Home
GWY-610 (Ethernet Gateway) USER`S MANUAL
Contents
1. 7 TH A TH NEKT Bi Bi PREVIOUS CPTOMUX 3 or 82 8 12 ETHERNET CABLE Cross Over Cable Connections Hook underneath RJ 45s From Ethernet switch to GWY 610 it should be straight cable and from GWY 610 to PC it should be cross over cable Doc UMAN GWY 610 1106 56 REVISION 2 Cable Diagram 8 13 YOKOGAWA CONTROLLER TO GWY 610 YOKOGAWA CONTROLLER SIDE GWY 610 SIDE WIRE OUTS DB9 MALE SIGNAL FROM PLC Shield Wire RS485 KA o ERE IN Shield Wire DB9 MALE PINOUTS Doc No UMAN GWY 610 1106 57 REVISION 2 Cable Diagram IBM CABLE a PC SIDE GWY 610 SIDE gt T yin o DB9 FEMALE DB9 MALE RS232 Shield Wire RS232 8 1 Doc UMAN GWY 610 1106 58 REVISION 2
2. ee Ni I ae re Dena Dera Com oa i i n TON i xx i i 1 TE Hafan TE IC 114 1 7 This a saa ba best comsnso son i mm d cintia and io check d m 5 a a phar cee Boon it RE an MEN g 1 This is implemented only for master drivers that support IDB 2 First register present in first row of IDB is taken as default communication register 3 The no of words field for default communication register are 1 user can change the value to maximum of 255 whichever is applicable 35 15 valid in above case Doc UMAN GWY 610 1106 25 REVISION 2 GWY 610 Features 4 7 Recipes Purpose To provide user definable write of configuration properties or control sequences at power on to the external Slave Devices Location User can access these Recipes Settings gt gt Recipes menu In case of some Slaves it is necessary to write configuration properties or control sequences at power on Drives Inverters generally require this kind of sequence After power on before Gatewa
3. Doc No UMAN GWY 610 1106 32 REVISION 2 on Communication Drivers 5 1 6 Control Word for IDB Purpose To provide user s control over the IDB block execution during run time 16 internal memory registers are added in each master driver IMOOOO to IM0015 Bits of these registers will control 255 IDB block executions lf bit value is 1 then IDB block will execute and if it is 0 then IDB block will not execute Initially at power on all internal memory register will have value OxFFFF so all IDB block will execute After communication is totally established user can change internal memory data to execute required IDB block Why when is the Control Word for IDB required Let us assume the User has defined different Blocks in the Project in Master Slave Mode that gives rise to 20 blocks in IDB of M1 as this is a Master Driver Now if the external Master M2 requires execution of only few of those 20 IDB blocks then using the Control Word for IDB user can select only the blocks that need to be executed currently The visible advantage is this will soeed up the Block execution and data exchange rate This feature is useful in Master Slave mode Bake Fade Tim Tiri fama E i Prise aeui __ aum onn 1 m
4. Doc UMAN GWY 610 1106 35 REVISION 2 Typical Projects 611 Connect Toshiba link port protocol PLC e g T1 T2 as Modbus TCP Server on Ethernet Network 1 Launch gateway set up software 2 Select GWY 6XX from product list as shown below GW Y 00 3 After selecting below given image will appear Select COM1 and COM2 side protocols and click Configure Caleway GWY 6XX thernet Gaicway Com Protocol Modbusi Gatewary 25 Sans m Toshiba Port PLC n T T3 V Series Teshiba ASD Yokogama controller AB D pastan THOMSON TECHO CONTROLLER Optomun FLLS Series Master SELECTED PROTOCOL PLC Name Toshiba T Link Pari PLC PLC Model TI Click Configure Project button on Toolbar Ta Configure the Project m m Upload Pt Upload Sy Protocal Modbus TCP Gabesamy Master Modbus TP Gateway Save SELECTED PROTOCOL PLC PLC Model ATU Click Configure Project button on Toolbar Cantigure the Project UMAN GWY 610 1106 REVISION 2 36 Typical Projects 4 Configure the project as shown below _ rnet Galmway Eat lew Communi Hardware Test Settings Block No Slave Port Slave A
5. A Entity PLC Iw Y xxx IP Address 132 158 0 250 subnet Mask 295 255 255 0 Default Gateway Address 192168 D 1 Input ww ard 3 xxx 30 30 Output COME Wek la LA A m a m va E v Aes AACE Ammer Doc UMAN GWY 610 1106 2 REVISION 2 GWY 610 Features CASE b Operation in case of Modbus TCP Client 1 Internal memory register 25 1 0025 is used for Input and Internal memory register 26 1 0026 is used for Output So 1 0025 is read only and 0026 is write only 2 While configuring the project user should map Input Word and Output Word to any register of serial driver This way user can access Input Word and Output word reo PLC an inna Conn i Fidi Bos m xxi 1 d 40000 an TETIT 1 e d TX Doc No UMAN GWY 610 1106 28 REVISION 2 Communication Drivers NOTE COMMUNICATION DRIVERS Doc UMAN GWY 610 1106 29 REVISION 2 on Communication D
6. Doc No UMAN GWY 610 1106 REVISION 2 52 Cable Diagram 8 8 TOSHIBA VF S11 TO GWY 610 TOSHIBA VF S11 SIDE GWY 610 8 MODULAR DB9 MALE CONNECTOR RS232 Shield Wire RS232 SIGNALS Pin SIGNALS Ka n 8 PIN MODULAR CONNECTOR PINOUTS 5 VIEW DB9 MALE PINOUTS FRONT VIEW Pin 1 Left side A Cable insert Cable insert end end Doc UMAN GWY 610 1106 53 REVISION 2 Cable Diagram 8 9 NS TO GWY 610 NS SIDE GWY 610 SIDE mN 9 MALE 5232 Shield Wire Shield Wire to DB9 body 9 MALE RS232 089 5 UMAN GWY 610 1106 REVISION 2 54 Cable Diagram 8 10 THOMSON TECHNOLOGY CONTROLLER TO GWY 610 EC P 117 00 THOMSON TECHNOLOGY GWY 610 SIDE la CONTROLLER lt 8 PINMODULAR 089 MALE CONNECTOR 85485 Shield Wire RS485 1 MODULAR hield Wi 8 uu CTO o 77 EN MALE FRONT VIEW R H S VIEW PINOUTS Pin 1 Left side Cable insert Cable insert end end Doc UMAN GWY 610 1106 56 REVISION 2 Cable Diagram 8 11 OPTOMUX TO GWY 610 SHIELDS TIED TO EARTH GROUND AT ONLY ONE POINT 25 Lo
7. HARDWARE In this chapter Dimensional Details And Mounting Instructions Communication Port Details LED Status Doc No UMAN GWY 610 1106 9 83 REVISION 2 2 1 Dimensional details And Mounting Instructions GWY 610 B unit can be shipped with a separate DIN rail plate which can be attached to the unit if desired User can use the unit with or without the DIN rail plate Following sketch shows dimensional details of Gateway with the DIN rail plate 70 00 Q 299 Follow instructions given below 1 Attach the DIN rail plate to the unit using the clamps on the DIN rail plate 2 Pull out the clip of the plate 3 Put the unit on the DIN rail 4 Push the clip in to secure the unit on the DIN rail reaal Doc UMAN GWY 610 1106 10 83 REVISION 2 2 2 Communication Port Details GWY 610 has three communication ports COM1 Ethernet and Pass Through Port COM1 port is compatible to RS232 RS422 RS485 and CMOS signal levels Pinout of this port is given as follows 1 Signal Ground RX RS422 RS485 D RS232C CMOS RS422 RS485 RX RS422 RS485 RS422 RS485 TXD CMOS 5VDC DO NOT USE DB9 Female Do not use no 6 of PLC1 COMI Refer our website www renuelectronics com for your specific Cable requi
8. OW T A Gateway E Coml Protocol Protocol Madeesisateway Masher Modbus TOR Gsbsway Master se Sle Toshiba TiLink Port PLC Modbus Gabeway as Shave 11 Opbomux emere Shep 7 Mico Pics DP LPUSS Loge Senes Meher SELECTED PROTOCOL SELECTED PROTOCOL PLC Toshiba T Link Port PLC PLC RTU PLC Model TI PLC Model ATU Click Confiqure Project button an Click Configure Project button on Toolbar Ta Configure the Project Configure the Project reas Doc No UMAN GWY 610 1106 39 REVISION 2 Typical Projects 3 Configure the project as shown below 1 Port PLC 1 aT Median am 1 15 a 5 iai Prat PLC i Ta 11 Node Addr Staring Add DataType Wordsfts SHpFor Cyde Shp on Comm 1 IDE Addr 1 fai Bodas d 4 40000 1 ista 166 D III YR Deere PU UMAN GWY 610 1106 40 REVISION 2 Typical Proje
9. man UND Perd ME Tang uro i Node Addr Starting Add DataType WordsiBits Scaling Skip For Cycle Skip on Comm Fail Value if 53 Eii Adeo Lors il LE xa Doc UMAN GWY 610 1106 33 REVISION 2 Typical Projects TYPICAL PROJECTS In this chapter Project Setup UMAN GWY 610 1106 34 REVISION 2 Typical Projects 6 1 Project Setup This Chapter explains how a simple Gateway project can be created and tested To develop a Gateway system select appropriate Gateway model depending on the system requirements A new project can be created as follows 1 Define the Gateway System 1 1 Protocol of Device s connected to PLC1 1 2 Protocol of Device s connected to PLC2 Load Microsoft Windows based Gateway Setup software Select devices to be connected on two ports Define Blocks for data transfer Set the communication parameters for the selected devices Set conditions for block execution if required Repeat Cycle Control Word etc Apply power to Gateway Download the Project and Communication Drivers into Gateway Remove Configuration Cable from PLC1 Connect Gateway Device cable to PLC1 Test system e o D oS
10. YO Green OFF Digital output 0 is ON O Digital output 0 is OFF Y1 Green OFF Digital output 1 is ON ON Digital output 1 is OFF Table continued on next Doc No UMAN GWY 610 1106 12 REVISION 2 Hardware OFF Digital output 2 is ON Digital output 2 is OFF OFF Digital output 3 is ON ON Digital output 3 is OFF Note For more information please refer section 3 3 1 For more information on LED behaviour refer section 3 5 1 Not all models support I Os respective LED s Doc No UMAN GWY 610 1106 13 83 REVISION 2 GETTING STARTED In this chapter Introduction GWY 610 GWY 610 Operation Quick Start Ethernet GWY 610 Function UMAN GWY 610 1106 14 83 REVISION 2 3 1 Introduction to GWY 610 GWY 610 is a communication bridge between Ethernet interface on one side and various serial protocols on the other side GWY 610 allows serial devices to act as Modbus TCP Client or Modbus TCP slave on Ethernet On COM side it supports serial protocols e g Modbus Master Modbus Slave and on 2 side it has Modbus TCP Client and Modbus TCP Server port acts as pass through for GWY 610 is externally powered from 3 pin terminal block and power is isolated from communication ports Both the communication ports are also isolated from
11. Modbus TCP Gateway as Slave ee WordsiBts Slave Port Slave Address Target PLC Target ID 1 10 Modbus TCP Gateway as Slave 400001 Modbus Gateway as Master 1 400001 12 10 Modbus TCP Gateway as Slave 400015 ModbusiGateway as Master 400015 dwie baaie wi m m L Chan koi Cornu mcloud FS Eee _ _____ ES Cmm Block 1 maps 10 words of Modbus Gateway as Slave starting from 400001 to Modbus Gateway as Slave starting from 400001 Block 2 maps 12 words of Modbus Gateway as Slave starting from 00001 to Modbus TCP Gateway as Slave starting from 000001 Doc UMAN GWY 610 1106 22 REVISION 2 GWY 610 Features In above example request from Modbus Master is executed as follows 1 Modbus Master connected on serial port 1 sends command to Gateway for setting holding register 400001 2 Gateway searches defined Blocks and checks whether this register is mapped to any Modbus 3 In example holding register 400001 Modbus Gateway as Slave is mapped to 400001 Modbus TCP Gateway as Slave in Block 1 Gateway accepts this command and sets 400001 Modbus TCP Gateway as Slave Master sends a command to read write a register coil not defined in any Block then Gate
12. a unit substitution basis only Do not attempt to remove replace or service any printed circuit board compo nents or any hardware software related with display product If problem within the display product occurs contact the factory for service information or repair NOTE Renu Electronics Pvt Ltd is dedicated to providing complete customer service and customer satisfaction lf you have any comments criticisms about how to improve the product features reliability Please make a note of the problem improvement and notify us We are always open to new ideas and improvements So please let us know your ideas and comments IMPORTANT Gateway Products are intended to be Protocol Converters Data Sharer devices that can also take control actions on request of device being connected It is assumed that user is well acquainted with the PLC Inverters Controllers being used Any Mechanical or Electrical Modification to this Unit will void all Warranties Contents INTRODUCTION 6 1 1 Purpose of this manual 7 1 2 Introduction to Gateway 1 3 GWY 610 Specifications 8 HARDWARE 9 2 1 Dimensional details And Mounting Instructions 10 2 2 Communication Port Details 11 23 LED Status 12 GETTING STARTED 14 3 1 Introduction to GWY 610 15 3 2 GWY 610 Configuration 15 3 3 Configuration of GWY 610 IBM Download 15 3 3 1 When GWY 610 can accept configuration 16 3 4 Quick Start To Ethernet 16 3 5 GWY 610 functionality and corresp
13. devices share data through Gateway Gateway communicates with a device to get the information required by the device connected on the other port The device that requires data is called Destination Device and the device that provides data is called Source Device Information could be value of a PLC register status of a PLC coil Command from Source Device to Destination Device to perform any action at the destination end Configuration Of Gateway Note Please refer IBM Download in section 3 4 Normal Operation Modbus TCP Client Server Serial Port Pass Through Port HMI Connect Modbus TCP devices to Gateway via Ethernet port and serial device PLC or Inverter via PLC s commu nication port correct cables are required and PLCs can easily exchange information through Ethernet At the same time local HMI can communicate with PLC connected on serial port Doc No UMAN GWY 610 1106 7 REVISION 2 Introduction 1 3 GWY 610 Specifications Power LED s Communication Ports 24 V DC 2 5 W 16 LED s for status indication 3 Communication ports with 5232 RS422 RS485 CMOS ETHERNET RS232 Isolation between communication ports and Power supply through DC DC coupler is 1 KV 1 PLC1 COM2 PLC2 Pass Through for COMI Connects to PC for setup download or connects to PLC1 at runtime Connects to PLC2 at run
14. driver and data is stored in internal database memory So time required for read cycle is optimized Write operations are on comparison basis Since all the registers data is already present in internal database memory of Gateway driver every time before performing Write operation data is compared with the internal memory data In this way unnecessary write operations can be avoided The PLC2 driver uses this data whenever needed according to gateway project Every Master driver has its own internal database of 3KBytes Data fetched by the master driver from external slave device is loaded into its internal memory in continuous fashion irrespective of block execution of Gateway project Background communication Enable Disable default setting depends on PLC or Device protocol The speed of data transfer is improved because of Internal database since it reduces the number of block executions required by the Gateway software Background Read Opera Write Opera Write in Internal Master Driver 3KBytes Write in External Figure 1 explains the operation of Master Master mode with background communication Doc UMAN GWY 610 1106 31 REVISION 2 h on Communication Drivers Advantages of background communication 1 Better speed For background communication each master driver has internal memory i e 1500 words If background communication is enabled master driver will use inputs
15. each other has three communication ports one with Ethernet interface 10 100 Mbps and one serial port with RS232 RS422 2 or 4 wire RS485 300 to 115 2K second serial port with RS232 300 to 115 2 Note For more details on pass through please refer to section 5 1 5 3 2 GWY 610 Configuration GWY 610 can communicate with serial and Ethernet devices using appropriate cables and configuration Microsoft Windows based configuration software Gateway Setup configures the GWY 610 unit Configuration means making the GWY 610 unit work as per user application Complete configuration for a GWY 610 using the Gateway Setup is termed as a Project A Project consists of Devices to be attached on two ports Communication settings for two ports to communicate with two devices Register addresses for data transfer Conditions for data transfer etc GWY 610 can now communicate with the specified devices without any change in the GWY 610 hardware To communicate with a device GWY 610 needs Communication Drivers for the devices and Gateway Device communication cables Each Device has a unique and predefined protocol for communication GWY 610 driver has this protocol to communicate with the desired device As two devices are connected on GWY 610 it requires two drivers for communication 3 3 Configuration of GWY 610 IBM Download User MUST download Firmware Project PLC1 driver and PLC2 driver in Gateway before install
16. mode rate While initialization it checks for IP conflict lf IP conflict occurs ETHERNET RED LED is lit for a second and then it enters to configuration download mode for 10 seconds After 10 seconds it again checks for any IP conflicts This cycle is repeated till the valid configura tion with valid IP address is downloaded If there is no IP conflict GWY 610 enters the Serial Init phase Serial Init phase Here the GWY 610 starts scanning nodes that are connected on COM1 port OK LED is lit green at this time If GWY 610 does not get response from COM port it enters in configuration download mode The OK LED flashes green at this stage It remains in configuration mode for nearly 10 seconds The configuration mode is used for firmware drivers and project download upgrade After 10 seconds it again starts scanning for the node This cycle continues until GWY 610 gets the response from Other LEDs will remain off till the cycle is repeating After getting response from COM 1 port GWY 610 starts communication on the COMM 1 port COM LED flashes green at this stage and OK LED is steady green Now the GW 610 enters the Ethernet Attach Phase Ethernet Attach Phase It starts attaching to Ethernet nodes Then according to Modbus TCP Client or Modbus TCP Server driver present in Gateway following is done a In case of Modbus TCP server driver GWY 610 waits for request from external client b In case of Modbus T
17. module can be viewed edited 4 Upload System Data This option enables viewing of version number status of firmware drivers used and boot block Doc UMAN GWY 610 1106 44 Cable Diagram CABLE DIAGRAMS In this chapter Communication Cables for GWY 610 IBM Cable for GWY 610 Doc UMAN GWY 610 1106 REVISION 2 45 Cable Diagram 8 1 OMRON CMOS PORT TO GWY 610 EC P 006A 00 OMRON CMOS GWY 610 SID SIDE C200H CN422 OMRON 20 PIN DB9 MALE CONNECTOR CMOS Shield Wire CMOS SIGNALS Pin SIGNALS JJ maa bri Shield Wire 09 pnmum a a 089 MALE 5 reaal Doc UMAN GWY 610 1106 46 REVISION 2 Cable Diagram 8 2 OMRON CQM1 PLC TO GWY 610 EC P 006B 00 OMRON CQM1 GWY 610 SID SIDE 2 mtr J m LO DB9 MALE DB9 MALE RS232 Shield Wire RS232 2 3 Gp _ om a om MM m pe Shield Wire 089 MALE PINOUTS Doc No UMAN GWY 610 1106 47 REVISION 2 Cable Diagram 8 3 A SLC DF1 PORT GWY 610 EC P 027B 00 AB SLC SIDE GWY 610 sie 1 N 089 FEMALE DB9 MALE RS232 Shield Wire RS232 089 5 08
18. 610 8 9 NS TO GWY 610 8 10 THOMSON TECHNOLOGY CONTROLLER TO GWY 610 EC P 117 00 8 11 OPTOMUX TO GWY 610 8 12 ETHERNET CABLE 813 YOKOGAWA CONTROLLER TO GWY 610 8 14 CABLE Doc No UMAN GWY 610 1106 REVISION 0 Introduction INTRODUCTION In this chapter Purpose of this manual Introduction Gateway GWY 610 Specifications reau Doc UMAN GWY 610 1106 6 REVISION 2 Introduction 1 1 Purpose of this manual Thank you for purchasing GWY 610 Product from Renu Electronics Pvt Ltd The intention of this User Manual is to provide a guide for Safe installation Configuration and operation of GWY 610 B or GWY 610 G Functionality of all the Gateway models is same Read this User manual thoroughly before installing and operating GWY 610 This document is based on information available at the time of its publication While efforts have been made to be accurate the information in this document may not cover all the details or variations in hardware or software Features described herein may not be present in all hardwares Renu Electronics Pvt Ltd reserves the right to update information in this publication without prior notice 1 2 Introduction to Gateway Gateway is a Protocol Converter Data sharer for devices like PLCs inverters Adjustable Speed Drives and other Controllers Gateway has two serial ports that connect with two different devices These
19. 64 bits Processor PENTIUM or higher Hard disk Space 5 MB or more Serial Mouse Required RAM 64 MB or more Display resolution 800 X 600 VGA or better Display colors 16 bit color 7 2 Installation Instruction Use the following procedure to install the Microsoft Windows based Gateway setup software This installation shows the procedure to install the software from a CD Disk on drive E On machines with different drive configura tions change the names as needed It is recommended that a backup disk of the Gateway setup software disk be created and stored a safe place 1 Launch the Windows operating system 2 Insert the setup CD into CD drive 3 Point to the start button then click RUN 4 In the command line box enter E Disk1 setup exe Click OK This will launch the Gateway installer 5 Follow the instructions to complete setup E DCT NN Gateway Project Each Gateway must be configured before connecting it to the PLC Gateway configuration software allows the following 1 Create a new Gateway project Select protocols for both communication ports of gateway Create blocks for data to be shared Set Communication Parameters for both the ports Set Control Word Optional Set Error Indication Bit etc Optional 2 Downloading Download Project Download drivers Download new firmware if required only for upgrading 3 Upload Project The existing project in the gateway
20. 9 FEMALE Shield Wire to DB9 PINOUTS Doc UMAN GWY 610 1106 REVISION 2 48 Cable Diagram 8 4 TOSHIBA T1 LINK PORT TO GWY 610 EC P 046A 00 TOSHIBA T1 LINK GWY 610 SIDE S PORT SIDE WIRE OUTS 089 MALE SIGNAL FROM PLC Shield Wire RS485 ae sx La wm fave IL JJ CD ls zl Shield Wire DB9 MALE PINOUTS Doc UMAN GWY 610 1106 49 REVISION 2 Cable Diagram 8 5 TOSHIBA T1 PLC TO GWY 610 EC P 019A 00 sa SIDE m 2 mtr SSS MINIDIN 8 PIN MALE DB9 MALE RS232 Shield Wire RS232 SIGNALS SIGNALS ___ olo Lo er EI ANL DB9 MALE 8 PIN MINIDIN CONNECTOR Shield Wire PINOUTS PINOUTS 6 e 2 7 3 Doc UMAN GWY 610 1106 REVISION 2 50 Cable Diagram 8 6 TOSHIBA T2 LINK PORT TO GWY 610 EC P 046B 00 GWY 610 TOSHIBA T2 LINK e SIDE L ATTACH PLC DB9 MALE Shield Wire RS485 DB15 MALE RS485 Shield Wire PINOUTS DB15 MALE PINOUTS Doc No UMAN GWY 610 1106 51 REVISION 2 Cable Diagram 8 7 TOSHIBA T2 PLC TO GWY 610 EC P 019B 00 TOSHIBA T2 GWY 610 SID rn DB9 MALE DB9 MALE RS232 RS232 Shield Wire DB9 MALE Shield Wire PINOUTS Note These details are also applicable to Siemens 57 300
21. CP client driver GWY 610 sends request to open connection to external server s and wait for the response If connection is opened successfully ETHERNET LED will lit green Otherwise it Continuously try to open the connection to external server Doc UMAN GWY 610 1106 17 83 REVISION 2 L ae Ethernet Init Phase 5 E 22 21 il Attach COMM1 IBM Config Mode 5 LN l Ethernet Attach Phase Ethernet Init F 5 Data 5 Successful Failure Doc No UMAN GWY 610 1106 18 REVISION 2 GWY 610 Features GWY 610 FEATURES In this chapter Gateway Modes Repeat Cycle Control Word Error Indication Bits Communication Parameters Default Communication Registers Recepies I Os reas Doc UMAN GWY 610 1106 19 REVISION 2 GWY 610 Features 4 1 Gateway Modes Gateway has two modes of operation Master Master and Master Slave Before explaining these modes further Master and Slave concept should be explained Master Master is a Device device driver which initiates communication Slave Slave is Device Device driver which processes Master s query takes necessary action and responds to the query if necessary 411 Master Master Configuration In this mode both Gateway ports are master in nature and de
22. Configuration In this mode one of the Gateway ports is a master and other is the slave so the devices connected on these ports are slave and master respectively Blocks do not control data transfer in this mode Data transfer takes place only when Master Device connected on slave port of Gateway sends a request to read write data This mode requires mapping registers for data transfer Mapping means defining one or multiple registers in the Slave Device corresponding to one or multiple registers coils in the Master Device Mapping can be done using the Block definition area so in this mode any Block is used for mapping registers of the two devices In Block Definition area Words Field indicates number of registers to be mapped linearly from the starting addresses of the Source Device to the Destination Device Maximum number of registers that can be mapped is 255 but this does not mean that Master Device has to read write 255 registers in one command In one command Master can read write registers from one Block only so if multiple registers are to be read written using a single command Words also limits the maximum number of registers to be read written Number of registers to be read written in one command also depends on Protocol of BOTH the devices Buffer capacity of Gateway Now let us take the example of Master Slave mode Configure Gateway ports as PLC1 Protocol Modbus Gateway as Slave PLC2 Protocol
23. GWY 610 Ethernet Gateway USER S MANUAL COPYRIGHT NOTICE This manual is a publication of Renu Electronics Pvt Ltd and is provided for use by its customers only The contents of the manual are copyrighted by Renu Electronics Pvt Ltd reproduction in whole or in part for use other than in support of Renu Electronics Pvt Ltd equipment is prohibited without the specific written permission of Renu Electronics Pvt Ltd SERVICE lf service is required then pack the unit in its original packaging container or if unavailable any suitable rigid container If a substitute container is used surround the unit with shock absorbing material damage in shipment is not covered by the warranty Include a letter with the unit describing the difficulty and Hardware Revision and Software Version Send to the following address Renu Electronics Pvt Ltd Survey No 2 6 Baner Road Pune 411045 India All returns will be tested to verify customer claims of noncompliance with the product warranty Improper return packaging which makes verification impossible will void the warranty If noncompliance is verified and is not due to customer abuse the other exceptions described with product warranty Renu Electronics Pvt Ltd will at its option repair or replace the Product returned to it freight prepaid which fail to comply with the foregoing warranty provided Renu Electronics Pvt Lid is notified of such noncompliance within the on
24. Mater aD 1 0 l GS 400020 Gateway arem li ee 1 ETI m 1 ETE 1 modes i EL 1 ux ela oe ata Tape fos Pe Pe __ Ful sper onum RE AT ee EST ee ee d v ko l ki pa Fr Ewe k Conw ACT Si banan eta Words defines number of registers coils to read written between two devices Block 1 Gateway reads 10 words starting from 400001 from Modbus and write these 10 words data register starting from 400001 of Modbus TCP Gateway as master Block 2 Gateway reads 1 word starting from 400020 of Modbus TCP Gateway as master and writes it to holding register 400020 of Modbus Gateway as master As this example has only two blocks Gateway will execute Block 1 after executing Block 2 continuing this cycle forever Notes 1 Maximum 255 blocks can be configured in any mode Doc UMAN GWY 610 1106 21 REVISION 2 GWY 610 Features 4 1 2 Master Slave
25. cts 5 Set PLC1 side settings as shown below PLE Datan g tcpclent pr Gateway GWY GAZiLiharnat Lalmay Pde 4 Cummduam 144 re Slave Address Target PLC Target Target Addres Seve Adore En 1 00100 000001 Modbus TCR GA 1 000001 2 00100 Medbus Ga 100001 Modbus 5 1 100001 1 00100 300001 Modbus TEPUS 1 300001 4 0010008 tthernel lable Ethemet PLC 1 25 PAdhe 182 168 0 15 FOR at Number 552 11 69535 Doc UMAN GWY 610 1106 41 REVISION 2 Typical Projects 7 Download the gateway configuration Select All gt gt Download 11 F AD kan il way Now your gateway is configured and ready for communication Doc UMAN GWY 610 1106 42 REVISION 2 Configuration Software CONFIGURATION SOFTWARE In this chapter System Requirements Installation Instruction Doc UMAN GWY 610 1106 REVISION 2 43 Configuration Software 7 1 System Requirements System Requirement for Gateway setup software are Windows Version Microsoft Windows 2000 Windows 7 VISTA 32
26. cycles For example suppose Blocks are defined with following Repeat Cycles Block 1 Repeat Cycle 1 Block 2 Repeat Cycle 2 Block 3 Repeat Cycle 3 Block 4 Repeat Cycle 4 After power up Cycles will be executed as follows Cycle 1 Block 1 Block 2 Block 3 Block 4 Cycle 2 Block 1 Cycle 3 Block 1 Block 2 Cycle 4 Block 1 Block 3 Cycle 5 Block 1 Block 2 Block 4 reas Doc No UMAN GWY 610 1106 23 REVISION 2 18 GWY 610 Features 4 3 Control Word Another way of controlling Block execution is by use of the Control Words 16 control words i e 255 control bits are available by which user can control 255 blocks Oth Control bit corresponds Oth bit of control word 1 16st Control bit corresponds Ost bit of control word 2 255th Control bit corresponds 15th bit of control word 16 By default 0 to 255 control bits are mapped to 1 to 256 blocks User can change value of the control bit Control Word can be enabled or disabled in Gateway Configuration Normally Control Word is disabled for a New project Just clicking on check box in the setup software can enable it Control Word can be chosen from any of the Devices connected If the Control Word field is enabled for the control bit chosen in the project block accordingly the number of words in the control field should be taken For example if 36th Control bit is chosen to control the block then number of wo
27. ddress Target PLC Target D Target Address Modbus TCP Gateway as Slave 400001 Toshiba T LinkPort PLC 1 XWDODO 6 Modbus Gateway as Slave 400020 Toshiba T Link Port PLC 1 og dome ka 5 Set ethernet side settings as shown below PELLS Th 6L LLL L IE ET 4 PLC Setting Doc UMAN GWY 610 1106 37 REVISION 2 Typical Projects 6 Set PLC1 side settings as shown below EET NEU LECT INIT IP NUS 6 ti Au 18 im Lcd Jib NE hw Aachen Target PL Tage Modum TC KOD Taha urd 1 cov kaba 1 Fargo Setting Advance Setting er m m a Doc UMAN GWY 610 1106 38 REVISION 2 Typical Projects Following Gateway examples show detailed setup for common Gateway configurations 6 1 2 Connect Toshiba link port protocol PLC e g T1 T2 as Modbus TCP Client on Ethernet Network 1 Launch gateway set up software 2 Select GWY 6XX from product list n 00 Product Selection GWT S58 GW I 100 LonWorks Gateveay Port Gw t 300 CAN Gateway 3 Select COM1 and COM2 side protocols and click Configure
28. devices Communication breaks can occur due to no cable connection wire faults device power failure at both ends of Gateway An Error bit can be designated in each external device connected to Gateway Using this bit fault at the PLC1 end can be reported to PLC2 Device and fault at PLC2 end can be reported to PLC1 Device When communication error occurs on PLC1 Gateway sets error bit in PLC2 device Error Indication Bit can only be used in Master Master mode In Master Slave mode any error can easily be detected by a communication time out on the Master Error indication bit can be enabled using Gateway configuration software Normally Error bit is disabled for a new project Just clicking on the check box in the setup software can enable it Error indication bit can be enabled in both or any one of the Devices connected to Gateway Error Indication bit is OFF to indicate error free communication In case of communication error on PLC2 Gateway sets error bit on PLC1 port and vice versa Note If error indication bit is a bit of a bit addresable word then don t use that word in project mapping eae Doc UMAN GWY 610 1106 24 REVISION 2 18 GWY 610 Features 4 5 Communication Parameters Communication Parameters of Gateway can be set from configuration Software This enables Gateway to readily communicate with any device Communication parameters for PLC1 and PLC2 ports can be configured independently This
29. e year warranty period ASSISTANCE This manual is designed to provide the necessary information for trouble free installation and operation of your new Gateway product However if you need assistance please call Renu Electronics Pvt Ltd at 91 20 27292840 or visit our web site at www renuelectronics com MANUAL REVISION If you contact us in reference to this please include the following document number Name Ethernet Gateway GWY 610 User s Manual Number URML207 Document UMAN GWY 610 1106 Revision Revision 1 14 02 2007 Revision 2 12 12 2011 System requirement for gateway setup software revised Warranty Certificate For New product This product is warranted against defects in materials and workmanship for a period of 12 months from the date of shipment to Buyer For Rectified Products Any product that will be replaced will have Warranty for 6 months or upto Original Product Warranty period whichever is greater The warranty is limited to repair or replacement of the defective unit at the option of the manufacturer This war ranty is void if the product has been altered misused dismantled or otherwise abused ALL OTHER WARRANTIES EXPRESSED OR IMPLIED ARE EXCLUDED INCLUDING BUT NOT LIMITED TO THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE MAINTENANCE amp SERVICE There are no parts that can be serviced by the user Service should be performed on
30. feature allows changes in Baud rate Number of stop bits Parity etc at any time without downloading the driver for that particular device After the driver for a particular device is downloaded simply selecting new communication parameters and downloading the same project can change the communication parameters 4 6 Default Communication Registers Purpose To provide flexible Attach Sequence This register is used to test communication with the device to see if device is connected and to check if settings are proper Location User can access these register in Settings gt gt Default Communication Register menu This feature is useful when external slave device does not allow single read operation or does not respond to any particular register For example Some energy meters allow reading in multiple of 16 registers only Previously for Modbus Driver only holding register 400001 was read for attach But if a particular device does not respond to 400001 then the initialization will fail What does the Default Communication Register do After power up default communication register is the first register that is fetched by the master driver from the slave device response for this register is received from slave then only gateway will start the Ethernet initialization Otherwise GWY 610 would continuously try to establish the communication with external Slave device by sending read request with the default communication register
31. from internal database IDB and continuously start fetching data for defined registers in IDB independent to other side driver This all data is stored in internal data memory When request comes from other end external master for mapped registers in gateway projects then data is given from internal memory so time for data fetching from slave device 15 minimized If IDB is not present then data is fetched by sending command to slave device and then it is transferred to other side device which consumes time and hence speed is low Skip on communication fail This feature is very useful when multiple slaves are connected to gateway This can be settable by user in IDB setup This feature will decide to skip data fetching from specific node if that node in the network is off If any node is off during normal communication gateway will skip this node in next data fetch cycle and gives failure indication by flashing led in RED on master port side 1 6 COM1 side of gateway and keep its normal data fetching from other nodes If any failed node is again come in the communication network to fetch data from this node user should have to reset the gateway Fail value lf communication break occurs between external slaves and gateway due power off of any particular slave then gateway moves specified value in other side mapped register At power on each master driver will get all inouts from their internal database Setup and according to that informati
32. ing any system using Gateway User needs a special IBM download cable for downloading configuration in Gateway All configurations can be downloaded only form Serial port Port 1 If any change in the current working project is made user must download the changed project in Gateway n Em DB9 Male Gateway Female 2 2 3 3 5 5 1 For downloading Firmware drivers and project switch off the GWY 610 unit 2 Power ON the unit again Ok LED starts blinking This means that unit is in download mode 3 For the first time download all firmware drivers and project IMPORTANT NOTE AS GATEWAY HAS MULTIPLE SIGNALS ON ITS COMMUNICATION PORTS IBM CABLE FOR GATEWAY MUST HAVE ONLY THREE RS232 SIGNALS TXD RXD AND GND AS MENTIONED ABOVE 9 9 PIN CORE CABLE SHOULD NOT BE USED If you are using USB to serial converter then please connect IBM cable to serial port of converter reas Doc No UMAN GWY 610 1106 15 REVISION 2 01 3 3 1 When GWY 610 accept configuration If current driver present for PLC1 port is Master e g Modbus Gateway as master First it is checked that whether device is connected on port lf device is connected continues normal operation If device is not connected it checks for IBM download mode for 10sec This sequence continues until either is satisfied If current driver present for PLC1 port is Slave e g Modbu
33. on starts fetching and loading data into its internal database memory irrespective of execution of project blocks The master driver will read all the data and load it into the internal database memory But in case of write operation each master driver will check the data available in the internal memory with the new data to be written If the data in the internal memory is same as the new data then Gateway software will skip the write command In case of different data master driver will initiate the write command 5 1 5 How does Pass Through work Please refer the diagram below Slave Device Sive Device Imagine situation where particular Slave PLC Inverter Drive is connected COM1 and Ethernet 2 Now if the user wants to monitor or change parameters of PLC with keypad or any special device that has same communication protocol as PLC without disconnecting it from Gateway then user can use the pass through port Ze I The pass through port itself is slave port the device connected on pass through port sends particular request on pass through port The request is passed to COM1 port When device on COM1 port responds then the response is passed to pass through port So in GWY 610 pass through port is for COM1 that has same communication protocol as well as same communication parameters as COM1 Note Right now Modbus is implemented on pass through Contact factory for other protocols
34. onding LED behaviour for different phases of GWY 610 17 GWY 610 FEATURES 19 4 1 Gateway Modes 20 4 11 Master Master Configuration 20 4 1 2 Master Slave Configuration 22 4 2 Repeat Cycle 23 4 3 Control Word 24 4 4 Error Indication Bit 24 4 5 Communication Parameters 25 4 6 Default Communication Registers 25 4 7 Recipes 26 4 8 I Os 27 NOTE ON COMMUNICATION DRIVERS 29 5 1 Note On Communication Drivers 30 5 1 1 How Modbus TCP server driver works 30 5 1 2 How Modbus TCP Client driver works 30 5 1 3 other serial drivers work 31 5 1 4 What is IDB Internal Data Base 31 5 1 5 How does Pass Through work 32 5 1 6 Control Word for IDB 33 TYPICAL PROJECTS 34 6 1 Project Setup 35 6 1 1 Connect Toshiba link port protocol PLC e g T1 T2 as Modbus TCP Server on Ethernet Network 36 6 1 2 Connect Toshiba link port protocol PLC e g T1 T2 as Modbus TCP Client on Ethernet Network 39 CONFIGURATION SOFTWARE 43 7 1 System Requirements 44 7 2 Installation Instruction 44 CABLE DIAGRAMS 45 8 1 OMRON CQM CPM CMOS PORT TO GWY 610 EC P 006A 00 46 8 2 OMRON CQM1 PLC TO GWY 610 EC P 006B 00 47 8 3 A B SLC DF1 PORT TO GWY 610 EC P 027B 00 48 Doc UMAN GWY 610 1106 REVISION 0 84 TOSHIBA T1 LINK PORT GWY 610 046 00 85 TOSHIBA 1 TO GWY 610 EC P 019A 00 8 6 TOSHIBA T2 LINK PORT TO GWY 610 EC P 046B 00 87 TOSHIBA 2 PLC TO GWY 610 EC P 019B 00 8 8 TOSHIBA VF S11 TO GWY
35. rds in the Control Word field should be 3 Number of control bits 16 Number of control words lf Number of control bits Yo 16 0 Non zero so add 1 in the number of words in the control field then Number of control words Number of control words 1 In the above example number of control bits are 36 So 36 16 2 Number of words in control field 36 16 4 i e Non zero so add 1 in the number of words in the control field so number of words in control field 2 1 3 So number of words in the control field should be chosen as For any block any control bit can be chosen Control Word can only be used in Master Master mode since no continuous data transfer takes place in Master Slave mode data transfer only takes place on Master s request When the Control Word is disabled Block execution is totally controlled by Repeat Cycle settings When the Control Word is enabled Block execution is controlled using discrete bits of that word Bit in control word controls execution of Block 1 Bit 1 in control word controls execution of Block 2 e Bit 15 in control word controls execution of Block 16 When a bit is high 1 corresponding Block is executed depending on its Repeat Cycle When a bit is low 0 execution of corresponding Block is disabled 4 4 Error Indication Bit This feature enables detection of communication breaks during error free communication between Gateway and two
36. rements Ethernet Port Pass Through Port Twisted Pair Transmit Output Positive Twisted Pair Transmit Output Negative NC 6 ko n 8 Twisted Receive Input Positive Twisted Pair Receive Input Negative x 0 a X a lt a 9 COM1 RS232 RS485 CMOS ETHERNET Pint Pint Doc No UMAN GWY 610 1106 11 83 REVISION 2 2 3 LED Status There are 13 LEDs for status indication LED OK Green OFF No Firmware Flashing IBM Download Communication OK OFF Configuration Ok Configuration Fault Green OFF No data received on COM1 Port Flashing Receiving data on COM1 Port OFF No error in COM1 attach or while block execution Flashing PLC1 attach error or error while block execution ETHERNET Green OFF Connection is not open with server O OFF No IP conflict Connection is open with server conflict or Modbus TCP server not attached Pass Through OFF No data received on Pass Through Port Flashing O 2 Receiving data Pass Through Port 7 0 Green Digital input 0 is ON O Digital input 0 is OFF 1 Green OFF Digital input 1 is ON O Digital input 1 is OFF X2 Green OFF Digital input 2 is ON Digital input 2 is OFF X3 Green OFF Digital input 3 is ON O Digital input 3 is OFF
37. rivers 5 1 Note On Communication Drivers 5 1 1 How Modbus TCP server driver works 1 A FIFO is maintained for clients So that when a query from one client is processed queries from other clients are accepted and stored 2 When the query arrives its stored in respective buffers According to the first come first served the query is processed 3 Maximum five clients are allowed in this scheme If sixth client tries to establish the connection with Gateway we do not allow opening the TCP connection We simply discard the frame When the query is received the client is identified and corresponding FIFO entry is updated Here we just acknowledge the query that we have accepted the query After receiving response from serial side it is sent to TCP client When we send the response to particular client we again update the corresponding FIFO entry 4 When a particular client is disconnected the respective client entry is deleted from FIFO as well as Ethernet TCP structure Another client is then allowed to communicate in place of previous disconnected client 5 Timeout at the TCP client should be greater than Serial timeout no of retry at serial side no Of clients on Ethernet side number of clients are not known then on safer side assume number Of clients on Ethernet side equal to 5 and set the timeout 6 lf timeout is less at TCP client side and before processing the particular query from the clien
38. s Gateway as Slave If Port of Gateway is Slave all the configurations should be downloaded Only once for 10sec at power Note Make sure that OK LED is blinking when you start downloading the configuration in Gateway 3 4 Quick Start To Ethernet This section provides quick example on how to get Ethernet running GWY 610 supports Modbus TCP Client as well as Modbus TCP Server at present These settings are for GWY 610 STEP 1 Configure the GWY 610 IP address User should configure IP address for GWY 610 through Gateway setup software PLC2 Settings gt Advanced gt Extended Setup gt IP address STEP 2 Configure Subnet Mask User should configure Subnet Mask for GWY 610 through Gateway setup software PLC2 Settings gt Advanced gt Extended Setup gt Subnet Mask Please note that gwy 610 IP address should be unique STEP 3 Configure Default Gateway Address User should configure Subnet Mask for GWY 610 through Gateway setup software PLC2 Settings gt Advanced gt Extended Setup gt Gateway Address In case of Modbus TCP Client some settings additional to above three are required and are as given below These settings are for PLCs with which GWY 610 will communicate STEP 4 Configure Node address Node address should be configured through Source address Destination address through data exchange blocks STEP 5 Configure Node Address IP Address Port Number User should configure Node Address IP Address Port Number for PLC
39. s with which GWY 610 will communicate through Gateway Configuration Software Settings gt Ethernet node table Note User can get the Information required for STEP 2 and STEP 3 through PC as follows 1 Make sure the PC is connected in Network through Ethernet cable 2 Go to command Prompt on PC reaal Doc UMAN GWY 610 1106 16 83 REVISION 2 3 ipconfig all After the entire configuration is downloaded GWY 610 And after power when LED is steady user ping the unit with GWY 610 s IP address If the response is received to the ping command it means all Ethernet configuration is correct C gt ping lt IP address of GWY 610 gt 3 5 GWY 610 functionality and corresponding LED behaviour for different phases of GWY 610 The GWY 610 initialization can be divided into three stages 1 Ethernet Initialization Phase Here baud rate is determined by auto negotiation and IP conflict is checked 2 Serial Initialization phase Here the communication parameters are initialized And it s checked whether the external slave is connected on the port 3 Ethernet attach phase Here it s checked whether the external server is connected on the port The above mentioned phases are executed sequentially Ethernet Initialization phase At power on GWY 610 initializes the Ethernet port Here the OK LED flashes at faster relative to the IBM Down load
40. t new query is arrived from the same client The previous query is discarded and new is processed 7 lf serial communication is beaked due to cable removal serial device powered off etc exception is sent to Ethernet side The exception code is 0x04 slave device failure 8 If a query from certain existing client is not arrived for two minutes connection is disconnected and new client is allowed this place Source ID and Destination ID related to Modbus TCP server driver does not have specific meaning 5 1 2 How Modbus TCP Client driver works While configuring the project user should give Node ID IP Address Communication Port of Modbus TCP servers with which Gateway Client would communicate For details refer to section Quick Start Section 3 4 IDB is used for Modbus TCP client Modbus TCP Client can communicate with multiple Modbus TCP servers maximum 32 connection with any of the servers is failed the particular server is disconnected regardless of Skip Communication fail setting in Gateway configuration software The only way to re establish the connection is as follows 1 Internal Memory register 00021 and 00022 are defined in Modbus TCP Client 2 You can map these register to any other register through gateway set up software 3 If data in IMOOO21 data is 0001 then node 1 is reconnected If in 00021 the data is 0x02 then node 2 is reconnected and so on 4 After node reconnec
41. time SCADA or local HMI can be connected Isolation between COM 1 and COM2 communication ports through Opto isolation is 1KV rms for 1 min Isolation between COM 3 and COM2 communication ports through Opto isolation is 1KV rms for 1 min Digital Inputs Digital Outputs Terminals Ethernet Baud Rate Operating Temperature Storage Temperature Humidity Mounting Dimensions DIN rail Weight Certifications Immunity to ESD Immunity to Transients Immunity to Radiated RF Immunity to Conducted RF Emissions 0 to 5 V DC low 12 to 28 V DC high Relay Outputs 230 2Amp 30VDC 2Amps Coil voltage 24VDC Pluggable Terminals 10 100 Mbps Autodetect 0 to 60 C 20 to 80 C 10 to 90 Non condensing DIN rail or back panel mounting 100mm L 35mm D 70mm W 200 gm approx CE with UL certification Level 3 as per IEC1000 4 2 Level 3 as per IEC1000 4 4 Level 3 as per IEC1000 4 3 Level 3 as per IEC1000 4 6 EN55011 CISPRA For more details on pass through please refer section Note on communication drivers Note Not all models support digital 1 05 Note ARP RARP IP TCP UDP Protocols are supported At application layer Modbus TCP server and Modbus TCP clients are supported at present New protocols based on tcp and udp are constantly added e g ethernet ip Contact factory for more information quje Doc No UMAN GWY 610 1106 gem 2
42. tion its 5 responsibility to again make the data in corresponding 0002 word as 0x00 Note For more details on configuring the project please refer section 6 1 2 IMO IM15 Control Word for IDB IM16 IM20 Reserved IM21 IM22 Node Reconnection IM23 24 Reserved IM25 Input Word 26 Output Word Doc No UMAN GWY 610 1106 30 REVISION 2 18 on Communication Drivers Note Please refer section 5 1 6 Note Please refer section 4 8 5 1 3 How other serial drivers work Example1 Toshiba ASD In drivers like Toshiba ASD s single parameter is read at a time It does not allow multiple parameters read So in case of Toshiba ASD s driver concept of Internal Database is not used Example2 Toshiba PLC Since drivers like Toshiba PLC Modbus allow multiple register reading in one block in this case concept of Internal Database is used Note Concept of Internal database IDB is explained next 5 1 4 Whatis IDB Internal Data Base Internal Data Base is a concept wherein the data for the registers mapped in the project is fetched internally or to say in the background and the values are maintained internally by the Master Drivers NOTE The Internal database is associated only with Master drivers Let us have a glance at Internal database Please refer the following example These blocks are uploaded read in continuous fashion in the background by Gateway
43. vices connected on these ports are slave Gateway ports initiate communication when the proper Gateway Device communication cable is attached Data is transferred in blocks This transfer can either be a continuous process or as per requirement A control word present in device on either side enabled from Gateway Setup Software can control the block execution When control word 15 disabled then block transfer is a continuous process A block of data is fetched from one device and transferred to the other device The amount of data to be transferred Number of words depends on Block definition in Block Definition Area in Configuration Software One block is executed at a time Acycle consists of execution of blocks from 1 to n Execution of blocks is performed as follows Block 1 Block 2 Block 3 Block 4 Block When Control word is enabled it decides which block has to be executed by writing a specific data in the control word Doc UMAN GWY 610 1106 20 REVISION 2 18 GWY 610 Features Let us see the example of Master Master mode as shown in the picture below Configure Gateway ports as PLC1 Protocol Modbus Gateway as Master PLC2 Protocol Modbus TCP Gateway as master deck d Won Source PLC Source Source Address Destination PLC Denna Comin 18 Gateway a L as
44. way sends exception response to master NOTES 1 If multiple registers are to be read or written in one command then all the registers have to be defined in one Block 2 As Gateway Setup Software is common for both the Gateway Modes titles in the Block Definition Area may not be appropriate when using Gateway in Master Slave mode e g Source ID Source PLC Destination PLC 3 Maximum 255 blocks can be configured in any mode 4 In Master slave mode If somebody mapped read only registers at destination end to any registers at Source end it s users responsibility that these registers are not going to be written by master 4 2 Repeat Cycle User can control Block execution by using the Repeat Cycle field This number decides whether the Block will be executed in each cycle Larger the number lower the priority of the Block Range for Repeat Cycle setting is 1 99 Repeat Cycle 1 Highest priority Repeat Cycle 99 Lowest priority Repeat cycle is important when using Gateway in Master Master mode If Gateway is used in Master Slave mode Repeat Cycle field should be kept as 1 Repeat cycle defines the number of times a Block will be skipped while executing Blocks in a sequential manner Block will not be executed for Repeat Cycle 1 cycles So if Repeat Cycle for a Block is 1 it will be executed in each cycle whereas if Repeat Cycle is 2 then this Block will NOT be executed in alternate
45. y Project Block execution starts Recipes blocks will be executed and the specified value will be written into the specified registers NOTE 1 Recipes are only useful for master drivers 2 All the fields in Recepies i e COM Port Station ID Words Register Address Value can be changed by user LOM Station ID Register Address Com 1 400003 o insert delete row right click on the table This register are initializes with the default values when the device is Power Cee Gee be Cow Doc UMAN GWY 610 1106 26 REVISION 2 GWY 610 Features 4 8 5 Four digital Inputs and four relay outputs are provided for GWY 610 CASE a Operation in case of Modbus TCP Server 1 Input Word should be configured as follows PLC2 settings Advanced Extended setup Input Word its input register 2 Output Word should be configured as follows its holding register PLC2 settings Advanced Extended setup Output Word 3 User can read the status of physical inputs in configured Input word i e Input Register 4 User can change the status of physical outputs from configured Output word i e Holding Register Important Note 1 Input Word and Output Word configured should not be used in actual project 2 Input Word reading and Output Word modifying should be done separately It should not be done with normal project registers Teti jesa ee
Download Pdf Manuals
Related Search
Related Contents
Instrucciones de servicio Hotpoint MWH211 User's Manual Kenwood KDC-2025 Car Stereo System User Manual 2014 Precedent Illustrated Parts List Samsung 943NW Наръчник за потребителя syslib-rm027 - Literature Library Unify OpenScape UC Web Client User Manual Lock-it Block-it LB-0001 Instructions / Assembly Copyright © All rights reserved.
Failed to retrieve file