        Flow-temperature controller for heating / cooling
         Contents
1.     If all the switching times are    A    deleted  or if the time is lost  power failure reserve is    exhausted  control operation will use setpoints Xs1 and Xs3     1  Is shown only if at least one additional switching command is entered     2  The fill level of the tank is indicated    7000927003 R4    on the bar chart for the control offset     Sauter Components    Manual  gt       View actual values Xi                         Actual value 1    Actual value 2    Actual value 3    Actual value 4    Actual value 5 1     Actual value 6 1       Averaged outdoor  temperature    B09365    View control deviations Xw                   Control deviation 2     Controller 1  PI 1       Controller 2  PI 2     Controller 3  PI 3     Controller 4  PI 4       Controller 5  PI 5     B09366a    1  Inputs for Ni1000 only  display      C     2  Depends on the model  sometimes hidden     7000927003 R4    1 21    Sauter Components    1 22    View and alter setpoints                            Manual    c X X       Setpoint for    Controller 1  PI 1     Setpoint 1    Setpoint 2       Values apply for heating   gt  and cooling modes       Controller 2  PI 2     Setpoint 1    Setpoint 2          Controller 5  PI 5     Setpoint          Controller 1  PI 1     Frost setpoint          Dewpoint limiter  PI 4     Dewpoint interval                  Calculated dewpoint    Calculated setpoints    Based on heating curve      Controller 1  PI 1     Controller 2  PI 2     Dewpoint limiter  PI 4       Auxi
2.    Flow temperature controller  for heating   cooling    User s Manual  part 1  RDT 300 F001    7000927003 R4    7000927003 R4 Sauter Components    About these operating instructions    Together with the RDT 300 controller for ventilation and air conditioning  you receive two  documents    Part 1  7000927  of the Operating Instructions  which contains all the necessary information  on manual and automatic modes  This part is intended for the user    Part 2  7000928  of the Operating Instructions  which describes how to put the controller  into operation for the first time for specialists  This Part also contains further information for  project engineers and interested users     The operating procedures have been described in this manual with the aid of illustrations   When entering numerical values  all positions must be filled  including preceding noughts     Example  20 5    C Enter  0205    In manual and automatic modes  incomplete entries are aborted automatically after two  minutes  The value that you have already entered will remain unchanged  Entries are ac   cepted only if they are in the permissible range  or if they are restricted to that range   The position requiring an input flashes in the display  user prompting  and it is marked by  an arrow in this manual     Follow the various input stations  press the corresponding keys and observe the result on  the display     7000927003 R4 Sauter Components    Table of contents    General information ae nen 3  Notes on s
3.   40 0  C    Final   25 0   60 0  C    Changeover mode 2     Release value for heating       Increase   A 220 1 0    10 0  C                     Differential value HK 1 0        hysteresis  for cooling                 30 0   150 0  C  0 0   200 0    0 0   100 0 r H   0 0   20 0g kg  0 0   100kJ kg   4999    4999                  Mininum operating period   in days        Eu 4               Time of interrogation MT  0   9 days       CT   00 00   23 59       Software version       Device type                B09370a    Floor drying function    When this function has been activated in service mode  heating begins with the setpoint  entered at ST  starting temperature     In the following night at 02 00 hrs  the setpoint is raised by the value set using Er     This daily increase is carried out as long as the end temperature that was set using End has  been reached  The floor drying function is then concluded     7000927003 R4 Sauter Components    1 26    Manual  gt       View and alter limit values                   Limit value 1    Switching point      Delay    Follow up    Limit value 2    Switching point      Delay    Follow up    Limit value 3    Switching point      Delay    Follow up    Limit value 4    Switching point      Delay    Follow up    Changeover    Switching point      Delay      Follow up    7000927003 R4        Enter switching point                             30 0   150 0  C  Xw  0 0   180 0   C  0 0   100 0    r H   0 0   20 0g kg  0 0   100kJ kg   4999    499
4.   View control offset Xw       Control action  min  or max  limitation   open close on command  for switching outputs    Operating modes              Control  Automatic          Manual             Service level          Enter control parameters    B09792a    7000927003 R4 Sauter Components    1 6    Display for control deviation Xw                                                             ap  lt   AA a Definition     Control deviation   actual value     setpoint  Xw   Xi     Xs  ST  B06970  Positive control deviation Negative control deviation  oP 44   r  Control deviation Xw Unit of meas  Control deviation Xw     gt   lt   lt   1 5 11 5 30 75 15 0   C  1 5   1 5  3 0  7 5  15 0  1 0 11 0 2 0 5 0 10 0       r H   kJ kg    1 0   1 0  2 0  5 0  10 0  0 2 10 2 0 4 1 0 2 0 g kg  0 2    0 2  0 4  1 0  2 0  50  50 100 250 500   1   50    50  100  250  500                B06971a    1  Free unit of measurement  with respect to displayed range 0   4999     7000927003 R4 Sauter Components    Examples of displays        automatic mode       actual value Xi3 with unit of  measurement       Xw display        Manual mode       Input for control parameters      Reset time for controller 1       View Xw        Service level      Upper setpoint limit 50 0   C        Service level       Minimum limitation Y2  ready for the input of the first  position    7000927003 R4       e       gt       e    leevee      A    A       B06975       B06976       B06977a       B06978a    Sauter Components    
5.  only    mode   Setpoints for cooling  Xs3 and Xs4  fixed as per the upper input  limit for the    cooling    setpoint that was set in service mode        In    cooling only    mode   Setpoints for heating  Xs1 and Xs2  fixed at the frost protection  setpoint that was set in service mode        In    OFF    mode   Xs1   Xs2   XSF  frost protection   Xs3   Xs4 as per the upper input limit for the    cooling    setpoint     2  Depends on the model  sometimes hidden     7000927003 R4 Sauter Components    1 12 Auto         View positioning signals and operating mode of the time channel and the relays                            Positioning signal Y1  Positioning signal Y2    Output variable Y3    weg  gt  1   Calcul  positioning signals    Controller 1  PI 1       Controller 2  PI 2       Controller 3  PI 3  auxiliary  controller for cascade       Controller 4  limiter  PI 4       Controller 5  PI 5                 Operating mode        Time channel To Display   4   Manual  continuously On    Relay 1  Vv   Manual  continuously Off for TO    Relay 2  EN   Automatic  weekly program     Relay 3  A  On    Relay 4 Rel  1   6  v   Off    Relay 5    Relay 6    B09357b       1  Depends on the model  sometimes hidden     7000927003 R4 Sauter Components    Auto    1 13    View date and time                                  aN CJ  O      Day of week  time  active Display    setpoint for controller 1 and   Day of week    operating mode time and active  setpoint for  controller 1   operating m
6.  the entries in the right order        Set the mode switch to    Automatic     The controller will start with the default values for the  setpoints  P band  proportional band  etc        Watch the installation  if necessary  match the parameters to the specific values for the  installation     Reaction in the event of a power failure    All data and parameters are captive  In the event of a power failure  the continuous outputs  drop to 0 Volt  the relay outputs cut out and the display goes blank  When power has been  restored  the controller re starts with the stored parameters  This also applies for lengthy  power failures     7000927003 R4 Sauter Components    1 4    Front view of controller       Service and adjustment keys     o      9  Numerical keys    PAR       Control parameters    SERV  Service    Clear    PRO        Weekly programme    i       Time  date       Information centre                7000927003 R4       AN  ol       memory         Flap holds instructions Memory  option  Mode switch      gt  Manual mode  CY Automatic mode   O Service level    User keys with  function keys    Setpoint  Actual value  I    Control deviation  Positioning signal  Input   Limit   Date and time    Forwards    Backwards and  minus sign    KBH          B09791    Sauter Components    The information centre    Day code       Enter value with preceding mathematical sign and unit  and time                                                                                  Parameters      
7. 7000927003 R4 Sauter Components    F  RD     Auto   1 9    Automatic mode          Control based on the setpoint    7000927003 R4 Sauter Components    1 10 Auto         View actual values Xi                                  Actual value 1    Actual value 2    Actual value 3    Actual value 4      Actual value 5     4    Actual value 6        Averaged outdoor  temperature    B09354    View control deviations Xw                            Control deviation       Controller 1  PI 1       Controller 2  PI 2     Controller 3  PI 3     Controller 4  PI 4       Controller 5  PI 5     B09355a    1  Input Ni1000 only   2  Depends on the model  sometimes hidden     7000927003 R4 Sauter Components    Auto         View and alter setpoints                            Setpoint for     Controller 1  PI 1     Setpoint 1    Setpoint 2    Controller 2  PI 2     Setpoint 1    Setpoint 2    2  Controller 5  PI 5       Setpoint    Controller 1  PI 1     Frost setpoint    Dewpoint limiter  PI 4     Dewpoint interval 1       Calculated dewpoint       Press button to alter setpoint    1 11                                                    1    r H      0 1 g kg       1 kJ kg   Free unit of measu   rement  dependent  on range    Calculated setpoints    Based on heating curve      Controller 1  PI 1     Controller 2  PI 2     Dewpoint limiter  PI 4       Auxiliary controller for  cascade controller       BO9356b    1  The dew point interval can be changed only in the manual level         In    heating
8. 9                                     Enter time                            0   9999s          By default inactive   OFF                             gt  Mode 1                   B09371c    Sauter Components    Manual    gt  1 27    Diagram of heating characteristic    The heating characteristic determines the setpoint of the secondary supply temperature as  a function of the outside temperature  The heating characteristic is determined in the main  by the base point TI       Xg4  and the slope                                                           Slope  2 5 0 3 5 4 0  es   3  5   4  100    C  1 8 90   l  1 6 80  1 4  70    1 2 3  2  2 1 0 60  gt   2 xe   7  iL  0 8 50  0 6    40  0 4  30  aay ya    5   20  15  10  5 0 5 10 15     C  Outside temp  Fr 5  Ad B01916    Spread of heating characteristics for Tj   20   C and curvature factor   0 5    The following applies  small heating surfaces require higher supply temperatures and large  heating surfaces require lower supply temperatures in order to be able to provide a certain  heating output     Recommended values for slopes     Hot water radiator heating 1 4  Low temperature heating 1 0  Underfloor heating 0 6    After the base point or the slope has been amended  the building  and possibly the heating  system  needs time to adapt itself to the new value  For this reason  no more than one ad   justment per day should be made     7000927003 R4 Sauter Components    1 28 Manual    gt     Printed in Switzerland   Right of amen
9. ar             Switchover from summer to  winter time   1h  Wi 10          Switchover from winter to  summer time   1h    So 3                   January  February  March  April   May  June   July  August  September  October  November  December       Flashing  hr x  BRA Ann is exhausted   e time will be lost   3 1 2 00 This status is signalled by the flashing    display   Wednesday 12 00     Time dependent switching operations B09362a  will only be executed after the time has   been corrected     1  The automatic changeover between summer and winter time occurs on the last Sunday  of the month that is entered  between 02 00 and 03 00   To deactivate the changeover from summer to winter time  enter identical months such  as WiSo   3 and SoWi   3     7000927003 R4 Sauter Components    1 20    View and alter week program                      Manual  gt                                                                                 E A He Memory diese   Setpoint switchover for       Controller 1  PI 1  Xs1  0 06 00 Delete displaved    Controller 2  PI 2  xs3  0 06 00 Swilcting tine      Controller 1  PI 1  Xs2  022 00 AN    Controller 2  PI 2  Xs4  0 22 00    Time channel TO    Tow  06 00     TOA  0 22 00      OL  AG  Note sequence   Setpoints 1   4  Time channel    On    Off  B09364a  Day of the week  1   Monday 5   Friday  2   Tuesday 6   Saturday  3  Wednesday 7   Sunday  4   Thursday 0   daily  The daily switching commands  0     are not executed on special days  e g  7__ __  
10. dment reserved    O Fr  Sauter AG  CH 4016 Basel   7000927003 R4 Sauter Components    
11. liary controller for  cascade controller        In    heating only    mode               30 0   150 0  C  0 0   100 0    r H   0 0   20 0g kg  0 0   100kJ kg   4999    4999    Setpoints for cooling  Xs3 and Xs4  fixed as per the upper input  limit for the    cooling    setpoint that was set in service mode         In    cooling only    mode     Setpoints for heating  Xs1 and Xs2  fixed at the frost protection    setpoint that was set in service mode       In    OFF    mode   Xs1   Xs2   XSF  frost protection     Xs3   Xs4 as per the upper input limit for the    cooling    setpoint     7000927003 R4    B09367b    Sauter Components    Manual     gt     1 23    View and alter positioning signals  view and alter operating mode  of the time channel and the relays                            Positioning signal Y1  Positioning signal Y2    Output variable Y3    1     Calcul  positioning signals    Controller 1  PI 1       Controller 2  PI 2       Controller 3  PI 3  auxil   controller for cascade       Controller 4   limiter  PI 4       Controller 5  PI 5     Operating mode    Time channel To      Relay 1    Relay 2    Relay 3    Relay 4    Relay 5      Relay 6                   Operating mode   Automatic  weekly program   Manual  continuously On       gt  Relay  Manual  continuously Off      B09368a    1  Depends on the model  sometimes hidden     2  Setting for TO    7000927003 R4    is adopted in automatic mode     Sauter Components    1 24 Manual    gt     View and alter control 
12. nual         Manual mode      In this mode  you can         set the positioning signals between 0   100        alter the setpoints  and       set the control parameters    7000927003 R4 Sauter Components    1 18 Manual      gt     View date  time and months for summertime wintertime change over                      Day of week  time  active Display    setpoint for controller 1 Day of week    and operating mode time and active  setpoint for  controller 1   operating mode       Day   month date          Year          Switchover from summer  to winter time   1h              Switchover from winter  to summer time   1h 1                 Flashing   3 12 00    B09363a    If the power failure reserve is exhausted  the time will be lost   This status is signalled by the flashing display     Wednesday 12 00   Time dependent switching operations  will only be executed after the time has been corrected     1  The automatic changeover between summer and winter time occurs on the last Sunday  of the month that is entered  between 02 00 and 03 00     7000927003 R4 Sauter Components    Manual   gt   gt  1 19    Set time  date and months for automatic summertime wintertime change over       SO  O SET  E  8  Enter time    FEER Input  Day of week  time  active    setpoint for controller 1 and  operating mode 00 00   23 59    Enter time and month     ci  ER SE Input  Cl 4 So  Day   month date Date i    Day  01   31  Year Yea Month  01   12                                                 Enter ye
13. ode   Day   month date          Year          Switchover from summer  to winter time   1h             Switchover from winter 1   to summer time   1h                 Flashing   3 12 00    B09359a    If the power failure reserve is exhausted  the  time will be lost    This status is signalled by the flashing display    Wednesday 12 00   Time dependent switching  operations will only be executed after the time  has been corrected     1  The automatic changeover between summer and winter time occurs on the last Sunday  of the month that is entered  between 02 00 and 03 00     7000927003 R4 Sauter Components    1 14 Auto         Change operating mode    Display   EH ER Day of week     time and active                               setpoint for          controller 1  1       Heating and cooling           Alter operating mode               Heating only    Cooling only      Off mode with frost  monitoring    B09360    7000927003 R4 Sauter Components    Auto         View limit values                            Limit value 1    Switching point      Delay    Follow up    Limit value 2    Switching point      Delay    Follow up    Limit value 3    Switching point      Delay    Follow up    Limit value 4    Switching point      Delay    Follow up    Changeover    Switching point      Delay      Follow up       1 15    Functions and values vary according to the model  so some might not be shown     7000927003 R4    Sauter Components    1 16 Auto         7000927003 R4 Sauter Components    Ma
14. parameters    aro PAR    E   6    Controller 1  PI 1     Proportional band                                                         Reset time  Controller 2  PI 2     250 0  C    Proportional band    200 0       100 0 r H     Reset time    20 0g kg    100kJ kg  Auxil  contr  3  PI 3  cascade  999    Proportional band  Tn     Reset time 0   9990s          Controller 4  PI 4     Proportional band               Reset time       Controller 5  PI 5     Proportional band                  Reset time       Auxil  contr  3  PI3  cascade                                     Lower setpoint limit 14 0  C     Upper setpoint limit    20 0  C  30 0   150 0  C  0 0   200 0     Command module 1 0 0   100 0 r H      Start of shift 0 0   20 0g kg  0 0   100kyJ kg     End of shift  4999    4999  Ws       Amount of shift i 0 0   150 0  C  0 0   200 0  C  0 0   100 0 r H    Command module 2 0 0   g kg            Start of shift 0 0   100 0kJ kg  SL  0 1   5 0               End of shift            Amount of shift       Heating curve 1                    Period of time for averaged  outdoor temperature          B09369b    Value depend depends on the model  sometimes hidden   1  Diagram of heating characteristic  see page 27     7000927003 R4 Sauter Components    Manual   gt   gt  1 25    View and alter control parameters  view software version                                  Dry flooring function     Starting temperature ST 15 0    Final temperature End 25 0    Increase per day Er 5 0       ST   10 0 
15. tarting operation    ennnen EEE RR RR RAR Rn 3  Recommended proced  fen  nnnse een 3  Reaction in the event of a power failUre                ccccccecceeeeeeeeeeeeeeeeeeeeeeeaaaaaeeeeeeeeeeeeeeeeeaaaaaees 3  Front View Of contr  ller   2 hen 4  The information centre u  aha ach 5  Display forcontroldeviati  N Wins nnd Buben 6  Examplesof displays au ue aa aa ted tstidadslsdiateiaveepieeamyetiees 7  v  N   Automatic mode 1 outpeanm eacmmemenenthema ante menn entmananentagnemeeneece 9  View actual VAISS Riesterrente 10  View control deviations XW     kn kenne 10  View and alter setp   IS 25 35  sbysstesnsss  keva beses e e E E E E ea rs reneeeah wines 11  View positioning signals and operating mode of the time channel and the relays               12  VIEW date and IME a E NN SNR 13  Change operating  Node za  ne m as Aa RNA ERAN ee ae hie 14  MIEW HMI Valle Se Masse voce ye ee RR ERS EHER era 15  Manual mede       Sidancscnaucsnndvnden aen a RTR 17  View date  time and months for summertime wintertime change over              cccceeeeeeeeeeees 18  Set time  date and months for automatic summertime wintertime change over                  19  View and  aller week progta Mi sipini en 20  VIEW KOB Fe TAVAS UTETES EA AAA A E E 21  View control deviations XW sissnmmsssssssrrrsrrrenenenersarrrrnnnnnnrrrarrrrnnnnn ere EEEE Ennn EnEn rr ran anna 21  View and aller SetDointS  iisen ae 22  View and alter positioning signals  view and alter operating mode of the time channel and   the rela
16. ys ionnann bensen   ar E a Eaa ar Eaa a e E anden apinain 23  View and alter control parameters sn en 24  View and alter control parameters  view software version s  smmeessrrrerrrrrrerrrrrrnrrrrrrrrrrrrer rr ren 25  View and aller limit values e ra rn Hrn 26  Diagram of heating characteristic       u   uun  00er 27    7000927003 R4 Sauter Components    7000927003 R4 Sauter Components    General information    Notes on starting operation    As soon as the RDT 300 controller for ventilation and air conditioning has been switched  on  it is ready for operation    Please make sure that the voltage supply is correct    version F001   230 VAC    The stored factory settings  default settings  for the parameters on the control model permit  immediate control operations    In order to make these instructions easier to understand  they are specially identified by a  grey background at the relevant points  these should be understood as examples  and they  are applicable to the normal operating mode of control model 0     Recommended procedure        Familiarise yourself with the controller s operating methods  Refer to the description of  the front view and the    information centre           Depending on the technical remit  such as the flow diagram   enter the appropriate con   figuration values in the service level  The measured value inputs must also be coded with  the help of jumpers  All the other entries can be made from the keypad  In the service  level  it is advisable to make
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
Bulldog - PAR-KY  SERVICE MANUAL AND PARTSLIST - Masini de cusut casnice  KX-TDA15/KX-TDA30 Modello KX-TDA100/KX  EC Declaration of Conformity We GOOD WILL INSTRUMENT CO  FOM 320  PKZIP 6.0 Command Line User`s Manual  NADO SINCRONIZADO      1) Electricity Licensing User Manual    Copyright © All rights reserved. 