InsightPower SNMP IPv6 for PDC User Manual

image

Contents

1. Seller warrants this product if used in accordance with all applicable instructions to be free from original defects in material and workmanship within the warranty period If the product has any failure problem within the warranty period Seller will repair or replace the product at its sole discretion according to the failure situation This warranty does not apply to normal wear or to damage resulting from improper installation operation usage maintenance or irresistible force i e war fire natural disaster etc and this warranty also expressly excludes all incidental and conseguen tial damages Maintenance service for a fee is provided for any damage out of the warranty period If any maintenance is required please directly contact the supplier or Seller WARNING The individual user should take care to determine prior to A use whether the environment and the load characteristic are suitable adequate or safe for the installation and the usage of this product The User Manual must be carefully followed Seller makes no representa tion or warranty as to the suitability or fitness of this product for any specific application 55 A NELTA NO UMEN3915100975 S35PDC120618 A NE L l A
2. Voltage THD Current THD select one if Please keep the field empty if you don t want to assign a new value 27 A NELTA Panel The number of panels and branch circuits may vary depending on your PDC s configurations Check panel s readings and status in this page To change a set ting simply click on it or select from the drop down menu on the bottom of the page Make sure to click Submit to take effect after the changes are made el e Kl sirene M NELTA e i 7 InsightPower SNMP IPv6 for PDC Web le power ina competitiveness Device i System Status Information System gt Status OverCurr gt Parameter Name Primary UnderCurr Secondary Panel 1 Panel 2 OverTHD PoorPF HighCurr Branch Neutral Current Power Factor Current THD gt Threshold Name Neutral 0 0 Over Current 110 8 138 5 Under Current 0 0 Power Factor 0 00 Current THD 0 0 Valu Newt Please keep the field empty if you don t want to assign a new value Branch Parameter Branch Demand Branch Sem Under current Over current Alarm select one Please keep Under Current Over Current empty if you don t want to assign a new value Branch select one v 5 1 2 Data Log Hover your cursor on a
3. System Configurations Step 2 Make sure the two DIP switches of the SNMP IPV6 are set to the OFF posi tion Normal Mode Step 3 For Windows 2000 2003 2008 and XP go to Start Programs Accesso ries Communications and select HyperTerminal Microsoft has removed HyperTerminal from Windows Vista and later ver sions If your operation system does not include the program a free alterna tive Telnet SSH client PUTTY can be downloaded from http www putty org Step 4 Enter a name choose an icon for the connection and click OK From the drop down menu Connect using select the COM port that is connected to the SNMP IPv6 B Enter details for the phone number that you want to dial Country region Taiwan 886 M Enter the area code without the long distance prefix 4rea code fos Phone number TT Detect Carrier Loss JV Use country region code and area code T Redial on busy Lok cancel 13 A NELTA Step 5 Click Configure and set up COM port parameters as follows COM3 Properties Step 6 Click OK to continue Set the two DIP switches of the SNMP IPV6 to the ON position Configuration Mode and HyperTerminal will automatically connect to the SNMP IPv6 If it does not connect click the telephone icon from the tool bar When connection is established log in with Administra tor s account password default admin password case sensitive Once you are logged in the Main Menu appears on the s
4. The power behind competitiveness Delta InsightPower SNMP IPv6 for PDC User Manual lt T 7 www deltapowersolutions com Save This Manual This manual contains important instructions and warnings that you should fol low during the installation operation storage and maintenance of this product Failure to heed these instructions and warnings will void the warranty Copyright 2012 by Delta Electronics Inc All Rights Reserved All rights of this User Manual Manual including but not limited to the contents information and figures are solely owned and reserved by Delta Electronics Inc Delta The Manual can only be applied to the operation or the use of this product Any disposition duplication dissemination reproduction modification translation extraction or usage of this Manual in whole or in part is prohibited without the prior written permission of Delta Given that Delta will continuously improve and develop the product changes may be made to the information in this Manual at any time without obligation to notify any person of such revision or changes Delta will make all possible efforts to secure the accuracy and the integrity of this Manual Delta disclaims any kinds or forms of warranty guarantee or undertaking either expressly or implicitly including but not limited to the completeness faultlessness accuracy non infringement merchantability or fitness for a particular purpose of the
5. System Location roc ie T Subnet Mask 255 6 Gateway IP 172 16 186 254 Date Time snte O Manual DNS IP 12 46 A 86 Time Zone GMT Dublin Lisbon London v 1st Time Server Name or IP POOL NTP ORG DHCPv6 Client Enable Disable op mime server Name one IP Address FE80 230 ABFF FE25 EBED ime Prefix Length 64 Set Current Time Date 01 01 2000 MM DD YYYY Gateway IP Time 00 00 00 hh mm ss ONS IP User Limitation Administrator In The LAN O Allow Any System Configuration Device Manager 1In The LAN O Allow Any HTTP Server Enable O Disable Read Only User OIn The LAN Allow Any Telnet Server Enable ODisable HTTP Server Port Reset to Default Telnet Server Port It is recommended to provide a static IP Address and disable the BOOTP DHCP Client option If it is the first time to configure your InsightPower device please assign an unique name in the Host Name field and given a Time Server for the device throught SNTP protocol if possible O4 Unable to connect to the SNMP IPV6 via its Host Name If you just assign a new static IP address to the SNMP IPv6 you may need to refresh the NetBIOS table so that it corresponds with the new setting Although Windows updates its NetBIOS table periodically you can still manually force it to refresh by entering the following command nbtstat R in DOS pro
6. 0Z5G iHuSL pBD wFIHHInBHMkLDoV7q4yq1R102T SE HZB203Gr6GlwyxOJBMUGLYS0S200yDMYisS eL Jw vipuj4ahigAKsBE Xx4FOzhWJ NkycVJ1G1l0sStwWaxfwa GPDGh22rInJ8R 7BwoB SilvbOYOXCOBJ awX1eZYCuLs d AVAIATKHDIUd xafmi0hvoS wi FsRixd4AAA GBR 5s qzs00oQCVXXMEINGYXF Key fingerprint ssh dss 1023 93 da 30 2a bf 4e ac e3 d5 28 ca 9e d9 52 eb 89 Key comment dsa key 20110707 Key passphrase Confirm passphrase Actions Generate a public private key pair Load an existing private key file Save the generated key Save public key Save private key Parameters Type of key to generate O SSH RSA O SSH 2 RSA SSH 2 DSA Number of bits in a generated key 1024 m 51 A NELTA 8 Upload the DSA RSA Public keys files to the InsightPower SNMP IPv6 for PDC Web Refer to 5 2 1 Administrator Console for more information O14 How to upload configuration firmware key files via SSH SFTP To quickly configure your SNMP IPv6 you can upload the files via SSH SFTP The SNMP IPv6 automatically imports your settings after the files are uploaded to the designated directories Refer to the following table Directory Files SNMP IPv6 s firmware upgrade package binary Device s firmware upgrade package binary Appears on specific devices only Upload files to their respective directories Make sure the filenames do not contain non English characters to avoid read error Overwrite existing files if prompted by your SFT
7. REPO so LCM gt Parameter Name Ambient Temperature Total Ground Current P 4Hour Statistics Name Value Max Voltage Min Voltage Max Current Min Current Max Frequency Min Frequency P System Setting Name LCD Contrast Upper Ambient Temperature Upper Ground Current 25 A NELTA Primary This page shows the PDC s input readings and settings You can change the threshold settings on the bottom of the page Device System Status Information System Primary Secondary Panel 1 Panel 2 gt status i UV ov gt Parameter Name Neutral L L Voltage Voltage THD Current THD gt Threshold Name Under Voltage Over Voltage Over Current Under Current Current THD select one x Please keep the field empty if you don t want to assign a new value InsightPower SNMP IPv6 for PDC 26 Secondary Chapter 5 InsightPower SNMP IPv6 for PDC Web This page shows the PDC s output readings and settings You can change the threshold settings on the bottom of the page Device i System Status System Primary Panel 2 Information gt Status UV OV Parameter Name L L Voltage L N Voltage Current Power Factor Voltage THD Current THD Neutral gt Threshold Neutral Under Voltage Over Voltage Over Current Under Current Power Factor
8. SNMP slot Insert the SNMP IPV6 into the SNMP slot Groove Step 3 From the accessory pack age pick a cover that fits the screw locations of your PDC s SNMP slot and secure it with the removed screws 7 A NELTA Chapter 4 System Configurations There are different ways you can configure your SNMP IPv6 If a network connection is available at your location the following methods can be used e Web based interface The InsightPower SNMP IPv6 for PDC Web offers com prehensive system management and monitoring Please refer to Chapter 5 InsightPower SNMP IPv6 for PDC Web EzSetting Use the provided program EzSetting to quickly set up your SNMP IPv6 Please refer to 4 2 Configuring with EzSetting e Telnet mode Configure your SNMP IPV6 in text mode Please refer to 4 3 Con figuring via Telnet The above mentioned methods require network connection If not available you can use direct COM port connection to set up your SNMP IPv6 Please see 4 4 Configur ing through COM Port NOTE 1 To ensure system security it is highly recommended that you change your account and password after the first login 2 If you have multiple SNMP IPv6 units installed in your network we highly suggest that you change the SNMP IPv6 s default Host Name to avoid con flicts Also it is recommended that you disable BOOTP DHCP and manu ally assign a valid static IP address to the SNMP IPv6 CHD Configuring via InsightPower S
9. Telnet SSH communication protocols and replace DSA RSA keys System Administration User Manager System Administration Console TCP IP gt Console gt Host Key Web Telnet Enable Disable DSA Key SSH SFTP Enable Disable Browse I Console Telnet Port 23 RSA Key FTP SSH Port 22 Browse Update the certificated files which are generated by openssh for new SSH connections Time Server Syslog gt Authentication Public Key Batch Configuration Public Key fra Provide the public key for authentication The public key can be generated by openssh or putty Upgrade e Console Enable disable Telnet and SSH FTP protocols Assign ports when used HostKey The SNMP IPv6 supports SSH encryption to secure data communication Refer to Chapter 7 Troubleshooting O13 to generate DSA RSA and public keys The keys can be uploaded via this page or via SFTP protocol To upload your keys refer to Chapter 7 Troubleshooting O14 FTP Enable disable FTP protocol Assign a port when used InsightPower SNMP IPv6 for PDC 34 Administration User Manager TCP IP Web Console FTP Time Server Time Server System Chapter 5 InsightPower SNMP IPv6 for PDC Web System Administration FTP gt FTP FTP Enable Disable FTP Port 21 You can manually set the time and date or enable automatic time synchroni zation w
10. reading to check detailed information The total number of log entries is shown on the top left of the page You can define a time period to show entries recorded during the specified time Click on the date to bring up a pop up window and specify a date Click Clear His tory Data to clear all stored entries for all ID tags To check a specific type of data entry select a type from the drop down menu specify how many entries to show per page and click Reload InsightPower SNMP IPv6 for PDC 28 Chapter 5 InsightPower SNMP IPv6 for PDC Web Click Forward Backward to select the display order of listed data logs To copy all data entries to an Excel spreadsheet click Select current log to copy Press CTRL C to copy Press CTRL V to paste in Excel el gt e k memasme E A Device Mon 06 11 2012 PM 04 32 33 Data Log P Data Log Total 36 From 6 11 2012 6 11 2012 9 46 08 To 6 11 2012 6 11 2012 16 23 10 Secondary Parameter ix Show 20 x entries per page Page ggi 12 Forward Select current log to copy Num Date Time L L L N Current KWH KVA CE KW PF 36 6 11 2012 16 23 10 205 5 205 5 204 9 118 3 119 0 118 4 101 0 78 4 94 9 100 7 27613 1 21382 2 24526 1 11 9 9 3 11 2 11 9 9 3 10 5 1 00 1 00 0 35 6 11 2012 16 13 10 205 5 205 5 204 9 118 3 119 0 118 4 101 0 78 4 94 9 100 7 27613 1 21382 2 24526 1 11 9 9 3 11 2 11 9 9 3 10 5 1 00 1 00 0 34 6 11 2012 16 03 10 205 5 2
11. security level auth priv passwords and access level for each account respectively e x i e lome 3 Logo NELTA eo sightPower SNMP IPV6 for PDC Web e power behind competitiveness System Notification SNMP Access System Notification SNMPv3 USM SNMPv3 USM o gt SNMPv3 USM SNMP Trap Auth Protocol MD5 Context Name cn1027 Mail Server Priv Protocol CBC DES 7 Auth Password Priv Password gt 8 bytes gt 8 bytes User Name Security Level Access Level Event Level 16 bytes max ity test Auth Priv iy 12345678 87654321 Read Write vi noAuth noPriv v Disable v noAuth noPriv a i I Disable v noAuth noPriv v Disable noAuth noPriv x Disable noAuth noPriv x Disable noAuth noPriv w Disable noAuth noPriv w Disable 39 A NELTA SNMP Trap SNMP Trap alerts users to event occurrences To enable SNMP Trap add Target IP addresses to the list Specify the community string port trap type and event level then click Add Click on an entry to update settings or remove it from the list elle Kl sereno M NELT a InsightPower SNMP IPv6 for PDC Web System Notification SNMP Access System Notification SNMP Trap SNMPv3 USM gt SNMP Trap Target List Target IP 0 0 0 0 a Communi
12. status alarm MainCB FregL1 Clear Event Log 43 A NELTA Chapter 6 SNMP Device Firmware Upgrade With the provided program EzSetting you can effortlessly perform a firmware up grade on your SNMP devices via LAN Please refer to the following instructions 2 InsightPower EzSetting v2 0 6 Press Discover button to search all of the SNMP devices in the LAN Discover Then select one of device in the Device List which you would like to configure or upgrade it But before to do that please provide the account name and password by pressing the Modify button Configuration is used to setup the IP address netmask enable or disable 7 networking services Upgrade button is used to load the device firmware file then transmit it to the single selected device Ignore the checkbox o Device List IP Address Host Name Account Password Version Model Product lt gt I Please mark the checkbox of the devices which are listed in the Device List then press the Batch Upgrade button to upgrade all of the marked devices sequentially LAN 172 16 186 104 Subnet 172 16 186 0 IPv4 Mask IPv6 Prefix length 255 255 254 0 Add an new item of SNMP device to the Device List manually Modify Set the account and password for the selected device Re Remove the selected device from the Device List Step 1 The subnet mask allows you to d
13. the network Provide additional in formation for system contact and location which are left blank by default InsightPower SNMP IPv6 for PDC 32 Chapter 5 InsightPower SNMP IPv6 for PDC Web Web eco DM C NELTA The power m competitiveness InsightPower SNMP IPv6 for PDC Web ini System Administration User Manager System Administration Web TCP IP gt Web gt SSL Certificate Web O HTTP Enable Disable Certificate File PEM format HTTPS Enable Disable HTTP Port 80 Update the certificated file which is generated by openssl for new SSL connections Console E FTP HTTPS Port 443 Time Server Web Refresh Period 10 Seconds Syslog Web Enable disable HTTP HTTPS protocols Change default ports HTTP 80 HTTPS 443 Specify the web refresh period default 10 seconds The De vice Status and Environment pages automatically refresh and update the provided information after the specified time elapses e SSL Certificate SSL Certificate can be used to encrypt data to improve connect security The SNMP IPv6 supports PEM format generated by OpenSSL Click Browse to upload a certificate file NOTE For more information regarding generating a private SSL certificate file please refer to Chapter 7 Troubleshooting O12 or visit http www openssl org 33 A NELTA Console This page allows you to enable or disable
14. throught SNTP protocol if possible Refer to Chapter 5 InsightPower SNMP IPv6 for PDC Web for complete configurations 11 A NELTA 4 3 Configuring via Telnet Step 1 Use a CAT5 network cable to connect the SNMP IPv6 s Network port to the network Step 2 Connect the workstation Windows or Linux to the LAN that the SNMP IPv6 is connected to Step 3 For Windows launch DOS prompt mode Start Run key in cmd and press Enter For Linux launch Shell Step 4 Enter the following command telnet InsightPower or telnet IP address to initiate telnet connection with the SNMP IPv6 Step 5 When connection is established enter Administrator s account and password default admin password case sensitive The Main Menu will appear on the screen Please refer to 4 5 Configuring via Text Mode for more information 1 The SNMP IPv6 terminates idle connections after 60 seconds 2 Refer to Chapter 5 InsightPower SNMP IPv6 for PDC Web for complete configurations 4 4 Configuring through COM Port If a network connection is not available at your location you can still set up the SNMP IPv6 via COM port connection Please follow the instructions below NOTE If you are running a non Windows system refer to your system s user manual for Telnet clients Step 1 Use the provided RJ45 to DB9 cable to connect the SNMP IPv6 s COM port to the workstations COM port InsightPower SNMP IPv6 for PDC 12 Chapter 4
15. 05 5 204 9 118 3 119 0 118 4 101 0 78 4 94 9 100 7 27613 1 21382 2 24526 1 11 9 9 3 11 2 11 9 9 3 10 5 1 00 1 00 0 33 6 11 2012 15 46 12 205 5 205 5 204 9 118 3 119 0 118 4 101 0 78 4 94 9 100 7 27613 1 21382 2 24526 1 11 9 9 3 11 2 11 9 9 3 10 5 1 00 1 00 0 32 6 11 2012 15 36 12 205 5 205 5 204 9 118 3 119 0 118 4 101 0 78 4 94 9 100 7 27613 1 21382 2 24526 1 11 9 9 3 11 2 11 9 9 3 10 5 1 00 1 000 31 6 11 2012 15 16 55 205 5 205 5 204 9 118 3 119 0 118 4 101 0 78 4 94 9 100 7 27613 1 21382 2 24526 1 11 9 9 3 11 2 11 9 9 3 10 5 1 00 1 00 0 30 6 11 2012 14 53 58 206 6 206 8 207 2 119 5 119 1 119 8 0 0 25 6 16 9 253 05 4343 185 9 0 0 3 0 2 0 0 0 2 9 2 0 0 00 0 95 1 29 6 11 2012 14 43 58 206 6 206 8 207 2 119 5 119 1 119 8 0 0 25 6 16 9 253 05 4343 185 9 0 0 3 0 2 0 0 0 2 9 2 0 0 000 951 28 6 11 2012 14 33 58 206 6 206 8 207 2 119 5 119 1 119 8 0 0 25 6 16 9 25 3 0 5 434 3 185 9 0 0 3 0 2 0 0 0 2 9 2 0 0 000 951 27 6 11 2012 14 23 58 206 6 206 8 207 2 119 5 119 1 119 8 0 0 25 6 16 9 253 0 5 4343 185 9 0 0 3 0 2 0 0 0 2 9 2 0 0 000 951 26 6 11 2012 14 13 58 206 6 206 8 207 2 119 5 119 1 119 8 0 0 25 6 16 9 253 05 4343 185 9 0 0 3 0 2 0 0 0 2 9 2 0 0 000 951 25 6 11 2012 14 03 58 206 6 206 8 207 2 119 5 119 1 119 8 0 0 25 6 16 9 25 3 05 4343 185 9 0 0 3 0 2 0 0 0 2 9 2 0 0 000 951 24 6 11 2012 13 53 58 206 6 206 8 207 2 119 5 119 1 119 8 0 0 25 6 16 9 25 3 05 4343 185 9 0 0 3 0 2 0 0 0 2 9 2 0 0 000 951 23 6 11 2012 13 42 46 206 6 206 8 207 2 119 5 119 1 119
16. 8 0 0 25 6 16 9 25 3 05 4343 185 9 0 0 3 0 2 0 0 0 2 9 2 0 0 000 951 22 6 11 2012 13 32 46 206 6 206 8 207 2 119 5 119 1 119 8 0 0 25 6 16 9 253 05 4343 185 9 0 0 3 0 2 0 0 0 2 9 2 0 0 000 951 21 6 11 2012 13 22 46 206 6 206 8 207 2 119 5 119 1 119 8 0 0 25 6 16 9 253 05 4343 185 9 0 0 3 0 2 0 0 0 2 9 2 0 0 000 951 20 6 11 2012 13 12 46 206 6 206 8 207 2 119 5 119 1 119 8 0 0 25 6 16 9 253 05 4343 185 9 0 0 3 0 2 0 0 0 2 9 2 0 0 000 951 19 6 11 2012 13 02 46 206 6 206 8 207 2 119 5 119 1 119 8 0 0 25 6 16 9 253 05 4343 185 9 0 0 3 0 2 0 0 0 2 9 2 0 0 00 0 95 1 18 6 11 2012 12 52 46 206 6 206 8 207 2 119 5 119 1 119 8 0 0 25 6 16 9 253 05 4343 185 9 0 0 3 0 2 0 0 0 2 9 2 0 0 00 0 95 1 17 6 11 2012 12 42 46 206 6 206 8 207 2 119 5 119 1 119 8 0 0 25 6 16 9 253 05 4343 185 9 0 0 3 0 2 0 0 0 2 9 2 0 0 00 0 95 1 ral m ad Clear History Data 5 1 3 Environment This page only appears when an EnviroProbe is connected You can check the tem perature humidity readings and the status of input contacts e lese e Device Mon 06 11 2012 PM 04 33 48 Environment gt Environment Sensor Information Input Contacts Contact Setting Temperature 31 3 C Smoke R1 Normal Smoke R1 Normal Open 88 3 F Fire R2 Normal Fire R2 Normal Open Humidity 43 Leak R3 Normal Leak R3 Normal Open Door R4 Normal Door R4 Normal Open 29 A NELTA 5 1 4 Configura
17. IPv6 Address The IPv6 address 7 IPv6 Prefix The IPv6 prefix length Length IPv6 Gateway IP The IPv6 gateway s IP address ee 9 IPv6 DNS IP IPv6 Domain Name Server s IP address DHCPV6 Enable disable DHCPV6 protocol Enable b Host Name The Host Name for the SNMP INSIGHTPOWER NetBIOS IPv6 17 A NELTA Description Default System The System Contact information Contact System The System Location information Location Auto Enable disable automatic transfer Negotiation rate 10 100Mbps negotiation If the Auto Negotiation is dis abled you can specify the trans fer rate If the Auto Negotiation is dis abled you can specify the duplex mode Telnet Idle Time Telnet connection time out 60 Seconds setting HTTP Server Enable HTTPS Server Enable Telnet Server Enable SSH SFTP Server Enable FTP Server Disable Syslog Disable HTTP Server Port 80 HTTPS Server Port 443 Telnet Server Port BS SSH Server Port 22 FTP Server Port 21 Syslog Serverl Syslog Server2 Syslog Server3 Syslog Server4 SNMP Get Set Port 161 Back To Previous Menu Please Enter Your Choice gt InsightPower SNMP IPv6 for PDC 18 Chapter 4 System Configurations No Item Description Default KOR meg M res sever sem as SSH Server Port SSH port FTP Server Port FTP port c Syslog Server 1 The Host Name of remote Syslog Server 1 d Syslog Se
18. Manual InsightPower SNMP IPv6 for PDC ii Table of Contents Table of Contents Chapter 1 Important Safety Instructions 1 1 1 Warnings 1 1 2 Standard Compliance 1 Chapter 2 Introduction 2 2 1 Product Description 2 2 2 Features _ _ ___ ___ 2 2 3 Package Contents 3 2 4 Interface A Chapter 3 Installation 7 Chapter 4 System Configurations 8 4 1 Configuring via InsightPower SNMP IPv6 for PDC Web 8 4 2 Configuring with EzSetting 10 4 3 Configuring via Telnet 12 4 4 Configuring through COM Port 12 4 5 Configuring via Text Mode 15 Chapter 5 InsightPower SNMP IPv6 for PDC Web 21 5 1 Device 22 5 1 1 Status 222 ne onan nnnn nena nn 23 Information 24 VAS S A Jo a aA a ieee aaa a S ae o o 25 Primary o a 26 SECONUATY a 21 Panel _ T _
19. NMP IPv6 for PDC Web To set up the SNMP IPv6 via your web browser please follow the instructions be low Step 1 Use a CAT5 network cable to connect the SNMP IPv6 s Network port to the network Launch your web browser In the address bar enter the SNMP IPv6 s default Host Name InsightPower or default IP address 192 168 1 100 If you are unable to connect please see Chapter 7 Trou bleshooting O6 InsightPower SNMP IPv6 for PDC 8 Chapter 4 System Configurations If you have previously changed the SNMP IPv6 s Host Name or IP address connect with the new settings Step 2 Log in as Administrator default account password admin password case sensitive Step 3 Specify your preferred display language default English from the drop down menu on the top right of the page The SNMP IPv6 remembers your language preference In the following instructions English is chosen as the display language Step 4 Click System Administration User Manager Manage your login accounts and passwords under the Local Authentication subhead The access permission for the account types is shown as follows 1 Administrator Allowed to modify all settings 2 Device Manager Allowed to modify device related settings 3 Read Only User Only allowed to view settings without the permis sion to make changes You can manually specify whether users are allowed to log in from other LANs If you wish to block login attempts from
20. P client Q15 How to test SNMPv3 in Linux Before you can access the SNMP OID Object Identifier via SNMPv3 protocol the SNMPv3 USM table must be organized Please refer to 5 2 2 Notification SNMPv3 USM for more information To test SNMPv3 in Linux launch shell and key in the following command snmpwalk v 3 u lt user gt l authPriv A lt pass word gt X lt password gt n lt context name gt t 3 lt ip gt ba l 0 v 1 for SNMPv1 3 for SNMPv3 Follow the security levels They are noAuthNoPriv authNoPriv and authPriv u The user name which is assigned from SNMPv3 USM table A The Auth Password which is assigned from SNMPv3 USM table InsightPower SNMP IPv6 for PDC 52 Chapter 7 Troubleshooting X The Priv Password which is assigned from SNMPv3 USM table n The Context Name which is assigned from SNMPv3 USM table t Timeout in seconds lt ip gt The IP address of the SNMP IPv6 lt oid gt The next available SNMP OID for example 1 3 6 1 2 1 1 1 0 Please refer to the RFC1213 MIB 53 A NELTA Appendix A Specifications Model Name InsightPower SNMP IPv6 for PDC Operating Temperature Storage Temperature 40 125 C Operating Humidity 0 90 Non condensing NOTE Refer to the rating label for the safety rating All specifications are subject to change without prior notice InsightPower SNMP IPv6 for PDC 54 Appendix B Warranty Appendix B Warranty
21. __ 28 5 1 2 Data Log 28 5 1 3 Environment 29 5 1 4 Configuration 30 iii A NELTA Connection 30 DALO i cc ee ce ee le 30 EVMONMEN Oe a ln el 30 5 2 System _______ 31 5 2 1 Administration 31 User Manage soy 31 TCP IP 32 Web 022 e e eee 33 Console 2222220200202020 nnn nnn nnn nnn nnn 34 FTP 34 TIME SEE o case aaa ee 35 Seo S A e eee 36 Batch Configuration 36 Upgrade 222_______________ 38 5 2 2 Notification 38 SNMP ACCESS ene 38 SNMPV3 USM AAA 39 SNMP Trap _ _ eee eee 40 Mail Server _ _ _ T_rrrr______ w 41 EventLeval ____r_____ ___ _ ___ se 42 5 2 3 History _2 Tz __ 43 Chapter 6 SNMP Device Firmware Upgrade 4A Chapter 7 Troubleshooting 47 Appendix A Specifications 54 Appendix B Warranty 55 InsightPower SNMP IPv6 for PDC iv Chapter 1 Important Safety Instructions Chapt
22. al packing materials came with the unit No o o 0 Item InsightPower SNMP IPv6 for PDC RJ45 to DB9 cable Software amp User s Manual CD Setting Guide for SNMP IPv6 Card s DIP Switches Cover Quantity 1 PC FPC 1 PC LPC 3 PCS A NELTA 2 4 Interface On the SNMP IPv6 you can find a Network port a COM port LED indicators a Reset button and DIP switches Please refer to the table below Top view Network Port 1802308 0030W U RISE REVA COM Port O amaA _ b ED Reset Button 000000000000 DIP Switches o Le o Network Port DIP Switches LED COM Port Reset Button Indicators Description Network Connects to the network Port COM 1 Connects to a workstation with the provided RJ45 to DB9 Port cable 2 Connects to an EnviroProbe optional InsightPower SNMP IPv6 for PDC 4 Chapter 2 Introduction No Item Description Reset Resets the SNMP IPv6 This does not affect the PDC Button LED When the SNMP IPV6 is initializing or upgrading firmware the Indicators two LED indicators flash simultaneously to show its status Refer to the following Rapid simultaneous flashing every 50ms Initialization or firmware upgrade in progress e Slow simultaneous flashing every 500ms Initialization failed WARNING Do NOT remove the SNMP IPV6 or dis A connect PDC s input power duri
23. before to do that please provide the account name and password by pressing the Modify button Subnet Configuration is used to setup the IP address netmask enable or disable Configuration eee networking services IPv4 Mask IPv6 Prefix length Upgrade button is used to load the device firmware file then transmit it to Upgrade the single selected device Ignore the checkbox Upgrade 255 255 254 0 Device List IP Address Host Name Account Password Version Model Product O 172 016 186 161 EMS1 27227777 01 11 02 EMS2000000 O 172 016 186 235 POUL 01 11 09 P0U1113 Add an new item of SNMP device D 172 016 186 053 PDU2 01 11 09 POU1113 to the Device List manually 172 016 186 136 INSIGHTPOW GES203NH20098 Modify A 172 016 186 132 INSIGHTPOW 1 16h GES 102R1120 Set the account and password for the selected device Remove Remove the selected device from the Device List Select All Deselect All Please mark the checkbox of the devices which are listed in the Device List then press the Batch Upg Batch Upgrade button to upgrade all of the marked devices sequentially 1 If you want to search SNMP devices in a different domain change the Subnet and IPv4 IPv6 Prefix Length and click Discover 2 If the SNMP IPv6 can not be found check UDP port 3456 on the worksta tion you are using Make sure it is open InsightPower SNMP IPv6 for PDC 10 Step 5 Chapte
24. ch you want to configure Select the modified configure ini file and press the Upload button to upload the file Wait for about 10 seconds for the system to update the changes InsightPower SNMP IPv6 for PDC 36 SNMP parameters at one time Please follow the following steps to complete the process Press the Download button to download the snmp ini file which includes all of the system parameters Please follow the file format There must has a Section before item_name item_value And the last line must be End section Edit the snmp ini file by the text edit software Remove the items which you don t want to be changed just leave the items which you want to configure Select the modified snmp ini file and press the Upload button to upload the file Wait for about 10 seconds for the system to update the changes Chapter 5 InsightPower SNMP IPv6 for PDC Web The batch configuration offers guick and effortless setup on multiple SNMP IPv6 units After system configuration is completed export configuration file and import on other units to duplicate settings and parameters e System Configuration This includes settings saved under the System administration tab To download a configuration file simply click Download configure ini To up load a configuration file click Browse select the configuration file you wish to upload and click Upload NOTE If you assign a static IP to your SNMP IPv6 open t
25. communication error e System overload V L Under voltage O U C UV oc PE Poorpowertacar n j U CM V C T C 23 A NELTA Information This page shows a quick review of PDC s status and system information includ ing model serial number capacity input output voltage and frequency Device System Status System Primary Secondary Panel 1 Panel 2 Reloa Reload System Status Main Panel 1 Panel 2 X1 X2 HT VL Li L2 VU L3 GF DSP FRAM EPO REPO so LCM gt Status fs Primary UV ov oc UC VT PF Secondary UV ov oc UC VT PF Panel 1 OverCurr UnderCurr OverTHD PoorPF HighCurr Panel 2 OverCurr UnderCurr OverTHD PoorPF HighCurr gt System Information Information i j PDC5503A1250098 Serial number 2210389001000 Capacity 100 KVA Input 220 V Output 120 V Freguency 60 Hz InsightPower SNMP IPv6 for PDC 24 Chapter 5 InsightPower SNMP IPv6 for PDC Web System In this page check PDC s status statistics and settings 4 Hour Statistics shows circuit readings that are recorded during the past four hours To change a setting simply click on it or select from the drop down menu on the bottom of the page Make sure to click Submit to take effect after the changes are made Device System Status Information System Primary Secondary Panel 1 Panel 2 Status M Main Panel 1 Panel 2 Xi X2 HT VL VU Li L2 L3 GF DSP FRAM EPO
26. creen Please refer to 4 5 Configuring via Text Mode for more information InsightPower SNMP IPv6 for PDC 14 CER Configuring via Text Mode Chapter 4 System Configurations You can configure the SNMP IPv6 via text mode by using Telnet SSH clients such as HyperTerminal and PuTTY In this section you can find descriptions and default set tings Main Menu Card Version 01 00 00 Address 00 30 ab 25 e9 le ser Manager TCP IP Setting Network Parameter Time Server Soft Restart Reset All To Default Exit Without Save Save And Exit Plea ite 24 3 4 se Enter Your Choice gt RADIUS Auth Disable server secret Porc Local Auth Sig L6 lt VIS Administrator Account admin Password KKKKAKKAA Limitation Only in This LAN Device Manager Account device Password kkkkkkkk Limitation Only in This LAN Read Only User Account user Password TS SS OS LOE OS Limitation Allow Any Back To Previous Menu Please Enter Your Choice gt 15 A NELTA No Item Description Default m RADIUS Auth ae whether RADIUS login is al Server The RADIUS server name The RADIUS port 1812 Administrator 5 admin Account The default account password for the Administrator Administrator case sensitive 6 password Password Rar Nator Restrict Administrator login area Sm Limitation 9 This LAN Device Manager The default account password case
27. ct the SNMP IPv6 s Network port to the network Step 2 Launch your web browser In the address bar enter the SNMP IPv6 s Host Name http InsightPower or IP address For encrypted connection enter https InsightPower or https 192 168 1 100 Step 3 When connection is established the login page appears Enter your ac count and password default admin password BO dE InsightPower SNMP IPv6 for PDC Login Site IP 172 16 186 82 Copyright 2011 Delta Electronics Inc All Rights Reserved 1 If you have previously changed the SNMP IPv6 s Host Name or IP address please connect with new settings If the login page is accessible but you are unable to log in with correct account and password additional network configuration may be needed The cause could be the IP subnet of the computer you are logging in to is different from the SNMP IPv65s To solve this issue please refer to Chapter 7 Troubleshooting Q3 The SNMP IPve will automatically log off idle connections after 30 min utes 21 A NELTA 5 1 Device In this page check PDC s system status and readings This page automatically refreshes every 10 seconds Click Reload to manually refresh A slide in window shows to provide additional information when you click on the fl icon Click Close the slide in window will disappear To change a setting select from the drop down menu or simply click on the item Input new value in the text box and click Submit
28. current alarm s A gt Recover from branch over curren alarm s a Branch under curren alarm s o Recover from branch under curren alarm s M Branch over current demand alarm s o Recover from branch over curren demand alarm s Branch under curren demand alarm s N o Recover from branch under curren demand alarm s N Branch over KW demand alarm s 8 Recover from branch over KW demand alarm s lt N wo Branch under KW demand alarm s 3 N gt Recover from branch under KW demand alarm s lt Device Three event levels including information blue warning yellow and alarm red can be assigned to PDC s events Click Submit to take effect Env Probe Assign event levels to EnviroProbe s events Click Submit to take effect InsightPower SNMP IPv6 for PDC 42 Chapter 5 InsightPower SNMP IPv6 for PDC Web 5 2 3 History VERA In this page check event entries Click lt lt and gt gt to turn pages Click on a page number to jump to that page To check event entries recorded during a time period select the dates and click Ap ply To download the entire event log click Download All and a pop up window prompts you to save the file csv You can open or edit the file in Microsoft Excel Click Clear Event Log to erase all event entries It is recommended to download and back up your event log first Ea e e s
29. device Account sensitive for the Device Manager This Device Manager account is only permitted to change 9 Password device related settings password Device Manager Only in a Restrict Device Manager login area This LAN Read Only The default account password case User Account sensitive for Read Only User This account is only allowed to view set tings without the permission to make password changes Read Only Restrict Read Only User login area Allow Any Read Only User Password InsightPower SNMP IPv6 for PDC 16 Chapter 4 System Configurations TCP IP Setting IPv4 Address 192 168 001 100 IPv4 Subnet Mask 255 205 205 000 IPv4 Gateway IP 192 168 001 254 IPv4 DNS or WINS IP 192 168 001 001 DHCPv4 Client Enable IPv6 Address fe80 230 abff fe25 900 IPv6 Prefix Length 64 IPv6 Gateway IP IPv6 DNS IP a DHCPv6 Enable Host Name NetBIOS INSIGHTPOWER System Contact System Location Auto Negotiation Enable Speed 100M Duplex Full i Telnet Idle Time 60 Seconds 0 Back To Previous Menu Please Enter Your Choice gt No Item Description Default IPv4 Address The IPv4 address 192 168 001 100 2 IPv4 Subnet The IPv4 subnet mask setting 255 255 255 000 Mask IPv4 Gateway IP The IPv4 gateway s IP address 192 168 001 254 4 IPv4 DNS or IPv4 Domain Name Server or 192 168 001 001 WINS IP WINS IP 5 DHCPv4 Client Enable disable DHCPv4 protocol 6
30. efine the device discovery range in the specified subnets Make sure the SNMP device you wish to upgrade is in the subnet that is specified If it is not please modify the subnet and sub net mask InsightPower SNMP IPv6 for PDC 44 Chapter 6 SNMP Device Firmware Upgrade Step 2 Click Discover A list of SNMP devices is shown 2 InsightPower EzSetting v2 0 6 LAN Press Discover button to search all of the SNMP devices in the LAN 172 16 186 104 v Then select one of device in the Device List which you would like to configure or upgrade it But before to do that please provide the account name and password by pressing the Modify button Configuration is used to setup the IP address netmask enable or disable 172 16 186 0 networking services IPv4 Mask IPv6 Prefix length Upgrade button is used to load the device firmware file then transmit it to Upgrade the single selected device Ignore the checkbox Upgrade Device List IP Address Host Name Account Password Version Model Product O 172 016 186 161 EMS1 2222277 01 11 02 EMS2000000 O 172 016 186 235 POUL 01 11 09 POU1113 Add an new item of SNMP device O 172 016 186 053 PDU2 01 11 09 PDU1113 to the Device List manually O 172 016 186 136 INSIGHTPOW 01 11 02 GES203NH20098 O 172 016 186 132 INSIGHTPOW 1 16h GES 102R1120 Set the account and password for the selected device Remove the selected device lt from the Dev
31. er 1 Important Safety Instructions 1 1 Warnings The InsightPower SNMP IPv6 for PDC hereafter referred to as SNMP IPV6 is de signed to work with a PDC Power Distribution Cabinet It needs to be installed in the PDC s SNMP slot Do not place or use this unit in the presence of flammable substances Do not attempt to disassemble the unit Do not attempt to perform any internal modifications on the unit Do not attempt to fix replace internal components When repair is needed re fer all servicing to your local dealer or service personnel Do not allow any objects or liquids of any kind to penetrate the unit Always follow this User Manual to install and operate this unit Do not play the included CD with a conventional CD player This could generate loud noise at a level that could result in permanent hearing loss P Standard Compliance e EN 55022 2006 A1 2007 Class A EN 61000 3 3 1995 A1 2001 A2 2005 EN 55024 1998 A1 2001 A2 2003 IEC 61000 4 2 1995 A1 1998 A2 2000 IEC 61000 4 3 2006 IEC 61000 4 4 2004 IEC 61000 4 5 2005 IEC 61000 4 6 2007 IEC 61000 4 8 1993 A1 2000 IEC 61000 4 11 2004 1 A NELTA Chapter 2 Introduction 2 1 Product Description The InsightPower SNMP IPv6 for PDC is an intelligent device that serves as an inter face between the PDC and your network It communicates with the PDC to obtain readings settings and status information from system
32. ereno G NELTA Er InsightPower SNMP IPv6 for PDC Web System History gt EventLog Paget Page lt lt 1 2 B 4 5 gt gt Download All From 10 05 2011 MM DDIYYYY to 10 05 2011 MM DD YYYY Apply Date Time Level Event Log 10 05 2011 16 22 40 System admin login to the WEB from 172 16 176 14 10 05 2011 15 40 01 Warning Main status alarm MainCB FregL 1 10 05 2011 15 40 00 Severity Secondary status alarm UV 10 05 2011 15 40 00 Severity Primary status alarm UV 10 05 2011 15 40 00 Severity PDC device connected BuslD 3 10 05 2011 15 00 36 System admin login to the WEB from 172 16 186 167 10 05 2011 14 59 15 System admin login to the WEB from 172 16 186 98 10 05 2011 14 59 02 System Logout from the WEB 10 05 2011 14 52 14 System admin login to the TELNET from 172 16 186 98 10 05 2011 14 47 33 System admin login to the WEB from 172 16 186 98 10 05 2011 14 18 02 System admin login to the WEB from 172 16 186 167 10 05 2011 14 16 58 Severity Secondary status alarm UV 10 05 2011 14 16 58 Severity Primary status alarm UV 10 05 2011 14 16 58 Warning Main status alarm MainCB FregL 1 10 05 2011 14 16 58 Severity PDC device connected BusID 3 10 05 2011 14 14 42 Warning Main status alarm Panel2CB 10 05 2011 14 14 42 Severity PDC device connected BuslD 6 10 05 2011 14 07 11 Severity Secondary status alarm UV 10 05 2011 14 07 11 Severity Primary status alarm UV 10 05 2011 14 07 11 Warning Main
33. ess _ n a Device Administration User Manager TCP IP Web Console FTP Time Server Syslog Batch Configuration Upgrade System System Administration TCP IP gt TCP IP gt System TCP IP Settings for IPv4 System DHCP Client Enable O Disable IP Address 10 0 10 187 Subnet Mask 255 255 255 0 Gateway IP 10 0 10 254 DNS IP 10 0 10 254 Search Domain deltaww com TCP IP Settings for IPv6 DHCP Client Enable O Disable IP Address fe80 230 abff feaa ff04 Prefix Length 64 Host Name System Contact System Location INSIGHTPOWER Gateway V6IP DNS V6IP IPv4TCP IP Settings for IPv4 Specify IPv4 IP address subnet mask gateway IP DNS IP and search domain If IPv4 DHCP is enabled the DHCP server automatically assigns an IP ad dress to the SNMP IPv6 If the Host Name you provided cannot be found the system appends the search domain to your Host Name IPv4TCP IP Settings for IPv6 Specify IPv6 IP address subnet mask gateway IP DNS IP and search domain If IPv6 DHCP is enabled the DHCP server automatically assigns an IP ad dress to the SNMP IPv6 If the Host Name you provided cannot be found the system appends the search domain to your Host Name e System Specify the SNMP IPv6 s Host Name on
34. external connections select Only in This LAN Otherwise select Allow Any Step 5 Click System Administration TCP IP to set Host Name IP address Subnet Mask and Gateway IP for the SNMP IPv6 Step 6 Click Time Server to manually set time and date for the system or enable automatic time synchronization between the SNMP IPv6 and the time servers To completely set up your SNMP IPv6 please refer to Chapter 5 Insight Power SNMP IPv6 for PDC Web 9 A NELTA 4 2 Configuring with EzSetting Included in the provided CD the EzSetting compatible with Windows 2000 2003 2008 XP Vista 7 allows you to easily configure your SNMP IPv6 and upgrade firm ware on your SNMP devices Follow the instructions below Step 1 Step 2 Step 3 Step 4 Use a CAT5 cable to connect the SNMP IPv6 s Network port to the net work Make sure the two DIP switches of the SNMP IPv6 are set to the OFF posi tion Normal Mode to enable network communication Make sure the workstation and the SNMP IPV6 are on the same LAN Insert the provided CD in the CD ROM drive From the root directory launch EzSetting Click Discover to search all available SNMP devices on the LAN A list of devices will be shown R InsightPower EzSetting v2 0 6 LAN Press Discover button to search all of the SNMP devices in the LAN 172 16 186 104 v Then select one of device in the Device List which you would like to configure or upgrade it But ERY
35. fication SNMP Access Oo System Notification SNMP Access SNMPv3 USM gt Port Configuration SNMP Server Port 161 SNMP Trap Mail Server Event Level IP address 0 0 0 0 represents it allows to Allowed NMS IP 10 0 10 0 24 receive the SNMP packets from any host Community String public Access Level Read Write Ada Update NMS IP Community Access Level 0 0 10 0 24 10 0 10 0 24 172 16 186 0 24 InsightPower SNMP IPv6 for PDC public afu public 38 Read Write Read Write Read Only Chapter 5 InsightPower SNMP IPv6 for PDC Web The SNMP IPV6 supports SNMP protocol and SNMP NMS Network Manage ment System which are commonly used to monitor network devices for situ ations that call for administrative attention To prevent unauthorized access specify the allowed NMS IP addresses their respective community strings and access levels You can assign up to 256 IP addresses NOTE If IP address 0 0 0 0 is added to the list the NMS IP access restriction is ignored SNMP IPv6 will check the community string to identify the ac cess level and permission according to your settings SNMPv3 USM The SNMPv3 protocol features packet encryption and user authentication to improve connection security The SNMPv3 USM User Session Management al lows you to assign eight user names whose access privileges are granted via the SNMPv3 protocol Specify the user name
36. he InsightPower SNMP IPv6 for PDC Web Please refer to 5 2 1 Administration Web Q13 How to generate DSA RSA and Public keys for SSH For Linux 1 Please download and install OpenSSH from http www openssh org 2 Launch Shell and enter the following commands to create your own keys please ignore it when prompted to provide passphrase InsightPower SNMP IPv6 for PDC 50 Chapter 7 Troubleshooting DSA Key ssh keygen t dsa RSA Key ssh keygen t rsa 3 Upload DSA and RSA keys to the InsightPower SNMP IPv6 for PDC Web Please refer to 5 2 1 Administration Console for more information For Windows 1 Please download and install PuTTY from http www putty org 2 Run puttygen exe from the installed directory 3 Select SSH 2 RSA from the Parameters area and click Key Generate key pair to generate a RSA key 4 Click Conversions Export OpenSSH Key and assign a filename to the RSA key Please ignore it when prompted to provide key passphrase 5 Select SSH 2 DSA from the Parameters clickt Key Generate key pair to generate a DSA key 6 Click Conversions Export OpenSSH Key and assign a filename to the DSA key Please ignore it when prompted to provide key passphrase 7 Copy the generated key from the text box paste in a text editor and save as a text file Z PnITY Key Generator File Key Conversions Help Key Public key for pasting into OpenSSH authorized_keys file ssh dss SASSB3NzaCT kc3M444C4 V
37. he configuration file with a text editor such as Notepad or Word Pad under the System section remove the following line IP xxx xxx xxx xxx TO modify as sign IP address for the SNMP IPv6 please see Chapter 4 System Con figurations e SNMP Configuration This includes settings under the System Notification tab To download a configuration file simply click Download To upload a configuration file click Browse select the file you wish to upload and click Upload NOTE Follow the instructions shown on this page to modify the configuration files 37 A NELTA Upgrade In this page upgrade SNMP IPv6 s firmware and check the current firmware version Click Browse choose the firmware patch file and click Upload The upgrade process should take about one minute to complete Device i System Administration User Manager System Administration Upgrade TCP IP gt Network Card Firmware Web Current Ver 01 12 10 Console Firmware File a _ Browse DescriptionThis feature is used to update the network card firmware Please follow the following steps to complete the process Time Server Syslog Select the network card firmware file and press the Upload button to upload the file to the network card Batch Configuration Wait about 1 minute for the network card to reprogram the flash and reboot again Upgrade 5 2 2 Notification SNMP Access Device System Noti
38. ice List Select All Deselect All Please mark the checkbox of the devices which are listed in the Device List then press the Batch Upgr Batch Upgrade button to upgrade all of the marked devices sequentially Subnet Step 3 Select a device from the Device List click Modify and key in Administra tor account and password IP amp Account SNMP Device Address IP Address Administrator Account Account Default admin Password Default password 45 A NELTA Step 4 Click Upgrade The upgrade dialog box pops up Click Browse to select a valid firmware binary file Verify the firmware version shown under File Information and then click Upgrade Now to continue Select Firmware File la Firmware File Name File Information Step 5 The upgrade process should take about 20 seconds Upgrading Now Step 6 When the upgrade is completed the following dialog box appears It takes about 1 minute for the device to reboot Upgrade OK Now the SNMP Web device is rebootng InsightPower SNMP IPv6 for PDC 46 Q1 Q2 Chapter 7 Troubleshooting Chapter 7 Troubleshooting How to set up an SNTP server on my workstation for the SNMP IPv6 to syn chronize To enable SNTP services in Windows XP go to Start Control Panel Add Remove Programs Add Remove Windows Components Networking Services check Simple TCP IP Services OK To enable time synchroni zation you need to
39. in information is prompted key in rstadmin within 30 sec onds and press enter The Administrator account and password are now reset to default admin password Q11 How to enable IPv6 in Windows XP If you are running Windows XP please enable IPv6 first click START RUN and enter ipv 6 install The SNMP IPv6 supports IPv6 with no additional configurations reguired However please note that IPv6 is automatically dis abled if an identical LLA Local link Address already exists on the LAN If the SNMP IPv6 obtains both IPv4 and IPv6 records from DNS resolution the IPv4 is used as the primary IP address for the given Host Name To learn more information regarding IPv6 compatibility please visit IETF http tools ietf org html or IPv6 Ready Logo Program http www ipv6ready org O12 How to generate a private SSL certificate file in PEM format for HTTPs connection To ensure connection security between the SNMP IPv6 and your worksta tion you can create your own SSL certificate file Please download and install OpenSSL Toolkit from http www openssl org Launch Shell or DOS prompt mode and enter the following command to create your own certificate file openssl reg x509 nodes days 3650 newkey rsa 1024 keyout cert pem out cert pem 1 Answer the prompted questions Proceed with the given directions Once it is completed a file named cert pem is created in the current working di rectory 2 Upload cert pem to t
40. ith SNTP servers Please note that if the assigned SNTP server is not responsive the event and data log will not be recorded even when the SNTP is enabled Administration User Manager TCP IP Web Console FTP Time Server Syslog Batch Configuration Upgrade System System Administration Time Server System Time SNTP Manual gt Simple Network Time Server Time Zone GMT 08 Beijing Taipei Primary Time Server 172 16 1 86 Secondary Time Server POOL NTP ORG Period Time o Day s 2 Hour s O Enable Daylight Saving MM DD From 04 01 to 11 01 Simple Network Time Server gt Manual Set Current Time Refer to Local PC Time Date 06 30 2011 MM DD YYYY Time 17 18 42 hh mm ss From the dropdown menu select the time zone for the location where the SNMP IPV6 is located Specify the IP addresses or domain names for the pri mary and secondary time servers The SNMP IPv6 synchronizes with the first responding server based on the frequency you specified If daylight saving is enabled during the assigned period the SNMP IPv6 ad justs forward one hour 35 A NELTA Manual If a time server is not accessible you can still manually set time and date Please note that every time you restart the SNMP IPv6 time and date is rein Stated to previous assigned settings Syslog Syslog is used to store event logs on remote sys
41. log servers This will not affect the local event logs Up to four syslog servers can be assigned e Be menisan o Engish m Ca NELTA The power behind competitiveness Device Wed 10 05 2011 PM 04 28 52 Administration User Manager System Administration Syslog TCP IP gt Syslog Web Syslog Enable Disable Syslog Server 1 Console Syslog Server 2 FIP Syslog Server 3 Time Server SISOS Syslog Enoish Wed 10 05 2011 PM 04 29 03 Device System Administration User Manager System Administration Batch Configuration TCP IP gt System Configuration gt SNMP Configuration Web System Configuration Download SNMP Configuration Download ose peed DescriptionThe batch configuration is used to configure all of the Console FIR DescriptionThe batch configuration is used to configure all of the Time Server Syslog Batch Configuration Upgrade system parameters at one time Please follow the following steps to complete the process Press the Download button to download the configure ini file which includes all of the system parameters Please follow the file format There must has a Section before item_name item_value And the last line must be End section Edit the configure ini file by the text edit software Remove the items which you don t want to be changed just leave the items whi
42. mpt mode After that you can now connect to the SNMP IPv6 by its Host Name Please also ensure that the Host Name assigned to the SNMP IPv6 does not ex ceed 16 bytes O5 How to check my workstation s IP address For Windows please enter ipconfig all in DOS prompt mode For UNIX please enter ifconfig in shell You should be able to check your IP and MAC Physical Address now Physical Address 6 6 6 c o o 00 23 4D A2 3A 2C Dilo ENEC o o o u o o u u o o 8 MES Autoconfiguration Enabled Yes Link local IPv6 Address fe80 ad55 5b9b 74c6 e5fc 12 Preferred IPv4 Addressee o u o o o o a o o 8 MAO IG ILS SY Rre Tenra Siblejel iuu IS 6 o o o o o o a o o 8 29293 254 0 CER InsightPower SNMP IPv6 for PDC 48 Chapter 7 Troubleshooting O6 Unable to ping the SNMP IPv6 from my workstation If the SNMP IPV6 is non responsive check the following If the green LED indicator on the SNMP IPv6 is OFF check if the network cable is correctly connected from the SNMP IPv6 to the router or hub 2 Ifthe green LED indicator is ON the current IP address could be unreach able Manually assign a valid IP address to the SNMP IPV6 3 If the green LED indicator flashes and 1 your network configuration in cludes a DHCP server make sure the DHCP service is working properly 2 Otherwise make sure the assigned IP is not already taken on the network Please note that if the current configuration i
43. nfiguration Upgrade System Administration User Manager User Manager O Use RADIUS Server 51 chars max Secret 32 chars max RFC2865 Service Type Administrator Device Manager Read Only User 1O0O0O0GOOGO Login User Framed User Callback Login Callback Framed Outbound Administrative NAS Prompt Authenticate Only Callback NAS Prompt Call Check Callback Administrative Login User v Framed User O Callback Login O Callback Framed O Outbound Administrative NAS Prompt O Authenticate Only O Callback NAS Prompt O Call Check Callback Administrative Local Authentication Login User C Framed User O Callback Login O Callback Framed O Outbound Administrative NAS Prompt O Authenticate Only O Callback NAS Prompt O Call Check Callback Administrative Privilege Password 16 chars max Account Name 16 chars max Login Limitation Administrator admin Device Manager device Read Only User user 31 Only in This LAN Allow Any Only in This LAN Allow Any Only in This LAN Allow Any A NELTA TCP IP Set up TCP IP protocol settings in this page c enne M S Home Logout Rai InsightPower SNMP IPv6 for PDC Web NELTA The power behind competitiven
44. ng initialization or firmware upgrade This could result in data loss or damage to the SNMP IPv6 The green LED indicator shows the network connection status ON Network connection established and the IPv4 address is useable OFF Not connected to a network Flashes slowly every 500ms Faulty IP address The yellow LED indicator shows the linking status between the SNMP IPV6 and the PDC e Flashes rapidly every 50ms PDC linked Flashes slowly every 500ms PDC not linked 5 A NELTA InsightPower SNMP IPv6 for PDC No Item Description DIP Switches Pass Through Mode Sensor Mode with Enviro Probe Configura tion Mode NOTE Determine the operation modes ic Description mode Normal Mode The SNMP IPv6 links with the PDC The SNMP IPv6 does not monitor the PDC but uses its COM port to connect the PDC and the workstation via Mod bus protocol Baud rate 9600 The SNMP IPv links with the PDC and EnviroProbe Configure your SNMP IPv6 via the COM port Refer to 4 4 Configure via COM Port To know more about the EnviroProbe refer to its user manual Chapter 3 Installation Chapter 3 Installation e Please follow the instructions below to install the SNMP IPv6 Step 1 Remove the cover and two screws on the SNMP SNMP slot slot NOTE Screw locations may vary depending on your PDC models Step 2 Locate the grooves on of the
45. panel and branch circuits With its user friendly web interface that features instant monitoring and manage ment you can easily manage your PDC and SNMP IPv6 It supports a wide range of common protocols including SNMPv3 HTTP SFTP and Telnet 2 2 Features Remote management and monitoring Manage your PDC from workstations connected in the network Comprehensive protocol support Including HTTP HTTPS SNMPv3 FTP SFTP and Telnet Compatible with EnviroProbe Works great with the Delta EnviroProbe sold separately to detect environment temperature and dry contact status Supports encrypted connections Including HTTPS SSH SFTP and SNMPv3 to improve connection security Comprehensive event and data log Show and keep track of PDC system status circuit readings and events Supports IPv6 protocol IPv6 Ready Logo Phase 2 Core for Host Logo ID 02 C 000624 Other features and supported protocols include User notification via SNMP Traps and e mail Network Time Protocol InsightPower SNMP IPv6 for PDC 2 BOOTP DHCP Chapter 2 Introduction RADIUS Remote Authentication Dial In User Service login and local authentica tion Syslog remote event log management 2 3 Package Contents Please carefully check the SNMP IPv6 and the included accessories Contact your local dealer if any item is missing or damaged Should you return any item for any reason ensure that they are carefully repacked using the origin
46. r 4 System Configurations Select the SNMP IPv6 that you want to modify from the Device List Click Modify and enter Administrator s account and password default admin password case sensitive IP amp Account SNMP Device Address IP Address Administrator Account Account Default admin Password Default password Step 6 Click Configuration to configure network settings Configuration System Identification Host Name NetBIOS IP2 System Contactor Date Time SNTP O Manual Time Zone GMT 08 Beijing Taipei x 1st Time Server Name or IP 172 16 186 116 2nd Time Server Name or IP PSE Set Current Time Date MM DDAYYYY Time 12 00 00 hh mm ss Reset to Default It is recommended to provide a static IP Address and disable the BOOTP DHCP Client option System Configuration IP Address Subnet Mask Gateway IP DNS IP BOOTP DHCP Client HTTP Server Telnet Server HTTP Server Port Telnet Server Port User Limitation Administrator Device Manager Read Only User UE ir 16 255 Zoo a 0 O Enable Enable Enable 172 dazio 16 186 254 16 176 1 168 Disable O Disable O Disable In The LAN OAllow Any In The LAN O Allow Any If it is the first time to configure your InsightPower device please assign an unique name in the Host Name field and given a Time Server for the device
47. rver 2 The Host Name of remote Syslog Server 2 e Syslog Server 3 The Host Name of remote Syslog Server 3 f Syslog Server 4 The Host Name of remote Syslog Server 4 SNMP Get Set Port The SNMP port Time Server You can manually adjust time and date for the SNMP IPv6 or set up automatic time server synchronization The SNMP IPv6 Windows XP and later versions support SNTP Simple Network Time Protocol If you need to start up a time server service on your workstation please refer to Chapter 7 Troubleshooting 01 19 A NELTA Time Selection Time Zone lst Time Server POOL NTP ORG 2nd Time Server Manual Date 01 01 2000 MM DD YYYY Manual Time 00 00 00 hh mm ss Back To Previous Menu Please Enter Your Choice gt No Item Description Default T 2 a 6 Time Server The secondtimeservertorsnte 5 6 Soft Restart Reset the SNMP IPv6 This will not affect the operation of the PDC Default Reset Reset to manufacture default Exit Without Saving Exit and ignore changes Save and Exit Preserve your changes and exit InsightPower SNMP IPv6 for PDC 20 Chapter 5 InsightPower SNMP IPv6 for PDC Web Chapter 5 InsightPower SNMP IPv6 for PDC Web To configure the SNMP IPv6 via the InsightPower SNMP IPv6 for PDC Web please fol low the steps below Step 1 Make sure that your SNMP IPV6 is connected to the LAN Use a CAT5 net work cable to conne
48. s not useable the SNMP IPv6 will reset to default IP settings IPv4 address 192 168 1 100 net mask 255 255 255 0 gateway 192 168 1 254 4 If the problem persists use a network cable to cross link your SNMP IPv6 and the workstation Ping the SNMP IPv6 s default or static IP address ac cording to your configurations If a ping response is successfully received indicating that the SNMP IPv6 is working properly check your network equipment If not contact your local dealer or service personnel for assis tance Q7 Unable to perform an SNMP Get command Refer to 5 2 2 Notification to check SNMP settings Make sure that the work Station s IP address is added to the NMS IP list with Read or Read Write access The community string on the workstation and the SNMP IPv6 must match O8 Unable to perform an SNMP Set command Refer to 5 2 2 Notification to check SNMP settings Make sure that the work station s IP address is added to the NMS IP list with Read Write permission The community string on the PC and the SNMP IPv6 must match Q9 Unable to receive SNMP trap Refer to 5 2 2 Notification to check SNMP Trap settings Make sure that the workstation s IP address is added to the Target IP list 49 A NELTA O10 Forgot Administrator s account and password You can reset Administrator s account and password via text mode Refer to 4 4 Configuring via COM Port to establish a COM port connection with the SNMP IPv6 When the log
49. set SNTP time server addresses in Time Server Please refer to Chapter 4 System Configurations How to make sure the linking between the SNMP IPv6 s and the PDC is es tablished If the linking between the SNMP IPv6 and the PDC is correctly established the yellow LED indicator should flash rapidly If not confirm that the device ID set ting on the SNMP IPv6 and the PDC is consistent C gt ping 172 16 186 230 Pinging 172 16 186 230 with 32 bytes of data Reply from 172 16 186 230 bytes 32 time 2ms TTL 64 Reply from 172 16 186 230 bytes 32 time 2ms TTL 64 Reply from 172 16 186 230 bytes 32 time 2ms TTL 64 Reply from 172 16 186 230 bytes 32 time 4ms TTL 64 Ping statistics for 172 16 186 230 Packets Sent 4 Received 4 Lost 0 0 loss Approximate round trip times in milli seconds Minimum 2ms Maximum 4ms Average 2ms CRAD O3 I can access the InsightPower SNMP IPv6 for PDC Web but cannot login In Please check the IP addresses of the SNMP IPv6 and the workstation on which you are trying to log in By default they must be within the same LAN so you can connect via the web interface You can enable external connections to solve this issue To do this launch EzSetting and change User Limitation to Al low Any as shown below 47 A NELTA Configuration System Identification IPv4 Host Name NetBIOS BOOTP DHCP Client Enable O Disable System Contactor sd IP Address 172 16 186 241
50. st Receiver name company com Event Level None v Receiver Event Level None If a DNS server is not available in the network you need to manually as sign an SMTP server address to enable the E mail notification system e If a Host Name is entered in SMTP Server Name or IP a DNS IP address should be added in the TCP IP page Specify the e mail address and event level When an event occurs a notifica tion will be sent to the target address Refer to the following 1 Information All event notifications are sent to the target address 2 Warning Warning and Alarm event notifications are sent to the target address 3 Alarm Only alarm event notifications are sent to the target address 4 A NELTA Event Level Device System Notification SNMP Access System Notification Event Level SNMPv3 USM Device Env Probe SNMP Trap D 1 2 3 4 5 6 7 8 Event Message Level PDC device disconnected s None Mail Server PDC device connected s Alarm E Event Level Main status alarm s Warning Recover from main status alarm s Warning Primary status alarm s Alarm ut Recover from primary status alarm s Alarm Secondary status alarm s lt Recover from secondary status alarm s 3 Panel status alarm s lt o Recover from panel status alarm s Subfeed status alarm s Recover from subfeed status alarm s A K jis A adb O N Branch over
51. tion Device f System Configuration Connection Data Log Environment Device ID 3 State Connected Run Time 2 09 15 Copyright 2011 Delta Electronics Inc All Rights Reserved Connection By default the PDC has a device ID of 1 which also represents the ID assigned in Modbus protocol To link the PDC with the SNMP IPv6 the device ID setting must match Select the PDC s device ID and click Restart DataLog Specify the data saving frequency for the Data Log The system automatically saves data after the specified time elapses Click Apply to take effect Environment This page only appears when an EnviroProbe is connected Set warning and alarm thresholds Entitle input contacts and select their contact types respec tively Click Submit to take effect InsightPower SNMP IPv6 for PDC 30 GA System Chapter 5 InsightPower SNMP IPv6 for PDC Web Check or change system configurations in the following pages 5 2 1 Administration User Manager The SNMP IPv6 supports RADIUS Specify server secret and port default 1812 Check User RADIUS and click Submit to activate Check specific service types for Administrator Device Manager and Read Only User If RADIUS is disabled local authentication will be used Specify account name password and login limitation for individual accounts ee k een DM System Administration User Manager TCP IP Web Console FTP Time Server Syslog Batch Co
52. to take effect NELTA a re InsightPower SNMP IPv6 for PDC Web Device i System Information System Primary Secondary Panel 1 Panel 2 System Status Main Panel 1 Panel 2 X1 X2 HT VL VU Li Bi L3 GF DSP FRAM EPO REPO so LCM gt Status fs Primary UV ov oc UC VT PF Secondary UV ov oc UC VT PF Panel 1 OverCurr UnderCurr OverTHD PoorPF HighCurr Panel 2 OverCurr UnderCurr OverTHD PoorPF HighCurr Branch System Information Item Information Model PDC5503A1250098 Serial number 2210389001000 Capacity Input Output Frequency InsightPower SNMP IPv6 for PDC 22 Chapter 5 InsightPower SNMP IPv6 for PDC Web 5 1 1 Status Panel 1 Panel 2 VL Ec EPO so The red and green flags represent the PDC s status A green flag shows to indicate normal operation A red flag means a warning event has occurred Refer to the fol lowing table for flags and the warning events they represent Description Flag Description A warning event of the Panel main breaker has occurred X1 Transformer tempera ture exceeds 125 c X2 Transformer tempera ture exceeds 150 c Voltage phase lacking L1 L2 L3 Frequency out of range CAN DSP communication error Emergency Power Off initiated A warning event of the panel breaker has occurred Ambient temperature too high Voltage unbalance Ground fault FRAM read write error Remote Emergency Power Off initiated CAN LCM
53. ty String public Mail Server Trap Type SNMPv1 v Port 162 Event Level None lv SNMP Trap Event Level click one row of fields if you want to modify it Port Community String 10 0 10 201 162 public 0 0 0 0 162 public SNMPv1 SNMPv2c and SNMPv3 Traps are supported If the SNMPv3 Trap is enabled the user names must be specified in SNMPv3 USM The target IP addresses receive event notifications based on the event levels you specified Three event levels are shown as follows Information All event notifications are sent to the target address Warning Warning and alarm event notifications are sent to the tar get address e Alarm Only alarm event notifications are sent to the target address Click Event Level on the left panel to change event levels for individual events InsightPower SNMP IPv6 for PDC 40 Chapter 5 InsightPower SNMP IPv6 for PDC Web Mail Server Configure an SMTP server to send event notifications to recipients specified on the mail list Up to 256 recipients can be added e emsa S 7 13 NELTA l InsightPower SNMP IPv6 for PDC Web e power ina competitiveness System Notification SNMP Access System Notification Mail Server SNMPv3 USM A gt Mail Server Configuration SNMP Trap SMTP Server Name or IP 51 bytes max Mail Server o Account 32 bytes max Event Level Password 16 bytes max Mail Li