Automation Components Inc.
Contents
1. 21 L Mess TE UC EE 22 j Configuring The Transceiver For MSTP RS485 Network 24 k Sending The Configuration File To The MOD9200 eseese 26 l Activating The Config File u g uarnismersiddsuasnnismekeimevnneinvedseede 29 IV Data AUTO E 31 BT Mn 31 b MOD9200BNT BACnet Transceiver Parameter 31 V MENT 35 a Configuration of the MOD9200BNT rooonnrrnonnnnnnnrrnnnvrnnnnnnnnnnrrrnnvrnnnnnnnnnnnnnnnn 35 b Installing the MSTP RS485 Network 35 P 4 of 37 Automation Components Inc MODBNT Rev 8 0 2011 Automation Components Inc MOD9200BNT BACnet Transceiver Installation amp Configuration I Introduction The ACI MOD9200BNT BACnet network transceiver utilizes reliable Spread Spectrum Mesh Network Radio technology When used with other Trs Systems wireless sensors the system can transmit remote sensor readings status alarm indications and MOD9200BNT control signals to a centralized networked monitoring BACnet Transceiver station or controller without the need for extensive wiring The MOD9200BNT is compatible with any control panels or automation systems that utilize the BACnet MSTP communication protocol a ACI MOD9200 Transceiver System MOD9200BNT BACnet MSTP Network Transceiver Receives input from up to 50 remote wireless sensor modules and or wireless output modules RD2402 amp RD2431 per Transceiver ACI signal repeater router RR2552 can be used to extend the wireless sensor transm
2. 10 P 36 of 37 Automation Components Inc MOD9200BNT BACnet Transceiver Installation amp Configuration 24 VAC Input Connect 24V AC 60 Hz and earth ground to the input terminals using 20 AWG wire as shown in the product data sheet Power up the MOD9200 Transceiver with the BACnet MSTP network Use BACnet Device Scan function to identify the MOD9200 Device Instance amp MSTP address Verify there is no address conflict with other node in the subnet Proceed to read object AI01 to AIXX amp AI101 to AI XX alarm property where XX is the last data register configured using the Trs Programmer Configuration software For AIXX XX Trs MOD9200 data Register Number 1 Automation Components Inc MODBNT Rev 8 0 2011 Automation Components Inc MOD9200BNT BACnet Transceiver Installation amp Configuration COPYRIGHT 2003 by Trs Systems Inc All rights reserved Trs Systems The Trs Systems logo WT2630A WT2630B WT2630C RC2100 RT2620A RT2620B RT2630A RT2630B RT2630C RT2630D RT2631A RT2631B RR2552 DT2630A DT2630B FT2630A FT2630B WH2630A WH2630B DH2630A DH2630B DH2630C OA2630A OH2630A OT2630A amp MOD9200 are trademarks of Trs Systems Inc All other brand or product names are trademarks of their respective holders For more information please contact Automation Components Inc 2305 Pleasant View Rd Middleton WI 53562 Telephone 1 608 831 2585 Fax 1 608 831 7407 P 370f37 Au
3. Click on Select File and a window will open Move to the Trs directory and select the appropriate file from the list Click on Open to automatically enter the selected file path as the File Name Automation Components Inc MODBNT Rev 8 0 2011 Automation Components Inc MOD9200BNT BACnet Transceiver Installation amp Configuration Enter the current IP Address of the Transceiver Note This can be different than the IP Address entered into the configuration file Bn ren ee C trs config ON B3 wm File Name TCP IP 1 92 168 0 1 IP Address TCP IP e Comm Status Disconnected Connect Disconnect File Status Get File returned as Se Cp ae ne L end File Cancel AMrsteonhig Con mu Click on Connect and the status of the connection will be displayed in the Comm Status window When the Transceiver is connected click on Send File to the send the config file to the Transceiver P 28 of 37 Automation Components Inc MODBNT Rev 8 0 2011 Automation Components Inc MOD9200BNT BACnet Transceiver Installation amp Configuration l Activating The Config File Once the config file has been sent to the Transceiver it will become active immediately If you have changed the IP Address in the config file you will lose your connection and have to reconnect using the IP Address and Subnet Mask that was sent in the new config file E me a C tre config LON B3 ini
4. Automation Components Ine MODBNTRev8 0 2011 e Input Register Configuration P 12 of 37 Automation Components Inc MOD9200BNT BACnet Transceiver Installation amp Configuration Each row of the configuration table is a unique data register having eight special attributes REG FUNCTION REG ADDRESS GROUP NAME POINT NAME TRANSMITTER ID TRANS CHAN DATA FORMAT LOG Identifies the function of the register Analog or Digital Discrete Note If selecting the Digital Discrete function be sure to set the appropriate Digital Capture Time Page 15 Assigns the address of the data register 0 to 99 Assigns a group name to the data register not used by BACnet Multiple data registers can have the same group name This is useful for monitoring and data logging programs Assigns a unique name to the data register to help identify the location of the sensor transmitter Not used by BACnet Multiple point names can have the same group name Assigns a wireless sensor transmitter address to the data register Each wireless sensor is factory configured with a unique hexadecimal address Assigns a wireless sensor transmitter data channel to the data register A wireless sensor transmitter may have up to four 4 analog channels and 4 digital status alarm channels Assigns the data type to the register temperature RTD or Thermistor 20K analog voltage totalizer or humidity This register is left bla
5. default temperature degrees C F and Digital Input Capture Time are set globally for all sensors using the Miscellaneous Dialog Screen Click on Settings gt Miscellaneous Unit Identifier POINT NAME TRANSMITTER ID TRANS CHAN Sunshade IE bes Serial Transport TCP IP Transport Network ID Miscellaneous Set the transmitter transmission timeout interval requires a minimum of 30 min by clicking in the Transmitter Timeout cell to open a drop down menu Use the scroll bar to scroll down to the appropriate value 1 to 60 min or type the value in the cell to automatically scroll to the appropriate value This will be used to generate an error message 1f the transmitter fails to transmit in the specified time interval Transmitter Timeout min Digital Capture Time 90 amp Seconds Minutes Digital Scaling Iw Digital Scaling On Degrees F Degrees C Register Yalue When Sensor Lost Retain Last Value Set to 19999 Cancel P 22 of 37 Automation Components Inc MODBNT Rev 8 0 2011 Automation Components Inc MOD9200BNT BACnet Transceiver Installation amp Configuration To select the timeout interval click on the appropriate value in the drop down menu The Digital Input Capture Time can be set to hold a momentary contact closure such as the override button on the WT2630B C for a period of time Default is 0 min amp recommended value is 1 min so the controller has time
6. File Name TCP IP 1 92 168 0 1 IP Address TCP IP e Comm Status Disconnected Connect Disconnect File Status Cancel To confirm that the appropriate configuration file is saved on the Transceiver reopen the File Transfer Dialog and click on Get File to retrieve a copy of the active configuration file from the Transceiver The Editor will automatically save this file in the folder trs with the file name of config in Click on File gt Open Config File and select the config ini file Click on Open to open the file in the Editor Confirm that the file 1s the same as the original configuration file Since the Group Name and the Point Name fields are not used by the MOD9200 transceiver these fields will now be blank All the other fields and settings should be the same as the original ini file P 29 of 37 Automation Components Inc MODBNT Rev 8 0 2011 Automation Components Inc MOD9200BNT BACnet Transceiver Installation amp Configuration File Settings Points Row RegisterEntry Register Bank REG ADDRESS GROUP NAME POINT NAME TRANSMITTER D TRANS CHAN DATA FORMAT ANALOG INPUTS 1 THERM 20k ANALOG_INPUTS 2 HUMIDITY ANALOG_INPUTS 1 THERM 20k ANALOG_INPUTS 1 THERM 20k ANALOG_INPUTS 1 THERM 20k ANALOG_INPUTS 1 THERM 20k NOTE The config ini file is a dynamic file If multiple MOD9200 Transceivers are being administered from the same PC the confg
7. Normal amp AV08 Lost Communication Example 2 AI108 returns a value of 40 representing AI08 Normal BV08 Lost Communication amp AV08 Lost Communication P 33 of 37 Automation Components Inc MODBNT Rev 8 0 2011 Automation Components Inc MOD9200BNT BACnet Transceiver Installation amp Configuration Example 3 AI128 returns a value of 42 representing AI28 Lost Communication BV08 Lost Communication amp AV08 Lost Communication Example 4 AI128 returns a value of 9 representing AI28 Low Battery Alarm BV08 Lost Communication amp AV08 Normal The MOD9200BNT Device Instance and MSTP MAC address will be preset from the factory and can be obtained using the BACnet Device Scan function To ensure no duplication of Instance address verify that no other node with the same address is present at the sub net where the MOD9200BNT will be residing For more implementation information please refer to the BACnet website www BACnet org or the ASHRAE American Society of Heating Refrigeration amp Air conditioning Engineers website www ashrae org P 34 of 37 Automation Components Inc MODBNT Rev 8 0 2011 Automation Components Inc MOD9200BNT BACnet Transceiver Installation amp Configuration V Quick Setup Instructions a Configuration of the MOD9200BNT l Connect the Transceiver to the TCP IP network using RJ45 Category 5 Ethernet cable or a crossover cable see Fig 1 page 4 to a noteb
8. mu file will be a copy of the configuration file from the last Transceiver administered P 300f37 Automation Components Inc MODBNTRev8 0 2011 Automation Components Inc MOD9200BNT BACnet Transceiver Installation amp Configuration IV Data Acquisition a BACnet Standard BACnet refers to the open communications protocol ANSI ASHRAE STD 135 created by the American Society of Heating Refrigerating and Air Conditioning Engineers ASHRAE and adopted shortly after its creation as a standard by the American National Standards Institute ANSI The BACnet standard defines a protocol for transmitting messages between various devices in a Building Automation or Control System The standard also specifies the networks over which these messages are exchanged o BACnet Ethernet amp BACnet IP Utilizing standard LAN technology o BACnet MSTP Master Slave Token Passing relies on the EIA 485 serial communication signaling standard o BACnet PTP point to point For temporary connections between devices b MOD9200BNT BACnet Transceiver Parameters P 31 of 37 The MOD9200BNT Transceiver BACnet MSTP device communicating at 76800BPS It receives data from up to fifty 50 wireless sensors and updates its data registers on a real time basis BACnet Object Types Supported AI Analog Input Objects AIO1 to AI200 BV Binary Value Objects BVO1 to BV100 AV Analog Value Objects AVO1 to AV100 The Pr
9. this License Agreement at any time by destroying or returning to ACI all copies of the Product and Documentation in your possession or under your control ACI may terminate this License Agreement for any reason including but not limited to if ACI finds that you have violated any of the terms of this License Agreement Upon notification of termination you agree to destroy or return to ACI all copies of the Product and Documentation and to certify in writing that all known copies including backup copies have been destroyed All provisions relating to confidentiality proprietary rights and non disclosure shall survive the termination of this Product License Agreement Additionally it is understood that termination of this Agreement will not effect a refund of any license fees paid or owed to ACI 10 General This License Agreement shall be construed interpreted and governed by the laws of the State of Wisconsin without regard to conflicts of law provisions thereof The exclusive forum for any disputes arising out of or relating to this License Agreement shall be an appropriate federal or state court sitting in the State of Wisconsin USA This License Agreement shall constitute the entire Agreement between the parties hereto Any waiver or modification of this License Agreement shall only be effective if it is in writing and signed by both parties hereto If any part of this License Agreement is found invalid or unenforceable by a court of competent juris
10. 9200BNT BACnet Transceiver Installation amp Configuration the remote unit executed the command issued by the MOD9200 It will send a feedback status of the analog output value to the MOD9200 The AI101 through AI200 Objects are the alarm registers for all the input and output data points AI01 100 BV01 50 and AV01 50 Each point utilizes 6 binary bits of information representing the alarm conditions of the Input Registers AI Object Digital Output Coil Register BV Object and Analog Output Holding Register AV Object AV Object AI Object Bit 5 amp 6 Bit 1 amp 2 000000 LH BV Object Bit 3 amp 4 The Present Value of each register displays a decimal value representing the alarm status of all 3 point types Each point type returns an individual alarm value in decimal format All 3 point types decimal values are added together to represent the status of the 3 alarm status The decimal values of different point types are The Input Register AI Object alarms 0 Normal 1 Low Battery Alarm Bit I set a 2 Lost Communication Alarm Bit 2 set The Digital Output Coil Registers BV Object alarm 0 Normal Si Lost Communication Alarm Bit 4 set The Analog Output Holding Registers AV Object alarm 0 Normal a 32 Lost Communication Alarm Bit 6 set Alarm Status Examples Example 1 AI108 returns a value of 33 representing AI08 Low Battery Alarm BV08
11. GG I Automation Components Inc T nainaarine 032427 Sansop ag User s Manual MOD9I200BNT BACnet Transceiver Configuration Software Manual Revision 8 0 Trs Prorammer 6 0 Automation Components Inc MOD9200BNT BACnet Transceiver Installation amp Configuration License Agreement for Automation Components Inc Software IMPORTANT READ THESE TERMS CAREFULLY BEFORE INSTALLING THIS SOFTWARE THESE TERMS AND CONDITIONS ESTABLISH A CONTRACT BETWEEN YOU INDIVIDUALLY IF YOU ARE AGREEING TO IT IN YOUR OWN CAPACITY OR IF YOU ARE AUTHORIZED TO AGREE ON BEHALF OF YOUR COMPANY OR ANOTHER ORGANIZATION BETWEEN THE ENTITIY FOR WHOSE BENEFIT YOU ACT YOU AND ACI BY OPENING THE SEALED CD ROM PACKAGE IN THIS MANUAL YOU ACKNOWLEDGE THAT YOU HAVE READ THIS LICENSE AGREEMENT THAT YOU UNDERSTAND IT AND THAT YOU AGREE TO BE BOUND BY ITS TERMS IF YOU DO NOT AGREE TO THE TERMS AND CONDITIONS OF THIS LICENSE AGREEMENT OR IF YOU DO NOT UNDERSTAND THEM PROMPTLY RETURN THE UNOPENED PACKAGE AND ALL ACCOMPANYING ITEMS TO ACI FOR A FULL REFUND 1 Grant of License for Registered Users ACI grants you a non exclusive non transferable license to use the software program with which this license is distributed the Product including any documenta tion files accompanying the Product Documentation on any single computer You may use the Product on a second computer so long as only one 1 is used at a time 2 Backup Copy You may make one back
12. ME for the data point by typing the name in the cell Enter the name in the cell by using the mouse to click on the next column Note DO NOT use commas or semicolons in the Point Name Automation Components Inc MODBNT Rev 8 0 2011 P 14 of 37 Automation Components Inc MOD9200BNT BACnet Transceiver Installation amp Configuration Editor CURRENTLY EDITING INF File Settings Points Row RegisterEntry Register Bank REG ADDRESS GROUP NAME POINT NAME TRANSMITTER ID Eth Floor Conf Arn l Assign a sensor transmitter to the data register by clicking in the TRANSMITTER ID cell to open a drop down menu Use the scroll bar to scroll to the correct address or automatically scroll to the address by typing the hexadecimal address in the cell To select the address click on the appropriate ID in the drop down menu Each Trs Systems transmitter is factory configured with a unique ID refer to the sensor product data sheet for the location of the transmitter ID or Conf Am Assign the appropriate sensor transmission channel to the data register by clicking in the cell to open a drop down menu Click on the appropriate transmission channel 01 to 04 to select I NAME TRANSMITTER ID TRANS CHAN TRANS TIMEOUT Automation Components Inc MODBNT Rev 8 0 2011 Automation Components Inc MOD9200BNT BACnet Transceiver Installation amp Configuration The active transmission channels are factory configured as f
13. building is as follows E Editor _config ini Settings Points Row RegisterEntry Register Bank REG FUNCTION ANALOG_INPUTS ANALOG_INPUTS ANALOG INPUTS ANALOG INPUTS ANALOG INPUTS ANALOG INPUTS REG ADDRESS GROUP NAME D First Floor 1 First Floor 2 First Floor 3 Warehouse 4 Warehouse 5 Warehouse TRANSMITTER ID POINT NAME YP Office VP Office general Office North West East TRANS CHAN DATA FORMAT 1 THERM 20k 2 HUMIDITY 1 THERM 20k 1 THERM 20k 1 THERM 20k 1 THERM 20k The columns may be resized by placing the cursor over one side of the column When the cursor changes to two arrows hold down the left mouse button and drag the side of the column to resize it f Digital Output Coil Register Configuration P 16 of 37 Select the Digital Output Coil Register table by clicking the RegisterBank tab Input Registers Digital Output Coil Registers Analog Output Holding Registers Automation Components Inc SMITTER ID MODBNT Rev 8 0 2011 P 17 of 37 Automation Components Inc MOD9200BNT BACnet Transceiver Installation amp Configuration First we will assign the REG ADDRESS by clicking in the cell Before entering register addresses ensure the RegisterEntry AutoSet is turned off as shown REG ADDRESS GROU Turn AutoSet ON TRANSMITTER ID TRANS CHAN Turn AutoSet OFF Enter the Register address in the REG ADDRESS window The valid range
14. diction the remainder of this License Agreement shall be interpreted so as to reasonably effect the intention of the parties Po Automation Components Inc MODBNT Rev 8 0 2011 Automation Components Inc MOD9200BNT BACnet Transceiver Installation amp Configuration Table of Contents I Introduction EEE 5 a ACI MOD9200 Transceiver System rrrrrrrnnnnnnnrnrrnnnvrnnnnnnnnnrnrnnvrnnnnnnnnrrnnnnvrnnnnn 5 Il BACnet Transceiver Installation amp Network Setup 6 A Transceiver Installation uno rqvrvvqeequasdnssmemarisgsmimnaaeiknidtaes 6 b Network Setup for Transceiver Configuration rrrrrrrrnnrrrnnnnnnnrrrrnnnrrnnnnnnnnnr 7 c Setting A ere e EE tte otout es 7 d Manually Resetting The Factory Default IP Address cc ceeeeeees 9 HI Configuration Software re 10 a Configuration Software Description rrrrrrrrnnnnnnrnrrrnnrrrnnnnnnnnrrrrnnrrnnnnnnnnnnnnnnn 10 b System ICCC Ree 10 c Configuration Software Installation rrrornnrrrrrrrnnrrnnnnnnnnrrrrnrrrnnnnnnnnnrrnnnvrnnnnn 10 d Creating A MOD9200 Configuration File 0000000no000oooonnnnnnossssseeeeesssssssee 11 e Input Register Configuration rrrnnnnnnrrrorrrnrrnnnnvvnrvrrrrnnnnnnnnnnnenensrrssrnrnnnnnnnne 12 f Digital Output Coil Register Configuration rrrornnrrrrrrrnnrrrnnnnnnrrrrrrnnvrnnnnn 16 g Analog Output Holding Register Conftoeuraton 19 h Setting the Mesh Network ID for the repeater router devices
15. drop down menu Si Editor C WE File Settings Points Row RegisterEntry Register Bank REG ADDRESS GROUP HAME POINT MAME TRANSMITTER ID TRANS CHAN SE k U Office West Sunshade Automation Components Inc MODBNT Rev 8 0 2011 Automation Components Inc MOD9200BNT BACnet Transceiver Installation amp Configuration Assign the appropriate digital or relay output TRANS CHAN to the data register by clicking m the cell to open a drop down menu Click on the appropriate transmission channel 01 to 04 to select NAME TRANSMITTER ID TRANS CHAN TRANS TIMEDUT I The active transmission channels or output number are factory set as follows Device Dat Amalog and relay 2 output module to relay 4 output 1 to 4 analog output module h Setting the Mesh Network ID for the repeater router devices Unit Identifier FOINT NAME TRANSMITTER ID TRANS CHAN Sunshade 38E v Serial Transport TCP IP Transport Network ID The mesh network ID of the MOD9200 Gateway can be set to specific network from 1 to 64 The MOD9200 functions as a network coordinator Any repeater router that has the same network ID will be able to communicate and channel sensor information to the MOD9200 P 21 of 37 Automation Components Inc MODBNT Rev 8 0 2011 Automation Components Inc MOD9200BNT BACnet Transceiver Installation amp Configuration i Miscellaneous Menu The transmitter timeout interval
16. e REG ADDRESS window The valid range is 0 to 49 File Settings Points Row RegisterEntry Register Bank SEES GROUP NAME POINT NAME TRANSMITTER ID TRANS CHAN Automation Components Inc MODBNT Rev 8 0 2011 P 20 of 37 Automation Components Inc MOD9200BNT BACnet Transceiver Installation amp Configuration Again use the mouse to move to the next column Enter a GROUP NAME if desired for the data set by typing the group name in the cell Enter the name in the cell by using the mouse to click on the next column Note DO NOT use commas or semicolons in the Group Name Editor File Settings Points Row RegisterEntry Register Bank REG ADDRESS GROUP NAME POINT NAME TRANSMITTER ID TRANS CHAN 0 Office West Enter a POINT NAME if desired for the data point by typing the name in the cell Enter the name in the cell by using the mouse to click on the next column Note DO NOT use commas or semicolons in the Point Name File Settings Points Row RegisterEntry Register Bank REG ADDRESS GROUP NAME POINT NAME TRANSMITTER ID TRANS CHAN D Office West SunShadel Assign a sensor transmitter to the data register by clicking in the TRANSMITTER ID cell to open a drop down menu This is the device ID of the remote output devices RD2432 Use the scroll bar to scroll to the correct address or automatically scroll to the address by typing the hexadecimal address in the cell To select the address click on the appropriate ID in the
17. e data type The MOD9200 Transceiver can have up to 100 addresses 0 to 99 data registers configured to be either Analog or Discrete 50 digital outputs and 50 analog outputs b System Requirements PC Notebook or desktop with Windows 98 XP Vista or Windows 7 Ethernet connection 10 MB of hard drive memory available c Configuration Software Installation Extract or unzip the ACI Programmer zip file and click start the setup exe program to install the program Follow the on screen instructions to complete the installation P 10 of 37 Automation Components Inc MODBNT Rev 8 0 2011 Automation Components Inc MOD9200BNT BACnet Transceiver Installation amp Configuration d Creating A MOD9200 Configuration File To create a new MOD9200 configuration file open the ACI Programmer by clicking on Start gt Programs gt Trs Programmer 6 XX guration Io Eile Settings Points Row RegisterEntry Register Bank To open a new configuration table Click on File gt New Gateway File A blank configuration table will open File Settings Points Row RegisterEntry Register Bank 4 REG FUNCTION REG ADDRESS GROUP NAME POINT NAME TRANSMITTER ID TRANS CHAN DATA FORMAT The default startup is the Input Register configuration table and System Setup page By clicking the RegisterBank tab you can go to the Digital Output Coil register configuration table or Analog Output Holding Register configuration table P llof37
18. en the count reaches 1 677 721 5 24 bits the count value rolls over to 0 and begins again The Present Value of BV01 through BV50 objects will correspond to the MOD9200 Digital Output Coil Register 0 through 49 For BVXX XX Trs MOD9200 Register Num 1 The BVO1 to BV50 Objects are used for command remote wireless digital outputs relays module 1 e ED2402D amp the SD2432D devices Values to be entered or sent is 1 on and O off The BV51 through BV100 Objects will be automatically assigned by the MOD9200BNT These 50 registers objects will display the status of the relays commanded via the previous BV1 thru BV50 objects After the remote unit executed the command issued by the MOD9200 It will send a feedback status of the relays to the MOD9200 The Present Value of AVOI through AV50 objects will correspond to the MOD9200 Analog Output Holding Register 0 through 49 For AVXX XX Trs MOD9200 Register Num 1 The AVO1 to AV50 Objects are used to command remote wireless analog outputs 0 10VDC or 0 SVDC module such as the SD2432D devices Value to be entered or sent is from 1 0 to 100 0 representing the percentage of full output range The AV51 through AV100 Objects will be automatically assigned by the MOD9200BNT These 50 registers objects will display the status of the analog output commanded via the previous AV1 thru AV50 objects After Automation Components Inc MODBNT Rev 8 0 2011 Automation Components Inc MOD
19. enu REG ADDRESS GROUP NAME POINT NAME TRANSMITTER ID TRANS CHAN 0 Garage Exhaust Fan 3456 Assign the appropriate digital or relay output TRANS CHAN to the data register by clicking in the cell to open a drop down menu Click on the appropriate transmission channel 01 to 04 to select File Settings Points Row RegisterEntry Register Bank REG ADDRESS GROUP NAME POINT NAME TRANSMITTER ID TRANS CHAN 0 Garage Exhaust Fan 3456 i 2 3 4 Automation Components Inc MODBNT Rev 8 0 2011 Automation Components Inc MOD9200BNT BACnet Transceiver Installation amp Configuration The active transmission channels or output number are factory set as follows RD2402 l to 2 Gr relay 1 NA Wireless Relay and relay 2 output module RD2432 I to 4 for relay 1 I to 4 for analog Wireless digital amp to relay 4 output 1 to 4 analog output module g Analog Output Holding Register Configuration P 19 of 37 Select the Analog Output Holding Register table by clicking the RegisterBank tab File Settings Points Row RegisterEntry Register Bank REG ADDRESS GROUP NAME Input Registers 0 Garage Digital Output Coil Registers Analog Output Holding Registers First we will assign the REG ADDRESS by clicking in the cell Before entering register addresses ensure the RegisterEntry AutoSet is turned off as shown Turn AutoSet ON Turn AutoSet OFF Enter the Register address in th
20. er and move the jumper from Norm to Init Turn on power and the Transceiver can be communicated with using the Factory Default IP Address 192 168 0 1 Subnet Mask 255 255 255 0 The Config File is no longer active while the jumper is in the Init position A new Config File can be downloaded to the Transceiver if desired To reactivate the Config File turn off the power to the Transceiver and move the jumper back to Norm Turn the power back on and the Config File will become active The Transceiver will have the IP Address that was set in the Config File w F w 7 w P 9 of 37 Automation Components Inc MODBNT Rev 8 0 2011 Automation Components Inc MOD9200BNT BACnet Transceiver Installation amp Configuration HI Configuration Software a Configuration Software Description The data registers of the Transceiver need to be configured prior to use The configuration program Trs Programmer exe can be downloaded from our website www workaci com The download instructions are included in the shipping document of the MOD9200 Transceiver The software will be used to configure the 3 different type of data registers as follows Assign the Input Register function Analog or Discrete Assign wireless Digital Output Coil Register function Assign wireless Analog Output Holding Register function Assign the register address Assign the Wireless Sensor ID and transmission channel Assign th
21. esent Value of AIO1 through AI100 will correspond to the MOD9200 data register 0 through 99 For AIXX XX Trs MOD9200 Register Num 1 All wireless sensor information analog and discrete input will be displayed as numeric values All digital status alarms will be received and stored by MOD9200 as I or 0 1 input contact closed amp 0 input contact open The Digital Capture Time can be set to hold momentary contact closures long enough to be picked up by the system Automation Components Inc MODBNT Rev 8 0 2011 P 32 of 37 Automation Components Inc MOD9200BNT BACnet Transceiver Installation amp Configuration The Digital Capture Time can be set up to 240 minutes 4 hours in applications where an extended period of time is needed such as unoccupied period by pass For data types DATA FORMAT as described previously THERM 20k RTD 1k RTD 1k Ext and HUMIDITY the analog data will be received and stored as real values with one decimal position 1 e 82 5 F For the data type DATA FORMAT as described previously ANALOG the data will be displayed in counts 0 to 409 5 In applications where WT2630Bs are used The setpoint adjustment is represented as analog value from 0 to 409 5 Heat position to Cool position on the setpoint adjustment scale For the data type DATA FORMAT as described previously TOTALIZER the data is displayed in counts 24 bits with a value of 0 1 representing one count Wh
22. he devices should be daisy chained or straight line connected by connecting all the A wires to the A terminals and the B wires to the B terminals Do not use spur lines or a star configuration P 60f37 Automation Components Inc MODPNT Rev 8 0 2011 Automation Components Inc MOD9200BNT BACnet Transceiver Installation amp Configuration RS485 Terminating Resistor If the MOD9200 is at the end of a RS485 loop a terminating resistor should be installed to match the electrical impedance characteristic of the twisted pair loop and prevent signal echoes from corrupting the data b Network Setup for Transceiver Configuration A network connection using a RJ45 Crossover cable is required during the initial setup of the Transceiver for transporting the Transceiver Configuration File via FTP Connect the MOD9200 Transceiver J2 to a 10 100Base T Ethernet network or use a crossover cable to connect directly to the PC Apply 24 VAC 60 Hz power to the MOD9200 Transceiver c Setting A New IP Address P 7 of 37 The MOD9200 is shipped from the factory with an IP address of 192 168 0 1 and a subnet mask of 255 255 255 0 Note To initially connect to the Transceiver the networked PC must have a static IP address in the form of 192 168 0 X where X is gt 2 with a subnet mask of 255 255 255 0 The IP Address can be changed by changing the IP Address in the Transceiver Config File Open either an exi
23. is 0 to 49 faa aves are ees Tee REGADDRESS ADDRESS GROUP NAME POINT MAME TRANSMITTER ID TRANS CHAN Again use the mouse to move to the next column Enter a GROUP NAME if desired for the data set by typing the group name in the cell Enter the name in the cell by using the mouse to click on the next column Note DO NOT use commas or semicolons in the Group Name File Settings Points Row RegisterEntry Register Bank EE eem REG ADDRESS GROUP NAME POINT NAME TRANSMITTER ID TRANS CHAN 0 Garage Automation Components Inc MODBNT Rev 8 0 2011 P 18 of 37 Automation Components Inc MOD9200BNT BACnet Transceiver Installation amp Configuration Enter a POINT NAME if desired for the data point by typing the name in the cell Enter the name in the cell by using the mouse to click on the next column Note DO NOT use commas or semicolons in the Point Name Settings Points Row RegisterEntry Register Bank REG ADDRESS GROUP NAME POINT NAME TRANSMITTER ID TRANS CHAN 0 Garage Exhaust Far Assign a sensor transmitter to the data register by clicking in the TRANSMITTER ID cell to open a drop down menu This is the device ID of the remote output devices RD2402 amp RD2432 Use the scroll bar to scroll to the correct address or automatically scroll to the address by typing the hexadecimal address in the cell To select the address click on the appropriate ID in the drop down m
24. ission distance 1f needed MSTP RS485 network connection MOD9200 Configuration Software Wireless Wall Temp amp Humidity a Sensor Wireless Remote Digital Analog f 4 FF BACnet MSTP Wireless Digital Wireless Immersion amp fk T t ST e Relay Outputs Input Modules amp Energy Totalizer Remote Sensors vs MOD9200BNT Wireless Outside Air Ze Bacneta Transceivers KI Temperature amp i Wireless Digital Humidity Repeater Increases amp Analog Outputs Transmission Distance if needed Sub System Overview P 50f37 Automation Components Inc MODBNT Rev 8 0 2011 Automation Components Inc MOD9200BNT BACnet Transceiver Installation amp Configuration II BACnet Transceiver Installation amp Network Setup a Transceiver Installation Choose a location close to the computer network hub or RS485 loop Mount the Transceiver on the wall using four 8 screws 24 VAC Input 500 mA nominal Connect 24VAC 60 Hz no secondary ground to the input terminals using 20 AWG wire as shown in the product data sheet TCP IP Connection J2 Connection J1 Default IP SREL ee Jumper T Bed HI LO Bias Not Available TERM Resistor NA 24 VAC ie Input erminalS Figure 1 MSTP RS485 Use 20 gauge shielded twisted pair wire to connect the Transceiver Terminals A amp B to the network See Figure 1 Multiple RS485 Devices If more than one RS485 device is used t
25. it Identifier E GROUPF NAME POINT NAME TRANSMITTER ID Vd Serial Transport TCP IP Transport Network ID Miscellaneous Click on the drop down menu arrow and select the Transceiver Unit Default ID of 1 from the drop down menu and click OK REG ADDRESS GROUP NAME POINT NAME 5 0 Bth Floor Conf Am 5 1 Bth Floor Conf Am B 5 2 Bth Floor Cont Am 5 Sen op a Ok Cancel CO J OH OT Fe GO I kg Click on Menu Comm gt Serial Transport to activate the Serial Comm Port dialog box POINT NAME d Serial Transport TCP IP Transport Network ID Miscellaneous Automation Components Inc MODBNT Rev 8 0 2011 Automation Components Inc MOD9200BNT BACnet Transceiver Installation amp Configuration Use the Serial Comm Port configuration dialog box to select the appropriate internal communication parameters Connect Speed Connect Preferences and Transport Mode for the Transceiver BR Serial Comm Port Properties Maximum Speed 38400 Modbus Transport e ATU Connection Preferences Data Bits E Parity NONE Stop Bits l1 C ASCII The MOD9200BNT requires internal communication parameters to be set as follows Maximum Speed 38400 BPS This communication speed is set for internal use by the MOD9200BNT Transceiver and it will not change the external BACnet MSTP communication speed
26. mitation of Liability IN NO EVENT WILL ACI BE LIABLE TO YOU OR ANY THIRD PARTY FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES INCLUDING WITHOUT LIMITATION INDIRECT SPECIAL PUNITIVE OR EXEMPLARY DAMAGES FOR LOSS OF BUSINESS LOSS OF PROFITS BUSINESS INTERRUPTION OR LOSS OF BUSINESS INFORMATION ARISING OUT OF THE USE OF OR INABILITY TO USE THE PROGRAM OR FOR ANY CLAIM BY ANY OTHER PARTY EVEN IF ACI HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES ACI S AGGREGATE LIABILITY WITH RESPECT TO ITS OBLIGATIONS UNDER THIS AGREEMENT OR OTHERWISE WITH RESPECT TO THE PRODUCT AND DOCUMENTATION OR OTHERWISE SHALL NOT EXCEED THE AMOUNT OF THE LICENSE FEE PAID BY YOU FORTHE PRODUCT AND DOCUMENTATION BECAUSE SOME STATES COUNTRIES DO NOT ALLOW THE EXCLUSION OR LIMITATION OF LIABILITY FOR CONSEQUENTIAL OR INCIDENTAL DAMAGES THE ABOVE LIMITATION MAY NOT APPLY TO YOU 8 Export Restrictions THIS LICENSE AGREEMENT IS EXPRESSLY MADE SUBJECT TO ANY LAWS REGULATIONS ORDERS OR OTHER RESTRICTIONS ON THE EXPORT FROM THE UNITED STATES OF AMERICA OF THE PRODUCT OR INFORMATION ABOUT SUCH PRODUCT WHICH MAY BE IMPOSED FROM TIME TO TIME BY THE GOVERNMENT OF THE UNITED STATES OF AMERICA YOU SHALL NOT EXPORT THE PRODUCT DOCUMENTATION OR INFORMATION ABOUT THE PRODUCT AND DOCUMENTATION WITHOUT CONSENT OF ACI AND COMPLIANCE WITH SUCH LAWS REGULATIONS ORDERS OR OTHER RESTRICTIONS 9 Termination This License Agreement is effective until it is terminated You may terminate
27. nk if the REG FUNCTION is Digital Discrete Not used for MOD9200LON First we will assign the REG FUNCTION by clicking in the REG FUNCTION cell to open a drop down menu Select the appropriate function File Settings Points Row RegisterEntry Register Bank REG FUNCTION REG ADDRESS GROUP NAME ANALOG_INPUTS m DISCRETE_INPUTS HOLDING_REGS 6 SENSOR CNTRL 7 SENSOR CNTRL 7 POINT NAME TRANSMITTER ID TRANS CHAN DATA FORMAT Automation Components Inc MODBNT Rev 8 0 2011 P 13 of 37 Automation Components Inc MOD9200BNT BACnet Transceiver Installation amp Configuration Use the mouse to move to the next column to assign the REG ADDRESS by clicking in the cell Before entering register addresses ensure the RegisterEntry AutoSet is turned off as shown File Settings Points Row RegisterEntry REG FUNCTION REG Turn AutoSet ON ES POINT NAME TRANSMITTER ID TRANS CHAN DATA FORMAT ANALOG_INPUTS Turn AutoSet OFF loor Conf Am v Enter the Register address in the REG ADDRESS window and press down arrow to enter Again use the mouse to move to the next column Enter a GROUP NAME for the data set by typing the group name in the cell Enter the name in the cell by using the mouse to click on the next column Note DO NOT use commas or semicolons in the Group Name i Editor Se File Settings Points REG FUNCTION REG ADDRESS GROUP NAME POINT NAME ANALOG INPUTS 0 5th Floor Enter a POINT NA
28. ny network or between any devices although you may use the Product to make such transmissions of other materials You may access the Product from only one computer at a time 6 Limited Warranty ACI WARRANTS THAT THE PRODUCT WILL OPERATE SUBSTANTIALLY IN ACCORDANCE WITH THE THEN CURRENT DOCUMENTATION SHOULD THE PRODUCT NOT SO OPERATE YOUR EXCLUSIVE REMEDY AND ACI S SOLE OBLIGATION UNDER THIS WARRANTY SHALL BE AT ACI S SOLE DISCRETION CORRECTION OF THE DEFECT OR REFUND OF LICENSE FEES PAID BY YOU FOR THE PERIOD DURING WHICH THE DEFECT WAS NOT CORRECTED AND MATERIALLY AFFECTED THE OPERATION OF THE PRODUCT ANY USE BY YOU OF THE PRODUCT IS AT YOUR OWN RISK THIS LIMITED WARRANTY IS THE ONLY WARRANTY PROVIDED BY ACI REGARDING THE PRODUCT EXCEPT FOR THE LIMITED WARRANTY ABOVE THE PRODUCT IS PROVIDED AS IS TO THE MAXIMUM EXTENT PERMITTED BY LAW ACI DISCLAIMS ALL OTHER WARRANTIES OF ANY KIND EITHER EXPRESSED OR IMPLIED INCLUDING WITHOUT LIMITATION IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ACI DOES NOT WARRANT THAT THE FUNCTIONS CONTAINED IN THE PRODUCT WILL MEET ANY REQUIREMENTS OR NEEDS YOU MAY HAVE OR THAT THE PRODUCT WILL OPERATE ERROR FREE OR IN AN UNINTER RUPTED FASHION OR THAT ANY DEFECTS OR ERRORS IN THE PRODUCT WILL BE CORRECTED OR THAT THE PRODUCT IS COMPATIBLE WITH ANY PARTICULAR PLATFORM SOME JURISDICTIONS DO NOT ALLOW THE WAIVER OR EXCLUSION OF IMPLIED WARRANTIES SO THEY MAY NOT APPLY TO YOU 7 Li
29. of 76800BPS Data Bits 8 Parity none Stop Bit I Modbus Transport RTU The MOD9200BNT Transceiver transmission mode and serial port parameters need to be exactly the same as shown above P29 0 37 Automation Components Inc MODBNT Rev 8 0 2011 Automation Components Inc MOD9200BNT BACnet Transceiver Installation amp Configuration To Save the configuration file click on File gt Save It 1s recommended that the cfg file be saved in the Trs folder already setup Le C trs config ea B D Computer gt Local Disk C gt trs config e gt Search config NJ NIE Organize v New folder A VX Favorites d ame E Desktop o LON B3 ini 5 11 2010 2 04PM Configuration sett 8 Downloads amp LON F config ini 4 16 20101 16 PM Configuration sett Z Recent Places z o LON F test Lini 4 2 201012 13 PM Configuration sett amp LON F test 2 ini 4 13 2010 2 42PM Configuration sett Libraries o LON F test 3 ini 5 11 2010 3 45PM Configuration sett 2 Documents amp LON F test new prog Lini 4 16 2010 5 59 PM Configuration sett adi Music Patterson Data input ini 8 13 2009 10 30 AM Configuration sett t Pictures o square_d_rtu ini 6 2 2008 9 56 AM Configuration sett E Videos 5 square_d_tcip ini 6 2 2008 9 55 AM Configuration sett 5 template ini 4 5 2010 8 00 PM Configuration sett amp Homegroup amp trickydicky ini 9 3 2008 2 06 PM Configuration sett File name Save a
30. ollows Analog CH 01 Analog CH 02 Digital CH 01 hj Le Therm 20K WT2630B Space Temp SetPoint Override Discrete Therm 20K Analog See page 15 to set the Digital Capture Time WT2630C Space Temp Override Discrete Digital Capture Time WH2630AC Humidity LI o MD LE mom ee fe Therm 20K Humidity OT2630A Outdoor Temp TT eaten OH2630A Outdoor Humidity J y TTT enn 206 DH2630A D Duo Humidity 1 gt dl id Therm 20K mo e Therm 20K Totalizer 01 Count CH 03 Totalizer 02 Count CH 04 See Device Label for Analog 4 and Digital 4 Configuration 1K Note For RT2630B 0 10V 0 5V amp 4 Dig Inputs The Data Format shall be ANALOG for the analog inputs The values will be displayed as 0 to 409 5 with the transmitter input from 0 to 10VDC or 0 to 5VDC Select the appropriate DATA FORMAT value by clicking in the cell to open a drop down menu B Editor File Settings Points Row RegisterEntry REG FUNCTION REG ADDRESS GROUP NAME POINT NAME TRANSMITTER ID TRANS CHAN DATA FORMAT LOG ANALOG_INPUTS D first floor room A P 150f37 Automation Components Inc MODBNTRev8 0 2011 Automation Components Inc MOD9200BNT BACnet Transceiver Installation amp Configuration To create a new data register row click on Row gt Append Continue to do this for each row data register that needs to be configured The completed configuration example for an office
31. ook or a desktop PC Apply 24 VAC 60 Hz power to the input terminals of the Transceiver The Transceiver current draw is less than 0 5 Amp The Transceiver is shipped with an IP address of 192 168 0 1 and a subnet mask of 255 255 255 0 see page 8 for instructions on changing the IP address To initially connect to the Transceiver the networked PC must have a static IP address of 192 168 0 X X can be any number except 1 or 2 with a subnet mask of 255 255 255 0 Installing The MOD9200 Configuration Software Configure the MOD9200BNT Transceiver b Installing the MSTP RS485 Network l 2 4 P 35 of 37 Choose a location close to the computer or RS485 loop Mount the Transceiver on the wall using four 8 screws MSTP RS485 Use 20 gauge shielded twisted pair wire to connect the Transceiver Terminals A amp B to the network See Figure 1 Multiple RS485 Devices If more than one RS485 device is used the devices should be daisy chained or straight line connected by connecting all the A wires to the A terminals and the B wires to the B terminals Do not use spur lines or a star configuration RS485 Terminating Resistor If the MOD9200 is at the end of a RS485 loop a terminating resistor should be installed to match the electrical impedance characteristic of the twisted pair loop and prevent signal echoes from corrupting the data Automation Components Inc MODBNT Rev 8 0 2011
32. s type c trs config ini D S Hide Folder Name Date modified Type k Sending The Configuration File To The MOD9200 Before sending the file to the MOD9200 it is important to ensure that the Serial Transport setting is checked as shown Unit Identifier DE GROUP NAME POINT NAME TRANSMITTER ID TRANS CHAN DATA FORMAT 1 THERM 20k 2 HUMIDITY 1 THERM 20k Network ID 1 THERM 20k 1 THERM 20k 1 THERM 20k EI Serial Transport ch TCP IP Transport Miscellaneous Always save the configuration file to the folder trs before sending it to the MOD9200 Transceiver P 260f37 Automation Components Inc MODPNT Rev 8 0 2011 P 27 of 37 Automation Components Inc MOD9200BNT BACnet Transceiver Installation amp Configuration To send the new configuration file to the MOD9200 Transceiver click on File gt File Transfer and a dialog box will appear File Settings Points Row RegisterEntry Register Bank New Gateway File PRESS GROUP NAME POINT NAME TRANSMITTER ID TRANS CHAN DATA FORMAT Open Gateway File 1 THERM 20k 2 HUMIDITY 1 THERM 20k 1 THERM 20k File Transfer 1 THERM 20k 1 THERM 20k Save Save As Exit Select File to Send C trs config LON B3 ini File Name TCP IP 192 168 0 1 IP Address TCPAP G Disconnected Comm Status Connect Disconnect Debesbbe set ie state Get File returned as Cend File Cancel c tes config _config ini
33. sting config file or a new config file using the Trs Programmer Software Click on Settings gt TCP IP Transport Bros File Settings Points Row RegisterEntry RE Unit Identifier GROUP NAME POINT NAME TRANSMITTER ID TRANS CHAN DATA FORMAT LOG Paro x Serial Transport V TCPAP Transport N Miscellaneous Automation Components Inc MODBNT Rev 8 0 2011 P 8 of 37 Automation Components Inc MOD9200BNT BACnet Transceiver Installation amp Configuration Enter the new IP Address and Subnet Mask and click OK The new IP Address will take affect when the Config File is downloaded to the Transceiver 1 92 168 0 1 IP Address 255 255 255 0 Subnet Router Setup Webserver Only f 92 168 0 254 Router IP Address Forwarded Port OK Cancel Our recommendation is not to change the default factory IP address of the transceiver since the Ethernet connection is used to configure the transceiver only and will not be required when the MSTP network is up and running Router Setup Webserver Only NOT USE Applicable for RM9500 WebLogger Setup ONLY Automation Components Inc MODBNT Rev 8 0 2011 Automation Components Inc MOD9200BNT BACnet Transceiver Installation amp Configuration d Manually Resetting The Factory Default IP Address The Transceiver can manually be reset to the default IP Address by moving the jumper J6 from Norm to Init Turn off the power to the Transceiv
34. to recognize the contact closure The Digital Capture Time can be set up to 240 minutes 4 hours in applications where an extended period of time is needed such as unoccupied period by pass Set the Digital Capture Time interval seconds or minutes by clicking on Seconds or Minutes Click in the Digital Capture Time cell to open a drop down menu Use the scroll bar to scroll down to the appropriate value 0 to 240 or type the value in the cell to automatically scroll to the appropriate value To select the timeout interval click on the appropriate value in the drop down menu Digital Scaling On check box Should be checked when configuring the MOD9200BNT BACnet transceiver or the MOD9200LON LonWorks Transceiver Units Select the appropriate default temperature scale F C Register Value When Sensor Lost The user has the options to select whether the sensor value should remain unchanged or set to 19999 when the communication link is lost with the sensor after the transmitter timeout period P 23 of 37 Automation Components Inc MODBNT Rev 8 0 2011 Automation Components Inc MOD9200BNT BACnet Transceiver Installation amp Configuration j Configuring The Transceiver For MSTP RS485 Network P 24 of 37 The Transceiver needs to be assigned an Identifier Address for device internal use To enter the Transceiver Unit ID into the Configuration File click on the Menu Comm gt Unit Identifier Un
35. tomation Components Inc MODBNTRev8 0 2011 30 mo no no Iwer apew aq ued sasueud aiojaq umop paJamod aq pjnous yun UOINNE unu eu ZT PON 0 T JPON LO Ul aS SSdJppy gt JUEISU JO PON JJOMIIN s3unas ayey pneg LN90076Q0W a OMAN A Jel a lt pue OI en u a s O A goe PPO IOSIHS sO Lrniivi P hes fey INdO0O0c6ECOW
36. up copy of the Product You may use it only to reinstall the Product 3 Ownership You have no ownership rights in the Product Rather you have a license to use the Product as long as this License Agreement remains in full force and effect Ownership of the Product Documentation and all intellectual property rights therein shall remain at all times with ACI Any use of the Product by any other person business corporation government organization or any other entity is strictly forbidden and is a violation of this License Agreement You may not make more copies of the Product than specified in this agreement or allowed by applicable law despite this limitation publish the Product for others to copy or rent lease or lend the Product 4 Copyright The Product and Documentation contain material that is protected by United States Copyright Law as well as other intellectual property law and international treaty provisions All rights not granted to you herein are expressly reserved by ACI You may not remove any proprietary notice of ACI from any copy of the Product or Documentation 5 Restrictions You may not publish display disclose rent lease modify loan distribute or create derivative works based on the Product or any part thereof You may not reverse engineer decompile translate adapt or disassemble the Product nor shall you attempt to create the source code from the object code for the Product You may not transmit the Product over a