Animeo IB+ OPC server

image

Contents

1. 10 seconds Prefix SYSTEM ERRORS Structure e SYSTEM ERRORS o XXX INSIDESENSORBOX 01 Error inside sensor box O1 INSIDESENSORBOX 02 Error inside sensor box 02 INSIDETEMP 04 Error inside temp sensor 04 Error outside sensor box Error Wind sensor 03 o o WINDSENSOR 03 Error Wind sensor 03 WINDSENSOR 04 Error Wind sensor 04 INSIDETEMP 01 Error inside temp sensor 01 File animeo IB OPC server User Manual 2 0 for the CD 2009 09 17 Page 18 of 23 sOomfy 5 11 Zone Info On first level the basic info Alias Angle Position End Product Isauto and Islocked is Shown XX could be 01 16 Alias e The name given to the zone then configure the system Angle e Show the current angle if a tilting end product is controlled Position e Show the current position of the end product 0 100 where 100 is fully down End Product e The type of end product for example Venetian Blind I sauto e Automated mode is on I slocked e The zone is locked Prefix ANIMEO ZONES ZONE_ XX Structure e ANIMEO ZONES o ZONE XX XXX ANGLE Value x degrees integer 90 to 90 ALIAS Value name string POSITION Value x down 0 100 ISAUTO Show if automated mode is on Boolean True false ISLOCKED Shows if zone is locked Boolean True false END PRODUCT Value name string File animeo IB OPC server User Manual 2 0 for the CD 2009 09 17 Page 19 of 23 sOomfy 5 12 Used functionality The values is updated accordi
2. function can simply be described as By analyzing the present weather data e g the solar shading devices are ordered to an optimized position The building is divided into zones A zone is typically a specific type of solar shading device in a specific weather direction One system can manage up to 16 zones and each zone can manage up to 400 motors Each zone has its own set of adjustable parameters these are called Zone functions There are also a number functions that valid for all zones these are called Building functions It s also fully possible to locally control any specific motor from a local control point this is called Local control An animeo IB system consists of following devices e Building controller BuCo The BuCo is the heart of the system This device analyzes all input a take all decisions A BuCo can control up to 8 zones If more zones are required an additional BuCo BuCo Extension can be used This leads to that a system can manage up to 16 zones The BuCo can also via potential free in and outputs communicate with other systems in a building e g fire alarm e Sensor boxes There are two different type of sensor boxes available One for interior and for exterior sensors A number of different types of sensors can be connected to each sensor box Up to two of each can be connected to a system e Motor controllers MoCo All motors and local control points e g a switch and or remote are
3. 9 17 Page 16 of 23 sOomfy 5 8 Wind Speed The system can have 4 wind speed sensors The value is shown in m s km h or mph The OPC server and animeo doesn t need to show the value in the same unit XX could be 01 04 Prefix SENSOR WINDSPEED XX Structure e SENSOR o WINDSPEED XX XXX VALUE Value m s or km h or mph integer ALIAS Value name string OPERATIONAL Boolean True False 5 9 System Shows the current status of the server and the connection between animeo and the building controller It also shows the update rate for sensor values settings and Server disconnect timeout Handles temperature and wind speed units used to present temperature and wind speed in the server Available wind units shall be the same as in animeo m s km h and mph Available temperature units shall also be the same as in animeo Celsius and Fahrenheit Note that it shall be possible to select different unit in the server and animeo Prefix SYSTEM Structure e SYSTEM o XXX SERVER_ONLINE Server online status SERVER SENDING DATA Server activity status ANIMEO ONLINE Animeo online status SENSOR UPDATE TIME Sensor update rate File animeo IB OPC server User Manual 2 0 for the CD 2009 09 17 Page 17 of 23 sOomfy 5 10 SYSTEM ERRORS System Errors shows status of the different errors True if error otherwise False The values are updated according to the settings in animeo values transmission interval default is every
4. D as it does not reflect the status of the system Prefix COMMANDS ZONE_XX Structure e COMMANDS o ZONE XX XXX Extend 100 pos 100 Go to secure position 0 pos 0 File animeo IB OPC server User Manual 2 0 for the CD 2009 09 17 Page 22 of 23 sOomfy 6 Warranty and limitation of liability Somfy does not warrant that other software running or installed on the PC do not interact with the Software or impact its performance Application of the warranty is limited to the replacement of the faulty Software SOMFY DOES NOT WARRANT THAT THE SOFTWARE WILL BE ERROR FREE OR PERFORM UNINTERRUPTED OR THAT SOMFY WILL CORRECT SOFTWARE ERRORS TO THE EXTENT PERMITTED BY LAW THESE WARRANTIES ARE EXCLUSIVE AND THERE ARE NO OTHER EXPRESS OR IMPLIED WARRANTIES OR CONDITIONS INCLUDING WARRANTIES OR CONDITIONS OF MERCHANTABILITY SATISFACTORY QUALITY AND FITNESS FORA PARTICULAR PURPOSE IN NO EVENT SOMFY SHALL BE LIABLE FOR ANY DIRECT INDIRECT INCIDENTAL SPECIAL PUNITIVE OR CONSEQUENTIAL DAMAGES UNDER THIS LICENSE AGREEMENT OR ANY LOSS OF PROFITS REVENUE DATA OR DATA USE 8 Confidentiality The Software its Documentation and its Contents are confidential Therefore You shall not disclose the Software its Documentation and its Contents to any third party during the execution of this license agreement and after its termination 9 Miscellaneous If any of the provisions of this license agreement Is judged to be illegal or unen
5. Servers must be unregistered in reverse order to their registration i e Last registered server is the only possible server to unregister Unregistering a server removes the connection between the OPC server and Somfy animeo IB Operating Software The OPC Server information is deleted from registry and the server won t be in the list of available OPC servers No software will be deleted and the server is easily registered again 4 4 Start Server Pressing start server starts the instance of Somfy animeo IB Operating Software associated with the selected OPC Server File animeo IB OPC server User Manual 2 0 for the CD 2009 09 17 Page 12 of 23 sOomfy 4 5 View Server log Opens the server log if it exists 4 6 Report options It s possible to get a summary of the OPC server settings either as a text document saved to file or printed out File animeo IB OPC server User Manual 2 0 for the CD 2009 09 17 Page 13 of 23 sOomfy 5 Node specification This chapter contains the format and values on the different Node Groups in the OPC server To save space the prefix on a node is omitted for example the node SENSOR OUTTEMP VALUE will be called VALUE in the list below To create the node structure in the OPC server a module shall be added to animeo that generates the structure specified below This module shall also handle the update of the nodes according to animeo value and settings transmission interval 5 1 Node structu
6. alse 5 4 Rain The system can have one rain sensor Together with the outside temperature sensor the system can indicate snow and frost The value is a Boolean for precipitation or No precipitation Prefix SENSOR RAIN Structure e SENSOR o RAIN XXX VALUE Boolean True False ALIAS Value name string OPERATIONAL Boolean True False 5 5 Wind Direction The system can have one wind dir sensor The value is shown in degrees from 0 359 Prefix SENSOR WIDDIR File animeo IB OPC server User Manual 2 0 for the CD 2009 09 17 Page 15 of 23 sOomfy Structure e SENSOR o WINDDIR XXX VALUE Value x degrees integer ALIAS Value name string OPERATIONAL Boolean True False 5 6 Inside Temperature The system can have four inside temperature sensors The value is shown in degrees Celsius or Fahrenheit The OPC server and animeo doesn t need to show the value in the same unit XX could be 01 04 Prefix SENSOR INSIDETEMP_ XX Structure e SENSOR o INSIDETEMP_XX XXX VALUE Value x degrees Celsius or Fahrenheit integer ALIAS Value name string OPERATIONAL Boolean True False 5 7 Sun The system can have 16 sun sensors The value is shown in Klux XX could be 01 16 Prefix SENSOR SUN_ XX Structure e SENSOR o SUN XX XXX VALUE Value x Klux integer ALIAS Value name string OPERATIONAL Boolean True False File animeo IB OPC server User Manual 2 0 for the CD 2009 0
7. connected to the MoCo There are a number of different MoCo s available Normally due to the motor type to be used e g 230V 120V 24V Encoders etc e APC and linked animeo PC software The system will work without the PC up and running except OPC functionalities The PC is used to make settings monitor the status and give commands The PC communicates with the BuCo over RS 485 LA 7 r r A a aN Wy 19 co o a ami o e MA cG rE O ra HAES File animeo IB OPC server User Manual 2 0 for the CD 2009 09 17 Page 4 of 23 sOomfy 2 1 Priorities All functions are divided into two different categories either Security or Non security The difference is that the Security functions are impossible to override even in Manual mode Non security functions are only active in Automatic mode The highest priority has Major Alarm and the lowest Non critical System Error Security functions Major Alarm PC Building lock 0 PC Zone lock 0 Key Building lock 0 Key Zone lock 0 Major Error Wind Speed Wind Direction Snow Frost Rain Building Timer Key Building 100 Non Security functions PC Zone Command Zone Timer Reset Building 0 Switch Building Command Switch Zone Command Solar Heating Solar Heating HVAC Maintain Heat Ventilation Cooling HVAC Zone Synergy Sun Non Critical System Error 2 2 Control mode When active the end products will take the programmed po
8. eatures instead of Do they have the driver to my unique device They don t have to create a custom interface that they must bear the full cost of creating and upgrading through operating system or device vendor changes Users were also assured of better quality connectivity as the OPC DA Specification codified the connection mechanism and compliance testing OPC interface products are built once and reused many times hence they undergo continuous quality control and improvement The user s project cycle is shorter using standardized software components And their cost is lower These benefits are real and tangible Because the OPC standards are based in turn upon computer industry standards technical reliability is assured The original specification standardized the acquisition of process data It was quickly realized that communicating other types of data could benefit from standardization Standards for Alarms amp Events Historical Data and Batch data were launched The OPC world is managed by the OPC Foundation www OPCFoundation org File animeo IB OPC server User Manual 2 0 for the CD 2009 09 17 Page 3 of 23 sOomfy 2 This is animeo IB First for detailed information please study the animeo IB owner s manual See also chapter Error Reference source not found So animeo IB is a control system for any type of solar shading device and various types of windows for natural ventilation and night cooling features The
9. esents the wind speed in the OPC Server 4 Wind Speed Unit mis File animeo IB OPC server User Manual 2 0 for the CD 2009 09 17 Page 11 of 23 sOomfy 4 2 5 Log Server traffic to file The OPC server is able to create a trace file Different level of tracing is available I Log Server traffic to file a ae M a oo a a A e Enable Logging Trace Level TraceLevel Mone File path C Users MjGoSoft Documents My Somfy animeo 2 1 OpcServerLog Somfy animeol File Name Somfy animeolB 1 1 bet The trace levels used are TraceLevel None e Default No trace messages are stored TraceLevel Connect e Log trace messages associated with client connectivity and server activation TraceLevel Group e Log trace messages associated with creating deleting modifying OPC groups TraceLevel Item e Log trace messages associated with item transactions For example read write and subscription transactions TraceLevel All e Log all message types The trace is saved on a log file stored under the existing Documents My Somfy animeo 2 1 folder created when installing animeo in a folder called OpcServerLog The filename is servername txt example Somfy animeolB 1 1 txt The maximum size in Megabytes that the trace log file can grow to is 10 Mb default When the file reaches this size it will start from the beginning of file Thus the trace log file is circular 4 3 Unregister Server
10. forceable the continuation in full force and effect of the remaining provisions of this license agreement shall not be invalidated or otherwise rendered ineffective This license agreement is the sole and entire agreement between You and Somfy with respect to its subject matter and is deemed to be made under and shall be construed in accordance with the laws of France exclusively without giving effect to the conflict of laws principles thereof All disputes in connection with the present license agreement including any question regarding its existence validity or interpretation shall be settled by the Tribunal de Grande Instance of Paris France This license agreement supersedes all proposals or other prior agreements oral or written and all other communications between the parties relating to the subject matter hereunder No modification of this license agreement will be binding the parties unless in writing and signed by an authorized representative of each party ACCEPT THE LICENCE AGREEMENT II DECLINE TO ACCEPT THE LICENCE AGREEMENT File animeo IB OPC server User Manual 2 0 for the CD 2009 09 17 Page 23 of 23
11. ivsaaa nE AATE tyes NE a Ee I SCR VER MNO e a E E TimMer o eN ernn EEEREN AA 3 Temperature UnNit seseerererrrrererrererrrrrrerrrrsrrrrrrerrrrne Wind speed UNU osrresrirsi rennyr EEEE 5 Log Server traffic to file cece ccccees esse eee eeeeeeeeeenenneees Unregister Server sssssensrrrrererrrrerrrrrrererrrrrrrrrrrerrrrrrerrrrne Stat Ger GM eaae EEEE Ea EEE AS ICV SCI GE Oea EE ET 4 6 Report Options cccccscceseeeeeeessecesssecueeesnetseugeererteennssegags PEE 3 Page 2 of 23 sOomfy 1 What is OPC OPC is a series of standards specifications The first standard originally called simply the OPC Specification and now called the Data Access Specification resulted from the collaboration of a number of leading worldwide automation suppliers working in cooperation with Microsoft Originally based on Microsoft s OLE COM component object model and DCOM distributed component object model technologies the specification defined a standard set of objects interfaces and methods for use in process control and manufacturing automation applications to facilitate interoperability The COM DCOM technologies provided the framework for software products to be developed There are now hundreds of OPC Data Access servers and clients Everyone s favourite analogy for needing the original Data Access Specification is printer drivers in DOS and then in Windows Under DOS the developer of each application had to also w
12. lable options are Exit and open server one Ta Manage OPCServer for Somfy animeo IB Ag Exit Save Settings Register Server Unregister Server Start Server View Serverlog Report Options Animeo Instance 1 a Somfy animeolB 1 1 Animeo OPC Manager F Som animeolh 2 i i SOMFY SAS capital 70 000 000 Euros RCS Bonneville 303 970 330 Copyright Somfy S45 2006 All nights reserved IDDN FR OOT 90004 0005 F 2006 000 3150 wa Somfy animeolb 3 1 FOUNDATION Pe somfy animeolb 7 1 P Somfy animeolB s 1 4 1 1 Server Instance Somfy animeo IB Operating Software supports a building with 16 zones if a building consists of more than 16 zones a second instance of Somfy animeo IB Operating Software is started and connected to a different port The OPC servers are then associated with a specific instance of Somfy animeo IB Operating Software File animeo IB OPC server User Manual 2 0 for the CD 2009 09 17 Page 8 of 23 somfy l e If an OPC server is enabled Somfy animeo IB Operating Software instance 1 is connected to OPC server instance 1 and so on 4 1 2 Register the first server To register a server and make it available in animeo IB press the link under the Animeo instance 1 Somfy animeolB 1 1 F a sl z Ji 5 Manage OPCServer for Somfy animeo IB a i __ Ag Exit Save Settings 3 Register Server Unregister Server Start Server View Serverlog Report Options Somfy animeolB 1 1_ a Somfy anime
13. must be given a unique ProgID and CLSID so that OPC clients may connect to your server Application Name e The name to be associated with the ApplD Appli D e The application identifier for the internal OPCServer object CLSID e The class identifier for the internal OPCServer object Clients may use the CLSID in the process of creating instances of your OPC server The buttons copy text next to App ID and CLS ID will copy the GUID identifier for the App ID and CLS ID File animeo IB OPC server User Manual 2 0 for the CD 2009 09 17 Page 10 of 23 sOomfy 4 2 2 Timer Settings Control different timer settings on the OPC Server Animeo Settings transmission interval e The update rate for the less frequently changed values in animeo for example used and active functions Animeo Values transmission interval e The update rate for the frequently changed values in animeo like sensor values Server Disconnect timeout e The time for the OPC server to wait before shutting down after the Request Disconnect message is sent to the client If no clients are connected the OPC Server is closed immediately 4 2 3 Temperature Unit Select the desired temperature unit used then the Somfy animeo IB Operating Software presents the inside and outside temperature in the OPC Server E Temperature Unit Celsius 4 2 4 Wind speed Unit Select the desired wind speed unit used then the Somfy animeo IB Operating Software pr
14. ng software Both the PC AND the animeo IB Operating software OPC server must be running to access OPC functionality e Size restrictions Normally only one system up to 16 zones can be controlled per OPC client Meaning if more zones are to be used this second system will require its own PC and animeo IB Operating software OPC server 3 3 Responsibilities Somfy is only responsible for configuring and commissioning of the animeo IB system and the installation of the OPC server Somfy does not take responsibility for the OPC server client integration This is the job of the integrator BMS supplier 3 4 Installation and PC requirements Simply insert the animeo OPC installation CD ROM in the PC that already has the animeo IB Operating software installed and run the setup Somfy OPCServer Manager file and follow the instructions The PC requirements are described in the animeo IB owner s manual File animeo IB OPC server User Manual 2 0 for the CD 2009 09 17 Page 7 of 23 somfy 4 OPCServer Manager The OPCServer Manager is the software used to manage the animeo IB OPC connection From the manager the user enables register or disables unregister one or many max 8 OPC server s NOTE IF RUNNING ON MICROSOFT VISTA START THE SOFTWARE AS ADMINISTRATOR RIGHT CLICK ON Somfy OPCServer Manager 2 0 ICON AND SELECT RUN AS ADMINISTRATOR 4 1 First start When the application is started the only avai
15. ng to the value specified in animeo Settings transmission interval default is every 30 seconds Prefix ANIMEO_ZONES ZONE_XX USED_ FUNCTIONS Structure e ANIMEO ZONES o ZONE XX USED FUNCTIONS e XXX USEKEYBUILDING _ _ o T USEKEYZONELOCK Key Zone lock used File animeo IB OPC server User Manual 2 0 for the CD 2009 09 17 Page 20 of 23 sOomfy 5 13 Active functionality The values are updated according to the settings in animeo values transmission interval default is every 10 seconds Prefix ANIMEO_ZONES ZONE_XX ACTIVE_FUNCTIONS Structure e ANIMEO ZONES o ZONE XX ACTIVE FUNCTIONS e XXX ACTFROST ACTKEYBUILDING ACTZONELOCK Zone lock activated Wind direction activated PRFMPRESENCENOLOCAL Performance mode Presence detector no local control PRFMTIMER Performance mode Timer PRFMTIMERNOLOCAL Performance mode Timer no Local Control SFUNCTIONACTIVE Security Function Active 5 14 Updatable items File animeo IB OPC server User Manual 2 0 for the CD 2009 09 17 Page 21 of 23 sOomfy A way for the BMS system to interact with the animeo system this is the only nodes that are updatable By sending the value 1 to any node below the animeo system will perform the required action Note The value on the node isn t updated but if it receives a request to update the value to 1 it will pass the node request to the animeo system Any other value but 1 is ignored The quality of these data is always BA
16. o a zone to go to a Specific position AND if locally e g a specific shading device in the zone is controlled to another position the BuCo will not be aware of this This means that ALL information and actions in an animeo system is on Zone level Meaning it s not possible to monitor or control a specific motor in a zone from the PC or OPC client File animeo IB OPC server User Manual 2 0 for the CD 2009 09 17 Page 6 of 23 sOomfy 3 Animeo 1B OPC server 3 1 General The OPC server is a third party component from Software Toolbox Inc www softwaretoolbox com Once installed It is a part of the Somfy animeo IB Operating Software The OPC server is compliancy tested according to the specifications of the OPC foundation www opcfoundation org Via the OPC interface it is possible to access status on both zone and building level as well as sending commands for each zone to change operating mode or to control the end products It is not possible to alter functional parameters via the OPC interface as these may change the configuration of the system in such a way that equipment in a worst case might be damaged 3 2 Limitations There are a few limitations to be aware about e Zones As already stated in chapter 2 2 that it is only possible to get the position for a zone Not for a single motor in a zone It s also only possible to give commands e g up or down on zone or building level e The PC and the animeo IB Operati
17. oIb 1 1 a 3 wa Server not registred a Server Info Description Program ID Application Name App ID 23769284 20 s A B5y Gor 28371 B copyted CLSID 6017 582 3738 A 19 87 A EFEBOABR YEG E Copy tet Timer Settings 3 Animeo Settings transmission interval j Animes Values transmission interval Maxi Celsius C Fahrenheit Wind Speed Unit 3 som animeolb 7 1 ee a ee mis C kmh Ci mph Animeo Instance 8 Log Server traffic to file Somfy animeolb 3 1 Enable Logging Information about the server default settings is shown but all settings are disabled The server icon has a red cross meaning that it s not yet registered To register the server press Register Server in the toolbar The server icon turns green and the settings are enabled Also it s now possible to register a new server Somfy animeolB 1 2 in a similar way File animeo IB OPC server User Manual 2 0 for the CD 2009 09 17 Page 9 of 23 somfy 4 2 Server Settings When opening a server that is registered the user can change some of the server s settings 4 2 1 Server Info The first field Server Info is always read only a Server Info Description OPCServer for Somfy animeo IB Application Name OPCServer an App ID CLS ID E be P Description e The description stored on the OPCServer object Program ID e The version dependent programmatic identifier for the OPCServer object It
18. or 100 on the internal sensor box is active more then 2s a manual group command is executed When active the zone will act to get heat from the sun E g move sun protection to 0 position When active the zone will act to get heat from the sun in combination with the HVAC system E g move sun protection to 0 position When active the zone will act to preserve heat by e g move sun protection to 100 position When active the zone will act for natural ventilation in combination with the HVAC system by e g by opening windows When active an internal sun protection zone adopts a locked external sun protection zone function to keep maximum performance of the building When active the zone will take it s programmed position When active a minor error has occurred These errors will not impact the security of the system and will not execute any action This is just an indication Each zone can be in either Manual or Automatic control mode In Automatic mode all functions are enabled In Manual mode all Non security functions are disabled Security functions are always enabled independent of Control mode See also chapter 2 1 File animeo IB OPC server User Manual 2 0 for the CD 2009 09 17 Page 5 of 23 sOomfy 2 3 Communication within an animeo 1B System Within the system all communication is bidirectional except between the BuCo and MoCo which is Mono directional It s then important to remember If the BuCo give a command t
19. re SENSOR a a a a ra B OUTTEMP Data RAIN Data WINDDIR Data INSIDETEMP_XX Data SUN_ XX Data WINDSPEED XX Data SYSTEM Data amp SYSTEM_ERRORS Data ANIMEO_ ZONES va ZONE XX Data XX 01 04 XX 01 12 XX 01 04 XX 01 16 amp USED_FUNCTIONS e Data amp ACTIVE FUNCTIONS e Data COMMANDS ra ZONE XX Data XX 01 16 File animeo IB OPC server User Manual 2 0 for the CD 2009 09 17 Page 14 of 23 sOomfy 5 2 Sensor Displays current sensor value for all sensors in the system All Sensors are included tn the server but only the used one will have a value The values are updated according to the settings in animeo values transmission interval default is every 10 seconds All sensors show three values Alias Value and Operational Alias e The name given to the sensor when system was configured Value e The sensor value can be a Boolean true False or an integer Operational e Tells if a sensor is used and active Boolean 5 3 Outside temperature The system can have one outside temperature sensor The value is shown in degrees Celsius or Fahrenheit The OPC server and animeo doesn t need to show the value in the same unit Prefix SENSOR OUTTEMP Structure e SENSOR o OUTTEMP XXX VALUE Value x degrees Celsius or Fahrenheit integer ALIAS Value name string OPERATIONAL Boolean True F
20. ris Enin ran NESNE KATA aT RA ea a a E E E euaaaeunnaates So WNO Dreco eeren E E E AEE EEA 5 6 Inside TEMPerature ccc eee e cece cece eeeeeeeeeeeeeeeeeeeeeneeeeeeeeenas eM eae ee ds E teenie ca endow n E S BO VAIN 3 DCCC eer nr ines roa tian tena E E nena mis Bed SY SUI ergata tee ace prance ewe tocar E cues orden E AR SO SSE ERRORS eee tate eas et ee ee Sek ZOOMING are ior eentere atone E E S12 Used functionality scicciraveiateane te crineiareeine nies tesiesareremass 5 13 Active functionality ccc cece eens eee e tees eeeeeeeeeeeeeeeeneas SA4 Updatable ICIS nse riventnatuaae eye tiara eon sean a emer A Eea 6 Warranty and limitation of liability ccc cece eceee seen eee eeeeeeees 8 Confidentiality cece cece eee ee eee eee eeee eee e sees eeeeeeeeeeeeeeeettananaaes D WISCENGNCOUS sincroreraseeaa EEE Rar ised N EEEE EEA File animeo IB OPC server User Manual 2 0 for the CD 2009 09 17 E rE A E ee ee re ern ee ENMICALIONG caanosscueeanunientcstetastucunpratervecentrnanebeugrienectinnesnanins Responsibilities 2 0 cece cece cece e ee eeee seen ee ee eeeeeeeeeaeeeeeeeeetenaggaes 4 Installation and PC requirements ccccceccceeeeeeeeeeeeeeeeeeeaes 4 OPCServer Manager vassetcccneerecitccagutcunstaseedrnceieeneteuetetesiavensmetceeus A PE A Erena a ee E E A EGS 1l Server INSTANCO esseri nAra TAEAE 2 Register the first server sssessrerrerererrrrerrrrerrrrrrrrerrue erver SeN S sivean
21. rite a printer driver for every printer So AutoCAD wrote the AutoCAD application and the printer drivers And WordPerfect wrote the WordPerfect application and the printer drivers They had to write a separate printer driver for every printer they wanted to support one for an Epson FX 80 and one for the H P Laser et and on and on In the industrial automation world Intellution wrote their Human Machine Interface HMI software and a proprietary driver to each industrial device including every PLC brand Rockwell wrote their HMI and a proprietary driver to each industrial device including every PLC brand not just their own Windows solved the printer driver problem by incorporating printer support into the operating system Now one printer driver served all the applications And these were printer drivers that the printer manufacturer wrote not the application developer Windows provided the infrastructure to allow the industrial device driver s solution as well Adding the OPC specification to Microsoft s OLE technology in Windows allowed standardization Now the industrial devices manufacturers could write the OPC DA Servers and the software like HMIs could become OPC Clients The resulting selfish benefit to the software suppliers was the ability to reduce their expenditures for connectivity and focus them on the core features of the software For the users the benefit was flexibility They could now choose software suppliers based on f
22. sition Often used to connect the buildings fire alarm system When active the all end product will take it s secure position When active the all end product in a zone will take it s secure position When the central lock 0 input on the building controller is active more then 2s all end product will take its secure position When a group lock 0 input on the internal sensor box is active more then 2s all end product in a zone will take it s secure position When active the all end product will take it s secure position When active the all end product in a zone will take it s secure position When active the all end product in a zone will take it s secure position When active the all end product will take it s secure position When active the all end product will take it s secure position When active the all end product will take it s secure position When active the all end product will take it s secure position When the central block input 100 on the building controller is active more then 2s all end product will take its secure position Active when a manual command is given from the PC When active the zone will take programmed position The position could be intermediate position 1 or 2 0 or 100 When active all zones will take 0 position Active when the central block inputs 0 or 100 on the building controller is active less then 2s a manual central command is executed Active when the group lock 0 inputs 0
23. somfy Animeo IB OPC server User Manual Manage OPCServer for Somfy animeo 184 Le ot Exit Save Settings Register Server Unregister Server View Serverlog Report Options Animeo Instance 1 a Somfy animeoIB 1 1 ___Animeoinstance2 SomFy animeolB 2 1 armeo instances ww Somfy animeolB 3 1 FOUNDATION ___Animeo instance 4 wa Somfy animeoIB 4 1 P Somfy animeoIB 5 1 ___Animeo instances w Somfy animeoIB 6 1 a Somfy animeolB 7 1 Animeo Instance amp a Somfy animeolB 8 1 Somfy SAS 50 avenue du Nouveau Monde 74300 Cluses France www somfty com File animeo IB OPC server User Manual 2 0 for the CD 2009 09 17 Page 1 of 23 sOomfy Table of content LEO Wa og OP gaa ee ne en ene nee ee ee eee 2 This is animeo UB Fresccedcecerecedeecanevicenteneeardancketeabesadewtensbacuatenasees 1 Priorities ennnennnunnnnnnnennrnnnnnnnrnnnrnananan nnan aran naana ra neran nrnna 2 COMTO MOE aeree a tae hae ee ep cee a 3 Communication within an animeo IB System cccceee eee 3 Animeo IB OPC Server cc cece cc cce cece cece eee eeeeeeeeeeeueeeeeueeneeenneneeags 1 2 3 2 2 2 3 3 3 a il l 4 S 2 4 NINN N N 4 4 2 4 4 4 4 4 3 4 4 4 5 Node SHCCHICALON sivsiscintcivavioiseawieacreriieeenaianae dine rtcianiseanans Sul NOG TUCU Gaee E E E E EE e N 10 a E E E E EAS 5 3 Outside temperat e escnorisiari nester ri