        Emergency Switch Device (ESD)/ Contacts port adapter card
         Contents
1.  s connector    to use the Shut down  RSD  function it is necessary to remove the  jumper of UPS   s EPO connector     Note  see the ESD RSD configuration on the user   s manual     If one of the previous operations is not applied the EPO and or RSD  function do not determine the switching off of the UPS        Remove the two screws that hold the expansion slot cover in place   Insert the card  as it is    Hot Swappable    it can be inserted or removed even  while the UPS is operating        Close the slot with the cover supplied in the kit and fasten it in place using the    two screws that were removed previously     16    OMNU030NPB    
2. Emergency Switch Device   ESD   Contacts port    adapter card    Installation and operation manual      ENGLISH      Congratulations for purchasing our ESD Porta a Contatti adapter  card    This manual will guide you in installing the card and configuring it  correctly  We recommend that you keep it together with the UPS    manual for future consultation purposes     10      ENGLISH      ENGLISH    1 PRESENTATION    KIT CONTENTS     ESD Contacts port adapter card     Metal slot cover      This manual    DESCRIPTION AND CHARACTERISTICS    The ESD Contacts port card is installed in the appropriate slot on the rear of the  UPS  The card has two removable terminal boards  One of these terminal  boards has the ESD signal  UPS Emergency ShutDown  and the RSD signal   Remote ShutDown   Other signals can also be associated with the card  such  as Battery Working  Bypass  Alarm and Battery Low  through zero potential  switchover or normally open contacts     WARNING  the contacts inside the board capable of carrying a max   current of 3A at 250Vac       222                   An  Do PO ON       VARZRDNZRZ    J1       ANW A  I AL    Z       Figure 1  Allocation of setting points and the terminal boards      ENGLISH      2 Ji TERMINAL BOARD   DESCRIPTION AND CONFIGURATION    EMERGENCY INPUT  ESD     The Emergency input  ESD  allows the immediate and safe shutdown of the  UPS in any emergency situation    With the two terminals on the ESD input connected together  with wire strap  or  eme
3. n    Warning  Configuration jumpers must never be connected across adjacent SW   s  referring to  Figure 3  the jumpers must not be positioned horizontally   Moreover  the same relay must not  be associated with two different signals     14         ENGLISH      CONFIGURATION OF DELAY TIMES ON THE CONTACTS PORT    Another configuration inserts a relay switching delay of approximately 8s from  the activation of the command signal  The delay may be useful for filtering brief  unwanted signals such as sudden mains blackouts  switching to bypass due to  distorting loads  etc  The default configuration and the association between the  signals and jumpers are shown in Table 2  The delay is active when the jumper  is closed     CLOSED OPEN    nn an    2 pin Jumper  JP1   JP4   graphic example of various setting possibilities                                  Associated Default  Command Jumper Configuration  Battery Working JP1 Closed  Battery Low JP2 Open  Bypass JP3 Open  Alarm JP4 Open  Table 2    N B  The activation of the delay effects both the closing and opening of the relay  as shown in    the figure   Command      Relay contact        T T1      ENGLISH      4 INSTALLING THE CARD  Only for installation on UPS without ESD    the UPS will shutdown immediately if the card is installed and the J1  female connector is not inserted     Only for installation on UPS with ESD    to use the EPO function it is necessary remove the J1 connector   s  jumper of this board and leave the UPS  
4. rgency button with N C  contact  etc    the UPS operates normally  If the  connection is opened  the UPS will shutdown immediately and cannot be  switched on until the connection is closed again     INSTALLATION  to use the ESD feature  remove the jumper from the terminal board and  replace it with one or more NC contacts connected in series   e g  emergency buttons      J1  ae  317     2 D N C  Contact    Mi     WARNING  If the strap is removed when the card is inserted in the UPS  the latter  if on  will be  shutdown     REMOTE SHUTDOWN INPUT  RSD     This allows you to shutdown the UPS with a remote command such as an  external control panel  a PLC output contact  a power switch on an electric  control panel  etc    Connecting the two terminals at the RSD inlet  the UPS is shut down  If the  connection is re opened  the UPS remains off and must be switched on again  manually  if the command was given when mains power was off and the UPS is  programmed to automatically power up after a remote shutdown command  the  UPS will power up automatically when mains power returns      INSTALLATION  to use the RSD feature  connect one or more NO contacts together in parallel   e g  external control panel      J1    aS  3    N O  Contact  2 IS  IN       HK    IMPORTANT  When this configuration is used  the strap between terminals 3 and 4 must  remain connected     12      ENGLISH      POWER SUPPLY OUTPUT    The J1 terminal board has a 12Vdc power supply that can be used by the user  p
5. rovided no more than the 80mA available is drawn     J1      IO   3 Y  n   2      IO  estos    3 DESCRIPTION AND CONFIGURATION OF THE  CONTACTS PORT SECTION    CONFIGURATION OF THE CONTACTS PORT SECTION    The Bypass  Battery Working  Battery Low and Alarm signals can be associated  with the four relays on the card  two with switchover contacts  SC  and two with  an  N O   contact      C  w       DW BUND 100                Figure 2  Contacts on the internal relays and how they are connected to the connector      ENGLISH      It is also possible to have the same signal associated with several contacts  as  shown in Table 1  This configuration is achieved by moving the straps on  jumpers SW1     SW8  The default configuration of the jumpers is shown in  Figure 3  Refer to Table 1 for indications on how to modify the initial  configuration     E g  to associate the    Battery Low    signal with relay RL1  insert the strap between jumper 1 and  jumper 2 in the SW2 column  N B  In this case  column SW1 must be left free                          VAN  SsSSsSsss s s  INS RAANG  1 1  2 2  3 3  d ANN  Sett  RL1     Sett  RL4  Sett  RL2 Sett  RL3  Figure 3  Command RL1 N O   RL2 SC   RL3 N O   RL4 SC    Battery Working SW1 2 3  SW3 2 3  SW5 2 3  SW7 2 3   Default  Battery Low SW2 1 2  SWA 1 2  SW6 1 2  SW8 1 2   Default  Alarm SW2 2 3  SW4 2 3  SW6 2 3  SW8 2 3   Default  Bypass SW1 1 2  SW3 1 2  SW5 1 2  SW7 1 2   Default                   Table 1  Signal relay association configuratio
    