Home

SAFEGUARD CONTROLLER User Manual

image

Contents

1. 6 2 2 CHANNEL CONFIGURATION MENUS T 7 2 21 CHANNEL SETUP ENTRY sse nennen rnnt nennen nns 8 222 ALARM 1 ALARM 2 HORN RELAY SET UP MENU 8 223 ALARM 3 FAULT ALARM sse rennen nnns nnne nns 9 2 2 4 DATA FROM MENU TO SET INPUT SOURCE seen 9 2 24a MIN MAX RAW COUNTS MENUS n anna 10 2 2 4b a MARKER MENS uuu atte ete itane Hg ao ad e 11 2 2 40 SENSOR LIFE DETECTION this feature is not used at this time 11 2 25 LINEARIZATION 12 226 CONFIGURE MENU obsit piden Rr A de ME XR aea ne 12 2 2 08 EUNITS MEASUREMENT NAME ASCII DATA FIELDS 12 2 2 60 INPUT MEASUREMENT 13 2 2 00 DECIMAL POINT RESOLUTION ennt 13 2 2 6d TURNING OFF UNUSED CHANNELS sse 13 2 2 66 COPY DATA TOZ eiie du 13 223 JgAEMODE 3 nea ER Hore mea 14 2 3 SYSTEM CONFIGURATION MENUS 15 231 COMMON ALARM RELAYS 1 amp 2 sse eere enne ennt 16 2 3 2 5410 0195 DISCRETE RELAY FAILSAFE
2. 17 2 33 COMMON HORN RELAY amp LOCAL PIEZO sese 17 2 8 8 COMM PORT 18 2 85 EIGHT SIXTEEN CHANNEL MODES sse 19 2 3 6 SENSOR INFORMATION this feature is not used at this 19 2 4 AUTHORIZATION MODE 20 2 5 LCD CONTRAST ADJUSTMENT 20 c 21 3 0 MAIN VO INTERFACE PCB ic icit tme Inn eon CE e n YS Rao sea Ese 21 Modbus Communication between SafeGuard and Digital Millennium Series Transmitters 22 3 1 INPUT OUTPUT OPTIONAL PCB s 1 24 3 OPTIONAL ANALOG INPUT PCB 5010 0158 24 1 4 3 1 2 OPTIONAL DISCRETE RELAY PCB SG10 0195 25 3 1 6 OPTIONAL 4 20mA ANALOG OUTPUT BOARD 5010 0167 27 3 1 8 OPTIONAL 24VDC 150 WATT POWER SUPPLY 28 jeje 29 4 0 SYSTEM DIAGNOSTICS 29 SECTION 5 1 2 22 223 223222022222220202552500220500
3. Entry Menu Input From menu Marker menu Figure 2 5 2 2 4 SENSOR LIFE DETECTION this feature is not used at this time Sensor Life should only be activated when the Marker event is Calibration and when a sensor life value is transmitted after each calibration For Sensor Life to record properly the monitor must perform as follows After the Calibration Marker interval 4 0mA transmits for 10 seconds to indicate its calibration mode is complete The monitor then transmits between 4 0mA and 5 0mA for five seconds depending on remaining sensor life where 4 0mA 0 and 5 0mA 100 remaining sensor life The SafeGuard Controller 11 SafeGuard Controller User Manual 0115 Rev 0 reads this value and records it as the channel s Sensor Life Sensor Life is stored the SafeGuard Controller s modbus database and displayed as a bar graph in the Sensor Info screen see section 2 3 6 It is a useful tool for planning sensor replacement schedules 2 2 5 LINEARIZATION MENU The linearization menu allows each channel to have its own linearization curve stored in the SafeGuard Controller s non volatile memory Input versus output points must be entered in percent of full scale values This means if the range is 0 200 ppm 25 then 100 ppm is 50 of full scale Zero input will provide a zero output and 100 input a 100 output Nine intermediate points may be entered to define the curve Channel Linearization
4. 0115 Rev 0 numbers define the location of the variable representing the input value and must be obtained from the manufacturer of the Modbus RTU device EDIT toggles the Data From entry between Analog Analog with Local Cal and Modbus RTU signed unsigned amp floating point Analog Input should be selected when the channel s input comes from a transmitter or monitoring device with a calibrated output such as 4 20mA Sensor Direct is identical to Analog Input with Local Cal and both activate the SafeGuard Controller s Cal Mode features Problems may arise if calibrations are performed in two places upon the same signal so Cal Mode menus are only visible when Sensor Direct or Analog Input with Local Cal is selected These applications would require the SafeGuard Controller to be used as the calibration point when calibration transmitter and sensor configuration at the SafeGuard Controller select Analog Input with Local Cal Note that gas sensors are not connected directly to the SafeGuard Controller at this time hence Sensor Direct is not used Channel hanne Channel Measure INPUT DATA FROM TEN Direct Gas Sensor inputs are not used at this time Sensor Direct Min Rau 00800 Max Rau 04000 Analog Input Min Raw 86800 Max Raw 64686 Marker Menu Alarm 1 Alarm 2 Alarm 3 Data From Linearize Conf igure Analog Input Min Raw 98800 Max Raw 849668 Marker
5. 1 0 GENERAL DESCRIPTION The Net Safety Monitoring Inc SafeGuard 16 channel Controller is designed to display and control alarm event switching for up to sixteen detectors Flame detectors or transmitters with gas sensor data points It may also be set as an eight channel SafeGuard Controller for applications needing fewer inputs Alarm features such as ON and OFF delays Alarm Acknowledge and a dedicated horn relay make the SafeGuard Controller well suited for many multi point monitoring applications Data may be input to the SafeGuard Controller by optional analog inputs or the standard Modbus RTU master RS 485 port A Modbus RTU slave RS 485 port is also standard for sending data to PC s PLC s DCS s or even other SafeGuard Controllers Options such as analog I O and discrete relays for each alarm are easily added to the addressable bus Option boards have 8 channels and therefore require 2 boards for 16 channel applications Note LEL Gas sensors are connected to the SafeGuard Controller via Net Safety Transmitters They are NOT connected directly to the SafeGuard Controller at this time Perform calibrations of the transmitter sensor head Calibrations may however be performed at the SafeGuard if the transmitter sensor configuration is in a location not easily accessible See Cal Mode A 240 x 128 pixel graphic LCD readout displays monitored data as bar graphs trends and engineering units System configuration is through use
6. 40 Appendix Appendix A Electrostatic Sensitive Device ESD Definition Electrostatic discharge ESD is the transfer between bodies of an electrostatic charge caused by direct contact or induced by an electrostatic field The most common cause of ESD is physical contact Touching an object can cause a discharge of electrostatic energy ESD If the charge is sufficient and occurs near electronic components it can damage or destroy those components In some cases damage is instantaneous and an immediate malfunction occurs However symptoms are not always immediate performance may be marginal or seemingly normal for an indefinite period of time followed by a sudden failure To eliminate potential ESD damage review the following guidelines e Handle boards by metal shields taking care not to touch electronic components e Wear grounded wrist or foot straps ESD shoes or heel grounders to dissipate unwanted static energy Prior to handling boards dispel any charge in your body or equipment e Ensure all components are transported and stored in static safe packaging e When returning boards carefully package in the original carton and static protective wrapping e Ensure ALL personnel are educated and trained in ESD Control Procedures In general exercise accepted and proven precautions normally observed when handling electrostatic sensitive devices A warning label is placed on the packaging identifying product using ele
7. SAFETY MONITORING INC SAFEGUARD CONTROLLER User Manual Revision 4 4 Firmware 6 03 amp later 0115 REV 0 August 13 2009 TABLE OF CONTENTS TABLE OF CONTENTS 1 SECTION LL I DN 1 IMPORTANT SAFETY ISSUES iere drin eror aque nce eoe cue ce ae iunt es Se cec aue san 1 1 0 GENERAL DESCRIPTION 2 1 1 DATA DISPLAY SCREENS J ce race 3 Td CTREND SCREEN ede 3 1 1 2 BAR GRAPHS SCREEN ze de e dp re e dp e E doe 3 1 1 3 COMBINATION SCREEN 3 1 2 lae eager 4 1 2 1 DC POWER SUPPLY REQUIREMENTS sess 4 1 2 1a 150 WATT AC 24VDC POWER 5 4 12 2 RELAYS ene Qu u i 4 1 2 8 AMBIENT TEMPERATURE 4 1 2 4 HUMIDBETY RANGE 5 1 hedge tue 4 12 5 MES gni 4 126 HOUSINGSZ uuu RE 5 1 2 6a NON INTRUSIVE MAGNETIC KEYPAD 5 W230 APPROVALS 2 aen Sau aa 5 jede p 5 2 0 BASIC OPERATION mec E 5 2 1 SETUP MENU CONFIGURATION nennen nnn nnn nnn 6 2 1 1 CHANGING MENU VARIABLES USING THE
8. Channel Measurement Name Out put Alim 4 10 00 10 00 Alarm 2 20 00 20 00 Alarm 3 30 00 30 00 Data From 40 00 40 00 mLinearize 50 00 50 00 Configure 60 00 60 00 70 00 70 00 80 00 80 00 90 00 90 00 Entry menu Linearization menu Figure 2 6 2 2 6 CONFIGURE MENU From the entry level setup menu in Figure 2 7 the CONFIGURE menu may be entered for setting variables defining how the SafeGuard Controller presents monitored data to the various graphic displays Channel CONFIGURATION Channel XX Measurement Name Alarm 1 Measurement Name Alarm 2 Eunits Alarm 3 Zero 0 000 Data From Span 100 0 Linearize Decimal Points 0 Configure Channel On YES Copy To Entry menu Input Copy To menu Figure 2 7 2 2 EUNITS MEASUREMENT NAME ASCII DATA FIELDS The first two items in this menu are for entering the 6 character engineering unit and 16 character Measurement Name ASCII fields Eunits should define the units of measure for what this channel is to display Measurement Name should describe the source of this data in the user s terminology Section 2 1 1 of this manual describes how to use the front keypad to modify these fields SafeGuard Controller User Manual 0115 Rev 0 2 2 66 INPUT MEASUREMENT RANGE The ZERO SPAN entries allow configuration of the measurement range displayed by the channel Measurement Range works along with A D Counts menus descr
9. Zero Value 05 32767 Type Channel First Last Read FC Write FC Notes Channel Value 1 16 33001 16 n a 4 n a 15bit 2s complement w 5 over under range Analog Output Notes 12 bit integer for Channel Reading value 800 counts zero value 4000 counts 100 value Type Channel First Last Read FC Write FC Notes Channel 1 16 31001 31016 4 12bit integer Reading SafeGuard Controller User Manual MAN 0115 Rev 0 Channel Status words contain configuration and status bits for channel They are as follows Read FC Write FC Notes Type Channel First Last Channel Status 1 16 31017 31032 Alarm Trip bitO Alarm 1 Horn Drive bit Alarm 3 Type bit2 Alarm 2 Horn Drive bit3 Linearize bit4 Alarm 3 Trip bit5 Input Marker bit6 Channel Disable bit7 Controller Channel Jn Cal bit8 Modbus Data Type bit9 reserved bit10 reserved bitll Alarm 1 Latch bit12 Alarm 2 Latch bit13 Alarm 3 Latch bit14 Alarm 2 Trip bit15 4 n a 1 Low 1 1 Level 1 1 1 Low 1 Input Marker Detected 1 Disabled 1 Local Cal Mode 1 4 byte float reserved reserved 1 Latching 1 Latching 1 Latching 1 Low 16bit integer see bit by bit definition below 0 High 0 Off 0 Fault 0 Off 0 Off 0 High 0 Normal Mode 0 Enabled 0 Normal Mode 0 2 byte integer reserved reserved 0 Non latching 0 Non latching 0 Non latching 0 High Alarm status words are bits packed into 16 bit
10. 1 Optional Analog Input PCB SG10 0158 and Figure 3 3 1 2 1a 150 WATT 24VDC POWER SUPPLY 110 120 VAC 3 2A max 220 240VAC 1 6A max A slide switch on the front of the power supply selects AC input range The SG10 0172 150 watt power supply Figure 3 6 is for powering the SafeGuard Controller and up to 16 detectors A minimum of 5 watts per channel is available for powering of external transmitters 1 2 2 RELAYS Common relays are standard and menus provide voting logic for ALARM 1 ALARM 2 FAULT and HORN Discrete relays are optional Relays are Form C dry contacts and are rated at 5 Amp for 28 VDC and 250 RESISTIVE loads IMPORTANT Appropriate diode DC loads or MOV AC loads snubber devices must be installed with inductive loads to prevent RFI noise spikes Relay wiring should be kept separate from low level signal wiring 1 223 AMBIENT TEMPERATURE RANGE 25 to 50 degrees C 1 2 4 HUMIDITY RANGE 0 to 90 R H Non Condensing 1 2 5 ALTITUDE Recommended up to 2000 meters SafeGuard Controller User Manual 0115 Rev 0 1 2 6 HOUSINGS General purpose panel mount weighing 7 lbs and including hardware for 19 rack mounting Figure 6 1 NEMA 4X wall mount in fiberglass enclosure weighing 17 lbs Figure 6 2 1 2 NON INTRUSIVE MAGNETIC KEYPAD The SafeGuard Controller s operator interface includes five front panel touch keys A magnetic keypad option offers these five keys
11. HOW TO RETURN EQUIPMENT A Material Return Authorization number is required in order to return equipment Please contact Net Safety Monitoring at 403 219 0688 before returning equipment or consult our Service Department to possibly avoid returning equipment If you are required to return equipment include the following information 1 A Material Return Authorization number provided over the phone to you by Net Safety 2 A detailed description of the problem The more specific you are regarding the problem the quicker our Service Department can determine and correct the problem 3 company name contact name and telephone number 4 A purchase order from your company authorizing repairs or request for quote 5 Ship all equipment prepaid to Net Safety Monitoring Inc 2721 Hopewell Place NE Calgary Alberta Canada T1Y 7J7 6 Mark all packages RETURN for REPAIR 7 Waybills for shipment outside Canada must state Equipment being returned for repair All charges to be billed to the sender Ensure a duplicate copy of the packing slip is enclosed inside the box indicating item 1 4 along with the courier and account number for returning the goods Pack items to protect them from damage and use anti static bags or aluminum backed cardboard as protection from electro static discharge ALL equipment must be shipped prepaid Collect shipments will not be accepted SafeGuard Controller User Manual MAN 0115 Rev 0
12. Manual 0115 Rev 0 SECTION 3 3 0 MAIN INTERFACE PCB The most basic SafeGuard Controller requires only the I O PCB shown in Figure 3 1 for interfacing to field wiring The SafeGuard Controller s primary power supply is applied to terminals 9 amp 11 of TB2 This may be from 10 30 VDC WARNING A HIGH VOLTAGES SUCH AS 115 VAC APPLIED TO THESE TERMINALS MAY CAUSE SEVERE DAMAGE DC output terminals 10 amp 12 on TB2 provide up to 500mA of output power for N powering remote devices such as lamps transmitters etc This PCB includes both master COMM 1 and slave COMM 2 RS 485 Modbus ports 5 amp form C relays for each common alarm event A1 A2 FAULT A3 amp HORN and power supply I O terminals JP1 allows the RS 485 ports to be configured for 2 or 4 wire operation A 26 pin ribbon cable connects the I O PCB to the SafeGuard Controller s CPU and Display nest assembly Two bus connectors allow addition of optional functions such as analog I O and discrete alarm relays for each channel Horizontal jumpers installed in JP1 connect the RS 485 port s RX amp TX lines simplifying 2 wire daisy chains by providing additional terminals for incoming and outgoing cables For example installing the 2 COM 1 jumpers connects screw terminals amp 5 and terminals 3 amp 7 Socketed RS 485 terminating resistors R6 COMM 1 and R12 COMM 2 are located on the MAIN I O board These resistors should be removed if communication
13. Menu Jee With Local CAL Entry menu Sensor Direct with Analog Input with Analog input Local Cal Local Cal L The Modbus Master RS 485 port supports most integer types resolutions and formats MODBUS 16 menu indicates 16 bit is maximum but also supports 8 10 12 bit formats by editing Min Max Raw menus to contain the correct counts range Channel INPUT DATA FROM w WIRELESS Min Raw 80200 MaxRau Remote ID Marker Menu Ineut Rea VALUE MODBUS 52 BIT Min Raw 66661 MaxRaw 66661 Remote ID Alias Min Raw MaxRaw 91800 Remote ID Alias 96561 Marker Menu Min Raw 1666 Remote ID Alias 33881 Marker Menu The Wireless Option and features are not used at this time 16 BIT Modbus 16 BIT SIGNED Wireless Monitor 32 BIT Modbus Modbus Figure 2 4 2 2 da MIN MAX RAW COUNTS MENUS The Min Raw and Max Raw counts entries included in Input Data From menus define the range of input counts that provide Measurement Range read out values described in section 2 2 6b This menu entry is determined by the A D converter resolution of the channel s input For example if the input is a 10 bit Modbus device with zero at 200 counts and 100 at 1000 counts then this me
14. characters per register 2 characters per register 2 characters per register 2 characters per register 2 characters per register 2 characters per register 2 characters per register 2 characters per register 2 characters per register 2 characters per register 2 characters per register 2 characters per register 2 characters per register Notes 2 characters per register 3 registers per channel 2 characters per register 3 registers per channel 2 characters per register 3 registers per channel 2 characters per register 3 registers per channel 2 characters per register 3 registers per channel 2 characters per register 3 registers per channel 2 characters per register 3 registers per channel 2 characters per register 3 registers per channel 2 characters per register 3 registers per channel 2 characters per register 3 registers per channel 2 characters per register 3 registers per channel 2 characters per register 3 registers per channel 2 characters per register 3 registers per channel 2 characters per register 3 registers per channel 2 characters per register 3 registers per channel 2 characters per register 3 registers per channel 31 Six character Value ASCII string Type Channel First Last Read FC Write FC Notes ASCII Value 1 40577 40579 3 n a 2 characters per register 3 registers per channel ASCII Value 2 40580 40582 3 n a 2 characters per register 3 registers per channel ASCII Value 3 40583 40585 3 n a 2 characters pe
15. determines the Setpoint value where the alarm trips It is entered in engineering units For example if a channel monitors 0 50 ppmH25 and the alarm must trip at 10 ppm the correct entry is 10 00 Latching determines either manual or automatic alarm reset operation YES requires a manual Alarm Reset see Figure 1 to unlatch the alarm even though an alarm condition no longer exists YES also causes this alarm group s common relay front panel LED and optional discrete relay to latch NO allows all outputs for this alarm to automatically reset as soon as the alarm condition clears e TRIP ON is set to HIGH for increasing alarms or LOW for decreasing alarms to determine if the alarm activates upon exceeding or falling below the setpoint The ON DELAY OFF DELAY entries allow ON and OFF time delays affecting how long the setpoint must be surpassed before an alarm event transition occurs ON delays are limited to 10 seconds while OFF delays may be as long as 120 minutes Delays are useful in many applications to prevent nuisance alarms and unwanted cycling into and out of alarm conditions Note For ON DELAY the alarm is activated after the set time is reached For OFF DELAY the alarm remains activated for the duration of the set time after the alarm condition has passed The HORN ON entry allows linking this alarm to the common horn relay NO causes the alarm to have no effect upon the horn relay Entering YES causes this ala
16. for a detector on channel 9 to trip the same relay as a detector on channel 2 The Group menus may restrict this For example channels 1 8 might be set to trip common relay 1 while channels 9 16 trip common relay 2 Another possibility is channels 1 8 be set to trip common relay while channels 9 16 trip relays on an optional discrete relay PCB configured for Alarm see section 3 1 2 Failsafe controls relay activation for this common relay Failsafe ON causes the relay to de energize during alarm conditions and energize when there is no alarm Thereby a power failure forces the relay contact to the alarm position Note the common Fault relay is always failsafe and may be monitored separately to indicate loss of power conditions in many applications A1 and A2 Votes allows creation of logical AND function equations that control common relay 1 amp common relay 2 Default settings for common relay are 1 Votes 01 and A2 Votes 00 which causes relay to trip if any channel has an A1 level alarm active Default settings for common relay 2 are A1 Votes 00 and A2 Votes 01 which causes relay 2 to trip if any channel has an A2 level alarm active Example If either default setting is modified such that A1 Votes z 02 and A2 Votes z 01 then any two channels must have an A1 level alarm active and any one channel must have an A2 level alarm active to trip that relay REMEMBER One of Al s and the A2 could be on the same channel These
17. integer where 156 channel 1 alarm status and msb channel 16 alarm status Alarm status bit 1 indicates alarm is active Read FC Write FC Notes Type Channel First Last Alarm 1 Status 1 16 31033 n a Alarm 2 Status 1 16 31034 n a Alarm 3 Status 1 16 31035 n a Relay Status n a 31036 n a 4 n a 4 n a 4 n a 4 n a packed 16bit integer packed 16bit integer packed 16bit integer packed 16bit integer Note Common Relay status bits register 31036 are as follows Relay 12 610 Relay 2 bitl Fault Relay bit2 Horn Relay bit3 Type Channel First Last Cal Status 1 16 31037 n a Trend Interval 1 16 31038 n a Timer Fault Status 1 16 31039 n a Read FC Write FC Notes 4 n a 4 n a 4 n a packed 16bit integer 16bit integer Time in Seconds packed 16bit integer Alarm LED flashing status bit 1 indicates LED is flashing Acknowledge clears all to 0 Read FC Write FC Notes Type Channel First Last Alarm 1 Status 1 16 31049 n a Alarm 2 Status 1 16 31050 n a Alarm 3 Status 1 16 31051 n a Common LED 1 16 31052 n a Status LCD Display Screen Displayed Integer First 31053 Channel n a Type LCD Screen Sensor Life not used at this time Last n a Type Channel First Last Sensor Life 1 31065 n a Sensor Life 2 31066 n a Sensor Life 3 31067 n a Sensor Life 4 31068 n a 4 n a 4 n a 4 n a 4 n a packed 16bit integer packed 16bit integer packed 16bit integer packed 16bit integer Rea
18. level alarms must come from a channel included in the Group entry described above 16 SafeGuard Controller User Manual MAN 0115 Rev 0 Turning Acknowledge ON not available on Alarm 1 allows the common relay to be deactivated during alarm conditions by an Alarm Reset This is useful if an audible device is being driven by the relay All relays rated at 5 Amp for 28 VDC 250 VAC RESISTIVE loads AN IMPORTANT Appropriate diode DC loads or MOV AC loads snubber devices must be installed with inductive loads to prevent RFI noise spikes Relay wiring should be kept separate from low level signal wiring 2 3 2 5810 0195 DISCRETE RELAY FAILSAFE MODE SG10 0195 Discrete relay options may also be configured to function in a Failsafe mode using the System Setup menu shown in Figure 2 11 Entering YES causes these discrete relays to have energized coils when no alarm condition exists for the associated channel and de energized coils when the alarm occurs Failsafe is useful for indicating failed relay coils and loss of power conditions Important SG10 0195 zoning jumpers see Figure 3 4 should not be used when Discrete Relays menus are set for failsafe Zoning jumpers cause ANY relay in the zone to energize ALL other relays in the same zone Zoning of failsafe relays may be accomplished with wiring at the relay contact terminals Setur System Setur aH Discrete Relays Al Failsafe H2 Failsafe
19. rectangular cutout Only two 8 channel I O option PCB s such as analog input or discrete relays may be mounted directly to the back of the enclosure Refer to section 3 for information on each option PCB Additional 8 channel I O option PCB s must be located external from the assembly on another mounting plate A 3 foot length of cable is also supplied for this purpose Weight is approximately 7 pounds Properly ground the enclosure and follow national and local electrical codes 10 60 gt 9 10 g 9 60 0 1 SIDE VIEW O O 5 22 FRONT VIEW C i Note Panel cut out 5 25 X 9 20 RACK PANEL MOUNT 19 RACK SPREADER PLATES amp PANEL MOUNT BEZAL NOT SHOWN Rack Panel Mount Part SG10 0208 Figure 6 1 36 SafeGuard Controller User Manual MAN 0115 Rev 0 6 2 SAFEGUARD N4 NEMA 4X WALL MOUNT FIBERGLASS ENCLOSURE The SafeGuard N4 shown in Figure 6 2 is a fiberglass NEMA 4X wall mount enclosure Seven 8 channel I O option PCB s such as analog input or discrete relays may be mounted inside this enclosure Refer to section 3 for information on each option PCB The enclosure may be mounted outdoors with a weather deflector shield It weighs approximately 17 pounds Figure 6 3 provides important warning information concerning correct grounding procedures for non metallic enclosures Condui
20. with adjacent magnetic keys This option is included as a standard feature It is useful in applications where it may be inconvenient to open the enclosure s door to access the touch keypad 1 2 7 APPROVALS CSA C22 2 No 1010 1 and ISA 882 02 CSA C22 2 No 152 for combustibles UL 1604 22 2 No 213 Div 2 Groups A B C D EN55011 amp EN61000 CE Mark CSA File 219995 and may be seen at CSA International org SECTION 2 2 0 BASIC OPERATION The SafeGuard Controller offers 3 graphic screens for viewing monitored data and a Set Up menu screen for operator interface to configuration menus They are shown below in Figure 2 0 The Bar Graphs screen allows viewing of all active channels simultaneously The Trend screen displays a 24 hour trend one channel at a time The Combination screen displays a bar graph large engineering units and a 30 minute trend one channel at atime Input channels may be displayed in sequence with the UP DOWN keys The NEXT key switches between the 3 graphic data screens When SafeGuard power is applied the graphic LCD returns to the screen active when power was last removed Setup menus are entered by pressing EDIT from any data screen and scrolling to the desired menu using the UP DOWN keys Pressing EDIT again enters the selected menu s tree of variables This Setup mode may be exited manually by pressing NEXT or automatically when no keys are pressed for 5 minutes Alarm relays and front panel alarm LED
21. 0115 Rev 0 PART 5810 0158 SafeGuard Analog Input board m x lt 22 een J 2 ao 07 JP1 determines if this 8 channel d A Analog Inpit ECB provides inputs z J1 amp J2 are interchangeable 12 t connectors used to add option PCB assemblies are required for 16 2 5 assemblies to the SafeGuard channels 7 Controller 5 Ly 58868686568 J 5 Socketed precision resistors R1 R8 Ri R3 R5 R7 100 ohm terminations for 4 20mA inputs 0 2 VDC voltage inputs 2 6 Re be accepted by removing resistor TB2 DCPWR TB2 is for powering bulk power to transmitters Q QI er other powered input devices is wired internally to channel EXC s and EXC to channel LO s DOODDODDGD GO GOO EXC LO EXC LO EXC LO EXC LO CH1 9 CH3 11 CH5 13 7 15 EXC o0o00000000000 EXC HI LO EXC LO EXC LO EXC HI LO CH2 10 CH4 12 CH6 14 CH8 16 ANALOG INPUTS Typical 2 8 wire 4 20mA transmitter wiring connect 2 Wire 4 20mA ire 4 correct power 24VDC or Transmitter Transmitter other to TB2 8 channel Analog Input Board Part SG10 0158 Figure 3 3 3 1 2 OPTIONAL DI
22. 050535055 85 05 00 02000 5 0050005080525 31 5 0 MODBUS RS 485 PORTS ers iterata 31 5 1 MODBUS SLAVE REGISTER 31 6 36 6 1 SAFEGUARD PANEL RACK MOUNT ENCLOSURE 36 6 2 SAFEGUARD 4 NEMA 4X WALL MOUNT FIBERGLASS ENCLOSURE 37 6 3 SAFEGUARD MAIN I O amp OPTION PCB FOOTPRINT DIMENSIONS 39 SECTION 7 HOW TO RETURN EQUIPMENT 40 APPENDIX deu ics mais kr mn wml mica 41 Appendix A Electrostatic Sensitive Device ESD 41 MAN 0115 REV 0 August 13 2009 SECTION 1 WARNING A Read amp understand contents of this manual prior to operation Failure to do so could result in serious injury or death IMPORTANT SAFETY ISSUES The following symbols are used in this manual to alert the user of important instrument operating issues operating and maintenance servicing instructions This symbol is intended to alert the user to the presence of important This symbol is intended to alert the user to the presence of dangerous voltage within the instrument enclosure that may be sufficient magnitude to constitute a risk of electric shock WARNINGS A Shock Hazard Disconnect or turn off power before servicing this ins
23. 5 5 2 J1 amp J h ble I2C lt 18 J2 are interchangeable 12 Q10 at Ot 7 47 connectors used to add option clu assemblies to the SafeGuard Ty o Controller Q9 gt Jo Jj Q8 Te C1 TP1 S Oli O Ret Adj allows trimming voltage c onTP1 2 048 volts provides 20mA 196 outputs with 100 a of full scale readings 64 5 R26 ag 9 m JS 5 9 C3 C6 Qe Q3 __ SafeGuard mA Output cH Board Assy 10 0167 S PCB 0010 1121 Rev 0 ai _ 24 VDC power for output current loops must be Connectto O DOOD O 9 Ole ews supplied through TB2 DC OUT 10 LO IO IO IO LO IO IO Connect to main PCB PCB B1 terminals 10 amp 12 of TB2 N m TB H H H H H H lt es SOR 28 888383838 Channel 4 20 mA Output Board Part SG10 0167 Figure 3 5 37 SafeGuard Controller User Manual MAN 0115 Rev 0 3 1 8 OPTIONAL 24VDC 150 WATT POWER SUPPLY The SafeGuard Controller may be powered from 10 30VDC However many applications require 24VDC power for the monitors or transmitters providing inputs to the SafeGuard Controller A 150 watt AC DC power supply may be included for these applications 115VAC or 230 VAC selected via slide switch When ordered from factory it is pre wired to provide 24VDC primary power for the SafeGuard Controller as well as any transmitters or monitors that may be connected by the
24. 57 Due to the large size MAX MIN or AVERAGE values may only be retrieved one at a time To improve bandwidth the master may retrieve the database in blocks of 120 registers at a time one half of a channel s data The only updates these 3 840 registers upon receiving an update command from the Modbus master Type Channel First Last Read FC Write FC Notes Update MIN n a 2065 n a n a 5 Moves 24 hour MIN data trend to trend data base Update AVG n a 2066 n a n a 5 Moves 24 hour MIN data trend to trend data base Update MAX n a 2067 n a n a 5 Moves 24 hour AVG data trend to trend data base This update requires several seconds Therefore a data ready register is available to notify the master upon completion Type Channel First Last Read FC Write FC Notes MIN Ready n a 12065 n a 2 n a 0 data ready 1 update in progress AVG Ready n a 12066 n a 2 n a 0 data ready 1 update in progress MAX Ready n a 12067 n a 2 n a 0 data ready 1 update in progress Trend database registers Type Channel First Last Read FC Write FC Notes 24 hr Trend 1 16 33017 36857 5 n a Transfers 24 hour trend for MAX MIN or AVG SafeGuard Controller User Manual 0115 Rev 0 35 SECTION 6 6 1 SAFEGUARD PM PANEL RACK MOUNT ENCLOSURE The SafeGuard Panel Mount shown in Figure 6 1 is a half width 19 rack enclosure It is supplied with hardware that allows mounting in either a full width 19 rack style cabinet or it may be panel mounted in a
25. H3 Failsafe VES Common Relay 1 Common Relay 2 w Disc Relays Horn Piezo Comm Ports 8716 Ch Mode Entry menu Discrete Relay Configure Figure 2 11 2 3 3 COMMON HORN RELAY amp LOCAL PIEZO The SafeGuard Controller is equipped with a low decibel audible piezo which chirps when keys are pressed and may be configured to audibly indicate alarm conditions The common horn relay is similar to the common Al amp A2 common relays System Setur System Setur Version Horn Relay Common Relas 1 Piezo Alarm OFF Common Relay 2 s Hlarm 1 Disc Relays Alarm 2 H HornzPiezo Failsafe OFF ete Horn Grour 1 16 Acknowledge YES Disrlay Alm Entry menu Piezo Horn Relay Figure 2 12 17 SafeGuard Controller User Manual 0115 Rev 0 Turning Piezo Alarm ON causes the audible piezo to duplicate the action of the horn relay This feature may be used to provide a low decibel indication of the status of the system s horn e Alarm 1 amp Alarm 2 menus control how the alarm level from each channel will affect the common horn relay Choices are OFF ON or BEEP one Hz Pulsating As an example A2 conditions might pulse the horn BEEP and conditions cause a steady horn ON Any other combination of these 3 choices is possible for Al and A2 levels affecting the horn relay This feature is very useful since it allows the horn relay to serve as another level level A2 or both for channe
26. P Switch settings See MAN 0082 1 Refer to MAN 0082 prior to setup Select the desired address for the device Example DIP Switch 1 positions 1 2 3 4 ON This corresponds to a Modbus Address of 1 Refer to MAN 0082 Baud Rate of 9600 bps 3 Set DIP Switch 2 positions 3 and 4 in OFF This allows 8 data bits no parity bit 2 stop bits also compatible to 1 stop bit SafeGuard Controller User Manual 0115 Rev 0 Set DIP Switch 2 position 1 OFF and position 2 ON This corresponds to a 22 Connection between the Digital Millennium II Transmitter series and SafeGuard 1 Prior to connection ensure that the SafeGuard and the transmitter are not powered up 2 Check to make sure the Millennium Sensor is properly connected to the Millennium Transmitter 3 Connect the transmitter power terminals to the DC Out terminals terminals 10 and 12 on the SafeGuard Take note of the SafeGuard s positive and negative terminals at DC Out 4 Connect the transmitter Modbus terminal A to the SafeGuard Master Comm 1 terminal 1 or Master Comm 1 terminal 5 on SafeGuard 5 Connect the transmitter Modbus terminal B to the SafeGuard Master Comm 1 terminal 3 or Master Comm 1 terminal 7 on SafeGuard Note that the SafeGuard s Master Comml terminals are the top terminals 1 3 5 7 See Figure 3 1 6 Jumper the transmitter s COM VDC terminal and the Communication COM terminal tie them togeth
27. PR 0350m5 Radio Setur Serial Ports SetuP hannel Mode s Channels 8 16 Channel Config SYSTEM CONFIGURATION MENUS Votes entry determines the number channels needed to set Relay 1 or Relay 2 Acknowledge is disabled when no A2 Votes are entered 2 Relay menus are identical RADIO CONFIG 200 MHZ HOP Channel System ID Mode CLIENT Figure 2 9 15 2 3 1 COMMON ALARM RELAYS 1 amp 2 READ THIS SECTION CAREFULLY AND TEST ALL SETTINGS BY SIMULATING INPUT CONDITIONS THAT SHOULD ACTIVATE THESE ALARM RELAYS Common Relay 1 amp Common Relay 2 menus are identical and therefore discussed only once It is very important to fully understand these menus since they determine the functions of each common relay Votes entry determines the number channels needed to set Relay 1 or Relay 2 System Setur m Setur Uersion 4 telas 1 2 Common Relay 1 Common Relay 2 Failsafe Disc Relays Al Votes Acknowledge is disabled when HornzPieza H2 Votes Comm Ports no A2 Votes are entered 6 16 Ch Mode Entry menu R1 R2 Relay menus are identical Figure 2 10 The Group menu entry offers additional flexibility by controlling which channels trip this menu s common alarm relay The 3 choices are 1 16 1 8 or 9 16 Some applications have different types of detectors or detectors in different areas connected to the same SafeGuard Controller In these cases it may be undesirable
28. SCRETE RELAY PCB SG10 0195 An optional Discrete Relay PCB shown in Figure 3 4 adds eight 5 amp resistive form C relays per sixteen channel alarm group 2 PCB s required when utilizing more than 8 channels Each PCB may be configured via rotary switch S1 to function for ALARM 1 ALARM 2 or ALARM 3 FAULT for channels 1 8 or 9 16 A one 1 minute time delay after power is provided to inhibit relay actuation until the system has had time to stabilize Alarm groups or zones may be created by connecting adjacent channels together using JP4 as shown This creates a wire OR function with selected channels causing any alarm included within the zone to actuate ALL zone relays Failsafe operation of SG10 0195 discrete relays may be programmed in the system menu as 25 SafeGuard Controller User Manual 0115 Rev 0 described in section 2 3 2 SafeGuard Controller applications utilize the common alarm relays see section 3 0 and do not require discrete relays for each of the 48 alarm events 16 Al s 16 A2 s amp 16 A3 s If discrete relays are needed for all 48 alarms then six PCB s are required 5 VDC power to the discrete relay option PCB s is normally supplied from the SafeGuard Controller via the slender cables connected to J2 and J3 However cables are limited in ability to carry this power further than a few feet without a significant voltage drop Some SafeGuard Controller applications with relays for a
29. SSED DURING THE DIAGNOSTICS MODE It is possible to miss important input values while utilizing this mode and appropriate safeguards should be in place However the Diagnostics Mode can prove invaluable when testing I O since relays and analog outputs may be stimulated without driving inputs to precise levels seks R HIM Ga InFuts will not be processed While in diagnostics noq Hlarm Relay nd Analo sue na change using fates a Fe tin connected this contra Press EDIT to enter diagnostics Ana other key to exit Sea ene ARE YOU SURE Press EDIT to enter diagnostics Ary other to exit Common Relays Discrete Relays Piezo Serial Ports Analog Outputs Printer Port Connected L Diagnostics menu Figure 4 1 29 SafeGuard Controller User Manual MAN 0115 Rev 0 Firmware Us Rev level Common Relays Discrete Relays Piezo Serial Ports Analog Outruts Analog Inputs Alarm LEDs Printer Port Connected 170 Use yP POWN kess to change comen Allows manual actuation of Common Alm1 Alm2 FAIL and HORN relays Front panel LED ON confirms PRESS NEXT KEY TO EXIT relay actuation Us Common Relays Discrete Relays Piezo Serial Ports Analog Outruts Analog Inputs Alarm LEDs Printer Port Connected 170 listes PUN Pose ED Allows manual actuation of 1 t for the relay energized any connec
30. allic enclosures do not provide grounding between conduit connections TYPICAL GROUNDING ILLUSTRATIONS METALLIC CONDUIT NON METALLIC CONDUIT CONNECTOR LOCKNU E NUT GHOUNDING BUSHING GROUNDING WIRE GROUNDING CONNECTION Figure 6 3 SafeGuard Controller User Manual 0115 Rev 0 ing bushings have provisions for connection of grounding wire 38 6 3 SAFEGUARD MAIN I O amp OPTION PCB FOOTPRINT DIMENSIONS SafeGuard Controllers have virtually unlimited possibilities for configuration of options such as analog I O discrete relays printer interface and others All SafeGuard enclosure styles require the Main I O PCB Figure 3 1 but also support the mounting of additional option PCB s as described below SafeGuard PM Panel Rack Mount supports 2 option positions as standard and 4 more with the SG10 0180 expansion plate since in panel rack mount installations SG10 0180 s must be mounted in user space behind panels or inside racks multiple SG10 0180 s may be incorporated to support the required option positions SafeGuard N4 Wall Mount supports 3 option positions as standard and 4 more with the 10 0180 expansion plate Figure 6 4 provides Main I O and option PCB dimensions 5 125 4975 4 125 holes 4 places MAIN I O amp OPTION s PCB FOOTPRINT A9 00 t a 0 0 16 2 56 2 80 Figure 6 4 SafeGuard Controller User Manual 0115 Rev 0 39 SECTION 7
31. alue pixel is then left blank leaving a gap in the vertical line This is demonstrated in the noisy area of the 24 hour trend in Figure 2 0 If the MAX amp MIN values are within 2 of each other there is no need for the vertical line and only the AVERAGE value pixel is darkened as in the quiet areas The top portion of each trend screen indicates channel real time reading in engrg units measurement name range and MIN MAX amp AVERAGE values for the preceding 24 hour period The SI field on the top right indicates number of seconds remaining in the current 6 minute subinterval 1 1 2 BAR GRAPHS SCREEN The SafeGuard Controller s Bar Graphs screen shown in Figure 2 0 allows all active channels to be viewed simultaneously Both engineering units values and bar graph values are indicated in real time Lines across the bars indicate the alarm trip points making it easy to identify channels at or near alarm A feature in the Systems menu tree allows new alarms to always force the LCD to the bar graphs screen This is useful for applications requiring channels with alarms to be displayed 1 1 3 COMBINATION SCREEN The SafeGuard Controller s Combination screen shown in Figure 2 0 offers a view of a single channel but displays the data as a 30 minute trend bar graph and large engineering units It 15 also useful for testing inputs for stability since MAX MIN amp AVERAGE values refresh each time this screen is selected For example to tes
32. annels are needed a second I O option PCB may be required System Setur 8 16 Channel Mode Common Relay 1 Channels 16 Common Relay 2 Disc Relays HornzPiezo Modbus 816 Ch Mode Entry menu 8 16 Channel Config Figure 2 14 2 3 6 SENSOR INFORMATION this feature is not used at this time Sensor Info is available when at least one channel has Sensor Life activated in the Marker menu see section 2 2 4b The Sensor Info screen displays each channel s sensor status as illustrated in Figure 2 15 Channels with Sensor Life disabled indicate Option Disabled above the corresponding empty bar graph If Sensor Life is enabled the channel will have its Measurement Name above the bar or an empty bar with a Cal Required label Cal Required indicates no Calibration Marker value has been received by the SafeGuard Controller 19 SafeGuard Controller User Manual 0115 Rev 0 SEMSOR LIFE 81 Measurement Ba Disabled Reauired rFtion Disabled System Setup a2 18 Version 4H nz Reauirecd 11 rtion Disabled Common Relay 2 Disc Relay as Cal Reauired iz Disabled Modbus 8716 Ch Mode AG Reauired i4 OrFtion Disabled Sensor Info L Common Relay 1 ad Cal Resuirerd 17 Disabled j ti 11 Entry menu ar 056 15 Ortion Disabled __ tion Disabled Reauired 16 rF
33. asa Raw 84686 Raw 99258 Marker Menu Remote ID Alias 55001 Marker Menu Alarm Input From menu If input is Modbus Alarm gt Data From Linearize Configure Input Output 18 08 26 68 E 38 08 Entry Menu 528 88 58 88 78 08 36 00 58 88 Linearization menu Channel CONFIGURATION Measurement Hame Eunits 6digit ZERO 9 088 100 8 Decimal Points Channel On Yes Cory To Input To menu Zero Span ZERO 4 488 SPAH 58 88 Unity Gain eto OFF OFF If input with Local Cal Figure 2 1 SafeGuard Controller User Manual 0115 Rev 0 2 2 1 CHANNEL SETUP ENTRY MENU The entry menu shown on the left side of Figure 2 1 allows access to all configuration variables for the selected channel These are Alarm 1 Alarm 2 Alarm 3 Data From Linearize Configure and Calibrate 2 2 2 ALARM 1 ALARM 2 HORN RELAY SET UP MENU Alarms 1 and 2 are identical except A1 may not be acknowledged and front panel LED indicators are yellow while A2 s are red Since their configuration menus are the same only one is shown in Figure 2 2 for clarity Channel Channel Measurement Hame ALARM 122 Setur Alarm 1 SSetroint 28 88 Alarm 2 Latching H Rlarm On HIGH Data From On Delay aus Linearize Off Delay Configure Horn Drive Yes Entry Menu Alarm or 2 menu Figure 2 2 The first entry
34. ctrostatic sensitive semiconductor devices SafeGuard Controller User Manual 0115 Rev 0 Net Safety Monitoring Inc 2721 Hopewell Place NE Calgary AB Canada T1Y 7J7 1 866 FIREGAS 347 3427 ph 403 219 0688 fx 403 219 0694 http www net safety com Email nsmsales net safety com PRODUCT SERVICES CONTACT INFORMATION MICROWATT Making Safety Work Tollfree in Western Canada 1 888 388 1592 microwatt com mwsales microwatt com NET 4 SAFETY MONITORING INC 42
35. d FC Write FC Notes 4 n a 8bit integer Read FC Write FC Notes 4 n a 4 n a 4 n a 4 n a Signed 16bit integer Signed 16bit integer Signed 16bit integer Signed 16bit integer SafeGuard Controller User Manual MAN 0115 Rev 0 33 Sensor Life 5 31069 4 Signed 16bit integer Sensor Life 6 31070 4 Signed 16bit integer Sensor Life 7 31071 4 Signed 16bit integer Sensor Life 8 31072 4 Signed 16bit integer Sensor Life 9 31073 4 Signed 16bit integer Sensor Life 10 31074 n a 4 n a Signed 16bit integer Sensor Life 11 31075 n a 4 n a Signed 16bit integer Sensor Life 12 31076 n a 4 n a Signed 16bit integer Sensor Life 13 31077 n a 4 n a Signed 16bit integer Sensor Life 14 31078 n a 4 n a Signed 16bit integer Sensor Life 15 31079 4 Signed 16bit integer Sensor Life 16 31080 4 Signed 16bit integer Note 2 Disabled 1 CAL Required 0 100 Sensor Life Coils Notes Set this coil to issue an alarm Acknowledge via modbus Type Channel First Last Read Write FC Notes Alarm Reset n a 2001 n a n a 5 write Oxff to high byte to set Memory Discretes Notes May be read as single discrete or packed with multiple register read Type Channel First Last Read FC Write FC Notes Chnl Alarm 1 1 16 12001 16 n a 2 n a discrete may be packed Type Channel First Last Read FC Write FC Notes Chnl Alarm 2 1 16 12017 32 n a 2 n a discrete may be packed Type Chann
36. driving 20mA through a 750 ohm load Outputs are self powered and DC power should not be provided by the receiving device Note This PCB requires nominal 24VDC power be connected to TB2 terminals amp 2 as shown in Figure 3 5 Suitable power is available from SafeGuard Controller s Main I O board s TB2 terminal 10 amp 12 see Figure 3 1 The current loop Milliamp output is completed between High and Low Terminals Note that the Low Terminal is the negative end common of the loop Since the PCB has 8 channels two PCBs are required for 16 channel applications 1 1 configures the outputs for channels groups 1 8 or 9 16 Also see 2 2 4b Marker Menu to configure the SafeGuard Controller for current output for a fault condition of a detector or transmitter and gas sensor configuration Par I D1 u 08 016 zza 8 P 017 015 T JP1 determines if this 8 channel 014 C Analog Output PCB provides JE outputs for CH s 1 8 or 9 16 ed S sicud 2 PCB assemblies are required di eia i for 16 channels oni
37. e changed to 45 to match the span calibration gas If the reading is only 40 LEL with the 50 gas applied a span calibration is needed Move the pointer to the Set Span entry and press EDIT twice Unity Gain may be used at anytime to cancel incorrect calibrations and start again See Figure 2 8 Channel Channel Measurement Hame CALIBRATIO N Rlarm 1 Zero Rlarm 2 Set SFan Rlarm Cal ZERO Data From Cal SFAH 58 88 Linearize Unity Gain Configure Zzero OFF Calibrate OFF Entry Menu If input with Local Cal Figure 2 8 14 SafeGuard Controller User Manual 0115 Rev 0 2 3 SYSTEM CONFIGURATION MENUS Some items needing configuration are not specific to a channel but affect the entire SafeGuard Controller system These are located in the system entry menu shown on the left side of Figure 2 9 System menus are accessed by pointing to the desired item and pressing EDIT 4 Common Relay 1 Common Relay 2 Disc Relay Horn Piezo Comm Ports 8416 Ch Mode Entry menu SafeGuard Controller User Manual MAN 0115 Rev 0 Failsafe Al Votes R2 Votes Setur BAL Failsafe R2 Failsafe NO AS Failsafe YES Discrete Relay Piezo Alarm OFF Alarm 1 BEEP Alarm 2 OH Failsafe orf Horn Grour 1 16 Acknowledge YES Disrlas Alm Piezo Horn Relay Slave ID a Slave Baud 3688 Parity UART Timer 085 Mastr Mastr
38. el First Last Read FC Write FC Notes Chnl Alarm 3 1 16 12033 48 n a 2 n a discrete may be packed Memory Reals Notes Real value represents float value without the decimal point such as 123 4 is returned as 1234 Decimal devisor is returned as 1 10 100 or 1000 for decimal position of 1 2 3 or 4 where 123 4 would return the value 10 Type Channel First Last ReadFC Write FC Notes Zero Real 1 16 41001 16 n a 3 n a zero real w o decimal point Zero DP 1 16 41017 32 n a 3 n a zero real divisor Span Real 1 16 41033 48 n a 3 n a span real w o decimal point Span DP 1 16 41049 64 n a 3 n a span real divisor Alarm 1 Real 1 16 41065 80 n a 3 n a alarm 1 real w o decimal point Alarm 1 DP 1 16 41081 96 n a 3 n a alarm 1 real divisor Alarm 2 Real 1 16 41097 112 n a 3 n a alarm 2 real w o decimal point Alarm 2 DP 1 16 41113 28 n a 3 n a alarm 2 real divisor Alarm 3 Real 1 16 41129 44 n a 3 n a alarm 3 real w o decimal point Alarm 3 DP 1 16 41145 60 n a 3 n a alarm 3 real divisor Fault Real 1 16 41161 76 n a 3 n a alarm 3 real w o decimal point Fault DP 1 16 41177 92 n a 3 n a alarm 3 real divisor SafeGuard Controller User Manual MAN 0115 Rev 0 24 Hour Trend Database The 24 hour MAX MIN and AVERAGE trend data may be retrieved over the Modbus serial interface Each channel consists of 240 MAX MIN and AVERAGE values or one value for every 1 10 hour 6 minutes Since there are 16 channels this database equals 3 840 registers in addresses 33017 368
39. end user 9 00 1 05050505050 869080898989 V ADJ OSOSOSOSO m WO 025262888 218 659606095690 4 Amp 5x20mm fuse located under 69695960 cover To access disconnect power 6262626 and remove A screw amp B plastic pin av 0809869 then slide cover left and lift 1 O56969 V abc 1 ogo o989 95 5 WARNING For continued protection against fire replace only with same o beat ot 9 type and rating of fuse 69 M og FG 75 2 18 999 N VACSZA B 02896 Lbs OSORGORC ica din E a o89898 RISK OF ELECTRICAL sewa sesi SHOCK DISCONNECT OR TURN OFF POWER 0626262 026259252 SERVICING 8888889 083898988 EQUIPMENT 2 00 RANGE U SELECTOR SWITCH m 150 Watt 24 VDC Power Supply Option 5610 0172 Figure 3 6 SafeGuard Controller User Manual 0115 Rev 0 28 SECTION 4 4 0 SYSTEM DIAGNOSTICS A System Diagnostic Mode shown in Figures 4 1 and 4 2 may be entered during normal operation from the Setup menu The entry menu indicates firmware revision and offers useful routines for testing front panel LED s relays serial ports and analog I O It is exited manually by pressing NEXT and automatically if no keys are pressed for 5 minutes It is very important to understand that CHANNEL INPUT DATA IS NOT PROCE
40. enu a pointer controlled by the UP DOWN keys indicates the selected variable Some are simple YES NO or ON OFF entries toggled by pressing the EDIT key Others such as Measurement Name and Eunits fields may have many ASCII character possibilities Allowed ASCII characters are as follows ABCDEFGHIJKLMNOPQRSTUVWXYZabcdefghijklmnopqrstuvwxyz blank space amp 0123456789 lt gt EDIT places a cursor over the item and UP DOWN scrolls through each allowed entry The NEXT key moves the cursor to the next position within a field When the field is complete EDIT clears the cursor and loads it into non volatile memory where it is retained indefinitely With no cursor present NEXT closes open menus in reverse order and returns the LCD to the most recent data display SafeGuard Controller User Manual MAN 0115 Rev 0 2 2 CHANNEL CONFIGURATION MENUS Figure 2 1 illustrates the menu tree for configuring Channel variables These items affect only the specific channel selected System specific variables are in the menu tree shown in section 2 3 CHANNEL MENUS TREE Setpoint 28 88 Latching HO On HIGH On Delay B s Off Delay 68m Horn Drive Yes Alarm 1 or 2 menu Setroint 5 000 Setroint 68 08 Tre FAULT Latching Trip On HIGH Tyre LEVEL Alarm 3 Fault menu If for A3 level Channel Channel IHPUT DATA FROM INPUT DATA FROM Analog Input HODBUS 8 BIT Min Raw Min Raw Ba
41. er 7 Power up the SafeGuard SafeGuard settings Note Leave Jumpers at JP1 in place for two wire RS 485 operation See Figure 3 1 1 Choose a Channel and select Data From then choose the following settings Modbus 16 Bit Min raw 00000 raw 00100 Remote ID 01 Alias 40001 Under System select Comm Ports and choose the settings as follows Slave ID 01 Slave Baud rate 9600 Parity None UART Timer 155 s Mastr TO 0200 ms Mastr PR 0200 ms ECHO ACK OFF Proper communication between the two devices will be confirmed by the TX1 and RX1 LEDs Note When configuring other Net Safety products refer to specific user manual 23 SafeGuard Controller User Manual 0115 Rev 0 3 1 INPUT OUTPUT OPTIONAL PCB s Telephone style RJ11 connections are used to add optional 8 channel analog and digital I O A screen appears briefly after power up indicating what options are connected and for which channels This information is also available from the Diagnostics Mode described in Section 4 PRESS NEXT KEY TO EXIT Figure 3 2 3 1 1 OPTIONAL ANALOG INPUT SG10 0158 Many transmitters detectors have analog output signals and the 12 bit Analog Input PCB shown in Figure 3 3 is available to accept these TB1 with 24 positions offers 3 terminals per channel for distributing power and receiving analog inputs These are EXC and HI LO inputs TB2 with only two positions is for connecting
42. er process inputs applied to this channel and no alarms will be tripped or data displayed Inactive channels have a line drawn through them on the Setup screen as indicated by channels 15 amp 16 in Figure 2 0 If less than 9 channels are to be activated the SafeGuard Controller may be set for 8 channel mode deactivating channels 9 16 This is done in the System Setup menu described in section 2 3 The SafeGuard Controller will only allow 15 channels to be turned off At least one channel must remain on 2 2 60 COPY DATA This menu simplifies the Setup procedure by allowing similar channels to be copied from one to another For example if all channels are identical except for the Measurement Name entry channel 1 could be configured and copied to channels 2 16 Only Measurement Name then must be configured on channels 2 16 Use EDIT to increment channel numbers and UP DN to point to Copy Now Press EDIT once more to copy 13 SafeGuard Controller User Manual MAN 0115 Rev 0 2 2 7 CAL MODE This SafeGuard Controller feature is only accessible when Sensor Direct or Analog Input with Local Cal is selected The Analog Input with Local Cal option may be used if the transmitter and sensor connected to the controller are located in an area not easily accessible A calibration tube should be fitted to the sensor and run to an easy access location where a gas canister is fitted and calibration performed using the calibration menu It sho
43. er read Sixteen character channel tag name Type Channel First Last Channel Tag 1 40401 40408 Channel Tag 2 40409 40416 Channel Tag 3 40417 40424 Channel Tag 4 40425 40432 Channel Tag 5 40433 40440 Channel Tag 6 40441 40448 Channel Tag 7 40449 40456 Channel Tag 8 40457 40464 Channel Tag 9 40465 40472 Channel Tag 10 40473 40480 Channel Tag 11 40481 40488 Channel Tag 12 40489 40496 Channel Tag 13 40497 40504 Channel Tag 14 40505 40512 Channel Tag 15 40513 40520 Channel Tag 16 40521 40528 Six character Eunits Tag Type Channel First Last EUNITS 1 40529 40531 EUNITS 2 40532 40534 EUNITS 3 40535 40537 EUNITS 4 40538 40540 EUNITS 5 40541 40543 EUNITS 6 40544 40546 EUNITS 7 40547 40549 EUNITS 8 40550 40552 EUNITS 9 40553 40555 EUNITS 10 40556 40558 EUNITS 11 40559 40561 EUNITS 12 40562 40564 EUNITS 13 40565 40567 EUNITS 14 40568 40570 EUNITS 15 40571 40573 EUNITS 16 40574 40576 SafeGuard Controller User Manual 0115 Rev 0 Read Write FC Notes 3 G WwW Read FC Write FC 3 GQ 2 characters per register 2 characters per register 2 characters per register 2
44. ibed in section 2 2 4a to define the range of the input signal s engineering units For example if a channel s input is 4 20mA from a transmitter monitoring 0 to 10ppm H2S then the Zero value should equal 0 000 and the Span value equal 10 00 The six ASCII engineering units previously entered are automatically displayed at the top of each menu asareminder Four digits must appear in this entry so trailing 0 s may appear here that are not displayed on other data screens 2 2 66 DECIMAL POINT RESOLUTION Resolution of displayed channel values is configured in this menu by setting the number digits trailing the decimal point Values are limited to a maximum of four digits and a polarity sign An auto ranging feature displays the highest resolution allowed by this menu s decimal point entry For example if three decimal points are entered and the range is 0 to 100ppm the reading will be 0 000 at Oppm and 100 0 at 100ppm However this may be undesirable due to the high resolution at zero unless the detector s output is extremely stable If decimal points are limited to one the Oppm reading becomes 0 0 and the 100ppm reading remains 100 0 Resolution may be limited further by setting decimal points to 0 In the above example this would cause Oppm to display 0 and 100ppm to display 100 2 2 6d TURNING OFF UNUSED CHANNELS The Channel On entry determines if this channel is to be utilized Turning it off will cause the SafeGuard Controller to nev
45. indicators remain active during the Setup mode An AUTHORIZE menu offers a password feature to prevent tampering with the SafeGuard Controller s parameters SafeGuard Controller User Manual MAN 0115 Rev 0 Chel PCTLEL 2 18 PCTLEL Chas PCTLEL PCTLEL a 5 6 a Chas PCTLEL F H PCTLEL il B Nea Char PCTLEL AS CS S eer hg SoM 5 OM PCTLEL 2 Measurement MAS 18 SETUP HIH 1 AUG 3 System Channel amp 81 Channel 89 SPAH OREL Channel 1 uthorize anne anne ene COUNTS PCTLEL ZERO i Diagnostics Channel 84 Channel 12 UNLOCKED Channel Bs Channel 13 Channel 86 Channel 14 Channel oF E Channel Ehan E MINUTES 4 Combination Setup Figure 2 0 2 1 SETUP MENU CONFIGURATION Variables inside system and channel menu trees allow optimum SafeGuard Controller configuration for a wide range of demanding multi point monitoring applications Access to menus is via the Setup mode by pressing EDIT and activating the Setup screen shown in Figure 2 0 Menu trees are provided for each of the 16 channels and another for system variables Select the desired menu by scrolling with UP DOWN and EDIT to enter the menus 2 1 1 CHANGING MENU VARIABLES USING THE KEYPAD Upon entering a m
46. interface to the SafeGuard Controller s Modbus slave port The Mastr TO master time out and Mastr PR master poll rate menu items affect the SafeGuard Controller s master Modbus port Time out sets length of time in milliseconds before a communications error Three consecutive timeout errors must occur before a communication error is indicated This item is useful for optimizing throughput to the SafeGuard Controller from other slave RTU s Poll Rate sets frequency of data requests to the RTU s in milliseconds This is useful when an RTU is limited in how fast it may respond to consecutive data requests 18 SafeGuard Controller User Manual 0115 Rev 0 RADIO COHFIG MHZ Common Relay 1 Slave ID HOP Channel Common Relay 2 Slave Baud 9688 System ID Disc Relays Parity Mode CLIENT UART Timer 5 Comm Ports Mastr TO 5 8716 Ch Mode Mastr PR 05595 NEXT PRadio Setur Entry menu Serial Ports Radio Config Figure 2 13 2 3 5 EIGHT SIXTEEN CHANNEL MODES The system menu allows setting the SafeGuard Controller to accept either 8 or 16 channels If 8 channels are selected by this menu they are channels 1 8 and 9 16 are disabled One way the SafeGuard Controller cost is kept low is Input Output option PCB s are arranged into groups of 8 channels Therefore users with less than 9 channels require only 1 PCB and do not pay for I O hardware for 16 channels If more than 8 ch
47. istors 7 A2 NO 8 HORN NO NL TB1 AUX 62 remove for short wire paths amp 9 A2 COM 10 HORN COM H PWR IN when the SafeGuard Controller is 11 A2 NC 12 HORN NC ev ele nmm ln ON not end of path TB4 TB2 VDDD DD VG 5 DID Apply only nominal 24 VDC 1A1 NO 2 A3 NO 1 COMM1 RXA 2 COMM2 RXA min 10 VDC max 30 VDC power A1 COM 4 A3 COM 3 COMM1 RXB 4 COMM2 RXB 2 2 6 40 12 2 2 e 42 to terminals 9 amp 11 of TB2 5A1 NC 6 A3 NC 5 TXA 6 COMM2 TXA comm2 7 A2 NO 8 HORN NO 7 TXB 8 TXB TB1 TB2 Dcour TB2terminals 10 amp 12 provide 9 A2 COM 10 HORN COM 9 DC IN 10 DC OUT 62 COMM1 Master SO Fused 24VDC power to the 11 A2 NC 12 11 DC IN 12 DC OUT od COMM2 Slave SafeGuard Controller option 1 COMM2 Slave Main PCB WITH COMMON RELAYS Figure 3 1 boards requiring such power Modbus Communication between SafeGuard and Digital Millennium II Series Transmitters Examples M2X AD ARD menu settings See MAN 0076 Refer to MAN 0076 prior to attempting setup Power up the unit and enter the transmitter Modbus menu option Modbus Setup Select address 001 or the desired address for each unit Choose Baud Rate of 09600 bps Select NO under parity Note that the unit will retain its settings if power is removed M2B D DI
48. ll 48 alarms may require up to 6 boards TB2 allows a heavier 5VDC power cable to be connected from terminals on the back of the SafeGuard Controller front panel assembly bypassing the cable A 20AWG pair connected to only one of the several TB2 s is sufficient when these boards are in close proximity to each other All relays are rated at 5 Amp for 28 VDC and 250 VAC RESISTIVE loads IMPORTANT Appropriate diode DC loads or MOV AC loads snubber devices must be installed with inductive loads to prevent RFI noise spikes Relay wiring should be kept separate from low level signal wiring TB2 is used to supply external 51 controls if discrete relays are tripped by 5VDC power to Alarm boards A1 A2 or A3 alarms for Ch s 1 8 or 9 16 when they are mounted 5 See Chart feet from the controller 12C ASSY 10 0195 8 DISCRETE RELAY i Wire TO 8 CH CHART cables provide T pees Wre TO U WITHSBELAYS STACH ISA occur with longer cable lengths tom controller selects Chs 1 8 81 3 Ch9 18 A2 or 9 16 for A1 2 amp S1 4 Ch9 16 5VDC ONLY See chart gt S1 5 Ch1 8 WARNING Voltages exceeding A0 gt S1 8 Chi 8 A2 6 volts may cause extensive IS1 7 Ch1 8_A3 damage to entire controller _ Q syo 2 TB 51 U3 J2 8 J3 interchangable 12C connectors used to add option PCB assemblies to the controller S
49. ls 1 16 1 8 or 9 16 Individual channel alarms may also be configured to not affect the Horn relay on a channel by channel basis see section 2 2 2 e Failsafe amp Horn Group menu entries are identical to the descriptions for menus Common Relay 1 amp Common Relay 2 in section 2 3 1 Turning Acknowledge OFF allows the common Horn relay to drive devices other than horns or sirens such as a light or a fan Display Alm YES forces the LCD to display the Bar Graphs screen upon any new alarm This feature is offered to satisfy applications requiring channels in alarm to be displayed automatically all channels are displayed on the Bar Graphs screen 2 3 4 COMM PORT MENUS The system Comm Port menu allows setting RTU Slave ID address Slave Baud rate Parity and UART Timer for the comm slave Modbus serial port comm1 master port ID settings are per channel as described in section 2 2 4 This slave port may be used to transfer the SafeGuard Controller data to a host device such as a PC PLC DCS or even another SafeGuard Controller The slave port is addressable allowing many SafeGuard Controllers to be connected to a single RS 485 cable The UART Timer setting is disabled with 00 seconds entered Entering a value causes the comm2 slave Modbus serial port to reinitialize if no modbus query is processed within this time period This ensures against serial port lockup Section 5 of this manual provides important information describing how to
50. menu to Alarm 3 The following example describes how to configure both the Fault out of range and Alarm 3 level trip points for a channel Example If the common Fault relay must trip as the input falls below negative 10 of full scale and the discrete alarms trip as the input exceeds a level then 1090 Fault setpoint must be entered first Toggle the TYPE menu entry to FAULT and enter 10 00 into the setpoint entry Next toggle menu back to LEVEL and enter the desired Alarm 3 level setpoint The 10 Fault value is retained in memory even though it no longer appears on the menu Channel Channel Channel Measurement Name ALARM 3 Setur ALARM 3 Setur Alarm 1 Setroint 5 000 W SetPoint 60 00 Alarm 2 Fault Latching Alarm 3 Trie On HIGH Data From Tyre LEVEL Linearize Configure Entry Menu Alarm 3 Fault menu If for A3 Level Figure 2 3 2 2 4 DATA FROM MENU TO SET INPUT SOURCE Channels may be independently configured to accept input data from the following sources also see Figure 2 4 e An analog input PCB attached to the bus A sensor input PCB may be attached to bus This Option Board is however not used at this time e The Modbus RS 485 master port connected to modbus slave devices Note Each Modbus menu selection also requests the RTU and the Alias register location of the data to be retrieved from the RTU Alias register SafeGuard Controller User Manual
51. nu s MIN should be set at 200 and MAX at 1000 If communicating with the SafeGuard Controller s optional 12 bit Analog Input PCB the MIN should be 800 and the MAX 4000 If the input device s resolution is unknown the live counts variable on the bottom of the screen displays actual raw A D counts currently being read by this channel This reading may be used to test the input device for what A D counts are provided for zero and 100 if these values are unknown Forcing the input device to read zero should provide the A D counts value needed to make this channel s display also read zero Likewise forcing the input device to read 100 should provide the A D counts value needed to make the SafeGuard channel s display also read 100 10 SafeGuard Controller User Manual 0115 Rev 0 If Modbus 32 BIT is selected a Byte Order entry appears at the bottom of the menu This determines WORD and BYTE alignment of data at the remote Modbus transmitter when sending its 4 byte IEEE Floating Point values With the pointer on this entry the EDIT key toggles between 4 possible modes Min Max Raw values are not used in this mode Note Each Data From item has a matching default Min Max counts value of 20 to 100 with 5 over under range applied If the default value is incorrect for the input device it should be edited 2 2 46 MARKER MENUS Some transmitters or monitoring devices providing SafeGuard Controller inputs also indicate s
52. pecial modes of operation such as Calibration Maintenance or Fault by transmitting a special lt 4mA or negative Marker value The SafeGuard Controller offers channel Marker menus for detecting and indicating such events see Figure 2 5 While active the SafeGuard Controller displays a 6 digit ASCII message to indicate the special event and if equipped with SG10 0167 4 20mA output option the SafeGuard Controller also transmits the same lt 4mA value e Marker Enabled turns the marker feature ON and OFF e The negative Marker value is entered into the Marker field as a negative percent of full scale For example 15 62 of full scale detects a marker value of 1 5mA 1 5mA is 15 62 of full scale when 4 20mA is the range e It should be noted that for Net Safety Flame Detectors the current output for a visual integrity fault is 2 0 mA this corresponds to a Marker of 12 5 For Net Safety Gas Sensor Fault Condition the current output is 2 5 mA which would correspond to a Marker of approximately 9 4 e The Mark As menu allows user entry of the 6 digit ASCII message to be displayed when the marker is detected Channel Channe Channel Kx channel Measurement Name INPUT DATA FROM INPUT MARKER Alarm 1 Analog Input Marker Enable v Alarm 2 Min Raw Marker 15 62 Alarm 3 Raw 84888 Mark As CAL Data From Marker Menu Sensor life VW Linearize Reset Sen Life Configure
53. r friendly menus and all configuration data is retained in non volatile memory during power interruptions The SafeGuard Controller s front panel is shown below in Figure 1 0 displaying the 8 channel bar graph screen Additional data screens are shown in Figure 2 0 PCTLEL PCTLEL PCTLEL PCTLEL PCTLEL PCTLEL PCTLEL PCTLEL Figure1 0 SafeGuard Controller User Manual 0115 Rev 0 1 1 DATA DISPLAY SCREENS The SafeGuard Controller offers 3 distinct graphic displays for depicting the monitored data These are Bar Graphs 24 Hour Trend and Combination Each is shown in Figure 2 0 1 1 1 TREND SCREEN The SafeGuard Controller s Trend screen shown in Figure 2 0 displays a 24 hour trend of input data for the channel selected Horizontal tic marks are each hour and vertical tic marks are each 10 of full scale Dashed lines indicate alarm levels The graphic LCD is 240 pixels wide so each pixel represents 1 10 hour or 6 minutes worth of data The trend is 100 pixels high so each represents 1 of full scale in amplitude Since each data point must be collected for 6 minutes before it may be displayed it is likely input values will fluctuate during this interval Therefore MAX MIN and AVERAGE values are stored in RAM memory for each 6 minute subinterval To accurately portray the trend a vertical line is drawn between MIN amp MAX values for each 6 minute subinterval The AVERAGE v
54. r register 3 registers per channel ASCII Value 4 40586 40588 3 n a 2 characters per register 3 registers per channel ASCII Value 5 40589 40591 3 n a 2 characters per register 3 registers per channel ASCII Value 6 40592 40594 3 n a 2 characters per register 3 registers per channel ASCII Value 7 40595 40597 3 n a 2 characters per register 3 registers per channel ASCII Value 8 40598 40600 3 n a 2 characters per register 3 registers per channel ASCII Value 9 40601 40603 3 n a 2 characters per register 3 registers per channel ASCII Value 10 40604 40606 3 n a 2 characters per register 3 registers per channel ASCII Value 11 40607 40609 3 n a 2 characters per register 3 registers per channel ASCII Value 12 40610 40612 3 n a 2 characters per register 3 registers per channel ASCII Value 13 40613 40615 3 n a 2 characters per register 3 registers per channel ASCII Value 14 40616 40618 3 n a 2 characters per register 3 registers per channel ASCII Value 15 40619 40621 3 n a 2 characters per register 3 registers per channel ASCII Value 16 40622 40624 3 n a 2 characters per register 3 registers per channel Memory Floating Point Notes Returned as 15 bit 2s complement with 5 over under range applied Therefore this must be considered when scaling values to be displayed at the modbus master The following equation may be used to determine a value for display Display Value MODBUS Value Span Value Zero Value 1 1 Zero Value Span Value
55. rm to turn the horn relay on steady or to pulse it depending upon horn configuration in the system menu see section 2 3 3 Discrete LED indicators on the front panel indicate the status of each alarm and relay Any new alarm event causes the associated LED to flash until Alarm Reset occurs SafeGuard Controller User Manual MAN 0115 Rev 0 causing an acknowledged steady on condition Operators should recognize new alarms by a flashing LED Alarm Reset also acknowledges or deactivates the horn relay until another new alarm occurs All relays are rated at 5 Amp for 28 VDC and 250 VAC RESISTIVE loads IMPORTANT Appropriate diode DC loads or MOV AC loads snubber devices must be installed with inductive loads to prevent RFI noise spikes Relay wiring should be kept separate from low level signal wiring 2 2 93 ALARM 3 FAULT ALARM MENU The discrete channel alarms identified as Alarm 3 Fault may be configured either as a 3 level alarm or as a Fault alarm indicating the input is out of range in the negative direction When used as a level alarm features such as on off delays latching and trip direction are also available It is important to understand that though discrete channel alarms LED s amp optional discrete relays may be set as Alarm 3 level alarms the common relay for this group is always a Fault alarm The fault out of range threshold for the channel is the most recent Fault trip point entered prior to changing the
56. t entries are not provided so installers may place entries as needed Bottom or lower side areas are recommended Care must be taken to avoid drilling into circuit boards mounted inside the enclosure Properly ground the enclosure and follow national and local electrical codes 13 16 10 00 AN A Y E YJ ge 8 50 Note 4 mounting holes 31 diameter SHOCK HAZARD ADD LOCKING DEVICE TO CLASP ON BOTTOM RIGHT SIDE TO PREVENT CONTACT WITH DANGEROUS VOLTAGES REMOVE AC POWER BEFORE SERVICING EQUIPMENT NEMA 4X WALL MOUNT Figure 6 2 37 SafeGuard Controller User Manual 0115 Rev 0 GROUNDING OF EQUIPMENT AND CONDUIT Ground in accordance with the requirements of the National Electrical Code Conduit hubs for metallic conduit must have a grounding bush ing attached to the hub on the inside of the enclosure Ground Non metallic conduit and hubs require the use of a grounding 4 wire in the conduit Grounding bushings are not required To avoid electric shock System grounding is provided by connection wires from all con grounding must be duit entries to the subpanel or to other suitable point which pro installed by the customer vides continuity Any device having a metal portion or portions as of the installation extending out of the enclosure must also be properly grounded Non met
57. t stability over a one hour period for an input begin timing as soon as the channel is selected One hour later record the MAX MIN amp AVERAGE values The difference between MAX amp MIN indicates peak to peak excursions over the one hour period and AVERAGE is the average for the hour Longer or shorter tests may also be run The numeric value shown below the bar graph indicates number of minutes samples have been taken After 999 minutes the AVERAGE buffer overflows and the error message UPDATE appears in the AVERAGE field Exiting this screen resets the buffer and clears the error message SafeGuard Controller User Manual 0115 Rev 0 1 2 SPECIFICATIONS 1 2 31 DC POWER SUPPLY REQUIREMENTS Standard SafeGuard Controller power requirements 10 30VDC 3 watts applied to terminals 9 amp 11 of TB2 on the standard I O PCB see section 3 0 Optional features increase power consumption as described below Discrete Relay PCB option add 2 watts per PCB assumes all 8 relays are energized Analog Input PCB option add 1 2 watt 4 20mA Output PCB option add 1 watt TB2 terminals 10 amp 12 of the standard PCB provide a maximum of 500mA fused output power for powering of auxiliary external devices such as relays lamps or transmitters Power consumed from these terminals should be considered when calculating system power consumption When wiring transmitters detectors to the SafeGuard Controller refer to 3 1
58. tandard configuration has a 1 minute POWER ON time delay 1__ Isoigggy 982 preventing relay actuation during EN the delay SB1 increases delay 2 time to 8 minutes 582 removes x channel alarms All zoning jumpers are placed vertically Jumper all time delay positions as seen create one zone ically for Channel 1 Channel 4 and tocreate ai another zone for Channel 5 Ch zones J Channel 7 All relays in a zone switch together Unused jumpers are placed horizontally JP4 allows zoning of adjacent Q Q Q Q Q Q Q Q Q NO NO C NC CH3 11 CH5 13 CH7 15 TB1 2 Q Q Q 00 Q Q QO Q Q NO C NC NO NO C NC CH2 10 CH4 12 CH6 14 CH8 16 5 amp form C dry contacts Contacts are unfused Switching inductive loads may create high levels of RFI Use appropriate RFI Snubbers on inductive load devices 8 channel discrete relay Option Board Part SG10 0195 26 Figure 3 4 3 1 6 OPTIONAL 4 20mA ANALOG OUTPUT BOARD 5610 0167 An optional 10 bit 4 20mA analog output board shown in Figure 3 5 may be connected to the bus Each channel 5 output will transmit 4mA for 0 readings and 20mA for 100 readings Loop drive capability depends upon the level of the SafeGuard Controller s primary DC power supply With at least 20 volts DC primary power they are capable of
59. ted discrete relays without stimulating the inputs Front panel LED ON confirms PRESS NEXT KEY TO EXIT relay actuation Common Relays P Discrete Relays Piezo Analog Outruts Analog Inputs Alarm LEDs Printer Port Connected 170 Serial Ports local piezo beeper ulses the controller s Common Relays Discrete Relays Piezo m Serial Ports Analog Outputs Analog Inputs Alarm LEDs Printer Port Connected 170 See AML unn together des si Provides simple means of testing the controller s serial ports Communications FAILED PASSED PRESS ANY KEY EXIT ys Serial Ports Analog Outruts Analog Inputs Alarm LEDs Printer Port Connected 170 Pre UP_DOWN keys to change channel ss EDIT to change outrut value Allows forcing 4mA 12 mA or 20mA to any connected analog output channels ERROR OUTPUT BOARD NOT FOUND Channel 01 Discrete Relays Serial Ports Analog Outputs Analog Inputs x S Alarm LEDs Printer Port Connected 170 Analog Outputs Printer Port Connected 170 Relays Displays A D counts re Piezo ceived from connected Initiates flashing pattern on Serial Ports all front panel LED s with Alar LEDS out affecting alarm relays ensor or Analog inputs ass Discrete Relays Piezo Serial Ports Analog Outputs Analog Inputs Alarm LEDs Prin
60. ter Port Connected 170 Use UP_BOWN keys to change Fort Press EDIT to test Tests printer ports by sending a brief test message to the printer PASSED Note The Printer Option is not PRESS KEY TO used at this time Di i ANALOG ANALOG ANALOG ANALOG ALARM2 THPUT OUTRUT OUTPUT Relay Connon ee FOUND FOUND FOUND FOUND FOUND Indicates all connected iscrete Relays Piezo Serial Ports Analog Dutruts Analog Inputs Alarm LEDs Printer Port Connected 170 SafeGuard Controller User Manual 0115 Rev 0 options If not indicated the option is not connected Or a problem exists Figure 4 2 30 5 0 MODBUS RS 485 PORTS SECTION 5 The SafeGuard Controller is equipped with Master COMM 1 and Slave COMM 2 modbus RTU ports Port configurations are described in sections 2 2 and 2 3 of this manual Section 5 0 defines register locations of data available via the SafeGuard Controller s slave port 5 1 MODBUS SLAVE REGISTER LOCATIONS The following tables describe the SafeGuard Controller s modbus slave database Any portion of this data may be read by a modbus master device such as a PC PLC or DCS Since the modbus port is RS 485 many SafeGuard Controllers may be multi dropped onto the same cable Memory Integer ASCII Notes ASCII may be read 2 characters at a time or in strings using a multiple regist
61. the power supply for powering external transmitters Precision 100 ohm resistors R1 R8 between each channel s IN LO and IN HI terminals are socketed termination resistors for 4 20mA inputs These may be removed if voltage inputs are to be applied EXC and IN LO terminals are bussed together internally EXC terminals are tied directly to TB2 1 and IN LO terminals are tied to TB2 2 Bussing allows transmitter power to be brought into the system at a single point TB2 and distributed back out at each channel s EXC IN LO terminals to simplify field wiring Figure 3 3 includes typical wiring to 2 amp 3 wire 4 20mA transmitters JP1 determines if the 8 analog inputs are applied to channels 1 8 or channels 9 16 Connecting more than 8 analog inputs requires 2 PCB s with one s set for channels 1 8 and the other set for channels 9 16 For a 3 wire transmitter detector the power wire from the transmitter is connected to the EXC terminal on the SafeGuard Analog Input Board the power wire is connected to LO terminal on the SafeGuard Analog Input Board and the 4 20mA signal wire is connected to HI terminal on the SafeGuard Analog Input Board For a 2 wire transmitter detector the power wire is connected to the EXC terminal on the SafeGuard Analog Input Board and the 4 20mA signal wire is connected to HI terminal on the SafeGuard Analog Input Board See Figure 3 3 24 SafeGuard Controller User Manual
62. tion Disabled Figure 2 15 2 4 AUTHORIZATION MODE A password entered in the AUTHORIZATION menu allows locking all menus Viewing menus is not denied but attempts to edit variables flashes the Locked message on the LCD Authorized individuals locking the system should first enter a name phone or other contact information into the 10 digit field To lock or unlock the system the correct 4 digit authorization number must be entered into the Enter Code field Point to the Unlock System menu entry and press EDIT to complete the unlock procedure It is very important to record the 4 digit code However if lost it may be displayed briefly at power up using the following procedure Remove power from the SafeGuard Controller Reapply power and as the alarm LED s begin scrolling down hold the following keys simultaneously UP DOWN NEXT amp EDIT Watch closely The 4 digit authorization code appears briefly at bottom left of the screen IMPORTANT DO NOT hold the keys before applying power since this causes a cold boot and returns all settings back to factory defaults Authorization ENTER NAME Enter Code Figure 2 16 2 5 LCD CONTRAST ADJUSTMENT The Setup menu item identified as CONTRAST allows users to adjust the LCD contrast to a level suitable to the ambient lighting Selecting CONTRAST and pressing EDIT causes the UP DOWN keys to increase and decrease LCD contrast 20 SafeGuard Controller User
63. trument NEMA 4X wall mount models should be fitted with a locking mechanism after installation to prevent access to high voltages by unauthorized personnel see Figure 6 2 Only the combustible monitor portions of this instrument have been assessed by CSA for C22 2 No 152 performance requirements This equipment is suitable for use in Class I Division 2 Groups A B C and D or non hazardous locations only WARNING EXPLOSION HAZARD SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS I DIVISION 2 WARNING EXPLOSION HAZARD DO NOT REPLACE FUSE UNLESS POWER HAS BEEN SWITCHED OFF OR THE AREA IS KNOWN TO BE NON HAZARDOUS WARNING EXPLOSION HAZARD DO NOT DISCONNECT EQUIPMENT UNLESS POWER HAS BEEN SWITCHED OFF OR THE AREA IS KNOWN TO BE NON HAZARDOUS Use a properly rated CERTIFIED AC power mains cable installed as per local or national codes A Certified AC power mains disconnect or circuit breaker should be mounted near the SafeGuard Controller and installed following applicable local and national codes switch is used instead of a circuit breaker a properly rate CERTIFIED fuse or current limiter is required to installed as per local or national codes Markings for positions of the switch or breaker should state I for on and O for off Clean only with a damp cloth without solvents SafeGuard Controller User Manual 0115 Rev 0 Equipment not used as prescribed within this manual may impair overall safety
64. uld be noted that the current output from the SafeGuard Analog Output Board will be 1 5 mA when the device is in calibration mode The CALIBRATION MENU allows entering the correct Cal ZERO amp Cal SPAN set point values needed to calibrate the sensor These are entered in the same engineering units as input range Set Zero amp Set Span controls in this menu allow pushbutton calibration by moving the pointer to each and pressing the EDIT key A live reading of the channel s value allows calibration checks to see if an adjustment is needed Unintentional calibrations are reset by the Unity Gain menu item Unity Gain resets zero offset to 0 and span gain to 1 It is useful for returning the calibration to a known starting place Sensor aging may be monitored by recording zero and span readings at Unity Gain when it is new and again at later dates when degradation may have occurred To check zero calibration apply the ZERO calibration value to the sensor and observe the live reading If the zero reading differs from the zero setpoint a calibration is needed To calibrate zero move the pointer to Set Zero and press EDIT A warning message explains that pressing EDIT again will change the zero calibration and any other key will exit The procedure for span calibration is identical For example if an LEL combustible sensor is to be spanned with 50 LEL span gas the span set point must be 50 If 45 LEL is to be used later the span set point must b
65. wire lengths are very short less than 25 feet or if the port is not at the end of the communication line An Auxiliary Relays piggyback PCB may be added to the I O PCB via ribbon cable J4 These add another form C contact set to the common A1 A2 and HORN alarms Auxiliary Relay contacts are available at the TB1 AUX terminals shown in Figure 3 1 21 SafeGuard Controller User Manual MAN 0115 Rev 0 J1 is 26 pin ribbon to 52 MAIN I O BOARD main controller eee ALARM ES SPARE RESET TB3 allows external 2 ao Alarm Reset contacts Spare shorting strips J4 COMM 2 92 Ribbon connector to 6A s TX1 RX1ITX2 RX2 J2 amp J3 connect to optional Auxilliary VN Saco ie 12C optional I O Common Relay PCB I AUX RELAY BOARD OPTIONAL 0 JJ U2 U4 Fuses DC OUT power to option boards that v require 24 VDC U3 US TB1 AUX RELAYS OPTION 10 0144 i Install horizontal shorting strips 1A1 NO 2 Aux Relay piggy z in JP1 for 2 wire RS 485 operation 3A1 COM 4 back Board shown 4 e 40 43 JP oo 5 6 in dotted lines LLL LL I RS 485 terminating res

Download Pdf Manuals

image

Related Search

Related Contents

取扱説明書  Manual, Nimbie NB11  Installation Guide - GS Global Resources  PDF (156.6 kibibytes)  TDSHーBA 保  Cantinero Electrónico  ソリューション総合カタログ  PAWAN HANS HELICOPTER LIMITED  Emerson 92W Drawings & Schematics  

Copyright © All rights reserved.
Failed to retrieve file