1. O1 PRIMEXTM 13 PC 3000 Specifications 2 RELAYS FUNCTION AUX RELAY COMMON TERMINAL AUX RELAY NORMALLY OPEN TERMINAL HIGH ALARM RELAY COMMON TERMINAL HIGH ALARM NORMALLY OPEN TERMINAL RELAY TERMINAL PUMP 3 NORMALLY OPEN TERMINAL PUMP 2 RELAY COMMON TERMINAL PUMP 2 NORMALLY OPEN TERMINAL PUMP 1 RELAY COMMON TERMINAL PUMP 1 NORMALLY OPEN TERMINAL LOW ALARM RELAY COMMON TERMINAL LOW ALARM NORMALLY OPEN TERMINAL CONNECTOR J3 INPUTS FUNCTION GROUND PUMP 1 AUX DISABLE INPUT PUMP 3 OVER TEMPERATURE SENSOR INPUT PUMP 2 OVER TEMPERATURE SENSOR INPUT PUMP 1 OVER TEMPERATURE SENSOR INPUT PUMP 2 AUX DISABLE INPUT PUMP 3 AUX DISABLE INPUT HIGH FLOAT INPUT MUTE RESET BUTTON INPUT PUMP 1 LEAK SENSOR INPUT PUMP 2 LEAK SENSOR INPUT PUMP 3 LEAK SENSOR INPUT ANALOG INPUT SENSE RESISTOR RETURN connect to ground GROUND ANALOG INPUT for loop powered devices connect to terminal 24 VDC LOOP POWER for loop powered devices connect to terminal NOTES HEADER AND PLUGS USE COPPER CONDUCTORS ONLY TORQUE REQUIREMENT 1 47 FT LB THIS UNIT OPERATES AT POLLUTION DEGREE 2 PRIMEX 14 PC 3000 Specifications ON 0 dn gt lt vNlt ii 119 dl 133378 HAI 0008 94 913 3000 Specifications 15 PRIMEX PRIMEX 12VDC IN TRANSMIT RECEIVE GND
2. 12VDC OUT GND GND WOO If SAV T 0 T C lt U n Z 4 J D C r J D lt m x D z J D D lt U J lt U X 16 SLANI f 24 VDC LEVEL IN GROUND SENSE RES PUMP 3 LEAK IN PUMP 2 LEAK IN PUMP 1 LEAK IN MUTE RESET HIGH FLOAT PUMP 3 AUX DIS PUMP 2 AUX DIS PUMP 1 TEMP IN PUMP 2 TEMP IN PUMP 3 TEMP IN PUMP 1 AUX DIS GROUND MOVE Dis 3000 Specifications LNO LNO 530 PC 3000 Specifications 17 PRIMEX 120VAC TRANSDUCER 0 Cet r j 1 LEAK LEAK LEAK 1 P2 TEMP Di P1 DISABLE DISABLE P3 DISABLE 3000 PUMP CONTROLLER FIG 4 HIGH FLOAT DRAWN BY WDB PAGE 1 OF 1 DWG P3_FIG4 DATE 2 28 06 th PRIMEX DWG NAME FIG 4 EXAMPLE PC 3000 TRIPLEX LIFT STATION CONTROLLER PRIMEX 18 PC 3000 Specifications PRIMEX CONTROLS k PC 3000 CONTROLLER DEPRESS FOR 10 SEC LEV XX X FT LP X DEPRESs UP amp FOR 10 SECONDS PUMPS LEVEL AT WHICH THE Z LEAD PUMP WILL START RANGE ERS LEVEL TRANSMITTER LEV XX X FT LP X LEV FT LP X TO
3. If the horn is enabled then it too will be activated As the level rises above the low alarm setpoint the low alarm condition will be cleared When the level rises above the lead pump on PRIMEX 3 PC 3000 Specifications setpoint the lead pump will be called to run Which pump is the lead pump is determined by the alternator The current lead pump is displayed on the right side of the top line of the display When the lead pump starts the liquid level should begin to fall as liquid is pumped out of the well When the level falls to the lead pump off setpoint then the lead pump will be stopped and the alternator sequenced if it is on If the level continues to rise it will reach the lag pump on setpoint and the lag pump will be called If the level then falls to the lag pump off setpoint then the lag pump will be turned off The lag pump will not be called if the total number of pumps setting is 1 If the lead and lag pump running do not cause the level to fall then the third pump will be called when the level reaches the lag2 on setpoint and if three pumps are selected for the maximum number of pumps If the level continues to rise then it will reach the high alarm setpoint and set a high alarm condition The high alarm light and relay will be activated If the horn is enabled then it too will be activated until the alarm condition clears or until the mute button is depressed 2 1 1 Single Float Backup Asingle float backup system is provided
4. s mimi PUMP CONTROLLER User Manual Ashland OH 800 363 5842 L PRI Detroit Lakes 888 342 5753 WWW PRIMEXCONTROLS COM Milford OH 513 831 9959 PN 1038551A 2013 SJE Rhombus Rev 09 13 PRIMEX is a trademark of SJE Rhombus Table of Contents 10 INIRODUGTION a 3 2 00OPERATION4 au aska sa aaa paz 3 2 1 PUMP DOWN OPERATION U uuu huk 3 2 led SINGDEEFLEOATP BAGKUPu 2 u ua 4 2 1 2 PUMP SEQUENGE TIMERS nrasane aaaea 4 2 1 3 TIME AT SETPOINT 4 2 14 FAILTOSTART IESTu u u L uuu uu 5 2 2 PUMP UP OPERA TON u I L 5 2 3 ALTERNATION uuu u uu uu 5 6 2 5 FRONT PANEL INDICATORS AND CONTROLS a 6 2 6 SETPOINT MENU uu u itive a a 8 2 7 CONFIGURATION 8 9 0 SPEGIFICATIONS aaah ads watasha 11 INPUTSIQNALS hoes 11 S 2 QUTPUT u D aaa Merrie nee 12 4 0 CONNEC TOR PINS 13 FIGURE 1 FRONT VIEW L 15 FIGURE 2 BACK VIEW E E ET 16 FIGURE 3 MOUNTING DIMENSIONS a 17 FIGURE4 EXAMPEE WIRING uuu u
5. LP X ETM3 XXXXX X HR DEPRESS NOTE AT ANY TIME YOU CAN DEPRESS THE TO RETURN TO THE MAIN SCREEN APPENDIX DEPRESS NEXT ll TIME FROM PUMP START epress NEXT Il FROM OTHER SIDE OF QUICK SETUP CHART 4 BACKUP CONTROLLER LEV XX X FT LP X OFF DELAY TIME BACKUP TIME XXXS 255 SEC SET TO ZERO TO DISABLE TO RUN CONFIRM LEV XX X FT LP X START TEST XXXS 63 SEC SET TO ZERO TO DISABLE LEV XX X FT LP X SEAL XXX YYYYY DEPRESS LEV FT LP X TEMP XXX YYYY DEPRESS NEXT J DEPRESS DEPRESS NEXT LEVEL AT WHICH THE DEPRESS NEXT LEVEL AT WHICH THE LEV XX X FT LP X HORN AUX R DEPRESS LEV FT LP X ALTERNATE XXXXX LEV XX X FT LP X MAX ON AT ONCE 1TO3 OUTPUT 15 4 LEV FT LP X A OUT LOW XX XFF OFFSET TO FULL SCALE OUTPUT IS 20 Ma LEV XX X FT LP X XX XFT A OUTHI PC 3000 Specifications
6. MAKE CHANGES IN THIS VALUE PRESS THE LEAD ON XX XFT oR DOWN HOLD THE MAX LEVEL DEPRESS NEXT IN THEN TURN THE ADJ KNOB 00 0 508 LEAD WILL STOP UNTIL THE VALUE IS WHEN COMPLETE LEVEL WHEN THE XDUCER 15 OUT OF THE WATER PRESS THE NEXT LEV XX X FT LP X LEV XX X FT LP X LEAD OFF DEPRESS OFFSET THE RETURN DEPRESS NEXT DEPRESS NEXT 00 i THE MAIN SCREEN NEXT LEVEL WHICH THE LAG PUMP WILL START NUMBER OF PUMPS IF THE CONTROLLER IS LEV XX X FT LP X CONFIGURED FOR ONLY LEV XX X FT LP X ONE PUMP THE MENU LAG ON XX XFT WILL SKIP TO THE HIGH HOW MANY PUMPS ALARM SETUP SCREEN DEPRESS NEXT DEPRESS NEXT 1103 LAG PUMP WILL STOP IF THE CURRENT VALUE HAS CHANGED THE SCREEN LEVEL AT WHICH THE WILL ASK IF YOU WANT TO SAVE THE CHANGE DELAY IN SECONDS BETWEEN PUMP STARTS SAVE Y N LEV XX X FT SAVE THE VALUE DEPRESS THE LEV XX X FT LP X LAG OFF START DELAY XXXS TO DISCARD THE CHANGE DEPRESS THE DEPRESS DEPRESS 255 SEC LEVEL AT WHICH THE LAG2 PUMP WILL START DELAY IN SECONDS BETWEEN PUMP STOPS IF THE CONTROLLER IS LEV XX X FT LP X CONFIGURED FOR ONLY LEV XX X FT LP X TWO PUMPS THE MENU LAG2 ON XX XFT WILL SKIP TO THE HIGH STOP DE
7. NORM LATCH SEAL FAIL WHEN SENSOR lt 50K OHM _ MANUAL RESET SEAL FAIL WHEN SENSOR gt 50K OHM RESETS WHEN CLEAR SEAL INVR AUTO R SEAL INVR LATCH SEAL FAIL WHEN SENSOR gt 50K OHM MANUAL RESET TEMPERATURE SENSOR SETUP USE THE UP AND DOWN KEYS TO SELECT ONE OF THE FOLLOWING TEMP NORM AUTO FAIL WHEN SENSOR OPEN RESETS WHEN CLEAR TEMP NORM LATCH TEMP FAIL WHEN SENSOR OPEN MANUAL RESET TEMP INVR AUTO TEMP FAIL WHEN SENSOR SHORTED RESETS WHEN CLEAR TEMP INVR LATCH TEMP FAIL WHEN SENSOR SHORTED MANUAL RESET AUXILLARY RELAY SETUP USE THE UP AND DOWN KEYS TO SELECT ONE OF THE FOLLOWING HORN AUX RELAY IS HORN RELAY AUX RELAY WILL CLOSE ON ANY SEAL FAIL AUX RELAY WILL CLOSE ON ANY TEMP FAIL AUX RELAY WILL CLOSE ON ANY SEAL OR TEMP FAIL COMMON ALARM RELAY HIGH LOW TEMP OR PUMP FAIL AUX R AUX SEAL TEMP AUX R ALL POWER UP MAIN SCREEN LEV XX X FT LP X ALL PUMPS OK Tae LEV XX X FT LP X ETM1 XXXXX X HR Tess LEV XX X FT LP X ETM VIEW DEPRESS DOW USE THE UP AND DOWN KEYS TO SELECT NORMAL OR JOCKEY PUMP ALTERNATIO TRHEE PUMP SYSTEMS gt USE THE UP AND DOWN KEYS TO SELEC THE MAXIMUM NUMBER OF PUMPS WHICH BE ON AT ONCE IF A OUT LOW IS SET HIGHER THAN A OUT HIGH THEN THE ANALOG OUTPUT WILL BE INVERTED gt ETM2 XXXXX X HR pessess Tess LEV XX X FT
8. where XX X is the current value for the lead pump on setpoint 3 you wish to change this value then use the UP or DOWN buttons or you can hold the ADJUST button down and turn the ADJUST knob until the value is correct After the value is correct then depress the MENU NEXT button to go to the next setpoint 4 If you have changed the value then the displays will ask SAVE Y N If you wish to save the new value then press UP YES if not then press DOWN NO The display should change to the next setpoint 5 The display should say LEAD OFF XX X FT where is the current lead off setpoint Repeat steps 3 and 4 above to make any changes you need to this setpoint 6 This process should be repeated until all of the setpoints have been examined and changed or until no further changes are required Once all setpoints have been done the screen will return to normal mode or you can at any time hit the MUTE RESET button and return to normal mode If the system is setup for 2 pumps then the setpoints for the lag2 pump will be skipped in the menu If the system is setup for only 1 pump then the setpoints for both lag pumps will be skipped The setpoints are stored in electrically erasable programmable memory EEPROM which will not lose its contents when powered down This is done every time the operator answers YES to the SAVE Y N prompt 2 7 Configuration Menu This menu is used to configure the PC 3000 controller for its application
9. LAY XXXS ALARM SETUP SCREEN DEPRESS I DEPRESS 127 SEC LEVEL AT WHICH THE Z LAG2 PUMP WILL STOP ALTERNATI O N MIN TIME FOR SETPOINT SATISFACTION LEV XX X FT LP X LEV XX X FT LP X LAG2 OFF TIME AT 5 XXXS DEPRESS NEXT DEPRESS NEXT 0 31 5 LEVEL WHICH THE THE HIGH ALARM WILL SET SET ALTERNATION ON HIGH ALARMLATCH UP LEV XX X FT LP X LEV FT LP X HI ALARM XX XFT HIGH LATCH PUMP IS DISPLAYED IN DEPRESS NEXT UPPER RIGHT OF DISPLAY DEPRESS NEXT CYES OR NO LEVEL AT WHICH THE THE LOW ALARM WILL SET CONTROLLER PUMP DIRECTION peron oram iare gt LEV FT LO ALARM XX XF UPP PUMP UP WITH LEVEL IN PSI PUMP UP DN XX DEPRESS QUICK SETUP CHART DEPRESS I OVER BACK PRIMEX APPENDIX PC 3000 Specifications PRIMEX PC 3000 QUICK SETUP CHART IF THE CURRENT VALUE HAS CHANGED THE WILL ASK IF YOU WANT TO SAVE THE CHANGE SAVE Y N TO SAVE THE VALUE DEPRESS THE TO DISCARD THE CHANGE DEPRESS THE CHANGES IN THIS VALUE PRESS THE OR OR HOLD THE IN THEN TURN THE ADJ KNOB UNTIL THE VALUE IS CORRECT WHEN COMPLETE PRESS THE NEXT SEAL LEAK SENSOR SETUP USE THE UP AND DOWN KEYS TO SELECT ONE OF THE FOLLOWING SEAL NORM AUTO R SEAL FAIL WHEN SENSOR lt 50K OHM __ RESETS WHEN CLEAR SEAL
10. LP 2 PRIMEXTM 5 PC 3000 Specifications For systems with two pumps alternation if on simply swaps lead pump duty between the two pump each pump cycle If there are three pumps alternation can be either of two options In normal alternation each pump cycle the next available pump is selected as lead so that if all pumps are available then each will be lead every third time The other option is jockey pump In this type of system pump 1 is a small pump and pumps 2 and 3 are large The small pump pump 1 is always the lead pump and the other two pump alternate as lag and lag2 When either of the two large pumps are on the small one is turned off This is useful in systems where demand can be low at some times and large at others 2 4 Startup When the PC 3000 is first powered up it executes an internal self test During this test many internal functions are checked and the displays are sequenced The system is controlled by an internal microcomputer which is monitored by a watchdog timer system which will restart the system in the unlikely event that the program fails to execute properly After the self test is complete several timers are started which prevent any relay outputs from activating until all of the system inputs have had a chance to settle and all of the input filtering has resolved to their proper values 2 5 Front Panel Indicators and Controls Figure 1 is a view of the front panel of the PC 3000 It includes eight LED lamp
11. This is normally only done once when the panel is built or at startup and would not be required again unless the configuration changed This menu is entered using the following procedure 1 Depress the UP and DOWN buttons at the same time and hold them until the first setting is displayed on the bottom line of the display This will take about 10 seconds 2 The display should say MAX LEVEL XX X FT where is the current value This parameter is the level when the level transmitter is at 20 mA full scale For example if the transducer is a 10 psig submersible pressure transducer then 10psi is 23 1 feet so adjust this value to 23 1 PRIMEX 8 PC 3000 Specifications 3 no change to this setting is required then press the MENU NEXT button To change this value we use the same procedure that we used on the setpoint menu Use the UP or DOWN buttons or depress the ADJUST button while turning the ADJUST knob After you have the value required depress the MENU NEXT button to go to the next parameter 4 If the parameter has changed then the display will ask SAVE Y N If the value is correct then press the UP YES button to save it or press the DOWN NO button to continue without saving the new setting 5 The display should say OFFSET XX X where XX X is the current value This parameter is the level when the level transmitter is at 4 mA For example if the transmitter is a submersible pressure transducer mounted 6 inches off of t
12. e to ground is less than 50 000 ohms and the alarm will auto reset if the alarm condition clears SEAL NORM LATCH In this mode the seal fail input is set to cause a failure if the resistance to ground is less than 50 000 ohms and the alarm will latch up and must be cleared by the MUTE RESET button SEAL INVR AUTO R In this mode the seal fail input is set to cause a failure the resistance to ground is greater than 50 000 ohms and the alarm will auto reset if the alarm condition clears SEAL INVR LATCH In this mode the seal fail input is set to cause a failure ithe resistance to ground is greater than 50 000 ohms and the alarm will latch up and must be cleared by the MUTE RESET button Use the procedure in steps 3 and 4 above to make any changes and go to the next parameter 14 The display should say TEMP XXX YYY This parameter is use to setup the mode of the temperature fail inputs Use the UP and DOWN buttons to select between the options available The options are TEMP NORM AUTO R In this mode the temp fail input is set to cause a failure if not shorted to ground and the alarm will auto reset if the alarm condition clears TEMP NORM LATCH In this mode the temp fail input is set to cause a failure if not shorted to ground and the alarm will latch up and must be cleared by the MUTE RESET button TEMP INVR AUTO R In this mode the temp fail input is set to cause a failure if shorted to ground and the alarm will auto reset if the alarm c
13. hange the value of the setpoint or parameter Depressing and holding the ADJUST button will cause the knob value to be placed in the current parameter or setpoint This can be used along with the up and down buttons to easily adjust all of the setpoints 13 32 CHARACTER DISPLAY This alpha numeric display has two lines of 16 characters each The first line always displays the current level in feet and the current lead pump The second line depends on the mode of the controller In normal mode this line displays pump status or the elapsed time meters Pressing the up or down buttons will sequence through the three elapsed time meters After 15 seconds this line will revert to pump status When pump status is displayed the display will read ALL PUMPS OK if there are no pump faults If there are pump faults such as temperature failures or seal failures they will be displayed one at a time every 2 seconds In either of the two menus the second line of the display shows the parameter being adjusted and its current value PRIMEX 7 PC 3000 Specifications 2 6 Setpoint Menu The setpoint menu is used to examine and chanoe the on and off setpoints for the pumps and the high and low alarm setpoints The menu is entered and updated using the following procedure 1 Depress the MENU button and hold it until the first setpoint appears on the bottom line of the display This will take about 10 seconds 2 The display should say LEAD ON XX X FT
14. he floor of the wet well then this setting should be 00 5 ft Use the procedure in steps 3 and 4 above to make any changes and go to the next parameter 6 The display should say HOW MANY PUMPS X where X is the current max number of pumps If this is a duplex station set this to 2 it is a triplex station then use Use the procedure in steps 3 and 4 above to make any changes and go to the next parameter 7 The display should say START DELAY XXXS where XXX is the current delay between pump starts This parameter is the minimum time between starting one pump and then starting another It is set in seconds from 0 to 255 Use the procedure in steps 3 and 4 above to make any changes and go to the next parameter 8 The display should say STOP DELAY XXXS where XXxX is the current delay between pump stops This parameter is the minimum time between stopping one pump and then stopping another It is set in seconds from 0 to 127 Use the procedure in steps 3 and 4 above to make any changes and go to the next parameter 9 The display should say TIME AT SP XXXS where XXX is the current setpoint time This parameter is the minimum time a setpoint condition must be continually met for the required action to take place for example starting a pump It is set in seconds from 0 to 31 Use the procedure in steps 3 and 4 above to make any changes and go to the next parameter 10 The display should say PUMP UP PUMP DN XX where XX is the current setting Th
15. in pump down mode only It can be useful if the primary level sensor fails A single normally open float switch is connected to the float input and suspended in the well at a point above the normal operating levels of the system In this way the float will only be submerged if level rises above that required to call on all available pumps The backup system is enabled by setting a backup time in seconds in the backup time setpoint of the configuration menu If this time is zero then the backup system is disabled If the high float is activated and backup is enabled and the controller is not already calling for all available pumps then the backup mode is initiated The float light on the front panel is turned on and the lead pump is called to run At the same time two timers are started one for 30 sec and one for 60 sec If the high float opens comes out of the liquid then these two timers are cleared and no further pumps will be called The lead pump will remain on for the period of time set in the backup time setpoint If the 30 second timer expires before the high float opens then the lag pump will be called if there are at least 2 pumps If the 60 second timer expires before the high float opens then the second lag pump will be called if there are three pumps All pumps will be sequentially turned off after the high float has been open for a period of time equal to the backup timer setpoint The float light on the front panel will remain on
16. inputs or pump disable inputs These inputs are designed to detect a short to ground VOLTAGE WHEN OPEN 5 0 VDG CURRENT WHEN SHORTED 0 5 3 1 5 MUTE RESET and High Float Inputs The PC 3000 has 2 inputs which are for the high float and for the MUTE button in the panel These inputs are designed to detect a short to ground VOLTAGE WHEN OPEN 5 0 VDG CURRENT WHEN SHORTED 0 5 3 2 Output Signals The PC 3000 has one analog output one loop supply output and six relay outputs PRIMEX 12 PC 3000 Specifications 3 2 1 Analog Output This is an analog 4 20 mA which is proportional to the system level It is self powered referenced to ground and not isolated MAXIMUM VOLTAGE OUT 10 VDC 3 2 2 Loop Power Supply This output is a 24 VDC output intended to power a level transmitter It is not isolated and is referenced to ground VOLTAGE OUT 22 TO 28 MAXIMUM CURRENT 30 mA 3 2 3 Relays The PC 3000 has 6 form SPST relay contacts which are used to control horns lights and motor starters MAXIMUM VOLTAGE 140 VAC MAXIMUM CURRENT 3 AMPS 4 0 CONNECTOR PINS CONNECTOR J1 POWER AND COMMUNICATION PIN FUNCTION 1 MAIN POWER IN HOT TERMINAL 120 VAC MAIN POWER IN NEUTRAL TERMINAL MAIN POWER IN GROUND TERMINAL 12 VDC INPUT RS 232 TRANSMIT TERMINAL RS 232 RECEIVE TERMINAL GROUND ANALOG OUT 4 20 mA OUTPUT GROUND 10 12VDC OUTPUT 0 1 AMP MAX 11 GROUND 12 GROUND
17. ion to most transducers and transmitters Adjustments are provided for both scale and offset e Inputs for pump seal leak sensors and pump over temperature sensors with display messages for out of specification conditions Fully scaleable 4 20 mA level output transmitter e Built in single float backup system for pump down applications Three auxiliary inputs which can be pump disable or pump run confirmation inputs for a fail to start test Built in horn relay with internal and input for external mute button Relay outputs for both high and low level alarms with adjustable setpoints Individually selectable on and off setpoints for up to three pumps All inputs are filtered and transient protected e Built in software no programming required All inputs operate on low voltage and current e Input power is 115 V AC internally fused and transient protected All terminal strips unplug without removing the wires for easy field replacement 2 0 OPERATION 2 1 Pump Down Operation Pump down is used in applications like wastewater lift stations where a liquid flows into a tank or well and must be pumped out As liquid flows in the level in the well rises The level is continually monitored by the level transmitter which sends a 4 20 mA signal to the controller which displays the level on the first line of the display If the level is below the low alarm setpoint then the low alarm light and relay are activated
18. is setting determines the overall pump mode of the controller If your system is draining a tank or well such as a lift station then set it to DN If you have a system which fills a tank or pressurizes a discharge then set this UPF for level display in feet or UPP for level in PSI Use the procedure in steps 3 and 4 above to make any changes and go to the next parameter 11 The display should say BACKUP TIME XXXS where XXX is the current float backup time This parameter is the time period after the high float comes out of the water that the pumps will remain on To disable the float backup system set this to 000 It is set in seconds from 0 to 255 Use the procedure in steps 3 and 4 above to make any changes and go to the next parameter 12 The display should say START TEST XXXS where XXX is the current start test delay time This parameter is the maximum time delay between a pump being called and the confirming pump run signal on the AUX DIS input To disable the fail to start test set this to 000 It is set in seconds from 0 to 63 Use the procedure in steps 3 and 4 above to make any changes and go to the next parameter PRIMEX 9 PC 3000 Specifications 13 The display should say SEAL XXX YYY This parameter is use to setup the mode of the seal fail inputs Use the UP and DOWN buttons to select between the options available The options are SEAL NORM AUTO In this mode the seal fail input is set to cause a failure if the resistanc
19. is time is zero then this test is disabled If the start test is enabled then the AUX DIS inputs for each pump must be connected through a dry contact to ground These contacts must close and short the AUX DIS input to ground when the pump is running The auxiliary contact on the starter or a switch on the check valve arm can be used If the start test is disabled time 0 then these inputs are pump disable inputs For example lets assume that the test is enabled with a START TEST time of 15 seconds When a pump is called a timer is started for that pump If the timer reaches 15 seconds and the AUX DIS input for that pump has not been shorted to ground then fail to start test failure is set for that pump The pump is then disabled and the next available pump is called in its place This failure condition is displayed on the front panel and will remain active until reset by either a reset button or reset input The high level alarm will also reset this condition This is to make sure that a broken or misadjusted check valve switch does not cause an overflow 2 2 Pump Up Operation Pump up mode is used in situations like water distribution where the pumps must maintain a pressure or fill a tank like a water tower For the purposes of this description assume we have three pumps which will be used to maintain the level in a water tank The level is sensed by pressure transmitter mounted in base of the tank and all three pumps send water to the ta
20. iscrete inputs They are all transient protected and use both electronic and software filters to reduce noise and improve reliability PRIMEX 11 PC 3000 Specifications 3 1 1 Transducer Input This is an analog 4 20 mA input which serves as the level sensing input for the controller A 125 ohm resistor is used to convert the current input to a voltage which is converted to digital information using a 12 bit analog to digital converter If the input signal is greater than 20 mA or less than 4 mA then an transducer error lamp on the front panel will illuminate The level data is processed through a 16 stage rolling average filter in the microcomputer to reduce sensitivity to wave action and other noise Figure 4 shows how this input is connected to a loop powered transducer INPUT IMPEDANCE 125 OHM MAXIMUM VOLTAGE 5 VDC LEVEL ACCURACY 0 5 3 1 2 Seal Fail Inputs The PC 3000 has 3 inputs for the leak sensors commonly found in submersible pumps The microcomputer measures the resistance from the input to ground to determine ifa leak has occurred VOLTAGE WHEN OPEN 5 0 VDG CURRENT WHEN SHORTED 0 5 3 1 3 Temperature Fail inputs The PC 3000 has 3 inputs for the over temperature sensors commonly found in pump motors These inputs are designed to detect a short to ground VOLTAGE WHEN OPEN 5 0 VDG CURRENT WHEN SHORTED 0 5 3 1 4 Aux Disable Inputs The PC 3000 has 3 inputs which can either be run confirming
21. jockey pump alternation Pump 1 is lead the other two pumps alternate and pump 1 is turned off if pump 2 or 3 is on 17 The display should say MAX ON AT ONCE X where X is the current max number of pumps which can be on at the same time This would normally be set to the number of pumps the station has unless some factor such as available power prevents proper operation with all pumps running at the same time Use the procedure in steps 3 and 4 above to make any changes and go to the next parameter 18 The display should say A OUT LOW FT where is the level at which the analog output signal is at its minimum or 4 mA This parameter and the next one set up the proportional scaling of the analog output of the PC 3000 Use the procedure in steps 3 and 4 above to make any changes and go to the next parameter 19 The display should say A OUT HI XX X FT where 1 the level at which the analog output signal is at its maximum or 20 mA Use the procedure in steps 3 and 4 above to make any changes and depress the MENU NEXT button which will complete setup and return you to the main display 3 0 SPECIFICATIONS General specifications SIZE H 5 9 W 7 2 D 3 5 WEIGHT 1 8 LB OPERATING TEMPERATURE 20 70 STORAGE TEMPERATURE 30 C TO 80 INPUT POWER 120 10 50 60 Hz 0 3 Amp max 3 1 Input Signals The PC 3000 has one analog input from the level or pressure transmitter and eleven d
22. nk As water is dispensed from the tank the level drops If the level drops far enough to reach the lead on setpoint then the lead pump is called to run This should cause the level to rise until the lead off setpoint is reached and the pump is shut down If the alternator is on then the lead pump will be sequenced to the next available pump If the level continues to fall then the lag on setpoint will be reached and the lag pump will be called As in pump down operation each pump has separate on and off setpoints and there are setpoints for high and low alarm Unlike pump down the pump up mode does not have a float backup system 2 3 Alternation The 3000 has an automatic alternation system which can be used to cause different pump to be used each pump cycle This is useful to equalize pump wear When the alternator is off the lead pump can be selected and that pump will always be called first The alternator on the PC 3000 is controlled by a toggle switch on the front panel When the switch is in the up position the alternator is on and the lead pump will be changed each cycle When the switch handle is in the center position the alternator is off and the lead pump is selected by pushing the handle down The handle has a spring return from the down position Each time the handle is pushed down the lead pump will be incremented to the next available pump The current lead pump is displayed on the right side of the first line of the display
23. ondition clears TEMP INVR LATCH In this mode the temp fail input is set to cause a failure if shorted to ground and the alarm will latch up and must be cleared by the MUTE RESET button Use the procedure in steps 3 and 4 above to make any changes and go to the next parameter 15 The display should say AUX R XXX This parameter is use to setup the function of the auxiliary relay output Use the UP and DOWN buttons to select between the options available The options are PRIMEX 10 PC 3000 Specifications HORN The aux relay is for an audible alarm horn The horn will sound on the following conditions High Level Low Level and H L Float SEAL The aux relay will close if there is a seal fail condition on any pump TEMP The aux relay will close if there is a temperature fail condition on any pump SEAL TEMP The aux relay will close if there is a seal fail or a temperature fail condition on any pump Use the procedure in steps 3 and 4 above to make any changes and go to the next parameter 16 The display should say ALTERNATE XX where XX is the current setting This parameter determines what type of alternation will be used If the controller is set for 1 or 2 pumps then this parameter is not used Use the procedure in steps 3 and 4 above to make any changes and go to the next parameter The options are NORMAL controller will use normal sequential alternation 1 2 3 2 3 1 3 1 2 1 JOCK The controller will use single
24. s a 32 character LCD display 5 push buttons one toggle switch and one adjustment knob They have the following functions 1 PUMP 1 THRU PUMP 3 LAMPS These three green LED lamps indicate which pump is currently being called 2 OFF LAMP This green lamp indicates that no pumps are currently called to run 3 HIGH LAMP This red lamp signals that the level is above the high setpoint 4 LOW LAMP This red lamp signals that the level is below the low setpoint 5 FLOATS LAMP This red lamp will be on if the system has had a float backup cycle since the last reset or power up 6 XDUCER LAMP This red lamp signals that the main level sensor input is outside of its normal range of 4 20 milliamps This is useful for detecting transducer failures 7 ALT SWITCH The alternate switch will turn alternation on when up and off when in the center position When it is pushed down the lead pump will be sequenced to the next available pump The current lead pump is indicated on the first line of the display 8 MENU BUTTON This button is depressed and held for 10 seconds to enter the setpoint menu PRIMEXTM 6 PC 3000 Specifications 9 UP YES BUTTON This button has several functions depending on the mode of the controller When the controller is in normal mode not in one of the menus this button causes the bottom line of the display to sequence between pump status and the three elapsed time meters After 15 seconds the bottom line of
25. the display always reverts to pump status in normal mode When the controller is in one of the two menus this button is used to increment the current parameter being adjusted or to tell the system to save the new value 10 DN NO BUTTON This button has several functions depending on the mode of the controller When the controller is in normal mode not in one of the menus this button caused the bottom line of the display to sequence between the pump status and the three elapsed time meters When the controller is in one of the two menus this button is used to decrement the current parameter being adjusted or to tell the system not to save the new value 11 MUTE RESET BUTTON This button will reset any current latched up alarms such as temp fail or backup float It will also silence the horn if an alarm is currently active 12 TEST ADJUST BUTTON AND KNOB The function of these two operators depends on the mode of the controller When the controller is in the normal not menus mode these operators are used to test the system When the TEST button is depressed and held the ADJUST knob will be the level for the system As you turn the knob up and down the level will go up and down This will call on pumps and make alarms just as if the level was coming from the transducer The controller will switch back to the transducer 8 seconds after the button is released When the controller is in one of the menus these operators are used to c
26. until cleared by the reset mute button on the panel or the external reset mute button 2 1 2 Pump Sequence Timers In both pump up and pump down modes there are two timers which prevent more than one pump from turning on or off at the same time These timers prevent excess power loads when pumps are turning on and some hydraulic problems water hammer when pumps are being turned off 2 1 3 Time At Setpoint The PC 3000 has a feature which prevents any pumps from being turned on or off until a setpoint condition has been satisfied for a minimum time This minimum time is the TIME AT SP setting in the setup menu and can be set from 0 to 31 seconds As an example assume this setting is set for 8 seconds and we have a pump down system lift station Then the water level in the tank must exceed the lead on setpoint continuously for 8 second before the lead pump will be called There is not much need for this in most lift stations as the level changes slowly but this feature can be very PRIMEX 4 PC 3000 Specifications useful in water pressure pump up systems where the pressure may swing wildly for several seconds after a pump is turned off or on If this time is set longer than the pressure takes to settle then no further pump calls will happen until the new pressure has stabilized 2 1 4 Fail to Start Test The PC 3000 has an optional fail to start test This optional test is controlled by the START TEST time in the setup menu If th
27. uuu uuu a ua aaa yaa A EEE ERREG 18 QUICK SET UP CHART APPENDIX PRIMEXTM 2 PC 3000 Specifications 1 0 INTRODUCTION The PC 3000 is a general purpose pump controller designed to control up to 3 pumps in either pump up or pump down applications It sequences pumps on and off in response to changes in level pressure or flow The primary sensor input is 4 to 20 mA current loop which can be connected to any sensor which has a 4 20 mA output When used to control level in a tank or well the input is usually connected to a pressure transducer or ultrasonic transmitter loop power supply is provided in the PC 3000 The PC 3000 can be configured for many applications using it s easy to use front panel user interface Wiring is easy using removable terminal blocks on the back cover Field replacement is easy because the terminal blocks unplug from the controller so no wires need to be disconnected FEATURES 32 character alpha numeric liquid crystal display for level status and setpoint information Alternation selection switch on front panel to turn alternation on and select the lead pump if alternation is off Simple menu structure for easy display and modification of setpoints and setup configuration e Built in elapsed time meters for all pumps They are nonvolatile and easily examined from the front panel 4 to 20 mA main sensor input with loop power supply for easy connect
Download Pdf Manuals
Related Search
Manual manual manualslib manuale digitale manual timesheet manual transmission manually meaning manual wheelchair manual definition manual arts high school manual muscle testing manually update your device drivers windows manually register devices with autopilot manual transmission cars for sale manual transfer switch manual for courts martial manual blood pressure cuff manualidad manual digital manual muscle testing grades manuale manual pdf manuale digitale art manuale digitale clasa 6 manual muscle testing grading manuale digitale edu ro
Related Contents
Bedienungsanleitung GERIMA SKF User Guide - ePlanning Scotland La Gestion des talents A user's guide to tabu search* Worldwide Homefurnishings 513-194RC Instructions / Assembly Class II, Type A2 and B2 Biological Safety Cabinets Ideal Graphic application 1110 (sharp knife 25°) Building Status Unit III Copyright © All rights reserved.