Operation manual PM-TOOL
Contents
1. Brief description With the PM TOOL configuration software the device lines M1 M2 M3 PM5 PU5 PW5 and PZ5 can be parameterised via a PC With this tool the device configuration can be generated readouted and safed on the PC Due to the easy to handle program surface the parameter can be changed whereat the operating mode and the possible options are preset by the program 2 Scope of delivery Contains the software on CD and one USB cable with device adapter 3 System requirements The PM Tool software is a PC software suitable for system software Windows XP Windows VISTA or higher and runs under NET Version gt 2 0 Required is a PC with USB interface Advice The communication with the indicator can be carried out via an optional RS232 RS485 interface or via the configuration interface using the provided USB cable The USB cable provides another COM interface which can be in general automatically installed via the internet If required the driver ca be found on CD too directory USB Driver This new COM interface needs to be selected in the program under menu item Extras Settings Under Port a selection of possible interfaces is given Device configuration and the current settings can be read out via menu File Import from device The file can be safed on the PC after the desired settings have been made This device configuration is not readable for all kind of device types and versions In this case a suitable c
2. Edit and the supporting point table can be edited RT PM Tool M1 T1 S0_P1 30_EN xmI eon x File Edit Device Extras Help Device profile Setpoint table Parameter lock Sea o s 50 Programming H alert 1 device name panel meter indicator M1 ii ED alert special function no set points input signal current loop 4 20mA sensor supply no analog output no alerts 2 switching points 0 interface ASCII default Value minimal Value maximal Value current Value 6 2 1 Device profile Via this option the device description can be edited and safed This description should contain all relevant information about this configuration file So the client or the facility can be stated where the devices shall be used RT PM Tool M1 T1 S0_P1 30_EN xml File Edit Device Extras Help 5 H a Deviceaddress 1 Programming LE 0 25 6 M1 xSR4x 0001 xxxx Item Description gt panel meter indicator M1 special funct no input signal current loop 4 20mA sensor supply analog output alerts switching po interface 6 Function description 6 2 2 Characteristic line of the device Setpoint table The option Characteristic line of the device is used only by special types of indicators If this option is available supporting points can be parameterised by insertion or removing Setpoint Table Setpoint Table 0 a Set
3. 1999 current Value 9999 20 11 7 Read and write data If a too small or too big value was given then the insertion field will be highlighted in red RT PM Tool M1 T1 S0_P1 30_ENxml aio File Edit Device Extras Help G Wd Deviceaddress 1 Programming a 0 235 0 3 M1 xSR4x 0001 xxx Eingang f tYPE input signal ff End end value e OFFS start value dot decimal point ff tArA tara value ZErO zero point tranquilization common H alert 1 H alert 2 2 set points The given value is added to the scaled value default Value minimal Value 0 maximal Value 1999 current Value 9999 7 Read and write data files During reading or writing data the parameter are read out from the indicator or transferred into the display In the process the parameter will be changed directly in the device If the configuration of the device should get lost it can be restored by a reset to the default values see user manual of the device A function for cancellation of the writing processes does not exist Thus it makes sense to save configurations in the PM TOOL Please note that the software saves only the parameter which are given in the configuration file A complete saving of all parameter in the device does not take place 8 PM TOOL terms of use 8 PM TOOL terms of use 8 1 Usage The software PM Tool was developed for usage with a Windows PC from up version XP only It may o
4. Operation manual PM TOOL Configuration software for parameterisation of the following display lines M1 M2 M3 PM5 PU5 PW5 and PZ5 RiT PM Tool M1 T1 S0_P1 30_EN xml File Edit Device Extras Help G 2 kd a Deviceaddress 1 Programming BT _JM1 xSR4x 0001 2000 Eingang H common HH alert 1 H alert 2 H set points PM TOOL_GB pdf Update 06 03 2015 device name panel meter indicator M1 Special function no input signal current loop 4 20mA sensor supply no analog output no alerts 2 Switching points 0 interface ASCII default Value minimal Value maximal Value current Value Software Contents oy SY ae a aS Brief description Scope of delivery System requirements Installation instructions Quickstart Function description 6 1 Data file 6 1 1 Open 6 1 2 Saving 6 1 3 Save under 6 1 4 Closing 6 1 5 Import from device 6 1 6 Printing 6 1 7 Last opened data files 6 1 8 Finish 6 2 Edit 6 2 1 Device profile 6 2 2 Characteristic line of the device setpoint table 6 2 3 Parameter lock 6 2 4 Extras Shows connection to PC 6 3 Help 6 4 Parameter adjustments 6 4 1 Parameter with check box 6 4 2 Direct insertion of parameter Read and write data files Terms of use O N N OO CO oO fF FB A A A A AA A A A N _ mh mh mt 0 oo no 1 Brief description 2 Scope of delivery 3 System requirements 4 Installation instructions 1
5. ated in Excel can be imported if they were saved in CSV format That way complex functions can be calculated in Excel e g different types of tanks and later on transferred into the indicators After the linearisation is completed it can be taken over 6 Function description 6 2 3 Parameter lock To protect parameter against misapplication a password can be assigned maximum 32 signs Parameter can only be changed and safed by entering the password Ril PM Tool M1 T1 S0_P1 30_EN xm Edit Extras Help Programming File Device a 2 A Sa Deviceaddress 1 H M1 xSR4x 0001 xxxx device name special Parameterprotection Current status unprotected panel meter indicator M1 function n nal 0 Password Repeat password 6 2 4 Extras minimal Value maximal Value current Value Under Characteristic line of the device the serial COM address can be selected which will be used for communication between the PC and the indicator RiT PM Tool M1 T1 S0_P1 30_EN xmI File Edit Device Extras Help Se ida Devices Settings ing l ea device name special function input signal sensor supply analog output alerts switching points interface boboi 2 33 10 panel meter indicator M1 no current loop 4 20mA no no 2 0 ASCII default Value minimal Value maximal Value curr
6. ce ASCH Configuration of the measuring input signal Measuring range 1 4 20mA 7 ann eae ee Device profile i Setpoint table Eingangskalibrierung 4 00 20 00 mA Eingangskalibrierung 4 00 20 00 mA Parameter lock OR Display value jije tn a si Fractional digits 0 0 4 H set points Fractional digits 0 0 gt arin wane Minimal value 1999 a o Insert after Delete 5 Quickstart Configuration of switching points RiT PM Tool M1 T1 S0_P1 30_EN xml File Edit Device Extras Help B aA amp Deviceaddress 1 Programming Bea o s BO 3 M1 xSR4x 0001 xxxx Eingang H common H alert 1 Specifies the threshold at which the alert should responds If the hysteresis be activated the lower limit of the alart is reduced Hy 1 hysteresis Fu 1 operation type H alert 2 H set points default Value minimal Value 200 maximal Value 1999 current Value 9909 200 Saving the configuration RT PM Tool M1 T1 S0_P1 30_ENxmi mm File Edit Device Extras Help 25 amp td amp Deviceaddress 1 Programming FIF 2 s 50 Eingang Writes the configuration to the device H common H alert 1 P G device name panel meter indicator M1 H alert 2 special function no H set points input signal current loop 4 20mA sensor supply no analog output no 2 alerts switching points 0 interface ASCII default Value minimal Value ma
7. d on an overview window appears in the lower corner on the right with available parameter Click on the desired parameter with the left mouse button to take it over a es SS RIT PM Tool M1 T1 S0_P1 30_ENxm sto File Edit Device Extras Help 5 2d G amp Deviceaddress 1 Programming a 2 258 0 B M1 xSR4x 0001 xxxx Eingang fm tYPE input signal Fm End end value em OFFS start value dot decimal point tArA tara value Defines the input type On the sensor calibration the sensor signal should have the right value at the j or teaching point ZErO zero point tranquilization H E common Parameter measuring range alert 1 0 sensor calibration 6 alert 2 1 4 20 mA H set points default Value minimal Value 1 maximal Value 0 current Value 0 sensor calibration 6 4 2 Direct insertion of parameter With this type parameter the current value can be edited directly via the cursor Just click once into the field RIT PM Tool M1 T1 S0_P1 30_EN xml o lie File Edit Device Extras Help S Wd a Deviceaddress 1 Programming 3 M1 xSR4x 0001 10x e a 2 23 0 Eingang tYPE input signal End end value i OFFS start value The given value is added to the scaled value dot decimal point tArA tara value ZErO zero point tranquilization H common alert 1 H alert 2 H set points x default Value minimal Value 0 maximal Value
8. e configuration file can be selected with the valid extension xml Thus all possible options of the desired device line can be displayed Parameter that were read or written at last are made recallable 6 1 2 Saving The just opened device configuration file can be saved with the ongoing given parameter under the current file name 6 1 3 Save under At new projects the file name should be changed first via the option Save under this way standard original data cannot be changed Thus the total configuration file including the currently given parameter is saved under the declared data file To avoid changes in the basic configuration files save such data files write protected 6 1 4 Closing The just opened device configuration file will be closed 6 1 5 Import from device The parameter of the configuration file are read out from the indicator into the PC Thus the correct COM interface needs to be adjusted 6 1 6 Printing Under menu item Printing the current parameter can be printed out in a formatted overview on a windows printer 6 1 7 Last opened data files The four last opened data files are provided for direct call and can be opened by simply clicking on 6 1 8 Finish The program PM TOOL is finished If the configuration had been changed then a dialog appears if the current configuration shall be safed 6 Function description 6 2 Edit The adjustments for the program will be deposited under menu
9. ent Value Via a check box available COM addresses can be selected A standard PC comes in general with two COM interfaces Using a laptop generally a USB RS232 Gateway is used The driver of the gateway simulates a RS232 interface so that a COM Port feely assigned and runs with this software too 6 Function description Settings ramming Sa a A EEEE Settings X Interface RiT PM Tool M1 T1 S0_P1 30_ENxml GBC serial Port in Edit Device Extras Help Bluetooth 3 2 a G amp Deviceaddress 1 Proc ee 3510 M1 xSR4x 0001 xxxx COM Port z BaudRate 9600 7 20mA Protocoll automatice Device behavior after programming dicator M1 unchanged reinitialized rebooted Language German English Device description file Langue EN English v Additional features Request device address not ready l Ok Abbrechen Note For device type M1 xS please adjust a Baudrate of 1200 6 3 Help Via menu item Help a program assistance and a program information can be called up These functions are common for Windows programs which is why we will not go deeper into this matter here RT PM Tool M1 T1S0_P1 30_ENam T File Edit Device Extras Help S H a Deviceaddress Index 1B Content About PM Tool a 2 85 6 device name panel meter indicator M1 special function no input signal current loop 4 20mA senso
10. nly be used in combination with the device lines of the manufacturer respectively copyright owner Every usage with other devices or assembly groups is forbidden 8 2 Copyright 8 2 1 The installation of the software is only allowed via the available data compilation 8 2 2 The dublicating of the complete data carrier or hard disc storage unit of the computer is only allowed for data backup reasons 8 2 3 The modification of the installation or the creation of modified data carrier for the software is forbidden 8 2 4 The transfer of the software to a third person is only allowed in combination with the corresponding digital indicator as well as the orignal installation carrier 8 2 5 An unregulated distribution of the software complete or in parts via the internet or data carrier is forbidden and will be avenged as copyright infringement 8 2 6 The number of installations which may be created via an existing original installation medium is not limited 8 2 7 The derived control files in XML format are not subject of copyright as long as they are used in connection with the digital indicators of the copyright owner 8 2 8 All text and contents on this medium are protected by copyright 8 3 Program code The program code of the software may not knowingly be changed neither on an installation medium nor on a computer Thereby it is irrelevant if the application is used commercial or private 8 4 Warranty The manufacturer ass
11. ontrol file is required as XML which needs to be loaded via the dialog File Open During the first communication with the indicator make sure that the correct device address is adjusted in the menu line It is always set on 1 in delivery status The PM Tool uses only the ModBus ASCIl protocol Changing to ModBus RTU and back is only possible manually via the front keypad of the display 4 Installation instructions The software installation on the CD happens via setup exe For software operation Net is needed which can be installed afterwards too if desired This must be confirmed in the installation dialog 5 Quickstart 5 Quickstart Install the software from the CD on your computer and follow the instructions on the display Plug the interface cable in the red socket on the rear side of the device and the other end of the interface cable into the USB port of your computer Connect the device to the corresponding voltage supply Now start the PM TOOL software Ensure that the correct COM port has been selected see picture 6 2 4 Extras on page 7 Readout the configuration of the device File GE do Deviceaddress Programming 6 E B Engang Reads the configuration from the denice HE common gt aen iB det Gevkename panel meter indicaor M specal function no vA ponts input sonat current loop 4 20evA senso supp no anaing output n ders 2 Suitching points inlerla
12. point Table Setpoint Table 0 sa Input value Input value Measuring range 1 4 20 mA v Measuring range 1 4 20 mA v Eingangskalibrierung 4 00 20 00 mA Eingangskalibrierung 4 00 20 00 mA Display value Display value Fractional digits 0 0 v Fractional digits 0 0 Minimal value 1999 Minimal value 1999 Maximal value 9999 Maximal value 9999 Setpoint Input Display gt Start 4 000000 400 End 20 000000 2000 In the upper area it is shown which measuring input has been selected at the moment Below follows the table in which all supporting parameter are listed Afterwards follows in the meantime the corresponding display value Below follows the table in which all supporting parameter are listed Then the corresponding display value follows in the same line List here which value shall be shown in the display before the analog input value To add or remove new supporting points the line needs to be selected first see above Via the right mouse button the contect menu can be called up This enables the insertion or removal of a parameter By insertion respectively removal a new line before the selected line will be highlighted in blue Offset and final value cannot be removed as these parameter mark the start and the end of the linearisation Caution The analog values are stated with positions after decimal point whereat they need to be separated by a decimal point Furthermore linearisations that have been gener
13. r supply no analog output no alerts 2 switching points 0 interface ASCII default Value minimal Value maximal Value current Value 6 Function description 6 4 Parameter adjustments The menu tree is used like the Windows Explorer If a stands in front of the description a group of parameter can be selected via this description This is comparable to a Windows Explorer directory RT PM Tool M1 T1S0_P1 30_ENxmi Ea File Edit Device Extras Help o amp d c Deviceaddress 1 Programming FET E ENO device name panel meter indicator M1 special function no input signal current loop 4 20mA sensor supply no analog output no alerts 2 switching points 0 interface ASCII default Value minimal Value maximal Value current Value Via double click on the identifier or a simple mouse click left mouse button on the scroll down button the following level can be opened RT PM Tool M1 T1 S0_P1 30_EN xml File Edit Device Extras Help B 2 wo Deviceaddress 1 Programming Si 1M1 xSR4x 0001 xxxx H Eingang H common alert 1 alert 2 device name panel meter indicator M1 E special function no set points input signal current loop 4 20mA sensor supply no analog output no alerts 2 switching points 0 interface ASCII default Value minimal Value maximal Value current Value 6 Function description On the parame
14. ter level there are no more scroll down buttons RiT PM Tool M1 T1 S0_P1 30_EN xmI File Edit Device Extras Help S id amp Deviceaddress 1 Programming E TTT EN E tYPE input signal Shain a device name panel meter indicator M1 vi OFFS start value special function no 9 dot decimal point input signal current loop 4 20mA i tArA tara value sensor supply no ZErO zero point tranquilization rear output x s alerts eee switching points 0 H alert 1 interface ASCII H alert 2 set points default Value minimal Value maximal Value current Value Once a device parameter has been selected a parameter information and the parameter values are shown on the right side of the window RiT PM Tool M1 T1 S0_P1 30_EN xml File Edit Device Extras Help 5 a G Deviceaddress 1 Programming a 0 825 0 M1 xSR4x 0001 xxxx Eingang ea YPE input signal End end value OFFS start value dot decimal point Defines the input type On the sensor calibration the sensor signal should have the right value at the tArA tara value a teaching point ZErO zero point tranquilization HE common Parameter measuring range H alert 1 0 sensor calibration H alert 2 1 4 20 mA H set points a default Value minimal Value 1 maximal Value 0 current Value 1 10 6 Function description 6 4 1 Parameter with check box As soon as current value is clicke
15. umes no liability for damages occured by usage or installation of the software The software has been checked accurately by the manufacturer The manufacturer assures that at the time of compilation of the installation files no fawlty effect of the software was known 8 5 Support 8 5 1 A claim for support has only the original purchaser 8 5 2 A claim for updates at no charges is not provided 8 5 3 An exception to 8 2 Copyright is if the current version is fawlty or the usage with the corresponding and provided indicator is not possible In this case the customer has a claim for an improved respectively updated version The manufacturer is given a period of up to 6 weeks after information of the defects for rework 8 5 4 If the customer should purchase an indicator at a later date which may not be supported by the current software version then this will not lead automatically to a claim for an update at no charge It can be granted on a voluntary basis 8 6 Exclusion If the specified menu items if the terms of use should have no or only a limited legal validity then this has no impact on the validity of the remaining menu items of the terms of use PM TOOL_GB pdf Update 06 03 2015
16. ximal Value current Value Remove the connection cable The device is now ready for operation Reset to factory setting RiT PM Tool M1 T1 S0_P1 30_EN xml File Edit Device Extras Help 6 amp A amp Deviceaddress 1 Programming gaan san 5 Eingang common H alert 1 F alert 2 device name panel meter indicator M1 T special function no set points input signal current loop 4 20mA sensor supply no analog output no 2 alerts switching points 0 interface ASCII default Value minimal Value maximal Value current Value 6 Function description 6 Function description With this software sets of parameter can be read out from a device or a PC or can be written into the display from the PC Therefor a device specific configuration file is necessary xml data file 6 1 Data file Via menu item Data file the most important program functions can be carried out RT PM Tool M1 T1 S0_P1 30_EN xml o File Edit Device Extras Help ki Gj Open 1 Programming bi Save Save as Sj Close device name panel meter indicator M1 special function no input signal current loop 4 20MA sensor supply no analog output no alerts 2 switching points 0 Import from device Print Recent files Exit interface ASCII default Value minimal Value maximal Value current Value 6 1 1 Open Here an availabl