PLC EEPROM CRC ERROR This error indicates that the power up diagnostics detected a CRC error on the EEPROM used for the stored
41. ev contact signal goes low Chapter 7 Programming Input and Output Image Tables Integer Data With Stored Message 1 3 4 and Full Rack Figure 7 13 Integer Mode 1 2 3 4 and Full Rack with Stored Message Displav Input Image Table Integer Mode 17 16 15 14 13 12 11 10 7 6 5 4 3 2 1 0 pee B KG PA KG L me B ee Output Image Table Integer Mode 17 16 15 14 13 12 11 1 3 0 7 6 5 4 3 2 1 0 EPIS Integer Data Stored Message Display Number SMD B ae NMNNNNNN ee LI AAA LU NEAL NN 1 4 Rack Using Stored Messages Stored message displav cannot be used with 1 4 rack configurations 7 30 Chapter 7 Programming Input and Output Image Tables BCD Data With Stored Message 3 4 and Full Rack Figure 7 14 BCD Mode 3 4 and Full Rack with Stored Message Displav Input Image Table BCD Mode 17 16 15 14 13 12 11 10 7 6 5 4 3 2 1 0 DEDO Output Image Table BCD Mode 5 14 13 12 11 10 5 4 2 1 s 17 16 1 7 6 0 1 4 and UP Rack Using Stored Stored message display cannot be used with 1 4 and 1 2 rack BCD Messages configurations 7 31 Chapter 7 Programming Input and Output Image Tables Binary Data With Stored Message 1 3 4 and Full Rack Figure 7 15 Binarv Mode 1 2 3 4 and Full Rack with Stored Message Displav Input Image Table Binary Mode 17 16 15 14 13 12 1 10 7 6 5 4 3 2 1 0 KIEL GO E 99 T7 Output Image Table Binary Mode 17 16 1
42. grammable function keys with LED s Figure 6 2 Keypad Layout e rut DOUNE DODENER DEE BEI The Keypad Module accepts up to eight digits of data e Six digits for 1 4 rack BCD 0 to 999 999 e Eight digits for 1 rack BCD 0 to 99 999 999 e Five digits for binary 0 to 65 535 e Five digits for integer 32 767 to 32 767 The module ignores any digits after the first eight Note For binary and integer the numeric value is checked for being in range before it is sent to the PLC The DELETE key clears one character at a time Each deletion shifts previously entered characters one position to the right Each function key and its LED is individually programmable through bits in the PLC image tables 6 3 Chapter 6 Operating Modes 6 4 To enter data vou must first kev in the desired numbers using the numeric kevpad The data will appear on the right hand side of the displav as the numbers are being keved To complete data entrv vou must press the ENTER key The entered data is placed directly into the data word s of the Input Image table Any ASCII characters in the left hand side of the display remain there during data entry unless the Split Display feature is enabled Split Display This feature controls the display during operator entry Split display must be enabled DIP switch 4 on switch bank 3 and DM 0 When the operator starts entering data the data shown in the right half of display is placed in t
43. h PLC Controllers Figure 4 5 Keypad Module with PLC 5 15 5 25 Scanner Port 1785 Figure 4 6 Keypad Module with any PLC 5 and Sub Scanner Sub Scanner Module 1771 SN 4 4 Chapter 4 Configuring the Bulletin 2705 Kevpad Module with PLC Controllers Figure 4 7 Keypad Module with SLC 5 02 RIO SLC 5 02 Scanner Port 1747 SN Compatible PLC Controllers and The Bulletin 2705 Keypad Module is compatible with all Allen Bradley Scanners scanners that support remote I O Tables 4 A 4 B and 4 C on this and the following page list applicable PLC s and scanners The 1771 SN sub I O scanner module allows a local PLC 2 or PLC 5 family processor to communicate with one to seven remote I O racks Table 4 A Applicable Programmable Controllers Catalog Number Description Related Pub No 1772 LP1 1772 6 8 1 1772 LP2 1772 6 8 1 1772 LP3 1772 6 8 3 1775 L1 L2 1775 6 4 1 1775 LP4 LP8 1775 2 20 DUI 1785 LT 1785 6 8 2 1785 LT2 PLC 5 25 1785 6 8 2 5250 LP1 LP2 5000 2 17 1785 L40 PLC 5 40 1785 2 1 1785 L60 PLC 5 60 1785 2 1 1747 1524 SLC 5 02 1747 804 45 Chapter 4 Configuring the Bulletin 2705 Kevpad Modules with PLC Controllers Table 4 B Applicable Programmable Controllers Requiring 1771 SN Sub scanner Catalog Number Description Related Pub No 1772 LS LSP Mini PLC 2 05 1772 6 8 6 1772 LV Mini PLC 2 15 1772 6 8 2 1772 LX LXP Mini PLC 2 16 1772 2 26 1772 LW LWP Mini PLC
44. he left half The operator can then enter new data in the right half Decimal Modes The decimal point key allows you to input decimal numbers You control the position of the decimal point either fixed or floating by setting bits in the output image table See Chapter 7 for input and output image tables Polarity The polarity key minus sign allows you to change the polarity of numbers The minus sign uses one character position limiting negative numbers to seven digits Destination Entry The keypad module has an additional entry feature known as the destination function This feature is selected by DIP switch 2 on switch bank 2 It is typically used to load data values into multiple locations such as a series of timer counter presets loop setpoints etc This function uses the destination word and destination bits in the Input Image table The keypad operator enters a destination number that defines which timer counter or PLC memory location is to be accessed The operator can then enter new data or monitor the present data in that timer counter or PLC memory location Messages Chapter 6 Operating Modes Figure 6 3 Displav for Destination Entr DATATA A O The kevpad operator starts bv pressing the ENTER kev The present destination is displayed between the gt gt gt gt symbols as shown in Figure 6 3 The flashing gt gt symbol prompts the operator for a new destination number followed by another E
45. hem according to their message number The later method is the most common means of displaying messages on the Keypad Module As described earlier in the System Configuration section several messages have already been entered into the Keypad Module Figure 7 3 below shows Rung 2 2 has been added to the sample program This will trigger a message in the Keypad Module Figure 7 3 COUNTER UP Counter Preset ulcus L 7 5 Chapter 7 Programming Rung 2 2 shows how the same input F1 which is used to move the accumulated value of the counter to the Kevpad displav can also trigger a stored message The MOVE instruction in rung 2 2 moves the constant 1 to 0 022 the word in the output image table where the Stored Message Displav SMD number is sent to the Kevpad Module See Figure 7 1 Input and Output Image Tables In this case when FI is pressed message number 1 C5 1 ACC will appear on the left side of the display and C5 1 accumulated value will appear on the right In Series B Rev D or earlier Keypad Modules the SMD number must be a BCD number only regardless of what data type the module has been set for Displaying a Full Line Stored In some instances the application requires a full line 16 character message Message to prompt the operator display machine status warnings or fault messages This is accomplished by turning on the DM bit in the output image table at the same time the message number is moved t
46. hese screws Figure 3 4 Mounting Bracket Thumbscrews 1101111 4 kuk wx The remote I O link begins at the scanner module The scanner modules and PLC controllers impose physical and logical limitations on the link You have to know these limitations to avoid exceeding them e To the rest of the system the Keypad Module looks like a remote I O rack and is addressed as such 9 You may distribute up to 16 remote I O devices along the link e The maximum cable length link distance is limited by the baud rate selected for the system 10 000 feet 2 800m for 57 5K baud 5 000 feet 1 400m for 115 2K baud 2 500 feet 700m for 230 4K baud The actual connection to the link is through a Serial Data Link cable Catalog No 1770 CD which wires to a connector plug for the Keypad Module 3 5 Chapter 3 Installing the Bulletin 2705 Keypad Module Connecting a Scanner Module 3 6 Connect the Keypad Module to the scanner module with Allen Bradley I O cable Catalog No 1770 CD or Belden 9463 Refer to Publication 1770 4 1 for detailed grounding and wiring guidelines The user s manual or product data sheet for your scanner module will also provide cabling information Important When first installed the Keypad Module may misinterpret the hardware configuration if the DIP switch settings are not entirely correct If the FAULT indicator flashes after installation verify the DIP switch settings and recycle po
47. ignal ON until the programmable controller recognizes it e Keyswitch Enables the terminal block for the security lockout keyswitch e Data Format Two DIP switches are used to select either binary BCD or integer data types Stored Message Display When enabled determines whether to display ASCII messages from the PLC or messages stored in the module s EEPROM Split Display Enables the split display feature Chapter Objectives Electrical Precautions Power Requirements Chapter Installing the Bulletin 2705 Kevpad Module This chapter lists electrical precautions and power and grounding requirements for installing the Bulletin 2705 RediPANEL Kevpad Module Topics also include selecting NEMA enclosures the mechanical installation of the module and connecting to remote I O links and to scanner modules Install the Bulletin 2705 Kevpad Module using publication NFPA 7TOE Electrical Safety Requirements for Employee Workplaces In addition to the NFPA general guidelines we have added some specific guidelines ATTENTION Do not program any of the function keys on the Keypad Module as emergency stop switches Emergency stop switches must be hard wired to the master control relay of the system in order to turn off all machine power completely Careful routing helps cut down on electrical noise Route incoming power to the module by a separate path from the communication cables Do not run communications
48. iguration 7 2 Triggering a Stored Message 7 5 Using the Destination Function 7 9 Power Requirements 3 1 Power Source Module Type 3 1 Switch Settings 3 1 Power up Sequence Error Message Display 8 2 Programming Examples PLC 2 7 16 PLC 5 7 2 R Rack Address 5 1 5 2 RACK CONFIG ERR A 1 Rack Size Calculating 4 7 Rating NEMA 2 1 Remote I O Architecture 4 2 Communications 2 4 Configuration 4 8 Connecting to 3 5 Link 1 2 Networking l 2 S Scanner Module Connecting to 3 6 Scanners Applicable PLCs and 4 2 SDP Scratched Decimal Position 7 26 Security Keyswitch 2 3 2 4 Serial Data Link Cable 3 5 Setting DIP Switches 5 2 SMD and Destination Format 5 5 Specifications 9 1 Split Display 5 5 6 4 Stored Message 2 4 5 5 Stored Message Display 2 4 7 5 7 25 Storing Messages on EEPROM 6 5 Switch Bank 1 First I O Group 5 2 Rack Address 5 2 Switch Bank 2 Baud Rate 3 5 5 4 Datatype 5 4 Destination Bits 5 4 l 4 Handshake 2 4 5 4 Keyswitch 2 4 5 4 Last Device 5 4 Last State 2 4 5 4 Switch Bank 3 Keyboard Style 5 5 SMD and Destination Format 5 5 Split Display 5 5 Stored Message 2 4 5 5 Symbols and Abbreviations for I O Image Tables 7 25 DM Display Message 7 25 EN Enter 7 25 H Handshake Bit 7 25 F1 F6 Function Keys 7 25 L1 L6 LEDs 7 25 SMD Stored Message Display 2 4 7 25 SYSTEM ERROR A 1 T Triggering a Stored Message 7 5 Trou
49. it Enable Bit from the PLC 5 N10 0 N10 5 es BLOCK TRNSFR WRITE L4 EN L 15 15 RACK ol SROUP 7 H DN MODULE 1l CONTROL BLOCK N10 5 H ER DATA FILE LENGTH CONTINUOUS ue The block transfer read and write instructions have certain parameters that you must enter The following is a description of these instruction parameters to help you configure your block transfer instructions Instruction Parameters e RACK refers to which I O rack number that the sub I O scanner is located in The number entered here will range from 0 3 if a PLC 5 15 is being used or 0 7 if a PLC 5 25 is being used e GROUP refers to which I O group of the rack that the sub I O scanner is located in The number entered here will range from 0 7 e MODULE refers to which slot within the I O group that the sub I O scanner is located The number entered here will be Oor 1 e CONTROL BLOCK is a 5 word integer file that controls the instruction s operation Enter this integer file address without the symbol for example N7 any integer file not N7 This is not the file type for control elements R e DATA FILE is the address of the block transfer file that will be written to or read from and it is from this file that the processor transfers data Enter this file address without the symbol The status of the inputs or outputs of the remote I O devices connected to the sub I O scanner will Chapter 7
50. le suppotts the following features Sixteen character alphanumeric displav Numeric kevpad with kevs for DELETE ENTER Decimal and Polaritv Six programmable function kevs with six programmable LED indicators Remote I O networking Up to 16 modules can be located along a single cable up to 10 000 feet awav from the PLC On board message storage and message editor NEMA Type 4X rating when panel mounted indoor use only Securitv kevswitch Securitv kevswitch option Complete diagnostics Binary BCD and integer data types Power Source 90 263 Volts AC or 18 30 Volts DC Power Source 120 240 Volts AC or 18 30 Volts DC UL listed Class I Division 2 versions available Additional data access with Destination Function IBM based Keypad Programming Software Replaces multiple thumbwheels e Acts like a remote I O rack Accepts operator input of numeric data and sends it to the Programmable Logic Controller PLC Retrieves data from the PLC e Displays numeric data with related text e Allows operators to display messages that can prompt operators display alarm messages display machine or process status e Provides alarm annunciator with acknowledgment capabilities Chapter 2 Product Introduction Applications The Kevpad Module combines the functions of standard thumbwheel or push button devices with the built in capabilities of a remote I O rack The Keypad Module communicates directly with the programmable cont
51. lt 8 1 Commands Editing 6 8 Communication Faults 8 1 Communications 4 1 Compatible PLCs and Scanners 4 5 Configuring Keypad Module 4 1 Appropriate Scanner 4 1 Calculating Rack Size 4 7 Number of Chassis and Amount of I O 4 8 Configuration Remote I O 4 8 Connecting to a Remote I O Link 3 5 Cable Length 3 5 Cable Type 3 5 Connecting to a Scanner Module 3 6 Cable Type 3 6 Wiring Connections 3 6 D Data Entry 6 3 Decimal Modes 6 4 Destination Entry 6 4 Polarity minus sign 6 4 Split Display 6 4 Data Type 24 5 4 BCD 2 4 5 4 Binary 2 4 5 4 Integer 2 4 5 4 DATA TYPE ERROR A 1 Datatype 5 4 DC Decimal Point Control 7 26 Dec Pos Decimal Position 7 26 Decimal Point Control 7 26 DC Decimal Point Control 7 26 Dec Pos Decimal Position 7 26 SDP Scratched Decimal Position 7 26 Decimal Point Key 2 3 DELETE Key 6 5 Destination Bits 5 4 Destination Entry 6 4 DELETE Key 2 3 6 5 ENTER Key 2 3 6 5 Minus Key 2 3 6 5 Destination Function Using the 7 9 DIP Switches 5 1 Switch Bank 1 5 2 Switch Bank 2 5 4 Switch Bank 3 5 5 Display Characters A 3 Display Keypad 6 1 Display Message 7 25 Display Stored Message 2 4 6 2 Displaying a Full Line Stored Message 7 6 Displaying Numeric Data 74 E Editing Commands 6 8 Editing Messages 6 7 Editor Message 6 6 EEPROM CRC ERROR A 2 EEPROM Storing Messages on 6 5 Electrical Precautions 3 1 Elect
52. ming 7 1 Keypad Output Display 6 1 ASCII Data 6 2 2 3 ASCII Message Display 6 2 Display Stored Message 2 4 6 2 Numeric Data 6 2 Keys Decimal Point 2 3 DELETE 6 5 ENTER 6 5 Minus 6 5 Numeric 2 3 6 3 Keyswitch 2 4 5 4 L Last Device 5 4 Last State 2 4 5 4 Link Remote I O 1 2 Maintenance and Troubleshooting 8 1 Mechanical Installation Dimensions 3 4 Procedures 3 4 Message Display 7 25 Message Display ASCII 6 2 Message Editor 6 6 MESSAGE ERROR A 2 Messages 6 5 ASCII Display 6 2 Editing 6 7 Entering 6 7 Error A 1 Keyboard 6 6 Minus Key Polarity 6 4 6 5 Move Instruction 7 4 N NEMA Enclosures 3 1 Convection Cooling 3 2 Horizontal Mounting 3 2 Installation 3 3 Module Spacing 3 3 Vertical Stacking 3 2 NEMA Rating 2 1 Networking Remote I O 1 2 Numeric Data 6 2 Numeric Data Displaying 7 4 O Operator Data Input 2 3 Output Display Keypad 6 1 OVERFLOW A 1 P PLC l 2 PLC SENT NON BCD A 2 PLC 2 Programming Example 7 16 Accumulated Values of Counter 7 21 Displaying 16 Character Message 7 23 Displaying Message and Variable Data 7 24 Example Program 7 17 Preset Value of Counter 7 22 Program Set up 7 19 Using Destination Bits to Retrieve Change Data 7 24 PLC 5 Programming Example 7 2 Displaying a Full Line Stored Message 7 6 Displaying Numeric Data 7 4 Entering or Changing Data 7 7 I O Image Tables 7 3 System Conf
53. n of the Allen Bradley Company is prohibited Throughout this manual we use notes to make you aware of safety considerations ATTENTION Identifies information about practices or circumstances that can lead to personal injury or death property damage or economic loss Attentions help you e identify a hazard 9 avoid the hazard 9 recognize the consequences Important Identifies information that is especially important for successful application and understanding of the product PLC is a registered trademark of Allen Bradley Company Inc Pyramid Integrator DTL and CVIM are trademarks of Allen Bradley Company Inc VAX is registered trademark of Digital Equipment Corporation Table of Contents RediPANEL Kevpad Modules User Manual Using this Manual Chapter 1 Chapter Objectives 0 0 E N R RR III 1 1 What this Manual Contains lees 1 1 Audience c a aeons ath wiw ete 4 1 2 Reference Materials 0 cece eee eee 1 2 Definition Of Vers coming repere tee nny a 1 2 Product Introduction Chapter 2 Chapter Objectives llle 2 1 Features iss See ew e Ree Rey Mobs UE Mie bee Meee EET ET ES 2 1 leti 2 1 Appli ations iii eer eel cond aed caw toad Seam edu v e is 2 2 Operator Data Input 2 2 0 see 2 3 Information Display RII 2 3 Remote I O Communications 6 2 3 Installing the Bulletin 2705 Chapter 3 Keypad Module m Chapter Objectives 3 1 Electrical Precautions 3 1 Power Requireme
54. nd power to the Keypad Module must be recvcled 7 35 Chapter 7 Programming Input and Output Image Tables Binary Data With Stored Message 1 4 Rack Figure 7 19 BCD Mode 1 4 Rack Input Image Table 11 10 7 6 5 4 3 2 1 DOCCOL 17 16 15 14 13 12 0 BCD3 BCD4 BCD5 BCD6 LSD Output Image Table 17 16 15 14 1 1 10 3 12 7 6 5 4 3 2 1 0 PTS Te peTeTeTe mm oom 1 Rack Figure 7 20 BCD Mode 1 2 Rack Input Image Table 17 16 15 14 13 6 5 4 3 2 il 0 BCD1 MSD BCD2 BCD3 BCD4 BCD5 BCD6 BCD7 BCD8 LSD Output Image Table 17 16 15 14 13 12 6 5 4 2 1 0 BCD1 MSD BCD2 BCD3 BCD4 BCD5 BCD6 BCD7 BCD8 LSD Two Alphanumeric Characters 7 36 Chapter 7 Programming Input and Output Image Tables Binarv Data No Stored Message 1 3 4 and Full Rack Figure 7 21 Binarv Mode 1 2 3 4 and Full Rack Input Image Table Binary Mode 17 16 15 14 13 12 11 10 7 6 5 4 Output Image Table Binary Mode 17 16 14 1 15 3 12 11 10 7 6 5 4 3 2 1 0 o Two Alphanumeric Characters Two Alphanumeric Characters Two Alphanumeric Characters Two Alphanumeric Characters 1 37 Chapter 7 Programming Input and Output Image Tables Binary Data No Stored Message 1 4 Rack Figure 7 22 Binarv Mode 1 4 Rack Input Image Table 17 16 15 14 13 12 11 10 7 6 5 4 3 2 1 0 Binary Data Output Image Table 17 16 15 14 13 12 11 10 7 6 5 4 3 2 1 0 Binary Data 7 38
55. nner has a keypad module configured for 1 2 rack connected to it Chapter 7 Programming Figure 7 7 PLC 5 15 and Sub I O Scanner Programming Example 1771 SN Sub I O Scanner 1771 1 0 1771 O 1771 O 1771 O Local Rack 0 Remote 1 Remote 2 Remote 3 Remote Rack 1 Starting Module Group 0 1 2 Rack N10 0 N10 5 i 15 15 RACK ol GROUP 7l 4DN MODULE 1l CONTROL BLOCK N10 0 ER DATA FILE N11 0 LENGTH CONTINUOUS N10 0 N10 5 15 15 RACK GROUP 7 DN MODULE 11 CONTROL BLOCK N10 5 H ER DATA FILE N12 0 1 LENGTH CONTINUOUS Chapter 7 Programming In the programming example shown in Figure 7 7 you ll notice the length has been set for 12 8 words for the block transfer utilitv functions and 4 words for the Kevpad Modules configured for 1 2 rack The DATA FILE for the block transfer read instruction begins at N11 0 This means the addresses in the ladder logic for the keypad input will begin with N11 8 00 The DATA FILE for the block transfer write instruction begins at N12 0 This means the addresses in the ladder logic for the keypad output will begin with N12 8 00 Programming Example Figure 7 8 shows an example of what the instruction addresses for the RediPANEL Keypad Module would look like in the ladder logic given the configuration shown in Figure 7 7 The first 8 words of files N11 and N12 have been reserved for the sub I O scanner utility wo
56. nts 3 1 Grounding 3 2 NEMA Enclosures 3 2 Mechanical Installation 3 3 Connecting to a Remote I O Link 3 5 Connecting to a Scanner Module 3 6 Chapter Objectives uis sss ee steep au a e e 11 12 SET AUTORUN Entering the Special Functions Menu SEI PORE a A e euius sheers at 1 12 Configuring the Bulletin 2705 Chapter 4 Keypad Module with PLC s a Chapter Objectives 4 1 Communications 4 1 Remote I O Architecture 4 2 Compatible PLC s and Scanners 4 5 Calculating Rack Size 4 7 Remote I O Configuration 4 8 Table of Contents RediPANEL Keypad Module User Manual Selecting Options Operating Modes Programming Chapter 5 Chapter Objectives DIP Switches Tvpical Switch Settings Setting Switch Bank 1 Setting Switch Bank 2 Setting Switch Bank 3 Chapter 6 Chapter Objectives Keypad Output Display Numeric Data ASCII Data Display Stored Message ASCII Message Display Data Entry Split Display Decimal Modes Polarity Destination Entry Messages Keyboard Entering Messages Storing Editing Editing Commands Chapter 7 Chapter Objectives Introduction to Programming with the Keypad Module PLC 5 Programming Examples System Configuration Input and Output Image Tables Displaying Numeric Data Triggering a Stored Message to Describe Data Displaying a Full Line Stored Message Entering or Changing Data with the Keypad Module Using the Destination Function to Load Multiple Timer Presets Using PLC 5 s and a
57. o the SMD word The DM bit is the 16th bit of the starting module group word in the output image table See Figure 7 1 I O Image Tables Figure 7 4 below shows one example of how to trigger a 16 character message with PLC 5 ladder logic Figure 7 4 for Rack 2 Keypad 0 020 i GRTR THAN OR EQUAL Source A 0 022 Source B 7 6 Entering or Changing Data with the Kevpad Module Chapter 7 Programming In Figure 7 4 function kev F3 is used to initiate a MOVE instruction The MOVE instruction moves the constant 3 to the Kevpad module s stored message word 0 022 This in turn triggers stored message number 3 16 CHARACTER MSG The second rung in Figure 7 4 Rung 2 4 uses a Greater Than Equal To instruction GEQ to control the DM bit In this case if the message number being displaved is 3 or more the DM bit 16 is turned on to allow all 16 characters of the message to be displayed The GEQ or LEQ Less Than Equal To instruction can be very useful in this application For example if your application requires 30 16 character messages use the stored message numbers between 90 and 120 Then you may use the GEQ instruction to turn on the DM bit anytime a stored message number of greater than or equal to 90 is moved to the Keypad If you wish to use the LEQ instruction you would enter those 30 messages using the first available stored message numbers of 1 through 30 To enter or change values in the PLC 5
58. of the Keypad Module Figure 6 4 shows the location of the receptacle and Figure 6 5 shows pin locations 6 5 Chapter 6 Operating Modes The Message Editor inside the module is accessed bv the kevboard when anv kev is depressed A prompt appears on the displav to begin the editing process The Message Editor contains commands to create edit and save single line 16 character alphanumeric messages Each message is assigned a message number for reference by the PLC or for future editing Figure 6 4 Keyboard Plug Receptacle Figure 6 5 Keyboard Plug Receptacle Pin Locations PIN1 KB CLOCK 2 KB DATA 4 GROUND 5 5 VOLTS 6 6 Entering Messages Chapter 6 Operating Modes The procedure for entering messages into the module is interactive Step 1 Remove power before plugging keyboard into the module Step 2 Depress any key to enter the edit mode Step 3 The module asks you for a message number EMT MESSAGE Lll Step 4 Type a message number 1 to 120 and depress ENTER or depress ENTER to edit message number displayed Step 5 If the number you entered has a message assigned to it the module displays that message for you to edit If the number is unassigned you get a blank display with the cursor in the left most position Step 6 Enter a message by typing the text you want up to 16 characters See the following page for a list of editing commands Step 7 Depress ENTER to complete
59. ols the numeric format for the destination word in the input image table and the SMD word in the output image table When BCD is selected the SMD and destination numbers are in BCD format When TRACKING is selected these values will follow the data type set by DIP switches 3 and 4 on switch bank 2 Note On Series B Revision D or earlier modules DIP switch 6 on switch bank 3 is not used and the format is always BCD 5 5 Chapter Objectives Kevpad Output Displav Chapter Operating Modes This chapter describes the operating modes of the Bulletin 2705 RediPANEL Kevpad Module Topics include e PLC output display of numeric and ASCII data and 16 character messages e Data entry decimal modes split display data entry e Message entering storing and editing e Destination entry The Keypad Modules vacuum fluorescent display shows 16 alphanumeric characters Figure 6 1 shows the features of the display Figure 6 1 Keypad Module Displa 6 1 Chapter 6 Operating Modes 6 2 Numeric Data Numeric data appears on the right hand side of the display in the eight right most character positions These positions display eight digits seven for negative numbers The decimal point if used does not require an additional character position ASCII Data Text starts on the left most element Text is displayed left to right Display Stored Message A maximum of 16 ASCII characters can be displayed when using a stor
60. pter 7 Programming Example Program The example program is shown below Each time a function kev is pressed on the RediPANEL its associated message is displaved This program also monitors the scanner s Enabled Device Fault bit M1 1 0 0 If communications are lost an alarm is activated If the communications d and Enabled MEO o 02 attempted and Enable Device Fault bits are fen ee MASKED EQUAL t ic la set to 1 activate the Source M1 1 0 2 alarm Mask 003 Compare 3 is If function key 1 is LLO E ae pressed bit 8 of input N MBUE word 0 T4 0 presetis l Hl I moved to the display 8 Source T4 0 PRE Dest Oii L pm When a new number is I 1 0 A MOV entered onto the Redi __ y LIMEN MOVE PANEL it is moved to fos I4 preset T4 0 kk Dest T4 0 PRE l A If function key 2 is ELO MOV pressed bit 9 of input i IL 2j MOVE pee word 0 RediPANEL IL s message 2 is trig 9 ource gered and displayed Dest 0 1 2 l L A 7 42 Chapter Objectives Using the Comm Fault LED Indicators Chapter Maintenance and Troubleshooting This chapter describes how to use the Comm Fault LED indicators and expl
61. rds Figure 7 8 PLC 5 15 and Sub Scanner Ladder Logic Example RediPANEL Address Profile Input Addresses Output Addresses N11 00 00 N11 07 15 8 Words N12 00 00 N12 07 15 8 Words Reserved for Sub Scanner Utility Functions Reserved for Sub Scanner Utility Functions N11 08 00 N11 11 15 4 Words N12 08 00 N12 11 15 4 Words 1 2 rack reserved for input image table of the 1 2 rack reserved for output image table of the keypad module module groups 0 3 keypad module module group 0 3 Keypad Module Moves T4 0 preset to F1 Push Button keypad data display Chapter 7 Programming PLC 2 Programming Example The following pages contain a PLC 2 example program which utilizes manv of the functions of the Kevpad Module Keep in mind that this program is simply an example your applications may or may not fit this structure The programming examples cover the following topics e Part A Examining accumulated values of a counter e Part B Changing and examining preset values of a counter e Part C Displaying a 16 character message e Part D Displaying a message and variable data simultaneously e Part E Destination bits for retrieval of data To operate the following program set the Keypad Module for BCD Mode Rack 1 3 4 Rack Configuration I O Group 0 Baud Rate 57 6K Enable Destination Bits Stored Message Split Display Disable Handshake Keyswitch Last State XT keyboard Note A table has been cons
62. re or liquids COMMUNICATIONS Remote I O Serial Data Link Communicates with the Allen Bradley PLC family via the following scanner modules Scanner Cat No PLC 1771 SN PLC 2 MINI 5 10 5 12 1772 SD20 PLC 2 30 1775 SAA B S5 PLC 3 1775 SR SR5 PLC 3 10 Integral PLC 5 15 5 25 5250 RS PLC 5 250 1747 SN SLC 5 02 D Scanner 1772 SD2 Rev 3 or later Communication Media Allen Bradley 1770 CD Belden Cable 9463 Chapter 9 Specifications 9 2 Baud Rates Selectable 230 4K baud 2500 ft 115 2K baud 5000 ft or 57 6K baud 10 000 ft Intercomnect 3 terminal plug and socket CONSTRUCTION NEMA Type 4X Approximate Weight 6 lbs 2 7 kg KEYBOARD COMPATIBILITY Series A IBM compatible XT style keyboard DIN 5 pin plug Series B or later IBM compatible AT XT style keyboard also Error Messages Appendix Appendix A This appendix describes the error messages displayed by the Keypad Module It also lists the display characters and their corresponding hexadecimal values as an aid The following list shows error messages and their explanations Items with the bullet e in the left margin are messages that refer to hardware or software faults that cannot be corrected by programming or changing the configuration settings SYSTEM ERROR A hardware failure has been detected on the Numeric Keypad Module EPROM CRC ERROR This error indicates that the power up diagnostics have detected a CRC
63. refer to the amount of I O the scanner can address To configure RediPANEL Modules with PLC controllers you need to know 1 The appropriate scanner module for the PLC controller This can be found in the next section titled Remote I O Architecture 2 The amount of I O the RediPANEL Module utilizes This is found in the section titled Calculating Rack Size on Page 4 7 3 The number of chassis and amount of I O that the scanner can accommodate This is found in the section titled Remote I O Configuration on Page 4 8 Chapter 4 Configuring the Bulletin 2705 Kevpad Modules with PLC Controllers Remote I O Architecture The following diagrams show applications using the Bulletin 2705 Kevpad Module in svstems using applicable PLC s and scanners Figure 4 1 Keypad Module with Mini PLC PLC 2 05 PLC 2 15 PLC 2 16 PLC 2 17 Scanner Mini PLC 2 Module 1771 SN 1771 scanner module must be mounted in rack with the PLC Figure 4 2 Keypad Module with PLC 2 20 or PLC 2 30 PLC 2 20 Scanner gt Module or PLC 2 30 1772 SD2 4 2 Chapter 4 Configuring the Bulletin 2705 Kevpad Module with PLC Controllers Remote I O Architecture continued PLC 3 10 Figure 4 3 Kevpad Module with PLC 3 Scanner Module 1775 S4A or 1775 S5 or 1775 S4B Figure 4 4 Keypad Module with PLC 3 10 Scanner Module 1775 SR or 1775 SR5 4 3 Chapter 4 Configuring the Bulletin 2705 Kevpad Modules wit
64. return to run mode Note Messages may also be entered stored on floppy disk and downloaded using a IBM PC or compatible with the Keypad Programming Software Catalog Number 2705 ND1 Refer to the Software User s Manual Catalog Number 2705 ND0023 for additional information Chapter Objectives Introduction Of Programming with the Kevpad Module Chapter Programming This chapter describes the process of creating a program for the Bulletin 2705 RediPANEL Kevpad module The detailed listing of the program example explains the ladder logic programming Applications for the Keypad Module are programmed in the Allen Bradley PLC controller The module itself has an on board message editor that can create and store up to 120 single line messages These messages are triggered from the program in the PLC All operations of the module inputting data displaving a PLC register value displaying a message and using the function keys correspond to fixed bits and word locations in the Input and Output Image Table of the PLC controller For example depressing a Function Key sends a 1 to its corresponding bit in the Input Image Table Depressing the ENTER key sends the number that the operator has entered through the numeric keypad to a fixed word location in the Input Image Table To display a register s contents you put that value into a word in the Output Image Table To display a message that is stored in the module you send i
65. roller via the Remote I O link You can install a 2705 module anywhere along that link To the PLC the Keypad Module looks like a hardwired remote I O rack The function keys and the LED output signals are programmed as discrete VO in the PLC Communication occurs through I O image table updates Figure 2 1 shows a typical application Figure 2 1 Typical RediPANEL Keypad Application 2705 RediPANEL Modules Combine Thumbwheels and Push Button Operator Stations with Remote I O ETA L Il IS 2705 RediPANELTM Message Displays Wiring Remote I O Modules Power Supply Keypad Module Thumbwheels O Node and Push Buttons Adapter Rack Pilot Lights Keypad 2 2 Operator Data Input Information Displav Chapter 2 Product Introduction The 2705 RediPANEL Keypad Module features a numeric keypad with DELETE ENTER decimal and polarity keys Using the keypad operators can enter up to eight 8 digits seven digits for signed numbers which appear on the right side of the 16 character display If an attempt is made to enter more than eight digits only the first eight are accepted If mistakes are made while entering data the display can be cleared one character at a time by depressing the DELETE key The data is not transmitted to the PLC until the ENTER key is depressed The DECIMAL POINT key allows operators to enter decimal numbers Six user definable function keys are also provided These keys can be used for
66. romagnetic Interference 3 1 3 2 Emergency Stop Switches 3 1 Enclosures NEMA 3 1 ENTER Key 6 5 1 2 Entering Messages 6 7 Editing 6 7 Editing Commands 6 8 Storing 6 7 Entering or Changing Data 7 7 EPROM CRC ERROR A 1 Error Messages A 1 BAD MSG NUMBER A 2 COMM SETUP ERR A 1 COMM START ERROR A 1 DATA TYPE ERROR A 1 EEPROM CRC ERROR A 2 EPROM CRC ERROR A 1 EXTERNAL RAM ERROR A 1 INTERNAL RAM ERR A 1 INT TIMER1 ERROR A 1 MESSAGE ERROR A 2 OVERFLOW A 1 PLC SENT NON BCD A 2 RACK CONFIG ERR A 1 SYSTEM ERROR A 1 WATCHDOG FAILURE A 2 EXTERNAL RAM ERROR A 1 F Fault Blinking 8 1 Indicator 8 1 LEDs 8 1 OFF 8 1 ON 8 1 Features Keypad Module 2 1 2 3 First I O Group 5 2 Format and Communication Parameters 5 1 5 4 Full Line Stored Message Displaying 7 6 Function Keys 7 25 Functions Keypad Module 2 1 G Grounding 3 1 Group First I O 5 2 H Handshake 2 4 54 7 28 Horizontal Mounting 3 2 Hexadecimal ASCII Values A 3 Image Tables I O 7 30 Indicator Fault 8 1 Information Display 2 3 Input and Output Image Tables 7 30 Integer Datatype 2 4 5 4 INTERNAL RAM ERR A 1 INT TIMER1 ERROR A 1 I O Image Tables 7 30 Symbols and Abbreviations 7 25 I O Remote Link 2 1 K Keyboard Style 5 5 Keypad Display 6 1 Keypad Layout 6 3 Keypad Modules 1 2 Applications 2 2 Configuring 4 1 Data Input 2 3 Features 2 1 2 3 Functions 2 1 Program
67. ters of ASCII data are displayed on the left side of the display and 8 digits of numeric data are displayed on the right side of the display This allows you to label numeric data with text The ASCII data can consist of either the first 8 characters of a stored message or 8 characters sent from the PLC controller The 8 digits of numeric data can represent either operator input from the keypad or 8 characters from the PLC controller The module can support three data type formats for numeric data binary BCD and integer The data type is selected via a DIP switch on the module Binary and BCD modes apply to the PLC 2 family of processors Data type formats for the PLC 3 and PLC 5 controllers can be either binary BCD or integer These data tvpe selections applv onlv to numeric values that are displaved 2705 RediPANEL Modules combine the functions of standard panel devices with the capabilities of a Remote I O Rack all in one package 2705 RediPANEL Modules connect to remote I O scanners and sub scanners just like remote I O racks This replaces large wire bundles with a single twin axial cable that connects the module to the programmable controller Up to 16 separate modules can be located on a single cable up to 10 000 feet away from the PLC The modules are addressed through DIP switch settings in the same manner as remote I O racks Additional DIP switches allow you to select the following features e Handshake Holds an input s
68. the input image table of the Keypad Module Depress the ENTER key again and rung 19 will get word 510 and take that numeric value and put it in the preset of counter 037 Note Word 510 is simply an arbitrary word To use destination bits you need a table of data to draw information from Our data base starts at word 510 for this example 7 24 Svmbols and Abbreviations for I O Image Tables Chapter 7 Programming The figures on the following pages show the input and output tables for the Keypad Module The following symbols and abbreviations appear in the input and output tables Refer to this list for identifying specific bits in the tables Represents a 0 No function is assigned for this bit location H Handshake bit Refer to page 7 28 for more information EN ENter bit This bit toggles when the ENTER key of the keypad module is depressed F1 F6 Function key bits These bits are input signals from the function keys When one of the function keys is depressed the corresponding bit will toggle L1 L6 LEDs located on each function key These bits are output signals that feedback to acknowledge a function key was depressed They can be used like pilot lights When bitz1 the LED is ON when bit 0 the LED is off DMDisplav Message This bit allows a 16 character stored message to be displayed or ASCII data No PLC numeric data when DM 1 Refer to Chapters 6 amp 7 for more information SMD Stored Mess
69. the message and save it in EEPROM Step 8 The module adds one to the message number then Step 9 Depress Control R any time to end the entry edit session Storing Messages go into EEPROM as you create them When you depress ENTER to complete a message the Module stores the message automatically No special procedures are needed Editing The message editing function is exactly the same as the message entry function When you have a message on the display any characters you type will overwrite the characters on the display Store the message when you have it to your liking by depressing ENTER 6 7 Chapter 6 Operating Modes Editing Commands 6 8 The editing commands are single kev strokes Left arrow lt Right arrow gt Down arrow J Up arrow T Control B Control D Control F Control R Control S ENTER ESC Control E Control I Move cursor one position to the left Move cursor one position to the right Decrement number of message to be created or edited Increment number of message to be created or edited Set message FLASH attribute Delete message and return to run mode Display number of free messages End edit and save current message then go to RUN mode Select message number Save message being edited and move on to the next message Cancel current edit and return to run mode Correct EEPROM CRC ERROR and return to run mode Initialize messages and
70. tructed to assign numeric values to word locations Word 477 0 Word 51121 D Word 51222 D Word 513 23 Word 510 500 Destination Bits D These numbers are used to call up stored messages from EEPROM in the Keypad Module Chapter 7 Programming PLC 2 Programming Example The example program below is explained on the following pages We present the program here and on the next page in its entirety for your reference Note Block transfer is only required when using the 1771 SN sub I Oscanner Block transfers allow communications between the sub scanner and PLC Block transfers are not required for anv other tvpe of scanner module BLOCKXFERREAD EN DATA ADDR 0030 17 MODULE ADDR 111 BLOCKLENGTH 14 FILE 0200 0215 BLOCK XFER WRITE DATA ADDR 0031 l MODULE ADDR 111 BLOCK LENGTH 14 FILE 0400 0415 FILE TO FILE MOVE COUNTER ADDR 0031 POSITION FILE LENGTH FILE A 0200 0215 FILE B 0300 0315 RATE PER SCAN 014 310 0500 L LL G 10 214 810 0513 LL L G 10 002 Chapter 7 Programming 10 11 12 13 14 15 16 17 l 540 0137 0412 eere iudei tet SO SOPA CTU 00 500 214 1 003 540 0515 043 l a e 5 AS az A PUT 00 002 003 540 310 0312 o137 l Tazza PUT 794 00 16 oo 210 0137 0412 pa pese made cic pe eec st PUT 4 16 500 214 540 310 540 Y Vi 2 2 1 A U 00 16 00 310
71. ts message number to a word in the Output Image Table The Input and Output Image Tables for the various combinations of Keypad Module features and rack size configurations are listed after the programming examples Chapter 7 Programming PLC 5 Programming Examples Svstem Configuration 7 2 The PLC 5 programming examples given on the following pages are based on the system configuration listed below Note System configuration may vary for different applications 1 A 1784 T45 Portable Terminal 2 A 1785 LT PLC 5 15 Processor Ser B Rev H Set for Scanner Mode 3 A 1771 P4 Power Supply 4 A 1771 A1B 4 slot chassis 5 A 2705 K11C1 RediPANEL Keypad Module Ser B Rev E The DIP switches on the Keypad Module have been set to A Rack 2 Module Group 0 B 57 6k Baud Rate C Destination Bits Enabled D Integer Data Type E Last Device F Rack Size 1 2 G Stored Message and Split Screen Enabled H Keyboard Style AT I Dest and SMD Format Tracking Prior to entering the sample program into the PLC 5 four messages were entered into the Keypad Module The messages are as follows MSG 001 C5 1 ACC MSG 002 C5 1 PRE MSG 003 16 CHARACTER MSG MSG 004 T4 0 PRE Chapter 7 Programming Input and Output Image Tables Figure 7 1 below shows the Input and Output Image Tables for the system configuration described on Page 2 Figure 7 1 Integer Mode 1 2 Ra
72. wer to clear the fault A connector plug is provided with each Keypad Module Wire the connector to the I O cable according to Figure 3 5 below Figure 3 5 Wiring Connections for the Communications Cable The Belden twin axial cable is the link that ties the Bulletin 2705 RediPANEL Modules to the Remote I O communications It is to be wired from the mating connector of the user s scanner module to the mating connector of the 2705 modules 2705 MODULE TWIN AXIAL CABLE MATING CONNECTOR Chapter Objectives Communications Chapter Configuring the Bulletin 2705 Kevpad Module with PLC Controllers This chapter lists compatibilitv considerations for operating the Bulletin 2705 RediPANEL Kevpad Module with programmable controllers via the remote I O link Topics also include the remote I O architecture and factors in calculating rack size Bulletin 2705 Keypad Modules communicate with all Allen Bradley programmable controllers that support the remote I O link The modules communicate with the PLC controllers through remote I O scanners and sub scanners The modules contain all of the necessary electronics to connect directly to the remote I O cable that originates from a scanner or sub scanner module The scanners have both physical and logical limitations The physical limitations refer to the number of separate chassis I O racks drive systems or RediPANEL Modules the scanner can accommodate The logical limitations
Download Pdf Manuals
Related Search
Related Contents
C2G 81933 Symantec™ Messaging Gateway 9.5 Command Line Reference Guide Practice questions for the Working with Numbers Test Whirlpool RBIOOPXY Oven User Manual G7717 取扱説明書.indd 47102V-MN - Amazon Web Services E-flite Carbon-Z Yak 54 3X 10535 TSBN-18 Possible-4 Copyright © All rights reserved.
Failed to retrieve file