Home

Smart Living User Manual

image

Contents

1. The SmartLiving intrusion control panel offers an array of innovative features In addition to the traditional User menu accessed by means of user code entry The SmartLiving System 9 e e e SMARTLIVING LI UU User s Manual this system provides a series of shortcuts refer to Shortcuts in Appendix associated with keys Fir F2 4 Generally intrusion control panels do not allow access to the system via keypad without code entry However by means of the customized personal shortcuts associated with keys Fi ral it is possible to enable building occupants to access and operate the system without code entry The installer must program the shortcuts to suit user requirements and explain how they are used For example it may be useful to allow all the building occupants to arm the system without code entry as this operation increases the level of system security However operations which lower the level of system security should be reserved for code users only Under normal circumstances Mz oux m ww operations which increase system security can be allowed without valid code entry whereas operations which lower system security Disarm Delete Alarm ze Tamper memory Deactivate Alarm Tamper outputs should be allowed only after LE Li pap o 5 wo f valid code entry ao Each keypad is assigned by the installer to the partitions it controls Gee c Ne ees inm JOY MAX keypads also provide
2. e Weekly the temperature set by the user is valid during the selected hours on specific days of the week e Antifreeze this is a forced operation If the temperature drops below 2 C the output connected to the heating system will activate Via Keypad Method 1 Activate the shortcut assigned to the Thermostat shortcut n 37 E and associated with one of the following keys Firs shown on the display with or without code entry to access the Thermostat section of the User Menu 1 Use the number keys to select the operating mode of the thermostat e Thermostat Off e Manual e Daily e Weekly e Antifreeze The display will show the 1 line operating mode of the thermostat and day of the week 2 line pre set temperature gauge and the Summer Winter operating mode icon 3 line temperature setting and operating hours 4 line temperature reading and the status of the heating system air condition ing system ON OFF 2 Select the operating mode Summer Winter of the thermostat using 6 mro 3 Select the temperature using keys and im Select the operating hours using 9 and 6 Select the day of the week using and O Press to exit and save Method 2 Access the Thermostat section of the User Menu by means of a valid PIN Follow the instructions described in Method 1 34 Method 5 13 Method 2 pop Method 2 v t Using the system
3. This refers to the status of a partition as requested by the user The user can carry out the following operations e Disarm this operation disables the partition completely In this way none of the zones belonging to the partition can generate alarms e Away mode this operation enables the interior and perimeter zones of the partition In this way all of the zones of the partition can generate alarms e Stay mode this operation enables only the perimeter zones of the partition In this way only the perimeter zones of the partition can generate alarms e Instant mode this operation enables the partition perimeter zones only and annuls o In this way violation of the perimeter zones of the partition will generate instant alarms e Hold this operation forces the partition to hold its current status A periodic inspection of the protected premises carried out by authorized security staff A zone that monitors the entrance points of the protected building Perimeter zones are usually direct entrance points such as doors and windows For example the front door of an apartment and windows that allow access from outside Devices connected to the control panel via the I BUS SmartLiving control panels manage the following peripherals e JOY series Keypads Proximity Readers nBy Expansions Flex5 Transceiver Air2 BS100 Sounder Ivy Isolators IB100 GSM dialer Nexus The period expressed in minutes before an aut
4. User s Manual unum SMAR ILIVING Listen in 5 14 This function can be activated over the phone only The listen in function allows you to eavesdrop on the protected premises through the microphones of JOY MAX keypads which have at least one partition in common with the entered PIN Shortcut n 10 must be assigned by your installer to one of the number keys relating to the code that generates this operation Over the phone Type in the PIN of a user code followed by X then press the key from O to 9 which the installer has programmed to activate Listen in shortcut n 10 The control panel will open a listen in channel between the phone and the first JOY MAX keypad configured in the system with at least one partition in common with the entered PIN To open a voice communication channel with another JOY MAX keypad during the listen in phase press the number key which corresponds to the address of the keypad you wish to use Also in this case the selected keypad must have at least one partition in common with the entered code Press to end the listen in phase and step back to the voice announced Shortcut menu Partition status enquiry 5 15 This function can be activated over the phone only The Partition status enquiry function allows you to listen to voice announcements regarding of the armed disarmed status of the partitions during telephone communications with the control panel or by activating the corre
5. The nBy S reader is suitable for indoor or outdoor installation and operates best under the following conditions e Temperature from 25 to 70 C e Maximum humidity 93 without condensation e Protection grade IP 34 e Environmental class IV Products certified and 1 4 conforming to directives When duly programmed the SmartLiving intrusion control panel and the devices described in this manual have been certified by the IMQ Security Systems agency as compliant with CEI 79 2 1998 Ab 2000 CEI EN 50131 3 2009 and CEI EN 50131 6 2008 The Control panel enclosure houses the following certified devices e NIM Electronics switching power supply e Mother board IN082 or IN088 e SmartLogos30M voice board accessory item e FLEX5 U input output expansion board accessory item e AUXREL32 relay board accessory item e SmartLAN SI and SmartLAN G LAN interface boards accessory items e IB100 RU BUS isolator board accessory item e ProbeTH thermal probe kit for battery charge optimization accessory item e TamperNO tamper protection kit accessory item e Backup battery 12 V 17 Ah e Motherboard IN082 and IN088 integrated Type B notification apparatus The control panel compliancy is also guaranteed when connected to the following certified devices e FLEX5 P input output expansion boards e Joy MAX Joy GR Concept G nCode G keypads e nBy S outdoor mount proximity readers e nBy X universal mount proximity readers
6. e IB100 RP BUS isolator e Self powered IB100 A BUS isolator e nCard access control card for proximity readers e nTag access control tag for proximity readers Compliancy is not guaranteed when the control panel is connected to the following uncertified devices e SmartLink GWB GSM interface with 12V 1 2 Ah battery e BUS connected Nexus interface e BUS connectable Ivy B Ivy BF Ivy BM and Ivy BFM self powered sounderflashers for outdoor installation e Wireless devices such as AIR2 AIR2 BS100 transceivers Air2 IR100 PIR detectors Air2 MC100 magnetic contacts Air2 KF100 access control keyfobs e SmartModem100 Teleservice modem ATS2 notification apparatus refer to EN50131 1 2008 02 paragraph 8 6 TYPE B NOTIFICATION Notification Table 10 page 46 Grade 2 and EN50136 characterized by APPARATUS e Transmission time classification D2 60 seconds e Transmission time max values M2 120 seconds e Classification time classification T2 25 hours e SO Substitution security no detection of device substitution e IO Information security no detection of message substitution 6 General information User s Manual unum SMARTLIVING Manuals 1 5 Installation Manual 1 5 1 The installer should read carefully through the Installation Manual and should be familiar with all the components and the operating procedures of the SmartLiving system In order to provide adequate protection the installer must adhere to a
7. After violation of a duly programmed zone which sends a command to the control panel e Via Wireless keyfob by means of keys F1 F4 as described in paragraph 2 6 1 Air2 KF100 Wireless keyfobs e Via Web by means of the integrated web server on the SmartLAN G if installed via any browser refer to paragraph 5 17 2 Access the web server Managing alarms 5 1 This paragraph describes the actions users can take during typical alarm and tamper conditions e Stop alarms deactivates instantly the outputs activated by zone partition alarm and tamper events and system tamper events The system tamper events are ee Open panel ee Dislodged panel ee Peripheral tamper expansion keypad reader ee Peripheral loss expansion keypad reader e Clear call queue clears the outgoing call queue and stops any ongoing calls e DeleteAlarm mem implements a Stop alarms operation and at the same time deletes memory of system and partition alarm and tamper events Via Keypad Method 1 Activate the shortcuts associated with keys Ffm shown on the display with or without code entry Using the system 23 SMARTLIVING User s Manual e The shortcut which is assigned to Alarm menu operations shortcut n 13 ES allows you to view the respective section You can select one of the following options using and activate it by means of the key ee Stop alarms ee Clear call queue ee DeleteAlarm mem e
8. part of the zone section after pressing the NG button if you are using a computer or after pressing Ci if you are using a mobile telephone device Select an output and activate or deactivate it using the buttons shown opposite 30 Method 2 activated Output e deactivate Y Method 2 s Method 2 Method 1 Activate selected output CI Deactivate selected output Using the system User s Manual SMARTLIVING Change date and time This option allows you to set the date and time in accordance with the selected format Via Keypad Method 1 Activate the Set date time shortcut shortcut n 35 E associated with one of the following keys Fi Fa to shown on the display with or without code entry to access the User Menu at the Set date time section 1 Use keys 9 and e to select the programming field hour minutes etc 2 Use keys and to change the value in the selected field 3 Press to save the setting Method 2 Access the Keypad date time section by means of a valid PIN Follow the instructions described in Method 1 Keypad settings This option allows you to program the display and buzzer settings e Brightness the level of brightness of the display backlight and LEDs when you press any key duration 20 seconds e Standby brightness the level of brightness of the display backlight and LEDs during standby status e Contrast allows you to adjust the black wh
9. saa P E CASES ERE TEER ERED HH ROS 5 1 2 Description of the product and various models 5 1 3 Environmental ConditionS ui ai i e RA cs NG AG 6 1 4 Products certified and conforming to directives 6 lab MANA 2 2 ae 4 09 878 e UR SOS ARCA HW DAL ROV ka R 7 1 6 Operator Qualifications x io cede cg ew ER s ede ax sd ec E yx 7 1 7 Access LevelS 4 eene hh ona koh kk ooo don osos 7 1 8 Conventions Glossary x saca x d dod GE OC AA Peo eee CUR E AA 7 Chapter 2 The SmartLiving System asaan ee ee ee ee es 8 dal AMUOCGCUCHON 2 2 255 3 04 iena 8 2 2 The LECHASIOGIES uolo descy aom ae ee 3 m X 4 Pp X dom Y GREK ODEO Rw 3 3X 9 LICHE i ecc AA AA 9 2 4 Reader nBV ca0 3 4a S MAG RR Sa XUNG EG BAKA RA 14 25 TISSPCOUOSA 94 4 PX 3 ad 3 AS 15 2 5 KEYS PA AE 16 2 7 Multi system access 17 2 8 Telephone functionS iii tenne Xue d x dou ae a 18 299 WEB e mail TUMCEONS 4 wew KAG GARA Eee 3e 18 2 10 Arming SCENANOGS iu 3 426556 Eo 8c YR UR OxCR OR ORASOS x6 3 A 3 CUm MEANT dee 18 Chapter 3 SHOMCULS easier 19 3 1 Keypad shortcuts 4a cds 2465464 een 19 3 2 Shortcut with code 4 ee dete acus a 20 3 3 Key and Reader shortcuts naasa a a ee a nns 20 3 4 SHOFCCUL TSE gaeta ORAS A RA 21 Chapter 4 Voice TUNCHONS uc uxor aae cac dee aD HE Edo ee Rae 22 Chapter 5 Using the system 23 5 1 Mabagino alafitis sug gina nia a i e Oe ia os 23 5 2 Arming and disarming partitions u ee a 24 5 3 Voic
10. the functions relating to the icons Note associated with the keys will not be activated Visual signals on the keypad LEDs 2 3 5 The following table describes the visual signals on the keypad LEDs Table 5 ru LEDs Be y All the a sa x are Open zones on the dcm Primary BEE Z 230V All the zones on the keypad At least one of the keypad At least one fault has been T Eus itinne partitions are in standby Primary power OK 230V a c partitions is armed detected status Ready to arm Fast blinking At least one E FAS At Sa one fault gt E and ON 0 15sec is armed Memory of alarm at least one zone belonging to r Au 0 15sec tamper on at least one of the the keypad partitions is either partitions For JOY MAX only i T I by an unplayed voice message is keypad partitions or memory disabled inhibited or is in present in the memo box Open zones on the keypad Slow blinking ni the keypad partitions are No faults present At least one 4 E M neis ON 0 5sec disarmed Memory of alarm of the zones belonging to the sa ae For JOY MAX OFF 0 5sec tamper on at least one of the keypad partitions is either oni y an unplaved voice keypad partitions or memory disabled inhibited or is in Rubi S dde in the of a system alarm Test status GRA box of a system alarm Test status 12 The SmartLiving System e e e e User s Manual INIM SMARTLIVING The list of faults signaled on the yellow fault LED A can
11. 8 pulses with 5 second pause Entry time 3 pulses with 5 second pause 4 short pulses with 5 second pause during the Exit time final 20 seconds of the Exit Time 1 pulse with 5 second pause Emergency status 2 3 7 In the event of a keypad configuration or communication error between the system peripherals the display will show one of the templates opposite If this occurs you must contact your installer immediately and get the fault cleared The SmartLiving System 13 SMARTLIVING LI LL User s Manual Reader nBy 2 4 The SmartLiving intrusion control panel manages nBy S and nBy X readers and also JOY MAX keypad readers The proximity reader is the easiest way for users to interact with the SmartLiving intrusion control system The wall mount nBy S model anchored by means of two screws is IP34 rated and therefore suitable for outdoor use It is equipped with a buzzer and 4 LEDs e Fi Red e F2 Blue e F3 Green e F4 Yellow The Universal flush mount nBy X Patent Pending has been especially designed to integrate with all brands of cover plates It is equipped with 4 LEDs red blue green and yellow Readers do not provide the same extent of system control as keypads however these devices are quick and easy to use and are extremely useful when carrying out day to day operations arm disarm partitions etc Readers are usually located near the main entry exit points of the protected building Th
12. Keypad Settings section of the User Menu by means of a valid PIN Follow the instructions described in Method 1 Change PIN This section allows you to change your User Code PIN If your code has Main User status it will also allow you to change the PINs of other users but not of other Main Users In order to be EN50131 compliant all PINs must have 6 figures Via Keypad Method 1 Activate the shortcut assigned to the Change PIN shortcut n 34 3 and associated with one of the following keys Fir shown on the display with or without code entry to access the Change PIN section of the User Menu 1 Use keys and followed by the user code you wish to change 2 Type in the new PIN 4 5 or 6 digits using keys 0 J then press 3 Type in the new PIN again using keys 0 5 then press to save Method 2 Access the Change PIN section of the User Menu by means of a valid PIN Follow the instructions described in Method 1 Change telephone numbers This section allows users to change the contact telephone numbers Only contact numbers with at least one partition in common with the entered PIN and keypad in use will be shown Via Keypad Access the phonebook 1 Use keys and to select the required phone number then press 0K each programming field accepts a 20 digit phone number 2 Use keys 9 and e to select the field you wish to change then use the number keys mM etc to edit th
13. Manual Shortcut with code Besides the keypad shortcuts provided by keys Fir F2 F4 each user code can have as many as 22 customized personal shortcuts Users can access their code shortcuts only after entering their PINs and pressing refer to paragraph 2 5 1 Accessing the User Menu Each code can be programmed to manage e Up to 12 shortcuts activated by keys Fira and identified by explicit icons e Up to 10 shortcuts activated by keys 0 7 9wxj If a code is enabled to operate the system over the phone these shortcuts will also be available on the telephone number keys Entry of a code associated with shortcut no 9 d at a JOY MAX keypad prompts the voice announcement of all the shortcuts assigned to the number keys To activate a shortcut at a keypad work though the following steps 1 Type in your code then press x 2 Access the User Menu using the method described in paragraph 2 5 1 Accessing the User Menu at point 2 3 Press the key Fix which corresponds to the shortcut icon or press the key 0 which is assigned directly to the shortcut To activate a shortcut over the phone 1 Establish communication with the control panel 2 Type in your code followed by 3 Listen to the voice prompts regarding the available shortcuts 4 Press the number key which corresponds to the required shortcut Key and Reader shortcuts nBy S and nBy X Reader shortcuts Hold
14. Method 2 v Method 5 2 Using the system User s Manual SMARTLIVING Via Keypad Method 1 Activate the shortcuts associated with keys Ffm shown on the display with or without code entry The shortcut which is assigned to Arm Disarm operations shortcut n 1 i 9 i Fia e 4i applies the pre set scenario e e The shortcut assigned to Arm Disarm Menu shortcut n 12 z Y M ethod 2 you to view the respective section and arm in Stay or Away mode or disarm alinea each partition separately Away mode Method 1 e e 1 Select the desired partition using keys and Jj P y 2 Select the required operating mode using keys and 4m 3 Once the required operation has been selected press Method 2 Access the Arm Disarm section of the User menu by means of a valid PIN Follow the instructions described in Method 1 Method 3 While the entry time is still running refer to Entry Time in Appendix A Technical terminology and Glossary type in a valid code followed by the code must have access to the Arm Disarm section of the User Menu the partitions the code and keypad concerned have in common will disarm instantly Method 2 Via Reader Hold a valid key in the vicinity of the reader and remove it when Arm Disarm shortcut n 1 is indicated on the LEDs the system will apply the pre set scenario S E Method 2 Over the phone T
15. a valid key in the vicinity of the reader as soon as the reader accepts the key a series of visual signals on the reader LEDs will indicate the various shortcuts When the required shortcut is indicated remove the key to activate the corresponding shortcut action The visual signals on the Reader LEDs are as follows refer to Table 7 Reader LEDs with key at reader 1 Red LED on for 3 seconds shortcut associated with the red LED of the reader or first shortcut of the key 2 Blue LED on for 3 seconds shortcut associated with the blue LED of the reader or second shortcut of the key 3 Green LED on for 3 seconds shortcut associated with the green LED of the reader or third shortcut of the key 4 Yellow LED on for 3 seconds shortcut associated with the yellow LED of the reader or fourth shortcut of the key 5 All LEDs on for 3 seconds first shortcut associated with the user key All LEDs off for 3 seconds disarm all the partitions 7 Tf the key is not removed the reader will run through the entire sequence again starting from the red LED Selection of the desired shortcut indi cated by a specific LED will not occur until the key is removed zn If during this phase any of the partitions are armed the LED sequence will start at point 6 If the installer has enabled option 50131ReadLedOFF the reader LEDs will be off therefore if you wish to activate a shortcut you must 1 Wave the key across the sensitive area of t
16. en eMethod 1 3 E Method 2 HHH Using the system e e e e e User s Manual unum SMARTLIVING ee System voltage ee Zone status allows you to view only the zones associated with the partitions the code and keypad concerned have in common Use keys and to scroll the list of accessible zones ee Faults ee PanelVersion e Other shortcuts which provide direct access to sub sections of the View section are ee Shortcut n 28 dell ec oe ec ee Shortcut n 33 ee Shortcut n 36 accesses View Faults Method 2 Access the View section of the User menu by means of a valid PIN Follow the instructions described in Method 1 Via Web Access the SmartLAN G web server refer to paragraph 5 17 2 Access the web server Press the Gy button It is possible to view only the partitions the user controls Operating mode e status Alarm memory Tamper memory Auto armec Partition in Noa JU No amba T empty saved to empty events saved to empty Disable Disarmed standby status memory memory Description of the Away mode Partition in SMP Enabled selected partition Stay mode alarm status Alarm event memory saved to Instant mode XX Partition in i tamper short MEMO circuit status a Press the button Use the mouse to select a partition and view in the top ub all the incited zones the user controls SSS fet Alarm memory Tamper memory No alarm events No tamper
17. in such a way to allow the system to read it and permit access to authorized operations Each key is programmed with e A random code selected from over 4 billion possible combinations e A label usually the name of the user e The partitions it controls arms disarms etc e A group of pre set parameters which allow the key user to operate the system in accordance with the authorized access level for example a key can be programmed to arm or disarm the system only at certain times of the day This device allows users to access and control the system Keypads can be connected to the system via the I BUS The keypad allows users to access and control the partitions which are common to both the code and keypad in use The user can arm disarm partitions view the status of the zones stop visual and audible signaling devices A generic magnetic contact is a detector sensor based on an magnet which when placed near the sensor provokes the mechanical closure of an electrical contact An electrical output point connected to a signaling or control device activated deactivated by the control panel in response to programmed events A group of zones A partition identifies a group of zones that belong to a spatial or logical portion of the protected premises For example a partition may comprise all the zones that protect the downstairs SARRI of a house spatial partition or all the entrances of an office building logical partition
18. on one or more partitions These generally indicate also the status of the partitions Under normal circumstances the zones of armed partitions can generate alarms Under normal circumstances the zones of disarmed partitions cannot generate alarms The system generates tamper alarms even when partitions are disarmed You can enable disable the Auto arm function on each separate partition If the auto arm option is enabled on a timer controlled partition the partition will arm disarm in accordance with the ON OFF settings of the timer This is the secondary power source of the system If primary 230 Vac power failure occurs the battery will take over A EE of outgoing event associated calls the control panel must send to programmed contact numbers Enabled users can clear the call queue manually Violation of a zone with this configuration will not generate an alarm but will trigger the associated Timer Entry time If the user does not disarm the partition s within the set Entry time the system will generate an alarm For example the zone that monitors the main door of a building is usually configured as a Delayed Entry Zone in order to give building occupants time to enter the building and disarm the partition without generating an alarm Violation of a zone with this configuration will not generate an alarm but will trigger the associated Timer refer to Exit time For example the zone that monitors the main door of a residence
19. system configuration will allow users to record memos Memos can be recorded played deleted as required An intrusion control system whose devices detectors keypads keyfobs communicate with the control panel over radio waves Usually only the control panel of wireless systems is mains powered 220Va c while the wireless devices are battery powered The battery life is of utmost importance in the design layout and operational capacity of these systems An electrical input point used for the management supervision of signals coming from an intrusion detection device PRIMARY POWER SOURCE READER NBY SCENARIO SHORTCUTS SUPERVISION TAMPER TELEPHONE ACTIONS TELESERVICE TEST ZONE TIMER TRANSCEIVER USER CODE USER MENU VOICE DIALER VOICE MEMO WIRELESS ZONE 42 Technical terminology and Glossary User s Manual SMARTLIVING SHORTCUTS AT DEFAULT m ICON description function parameter Applies a pre set scenario lately deactivates the outputs relative to Stop alarms zone partition alarm and tamper events and system tamper events Cancels the call queue and stops ongoing calls if any Carries out a Stop alarms operation and at the same time deletes memory of system and partition alarm and tamper events Scenario Activates one of the Activate outputs 5o c mmed outputs Output Deactivates one of the Deactiv OUtputs 5o o mmed outputs
20. the User Menu Enable timers section Activations Timers Accesses the User Menu Enab auto arm section Activations Auto arm Accesses the User Menu section View Events log Accesses the User Menu View alarm log section View Alarms log Accesses the User Menu section View Faults log View events log View faults log Accesses the User Menu View arm ops log section View Arm Disarm Op Accesses the User Menu section View System Voltage ViewSystemStatu S Accesses the User Menu section View Zone status Accesses the User Menu Accesses the User Menu Accesses the User Menu Accesses the User Menu 43 View zone status SMARTLIVING LI LL User s Manual Appendix C FAULT SIGNALS The following table shows how system faults indicated by the yellow LED are signaled clearly on the keypad A i User menu string View Excessive current draw on the AUX terminals zone fuse blown Zone fuse fault AETERNE D Excessive current draw on the terminal on BUS fuse blown IBUS fuse fault n NENNEN Backup battery low or Low batter The control panel backup battery is running low disconnected J or is not connected properly Primary power source Mains failure The primary power source 230 Vac has failed failure blackout or is not connected properly Telephone line down Tel line down The telephone line is not working SE Wireless noise ammi n Rogue wireless signal tt Low wireless detector Th
21. thoroughly before starting up SmartLiving system Once you have become accustomed to the day to day operations your installer will explain and if required program the a advanced functions provided by the system A typical system comprises e SmartLiving control panel e intrusion detection devices PIR or microwave detectors magnetic contacts linear beam detectors etc e System control peripherals proximity readers keypads e alarm signaling devices which generally signal the events detected by the system sounders flashers etc The keypad Joy GR Joy MAX nCode G or Concept G is an extremely flexible peripheral device which allows you to manage the system with ease The graphic display provides all the information necessary for fast understanding of the system status and the steps necessary to take in the event of an alarm All users have PINs which allow them to access and control the system in accordance with their permitted access level Advanced voice technology guides you through the operations by means of clear voice prompts which explain the operations you must undertake nBy readers 2 versions available nBy S wall mount and By X flush mount MARTA s allow you to access and control the system Although these devices are not as flexible as keypads they provide a quick and easy way of carrying out day to day operations such as arming and disarming the system Authorized digital key users can operate the syste
22. 2 168 1 92 becomes https 192 168 1 92 mobile AREA 002 E Once access to the web server has been achieved the cellphone display will AREA O03 n show po e e the icons which access the various sections top of display AREA MH e the various objects available for selection centre of display e the icons that represent the functions available for the selected objects bottom of display All operations must be carried out as follows 1 Select the desired section from those available at the top of display Press A to update the display The difference between the web interface and the computer interface is that mobile phone devices do not have access to a virtual keypad however they have two additional sections Table 11 Web server sections Icon Key Note Tm This section allows users to activate the scenarios they have access to refer to paragraph 5 2 Arming m This section will allow users to view the status of the outputs and also activate deactivate them refer to Outputs management paragraph 5 5 View e paragraph 5 6 Activating Deactivating outputs Lb T7 38 Using the system User s Manual unum SMARTLIVING Appendix A TECHNICAL TERMINOLOGY AND GLOSSARY These are 4 5 or 6 digit PINs which allow the building occupants users to access the system Each code can be programmed to control specific functions only and to operate the system to suit the requirements of the Main user Code ty
23. Certified by IMQ Security systems CEI 79 2 EN 50131 3 EN 50131 6 T014 USER S MANUAL ELECTRONICS SMARTLIVING LI LL User s Manual INIM Electronics s r l Seller Our Us warrants the original purchaser that this Warra nty product shall be free from defects in materials and workmanship under normal use for a period of 24 months As INIM Electronics s r l does not install this product directly and due to the possibility that it may be used with other equipment not approved by Us INIM Electronics s r l does not warrant against loss of quality degradation of performance of this product or actual damage that results from the use of products parts or other replaceable items such as consumables that are neither made nor recommended by INIM Electronics Seller obligation and liability under this warranty is expressly limited to repairing or replacing at Seller s option any product not meeting the specifications In no event shall INIM Electronics s r l be liable to the purchaser or any other person for any loss or damage whether direct ot indirect or consequential or incidental including without limitation any damages for lost profits stolen goods or claims by any other party caused by defective products or otherwise arising from the incorrect or otherwise improper installation or use of this product This warranty applies only to defects in parts and workmanship relating to normal use It does not cover e damage
24. Description of the ae zones which belong Zone in alarm Zone empty Zone not in test Led to to the selected status unbypassed pty status Alarm event memor Pero XX in tamper o i short circuit A pend status The outputs the user has access to will be shown in the field in the lower part of the zone section after pressing the 9 button if you are using a computer or pressing the NG y g a comp ON onice 1 4 i m escriptions Output after pressing We if you are using a mobile telephone device OFF X gasa ad P Press the a button It will be possible to view all the timers Timer ON Timer active EP Pap Timernat active Using the system 29 SMARTLIVING User s Manual PES Press the button then the UpdateLog button It will be possible to view all the events saved to the log Date Time Location Category mE A and time of the The group 0 Pirati ana LL ang Progressive number event saved to the partitions involvedin User ID or event ocation of the of the event control panel events Event description the event if trigger if applicable peripheral involved Event category log applicable if applicable 5 6 Activating Deactivating outputs This section allows you to activate deactivate manually the outputs the code controls Via Keypad Method 1 Activate the shortcuts associated with keys Fix shown on the display with or without code entry e T
25. Faults on IVY BUS LowBatt Soundfl inhibit the sounder and activate only the flasher have at least one fault present sounderflasher i in the event of an alarm If the voltage drops Press on the selected below 8V the s ie DELE the sounder sounderflasher to access the list of current faults on the device An excessive internal resistance has been concerned Sounder faults detected on the sounderflasher battery This type Batter y res ist of deep fault indicates corrosion inside the battery therefore the battery must be replaced Violation of zones with Violation has occurred on one or more zones with Press to access the list of Faults on zones the Fault zone option enabled involved AA Fault signals DCMUINEOSLIVINGE R400 20110121 User s Manual unum SMARTLIVING Notes 45 SMARTLIVING unum User s Manual 46 User s Manual unum SMARTLIVING 47 ELECTRONICS ISO 9001 2008 Registered company via Fosso Antico Loc Centobuchi 63076 Monteprandone AP ITALY Tel 39 0735 705007 Fax 39 0735 704912 info inim biz
26. LL with confirmation request Press the respective key Flr F4 the system will ask if you wish to continue or not If you press the shortcut will activate instantly if you press or Esc the operation will be abandoned This method protects against accidental operations The shortcut will affect all the keypad partitions Code users only Press the respective key Fiz then enter a valid code the shortcut will activate after code recognition The shortcut will affect the partitions common to both the keypad and code Code users only when activation of the shortcut lowers system security If a shortcut involves a scenario that completely disarms a parti tion or switches a partition from Away mode to Stay mode the security of your system will obviously be at risk therefore the system will request code entry The shortcut will affect the partitions common to both the key pad and code To activate a shortcut press the key Firs which corresponds to the shortcut icon The system will either activate the shortcut instantly case 1 or will request confirmation case 2 or code entry cases 3 and 4 before carrying out the operation Shortcuts Chapter 3 3 1 e e e 6 O e 0 0 e a bem 0 er Shortcut O activation 1 Shortcut activation 2 Fia Rw Be Fao i E E OK Shortcut activation 3 4 19 SMARTLIVING LI LL User s
27. Output Delays auto arming time of partitions by 30 minutes Sends a call to the Installer Teleservice req company number Teleservice number Plays a recorded message which announces the shortcuts assigned to the number keys Allows eavesdropping over the phone by means of a microphone located on suitably placed keypad Accesses the User Menu section Voice functions Intercom Call User code Listen in Keypad Arm disarm Accesses the User Menu menu section Arm Disarm Accesses the User Menu section Manage alarms Voice func Accesses the User Menu menu section Voice functions Activations Accesses the User Menu menu section Activations Accesses the User Menu aa Provides voice Information KO regarding the armed Arming status armed status of the partitions Keypad Accesses the User Menu sett menu section Keypad Keypad Shortcuts at default Appendix B n CON DESCRIPTION funcion ZoneBypass Accesses the User Menu menu section Activations Zones z Accesses the User Menu Voice memo section Voice functions Accesses the User Menu Output control section Outputs ON OFF Accesses the User Menu section Activations Answerphone Enab answerpho ne l Accesses the User Menu Enab teleservice section Activations Teleservice Accesses the User Menu Enable codes section Activations Codes Accesses the User Menu aL Enable keys section Activations Keys Accesses
28. The following shortcuts activate the associated commands ee Shortcut n 2 Xe Stop alarms ee Shortcut n 3 gm Clear call queue ee Shortcut n 4 pag DeleteAlarm mem Method 2 Access the Alarm management section User Menu by means of a valid PIN Follow the instructions described in Method 1 Via Reader Hold a valid key in the vicinity of the reader until the reader LEDs or display indicates Stop alarms shortcut n 2 Clear call queue shortcut n 3 or DeleteAlarm mem shortcut n 4 Over the phone Type in the PIN of a user code followed by the user code must be enabled to operate the system over the phone then press the key from O to 9 which the installer has programmed to activate Stop alarms Shortcut n 2 Clear call queue shortcut n 3 or DeleteAlarm mem shortcut n 4 Via Wireless keyfob Push the respective button on the keyfob and verify the outcome of the requested operation as described in paragraph 2 6 1 Air2 KF100 Wireless keyfobs Via Web Access the SmartLAN G web server and press Gy button Use the mouse to select a partition then press button Ry to delete the alarm memory and if allowed tamper memory Arming and disarming partitions You can arm disarm the system partitions via keypad reader over the phone zone command wireless command Internet as follows If you enter an arm partition s command at a keypad and not all the respective
29. a programmable chronothermostat function This ia function allows you to set up zone management one zone per keypad of the heating air conditioning system The temperature is gauged by a built in temperature sensor The hysteresis is fixed at 0 4 C The Concept G keypad provides a further two options relating to direct user access A special feature allows activation of the backlight of the display and keys when users approach the keypad This is achieved through a proximity sensor which can be activated by pressing keys 1 and O simultaneously and deactivated by pressing and o The other option block unblock keypad can be achieved by pressing key O for 3 seconds If the block keypad option is enabled the display will show the icon opposite Display description 2 3 1 The brightness and contrast of the backlit graphic LCD 96 x 32 pixel can be adjusted by way of the respective options on the User Menu refer to paragraph 5 8 Keypad settings The first line of the display shows the date and time If you are using a JOY MAX keypad the date and room temperature will alternate on the screen every 3 seconds The left side of the second line shows the characters that indicate the current status of the partitions the keypad is assigned to e D partition disarmed e A partition armed in Away mode interior and perimeter zones armed e S partition armed in Stay mode perimeter zones armed partition ar
30. alled Only authorized users can operate the system The most common operations can be carried out without code key verification This method must be expressly requested by the main user as it considerably lowers the security level of the system and may cause false alarms accidental arm disarm operations etc Access Levels 1 7 The normative defines the following system access levels regardless of system access limitations Level 1 access by any person e g passer by Level 2 user access Level 3 installer or maintenance operator access authorized by user level 2 Level 4 manufacturer access Conventions Glossary 1 8 In order to help users understand the terminology utilized in this manual and improve your knowledge of this system and its operating procedures read carefully through the Technical Terminology Glossary refer to Appendix A Technical terminology and Glossary The appendix contains the definitions of technical terms commonly used in the field of security therefore relevant to the SmartLiving system General information 7 SMARTLIVING LI LL User s Manual Chapter 2 THE SMARTLIVING SYSTEM Introduction 2 1 INIM Electronics wishes to thank you for choosing this SmartLiving intrusion control system Its advanced technology and user friendly operations provide an extremely high level of protection combined with ease of use INIM Electronics recommends that all parts of this manual be read
31. arising from improper maintenance or negligence e damage caused by fire flood wind or lightning e vandalism e fair wear and tear INIM Electronics s r l shall at its option repair or replace any defective products Improper use that is use for purposes other than those mentioned in this manual will void the warranty Contact Our authorized dealer or visit our website for further information regarding this warranty INIM Electronics s r l shall not be liable to the purchaser or any other person for Limited damage arising from improper storage handling or use of this product Wa rra nty Installation of this Product must be carried out by qualified persons appointed by INIM Electronics Installation of this Product must be carried out in accordance with Our instructions in the product manual The information contained in this document is the sole property of INIM Copyright Electronics s r l No part may be copied without written authorization from INIM Electronics s r l All rights reserved Hereby INIM Electronics s r l declares that the SmartLiving series of intrusion European control panels the Air2 series of devices and the SmartLink product are in Directive compliance with the essential requirements and other relevant provisions of s Directive 1999 5 CE com pliance Moreover INIM Electronics s r l also declares that all other devices mentioned in this manual are in compliance with the essential requirements and other rel
32. artitions codes keys therefore they will function in accordance with Timer Off status All the timers will be activated automatically when you exit the programming session You Note must deactivate timers which are not used for system control purposes e Dialer a deactivated disabled dialer cannot send voice or digital calls However if duly programmed it will be able to manage incoming calls e Answerphone function if activated enabled the control panel will answer incoming calls with the pre recorded voice message Answerphone message e Teleservice if activated enabled the installer will be able to access the system via modem The Teleservice call allows the installer to work on the control panel parameters Teleservice operations involve a request from you and the installers acceptance therefore this option needs to be enabled only when required If the Answerphone and Teleservice functions are both enabled the control panel will Note give incoming call priority to the Teleservice call After picking up the call the control panel will allow the installer company modem 30 seconds to establish communication If the modem fails to communicate within this period the control panel will play the pre recorded Answerphone voice message e Internet access If this option is enabled and the system is equipped with a SmartLAN G board the control panel will allow user authorized access to the system via LAN Intern
33. be found in the table in Appendix C Fault signals Following is the list of events which cause the Red System Alarm LED te to blink e Open panel tamper e Dislodged panel tamper e Expansion tamper e Keypad Tamper e Reader Tamper e Expansion Loss e Keypad Loss e Reader Loss e False key If the False key event is configured as a Silent event the red LED will not FALSE KEY blink If this option is enabled the status of the partitions will be hidden If a valid code 50131STATHIDDEN is entered at a keypad the real time status will be indicated on the keypad concerned for 30 seconds Additionally e If the partitions are armed the status of the system will be hidden from non authorized users ee Red keypad LED Off ee Yellow keypad LED Off ee Green keypad LED On solid ee Status icons not present ee Alarm and Tamper memory hidden ee If a particular event occurs more than 5 times when the partitions are armed it will not be signaled as having occurred more than 5 times This is due to the limitation placed on the counter of each event The counters will reset to zero each time all the partitions are disarmed e If the partitions are DISARMED ee LEDs operating normally ee Status icons present ee Alarm and Tamper memory visible Signaling on the Buzzer 2 3 6 The buzzer signals the running Entry Exit and Pre arm times refer to Appendix A Technical terminology and Glossary of enabled partitions
34. can be programmed with its own Exit time These boards can be used to increase the number of terminals zones or outputs and or the size of the system in order to extend it over a larger partition Expansion boards can be connected to the system via the I BUS A condition which indicates that a system component is not working properly Some faults can jeopardize the performance of the entire system Mains failure 230V a c telephone line down and low battery are typical faults A device which allows the control panel to make telephone calls over the GSM network and also allows users to interact with the control panel over the phone or by means of SMS text messages The Nexus dialer is a peripheral device which is completely SmartLiving system integrated and is managed by the control panel BUS INIM s SmartLink is a similar device which is also compatible with control panels manufactured by other makers This device is capable of providing the control panel with a telephone line even in the event of telephone line tamper line cutting This function increases the level of security considerably This is the two way communication line 4 wires only which connects the peripheral devices keypads readers expansions etc to the control panel The 4 easily identifiable wires on the control panel motherboard and on the expansions are e power 12 Volt e D data e S data e Ground gt disabled zone inhibited cann
35. ce of a new memo in the memo box will be indicated on the blue LED on the keypad as described in Table 5 Keypad LEDs The SmartLogos30M voice board provides a total of 60 seconds memo time shared by all the JOY MAX keypads in the system 15 memo slots are available Note 22 Voice functions User s Manual unum SMARTLIVING Chapter 5 USING THE SYSTEM This chapter describes all the operations users can carry out with or without authorization user PIN entry The tools and methods which allow access the system operations are as follows The system can be accessed e Via keypad JOY GR JOY MAX nCode G Concept G The keypad allows users to operate the system 1 By means of shortcuts refer to paragraph 3 1 Keypad shortcuts 2 By means of access codes via the User Menu refer to paragraph 2 5 User Codes and paragraph 3 2 Shortcut with code Users have various ways of viewing their personal menus refer to paragraph 2 5 1 Accessing the User Menu however this chapter describes the procedure via menu and pro vides the visual information relating to the sections described at point 1 in paragraph 2 5 1 Accessing the User Menu e Via Reader nBy X nBy S built into JOY MAX keypads This proximity key reader provides users with only one way of accessing the system as described in paragraph 3 3 Key and Reader shortcuts e Over the phone During a call from to the control panel after valid code PIN entry e Via Command Zone
36. display indicates the level of signal strength on a scale of O to 7 the higher the value the better the signal If you access the control panel via browser it will be possible to view the status of Partitions menu Outputs Timer Events log Via Keypad Method 1 Activate the shortcuts associated with keys Fim shown on the display with or without code entry e The shortcut assigned to View menu shortcut n 16 allows you to access the respective section in the User Menu and view the contents of the ee Events log ee Alarms log ee Faults log ee Arm Disarm op User access to the information in the Logs is filtered For example a user can view only the zone alarms relating to the partitions the code and keypad concerned have in common Press keys and to scroll the chronological events list For some events key SJ allows you to view the partitions details For example the details of an Arm command will show the code and keypad concerned and if you press o the list of partitions involved ee Nexus status The display will show the 1 line GSM network provider Vodafone etc 2 line GSM signal reception value between 1 and 100 3 line balance at the last operation expressed in the local currency 4 line faults if present access the View Faults ongoing section for details 28 Deactivate gere the selected zone Activate unbypass the selected zone 5 5 F1
37. due to zones ready to arm due to zones ready to arm due to zones ready to arm due to zones which are not in standby which are not in standby which are not in standby which are not in standby status status status status Fast blinking ON 0 15sec If the shortcut associated with the key is an arming operation one of the partitions concerned is not ready to arm due to OFF 0 15sec zones which are not in standby status ALL LEDs If a key is present all operations arm disarm etc will apply only to the partitions Note common to both the key and reader If this option is enabled and there are no keys present at the reader the reader 50131READERLEDOFF LEDs will be Off User Codes 2 5 Each User Code comprises a PIN for identification purposes and a group of parameters which determine its rank in the system code hierarchy and the operations the user is entitled to perform The PIN is made up of 4 5 or 6 digits that the user must enter in order to allow identification The PIN of the only user code enabled at default is 0001 The PINs of the successive codes are 0002 0003 etc The installer is allowed to change User code PINs The installer provides the system users Note with default user PINs which they must change immediately to PIN codes of their choice Each user code is characterized by the following parameters programmed by the installer in accordance with specific user rank e Partitions User codes can con
38. e activated deactivated manually After accessing the Outputs ON OFF section User Menu the user can activate v deactivate the duly programmed outputs e The Menu Sections are the authorized User menu sections refer to paragraph 2 5 1 Accessing the User Menu point 1 m m Di s arm op e Customized Shortcuts Each code can be programmed to manage Voice functions ee up to 12 customized personal shortcuts assigned to keys Fi raj ee up to 10 customized personal shortcuts assigned to keys 0 These shortcuts are available only after accessing the User Menu The SmartLiving System 15 SMARTLIVING unum User s Manual Accessing the User Menu In order to access a customized personal menu it is necessary to type the respective PIN and press key OK At this point there are 3 different ways of allowing first access to the user menu depending on the system setup as follows 1 The user can access the menu directly as shown in the figure opposite 1 using keys and amp m gt the user can select the desired menu sec tion and press for access Following is a the list of available User Menu sections e Manage alarms e Arm Disarm op e Voice functions e Activations e View e Outputs ON OFF e Set date time e Set Keypad e Change PIN e TelephoneNumbers e Teleservice req e Overtime e Thermostat 2 The keypad cancels the shortcut icons associated with keys Fira and replaces the
39. e battery of at least one wireless detector is For information relating to Low battery WLS and WLS zone loss signaling access the User menu View Faults Wireless detector loss WLS zone loss At least one wireless naa is not responding press Rto view the list of lost devices involved battery Low battery WLS running out GSM E P ki Low The GSM network signal is insufficient GSM fault GSM The GSM module of the Nexus dialer is not module fault operating properly Call your Installer company Fault on Nexus GSM GSM fault SIM The SIM card does not respond or is not present press OR on GSM fault to alaler commun fault The SIM card PIN is not disabled access the list of current faults GSM fault Low The remaining credit on the SIM card is below credit the minimum credit threshold GSM fault Provider The GSM network provider of the SIM in use is missing unavailable One of the following events is present Panel open Panel dislodged Expansion tamper Keypad tamper Reader tamper Sound flash Tamp Expansion loss Keypad loss Reader loss Sound flash Loss Sounder faults Horn JA defect damage has been detected on the horn fault sounder Loss or tamper running LossTamp ongoi ng A low voltage value has been detected on the sounderflasher battery Press on Sounder faults to i i the list of devices which Sounder faults If the voltage drops below 10V the device will QECES5
40. e functions and Intercom JOY MAX only 26 Scb ACCVOLUDNS 3 4 9 9 2 4 9 04 9 FAR a 26 Do WEN 2 2 3909 de uo dice ce ae Ee ORE Dc o Az a e NE iE pia 28 5 6 Activating Deactivating outputs o 30 5 7 Change date and time aaa KA ke bbe E rub HERR E ek 31 5 8 Keypad settingS saviano ieri 31 5 9 CHange PIN 24444 xo aca rada GA SA KNA DAG OR a ee o3 WG 92 SMARTLIVING LI LL y User s Manual 5 10 Change telephone numbers rmn 32 5 11 Teleservice request llle Rn rs 33 5 12 Overtime request x vr RR 23 5 13 Thermostat JOY MAX keypads only 34 oi RR TREE kea ee ee EE 35 5 15 Partition status enquiry aos dos ha a dia ai 35 5 16 Commands over the phone ee 35 5 17 Using the SmartLAN G 5 22k ae aw e Awe eee Ros 37 Appendix A Technical terminology and Glossary 39 Appendix B Shortcuts at default aaa aa aaa aaa a 43 Appendix C Fault signalS 000 eee ee 44 NOUCS S Rd ene RR 45 User s Manual unum SMARTLIVING Chapter 1 GENERAL INFORMATION Manufacturer s details 1 1 Manufacturer INIM Electronics s r l Production plant Via Fosso Antico Centobuchi 63076 Monteprandone AP Italy Tel 39 0735 705007 Fax 39 0735 704912 e mail info inim biz Web www inim biz Any persons authorized by the manufacturer to repair or replace the parts of this system hold authorization to work on INIM Electronics brand d
41. e number Accepts also 2 second pause and 3 Press to confirm and exit 32 5 9 Method 2 e Method 2 Method 2 Method 1 5 10 Using the system User s Manual SMARTLIVING Teleservice request This command sends a call to the installer company Your installer must enable control panel option NumiOForTeleserv otherwise this function will not be available Via Keypad Method 1 Activate the shortcut assigned to the Teleservice req shortcut n 8 By Method 2 Access the Teleservice section of the User menu by means of a valid PIN Via Reader Hold a valid digital key in the vicinity of the reader until the reader LEDs or display indicates Teleservice Request shortcut n 8 Overtime request This operation can be carried out under the following conditions only e The partition concerned must be timer controlled e The auto arm option must be enabled refer paragraph 5 4 Activations Each overtime request postpones the auto arming operation by 30 minutes Via Keypad Method 1 Activate the shortcut assigned to the Overtime shortcut n 7 to Method 2 Access the Overtime req section of the User Menu by means of a valid PIN Via Reader Hold a valid digital key in the vicinity of the reader until the reader LEDs or display indicates Overtime shortcut n 7 Over the phone Type in the PIN of a user code followed by X then pr
42. er events on the Partitions the key and reader have in common This type of key can select the reader shortcuts and its customized personal shortcuts Air2 KF100 Wireless keyfobs 2 6 1 The KF100 keyfob has 4 remote control buttons which can each be programmed with a shortcut ask your installer for details The graphic choice feature allows specifications you to identify the buttons by numbers or icons i Batter 3V CR2032 Lithium y battery included The keyfob also provides 4 button associated LEDs and a confirmation LED As a result of two way communications with the BS100 transceiver the KF100 keyfob imparts audible and visual feedback signals beep and LED signals which notify the user of the outcome of requested operations Soe with numbers Table 9 Feedback signals provided by KF100 Ia fash Shortcut activation 4 4 flashes 4 flashes Keyfob blocked If an operation is successful but the corresponding LED fails to light it is an indication that Note the battery is low The battery must be replaced before it runs out completely Feedback from panel Soma LED Confirmation LED red Command not eerie seo Operation done 3 flashes Tong beep Multi system access 2 7 Users can access several systems using the same code key keyfob The user code key or keyfob must be enrolled separately on the control panels concerned and can be programmed with different attributes and functions in acco
43. eripherals in the system Paplbheral Loss system configuration are At Ci aa aa configuration are responding properly B p responding properly ras ni O deri however loss of a peripheral has been Present i property detected and cleared Peripheral Loss memory Icon blinking bl m 00 0 0 i Pd e Interchanging icon The Control panel is The Control panel is in tamper The Control panel is properly placed and Control panel Tamper properly placed and the status enclosure open or device the enclosure is closed however panel enclosure is closed dislodged tamper has been detected and cleared Panel tamper memory i The keypad thermostat option is E enabled in Winter mode The thermostat option is Heating disabled The keypad thermostat option is Gummer neds enabled in Summer mode Air conditioning Thermostat m db Heating Air Aa UA Heating Air conditioning On conditioning If duly programmed by the installer the icon PI will not be shown when Teleservice is Note enabled The remaining section of the display that is the third and fourth line is occupied by the icons which correspond to the Shortcuts associated with keys Firs F40 If the function keys have not been associated with shortcuts the third and fourth line will be empty Display standby status A 1f the control panel is in Maintenance status the first line on the screen will show the string indicated in the figure The charac
44. ese devices allow system access to valid keys only The system readers are capable of recognizing a large number of keys each characterized by customized parameters Each reader is enabled to operate on specific partitions whereas each key is enabled to operate only on the partitions the user is allowed to control Therefore if a key is held in the vicinity of a reader it will be possible to control only the partitions which the two devices have in common Each reader can be programmed with up to 4 shortcuts one per LED Each key can be programmed with up to 4 shortcuts Unlike most traditional readers which generally carry out arm disarm operations only nBy readers also manage a series of useful shortcut commands For example it is possible to associate two shortcuts to the red and blue LEDs for arm and disarm operations and a shortcut to the green LED for gate control and yet another to the yellow LED for Clear call queue operations The buzzer signals the running Entry Exit and Pre arm time of the reader partitions refer to paragraph 2 3 6 Signaling on the Buzzer Signaling on the Reader LEDs 2 4 1 The LEDs have two distinct operating in modes 1 When no key is present at the reader refer to Table 6 Reader LEDs with no key at reader the LEDs will indicate the current status of the associated shortcut 2 When a key is present at the reader refer to Table 7 Reader LEDs with key at reader the LEDs will indicate i
45. ess the key from O to 9 which the installer has programmed to activate Overtime shortcut n 7 Via Wireless keyfob Push the respective button on the keyfob and verify the outcome of the requested operation as described in paragraph 2 6 1 Air2 KF100 Wireless keyfobs Using the system 5 11 Method 2 e Method 2 v deco Service call Method 1 activated a 5 12 Method 2 dii soco Auto arming Method 1 postponed 33 SMARTLIVING LI I y User s Manual Thermostat JOY MAX keypads only The Thermostat function provided by JOY MAX keypads manages the heating or air conditioning system in accordance with its setting e ik Summer when the sensor detects that the temperature has risen above the value set by the user the output connected to the air conditioning system will activate indicated on the display by d e Winter when the sensor detects that the temperature has fallen below the value set by the user the output connected to the heating system will activate indicated on the display by fp This function provides 5 operating modes for the user to choose from e Off the thermostat is off the output associated with the heating or air conditioning system is deactivated e Manual the temperature set by the user is valid for 24 hours per day for 7 days per week e Daily the temperature set by the user is valid during the selected hours for 7 days per week
46. et If this option is disabled the control panel will allow user authorized access to the system via Teleservice if authorized e e Enable install If enabled the Installer PIN will be accepted by the system F1 ro F2 5 e and the installer will have access to the Installer menu If disabled entry of e8 e the installer PIN will generate an Invalid Code event and the installer will be e denied access to the respective menu Method 1 o Method 2 peeeee Via Keypad Method 1 Activate the shortcuts associated with keys Fim shown on the display with or without code entry Method 2 EE 2 allows e The shortcut assigned to the Activations menu shortcut n 15 you to view the respective section in the User Menu 1 Use keys and followed by to select the category of elements you wish to activate deactivate zones codes etc 2 Use keys and followed by OK to select the single element you wish to activate deactivate 3 Use to activate the selected element or to deactivate it e Other shortcuts which provide direct access to sub sections of the Activations section are ee Shortcut n 19 accesses Activations Zones ee Shortcut n 22 Bg accesses Activations Answerphone ee Shortcut n 23 hy accesses Activations Teleservice ee Shortcut n 24 Ba accesses Activations Codes ee Shortcut n 25 Ek accesses Activations Keys ee Shortcut n 26 EP accesses Activatio
47. evant provisions of Directive 2004 108 CE The full declarations of conformity can be found at URL www inim biz dc html The devices described in this manual in accordance with the settings selected State of the art during the installation phase and the following illustrated guidelines are I alternatively in compliance with the the Italian Normative CEI 79 2 1998 Ab 2000 Installations performance level 2 or European Normative CEI EN 50131 3 2009 in reference to DM 37 08 Control and indicating equipment intrusion control panels and CEI EN 50131 6 2008 in reference to Power supplies security grade 2 In support of research development installation testing commissioning and maintenance of intrusion alarm systems installed in buildings please refer to the following normative documents CEI 79 3 e CEI CLOTS 50131 7 When installing INIM systems it is up to the installer company to install systems equipped with Normative CEI 79 2 compliant devices rather than devices compliant with European Normatives series EN50131 within and not over the DOWs summarized in amendment CEI 79 2 V1 2010 User s Manual unum SMARTLIVING Table of contents arias 2 Limited Warranty saasaa 2 CODVHIGN as darla aan i ei 2 European Directive compliance 0 00 ee es 2 State of the art Installations DM 37 08 2 Table of contents a a 3 Chapter 1 General information 0 seen 5 1 1 Manufacturer s detallS
48. evices only Description of the product anda 1 2 various models Description Intrusion control panel Models SmartLiving 505 SmartLiving 515 SmartLiving 1050 SmartLiving 1050L SmartLiving 10100L Applied Normative CEI 79 2 1998 Ab 2000 CEI EN 50131 3 2009 and CEI EN 50131 6 2008 Certification agency IMQ Security Systems Security rating 2 The following table describes the main features of the various models of the SmartLiving series Table 1 Control panel Main Features U Smartivingintrusioncontrolpanels 505 515 1050 10501 10100L_ UU ferminals on pani 3 1 Terminals on panel configurable as inputs 5 10 TermimalsonpamelconfigurableasRollerlind Shock 2 Terminals on panel configurable as outputs GT 8 Totalzons i0 3 39 A35 Relay outputs on panel motherboard 1 SCS Portion fs fa U Reypads JOY nCode G Concept G 5 10 s nByRedes i0 39 3 Digital Keys and keyfebs 50 w w UTE Codes E sh CU Semres 3 General information 5 SMARTLIVING LI UU y User s Manual Environmental Conditions 1 3 The JOY GR JOY MAX nCode G Concept G IB100 FLEX5 Nexus and nBy X peripheral devices are for indoor installation only and operate best under the following environmental conditions e Temperature from 10 to 40 C e Maximum humidity 75 without condensation e Environmental class II
49. functions which will be indicated when necessary Table 4 The keys Kes Mame ypical application O y O fesa 7 pars 9 wz Number keys Used to type in User PINs Sw lt UBDOWN Navigate through the menu lists or adjust keypad volume LEFT RIGHT Scroll along the data rows for example partitions in the events log etc Steps back on the open menu without changing the selected item parameter etc or after entering a User PIN and pressing 0K runs through the 3 User menu templates refer to paragraph 2 5 User Codes each time it is pressed EE e Exits the User menu without changing the selected item parameter etc ENABLE Enables options refer to paragraph 5 4 Activations DISABLE Disables options Emergency keys 2 3 4 This control panel provides 3 key duos for Emergency Calls which can be activated by pressing the respective keys on any of the system keypads 1 Fie F2 Fire Emergency 2 Flr Ambulance Emergency 3 Fie Police Emergency 2 3 O Utilization of any of the key duos will generate the respective events and a HQ a D actions e g activation of outputs and calls r To activate an emergency call press simultaneously and hold keys Fl x F2 amp or Ffm F3 or Fia for at least 3 seconds until the selected Press simultaneously emergency call is confirmed by a beep If any two function keys are pressed at the same time
50. he reader the LEDs will signal the respective status for 30 seconds 2 During this 30 second period hold a valid key in the vicinity of the reader in order to generate the visual signals on the reader LEDs Remove the key when the required operation or pre set scenario is indicated on the LEDs 20 3 2 3 3 1 Shortcuts User s Manual SMARTLIVING Shortcuts on JOY MAX 3 3 2 keypad readers Hold a valid key in the vicinity of the reader area of the JOY MAX keypad indicated by 9 The key and reader shortcuts will flash one by one at 3 second intervals on the keypad display Fim F2 5 8 When the required shortcut is indicated remove the key to activate the corresponding action The shortcuts appear on the display in the following order 3 seconds 1 Description of the first reader shortcut for 3 seconds Description of the second reader shortcut for 3 seconds Description of the third reader shortcut for 3 seconds Description of the fourth reader shortcut for 3 seconds Description of the fourth reader shortcut for 3 seconds Disarm disarms all the partitions for 3 seconds 7 Then back to point 1 if the key is not removed pg 9 JM 3 seconds Y If during this phase any of the partitions are armed the LED sequence will start at point 6 Keyfob shortcuts 3 3 3 To activate the shortcuts programmed by your installer assigned to the 4 keys F1 FA on the keyfob simply push the button w
51. he shortcut assigned to Output control shortcut n 21 allows you to view the Outputs ON OFF section of the User Menu where you can 1 Use keys and to select the output you wish to activate deactivate 2 Press to activate the selected output or to deactivate it e The shortcut assigned to the Activate outputs operation shortcut n 5 Eg will activate the output when the respective button is pressed e The shortcut assigned to the Deactiv outputs shortcut n 6 9 will deactivate the output when the respective button is pressed Method 2 Access the Outputs ON OFF section of the User Menu by means of a valid PIN Follow the instructions described in Method 1 Via Reader Hold a valid digital key in the vicinity of the reader until the reader LEDs or display indicates Activate outputs shortcut n 5 or Deactiv outputs shortcut n 6 Over the phone Type in the PIN of a user code followed by then press the key from 0 to 9 which the installer has programmed to trigger Activate outputs shortcut n 5 or Deactiv outputs shortcut n 6 Via Wireless keyfob Push the respective button on the keyfob and verify the outcome of the requested operation as described in paragraph 2 6 1 Air2 KF100 Wireless keyfobs Via Web Access the SmartLAN G web server refer to paragraph 5 17 2 Access the web server The outputs the user has access to will be shown in the field in the lower
52. here xxxxxx stands for the user s PIN the user will receive an SMS text message indicating the remaining credit balance e Status enquiry relating to the Nexus If the following SMS text message is sent XXXXXX STATUS where xxxxxx stands for the user access PIN the user will receive an SMS text message indicating the ee device name and firmware revision ee GSM network provider ee GSM signal reception level ee device tamper status ee BUS status ee Balance remaining credit e Inhibition using the EXC or ESC command or activation using the INC command of the control panel zones If the following SMS text message is sent 36 Using the system User s Manual unum SMARTLIVING XXXXXX EXC zone description where ee XXXXXX is the PIN of a control panel user coded followed by a blank space ee EXC or ESC or INC is the command to be implemented on the zone followed by a space ee zone description is the name zone to be inhibited or activated Using the SmartLAN G e mail The event related e mail sent to the user via the SmartLAN G board must be programmed entirely by the installer Below is an example of an e mail associated with a Valid Code event SmartLiving control Text edited by the installer associated with panel Valid code the respective event in square brackets SmartLAN inim bi File User1 inim biz User2 inim biz Lm Parameters se
53. hich corresponds to the desired command The successful outcome of the operation will be signaled by the buzzer and feedback LEDs on the keyfob refer to Table 9 Feedback signals provided by KF100 Shortcutlist 3 4 For the complete list of shortcuts refer to the table in Appendix B Shortcuts at default Shortcuts O to 8 shown in the table carry out the specified actions instantly Shortcut 9 4 can be activated over the phone only telephone shortcut Shortcut 17 AE can be activated over the phone or at a keypad All other shortcuts from 10 to 16 and from 18 to 37 provide direct access to specified sections in the User Menu therefore can be activated at keypads only Shortcuts 21 SMARTLIVING LI LL User s Manual Chapter 4 VOICE FUNCTIONS If the SmartLiving control panel is equipped with a SmartLogos30M voice board you will be able to take advantage of all the voice functions provided by the JOY MAX keypad and the over the phone voice guide Your installer will program the voice messages you require e for event associated calls e for event associated announcements on the JOY MAX keypad at address 1 Each JOY MAX keypad has a memo box for user memo recording playback This handy function will allow you to leave messages for other users who have access to the keypad refer to paragraph 5 3 Voice functions and Intercom JOY MAX only You can record play and delete messages at your own discretion The presen
54. ion etc Each event e g mains failure can be associated with an activation event when the event occurs and a restoral event when the event ends Each event can be programmed to generate the following actions e activation of one or more outputs e transmission of one or more e mails e transmission of one or more SMS text messages e activation of one or more voice calls e activation of one or more digital calls This is the non volatile portion of the memory the panels saves events to The events are saved in chronological order with the following details e event description with details regarding new events and restorals e information regarding the user or the cause of event e event location e event date and time The events log can be viewed by the system users and the installer Partition events zone alarms partition alarms arm disarm operations recognized codes and i RU can be viewed by users with at least one partition in common with the event element For example if a user arms several partitions from a keypad the events log will show e description of the event Arm request description of the code and partitions involved description label of the keypad involved date and time of the request A short period expressed in minutes or seconds during which the user must disarm the partition after violation for example after opening the front door otherwise the system will generate an alarm Each partition
55. ite contrast e Volume allows you to adjust the buzzer volume 3 levels available ee Off ee ow volume ee High volume e Keypad options ee Temperature off if enabled the temperature value read by the built in temperature sensor will not be shown JOY MAX keypads only ee NoExitTimeSignal if enabled the buzzer will not emit audible signals during partition Exit time ee NOEntryTimeSignal if enabled the buzzer will not emit audible signals during partition Entry time ee Beep on output if enabled the buzzer will emit audible signals during partition Exit time These settings apply only to the keypad you are working on and will be saved even in the event of panel shutdown Via Keypad Method 1 Activate the shortcut assigned to the Keypad set menu shortcut n 18 HEN and associated with one of the following keys Fira shown on the display with or without code entry to access the Keypad settings section of the User Menu 1 Use keys and followed by to select the required parameters 2 Use keys and to increase or decrease the value of the selected parameter To activate the selected option press amg to deactivate it press Er 3 Press to save Using the system 5 7 F Method 2 6 e Method 2 Method 2 Method 1 T Co F Method 2 Method 2 in Method 1 e 31 SMARTLIVING User s Manual Method 2 Access the
56. l allows you to view the Voice functions section Select the required function by means of keys e then press x ee Record Playback the operation time out expressed in seconds will be signaled by a counter and a progress bar on the display If you wish to interrupt the record playback operation manually press OK otherwise it will end automatically when the pre set time out expires You can adjust the volume during the playback phase using keys and ib ee Delete this operation must be confirmed by pressing e ee IntercomCall the display provides the list of keypads you can call Use Qui and to select the keypad you wish to contact then press to send the call The recipient keypad will emit a series of beeps to signal an incoming call and the display will be as shown in the figure The recipient can press to answer the call or Esc to reject it Both the sender and the recipient can end the call by pressing Esg The volume can be adjusted during the listen phase by pressing keys and ib e The IntercomCall shortcut shortcut n 11 Ed a allows you to view the previously described Intercom call section Method 2 Access the Voice functions section of the User Menu by means of a valid PIN Follow the instructions described in Method 1 Activations The activation deactivation of the SmartLiving system peripherals and elements described in the following section enables them to operate in accordance with
57. ll the manufacturer s guidelines relating to the active and passive security devices of this system It is the installer s responsibility to inform the system users that regardless of its capabilities an intrusion alarm system is not a substitute for the necessary precautions building occupants must take to prevent intrusion User s Manual 1 5 2 this manual DCMUINEOSLIVINGE MANUAL CODE 4 00 VERSION The installer should read carefully through the User s Manual supplied with each control panel Once the system has been installed the installer must ensure that the User s Manual is available to the users for consultation and that they fully understand how the system works and are aware of all the functions settings and procedures Operator Qualifications 1 6 Installer 1 6 1 The installer is the person or group of persons who sets up and programs the entire security system in accordance with the purchaser s requirements and in respect of the safety laws in force As the only individual in contact with system users it is the installer s responsibility to instruct them on how to use the security system properly Under normal circumstances the installer is not allowed to arm disarm the system without previous authorization from the user All the system partitions must be disarmed before accessing the parameter programming phase User 1 6 2 The users are the occupants of the building where this intrusion control panel is inst
58. ller in accordance with user requirements For example if all the occupants are leaving the building you can apply a scenario that arms all the partitions and activates the outputs which closes the rollerblinds and switches off the lights On returning to the building you can apply a scenario that disarms some of the partitions those required and activates an output which switches on the garden lights The installer will set up the and make available the scenarios which best suit user requirements The scenarios can be activated via keypad reader remote control and over the phone using shortcut commands refer to Chapter 3 Shortcuts or through a web server with a mobile phone interface by accessing the Scenario activation section paragraph 5 17 3 Mobile phone web interface 18 The SmartLiving System User s Manual SMARTLIVING SHORTCUTS Keypad shortcuts Each keypad can be programmed with up to 12 shortcuts associated with 4 function keys FL F2 4 F4 The shortcuts are identified by icons which appear on the lower part of the display Arrows to the right and left of the icons indicate that keys 9 and e will allow you to view and use other shortcuts if programmed The 12 keypad shortcuts can be activated in 4 different ways as follows 1 By ALL Press the respective key F1x to activate the shortcut instantly without code entry The shortcut will affect all the keypad parti tions By A
59. m in accordance with their programmed access level enabled functions etc by holding the key in front of the proximity key reader All SmartLiving control panels are capable of managing INIM s Air2 two way wireless system This system integrates wireless devices detectors keyfobs etc into the hardwired environment SmartLiving control panels are capable of managing various event types alarms faults tamper code key identification arm disarm operations etc and event response actions audible visual signaling telephone calls SMS text messages over the GSM network and with the addition of the optional SmartLan G board e mails with attachments The calls can be 1 report calls to alarm receiving centres via the most widely used reporting protocols 2 voice calls to contact numbers using advanced voice technology to inform contact persons of the active alarm condition Events can also be announced on JOY MAX keypads The SmartLiving intrusion control panel also provides automatic features such as e arm and disarm operations set up on a weekly basis e simple yet useful access control functions which allow the system to deny access to specific keys codes at certain times e pre set activation deactivation of household devices building automation such as courtesy lights e other similar automatic facilities 8 The SmartLiving System User s Manual unum SMAR ILIVING The technologies 2 2 Expertise in the are
60. m with the customized shortcut icons associated with the code as illustrated opposite 2 using keys Fim and 0 select the desired shortcut 3 You can access a descriptive menu of the customized shortcuts assigned to keys Ffm as opposite 3 To activate the shortcuts use key Or to scroll for the description of the required shortcut then press x All methods allow first access to the menu after a valid code entry followed by 0K At this point each time you press key 3 different objects will appear select the one that applies to the operation concerned and then continue Keys The SmartLiving system is capable of managing INIM s contact free digital keys which are available in three versions e nKey proximity keyfob e nCard proximity card e Air2 KF100 wireless keyfob Each key is unique and is identified by a random code selected from over 4 billion code combinations During the installation phase each key is enrolled on the system in order to allow it to operate Each key is characterized by the following parameters programmed by the installer in accordance with the requirements of the key user e Partitions User codes can control only the partitions they are assigned to If a key is used at a reader it can operate only on the partitions the two devices have in common For example if the key controls partitions 1 3 and 5 and the reader controls partitions 1 2 and 6 the key can o
61. med in Instant mode perimeter zones armed with no delay e partition does not belong to the keypad The displays of the SmartLiving 505 and 515 models show 5 characters indicating the status of partitions 1 to 5 both models have 5 partitions The displays of the SmartLiving 1050 and 1050L models show 10 characters indicating the status of partitions 1 to10 both models have 10 partitions The display of the SmartLiving 10100L model alternates at 3 second intervals between 10 characters indicating the status of partitions 1 to 10 and 5 characters indicating the status of partitions 11 to 15 the 10100L model has 15 partitions If a partition has memory of an alarm or tamper condition the character that represents the partition concerned will blink The right side of the second line shows several icons which provide visual information regarding the system 10 The SmartLiving System User s Manual SMARTLIVING Table 3 The icons shown on the second line of the display Name Notpresm Onsolid Blinkingorinterchanging icons Interchanging icon i At least one peripheral keypad _ All peripherals are properly reader expansion is in tamper All peripherals are properly placed and all Peripheral tamper placed and all enclosures i enclosure covers are closed however covers are closed status aala ed or device tamper has been detected and cleared us Tamper memory a e kai All the peripherals in the All the p
62. most cases also when it ends During the call the call recipient can e press to go to the next message or if there is only one message end the successful call e Type in a valid PIN followed by X and access the customized shortcuts assigned to the code The control panel will activate the voice guide which will announce the available shortcuts and the number keys to press The control panel will activate the corresponding shortcut as soon as the selected number is pressed on the telephone keypad Using the system 35 SMARTLIVING LI UU y User s Manual User to panel calls 5 16 2 If the Answerphone function refer to paragraph 5 4 Activations is enabled users can call the control panel from any remote telephone and send commands to the system refer to paragraph 3 2 Shortcut with code and or activate Listen in sessions refer to paragraph 5 14 Listen in in the following way 1 Dial the control panel telephone number 2 Allow the phone to ring for the pre established number of rings The control panel will answer and will play message n 216 3 Type in your PIN followed by 4 The control panel will activate the voice function which will announce the available shortcuts and the number keys to press 5 As soon as the selected number is pressed on the telephone keypad the control panel will activate the corresponding shortcut If the system is equipped with a Nexus dialer the user can operate on the control
63. n at a time Therefore if another user is already connected to the control panel access will be denied and the following message will be shown Too many connections Access will be denied in the following cases the entered PIN is not recognized the entered PIN does not belong to any partition the entered PIN is not enabled the entered PIN is associated with a timer and the timer concerned is OFF The Internet Access option from the Activations section in the User menu is disabled Using the system Download mail User granted http www inim biz E mail client a Modify View Go Message Tools Write Address book Reply Reply to all SmartLiving control panel Valid code smartl AN inim biz user inim biz user inim biz 01 01 2008 18 23 00 001 005 001 map pdf 5 17 2 Login Username Password Code Click on login to access CES Login gt Language 37 SMAR ILIVING User s Manual If the connection is successful the browser will show the first page of the web server The six icons listed below represent the six keys which allow the user to access the various sections Table 10 Web server sections The keypad which is shown is the exact replica of the system keypad Accessing de virtual yp p y yp use the virtual keypad in the same way as you would use the real one access functions etc The system will allow users to view only information relati
64. n rapid succession the available shortcuts Table 6 Reader LEDs with no key at reader OFF All the reader partitions are disarmed All LEDs Off No alarm tamper memory on the reader partitions or system tamper memory ON OFF The scenario associated with The scenario associated with The scenario associated with The scenario associated with the arming shortcut of the red the arming shortcut of the LED is active inactive blue LED is active inactive The output associated with the The output associated with the output activation shortcut of output activation shortcut of the red LED is active inactive the blue LED is active inactive Faults are present not present Faults are present not present the arming shortcut of the the arming shortcut of the green LED is active inactive yellow LED is active inactive The output associated with the The output associated with the output activation shortcut of output activation shortcut of the green LED is active the yellow LED is active inactive inactive Faults are present not present Faults are present not present Intermittent blinking At least one Reader partition is ON 2 3sec armed OFF O 1sec Slow blinking The reader partitions are ON 0 5sec disarmed OFF 0 5sec Alarm tamper memory on at The scenario associated with least one of the reader the last key used is active partitions or system tamper memory Fast blinking At least one Reader pa
65. na of total security and a commitment to precision and high quality allow INIM s R amp D professionals to deliver excellence in design technology and dependability through time EASY4U 2 2 1 This user friendly tool provides an interesting array of graphic features and functions All SmartLiving intrusion control panels are controlled by keypads equipped with 96x32 pixel graphic displays The four line alphanumeric display screen 16 characters per line can be edited or used to view the icons associated with various customized user operations The keypad shortcuts allow time consuming sequences to be transformed into simple keystroke actions In this way frequently used or repetitive sequences of keystrokes can be eliminated The shortcuts can be used for a variety of tasks and make operations less tedious and less error prone The use of customizable graphic objects which indicate the system status helps users to understand what is happening on the system Besides accepting various commands Away Arm Stay Arm Disarm etc the nBy reader also allows users to manage the shortcuts programmed on the keypad The JOY MAX keypad provides a built in nBy key reader VOIB 2 2 2 This is an acronym for Voice Over Inim Bus VOIB technology allows the system to manage end to end digitized voice transmissions at extremely high speed over the IBUS Voice transmissions can be carried to all points of the IBUS The JOY MAX keypad provides a b
66. ng to the partitions they control refer to paragraph 5 2 Arming and disarming partitions paragraph 5 1 Managing alarms and paragraph 5 5 View keypad Use Comer to select another type of keypad if required from the top right section At this point Using the mouse select the desired partition The system will show information regarding the zones belonging to the selected partition only and will allow you to inhibit unbypass the zones as required refer to paragraph 5 4 Activations and paragraph 5 5 View The lower section allows you to view the current status of the outputs and activate deactivate them as required refer to paragraph 5 5 View and paragraph 5 6 Activating Deactivating outputs Manage zones and outputs View timers This section allows you to view the status of the 10 control panel timers refer to paragraph 5 5 View View events log Press UpdateLog to initialize and update the control panel events log refer to paragraph 5 5 View Mobile phone web interface 5 17 3 The web server interface for mobile phone devices provides the same functions the user has access to when operating on the control panel from a remote computer To use this interface you must connect to the SmartLAN address via a mobile phone or similar device the connection will be diverted automatically to the respective page Otherwise you can connect manually by adding mobile to the end of the SmartLAN G address e g http 19
67. not generate alarms activate audible and visual signaling devices However any alarm events that occur will be saved to the events memory If zones are not operating properly the Test option will allow the installer to check them without the risk of generating false alarms A logical entity for automatic time management of programmed peripherals or elements SmartLiving control panels provide 10 timers Transceiver equipped devices In two way wireless systems all the devices are equipped with transceivers In one way wireless systems the main unit is equipped with a receiver module whereas the peripheral devices are equipped with transmitters Each code is programmed with e A4 5 or 6 digit PIN which allows access the system e A label which identifies the user usually the user s name e The group of partitions it controls arms disarms etc e Agroupof pre set parameters which allow the operator to work on the system in accordance with its authorized access level for example a code can be enabled to consult the events log but not to change the date and time List of functions available to the user after valid code entry at a keypad This device allows the control panel to send voice calls to programmed contact numbers In SmartLiving control panels the voice dialer function is provided by the SmartLogos30M board accessory item If the system is equipped with a SmartLogos30M voice board each JOY MAX keypad in the
68. ns Timers ee Shortcut n 27 A accesses Activations Auto arm Using the system 27 SMARTLIVING User s Manual Method 2 Access the Activations section of the User menu by means of a valid PIN Follow the instructions described in Method 1 Via Web Access the SmartLAN G web server refer to paragraph 5 17 2 Access the web server Press the NG button Use the mouse to select the partition and the zone in the top section then press the buttons shown opposite View This section allows you to view the events log and the current status of some of the system peripherals and elements The Events log Alarms log Faults log and Arm Disarm op allow you to view the start and end of the corresponding events in chronological order The Nexus status section shows on the display some of the parameters of the Nexus dialer The System voltage section allows you to view the respective voltage panel The Zone Status section shows the status of the zone Standby Alarm Shorted Tamper and Unbypassed Inhibited status Unbypassed capable of generating alarms Inhibited incapable of generating alarms The Faults section allows you to view current faults only refer to Appendix C Fault signals The Panel version section allows you to view the firmware version and model of your SmartLiving control panel When viewing the wireless zones the last line on the
69. o arm option for the partitions concerned Via Web Y Arm SS KO Ro DONI ANAN Access the SmartLAN G web server and press Gy button Use the mouse to n 7 select a partition then press the buttons shown opposite to activate the a Disarm selected partition operations Access the Scenario activation section through the mobile phone interface press NG Select the desired scenario from those available by clicking on the scenario label or icon 2 In response the system shows the icons opposite Fi Scenario activated correctly Scenario not activated Using the system 25 SMARTLIVING User s Manual Voice functions and Intercom JOY MAX only Voice communication during keypad to keypad intercom calls is one way therefore only one person should speak while the other listens The user who wishes to speak must press on the keypad in use The voice functions are e Record starts the recording phase of the memo in the memo box of the keypad you are working on e Playback starts the playback phase of the memo in the memo box of the keypad you are working on e Delete deletes the memo in the memo box of the keypad you are working on e Intercom allows two way voice communication with another JOY MAX keypad Via Keypad Method 1 Activate the shortcuts associated with keys Fim shown on the display with or without code entry e The shortcut assigned to the Voice functions menu shortcut n 14 E
70. omatic arming operation For example if a partition is set to arm automatically at 10 30 with a Pre arm time of 5 minutes all the partition keypads and readers will initiate an audible countdown at 10 25 in order to warn users of the forthcoming arming operation Each partition can be programmed with its own Pre arm time The installation site e the building or part protected by the intrusion control system generally a house or office Technical terminology and Glossary INSTALLER CODE INSTALLER MENU INTERIOR ZONE KEY KEYPAD JOY MAGNETIC CONTACT AIR2 MC100 OUTPUT PARTITION PARTITION ARM DISARM OPERATIONS PATROL PERIMETER ZONE PERIPHERALS PRE ARM TIME PREMISES 41 SMARTLIVING LI WU User s Manual Under normal circumstances the mains power supply 230Vac 50 Hz 110V a c 60Hz in some countries Usually connected to a switching power supply or transformer depending on the model that provides the stabilized voltage to the system and the charge source to the batteries This device allows users to access and control the system The system readers are connected to the control panel via the I BUS The key TAG allows the user to activate shortcuts refer to Shortcuts and arm disarm the partitions which are common to both the key TAG and reader in use The key TAG must be held in the vicinity of the reader in such a way to allow the system to read it and permit access to authorized
71. operations Although readers provide a more limited access to the system they are easiest way of carrying out day to day operations arm disarm etc A pre set arming configuration which applies various operating modes to the system partitions The shortcuts allow quick access to User Menu options which normally require several step by step operations The supervision time is the interval during which the wireless system devices in general wireless detectors in permanent placements must signal to the control panel that they are operating in the network If a wireless device fails to signal before the supervision time expires it will be classified as Lost and the control panel will trigger a peripheral loss fault event Detection of a serious condition that jeopardizes the operating capacity of the device concerned and thus puts the system at risk Tamper conditions are detected by tamper switches connected to the system zones keypads readers expansions and control panel Generally these events are triggered by system violation such as unauthorized opening of a keypad cover These are calls sent to programmed contact numbers when specific events start and end restoral This is a service provided by the installer company The installer company requires the user s collaboration and authorization before opening a teleservice session and working on the system via telephone line A zone with this attribute can
72. or building is usually configured as a delayed exit zone in order to give occupants time to leave the partition after an arming operation If the user does not leave the zone within the set Exit time the system will generate an alarm Technical terminology and Glossary ACCESS CODES ALARM ALARM OR TAMPER MEMORY ALARM RECEIVING CENTRE ARC ANSWERPHONE ARM DISARM AUTO ARM BACKUP BATTERY CALL QUEUE DELAYED ENTRY ZONE DELAYED EXIT ZONE 39 SMARTLIVING LI LL y User s Manual This is an explicit user command which ends signaling on the red keypad reader LEDs of the following events e Zone Alarm terminal tamper open panel or dislodged panel peripheral tamper keypads expansions readers peripheral loss keypads expansions readers e false key you delete the alarm tamper memory the visual signals on the red reader keypad LEDs will clear This device allows the control panel to send report calls to Alarm Receiving centres ARC SmartLiving control panels provide a built in digital dialer which supports all the most widely used protocols The time expressed in minutes or seconds that the system allows the user to disarm the PO after zone violation It the system is not disarmed within the set time it will generate an alarm Each partition can be programmed with its own Entry time An operative status recognized by the system For example detector alarm mains failure user code recognit
73. ot generate alarms Activation Deactivation of zones can be carried out manually by users or under certain circumstances automatically by the control panel DELETE ALARM TAMPER MEMORY DIGITAL DIALER ENTRY TIME OR ENTRY DELAY EVENT EVENTS LOG OR EVENTS MEMORY EXIT TIME OR EXIT DELAY EXPANSION BOARDS FLEX5 FAULT GSM DIALER I BUS INHIBITION DEACTIVATION OF A ZONE 40 Technical terminology and Glossary User s Manual unum SMARTLIVING The Installer code is identified by a 4 5 or 6 digit PIN This PIN allows the installer to access the system Programming Menu either from a keypad or via the respective software application on condition that all the system partitions are disarmed List of system functions and respective parameters accessed via keypad This menu allows the installer to program check and change nearly all of the system parameters The Installer Menu can be accessed from any keypad or via computer with the SmartLeague software on condition that all the system partitions are disarmed A zone that monitors the inside of the protected building For example the interior zones of an office building are the zones that monitor offices and entrance points If a partition that a zone belongs to is armed in Stay mode it will be unable to generate alarms A control device card or keyfob which allows the authorized user to access the system The key must be held in the vicinity of the reader
74. panel via voice call to the SIM card of the Nexus If duly configured by the installer the user will receive feedback SMS text message or ring from the Nexus relating to successfully implemented commands SMS text message to the user 5 16 3 If the system is equipped with a duly programmed Nexus dialer the user may receive SMS text messages signaling that events have occurred If an event which has been duly configured by the installer occurs or restores the control panel will send notification to the programmed users via SMS SMS text message to the 5 16 4 control panel If the system is equipped with a duly programmed Nexus dialer the user can operate on the control panel by sending SMS text commands to SIM card of the Nexus Users who wish to activate a command via SMS text must enter the command details as follows XXXXXX SMS Text where e XXXXXX stands for the user s PIN e a blank space must be keyed in after PIN entry e SMS Text which is the command identifier this parameter must be provided by your installer If duly configured by the installer the user will receive feedback SMS text message or ring from the Nexus relating to successfully implemented commands The SmartLiving control panel is programmed with five predefined default SMS TEXT AT DEFAULT commands e Balance enquiry relating to the SIM card of the Nexus If the following SMS text message is sent XXXXXX CREDIT BALANCE w
75. perate on partition 1 only as it is the only partition the key and reader have in common If a keyfob button is pressed the user will be allowed access only to the partitions the wireless keyfob is assigned to e Up to 4 Shortcuts e A Timer can be set up to restrict the use of a key The system will allow the key to operate the system only when the Timer is active In this way the user will be unable to access the system at all other times e Patrol attribute This option is usually enabled on keys used by security personnel or night watchmen who must patrol the protected premises at regular intervals This type of key does not allow the user to select the Arm Type When a key with this attribute is recognized the system will perform the following operations 16 2 5 1 O e eec The SmartLiving System User s Manual unum SMARTLIVING 1 Disarm the partitions common to the key and reader concerned 2 Activate the respective Patrol Time for the partitions concerned 3 Re arm the partitions as before when the Patrol Time expires If the patrol key is held in the vicinity of the reader while the Patrol Time is still running for example if the inspection ends ahead of time the Patrol Time will end immediately and the partitions will arm as before e Maintenance option On acceptance of a key with this attribute the system will deactivate any outputs associated with Zone alarm tamper and Partition alarm tamp
76. pes e Installer code used by the installer company technician e User code assigned to the building occupants Detection of non authorized entry into the protected building More specifically activation of alarm signaling devices detectors In the event of Zone Alarm terminal tamper open panel or dislodged panel peripheral tamper keypads expansions readers peripheral loss keypads expansions readers e false key The red LEDs on the system keypads and readers go On each time one of the previously mentioned events occur This visual warning signal is held even after the event ends alarm memory in order to warn you that an event occurred during your absence This visual warning signal will be held until you clear the event memory refer to Delete Memory This is a private company that monitors premises protected by intrusion control systems equipped with Digital or Voice dialers refer to Digital dialer and Voice dialer Alarm Receiving Centres receive alarm reports from monitored systems and take all the necessary actions to protect the occupants of the protected premises The Answerphone function if enabled by the user allows the control panel to answer incoming calls after a pre set number of rings The control panel will pick up and play the recorded answer message During the call the recipient can type in a valid PIN enabled for over the phone control and access the authorized functions User operations
77. rdance with the requirements of each specific system The keys and codes provide the systems with random codes for keys or PINS for codes which the system associates with the respective attributes and functions programmed by the installer For example a user key code may be enabled on partitions 1 and 2 on system A on partitions 7 8 and 9 on system B and on partitions 4 and 5 on system C This operating method is possible for all keys and codes The SmartLiving System 17 SMARTLIVING LI LL User s Manual Telephone functions 2 8 The SmartLiving control panel events can be programmed to trigger report calls to an Alarm receiving Centre via digital dialer and also voice calls and SMS messages to contact numbers The SmartLiving control panel also accepts commands over the phone Shortcut commands can be sent during calls to from the control panel after valid PIN entry on the telephone keypad The commands can be activated by keys 0 to 9 on the telephone keypad which the system associates with various shortcut actions Each code can be programmed with customized shortcuts such as arm disarm activate deactivate outputs delete alarm memory etc If the system is equipped with a SmartLogos30M voice board the code shortcuts assigned to keys O to 9 will be announced over the phone in order to facilitate operations Additionally the Listen in function allows you to eavesdrop on the protected premises b
78. rtition is ON 0 15sec armed OFF 0 15sec Alarm tamper memory on at least one of the reader in accordance with the associated shortcut partitions or system tamper memory 14 The SmartLiving System User s Manual SMARTLIVING Table 7 Reader LEDs with key at reader um Ret Be Gm Yellow aka light Request to arm ALL the partitions common to both the key and reader ON Request to activate the Request to activate the Request to activate the Request to activate the only one LED shortcut associated with the shortcut associated with the shortcut associated with the shortcut associated with the On red LED on the reader or the blue LED on the reader or the green LED on the reader or yellow LED on the reader or first shortcut of the key second shortcut of the key the third shortcut of the key the fourth shortcut of the key ON All Paba abaka Request to activate the shortcut associated with the key On Fast blinking If the shortcut associated with If the shortcut associated with If the shortcut associated with If the shortcut associated with ON 0 15sec the red LED is an arming the blue LED is an arming the green LED is an arming the yellow LED is an arming OFF 0 15sec operation one of the operation one of the operation one of the operation one of the one LED only partitions concerned is not partitions concerned is not partitions concerned is not partitions concerned is not ready to arm
79. sponding shortcut from a JOYMAX keypad The control panel will announce the armed disarmed status of the partitions the entered PIN is assigned to If you activate this shortcut from a JOY MAX keypad the control panel will announce the Note armed disarmed status of the partitions the entered PIN is assigned to regardless of the keypad partitions The user code must be enabled by the installer to activate shortcut n 17 via keys Ffm or the number keys Over the phone Type in the PIN of a user code followed by then press the key from O to 9 which the installer has programmed to activate Arming status shortcut n 17 The control panel will announce in order the descriptions of the partitions the entered PIN is assigned to and their current armed disarmed status Press X4 to step back to the main menu to listen to all the voice announcements relating to the entered PIN Via Keypad After entering a valid user code PIN press the key which is assigned to the Arming status shortcut shortcut n 17 The control panel will announce in order the descriptions of the partitions the entered PIN is assigned to and their current armed disarmed status Commands over the phone 5 16 Panel to user calls 5 16 1 Your installer will instruct you as to which events generate voice calls Event report calls will be sent to the programmed contact numbers of your choice when the event occurs and in
80. t by the installer The first part of the e mail shows the date and time of the event when saved to the events log and any relative details E Subject From To 01 01 2009 18 23 00 Valid code CODE 001 KEYP 005 Message PARTITION 001 text Valid code CODE KEYPAD PART Access with valid code entry saved to log http www inim biz Access the web server The security of the connection with the computer is guaranteed by integrated cryptography The security of the connection of mobile phone devices is guaranteed by the SSL protocol used for HTTPS connections Following is a description of the method of access to the interface which allows remote management of the control panel Optional text Link to an internet website or IP address if applicable Document file sent with the e mail a Attach 1 Type in the IP address on the navigation bar of the browser If you wish to use HTTPS protocol simply add the letter s to the http prefix for example http 192 168 1 92 would become https 192 168 1 92 2 The control panel will open a page similar to the one opposite type in System user System password supplied by your installer and your user code PIN If you type the installer code this will be accepted only if the Teleservice is enabled paragraph 5 4 Activations 3 Press to start the connection Please note that the SmartLAN G board is capable of managing one connectio
81. ters K03 indicate the address assigned to the keypad in the example the keypad is at address 3 If you are using a Joy MAX keypad the string will also show PO5 which is the address assigned to the built in proximity reader in the exam ple the reader is at address 5 B If any of the keypad partitions has Alarm or Tamper memory the first line of the screen will flash the descriptions of the zones concerned every 3 sec onds In the event of Alarm or Tamper memory the red LED on the key pad and the characters corresponding to the partitions concerned will blink C If the control panel is in Maintenance status and any of the keypad parti tions has memory of an Alarm or Tamper condition the first line on the screen will show the strings described in points A and B D If the View open zones of disarmed partitions option is enabled the first line on the screen will flash approximately every 3 seconds the descrip tions of any zones which are not in standby status when the keypad parti tions disarm Any auto bypassable zones will be shown in white on black background Case D is discernible from case B in the fact that in case B the red LED on the keypad blinks Case D is viewable only when the conditions of cases A B and C are not present The SmartLiving System 11 SMARTLIVING User s Manual Using the keypad 2 3 3 The following section describes how the keys are normally used Some of the keys may have specific
82. their settings activation or disables their functions completely deactivation The user has full control over activation deactivation of the SmartLiving system peripherals and elements The following section describes the consequences of activation deactivation e Zone disabled zones cannot generate alarms inhibited e Auto arm operations can be activated deactivated separately on each single partition If this option is enabled on a partition it will arm and disarm in accordance with the On Off settings of the respective timer 26 e e sanas a Method 1 i Method 2 pececeoaga v Method 2 Caller keypad KEYP 001 1 Recipient keypad KEYP 002 1 Using the system e e e e User s Manual num SMARTLIVING e Codes deactivated disabled codes cannot access the system e Keys deactivated disabled keys cannot access the system e Keypads deactivated disabled keypads cannot provide access to the system therefore cannot generate commands or shortcuts However the LEDs and display will be refreshed e Readers deactivated disabled readers cannot provide access to the system therefore cannot accept keys or generate commands However the LEDs will indicate the current status of the system e Timers activated timers On manage their associated elements partitions codes keys in accordance with their settings Deactivated timers cannot time manage their associated elements p
83. trol only the partitions they are assigned to If a 1 2 asc 3 a user code is entered at a keypad the user can control only the partitions which are common to both the code and keypad concerned For example if a code enabled on partitions 1 2 3 4 and 5 is entered at a keypad which enabled on partitions 4 5 6 and 7 it will be able to operate on partitions 4 and 5 only e User Code Type Rank There are two user code types ranks Main User and User Main User codes can disable ordinary User codes and change o their PINs However a Main User code cannot be used to disable another Main User code or change its PIN User codes can change their own PINs only e User Menu Access mode Each User code can access its customized menu in 3 different ways refer to paragraph 2 5 1 Accessing the User Menu e Commands over the phone This option enables access to the system via remote telephone If this option is enabled the User can send commands to the control panel over the phone Commands can be sent during calls to from the control panel After a valid PIN entry on the telephone keypad the user can o activate specific shortcuts refer to Chapter 3 Shortcuts This method of entering commands will affect the code partitions only e Timer Restriction If a code is associated with one of the timers it will be i able to operate the system only when the Timer is On 6 e e Group of outputs which can b
84. uilt in microphone and speaker for message recording and playback The 30 minute capacity voice board allows each event to be associated with a message Voice digitizing and compression allow the signal to be transmitted in data packets over the bus to recipient keypads where it is announced Voice digitizing and the characteristics of the I BUS allow end to end noise immune voice transmissions without the need of any additional wiring Keypads 2 3 The keypad allow users to manage all aspects of the security system SmartLiving control panels support JOY GR JOY MAX nCode G and Concept G keypads The features of these keypads are described in the following table Table 2 Keypads functions ova ov ncode e concent Graphicdisplay display su _ AG in pr o ud ss Signaling LEDs SignaingLEDs O mam 3 Meehme X M yo PU toudopeaker Xs HM Bumin proximity reader w o PU Temperature sensor Re o sensor Block keypad o Se ve The various keypad models provide diverse functions casings and key access Joy keypads have a flip which protects the keys whereas the keys of the nCode G and Concept G keypads are on view The Concept G is a touch keypad The keypad is the device that allows authorized code users to control the entire system or specific partitions However system control can be extended to other building occupants who do not hold a valid code
85. y means of the keypad microphones When a user requests an operation via a correctly formatted SMS message or voice call to the SIM card of the Nexus the control panel will activate the respective shortcut event and send confirmation feedback of the successfully implemented command WEB e mail functions All SmartLAN G equipped SmartLiving control panels are capable of sending event associated e mails SmartLAN G is an optional accessory board The e mail text subject attachments and recipients must be edited by your installer No changes whatsoever should be made to the e mail structure Each e mail text is capable of containing a direct link to a website or to an IP addressable device such as an IP camera and an attachment document file For a description of a typical e mail format refer to paragraph 5 17 1 e mail In addition to e mails the SmartLAN G board allows you to interface with the control panel from any computer or mobile phone device PDA mobile phone etc via any internet browser The SmartLAN G board integrates a web server which allows users to operate the control panel from remote locations without the need of authentication For further details regarding the web server refer to paragraph 5 17 2 Access the web server Arming scenarios 2 10 A scenario is a pre set arming configuration which applies various operating modes to the SmartLiving system partitions the scenarios are programmed by the insta
86. ype in a valid code PIN followed by Press the number key from 0 to 9 associated with the Arm Disarm shortcut shortcut n 1 in order to apply the pre set scenario Method 1 Via Command Zone Under normal circumstances a command zone comprises a mechanical key lock or callpoint which activates an electrical contact wired to the command zone In accordance with how the command zone is configured it is possible to e arm the partitions the zone belongs to e disarm the partitions the zone belongs to e Switch the status of the partitions arm any disarmed partitions and disarm any armed partitions refer to Switch Zone in Appendix A Technical terminology and Glossary e arm the partitions the zone belongs to when the command zone is violated and disarm the partitions the zone belongs to when it restores to standby Via Wireless keyfob Push the respective button on the keyfob and verify the outcome of the requested operation as described in paragraph 2 6 1 Air2 KF100 Wireless keyfobs Via Auto arm operations v If a partition is associated with a timer which controls automatic arming oe Arm selected partition in Away operations it will arm when the timer switches ON and disarm when the timer mode switches OFF Users who are enabled to control Auto arm operations refer to paragraph 5 4 Activations must ET Arm selected partition in Stay e activate the timer associated with the Auto arm operations mode e enable the Aut
87. zones are in standby status thus execution of the command would generate an instant alarm the keypad will provide a list of the zones concerned as shown in the figure opposite Use keys and to scroll the list and view the zones which are not in standby status If you wish to go ahead with the operation despite the consequences press x In this case you will trigger an instant alarm on the zones indicated on the display If you enter an arm partition s command at a keypad and conditions programmed by the installer which lower the security of the system are present the keypad will provide a list of the conditions concerned as shown in the figure opposite Use keys and to scroll the list and view the conditions which lower the security of the system If you wish to go ahead with the operation despite the consequences press x Arming the system under such circumstances will generate a Forced arming on partition event This event highlights the fact that partitions were armed when conditions which lowered the security of the system were present for example Low battery or Mains failure If however the installer included the LossTamp ongoing event in the list of conditions which lower security and this condition is active you can cancel the operation by pressing OK 24 F1 m F2 5 F3 Fa Alarm stopped Call queue 9 cleared Xy Memory deleted Method 2 dl

Download Pdf Manuals

image

Related Search

Related Contents

Samsung GT-C3750 Benutzerhandbuch  SMART SERIES Viscosimètre Rotatif  Samsung Samsung Champ 2 Lietotāja rokasgrāmata  Broyeur à glace/ IceCrusher  User Manual for iOS App  Samsung Samsung ATIV S Manual de Usuario(open)  Information Guide  Remote Wireless  Manuel de vol Robin DR400-160  Testability Considerotions in Microprocessor  

Copyright © All rights reserved.
Failed to retrieve file