1. 1 5 met For equipment other than that specified the contractor shall supply proof that such substitute equipment equals or exceeds the features functions performance and quality of the specified equipment Shop Drawings 1 Sufficient information clearly presented shall be included to determine compliance with drawings and specifications 2 Include manufacturer s name s model numbers ratings power requirements equipment layout device arrangement complete wiring point to point diagrams and conduit layouts 3 Show system layout configurations and terminations Manuals 1 Submit simultaneously with the shop drawings complete operating and maintenance manuals listing the manufacturer s name s including technical data sheets 2 Wiring diagrams shall indicate internal wiring for each device and the interconnections between the items of equipment 3 Provide a clear and concise description of operation that gives in detail the information required to properly operate the equipment and system Software Modifications 1 Provide the services of a qualified technician to perform all system software modifications upgrades or changes Response time of the technician to the site shall not exceed 4 hours Provide all hardware software programming tools and documentation necessary to modify the fire alarm system on site Modification includes addition and deletion of devices circuits zones and chang
2. indicators used by the system operator 2 The display shall include status information for all intelligent detectors addressable modules and zones 3 The display shall contain dedicated LEDs for the annunciation of AC POWER FIRE ALARM SUPERVISORY TROUBLE and GROUND FAULT SILENCED LOW BATTERY and WALKTEST 4 The keypad shall be part of the standard system and have the capability to command all system functions Installer password level shall be provided to prevent unauthorized system control or programming 5 The display shall include the following operator control switches ACKNOWLEDGE ALARM SILENCE DRILL alarm activate ALARM ID SUPERVS ID TROUBLE ID and SYSTEM RESET Signaling Line Circuit SLC 1 The SLC interface shall provide power to and communicate with up to 25 devices of any type including intelligent detectors photoelectric or thermal addressable pull stations intelligent modules monitor or control Each SLC shall be capable of NFPA 72 Style 4 Class B wiring 2 The CPU shall receive information from all intelligent detectors to be processed to determine whether normal alarm or trouble conditions exist for each detector The software shall automatically compensate for the accumulation of dust in each detector up to allowable limits The information shall also be used for automatic detector testing and for the determination of detector maintenance conditions 3 The detector software shall meet NF
3. zone of conventional alarm initiating devices any normally open dry contact device to one of the fire alarm control panel SLCs The IDC zone shall be suitable for Style B Class operation An LED shall be provided that shall flash under normal conditions indicating that the monitor module is operational and in regular communication with the control panel Addressable Control Relay Module 1 2 Addressable control relay modules shall be provided to control the operation of fan shutdown and other auxiliary control functions The control module shall mount in a standard 4 inch square 2 1 8 inch deep electrical box or to a surface mounted backbox The control relay module will provide a dry contact Form C relay The relay coil shall be magnetically latched to reduce wiring connection requirements and to insure that 100 of all auxiliary relays may be energized at the same time on the same pair of wires The control relay module shall be suitable for pilot duty applications and rated for a minimum of 0 6 amps at 30 VDC Annunciator 1 The main control must have a built in annunciator with three characters of display 2 5 2 6 each consisting of seven segments and feature LED s for AC General Trouble Silenced Ground Fault Low Battery Walk Test NAC 1 and 2 Active and Trouble and Zones 1 through 5 Alarm Supervisory and Trouble 2 All control and programming keys are a membrane style buttons 3 The annunciat
4. PA 72 requirements and be certified by UL as a calibrated sensitivity test instrument The control panel will have the capability of Reverse Polarity Transmission or connection to a Municipal Box for compliance with applicable NFPA standards Digital Alarm Communicator Transmitter DACT The DACT is an interface for communicating digital information between a fire alarm control panel and a UL Listed central station 1 Communication shall include vital system status such as Independent Zone Alarm trouble non alarm supervisory Independent Addressable Device Status AC Mains Power Loss Low Battery and Earth Fault System Off Normal 12 and 24 Hour Test Signal Abnormal Test Signal per UL requirements The DACT shall support independent zone point reporting via the Contact ID format In this format the DACT shall support the transmission of addressable points within the system This format shall enable the central station to have exact details concerning the location of the fire for emergency response Enclosures 1 3 The control panel shall be housed in a UL listed cabinet suitable for surface mounting The cabinet and front shall be corrosion protected and painted black via the powder coat method with manufacturer s standard finish The back box and door shall be constructed of steel with provisions for electrical conduit connections into the sides and top The door shall provide a key lock and
5. SECTION 13850 28 31 00 FIRE DETECTION AND ALARM SYSTEM ENGINEERING SPECIFICATION 25 POINT INTELLIGENT COMMUNICATING FIRE DETECTION SYSTEM PART 1 GENERAL 1 1 A DESCRIPTION This section of the specification includes the furnishing installation connection and testing of the microprocessor controlled intelligent reporting fire alarm equipment required to form a complete operative coordinated system It shall include but not be limited to alarm initiating devices alarm notification appliances Fire Alarm Control Panel FACP auxiliary control devices power supplies and wiring as shown on the drawings and specified herein The fire alarm system shall comply with requirements of NFPA Standard No 72 for Local Protected Premises Signaling Systems except as modified and supplemented by this specification The system field wiring shall be supervised either electrically or by software directed polling of field devices 1 The Secondary Power Source of the fire alarm control panel will be capable of providing at least 24 hours of backup power with the ability to sustain 5 minutes in alarm at the end of the backup period The fire alarm system shall be manufactured by an ISO 9001 certified company and meet the requirements of BS EN9001 ANSI ASQC Q9001 1994 The FACP and peripheral devices shall be manufactured 100 by a single U S manufacturer or division thereof Underwriters Laboratories Inc UL USA UL 38 Man
6. ble LEDs to steady ON mode 2 Alarm Silence Switch Activation of the alarm silence switch shall cause all programmed alarm notification appliances and relays to return to the normal condition after an alarm condition The selection of notification circuits and relays that are silenceable by this switch shall be fully field programmable within the confines of all applicable standards The FACP software shall include silence inhibit and auto silence timers 3 Alarm Activate Drill Switch The Alarm Activate switch shall activate all notification appliance circuits The drill function shall latch until the panel is reset 4 System Reset Switch Activation of the System Reset switch shall cause all electronically latched initiating devices appliances or software zones as well as all associated output devices and circuits to return to their normal condition 5 Lamp Test The System RESET switch shall also function as a Lamp Test switch and shall activate all system LEDs and light each segment of the display System Capacity and General Operation 1 The control panel shall provide or be capable of expansion to 25 intelligent addressable devices of any type detector or module 2 The control panel shall include two Form C programmable relays which can be used for Alarm and Supervisory and a fixed Trouble relay rated at a minimum of 2 5 amps 24 VDC It shall also include 2 programmable Notification Appliance Circuits NACs
7. capable of being wired as NFPA Style Y Class B Either programmable Notification circuit shall also be capable of providing auxiliary power when programmed as such 3 The control panel must have a built in annunciator with three characters of display each consisting of seven segments and feature LED s for AC General Trouble Silenced Ground Fault Low Battery Walk Test NAC 1 and 2 Active and Trouble and Zones 1 through 5 Alarm Supervisory and Trouble All control and programming keys are a membrane style buttons The annunciator must be able to silence and reset alarms by opening the cabinet door and pressing SILENCE or RESET once The annunciators must have an installer code that will allow the limitation of operating system programming to authorized individuals 4 Modifications to the default panel program can only be accomplished using the embedded web server of the control panel There are two ways to connect to the panel connected to an existing network with a DHCP Dynamic Host Configuration Protocol server present or plugged in directly to a PC using a standard CAT5e Ethernet cable 5 The system shall allow the programming of any input to activate any output 6 The FACP shall provide the following features a Drift compensation to extend detector accuracy over life Drift compensation shall also include a smoothing feature allowing transient noise signals to be filtered out b Detector sensitivity test meeting requir
8. de a photoelectric sensing element thermal sensing element IR Infrared sensing element and CO carbon monoxide sensor Intelligent Photoelectric Smoke Detector 1 The detectors shall use the photoelectric light scattering principal to measure smoke density and shall on command from the control panel send data to the panel representing the analog level of smoke density Intelligent Thermal Detectors 1 Thermal detectors shall be intelligent addressable devices Thermal detectors shall be available with a rating of 135 degrees Fahrenheit 58 degrees Celsius fixed fixed 135 degree F with a rate of rise feature at 15 degrees F 9 4 degrees C per minute and a high temperature thermal rated at 190 degrees F 88 degrees C It shall connect via two wires to the fire alarm control panel signaling line circuit Intelligent Duct Smoke Detector 1 The smoke detector housing shall accommodate either an intelligent ionization detector or an intelligent photoelectric detector of that provides continuous analog monitoring and alarm verification from the panel When sufficient smoke is sensed an alarm signal is initiated at the FACP and appropriate action taken to change over air handling systems to help prevent the rapid distribution of toxic smoke and fire gases throughout the areas served by the duct system Addressable Dry Contact Monitor Module 1 Addressable monitor module shall be provided to connect one supervised IDC
9. ements of NFPA 72 Maintenance alert with two levels maintenance alert maintenance urgent to warn of excessive smoke detector dirt or dust accumulation c Alarm verification with counters and a trouble indication to alert maintenance personnel when a detector enters verification an excessive number of times d Periodic detector test conducted automatically by the software e Walk test mode shall be a standard feature of the fire alarm control panel The walk test feature shall function so that each alarm input tested will operate the associated notification appliance for three seconds The FACP will then automatically perform a reset and confirm normal device operation D Central Microprocessor 1 The microprocessor shall be a state of the art it shall communicate with monitor and control all external interfaces It shall include non volatile memory for building specific program storage and a watch dog timer circuit to detect and report microprocessor failure 2 The microprocessor shall contain and execute all specific actions to be taken in the condition of an alarm Control programming shall be held in non volatile programmable memory and shall not be lost even if system primary and secondary power failure occurs 3 An auto programming capability JumpStart shall be provided to quickly identify devices connected on the SLC and make the system operational Display 1 The display shall provide all the controls and
10. er manual indicating Sequence of Operation END OF SECTION
11. es and Cabinets All boxes and cabinets shall be UL listed for their use and purpose The fire alarm control panel shall be connected to a separate dedicated branch circuit maximum 20 amperes This circuit shall be labeled at the main power distribution panel as FIRE ALARM Fire alarm control panel primary power wiring shall be 12 AWG The control panel cabinet shall be grounded securely to either a cold water pipe or grounding rod 2 3 1 The FACP shall be capable of coding Notification Appliance Circuits in Temporal NFPA 72 or Constant On 24 VDC power Main panel notification circuits NACs 1 amp 2 shall also automatically synchronize any of the following manufacturer s notification appliances connected to them System Sensor Wheelock Gentex or Amseco with no need for additional synchronization modules MAIN FIRE ALARM CONTROL PANEL The FACP shall be a NOTIFIER Model NSP 25 and shall contain a microprocessor based Central Processing Unit CPU The CPU shall communicate with and control the following types of equipment used to make up the system HFS intelligent addressable smoke and HFS thermal heat detectors HFS addressable modules NOT BG12LX pull station and Digital Dialer Operator Control 1 Acknowledge Switch a Activation of the control panel Acknowledge switch in response to new alarms supervisory and or troubles shall silence the local panel piezo electric signal and change the alarm supervisory and trou
12. es to system operation The system structure and software shall place no limit on the type or extent of software modifications on site Modification of software shall not require power down of the system or loss of system fire protection while modifications are being made GUARANTY All work performed and all material and equipment furnished under this contract shall be free from defects and shall remain so for a period of at least one 1 year from the date of acceptance The full cost of maintenance labor and materials required to correct any defect during this one year period shall be included in the submittal bid MAINTENANCE 1 6 1 7 Maintenance and testing shall be on a semi annual schedule or as required by the local AHJ A preventive maintenance schedule shall be provided by the contractor describing the protocol for preventive maintenance The schedule shall include 1 Systematic examination adjustment and cleaning of all detectors manual fire alarm stations control panels power supplies relays waterflow switches and all accessories of the fire alarm system 2 Each circuit in the fire alarm system shall be tested semiannually 3 Each smoke detector shall be tested in accordance with the requirements of NFPA 72 As part of the bid proposal include a quote for a maintenance contract to provide all maintenance tests and repairs described below Include also a quote for unscheduled maintenance repairs includi
13. evice circuits and verify that the trouble signal actuates Open and short signaling line circuits and verify that the trouble signal actuates Open and short notification appliance circuits and verify that trouble signal actuates Ground all circuits and verify response of trouble signals Check presence and audibility of tone at all alarm notification devices Check installation supervision and operation of all intelligent smoke detectors using the walk test Each of the alarm conditions that the system is required to detect should be introduced on the system Verify the proper receipt and the proper processing of the signal at the FACP and the correct activation of the control points When the system is equipped with optional features the manufacturer s manual shall be consulted to determine the proper testing procedures This is intended to address such items as verifying controls performed by individually addressed or grouped devices sensitivity monitoring verification functionality and similar FINAL INSPECTION 2 10 At the final inspection a minimum NICET Level Il technician shall demonstrate that the system functions properly in every respect INSTRUCTION Instruction shall be provided as required for operating the system Hands on demonstrations of the operation of all system components and the entire system including program changes and functions shall be provided The contractor or installing dealer shall provide a us
14. he intelligent addressable smoke detectors in the system may be independently programmed for verification of alarm signals The alarm verification time period shall not exceed 250 seconds 2 Zone Disable Any addressable device in the system may be enabled or disabled through the system keypad 3 Zone Read The system shall be able to display the following point status 2 4 a Alarm ID b Supervisory ID c Trouble ID Automatic Detector Maintenance Alert The fire alarm control panel shall automatically interrogate each intelligent detector and shall analyze the detector responses over a period of time If any intelligent detector in the system responds with a reading that is above or below normal limits then the system will enter the trouble mode and the particular detector will be annunciated on the system display This feature shall in no way inhibit the receipt of alarm conditions in the system nor shall it require any special hardware special tools or computer expertise to perform The fire alarm control panel shall include Silent and Audible Walk Test functions Silent and Audible It shall include the ability to test initiating device circuits and Notification Appliance Circuits from the field without returning to the panel to reset the system The operation shall be as follows a Alarming an initiating device shall activate programmed outputs which are selected to participate in Walk Test Supervisory Operation An alar
15. intenance free No liquids are required Fluid level checks for refilling spills and leakage shall not be required PART 3 0 EXECUTION 2 7 INSTALLATION 2 8 nm OO O W I 2 9 Installation shall be in accordance with the NEC NFPA 72 local and state codes as shown on the drawings and as recommended by the major equipment manufacturer All conduit junction boxes conduit supports and hangers shall be concealed in finished areas and may be exposed in unfinished areas Smoke detectors shall not be installed prior to the system programming and test period If construction is ongoing during this period measures shall be taken to protect smoke detectors from contamination and physical damage Manual pull stations shall be suitable for surface mounting or semi flush mounting as shown on the plans and shall be installed not less than 42 inches 1067 mm nor more than 48 inches 122 mm above the finished floor TEST The service of a competent NICET level II technician shall be provided to technically supervise and participate during all of the adjustments and tests for the system All testing shall be in accordance with NFPA 72 Before energizing the cables and wires check for correct connections and test for short circuits ground faults continuity and insulation Close each sprinkler system flow valve and verify proper supervisory alarm at the FACP Verify activation of all waterflow switches Open initiating d
16. ipment and components shall be installed in strict compliance with manufacturers recommendations Consult the manufacturer s installation manuals for all wiring diagrams schematics physical equipment sizes etc before beginning system installation All equipment shall be attached to walls and ceiling floor assemblies and shall be held firmly in place e g detectors shall not be supported solely by suspended ceilings Fasteners and supports shall be adequate to support the required load CONDUIT AND WIRE Conduit 1 Conduit shall be in accordance with The National Electrical Code NEC local and state requirements 2 Where required all wiring shall be installed in conduit or raceway Conduit fill shall not exceed 40 percent of interior cross sectional area where three or more cables are contained within a single conduit 3 Cable must be separated from any open conductors of power or Class 1 circuits Wire and shall not be placed in any conduit junction box or raceway containing these conductors per NEC Article 760 With the exception of telephone connections wiring for 24 volt DC control alarm notification emergency communication and similar power limited auxiliary functions may be run in the same conduit as initiating and signaling line circuits All circuits shall be provided with transient suppression devices and the system shall be designed to permit simultaneous operation of all circuits without interference or
17. loss of signals Conduit shall not enter the fire alarm control panel or any other remotely mounted control panel equipment or backboxes except where conduit entry is specified by the FACP manufacturer Conduit shall be 3 4 inch 19 1 mm minimum Fire alarm system wiring shall be new or existing and meeting system requirements Wiring shall be in accordance with local state and national codes e g NEC Article 760 and as recommended by the manufacturer of the fire alarm system Number and size of conductors shall be as recommended by the fire alarm system manufacturer but not less than 18 AWG 1 02 mm for Initiating Device Circuits Signaling Line Circuits or Notification Appliance Circuits All wire and cable shall be listed and or approved by a recognized testing agency for use with a protective signaling system Wire and cable not installed in conduit shall have a fire resistance rating suitable for the installation as indicated in NEC 760 e g FPLR Wiring used for the multiplex communication circuit SLC shall support a minimum wiring distance of 10 000 feet when sized at 12 AWG All field wiring shall be electrically supervised for open circuit and ground fault The fire alarm control panel shall be capable of T tapping NFPA Style 4 Class B Signaling Line Circuits SLCs Systems which do not allow or have restrictions for the number of T taps length of T taps etc are not acceptable Terminal Boxes Junction Box
18. m from a supervisory device shall cause the appropriate indication on the control panel display light a Zone supervisory LED Signal Silence Operation The FACP shall have the ability to program each output circuit notification circuit or relay to deactivate upon depression of the Signal Silence switch SYSTEM COMPONENTS Addressable Manual Fire Alarm Box manual station 1 Addressable manual fire alarm boxes shall on command from the control panel send data to the panel representing the state of the manual switch and the addressable communication module status They shall use a key operated test reset lock and shall be designed so that after actual emergency operation they cannot be restored to normal use except by the use of a key All operated stations shall have a positive visual indication of operation and utilize a key type reset Manual fire alarm boxes shall be constructed of Lexan with clearly visible operating instructions provided on the cover The word FIRE shall appear on the front of the stations in raised letters 1 75 inches 44 mm or larger Advanced Multi Criteria Intelligent Detector 1 The intelligent multi criteria IntelliQuad detector shall be an addressable device combining four sensing elements in a single sensing device providing the ability to detect all four major elements of a fire The detector design shall allow sensitivity setting between 1 to 4 per foot obscuration The detector shall inclu
19. ng hourly rates for technicians trained on this equipment and response travel costs for each year of the maintenance period Submittals that do not identify all post contract maintenance costs will not be accepted Rates and costs shall be valid for the period of five 5 years after expiration of the guaranty POST CONTRACT EXPANSIONS The contractor shall have the ability to provide parts and labor to expand the system specified if so requested for a period of five 5 years from the date of acceptance As part of the submittal include a quotation for all parts and material and all installation and test labor as needed to increase the number of intelligent or addressable devices by ten percent 10 This quotation shall include HFS intelligent smoke detectors HFS intelligent heat detectors addressable manual stations and HFS addressable monitor modules equal in number to one tenth of the number required to meet this specification list actual quantity of each type The quotation shall include installation test labor and labor to reprogram the system for this 10 expansion If additional FACP hardware is required include the material and labor necessary to install this hardware Do not include cost of conduit or wire or the cost to install conduit or wire except for labor to make final connections at the FACP and at each HFS intelligent addressable device Do not include the cost of conventional peripherals or the cost of initiating de
20. odular expansion audio visual power supplies 3 The power supply shall provide an integral battery charger or may be used with an external battery and charger systems Battery arrangement may be configured in the field 4 The main power supply shall continuously monitor all field wires for earth ground conditions 5 The main power supply shall operate on 120 VAC 60 Hz and shall provide all necessary power for the FACP Programmable Electronic Sounders 1 Electronic sounders shall operate on 24 VDC nominal 2 Electronic sounders shall be field programmable without the use of special tools at a sound level of at least 90 dBA measured at 10 feet from the device 3 Shall be flush or surface mounted as shown on plans Strobe lights shall meet the requirements of the ADA UL Standard 1971 be fully synchronized and shall meet the following criteria 1 The maximum pulse duration shall be 2 10 of one second 2 Strobe intensity shall meet the requirements of UL 1971 3 The flash rate shall meet the requirements of UL 1971 Horn Strobes 1 Operate on 24 VDC 2 Have two selectable tone options of temporal 3 and non temporal continuous pattern Have at least 2 audibility options Maximum Pulse Duration 0 2 second Strobe Intensity UL 1971 Flash Rate UL 1971 Strobe Candela Rating Determine by positioning selector switch on back of device NONA Specific System Operations 1 Alarm Verification Each of t
21. or must be able to silence and reset alarms by opening the cabinet door and pressing SILENCE or RESET once 4 The annunciators must have an installer code that will allow the limitation of operating system programming to authorized individuals Field Wiring Terminal Blocks For ease of connection for heavy solid gauge wire all panel I O wiring terminal blocks shall be screw type barrier strips and have sufficient capacity for 22 to 12 AWG wire SYSTEM COMPONENTS ADDRESSABLE DEVICES Addressable Devices General 1 Addressable devices shall employ the simple to set decade addressing scheme Addressable devices which use a binary coded address setting method such as a rotary dials 2 Detectors shall be addressable and intelligent and shall connect with two wires to the fire alarm control panel signaling line circuits 3 The detectors shall be listed by UL as meeting the calibrated sensitivity test requirements of NFPA Standard 72 4 Detectors shall be ceiling mount and shall include a separate twist lock base with tamper proof feature 5 Detectors shall provide a test means whereby they will simulate an alarm condition and report that condition to the control panel BATTERIES Upon loss of Primary AC power to the control panel the batteries shall have sufficient capacity to power the fire alarm system for required standby time 24 or 60 hours followed by 5 minutes of alarm The batteries are to be completely ma
22. rriving at the main FACP shall not be lost following a primary power failure or outage of any kind until the alarm signal is processed and recorded 5 Panel shall meet requirements of UL 864 Ninth Edition BASIC SYSTEM FUNCTIONAL OPERATION When a fire alarm condition is detected and reported by one of the system initiating devices the following functions shall immediately occur 1 The Zone Alarm LED for the particular zone in alarm shall light 2 A local sounder with the control panel shall sound 3 In response to a fire alarm condition the system will process all control programming and activate all system outputs alarm notification appliances and or relays associated with the point s in alarm 4 In response to a fire alarm condition the system will process all control programming and activate all system outputs alarm notification appliances and or relays associated with the point s in alarm Additionally the system shall send events to a central alarm supervising station via dial up over PSTN SUBMITTALS General 1 Two copies of all submittals shall be submitted to the Architect Engineer for review 2 All references to manufacturer s model numbers and other pertinent information herein is intended to establish minimum standards of performance function and quality Equivalent compatible UL listed equipment from other manufacturers may be substituted for the specified equipment as long as the minimum standards are 1 4
23. shall provide for the viewing of all indicators Field Charging Power Supply The FCPS is a device designed for use as either a remote 24 volt power supply or as a booster for powering Notification Appliances 1 The FCPS shall offer up to 8 0 amps 6 0 amps continuous of regulated 24 volt power It shall include an integral charger designed to charge 18 0 amp hour batteries 2 The Field Charging Power Supply shall have two input triggers The input trigger shall be a Notification Appliance Circuit from the fire alarm control panel or a control relay Four NAC outputs wired NFPA Style Y or Z shall be available for connection to the Notification devices 3 The FCPS shall optionally provide synchronization of all connected strobes or horn strobe combinations when System Sensor Wheelock or Gentex devices are installed 4 The FCPS shall function as a sync follower as well as a sync generator 5 The FCPS shall include a surface mount backbox 6 The Field Charging Power Supply shall include the ability to delay the reporting of an AC fail condition per NFPA requirements 7 The FCPS shall provide 24 VDC regulated and power limited circuitry per UL standards Power Supply 1 The main power supply for the fire alarm control panel shall provide up to 2 0 amps of available power for the control panel and peripheral devices 2 Provisions will be made to allow the audio visual power to be increased as required by adding m
24. ually Actuated Signaling Boxes UL 228 Door Closers Holders for Fire Protective Signaling Systems UL 268 Smoke Detectors for Fire Protective Signaling Systems UL 268A Smoke Detectors for Duct Applications UL 346 Waterflow Indicators for Fire Protective Signaling Systems UL 464 Audible Signaling Appliances UL 521 Heat Detectors for Fire Protective Signaling Systems UL 864 Standard for Control Units for Fire Protective Signaling Systems UL 1481 Power Supplies for Fire Protective Signaling Systems UL 1638 Visual Signaling Appliances UL 1971 Signaling Devices for Hearing Impaired 1 The FACP shall be UL 864 Ninth Edition Listed Systems listed to previous UL 864 Editions shall not be accepted 1 2 1 3 The installing company shall employ NICET minimum Level II Fire Alarm Technology technicians on site to guide the final check out and to ensure the systems integrity SCOPE An intelligent microprocessor controlled fire alarm detection system shall be installed in accordance to the project specifications and drawings Basic Performance 1 Initiation Device Circuits IDC shall be wired Class A NFPA Style D as part of an addressable device connected by the SLC Circuit 2 All circuits shall be power limited UL864 9 edition requirements 3 A single ground fault or open circuit on the system Signaling Line Circuit shall not cause system malfunction loss of operating power or the ability to report an alarm 4 Alarm signals a
25. vices connected to the addressable monitor control modules Submittals that do not include this estimate of post contract expansion cost will not be accepted APPLICABLE STANDARDS AND SPECIFICATIONS The specifications and standards listed below form a part of this specification The system shall fully comply with the latest issue of these standards if applicable National Fire Protection Association NFPA USA 1 8 No 13 Sprinkler Systems No 70 National Electric Code NEC No 72 National Fire Alarm Code No 101 Life Safety Code The system and its components shall be Underwriters Laboratories Inc listed under the appropriate UL testing standard as listed herein for fire alarm applications and the installation shall be in compliance with the UL listing Local and State Building Codes All requirements of the Authority Having Jurisdiction AHJ APPROVALS The system shall have proper listing and or approval from the following nationally recognized agencies ETL listed to ANSI UL 864 Ninth Edition Standard UL listed to 864 Ninth Edition Standard PART 2 0 PRODUCTS 2 1 A 2 2 EQUIPMENT AND MATERIAL GENERAL All equipment and components shall be new and the manufacturer s current model The materials appliances equipment and devices shall be tested and listed by a nationally recognized approvals agency for use as part of a fire protective signaling system meeting the National Fire Alarm Code All equ
Download Pdf Manuals
Related Search
Related Contents
Betriebsanleitung - VEGA Americas, Inc. Installation Manual - Quick Reference Guide TB Touch Aqua 8 8GB Green, White NOTICE PULSIVE VENTIL ANEXO II - EDITAL 072013 - MEMORIAL DESCRITIVO Guide pour le retrait du matériel à risque spécifié (MRS E47296 30+6+1 LED extendable workshop Kenwood KDC-119S CD Player User Manual Copyright © All rights reserved.