User manual and installation instruction Control Unit for Fire

image

Contents

1. 7 Sit gia 7 o o 2 Brown 3 4 FOWN 3s 4 ree a Pee 1 4 7 L2 Up A Next LIP Next LIP Extra relay print 111655 mot 6 a provides 4 additional os Go potential free switches Firer neni oe WSK 3 28 each 30V 0 5A Fit J1 in last WSK S 3G Connection diagram LC SVM24 for line monitoring only last sensor Drawing 211704 C Control for Fire and Comfort Ventilation Type SVM 24V 5A SVM 24V 8A LEDs on main board and front panel LED Symbol Operation possibilities for Alarm Comfort colour fire operation ioma __ Actuator open ret Lights when acwatoropens EDaren __ Actuator close green Lights when actuator clos _ paired __ Weather sensor active ed Lights when weather sensor is active Yes No paired Line eror on actuator ed Lights when actuator has ine eror Yes Only cose iosa _ Line error on fire switch red Lights when fire switch has line error Yes Only close LD6 red Line error on smoke detector red Lights when smoke detector has Yes Only close line error Green Board Front lights if everything is ok Yes Yes switched off by local error on this control flashes by error message from other controls received by bus Yellow Board Front AeA LD7 red Bus error red Lights when BUS signal from other controls is Yes Only close missing Only relevant if J24 or J25 is mounted A Fault Only close flashes by local error on this control or by error message from
2. 5A controls 8A controls Haandvaerkervej 2 9560 Hadsund 151x65x98mm Denmark 111710 Fire switch reset IP40 Actulu Fire switch IP 40 declare under our sole responsibility that the product 11703 Replacement glass f WSK Replacement glass for fire switch erkl ren in alleiniger Verantwortung dass das Produkt 11702 Tool key fireswitch WCP111720 Key for fire switch for operation without breaking glass erkl rer under eget ansvar at produktet 7 7 certifions sous notre propre responsabilit que le produit 11725 Fireswitch WSK in IP65 Box Fire switch built in IP65 box dichiara sotto la propria responsabilit che il seguente prodotto 111730 Wind and rain sensor 24VAC DC Wind and rain sensor closes everything when raining or strong wind SVM 24V 5A SVM 24V 8 111735 Heat detector base 75 degree Heat detector 75 degrees temperature activation l l name type or model lot batch or serial number possible sources and numbers of items TE Bezeichnung Typ oder Modell Los Chargen oder Seriennummer m glichst Herkunft und St ckzahl 111741 Heat detector base 90 degree Heat detector 90 degrees temperature activation navn type eller model m ngde parti eller serienummer mulig oprindelse og stykantal nom type ou mod le lot ou num ro de s rie origine et quantit 11740 Smoke detector optical Optical smoke detector nome tipo o modello lotto serie o numero di serie sorgenti possibili e numeri d
3. 8 Contact person Connection of smoke heat ACHE O UES ss sccsiaiesies cuswednbinsisnancbiaetdiaivtesscenecbuiiatedbalaebeacuibeiecesasanaieiisinsteiss 9 Comfort ventilation connection and settings caswiesesexesdsauctdsesananoueresbsecdsncdeasdiasarvesdaaroosseuabodsasadeasdies 9 E EE E T Diagramme control unit and CONMECHIONG scesssscrssrsrssesscssesrensssonssesnesessensscsnesssessssesseses 10 11 ate OL nstaauon Extenial LEDs on th front panel LED DOatG oid ssctscatessveaatdocieasovedecresatsaasossrlaasonsserabiosesearysolitacnibids 12 Internal LED indication on th main board xsi cnc siusdasacss doaksoodlaracsenssetasGetdwieseeddicoudssaaddivasiRaseclecesiasax 12 Fuse SPSCINCAMOIS senesan e e rene er E E N CEEE AEE EEEE a ous aE E RESSA ET EEE 12 i CompletejJ mper Seting Suuria a r EE N EES EE E A TE EE 13 Installation Connection of more control units to one fire group bus connection c ceeeeseseseseseseseseseseseseseees 14 Connection of weather sensory Close all function lt setissdsscrccsntsnansidsasasisescesee Gadddcoudaaccdesniaciesiedeoveies 15 Number of control units and type ex SVM 24V 5A External signal transfer connection of AFA systems and other systems c ccccecsseceteceeeeeeeeeeaees 15 Special FUN HONS esis o be cal e Ge carteisas E EE EE a TENE 16 CAS AEE E S ENE E A E E E neaboneed 16 17 Number of fire ventilation groups Part nos and ACCESSOTICS 0 eeevsssssseeeesssssnneceeeesnsnnneceeees
4. Line failure actuator red Lit for line failure on actuator LDS Line failure fire switch red Lit for line failure on fire switch LD6 Line failure smokesensor red Lit for line fail on smokes LD7 BUS failure red Lit when local unit is not recieving signal e288 8 8 8 PEE EEE x 24V Red 2 5mm2 O ing RESET Potmeter for i comfort features ae w S a lt x 1 i i D 20 s0 340 os Lel Ce CeT 2 AC FAIL LINE FAIL BATT LOW 7 o z 5 F Black 2 5mm2 sthe Jupu Bs eaespeteeszce ez E D Tuun SEBR REP S522 FIRE ON TTT orr gt m ele e e ele lefele m a DIPNOI 2345678 9 0 1 12 CLOSE E 3 24VDC E 5 a gt g Brue E S DOME OPEN 5 5 2 COMFORT COMFORT wn a a wi no Y J4 JS J6 J7 Z gt START TERM MASTER SLAVE END TERM 2 o Z up DOWN pas v awn m c c oat 5 a 2 C au Max 8A 6 Le oS Su n gt 5 a 2 BE 58 FUSE F1 fast 5 p ce 5S LS a oe uo ee ee a a E 55 e sv I Actuator F g a vi w Motor line monitor amp S 42 ga un Sec co lt us en 5 Ext 3 wire monitor line 1 e gt oo 5 5 Sa z 4 33 va as lt 3 2 Alarm Out Failure Out z 5 1 21 1 2 3 Line 1 A z QO Actuator 24V Out 2 o 5 EE g5 5 gen 5 o 2 ae ze 4 eg c c w no o wo 5 1 channel LIP eu ae 2 3 Lin 2 1 2 1 LIP4 LIPS a oo 1S 22 Oe i2 Blue example ae Jg 3 Nr 1 Blue z 25 x ee x am TH out i 2 rs 2 5 EIS g2 T1 Ou aks Z5 Z a a 222 2 Down
5. 6 Fail Relay no Failure relay works as indication that Normal mode works as failure skylight is open relay DIP 7 Week open no Weekly open 2 sec close Weekly open close not activated 5 sec cycle activated DIP 8 AG Mode special Jno Special Fire close button enabled DIP 9 Sprinkler no Motor output closes by active Normal mode motor output opens detector opens by activating the fire by ative detectors or fire switches switch DIP 10 Bus comfort no The control reacts on comfort signal The control does not react on via bus activity comfort signals via bus activity NB Always reaction on weather signal and failures via bus activity and own comfort signal DIP 11 Bus fire no The control reacts on alarm signal The control does not react on alarm via bus activity signal via bus activity NB Always reaction on weather signal and failures via bus activity and own alarm signal detector or fire switch DIP 12 BR Mode special no Special fire switch alarm mode and Normal mode comf active at all failures J3 1 2 3 4 Pos 1 Connect according to number of No line monitoring motor 27KQ terminal resistors on actuator Mot Mon act yes 2 wire line monitoring via 27KQ J2 terminal 2 3 ee o er TEJE o line monitorin motor Ext Li Mon act no 3 wire line monitoring with direct 7 motor connection actuator J4 Bus _ Start term A First control unit in the bus network Master J5 Bus Jno See section concerning conn
6. BUS Master BUS Slave END termination F START TERM Please no mounted jumpers JS MASTER ice J6 SLAVE Serial Out Serial In A1 A2 A3 B1 B2 B3 J END TERM START termination BUS Master BUS Slave END termination o F START TERM J5 MASTER J6 SLAVE 2 22 32 Serial Out B1 B2 B3 END TERM START TERM START termination BUS Master BUS Slave END termination J5 MASTER Serial In BUS connection 3x 0 5mm2 Fireproof Al A2 A3 0 222 BUS connection 3x 0 5mm2 Fireproof Serial Out J6 SLAVE J1 END TERM B1 B2 B3 Serial In 2 2 22 2 Al A2 A3 Connection of weather sensor Close all function A weather sensor can be connected to the control unit The weather sensor is adjusted according to the instructions Actuators should be closed when the wind is above 6 m s LED LD3 on the main board indicates active weather sensor lights as long as input is active As long as the weather sensor is active motor inputs cannot be opened with comfort switches The weather sensor closes on all controls which are connected through bus connection On the input to weather station a weekly timer can be connected which
7. User manual and installation instruction Control Unit for Fire Ventilation SVM 24V 5A SVM 24V 8A R GVENTILATION Fire ventilation Comfort ventilation 24VDC max 5A 8A 1 fire ventilation group comfort group Connection for fire switches wind and rain sensor comfort switches smoke detectors Possibility for bus connection of 10 control units 211631 Control for Fire and Comfort Ventilation Type SVM 24V SA SVM 24V 8A Control for Fire and Comfort Ventilation Type SVM 24V 5A SVM 24V 8A Address of installation Table of contents Name Address OF installation Description of mstallation ssasssescssvien aiavovs csancumasaseisigeaasisnasiosdanaatetaviaabinegs 2 General d sCiptioi ssa ceisba setae eer eair a ie ta eei iae E TEE ae aa aE TE Eae ATEKA R E Eei 4 Safety rules during installation and operation cscccsssasdeasisasesdcassuccsetesanetssaasncdscsavecedecacsscteudsvssssadsordees 5 Address Explosion IAIN scnis E a E E E E RE OEE OEE ETE 5 E Wigs Vell E NKO o PSEA ASEEN A A E E E AA AAE 5 Yearly legal requirement of maintenance and control wise sesziccsiadescnsseeesGetsvandsededdveudssavdinasiaadeciicsiaias 5 Phone no Connection to motor actuator outputs and line monitoring eee eee cece eetceeeeeceteeeeeeeeseeesaeees 6 C rent limiter type LIP asirar a AE Er SEERA ENEE T Operation and connection of fire switches jnnsssceannceseasxaveseanteasseasboveiceauesnsstasbedeacstdecspusbontaduatncoiaaaberss
8. Weekly timer channel Weekly timer can e g close everything in the evening til hvilket denne erkl ring henf rer er i overensstemmelse med de f lgende standard er eller andre 11758 Comfort switch FUGA w housing Comfort switch Fuga complete with housing a N Erkl rung bezieht mit der den folgenden Norm en oder normativen Dokument en following the provisions of Directive 73 23 EEC 89 336 EEC and 93 68 EEC gem ss den Bestimmungen der Richtlinie 73 23 EEC 89 336 EEC und 93 68 EEC i henhold til direktivets bestemmelser 73 23 EEC 89 336 EEC og 93 68 EEC selon les stipulations des directives 73 23 EEC 89 336 EEC et 93 68 EEC ed alle direttive 73 23 EEC 89 336 EEC ed 93 68 EEC Hadsund 10 February 2012 Jens Buus Place and date of issue Name and signature or equivalent marking of authorized person Ort und Datum der Ausstellung Name und Unterschrift oder gleichwertige Kennzeichnung des Befugten Sted og dato for udstedelse Navn og underskrift eller kvivalent m rkning af autoriseret person Posto e data d emissione Nome e firma o marcatura equivalente della persona autorizzata Lieu et date d mission Nom et signature ou apposition quivalente d une personne authoris e Control for Fire and Comfort Ventilation Type SVM 24V 5A SVM 24V 8A Technical specifications SVM 24V 5A SVM 24V 8A 230V AC max 250VA 5 C 60 C IP 50 RAL 9003 286x238x113 mm 7 5 kg Incl 72 hour
9. bout ok operation and error and alarm condition to other systems in the building The polarity of the motor supply is reversed when opening or closing The control unit has built in 72 hours battery back up By a unique bus system consisting of a 3 wire cable the control units can be mutually connected so that up to 10 control units can be connected and operate as an integrated system Connection of cables to the in and outputs of the control unit is described in the connection drawing on page 10 11 A more detailled connection to the individual in and outputs is described in the individual sections in this manual Selection of cable sizes on page 17 By means of jumpers and dip switches the control unit has different setting possibilities for in and outputs These settings are indicated in a complete table please see section with jumper settings on page 13 Examples of types of openings systems and the max power consumption which can be connected to the control unit Type 24V power supply SA Power Single 4A SA Power Double 8A 2x4A SA Power Large 8A Rotary 100 2 5A Others See specification of max power consumption on the opening system Control for Fire and Comfort Ventilation Type SVM 24V SA SVM 24V 8A Safety rules during installation and operation The control unit may only be installed and maintained by personnel authorized for installation of automatic electrical fire ventilation equipment Explosion dange
10. e sure that the fire ventilation system meets the standards and works correct in an emergency The two most important factors are the ability of the cables to resist heat and to make sure that the voltage drop in the cables to the actuators do not exceed 15 at full load on the fire ventilation hatches Fire resistant cables according to IEC 60331 must be used for the following functions Opening systems with actuators 24V 2 wires see diagramme 3 wire by external line surveillance Fire switch 24V Min 6 x 0 5 mm Smoke detector 24V Min 2 x 0 5 mm Min 2 x 0 5 mm Cable between control units bus Normal cables can be used for the following functions Supply for control 230VAC e g 3 x 1 5PVIK J Comfort ventilation button 24V Min 3 x 0 5 mm Wind and rain sensor 24V Min 4 x 0 5 mm Control for Fire and Comfort Ventilation Type SVM 24V 5A SVM 24V 8A Control for Fire and Comfort Ventilation Type SVM 24V SA SVM 24V 8A Part nos and accessories Actulux N Spare parts Name of part Description DECLARATION OF CONFORMITY UK o KONFORMITATSERKLARUNG G OVERENSSTEMMELSESERKL RING DK 21609 Cont PCE oe pd meets 211060 Power supply 150W 27VDC MW Power supply 230VAC 27VDC for 5A control ATTESTAZIONE DI CONFORMITA IT 211070 Power supply 200W 27VDC MW Power supply 230VAC 27VDC for 8A control 211210 Circuit breaker 10A Automatic fuse 10A input terminal We Actulux A S 800248 Batteri 12V 7 2AH Battery for 24A
11. ection J6 Bus Slave no Middle and last control unit in the of controls units in bus connection bus network page 14 J7 Bus fEndterm no sd Last control unit in the bus network Others Reset time 90 sec closing Cut off motor output and loading after 360 sec Comf var potetiometer 1 60 sec Control for Fire and Comfort Ventilation Type SVM 24V 5A SVM 24V 8A Connection of more controls to one fire group bus connection By means of a bus communication it is possible to make 2 10 control units to work as a complete system The control units communicate with each other via a 3 wire bus connection This could e g be a 3x0 5 mm fireproof cable Terminal no Al A2 A3 are for the incoming connection and B1 B2 B3 for the outgoing connection In the first control unit start Bus J4 has to be on This control is Master and J5 must therefore also be on The bus cable is connected on the output terminals B1 B2 B3 and lead to the next control unit which is a slave J6 must therefore be on The cable is connected to the input terminals A1 A2 A3 of the next control unit and further to the next slave control unit from terminal B1 B2 B3 In the last slave control unit J7 and J6 must be on in order to terminate the bus connection ALARM Connection of alarm inputs works across all controls so that if a fire switch or a smoke heat detector on one control is activated all connected control units also go into alarm co
12. i articoli 11742 Smoke detector Ion detector Ion smoke detector for invisible smoke 11753 Comfort switch OPUS w housing Comfort switch Opus complete with housing to which this declaration relates is in conformity with the following standard s or other normative document s normgivende dokument er HTS Comfort sw up down OPUS IP44_ Comfort switch Opus 44 white r f rant a ce certificat est conforme au x standard s ou autre s document s normatif s 111767 AUTO MAN switch OPUS w Switch Auto man OPUS white activates room thermostat or conforme alle disposizioni e normative sotto indicati housin weekly timer aniooni 11770 Room thermostat RTR w resis Room thermostat for control of comfort ventilation EN61000 6 2 2005 EN61000 6 4 2001 11655 Relay PCB extra 2Xoutp in box Board with 2x2 extra relay outputs 30V 0 5A ENO1000 3 2 2005ENG1000 9 3 1995 11 168 1 Relay box coil 24VDC Contacts Relay box with 3x23 oV shift contacts Title and or number and date of issue of the standard s or other normative document s 3x23 OV shift Titel und oder Nummer sowie Ausgabsdatum der Norm en oder der anderen normativen Dokumente Title og eller nummer samt udgivelsesdato for standard er eller andre normgivende dokument er Titre et ou num ro ainsi que date de publication de s standard s ou autre s document s normatif s Titolo ed o numero e data d emissione dello standard o dell altro documento documenti normativo 11760
13. l free switches each 30V 0 5 A Control for Fire and Comfort Ventilation Type SVM 24V SA SVM 24V 8A Control for Fire and Comfort Ventilation Type SVM 24V 5A SVM 24V 8A Special functions Table for SVM 24V 5A 8A allowed voltage drop 15 3 6V Sprinkler function DIP 9 On a special function comes in use where sprinkler systems are installed With this function Power a EEA TIE EE PEET keoies activated the actuator output closes if smoke heat detector input is activated consumption If the fire switch is activated the actuator output opens per groupin 2x1 5 mm 2x2 5 mm 4x1 5 mm 4x2 5 mm 2x6 mm 5x2 5 mm 2x10 mm ampere 2x1 5 2x1 5 2x2 5 2x2 5 2x2 5 3x2 5 Weekly open close DIP 7 On the motor output opens shortly 3 seconds once a week and closes immediately after This function is used to give the right tension on the packing of the skylights to keep them watertight 6 235m 4m 50m 82m 98m 102m 164m Function of heat detector in LIP Cs iem sim sem om nm m am DIP 3 On a heat detector 70 100 can be mounted in each LIP If the temperatur is exceeded the control unit goes into alarm and the opening system is opening Special mode DIP 12 On possible to use comfort switch also during line fault low batt no AC Alarm only as long as fire input is active or detector is activated Cable sizes It is very important to use the correct cable types and sizes to mak
14. lete opening time In order to avoid actuator pumping max 3 successive closing attempts will be allowed Potentiometer in Const pos As long as up signal or down signal are given the actuators are running Potentiometer in Puls variable pos The time on the above mentioned pulse opening can be adjusted from 1 60 sec on the L1 In potentiometre Smoke or heat sensors When moving the potentiometer into the different positions the LED batt low will flash for about 4 sec to indicate when in puls mode LED line fail flashes 4 sec when L1 Out in constant and AC fail flashes when in puls varaiable Potmeter for comfort features YEL YEL YEL AC FAIL LINE FAIL BATT LOW S as up S OB Down Q I snd 0 O Down O O Room thermostats weekly timers CCS and Up other external control equipment for comfort m z ventilation can be connected on the input of the 55 comfort control 5 z only last sensor Control for Fire and Comfort Ventilation Type SVM 24V SA SVM 24V 8A Control for Fire and Comfort Ventilation Type SVM 24V 5A SVM 24V 8A Connection om SVM 24V SA 8A D Kai Ce Lore FAILURE LD1 Actuator open red Lit when actuator is opening LD2 Actuator closing green Lit when actuator is closing BUZZER ON OFF LD3 Weather sensor active red Lit when weather sensor is active LD4
15. line monitoring on the actuator output the factory setting is connected The cables to the actuators can be connected in series or parallel or a combination of these please see drawing with examples or connection diagramme on the central pages It is important to keep the right polarity of the cables The actuators must always be connected through a current limiter e g the Actulux LIP or similar Cable monitoring line monitoring on the motor output The control is equipped with 3 possible settings for cable monitoring line monitoring which can be configured by means of jumper J2 Line monitoring between terminal 2 3 eae net Jumper J3 actuator output is set according to the number of termination resistors 27KQ to 3 be detected 1 to max 4 lines can be detected by moving jumper J3 this means that the cable VY VY Y installation between the control unit and the actuators can be established in series connection j 7 3 cable connection from e g skylight 1 further iel eiar to skylight 2 etc or parallel connection cable 24V Out connection from each skylight to the control or a combination of these However as mentioned max 4 different lines can be detected each 1 channel LIP 2 1 2 1 LIP4 LIPS Blue example Jumper J2 mounted in pos Motor line ety Ext 3 wire monitor line 1 NW FF CH 1 terminated with a 27KQ resistor Fo
16. makes sure that everything is closed e g by end of a working day External signal transfer connection to AFA systems and other control systems The control unit can receive potential free alarm signals from e g AFA systems on the input to fire switch or smoke heat detector Line monitoring resistor must be fitted on the contact in the AFA system The control unit can forward alarm condition to external connected systems by means of potential free contacts on the terminals 4 com 5 NC and 6 NO The control unit can forward failure condition to external connected systems by means of potential free contacts on the terminals 7 com 8 NC and 9 NO Alarm and error contacts work parallel on all controls connected with bus connection DIP6 fail relay On Fail relay changes function to indicate open closed window Control for Fire and Comfort Ventilation Type SVM 24V 5A SVM 24V 8A 24V N Ww S x Weather S ON Gnd Ji Wind and rain sensor Close all a DA Alarm Out Failure Out fo vu fo oO vu fo kad w m at 4 5 6 7 8 9 a pe SL j 3 _ oo Ee ce D E u DJ omg eS w f n n Cc Cc oO Vo X S lt o Z y m L D uw y aoc w u c aq J Es L OoN G oN U o T US L gt TYS gt Eeo Z c st C 4 u _ o E XxX E x Ooo oo A oS eee aV eS Extra relay print 111655 provides 4 additional potentia
17. me direction is allowed After that it will not be possible to run in this direction again before the motor has run in the opposite direction This in order to protect the actuator gear mechanism Please note that when opening the red LED in the LIP must light This indicates that polarity to actuator is correct Table of LIP settings Opening system 3A SA Power 4A SA Power 2 5A Rotary 100 DIP DIP 2 Type Part no Board Voltage and DIP 1 DIP2 DIP3 DIP4 DIPS DIP6 DIP7 DIP8 board description function LIP3 111305 A028 24 V 2 channels delay ON LIP4 111315 A036 24Vi1channel See diagram 97 Not mounted above ON LIP3 111330 A040 24V 2 channels OFF ON delay ON LIP5 121315 A043 24 48V 1 channel 27K Not mounted ON LIP6 121330 A044 24 48V OFF ON 27K M1 M2 Not mounted 2 channels ON delay ON SA Power Large parallel operation Jumper OPT mounted both motors stop at the same time if one stops because of overload Control for Fire and Comfort Ventilation Type SVM 24V 5A SVM 24V 8A Operation and connection of fire switches e g type WSK 320 The fire switch will generally contain the following e Breakable glass window and red control button is activated by pressure this puts the control unit in ALARM condition by which Con Fire Sw FAIL SAFE the motor output is activated for normal service and testing the lid ON gt alal can be opened with a key OFF gt e RESET button which bring
18. ndition RESET If the reset button on one control or in one fire switch is activated the reset function on all connected controls is activated and starts the closing function on all motor output in approx 90 sec COMFORT The comfort control can work locally on each control unit or via the bus on more control units If a wind and rain sensor is connected it will work on all control units on the bus Function description for control units connected with bus connection If more control units are connected by means of a bus connection the following are monitored communicated between the control units Adetected bus error makes the LED LD7 on the main board light flash Adetected bus error brings all controls on the bus connection in error condition line error Ifone of the control units in the network goes into alarm condition all go into alarm condition Ifone of the control units goes into a certain error condition line error AC error battery error or bus error the other control units also go into error condition the type of the error is indicated on the board of the front plate of all control units on the control unit s which have not caused the error the ok LED on the board of the front plate flashes at the same time as the error On the control unit s which have caused the error the OK LED is switched off Master Slaves Slave First central on BUS 0 8 middle centrals on BUS Last central on BUS START termination
19. nnnsseceeesssnnsncteessnnnansceeesennnsseteesennnsnscessesnansssss 18 CE Declaration of COMMOMMMIIY os cecocivecativslsndeboslcasunuussteasdanshovelaauabumestavtoaenstiasahouseadkiooaleibuqusnteuoubins 19 Techical specifications 3a socscacson pp caicasuldiekeseicadaclap dente duuacedelasubovdencda baseebesduetcolediaduesdiqumcUu ansonase 20 Type of opening system Type of opening system Rev 0 04 05 09 2012 Type of opening system External controls AFA CCS Comfort control Wind and rain sensor Manufacturer 22 ivf Actulux A S TIf 45 98 57 40 90 OV power supply from group Handango Fax 45 96 15 28 00 9560 Hadsund e mail info actulux com Denmark www actulux com Control for Fire and Comfort Ventilation Type SVM 24V SA SVM 24V 8A General description The control unit can be used for electrical opening of e g skylights smoke hatches or similar in connection with fire and comfort ventilation The control unit has different inputs with line monitoring which can be activated by e g fire switches smoke detectors heat detectors AFA systems and CCS systems For control of the indoor climate comfort ventilation manual switches weekly timer room thermostat and outdoor weather sensors can be connected By means of LEDs in the the front panel the control indicates the operating condition ok operation and error and alarm condition just as it by means of the built in potential free relay contacts can re lay operating information a
20. other controls received by bus Yellow Board Front Line error Only close flashes by local error on this control or by error message from other controls received by bus Yellow m AC error Only close Board Front flashes by local error on this control or by error message from other controls received by bus Red 4 Alarm Yes Board Front S lights red constantly pa tan o Board Front flashes by local battery error on this control Blue S lights blue constantly in open condition when windows are open Board Front or by error message from other controls received by bus All lights PF time for yearly service please call for supplier Fuse specifications ie a ee F1 8A fast ading fuse 1 pc for 24V motor output Control for Fire and Comfort Ventilation Type SVM 24V SA SVM 24V 8A Complete jumper settings standard setting marked in bold Software version gt 0024 Text on board Factory Mounted ON function Dismounted OFF function mounted DIP 1 Conf Fireswitch no Fire switch active from 500 3KQ Fire switch active from 0 3KO DIP 2 Failsafe no Line error on fire switch or detector Normal mode puts the control in alarm DIP 3 Temp Detekt no Line error on motor line upper Normal mode resistor area alarm er DIP 5 Snitch no LED s remember errors line Normal mode errors AC Batt error bus error The LED s can only be switched off reset again by setting dip switch off DIP
21. r The control unit is supplied with back up batteries which contain large amounts of energy which can be released as explosion in case of wrong handling the following safety rules must therefore always be observed e Never short circuit a back up battery e Do not use external chargers on installed batteries If unauthorized chargers are used explosive gasses can be released from the battery e Do not drop back up batteries as strong acids can be released if they are broken Installation The control unit can weigh up to 7 kg and must be installed on a stable wall The mounting holes for wall mounting are placed on the metal plate underneath the platic lid All cables are connected according to the drawing on the central pages and are dimensioned according to table page 16 Keep in mind that the operating voltage from the control unit is 24V and that the max voltage drop is 15 which demands correct cable dimension according to table on page 17 Please be aware that it often may be required in order to keep the demands on the CE marking of the complete installation or another law that the control unit is supplied with 230V AC from separate powerline with its own ground error circuit interruper and that a repair interrupter is mounted on the motor line After connection the control unit must charge the batteries min 12 hours before complete testing Yearly requirement of maintenance and control authorized The functions of the control uni
22. r SVM 24V 5A the max allowed current is 5A For SVM 24V 8A it is 8A Blue uw 1 LIP 1 LIP Jumper description J3 Number of connected 27Kohm terminal resistors for actuator output J2 Brown 3 E Brown 3 F Next LIP Next LIP Chooses line monitoring through motor terminals 2 3 Mot Mon or separate wire terminals 1 3 Ext Li Mon or no line monitoring when J2 J3 is removed Fuse 8A for actuator output Control for Fire and Comfort Ventilation Type SVM 24V 5A SVM 24V 8A Actuator 22 Motor line monitor Jumper J2 in pos Ext 3 wire A Ai arenonioilinei Line monitoring between terminal 1 3 With jumper J3 actuator output it is chosen how many lines number of 27KQ you wish to detect the same way as the motor line This setting demands 3 wire cable from motor output ae oe to motor LV Our Jumper J2 J3 is not mounted No line monitoring for actuator output OO nh WwW 2 3 27K Ohm Only last actuator Current limiter type LIP function and setting if mounted The current limiter type LIP mounted on the opening system is used as current limiter between the 24V DC supply and 1 or 2 actuators When the adjusted current limit is reached the speed of the actuators is reduced When the max power on the actuator is exceeded the actuator stops On the 24V types LIP5 max 5 times overload cut outs in the sa
23. s 24V 5A 8A 1 pe terminals 6mm 1 2 3 or 4 lines with line monitoring 1 pc with line monitoring max 10 pcs external WSK fire Power supply Operating temperature Density Colour Dimensions WxHxD Weigh incl batteries Battery back up Max total load motor output Motor output Fire switch group Comfort group Smoke and heat detectors Wind and rain sensor Serial connection of controls Alarm output Fault output Supply out Line surveillance Visual indication LED Manufacturer Actulux A S Handveerkervej 2 9560 Hadsund Denmark switches 1 pe unlimited number of switches 1 line with line monitoring max 20 pcs detectors Input for close all Bus connection integrates most functions Fra 2 10 controls in the same bus connection Potential free SPDT change over max 48V 0 5A Potential free SPDT change over max 48V 0 5A 24VDC 0 5A at 230VAC operation Motor lines fire switches smoke detector inputs and bus connection OK AC fault DC fault Line fault Alarm Tel 4 Fax 4 e mai www 45 98 57 40 90 45 96 15 28 00 1 info actulux com actulux com
24. s the control unit out of the alarm Be condition and starts the closing sequence for about 90 seconds Please note that RESET does not cancel errors on the system e g line errors etc These must be found and corrected e RED LED indicates that the control unit is in ALARM condition and that the motor output either is or has been activated e YELLOW LED indicates faults on the system please call for a service technician e GREEN LED indicates that the system is in normal operation condition without errors CONNECTION of the fire switch is made as shown on the drawing The installation with fire switches must be terminated with a 10KQ or 27KQ resistor in the last switch in order to establish the line monitoring correctly this can either be done by moving the factory mounted resistor from the terminal strip to the last fire switch or connect jumper J1 in the fire switch type WSK 320 is mounted by this a 10KQ resistor is also connected By means of DIP switches the control unit has different possibilities of settings for the input to the fire switch DIP 1 Conf firesw On ALARM condition from 500 3KQ indication of line error by direct short circuit or open circuit Off ALARM condition from 0 3KQ indication of line error by open circuit DIP 2 Failsafe On Any line error on fire switch or smoke detector puts the control unit in ALARM condition This function can be used if cables to fire switches and smoke detec
25. t and the opening system must be tested by authorized personnel at least once a year The control unit informs when the maintenance should be done The external LEDs on the front panel flashes fast The control unit and opening system are of course still full operating Please call a service technician at your earliest convenience in order to carry out the maintenance and to test the control and opening system in order to prepare it for another year of operation The legal requirements for this must be observed and the testing and control must as a minimum include the following e Control that all opening systems move to full opening when the fire function is activated should not be carried out if the wind is more than 6 m sec as there might be a risk that the opening system cannot close automatically e Control of the batteries If the batteries are replaced it is important to use the same type as the batteries are carefully chosen to be able to deliver the current for which the control is specified e Control of in and outputs on the control e Control of fire switches and smoke and heat detectors The batteries should be replaced as required however at least every third year Control for Fire and Comfort Ventilation Type SVM 24V 5A SVM 24V 8A Connection to motor actuator output and line monitoring The actuators motors must be connected to the actuator output on the output terminals 2 3 It is possible to connect and disconnect the
26. tors are not fireproof Off An error condition does not report ALARM condition Green LED w Red LED WSK 320 for line monitoring 1 green LED OK lights when OK and while 1 2 3 4 5 6 RENE closing r L F 2 yellow LED lights on error mer 3 red LED alarm emergency opening BB i 9 4 ground gea 2 lo 5 not used ai e gt O i 6 fire switch reset l a 7 fire switch emergency opening green yellow red g it Jumper J1 must only be set in the last or onl Yy Y i Peg TO P y y oR R m i A AA ul fire switch 2 Fit J1 in last WSK Control for Fire and Comfort Ventilation Type SVM 24V 5A SVM 24V 8A Connection of smoke heat detectors Smoke and heat detectors are connected as shown Line monitoring Correct line monitoring can only be guaranteed with detectors delivered from the supplier Other detectors may have different internal resistances and stand by power consumption Comfort ventilation Connection and settings The motor output can be controlled separately with a comfort switch For comfort ventilation there are the following possibilities Potentiometer in Puls pos It is possible to press the up button 3 times which each gives 6 seconds of opening time after that nothing happens Continuous up signal gives 3x6 sec 18 sec One press on down closes the actuator completely for a period which is the double of the comp