1. Zennio KNX IP Router provides a web interface for consulting the device configuration activating the programming mode or updating the firmware The web interface can be accessed through port 8080 of the IP address of the device For example if the IP address is 192 168 1 222 d http 192 168 1 222 8080 The following URL will be equivalent d http KNX IPrt xxxxxx 8080 where xxxxxx refers to the last six digits of the MAC address of the device The IP address of the device can be easily obtained in ETS as long as the device belongs to the same LAN segment than the PC On the other hand the MAC address must be printed on the cover of the device Figure 8 shows the information displayed in the web interface http www zennio com Technical Support http zennioenglish zendesk com 15 Zennio Zennio KNX IP Router Zennio Zennio KNX IP Router Device is currently running in normal mode Status normal operation Device Info DHCP true IP Address 192 168 27 190 Subnet Mask 299 205 255 0 Gateway 192 168 27 1 DNS 192 168 27 1 Update Http Port 8080 MAC Address DO 76 50 00 01 2F KNX Serial 72 4E 2A4 00 08 00 Hostname KNX IP router Description KNX IP router UDN uuid 1f6b0c5e 1f6b 0c3a 8faf d0765000012f Hardware Version 1 1 Sofware Version 1 01 ETS Version 1 0 Program Figure 8 Web interface device information 2 5 1 FIRMWARE UPDATE The Update section of the web inter
2. Pass all telegrams d Pass physical telegrams d Pass group telegrams Please refer to section 3 5 for the parameterisation in ETS of the manual function and for a detailed description of the different options 2 4 1 HARD RESET TO FACTORY DEFAULTS The manual function button permits performing a hard reset of the device which will set it back to the factory default state including the initial individual address The default parameters of the device are d Physical address 15 15 0 d Host name KNX IP router see section 3 2 d DHCP activated http www zennio com Technical Support http zennioenglish zendesk com 14 Zennio Zennio KNX IP Router d KNX Multicast address 224 0 23 12 see section 3 4 d Transmit all for group telegrams and physical telegrams These are the steps to restore the factory settings d Press the manual function button for at least 15 seconds The main line KNX line and group filter state LEDs will light in orange or red if they were not green previously and the physical address filter state LED will turn yellow or orange if it was not green previously d Release the manual function button and press it again for about 5 seconds The device will be then automatically reset e Keep in mind that before entering the reset mode 15s press the device will first enter the manual function mode which will also make some LEDs change 2 5 WEB INTERFACE
3. Zennio Passion for KNX innovation 8 Zennio KNX IP ROUTER KNX ZSY IP ROU Bus Stat IP TP Traffic O O i sono A Function Led v v Prog OD J Zennio KNX IP Router KNX IP Line Area Coupler ZSY IP ROU lt D zZ lt gt oc LU Y gt Application Program version 1 0 User Manual version 1 0 _a www zennio com Zennio Zennio KNX IP Router CONTENTS Eeer H NR o A E A In 3 1 1 e 3 1 2 Pe a AP O 5 1 3 Zennio KNX IP Router as a Programmer 6 1 3 1 Parallel Downloads 6 Lo ico A o o En 7 2 EE 8 2 1 Hne or Area COUP E 8 2 2 MOS CAG EE ebe 9 2 3 LEDINO AU OS ado 11 2 4 Manual Function Button cccccccnconnncccnnnnnnnnnnnnonnnnnnnnnonnnnnnnnnnnnnonnnnnrnnnnnnnnnnnnaeninss 14 2 4 1 Hard Reset to Factory Defaults cccooonccnconoccnnonaconnnnononnnonaronnnnaronncnancnnnnnnoss 14 2 5 WY SNCS re uns odia 15 2 5 1 A An 16 3 Elo Partametetis Te e rondas pio pio iia pias 18 3 1 DOTA alae MISA ON ie 19 3 2 Genera noria dc 20 3 3 E E on na 20 3 4 WC Malica e ans aa EN 3 5 Mc a 22 3 6 ae EE 23 3 7 B 25 http www zennio com Technical Support http zennioenglish zendesk com 2 Zennio Zennio KNX IP Router 1 INTRODUCTION 1 1 ZENNIO KNX IP ROUTER a Se Zennio KNX IP ROUTER KNX ZSY IP ROU Bus Stat O Q Traff 210 ie SH nO Function Led v v Prog OD Figure 1 Zennio KNX IP R
4. and Ethernet 7 cables as well as the external power 6 must be connected After the connection the device can be conveniently mounted on the DIN rail by the usual procedure The programming button 11 shown in Figure 3 may be pressed to set Zennio KNX IP Router in programming mode After a short press the programming LED 5 will light in red The behaviour of the additional LEDs and the manual function button will be described In section 2 4 For detailed information about the technical features of the device as well as on security and installation procedures please refer to the device Datasheet bundled within the original packaging of the device and also available at http www zennio com http www zennio com Technical Support http zennioenglish zendesk com 5 Zennio Zennio KNX IP Router 1 3 ZENNIO KNX IP ROUTER AS A PROGRAMMER Zennio KNX IP Router can be used in ETS as a programming interface In addition to an IP address this device must be assigned a KNX individual address for this purpose Note to detect the device as a programmer in ETS it needs to be powered up and connected to the same network as the PC as well as to a TP line If the latter line is disconnected the device will no longer be visible as a programmer 1 3 1 PARALLEL DOWNLOADS ETS offers the option to perform multiple parallel downloads from a single project This option is only available for connections via a KNX IP router
5. downloading the updated filter table to the line coupler Example f the line coupler has been parameterised to filter group addresses from both lines when it receives a telegram from the mainline destined to a group address e g 2 5 13 it will check that there is a device in the secondary line with objects that have been assigned such group address or that such address has at least been marked in ETS to pass through the line coupler see Figure 6 If so then the line coupler will let it pass Otherwise it won t be transferred to the secondary line The same would also apply to the inverse case a telegram originating in the secondary line Note main group addresses in the range 14 to 31 cannot be filtered only routing or dropping all telegrams destined to them is possible The Preview of the filter table option in ETS does show these addresses but they are not downloaded to the device in the actual table http www zennio com Technical Support http zennioenglish zendesk com 9 Zennio Zennio KNX IP Router a YF 4 Properties Add Group Addresses Delete New Dynamic Folder LJ a Settings Comments Information Object Device Sendi ACK D Data Typ d Group Addresses Ka Dynamic Folders Name d Sin Wees i sample Address d 1 1 Sub Group 1 1 1 1 Sample Add me m n i e ample ress ll Description Group address settings _ Central C Fass thro
6. no telegram filtering or dropping gt Block all telegrams will be dropped gt Filter default option telegrams will be filtered dropping the corresponding ones see section 2 1 Note transmitting all telegrams no telegram filtering or dropping is intended for diagnostic purposes and may cause risks or conflicts or generate a large amount of traffic in the KNX installation if permanently activated However being able to perform downloads to devices in a different line than the programmer requires setting this option to Transmit All http www zennio com Technical Support http zennioenglish zendesk com 24 Zennio Zennio KNX IP Router 3 7 LINE This screen permits parameterising the behaviour of Zennio KNX IP Router regarding the telegrams received from the KNX line As shown in Figure 18 the available parameters are completely analogous to those in the Main line tab General IP configuration KNX multicast address Manual Settings Main line Line Configuration groups physical filter Group telegrams filter Main group telegrams 14 15 transmit all Physical telegrams filter Physical Repetition if errors on line normal Group Repetition if errors on line normal Telegram confirmations on line if routed Send confirmation on own telegrams no Figure 18 KNX line configuration tab Please refer to section 3 6 for a detailed description of these parameters taki
7. 0 0 LC LC PJ H Oe 7091 f uz A A DS 4 2 1 3 1 0 3 2 0 i 3 1 2 d 3 2 2 A 3 1 1 21 Main Line 3 0 0 LC J E a Area Line backbone ZS Figure 5 Line Coupling Whatever the topology Zennio KNX IP Router offers an insulated coupling interface with the possibility of filtering the traffic according to the topology in the installation or http www zennio com Technical Support http zennioenglish zendesk com 8 Zennio Zennio KNX IP Router to group oriented criteria In other words Zennio KNX IP Router will or will not let telegrams pass from one medium to the other according to the parameterisation Note the individual address of a line coupler needs to be of the form X Y O or X 0 0 in case of working as a backbone coupler 2 2 TELEGRAM FILTERING The device provides two complementary and optional filter types d Group address filtering ETS automatically generates a group address table for the project loaded This table is transferred to the line coupler during complete ETS downloads over it When a telegram containing a group address in the destination address field arrives the line coupler will look up if such address exists in the group table and eventually transmit the telegram to the other side if the address is found or drop block it if it is not Note making further changes to a project addresses etc requires
8. 4 E 1 0 Main line 11 0 0 Zennio KNX IP Router E 1 1 New line 4 EE Topology Dynamic Folders 4 tr 0 Backbone area Lann Backbone line 4 Ek 1 New area fey 1 0 Main line 4 E 1 1 New line A Inn Zennio KNX IP Router Figure 12 Zennio KNX IP Router as a Line Coupler Name Backbone line Address d 0 Description Status Unknown v Medium Figure 11 Zennio KNX IP Router as an Area Coupler Name Main line Address 0 We Description Status Unknown v Medium Finally clicking on the device with the secondary mouse button will permit selecting Edit Parameters in order to start the configuration The following sections provide a detailed explanation about each of the different parameters of the device 3 1 DEFAULT PARAMETERISATION When entering the parameter edition of Zennio KNX IP Router for the first time a window similar to Figure 13 will be shown where six main tabs are available General IP Configuration KNX multicast address Manual Settings Main line and Line Note that this application program does not implement communication objects http www zennio com Technical Support http zennioenglish zendesk com 19 Zennio Zennio KNX IP Router General Host name 30 signs KNX IP Router IP configuration KNX multicast address Enable slow connections disable Manual Settings Main line Line Figure 13 General 3
9. consists in sending telegrams destined to a physical address in order to make downloads to a device in a certain line for example the device with address 4 1 1 in Figure 5 from a programmer not in that line it is necessary that the line coupler is configured to let pass all physical addresses from the main line 2 3 LED INDICATORS Zennio KNX IP Router incorporates seven LED lights on the top of the device that make it easy to monitor the status of the buses and to detect typical communication problems as detailed next Fei S Zennio KNX IP ROUTER KNX ZSY IP ROU Bus stat O IP TP tO O aO aO Function Led v v Prog Figure 7 LEDs d Mainline LAN Status LED shows the status of the primary bus gt OFF error or mainline not connected or not powered gt ON green Ethernet connection OK gt ON orange manual function in execution or factory reset preparation Note the LED colours are independent It must be taken into account that when the green and red colours are on at the same time the result colour is orange The update of the LED status can be delayed a few seconds after the trigger event e g after the disconnection of the main line d KNX Line Status LED shows the status of the secondary bus http www zennio com Technical Support http zennioenglish zendesk com 11 Zennio Zennio KNX IP Router gt OFF error or secondary line not connected gt ON
10. green OK gt BLINKING green boot mode see section 2 5 1 gt ON red factory reset in execution see section 2 4 1 Note the LED colours are independent It must be taken into account that when the green and red colours are on at the same time the result colour is orange d Mainline LAN Traffic LED shows the traffic status in the Ethernet gt BLINKING green traffic gt FF no traffic gt ON red errors in the transmissions d KNX Line Traffic LED shows the traffic status in the secondary bus gt BLINKING green traffic gt OFF no traffic gt BLINKING red errors in the transmissions d Group Address GA Filter Status LED shows the current configuration of the group address routing gt OFF different configuration for the Ethernet and the secondary lines gt ON green filtering active gt ON red and green orange all group addresses routed filtering disabled gt ON red all group addresses blocked d Physical Address PA Filter Status LED shows the current configuration of the individual address routing http www zennio com Technical Support http zennioenglish zendesk com 12 Zennio Zennio KNX IP Router gt OFF different configuration for the Ethernet and the secondary lines gt ON green filtering active gt ON red and orange yellow all physical addresses routed filtering disabled gt ON dark orang
11. 2 Zennio Zennio KNX IP Router 3 6 MAIN LINE General Configurati groups physical filter IP confiquration di E a KNX multicast address Group telegrams filter Manual Settings Main line Main group telegrams 14 15 transmit all Li ms Physical telegrams filter Figure 17 Main Line tab This screen permits parameterising the behaviour of Zennio KNX IP Router regarding the telegrams received from the main line Ethernet The available parameters are described next d Configuration permits selecting a predefined set of parameters for the mainline or enabling the manual configuration of each parameter option Configure The available options are gt Groups filter Physical block enables the group address filtering and drops all telegrams destined to physical addresses gt Groups Physical filter default option enables both the group address and the physical address filtering gt Groups route Physical filter performs no blocking or filtering over the group address but does filter telegrams destined to physical addresses gt Groups Physical route performs no telegram filtering or dropping at all Note transmitting all telegrams no telegram filtering or dropping is intended for diagnostic purposes and may cause risks or conflicts or generate a large amount of traffic in the KNX installation if permanently activated The following paramet
12. 2 GENERAL As shown in Figure 13 this screen contains two parameters d Host Name string of up to 30 characters to easily identify the device in ETS or from a KNXnet IP system d Enable Slow Connections allows slow connections between ETS and the device 3 3 IP CONFIGURATION General _ ____ u_u e DHCP do not use IP configuration KNX multicast address Byte 1 Byte2 Byte3 Byte4 Manual Settings Main line line IP adress IP Byte 1 0 C IF Byte 2 0 LG Le IP Byte 3 0 IP Byte 4 0 Net mask La NM Byte 1 a Le ES NM Byte 2 o EN ES NM Byte 3 0 La NM Byte 4 0 Gateway GW Byte 1 0 LG GW Byte 2 0 E GW Byte 3 0 ES La GW Byte 4 d Figure 14 IP Configuration tab DHCP do not use http www zennio com Technical Support http zennioenglish zendesk com 20 Zennio Zennio KNX IP Router Zennio KNX IP Router is provided with the DHCP protocol enabled by default and therefore can gain an IP address automatically as long as a DHCP server is available in the local network From ETS it is possible to disable the use of the DHCP and manually set an IP address for the device as well as the subnet mask and the IP address of the the network gateway Thus it is advisable to contact the manager of the local network Notes d To make this configuration effective after the download from ETS it is necessary to interrupt the external power supply
13. e all physical addresses blocked Note please be careful not to confuse yellow and dark orange d Physical Address PA programing LED gt OFF normal operation gt ON red programing mode active gt BLINKING red Ethernet cable disconnected Please refer to section 3 for a detailed explanation of the different behaviours and parameterisations of the Zennio KNX IP Router application program http www zennio com Technical Support http zennioenglish zendesk com 13 Zennio Zennio KNX IP Router 2 4 MANUAL FUNCTION BUTTON Zennio KNX IP Router features an additional pushbutton on the top cover next to the status LEDs see 4 in Figure 3 A three second press on this button will set the device in manual mode thus activating a customisable manual function and will turn the main bus status LED orange or red depending on the previous status of the LED green or off Depending on the parameterised manual function other LEDs may also change their colours lf the manual function button is pressed again for three seconds or if the parameterised fall back timer expires the device will leave the manual mode and recover the normal mode Note that switching from the normal mode to the manual mode and then back to the normal mode does not cause the loss of the parameters or filter tables previously downloaded In the application program of the device the selectable manual functions are d Disabled d
14. erforming as a programmer does not allow bus monitoring the ETS bus monitor will not be available Moreover Zennio KNX IP Router does not allow being unloaded unprogrammed from ETS Equivalently it can be reset to the factory default state as explained in section 2 4 1 http www zennio com Technical Support http zennioenglish zendesk com 7 Zennio Zennio KNX IP Router 2 DESCRIPTION 2 1 LINE OR AREA COUPLER Zennio KNX IP Router can be used as a line coupler for coupling both a line to a mainline or as an area coupler for coupling a main line to an area line also referred to as backbone line The operation on both cases is analogous being a line coupler or an area coupler only depends on the location of the device within the topology Figure 5 shows a typical scenario where Zennio KNX IP Router can be installed as any of the nodes the nodes labelled as AC area coupler or LC line coupler d Coupling an area line and a main line requires an area coupler AC Zennio KNX IP Router is intended for cases where the medium of the former is Ethernet while the medium of the latter is TP d Coupling a main line and a line requires a line coupler LC Zennio KNX IP Router is intended for cases where the medium of the former is Ethernet while the medium of the latter is TP In such cases the medium of the area line if any is assumed to be Ethernet as well 4 1 0 4 2 0 Main Line 4
15. ers will be locked unless Configure has been selected under Configuration d Group Telegrams sets the behaviour of the device regarding telegrams destined to group addresses The available options are gt Transmit all no telegram filtering or dropping http www zennio com Technical Support http zennioenglish zendesk com 23 Zennio Zennio KNX IP Router gt Block all telegrams will be dropped gt Filter default option telegrams will be filtered dropping only the corresponding ones according to the filter table see section 2 2 Note transmitting all telegrams no telegram filtering or dropping is intended for diagnostic purposes and may cause risks or conflicts or generate a large amount of traffic in the KNX installation if permanently activated d Main Group Telegrams 14 15 sets whether telegrams destined to group addresses beginning with 14 or greater e g 14 1 1 will be dropped or transmitted The options are Transmit all default option and Block Note ETS does not include in the filter table the following group addresses gt 14 0 0 to 31 7 255 in three level topologies gt 14 0 to 31 2047 in two level topologies gt 28672 7000 to 65535 FFFF in level free topologies d Physical Telegrams sets the behaviour of the device regarding telegrams destined to individual addresses The available options are gt Transmit all
16. face permits updating the internal firmware of the device whenever Zennio releases a new firmware version through the http www zennio com website by following these steps please see Figure 9 d Authorise the update gt Set the device into the programming mode gt Press the manual function button gt Wait for the update authorized message on the screen d Request the update gt From the Update section press the Request Update button and wait until the device reboots and enters Boot mode d Upload the firmware gt Browse for the hexadecimal file gt Press the Upload button http www zennio com Technical Support http zennioenglish zendesk com 16 Zennio Zennio KNX IP Router Zennio KNX IP Router BOOT MODE To initiate a firmware update please select a valid file in hex format below Otherwise the device will log out automatically after 10 minutes Status update authorized Select update file Seleccionar archivo Ning n archivo seleccionado Upload Abort Figure 9 Web interface firmware update After the second step update request the device switches to Boot mode which interrupts the normal device operation telegram filtering etc being no longer possible to connect to it It will remain in this mode for ten minutes to allow the firmware update before returning to the normal mode During the Boot mode the TP line status LED indicato
17. ll make the device respond with an IACK message only if the received telegram is routed towards the mainline gt Always will make the device send a confirmation for every telegram it receives even if not routed to the line on the other side d Send confirmation on own telegrams permits enabling Yes or disabling No default option self acknowledgment This extra feature offers the possibility of sending an ACK to the destination line immediately after passing the telegram itself so the telegram will show as confirmed on it therefore preventing repetitions in case of faulty projects etc even if no device is receiving it In case of reception errors on the destination line negative ACKs sent by the devices will overwrite this ACK so having this parameter enabled will cause no damage or information loss http www zennio com Technical Support http zennioenglish zendesk com 26 Zennio Passion for KNX innovation Join and send us your inquiries about Zennio devices http zennio zendesk com Zennio Avance y Tecnolog a S L C Rio Jarama 132 Nave P 8 11 45007 Toledo Spain Tel 34 925 232 002 Fax 34 925 337 310 eeng ENR CE RoHS
18. ng into account that section 3 6 applies to the main line instead of the line The following parameters are specific for the line they are not available for the main line d Physical Repetition if errors on line sets the desired reaction upon transmission errors in the line e g busy receiver acknowledgement not received negative acknowledgement etc of telegrams destined to physical addresses The options are gt No the undelivered telegram will not be re sent gt Normal default option the undelivered telegram will be re sent up to three times gt Reduced the undelivered telegram will be re sent once d Group Repetition if errors on line sets the desired reaction upon transmission errors in the line e g busy receiver acknowledgement not http www zennio com Technical Support http zennioenglish zendesk com 25 Zennio Zennio KNX IP Router received negative acknowledgement etc of telegrams destined to a group address The options are gt No the undelivered telegram will not be re sent gt Normal default option the undelivered telegram will be re sent up to three times gt Reduced the undelivered telegram will be re sent once d Telegram confirmations on line sets when the device should confirm by sending an immediate ACK message or IACK the reception of telegrams gt If routed default option wi
19. nual operation 1 hour Manual Settings Manual function pass all telegrams Main line Line Figure 16 Router configuration tab As shown in Figure 16 this screen contains two parameters related to the device manual mode see section 2 4 d Fallback Time for Manual Operation sets the maximum operation time for the manual mode Once exceeded the device will automatically leave manual mode and return to normal mode The available values are 10 minutes 1 hour default 4 hours and 8 hours d Manual Function sets the desired function to be executed by the device while in the manual mode The available values are gt gt Disabled no action Pass all telegrams default option the device will not filter drop any telegram transferred from one line the other Pass physical telegrams the device will not filter drop physical addresses in other words all telegrams destined to physical addresses will be transmitted while in manual mode on the other hand group telegram filtering will stay the same as in normal mode Pass group telegrams the device will not filter drop group addresses in other words the group address filter table will stay disabled while in manual mode on the other hand physical address filtering will stay the same in normal mode http www zennio com Technical Support http zennioenglish zendesk com 2
20. of the device for an instant and afterwards restore it d A wrong configuration of these parameters e g IP address 0 0 0 0 or subnet mask 0 0 0 0 may leave the device locked with the LAN traffic status LED lighting in red colour To exit this status it is necessary to disconnect the Ethernet cable and restore the factory defaults section 2 4 1 3 4 KNX MULTICAST ADDRESS Telegrams sent from the KNX bus to the IP network or vice versa travel through the latter as multicast IP packets addressed to port 3671 at IP address number 224 0 23 12 so that they reach all KNX IP interfaces available on the network Such address is reserved by the IANA organisation for the KNXnet IP protocol and should only be changed in parameters Use Default Multicast Address No in case the network configuration requires it or to create different independent topologies within the same IP network Otherwise it should be left as is Use Default Multicast Address Yes General Use default multicast address No 7 IP configuration KNX DEE address Byte 1 Manual Settings Main line Byte 2 0 255 o Line E 3 Byte 3 0 255 0 Byte 4 0 255 A Figure 15 KNX multicast address configuration tab http www zennio com Technical Support http zennioenglish zendesk com 21 Zennio Zennio KNX IP Router 3 5 MANUAL SETTINGS General IP configuration KNX multicast address Fallback time for ma
21. or a KNX IP interface Certain conditions must be met d Each download must be performed on a different line e For each line it is necessary to select one Zennio KNX IP Router or one Zennio KNX IP Interface to perform the download This is configured by right clicking on the line and under Set Connection selecting the desired connection once selected it will not be available for other lines O O Ze Running Active History 7 Waiting 4 1 1 1 Touch MyDesign Plus 6 Connecting to device t Download Appl Download 4 1 2 1 MAXinBOX 66 Connecting to device t Download Appl Downloading 4 trl New area L 1 0 Main line 4 E 11 Line 1 l 01 1 0 Zennio KNX IP Router EE J A TI Touch MyDesign Plus 6 ES Dal iTS 44 Cownload A Hane o Router line 1 192 168 27 133 4 E 12 line 2 imi 1 2 0 Zennio KNX IP Router Fay 7 11 2 1 MAXinBOX 66 Get Object Description from b 12 2 Touch MyDesign Plus 6 yh Add to Favorites b Figure 4 ETS parallel downloads http www zennio com Technical Support http zennioenglish zendesk com 6 Zennio Zennio KNX IP Router An additional restriction applies to the parallel downloads they are not available to download physical addresses When performing this type of downloads the link device used by ETS is not the one configured for the line but the general one 1 3 2 LIMITATIONS It is important to note that Zennio KNX IP Router when p
22. outer Zennio KNX IP Router is the KNX twisted pair to Ethernet line coupling solution from Zennio IP routers are similar to twisted pair line couplers except that they use Ethernet as the main line Zennio KNX IP Router can be used as a line or area coupler and provides a data connection between the upper KNXnet IP line area line or backbone and the lower KNX twisted pair bus line lt also provides a connection point for ETS to enable programming up to four parallel connections and monitoring the line Backbone line Figure 2 Context Topology http www zennio com Technical Support http zennioenglish zendesk com Zennio Zennio KNX IP Router In contrast to the Zennio KNX IP Interface device which offers a simple KNX to IP coupling solution Zennio KNX IP Router incorporates an additional configurable telegram filtering system according to their destination group physical address These are the most outstanding features of the device d Support for long messages up to 250 bytes d Use as an area or line coupler with a LAN as main line or main area line offering a fast communication medium for telegram exchange d Up to 4 parallel connections from ETS for programming and monitoring d Low power consumption d Traffic filtering according to the project topology and to the built in address table d Telegram dropping d Blockage of device configuration telegrams telegrams de
23. r blinks in green Notes d The Boot mode can be alternatively accessed by disconnecting the power supply and re connecting it while pressing the Programming or the Manual Function buttons or both together http www zennio com Technical Support http zennioenglish zendesk com 17 Zennio Zennio KNX IP Router 3 ETS PARAMETERISATION To begin with the parameterisation process of the device it is necessary once the ETS program has been opened to import the database of the product KNX IP Router application program 4 Properties 9 Settings Comments information Name ennio KNX 1P Router Individual Address Description Product ennio KNX IP Router Program ennio KMX IF Router Last Modified 24 02 2015 7 46 Last Downloaded Status Unknown d Figure10 Properties of the Zennio KNX IP Router Application Program Next the device should be added to the project where desired Note that depending on where the device is placed the upper levels of the topology need to be configured as KNXnet IP d The backbone line in case of working as an area coupler d The backbone line and the main line of the area the device belongs to in case of working as a line coupler http www zennio com Technical Support http zennioenglish zendesk com 18 Zennio Zennio KNX IP Router EE Topology Dynamic Folders 4 11 0 Backbone area L 0 0 Backbone line 4 Ek 1 New area
24. stined to ohysical addresses d High capacity buffer for the reception of telegrams from the Ethernet network d Web interface to display the device settings to switch to the programming mode and for firmware updates d Customisable pushbutton for triggering the manual mode useful at runtime and for set up and troubleshooting purposes d 7 lighting indicators LEDs two bus state indicators per line with detection of abnormal situations excessive bus load message retransmissions etc one more indicator per line for the state of the filtering function and one additional indicator for the programming mode http www zennio com Technical Support http zennioenglish zendesk com 4 Zennio Zennio KNX IP Router 1 2 INSTALLATION LD Y NN Main line LAN status LED Main line LAN traffic LED Group address filter status LED Manual function button Programming LED External power supply 12 24V Main line LAN connector Secondary line KNX status LED 9 Secondary line KNX traffic LED 10 Physical address filter status 11 Programming button 12 Secondary line KNX connector 2 A ES 12 Figure 3 Element Diagram This device requires an external power supply 12V to 30V DC through connector 6 as it is not powered through the KNX bus Figure 3 shows a scheme with all the LED indicators and connections To couple a KNX twisted pair TP line and a LAN the KNX bus 12
25. ugh Line Coupler Figure 6 ETS Option to Force Passing a Group Address through the Line Coupler d Physical address filtering when the device receives a telegram where the destination address is a physical individual address for example during downloads it will compare such address with its own physical address no particular filter table is required for physical address filtering but a simple comparison The physical address of the line coupler determines the line it belongs to which then and according to the parameterisation determines if the telegram will be routed or eventually dropped blocked This can be parameterised separately for the mainline and for the line Example in the example shown in Figure 5 if the coupler with address 3 2 0 reads a telegram on the mainline destined to a device with individual address 3 1 2 it will compare both addresses and conclude that 3 1 2 does not belong to the secondary line and therefore not transmit it Notes gt The device that sends a telegram needs to have been assigned a physical address that really corresponds to its line In Figure 5 if the device with address 3 1 1 a KNX programmer for instance changes its address to 255 it will not be able to send telegrams to for example the device with address 4 0 1 http www zennio com Technical Support http zennioenglish zendesk com 10 Zennio Zennio KNX IP Router gt Important as device programming