Home
        BULLETIN 193 - Rockwell Automation
         Contents
1.                                 Wiring Figure 1 5 Wiring Diagram  5   i NC  2  NC  eoo 3  B Line  0000 4  RTS  9   5  GND BUS  6   5V BUS OUT  7  NC  8  A Line     I1      i SHIRE  ousing     A2    Q04 264VDC   ir S  aw et  gl S amp S Ssv  S IN2  Q IN1  OUTA j      B300       of x    Table 1 1 Wire and Size Torque Specifications    5 Ib  in    C c  1X 24   12 AWG  2X 24   16 AWG              gt  1X 02   25 mm   2X 0 25   1 mm     0 55 Nem  Ces  C  Gm 1X 0 2   2 5 mm   2X 0 2   1 mm              Publication 193 UM010A EN P     January 2008    1 4 Installation and Wiring       Dimensions Figure 1 6 Dimension Diagram    J  a    F                                                                                                                                                                                  O  O  Qj  9        t          M                                                                            Y  ra  e  Table 1 2 Dimension Specifications   Contactor Cat  No    E1 Plus Cat  No  A B C D E F G H J K L  100 C09   C12   C16    193  EE B mm 67 48 85 2 24 5 13 9 35 60 86 5 2 4 5 22   C23  in  2 64   5 83  3 35 96   55   1 38   2 36   3 40    08  17  86   100 C30   C37 193 EE_D mm 67 48 101 2 24 5 13 9 35 60 104 2 45 22    in  2 64   5 83  3 98 96   55   1 38   2 36   4 09    08  17  86   100 C43 mm 715 48 101 2   24 5 184   45 60 104 2 45 22    in  2 82   5 83  3 98  96  44   1 77   2 36   4 09    08  17  86   100 C60   C72   C85 193  EE_E mm 94 91 6 120 4 29 23 8 55 100
2.      Remove the control circuit power and check for continuity across the appropriate o    13 14   If the continuity test indicates the output is open  replace the E1 Plus PROFI  he supply voltage against the ratings of the contactor and the relay output before i      Remove control circuit power and check the control circuit fuse and the control wir    PROFIBUS Module output terminals     ratings       Check the DEVICE STATUS and TRIP STATUS parameters  If a Protection Fault exist  and Warning troubleshooting procedure  If a PROFIBUS related fault exists  refer to the PROFIBUS       roubleshooting procedure       Check the OUTA Pr FitState  Pr FitValue  Pb FitState  Pb FitValue  Pb IdlState  and P    programmable parameters  The Pr FltState and Pr FltValue parameter supersede th  parameters     utput terminals   BUS Module  Check  nstalling a new unit   ing to the E1 Plus      Check the control circuit power supply  Verify the voltage is within the contactor and overload relay    s  refer to the Trip    b IdiValue  e Pb Fit or Pb Idle       OUTA    Output A does not appear to  turn off  open  when  commanded to do so       Check the programmable controller ladder logic and 1 0 mapping      Remove the control circuit power and check for continuity across the appropriate o  13 14   If the continuity test indicates the output is closed  replace the E1 Plus PROFIBUS Module   Check the supply voltage against ratings of the contactor and the relay output before installing a new   
3.   at 240V AC   0 25 A  at 110V DC   0 1 A  at 220V DC   Minimum Operating Current 10 mA at 5V DC  Rating Designation B300  Utilization Category AC 15  Resistive Load Rating 5 A  250V AC   p f  1 0  5 A  30V DC  Inductive Load Rating 2 A  250V AC   p f  0 4    L R 7 ms  2 A  30V DC  Short Circuit Current Rating 1 000 A  Recommended Control Circuit Fuse KTK R 6   6 A  600V   Rated Number of Operations  Out A   W 100 C 09    100 C43 5 000 000  W 100 C 60    100 C85 2 500 000  W NEMA Size 0   2 1 000 000  W NEMA Size 3 300 000  Input Ratings   Terminals  IN 1  1  IN 2  2  SSV  Sensor Supply Voltage  3  Supply Voltage  provided by module  20 4   26 4V DC    Publication 193 UM010A EN P     January 2008    A 2 Specifications                            Type of Inputs Current Sinking  ON State Voltage 15V DC  On State Current  turn on  15mA   Steady State Current 15 mA  Off State Voltage 5 VDC  Off State Current 0 5 mA  Transition Voltage 5    15 VDC  Transition Current 0 5    15mA    Environmental Ratings                             Ambient Temperature Tamb  Storage  40   485 C   40    185  F   Operating   Open   20   460 C   4    140  F    Enclosed   20   440 C   4    104  F   Humidity  Operating 5   95  non condensing  Damp Heat   Steady State per IEC 68 2 3  Damp Heat   Cyclic per IEC 68 2 30  Cooling Method Natural Convection  Vibration  per IEC 68 2 6  3G  Shock  per IEC 68 2 27  30 G  Maximum Altitude 2000 m  Pollution Environment Pollution Degree 2  Terminal Marking EN 50012  
4.   indication must be determined and corrected before attempting    ATTENTION    operation  Failure to correct a control system or mechanical malfunction  may result in personal injury and or equipment damage due to  uncontrolled machine system operation        The E1 Plus PROFIBUS Module has four PROFIBUS modes of operation  Power up Mode   Run Mode  and Configuration Error Mode     Power Up Mode    During power Up Mode  the NETWORK STATUS LED should flash green for approximately  1 4 second  then red for 1 4 second        The E1 Plus PROFIBUS Module protection functions are still  operational even without an established network connection     IMPORTANT       If the power up is successful  the overload relay will enter Run Mode     Run Mode    In Ran Mode  the E1 Plus PROFIBUS Module will operate as a slave device to a master device   The NETWORK STATUS LED will blink green if the PROFIBUS interface is in idle mode   When on line  the NETWORK STATUS LED will turn solid green     In the Run Mode  the E1 Plus PROFIBUS Module will       Exchange Cyclic I O with a master on the PROFIBUS network     Respond to Acyclic  DP V1  read  and write  services    If a communication error is detected  the E1 Plus PROFIBUS Module will either enter the  Configuration Error Mode     Publication 193 UM010A EN P     January 2008    4 2 Troubleshooting       Configuration Error Mode    In this mode  the E1 Plus PROFIBUS Module   s NETWORK STATUS LED flashes ted at 1Hz     Configuration Error Conf
5.   match the actual size of the parameter                          OxC1 X Write access to a read only parameter    Write constrain conflict   0xC3 X Write acces to a parameter mappedas       Resource Busy  Cyclic I O  Input and Output The following table lists problems related to the on board inputs and outputs     Troubleshooting Procedures possible causes  and corrective actions     Table 4 6 Input and Output Troubleshooting Procedures    Failure Type Failure Description Corrective Action  Input 1  2 Input 1 or 2 does not appear to 1  Check the supply voltage  recognize a contact closure 2  If the applicable contact closed but the E1 Plus PROFIBUS Module Input does not recognize the closure     check the continuity and wiring to the connected contact    3  Measure the voltage across and current through the applicable input  Verify they are within the ratings  of the E1 Plus PROFIBUS Module  See Appendix A     4  Check the programmable controller ladder logic and 1 0 mapping              Input 1  2 Trip reset operation Check the programming of Parameter 28   N7 Assignment or Parameter 29  IN2 Assignment     Publication 193 UM010A EN P     January 2008    4 4 Troubleshooting       Table 4 6 Input and Output Troubleshooting Procedures  Continued     Failure Type  OUTA    Failure Description    Output A does not appear to  turn on  close  when  commanded to do so     Corrective Action      Check the supply voltage    Check the programmable controller ladder logic and I O mapping
6.  0   Disabled Units      Min  Value 0000000000000000  Max  Value 0000000001101101  Default Value 0000000000000000  Bit Function   15 14 13 12 11 10 7 6 5 4 3 2 1 0  X Overload  X Not Used  X Jam  X Underload  X Not Used  X Comm Fault  X Comm Idle  X X X X X X X Not Used  Single Three Ph Index No  10  This parameter configures the PROFIBUS Module for single    Access Rule Read Write  or three phase application  This parameter should be set to S 1b     Single Phase  when Bulletin 193S or 592S devices are Li yte  employed  Group Advanced Setup  Units      Min  Value 0   Single Phase  Max  Value 1   Three Phase  Default Value 1  OL Reset Mode Index No  11  This parameter defines whether a trip can be automatically   Access Rule Read Write  or manually reset  This setting overrides the E1 Plus DIP s  switch adjustment while the PROFIBUS Module is powered    Size 1 byte  Note  however  that the E1 Plus manual reset button  Group Advanced Setup  accessible at the front  is always active     Units      Min  Value 0   Manual  Max  Value 1   Automatic  Default Value 0  OL Warning Level Index No  12  This parameter sets the overload warning level  Access Rule Read Write  Size 1 byte  Group Advanced Setup  Units   Thermal Utilization  Min  Value 0  Max  Value 100  Default Value 90          Publication 193 UM010A EN P     January 2008    3 8 PROFIBUS Configuration       Publication 193 UM010A EN P     January 2008    Jam Inhibit Time    This parameter defines the amount of time for which 
7.  126 2 5 4 22    in  3 70     7 54  474 1 14  94   2 16     3 94     4 94     08  21  86                                                                 Publication 193 UM010A EN P     January 2008    Introduction    Trip Status   Identification    Trip Resetting    Trip and Warning Enable    Overload and Phase Loss  Protection    No       Protection Functions    The purpose of this chapter is to provide detailed information regarding the protective trip and  warning functions that the 193 EPRB PROFIBUS Module adds to the E1 Plus Overload Relay   In this chapter  you will find considerable mention given to parameters as they relate to these  functions  For complete descriptions of the programming parameters  refer to Chapter 3    PROFIBUS Configuration     The PROFIBUS Module determines trip status and identification through monitoring of  reference signals inside the E1 Plus Overload Relay  On power up  it assumes that the E1 Plus  Overload Relay is in a non tripped condition  For definitive feedback on trip status of the E1  Plus Overload Relay  one of the PROFIBUS module inputs may be wired to the N O  auxiliary  contact  terminals 97 and 98  of the E1 Plus Overload Relay  Parameters 28 and 29 are used to  configure the assignment of the inputs  For this function  use the  OL Contact  configuration     The following options are available for resetting a tripped E1 Plus Overload Relay with a  PROFIBUS module   e Blue mechanical reset button located on the front of the E1 Pl
8.  Index No     Access Rule       3  Read       Size    2 bytes       Group    Monitor       Units       Min  Value       Max  Value       Default Value       Function        15    14    13    12    11    10    Overload    None          Phase Loss       Jam                                  Warning Status                This parameter provides warning identification       1   Warning  0   No Warning    Bit       ot Used       Index No     Access Rule    4  Read       Size    2 bytes       Group    Monitor       Units       Min  Value       Max  Value          Default Value    Function        15    14    13    12    11    10    Overload       None       Not Used       Jam       Underload       Not Used       Comm Fault       Comm Idle       Nonvolatile Memory Fault                               Device Status    This parameter provides status information related to the E1          Plus Overload Relay and  1   On or Present  0   Off or Not Present       he PRO             FIBUS Module           Not Used    Index No     Access Rule    5  Read       Size    2 bytes       Group    Monitor       Units       Min  Value       Max  Value          Default Value       None    Publication 193 UM010A EN P     January 2008    3 6 PROFIBUS Configuration                                                                                                                                                                      Bit Function   15 14 13 12 11 10 7 6 5 4 3 2 1 0  X Trip  X Warning  X Out A  X 
9.  M              0002 0 eee B 4  Rockwell Automation Support  5s ripe s ae ed Rn B 4  Installation Assistance sse cesses tee Re dd B 4    New Product Satisfaction Return    0    0    cee eee B 4    Introduction    Chapter 1       Installation and Wiring    The purpose of this chapter is to provide the necessary instructions to successfully install a  193 EPRB PROFIBUS Module to an E1 Plus Overload Relay and properly connect to a    E  O   rj  e  ies   C  Nn  2  2  o  4  Aa       ATTENTION To prevent electrical shock  disconnect from power source before    installing or servicing  Install in suitable enclosure  Keep free from  contaminants      l          ATTENTION The side mount module contains ESD  electrostatic discharge  sensitive  parts and assemblies  Static control precautions are required when  installing  testing  servicing  or repairing this assembly  Component    damage may result if ESD control procedures are not followed  If you     l    are not familiar with static control procedures  refer to Rockwell  Automation publication 8000 4 5 2     Guarding Against Electrostatic  Damage     or any other applicable ESD protection handbook           The purpose of this document is to serve as a guide for proper  ATTENTION i i        installation  The National Electrical Code and any other governing   regional or local code will take precedence  Rockwell Automation cannot    assume responsibility for the compliance or proper installation of the     l    side mount module or 
10.  Pr FitValue            The jam inhibit timer starts after the load current transitions from 0 A to  30  FLA  The PROFIBUS Module does not begin monitoring for a jam  condition until the Jam Inhibit Time expires     IMPORTANT       Jam Warning  Parameter 16  Jaw Warn Level  allows the installer to define the current at which the PROFIBUS  Module will indicate a warning  It is user adjustable from 100   600  FLA   The PROFIBUS Module will indicate a Jam warning if   e No warning currently exists    Jam Warning is enabled    Jam Inhibit Time has expired  e The motor current is equal to or greater than the Jam Warn Level  When the Jam Warning conditions are satisfied  the following will occur   e Bit 2 in Parameter 4  Warning Status  will go to    1       e Bit 1 in Parameter 5  Device Status  will go to    1          IMPORTANT The Jam Warning function does not include a time delay feature  Once  the Jam Inhibit Time has expired  the Jam Warning indication is    instantaneous        Motor current less than a specific level may indicate a mechanical malfunction in the installation   such as a torn conveyor belt  damaged fan blade  broken shaft  or worn tool  Such conditions  may not harm the motor  however  rapid detection may help to minimize equipment damage  and loss of production     Publication 193 UM010A EN P     January 2008    2 4 Protection Functions       Communication Fault  Protection    Communication Idle Protection    Publication 193 UM010A EN P     January 2008    
11.  by the PROFIBUS  module parameter 11  OL Reset Mode  while the PROFIBUS module is    powered        Overload Warning  The PROFIBUS Module continuously monitors the E1 Plus Overload Relay s percentage of  thermal utilization signal  Parameter 2  Therm Utilized  provides this value     Parameter 12  OL Warning Level  is used to adjust the setpoint to alert for an impending overload  trip and is adjustable from 0   100  TCU     The PROFIBUS Module will indicate an overload warning if all the following conditions are  met     e No warning currently exists    Overload warning is enabled  e  Therm Utilized is equal to or greater than OL Warning Level  When the overload warning conditions are satisfied  the following will occur   e Bit 0 in Parameter 4  Warning Status  will go to    1         Bit 1 of Parameter 5  Device Status  will go to    1          IMPORTANT  Therm Utilized will stabilize at a value of approximately 88  with the    motor operating continuously at rated current        Motor current greater than the motor s nameplate rating can indicate a high overload or stall  condition  such as an overloaded conveyor or jammed gear  These conditions can result in  overheating of the motor  and equipment damage  Rapid jam fault detection helps to minimize  damage and loss of production     By continuously monitoring the motor current level signal as a percentage of the E1 Plus  Overload Relay s dial FLA setting  the PROFIBUS module allows jam trip and warning  capability     J
12.  byte  3  is set as  Enabled   Note that this will result in any previous settings stored in non  volatile memory to be replaced     Initial values supplied through the User Prm Data will only be used if all initial parameter values  are valid  In case an illegal initial parameter value is specified  an out of range parameter error  will be signalled to the PROFIBUS master     e loading of initial data also includes the  Program Lock  setting  which means that it is  The loading of initial data al ludes the  Program Lock  setting  which that it  possible to specify a default configuration during startup  which will then be protected from  write access during runtime        IMPORTANT Initial values supplied through the User Prm Data will only be used if all    initial parameter values are valid  In case an illegal initial parameter value  is specified  an out of range parameter error will be signalled to the  PROFIBUS master           IMPORTANT Special care has to be taken for parameters mapped as Cyclic I O  since    their value may be overwritten during the first bus cycle  This can be  prevented using parameter 20  Program Lock   however as soon as the  Program Lock is disabled  the value of these parameters will be replaced  by the corresponding I O data        The GSD file is used to house the Control  and Status Registers  These registers controls  and  reflects the overall status of the module respectively     Control Register    The structure controls various aspects o
13.  in parameter 5  Device Status   e Bit 6  Save Ready     Used to indicate that a save of parameter values of parameters mapped as  Cyclic I O has been performed  The bit can be cleared again by clearing the  Save  bit  in the Control Register   e Bit 7  Motor Current     Same functionality as bit 5 in parameter 5  Device Status   Parameter Programming Program Lock    Parameter 20  Program Lock  provides a degree of security from having parameter settings    unintentionally altered when programmed to the    locked    setting     If enabled  all parameters except Program Lock  20  are protected from acyclic  DP V1  write    access  and any changes made to the value of parameters mapped as Cyclic I O will be ignored     The  Program Lock  parameter will  if mapped as Cyclic I O  be processed prior to processing  other parameters mapped as Cyclic I O  The loading of initial data is not affected by the    Program Lock     Publication 193 UM010A EN P     January 2008    3 4    PROFIBUS Configuration    Table 3 3 Parameter Groups    Resetting to the Factory Default Values       Parameter 25  Set zo Defaults  allows the installer to reset all parameter settings  including trip    logs  to the factory default values        IMPORTANT    Resetting to factory default values also resets the node address of the  PROFIBUS module to its default value of 126        Parameter Group Listing    The 193 EPRB PROFIBUS Module contains six parameter groups                                            
14.  networks gsd         The PROFIBUS Module supports the Set Slave Address  SSA  service  which can be used to  specify the node address from the PROFIBUS Master     If successful  the new node address will be stored in non volatile memory  replacing the previous  value of parameter 35  SSA Node Address     NOTE  This service will be rejected if a previous SSA service request has specified that no  further changes should be allowed  or if the PROFIBUS Module is in Data Exchange     The PROFIBUS Module detects the baud rate automatically  and supports all standard baud  rates     Supported baud rates   e 9 6kbps  e 19 2kbps  e 45 45kbps  e 93 75kbps  e 187 5kbps  e 500kbps  e 1 5Mbps  e 3Mbps  e 5Mbps  e 12Mbps    PROFIBUS Information B 3       PROFIBUS Identity    The module has the following identity on PROFIBUS           PI Identification Number Ox0AC7  Vendor Name Allen Bradley  Model Name  193 EPRB        Identification and Maintenance  I amp M     Identification  amp  Maintenance  I amp M  provides a standard way of gathering information about an  I O device  The intention is to help the end user in maintenance of the product     The module features the following I amp M records                                      Table B 6 IMO Record  Information Size Default Value  Manufacturer ID 2 octets 0x0002  Order ID 20 octets 193 EPRB  Serial Number 16 octets  assigned during manufacturing   Hardware Revision 2 octets  assigned during manufacturing   Software Revision 4 octets  a
15.  this manual     Reproduction of the contents of this manual  in whole or in part  without written permission of  Rockwell Automation  Inc  is prohibited     Throughout this manual  when necessary we use notes to make you aware of safety  considerations        Identifies information about practices or circumstances that can    cause an explosion in a hazardous environment  which may lead  to personal injuty or death  property damage  ot economic loss           IMPORTANT Identifies information that is critical for successful application    and understanding of the product           Identifies information about practices or circumstances that can lead to    ATTENTION    personal injury or death  property damage  or economic loss  Attentions  help you      identify a hazard     avoid a hazard      recognize the consequence          SIH avy Labels may be located on or inside the equipment  e g   drive or  motor  to alert people that dangerous voltage may be present           BURN HAZARD Labels may be located on or inside the equipment  e g   drive or  motor  to alert people that surfaces may be dangerous    temperatures        Chapter 1    Installation and Wiring    Chapter 2    Protection Functions    Chapter 3    PROFIBUS Configuration    Table of Contents    TEAPORUCHON ao his Grats PUN etude ALS reek None patat dete qs 1 1  FOATH  ES re anian tepdt Accra ue lit bot Gta glee PUDE ferte p 1 2  Installatloty sssr pero oes tete esr MES natabh ate E se 1 2  METTI osi pt e Sede KI 
16.  unit       Remove control circuit power and check the control circuit fuse and the control wir    PROFIBUS Module output terminals          Check the OUTA Pr FitState  Pr FitValue  Pb FitState  Pb FitValue  Pb IdiState  and P       programmable parameters  Then check the DEVICE STATUS and TRIP STATUS para  Protection Fault exists  refer to the TRIP STATUS parameters  If a Protection fault ex    roubleshooting procedure     utput terminals    ing to the E1 Plus    b IdiValue  meters  If a  ists  refer to the Trip    and Warning troubleshooting procedure  If a PROFIBUS related fault exists  refer to the PROFIBUS       OUTA       The contactor connected to    Output A appears to  chatter     Trip and Warning  Troubleshooting Procedures         Check the programmable controller s ladder logic program     Check the control circuit supply voltage  Verify it is within the ratings of the contac       overload relay s outputs       Remove the control circuit power  Verify all control wiring is properly secured     Table 4 7 Trip Warn LED Troubleshooting Procedures       or coil and the    The following table lists the possible causes for each trip type and the recommended action to          Overload 1  Motor overloaded 1  Check and correct source of overload  load  mechanical transmission  components  motor bearings    2  Improper setting 2  Set FLA dial and trip class to match the motor and application requirements   Phase Loss 1  Missing supply phase 1  Check for open line  i e  bl
17. 00   3 4  Parameter Group Listing  x0 uve o ROO ret NACTUS 3 4  Monitor GTOUD oss HON WERE Ya exa vae Dea NONI RS 3 4  Advanced Setup Group ex eX xs tte baee Eat Deae ame ed gs 3 7  Reset  Lock Groupes einasi oath eld on bts non fte lior 3 9  I O Setup Group  35 c RS ST Es DIE ah V 3 10  Tip Histo Gro  p 2 isses cs cwlont devi ur qoi tetto iy odas 3 11  PROFIBUS Setup Groups ssh in oua ds e ae ee toes 3 12    Publication 193 UM010A EN P     January 2008    Chapter 4    Troubleshooting    Appendix A   Specifications    Appendix B    PROFIBUS Information    TntroducttO fi  veo did wks Rs eS ee un 4 1  PROFIBUS Modes of Operation n0 haw chinese Wane ue t C i n 4 1  Powe  Up Mode Las gira thts vereda anette NE 2 4 1  R  n Modes uo die ee  eat bd d ane mer 4 1  Configuration Error Mode  seed cet ttt ER Rc ct et 4 2  Fatal Error Mode  iiu eva BEL exu PENSA Ae 4 2  PROFIBUS Troubleshooting Procedures             0 0 00005 4 2  Network Status LB  eee e EE e bear Eae 4 2  DP VTEttOf Codes  setae eR nA RES CES 4 3  Input and Output Troubleshooting Procedures              004  4 6  Trip and Warning Troubleshooting Procedures               4  4 8   ICD A 1  Structure of the  Set Prm Data  telegram   aacra y Reha B 1  Ele  ttonic Data Sheet ijt da nad iore oS ure Ue AA B 2  oet DAVE AG AEES Sn s RR e ae aut ate RR RNC De RAN T CS B 2  Supported Baud Rates saan bo dd eter m e dead ie bea B 2  PROTEIBUS Idetitity  2122 Ex usce Dim EA Ud dade d dade B 3  Identification and Maintenance  I amp
18. 2008    Appendix B       PROFIBUS Information    Structu re of the  Set Prm During startup of the network  it is possible to force start up values for all writable parameters   D ata  telegram through the User Prm Data  The module will use the settings provided that the  Parameter  Initialization  setting  User Prm Data byte  3  is set as  Enabled   Note that this will result in  any previous settings to be replaced by the settings from the User Prm Data     Table B 5 Structure of the  Set Prm Data  telegram                                                                                                          Byte no  Name Description   0 2 DP V1 standard bytes   3 Parameter Initialization Enables Disables initialization of parameters via parameterization data   O  Disanied   4 5 Trip Enable Initial value for parameter 8  Trip Enable   6 7 Warning Enable Initial value for parameter 9  Warning Enable   8 Single Three Ph Initial value for parameter 10  Single Three Ph   9 OL Reset mode Initial value for parameter 11  OL Reset mode   10 OL Warning Level  96Therm  Util   Initial value for parameter 12  OL Warning Level   11 Jam Inhibit Time  1s  Initial value for parameter 13  Jam Inhibit Time   12 Jam Trip Delay  0 15  Initial value for parameter 14  Jam Trip Delay   13 14 Jam Trip Level  96FLA  Initial value for parameter 15  Jam Trip Level   15 16 Jam Warn Level  96FLA  Initial value for parameter 16  Jam Warn Level   17 UL Inhibit Time  1s  Initial value for parameter 17  U
19. Degree of Protection IP20    Electromagnetic Compatibility    Electrostatic Discharge Immunity       Test Level 8 kV Air Discharge  4 kV Contact Discharge  Performance Criteria 12   Radiated RF Immunity  Test Level 0V m  Performance Criteria 12        Electrical Fast Transient Burst Immunity   Test Level 2 kV  Power   kV  control   Performance Criteria   1  2        Surge Immunity   Test Level 2 kV L E  kV L L  Performance Criteria       a2        Radiated Emissions Class A          Conducted Emissions Not tested    WARNING  This is a class A product  In domestic environment  this product may cause radio interference  in which case the  user may be required to take adequate measures        PROFIBUS Communications           Baud Rate 9 6 k  19 2 k  45 45 k  93 75 k   187 5 k  500 k  1 5 M  3M  6 M   12M   Auto Baud Rate identification Yes    Publication 193 UM010A EN P     January 2008    Specifications A 3                               DP V0  Cyclic data exchange  Yes  DP V1  Acyclic services  Yes  DP V2  Acyclic services  No  Set Slave Address  SSA  support Yes  Jam Protection   Trip Level 150   600  FLA  Trip Delay 0 1   25 0 sec   Inhibit 0   250 sec   Standards  UL 508  CSA 22 2  No  14  EN 60947 4 1   Performance Criteria 1 requires the DUT  device under test  not to experience degradation or loss of      performance    2     Environment 2   Heavy Industrial     Publication 193 UM010A EN P     January 2008    A 4 Specifications    Publication 193 UM010A EN P     January 
20. In 1  X In 2  X Motor Current  X X X X X X X X Not Used  Firmware Revision Index No  6  This parameter reports the firmware revision of the PROFIBUS Access Rule Read  Module  f  Format  Size 2 bytes  0x0107 equals version 1 07 Group onitor  Units      Min  Value 0  Max  Value 65535  Default Value one  Serial Number Index No  7  This parameter reports the serial number assigned during Access Rule Read  production of the PROFIBUS Module  Size T bytes  Group onitor  Units      Min  Value 0  Max  Value OxFFFFFFFF  Default Value one  Advanced Setup Group  Trip Enable Index No  8  This parameter allows the installer to enable or   Access Rule Read Write  disable the Jam Trip function    1   Enabled Size 2 bytes  0   Disabled Group Advanced Setup  Units      Min  Value 0000000000000000  Max  Value 0000000000000100  Default Value 0000000000000000  Bit Function   15 14 13 12 11 10 7 6 5 4 3 2 1 0  X Not Used  X Not Used  X Jam  X X X X X X X X X X X Not Used       Publication 193 UM010A EN P     January 2008                                                 PROFIBUS Configuration 3 7                                                                                                                                                                Warning Enable Index No  9  This parameter allows the installer to enable or   Access Rule Read Write  disable the warning functions separately  All S B  warning functions are disabled from the zg 2 bytes  factory  Group Advanced Setup  1   Enabled   
21. L Inhibit Time   18 UL Warn Level  96FLA  Initial value for parameter 18  UL Warn Level   19 Program Lock Initial value for parameter 20  Program Lock   20 OutA Pr State Value Bit 0  Initial value for parameter 22  OutA Pr FitState  Bit 1  Initial value for parameter 23  OutA Pr FitValue   Other bits  Not used  Must be set to 0    21 OutA Pb State Value Bit 0  Initial value for parameter 24  OutA Pb FitState  Bit 1  Initial value for parameter 25  OutA Pb FitValue   Other bits  Not used  Must be set to 0    22 OutA Pb IdiState Value Bit 0  Initial value for parameter 26  OutA Pb ldlState  Bit 1  Initial value for parameter 27  OutA Pb ldlValue   Other bits  Not used  Must be set to 0    23 IN1 Assignment Initial value for parameter 28  IN1 Assignment   24 IN2 Assignment Initial value for parameter 29   N2 Assignment   Electronic Data Sheet Electronic data sheet  GSD  files are specially formatted ASCII files that provide all of the    information necessary for a PROFIBUS configuration tool to access and alter the parameters of    a device  The GSD file contains all the parameter information of a device  number of    parameters  groupings  parameter name  min  max  and default values  units  data format and    Publication 193 UM010A EN P     January 2008    B 2 PROFIBUS Information       Set Slave Address    Supported Baud Rates    Publication 193 UM010A EN P     January 2008    scaling  The GSD file for the E1 Plus PROFIBUS Module is available from the Internet at  www ab com
22. Publication 193 UM010A EN P     January 2008                                                                Monitor parameters Advanced Setup Reset Lock 1 0 Setup Trip History PROFIBUS Setup  1 Average  FLA 8 Trip Enable 19 Trip Reset 22 OutA Pr FitState 30 Trip Log 0 35 SSA Node Address  2 Therm Utilized 9 Warning Enable 20 Program Lock 23 OutA Pr FitValue 31 Trip Log 1  3 Trip Status 10 Single Three Ph 21 Set to Defaults 24 OutA Pb FitState 32 Trip Log 2  4 Warning Status 11 OL Reset Mode 25 OutA Pb FitValue 33 Trip Log 3  5 Device Status 12 OL Warning Level 26 OutA Pb IdiState 34 Trip Log 4  6 Firmware Revision 13 Jam Inhibit Time 27 OutA Pb IdlValue  7 Serial Number 14 Jam Trip Delay 28 IN1 Assignment  15 Jam Trip Level 29 IN2 Assignment  16 Jam Warn Level  17 UL Inhibit Time  18 UL Warn Level  Monitor Group  Average  FLA Index No  1  This parameter reports the average motor current  The value is Access Rule Read  reported as a percentage of motor rated current  dial setting on    the E1 Plus Overload Relay   and is reported in increments of 5  Size 2 bytes  Group Monitor  Units 9oFLA  Min  Value 0  Max  Value 1275  Default Value None    Therm Utilized Index No  2  This parameter reports the percent thermal utilization of the Access Rule Read  connected motor  Size 1 byte  Group Monitor  Units    Min  Value 0  Max  Value 100  Default Value None       Trip Status    This parameter provides trip identification     1   Trip  0  No Trip    Bit    PROFIBUS Configuration 3 5   
23. USER MANUAL    LISTEN     THINK   7 BULLETIN 193  SOLVE  E1 Plus PROFIBUS Module       CATALOG NUMBER 193 EPRB       Rockwell  ALLEN BRADLEY e ROCKWELL SOFTWARE Automation    Important User Information    Solid state equipment has operational characteristics differing from those of electromechanical  equipment  Safety Guidelines for the Application  Installation and Maintenance of Solid State Controls   Publication SGI 1 1 available from your local Rockwell Automation sales office or online at  http   www ab com manuals gi  describes some important differences between solid state  equipment and hard wired electromechanical devices  Because of this difference  and also  because of the wide variety of uses for solid state equipment  all persons responsible for  applying this equipment must satisfy themselves that each intended application of this  equipment is acceptable     In no event will Rockwell Automation  Inc  be responsible or liable for indirect or consequential  damages resulting from the use or application of this equipment     The examples and diagrams in this manual are included solely for illustrative purposes  Because  of the many variables and requirements associated with any particular installation  Rockwell  Automation  Inc  cannot assume responsibility or liability for actual use based on the examples  and diagrams     No patent liability is assumed by Rockwell Automation  Inc  with respect to use of information   circuits  equipment  or software described in
24. Underload Warning    The following parameters are available for configuring the PROFIBUS Module s underload  warning performance     e Parameter 17  UL Inhibit Time  allows the installer to inhibit an underload indication  from occurring during the motor starting sequence  It is adjustable from 0   250  seconds     e Parameter 18  UL Warn Level  allows the installer to define the current at which the  PROFIBUS Module will indicate a warning  It is user adjustable from 30   100  of the  FLA dial setting     The PROFIBUS Module will immediately indicate an Underload warning if   e No warning currently exists   Underload Warning is enabled     UL Inhibit Time has expired    e The motor current is less than the UL Warn Level    When the Underload Warning conditions are satisfied  the following will occur     e Bit 3 in Parameter 4  Warning Status  will go to    1         Bit 1 of Parameter 5  Device Status  will go to    1          IMPORTANT The Underload Warning function does not include a time delay feature   Once the UL Inhibit Time has expired  the Underload warning indication  is instantaneous        A disruption of the communication link between the E1 Plus PROFIBUS Module and a  PROFIBUS network can result in the loss of application control and or critical process  diagnostic data  Rapid communication fault detection helps minimize potential damage due to  uncontrolled or unmonitored applications     Comm Fault Warning    The PROFIBUS Module will indicate a Comm Fault warn
25. am Trip    The following parameters are available for configuring the PROFIBUS Module s jam trip  performance       Parameter 13  Jam Inhibit Time  allows the installer to inhibit a jam trip from occurring  during the motor starting sequence  It is adjustable from 0   250 seconds      Parameter 14  Jam Trip Delay  allows the installer to define the time period a jam  condition must be present before a trip occurs  It is adjustable from 0 5   25 0 seconds      Parameter 15  Jam Trip Level  allows the installer to define the current at which the E1  Plus Overload Relay will trip on a jam  It is user adjustable from 150   600  of the FLA  dial setting     Protection Functions 2 3       Underload Protection    The PROFIBUS Module will command the E1 Plus Overload Relay to trip if all the following  conditions are met    e No trip currently exists      Jam Protection is enabled      Jam Inhibit Time has expired     The motor current is greater than the Jam Trip Level for a time period greater than the   Jam Trip Delay   When the conditions for a jam trip are satisfied  the following will occur    e Bit 2 in Parameter 3  Trip Status  will go to    1        Bit 0 in Parameter 5  Device Status  will go to    1        The E1 Plus Overload Relay s trip relay contacts  95 and 96  will open      Out A will be placed in their Protection Fault State  if so programmed        The Protection Fault State of OUT A is defined by parameter 22    IMPORTANT  OUTA Pr FitState  and parameter 23  OUTA
26. associated equipment  A hazard of personal injury  and or equipment damage exists if codes are ignored during installation           ATTENTION An incorrectly applied or installed side mount module can result in  damage to the components or reduction in product life  Wiring or  application errors such as supplying incorrect or inadequate supply    voltage  or operating storing in excessive ambient temperatures may     l    result in malfunction of the product        Only personnel familiar with the side mount module and associated    ATTENTION       machinery should plan to install  set up  and maintain the system  Failure  to comply may result in personal injury and or equipment damage      l          This is a Class A product  In a domestic environment  this product may    ATTENTION    cause radio interference  in which case  the user may be required to take  adequate measures        Installation and Wiring    1 2    Figure 1 1 Features  PROFIBUS Connector    Features    Network Status LED  T O Connector                                                    Figure 1 3 Installation  2     Figure 1 2 Installation  1     Installation                 2 Driver       0 7 1 1N  m   6  10 Ib in           Figure 1 4 Installation  3                       0 6mm X 3 5mm Blade    02 in X 14 in Blade        0 5 0 6N m     4 4   5 3 Ib in     Installation and Wiring 1 3                                                                                                                             
27. b opes wants Eat pu 1 3  JOUienetols 1G chy mee Qe eh a LAS eo ns Ge TETEN ESTEE 1 4  TER PORUGHOG A di a eei anal eec Het c bere Pets 2 1  Trip Status   Identification   i sinew erento de Petra oed 2 1  Tip Resetine  esie otis teas autos asda ena pa re a ye 2 1  Trip and Warning Enable JS cista Rio pets Si Sa eS 2 1  Overload and Phase Loss Protection    ois  cee dated sae eee es 2 1  Oyerload Wana ss sea rs cete e e patil na e dee es 2 2  Jani Protechon 0  vr qu UE er P teta t dea tad 2 2  Jam Dg eds vert tte te bt bentes et pario rta 2 2  Jam Warnes hatt apace dng ne mor bra ramosi seo d ash t s 2 3  U  derlond Protectorin sk i a iy petiole dan a oe qure d x 2 3  Underload Warn  1 eie RR ADOS YR 2 4  Communication Fault PYOUCHORS a   e vio SEL CR ERROR 2 4  Comi Fault Ware vases ueber E buenos yeah wed ws 2 4  Communication Idle Protection 2o de ot eO NR e erenn 2 4  Comm ddile Warming tisores d tack Tee e EE Vaters 2 5  Itroduetion eva e iere re ea Cea x ER ERE du SS 3 1  Acyclic Parameter Access  DPV  os cw eR ARM RR RR RE 3 1  Cyclic Parameter Access  DP VO  iis esce cerne mee es 3 1  Tatal Dat eot cote oed b he e Di of co No E 3 2  Control  and Status Registers o ees d elo be beo UU ari bete 3 2  Conttol 8 SECT us rods cioe wn ed tica epo eo bt andit is 3 2  Status Reststefe nosa aa Ae paste TE c sp PRD 3 3  Parameter Probramiine   oiov ot Pe See a es ees 3 3  propa LOCK 4 ee eS Ia ME Rad a to me takes Pvt   3 3  Resetting to the Factory Default Values                 
28. f the module as follows     Table 3 1 Control Register contents                Bit Function   7 6 5 4 3 2 1 0  X OutA  X Trip Reset  X Save  X X X X X Not Used                              Bit 0  OutA     Control of the Output relay  The bit is flank triggered  i e  a state transition  from 0 to 1 or from 1 to 0 must be performed to change the state of the relay     Bit 2  Trip Reset     Same functionality as parameter 19  Trip Reset  The bit is flank  triggered  i e  a state transition from 0 to 1 must be performed to trigger a trip reset      Bit 6  Save     Used to trigger a save  to non volatile memory  of parameter values of  parameters that are mapped as Cyclic I O  The bit is flank triggered  i e  a state transition  from 0 to 1 must be performed to trigger a save operation     PROFIBUS Configuration 3 3       Status Register    The Status Register reflects the overall status of the module as follows     Table 3 2 Status Register contents                                                    Bit Function   7 6 5 4 3 2  Trip  Warning  X OutA Stat  X Not Used  X Input 1  X Input 2  X Save Ready  X Motor Curr     Bit 0  Trip     Same functionality as bit 0 in parameter 5  Device Status   e Bit 1  Warning     Same functionality as bit 1 in parameter 5  Device Status   e Bit 2  OutA Stat     Same functionality as bit 2 in parameter 5  Device Status     Bit 4  Input 1     Same functionality as bit 3 in parameter 5  Device Status   e Bit5  Input 2     Same functionality as bit 4
29. hts Reserved  Printed in USA     
30. iguration fault or parameter fault Flashing Red  1Hz     Fatal Error Mode    In Fatal Error Mode  the E1 Plus PROFIBUS Module   s NETWORK STATUS LED turns solid  red  The overload relay continues in this state as long as the device is powered        The only way to recover from this mode is to power cycle the module     Power up initialization failure Solid Red    Fatal communication error    PROFIBUS Troubleshooting Network Status LED    Procedures The following table identifies possible causes and corrective actions when troubleshooting  PROFIBUS related failures using the NETWORK STATUS LED            Error Type          Table 4 4 Troubleshooting using NETWORK STATUS LED                               Color State Possible Cause Corrective Action  None   1  The E1 Plus PROFIBUS Module is not receiving power at Check power and PROFIBUS cable connections   the PROFIBUS connector   2  The module is off line  Green Flashing  once  Normal operating state  The E1 Plus PROFIBUS Module is No action required  the Network Status LED flashes  Red performing internal initialization procedures  green red off during a normal power up sequence   Off  Green Flashing  1Hz  Normal operating state  E1 Plus PROFIBUS Module is in idle No action required   state   Green Solid Normal operating state  the E1 Plus PROFIBUS Module is No action required   on line   Red Flashing  1Hz  1  Configuration fault Correct the configuration and restart the PROFIBUS master   2  Parameter fault  Red Solid A fata
31. il the installer applies or  downloads the new settings to the device        Cyclic Parameter Access  DP V0     All parameters can be accessed cyclically by adding the corresponding GSD module to the  network configuration  GSD modules can be added  i e  mapped as Cyclic I O  as needed  in  any order  with a few restrictions     e At least one byte must be mapped as Cyclic I O  This can either be device parameters    or   the Control  and Status Registers     e It is not permitted to map the same parameter to the Cyclic I O configuration more  than once     e Parameters mapped as Cyclic I O cannot be written using Acyclic  DP V1  services        IMPORTANT For technical reasons  writeable parameters mapped as Cyclic I O will    not be saved automatically in non volatile memory  To save such  paramaters  a save operation must explicitly be triggered by means of a  bit in the Control Register        Publication 193 UM010A EN P     January 2008    3 2 PROFIBUS Configuration       Control  and Status Registers    Publication 193 UM010A EN P     January 2008       IMPORTANT All changes made to parameter values  saved or not  will take effect    immediately even during Data Exchange        Initial Data    During startup of the network  it is possible to load start up values  loaded on each transition  from offline to online  for all writable parameters by means of the User Prm Data  The  PROFIBUS Module will use these settings provided that  Parameter Initialization   User Prm  Data
32. ing if   e No warning currently exists    Comm Fault Warning is enabled    The PROFIBUS Module experiences a loss of communication  When the Comm Fault warning conditions are satisfied  the following will occur   e The Network Status LED will go out  e Bit 5 in Parameter 4  Warning Status  will go to    1         Bit 1 of Parameter 5  Device Status  will go to    1          The Comm Fault State of OUT A is defined by Parameter 24  OUTA Pb  IMPORTANT FirState  and parameter 25  OUTA Pb FitValue         When a programmable controller is placed into the program mode  the execution of its ladder  program is suspended  and any connected networks go to an idle state  If inadvertent  this can  result in the loss of application control and or critical process diagnostic data  Rapid    Protection Functions 2 5       communication idle detection helps minimize the potential damage due to uncontrolled or  unmonitored applications     Comm Idle Warning    The PROFIBUS Module will indicate a Comm Idle warning if   e No warning currently exists    Comm Idle Warning is enabled    The PROFIBUS module is in idle  clear  mode  When the Comm Idle warning conditions are satisfied  the following will occur   e Bit 6 in Parameter 4  Warning Status  will go to    1         Bit 1 in Parameter 5  Device Status  will go to    1          The Comm Idle State of OUT A is defined by Parameter 26  OUTA Pb  IMPORTANT IdiS tate  and parameter 27  OUTA Pb Id Value         Publication 193 UM010A EN P     Janua
33. jam  detection is inhibited during a motor starting sequence     Jam Trip Delay    This parameter allows the installer to program a time  duration for which a jam condition must exist at the  programmed level prior to the device tripping     Jam Trip Level    This parameter sets the jam trip level     Jam Warn Level    This parameter sets the jam warning level     UL Inhibit Time    This parameter defines the amount of time for which  underload detection is inhibited during a motor starting  sequence                                                                                                  Index No  13   Access Rule Read Write  Size 1 byte   Group Advanced Setup  Units Seconds   Min  Value 0   Max  Value 250   Default Value 10   Index No  14   Access Rule Read Write  Size 1 byte   Group Advanced Setup  Units Seconds   Min  Value 0 5   Max  Value 25 0   Default Value 5 0   Index No  15   Access Rule Read Write  Size 2 bytes   Group Advanced Setup  Units   FLA   Min  Value 150   Max  Value 600   Default Value 250   Index No  16   Access Rule Read Write  Size 2 bytes   Group Advanced Setup  Units   FLA   Min  Value 100   Max  Value 600   Default Value 150   Index No  17   Access Rule Read Write  Size 1 byte   Group Advanced Setup  Units Seconds   Min  Value 0   Max  Value 250   Default Value 10       UL Warn Level    This parameter sets the underload warning level     Reset Lock Group  Trip Reset    This parameter provides the user with the capability of  resetting a trip 
34. l error has occurred in the module  Cycle power to the unit and network  If the fault still exists   replace unit   Red Lit 1s then off Major internal fault Cycle power to the unit and network  If the fault still exists     replace unit  If the problem persists  contact technical support              Publication 193 UM010A EN P     January 2008    Troubleshooting 4 3       DP V1 Error Codes    The following table lists PROFIBUS DP V1 error codes  possible causes  and corrective actions     Table 4 5 Troubleshooting by DP V1 Error Code                      DP V1 ErrorCode1 DP V1 DP V1 Possible Cause Corrective Action  Read Write   0xA0 X Read access to paramater  which could   Read Error  not be retrieved  e g  EEPROM error   0xA1 X Write access filed  e g  due to   Write Error  EEPROM error   0xB0 X X Accessing a non existing parameter  Correct the Index in the service request and   Invalid Index  retry   0xB1 X Write access with incorrect amount of data Correct the number of bytes in the service   Write Length Error  supplied  request and retry   0xB5 X Write access to a parameter currently being If applicable  unlock the parameter and retry    State Conflict  locked with the parameter lock   OxB7 X The value in the service request was Correct the value in the service request   Invalid Rangel outside the specified range  and retry   0xCO X The length in the request doesn t The length in the request doesn t     Read constrain conflict  match the actual size of the parameter  
35. le  Default Value None   Index No  33   Access Rule Read   Size 2 bytes   Group Trip History   Units       Min  Value See Trip Status table  Max  Value See Trip Status table  Default Value None   Index No  34   Access Rule Read   Size 2 bytes   Group Trip History   Units       Min  Value See Trip Status table  Max  Value See Trip Status table  Default Value None   Index No  35   Access Rule Read Write   Size 1 byte   Group PROFIBUS Setup  Units       Min  Value 0   Max  Value 126   Default Value 126       Introduction    PROFIBUS Modes of Operation    Chapter 4       Troubleshooting    The purpose of this chapter is to assist in troubleshooting the E1 Plus PROFIBUS module        Servicing energized industrial control equipment can be hazardous     ATTENTION    Electrical shock  burns  or unintentional actuation of controlled  industrial equipment may cause death or serious injury  For safety of  maintenance personnel  as well as other who may be exposed to  electrical hazards associated with the maintenance activities  follow the  local safety related work practices  for example  the NFPS 70W  Part II   Electrical Safety for Employee Workplaces  in the United States  when working  on or near energized equipment  maintenance personnel must be trained  in the safety practices  procedures  and requirements that pertain to their  respective job assignments  Do not work alone on energized equipment           Do not attempt to defeat or override fault circuits  The cause of a fault
36. lue 2   OL Contact  Default Value 0  Trip History Group   Trip Log 0 Index No  30   This parameter records the latest trip  Access Rule Read  Size 2 byte  Group Trip History  Units      Min  Value See Trip Status table  Max  Value See Trip Status table  Default Value None   Trip Log 1 Index No  31   This parameter records the trip previous to Trip Log 0  Access Rule Read  Size 2 bytes  Group Trip History  Units      Min  Value See Trip Status table  Max  Value See Trip Status table  Default Value None          Publication 193 UM010A EN P     January 2008    3 12 PROFIBUS Configuration       Trip Log 2    This parameter records the trip previous to Trip Log 1     Trip Log 3    This parameter records the trip previous to Trip Log 2     Trip Log 4    This parameter records the trip previous to Trip Log 3     PROFIBUS Setup Group    SSA Node Address    This parameter holds the latest node address sent by the Set  Slave Address telegram  This is the node address the slave  will start up with after the next power cycle    NOTE  This parameter is added to provide a way to change  the node address in the case that the master does not  support the SSA service    Normally this parameter does not need to be used     Publication 193 UM010A EN P     January 2008                                                                                     Index No  32   Access Rule Read   Size 2 bytes   Group Trip History   Units       Min  Value See Trip Status table  Max  Value See Trip Status tab
37. over the PROFIBUS network  After a trip is  reset  the parameter automatically returns to a    Ready     state     Program Lock    This parameter prohibits the device parameters from being  altered when set to    Locked     It must be set to    Unlocked     to allow parameter modification     Set To Defaults    This parameter allows the user to reset the parameter  settings to the factory default values  After parameter  values have been reset to the factory default settings  the  parameter automatically returns to a    Ready    state     PROFIBUS Configuration 3 9                                                                                           Index No  18   Access Rule Read Write  Size 1 byte  Group Advanced Setup  Units   FLA   Min  Value 30   Max  Value 100   Default Value 70   Index No  19   Access Rule Read Write  Size 1 byte  Group Reset Lock  Units       Min  Value 0   Ready  Max  Value 1   Reset Trip  Default Value 0   Index No  20   Access Rule Read Set  Size 1 byte  Group Reset Lock  Units       Min  Value 0   Unlocked  Max  Value 1   Locked  Default Value 0   Index No  21   Access Rule Read Write  Size 1 byte  Group Reset Lock  Units       Min  Value 0   Ready  Max  Value 1   Reset Defaults  Default Value 0    Publication 193 UM010A EN P     January 2008    3 10 PROFIBUS Configuration       Publication 193 UM010A EN P     January 2008    1 0 Setup Group    OutA Pr FitState    This parameter  in conjunction with parameter 23   defines how Output A will res
38. own fuse    2  Poor electrical connection 2  Check all power terminations from the branch circuit protecting device down to  the motor for proper tightness  Ensure that the overload connection to the  3  Contactor operation contactor is secure   4  Improper device type 3  Inspect contactor for proper operation   4  Bulletin 193S or 592S are required for single phase applications   Jam 1  Motor current has exceeded the programmed jam level   Check for the source of the jam  i e  excessive load or mechanical transmission  2  Improper parameter settings component failure      Parameter 15  Jam Trip Level  is set too low for the application  Check to ensure  that the FLA dial is set correctly        Publication 193 UM010A EN P     January 2008       Appendix A       Specifications    Terminal Ratings     Terminal Screw    M3       Wire Cross Section    See wiring diagram section                                                                            Torque 0 5   0 6 Nem  4 4   5 3 Ib  in   Degree of Protection IP20  Power Supply Ratings   Rated Supply Voltage Us 24V DC  Rated Operating Range Ue 20 4   26 4  Rated Supply Current le 0 1A  Maximum Surge Current at Power Up 25A  Maximum Power Consumption 25W  Maximum Power Interruption Time 0 5ms  Output Relay Ratings   Terminals  OUT A  13 14  Type of Contacts Form A  SPST   NO  Rated Thermal Current lihe 5A  Rated Insulation Voltage Ui 300V AC  Rated Operating Voltage Ue 240V AC  Rated Operating Current le 3A  at 120V AC   1 5 A
39. pond when a trip occurs   When set to    1     Output A will continue to operate as  commanded via the network  When set to  0   Output A  will open or close as determined by the setting of  parameter 23     OutA Pr FitValue    This parameter determines the state that Output A assumes    when a trip occurs and Parameter 22 is set to  0      OutA Pb FitState    This parameter  in conjunction with Parameter 25   defines how Output A will respond when a PROFIBUS  network fault occurs  When set to  1   Output A will  hold the state prior to PROFIBUS fault occurrence  When  setto  0   Output A will open or close as determined by  the setting of Parameter 25     OutA Pb FitValue    This parameter determines the state that Output A assumes  when a PROFIBUS network fault occurs and Parameter 24 is    set to  0      OutA Pb IdiState    This parameter  in conjunction with parameter 27   defines how Output A will respond when the PROFIBUS  network is idle  When set to  1   Output A will hold the  state prior to PROFIBUS fault occurrence  When set to   0   Output A will open or close as determined by the  setting in Parameter 27  The Pb Fit parameters  supersede the Pb Id  parameters                                                                                                                    Index No  22  Access Rule Read Write  Size 1 byte  Group 1 0 Setup  Units      Min  Value 0   Go To FltValue   23   Max  Value 1   Ignore Fault  Default Value 0  Index No  23  Access Rule Read W
40. rite  Size 1 byte  Group 1 0 Setup  Units      Min  Value 0   Open  Max  Value 1   closed  Default Value 0  Index No  24  Access Rule Read Write  Size 1 byte  Group 1 0 Setup  Units      Min  Value 0   Go To FitValue   25   Max  Value 1   Hold Last State  Default Value 0  Index No  25  Access Rule Read Write  Size 1 byte  Group 1 0 Setup  Units      Min  Value 0   Open  Max  Value 1   Closed  Default Value 0  Index No  26  Access Rule Read Write  Size 1 byte  Group 1 0 Setup  Units      Min  Value 0   Go To IdlValue   27   Max  Value 1   Hold Last State          Default Value       0    PROFIBUS Configuration 3 11                                                                                                 OutA Pb IdiValue Index No  27   This parameter determines the state that Output A assumes   Access Rule Read Write   when the network is idle and parameter 26 is set to  0   Sine 1 byte  Group 1 0 Setup  Units      Min  Value 0   Open  Max  Value 1   Closed  Default Value 0   IN1 Assignment Index No  28   This parameter allows the user to assign a specific function   Access Rule Read Write   to the discrete IN1 input  Size 1 byte  Group 1 0 Setup  Units      Min  Value 0   Normal   1   Trip reset   Max  Value 2   OL Contact  Default Value 0   IN2 Assignment Index No  29   This parameter allows the user to assign a specific function   Access Rule Read Write   to the discrete IN2 inputs  Size 1 byte  Group 1 0 Setup  Units      Min  Value 0   Normal   1   Trip Reset  Max Va
41. rmation that s contained in this manual  You can also contact a special  Customer Support number for initial help in getting your module up and running     United States 1 440 646 3223  Monday     Friday  8am     5pm EST       Outside United States   Please contact your local Rockwell Automation representative for any technical support  issues     New Product Satisfaction Return    Rockwell tests all of its products to ensure that they are fully operational when shipped from the  manufacturing facility  However  if your product is not functioning and needs to be returned     United States Contact your distributor  You must provide a Customer Support case number  see phone  number above to obtain one  to your distributor in order to complete the return process     Outside United States   Please contact your local Rockwell Automation representative for return procedure        www rockwellautomation com    Power  Control and Information Solutions Headquarters   Americas  Rockwell Automation  1201 South Second Street  Milwaukee  WI 53204 2496 USA  Tel   1  414 382 2000  Fax   1  414 382 4444   Europe Middle East Africa  Rockwell Automation  Vorstlaan Boulevard du Souverain 36  1170 Brussels  Belgium  Tel   32  2 663 0600  Fax   32  2 663 0640  Asia Pacific  Rockwell Automation  Level 14  Core F  Cyberport 3  100 Cyberport Road  Hong Kong  Tel   852  2887 4788  Fax   852  2508 1846    Publication 193 UM010A EN P     January  2008  Copyright   2008 Rockwell Automation  Inc  All Rig
42. ry 2008    2 6 Protection Functions    Publication 193 UM010A EN P     January 2008    Introduction       PROFIBUS Configuration    The PROFIBUS Module supports DP V0 and DP V1 communications  It is commissioned for  a PROFIBUS network using a GSD file which contains information about parameters  profiles   I O types  and sizes specific for this module  The GSD file for the 193 EPRB can be  dowloaded from http   www ab com networks gsd      Acyclic Parameter Access  DP V1     The preferred way of accessing device parameters is by means of Acyclic  DP V1  read  and  write services  When accessed acyclically  parameters are addressed by their corresponding  Index  index equals parameter number   Note that due to technical reasons imposed by the  PROFIBUS networking system  it is required to map at least one byte of Cyclic I O in either  direction  Any parameter can be used for this purpose     Note  The slot number is not significant  i e  it   s ignored by the module        Write requests towards writeable parameters will automatically cause the  IMPORTANT ii P i    corresponding setting to be saved in non volatile memory  For  consistency reasons  all parameters mapped as Cyclic I O will be  read only when accessed acyclically           IMPORTANT Changes made to parameter values will take effect immediately even    during a    running    status   2          IMPORTANT Parameter setting changes made in a PROFIBUS configuration tool do  not take effect in the PROFIBUS Module unt
43. ssigned during manufacturing   Revision Counter 2 octets 0x0000  Profile ID 2 octets OxF600  Profile Specific Type 2 octets OxF600  IM Version 2 octets 0x0101  IM Supported 2 octets Ox001E          Table B 7 IM1 Record             Information Size Default Value   Tag Function 32 octets Blank  0x20    Tag Location 22 octets Blank  0x20   Table B 8 IM2 Record   Information Size Default Value   Installation Date 16 octets Blank  0x20   Table B 9 IM3 Record   Information Size Default Value   Descriptor 54 octets Blank  0x20           Publication 193 UM010A EN P     January 2008    B 4 PROFIBUS Information       Rockwell Automation Support    Publication 193 UM010A EN P     January 2008    Rockwell Automation provides technical information on the web to assist you in using its  products  At http    support rockwellautomation com  you can find technical manuals  a  knowledge base of FAQs  technical and application notes  sample code and links to software  service packs  and a MySupport feature that you can customize to make the best use of these  tools     For an additional level of technical phone support for installation  configuration and  troubleshooting  we offer TechConnect Support programs  For more information  contact your  local distributor or Rockwell Automation representative  or visit  http   support rockwellautomation com     Installation Assistance    If you experience a problem with a hardware module within the first 24 hours of installation   please review the info
44. us Overload Relay     Setting Parameter 19  Trip Reset  to    Reset       Setting the  Trip Reset  bit bit in the Control Register      Using a push button  N O  contact configuration  wired to one of the PROFIBUS  Module inputs  programming the corresponding input assignment parameter  28 or 29   to  Trip Reset        Setting parameter 11  Reset Mode  to    Automatic    does not result in other  IMPORTANT BP o  reset commands being ignored        Parameter 8  Trip Enable  allows the installer to enable or disable the jam trip protective function     Parameter 9  Warning Enable  allows the installer to enable or disable the overload  jam and  underload warning protective functions        ATTENTION The Trip Enable settings should not be altered during machine    operation  as unexpected behavior could occur  This may result in an  unintended actuation of controlled industrial equipment  with the  potential for machine damage or serious injury to personnel        Thermal overload and phase loss trip protection is provided exclusively by the E1 Plus Overload  Relay  The E1 Plus Overload Relay provides uninterrupted protection to the motor  even in the    Publication 193 UM010A EN P     January 2008    2 2 Protection Functions       Jam Protection    Publication 193 UM010A EN P     January 2008    event of a PROFIBUS Module failure  Settings for FLA and trip class are found directly on the  E1 Plus Overload Relay        IMPORTANT The reset mode DIP switch adjustment is overridden
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
CASA BLANCA - OPEN TAQAFA  VPCJ2 Series - Sony Europe    研究分野 研究概要 キーワード 所 属 (学部・学科) 氏 名  RP-HC700 - Support  PIRANHA® MANUAL DEL OPERADOR  MiniTracker III User Manual  Rythmes scolaires  MultiBoard Mode d`emploi  iPad Manuale Utente - Migros    Copyright © All rights reserved. 
   Failed to retrieve file