C-more Hardware User Manual
Contents
1. PLC generated error codes for the Omron FINS protocol continued on the next page A 34 Cmor D EA USER M Hardware User Manual 2nd Ed Rev G 08 14 Appendix A Panel amp PLC Error Code Tables Omron FINS Protocol PLC Error Code Table cont d PLC Error Codes for Omron FINS D Panel Error Code PLC 499 Hex Value Description 0x1104 Parameter Error Address range exceeded 0x1106 Parameter Error Program Missing 0x1109 Parameter Error Relational Error 0x110A Parameter Error Duplicate Data Access 0x110B Parameter Error Response too long 0x110C Parameter Error Parameter Error 0x2002 Read Not Possible Protected 0x2003 Read Not Possible Table missing 0x2004 Read Not Possible Data missing 0x2005 Read Not Possible Program missing 0x2006 Read Not Possible File missing 0x2007 Read Not Possible Data mismatch 0x2101 Write Not Possible Read Only 0x2102 Write Not Possible Protected cannot write data link table 0x2103 Write Not Possible Cannot register 0x2105 Write Not Possible Program missing 0x2106 Write Not Possible File missing 0x2107 Write Not Possible File name already exists 0x2108 Write Not Possible Cannot change 0x2201 Not executable in current mode Not possible during execution 0x2202 Not executable in current mode Not possible while running 0x2203 Not executable in current mode Wrong PLC mode Program 0x2204 Not executable in current mode Wrong PLC mode
2. Ox2FOC Buffer message timeout An expected Text Buffer or Connection Data message was not received within the configured T5 time interval Serial output timeout The CMM module was unable to transmit a Break an SNP message or SNP 0x300C acknowledge ACK or NAK from the serial port May be due to missing CTS signal when the CMM module is configured to use hardware flow control 0x310C SNP slave did not receive a response from the Service Request Processor in the PLC CPU 0x320C COMMREQ timeout Se e The COMMREQ did not complete within the configured time interval 0x330C An SNP Request or Response was aborted prior to completion due to reception of a Break 0x340C PLC backplane communications error Invalid Piggyback Status data memory type or address 0x350C Communications have not been established 0x360C Invalid SNP Slave SNP ID Must be a 0 7 ASCII characters plus a terminating null character 00h The Null SNP ID eight bytes of 00h may be used to specify any single slave device The SNP master has received a response message containing an unexpected data length Usually indicates 0x370C a problem with the remote SNP slave device May occur when Series 90 70 commands Task Memory or Program Block Memory Read Write are issued to a Series 90 30 slave device 0x380C Response code in received SNP X response message does not match expected value Response code must equal the request code 80h 0x390C SNP X Response message exce
3. Invalid command sent to PLC There an invalid command sent to the PLC that wasn t recognized by the PLC PLC 013 ENQ received from PLC If the data packet does not include a negative acknowledgement NAK 0x15 value in the defined packet field then an enquiry ENQ control code error will be displayed PLC 014 Transaction ID does not match This error will be displayed if after checking the Transaction ID Bytes in the data packet there is no match to what was requested PLC 015 Device No device found A PLC device designated as Device could not be found PLC 016 Data byte communication error 0 byte of data is recieved PLC 017 Out of address range The touch panel requested a file number larger than 255 PLC 018 Panel communication timeout The server panel did not respond when using the Panel Pass Through PLC 019 Found in parity error by hardware An error detected in the PLC memory PLC 020 Can t open serial port Cannot open the Serial Port If this error shows on the panel it indicates a hardware problem PLC 021 PLC number does not match The PLC number does not match the PLC number configured PLC 022 Cant reset DCB Unable to reset the data communication bit PLC 023 Cable not connected properly Communication cable incorrectly installed C more Touch Panel Error Code Table continued on the next page Cmor D EA
4. PLC 705 Protocol does not match The protocol for the device does Not match between the server and client when using the panel pass through A 4 C mm D EA USER M Hardware User Manual 2nd Ed Rev G 08 14 Appendix A Panel amp PLC Error Code Tables DirectLOGIC Panel Error Code PLC 499 Explanation The PLC 499 error code is used to show any errors that are generated by the connected PLC D The PLC 499 error message includes a four digit hexadecimal value embedded in the message This value can be looked up in the specific PLC s error tables to determine the cause of the error The possible PLC generated error codes for the DirectLOGIC communication protocol are represented by a hexadecimal value as shown in the following message example DirectLOGIC Error Code PLC 499 Message Example i Error code 0003 retumed from PLC DirectLOGIC K Sequence Protocol PLC Error Code Table The following table lists the errors that can be generated by the DirectLOGIC PLC when using the K Sequence protocol PLC Error Codes for DirectLOGIC K Sequence Panel Error Code ee PLC 499 Hex Value Description 01F8 Error setting value 020D Error in key mode 021C Password protected panel and displayed on the touch panel s screen as a hexadecimal value in panel error code PLC 499 message if active Please refer to the PLC manufacturer s documentation for additional information DirectLOGIC DirectNET Proto
5. 0x010315 Connection Manager invalid segment type or segment value in path 0x010316 Connection Manager Path and Connection not equal in close 0x010317 Connection Manager Ether Segment not present or Encoded Value in Network Segment is invalid 0x010318 Connection Manager Link address to self invalid 0x010319 Connection Manager Resources on Secondary unavailable 0x01031a Connection Manager Connection already established 0x01031b Connection Manager Direct connection already established 0x01031c Connection Manager Miscellaneous 0x01031d Connection Manager Redundant connection mismatch 0x01031e Connection Manager No more consumer resources available in the producing module 0x01031f Connection Manager No connection resources exist for target path a Connection Manager Vendor specific 0x020000 Resource unavailable Connection Manager resources are unavailable to handle service request 0x030000 Invalid parameter value 0x040000 Path segment error The path segment identifier or the segment syntax was not understood by the processing node 0x050000 Path destination unknown The path is referencing an object class instance or structure element that is not known or is not contained in the processing node 0x060000 Partial transfer Only part of the expected data was transferred 0x070000 Connection lost The messaging connection was l
6. PANEL amp PLC PENDIX ERROR CODE TABLES In This Appendix Introduction 2 0002 ae an an ww ed A 2 C more Touch Panel Error Code Table A 3 DirectLOGIC Panel Error Code PLC 499 Explanation 06 A 5 DirectLOGIC K Sequence Protocol PLC Error Code Table A 5 DirectLOGIC DirectNET Protocol PLC Error Codes 22 22er rennen A 5 Modbus Protocols Error Code P499 Explanation A 6 AutomationDirect CLICK AEN esa e essa cede eee dence ee oe etm ew A 6 AutomationDirect DirectLOGIC Modbus Koyo A 6 Modicon Modbus RGU sss deeded de dee a ew ed Ran Rane eines A 6 Entivity Modbus RTU i ctedesedeccdeee errr Errr r EA ddd aaa A 6 DirectLOGIC ECOM Protocol PLC Error Codes 00 e cece eee eens A 6 Productivity3000 Error Code PA A 7 Allen Bradley Panel Error Code PLC 499 Explanation 0 A 8 Allen Bradley DEI amp DH485 Protocols PLC Error Code Tables A 9 Allen Bradley EtherNet IP Protocol Panel Error Code PLC 496 497 and 498 Explanation ue Seet EE len aaa a aaa arenas aaa a A 11 Allen Bradley EtherNet IP Protocol PLC Error Code TablesControlLogix CompactLogix amp FlexLogix A 12 Allen Bradley EtherNet IP Protocol PLC Error Code TablesMicroLogix 1100 1400 amp SLC 5 05 both via native Ethernet port MicroLogix 1000 1100 1200 1400 1500 SLC 5 03 04 05 all via ENI Adapter A 16 Generic EtherNet IP Proto
7. Debug 0x2205 Not executable in current mode Wrong PLC mode Monitor 0x2206 Not executable in current mode Wrong PLC mode Run 0x2207 Not executable in current mode Specified node not polling node 0x2208 Not executable in current mode Step cannot be executed 0x2301 No such device File device missing 0x2302 No such device Missing memory 0x2303 No such device Clock missing 0x2401 Cannot Start Stop Table missing 0x2502 Unit Error Memory Error 0x2503 Unit Error UO setting Error 0x2504 Unit Error Too many 1 0 points 0x2505 Unit Error CPU bus error 0x2506 Unit Error 1 0 Duplication PLC generated error codes for the Omron FINS protocol continued on the next page Cmor D EA USER M Hardware User Manual 2nd Ed Rev G 08 14 A 35 Appendix A Panel amp PLC Error Code Tables Omron FINS Protocol PLC Error Code Table cont d D PLC Error Codes for Omron FINS Panel Error Code SE PLC 499 Hex Value Description 0x2507 Unit Error 1 0 bus error 0x2509 Unit Error SYSMAC BUS 2 error 0x250A Unit Error CPU Bus Unit Error 0x250D Unit Error SYSMAC BUS No duplication 0x250F Unit Error Memory Error 0x2510 Unit Error SYSMAC BUS terminator missing 0x2601 Command Error No protection 0x2602 Command Error Incorrect password 0x2604 Command Error Protected 0x2605 Command Error Servi
8. 0xE0 not used OxFO Error code in the EXT STS byte See the error code table on the next page PLC generated error codes for the Allen Bradley DF1 protocol continued on the next page Cmor D EA USER M Hardware User Manual 2nd Ed Rev G 08 14 A 9 Appendix A Panel amp PLC Error Code Tables Allen Bradley DF1 amp DH485 Protocols PLC Error Code Tables D PLC Errors for Allen Bradley DF1 and DH485 Protocols EXT STS Command Code for FO Command Panel Error nti Drake SE 0x0 not used 0x1 A field has an illegal value 0x2 Fewer levels specified in address than minimum for any address 0x3 More levels specified in address than system supports 0x4 Symbol not found 0x5 Symbol is of improper format Address does not point to something usable File is wrong size Cannot complete request situation has changed since start of the command Data or file size is too large Transaction size plus word address is too large Access denied improper privilege Condition cannot be generated resource is not available Condition already exists resource is readily available Command cannot be executed Histogram overflow No access Illegal data type Invalid parameter or invalid data Address reference exists to deleted area Command execution failure for unknown reason possible PLC 3 histogram overflow Data conversion error Scanner not able to commun
9. A negative acknowledgement NAK control code has been generated during a read write request PLC 003 EOT received from PLC An End of Transmission EOT control code is sent by the PLC in response to a Read Write SetBit request PLC 004 STX is not found A Start of Text STX control code was not found in the data packet received from the PLC PLC 005 ETX or ETB is not found Neither an End of Text ETX nor an End of Transmission Block ETB control code was found in the data packet received from the PLC PLC 006 LRC does not match There was an incorrect Longitudinal Redundancy Check RC contiol code in the communications packet received from the PLC This is an indication that the data in the packet is corrupted PLC 007 CRC does not match There was an incorrect Cyclic Redundancy Check CRC control code in the communications packet received from the PLC This is an indication that the data in the packet is corrupted PLC 008 Address does not match The address value returned in the data packet from the PLC is incorrect PLC 009 Different function code received from PLC The function code returned in the data packet from the PLC is incorrect PLC 010 Data size does not match There are an incorrect number of bytes found in the data packet returned from the PLC PLC 011 Invalid value in function code There is an invalid value in the function code PLC 012
10. GE 90 30 SNPX protocol continued on the next page A 28 Cmor D EA USER M Hardware User Manual 2nd Ed Rev G 08 14 Appendix A Panel amp PLC Error Code Tables GE 90 30 SNPX Protocol PLC Error Code Tables cont d PLC Errors for GE 90 30 SNPX Protocol Minor Major cont d D Panel Error Code PLC 499 Hex Value Description An invalid message type was received when an X Attach Response was required when re establishing an 0x530C existing SNP X communication session Communications have not been established 0x530F An invalid Message Type was received when an X Attach message was required For an X Attach message the message type must be 58h T An invalid Next Message Type value was detected in an X Attach Response message when re establishing 0x540C an existing SNP X communication session Communications have not been established 0x540F An invalid Next Message Type value was detected in a received X Attach message For an X Attach message the Next Message Length must be zero An invalid response code was detected in an X Attach Response message when re establishing an existing 0x550C SNP X communication session Communications have not been established 0x550F An invalid request code was detected in a received X Attach message An expected X Attach Response message was not received within the response timeout interval when re 0x560C establishing an existing SNP X communication session The master has retrie
11. Omron Error Code PLC 499 Message Example Error code 0011 returned from PLC A 32 C mor D EA USER M Hardware User Manual 2nd Ed Rev G 08 14 Appendix A Panel amp PLC Error Code Tables Omron Host Link Protocol PLC Error Code Table The following table lists the errors that can be generated by the Omron PLC when using the D Host Link protocol panel and displayed on the touch panel s screen as a hexadecimal value in panel error code PLC 499 E Note The following errors can be generated from the designated PLC are monitored by the C more touch message if active Please refer to the PLC manufacturer s documentation for additional information PLC Error Codes for Omron Host Link Panel Error Code i PLC 499 Hex Value Description 0x0000 Normal Completion 0x0001 Not executable in RUN mode 0x0002 Not executable in MONITOR mode 0x0003 Not executable with PROM mounted 0x0004 Address over data overflow 0x000B Not executable in PROGRAM mode 0x000C Not executable in DEBUG mode 0x000D Not executable in LOCAL mode 0x0010 Parity error 0x0011 Framing error 0x0012 Overrun 0x0013 FCS error 0x0014 Format error parameter length error 0x0015 Entry number data error parameter error data code error data length error 0x0016 Instruction not found 0x0018 Frame length error 0x0019 Not executable due to Un executable error clear non registration of 1 0 table etc 0x0020 1 0 table gener
12. USER M Hardware User Manual 2nd Ed Rev G 08 14 A 3 Appendix A Panel amp PLC Error Code Tables Error Code C more Touch Panel Error Code Table cont d C more Touch Panel Error Code Table cont d Error Message Cause PLC 024 Cannot detect other devices on network The panel is not communicating with other devices on the network PLC 025 Panel not in polling list PLC 026 PLC connection timeout A timeout occured after sending a request to the PLC PLC 027 Memory type incorrect PLC 028 PLC failed to respond The PLC failed to respond after sending a request to the PLC PLC 495 Omron Ethernet Error An error code specific to Omron Ethernet with a Value of XXXX has been returned from the PLC See the explanation for error code PLC 495 proceeding the Omron CS CJ FINS Ethernet error code tables PLC 496 Error code Oxaaaaaaaa returned from PLC Allen Bradley EtherNET IP specific Encapsulation Error See the explanation for error code PLC 496 proceeding the Allen Bradley EtherNet IP error code tables PLC 497 Error code Oxaaaaaaaa returned from PLC Allen Bradley EtherNET IP specific CIP Error See the explanation for error code PLC 497 proceeding the Allen Bradley EtherNet IP error code tables PLC 498 Error code Oxaaaaaaaa returned from PLC Allen Bradley EtherNET IP specific Service Packet Error See the explanation for error code PLC 498 proceedi
13. amp FlexLogix cont d PLC Errors for Allen Bradley EtherNet IP Protocol CIP Errors Error code Oxaaaaaaaa returned from the PLC Panel Error Code a PLC 497 Hex Value Description 0x230000 Reserved by CIP for future extensions 0x240000 Reserved by CIP for future extensions 0x250000 Key failure in path The key segment was included as the first segment in the path does not match the destination module The object specific status shall indicate which part of the key check failed 0x260000 Path Size Invalid The size of the path which was sent with the Service Request is either not large enough to allow the Request to be routed to an object or too much routing data was included 0x270000 Unexpected attribute in list An attempt was made to set an attribute that is not able to be set at this time 0x280000 Invalid Member ID The Member ID specified in the request does not exist in the specified Class Instance Attribute 0x290000 Member not settable A request to modify a non modifiable member was received Group 2 only server general failure This error code may only be reported by DeviceNet group 2 only 0x2a0000 servers with 4K or less code space and only in place of Service not supported Attribute not supported and Attribute not settable 0x2b0000 Oxcf0000 Reserved by CIP for future extensions 0xd00000 Reserved for Object Class and service errors This range of error codes is to be used to indi
14. error This is the error received when station set in the command does not match the station of the Ethernet module 1100 Parameter error UDP socket number bad 1101 Parameter error Address requested does not exist in PLC 1103 Parameter error Address area requested in not accessible 220F Status error Duplicate Socket error 2210 Status error Specified socket not open 2305 Environment Error IP address conversion failed Only encountered when using routing tables 2307 Environment Error IP address conversion set for automatic 2503 Unit error 1 0 setting error 2505 Unit error CPU bus error 250A Unit error CPU Bus Unit error A 38 Chor D EA USER M Hardware User Manual 2nd Ed Rev G 08 14 Appendix A Panel amp PLC Error Code Tables Siemens Panel Error Code P499 Explanation The PLC 499 error code is used to show any errors that are generated by the connected PLC D The PLC 499 error message includes a four digit hexadecimal value displayed at the end of the message This value can be looked up in the specific PLC s error tables to determine the cause of the error The possible PLC generated error codes for the Siemens PPI communication protocols breakdown into a four digit hexadecimal value as shown in the following message example Siemens Error Code PLC 499 Message Example 0 code 0x8702 returned from PLC C m
15. in a list of attributes that was needed by the service to perform the requested behavior 0x1d0000 Invalid attribute value list The service is returning the list of attributes supplied with status information for those attributes that were invalid 0x1e0000 Embedded service error See Service Packet error list PLC 498 Error codes below 0x110000 Vendor specific error A vendor specific error has been encountered This occurs when none of the specified errors relate to the error in the device 0x200000 Invalid parameter A parameter associated with the request was invalid This code is used when a parameter does meet the requirements defined in an Application Object specification 0x210000 Write once value or medium already written An attempt was made to write to a write once medium that has already been written or to modify a value that cannot be change once established Invalid Reply Received An invalid reply is received example service code sent doesn t match service code 0x220000 received PLC generated error codes for the Allen Bradley EtherNet IP protocol for ControlLogix CompactLogix and FlexLogix continued on the next page A 14 C mm E EA USER M Hardware User Manual 2nd Ed Rev G 08 14 Appendix A Panel amp PLC Error Code Tables Allen Bradley EtherNet IP Protocol PLC Error Code Tables ControlLogix CompactLogix
16. non modifiable member was received Group 2 only server general failure This error code may only be reported by DeviceNet group 2 only 0x2a0000 servers with 4K or less code space and only in place of Service not supported Attribute not supported and Attribute not settable 0x2b0000 0xcf0000 Reserved by CIP for future extensions 0xd00000 Reserved for Object Class and service errors This range of error codes is to be used to indicate Object Oxff0000 Class specific errors Use of this range should only be used when errors in this table don t accurately reflect the error encountered PLC generated error codes for the Allen Bradley EtherNet IP protocol for MicroLogix 1100 SLC 5 05 or ENI Adapter continued on the next page Cor D EA USER M Hardware User Manual 2nd Ed Rev G 08 14 A 19 Appendix A Panel amp PLC Error Code Tables Allen Bradley EtherNet IP Protocol PLC Error Code Tables MicroLogix 1100 1400 amp SLC 5 05 both via native Ethemet port MicroLogix 1000 1100 1200 14400 1500 SLC 5 03 04 05 all via ENI Adapter PLC Errors for Allen Bradley EtherNet IP Protocol Service Packet Errors Error code Oxaabbbb returned from the PLC Panel Error Code SS PLC 498 Hex Value Description 0x010000 DST Node is out of buffer space 0x020000 Cannot guarantee delivery link layer The remote node specified does not ACK command 0x030000 Duplicate tok
17. to update the datagram Series 90 70 PLC CPUs only PLC generated error codes for the GE 90 30 SNPX protocol continued on the next page Cor D EA USER M Hardware User Manual 2nd Ed Rev G 08 14 A 23 Appendix A Panel amp PLC Error Code Tables GE 90 30 SNPX Protocol PLC Error Code Tables cont d Panel Error Code PLC 499 Hex Value PLC Errors for GE 90 30 SNPX Protocol Minor Major cont d Description PLC Error 0x010C WAIT type COMMREQ is not permitted must use NOW AIT type PLC Error 0x010E Not used PLC Error 0x010F The service request code in an X Request message is unsupported or invalid at this time This error may occur if an SNP X communication session has not been success fully established at the slave device PLC Error 0x020C COMMREQ command is not supported PLC Error 0x020E The modem command string length exceeds 250 characters PLC Error 0x020F Insufficient privilege level in the slave PLC CPU for the requested SNP X service Password protection at PLC CPU may be preventing the requested service PLC Error 0x0213 Unsupported COMMREQ These errors are only generated when there is no protocol currently being run on a port and the port receives a COMMREQ f f W s The port may be disabled or an error has occurred in processing a new configuration PLC Error 0x030C SNP communication is not active Must initiate anew SNP communication
18. 00000065 The target received a message of invalid length 0x00000066 Reserved for legacy Rockwell Automation 0x00000069 Unsupported encapsulation protocol revision ae 7 Reserved for future expansion PLC Errors for Allen Bradley EtherNet IP Protocol CIP Errors Error code Oxaabbbb returned from the PLC Panel Error Code WS PLC 497 Hex Value Description 0x010100 Connection Manager Connection in Use or Duplicate Forward Open 0x010103 Connection Manager Transport Class and Trigger combination not supported 0x010106 Connection Manager Ownership Conflict 0x010107 Connection Manager Connection not found at target application 0x010108 Connection Manager Invalid connection type problem with type or priority 0x010109 Connection Manager Invalid connection size 0x010110 Connection Manager Device not configured 0x010111 Connection Manager RPI not supported Could also be problem with inactivity timeout PLC generated error codes for the Allen Bradley EtherNet IP protocol for MicroLogix 1100 1400 SLC 5 05 or ENI Adapter continued on the next page A 16 Cmor D EA USER M Hardware User Manual 2nd Ed Rev G 08 14 Appendix A Panel amp PLC Error Code Tables Allen Bradley EtherNet IP Protocol PLC Error Code Tables MicroLogix 1100 1400 amp SLC 5 05 both via native Ethemet port MicroLogix 1000 1100 1200 1400 1500 SLC5 03 04 05 all via ENI Adapte
19. 1 Getting Started As with any network communications errors will occur To make it more simple for the user to identify the cause of the possible error we have provided a error code table for all of the possible errors that C more can detect If a C more communications error does occur the error message will appear across the top of the screen The C more touch panel also monitors any errors that are generated by the various PLCs that are connected to it If any of the PLC generated errors are detected they are displayed across the top of the panel s display embedded as a hexadecimal value in error code P499 s message An explanation of how the specific PLC error is identified in the panel error code P499 is shown proceeding the specific manufacturer s PLC error tables How the hexadecimal error code value is interrupted is slightly different between manufacturers so it is important to check the explanation at the beginning of each manufacturer s tables Note These PLC error codes are provided by the manufacturer of the related PLC and are subject to change by the PLC manufacturer Please refer to the manufacturers documentation for a more complete and up to date list of error codes All errors are also logged into the panel s Error log under the Information tab in the panel s System Setup Screens and are identified by the error code number See Chapter 5 System Setup Screens for additional details If you ha
20. 9 Block does not exist 0xD20E No Block does not exist 0xD210 Block number incorrect mar D EA USER M Hardware User Manual 2nd Ed Rev G 08 14 A 4l
21. C 499 Hex Value Description 0x1A0C Datagram area size is too small to include data for all specified point formats 0x1B0C Invalid number of Control Program Names Must be 1 8 OX1COC SNP X Request exceeds maximum data size A bytes Must use a smaller data length Use multiple COMMREQs if necessary Ox1D0C Invalid SNP X communication session type Must be 0 for a single slave device or 1 for multiple slave devices Illegal destination SNP ID specified for SNP X slave Must be 0 7 ASCII characters plus a terminating null 0x1E0C character 00h The Null SNP ID ight bytes of 00h may be used to specify any single device The Broadcast SNP ID eight bytes of FFh may be use to specify all slave devices on the serial link Destination SNP ID does not match SNP X session type Ox1F0C The Broadcast SNP ID is not permitted in a single slave SNP X session The Null SNP ID is not permitted in a multiple slave SNP X session Inactivity timeout T3 The SNP slave has not received any new SNP messages within the configured T3 0x2006 time interval 0x200F Invalid Message Type field in a received X Request message The message type of an X Request message must be 58h 0x210C A Parity error has occurred on an Attach Attach Response or Update Real time Datagram message Communications have not been established Invalid Next Message Type or Next Message Length field in a received X Request message If this request does not use a buffer 0 2
22. EM key is NULL inactive 0xC305 Text length does not match traffic type 0xC405 Verify with FA Card or EEPROM failed 0xC505 No tasklevel Rack Slot configuration to read or delete 0xC605 Control Program CP tasks exist but requestor not logged into main CP 0xC705 Passwords are set to inactive and cannot be enabled or disabled OxC805 Password s already enabled and can not be forced inactive 0xC905 Login using non zero buffer size required for block commands OxCA05 Device is write protected 0xCB05 A comm or write verify error occurred during save or restore OxCC05 Data stored on device has been corrupted and is no longer reliable 0xCD05 Attempt was made to read a device but no data has been stored on it OxCE05 Specified device has insufficient memory to handle request 0xCF05 Specified device is not available in the system not present 0xD005 One or more PLC modules configured have unsupported revision 0xD105 Packet size or total program size does not match input 0xD205 Invalid write mode parameter 0xD305 User Program Module UPM read or write exceeded block end 0xD405 Mismatch of configuration checksum 0xD505 Invalid block name specified in datagram 0xD605 Total datagram connection memory exceeded 0xD705 Invalid datagram type specified 0xD805 Point length not allowed 0xD905 Transfer type invalid for this Memory Type selector 0xDA05 Null pointer to data in Memory Type selector 0xDB05 Invalid Memory Type selector
23. F00900 Transaction size plus word address is too large 0xF00B00 Access denied improper privilege This will occur if data file is set to constant or protected 0xF00C00 Condition cannot be generated resource is not available OxFOODO0 Condition already exists resource is readily available PLC generated error codes for the Allen Bradley EtherNet IP protocol for MicroLogix 1100 1400 SLC 5 05 or ENI Adapter continued on the next page A 20 Chor D EA USER M Hardware User Manual 2nd Ed Rev G 08 14 Appendix A Panel amp PLC Error Code Tables Allen Bradley EtherNet IP Protocol PLC EnorCode Tables MicroLogix 1100 1400 amp SLC 5 05 both via native Ethemet port D MicroLogix 1000 1100 1200 14400 1500 SLC 5 03 04 05 all via ENI Adapter PLC Errors for Allen Bradley EtherNet IP Protocol Service Packet Errors Error code Oxaabbbb returned from the PLC Panel Error Code a PLC 498 Hex Value Description OxFOOEOO Command cannot be executed OxFOOFO0 Histogram overflow 0xF01000 No access 0xF01100 Illegal data type 0xF01200 Invalid parameter or invalid data 0xF01300 Address reference exists to deleted area 0xF01400 Command execution failure for unknown reason possible histogram overflow 0xF01500 Data conversion error 0xF01600 Scanner not able to communicate with 1771 rack adapter 0xF01700 Type mism
24. M 0xD209 Block does not exist OxD20E No Block does not exist 0xD210 Block number incorrect A 40 Chor D EA USER M Hardware User Manual 2nd Ed Rev G 08 14 Appendix A Panel amp PLC Error Code Tables Siemens ISO over TCP Protocol PLC Error Code Table PLC PDU Header Errors for 7 200 CPU 7 300 S7 1200 Ethernet D Panel Error Code PLC 499 Hex Value Description 0x0001 Hardware Fault Object access not allowed Occurs when access to Timer and Counter data type is set to Signed Integer 0x0003 and not BCD 0x0004 Context not supported Address out of range Occurs when requesting an address within a Data Block that does not exist or is out 0x0005 of range 0x0006 Address out of range 0x0007 Write Data size mismatch 0x000A Object does not exist Occurs when trying to request a Data Block that does not exist 0x8000 Function being used 0x8001 Action is not allowed in current mode 0x8101 Hardware fault 0x8103 Access not allowed 0x8104 Function not supported 0x8105 Address invalid 0x8106 Data Type not supported 0x8107 Data Type is not consistent with size 0x810A Object does not exist 0x8500 PDU Size is incorrect 0x8702 Address is invalid 0xD201 Block name syntax error 0xD202 Error with function parameter 0xD203 Error with block type 0xD204 No linked block 0xD205 Object already exists 0xD206 Object already exists 0xD207 Block already used in EPROM 0xD20
25. Protocol Error Code PLC 499 Breakdown Remote Local EXTSTS 4 7 bits 0 3 bits byte A A A fr yY N N bit ATi Ja T loloJoJololoJo 1Jof l 15 14 13 12 11 10 9 gr 65 4 83 24 H yY K Ne a en of an EXT STS error PLC 499 Error Code Message F loli 7 for a Type mismatch Displayed Hexadecimal Value hex A 8 Error code 1700 retumed from PLC AB DF1 and DH485 Protocol Multiple Error Code Examples Remote 4 7 bits Local 0 3 bits EXT STS byte Error PLC 499 Value Displayed Example 1 Example 2 Example 3 F X 1 x F x x 7 C mm D EA USER M Hardware User Manual 2nd Ed Rev G 08 14 Appendix A Panel amp PLC Error Code Tables Allen Bradley DEL amp DH485 Protocols PLC Error Code Tables The following PLC error code tables cover possible errors that are detected by the panel from D Allen Bradley PLCs using the DF1 and DH485 protocols DF1 includes full and half duplex communications for the MicroLogix 1000 1100 1200 1400 1500 SLC 5 03 04 05 ControlLogix CompactLogix and FlexLogix and full duplex communications for the PLC5 DH485 includes all MicroLogix and SLC500 PLC s and any communication connection using an Allen Bradley AIC device using the DH485 protocol Note The following errors can be generated from the designa
26. Request Processor response exceeds 1000 bytes 0x080F the SNP X slave device cannot return the data in an X Response message This error applies to CMM module only 0x090C Master device memory data length exceeds maximum data size of CMM module 2048 bytes Must use a smaller data length Use multiple COMMREQs if total data length exceeds this maximum value 0x090E Modem responded with ERROR Modem is unable to complete the requested command Check the modem command string and modem Ox0A0C Slave device memory type is missing or not valid OxOAOE Modem responded with RING indicating that the modem is being called by another modem Modem is unable to complete the requested command Retry the modem command at a later time 0x0B0C Slave device memory address is missing or zero An unknown response was received from the modem Modem is unable to complete the requested 0x0B0E command Check the modem command string and modem The modem response is expected to be either CONNECT or OK COMMREQ Data Block Length is too small Ox0C0C When expected COMMREQ length is 6 words or less An improper length may cause other minor error codes 6 11 Ox0D0C Invalid Diagnostic Status Word DSW starting word or length Ox0EOC Invalid maximum SNP message data size Must be an even value from 42 to 2048 Ox0FOC Invalid Privilege Level Must be 0 through 4 or 1 0x100C Invalid Fault Table selector Must be 1 for I O Fa
27. The following errors can be generated from the designated PLC are monitored by the C more touch message if active Please refer to the PLC manufacturer s documentation for additional information PLC Error Codes for Omron CS CJ FINS Ethernet Panel Error Code PLC 495 Hex Value Desoupuon 0103 Local Error Send Error from lack of buffer space Try reducing Ethernet load to the module 0201 Destination Node Error IP address of remote node not set correctly 0202 Destination Node Error No node with the specified unit address found 0205 Destination Node Error Packet corrupted or Response timeout Try increasing timeout 0301 Controller Error Communications controller error 0302 Controller Error CPU Unit error Check error LEDs on PLC Refer to documentation for that CPU 0304 Controller Error Unit number error Make sure Unit number is not used twice 0401 Service unsupported Undefined command 0501 Routing table error Destination address setting error Routing table incorrect 0502 Routing table error No routing tables 0503 Routing table error Routing table error 0504 Routing table error Too many relays 1001 Command format error Command too long Bad packet check for electrical noise and grounding 1002 Command format error Command too short Bad packet check for electrical noise and grounding 1003 Command format error Elements data don t match Bad packet check for electrical noise and grounding 1005 Command format error Header
28. ablished 0x440D A datagram error occurred in a Series 90 70 slave device dual port error Ox440F PLC backplane communications error 0x450C An invalid response code was detected in an X Attach Response message when establishing a new SNP X communication session Communications have not been established 0x460C An expected X Attach Response message was not received within the response timeout interval when establishing a new SNP X communication session The master has retried the X Attach message twice without receiving a response Communications have not been established 0x500C A parity error has occurred on an X Attach Response message when re establishing an existing SNP X communication session Communications have not been established 0x500F A parity error has occurred in a received X Attach message 0x510C A framing or overrun error has occurred on an X Attach Response message when re establishing an existing SNP X communication session Communications have not been established 0x510F A framing or overrun error has occurred in a received X Attach message 0x520C A BCC Block Check Code error has occurred on an X Attach Response message when re establishing an existing SNP X communication session Communications have not been established 0x520F A BCC Block Check Code error has occurred in a received X Attach message PLC generated error codes for the
29. ach other A value contained in the query data field is not an allowable value for the server or slave This indicates a fault in the structure of the remainder of a complex request such as that the implied length is incorrect It specifically 0x0003 does NOT mean that a data item submitted for storage in a register has a value outside the expectation of the application program since the Modbus protocol is unaware of the significance of any particular value of any particular register 0x0004 An unrecoverable error occurred while the server or slave was attempting to perform the requested action Cmor D EA USER M Hardware User Manual 2nd Ed Rev G 08 14 A 7 Appendix A Panel amp PLC Error Code Tables Allen Bradley Panel Error Code PLC 499 Explanation The PLC 499 error code is used to show any errors that are generated by the connected PLC The PLC 499 error message includes a four digit hexadecimal value embedded in the message This value can be looked up in the specific PLC s error tables to determine the cause of the error The possible PLC generated error codes for the Allen Bradley D I and DH485 communication protocols are represented by a hexadecimal value as shown in the following diagram Please note that the error code is broken down into three sections It is possible for more than one type of PLC error to be displayed in this value Allen Bradley Error Code PLC 499 Message Example AB DF1 and DH485
30. al Error Local node not in network 0x0102 Local Error Token Timeout 0x0103 Local Error Retries Failed 0x0104 Local Error Too many send frames 0x0105 Local Error Node address range error 0x0106 Local Error Node Address Duplication 0x0201 Destination Node Error Destination Node not in network 0x0202 Destination Node Error Unit Missing 0x0203 Destination Node Error Third Node missing 0x0204 Destination Node Error Destination Node busy 0x0205 Destination Node Error Response Timeout 0x0301 Controller Error Communications Controller Error 0x0302 Controller Error CPU Unit Error 0x0303 Controller Error Controller Error 0x0304 Controller Error Unit number Error 0x0401 Service Unsupported Undefined Command 0x0402 Service Unsupported Not supported by Model Version 0x0501 Routing Table Error Destination address setting error 0x0502 Routing Table Error No routing tables 0x0503 Routing Table Error Routing table error 0x0504 Routing Table Error Too many delays 0x1001 Command Format Error Command too long 0x1002 Command Format Error Command too short 0x1003 Command Format Error Elements Data don t match 0x1004 Command Format Error Command format error 0x1005 Command Format Error Header Error 0x1101 Parameter Error Area classification missing 0x1102 Parameter Error Access Size Error 0x1103 Parameter Error Address range error
31. as not received 0x740C An invalid next message type value was detected in an Intermediate Response message 0x750C An invalid response code was detected in an Intermediate Response message 0x760C An expected Intermediate Response message was not received within the response timeout interval PLC generated error codes for the GE 90 30 SNPX protocol continued on the next page Cor D EA USER M Hardware User Manual 2nd Ed Rev G 08 14 A 29 Appendix A Panel amp PLC Error Code Tables GE 90 30 SNPX Protocol PLC Error Code Tables cont d D PLC Errors for GE 90 30 SNPX Protocol Minor Major cont d Panel Error Code ER PLC 499 Hex Value Description Ox8D0A Bad DOS Version Must have DOS 2 0 or later to support the SNP DOS Driver Ox8E0A PC Serial port configured for SNP Master driver is not open no communication can take place Ox8F0A Out of Sequence SNP message SNP message type received was not the type expected Bad SNP BCC encountered Transmission was aborted after maximum retries due to a bad Block Check 0x900A Code 0x910A Bad SNP communication Transmission was aborted after maximum retries due to serial errors that is parity overrun or framing errors 0x920A No SNE communication Either communication has been lost or a communication session has not been established 0xC105 Invalid block state transition 0xC205 The O
32. atch 0xF01800 1771 module response was not valid 0xF01900 Duplicated label 0xF02200 Remote rack fault OxF02300 Timeout OxF02400 Unknown error OxF01A00 File is open another node owns it 0xF01B00 Another node is the program owner OxF01C00 Reserved OxF01D00 Reserved 0xF01E00 Data table element protection violation 0xF01F00 Temporary internal problem Generic EtherNet IP Protocol PLC Error Codes Only errors as listed in the Touch Panel Error Code Table shown on page A 3 can occur when using the Generic Ethernet IP protocol there are no PLC generated errors C mor D EA USER M Hardware User Manual 2nd Ed Rev G 08 14 A 2 1 Appendix A Panel amp PLC Error Code Tables GE 90 30 Panel Error Code PLC 499 Explanation D The PLC 499 error code is used to show any errors that are generated by the connected PLC The PLC 499 error message includes a four digit hexadecimal value embedded in the message This value can be looked up in the specific PLC s error tables to determine the cause of the error The possible PLC generated error codes for the GE 90 30 communication protocol are represented by a hexadecimal value as shown in the following message example GE 90 30 Error Code PLC 499 Message Example Error code 0013 retumed from PLG A 22 C mm D EA USER M Hardware User Manual 2nd Ed Rev G 08 14 Appendix A Panel amp PLC Error Co
33. ation impossible unrecognized remote 1 0 unit channel over duplication of optical transmitting 1 0 unit 0x00A0 Abort due to parity error in transmit data under process 0x00A1 Abort due to framing error in transmit data under process 0x00A2 Abort due to overrun in transmit data under process 0x00A3 Abort due to FCS error in transmit data under process 0x00A4 Abort due to format error in transmit data under process 0x00A5 Abort due to frame length error in transmit data under process 0x00A8 Abort due to entry number data error in transmit data under process 0x00B0 Un executable due to program area capacity other than 16k bytes Cmor D EA USER M Hardware User Manual 2nd Ed Rev G 08 14 A 33 Appendix A Panel amp PLC Error Code Tables Omron FINS Protocol PLC Error Code Table D The following table lists the errors that can be generated by the Omron PLC when using the FINS protocol panel and displayed on the touch panel s screen as a hexadecimal value in panel error code PLC 499 E Note The following errors can be generated from the designated PLC are monitored by the C more touch message if active Please refer to the PLC manufacturer s documentation for additional information PLC Error Codes for Omron FINS Panel Error Code Ze PLC 499 Hex Value Description 0x0000 Normal Completion 0x0001 Service Canceled 0x0101 Loc
34. by sending an Attach or Long Attach COMMREQ PLC Error 0x030E COMMREQ Data Block Length is too small Output command string data is missing or incomplete PLC Error 0x030F Invalid slave memory type in X Request message PLC Error 0x0313 Invalid COMMREGQ length PLC Error 0x040C SNP slave did not respond to Attach message from master PLC Error 0x040E Serial output timeout The CMM module was unable to transmit the modem autodial output from the serial port May be due to missing CTS signal when the CMM is configured to use hardware flow control PLC Error 0x040F Invalid slave memory address or range in X Request message PLC Error 0x0413 Invalid COMMREQ status word location PLC Error 0x050C Unable to write SNP Status Word to local PLC memory may be due to invalid Status Word memory type or address PLC Error 0x050E Response was not received from modem Check modem and cable PLC Error 0x050F Invalid data length in X Request message Data length must be non zero and may not exceed decimal 1000 bytes PLC Error 0x0513 Invalid COMMREQ data PLC Error 0x060C Master device memory type is not valid in this PLC PLC Error 0x060E Modem responded with BUSY l Modem is unable to complete the requested connection The remote modem is already in use retry the connection request at a later time PLC Error 0x060F X Buffer data length does not match
35. bytes of data the Next Message Type must be zero If this request will be 0x210F followed with a buffer message more than 2 byte the Next Message Type must be 54h T and the Next Message Length must specify the length of the X Buffer message Valid X Buffer message lengths are 9 1008 bytes data length plus 8 bytes 0x220C A BCC Block Check Code error has occurred on an Attach Attach Response or Update Realtime Datagram message Communications have not been established 0x220F Invalid Message Type field in a received X Buffer message The message type of an X Buffer message must be 54h T 0x230C A Framing or Overrun serial error has occurred on an Attach Attach Response or Update Realtime Datagram message Communications have not been established 0x230F Invalid Next Message Type field in a received X Buffer message Since an X Buffer message is never followed by another message the Next Message Type must always be zero 0x240C An invalid SNP message type was received when an Attach Attach Response or Update Realtime Datagram message was required Communications have not been established 0x250C An invalid next message length value was specified in an Attach Attach Response or Update Realtime Datagram message Communications have not been established 0x260C An unexpected SNP message type was received when an Attach Attach Response or Update Realtime Datagram was required Communications have not been established A
36. cate Object Oxff0000 Class specific errors Use of this range should only be used when errors in this table don t accurately reflect the error encountered PLC Errors for Allen Bradley EtherNet IP Protocol Service Packet Errors Error code Oxaaaaaaaa returned from the PLC Panel Error Code inti PLC 498 Hex Value SEN 0x040000 This general status codes that the tag name could not be deciphered This could mean that the tag name was entered incorrectly or does not exist in the PLC 0x050000 The particular item referenced usually instance could not be found 0x060000 The amount of data requested would not fit into the response buffer Partial data transfer has occurred 0x0a0000 An error has occurred trying to process one of the attributes 0x130000 Not enough command data parameters were supplied in the command to execute the service requested 0x1c0000 An insufficient number of attributes were provided compared to the attribute count 0x260000 The tag name length specified did not match what was in the message Oxff0521 You have tried to access beyond the end of the data object Oxff0721 The abbreviated type does not match the data type of the data object Oxff0421 The beginning offset was beyond the end of the template C mor D EA USER M Hardware User Manual 2nd Ed Rev G 08 14 A 15 Appendix A Panel amp PLC Error Code Tables Allen Bradley EtherNet IP Protocol PLC Error Cod
37. ce already executing 0x2606 Command Error Service stopped 0x2607 Command Error No execution right 0x2608 Command Error Settings not complete 0x2609 Command Error Necessary items not set 0x260A Command Error Number already defined 0x260B Command Error Error will not clear 0x3001 Access Right Error No access right 0x4001 Abort Service aborted A 36 Chor D EA USER M Hardware User Manual 2nd Ed Rev G 08 14 Appendix A Panel amp PLC Error Code Tables Omron Panel Error Code P495 Explanation The PLC 495 error code is used to show any errors that are generated by the connected PLC D The PLC 495 error message includes a four digit hexadecimal value embedded in the message This value can be looked up in the specific PLC s error tables to determine the cause of the error The possible PLC generated error codes for the Omron CS CJ FINS ethernet communication protocol are represented by a hexadecimal value as shown in the following message example Cmor D EA USER M Hardware User Manual 2nd Ed Rev G 08 14 A 37 Appendix A Panel amp PLC Error Code Tables Omron CS C FINS Ethernet Protocol PLC Error Code Table D The following table lists the errors that can be generated by the Omron PLC when using the CS CJ FINS Ethernet protocol panel and displayed on the touch panel s screen as a hexadecimal value in panel error code PLC 495 E Note
38. col PLC Error Codes Only errors as listed in the Touch Panel Error Code Table shown on page A 3 can occur when using the DirectLOGIC DirectNET protocol there are no PLC generated errors E Note The following errors can be generated from the designated PLC are monitored by the C more touch DirectLOGIC error code tables continued on the next page Cmor D EA USER M Hardware User Manual 2nd Ed Rev G 08 14 l A 5 Appendix A Panel amp PLC Error Code Tables Modbus Protocols Error Code P499 Explanation D The following table lists the errors that can be generated by the Modbus protocols AutomationDirect CLICK AutomationDirect DirectLOGIC Modbus Koyo Modicon Modbus RTU Entivity Modbus RTU panel and displayed on the touch panel s screen as a hexadecimal value in panel error code PLC 499 E Note The following errors can be generated from the designated PLC are monitored by the C more touch message if active Please refer to the PLC manufacturer s documentation for additional information PLC Error Codes Modbus Protocols Panel Error Code Name Meaning P499 Hex Value The function code received in the query is not an allowable action for the server or slave This ILLEGAL may be because the function code is only applicable to newer devices and was not 0x0001 FUNCTION implemented in the unit selected It could also indicate that the server or slave is in the wrong state to process a request of this type for exampl
39. col PLC Error Codes 0 eee eee eeee A 21 GE 90 30 Panel Error Code PLC 499 Explanation 00005 A 22 GE 90 30 SNPX Protocol PLC Error Code Tables 000000 A 23 PANEL amp PLC PENDIX ERROR CODE TABLES Mitsubishi FX Protocol PLC Error Codes 2 eee eee eee eee eee A 32 Omron Panel Error Code PLC 499 Explanation A 32 Omron Host Link Protocol PLC Error Code Table A 33 Omron FINS Protocol PLC Error Code Table 0 02 e eee ee eee A 34 Omron Panel Error Code P495 Explanation A 37 Omron CS CJ FINS Ethernet Protocol PLC Error Code Table A 38 Siemens Panel Error Code P499 Explanation 0 0 00 cece eee eee A 39 Siemens PPI Protocol PLC Error Code Table 0 eee eee eee A 40 Siemens ISO over TCP Protocol PLC Error Code Table A 41 This page intentionally left blank Appendix A Panel amp PLC Error Code Tables Introduction The C more family of touch panels is capable of communicating with a wide variety of Programmable Logic Controllers C more is capable of communicating over RS232 RS422 and RS485 serial networks as well as Ethernet networks It communicates with all AutomationDirect PLCs utilizing various protocols C more also communicates with other brands of PLCs by their different protocols For a complete list of PLCs and protocols see the table on page 16 of Chapter
40. d the X Attach message twice without receiving a response Communications have not been established 0x600C A parity error has occurred on an X Response message 0x600F A parity error has occurred in a received X Request message 0x610C A framing or overrun error has occurred on an X Response message 0x610F A framing or overrun error has occurred in a received X Request message 0x620C A BCC Block Check Code error has occurred on an X Response message 0x620F A BCC Block Check Code error has occurred in a received X Request message 0x630C An invalid message type was received when an X Response message was required 0x640C An invalid next message type value was detected in an X Response message 0x650C An invalid response code was detected in an X Response message 0x660C An expected X Response message was not received within the response time 0x700C A parity error has occurred on an Intermediate Response message 0x700F A parity error has occurred in a received X Buffer message 0x710C A framing or overrun error has occurred on an Intermediate Response message 0x710F A framing or overrun error has occurred in a received X Buffer message 0x720C A BCC Block Check Code error has occurred on an Intermediate Response message 0x720F A BCC Block Check Code error has occurred in a received X Buffer message 0x730C An invalid message type was received when an Intermediate Response message was required 0x730F An expected X Buffer message w
41. de Tables GE 90 30 SNPX Protocol PLC Error Code Tables The following table lists the errors that can be generated by the GE 90 30 PLC when using the D SNPX protocol panel and displayed on the touch panel s screen as a hexadecimal value in panel error code PLC 499 E Note The following errors can be generated from the designated PLC are monitored by the C more touch message if active Please refer to the PLC manufacturer s documentation for additional information PLC Errors for GE 90 30 SNPX Protocol Major Panel Error Code SC PLC 499 Hex Value Description No error Successful completion This is the expected completion value in the COMMREQ Status Word 0x0002 Insufficient Privilege For Series 90 70 PLC the minor error code contains the privilege level required for the service request 0x0004 Protocol Sequence Error The CPU has received a message that is out of order 0x0005 Service Request Error the minor error code contains the specific error code 0x0006 Illegal Mailbox Type Service request mailbox type is either undefined or unexpected 0x0007 The PLC CPU s Service Request Queue is full The master should retry later It is recommended that the master wait a minimum of 10 msec before sending another service request 0x000A SNP DOS Driver Error The minor error code contains the specific error code Illegal Service Request The requested service is either not defined or not supported This value is 0x000B retur
42. e Tables D Microtogix 1100 14008 SLC5 05 both vianative Ethemet port MicroLogix 1000 1100 1200 1400 1500 SLC5 03 04 05 al via ENI Adapter The following PLC error code tables cover possible errors that are detected by the panel from Allen Bradley PLCs using the EtherNet IP protocol This includes MicroLogix 1100 1400 amp SLC 5 05 both using their native Ethernet port and MicroLogix 1000 1100 1200 1400 1500 SLC 5 03 5 04 and 5 05 using an Allen Bradly ENI Adapter Note The following errors can be generated from the designated PLC are monitored by the C more touch panel and displayed on the touch panel s screen as a hexadecimal value in panel error code PLC 496 message if active Please refer to the PLC manufacturer s documentation for additional information PLC Errors for Allen Bradley EtherNet IP Protocol Encapsulation Errors Error code Oxaaaaaaaa returned from the PLC Panel Error Code nern PLC 496 Hex Value Description 0x00000001 The sender issued an invalid or unsupported encapsulation command 0x0000000 Insufficient memory resources in the receiver to handle the command You can get this error if the 1761 NET ENI cannot connect to the PLC serially 0x00000003 Poorly formed or incorrect data in the data portion of the encapsulation message en Reserved for legacy Rockwell Automation 0x00000064 An orginator used an invalid session handle when sending an encapsulation message to the target 0x
43. e because it is unconfigured and is being asked to return registered values The data address received in the query is not an allowable address for the server or slave More specifically the combination of reference number and transfer length is invalid For a controller with 100 registers the PDU addresses the first register as 0 and the last one as 99 0x0002 ILLEGAL DATA If a request is submitted with a starting register address of 96 and a quantity of registers of 4 ADDRESS then the request will successfully operate address wise at least on registers 96 97 98 99 If a request is submitted with a starting register of 96 and a quantity of registers of 5 then the request will fail with Exception code 0x02 Illegal Data Address since it attempts to operate on registers 96 97 98 99 and 100 and there is no register with address 100 A value contained in the query data field is not an allowable value for server or slave This ILLEGAL DATA indicates a fault in the structure of the remainder of a complex request such as that the implied VALUE length is incorrect It specifically does NOT mean that a data item submitted for storage in a register has a value outside the expectation of the application program since the Modbus protocol is unaware of the significance of any particular value of any particular register 0x0004 SLAVE DEVICE An unrecoverable error occurred while the server or slave was attempting to perform the FAILURE requ
44. eds maximum data size decimal 1000 bytes Data in the Response is ignored 0x400C A parity error has occurred on an X Attach Response message when establishing a new SNP X communication session Communications have not been established 0x400D The requested service is not supported by the SNP slave 0x400F Serial output timeout The slave was unable to transmit an SNP X message from the serial port May be due to missing CTS signal when the CMM module is configured to use hardware flow control PLC generated error codes for the GE 90 30 SNPX protocol continued on the next page Cmor D EA USER M Hardware User Manual 2nd Ed Rev G 08 14 A 27 Appendix A Panel amp PLC Error Code Tables GE 90 30 SNPX Protocol PLC Error Code Tables cont d PLC Errors for GE 90 30 SNPX Protocol Minor Major cont d Description A Panel Error Code PLC 499 Hex Value 0x410C A framing or overrun error has occurred on an X Attach Response message when establishing a new SNP X communication session Communications have not been established 0x410D SNP slave on CMM module requires PLC CPU privilege level 2 to operate The SNP slave has rejected a request to change to a higher or lower privilege level Ox410F An SNP X request was aborted prior to completion due to reception of a Break 0x420C A BCC Block Check Code error has occurred on an X Attach R
45. en holder detected 0x040000 Local port is disconnected 0x050000 Application layer timed out waiting for response 0x060000 Duplicate node detected 0x070000 Station is offline 0x080000 Hardware fault 0x100000 Illegal command or format Typical error received from PLC when addressed requested to the PLC does not exist Usually occurs if memory map has not been expanded in PLC to the range requested from panel 0x200000 Host has a problem and will not communicate 0x300000 Remote node host is missing disconnected or shut down 0x400000 Host could not complete function due to hardware fault 0x500000 Addressing problem or memory protected rungs 0x600000 Function not allowed due to command protection selection 0x700000 Processor is in Program Mode 0x800000 Compatibility mode file missing or communication zone problem 0x900000 Remote node cannot buffer command 0xA00000 Wait ACK 1775 KA buffer full 0xB00000 Not used 0xC00000 Not used 0xD00000 Error code in the EXT STS byte See the error code table below 0xE00000 Fewer levels specified in address than minimum for any address 0xF00300 More levels specified in address than system supports 0xF00400 Symbol not found 0xF00500 Symbol is of improper format 0xF00600 Address does not point to something usable 0xF00700 File is wrong size 0xF00800 Cannot complete request situation has changed since start of the command 0xF00900 Data or file size is too large 0x
46. equested service Reply data too large The data to be transmitted in the response buffer is larger than the allocated response 0x110000 buffer 0x120000 Fragmentation of a primitive value The service specified an operation that is going to fragment a primitive data value For example trying to send a 2 byte value to a REAL data type 4 byte 0x130000 Not enough data The service did not supply enough data to perform the specified operation 0x140000 Attribute not supported The attribute specified in the request is not supported 0x150000 Too much data The service supplied more data than was expected 0x160000 Object does not exist The object specified does not exist in the device 0x170000 Service fragmentation sequence not in progress The fragmentation sequence for this service is not currently active for this data 0x180000 No stored attribute data The attribute data of this object was no saved prior to the requested service 0x190000 Store operation failure The attribute data of this object was not saved due to a failure during the attempt 0x120000 Routing failure request packet too large The service request packet was too large for transmission on a network in the path to the destination 0x1b0000 Routing failure response packet too large The service reponse packet was too large for transmission on a network in the path from the destination 0x1c0000 Missing attribute list entry data The service did not supply an attribute
47. esponse message when establishing a new SNP X communication session Communications have not been established 0x420D SNP Request or Response message exceeds maximum data length of the CMM module Total data length for Mailbox and all following Buffer messages is 2048 bytes The master must use a smaller data length Use multiple requests if total data length exceeds the maximum value 0x420F An X Buffer message was received containing greater than 1000 bytes of data The data is ignored 0x430C An invalid message type was received when an X Attach Response was required when establishing a new SNP X communication session Communications have not been established 0x430D Improper Write Datagram message format Series 90 70 slave devices use a different format for this message than Series 90 30 or Series 90 20 slave devices The master must use the proper message format for this SNP slave device The SNP master in the CMMmodule sends this message as part of the Establish Datagram COMMREQ command The datagram has been partially established but is not usable the datagram should be cancelled by using the Datagram ID returned by the COMMREQ 0x430F The SNP X slave did not receive a response from the Service Request Processor in the PLC CPU 0x440C An invalid next message type value was detected in an X Attach Response message when establishing a new SNP X communication session Communications have not been est
48. ested action DirectLOGIC ECOM Protocol PLC Error Codes Only errors as listed in the Touch Panel Error Code Table shown on page A 3 can occur when using the DirectLOGIC ECOM protocol there are no PLC generated errors 0x0003 A 6 Chor D EA USER M Hardware User Manual 2nd Ed Rev G 08 14 Appendix A Panel amp PLC Error Code Tables Productivity3000 Error Code P499 Note The following errors can be generated from the designated PLC are monitored by the C more touch D panel and displayed on the touch panel s screen as a hexadecimal value in panel error code PLC 499 message if active Please refer to the PLC manufacturer s documentation for additional information PLC Error Codes for Productivity3000 Panel Error Code Meaning P499 Hex Value The function code received in the query is not an allowable action for the server or slave This may be because 0x0001 the function code is only applicable to newer devices and was not implemented in the unit selected It could also indicate that the server or slave is in the wrong state to process a request of this type for example because it is unconfigured and is being asked to return registered values Address out of range Check to make sure that the C more tag and System ID match the Productivity3000 0x0002 Programming Software Tag Name and System ID The project file in the Productivity3000 system and the imported CSV into C more must be in sync with e
49. ey EtherNet IP Protocol PLC Error Code Tables ControlLogix CompactLogix amp FlexLogix cont d PLC Errors for Allen Bradley EtherNet IP Protocol CIP Errors Error code Oxaaaaaaaa returned from the PLC Panel Error Code ae PLC 497 Hex Value Description 0x010117 Connection Manager Invalid connection point 0x010118 Connection Manager Invalid configuration format 0x010119 Connection Manager Connection request fails since there is no controlling connection currently open 0x01011a Connection Manager Target application cannot support any more connections 0x01011b Connection Manager RPI is smaller than the Production Inhibit Time 0x010203 Connection Manager Connection cannot be closed since the connection has timed out 0x010204 Connection Manager Unconnected Send timed out waiting for a response 0x010205 Connection Manager Parameter error in Unconnected send service 0x010206 Connection Manager Message too large for Unconnected message service 0x010207 Connection Manager Unconnected acknowledge without reply 0x010301 Connection Manager No buffer memory available 0x010302 Connection Manager Network Bandwidth not available for data 0x010303 Connection Manager No Tag filters available 0x010304 Connection Manager Not configured to send real time data 0x010311 Connection Manager Port specified in Port segment not available 0x010312 Connection Manager Link address specified in port segment not available
50. icate with 1771 rack adapter Type mismatch 1771 module response was not valid Duplicated label Remote rack fault Timeout Unknown error File is open another node owns it Another node is the program owner Disk File is write protectid or otherwise unavailable Disk File is being used by another application Update not performed offline only Data table element protection violation Temporary internal problem A 10 Chor D EA USER M Hardware User Manual 2nd Ed Rev G 08 14 Appendix A Panel amp PLC Error Code Tables Allen Bradley EtherNet IP Protocol Panel Error Code PLC 496 497 and 498 Explanation D The PLC 496 PLC 497 and PLC 498 error codes are used to show any errors that are generated by the connected PLC These error messages include an eight digit hexadecimal value displayed embedded in the message This value can be looked up in the specific PLC s error tables to determine the cause of the error The possible PLC generated error codes for the Allen Bradley EtherNet IP communication protocol is represented by a hexadecimal value as shown in the following message example Allen Bradley Error Code PLC 496 497 498 Message Example C mor D EA USER M Hardware User Manual 2nd Ed Rev G 08 14 A 11 Appendix A Panel amp PLC Error Code Tables Allen Bradley EtherNet IP Protoco
51. id program cannot log in OxF305 1 0 configuration mismatch OxF405 Invalid input parameter in request OxF505 Invalid password OxF605 Invalid sweep state to set OxF705 Required to log in to a task for service OxF805 Invalid Task Name referenced OxF905 Task address out of range OxFA05 Cannot replace 1 0 module OxFB05 Cannot clear 1 0 configuration OxFC05 1 0 configuration is invalid OxFD05 Unable to perform auto configuration OxFEO5 No privilege for attempted operation OxFFO5 Service Request Error has been aborted Cmor D EA USER M Hardware User Manual 2nd Ed Rev G 08 14 A 3 1 Appendix A Panel amp PLC Error Code Tables Mitsubishi FX Protocol PLC Error Codes D Only errors as listed in the Touch Panel Error Code Table shown on page A 3 can occur when using the Mitsubishi FX protocol there are no PLC generated errors Omron Panel Error Code PLC 499 Explanation The PLC 499 error code is used to show any errors that are generated by the connected PLC The PLC 499 error message includes a four digit hexadecimal value embedded in the message This value can be looked up in the specific PLC s error tables to determine the cause of the error The possible PLC generated error codes for the Omron Host Link and FINS communication protocol are represented by a hexadecimal value as shown in the following message example
52. in datagram OxDC05 Unable to find connection address 0xDD05 Unable to locate given datagram connection ID OxDE05 Size of datagram connection invalid OxDF05 Invalid datagram connection address PLC generated error codes for the GE 90 30 SNPX protocol continued on the next page A 30 Chor D EA USER M Hardware User Manual 2nd Ed Rev G 08 14 Appendix A Panel amp PLC Error Code Tables GE 90 30 SNPX Protocol PLC Error Code Tables cont d PLC Errors for GE 90 30 SNPX Protocol Minor Major cont d D Panel Error Code PLC 499 Hex Value Deseription OxE005 Service in process cannot login OxE105 No 1 0 configuration to read or delete OxE205 IOS could not delete configuration or bad type OxE305 CPU revision number does not match OxE405 Memory Type for this selector does not exist 0xE505 DOS file area not formatted 0xE605 CPU model number does not match 0xE705 Configuration is not valid OxE805 No user memory is available to allocate OxE905 Memory Type selector not valid in context OxEA05 Not logged in to process service request OxEB05 Task unable to be deleted OxEC05 Task unable to be created OxED05 VME bus error encountered OxEE05 Could not return block sizes OxEF05 Programmer is already attached 0xF005 Request only valid in stop mode OxF105 Request only valid from programmer OxF205 Inval
53. its current mode state 0x0d0000 Object already exists The requested instance of object to be created already exists 0x0e0000 Attribute not settable A request to modify non modifiable attribute was received 0x0f0000 Privilege violation A permission privilege check failed 0x100000 Device state conflict The device s current mode state prohibits the execution of the requested service Reply data too large The data to be transmitted in the response buffer is larger than the allocated response 0x110000 buffer 0x120000 Fragmentation of a primitive value The service specified an operation that is going to fragment a primitive data value For example trying to send a 2 byte value to a REAL data type 4 byte 0x130000 Not enough data The service did not supply enough data to perform the specified operation 0x140000 Attribute not supported The attribute specified in the request is not supported 0x150000 Too much data The service supplied more data than was expected 0x160000 Object does not exist The object specified does not exist in the device 0x170000 Service fragmentation sequence not in progress The fragmentation sequence for this service is not currently active for this data 0x180000 No stored attribute data The attribute data of this object was no saved prior to the requested service 0x190000 Store operation failure The attribute data of this object was not saved due to a failure during the attempt 0x120000 Routing failu
54. l PLC Error Code Tables D ControlLogix CompactLogix amp FlexLogix The following PLC error code tables cover possible errors that are detected by the panel from Allen Bradley PLCs using the EtherNet IP protocol This includes all ControlLogix Panel Error Code CompactLogix and FlexLogix PLCs PLC 496 Hex Value Description 0x00000001 The sender issued an invalid or unsupported encapsulation command 0x0000000 Insufficient memory resources in the receiver to handle the command You can get this error if the 1761 NET ENI cannot connect to the PLC serially 0x00000003 Poorly formed or incorrect data in the data portion of the encapsulation message une Reserved for legacy Rockwell Automation Note The following errors can be generated from the designated PLC are monitored by the G more touch panel and displayed on the touch panel s screen as a hexadecimal value in panel error code PLC 496 message if active Please refer to the PLC manufacturer s documentation for additional information PLC Errors for Allen Bradley EtherNet IP Protocol Encapsulation Errors Error code Oxaaaaaaaa returned from the PLC 0x00000064 An orginator used an invalid session handle when sending an encapsulation message to the target 0x00000065 The target received a message of invalid length De Reserved for legacy Rockwell Automation 0x00000069 Unsupported encapsulation protocol revision A i Reserved for future expa
55. le for data 0x010303 Connection Manager No Tag filters available 0x010304 Connection Manager Not configured to send real time data 0x010311 Connection Manager Port specified in Port segment not available 0x010312 Connection Manager Link address specified in port segment not available 0x010315 Connection Manager invalid segment type or segment value in path 0x010316 Connection Manager Path and Connection not equal in close 0x010317 Connection Manager Ether Segment not present or Encoded Value in Network Segment is invalid 0x010318 Connection Manager Link address to self invalid 0x010319 Connection Manager Resources on Secondary unavailable 0x01031a Connection Manager Connection already established 0x01031b Connection Manager Direct connection already established 0x01031c Connection Manager Miscellaneous 0x01031d Connection Manager Redundant connection mismatch 0x01031e Connection Manager No more consumer resources available in the producing module 0x01031f Connection Manager No connection resources exist for target path ud Connection Manager Vendor specific PLC generated error codes for the Allen Bradley EtherNet IP protocol for MicroLogix 1100 1400 SLC 5 05 or ENI Adapter continued on the next page Cor D EA USER M Hardware User Manual 2nd Ed Rev G 08 14 A 17 Appendix A Panel amp PLC Err
56. ned in lieu of the actual 01h value passed in the SNP error message to avoid confusion with the normal successful COMMREQ completion Local SNP SNP X Error An error occurred within the SNP task in the CMM module in this PLC B 0x000C This error may occur in either an SNP master or an SNP slave The minor error code contains the specific error code 0x000D Remote SNP Error An error occurred within the SNP slave task in the CMM module in the remote PLC The minor error code contains the specific error code 0x000E Autodial Error An error occurred while attempting to send a command string to an attached external modem The minor error code contains the specific error code 0x000F SNP X slave error An error occurred within the SNPX task in the remote slave device The minor error code contains the specific error code 0x0013 Port configurator error 0x0050 Problem with sending mail to the slave Service Request task Series 90 70 PLC CPUs only 0x0051 Problem with getting mail from the slave Service Request task Series 90 70 PLC CPUs only Slave SNP task timed out before receiving an SRP response 0x0055 Series 90 70 PLC CPUs only 0x0056 Slave SNP task could not find the requested datagram connection Series 90 70 PLC CPUs only Slave SNP task encountered an error in trying to write the datagram 0x0057 Series 90 70 PLC CPUs only 0x0058 Slave SNP task encountered an error in trying
57. ng the Allen Bradley EtherNet IP error code tables PLC 499 Error code XXXX returned from PLC An error code with a value of XXXX has been returned from the PLC See the explanation for error code PLC 499 below for DirectLOGIC and proceeding each set of PLC error code tables that use this error code PLC 500 Cannot write to Serial Port Data cannot write to the Serial port Data was sent to the PLC via the Serial Port If this error shows on the Panel it indicates a Hardware Problem PLC 700 Not enough buffer memory There was an error while allocating memory for the read buffer When this error is displayed a memory leak may have occurred PLC 701 Access to inaccessible PLC memory Request to inaccessible memory from the HMI layer to the PLC protocol layer This error is an indication that there is a problem in the HMI layer PLC 702 Cannot access by different function code A Read Write SetBit request has been sent to an invalid memory area This error is an indication that there is a problem in the HMI layer PLC 703 Write request to PLC Read Only Memory A PLC Write request was made to the PLC s Read Only memory area This error is an indication that there is a problem in the HMI layer or the PLC protocol layer PLC 704 Bad device access No device PLC exists in the server panel or the device name does not match between the server and client when using the Panel Pass Through
58. nother Break was received while SNP slave was waiting for an Attach or Update Realtime Datagram 0x270C message An SNP message has been sent and retried the maximum number of times 0x280C A maximum of two retries are permitted A retry is caused by a NAK from from the remote SNP device 0x290C A received SNP message has been NAKed the maximum number of two times The NAKed message may be retransmitted a maximum of two times PLC generated error codes for the GE 90 30 SNPX protocol continued on the next page A 26 Chor D EA USER M Hardware User Manual 2nd Ed Rev G 08 14 Appendix A Panel amp PLC Error Code Tables GE 90 30 SNPX Protocol PLC Error Code Tables cont d PLC Errors for GE 90 30 SNPX Protocol Minor Major cont d D Panel Error Code PLC 499 Hex Value Kal Ox2A0C An unknown message was received when an acknowledge ACK or NAK was required 0x2B0C Sequence Error An unexpected SNP message type was received 0x2C0C Received SNP message contains bad next message length value Acknowledge timeout An acknowledge ACK or NAK was not received within the configured T2 time 0x2DOC interval A slave device may generate this error if the master device has aborted after maximum response NAKs and does not NAK the next response retry Response timeout The SNP Master did not receive an SNP Response message within the configured T5 Ox2E0C time interval
59. nsion PLC Errors for Allen Bradley EtherNet IP Protocol CIP Errors Error code Oxaaaaaaaa returned from the PLC Panel Error Code Se PLC 497 Hex Value Description 0x010100 Connection Manager Connection in Use or Duplicate Forward Open 0x010103 Connection Manager Transport Class and Trigger combination not supported 0x010106 Connection Manager Ownership Conflict 0x010107 Connection Manager Connection not found at target application 0x010108 Connection Manager Invalid connection type problem with type or priority 0x010109 Connection Manager Invalid connection size 0x010110 Connection Manager Device not configured 0x010111 Connection Manager RPI not supported Could also be problem with inactivity timeout 0x010113 Connection Manager Connection Manager cannot support any more connections 0x010114 Connection Manager Either the vendor ID or the Product Code in the key segment did not match the evice 0x010115 Connection Manager Product Type in the key segment did not match the device 0x010116 Connection Manager Major or minor revision information in the key segment did not match the device PLC generated error codes for the Allen Bradley EtherNet IP protocol for ControlLogix CompactLogix and FlexLogix continued on the next page A 12 CHnor D EA USER M Hardware User Manual 2nd Ed Rev G 08 14 Appendix A Panel amp PLC Error Code Tables Allen Bradl
60. or Code Tables Allen Bradley EtherNet IP Protocol PLC Error Code Tables D Microtogix 1100 14008 SLC5 05 both via native Ethemet port MicroLogix 1000 1100 1200 1400 1500 SLC 5 03 04 05 all via ENI Adapter PLC Errors for Allen Bradley EtherNet IP Protocol CIP Errors Error code Oxaabbbb returned from the PLC Panel Error Code inti PLC 497 Hex Value Description 0x020000 Resource unavailable Connection Manager resources are unavailable to handle service request 0x030000 Invalid parameter value 0x040000 Path segment error The path segment identifier or the segment syntax was not understood by the processing node 0x050000 Path destination unknown The path is referencing an object class instance or structure element that is not known or is not contained in the processing node 0x060000 Partial transfer Only part of the expected data was transferred 0x070000 Connection lost The messaging connection was lost 0x080000 Service not supported The requested service was not implemented or was not defined for this Object Class Instance 0x090000 Invalid attribute value Invalid attribute data detected Attribute list error An attribute in the Get_Attribute_List or Set_Attribute_List response has a non zero 0x0a0000 status 0x0b0000 Already in requested mode state The object is already in the mode state being requested by the service 0x0c0000 Object state conflict The object cannot perform the requested service in
61. or E EA USER M Hardware User Manual 2nd Ed Rev G 08 14 A 39 Appendix A Panel amp PLC Error Code Tables Siemens PPI Protocol PLC Error Code Table PLC PDU Header Errors for S7 200 PPI Description A Panel Error Code PLC 499 Hex Value 0x0001 Hardware Fault 0x0003 Object access not allowed Occurs when access to Timer and Counter data type is set to Signed Integer and not BCD 0x0004 Context not supported 0x0005 EE out of range Occurs when requesting an address within a Data Block that does not exist or is out of range 0x0006 Address out of range 0x0007 Write Data size mismatch 0x000A Object does not exist Occurs when trying to request a Data Block that does not exist 0x8000 Function being used 0x8001 Action is not allowed in current mode 0x8101 Hardware fault 0x8103 Access not allowed 0x8104 Function not supported 0x8105 Address invalid 0x8106 Data Type not supported 0x8107 Data Type is not consistent with size 0x810A Object does not exist 0x8500 PDU Size is incorrect 0x8702 Address is invalid 0xD201 Block name syntax error 0xD202 Error with function parameter 0xD203 Error with block type 0xD204 No linked block 0xD205 Object already exists 0xD206 Object already exists 0xD207 Block already used in EPRO
62. or specific error A vendor specific error has been encountered This occurs when none of the specified errors relate to the error in the device 0x200000 Invalid parameter A parameter associated with the request was invalid This code is used when a parameter does meet the requirements defined in an Application Object specification 0x210000 Write once value or medium already written An attempt was made to write to a write once medium that has already been written or to modify a value that cannot be change once established Invalid Reply Received An invalid reply is received example service code sent doesn t match service code 0x220000 received 0x230000 Reserved by CIP for future extensions 0x240000 Reserved by CIP for future extensions 0x250000 Key failure in path The key segment was included as the first segment in the path does not match the destination module The object specific status shall indicate which part of the key check failed 0x260000 Path Size Invalid The size of the path which was sent with the Service Request is either not large enough to allow the Request to be routed to an object or too much routing data was included 0x270000 Unexpected attribute in list An attempt was made to set an attribute that is not able to be set at this time 0x280000 Invalid Member ID The Member ID specified in the request does not exist in the specified Class Instance Attribute 0x290000 Member not settable A request to modify a
63. ost PLC generated error codes for the Allen Bradley EtherNet IP protocol for ControlLogix CompactLogix and FlexLogix continued on the next page Cor D EA USER M Hardware User Manual 2nd Ed Rev G 08 14 A 13 Appendix A Panel amp PLC Error Code Tables Allen Bradley EtherNet IP Protocol PLC Error Code Tables ControlLogix CompactLogix amp FlexLogix cont d PLC Errors for Allen Bradley EtherNet IP Protocol CIP Errors Error code Oxaaaaaaaa returned from the PLC Panel Error Code Se PLC 497 Hex Value Description 0x080000 Service not supported The requested service was not implemented or was not defined for this Object Class Instance 0x090000 Invalid attribute value Invalid attribute data detected Attribute list error An attribute in the Get_Attribute_List or Set_Attribute_List response has a non zero 0x0a0000 status 0x0b0000 Already in requested mode state The object is already in the mode state being requested by the service 0x0c0000 Object state conflict The object cannot perform the requested service in its current mode state 0x0d0000 Object already exists The requested instance of object to be created already exists 0x0e0000 Attribute not settable A request to modify non modifiable attribute was received 0x0f0000 Privilege violation A permission privilege check failed 0x100000 Device state conflict The device s current mode state prohibits the execution of the r
64. r PLC Errors for Allen Bradley EtherNet IP Protocol CIP Errors Error code Oxaabbbb returned from the PLC Panel Error Code a PLC 497 Hex Value Description 0x010113 Connection Manager Connection Manager cannot support any more connections 0x010114 Connection Manager Either the vendor ID or the Product Code in the key segment did not match the evice 0x010115 Connection Manager Product Type in the key segment did not match the device 0x010116 Connection Manager Major or minor revision information in the key segment did not match the device 0x010117 Connection Manager Invalid connection point 0x010118 Connection Manager Invalid configuration format 0x010119 Connection Manager Connection request fails since there is no controlling connection currently open 0x01011a Connection Manager Target application cannot support any more connections 0x01011b Connection Manager RPI is smaller than the Production Inhibit Time 0x010203 Connection Manager Connection cannot be closed since the connection has timed out 0x010204 Connection Manager Unconnected Send timed out waiting for a response 0x010205 Connection Manager Parameter error in Unconnected send service 0x010206 Connection Manager Message too large for Unconnected message service 0x010207 Connection Manager Unconnected acknowledge without reply 0x010301 Connection Manager No buffer memory available 0x010302 Connection Manager Network Bandwidth not availab
65. re request packet too large The service request packet was too large for transmission on a network in the path to the destination 0x1b0000 Routing failure response packet too large The service reponse packet was too large for transmission on a network in the path from the destination 0x1c0000 Missing attribute list entry data The service did not supply an attribute in a list of attributes that was needed by the service to perform the requested behavior PLC generated error codes for the Allen Bradley EtherNet IP protocol for MicroLogix 1100 1400 SLC 5 05 or ENI Adapter continued on the next page A 18 Chor D EA USER M Hardware User Manual 2nd Ed Rev G 08 14 Appendix A Panel amp PLC Error Code Tables Allen Bradley EtherNet IP Protocol PLC EnorCode Tables MicroLogix 1100 1400 amp SLC 5 05 both vianative Ethemet port D MicroLogix 1000 1100 1200 1400 1500 SLC5 03 04 05 all via ENI Adapter PLC Errors for Allen Bradley EtherNet IP Protocol CIP Errors Error code Oxaabbbb returned from the PLC Panel Error Code SES PLC 497 Hex Value Description 0x1d0000 Invalid attribute value list The service is returning the list of attributes supplied with status information for those attributes that were invalid 0x1e0000 Embedded service error See Service Packet error list PLC 498 Error codes below 0x1f0000 Vend
66. ted PLC are monitored by the C more touch panel and displayed on the touch panel s screen as a hexadecimal value in panel error code PLC 499 message if active Please refer to the PLC manufacturer s documentation for additional information PLC Errors for Allen Bradley DF1 and DH485 Protocols Local STS Errors 0 3 bits Panel Error Code rn PLC 499 Hex Value Description 0x0 Success no error 0x1 DST node is out of buffer space 0x2 Cannot guarantee delivery link layer The remote node specified does not ACK command 0x3 Duplicate token holder detected 0x4 Local port is disconnected 0x5 Application layer timed out waiting for response Duplicate node detected Station is offline Hardware fault PLC Errors for Allen Bradley DF1 and DH485 Protocols Remote STS Errors 4 7 bits PLC 499 Hex Value Description 0x0 Success no error 0x10 Illegal command or format 0x20 Host has a problem and will not communicate 0x30 Remote node host is missing disconnected or shut down 0x40 Host could not complete function due to hardware fault 0x50 Addressing problem or memory protect rungs 0x60 Function not allowed due to command protection selection 0x70 Processor is in Program Mode 0x80 Compatibility mode file missing or communication zone problem 0x90 Remote node cannot buffer command 0xA0 Wait ACK 1775 KA buffer full 0xB0 Remote node problem due to download 0xC0 Wait ACK 1775 KA buffer full 0xD0 not used
67. the service request in X Request message The X Buffer message length is obtained from the Next Message Length field in the X Request message the length of the data within the buffer message is always the message length PLC Error 0x070C Master device memory address or length is zero PLC Error 0x070E Modem responded with NO CARRIER Modem is unable to complete the requested connection Check the local and remote modems and the telephone line PLC Error 0x070F Queue Full indication from Service Request Processor in slave PLC CPU The slave is temporarily unable to complete the service request The master should try again later It is recommended that the master wait at least 10 msec before repeating the X Request PLC generated error codes for the GE 90 30 SNPX protocol continued on the next page A 24 C mm D EA USER M Hardware User Manual 2nd Ed Rev G 08 14 Appendix A Panel amp PLC Error Code Tables GE 90 30 SNPX Protocol PLC Error Code Tables cont d PLC Errors for GE 90 30 SNPX Protocol Minor Major cont d D Panel Error Code PLC 499 Hex Value Description 0x080C Unable to read or write master device memory locations specified in COMMREQ Usually caused by invalid memory address for this PLC SNP message exchange may have taken place 0x080E Modem responded with NO DIALTONE Modem is unable to complete the requested connection Check the modem connections and the telephone line Service
68. ult Table or 2 for PLC Fault Table Unexpected Service Request Processor error i f f 0x100F This error applies to CMM module only the unexpected SRP error code is saved in the Diagnostic Status Words in the CMM module 0x110C Invalid Fault Table starting index Must be 1 32 for I O Fault Table or 1 16 for PLC 0x120C Invalid fault count Must be 1 32 for I O Fault Table or 1 16 for PLC Fault Table 0x130C Invalid Set PLC Date Time mode Must be 1 4 0x140C Invalid Set PLC Date Time date time or day of week value 0x150C Unable to retrieve master device PLC time date from PLC CPU Ox150F Requested service is not permitted in a Broadcast request The master must direct the X Request message to a specific SNP X slave device Ox160C Invalid slave PLC type Must be 0 for Series 90 70 or 1 for Series 90 30 or Series 90 20 0x170C Invalid datagram type Must be 01h for normal datagram or 81h 129 for permanent datagram 0x180C Missing or too many datagram point formats Must be 1 32 0x190C Invalid datagram point format data PLC generated error codes for the GE 90 30 SNPX protocol continued on the next page Cor D EA USER M Hardware User Manual 2nd Ed Rev G 08 14 A 25 Appendix A Panel amp PLC Error Code Tables GE 90 30 SNPX Protocol PLC Error Code Tables cont d D PLC Errors for GE 90 30 SNPX Protocol Minor Major cont d Panel Error Code SE PL
69. ve difficulty determining the cause of the error please refer to Chapter 8 Troubleshooting for some troubleshooting tips or contact our technical support group at 770 844 4200 or the 3rd party PLC manufacturer Stride Ethernet Switch 10 100 Base T such as SE SW5U HO ECOM HO ECOM100 Ethernet Module Q lt gt C more Touch Panel Ethernet Port GG Set Im Bottom View Ethernet CAT5 Cable Straight thru A 2 Cor D EA USER M Hardware User Manual 2nd Ed Rev G 08 14 Appendix A Panel amp PLC Error Code Tables C more Touch Panel Error Code Table The following table includes all of the error codes and error messages that the panel will display if the listed cause is detected All of these errors involve problems that could result with the panel communicating with the connected PLC Be aware that not all of the panel errors are used with each type of PLC that can be connected to the panel Error Code C more Touch Panel Error Code Table Error Message Cause PLC 001 Ge Communication Timeout for single Device PLC Communication Timeout for multiple PLCs such as RS 422 485 A timeout occurred after sending a request to the PLC Device Device indicates the device name such as DEV001 parle error message for multiple PLCs DEV001 PLC Communication imeout PLC 002 NAK received from PLC