        User Guide 4 wire Earth Resistance Tester Model GRT300
         Contents
1.  EN v1 1 08 13    Specifications          Measuring Ranges    Earth Resistance  0 20  0 200  0 200Q  0 2kQ                Earth Voltage  0 300V AC  40 to 500Hz   Accuracy Earth Resistance    2 rdg 3dgt   Earth Voltage    2 rdg 3dgt   Earth Resistance 0 20   0 010  Resolution 0 200   0 10  0 2000   10  0 2kQ   0 01kQ  Test Frequency 820Hz  Test Current 2mA       Temperature  amp  Humidity    Operating   0 to 50  C  32 to 122  F   lt 80 R H     Storage    10 to 60  C  14 to 140  F  S80 R H        Power Source    1 5V AA  x 8                   Dimensions 250 L  x 190 W  x 110 D mm  9 84x7 5x4 33      Weight Approx  1430g battery included   Fuse  0 1A 250V 5 x 20mm       8 GRT300 EU EN v1 1 08 13       Copyright    2013 FLIR Systems  Inc   All rights reserved including the right of reproduction in whole or in part in any form  1SO 9001 Certified    www extech com    9 GRT300 EU EN v1 1 08 13    
2. User Guide    EXTECH    INSTRUMENTS    4 wire Earth Resistance Tester  Model GRT300       Introduction       Congratulations on your purchase of Extech   s 4 Wire Earth Resistance Tester  The Model GRT300  has been designed and tested according to the IEC Publication 348  safety requirements for Electronic  Measuring Apparatus  EN 61010 1  EN 61326 1  EN 61557 1   EN 61557 5 and other safety  standards  Proper use and care of this meter will provide many years of reliable service     Safety Notes         Read the all safety information carefully before attempting to operate or service the meter      Use the meter only as specified in this manual  Otherwise  the protection provided by the meter  may be impaired      Rated environmental conditions       Indoor  amp  outdoor use      Installation Category IV 300V      Pollution Degree 2      Altitude up to 2000m      Relative Humidity 80  max      Ambient temperature 0 40  C     Observe the International Electrical Symbols listed below       2  Detector is protected throughout by double insulation or reinforced insulation     4 Warning   Risk of electric shock     A Caution   Refer to this manual before using the detector       Earth ground  terminal              Equipment complies with current EU directives     WARNING  To avoid electrical shock  do not touch the terminals during tests  Never apply Voltage higher than 300V across P1 and P2 terminals     2 GRT300 EU EN v1 1 08 13    Features       Microprocessor controlled with 
3. advanced safety features  Two line LCD display   Auto Ranging   Earth resistance testing with four ranges  0 20 0 200 0 2000 0 2kQ  Earth voltage measuring range of 0 300Vac   Automatic C spike check    Automatic P spike check    2 wire test   3 wire test   4 wire test   Auto power off   Data hold   Safety standard  EN 61010 1 CATIV 300V  EN 61326 1          Meter Description  1  C1 terminal   Black test lead connection   2  P1 terminal   Green test lead connection   3  P2 terminal   Yellow test lead connection   4  C2 terminal   Red test lead connection   5 Display 5  6  RcLED  7  RpLED 6  8 2 Wire button     9  3 Wire button  10  4 Wire button  11  ACV button  12  Power button  13  TEST STOP button BIO    3 GRT300 EU EN v1 1 08 13    Operation       Battery Voltage check  1  Press the  ON OFF  button  if  Battery Low  appears on the display  replace the batteries     Earth Voltage measurement    1  Connect the test leads as shown below     ES  A     OO A  P     C         1  Earth electrode  rod  under test  2  Test spike    2  Press the  ON OFF  button and wait for    Select Function    to appear on the display   3  Press the  ACV  button and then the  TEST STOP  button   4  The earth voltage will be displayed on the display     Note  When the earth voltage is more than 10V  errors in earth resistance measurements may  occur  Make sure that the indicated value is less than 10V     4 GRT300 EU EN v1 1 08 13    Earth Resistance measurement  Note  The measured results may be i
4. nfluenced by inductive or capacitive coupling if the test leads  are twisted or adjacent to each other  When connecting the Probes  keep the leads separated     Setup  Insert the Potential spike and the Current spike  if required  as deep as possible into the soil  The  distance between spikes must be 5 to 10 meters  16 to 32 feet      Four terminal earth resistance measurements    ES S H  A    Si       P     C  P          C         1  Earth electrode  rod  under test  2  Potential spike  3  Current spike    Three terminal earth resistance measurements    ES S H   0 T aca    O  e  IN  L    P         1  Earth electrode  rod  under test  2  Potential spike  3  Current spike    Two terminal earth resistance measurements    MAX   AC 300V  e        1 2   1  Earth electrode  rod  under test  2  Potential spike    5 GRT300 EU EN v1 1 08 13    Testing    Connect the test leads for 2  3 or 4 terminal testing    Press the ON OFF button and wait for the    Select Function    screen to appear   Press the  2P    3P  or  4P  button that agrees with the setup    Press  TEST STOP  button to begin the test     The meter will beep while the test is in progress  approximately 10 seconds  and then the  reading will appear on the lower line of the display     an BOT Ns    Notes    Re   amp   Rp  LED indications     Rc  No test current output  Check connections   Rp  If Rp is on and the display indicates     gt  2 kQ     the earth resistance is greater than 20000   If  in  4P  mode  the display sh
5. ows  Vp Error   short circuit C1 black  and P1 green      Measurement Considerations    2 terminal testing of earth resistance is appropriate for most general purpose testing in normally  conductive soil  But  2 terminal measurements include test lead and contact resistance in the  measurement and the result will be a reading slightly higher than the true earth resistance  When  measured results are higher than desired or if measurement directives require multi terminal  techniques  switch to the 3 or 4 terminal techniques as needed     6 GRT300 EU EN v1 1 08 13    Maintenance       1  Rear cover  2  Battery  3  Fuse       Fuse Replacement  1  Disconnect the test leads from the instrument   2  Remove the rear cover by removing two screws     3  Remove and replace the fuse with the new one of the same value and size 0 1A 250V  5 x  20mm     4  Replace and secure the rear cover     Battery replacement  When  Battery Low  appears on the display  replace the batteries   1  Disconnect the test leads from the instrument and remove the rear cover and the batteries   2  The tester s battery is situated under the tester   3  Replace with eight 1 5V AA light batteries  taking care to observe correct polarity   4  Reinstall battery holder and the battery cover     Cleaning And Storage  WARNING  To avoid electrical shock or damage to the meter  do not get water inside the case     Periodically wipe the case with a damp cloth and detergent  do not use abrasives or solvents     7 GRT300 EU
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
ROUTE ADRESSE® Version 2.1  CN51 FAQ  - Honeywell Partner Concierge  MANUAL DE USUARIO - Ayudas Dinámicas  3410, 3440 et 3450  Sept secrets pour une performance optimale!    iP-55取扱説明書  Donnez - - Aix Marseille Université  Toastmaster ICM15 User's Manual  User Manual    Copyright © All rights reserved. 