1. NOTE The 200mm and 300mm maintenance bypass cabinets ship attached to the UPS The 600mm and 800mm maintenance bypass cabinets ship separately from the UPS 7 Liebert eXM MBC Mechanical Installation 1 6 1 Power Cable Connection Procedure The system input UPS bypass UPS output and system output cables all require lug type terminations are connected to power blocks behind the power isolator switches as shown in 2 0 Installation Drawings These are accessible when the side or top panel is removed Equipment Ground The equipment ground busbar is near the input and output power supply connections as shown in 2 0 Installation Drawings The grounding conductor must be connected to the ground busbar cabinets and cable trunking should be grounded in accordance with local regulations WARNING Risk of electric shock cause equipment damage injury and death Failure to follow adequate grounding procedures can result in electric shock hazard to personnel and the risk of fire should a ground fault occur A AVERTISSEMENT Risque de d charge lectrique pouvant entra ner des dommages mat riels des blessures et m me la mort Le non respect des proc dures de mise la terre peut entra ner des risques d lectrocution du personnel ou des risques d incendie en cas de d fectuosit de la mise la
2. Neutral Busbar RIB BIB MIB MBB Terminal Strip FRONT VIEW RIGHT SIDE VIEW with Door Removed with Panel Removed EXM15105 Liebert eXM 16 Installation Drawings Figure 11 Outline drawing 200mm Liebert eXM MBC two to four breakers 10 40kVA system Conduit Landing Ventilation TOP VIEW BOTTOM VIEW 8 2 39 1 993mm 208mm 7 8 200mm i Leveler DETAIL A NOTES 1 All dimensions are in inches mm 2 24 610 minimum clearance above unit and 36 914 front access required for service 3 Keep cabinet within 15 degrees of vertical 4 Top and bottom cable entry available through removable access plates Remove punch to suit conduit size and replace Unit bottom is structurally adequate for forklift handling Control wiring and power wring must be in separate conduits 7 All wiring is to be in accordance with national and local electrical codes FRONT VIEW RIGHT SIDE VIEW 17 Liebert eXM Installation Drawings Figure 12 Outline drawing 300mm Liebert eXM two to four breakers 60 100 system Conduit Landing Ventilation TOP VIEW 12 1 11 8 308mm 300 FRONT VIEW 8 6 218 Conduit Landing BOTTOM VIEW 39 1 993mm NOTES 1 All dimensions are in inc
3. cs cs Liebert eXM 12 Installation Drawings Figure 6 Main components 200mm Liebert eXM MBC two to four breakers 10 40kVA system TB2 TB4 Dual Input Systems 7 9 200mm RIB 37 5 953mm BIB 788 2001 Neutral Busbar Ground Busbar LEFT SIDE RIGHT SIDE Panel Removed Door Removed Panel Removed Table 2 configuration 200mm Liebert two to four breakers 10 40kVA system Liebert eXM MBC Breaker Configuration Configured Breaker TE 3 BIB MBB MIB 4 RIB BIB MBB MIB Table 3 Terminal block details 200mm Liebert eXM MBC two to four breakers 10 40kVA system Terminal Single Input Dual Input Block System System TB2 Input Bypass TB3 Output Output TB4 Rectifier 13 Liebert eXM Installation Drawings Figure 7 LEFT SIDE VIEW Panel Removed Table 4 TB4 Dual Input Systems 1994mm system Ground Busbar a al al isl 3 a al ql a ql a a a B al a RIGHT SIDE VIEW Panel Removed Breaker configuration 300mm Liebert eXM MBC two to four breakers 60 100kVA Liebert eXM MBC Breaker Configuration Configured Breaker 2 3 BIB MBB MIB 4 RIB BIB MBB MIB Table 5 system Terminal Si
4. VV06 C 4 tr 2x Output q 11 cory MIB 4 som Kirk lt gt ec See Note 7 plie 4 Key K1 mi __ W89 _ __ a A j ac o W90 705 Ju F 1 TM O 1 Utility PIER Output Fuses 2 555 Ground NE s 1 IU 1 E PAS Ground to 518 288 Unit Frame aM sn M Y RIB 8 8 Phil HH SKRU 1 nput 1 1 III ui Ar Optional LIE See Note 9 1 3 4 5 6 7 8 95 10 2 1 h 1 E Input i 1 5 Main Ground Busbar Lamp pen 2299 et 120V Field Supplied Wiring See Note 1 lt a Door Factory Supplied Wiring Ground to Unit Frame 1 SKRU Solenoid Unit DETAIL 1 Customer furnished electrode conductor to be installed in accordance X9J2 With national and local electrical codes 2 See installation manual for additional connection information MFP O1 ur 77777 7 7 3 Overcurrent protection is based on 80 rated devices S310O 4 MBB auxiliary switch connections are on the normally closed and common positions 510 5 MIB auxiliary switch connections are on the normally opened and common positions 6 MBC when c
5. block torque with compression lugs for control wiring NOTE Refer to the manufacturer s data for proper torque for circuit breaker power connections Liebert eXM 38 Specifications NOTES 39 Liebert eXM Specifications Liebert eXM MBC 40 While every precaution has been taken to ensure the and completeness of this literature Liebert Corporation assumes responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions 2014 Liebert Corporation All rights reserved throughout the world Specifications subject to change without notice Liebert is a registered trademark of Liebert Corporation All names referred to are trademarks or registered trademarks of their respective owners SL 25652_REV1_06 15 Emerson Network Power Liebert www emerson com Technical Support Service Web Site www liebert com Monitoring liebert monitoring emerson com 800 222 5877 Outside North America 00800 1155 4499 Single Phase UPS amp Server Cabinets liebert upstech emerson com 800 222 5877 Outside North America 00800 1155 4499 Three Phase UPS amp Power Systems 800 543 2378 Outside North America 614 841 6598 Environmental Systems 800 543 2778 Outside the United States 614 888 0246 Locations United States 1050 Dearborn Drive P O Box 29186 Columbus OH 43229
6. gt On m mm m gt Bypass Output AC Output AC Input MIB Busbar 208V 220V 4 Wire GND Q 4 Wire GND cy Rectifier 1 Input 4 Wire GND 1 1 1 1 1 1 1 BATTERY C 1 1 NOTES 1 Install in accordance with national and local electrical codes RIB Rectifier Input Breaker 2 Input and bypass must share the same single source BIB Bypass Isolation Breaker 3 neutral is required from the system AC input source MBB Maintenance Bypass Breaker A full capacity neutral conductor is recommended Grounding MIB Maintenance Isolation Breaker conductors are recommended External Overcurrent Protection by Others 4 Bypass and rectifier inputs and output cables must be Field Supplied Wiring Figure 5 Bend radius Neutral and ground wires through bottom feed 10 40kVA system When attaching neutral and ground wires from the bottom feed connection must be made to the top of the neutral and ground busbar for required bend radius 000 0 Busbar o000000000e0000006 00 0000000000000000Q 00000000 o Po 5 o Sieg o o o M P Le 5 o 5 8 Ground 8 6 9 NS o o
7. Mets bee ts 34 3 2 Torque Requirements suisse da ease need rue ee honte ute e CRT 38 Figure 1 Figure 2 Figure 3 Figure 4 Figure 5 Figure 6 Figure 7 Figure 8 Figure 9 Figure 10 Figure 11 Figure 12 Figure 13 Figure 14 Figure 15 Figure 16 Figure 17 Figure 18 Figure 19 Figure 20 Figure 21 Figure 22 Figure 23 Figure 24 Figure 25 Figure 26 FIGURES Cabinet arrangement Liebert eXM UPS battery cabinets maintenance bypass cabinet 7 One line diagram dual input two breaker Liebert 10 200kVA system 10 One line diagram single input three breaker Liebert MBC 10 200kVA 11 One line diagram dual input four breaker Liebert MBC 10 200kVA 12 Bend radius Neutral and ground wires through bottom feed 10 40 system 12 Main components 200mm Liebert eXM MBC two to four breakers 10 40kVA system 13 Main components 300mm Liebert eXM MBC two to four breakers 60 100kVA system 14 Main components 600mm Liebert eXM MBC three to four breakers 120 160kVA system 15 Main components 600mm Liebert eXM MBC two breakers 120 200kVA system 15 Main components 800mm Liebert eXM MBC three or four breakers 160 200kVA system 16 Outline drawing 200mm Liebert eXM MBC two to four breakers 10 40kVA system 17 Outline drawing 300mm Liebert eXM MBC two to four breakers
8. The Liebert eXM MBC s weight ranges from 198 to 700 lb 89 9 to 317 5 kg Locate center of gravity symbols 4 and determine unit weight before handling each cabinet Test lift and balance the cabinets before transporting Maintain minimum tilt from vertical at all times Slots at the base of the cabinets are intended for forklift use Base slots will support the unit only if the forks are completely beneath the unit In case of fire involving electrical equipment use only carbon dioxide fire extinguishers or those approved for use in fighting electrical fires Extreme caution is required when performing maintenance Be constantly aware that the system contains high DC as well as AC voltages Check for voltage with both AC and DC voltmeters prior to making contact AVERTISSEMENT Le centre de gravit lev des appareils pr sente un risque de renversement lors des d placements pouvant entra ner des dommages mat riels des blessures et m me la mort Faites preuve d une extr me prudence lors de la manutention des armoires afin d viter de les endommager ou de blesser le personnel Les armoires de d rivation d entretien eXM de Liebert p sent de 198 700 Ib de 89 9 317 5 kg Identifiez les symboles de centre de gravit et d terminez le poids de l appareil avant de manipuler chaque armoire Testez le levage et l quilibre des armoires avant de transporter l appareil Maintenez en tout temps l inclinaison verticale
9. Figure 15 Terminal details 200mm Liebert eXM MBC two to four breakers 10 40kVA system Conduit Landing NOTES 1 All dimensions are in inches mm 2 Control wiring and power wiring must Conduit den be run in separate conduits Landing 3 All wiring is to be in accordance with national and local electrical codes 4 If the maintenance bypass cabinet is attached to the UPS Emerson will supply the interconnection cables RIB BIB MBB MIB TB3 Neutral Busbar Ground Busbar LEFT SIDE VIEW FRONT VIEW RIGHT SIDE VIEW Panel Removed Door Removed Panel Removed Table 6 Breaker configuration 200mm Liebert eXM two to four breakers 10 40kVA system Liebert eXM MBC Breaker Configuration Configured Breaker 2 MBB MIB 3 BIB MBB MIB 4 RIB BIB MBB MIB Table 7 Terminal block details 200mm Liebert eXM MBC two to four breakers 10 40kVA system Terminal Single Input Dual Input Block System System TB2 Input Bypass TB3 Output Output TB4 Rectifier 21 Liebert eXM Installation Drawings Figure 16 Terminal details 300mmLiebert eXM two to four breakers 60 100kVA system Conduit Landing NOTES 1 All dimensions are in inches mm 2 Control wiring and power wiring must be run in separate conduits 3 All wiring is to be in accordance with national and local electrical codes 4 If the maintenance bypass cabinet is at
10. Liebert eXM 24 Installation Drawings Figure 19 Terminal details 600mm Liebert eXM four breakers 120 160kVA system Bypass Input See DETAIL A Bypass Input See DETAIL A Hl n n B n n n n n n y Neutral Busbar BL ele 515 ele 51578 See DETAIL B k 1 he RIB _ INE See DETAIL B cr See DETAIL lt 1593mm MIB See DETAIL B Ground Busbar See DETAIL A Output See DETAIL LI CCE F Bt LEFT SIDE VIEW FRONT VIEW RIGHT SIDE VIEW with Panel Removed with Door Removed with Panel Removed 20 56 2 7 1 75 44mm 20 56 14mm 69mm Typical 14mm 1 75 0 59 44 1 75 15mm 44mm 90 44 0 55 11mm 14mm DETAILA DETAIL B Neutral Busbar Phase Busbar Connections Notes 1 Control wiring and power wiring must be run in separate conduits EXM16105 2 All wiring is to be in accordance with national and local electrical codes Rev 1 3 If the Liebert eXM MBC is attached to the UPS Emerson will supply the interconnection cables 25 Liebert eXM Installation Drawings Figure 20 Terminal details 800mm Liebert eXM three breakers 160 200 system Notes 1 All dimensions are in inches mm 2 Control wiring and power wiring must be run in separate conduits 3
11. minimale Les fentes situ es la base des armoires sont con ues pour utiliser le chariot l vateur Les fentes situ es la base peuvent soutenir le syst me seulement si les fourches se trouvent compl tement sous le syst me En cas d incendie associ du mat riel lectrique n utilisez que des extincteurs dioxyde de carbone ou homologu s pour la lutte contre les incendies d origine lectrique Les op rations d entretien requi rent une extr me prudence Soyez toujours conscient du fait que le syst me contient des tensions c c et c a lev es V rifiez les tensions avec des voltm tres c a et c c avant d tablir tout contact 1 Liebert eXM Important Safety Instructions Read this manual thoroughly before working with the Maintenance Bypass Cabinet Retain this manual for use by installing personnel WARNING Risk of arc flash and electric shock Can cause equipment damage injury and death Under typical operation and with all doors closed only normal safety precautions are necessary The area around the system should be kept free of puddles of water excess moisture and debris Special safety precautions are required for procedures involving handling installation and maintenance of the Maintenance Bypass Cabinet Observe all safety precautions in this manual before handling or installing the Maintenance Bypass Cabinet Observe all precautions in the Operation and Maintenance Manual befo
12. toute intervention sur une pi ce d quipement sous tension Les responsables de l entretien doivent porter des chaussures isolantes pour pr venir tout contact direct avec le plancher Une personne ne devrait jamais travailler seule m me si toute l alimentation de l quipement est coup e Une deuxi me personne devrait toujours tre pr sente pour porter assistance ou chercher de l aide en cas d accident Liebert 2 Mechanical Installation 1 0 MECHANICAL INSTALLATION 1 1 1 2 Introduction This section describes the requirements that must be taken into account when planning the positioning and cabling of the Liebert eXM MBC This chapter is a guide to general procedures and practices that should be observed by the installing engineer The particular conditions of each site will determine the applicability of such procedures WARNING Risk of arc flash and electric shock Can cause equipment damage injury and death Installation must be performed only by properly trained and qualified personnel wearing appropriate safety clothing Eye protection should be worn to prevent injury from accidental electrical arcs Remove rings watches and all other metal objects Only use tools with insulated handles Wear rubber gloves AVERTISSEMENT Risque d arc ou de d charge lectrique pouvant entra ner des dommages mat riels des blessures et m me la mort L installation ne doit tre c
13. 000 x 2000 UPS with 300mm 35 1 2 x 39 1 2 x 78 3 4 900 x 1000 x 2000 Table 12 Weights Liebert eXM UPS 10 40kVA and 200mm Liebert eXM Liebert eXM Combined Weight UPS Weight MBC 200mm UPS and Liebert UPS Rating kVA Ib kg Weight Ib kg eXM MBC Ib kg 10 604 274 198 90 802 364 15 604 274 198 90 802 364 20 604 274 198 90 802 364 30 678 308 198 90 876 397 40 678 308 198 90 876 397 Table 13 Weights Liebert eXM UPS 60 100kVA and 300mm Liebert eXM MBC Liebert eXM Combined Weight UPS Weight MBC 300mm UPS and Liebert UPS Rating kVA kg Weight Ib kg eXM MBC Ib kg 60kVA 807 308 288 131 1095 497 80kVA 881 400 288 131 1169 530 100kVA 955 433 288 131 1243 564 Table 14 Additional weight for Liebert eXM 10 40kVA UPS with internal batteries Battery Added Battery Battery Model Code Weight Ib kg 12HX100 FR F 528 240 12HX150 FR H 768 468 12HX205 FR M 1032 468 HR1500 G 576 261 HR2000 L 924 419 For total system weight add the weight for the UPS Liebert eXM MBC and the Liebert eXM 10 40kVA UPS internal batteries 33 Liebert eXM Specifications 3 1 Electrical Characteristics The breakers and cables used must be in accordance with ANSI NFPA 70 A disconnect breaker must be provided for AC input Bypass
14. 2 20027 20 68 90 3W N G 115 1 2 1 1 0 30 102 150 3W N G 175 1 2 0 1 4 0 M10 220427 40 196 175 3W N G 230 1 4 0 21 0 220427 60 208 300 3W N G 400 2 3 0 24 0 M10 220427 80 ane 350 3W N G 460 2 4 0 2 300 M10 320 127 100 450 3W N G 610 2 350 2 400 M10 22127 120 209 600 3W N G 760 2 500 3 350 M12 220427 140 478 600 3W N G 760 2 500 3 350 M12 220127 160 700 3W N G 930 3 350 3 500 M12 220127 180 ae 800 3W N G 1140 3 500 4400 M12 te 200 682 1000 3W N G 1240 4 350 4 500 M12 35 Liebert eXM Specifications Table 17 Liebert eXM input currents dual input bypass Bypass Bypass Input Current Recommended 75 C Wire Voltage Rating BIB MBB Upstream Current Copper Aluminum Bolt 3 Ph 60 2 Protection Wire Wire Size 220427 10 28 40 3W N G 50 1 6 1 4 220127 15 42 60 3W N G 85 1 4 1 2 M10 220127 20 3 70 3W N G 115 1 2 1 2 220127 30 E 110 3W N G 130 1 1 0 1 20 40 111 150 3W N G 175 1 3 0 1 4 0 M10 52027 60 187 225 3W N G 285 2 300 2 20 ce 80 222 300 3W N G 400 2 3 0 2 4 0 M10 25015 100 278 350 3W N G 460 2 4 0 2 300 M10 220127 120 333 450 3W N G 620 2 350 2 500 M12 220127 140 393 500 3W N G 620 2 3
15. 50 2 500 M12 160 444 600 760 2 500 3 350 12 220127 180 899 700 3W N G 930 3 350 3 500 M12 220127 200 999 700 3W N G 930 3 350 3 500 M12 Liebert eXM 36 Specifications Table 18 Liebert eXM MBC output currents System 75 C Output Recommended Wire Voltage MBC Current Upstream Current Copper Aluminum Bolt 3 Ph 60Hz Rating kVA A Max Phase Protection A A Total Wire Wire Size 208 120 220 127 10 28 3W N G 40 50 1 6 1 4 M10 208 120 220 127 15 42 3W N G 60 85 1 4 1 2 M10 208 120 220 127 20 56 3W N G 70 115 1 2 1 2 M10 208 120 220 127 30 83 3W N G 110 130 1 1 0 1 2 0 M10 208 120 220 127 40 111 3W N G 150 175 1 3 0 1 4 0 M10 208 120 3 220 127 60 167 3W N G 225 285 2 300kcmil 2 2 0 M10 208 120 220 127 80 222 3W N G 300 400 2 3 0 2 4 0 M10 208 120 220 127 100 278 3W N G 350 460 2 4 0 2 300kcmil M10 208 120 220 127 120 333 3W N G 450 620 2 350 2 500 M12 208 120 220 127 140 389 3W N G 500 620 2 350 2 500 M12 208 120 220 127 160 444 3W N G 600 760 2 500 3 350 M12 208 120 220 127 180 500 3W N G 700 930 3 350 3 500 M12 208 120 220 127 200 555 3W N G 700 930 3 350 3 500 M12 Table 19 Recommended lug sizes compression type M10 3 8 bolt T amp B Copper T amp B A
16. 60 100kVA system 18 Outline drawing 600mm Liebert eXM MBC 120 200kVA system 19 Outline drawing 800mm Liebert eXM MBC 160 200kVA system 20 Terminal details 200mm Liebert eXM two to four breakers 10 40kVA system 21 Terminal details 300mmLiebert eXM two to four breakers 60 100kVA system 22 Terminal details 600mm Liebert eXM two breakers 120 200kVA system 23 Terminal details 600mm Liebert eXM MBC three breakers 120 160kVA system 24 Terminal details 600mm Liebert MBC four breakers 120 160kVA system 25 Terminal details 800mm Liebert eXM MBC three breakers 160 200kVA system 26 Terminal details 800mm Liebert eXM MBC four breakers 160 200kVA system 27 Control wiring diagram Liebert eXM MBC two to four breakers with interlock 28 Solenoid key release unit 200mm Liebert eXM MBC 29 Solenoid key release unit 300mm Liebert eXM MBC 30 Solenoid key release unit 600mm Liebert eXM MBC 31 Solenoid key release unit 800mm Liebert eXM MBC 31 Table 1 Table 2 Table 3 Table 4 Table 5 Table 6 Table 7 Table 8 Table 9 Table 10 Table 11 Table 12 Table 13 Table 14 Table 15 Table 16 Table 17 Table 18 Table 19 Tabl
17. All wiring is to be in accordance with national and local electrical codes 4 If maintenance bypass cabinet is attached to UPS Liebert will supply the interconnection cables Bypass Input Busbar See DETAIL S Neutral B 3 33 5 B BIB m See DETAIL B MIB See DETAIL B MBB See DETAIL B Ground Busbar See DETAIL A Output Busbar See DETAIL A LEFT SIDE VIEW LEFT SIDE VIEW FRONT VIEW RIGHT SIDE VIEW with Panel Removed with Panel Removed with Door Removed with Panel Removed 200kVA Model Only 160 180kVA Models 20 56 1 75 44mm Typical 14mm 1 75 20 56 F 059 15mm SM 14mm n 20 44 1 75 1 17 41 44mm 43mm DETAIL Neutral Busbar EXM16107 DETAIL Phase Busbar Connections Rev 1 Liebert eXM 26 Installation Drawings Figure 21 Terminal details 800mm Liebert eXM MBC four breakers 160 200kVA system Notes 1 All dimensions are in inches mm 2 Control wiring and power wiring must be run in separate conduits 3 All wiring is to be in accordance with national and local electrical codes 4 If maintenance bypass cabinet is attached to UPS Liebert will supply the interconnection cables BP Input Busbar See DETAIL A Main Input Busbar See DETAIL A Neutral
18. Busbar RIB LB BIB See DETAIL B MBB See DETAIL B MIB LB See DETA See DETA Ground Busbar LEFT SIDE VIEW with Panel Removed LEFT SIDE VIEW with Panel Removed See DETAIL A 4847 Output Busbar 493mm See DETAIL FRONT VIEW with Door Removed RIGHT SIDE VIEW with Panel Removed 200 Model Only 160 180kVA Models 20 56 20 56 1 75 44mm 14 0 59 Typical Tamim p imm FRE I 15mm 1 75 9 9 85 44mm T 20 44 0 55 43mm 11mm DETAIL B EXM16108 Neutral Busbar DETAIL A Phase Busbar Connections Rev 1 27 Liebert eXM Installation Drawings Figure 22 Control wiring diagram Liebert eXM two to four breakers with interlock Output Neutral Customer Feed MBB See Note 6 QA 5 5 WAL A NEN 28255 WOS
19. EW RIGHT SIDE VIEW with Panel Removed with Door Removed with Panel Removed EXM16013 Rev 1 1 75 44 20 96 Typical 14mm 4 75 0 59 15mm TRI 20 44 11mm o 0 DETAIL 14 14mm DETAILA Phase Busbar Connections Neutral Busbar 23 Liebert eXM Installation Drawings Figure 18 Terminal details 600mm Liebert eXM three breakers 120 160 system Notes 1 All dimensions are in inches mm 2 Control wiring and power wiring must be run in separate conduits 3 wiring is to be in accordance with national and local electrical codes 4 If maintenance bypass cabinet is attached to UPS Liebert will supply the interconnection cables Bypass Input See DETAIL A Neutral Busbar BIB See DETAIL B MBB See DETAIL B ELI 62 7 MIB Ground Busbar d See DETAIL B Output 1 See DETAIL 3 B 58 LEFT SIDE VIEW FRONT VIEW RIGHT SIDE VIEW with Panel Removed with Door Removed with Panel Removed EXM16104 Rev 1 20 56 S 2 7 1 75 44mm 14mm 20 56 69mm Typical 1 75 1 Ju 14mm 0 59 15mm 1 7 20 44 44mm Camm o0 O O 55 DETAIL B 14 DETAILA Phase Busbar Connections Neutral Busbar
20. Europe Via Leonardo Da Vinci 8 Zona Industriale Tognana 35028 Piove Di Sacco PD Italy 39 049 9719111 39 049 5841 257 Asia 29 F The Orient Square Building Ortigas r Road Ortigas Center Pasig City 1605 Philippines 63 2687 6615 Fax 63 2 730 9572
21. Liebert eXM User Manual 10 200kVA 60Hz EMERSON Network Power 5 IMPORTANT SAFETY INSTRUCTIONS 00000 cece ee eee eee eee eee ees 1 SAVE THESE INSTRUCTIONS 1 1 0 MECHANICAL INSTALLATION 43 239 vo woe dcn ee eee 3 1 1 Introduction PaL eve ui EN hs S S I A OR a 3 1 2 Preliminary Checks 2004 44 ne ent eq SA a a 3 1 3 Environmental Considerations pe RR Fac e baad 4 Teen ROOM i ERE Dette e eoa ar exe SET DR Lap oat ROS 4 etre Et reb EU d sore dot eer Pet ted A doe Pati 4 1 4 Positionmeg ion 8 LC e OT V rd 4 14 1 Movmegth Cabinets ee tlc a oss ro dec E rare 4 14 2 Clearances 1 wacked ate br boe dob ace ARR USO 5 1 4 8 Floor Installation Anchoring 5 1 5 Cable Entr D armee ns A rt 5 1 6 Power Cables eus aXe ue op Ine cede OR ea a a etae eae date 6 1 6 1 Power Cable Connection Procedure 8 2 0 INSTALLATION DRAWINGS eee Re este Aa ee eed 10 3 0 SPECIFICATIONS ie eee ee ina cc e a 32 3 1 Electrical Characteristics cs zz shui
22. Liebert eXM MBC s weight ranges from 198 to 700 lb 89 8 to 317 5 kg Locate center of gravity symbols 45 and determine unit weight before handling each cabinet Test lift and balance the cabinets before transporting Maintain minimum tilt from vertical at all times Liebert 4 Mechanical Installation 1 4 2 1 4 3 1 5 AVERTISSEMENT Le centre de gravit lev des appareils pr sente un risque de renversement lors des d placements pouvant entra ner des dommages mat riels des blessures et m me la mort Faites preuve d une extr me prudence lors de la manutention des armoires afin d viter de les endommager ou de blesser le personnel Les armoires de d rivation d entretien eXM de Liebert p sent de 198 700 Ib de 89 8 317 5 kg Identifiez les symboles de centre de gravit et d terminez le poids de l appareil avant de manipuler chaque armoire Testez le levage et l quilibre des armoires avant de transporter l appareil Maintenez en tout temps l inclinaison verticale minimale Clearances Liebert eXM have no ventilation grilles at either side or at the rear Clearance around the front of the equipment should be sufficient to enable free passage of personnel with the doors fully opened It is important to leave a distance of 24 610mm between the top of the cabinet and any overhead obstacles to permit adequate circulation of air coming out of the unit Floor Installation Ancho
23. Liebert eXM UPS with Liebert eXM MBC Weights Liebert eXM UPS 10 40kVA and 200mm Liebert eXM Weights Liebert eXM UPS 60 100kVA and 300mm Liebert eXM Additional weight for Liebert eXM 10 40kVA UPS with internal batteries Liebert eXM MBC input currents single input Main Liebert eXM MBC input currents dual input rectifier Liebert eXM MBC input currents dual input bypass Liebert eXM MBC output currents Recommended lug sizes compression type M10 3 8 bolt Recommended lug sizes Compression Type M12 1 2 bolt Busbar torque for power wiring Terminal block torque with compression lugs for control wiring iii Important Safety Instructions IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions that should be followed during installation of your Liebert eXM Maintenance Bypass Cabinet WARNING Risk of moving heavy units and tipping hazard Can cause equipment damage injury and death Exercise extreme care when handling cabinets to avoid equipment damage or injury to personnel
24. M Mechanical Installation 1 3 1 3 1 1 3 2 1 4 1 4 1 Environmental Considerations Room The Liebert is intended for indoor installation and should be located in a cool dry clean air environment with adequate ventilation to keep the ambient temperature within the specified operating range see 3 0 Specifications models of the Liebert MBC are convection cooled To permit air to enter and exit and prevent overheating or malfunctioning do not cover the ventilation openings When bottom entry is used the conduit plate can be removed and punched and replaced The bottom conduit plate must be replaced for proper airflow If necessary to cool the room install a system of room extractor fans The Liebert eXM is suitable for mounting only concrete and other noncombustible surfaces Storage Should the equipment not be installed immediately it must be stored in a room for protection against excessive humidity and or heat sources see Table 10 Positioning The cabinet is structurally designed to handle lifting from the base Access to the power terminals auxiliary terminals blocks and power switches is from the top and sides The top and side removable panels are secured to the chassis by screws The side panel can be removed for access to the power connections bars auxiliary terminal blocks and power isolators Moving the Cabinets The route to be travel
25. W 10 40 60 100 120 140 160 200 Output Voltage VAC 208 120V or 220 127V 3 Phase 4 Wire Output Current AAC Refer to Table 18 Output Frequency Hz 60 Physical Parameters and Standards in mm Sue ee 8 2 208 12 0 308 23 9 608 31 8 808 Depth 39 4 1000 Height 78 74 2000 Weight Ib kg 198 89 9 288 130 6 535 242 7 700 317 5 Color Black ZP 7021 Degree of Protection for UPS Enclosure IP 20 with and without front door open Standards and Conformities UL1778 5th Edition CSA 22 2 107 3 14 ISTA Procedure 1H WEEE Minimum Clearance Top in mm 24 610 Minimum Clearance Back in mm 0 Minimum Clearance Sides in mm 0 Cable Entrance Top or Bottom Environmental Parameters Storage Temperature Range F C 13 to 158 25 to 70 Operating Temperature Range F 0 to 40 UPS Relative Humidity Maximum 95 Non Condensing Operating and Non Operating Maximum Altitude above MSL ft Refer to UPS Manual SL 25648 or SL 26100 Liebert eXM 32 Specifications Table 11 Dimensions for Liebert eXM UPS with Liebert eXM MBC UPS Rating kVA 10 40 60 100 Components Dimensions WxDxH mm UPS Only 23 5 8 x 39 1 2 x 78 3 4 23 5 8 x 39 1 2 x 78 3 4 600 x 1000 x 2000 600 x 1000 x 2000 UPS with 200mm MBC 31 1 2 x 39 1 2 x 78 3 4 800 x 1
26. and AC output Recommended cable sizes are suitable for operation at a maximum temperature of 104 F 40 C Table 15 Liebert eXM MBC input currents single input main System 75 C MBC Input Recommended Wire Voltage Rating Current Upstream Current Copper Aluminum Bolt 3 Ph 60 Hz kVA A Max Phase Protection A A Total Wire Wire Size 220 127 10 34 SW N G 45 65 1 6 1 4 M10 220127 75 2 70 65 1 4 1 2 220127 20 68 TON ENS 90 115 1 2 11 0 30 102 3W N G 150 175 1 2 0 1 4 0 M10 40 136 3W N G 175 230 1 4 0 2 1 0 M10 208 120 205 3W N G 300 400 2 3 0 2 40 60 273 3W N G 350 460 2 4 0 2 300 M10 22017 100 341 3W N G 450 610 2 350 2 400 M10 220027 120 409 3W N G 600 760 2 500 3 350 M12 250077 140 478 3W N G 600 760 2 500 3 350 M12 208 120 160 546 3W N G 700 930 3 350 3 500 M12 bee 200 682 3W N G 1000 1240 4 350 4 500 M12 Liebert eXM 34 Specifications Table 16 Liebert eXM input currents dual input rectifier Rectifier Voltage MBC Rectifier Recommended 75 C Wire 3 Phase Rating Input Current Upstream Current Copper Aluminum Bolt 60 2 RIB A Max Protection A Phase A Total Wire Wire Size 52027 10 43 3W N G 65 1 6 1 4 520127 18 sl 70 3W N G 85 1 3 1
27. e 20 Table 21 Table 22 TABLES Control wiring for Liebert eXM UPS to Liebert eXM MBC Breaker configuration 200mm Liebert eXM MBC two to four breakers 10 40kVA System Sake A Rosi ee ge eR EE Terminal block details 200mm Liebert eXM MBC two to four breakers 10 40kVA SYS et Breaker configuration 300mm Liebert two to four breakers 60 100kVA SV SUC v oie S 2 ES aute Sept ks te EO DE Terminal block details 300mm Liebert eXM two to four breakers 60 100kVA SySLOT tpe Ar NEA ere Aet Sai ERO Bed ete uf Breaker configuration 200mm Liebert eXM MBC two to four breakers 10 40kVA System voten Skeets 1 pet SORS ales gre der OR Roepe nent te pt Terminal block details 200mm Liebert eXM MBC two to four breakers 10 40kVA Sy STE MaA a IRA See eR Bette eee Rat Breaker configuration 300mm Liebert eXM MBC two to four breakers 60 100kVA SYSTEM s A od Marieke ure varese ENTE ha wa ed Terminal block details 300mm Liebert eXM two to four breakers 60 100 SySLem es ens gr nee eau V Meta OO heehee dusted Liebert eXM MBC specifications Dimensions for
28. eau d humidit excessive et de d bris Des pr cautions de s curit sp ciales sont requises pour les proc dures associ es la manutention l installation et l entretien de l armoire de d rivation d entretien Observez toutes les pr cautions de s curit d crites dans le pr sent manuel avant de manipuler ou d installer l armoire de d rivation d entretien Observez galement toutes les pr cautions d crites dans le manuel d utilisation et d entretien avant et pendant toutes les proc dures d entretien Cet quipement comporte des circuits haute tension Seuls des quipements d essai con us pour le d pannage doivent tre utilis s Cette mise en garde couvre notamment les oscilloscopes Utilisez toujours un voltm tre c a et c c pour v rifier les tensions avant d tablir un contact ou d utiliser des appareils Des tensions dangereusement lev es peuvent demeurer dans le syst me m me une fois l alimentation coup e Tous les c bles d alimentation et de contr le doivent tre install s par un lectricien qualifi Tous les c bles d alimentation et de contr le doivent tre conformes au Code national de l lectricit des Etats Unis NEC et ainsi qu aux codes locaux en vigueur L entretien de l armoire de d rivation d entretien ne doit tre confi qu des professionnels qualifi s et d ment form s Les responsables de l entretien et l quipement d essai doivent reposer sur des tapis de caoutchouc lors de
29. ed Wiring run in separate conduits 5 Control wiring must be run in separate conduits 6 Customer must supply shunt trip on bypass breaker with 120V coil BIB Bypass Isolation Breaker MBB Maintenance Bypass Breaker MIB Maintenance Isolation Breaker External Overcurrent Protection by Others Liebert eXM 10 Installation Drawings Figure 3 One line diagram single input three breaker Liebert 10 200kVA MAINTENANCE BYPASS CABINET Bypass ened AC Output AC Input 80 1 208V or 220V 4 Wire GND 14 Wire GND EE Static Bypass UPS CABINET BATTERY d nm EGG zl NOTES 1 Install in accordance with national and local electrical codes Bypass Isolation Breaker 2 Input and bypass must share the same single source MBB Maintenance Bypass Breaker 3 A neutral is required from the system AC input source MIB Maintenance Isolation Breaker A full capacity neutral conductor is recommended Grounding External Overcurrent Protection by Others conductors are recommended Field Supplied Wiring 4 Bypass and rectifier inputs and output cables must be run in separate conduits 5 Control wiring must be run in separate conduits 11 Liebert eXM Installation Drawings Figure 4 One line diagram dual input four breaker Liebert 10 200kVA
30. electrically isolated and post any necessary warning signs to prevent their inadvertent operation 2 Remove the panels 3 Connect the ground and any necessary main bonding jumper to the equipment ground busbar NOTE The grounding and neutral bonding arrangement must be in accordance with local and national codes of practice Care must taken when routing power cables Ensure that the cables do not touch other busbars Liebert 8 Mechanical Installation 4 Connect the AC input supply cables between the power distribution panel and the Maintenance Bypass input supply busbars A B C or A B C N terminals and tighten the connections to the proper torque see Table 21 Ensure correct phase rotation 5 Connect the UPS Input For two breaker Liebert eXM MBC s i Ifthe system is a two input type connect the AC input supply cables between the Liebert and the UPS bypass input supply busbars A B C or A B C N terminals and between the power distribution panel and the UPS rectifier input supply busbars or terminals Tighten the connections to the proper torque Ensure correct phase rotation 11 Ifthe system is a single input type connect the AC input supply cables between the Liebert eXM MBC and the UPS bypass input supply busbars A B C or A B C N terminals and connect AC jumper connectors between UPS bypass input supply busbars and UPS recti
31. fier input supply busbars A B C terminals Tighten the connections to the proper torque see Table 21 Ensure correct phase rotation 6 Connect the system output power cables between the Liebert eXM MBC output A B C or A B C N terminals and the critical load and tighten the connections to the proper torque see Table 21 Ensure correct phase rotation 7 Connect the control wiring from the Liebert eXM MBC terminal block TB1 to the Liebert eXM UPS Bypass Module X9 J23 and J26 Tighten the connections to the proper torque see Table 21 8 Replace the panels Table 1 Control wiring for Liebert eXM UPS to Liebert eXM MBC From Liebert eXM UPS Bypass Module To Liebert eXM MBC X9 J23 and J26 Terminal Block TB1 J26 15 TB1 6 J26 13 TB1 5 J26 11 TB1 4 J26 9 TB1 3 J23 3 TB1 9 J23 4 TB1 11 J23 6 TB1 12 Notes Refer to the Liebert eXM UPS installation manual SL 25648 SL 25650 or SL 26100 for additional details about the Liebert eXM 10 40 60 100kVA and 120 200kVA UPS s The manual 15 available at the Liebert Web site www liebert com The following are guidelines only and are superseded by local regulations and codes of practice where applicable Take special care when determining the size of the neutral cable because current circulating on the neutral cable may be greater than nominal current in the case of non linear loads The ground conductor should be sized according to local or NEC codes cable length
32. hes mm 2 24 610 minimum clearance above unit and 36 914 front access required for service 3 Keep cabinet within 15 degrees of vertical 4 Top and bottom cable entry available through removable access plates Remove punch to suit conduit size and replace 5 Unit bottom is structurally adequate for forklift handling 6 Control wiring and power wiring must be run in separate conduits 7 All wiring is to be in accordance with national RIGHT SIDE VIEW and local electrical codes Liebert eXM 18 Installation Drawings Figure 13 Outline drawing 600mm Liebert eXM 120 200kVA system 27 518mm 69mm Power Cable Entry 20 7 x 17 7 526mm x 450mm Control Cable Entry 4 7 119mm x 1 6 41mm 719mm Breakout Centers Control Cable Entry 5 9 x 2 0 150mm x 51mm Ventilation Power Cable Entry 10 6 269mm x 16 9 429mm See DETAILA BOTTOM VIEW 23 9 Caster 23 6 600mm 39 1 993mm prs DETAIL Leveler 78 7 2000mm Notes 1 24 610mm minimum clearance above unit for air exhaust 36 914mm front access required for service Keep cabinet within 15 degrees of vertical Top and bottom cable entry available through removable access plates Remove punch to suit conduit size and replace Unit bottom is structurally adequate for forklift handling Control wiring
33. ique pouvant entra ner des dommages mat riels des blessures et m me la mort P R vant de proc der au c blage de armoire assurez vous que vous tes au courant l emplacement et du fonctionnement des isolateurs externes qui raccordent l alimentation d entr e ou de d rivation V rifiez que ces raccords sont isol s lectriquement et installez tous les panneaux d avertissement n cessaires pour emp cher leur utilisation accidentelle The following are guidelines only and are superseded by local regulations and codes of practice where applicable Take special care when determining the size of the neutral cable grounded conductor because current circulating on the neutral cable may be greater than nominal current in the case of nonlinear loads The grounding conductor should be sized according to local or NEC codes cable lengths type of protection etc The grounding cable connecting the UPS to the main ground system must follow the most direct route possible Consider using smaller paralleled cables for heavy currents as a way of easing installation Liebert exM 6 Mechanical Installation Figure 1 Cabinet arrangement Liebert eXM UPS battery cabinets maintenance bypass cabinet If a maintenance bypass cabinet is used it must be installed on the right side of the Liebert eXM UPS dditi Battery abine Matchi Battery Cabinet Matching Matching
34. led between the point of arrival and the unit s position must be planned to make sure that all passages are wide enough for the unit and that floors are capable of supporting its weight for instance check that doorways lifts ramps etc are adequate and that there are no impassable corners or changes in the level of corridors Ensure that the cabinet weight is within the designated surface weight loading kg cm of any handling equipment See Table 12 for the weight of the Liebert eXM MBC 200mm 300mm 600mm and 800mm models Tables 11 through 14 provide detailed dimension and weight information for the Liebert eXM UPS and Liebert eXM MBC when they are bolted together and shipped as a system Ensure that any lifting equipment used in moving the cabinet has sufficient lifting capacity The Liebert eXM MBC can be handled by means of a fork lift or similar equipment For operations with a fork lift refer to installation drawings in 2 0 Installation Drawings Because the weight distribution in the cabinet is uneven use extreme care during handling and transporting When moving the unit by forklift care must be taken to protect the panels Do not exceed a 15 degree tilt with the forklift Handling the unit with straps is not authorized A WARNING Risk of moving heavy units and tipping hazard Can cause equipment damage injury and death Exercise extreme care when handling cabinets to avoid equipment damage or injury to personnel The
35. luminum Cable Size One Hole One Hole 8AWG 54132 60104 TB 6AWG 54136 60109 4AWG 54140 60114 2AWG 54143 60118 1AWG 54148 60124 1 0AWG 54109 60130 2 0AWG 54110 60136 3 0AWG 54111 60142 4 0AWG 54112 60148 250kcmil 54174 60154 300kcmil 54179 60160 350kcmil 256 30695 112 400kcmil 256 30695 1403 500kcmil 256 30695 339 37 Liebert eXM Specifications Table 20 Recommended lug sizes Compression Type M12 1 2 bolt T amp B Copper T amp B Aluminum Cable Size Two Hole Two Hole 6AWG 256 030695 868 4AWG 256 030695 733 2 3AWG 54811BE 1AWG 54857BE 1 0AWG 256 30695 593 2 0AWG 54862BE 60238 3 0AWG 54864BE 60244 4 0AWG 54866BE 60250 250kcmil 54868BE 60256 300kcmil 54870BE 60262 350kcmil 54872BE 60267 400kcmil 54874BE 60269 500kcmil 54876BE 60273 600kcmil 54878BE 60275 700kcmil 54879BE 60277 750kcmil 54880BE 60278 3 2 Torque Requirements electrical connections must be tight Tables 21 and 22 provide the torque values for the connections to the Liebert eXM MBC Use these values unless the equipment 15 labeled otherwise Table 21 Busb ar torque for power wiring Torque Bolt Shaft Size Lb in Nm 3 8 M10 192 22 1 2 M12 428 48 Table 22 Termina AWG Wire Size or Range 22 14 Lb in 3 5 to 5 3 0 4 to 0 6
36. must be run in separate conduits All wiring is to be in accordance with national and local electrical codes The maintenance bypass cabinet will always be attached to the UPS NOS 12014 FRONTVIEW RIGHT SIDE VIEW 19 Liebert eXM Installation Drawings Figure 14 Outline drawing 800mm Liebert eXM MBC 160 200kVA system 22 8 579mm Control Cable Entry 4 Ventilation 4 7 x 1 6 34 3 119mm x 41mm 872mm 28 3 719mm Breakout Centers Power Cable Entry 28 3 x 17 5 719mm x 445mm Power Cable Entry 26 8 x 16 8 681mm x 427mm Control Cable Entry 5 9 x 2 0 TOP VIEW 150mm x 51mm See DETAIL 31 8 808mm 31 3 800mm m Md 78 7 DETAILA 2000mm Notes 1 24 610mm minimum clearance above unit for air exhaust 36 914mm front access required for service 2 Keep cabinet within 15 degrees of vertical 3 Top and bottom cable entry available through removable access plates Remove punch to suit conduit size and replace 4 Unit bottom is structurally adequate for forklift handling 5 Control wiring must be run in separate conduits 6 All wiring is to be in accordance with national and local electrical codes 7 The maintenance bypass cabinet will always be attached to the UPS EXM12015 Rev 1 FRONT VIEW RIGHT SIDE VIEW Liebert eXM 20 Installation Drawings
37. ngle Input Dual Input Block System System TB2 Input Bypass TB3 Output Output TB4 Rectifier Main components 300mm Liebert eXM two to four breakers 60 100 system 37 5 11 8 300mm RIB o L T BIB EH TE 59 __1_ _ 33 L al n ci EC IO noo lo IX TE FRONT VIEW Door Removed Terminal block details 300mm Liebert eXM MBC two to four breakers 60 100 Liebert eXM 14 Installation Drawings Figure 8 Main components 600mm Liebert eXM three to four breakers 120 160kVA system Neutral Busbar RIB BIB MIB D MBB Terminal Strip LEFT SIDE VIEW FRONT VIEW RIGHT SIDE VIEW with Panel Removed with Door Removed with Panel Removed EXM15103 Figure 9 Main components 600mm Liebert eXM two breakers 120 200 system Neutral Busbar MBB MIB LEFT SIDE VIEW FRONT VIEW RIGHT SIDE VIEW With Panel Removed With Door Removed With Panel Removed EXM15104 15 Liebert eXM Installation Drawings Figure 10 Main components 800mm Liebert eXM MBC three or four breakers 160 200 system LEFT SIDE VIEW with Panel Removed 200 Model Only LEFT SIDE VIEW with Panel Removed 160 180kVA Models
38. onfi e qu des professionnels qualifi s et d ment form s portant des v tements de s curit ad quats Des lunettes de s curit doivent tre port es afin de pr venir les blessures en cas d arcs accidentels Retirez montre bagues et tout autre objet m tallique Utilisez uniquement des outils dont le manche est isol Portez des gants de protection en caoutchouc NOTICE Risk of improper installation Can cause equipment damage and void warranty The Liebert eXM MBC should be installed by a qualified engineer in accordance with the information contained in this chapter equipment not referred to in this manual is shipped with details of its own mechanical and electrical installation Do not apply electrical power to the UPS equipment before the arrival of the commissioning engineer Preliminary Checks Before installing the Liebert eXM carry out the following preliminary checks Visually examine the equipment for transit damage both internally and externally Report any damage to the shipper immediately Verify that the correct equipment is being installed The equipment supplied has an identification tag on the back of the main door reporting the type size and main calibration parameters of the UPS Verify that the room satisfies the environmental conditions stipulated in the equipment specifications paying particular attention to the ambient temperature and air exchange system 3 Liebert eX
39. onnected to UPS module all control and power wiring is supplied by Emerson Main 85 3 21 O If the is remote from the UPS module the cables between the MBC and UPS module Main 5 41 must supplied others Main abn C elo Optional SKRU and associated wiring 703 704 706 Shown is typical for a four breaker configuration Also available a two breaker configuration MIB MBB and a three breaker configuration BIB MIB MBB 9 If configuration is two breaker the 120V must be supplied the customer for the bypass line only EXM14004 Rev 0 Wiring shown for a four breaker system Refer to Notes 8 and 9 for two and three breaker configurations GND Dry 15 O Q5 Status 13 O GND_Dry 11 O Q5 Status 9 O Liebert eXM 28 Installation Drawings Figure 23 Solenoid key release unit 200mm Liebert eXM Ag Fuseblock for SKRU E 3 F 85 Q h Solenoid key release unit is mounted between the BIB and MBB breakers 29 Liebert eXM Installation Drawings Figure 24 Solenoid key
40. re as well as during performance of all maintenance procedures This equipment contains circuits that are energized with high voltage Only test equipment designed for troubleshooting should be used This is particularly true for oscilloscopes Always check with an AC and DC voltmeter to ensure safety before making contact or using tools Even when the power is turned Off dangerously high potential electric charges may exist All power and control wiring should be installed by a qualified electrician All power and control wiring must comply with the NEC and applicable local codes ONLY properly trained and qualified personnel should perform maintenance on the Maintenance Bypass Cabinet When performing maintenance with any part of the equipment under power service personnel and test equipment should be standing on rubber mats The service personnel should wear insulating shoes for isolation from direct contact with the floor ground One person should never work alone even if all power is removed from the equipment A second person should be standing by to assist and summon help in case of an accident A AVERTISSEMENT Risque ou de d charge lectrique pouvant entra ner des dommages mat riels des blessures et m me la mort Les pr cautions de s curit habituelles suffisent lorsque le syst me est en mode de fonctionnement normal et que toutes les portes sont ferm es La zone entourant le syst me doit tre exempte de flaques d
41. release unit 300mm Liebert eXM MBC 5 5 KO 56 Fuseblock for SKRU a 6 S 9s 5 2 0 2 2 2 22 2 2 2 2 2 2 2 2 2 2 O 2 2 2 0 Solenoid key release unit is mounted between the BIB and MBB breakers 30 Liebert eXM Installation Drawings Figure 25 Solenoid key release unit 600mm Liebert eXM MBC Fuseblock for SKRU TB1 15 Y 998588888888888585885885 985888888858888880888 oR of Fuseblock for SKRU TB1 31 Liebert eXM Specifications 3 0 SPECIFICATIONS Table 10 Liebert eXM MBC specifications Model Size Input Parameters 10 40kVA UPS 60 100kVA UPS 120 140kVA UPS 160 200kVA UPS Input Voltage to Bypass VAC 208 120V or 220 127V 3 Phase 4 Wire Input Current AAC Refer to Tables 15 16 and 17 Input Frequency Hz 60 Output Parameters Output Power k
42. ring The installation diagrams in 2 0 Installation Drawings of this manual identify the location of the holes in the base plate through which the equipment can be bolted to the floor If the equipment is to be located on a raised floor it should be mounted on a pedestal suitably designed to accept the equipment point loading Cable Entry Cables can enter the Liebert from the bottom or top 5 Liebert eXM Mechanical Installation 1 6 Power Cables The Liebert eXM MBC requires both power and control cabling once it has been mechanically installed control cables must be separate from the power cables Run control cables in metal conduits or metal ducts that are electrically bonded to the cabinets they are connected to The cable design must comply with the voltages and currents provided in Tables 15 through 17 follow local wiring practices and take into consideration the environmental conditions temperature and physical support media For cable entry locations refer to Figures 11 and 12 WARNING Risk of electric shock Can cause equipment damage injury and death Before cabling up the cabinet ensure that you are aware of the location and operation of the external isolators that connect the input bypass supply Check that these supplies are electrically isolated and post any necessary warning signs to prevent their inadvertent operation AVERTISSEMENT Risque de d charge lectr
43. s type of protection etc The ground cable connecting the UPS to the main ground system must follow the most direct route possible Consideration should be given to the use of smaller paralleled cables for heavy currents as a way to ease installation In most installations the load equipment is connected to a distribution network of individually protected busbars fed by the Liebert eXM MBC output rather than being connected directly to the Liebert eXM MBC itself Where this is the case the Liebert eXM MBC output cables can be rated to suit the individual distribution network demands rather than being fully load rated When laying the power cables do not form coils to avoid increasing formation of electromagnetic interference 9 Liebert eXM Installation Drawings 2 0 INSTALLATION DRAWINGS Figure 2 One line diagram dual input two breaker Liebert 10 200kVA system gt Bypass Output AC Output AC Input MIB 208V 220V 4 Wire GND 4 Wire GND See Note 6 AC Input Static Bypass 4 Wire GND NOTES 1 Install in accordance with national and local electrical codes 2 Input and bypass must share the same single source 3 A neutral is required from the system AC input source A full capacity neutral conductor is recommended Grounding conductors are recommended A 4 Bypass and rectifier inputs and output cables must be mmmmmmm Field Suppli
44. tached to the UPS Emerson will supply the interconnection cables Conduit Landing BOTTOM VIEW TOP VIEW TB2 TB4 Dual Input Systems 11 8 300mm 9 2 55 RIB BIB MBB Tar Neutral MIB Busbar TE LEFT SIDE VIEW FRONT VIEW RIGHT SIDE VIEW Panel Removed Door Removed Panel Removed Table 8 Breaker configuration 300mm Liebert eXM MBC two to four breakers 60 100kVA system Liebert eXM MBC Breaker Configuration Configured Breaker 2 MBB MIB 3 BIB MBB MIB 4 RIB BIB MBB MIB Table 9 Terminal block details 300mm Liebert eXM MBC two to four breakers 60 100kVA system Terminal Single Input Dual Input Block System System TB2 Input Bypass TB3 Output Output TB4 Rectifier Liebert eXM MBC 22 Installation Drawings Figure 17 Terminal details 600mm Liebert eXM two breakers 120 200kVA system Notes 1 All dimensions are in inches mm 2 Control wiring and power wiring must be run in separate conduits 3 All wiring is to be in accordance with national and local electrical codes 4 If maintenance bypass cabinet is attached to UPS Liebert will supply the interconnection cables MBB Input see DETAIL A Neutral Busbar MBB Input see DETAIL B MIB See DETAIL B Ground Busbar see DETAIL A LEFT SIDE VIEW FRONT VI
45. terre WARNING Risk of electric shock cause equipment damage injury and death The operations described in this section must be performed by authorized electricians or properly trained and qualified technical personnel wearing adequate safety clothing eye protection and gloves If you have any difficulties do not hesitate to contact Emerson Network Power Liebert Services See the back page of this manual for contact information A AVERTISSEMENT Risque de d charge lectrique pouvant entrainer des dommages mat riels des blessures et m me la mort Toutes les op rations d crites dans cette section ne doivent tre effectu es que par des lectriciens ou des techniciens professionnels d ment form s et qualifi s portant gants unettes et v tements de protection ad quats En cas de probl me n h sitez pas communiquer avec Emerson Network Power Liebert Services Pour obtenir les renseignements de contact consultez la derni re page de ce manuel Proper grounding considerably reduces problems systems caused by electromagnetic interference Once the equipment has been finally positioned and secured connect the power cables as described in the following procedure Refer to the appropriate cable connection drawing in 2 0 Installation Drawings 1 Verify that the bypass equipment is isolated from its external power source and all the power isolators are open Check that these supplies are