1.               System     Model  Serial Number   l    l      CAES  l  Y  Version NUT    Address     General  Ventilation mode  Outdoor temperature  Timechannel normal sped   Timechannel reduced sp    Extended operation nomi   Extended operation redi     Supply Air    Supply temperature  Supply setpoint  Controller Output      Extract Air  Extract temperature  Extract setpoint  Controller Output     controlled   Actual Setpoint Compensi     Output normal speed 5   i i          Output reduced speed 15 30 15 31 40 15 33 20 15 35 15 36 40 153820 15 39 35  Controller Output         02 11 2012  15 38 35                       Frequency controlled  Curve   Scale Last value 1l  13 9  C    Supply temperature    ces one eee E Controller Output    Output reduced speed   Controller Output     Outdoor Comp    Outdoor temperature for Iq        Pressere compensation aj   Outdoor temperature for  Pressure compensation at higer    0 Pa  Pressure flow compensation o    Off  san Basses nanka  oe          A real time trend chart is created with this function  Up to four freely selectable  parameters can be recorded  The selected parameters are listed in the box on the  bottom  along with information on the different colours  the associated scale and the  most recently stored value     The chart has a left and right vertical scale with individually adjustable ranges  The  horizontal time axis can be adjusted so that shorter and longer time intervals can be  displayed    Using the scroll bar under t
2.      DF Alarm Status     4 Input Output   Qa Time Control     Settings   y Manual Auto    e Configuration            General  Ventilation mode  Outdoor temperature  Timechannel normal speed  Timechannel reduced speed  Extended operation normal speed  Extended operation reduced speed       Extract temperature  Setpoint room  Ventilation efficiency  Supply Air Fan run time  Extract Air Fan run time     Supply Air  Supply temperature  Supply setpoint  Controller Output  Setpoint offset if reduced speed     Extract Air  Extract temperature  Controller Output  Extract setpoint     Frequency controlled Supply Air Fan  Controller Output  Actual Setpoint Compensation  Dutput normal speed  Dutput reduced speed     Frequency controlled Extract Air Fan  Controller Output  Actual Setpoint Compensation    Dutput normal speed    Dutput reduced speed     Outdoor Comp  Curve Pressure Flow Setpoint  Dutdoor temperature for lower point          Real time trend chart    Stopped  6 11 C  Off   Off   Off   Off  24 45   C  20 66  C  0   78 82 h  78 64 h    19 95  20  C  0   HSE    24 45   C  20   20  C    0   0   75   50   0   0   75   50      20  C            You can create a real time trend chart by right clicking some of the groups  The chart  is created with the first four parameters recorded in the group     8 4  Consumption  tab  o Displayed only with CASE flexotron Heating     P100012097 B    Displays the consumption values of energy meters  water meters and cold water    meters     The val
3.    11    SAUTER CASE flexotron VC SAUTER    Menu bar  6 Menu bar  6 1  File     P100012097 B    The menu bar has five drop down menus    File    Edit    View    Settings  and  Help        Qj SAUTER CASE flexotron Ventilation    Untitled  e LO mE Sol   Eie   Edit View Tools Help     E new coun plg ol pe lay V SAUTER    etpoint    D Alarm Status     Input Output fn Time Control   Pa Settings      Manual Auto   El Configuration         RDT828F221  xx1110310482  3 1214  254254       li Stopped  Outdoor temperature 6 11   C  Timechannel nomal speed Of  Timechannel reduced speed Off    The sub menus are used to edit the configuration files   The configuration data can be saved as a file   Any number of different configurations can be stored   The file is saved as one of the following    e   Vtc for ventilation control   e    htc for heating control  and requires approximately 22 KB of hard disk space     The files are plain text files and can be opened with regular text editors such as  Notepad or Wordpad               New    File      New  opens a new  untitled file     You can select the flexotron800 model in the input window that opens  If you do not  know the model  you can find the item number on the right side of the controller   Make sure you have selected the correct model  If the wrong model is loaded onto  the flexotron controller  inexplicable alarms and similar errors can occur  because  functions may be activated that do not exist in the actual model used        Open  
4.    15    SAUTER CASE flexotron VC SAUTER    Menu bar    P100012097 B       This function is used to load updated programs to the controller  It can also be used  for converting from flexotron Heating to flexotron Ventilation or vice versa     Here it is important to note that  due to different hardware sizes of the controllers  the  CASE flexotron program and the flexotron800 model must be compatible with each  other     For example  to load a flexotron RDT815  the corresponding CASE flexotron must be  set up for the RDT815  Otherwise  unexpected events can occur     CASE flexotron automatically detects whether the connected controller is a  flexotron800 or flexotron800 V2  If the controller is a flexotron800  the following  dialogue box appears  in which you can choose between versions 2 1  2 3 or 3 2     Reload Controller bi li     E  Tou are about to reload the Controller  The    following steps will be carried aut     1  Select language that will be loaded ta the Controller     English      2  The tool parameter settings will be synchronized with the  Controller parameter settings  Select the parameters you  want to keep in this step     3  Checking the Controllers operating system and upgrade if  needed     4  The Controller will be reloaded  Select program version  that will be loaded to the Controller     5  The tool parameter settings will be loaded to the Controller     If the controller is a flexotron800 V2  the version of CASE flexotron is loaded that  matches the 
5.    Opens a saved file        Save       Saves the current file to the local hard disk  If a name has not yet been entered  you  will be prompted to do so      Save as   Saves the current file to the local hard drive under a name of your choosing        Read only       This sub menu can usually be ignored  However  if for some reason two instances of  the same file are opened  one will be marked as    Read only    so as to avoid data  conflicts        Print       Prints a list with all configuration settings of the current file     12    SAUTER CASE flexotron SAUTER    Menu bar  6 2    Edit     6 3    View       P100012097 B       Close       Closes CASE flexotron  If the current configuration has not been saved  you will be  asked if you want to save it before the program is closed     The    Edit    menu contains one sub menu                     3 SAUTER CASE flexotron Ventilation    Untitled      Co   File Edit View Tools Help  AA elf  Al Selen V SAUTER     E Overview   T Actual Setpoint      OF Alarm Status     4 Input Output  n Time Control     Settings       Manual Auto   El Configuration       System       Model RDT828F221  Serial Numher xx1110310482 e a en de  171 33  Delete    The delete function is only used in connection with holiday periods  It allows the  entered times to be deleted     The  View  menu contains one sub menu           6 SAUTER CASE flexotron Ventilation    Untitled     ale  e  Ele Edit View Tools Help  AOS SB   S cle Aw    SAUTER      E Overview   
6.    P100012097 B      Load parameters    Supply Setpoint Curve   lt 1    Supply Setpoint Curve  Y1    Supply Setpoint Curve   lt 2   Supply Setpoint Curve  Y 2    Supply Setpoint Curve  X3    Supply Setpoint Curve  Y3    Supply Setpoint Curve  X4    Supply Setpoint Curve  Y4   Supply Setpoint Curve   lt 5    Supply Setpoint Curve  Y5    Supply Setpoint Curve  X6    Supply Setpoint Curve  Y6    E Tm         Load default password for the display to OK    the Controller     Save all parameters as factory settings in    the Controller       O  4444  is not used by the controller  and    5555    of the Basic level should not be  changed        Load new default setting     Ventilation only     Y Load parameters         Supply Setpoint Curve  Y6  Beo cs E  4      Load default password for the display to    5 Save all parameters as factory settings in  the Controller       If    Yes    was selected for LoadDiaPassWordVisible  you can tick the box  marked in  red  so save the downloaded parameters as default settings in the controller     The values are then used by the function    Reset all parameters to default values           Additional information can be found in the flexotron800 Ventilation manual     19    SAUTER CASE flexotron VCSAUTER    Menu bar    P100012097 B       Real time chart          SAUTER CASE flexotron Ventilation    Untitled  cei  8                              72 Actual Sebmaintl 20 Alara Chabus   c Real time chart    9cmielmi eieocimmt SAUTER    4      Overview 
7.    controls com into an IP address  Multiple DNS servers are part of a system  but  only the IP address of one server needs to be known     IP configuration  A complete IP configuration includes the IP address of the computer  the subnet  brief summary mask  the IP address  the nearest router  also known as the default gateway  and a  DNS server     11 3 DHCP  static and dynamic addresses    otatic and If the IP settings were manually configured in a device  this is referred to as a static   dynamic IP address  if the IP address was automatically assigned by a DHCP server on the  subnet  it is a dynamic IP address    Dynamic IP Using dynamic addresses is a problem when other devices try to connect to the   address device  because the dynamic addresses are not known in advance and are subject    to change  To be able to establish connections to devices with dynamic IP  addresses  the device at hand must use DNS  which needs to be updated if the  dynamic address changes via DHCP  This is commonly used in corporate networks  and Windows computers  However  most internet service providers and many  controllers do not support updating via DHCP and thus need to use a static IP  address     P100012097 B 43    SAUTER CASE flexotron SAUTER    TCP IP network terms    11 4 Internal and public addresses    Internal There is a shortage of IP addresses on the internet  For this reason  organisations   addresses are asked to use internal IP addresses on the intranet  Several companies can u
8.   For more detailed information on this  see  section 11        Update operating system for web server      displayed only for flexotron800 with TCP     If the controller is not up to date  we recommend that you update the TCP IP  operating system of the controller        Log in     flexotron800 has four different login levels  1  2  3 and 5   e 5is the Basic level with the lowest access  e 3is the User level with greater access  e 2isthe Service level with even greater access  e 1 is the Administrator level with full access  CASE flexotron uses only level 3  User  and level 1  Administrator      17    SAUTER CASE flexotron SAUTER    Menu bar    P100012097 B    When the flexotron800 is put into service  the following passwords are the defaults  for the different levels     e Administrator 1111    e Service 2222  e User 3333  e Basic 5555    If a setting is to be made that requires greater access rights than those associated  with the level being used  it is necessary to change to a higher login level        Log out     This function is active only when you are logged in as User or Administrator  it allows  you to log out into the Basic level      Change password     This function is active only when you are logged in as User or Administrator  It allows  you to change the password for the current login level        Load new default password     File Edit Search View Encoding Language Settings Macro Run Plugins Window         o E e s amp     DA  Cc sta  t     03 63  zm m Lae   
9.   Host name   Domain     If the controller is configured to obtain IP settings automatically  by DHCP   this name will be  registered in the DNS server  This makes it possible For the main computer to connect to this  controller using the DINS name as the network address     This requires that the DHCP and ONS servers can coo perate        Load TCP IP settings Cancel    In this window  the following settings can be made                    Here you select whether the flexotron800 is to have a static IP address or the  DHCP server is to assign a dynamic IP address     If the TCP IP interface has a fixed IP and an e mail server is specified with the help  of the network name  a DNS server must also be specified under    Use the following  IP Settings     The TCP IP interface can then convert the network name into an IP  address  If DHCP is used  this happens automatically     The flexotron800 can be associated with a DNS name  such as DNS name     49    SAUTER CASE flexotron SAUTER    flexotron800 with TCP    Flexotronweb  domain  sauter controls com  The IP address of the controller is then  associated with the DNS name flexotronweb sauter controls com     Encrypted The encryption is intended to prevent other users in the TCP IP network from  communication connecting with the flexotron800 via CASE flexotron     The password is used only to connect the flexotron800 via CASE flexotron  If the  password is lost  the settings must be cleared and the controller reloaded     Web user
10.   Sum Alarm Off  DI4   NO   Deicing Dff DOS   Cooling Activate Dff  DI5   NO   Heat Pump Indication Off  DIB   NO   Filter Guard 1 Off  DIS   NO   EAF Indication Off  UDI4   ND   Fire Alarm On          No changes can be made on this tab  read only    Unconfigured inputs outputs are shown in grey     P100012097 B    34    SAUTER CASE flexotron    Folders    8 7    Time Control  tab    VSAUTER                                       SAUTER CASE flexotron Ventilation    Untitled      yp  m  File Edit View Tools Help  AMS eimi S e He Vc SAUTER    Overview   T Actual Setpoint    D Alarm Status    25 Input Output Gp Time Control    F Settings       Manual Auto        Configuration    4  Ga Time Control    m Es Time Schedule Period 1 00 00   18 00  NC Normal speed time     00 00   00 00  T NUNT    Tuesday  Y Reduced speed time Period 1 07 00   18 00     5 Estra Time Channel 1 Period 2 00 00   00 00   9 Extra Time Channel 2    W       Extra Time Channel 3 Period 1 07 00   18 00      Extra Time Channel 4 Period 2 00 00   00 00   9 Extra Time Channel 5 E  x Period 1 07 00   18 00  EE  Holiday Schedule Period 2 00 00   00 00  Friday  Period 1 07 00   16 00  Period 2 00 00   00 00     Sat  Period 1 00 00   00 00  Period 2 00 00   00 00    Sunday  Period 1 Period 2 00 00   00 00  Period 2 00 00   00 00    Holiday  Period 1 00 00   00 00  Period 2 00 00   00 00             CASE flexotron Heating    o A period of use cannot be set across midnight  If a period of use of 18 00   02 00 is  to be
11.   Then the web server in flexotron800 sends the information on the layout of the  website back to the client computer  via the same NAT connection   A Java  application is also opened on the client computer  which controls EXOline  communication  among other things     P100012097 B 47    SAUTER CASE flexotron VC SAUTER    flexotron800 with TCP    The router settings in the example may differ depending on the manufacturer  See  the example below for guidance                                Advanced Settings Status Log Off  Internet Port Forwarding f  mcn Protocol Public port Local port Local IP address Comment Enabled  Firewall LL     TCP amp UDP    80  80 192   168   0 J 20 VentHTTP Iv Delete  Address Translation  NAT  a 2    Port Triggering  TCP amp UDP  m   26486  26486 192  168  0   20  VentEXO lv Delete    TCP amp UDP x   81  en 192 168   0 J 30 HeatHTTP  v Delete  t IA UM    n  TcPaUDP  v   26000  26486 192  168  0  30 HeatEXO v Delete  Dynamic DNS EN  QoS  e  se      12   168  0      Iv Add  Local Network Predefined applications    FTP iv  192 168  0    FTP Vv Add  Wireless Network  Administration OK   Cancel             P100012097 B    SAUTER CASE flexotron SAUTER    flexotron800 with TCP    12 3 Web server configuration    IP settings    DNS name    P100012097 B    0  O    As before  all configuration of the controller parameters is done through CASE  flexotron or directly on the display     Configuration cannot take place via the web server     Information on configur
12.  9  4 1 Program windOW               esssssssseeeee nnne n nnns nari nnns 9  5  Slan UD mer E               P 10  O  MGR Dal e                     12  6 1 AAA PP O 12  6 2 uro                             E 13  6 3 E A E PESE EE EE 13  6 4 OEO S eL 14  6 5    HED ameamua uena a a arias ade nae ices 27  T  OOM AN eec EI 28  o FOO iii iii 29  8 1 General inforMatiQON      ccccoonncnnccccnonnnnncnononcnnnononancnnnnnnnncnnnonnnanrnnnonnnanennnnss 29  8 2 gear 30  8 3  C  rrenuselpols  TaD sx os viste ieri id 31  8 4  GONSUMPUON    CANO m RET Rae oneal is 31  8 5  Alarm Status  tab             cccccccscccsscecseeceseeceeeeceeeesaeesaeeeeseeeeeeesegeesaeeeseeeeses 32  8 6  Inputs Outputs TAD aai occ do EET eto us tat detects ie ee dur od 34  8 7    HME GORTOl TDi ET UT 35  8 8 perudac ddorm                               a 37  8 9  Manual Automatic  tab       ccooocccoccncccnnnccnccncnccncnonaconnanonnnnonnnnconnnonacnnnanonos 39  8 10    System Configuration    tab            occcoocccconnoconccconcconnccnnnonannonanconancnnnnonaness 39  9 Expansion E vedi  40  10  Updating OF TEXOUONSOG msi a 41  11 TCP IP network terms sra ais 43  11 1 Networks  subnets and routers                     eeseeeem mre 43  11 2 IP address  subnet mask  default gateway  DNS server                          43  11 3 DHCP  static and dynamic addresses        ccccccoccnncccncnnccconnnnonononnncnncnnnnnos 43  11 4 Internal and public addresses          cccccccconcnncccconnconcnononcnnnnnonancnnnononanennnos
13.  9  Actual Setpoint     E  Alarm Status    2  Input Output   Gp Time Control   A Settings     Manual Auto    EI Configuration       System 4    lt      Update       CASE flexotron is not a dynamic program  If a parameter value has changed in a  connected controller     the temperature  for example     the corresponding value is not  automatically updated in the program  The operator must first initiate reading of the  parameter values from the controller    An update then starts reading all dynamic parameters from the controller  The entries  are updated with the new values    If you switch between the tabs  an update starts automatically    Alternatively  you can use the update field in the toolbar  see toolbar below  or the F5  key on the keyboard to start the update    The displays can also be updated automatically with dynamic values  see  Options   on page 23    If the controller software version is older than the CASE flexotron software version   they can be adapted to one another  See section 9     13    SAUTER CASE flexotron VC SAUTER    Menu bar    6 4    Settings                SAUTER CASE flexotron Ventilation    Untitled         gt      d   a                 File Edit View  Tools   Help    EE  a   E E Load all parameters     k            w SAUTER      n Time Control   P af Settings       Manual Auto   Y Configuration         a     Synchronize all parameters             System  Model       Reset all parameters to default values                    Search for Control
14.  Alarm Status        E Overview     4 Input Output     i Time Control     Settings   Y Manual Auto   E Configuration      If the cursor is placed on an icon in the toolbar  a brief description of its function is  displayed   All options except for the  Update  function have already been described     28    SAUTER CASE flexotron VC SAUTER    Folders   8 Folders  The contents of the various folders depend on the CASE flexotron program  Heating  or Ventilation  but also on the model  RDT828  RDT815 or RDT808  for which the  program was configured   Therefore  the contents will not be discussed further    8 1 General information    Items in a folder that are associated in some way are grouped together   Group names are in bold     The groups are usually displayed expanded  that is  all items in the group are  displayed  and the group name is listed in the first position     To collapse a folder  click the    minus  box to the left of the group name  This causes  only the group name to be displayed  When a group is collapsed  a   appears in the  box next to the group name     To expand the group  simply click the       Setting values    Many of the folders contain adjustable values  If the cursor is pointing at such a  value  a text box with the permitted range appears     With a flexotron800 connected  a value must be loaded into the controller in order to  activate it     The values can be downloaded into the controller in several ways   1  Right click any item  2  Select  Load 
15.  EJ RDT808 fix value  draft 1 vtc    Cor FilterAlarmReset    0    Cor ALarmCategory2  36  mo AM  AlaData AlaPt87 DelayValue  gm  Cor ExtraStopCategory2  36  aum    AlaTextEnu Records 86  Txt     Manual Y4 Extra Sequence control   Cor ALarmCategory2 37     i     AlaData AlaPt88 DelayValue  O     wow  i    Cor ExtraStopCategory2  37     AlaTextEnu  Records  87   Txt  Restart blocked after power on      TcpCfg     TcpEnabled    No      DiaPasswords   LoadDiaPassWordVisible      Diala DiaPasswords  0   Diala DiaPasswords  1   Diala DiaPasswords  2   Diala DiaPasswords 3     Diala DiaPasswords 4              Nort length   33570 lines   1147 Ln 1 Col 1 Sel 0 Dos Windows ANSI INS    If vtc or htc files are loaded  it is possible to define new passwords for all levels  The  files are text files that describe the configuration  The files can be opened with  Wordpad or Notepad  for example  At the end of the vtc file is the DiaPasswords  section  which deals with the login codes     Changing the default password  1  Open the vtc or htc file  2  On the    LoadDiaPassWordVisible    line  overwrite the  No  value with  Yes      3  Change the Administrator  1111   Service  2222  and User  3333  levels to  the desired values     4  Save the vtc or htc file  Start CASE flexotron  6  Import the file       If the passwords are to be downloaded  you can click this action  marked  in red  when loading the parameters onto the flexotron800     e    18    SAUTER CASE flexotron VCSAUTER    Menu bar 
16.  Run Error P1 Cooler 4 B 5s  tea ie P1 Exchanger is out of operation Run Error P1 Exchanger 5 B 20s  Filter quard Filter guard B B 180s  z Flow guard Flow guard 7 B Es  lv External frost guard External frost guard 8 A Os  Vv Deicing pressure guard Deicing pressure guard 3 B E  M Fire alarm Fire alarm     E External switch Extel A Settings  External alarm Exte    Supply Air control error Supl  High supply air temp Hig   Low supply air temp Lo  High room temp i               Low room temp          Delay  Stop ventilation unit if alarm active No   Alarm text Low room temp  Low room temp 10  C       High extract air temp  Low extract air temp    Acknowledge  Block  Electric heating is overheated  Settings    Low frost guard temp  Low efficiency    Sensor error Outdoor temp  Rotation guard exchanger   Fire damper is out of operation  Supply Air Fan external operation  Extract Air Fan external operation  Ventilation stopped   Manual supply air control Mank  Manual Supply Air Fan mode     Manual Supply Air Fan freq control Manual Supply Air Fan freq control 38  Manual Extract Air Fan mode Manual Extract Air Fan mode 38  Manual Extract Air Fan freq control Manual Extract Air Fan freq control 40        ea                      623 623 2623  ooo    v v  ecaa            The alarm text  including all soaces  may not be longer than 38 characters  divided  into 2 lines of 19 characters each     If the maximum length on the first line is exceeded by the word on the end  the whole  word is mo
17.  available  a    broadcast    address is used  Therefore  it is  important that the computer is connected directly to the current controller  with a crossover Catb cable     If the search is successful  the IP settings of the controller are displayed   e IP address  e Subnet mask  e Default gateway  if present   If no values are displayed  then   1  Select  Search        A browser window opens  the TCP IP card of the controller is found  and its  Ethernet address  MAC address  is displayed in the window     2  Select a line and press  OK    If no controller is found   1  Check the cables and connections  2  Check that there are no active network connections   Control Panel       Network Connections   3  Deactivate everything except  Connection to the local network    4  Select  Search  again  5  Enter the IP address  the subnet mask and  if applicable  the gateway for the  controller  6  Select  TCP IP Settings  for loading   If successful  a message is displayed   7  Press  OK      A message may appear indicating that a TCP IP connection has been    established  but that no controller with the address 254 254 could be found   Instead  a controller with another PLA ELA address was found     8  Answer  YES  to the question of whether this controller should be used  instead     The CASE flexotron can now be used for  configuration loading extension synchronisation and so on     If the message    Not possible to read the index variables 255 30   QSystem PLA  not  responding    a
18.  configured  it must be divided into two periods of use  Day 1 from 18 00 to    Daily comfort times can be set here   Each control function has its own time programme   For each day  there are two periods of use     The 8th day  Public holiday   holiday period  controls the activities on all days    that are marked as such in the holiday period calendar  see below     The time programmes for Clock channel output 1   5 determine the activation    of the corresponding digital output signal   To disable a period of use  set the time to 00 00 00     To make the controller run 24 hours a day  set the time to 00 00 24 00     24 00 and Day 2 from 00 00 to 02 00     P100012097 B    35    SAUTER CASE flexotron SAUTER    Folders    P100012097 B    CASE flexotron Ventilation  e Daily operating times can be set here   e For single speed fans  there is only one time programme     e With two speed fans  there are two time programmes  One is for normal  speed  level 2  and another for reduced speed  level 1      e For each day  there are two periods of use     e If the running times of the normal speed  level 2  overlap with the reduced  speed  level 1   the normal speed  level 2  has priority     e The 8th day  Public holiday   holiday period  controls the activities on all days  that are marked as such in the holiday period calendar  see below     e The time programmes for Clock channel output 1   5 determine the activation  of the corresponding digital output signal     e To disable a pe
19.  login Passwords for logging into the website  Guests can view all the values  Operators   passwords  users  can view and modify values  The service has no function through the web  and instead functions as an operator    E mail server Network address for the e mail server   network settings The outgoing SMTP e mail server with which the TCP IP interface e mails are to be    sent is specified here  Either as the network name  DNS name  such as  smtp exampledomain com  or as an IP address     An IP address is usually assigned within local networks  When there is a connection  to the internet  network names are more common  Which e mail server is to be  specified can be obtained from the network technician or internet service provider     Note  The specified network name must be directly associated with the e mail  server  It cannot be an alias or another network name  To check whether you have  a directly associated network name  proceed as follows     1  Use the Windows command prompt     Start Menu   gt   All Programs   gt    Accessories   gt   Command Prompt    to execute the ping command on the  network name  e g  ping smtp exampledomain com      2  Here you check whether the command  Pinging smtp exampledomain com   receives a response     Login Name and Login Password   These two fields are used only if the outgoing e mail server requires a login and  supports the AUTH LOGIN method  Otherwise  this field does not need to be  completed    Other login methods or encodings 
20.  module controller     This function is used to edit the address of the connected controller  The address is  usually 254 254  If the controller is to be used in a network  the address must be  edited because the connected controllers have different addresses      Reload module   modulezcontroller   Loads the current controller program from CASE flexotron onto the controller              PEEL       v SAUTER            Model  Serial Number    Version  Address     General  Ventilation mode  Outdoor temperature  Timechannel normal speed  Timechannel reduced speed    RDT815F022    3 3 0 26  254254    Extended operation normal spe     Extended operation reduced sp          Supply Air  Supply temperature  Actual Supply setpoint  Controller Output      Frost Protection  Frost protection temperature  Setpoint when stopped  P band when running  Controller Output     Energy calculation   Actual calculated power    P100012097 B       E Overview      Actual Setpoint   ir Alarm Status    25 Input Output   Qa Time Control   Pd Settings       Manual Auto   Y Configuration                       Reload controller      flexotron   4 N    following steps will be carried out        i Y ou are about to reload the controller  The            The tool parameter settings will be synchronized with the  controller parameter settings  Select the parameters you want  to keep in this step           The controller will be reloaded       The tool parameter settings will be loaded to the controller     x    
21.  up    D otart up    P100012097 B    de Notepad     Lo NVIDIA Corporation  do PDFCreator   4   PROCAD    SAUTER           J SAUTER CASE flexotron J           Y SAUTER CASE flexotron Heating  O SAUTER CASE flexotron Ventilation   de Skype   de Snagit 10   Lo Spiele   dy Symantec Endpoint Protection   jJ   USC   Le VideoLAN   Ly Wartung X    4 Zur  ck                   The installation program creates a folder in the Programs folder of the Start menu   This folder contains links to CASE flexotron Ventilation and CASE flexotron Heating     Starting a program    l     2   3   4    Click  Start  on the bottom left of the screen  Continue to  All Programs    Select the SAUTER CASE flexotron folder  Start the program by double clicking it       The program starts     An input window appears  with each start        An overview of the models is SIE Sy    File Edit View Tools Help  Bcm aelm s clemt           Ya Actual Setpoint   zr Alarm Status       Input Output   fn Time Control      Settings      Manual Auto   Y Configuration         c SAUTER           lt S Overview               System    Model RDT828F232  Serial Number  Version 3 3 0 26  Address 254 254      General    Ventilation mode  Outdoor temperature  Timechannel normal speed  Timechannel reduced speed  Extended operation normal spe     Extended operation reduced sp         Supply Air  Supply temperature  Actual Supply setpoint  Controller Output      Frost Protection  Frost protection temperature  Setpoint when stopped 25  
22.  workstation to a host   networks computer on a corporate network with internal IP addresses to use a tunnel in the  network  A tunnel means connecting two networks via the internet using internal IP  addresses  For this purpose  all network packets to the destination network are  encrypted  encryption of IP addresses and other information   The encryption is  carried out by a network firewall  A new  address label  with the public addresses of  the other firewalls is assigned to the packet  This firewall decrypts the content and  forwards it to the target workstation in the corresponding network  Decryption  requires that the password be known to all recipients  This technology is also known  as VPN     PC internal A tunnel can also be created between an individual computer and an internal   network network  When employee are travelling on business  they often to first connect their  laptop via GPRS and internet  and then connect to the corporate network using a  tunnel  In the same way  technicians on standby duty can connect to the  workstation from home or from the service vehicle and so on     P100012097 B 44    SAUTER CASE flexotron VC SAUTER    flexotron800 with TCP    12 flexotron800 with TCP       The terms used here are explained in section 11     12 1 Connection  The controller must be connected to a static  public IP address  The following  connection methods were tested for flexotron800 with TCP     e Direct connection to an ADSL cable modem  e Connection to a ro
23. C  P band when running 5  Controller Output      Deicing  Deicing temperature  Setpoint 3  Hysteresis FG       Number of   0s Model       gt   28 y   RDT828F232 y   cora            Controller Output     Energy calculation  Actual calculated power       5  Select the flexotron800 model in use       Be sure to make the correct selection here in order to avoid possible errors  in the control setting and alarm handling     10    SAUTER CASE flexotron SAUTER    Start up    P100012097 B    To make it easier to open the program  you can create a shortcut on the desktop     Creating a shortcut   1  Move the cursor onto the program name   2  Hold down the right mouse button to highlight the program name  3  Drag the program from the folder to your desktop  4    Release the right mouse button and complete the process with    Create  shortcut here       Creating a shortcut in the taskbar   When installed in Windows 8  CASE flexotron is stored under  All apps        All apps   can be accessed from the start screen    From here  just click the appropriate icon to start the program     In addition  you can create a shortcut to CASE flexotron in the taskbar   1  Todo so  right click the icon     2  Use the toolbar at the bottom of the screen to select    Pin to taskbar        When the program is started  it automatically searches for a controller that is  connected to the computer and also suitable for the loaded program  If no suitable  controller is found  the program will start offline  
24. VSAUTER                                            d SAUTER CASE flexotron Ventilation    Untitled               File Edit Vie    Hein    BOBS DBA      E Overview   52 Actual S etpoint   ik Alarm Status           gt  SAUTER      Input Output   Gn Time Control   4 Settings       Manualr  uto   lel Configuration         H System  Model RDT828F221  Serial Number xx1110310482  Mersion 3 1 1 4  Address 254 254   i i General  Ventilation mode Stopped  Outdoor temperature 6 11 T    Timechannel normal speed Off  Timechannel reduced speed OF  Extended operation normal spe    Off  Extended operation reduced sp    Off    E  Supply Air  Supply temperature 19 9 C  Supply setpoint 20  C  Controller Output 0       Extract Air  Extract temperature 2445 C  Extract setpoint 20 C  Controller Output 20    zi Frequency controlled Sup     Actual Setpoint Compensation 0   ee se OOOOOOOCOOD0002  Controller Output 0     i i Frequency controlled Extr     Actual Setpoint Compensation     02     Qutput normal speed OC   Output reduced speed 50   Controller Output 0     SAUTER CASE flexotron    User Manual  P100012097 B    SAUTER CASE flexotron VC SAUTER    P100012097 B    SAUTER CASE flexotron    Table of contents    Table of contents    P100012097 B    Table oft conte COT ici 2  Nue  tirita ni rios 5  T  ml e Ls OP PAR E a a E a S a 6  2  AD  DOULDIS Manualen aa daa 7  Se   MISMA ION a A a a A E Aa AEE 8  4 About the CASE flexotron t0Ol        sssnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnn nnmnnn
25. are not currently supported     E mail sender The address that is to serve as the sender in the e mail is specified here  Many e    address mail servers and junk mail filters require a real e mail address here  Otherwise  a  fictitious sender address can be specified  e g  MyControllere MyDomain com  If  you are unsure about what to enter  ask your network technician     Setting up After the settings described above have been performed  you download the settings  TCP IP settings to the TCP IP card in the controller by clicking this box     P100012097 B 90    SAUTER CASE flexotron    flexotron800 with TCP    12 4 Website settings    In the  System   gt  Website  sub folder and  E mail  in the Configuration folder  the  following settings can be made for the website     Website  heading    Link  heading    Process image    E mail    P100012097 B    VSAUTER    Here you can select a heading that appears on the first page when visitors surf the  flexotron800 website     Up to four different links to small PDF files or other internet sites can be added to the    website     Note  The total size of the PDF files and the process image should not exceed 150    kB  Under Link1  heading  enter the heading for Link 1  under Link2  heading  the  heading for Link 2     elc     The heading must not contain any spaces  For example  for Fr Sauter  you must enter  Fr Sauter  That is the default setting for heading 4     The selected image is displayed in the heading on the web  Due to the low 
26. atively  you can select the period by clicking the  start date  pressing the  Shift  key  and simultaneously clicking the end date   Then confirm your choice with  OK      36    SAUTER CASE flexotron VC SAUTER    Folders    e Even if the calendar extends far into the future  holiday periods can be set up  to one year in advance  If you try to choose a date that is more than 365  days in the future  the end date will be set to one year from the current date     e Click the  Delete  button on the toolbar of CASE flexotron to delete holiday  times     e Set holidays   holiday periods apply each year  They should not be deleted   Christmas and New Year s Eve thus need to be entered only once     8 8    Settings    tab                6 SAUTER CASE flexotron Ventilation    Untitled    gt  EA  File Edit View Tools Help  paellas c es mies   SAUTER  c Overview   TA Actual Setpoint   zL  Alarm Status     5 Input Output am Time Control     Settings   e Manual Auto    zi Configuration      Settings   Supply Air   P  Controller Settings o upply P band S T  ote    time s  Menem Stara   Extract Air   C Alarm objects Extract P band 2 5    time Os       Frequency controlled Supply Air Fan  Min output 0      Frequency controlled Extract Air Fan  Min output 0      Frost Protection  P band when stopped 100  C    time 100s          Controller settings  Setting of the control parameters  such as P band and I time             SAUTER CASE flexotron Ventilation   RDT828 cascade CO2 drafti  C  Users s
27. e moved along the time axis   With an active cursor  the values at the cursor position are displayed  not the most  recently recorded values  In this way  previously recorded values can be traced      Go to home     The home position is the chart position in which the  recording pins  on the right edge  of the chart are located  If you scroll back along the time line  you can use this  function to return to the normal starting position      9     Zoom out   Makes the view smaller       Pause       Stops the chart  Trend recording is stopped  no new values are added to the display   However  data recording continues  and new values are stored every five seconds   Pressing    Pause    causes all stored recordings to be added to the chart     21    SAUTER CASE flexotron VC SAUTER    Menu bar     1   Option   Setting of various options       Time scale    Interval     Left scale        Maximum value     Minimum value       Right scale    Maximum value     Minimum value           Time scale  is the time interval shown on the screen      Left scale    determines the scale for the left scale      Right scale    determines the scale for the right scale      42     Time scale       Determines the time interval of the display     P100012097 B    22    SAUTER CASE flexotron VC SAUTER    Menu bar    P100012097 B    Parameter list            02 11 2012  14 14 45 di Ls    Aussentemperatur Left 6 11   C  E Vorlauf Temperatur Left  O Reglerausgang Left       The parameter list shows the para
28. effect   To download controller parameters     e Either right click the parameter name or the parameter group name and  select  Load all parameters      e Orclick  Load all parameters  in the CASE flexotron toolbar or in the menu     P100012097 B 3     SAUTER CASE flexotron VC SAUTER    Folders    P100012097 B    Alarm settings   alarms  Setting the alarm parameters     The settings can also be performed in the Alarm Status folder  Information in this  regard can be found in the Alarm status section     Unused alarms are removed from the list and saved in the Alarm Status folder     Activate A and B C alarms depending on the configuration of the digital outputs A   alarm or B alarm  Both activate the common alarm output  if configured      Alarm text in flexotron800    The alarm text shown in the flexotron800 when an alarm is activated is shown on the  Alarm text line  This text can be changed in CASE flexotron     The alarm text  including all spaces  may not be longer than 38 characters  divided  into 2 lines of 19 characters each     If the maximum length on the first line is exceeded by the word on the end  the whole  word is moved to the second row  If you use a hyphen as the 19th character   followed by a space  you can prevent the entire word from being moved to the next  line     Example        Sensor error Relative Humidity supply air  consists of 40 characters  but  since the  third word extends beyond the 19th character  the following appears on the display     Sen
29. er is  running     For time periods for which there are no values  or these values are not applicable    an empty string is displayed for the value     Example    01 jul 2014 Hoom Hoom Supply air fan Return air fan  temperature    C  X setpoint    C  pressure  Pa  pressure  Pa    10 28 00   10 29 00 23 1 23 0 87 86   10 30 00 23 1 23 0 85 87   10 31 00 23 1 23 0 87 85   10 32 00 23 1 23 0 85 86   10 33 00 23 0 23 0 87 86   10 34 00 23 1 23 0 88 86   10 35 00 23 1 23 0 89 86   10 36 00 23 0 23 0 86 85    P100012097 B 53    SAUTER CASE flexotron    Printed in Switzerland    Subject to changes     Fr  Sauter AG  CH 4016 Basel    P100012097 B    VSAUTER    54    
30. flow rate can be selected here      Communication settings   Communication settings between CASE flexotron and controllers     The choice of communication depends on the controller model loaded in CASE  flexotron when it was put into service  Serial communication is the default for all  models except flexotron800 with TCP     a Communication settings ML    m Use Serial communication    E Serial Number    Search       Communication Channels         C Use a TCP IP port in this controller    Current Name    Search       Serial Number   E thernet Address     Description     TCP IP  WEB site and E mail settings               Checking communication channels  1  Click the    Communication channels    button  2  Select the  Serial  channel          Communication Channels    Project Edit Tools Help      New   i do   Set as defaut   Routings      Connect        Act as server  gt      Name   USB    Title   Default  USB        Default port   Bit rate  bps   Default  9600   Flow control  Default  No   Message time out  ms     Default   lt  100 ms   Character time out  ms     Default   lt  100 ms              3  Check whether the suggested COM interface matches the interface assigned  by the computer to the interface converter     P100012097 B 24    SAUTER CASE flexotron VC SAUTER    Menu bar    P100012097 B       Checking the COM interface   The interface can be checked under  System Settings      System      Device  Manager     gt     Connections  COM  amp  LPT        TCP IP communicatio
31. he chart  you can scroll along the time axis and display  each position of the recording     Values are recorded every 5 seconds  All recorded data can be stored as a text file  for later use  in a spreadsheet program such as Excel  for example      If more than four parameters are to be observed  several sessions of the real time  trend chart can run simultaneously     The chart cannot be saved  When you exit the program  all the settings are lost   However  you can use the  Print  button to create a screenshot of the current  diagram and then save that     20    SAUTER CASE flexotron SAUTER    Menu bar    P100012097 B    Real time chart functions    UJ bs ll Wile ll o miu  hoan a  000000600 OM  A     1     Export      Exports all recorded values to a  txt file  The values are separated by tabs for easy  import into Excel  for example  Each line of the text file contains the values of a  recording together with the recording time  Recorded data is stored for approx  24  hours      2    Add curves       Click this field for a list of all flexotron800 parameters that can be shown in the trend  chart  Up to four parameters can be selected      3     Delete all curves     Deletes all the selected curves        Showlhide left right grid           The chart grid on the left and right side can be shown or hidden      6   Show node points   Each time of recording can be marked on the curve and displayed      7   Show cursor     Displays a vertical line on the chart  The cursor can b
32. ing the controller can be found in the previous sections of  this manual or in the corresponding manuals for flexotron800 Heating and  Ventilation     If the configuration of the controller parameters is changed  the website is  automatically downloaded to the web server  If the website settings have been  changed  it is only necessary to update the website     TCP IP interface configuration    The TCP IP interface is configured in the flexotron800 via the  Settings    gt    Communication Settings  menu item     1  Select  Use TCP IP interface in this controller    When prompted  select the  right cable    Use the search function to find the correct controller   Once the correct controller has been found  confirm the selection with  OK   Press the  TCP IP  WEBsite and e mail settings  button    gt  The following input window opens    Gr  lt  gt  o I       TCP IP  WEBsite and e mail settings  input window    f  s  TCP IP  website and e mail settings                Y Use the following IP settings    E Connection to main computer   D Security    JE  mail      IP settings  E    Obtain IP settings automatically  by DHCP   S C Use the following IP settings     IP address rq  Subnet mask i 73  Default gateway DL 5     03  DNS server         IP settings can be assigned autom lly if th supported by the network  DHCP   Otherwise  as ety strat    DNS name    w Full DNS name       Enter host name and domain of the controller  Ask the network administrator    for the appropriate domain   
33. is particularly important if the communication goes through a firewall   If the controller and the computer on which CASE flexotron is installed are on the  same subnet  no DNS name or domain needs to be specified     However  if the controller and the computer are on different subnets  a DNS name  and the domain must be specified  The domain name can be obtained from the  network administrator     Static IP address  In this case  the static IP address is specified by the controller     This configuration is best suited for networks without a DHCP server  It can also be  used if the network service is not fully trusted  because it is communication with the  best functionality  in contrast to servers   As long as routers and switches operate satisfactorily  the alternative configuration  will also work   The following requirement must be met    e  CP port 26486 must be open from the controller to the host computer  This   is particularly important if the communication goes through a firewall     The static IP address  net mask and default gateway can be obtained from the  network administrator     Provides access to manuals  lists of variables and information about the program  versions     27    SAUTER CASE flexotron VC SAUTER    Toolbar    7 Toolbar    P100012097 B    The toolbar provides quick access to selected functions      fj SAUTER CASE flexotron Ventilation    Untitled     _  jm   File Edit View Tools Help          AMA ST  Vv S cle He SAUTER  E TA Actual Setpoint   ir
34. larm classes     e Collective alarm A  e Collective alarm B  e Collective alarm C    A and B alarms activate the digital outputs A Alarm or B Alarm  provided they have  been configured  Both activate the collective alarm output  provided it has been  configured     C alarms are only internal     C alarms do not need to be acknowledged  In case of a reset  these alarms  automatically change back to normal status     Alarms can be displayed according to their class   e A B  Cor all classes    e According to status Normal  Blocked  Acknowledged  Back to normal  Alarm  active and All statuses     Alarm text in flexotron800    The alarm text shown in the flexotron800 when an alarm is activated is shown in  column 2  Alarm text  This text can be changed  but only through CASE flexotron     Alarm parameters    Double click the alarm text to open a field where you can edit various alarm  parameters  such as alarm texts                              fj SAUTER CASE fiexotron Ventilation    Untitled  e    X  DAENDA S leE SAUTER  Les Overview    9  Actual Setpoint    O Alarm Status     5 Input Output      En Time Control   AF Settings       Manual  amp uto    e Configuration     4  Alarm Alarm text Nbr   Class Delay Status  All classes Iv Alarm objects   v Supply Air Fan is out of operation Run Error Supply Air Fan 1 B 120s   7 Extract Air Fan is out of operation Run Error Extract Air Fan 2 B 120s  E P1 Heater is out of operation Run Error P1 Heater 3 B 5s  E P1 Cooler is out of operation
35. lers           a xi    Serial Numbet  Version  PERS Change Controller address        General  Ventilation ma  Outdoor temp  Timechannel  Timechannel       Set Controller date and time            Reload Controller            Load Web site to the Controller           Upgrade operating system for Web server  TCP IP          Upgrade COntroller operating system       Extended ope  Extended ope  Ci Supply Air  Supply tem              Log on           TU dicic  c         Supply setpoi  Controller Out     Frost Prote4   Real time chart     Frost protecti  Setpoint wh E  P band when  g     Controller Out  2 7                Note                   Options              Communication settings           Hyst  Controller Output              S3 Online    Normal     Logged off 05 11 2012 14 02 04          Load all parameters   Download all current parameters from CASE flexotron to the flexotron800 controller        Synchronise all parameters       All parameters in the flexotron800 are compared with the values in CASE flexotron   All differences are listed     Settings are usually selected with ticks  You can remove a setting from the selected  list by removing the tick     CASE flexotron can then be updated with the controller values or the controller can  be updated with the CASE flexotron values        Reset all parameters to default values     Resets all CASE flexotron parameter values to the default values     P100012097 B    SAUTER CASE flexotron    Menu bar    VSAUTER     Search for m
36. meters assigned to the chart  To remove a  parameter  right click it and select Remove     You can reassign the right or left scale by right clicking Properties or by double   clicking the left mouse button        Notes       Access to the notes area  Each text written here is saved together with the  configuration file  If the configuration is printed  the note text is included on the  printout        Options     Allows several program parameters to be set       y uem    Log on timeout  5 min  Number of decimals  2  Cancel      Lock configuration E    Also show non active signals in    In Output tab    Synchronize alarm texts when        synchronizing all    Auto refresh  F5   V every  6    Temperature unit  Celsius Y    Flow unit  m3 h Y         It is possible to automatically update the display with dynamic values     Log on timeout    After a configurable period of inactivity  the login is reset to the lowest access level      Number of decimals       Sets the decimal places displayed  All calculations are carried out with full precision   however        Lock configuration      Blocks access to the Configuration tab       Also show non active signals in In Output tab     All inputs outputs are displayed on the  In Output  tab     23    SAUTER CASE flexotron VC SAUTER    Menu bar     Synchronize alarm texts when synchronize all   During synchronization of all parameters  the alarm texts are also synchronized        Temperature Flow unit   Various units for temperature and 
37. ms are indicated with a red box with a lightning bolt symbol     e Alarms that have been reset  but not yet acknowledged  are indicated by a  yellow box with a lightning bolt symbol     e Active acknowledged alarms are indicated with a blue box and a lightning  bolt symbol     e Blocked alarms are indicated with a grey box and a prohibition symbol     Alarm Alarm text Nbr Class Delay Status    Alarm objects    Supply Air Fan is out of operation Run Error Supply Air Fan 1 B 120s    Extract Air Fan is out of operation Run Error Extract Air Fan 2 B 120s  P1 Heater is out of operation Run Error P1 Heater 3 B 5s o  P1 Cooler is out of operation Run Error P1 Cooler 4 B 5s   P1 Exchanger is out of operation Run Error P1 Exchanger 5 B 2D s   Filter quard Filter quard 6 B 180 s   Flow guard Flow guard 7 B 5s   External frost guard External frost guard 8 A Os   Fire alarm Fire alarm 10 A Os  amp     External switch External switch 11 C Os  External alarm External alarm 12 B Os    All alarm status changes in CASE flexotron are immediately transmitted to the  controller without it being necessary to use the    Load all parameters    function     By contrast  alarm status changes in the controller are not displayed in CASE  flexotron if no update has been carried out     32    SAUTER CASE flexotron SAUTER    Folders    P100012097 B    The changes can be tracked at any time using the alarm window in the status bar at  the bottom of the window     Alarm classes  The flexotron800 has three a
38. n   If Case flexotron is opened with a flexotron with TCP  you can choose whether  communication takes place via USB cable  serial  or TCP IP interface     a Communication settings _    E Serial Number    Search         Communication Channels         C Use a TCP IP part in this controller    HE m Current N ame    Search    Serial Number  SSS  Ethernet Address  SSS  Description ee    TCP IP  WEB site and E mail settings     n      If the controller has a TCP IP interface  TCP models   it can communicate via a  TCP IP network     To do this  activate the    Use a TCP IP port in this controller  radio button     Selecting    TCP IP  website and e mail settings    allows you to select between  three different connection options     e Crossover network cable  e Automatically with DHCP  dynamic IP address   e Static IP address   See section 11 for further setting options     Crossover network cable    In these cases  a crossover network cable is used  The user is directly connected  with the controller     1  Connect a crossover TCP IP cable directly between the controller and the  computer    2  Start CASE flexotron    3  Open the    Communication Settings    function in the    Settings    menu or  through the icon in the toolbar    4  Select    Use TCP IP interface in this controller          he program asks about using a crossover network cable  5  Confirm with  YES   6  The controller search is started     25    SAUTER CASE flexotron VC SAUTER    Menu bar       Since no DHCP is
39. nect to through the different WAN ports     For the second flexotron800  the communication interface must be set to  EXOline    This setting is made under  Configuration   gt  System      Website   For example  your have the possibility of setting the port to 26486 instead of 26000       Web site  Headline Web site Heating System Controller  Link 1  Headline  Link 1  Link 2  Headline  Link 2  Link 3  Headline  Link 3  Link 4  Headline  Link 4  26496    Processpicture C  EXO images Heating Pictures ProcessPicture  jpg    Then call up    Tools   gt  Load website to the controller    to load the new setting onto the  unit  If a third flexotron800 is used  it can be configured so that it is connected to  EXOline via port 26001  for example     46    SAUTER CASE flexotron VC SAUTER    flexotron800 with TCP  The following figure shows the communication routes in a router for which the NAT    connection was set to two flexotron800 units  The same scheme also applies when  3  4  5 or more units of the flexotron800 are used           L   TCP IP p       INTERNET diii  White IP    ROUTER  26486    WAN  x   ABD aA ATIP APO     Public port      WS    LAN     Local port  80               1  i   1    i       rN     i  i       IP  192 168 0 20 IP  192 168 0 30    For example  if you want to access the unit with the black IP address 192 168 0 30   in the address field of the web browser of the client computer you need to enter the  white IP address or DNS of the router  followed by    81     
40. nput Output   Fn Time Contra    Pa etna    n Maruat uto   ie Configuration     System       Model RDT828F221   Serial Number xx1110310482   Version 31 14   Address 254 254     General  Ventilation mode d  Outdoor temperature 6 11  C    Timechannel normal speed Of    Timechanne  reduced speed Off  Extended operation normal spe   ON       Supply temperatura 193  C  Supply setpoint 20  C  Controller Output 0    Extract Ar  Extract temperature 24 45   C  Deract setpoint 20 C  Controller Output 20   z controlled Sup  Actual Setpoint Compensation 0   Output normal spaad 75  Output reduced speed 50  Controller Output 0   controlled Extr  Actual Setpoint Compensation 0  Output normal speed 75  Output reduced speed 50  oler Output 0       The program window is divided into several areas    D The menu bar with Windows style drop down menus      2  The toolbar with direct access to various functions  All the functions of the  CASE flexotron toolbar can also be accessed via the menu bar      3  Various tabs Select the tabs to see the folders below them      4  Status bar     This manual describes the functions of the various items in the menu bar and the  CASE flexotron toolbar  The functions are essentially the same for all flexotron800  applications    Because the contents of the folders differ depending on the program  they are not  discussed in detail here        For more information  see the relevant flexotron800 controller manual     P100012097 B 9    SAUTER CASE flexotron    Start
41. odules   search for controllers             SAUTER CASE flexotron Ventilation    Untitled  cg  X  AMS eif     s c  i mI SAUTER    4         E Overview   T Actual Setpoint   ir Alarm Status       Input Output   Ga Time Control   Pd Settings       Manual Auto    El Configuration       Extended operation normal spe         Supply Air  Supply temperature  Supply setpoint  Controller Output      Extract Air  Extract temperature  Extract setpoint  Controller Output         Frequency controlled Sup      Actual Setpoint Compensation  Output normal speed   Output reduced speed  Controller Output       Frequency controlled Extr       Actual Setpoint Compensation  Output normal speed    Extended operation reduced sp          System  Model RDT828F221  Serial Number 901110310482     die  3114 flexotron  Address 254254     General  Outdoor temperature  Timechannel normal speed  Timechannel reduced speed       Select Model       Version        RE          If CASE flexotron cannot establish a connection to a connected controller when it is  put into service  this is often caused by an incorrect controller address  This function  scans all possible addresses and address lists to find the controller that is connected  to the computer  These addresses are then entered in the address field in the  Configuration System folder        Set module date and time   module controller   Synchronises the date and time of the controller with the date and time of the    computer        Edit module address  
42. ommerue Desktop Applications        Datei Ansicht Einstellungen Hilfe             Bamielm iscimmt SAUTER        bersicht   T Aktuelle Sollwerte      O Alarm Status   ees Ein Ausg  nge   un Zeitkontrolle 4 Einstellungen       Manuell Automatik   JE Systemkonfiguration    4    F Einstellungen    Zuluftventilator Lauf  berwachung     D    Reglereinstellungen hak       AL Alarmeinstellungen Nesta Tena   Petey s Stop Ventilator bei aktivem Alarm Nein   Alarm text Run Error Supply Air Fan          Abluftventilator Laufuberwachung  Klasse B       Verzogerung 120s   Stop Ventilator bei aktivem Alarm Nein   Alarm text Run Error Extract Air Fan     P1 Heizregisterpumpe Storung   Klasse B   Verzogerung 5s   Stop Ventilator bei aktivem Alarm Nein   Alarm text Run Error P1 Heater     P1 Kuhlregisterpumpe St  rung   Klasse B   Verzogerung 5s   Stop Ventilator bei aktivem Alarm Nein   Alarm text Run Error P1 Cooler     P1 WRG Storung   Klasse B   Verzogerung 20s   Stop Ventilator bei aktivem Alarm Nein   Alarm text Run Error P1 Exchanger       Filterwachter  Klasse B             Verzogerung 180 s  Stop Ventilator bei aktivem Alarm Nein  Alarm text Filter guard     Stromungswachter  Klasse B  Verzoaeruna 5s E  2 Online    3  Normal      Eingeloggt  Benutzer 02 11 2012 14 26 42          When you place the cursor on a parameter value  the setting intervals possible for  this parameter and the default value are displayed     Changes need to be downloaded to the controller before they come into 
43. on    tab               SAUTER CASE flexotron Ventilation    Untitled   a    yo m   File Edit View Tools Help  DAMADA Sollee K SAUTER       Overview   52 Actual Setpoint      DF Alarm Status     4 Input Output   Fs Time Control   AF Settings       Manual Auto    l Configuration    75    General  Model RDT828F221  Language English  System Start Screen Show headline  date time  vent mode  supply temp setp  Start Screen Headline flexotron 800   ex Note screen line 1 Cascade Control  amp CO2  Note screen line 2 Ventilation  Input Output Note screen line 3 Made by   Note screen line 4 Fr  Sauter AG  Automatic switch between summer and winter time On   e z i   es 3  Time before automatically logging off in display  unit 5 sec  60  Analog Input Start up wizard in display Off  PLA Address 254  ELA Address 254  tg Fares Process Picture C  Program Files EXO  lmages    entiation Pictures S auterC       Modbus  2i ES   DialUp  Gt    SMS function    Additional Functions   Web site     E mail  C Communication settings  n  Pump Control       This tab contains all the configuration parameters for the flexotron800   Since the contents of the tab are quite extensive  they are divided into sub folders   You can go directly to the sub folders using the list on the left side        For more information about the sub folders  consult the relevant controller manual     P100012097 B 39    SAUTER CASE flexotron SAUTER    Expansion units    9 Expansion units    P100012097 B    One or two extension uni
44. on Temp    Filter Guard 1   Heat Pump Indication  Cooling Pump Indication  Fire Alarm   Fire Damper Indication  Extended Operation  Normal  External Alarm   External Switch   SAF Indication   EAF Indication    Heating Y 1  Exchanger Y2  Cooling Y3  Not used   Not used    SAF Start 1 1 Normal Speed  EAF Start 1 1 Normal Speed  Heating Pump Start                      s     02 11 2012 15 58 30                      51    SAUTER CASE flexotron VCSAUTER    flexotron800 with TCP    12 5 Logging into the website    The following image shows the login page for the flexotron800         Air Handling Controller  flexotron 800          SAUTER       Login          Air Handling Controller    Login    Password     2  C  Remember the password    Login       Log in by entering the password specified under    TCP IP   gt  WEBsite and e mail  settings      12 6 Changing values on the website    P100012097 B          SAUTER    Ls Overview     gt  Actual Setpoint      Alarm Status   2  Input Output Gin Time Control   Settings     Manual Auto    Air Handling Controller    Q Climate    L  Ventilation  Za       All values in blue can be changed     Once a value has been changed and confirmed with Enter  the value is downloaded  to the flexotron800     Real time trend charts in flexotron800 with TCP  This feature allows real time trend charts to be managed directly on the website     You can use the  Copy to clipboard  command to copy the currently displayed values  into the chart  as tab delimited te
45. onfiguration       gt    Inputs  xt Dudo Temp       GE ei S S Le REIN v SAUTER       y Supply Temp  System p    o Synchroreze parameters   m  gg UAIT     The parameters shown below does not have the same value in the cortealler as in the tool  hide UAIZ     Select the parameters you want to update  Input Output UAI3  ualg    Parameter Corirolier value Tool Value    Y  vee  nalog Input                          gt  The controller should now have the latest version and can be configured    as before the upgrade     Q    d 03  Run Indication Motor Protectan  9 Ans   e pot      Actuatot Corirol Signal DO2    BeadNow  Selectas   Unselect Al Update Toot        Update Controle   e a   00d          Ei rire f Nama      Logged ofi 02 11 2012  155857       10  Make sure the parameter settings not available in the previous version have    the correct values     42    SAUTER CASE flexotron VC SAUTER    TCP IP network terms    11 TCP IP network terms    11 1 Networks  subnets and routers    IP network An IP network is a cluster of cables and devices in which devices with IP addresses  can communicate with any other device with a different IP address  The internet is a  network  and when a computer is connected to the internet  it becomes part of the  internet     Subnet The networks are divided into subnets  which are  in turn  connected with routers   The routers need a map of the network  or at least the nearest subnets  and an  address in order to send the information  A computer require
46. parameter    gt  This causes this particular parameter to be downloaded    1  Right click a group name  2  Select  Load parameter      All parameters for the selected group are downloaded    1  Click the  Load all parameters  field in the toolbar    1  Click  Settings  in the menu bar and select  Load all parameters    With the last two methods  all parameters are loaded onto the controller     The parameters can also be synchronised as described above  To do this  select     Synchronise all parameters      This is a useful feature for comparing the controller settings to those in CASE  flexotron     Resetting parameters to default values   1  Right click to select the  Reset all parameters to default values      P100012097 B 29    SAUTER CASE flexotron    Folders    8 2  Overview  tab    VSAUTER          rn  G SAUTER CASE flexotron Ventilation    Untitled             Eje Edt Vew Toos tip zi     m eajmi ls ciemt                System    Model   Serial Number  Version  Address       General    Ventilation mode   Outdoor temperature  Timechanne  normal speed  Timechannel reduced speed  Extended operation normal spe     Extended operation reduced sp       ido Rar    Supply temperature  Supply setpoint  Controller Output       Extract Air    Extract temperature  Extract setpoint  Controller Output       Frequency controlled Sup       Actual Setpoint Compensation  Output normal speed   Output reduced speed  Controller Output      Frequency controlled Extr       Actual Setpoint Com
47. pensation  Output normal speed   Output reduced speed  Controller Output       Outdoor Comp  Curve Pre       Outdoor temperature for lower      Pressere compensation at lowe     Outdoor temperature for higher      Pressure compensation at higer     Pressure flow compensation o     Pressure flow compensation o         C02    CO  sensor       Online  F Normal       Logged off    RDT828F221  xx1110310482  3 1214  254 254    Stopped   amp  11 C    19 9   C    24 45   C    822 nnm zl       02 11 2012 15 45 44                                                  Most of this tab consists of the start screen or a process diagram     The diagram is a static bitmap image that can be created and edited with MS Paint     for example  Any number of different diagrams can be saved   The diagram displayed depends on the parameter settings for plant schematics in    the System sub folder of the Configuration folder     A list of the main setting parameters is located on the bottom left in the folder   To update these values  you can either use F5 or the refresh function on the toolbar   It is also possible to update the display with dynamic values automatically  see     Options  on page 23      P100012097 B    30    SAUTER CASE flexotron    Folders    8 3  Current Setpoints  tab    Displays relevant setpoints and actual values     SAUTER                 e SAUTER CASE flexotron Ventilation    Untitled  A c      File Edit View Tools Help  E  e  eimi sS zie Ae SAUTER  Coven  E  7  Actual Setpoint 
48. ppears  there is no connection between the TCP IP card of the  controller and the operating system on the motherboard of the controller    The reason for this may be an old version in combination with a specific version of a  component on the TCP IP card    The problem can be solved by loading the latest version onto the controller   However  a connection must be established first  a catch 22 situation   A connection  can be established through repeated restarting and searching  Otherwise  the  controller must be returned to the factory for updating     P100012097 B 26    SAUTER CASE flexotron SAUTER    Menu bar    6 5    Help       P100012097 B    Automatically with DHCP  dynamic IP address   In this case  select the standard setting    Obtain IP settings automatically  with  DHCP       This configuration is appropriate for most networks equipped with a DHCP server   and especially when dynamic allocation of IP addresses to the controllers is required   The following requirements must be met   e The DHCP server and DNS server must co operate with each other   because the controller sends its DNS name to the DHCP server  Windows  2000 Server  Windows 2003 Server and Windows 2008 Server support this  feature  This feature is included in most routers  The DHCP server assigns  an IP address to the controller and registers the IP address or DNS name in  the DNS server   e Each DNS name must be unique   e TCP port 26486 must be open from the controller to the host computer  This  
49. ribes all program specific functions except for the parameters of the  flexotron800 controller     For these  read the controller manual and use the appropriate application     The website for the TCP models of the flexotron controller now has a dynamic flow  chart that changes according to the current configuration     SAUTER CASE flexotron    Installation    3 Installation    VSAUTER    CASE flexotron can be installed and used with the following operating systems     Windows 2000  Windows XP  Windows Vista  Windows 7  Windows 8    In order to use the web versions of the flexotron800     Internet Explorer 7 0 or higher  and Java    are required     An interface converter  RS485 to USB  is required for the connection     Installation    1     d    P100012097 B    Download CASE flexotron from the SAUTER homepage  www sauter   controls com     Unzip the zip file  otart the setup exe file located in the unzipped folder  Follow the instructions of the installation program    SAUTER CASE flexotron VC SAUTER    About the CASE flexotron tool    4 About the CASE flexotron tool    CASE flexotron Ventilation and CASE flexotron Heating are Windows based PC  programs for configuration and maintenance of various controllers of the flexotron800  series     CASE flexotron was not designed to be a complete SCADA program              4 1 Program window   e SAUTER CASE flexotron Ventilation    Untitled  ce 3   DE aml aln els cle EK c SAUTER  GH Em   T Actual Setpoint      dlam Status      Se I
50. riod  period of use   set the time to 00 00 00    e To make the controller run 24 hours a day  set the time to 00 00   24 00   A period cannot be set across midnight  If a period of use of 18 00   02 00 is to be  configured  it must be divided into two periods of use     e Day 1 from 18 00 to 24 00  e Day 2 from 00 00 to 02 00    Public holiday   holiday period calendar               SAUTER CASE flexotron Ventilation    Untitled  cg  X  DABAT AlS cli me V SAUTER    Overview   T Actual Setpoint      D Alarm Status       Input Output Ga Time Control    F Settings       Manual Auto        Configuration       1  on Time Control Add holiday period         La Time Schedule   5  Normal speed time   5  Reduced speed time   5  Extra Time Channel 1    Holiday Period 1        Extra Time Channel 2    e   Extra Time Channel 3 Select a holiday period in the calender below   5 Extra Time Channel 4        9 Extra Time Channel 5   23 Holiday Schedule                         e Up to 24 different holiday periods and public holidays can be configured  A  holiday period can be both a single day and up to 365 consecutive days     e A holiday period can be created using the Add holiday period field on the  bottom right     e lf only a single date is to be selected  just click it and confirm your choice  with  OK     e  o mark a period  click the start date  hold the mouse button down and drag  the cursor to the end date  and then release the mouse button  Then confirm  your choice with  OK   Altern
51. s 44  UENIT                                         44  3    VSAUTER    SAUTER CASE flexotron VC SAUTER    Table of contents    12 TiexolroneDO with TCP 45  121   CONMOCHON MR                 45  12 2 Two or more flexotron800 with TCP units through a single router           46  12 9  Webserver cohligblatloEi cid a 49  12 44  Website Selllligs sesos 51  12 5 Logging into the website         ccccccoonccnccccccncnnnccnnoncnnonononnnnnononancnnnononanenonoss 52  12 6 Changing values on the website            oooccccccccccnconccononccnnononancnnncnnnanenonoss 52    P100012097 B 4    SAUTER CASE flexotron VC SAUTER    List of changes    List of changes    Date Rev  Ver  issue Change Section Page  12 02 2013 P100012097 New document All All  01 08 2014 P100012097 B Software update to version 3 3        P100012097 B    SAUTER CASE flexotron VC SAUTER    Preface    1 Preface    P100012097 B    The SAUTER CASE flexotron user manual applies to the following control systems     e Heating control  CASE flexotron Heating   e Ventilation control  CASE flexotron Ventilation     This manual is provided by SAUTER without a guarantee   SAUTER may modify or improve this manual at any time and without prior notice   All changes will be included in future versions of this manual     Revision status B  August 2014     SAUTER CASE flexotron VC SAUTER    About this manual    2 About this manual    P100012097 B    O    This manual is intended to help users install and operate CASE flexotron     It desc
52. s only the address of  the nearest router  A locally connected Ethernet network is a subnet  Routers can  have multiple Ethernet interfaces for different Ethernet networks  or an Ethernet  interface and an ADSL connection     11 2 IP address  subnet mask  default gateway  DNS server  IP address Every computer or network attached controller has an IP address consisting of four  numbers between 0 and 255  with a total of 32 bits   Subnet mask Every computer or controller attached to a network also has a subnet mask with 32  bits     Example  If the IP address is 192 0 2 73 and the subnet mask is 255 255 255 0  the  subnet addresses range from 192 0 2 0 to 192 0 2 255  192 0 2 73 is the address of  your subnet  The subnet mask is sometimes determined by the number of bits used   it always starts at the beginning of the subnet mask   The subnet is then  192 0 2 0 24  and the IP address and subnet mask can be specified together   192 02 73 24     Default gateway Every computer and every controller that uses TCP IP communication must know  the IP address for the router that goes out from the subnet  The IP address of the  router is usually called the default gateway  All information sent from the local  subnet is sent to the default gateway     DNS name The computer or the controller must know the device address with which tt is  connected  This information can be given as an IP address or DNS name  DNS is a  function that can convert hierarchical names such as masterrechner sauter
53. se  the same address  since the internal workstations do not connect with each other   This type of addressing is called internal addressing     Reserved The following addresses are reserved for internal networks   addresses 192 168 0 0   192 168 255 255   172 16 0 0   172 31 255 255   10 0 0 0   10 255 255 255    See also  RFC1918  Address Allocation for Private Internets  Online document     cited Nov 29 2005   available at http   www  ietf org ric ric1918 txt    Public Unique addresses on the internet are called public addresses  Further information  addresses on the use of IP addresses can be found under RFC3330  Special use  IPv4  addresses  http   www ietf org rfc rfc3330 txt     NAT During internet retrieval  firewalls can function as agents with computers with  internal IP address  The connection from a computer with an internal IP address is  converted into a connection from the firewall  with a public IP address  to the  internet server  The information retrieved from the internet server is sent back to the  firewall  which forwards it to the computer with an internal IP address  This process  is called NAT  Network Address Translation  or  P masking     NAT router A NAT router can also forward information from the public network to a computer on  the internal network  For this  a special TCP or UDP interface forwards the  information to an IP address on the internal network     11 5 Tunnel    Two internal Another way of enabling a connection via the internet from a
54. sor error    Relative Humidity su  9 ept 00 52 Class B       If the text is changed to    Sensor error RH Supply air     the following appears     Sensor error RH    SUPP alr  SE SES Class TB       38    SAUTER CASE flexotron VCSAUTER    Folders    8 9  Manual Automatic  tab    Most controller functions can be manually operated on this tab  This is useful mainly  for testing purposes               fj SAUTER CASE flexotron Ventilation    Untitled         os XT  File Edit View Tools Help  Baila iD    c  i ae    SAUTER       Overview   T Actual Setpoint      Df Alarm Status    S  Input Output      gp Time Control    F Settings i Sh    Manual Aulo   Y Configuration         Supply Air    Ventilation Unit  Mode Auto Mode Auto  Controller Output 0  Ventilation mode Stopped     Frequency controlled Supply A      Supply Air Fan  Mode Auto Mode Auto  Controller Output 0  Normal speed     Frequency controlled Extract     Reduced speed  Mode Auto    Extract Air Fan    Controller Output 0  Mode Auto  lg Exchanger Normal speed    Mode Auto Reduced speed  Controller Output 0    Heater Pump      Heater Mode Auto    Mode Auto Pump On  Controller Output 0      Cooler  Mode Auto  Controller Output 0        Manual operation of functions causes alarms to be generated  which ensures that the  control is reset to automatic mode     In this menu  all changes are downloaded directly into each connected controller   The    Load parameters    function is not required here     8 10    System Configurati
55. storage    capacity  the image should be in  jpg format or similar     The e mail address to which the alert is to be sent  the title and the subject of the    message must be specified here     After you have made all the above settings and downloaded them to the TCP IP  card  all you need to do is download the settings to the web server in the  flexotron800  This is done with the Settings   Load website to controller command        r  6 SAUTER CASE flexotron Ventilation    Untitled              File Edit View   Tools   Help   E  Gl   E E Load all parameters     ra  k    D      c Overview      Synchronize all parameters       Reset all parameters to default values       En Time Control     Settings      Manual Auto JE Configuration         v SAUTER            Reload Controller       E Search for Controllers     EA     S Set Controller date and time     Change Controller address         Load Web site to the Controller          Upgrade COntroller operating system           Log on       Contre    zu  O  m  O  E Upgrade operating system for Web server  TCP IP      o  3           Ge      Realtime chart       Additior          Note     a  n    Z Options          Run Indication Motor Protection    SA    Actuator Control Signal       z     E Offline   0  Normal     Logged off          ff  Communication settings            401  A02  AD3  AD4  AD5       Digital Outputs  0    D02  D03    moe    Outdoor Temp  Supply Air Temp  Extract Air Temp  Room Temp 1    Deicing Temp  Frost Protecti
56. temp 20 B 30 min  High extract air temp High extract air temp 21 B 30 min  Unblock Low extract air temp Low extract air temp 22 B 30 min  Electric heating is overheated Electric heating is overheated 23 A Os  Low frost guard temp Low frost guard temp 25 A Os  Low efficiency Low efficiency 26 B 30 min  Sensor error Outdoor temp Sensor error Outdoor temp 27 B 5s  Rotation guard exchanger Rotation guard exchanger 29 B 20s  Fire damper is out of operation Fire damper is out of operation 30 B 30 s o  Supply Air Fan external operation Supply Air Fan external operation 33 E 120s eo  Extract Air Fan external operation Extract Air Fan external operation 34 E 120s eo  Ventilation stopped Ventilation Manual mode 35 E Os o  Manual supply air control Manual supply air control 36 E Os  Manual Supply Air Fan mode Manual Supply Air Fan mode 37 E Os  Manual Supply Air Fan freq control Manual Supply Air Fan freq control 38 E Os  Manual Extract Air Fan mode Manual Extract Air Fan mode 39 E Os  Manual Futrart Air Fan fran oantal Manual Folract Air Fan fran oantal An i Mo       The alarm settings can be changed in one of the following ways   e By double clicking the alarm  e Or by selecting the alarm and clicking Settings  e Orin the    Settings   gt  Alarm Settings    folder    Changes to the alarm settings must be loaded into the controller for activation     Alarm display  The following statuses exist for the alarm   e  Non activated alarms are indicated with a green status box   e Active alar
57. ts can be connected to the flexotron800  A controller of type  flexotron800 V2 is required for this purpose     Any flexotron800 model can be used as an extension unit  However  a flexotron800  without a display is preferable because nothing is shown on the display of the  extension unit    Either  Extension unit 1  or  Extension unit 2  can be selected under Applications in  the controller    After the extension units have been put into service and the program has been  configured  all flexotron800 units are connected  To download the configuration  the  main controller is then connected to the computer through the selected port  The  controller s configuration corresponds to the description in section 8     40    SAUTER CASE flexotron SAUTER    Updating of flexotron800    10 Updating of flexotron800    CASE flexotron should always be updated with the latest program version  If the  latest version of CASE flexotron is connected with a flexotron800 controller with an  older version of the program  CASE flexotron displays two warnings     An alternative is to temporarily downgrade CASE flexotron to the version of the  controller  All controller settings are retained  and the controller keeps its software  version     The second alternative is to adapt the controller to the CASE flexotron version  This  causes the flexotron800 to be temporarily taken out of service  Previous settings are  permanently deleted     If the following steps are carried out  a new configuration is req
58. ues are calculated using the pulse value that can be set in the Pulse Value  sub menu in the Configuration folder     31    SAUTER CASE flexotron    Folders    SAUTER    8 5    Alarm Status    tab    P100012097 B    Allows the alarms to be edited                        fj SAUTER CASE flexotron Ventilation    Untitled  a            jm Sm   File Edit View Tools Help  EB  amp iv  lgsitmieitciemt SAUTER  Les Overview   2 Actual Setpoint i Alarm Status     5 Input Output   Ga Time Control   Pa Settings       Manual Auto    zl Configuration    4  Alarm Alarm text Nbr Class Delay Status    All classes Iv Alarm objects  Iv Supply Air Fan is out of operation Run Error Supply Air Fan 1 B 120s   v Extract Air Fan is out of operation Run Error Extract Air Fan 2 B 120s  B P1 Heater is out of operation Run Error P1 Heater 3 B 5s  m P1 Cooler is out of operation Run Error P1 Cooler 4 B 5s  P1 Exchanger is out of operation Run Error P1 Exchanger 5 B 20s  All statuses v Filter guard Filter quard 6 B 180   eo  E Flow guard Flow guard 7 B 5s  Vv External frost quard External frost quard 8 4 Os  Iv Deicing pressure guard Deicing pressure guard 9 B 5s  z Fire alarm Fire alarm 10 4 Os  M External switch External switch 11 E Os  External alarm External alarm 12 B Os  Supply Air control error Supply Air control error 13 B 30 min  High supply air temp High supply air temp 15 B 5s  Low supply air temp Low supply air temp 16 B Bs  Block High room temp High room temp 19 B 30 min  Low room temp Low room 
59. uired   1  Start CASE flexotron and connect to the controller        When prompted  downgrade the version of CASE flexotron to the controller  version     Incompatible controller detected _    The controller contains program version 3 2  which  is older than your configuration  3 3   Select an  action below to resolve the problem     Make the configuration compatible with the     controller  Note that some newer features may  be lost     Make the controller compatible with the   r  configuration  i e  reload the controller with a  newer program version  Note that the controller  settings will be lost         Cee     2  Inthe    Settings    menu  select Synchronise all parameters   Then choose Update Tool     gt  CASE flexotron should now have an exact copy of the controller  configuration     Use Save as to save the configuration under an appropriate name   Close CASE flexotron    Reopen CASE flexotron    Choose the option of loading the controller with a new version       The controller is reloaded   8  Open the saved configuration file       p9    pt Se ok    P100012097 B 41    SAUTER CASE flexotron    Updating of flexotron800    P100012097 B    9  Synchronise all the parameters and choose Update Controller     VSAUTER       E  Oo SAUTER CASE flexotron Ventilation   RDT828 cascade CO2 draft  CAlUsersisommerve Desktop Applications        Ale Edit Wew Took Hep      E Qveeview    7  AguaySetpont      LF Atam Status    2   rouDupa   Gp Tine Cora   A Settings   O Manualiuto LE C
60. uter  which  in turn  is connected to an ADSL cable  modem    o flexotron800 with TCP has not yet been tested with all internet service providers   If the flexotron800 is connected behind a router with a built in firewall  the router must  be configured   The router should have a fixed public IP address     The controller must be found by the router  either by sending the IP address to the  controller or by specifying the MAC address of the flexotron800    All incoming traffic on ports 80 and 26486 should be routed with NAT to the  flexotron800 internal IP address        Additional information can be found in the router manual     Ports 80 and 26486 on the internet modem thus have to be open for inbound data  traffic     This web server technology is built into the flexotron800 and is based on the web  server integrated in the flexotron800     With a NAT connection  you can connect to more than one web server with a single  white IP address     A flexotron800 can handle up to five connections from CASE flexotron and Internet  Explorer simultaneously     P100012097 B 45    SAUTER CASE flexotron VC SAUTER    flexotron800 with TCP    12 2 Two or more flexotron800 with TCP units through a single router    P100012097 B    You can connect to two or more flexotron800 with TCP units through one router if the  communication routes are defined in the router     This is called port forwarding or NAT connection  In this method  the router knows  which black IP address  LAN  it should con
61. ved to the second row     If you use a hyphen as the 19th character  followed by a space  you can prevent the  entire word from being moved to the next line     33    SAUTER CASE flexotron SAUTER    Folders    Example      Sensor error Relative Humidity supply air  consists of 40 characters  but  since the    third word extends beyond the 19th character  the following appears on the display     Sensor error    Relative Humidity su  OM SCO US 52 Clas e       If the text is changed to     Sensor error RH Supply air     the following appears     Sensor error RH  SUDIOTO w o eile  Sept Gila ss o       8 6    Inputs Outputs    tab    Displays current values for all inputs outputs            fj SAUTER CASE flexotron Ventilation    Untitled          jm S   File Edit View Tools Help  Bagg eifm vi  cimrmt SAUTER       Overview   T Actual Setpoint      Df Alarm Status   254 Input  Output      n Time Control   AF Settings       Manual Auto   JE  Configuration         Analog Inputs    Analog Outputs  A11   Outdoor Temp 6 11   C 401   Heating Y1 oy  Al2   Supply Air Temp 19 9  C AD2   Exchanger Y2 Dv  AI3   Frost Protection Temp 32 39   C 403   Cooling Y3 Dv  Al4   Extract Air Temp 24 45   C AD4   SAF 0v  UAI   C02 Sensor 822 ppm AD5   EAF oy  UAI2   Extra Sensor Temp 1 20 66  C    Digital Outputs     Digital Inputs DO1   Heating Pump Start On  DI   NO   External Switch Off DO2   SAF Freq Start Off  DI2   NC   Frost Protection On DO3   EAF Freg Start Off  DI3   NO   SAF Indication On DO4 
62. version installed on the computer  The following dialogue window  appears     Reload controller    Y ou are about to reload the controller  The  following steps will be carried out       The tool parameter settings will be synchronized with the  controller parameter settings  Select the parameters you want  to keep in this step       The controller will be reloaded       The tool parameter settings will be loaded to the controller     x          Click  OK  to load the new controller  The  Synchronize parameters  dialogue  window is displayed     16    SAUTER CASE flexotron VC SAUTER    Menu bar    P100012097 B          The parameters shown below does not have the same value in the controller as in the tool   Select the parameters vau want to update     Parameter Controller value Tool Value Description  Room setpoint 2  2    404 Not used Extra Sequence Y 4    I Ventilation contral mode Cascade room temp control Constant supply air          Read Now   Select All   Unselect All   Update Tool   Update Controller   Close      The application program is loading into the  controller  press Cancel to interupt     After the controller has been reloaded with the new application program  the  following dialogue window appears     SAUTER CASE flexotron Ventilation    Untitled     A The controller is successfully reloaded  in partition 16        Load website to controller       Loads the configuration onto the web server in the flexotron800  A model with  TCP IP communication must be used
63. xt   TSV      This text can then be copied to an Excel  file  for example     If the  Copy to clipboard  command is executed  a dialogue box opens in which the  granularity of the values to be copiedcan be selected     The following options are available     e 1 hour  e 15 minutes  e 1 minute    e 5 seconds    52    SAUTER CASE flexotron VC SAUTER    flexotron800 with TCP    The most suitable alternative is pre selected  taking into account the current interval           e Air Handling Controller  flexotron 800   Windows Internet Explorer provided by Fr  Sauter AG PAS  vere WW      Add signal     AUW  v         y  Auto         17 04 17 05 17 06 17 07 17 08 17 09 17 10 17 11 17 12 17 13 17 14  05 Feb 2013 05 Feb 2013    Signal Scale Last value Show  B supply temperature Left 16 1 G a  A Supply setpoint Left 20 0   C          During the copying process  a title line is first created  Then a line is generated for  each period duration  based on the selected granularity  for the time range displayed  in the chart  along with the signals     e The title line consists of a date  followed by the names of the different  signals  including the units  in parentheses      e The additional lines consist of a time that the values for the different signals  follow  with the configured number of decimal places  but without units      Date and time specifications and decimal symbols are displayed in country specific  format and according to the settings of the computer on which the web brows
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
- Wavecom Instruments  Bedienungsanleitung BE1-28 Glastür-Kühlschrank  Küppersbusch EMWK 6260.0  Terms and Conditions  Samsung LE-55B650T2WXZG LCD TV  Cassetta per la messa in fase del motore - FORD Engine  HP D2D2504 User's Manual  the User Manual Here - NVT OnDemand  Oxygen Concentrator 7F-5 User`s manual      Copyright © All rights reserved. 