         Contents
1.  connection diagram on  the inside of the external cover will assist in identifying the LED    NOTE  The battery might show a    Low Battery Fault    initially until it has had time to charge  up to the required level     If by some chance the fault will not cancel  and only on the advice of our Technical  Support Department  return the P C B  CHASSIS ONLY to your supplier  DO NOT return  the plastic box    Once the panel is found to operate satisfactorily in the NORMAL MODE  it is time to  connect the external circuits    It has been assumed that prior to making the connection at the panel  the integrity of  the system ALL wiring has been comprehensively tested  including insulation to earth     Isolate the mains supply and disconnect the battery connection      Fitthe Active End of Line Device to the last detection device of zone one       Ensure all terminations are made correctly and all detector heads are plugged into  their bases       Connect Detector circuit ONE to the panel terminal block     Power up the panel with the mains and battery      Press RESET button    The panel should be in the    NORMAL MODE        NOTE  If General Fault and zone 1 FAULT LED s illuminate  there is a wiring   connection  problem  Check the polarity of the connection  the connection of the devices and whether  a head is removed    Check the EOL proper polarity and position       Operate ALL detection devices applicable to this zone  to ensure correct receipt of a fire signal  andthe corre
2. CONNECTION DEPENDS ON THE RECOMMENDED USE SCHOTTKY  TYPE OF THE DETECTOR DIODE TYPE 1N4819 OR SIMILAR  AC 230V   50 60 Hz    FAULT  RELAY  OUTPUT  CHANGE       Connection Circuit AE C5 4P    18010282 REV  1 0    FIRE ALARM  CONTROL PANEL        54   1 2 4  1997         6    SOUNDER 1 BATT   T  0 315A  T  2A    SOUNDER 2 AUX        0 315A    CABLE SHIELD   TERMINAL       REMOVE JUMPER       DISABLE EARTH FAULT    EE       o        e  e                      o  o  o  o    Break from   the box and   fix it to position      LASTDEVICE CALL DETECTOR CALL DETECTOR  ONZONE POINT  TYPE1 POINT TYPE2    f          CONNECTION DEPENDS ON THE RECOMMENDED USE SCHOTTKY  TYPE OF THE DETECTOR DIODE TYPE 1N4819 OR SIMILAR       230V   50 60 Hz    FIRE  RELAY  OUTPUT  FAULT  RELAY  OUTPUT  AUX 24V       Fire Alarm Record  Installation Address  ss    ContactPersonz               Le tete             eek edet dd  Telephone                    GIRL REOR E a               Date Completed  atia a E ir          EEaren  Commissioned LAL  alua AS laa ar  Service Intervals  Monthly   Quarterly   Half Yearly   Annually    ZONE LOCATION DETECTOR TYPE and SOUNDERS  NUMBER QUANTITY PER ZONE Zone Quantity and  Related Circuit    en       rer                                   FAX     Erkara iberia onini Cer rete a rd e S d E EA ER    10    Service Record    Date Zones Tested Faults Rectified Signature of   Next Visit  Completed Engineer Due                                     To IN IN IN m IN IN IN      NIN    ZO
3. NE   FAULT yes no and TYPE   ACTION TAKEN             number                         11       aguilera  electronica    eS aguilera    
4. USER MANUAL    FIRE CONTROL PANEL    AE C5 2P  AE C5 4P          INSTALLER Instructions    Contents Page  General Information    eic eed eee ene          2  Using aleka uuu eo dete        3  Indicators   SU           or Le ener eroe ae 3  Engineers  Facilities    inne Deb MED eI HERR 3  Installing the  Panel    2  Renee tede tetur 4  Testing    the              Gi tr tte e cfe      dard d 4  Engineers  FacilitlGs     s  3    1 eterne ae dm bet etait 6  Connecting the Additional Facilities rra 7  Specification        etel eut atti 8  Gotinection Seg 9  Fire Alarm Record sr 10  Service  Record   a cp E AEA ete tou 11  Fire Alarm                          ies 11  WARNING    This manual contains information on limitations regarding product use and function and information  on the limitations as to liability of the manufacturer  The entire manual should be carefully read     General Information  The systemis to be installed by a qualified person to the latest Fire Alarm and Installation Regulations  which are mandatory in the applicable country of installation     Before commencing the installation of this Fire Alarm Panel  ensure it is sited in a position  which is  visible to the Fire Brigade when entering the premises  and where ease of access is provided for users  andservice engineers  Space must be available to easily open external and internal doors    The Electrical Supply to the panel must be isolated and must not be capable of being accidentally  switched off  A    Lockab
5. a safe position    Drill the wall to suit the back box center fixing position  plug and insert a fixing screw   Temporally hang the back box from the fixing screw and mark out the two bottom left  and right fixing locations    Remove the back box from the center fixing screw position and drill and plug the bottom  fixing holes    Hang the back box from the center fixing position and fix securing screws through the  bottom fixing holes    Tighten all the fixing screws    Route the external cables onto the back box  make off connection glands etc   BUT DO  NOT make any connections at this stage  ENTER THE MAINS CABLE THROUGH ITS  OWN CABLE ENTRY POINT AND KEEP MAINS WIRING AWAY FROM SYSTEM AND  OTHER LOW VOLTAGE WIRING   Re fit the PCB chassis and re connect the chassis mains connection    Connect the mains supply and earth to the main terminal block BUT DO NOT apply the  main electrical supply at this stage    Position the standby battery in an upright position     The panel is now ready for testing     Testing the Panel    Connect the battery leads from the black power supply box to the positive and  negative battery terminals    Apply the mains power    If the buzzer and indicator LED   s are operating  press the RESET button    If in the Normal Operating Mode other LED   s are illuminated and the buzzer is sounding     carefully check that fuses and connections are sound  Refer to the part of the internal  connections or circuitry the associated yellow LED   s apply to  The
6. arity of the connection of each of the devices  the  polarity of the connection of the devices to the Panel terminal block or whether an earth fault  exists     Engineers Facilities     To Disable Zone 1   Press ENABLE   DISABLE button     Press ENABLE  DISABLE button   Press RESET   To Enable Zone 1     Press ENABLE   DISABLE button TWICE     Press RESET   To Disable Zone 2     Press ENABLE   DISABLE button     Press TEST   SCROLL button     Press ENABLE  DISABLE button     Press RESET   To Enable Zone 2     Press ENABLE   DISABLE button     Press TEST   SCROLL button     Press ENABLE  DISABLE button     Press RESET   To    One Man    Test a Zone     Press TEST   SCROLL button     Press TEST   SCROLL button     The  One Man    Test Mode will exit when pressing the TEST   SCROLL button again  or at any time     by pressing RESET     Zone 1 lamp will flash   DISABLE   ENABLE lamp will flash     The zone lamp will become steady   At this point the zone 1 is disabled     Zone 1 lamp will flash   DISABLE   ENABLE lamp will flash     Atthis point the zone 1 is disabled     Zone 1 lamp will flash   ENABLE   DISABLE lamp will flash     Zone 2 lamp will flash    ENABLE   DISABLE lamp will flash   Zone 2 lamp will become steady   ENABLE   DISABLE lamp will flash     Atthis point the zone 2 is disabled     Zone 1 lamp will flash    ENABLE   DISABLE lamp will flash   Zone 2 lamp will be steady   ENABLE   DISABLE lamp will flash   Zone 2 lamp will flash    ENABLE   DISABLE lamp will flas
7. cover of the box  remembering to connect the earth bonding lead to the continuity    terminal     Specification    Maximum number of detectors per zone    Thresholds for zone conditions    0 2 mA     2 6 mA    6       mA     110 mA   Short circuit    Power Supply  Main Power supply    Standby Power supply  Maximum current available for system  devices  with fully charged battery     Current consumption   mains failure    Outputs  Sounder Circuit 1    Sounder Circuit 2    Fault Relay    Auxiliary output  Cabling    Environment    Up to 32 conventional detectors and unlimited  number of manual call points     Open circuit fault condition   Normal condition   Fire Alarm condition     Short circuit condition     230V AC   10    0 315A fuse   1x 12   Sealed Lead Acid Battery  Up to 7Ah internally   2A fuse              50 mA    24V  0 315A   0 3A fuse   24V  0 315A   0 3A fuse   volt free changeover contacts  12V 1A or 24V 0 5A   Max voltage 125V   Max current 2A    24V DC 0 3A fuse    Maximum 2 5mm diameter    Working temperature 0 to 40 degrees C  Storage temperature  20 to 60 degrees C  Humidity 0 to 95     Connection Circuit AE C5 2P    18010278 REV  1 0    FIRE ALARM  CONTROL PANEL  EN54   1 2 4   1997         6    SOUNDER 1   T  0 315A  SOUNDER 2   T  0 345     T  0 315A    AUX    CABLE SHIELD     TERMINAL  A    REMOVE JUMPER TO  DISABLE EARTH FAULT    Break from   the box and   fix it to position A LASTDEVICE CALL DETECTOR CALL DETECTOR  ONZONE POINT TYPE 1 POINT TYPE 2    
8. ct operation of the panel controls  Refer to the User Instructions on the inside of the  panel      Repeatthe connection process for zone two as stated above  ENSURE the supply voltages are  initially disconnected prior to each stage    ONCE THE CONNECTION OF THE ZONES ARE COMPLETED  CONNECT AND TEST   ANY OF THE OTHER AUXILIARY CIRCUITS BEFORE CONNECTING THE EXTERNAL   SOUNDER CIRCUITS    Relay Connection   The onboard relay volt free change over terminals are for low   voltage use only    MAINS SUPPLY MUST NOT BE APPLIED TO THESE TERMINALS    Once the zone and auxiliary circuits have been connected and tested to function   correctly  it is time to connect the first external sounder circuit       solate the mains supply and disconnect the battery connection       Remove the End of Line Monitoring Resistor from the terminal block of sounder circuit 1   SND 1  and fit to the last sounder of circuit one       Check all sounder connections are made      Connect sounder circuit ONE to the panel terminal block      Apply mains and battery power      Press RESET   The panel should be in the    NORMAL MODE       Activate a zone Call Point  The sounders should operate  Press the reset button     Repeat the connection process for the second external sounder circuit  as stated above   ENSURE the supply voltages are initially disconnected prior to each stage     NOTE  If General Fault and SOUNDER FAULT   DISABLE LED     s illuminate  there is a wiring   connection problem  Check the pol
9. fault condition should they fail  Selecting an  Engineers  Facility    will indicate and announce a Fault condition at the panel     NOTE  FAULT CONDITIONS WILL NOT BE ANNOUNCED INSTANTLY  THERE WILL  BEA SHORT DELAY WHICH WILL VARY FROM CONDITION TO CONDITION  FAULTS  WHEN CLEARED WILL AUTOMATICALLY RESET AT THE PANEL     Engineers Facilities     PANELS has the ability to select various facilities to assist the  engineer during installation and testing of the system  These  facilities include     Zone Test    Isolate Sounders   System can be tested without operating the Sounder circuits   Disable   Enable Zone   Each zone can be disabled   enabled     3    Installing the Panel    Decide the best location for the panel position  with an ambient temperature between  0       40   C  away from heating systems  environmental dust and potential water ingress   Remove all packaging    Inspect the panel for any damage    Carefully remove the outer cover  by inserting unscrewing the two allen screws  Stow  the cover in a safe position    Inspect the internal PCB and make sure the internal components are firmly in place   Observe the main PCB chassis and the associated securing screw  located in the front  of the terminal blocks    Unfasten the chassis securing screw and remove the chassis  Stow in a safe location   Choose which cable entry points to knock out and carefully remove the knock outs   Observe the top center fixing location at the back of the panel    Stow the back box in 
10. h     At this point zone 2 is enabled     TEST AND ZONE yellow LED   s will flash   Zone 1 is in Test Mode    Flashing LED will move down to zone 2   Zone 2 is in Test Mode     Disable Sounders     Press DISABLE   ENABLE button     Press TEST   SCROLL button again     Press TEST   SCROLL button  once again     Press ENABLE   DISABLE button     Press RESET     To enable Sounders   Press DISABLE   ENABLE button   Press TEST   SCROLL button     Press TEST   SCROLL button  once again     Press ENABLE   DISABLE button     Press RESET     DISABLE   ENABLE lamp will flash   Zone 1 lamp will flash   Zone 2 lamp will flash     SOUNDER FAULT   DISABLE lamp will flash   DISABLE   ENABLE lamp will flash     SOUNDER FAULT   DISABLE lamp changes to steady   ENABLE   DISABLE lamp flashes   At this point zone the sounders are disabled     DISABLE   ENABLE lamp will flash  Zone 1 lamp will flash   Zone 2 lamp will flash     SOUNDER FAULT   DISABLE lamp will be steady   DISABLE   ENABLE lamp will flash     SOUNDER FAULT   DISABLE lamp change to flashing   ENABLE   DISABLE lamp flashes   At this point zone the panel has reset     Connecting The Additional Facilities    Class Change     Connect a    non latching    switch to the class change terminals at the top of the MAINBOARD     Operation of the switch will cause the external sounders to pulse one second on followed by one    second off     Oncethe panel connections and facilities have been functionally tested  replace and secure  the front 
11. le Switch fuse Unit    positioned within 2 meters of the panel should be  clearly labelled FIRE ALARM   DO NOT SWITCH OFF     EN 54 2 compatible panels     All specifications are subject to change without notice     Using the Controls    Refer to the instructions on the inside of the outer door     Indications   Outputs  NORMAL  e The green LED next to the    power Supply 230V      will be illuminated     FIRE    Two integrated red status FIRE LED   s and a zone identification LED will flash  together on receipt of a FIRE condition and become steady after the Silence Alarm  button is pressed       Aninternal buzzer will operate until silenced     The external sounders will operate     The FIRE relay will energize     FAULT     Ayellow General Fault LED will always illuminate together with an external or  internal identification LED       Aninternal buzzer will sound      The FAULT relay will de energize    Faults are monitored as follows      Zone fault   open or short circuit  Detector head removed       Sounder Circuit One fault   open or short circuit  reverse connected sounder  or  bad sounder parameters       Sounder Circuit Two fault   open or short circuit  reverse connected sounder  or  bad sounder parameters       A C  Loss or Battery charger fault    A C  Loss  means Mains Supply     Battery Loss      Low Battery condition      24V DC Supply fault      Processor fault      Auxiliary supply fault      Shortcircuitto earth     All fuses are monitored and will cause a 
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
Bissell 92L3 Vacuum Cleaner User Manual  Hand Blender Set SSMS 600 B3    TRAY/CAP/LAM NATURAL  3M Quest Outdoor Measurement System Enclosure Kit User Manual    ABI User Manual - Global Medical Solutions  取扱説明書等  The game manual  MANUAL DE UTILIZAÇÃO DA IMPRESSORA / PC-FAX    Copyright © All rights reserved. 