Home
        IO-16-REM-H - QWERTY: Control Systems & Engineers
         Contents
1.           3 62     92mm        y                NPB PWR UN H or  10 16 REM H 10 16 REM H             3 25      82 55mm     Distance between center of tabs from  one unit to another unit     Fig  14  Tab mounting dimensions     95 7768   03 22    23    95 7768   03    Automation and Control Solutions  Honeywell International Inc    1985 Douglas Drive North   Golden Valley  MN 55422    Honeywell Limited Honeywell Limit  e  35 Dynamic Drive  Toronto  Ontario M1V 4Z9    U S  Registered Trademark       2010 Honeywell International Inc     95 7768   03 M S  Rev  04 10  customer honeywell com EIRA    Honeywell    
2.      power blip    backup only for its on board circuitry  as well as a    graceful shutdown    of its running station  if a longer power outage  occurs        NOTE  The other    direct attachment type    I O expansion modules  lO 16 H  IO 34 H  using Ndio driver  already provide this  type of    shutdown protection    described above        An  O 16 REM H with battery backup can provide continuous system operation during a power event   essentially making it a     non event    for both the controller and the 1O 16 REM H module  Depending on the capacity of the external battery ies   this  backup operation can extend over many minutes of AC power loss  and or over multiple successive power blips  An  10 16 REM H wired this way is often described as    powered by the controller     although during normal operation  sometimes  power is actually supplied by the NPB PWR UN H module attached to  and powering  the controller itself     Note this    supplied by controller    battery backup operation is not available when using  O 16 REM H modules with WEB 201 600  or CP 201 600 series controllers  that is controllers without the 6 position power RS 485 connector  Or  in any scenarios where  1O 16 REM H modules must be located many hundreds of feet away from the controller  cabling    voltage drop    issues   In these  cases  you must locally power those IO 16 REM H modules  using one of two methods     e Local NPB PWR UN H attachment to the 1O 16 REM H module s   Although convenient
3.    United States    Phone  804 254 7086  ext  11    Return to     Tridium  Inc    2256 Dabney Road  Suite C  Richmond  VA 23230   Attn  Return Department RA     Asia Pacific  Phone   65 6887 5154 Fax   65 6887 5342  Mobile   65 9665 6024  Address   Tridium Asia Pacific Pte Ltd Email for technical support   101 Cecil Street  hclim tridium com     10 11  Tong Eng Building   Singapore 069533  Attn  Mr Lim Hoon Chiat  Engineering Manager RA     Sales   Australia   Phone   61 7 5539 1211 Fax   61 7 5597 2334   Japan   Phone   81 044 829 1750    CERTIFICATIONS    Federal Communications Commission  FCC    This equipment generates  uses  and can radiate radio frequency energy  and if not installed and used in accordance with the  instruction manual  may cause interference with radio communications  It has been tested and found to comply with the limits for  a Class A computing device pursuant to Subpart J of Part 15 of FCC Rules  which are designed to provide reasonable protection  against such interference when operated in a commercial environment  Operation of this equipment in a residential area may  cause interference  in which case  users at their own expense will be required to take whatever measures may be required to  correct the interference  Any unauthorized modification of this equipment may result in the revocation of the owner s authority to  continue its operation     Canadian Department of Communications  DOC     e This Class A digital apparatus meets all requirements 
4.   Battery backed                           DC    10 1 ween  Voltage             Output                                        D    NOTES  Not shown is RS 485 Communications wiring  on    the bottom 3 positions of the 6 position connector plugs   Here  terminal    BB    is not used  and may be left unwired           Fig  6  Third party 12Vdc  battery backed  power supply powering I0 16 REM H modules        NOTE  Power must be regulated to within   4      The power supply and its enclosure must be UL 294 approved   Power supply models furnishing 12Vdc output are the most commonly available     Only remote  O 16 REM H modules can be powered by a 12Vdc power supply   the controller requires 15Vdc   Depending on controller model  this 15Vdc may be furnished by an integral power supply  or from an external power  supply module  such as the NPB PWR UN H  See the appropriate controller  model  Mounting  amp  Wiring Guide docu   ment for details        95 7768   03 12    REMOTE I O MODULE  I0 16 REM H     RS 485 Communications    RS 485 communications from the controller to each  O 16 REM H module  or assembly of modules  requires a continuous     daisy chain    wiring topology using a shielded  twisted pair cable  Wire between device assemblies using the 6 position end  connector plugs  Use shielded 18 22AWG wiring  refer to the TIA EIA 485 standard     Wire in a continuous multidrop fashion  meaning    plus to plus        minus to minus     and    shield to shield     Connect the sh
5.   be aware that this invites power  event issues  See    Operation without battery backup       e Third party  battery backed 12 15Vdc power supply  wired to the PS  and PS  terminals of the IO 16 REM H module   s 6   position end connector  This is typically recommended  for reasons noted below     Note that power wiring for all different scenarios is included in this document  See    Wiring Details     page 9     Operation without battery backup    If a  O 16 REM H module is powered locally with a NPB PWR UN H  for example  a WEB 600 or CP 600 controller   and a  momentary AC power loss occurs  a number of undesirable things can result  including     e Load cycling from  O 16 REM H relays dropping out  including several seconds lag to first re establish communications with  the controller  Nrio driver  before relays can pull in again  as needed    e Totalized    counts    zeroed out    e History  logging  entries for associated IO points as    down     as well as Nrio    device down    alarms     Additionally  loss of power without battery backup makes an IO firmware upgrade a risky operation  Such an upgrade is initiated  from the    Nrio Device Manager    view  in a station connection to the controller   If this upgrade process is interrupted by a  IO 16 REM H power cycle  the module may be rendered inoperable   and will likely need to be replaced     Therefore  consider powering  O 16 REM H modules with a battery backed 12V power supply  as necessary     Voltage drop con
6.  controller   s 6 position    Powered RS 485    connector  such as on a SEC H 600 controller  This  is the recommended method       Using a DIN mountable NPB PWR UN H power supply to furnish 15Vdc power to the 1O 16 REM H       Using a third party 12 15Vdc power supply  with output regulated to within   4      If DIN mounting  a DIN rail  type NS35 7 5  35mm x 7 5mm  and DIN rail end clips  stop clips   and screws for mounting  See  Fig  1  If DIN rail not used  suitable screws for mounting base of Remote I O Module module   e Suitable tools and supplies for making all wiring terminations     PRECAUTIONS    This document uses the following warning and caution conventions       CAUTION    Cautions remind the reader to be careful  They alert readers to situations where there is a chance that the reader  might perform an action that cannot be undone  might receive unexpected results  or might lose data  Cautions  contain an explanation of why the action is potentially problematic     A WARNING    Warnings alert the reader to proceed with extreme care  They alert readers to situations where there is a chance  that the reader might do something that can result in personal injury or equipment damage  Warnings contain an  explanation of why the action is potentially dangerous     5 95 7768   03    REMOTE I O MODULE  IO 16 REM H     Safety Precautions    The following items are warnings of a general nature relating to the installation and start up of a compatible controller  Be sure 
7.  issue or mis configuration problem        95 7768   03 18    REMOTE I O MODULE  10 16 REM H   REPLACING THE I0 16 REM H      CAUTION    Before handling circuit boards  discharge any accumulated static by touching the nearby earth grounding point   For details  see the    Static Discharge Precautions    section on page 6     To replace the l1O 16 REM H accessory module in the field  proceed as follows     REPLACING THE 10 16 REM H ACCESSORY MODULE   1  Using the appropriate NiagaraAX software tool  back up the controller s configuration to your PC   2  Remove power to the  O 16 REM H  The unit should power down automatically     NOTE  If any I O points have voltage  turn the devices off or disconnect power to them     3  Note positions of all I O wiring going to the  O 16 REM H module to be replaced  as well as for any other installed  modules  If necessary  label connectors and accessory modules to avoid mis connection later  after  O 16 REM H is  replaced   The software that runs on the controller expects the terminal positions to be the same in the replacement  10 16 REM H  in order to collect data from or to control the attached devices    4  Unplug all connectors from the  0 16 REM H  including all I O connectors and earth ground wire     NOTE  Removal of the four pin mounted I O connector plugs may be difficult  For related details about removing them  see     About Screw Terminal Connectors     page 8     5  Remove any screws or DIN rail clips securing the  O 16 REM H 
8.  removing it from its mounting  See Fig  1 for details  on removal from  and mounting onto  DIN rail    6  Mount the replacement  O 16 REM H as it was previously  using the same DIN rail location and or screws    7  Reconnect the earth ground wire to the 1O 16 REM H grounding lug    8  Reconnect all I O connectors to the  O 16 REM H    9  If any of your I O points have voltage  turn the devices back on  or reconnect power to them    10  Reconnect the 6 position end mount connector  and ensure that power is applied to the IO 16 REM H as well as the    controller  For related details  see the    Power up and Initial Checkout    section on page 18   11  For more details  see the Niagara    NRIO Guide and Controller Niagara  Install and Startup Guide     19 95 7768   03    REMOTE I O MODULE  IO 16 REM H     Returning a Defective Unit    NOTE  Ifthe defective unit is under warranty  please follow return instructions provided in this section   If the unit is out of warranty  please discard it     Do not return an out of warranty IO 16 REM H module to Tridium     There is no    return for repair and return    service available for any controller accessory products        For proper credit on an in warranty unit  ship the defective unit to Tridium within 30 days     Prior to returning the unit  contact one of the following Tridium offices to obtain a return authorization  RA  number and other  instructions  Please provide       Product model    Serial number     Nature of the defect 
9. 4  digital Relay Outputs and four  4  0   10 volt Analog Outputs     Relay Outputs    Each relay output is rated at 24 Vac or Vdc at 0 5A  Relay outputs have MOV  metal oxide varistor  suppressors to support    inductive type loads such as heavy duty relay coils     A WARNING    Relays are not rated for AC mains  line level  powered loads  instead  24V maximum      Use an external 24V transformer or a 24Vdc power supply to power loads     Use a RelayOutputWritable in the station for each output  Fig  12 shows an example wiring diagram        24Vac AC  Transformer   Mains   see above    Line                 or             Use point  RelayOutputWritable             24Vdc Power 24Vdc  Supply                                  Fig  12  Relay output wiring diagram     95 7768   03 16    REMOTE I O MODULE   0 16 REM H     Note that the two common DO terminals  1C2  3C4  are isolated from each other  This is useful if controlled loads are powered  from different circuits     An LED status indicator for each relay  D1   D4  is located on the board  see Fig  2   and also visible through the cover  Under  normal operation  each digital status LED indicates activity as follows    e Off   relay open   no current flows    e On   relay closed   load current flows     Therefore  an On status indicates that the load is powered     Analog Outputs    Analog outputs  AO  are referenced by the terminals labeled An and OV  ground   Each AO can supply a maximum of 4 mA over  the entire 0 to 10Vdc ra
10. Honeywell    Remote I O Module  l10 16 REM H        APPLICATION    This document covers the mounting and wiring of a Remote  I O Module  lO 16 REM H   for expanding a WEBs AX or  ComfortPoint 200  600  or 700 series controller or SEC H 600  controller  It assumes that you are an engineer  technician  or  service person who is performing system design or  installation  Please read through this entire document before  beginning the installation procedures        NOTE  This document does not discuss mounting and wiring  of other components  or software configuration  For  more information on these topics  refer to documents  listed in    Related Documentation     page 2    Contents   FG ALUICS a cscs nice ccs renra beacttcedel ceded eaa a AERE inea 1   System PANNING essene a eE er 2   Preparation a ssc2 ce  cceecciesedeaesdes inteececssnetesteessuetestasensteseeess 5   PROCAUUOMNS  ccsact eytcctessisetceceieunesceceucateacuerwrayencceustensentacesaers 5   Installation and Start up Outline    0          cc eeeeeeeeeeeeees 6   Physical Mounting               c cceceeeeeceeeeeeeecaeeeeeeeneaeeetetenaeees 7   10 16 REM H Board Layout and Terminals                   8   Wiring Details 9   Grounding Rertrenerrenreere ter a ani 9   Power from controller 6 position connector s es 10    INSTALLATION INSTRUCTIONS    FEATURES    e The 1O 16 REM H expands a WEBs AX controller   controller with NiagaraAX 3 4 51 or later and an  available RS 485 port  see    System Planning     page 2  for m
11. OUT US   a E E aaa E E AE ENERE 16  Nrio16 Module  Software  Representation       17  Power up and Initial Checkout             ccccccccceeeeeeeeeeeeeeeeees 18  Replacement Parts              2 c ccccceecececeeeeeceeneaeeseeeenaeeeeeeees 18  Replacing the 10 16 REM H sssssssesseessrserrresresenn 19  Certifications 2  cisco  iiide ih cori seedrestceegesecststbietecceeesteca    95 7768 03    REMOTE I O MODULE  IO 16 REM H     RELATED DOCUMENTATION    For more information on mounting and wiring a system  refer to appropriate       WEB 201  CP 201  WEB 600  CP 600 Installation Instructions  Form   95 7722   e WEB 202 XPR  CP 202 XPR  WEB 602 XPR  CP 602 XPR Installation Instructions  Form   95 7775      WEB 700  CP 700 Installation Instructions  Form   95 7776   e SEC H 600 Installation Instructions  Form   95 7759   For software configuration details on the I O points provided by the 1O 16 REM H module  refer to   e NiagaraAX NRIO Guide     SYSTEM PLANNING    The maximum number of  O 16 REM H modules supported by a controller differs according to its model type  In addition   depending on the station resource usages in a controller  the  O 16 REM H modules may be limited to fewer than the maximum  specified in order to retain acceptable system operation  See    Supported numbers of  O 16 REM H    on page 2     Other considerations also apply when adding IO 16 REM H modules  For example  a  O 16 REM H module under a WEB 201   CP 201  WEB 600  or CP 600 series controller will not 
12. ail                                         Fig  1  1O 16 REM H module DIN mounting details        NOTE  To remove a lO 16 REM H module from DIN rail  remove DIN rail end clips or mounting tab screws  and  if applicable     slide it away from other modules  Insert a screwdriver in the center plastic locking tab and pull downwards  then lift the  unit outwards        7 95 7768   03    REMOTE I O MODULE  IO 16 REM H      O 16 REM H BOARD LAYOUT AND TERMINALS    The IO 16 REM H module provides 8 universal Inputs  4 digital Relay Outputs  and 4 0   10Vdc Analog Outputs  Wiring terminal    positions are shown below  Fig  2   along with LED locations   Analog Vdc Outputs   AOs  1 4                          Digital Relay Outputs   DOs  1 4                   6 Pin PS  f  Power In   PS  6 Pin Connector  RS 485 BB  Expansion Bus    Expansion RS 485     includes RS 485                               Bus  RS 485    RS 485 S  Earth Grounding  Connector Lug  Universal Inputs  gt    gt     s35 3 85S558  lt  lt  Universal Inputs   Uls  1 4  Uls  5 8                               Fig  2  Remote I O Module Wiring Terminal Locations  screw terminal connectors shown installed      About Screw Terminal Connectors    Screw terminal connectors are shipped loose in a separate hardware bag  If desired  you can make wiring terminations to  connectors before installing on the 1O 16 REM H circuit board pins  Removal of the pin mounted connectors may be difficult   especially if they are pushed all the wa
13. al    BB    is not used  and may be left  unwired                          Fig  5  NPB PWR UN H power supply module used to power IO 16 REM H modules     If the NPB PWR UN H powers additional  O 16 REM H modules  not attached in same assembly   wire a single pair cable with  shield between assemblies  connecting PS  to PS      and PS  to PS  in a    shortest route    fashion  See Fig  5  right     11 95 7768   03    REMOTE I O MODULE  IO 16 REM H     Power from third party 12 15Vdc power supply    1O 16 REM H modules can be powered by a third party  12V   15Vdc power supply  as an alternative to using a NPB PWR UN H    power  power    supply module  A    battery backed    power supply is recommended  This provides power to the IO module s  during AC  loss scenarios     Fig  6 shows wiring for two assemblies of  O 16 REM H modules powered by a battery backed power supply        NOTE  For power budgeting purposes  estimate each  O 16 REM H module to consume 2W nominal  125mW   15V   Typical    current will be less    as this estimate factors in all four relays being pulled in   For other wiring on the 6 position end connector  see    RS 485 Communications     page 13     Do not apply power  energize the power supply  until all other wiring is completed  See    Power up and Initial Checkout      page 18              Singl  to IO  Grou                e pair cable from power supply enclosure   16 REM H enclosure  PS   PS    mo    nd shield drain wire at one end only               
14. all four relays being pulled in     Do not apply power  plug in the 6 position connector at the controller  until all other wiring is completed  See    Power up  and Initial Checkout     page 18              Connect shield wire to  ground at one end only              Controller  with 6     position           powered    D   RS 485    3   connector Power Supply  15V  and 12V Backup Battery is routed to remote   IO modules using a 3 conductor with shield cable  Use the    gt  shortest wiring route possible for power wiring   star  tee  bus    and loop topologies are all permissible   NOTE  The    BB    wire is needed only if the controller has an  external  connected  sealed lead acid backup battery                    OOO                            RS 485 communications must be    daisy chained       to remote IO  modules using a separate shielded twisted pair cable                                      Connect RS 485 Shield wire  ae to ground at one end only                 1O 16 REM H             Fig  4  1O 16 REM H modules powered by controller connection  RS 485 wiring also shown      In some cases  some number of  O 16 REM H modules may be powered this way  from controller   while others may be powered  locally using either a NPB PWR UN H power supply module or a third party 12   15Vdc power supply  This may be advisable  when IO modules are located long distances from the controller  to avoid excessive voltage drops due to wiring resistances  See  the following sections    
15. ay not operate correctly   especially during emergency  battery backup  operation     The maximum allowable voltage drop due to wiring is 1 5V  This equates to the difference in voltage measured across the  PS  and PS  at the source controller power supply  and the PS  and PS  at the furthest expansion module  lO 16 REM H   Or   when powered by battery backup  the difference in voltage measured across the BB and PS  at the source controller  and the BB  and PS  at the furthest expansion module  lO 16 REM H      Table 3 provides a voltage drop chart  showing voltage drops per 100 feet of paired wire of different gauges  AWG   at different  load amps     Table 3  Voltage Drop Per 100 Feet Run  30m  of Paired Wire                                Gauge Load Current    AWG  0 10A 0 25A 0 5A 1 0A 1 5A 2 0A 4 0A  10 0 020 0 05 0 10 0 20 0 30 0 40 0 80  12 0 032 0 08 0 16 0 32 0 48 0 64 1 27  14 0 050 0 13 0 25 0 50 0 75 1 01 2 02  16 0 080 0 20 0 40 0 80 1 20 1 60 3 20  18 0 127 0 32 0 64 1 27 1 91 2 54 5 08  20 0 202 0 50 1 01 2 02 3 03 4 03 8 07  22 0 320 0 80 1 60 3 20 4 80 6 40 12 81                                     For an example  consider a system where two  O 16 REM H modules are mounted remotely in a location 500 feet  366m  away   In this example  worst case amps used by each remote  O 16 REM H is 0 125A  Looking at Table 3 at the 0 25A column  a  16  AWG cable pair drops 0 20V per 100 feet  meaning a 500 foot run would drop slightly over 1V   this would be a good choice 
16. d thermistor curve xml files  See the NiagaraAX NRIO Guide for details     Fig  8 shows the wiring diagram        Ul1 OV Ul2 UI3 OV Ul4       Cut and tape  shield wire back at  Thermistor     10K Thermistor                       Use point  ThermistorinputPoint                Shielded  Twisted  Cable  61m  200 ft   maximum    Shield  O Stud in enclosure                Fig  8  Thermistor wiring     Resistive 0   100K ohms    Inputs can read a resistive signal within a range from 0 to 100 000 ohms  Wiring is the same as shown for a Thermistor  temperature sensor  Fig  8      Resistive signals require a ResistivelnputPoint       CAUTION    UI inputs provide optimum resistive to temperature resolution in the 10K ohm range  For a sensor with a range  far from 10K ohms  such as a 100 ohm or 1000 ohm sensor   resolution is so poor as to be unusable  To  successfully use such a sensor  install a transmitter that produces a Vdc or mA signal  and then wire the  transmitter to the Ul according to the 0   10 Vdc or 4   20 mA instructions     0 10 Vde    Inputs support self powered 0   10 Vdc sensors  Input impedance is greater than 5K ohms  0   10 volt accuracy is  2  of span   without user calibration  Fig  9 shows the wiring diagram for a 0   10 Vdc sensor     0   10 Vdc sensors require a VoltagelnputPoint     Range  0 10 Vdc Ul1 OV Ul2 UI3 OV Ul4  Input Impedance  gt  5K ohms          Cut and tape  shield wire back  0   10Vdc Sensor at sensor      self powered sensor     2l       Use p
17. differ   If powering the 1O 16 REM H from a controller with a 6 position    Powered RS 485    connector  supplies 15Vdc and bat   tery backup on 3 wires of this connector   unplug this connector at the controller  Then wire to the 6 position connector  plug for each assembly of IO 16 REM H modules  in a    shortest route    fashion  See    Power from controller 6 position  connector     page 10   b  If powering the 1O 16 REM H from a local NPB PWR UN H power supply module  wire the disconnected AC line cir   cuit to the 2 position terminal block under the NPB PWR UN H   s cover   See    Power from local NPB PWR UN H module    on page 11   c  If powering the 1O 16 REM H from a third party 12   15Vdc power supply  wire the positive and negative lines from the  power supply to the PS  and PS  terminals of the 6 position end connector plug   See    Power from third party 12 15Vdc power supply    on page 12   3  Connect RS 485 wiring between the IO 16 REM H and the controller  and  if applicable  to other remote 1O 16 REM H  modules  in a continuous multidrop fashion  See    RS 485 Communications    on page 13   4  Connect I O wiring  See sections    Inputs    on page 13  and    Outputs    on page 16   5  Apply power to the unit  See    Power up and Initial Checkout     page 18     Grounding    An earth ground spade lug  0 187   is provided on the circuit board of the 1 O 16 REM H  and NPB PWR UN H  for connection to  earth ground  For maximum protection from electrostatic dischar
18. e    Power from local NPB PWR UN H module     page 11    e    Power from third party 12 15Vdc power supply     page 12    95 7768   03 10    REMOTE I O MODULE  I0 16 REM H     Power from local NPB PWR UN H module    If powering 1 O 16 REM H modules from a directly attached AC power supply  NPB PWR UN H module   wire the AC circuit to  the NPB PWR UN H   s 2 position terminals  must remove cover   See Fig  5  left     A WARNING    A 120Vac or 240Vac circuit powers the NPB PWR UN H  Disconnect power to this circuit before installation to  prevent electrical shock of equipment damage     Make all connections in accordance with national and local electrical codes  Use copper conductors only     Do not exceed the 30W capacity of NPB PWR UN H by the powered devices        NOTE  For power budgeting purposes  estimate each  O 16 REM H module to consume 2W nominal  125mW   15V   Typical  current will be less    as this estimate factors in all four relays being pulled in     For other wiring on the 6 position end connector  see    RS 485 Communications     page 13     Do not apply power  energize the NPB PWR UN H  until all other wiring is completed  See    Power up and Initial Check   out     page 18                   NPB PWR UN H  with cover removed                                  120 or 240Vac  50 60 Hz  Single Phase    Earth Ground                         NOTES  Not shown is RS 485 Communications  wiring  on the bottom 3 positions of the 6 position  connector plugs    Here  termin
19. e the NrioNetwork   s    Port Name    property to match the controllers RS 485 port COM assignment  for exam   ple  COM2   and set its    Trunk    property to a unique number Nrio wide  say  2     4  From the NrioNetwork   s Nrio Device Manager view  perform a Discover   Each discovered remote I O module will be listed in the top    Discovered    pane in the view  with each 1 O 16 REM H  appearing as an    lo16    device type     NOTE  To associate a discovered device to a specific  O 16 REM H  issue a right click    Wink Device    action   this cycles a  relay output on that  O 16 REM H several times  which you can hear or see if nearby  This action is available both  before and after a discovered device is added to the station     5  Add each discovered  O 16 REM H to the station  renaming to reflect its actual location  see Note above   Each IO  module is represented by an Nrio16Module component   6  Verify that each IO 16 REM H module   s board status LED is now lit solid green     NOTE  Ifan Nrio16Module is selected in the Nrio Device Manager view  and the Upgrade Firmware button is active  it is rec   ommended that you upgrade its firmware  After selecting this  do not interrupt power to the 1O 16 REM H and con   troller  or the communications between them  until the firmware upgrade job finishes  Typically  this takes less than 2  minutes  with job competition signaled in the Workbench view     7  You can now discover  add  and configure IO points under each Nrioi16Mod
20. estore power to such external power  supplies     Binary Input  Inputs support both pulse contacts and normal dry  equipment status  contacts   e Pulse contacts may have a change of state  COS  frequency of up to 20 Hz with a 50  duty cycle   Note  Minimum dwell time must be  gt  25ms   Contacts must remain open at least 25ms and be closed at least 25ms      e Standard dry contacts must have a 1 Hz   or less  COS frequency  with minimum dwell time  gt  500ms    Contacts must remain open at least 500ms and be closed at least 500ms      Both types of dry contacts support 3 3 Vdc open circuits or 330 pA short circuit current  For a pulse contact  use the  CounterInputPoint in the station database  For other dry contacts  use the BooleanInputPoint     Fig  11 shows the wiring diagram  which is identical for both uses   but with different types of Nrio software points used for either  application     15 95 7768   03    REMOTE I O MODULE  IO 16 REM H        Uli OV Ul2 UIS OV Ul4             Pulse Cut and tape  Range  Up to 20 Hz  shield wire back  50  Duty Cycle at contacts   Minimum dwell time   gt  25ms    20202802          Shielded  Twisted  Cable  61m  200 ft   maximum    Use point  CounterinputPoint                 Cut and tape    Dry Contacts shield wire back  at contacts              Use point  BooleaninputPoint    i Shielded  Twisted    Cable  61m  200 ft     i Stud in enclosure  maximum             Fig  11  Binary input wiring     Outputs    A 10 16 REM H module has four  
21. ge or other forms of EMI  connect each device   s earth ground  using a  16 AWG or larger wire  Keep these wires as short as possible     See Fig  3 for the location of the earth grounding wire for both the 1O 16 REM H and NPB PWR UN H                     One or more  10 16 REM H  modules             a             m lla                      NPB PWR UN H   if used for power              Earth Ground    Fig  3  Earth ground connection required to each IO 16 REM H module as well as NPB PWR UN H  if using         NOTE  Connect any remote  O 16 REM H modules to a nearby earth ground in the same manner        9 95 7768   03    REMOTE I O MODULE  IO 16 REM H     Power from controller 6 position connector   If powering one or more  O 16 REM H modules from a controller equipped with a 6 position    Powered RS 485    connector  the  15Vdc and 12V backup battery  BB  is typically routed to remote modules using a 3 conductor with shield cable  The remaining 3  conductors are used for RS 485 communications between the controller and the IO modules  using a separate shielded twisted  pair cable  See Fig  5       NOTE  Ifthe controller is not connected to a  optional  external  sealed lead acid battery  the    BB    wire is not required  This per   mits use of a single pair shielded cable  versus a 3 conductor with shield cable     For power budgeting purposes  estimate each  O 16 REM H module to consume 2W nominal  125mW   15V   Typical  current will be less    as this estimate factors in 
22. have the inherent    battery backup    feature provided by the WEB or CP  700 controller platform  See    About battery backup operation    on page 3     Finally  when cabling power to  O 16 REM H modules located in locations other than the controller  allowances must be made for     voltage drops    introduced by cabling distances  See    Voltage drop considerations    on page 3     Supported numbers of  O 16 REM H    Table 1 below provides a quick comparison of controller models compatible with  O 16 REM H modules  including the maximum  possible number of  O 16 REM H modules supported        NOTE  Station operation of each controller at maximum limits below with only the necessary NiagaraAX software components   Nrio driver and associated points  is roughly at 50  resource usage  without other driver networks  control logic  and so  on  Therefore  maximum numbers may be less for a controller  particularly if an existing WEB 201  CP 201  WEB 600 or  CP 600 is connected to one or more    Ndio based     lIO 34 H  1O 16 H  modules     Currently  only controller models listed below  at NiagaraAX 3 4 or later  support  O 16 REM H modules        Table 1  Maximum number of 1O 16 REM H modules supported  by compatible controller platform models                          Max  Number of  Controller model 10 16 REM H  6 Position Power RS 485  WEB 201  CP 201 4 On board RS 485 port or  NPB 2X RS485 Option Card  gt   WEB 202 XPR  CP 202 XPR 3 6 Position Connector w  Power and Battery Ava
23. ield to  earth ground at one end only  such as at the controller  See Fig  7           Controller RS 485 Port   either on the 6 position     Pwr 485    connector or a  separate 3 position  RS 485 port              Shielded   twisted pair  cabling          Connect RS 485  shield wire to ground  gt   at one end only                                                  Oo F Terminals on the  2   lt 4    6 position  connector plugs  used for RS 485  between  assemblies                                    10 16 REM H          Lh  3  2i  21  2i             Fig  7  RS 485 wiring from the controller to one or more  O 16 REM H modules uses a    daisy chain    connection     Inputs    Each of the 8 universal inputs  UI  can support any one of the following     Type 3 10K ohm Thermistor  also see Caution on page 14   e Resistive O   100K ohms  e 0 10 Vdc  e 4 20 mA     Binary Input    13 95 7768   03    REMOTE I O MODULE  IO 16 REM H     Thermistor    Inputs support 10K Thermistor temperature sensors  Input accuracy is in the range of  1  of span  By default  conversion is for  a standard Type 3 thermistor sensor  with a sensor range of  10   to 135  F  23 3   to 57 2  C   Using a conversion type of    Tabular  Thermistor     you can specify a different thermistor response curve  by importing a thermistor curve  xml file  Currently  the kitlo  module contains an xml folder with thermistor curves for a various thermistor temperature sensors  You can also edit and export   for reuse  customize
24. il     WEB 600  CP 600 16 On board RS 485 port or  NPB 2X RS485 Option Card  gt   WEB 602 XPR  CP 602 XPR 15 6 Position Connector w  Power and Battery Avail       WEB 700  CP 700 16 6 Position End Connector w  Power and Battery Avail      SEC H 600 49 NPB 2X RS485 Option Card  gt   SEC H 201 N A No connection to SEC H 201                   a Maximum number of  O 16 REM H modules may be reduced due to utilization of controller resources    gt  Provide power to modules from an NPB PWR UN H module or a battery backed 12 15V DC Power Supply         Approximately 4 IO 16 REM H modules may be powered by the controller power supply  Calculate total current draw of the  controller and powered devices to determine the actual count  Additional IO 16 REM H modules may be powered by an  NPB PRW UN H power supply or a battery backed 12 16 V DC Power Supply    d A total of 15 Modules may be connected to an SEC H 600 controller  Connecting  O 16 REM H will reduce the number of  Security Modules that can be connected     95 7768   03 2    REMOTE I O MODULE  I0 16 REM H     About battery backup operation    When IO 16 REM H modules are powered by controller platforms with 6 position power RS 485 connectors  that is  wired to the  PS   PS   and BB terminals  they can benefit from    battery backed    protection against system power events  Note this requires  the controller to have the optional  external  sealed lead acid battery installed   as the controller   s internal NiMH battery provides
25. l ensures accurate alignment of connectors between all modules     If DIN rail mounting is impractical  you can use screws in mounting tabs on the  O 16 REM H  Mounting tab  dimensions are on page 22 of this document     TO MOUNT I0 16 REM H MODULE ON INSTALLED DIN RAIL    Position the  O 16 REM H module on the rail  tilting to hook DIN rail tabs over one edge of the DIN rail  Fig  1     Use a screwdriver to pry down the plastic locking clip  and push down and in on the  O 16 REM H  to force the lock   ing clip to snap over the other edge of the DIN rail    Slide the 1O 16 REM H module along the DIN rail to its intended location    If connecting to another module already mounted  seat its 6 position plug into that module   s connector socket   Install DIN rail end clips to secure the assembly  or install screws in mounting tabs    Repeat this for all items  until all are mounted on the DIN rail s   firmly connected to each other  and secured with DIN  rail end clips or mounting tab screws           Mounting on DIN Rail Removing from DIN Rail                               NPB PWR UN H             Ne i    ade ee   alent  gt  with cabling to  assembly   controller and  other remote     if used for power                                                 modules                                      D  e  Wiseni    gt                    Secure with screws in two  mounting tabs on right side  of last unit in assembly   NOTE  Be careful screws  do not twist or torque unit on  the DIN r
26. nge  For this 0   10V full range  the minimum input impedance of a device controlled by the AO must be  greater than 2500 ohms     If the device   s input impedance is  ess than 2500 ohms  the 4 mA    max  current    limits the voltage output range  For example  if a  device with a 1000 ohm input impedance  the AO would work as a 0   4Vdc analog output     Fig  13 shows typical wiring for an AO  For each AO  use a VoltageOutputWritable in the station database              O0   10Vdc device       Use point  VoltageOutputWritable             Input impedance  is greater than  2500 ohms    Common        Shielded  Twisted Cable   61m  200 ft  maximum    OOOO          AO1 0V A02 AO3 0V A04  Fig  13  Analog output wiring diagram        NRIO16 MODULE  SOFTWARE  REPRESENTATION    In the NiagaraAX station interface to the controller and 1O 16 REM H module  the module   s I O is modeled in the station   s  NrioNetwork  copied from the nrio palette   under a child Nrio16Module    device level    component  This Nrio16Module has a  default name of    io16_n           NOTE  After a remote I O module is discovered and added to the station under this NrioNetwork  each as one as an  Nrio16Module   the serial status LEDs for the controller s RS 485 port continually flash  reflecting polling activity  At this  time  the    STATUS    LED on that 1O 16 REM H module lights solid green    Any time a  O 16 REM H module   s status LED is not lit solid green  all of its outputs are in    fail safe    
27. of the Canadian Interference Causing Equipment Regulations        Cet appareil numerique de la classe A respecte toutes les exigencies du Reglement sur le material broilleur du  Canada     95 7768   03 20    REMOTE I O MODULE  I0 16 REM H     RoHS Compliance    This product meets RoHS  Restriction of Hazardous Substances  requirements of Directive EU 2002 95 EC     CE Declaration of Conformity             Date  June 19  2009  Application of Council Directive  EU EMC 2004 108 EC  Manufacturer  Tridium Inc    3951 Westerre Parkway  Suite 350   Richmond  Virginia 23233   United States of America   Manufacturer   s Representative  Steve Fey  President  Tridium Inc   Product Model Numbers   O 16 REM H  with the following  MDR 20 15  10722  10903  10724  10723   Type of Equipment  Electrical Equipment for Measurement  Control and Laboratory Use  EMS Standards Applied  Standard Description Criteria Met  EN 61000 6 4 Electro Magnetic Compatibility Emissions  Generic Compliant  EN 61000 6 2 Electro Magnetic Compatibility Immunity Compliant  as  noted below   CISPR 22  2006 Conducted Emissions   Telecom Compliant   CISPR 16 2 1 and Limits of Radio Disturbance   Conducted Emissions Pass Class A   CISPR 16 2 2 Pass Class A   CISPR 16 2 3 Radiated Emissions Compliant   IEC 61000 4 2 Electrostatic Discharge Immunity Pass Class B   IEC 61000 4 3 Radiated Field Immunity Pass Criteria A   IEC 61000 4 4 Electrical Fast Transient Immunity  Signal Ports  Pass Criteria B  Electrical Fast Transien
28. oint  VoltagelnputPoint  Conversion  Linear                Shielded  Twisted    Cable  61m  200 ft   maximum        Shield O Stud in enclosure  ie             Fig  9  0   10 Vdc wiring     95 7768   03 14    REMOTE I O MODULE  I0 16 REM H     420 mA    Inputs support self powered 4   20 mA sensors  Input accuracy is  2  of span  without user calibration  Fig  10 shows the wiring  diagram  which requires a 499 ohm resistor wired across the input terminals     4 20 mA sensors also require the VoltagelnputPoint        Ul1 OV Ul2 UI3 OV Ul4       4   20 mA Sensor Cut and tape   self powered sensor    Shield wire back  Range  0   20 mA atisensor                        Use point  VoltagelnputPoint  Conversion  500 Ohm Shunt  499 Ohm resistor secondary conversion  Linear   supplied with   unit                                Shielded  Twisted  Cable  61m  200 ft   maximum        Stud in enclosure  Shield             Fig  10  4 to 20 mA wiring       CAUTION    When using an externally powered 4 20 mA sensor  be sure to de energize its power supply before making or  changing any wiring connections to the IO 16 REM H module  This is in addition to removing power from the  10 16 REM H module     It is important to not apply external power to the UI inputs without the 499 ohm resistor in place  Otherwise  even  a momentary application of power  say  24Vdc  to the Ul terminals without the resistor may damage circuitry on  the 1O 16 REM H  Only after completing all input wiring should you r
29. onnect more than the maximum number of 1O 16 REM H modules to the RS 485 port of the parent  controller  See    Supported numbers of 1O 16 REM H     page 2     INSTALLATION AND START UP OUTLINE       NOTE  If installing the controller and  O 16 REM H module at the same time  please refer to the appropriate controller Mounting   amp  Wiring Guide document to install the controller        The major steps to installing and starting the  O 16 REM H module are outlined as follows     1  Physically mount the l1O 16 REM H module onto DIN rail  See    Physical Mounting     If directly attaching to other modules   ensure that the 6 position end connector s  are properly seated into the end connectors of the other units  Note the previ   ous    Module Connection Precautions    on page 6    2  Make wiring connections for grounding  power  RS 485 communications  and I O points  See    Wiring Details     page 9    3  Apply power and perform an initial checkout  See    Power up and Initial Checkout    on page 18     95 7768   03 6    REMOTE I O MODULE  l0 16 REM H     PHYSICAL MOUNTING    The following applies to mounting a  O 16 REM H Remote I O Module     You can mount the unit in any orientation  It is not necessary to remove the cover before mounting     Mounting on a 35mm wide DIN rail is recommended  The l1O 16 REM H unit base has a molded DIN rail slot and  locking clip  which simplifies mounting 2 or more units together  and or to a NPB PWR UN H power supply  Mounting  on a DIN rai
30. ore details  with 16 I O points that can be  remotely located  including     e 8    universal inputs  Uls   compatible with 0     10Vdc  4   20mA  dry contacts  pulsing dry  contacts  0   100K ohm resistive  or Type 3  thermistor temperature sensors     e 4 digital outputs with Form A relay contacts   for on off control of loads up to 24Vac dc  at  0 5A max     e 4 0 10Vdc analog outputs for analog control  of loads at 2 5K ohm minimum  or 4mA drain  maximum     e The lO 16 REM H modules use DIN rail mounting  and  have two end mounted 6 pin connectors that support  direct chaining  in line attachment  to other  10 16 REM H modules     e Communications to the remote controller are  accomplished using RS 485 multidrop on 3 wires of an  end mounted 6 pin connector or from an RS 458  Option Card  The other 3 wires on the end mount  connector are primary DC power and battery backup  for the module  which can be supplied from that same  controller if that controller is equipped with external  battery backup  Alternatively  you can power the  10 16 REM H locally with a DIN mountable NPB PWR   UN H universal AC power supply  or a third party  12 15Vdc power supply  and wire only the RS 485 bus  back to the parent controller     Power from local NPB PWR UN H module                 2 0 11  Power from third party 12   15Vdc power supply                 12  RS 485 Communications               cccccceeeeeseceeeeeeeeeteeeeeetees 13  Ig  0  8  eerereeereee tere rerrerer tere rr E tere 13  
31. over  an  18 AWG cable  which would drop over 2V  above the 1 5V maximum allowable drop      95 7768   03 4    REMOTE I O MODULE  I0 16 REM H     PREPARATION    Unpack the 1O 16 REM H module and inspect the contents of the package for damaged or missing components  If damaged   notify the appropriate carrier at once  and return for immediate replacement  see    Returning a Defective Unit     page 20   See the  next sections    Included in this Package    and    Material and Tools Required        Included in this Package    Included in this package you should find the following items       a Remote I O Module  lO 16 REM H    e this Remote I O Module  lO 16 REM H  Mounting and Wiring Instructions  Form Number 95 7768     a hardware bag containing the following items       Four  4  pin mount  6 position  screw terminal connectors for connection of universal inputs  analog outputs  and relay  outputs  For more details  see    About Screw Terminal Connectors     page 8       One  1  6 position screw terminal end plug  for wiring RS 485 communications from the parent controller  as well as  15Vdc power and battery backup       One  1  grounding wire  with quick disconnect 0 187  female connector       Eight  8  499 ohm resistors  used for 4   20mA inputs     Material and Tools Required    The following supplies and tools are required for installation     e Approved 12   15Vdc power supply source and  optional  12Vdc backup battery source  by either       Wiring to the remote parent
32. siderations   When using the controller and its backup battery to power IO 16 REM H modules  and some modules are not in the same  enclosure with the controller  you must be aware of voltage drops in the connecting    trunk power    cabling  Typically  this applies  only if modules are located in different locations   that is  not near the controller     NOTE  The 15Vdc power supply and the backup battery ies  charged by the controller must always be located nearby the  controller  either in the same enclosure  typical   or in an adjacent enclosure        Note that each 1O 16 REM H draws  at most  when all four relays are pulled in  0 125A  and thus can introduce voltage drop  when long cabling distances are used for power backup battery  In addition  when sizing the sealed lead acid battery ies  for a  controller  you should factor in additional Ah capacity according to the numbers of IO 16 REM H modules  Table 2 provides a  summary of 1O 16 REM H power consumption for these purposes     3 95 7768   03    REMOTE I O MODULE  IO 16 REM H     Table 2  Amps Watts  and Recommended Minimum 12V SLA battery A Hr capacities  per 1O 16 REM H           12V Backup Battery  4  hours   Max per Amps  W used min  recommended Ah  Device System   15Vdc  each   each  Notes  10 16 REM H See Table 1   0 125 A   1 88 W 0 65 Ah Has 4 on board relays                       Undersized selection of power cabling can result in unacceptably high voltage drops  and remotely located  O 16 REM H  modules m
33. state  all relay out   puts OFF  and all AOs are at a 0 volt level      Blinking of a remote I O module   s status LED occurs for two reasons  shown at different rates     Rapid flash  low duty cycle   meaning the unit is unconfigured  Discovery and addition to the station database is  required     Equal time on and off  50  duty cycle   meaning the unit is configured  but currently offline with the controller  Check  RS 485 wiring between the controller and remote I O module        Each input or output used requires a special Niagara Remote Input Output  Nrio  point to be added in the station database   These components act as the station interface to the physical I O points  The Nrio points you need for each input or output type  are noted in previous wiring sections in boldface     For Nrio software details  see the NiagaraAX NRIO Guide in Workbench online Help  or that document in PDF     17 95 7768   03    REMOTE I O MODULE  IO 16 REM H     POWER UP AND INITIAL CHECKOUT    1  Apply power to the 1O 16 REM H  depending on power source  this may mean plugging in a 6 position end connec   tor  energizing a NPB PWR UN H power supply module  or powering on the connected controller or third party 12     15Vdc power supply     The lO 16 REM H module   s board status LED  Fig  2  will initially be blinking   2  Using Workbench  open a station connection to the controller  If not already present  add an NrioNetwork compo     nent to the station   s Drivers Container    3  Configur
34. t Immunity  AC Power  Pass Criteria B   IEC 61000 4 5 Surge Immunity Pass Criteria B   IEC 61000 4 6 Conducted Immunity Pass Criteria B   ICES 003  Issue 4 Conducted Emissions   Voltage  Class A Compliant   ICES 003  Issue 4    Radiated Emissions   Class A Compliant   IEC 61000 4 11 Voltage Dips Pass Criteria A  Voltage Interrupts Pass Criteria C   IEC 61010 10 1  Safety requirement for electrical equipment Pass   90  A1 92   A2 95 for measurement  control and laboratory use          Steve Fey  President of Tridium Inc   hereby declare that the equipment specified above conforms to the above Directives and  Standards        NOTE  For CE compliance  the NPB PWR H power supply cannot be used to power the 1O 16 REM H or a WEBs AX Control   ler  In its place  use the DIN mountable Tridium model MDR 20 15  This CE approved power supply is 100 240Vac  input  with 15Vdc output at 20W    Or  power the l1O 16 REM H using another third party  CE approved  battery backed 12Vdc power supply     A WEBs AX Controller must be powered by a 15Vdc power supply with CE approval        21 95 7768   03    REMOTE I O MODULE  IO 16 REM H     TAB MOUNTING DIMENSIONS  q    3 25     82 55mm    OO Sna   0 170    Dia    t    IO 16 REM H  4 32mm        or  NPB PWR UN H       Note  Electronic and  printed versions of this  guide may not show  dimensions to scale   Verify all measurements    Fass       4          before drilling                 DIN mounting is  recommended over tab  mounting    See Fig  1 
35. to  heed these warnings to prevent personal injury or equipment damage     A WARNING    A 15Vdc circuit powers the lIO 16 REM H module from the controller  Disconnect power before installation or  servicing to prevent electrical shock or equipment damage     Make all connections in accordance with national and local electrical codes  Use copper conductors only   To reduce the risk of fire or electrical shock  install in a controlled environment relatively free of contaminants     Controllers and I O modules are only intended for use as monitoring and control devices  To prevent data loss or  equipment damage  do not use them for any other purposes     Static Discharge Precautions    These items are cautionary notes to help prevent equipment damage or loss of data caused by static discharge       CAUTION    Static charges produce voltages high enough to damage electronic components  The microprocessors and  associated circuitry within a Remote I O Module are sensitive to static discharge  Follow these precautions when  installing  servicing  or operating the system    Work in a static free area     Discharge any static electricity you may have accumulated  Discharge static electricity by touching a known   securely grounded object     Do not handle the printed circuit board  PCB  without proper protection against static discharge  Use a wrist  strap when handling PCBs  with the wrist strap clamp secured to earth ground     Module Connection Precautions      CAUTION    Do not c
36. ule   s Points device extension  For more  details about Nrio components  refer to the NiagaraAX NRIO Guide  also available in Workbench online Help  doc  Nrio      REPLACEMENT PARTS    Servicing the  O 16 REM H may call for replacement parts  There are two categories of parts      Standard Replacement Parts    e New Replacement Units    Standard Replacement Parts    Standard replacement parts are listed in Standard  O 16 REM H replacement parts  and can be ordered from stock without  restriction  Standard replacement parts cannot be returned for credit and should be disposed of in an appropriate manner     Table 4  Standard  O 16 REM H replacement parts              Part Number Description  H10716 6 position pin mount screw terminal block  H10429 6 position end mount screw terminal plug                New Replacement Units    To replace a faulty unit  order and install a new  O 16 REM H accessory module   please note that controller accessories do not  have special    field replacement units     or FRUs  with separate part numbers     If the faulty  O 16 REM H is still in warranty  you can receive credit by returning it to Tridium  Be sure to contact Tridium for a  return authorization  RA  number before shipping an item for return credit  See    Returning a Defective Unit     page 20  for more  details        NOTE  Before ordering a new IO 16 REM H  it is strongly recommended that you contact your normal technical support  resource to eliminate the possibility of a software
37. y down and wiring has been landed     In general  it may be easiest to wire to loose connectors  held next to pins   then install them after completing       CAUTION    Before using the method below to remove connectors  remove all power to the 10 16 REM H  and remove power  to any other connected external devices  Otherwise  a short circuit will result     To remove a pin mounted connector plug using needle nose pliers  with all power removed  see Caution above     e Insert the tips of the pliers into the outermost wiring termination ports of the connector  Note that if wiring is already  landed in those ports  you may need to remove those wires first   e With a gentle rocking motion  pull upwards  perpendicular to the circuit board     e The connector will come free from the circuit board pins  If you removed wiring from the outermost connector ports   reconnect that wiring as it was before     95 7768   03 8    REMOTE I O MODULE  I0 16 REM H     WIRING DETAILS    See Fig  2 to locate connectors and other components on the Remote I O Module   Make connections to the Remote I O Module in the following order     1  Connect the earth grounding wire  with spade connector  from the earth ground lug on the IO 16 REM H to a nearby earth  grounding point  See the    Grounding    section on page 9 for details   2  Wire to supply power to the IO 16 REM H  but do not energize the power source until all other wiring is completed   a eee on how you are powering the  O 16 REM H  methods 
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
Samsung DVD-R120 Manuel de l'utilisateur  Dossier Galettes    安 全 上 の ご 注 意 ※必ずお守り取扱説明書  Altronix MAXIMAL11D power distribution unit PDU    MKV-A BOSS User`s Manual Drawing Number: SWM69000940  Graco Stroller PD216493B User's Manual    Copyright © All rights reserved. 
   Failed to retrieve file