User Manual - Zeta Alarm Systems

image

Contents

1. Maximum Supply Current Maximum Pipe Length Operating Temperature 10 to 50 C Operating Humidity 10 to 95 RH non condensing Approvals CEA 4022 by VdS G206066 EN61000 6 3 2001 A11 2004 EMC CE Certification EN60950 1 2006 Safet 11 1 TYPICAL SUPPLY CURRENT FAN SPEED Bargraph Value o 1 110 120 150 170 265 300 Typical current consumption figures for different fan speeds Results are based upon an ASD2 installation with 10m of standard 25mm aspirating pipe per channel The unit was powered from a 24V supply WEEE DIRECTIVE 2002 96 EC Waste Electrical and Electronic Equipment The symbol shown is marked on this product to indicate that it must not be disposed of with other waste Instead it is the user s responsibility to dispose of their waste equipment by handing it over to a designated collection point for the recycling of waste electrical and electronic e equipment The separate collection and recycling of your waste at the time of disposal will help to conserve natural resources and ensure that it is recycled in a manner that protects human health and the environment For more information about where you can drop off your waste equipment for recycling please contact your local city office your household waste disposal service or where you purchased the product GLT Exports Limited VdS Detection House 72 78 Morfa Road Hafod Swansea SA1 2EN United Kingdom Tel
2. of the test aerosol sprays for point detectors do NOT work on aspirated systems If it is possible to get close to the sampling point then a basic functional check can be carried out with smoke matches or lighted taper etc but for measurable performance tests then refer to Appendix A of the BFPSA Code of Practice for Aspirating Systems to select the appropriate test for the installation 8 MAINTENANCE With normal use the filter elements will eventually become contaminated with dust particles impeding airflow and it is recommended that the filter elements order code FL55 are changed every six months MAINTENANCE SHOULD ONLY BE CARRIED OUT BY QUALIFIED PERSONNEL BEFORE CARRYING OUT ANY MAINTENANCE NOTIFY THE PROPER AUTHORITIES AND ISOLATE UNIT FROM THE FIRE CONTROL PANEL TO PREVENT UNWANTED ALARMS 1 Remove the transparent cover using the special tool provided to unscrew the tamper proof fasteners 2 Lift out the foam filter elements from the filter tube tweezers or long nosed pliers are recommended for this operation 3 Fit a new filter element set ensuring that the coarse grade filter is inserted into the tube first Care should be taken to ensure that the filters are not compressed during fitting and that the fine filter is positioned flush with the top of the filter tube 4 Replace the top cover ES THE DETECTORS SHOULD BE SERVICED IN ACCORDANCE WITH THE MANUFACTURERS RECOMMENDATIONS 9 CEA 4022 CERTIFIED DE
3. ASPIRATED SMOKE DETECTOR ASD2 Dual Channel INSTALLATION OPERATION amp MAINTENANCE INSTRUCTIONS CE 1 INTRODUCTION The dual channel ASD2 has provision for two separate conventional or analogue addressable point detectors each monitoring a separate sampling pipe run Airflow levels are displayed on a pair or 10 element bar graphs with adjustments for sensitivity and high low flow thresholds Flow failure is reported to the central control panel via separate volt free contacts CAUTION THE ASD2 SYSTEM HAS BEEN INDEPENDENTLY TESTED AND CERTIFIED TO CEA4022 AND MUST BE INSTALLED IN STRICT COMPLIANCE WITH THE INSTRUCTIONS BELOW IF THE CERTIFICATION IS TO BE MAINTAINED 2 SYSTEM INSTALLATION WARNING THIS EQUIPMENT MUST BE INSTALLED BY A QUALIFIED INSTALLER IN ACCORDANCE WITH ALL LOCAL AND NATIONAL REGULATIONS Remove the transparent cover using the special tool provided to unscrew the tamper proof fasteners Use the template provided to accurately position the holes then secure the unit to a suitable surface through the 4 corner fixing points Ensure that the correct fasteners are used for the type of surface that the unit is mounted on 3 WIRING For correct operation of the unit it is essential that the case is fully sealed so that air can only be pulled into the system through the aspirating pipe For this reason all wiring must pass through the cable seals provided and no additional holes should be made In order to pass a ca
4. FLOW LOW AIRFLOW The following LEDs are common to both channels O 5 POWERON O 6 GENERAL FAULT Mains PSU Option Only O 7 A MAINS FAILURE Mains PSU Option Only O 8 BATTERY LOW Mains PSU Option Only O 9 9 FANFAULT lt 0 10 cope CODE ENTRY O 11 w UNLOCK 6 2 USER FUNCTIONS Press and hold SELECT and CHANGE keys simultaneously for 1 second to initialise function selection Press and release SELECT key to sequentially step through functions Press and release CHANGE key to modify setting The relevant LED flashes continuously to indicate the function selected Enter 3 digit access code 510 Each number must be selected in turn e g press CHANGE six times to illuminate the number 5 LED on the display then press SELECT etc CODE LED flashes UNLOCK LED illuminates on successful entry 1 Set fan speed POWER LED flashes 2 Set sensitivity of bar graph to changes in airflow velocity FLOW1 OK flashes 3 Set sensitivity of Channel 2 Bar Graph to changes in airflow velocity FLOW 2 OK flashes 4 Select the BARGRAPH 1 LED segment above which the FLOW HIGH 1 LED will be illuminated FLOW HIGH 1 flashes 5 Select the BARGRAPH 1 LED segment below which the FLOW LOW 1 LED will be illuminated FLOW LOW 1 flashes 6 Select the BARGRAPH 2 LED segment above which the FLOW HIGH 2 LED will be illuminated FLOW HIGH 2 flashes 7 Select the BARGRAPH 2 LED segment below which the FLOW L
5. OW 2 LED will be illuminated FLOW LOW 2 flashes 8 Calibrate flow sensors FAN FAULT LED flashes CHANGE key must be pressed for at least 2 seconds to initiate the flow calibration process FAN and POWER LEDs flash to indicate calibration in progress Fan is temporarily stopped as part of the calibration process The system will reset and revert to normal operating mode when flow calibration is completed Pressing the SELECT key for longer than 1 second when the unit is unlocked will cause the unit to revert to normal operating mode 6 3 SET UP NOTES The Fan Speed Flow Limits and Flow Sensitivity need to be set for each installation prior to Flow Calibration and testing It is not possible to provide the settings for all possible installations but the following guidelines should assist in the commissioning of the unit 6 3 1 FAN SPEED The Fan Speed should be set as high as possible to achieve the fastest transport time from the sampling point to the detectors this is especially important for longer pipe lengths and for installations that must conform to the requirements of CEA4022 see Section 9 There is however a balance to be achieved between performance and the units power requirements and reference should be made to the current consumption figures in the specifications prior to setting this value Fan speeds 3 and below should not be used for standard configurations 6 3 2 FLOW SENSITIVITY This setting determines the syst
6. RTIGHT SEAL SOLVENT ADHESIVE SHOULD NOT BE USED FOR THIS JOINT 5 2 FIXINGS The normal fixing methods are pipe clips saddle clamps or even tie wraps Fixing centres are typically 1 5m apart 5 3 END CAP The end of the pipe is terminated with a cap with a hole drilled in its centre If the end cap is not used then practically no air will be drawn through the side holes If the end cap does not have a hole then the contributions from the side holes will tend to be very unbalanced 5 4 BENDS Bends are either 45 or 90 degrees For the 90 degree bends it is very important that swept bends are used and not sharp elbows as this will introduce unacceptable pressure losses and significantly increase the response times from holes beyond the bend 5 5 HOLES The sampling pipe is perforated with sampling holes and can either be pre drilled or drilled in situ Care should be taken to avoid swarf entering the pipe Always blow compressed air through the pipe after drilling to clear any debris before final connection to the equipment In standard configuration with pipe hanging from ceiling the holes should be placed underneath so the smoke can easily rise up into the hole 5 6 EXHAUST In most installations the exhaust should be left open but there are some circumstances when it may be necessary to connect pipe to the exhaust port to divert the exhaust away from the location of the unit e g to reduce noise reduce risk of interf
7. TECTORS The following detectors have been independently tested and certified for use in the ASD2 unit The table shows the limits which should not be exceeded if the installation is to conform to this requirement All figures are based on the standard configuration shown in Section 5 8 with maximum 50m pipe length per channel and fan speed of 9 Detector Brand Detector Model Sampling Hole Limits per pipe po XPOS Optical 1x8mmEndHoe po DISCOVERY Optical 1x 8mMEnd Hole SCC DISCOVERY Optical 2x 5mMHoles _ po ZOO AX BmMMENd Hole po BOD x BmMMENd Hole po PT BX AmMMHOles O po POG KX AMMHOles Po PAX BmMENd Hole pO x BmMENd Hole po EME x SmMHOles O po 251 PINNACLE 8x 3mm 6mm End Hole 1 Using standard sensitivity alarm level of 55 2 Using pre alarm sensitivity level of 45 3 Using high sensitivity mode 4 Using standard sensitivity alarm level of 2200 5 Using high sensitivity alarm level of 1800 6 Using alarm level 3 SIGNIFICANT REDUCTIONS IN PIPE LENGTH MAY ALLOW THE FAN SPEED TO BS BE REDUCED AND OR NUMBER OF HOLES INCREASED RESULTS OF SUCH CHANGES MUST BE VERIFIED WITH THE PIPE SIMULATION UTILITY OTHER DETECTORS AND PIPE LENTHS UP TO 100m MAY BE USED IF CEA 4022 CERTIFICATION IS NOT A REQUIREMENT DESIGNS SHOULD BE VERIFIED WITH THE PIPE SIMULATION UTILITY TO ENSURE PERFORMANCE IS SUITABLE FOR APPLICATION 10 PROBLEM SOLVING PROBLEM POSSIBLE SOLUTIONS Power light flashing Ensure supply to BAT
8. TERY connector within limits Fan not running BAT FUSE correctly seated in socket and fuse not blown Fan running OK boards Flow HI LO light on Ensure sampling pipes correctly installed lid fitted and box fully sealed Ensure filters not blocked Section 8 Ensure flow calibration procedure has been carried out Flow reading on Decrease Flow sensitivity setting and re calibrate air Bargraph display moves flows Section 6 2 erratically Flow reading on Increase Flow sensitivity setting and re calibrate air flows Bargraph unresponsive Section 6 2 to broken blocked pipes Detector s Ensure sampling pipe installed correctly and undamaged unresponsive to smoke Section 5 Ensure that holes and pipe length do not tests exceed limits for detector Section 9 Ensure that recommended baffles are fitted Section 4 1 Ensure that recommended test method is used Section 7 2 11 SPECIFICATIONS Number of Detectors f 2 Analogue Addressable or Conventional not supplied Filtration Cartridge dust particle filter Thermal device high and low thresholds 10 Flow Monitoring element bar graph indication Loop or relay fault reporting Supply Voltage 18 30V DC 24V DC Nominal 350mA 24V DC with no aspirating pipe See table below for typical Currents Fan Speeds Up to 100 metres per pipe 50m per pipe for CEA 4022 dependant on detector type amp application Environmental Protection IP65 with exhaust fitted IP53 without
9. ble through a seal it is necessary to make a small hole in the centre of the seal with a pointed implement e g small screwdriver and then force the cable through the hole into the box The small hole will expand to accommodate any cable diameter from 4 to 10mm and then provide an airtight seal In order to gain access to the main circuit board for connection of the wiring it is necessary to remove the display detector mounting board which is held in place by the clear top cover Care should be taken when removing the board to ensure that the ribbon cable on the underside is not strained The ribbon cable may be removed from the connector on the underside of the board to allow the board to be fully removed WARNING TO PREVENT RISK OF ELECTRIC SHOCK OR POSSIBLE INJURY FROM THE ROTATION OF THE HIGH PERFORMANCE FAN THE SYSTEM SHOULD BE ISOLATED FROM THE SUPPLY WHEN THE TOP COVER IS REMOVED All connections to the main circuit board are to pluggable terminals that can accommodate wire sizes up to 2 5mm 3 1 FIELD CONNECTIONS BATTERY BAT LOOP IN LOOP OUT 24V OV FUSE FAULT 1 FAULT 2 NO COM NC NO COM NC 3 1 1 BATTERY The ASD2 unit is designed to run from a nominal 24V DC supply The supply should be connected to the 2 way BATTERY connector on the main circuit board ensuring that the wires are correctly orientated It is recommended that the wires should be a minimum size of 16 x 0 25mm 18AWG or larger if t
10. e installation follows with examples of standard configurations and should contain all the information required for simple installations based on the standard configurations REFER TO THE PIPE INSTALLATION MANUAL AVAILABLE AS OPTIONAL CD LS ROM OR DOWNLOAD FROM FIRETRACER COM FOR DETAILED INFORMATION AND MORE PRACTICAL EXAMPLES THE ICAM PIPE SIMULATION UTILITY AVAILABLE AS OPTIONAL CD ROM OR DOWNLOAD FROM FIRETRACER COM SHOULD BE USED TO CALCULATE TRANSPORT TIMES DILUTION EFFECTS ETC FOR ALL INSTALLATIONS BEYOND THE SCOPE OF THIS GUIDE Use 25mm or Red ABS pipe with sampling point holes drilled along its length The pipe run is terminated with an end cap that has a hole drilled in its centre The position of each individual sampling point should be in accordance with the rules for the positioning of point detectors It is important to note that the concentration of smoke on an individual sample point will be diluted by the clean air from the other sample points and the end cap hole 5 1 PIPE SPECIFICATION For CEA4022 compliance the pipe should be Red ABS to EN 50086 1 Crush 1 Impact 1 Temp 33 with a nominal diameter of 25mm or The sample pipe is normally supplied in 3 metre lengths and is cut as required and joined by solvent welded sockets permanent or socket unions removable THE ASD2 INLET PORTS ARE TAPERED TO ALLOW A PUSH FIT OF THE LES SAMPLING PIPE THE PIPE SHOULD BE CUT SQUARELY TO ENSURE A GOOD AI
11. ems responsiveness in reporting blocked sampling points or broken pipes The number of sampling points and fan speed are the main factors to consider for this setting The following table shows typical settings for a variety of standard fan speed hole quantity combinations Other speed hole combinations should be verified by testing during commissioning 6 3 2 1 TYPICAL FLOW SENSITIVITY SETTINGS PIPE SETUP RECOMMENDED FLOW all 50m lengths unless otherwise stated FAN a cee eee 13 x 3mm Sampling Holes 1 x 6mm End Hole 8 x 3mm Sampling Holes 1 x 6mm End Hole 4 x 3mm Sampling Holes 1 x 6mm End Hole 1x 5mm Sampling Hole 1 x 5mm End Hole 1 x 8mm End Hole 1x 8mm End Hole 10m Pipe 7 TESTING TESTING SHOULD ONLY BE CARRIED OUT BY QUALIFIED PERSONNEL BEFORE UNDERTAKING ANY TESTING ENSURE THAT THE PROPER AUTHORITIES HAVE BEEN INFORMED AND THAT THE UNIT HAS BEEN ISOLATED FROM THE FIRE CONTROL PANEL IF NECESSARY TO PREVENT UNWANTED ALARMS 7 1 DETECTORS With the unit powered up and top cover removed the detectors can be tested for functionality using methods described by the manufacturer e g aerosol spray etc 7 2 SYSTEM The installed system must be checked with the top cover securely fitted As a minimum smoke should be introduced to the furthest sampling point from the ASD2 unit on each branch of the pipe The choice of smoke source is dependant on the installation but in all cases the smoke must be present for the duration
12. ephone 44 0 1792 455175 Fax 44 0 1792 455176 e mail address web site www zeta alarms co uk ASD2 Manual CE Issue 10 0 Part No 09 0102 10
13. erence deliberate obstruction improved environmental protection etc Pipe of the same specification as the sample runs should be used and its length limited to a maximum of 10m to avoid significant reduction in the air flow Care should be taken to position the new exhaust outlet where it cannot be accidentally or deliberately blocked 5 7 FILTERS replacement order code FL55 before entering the detector The sampled air is passed through a 2 stage filter chamber As standard the filtration should be sufficient for all but extremely dusty conditions where a Harsh Environment Filter order code FLU1 3 4 FLU2 25mm should be fitted between the unit and the first sampling point 5 8 STANDARD CONFIGURATION Drawing not to scale ASD2 with 2 pipes Pipes should be balanced i e equal length and equal sizes number of holes The use of additional bends as described in Section 5 4 will have a minimal effect on performance i e response time THE PIPE SIMULATION UTILITY SHOULD BE USED TO VERIFY THE BS PERFORMANCE OF ANY NON STANDARD CONFIGURATIONS OR WHERE UNBALANCED PIPE RUNS ARE REQUIRED SEE TABLE IN SECTION 9 FOR CEA 4022 HOLE AND PIPE LENGTH LIMITS FOR CERTIFIED DETECTORS 6 SETUP 6 1 DISPLAY FUNCTIONS Each channel has the following function LEDs 4 C COCOCCCCO 0 1 2 3 4 5 6 7 8 BARGRAPH of AIRFLOW SPEED o 0 0 23 4 PK uf Lo AIRFLOW OK HIGH AIR
14. he supply is further than 5m from the system A ferrite core is provided for EMC compliance This should be fitted to the supply wiring as shown above The power requirements are dependant on the fan speed see table in Section 11 1 for details 3 1 2 LOOP IN LOOP OUT The Loop In Loop Out terminals are connected to the detector terminals on the display board This provides a convenient means of connecting the loop circuit wiring to the unit and allows the display and detectors to be removed during servicing by simply disconnecting the ribbon cable The loop circuit wiring can also be connected directly to the detectors if required 3 1 3 FAULT 1 FAULT 2 In the event of a fault condition one or both of the Fault relays will change state The terminals provide for Normally Open NO or Normally Closed NC operation and these can be wired using terminating resistors to simulate a zone fault on a conventional control panel or via a loop interface module for an analogue addressable panel ES NO NC REFERS TO THE UN POWERED STATE OF THE FAULT RELAYS UNDER NORMAL NON FAULT CONDITIONS NO IS CLOSED AND NC IS OPEN ES PLEASE NOTE THAT THE FLOW SENSOR IN THE CHANNEL 1 POSITION WILL OPERATE THE FAULT 2 RELAY AND VICE VERSA 4 POINT DETECTORS Ensure that the selected detectors have sufficient sensitivity for the application See Section 5 below for further details of how dilution affects detector sensitivity If the installation
15. ill produce a zone fault BATTERY 24V BATTERY 0V FAULT 1 KAIS comh cpe FAULT 2 LOOP IN LOOP IN 4 3 2 SERIES OF ASD2 UNITS ON A CONVENTIONAL DETECTION CIRCUIT Schematic shows first and last units Zone circuit wiring returned from last unit to first via both fault relay contacts in each unit and terminating resistor fitted to first unit as shown Flow fault condition in any unit will break the connection to the terminating resistor and indicate a zone fault without affecting the operation of the detectors themselves FAULT 1 not S comb S ncp e T2 8 T FAULT 1 8 NO COM NC TERY 24V TERY OV TERY 24V TERY OV 4 3 3 ASD2 WITH ANALOGUE ADDRESSABLE DETECTORS Fault relays connected to loop via interface modules BATTERY 24V BATTERY 0V FAULT 1 Nop COM NC FAUL NO COM NC 5 PIPE INSTALLATION A simple guide to pip
16. is to be in accordance with the CEA 4022 certification then the detector must have been tested for use in the system Please refer to the list of approved detectors in Section 9 4 1 BAFFLES Due to the large variation in the sizes and shapes of point detectors it is necessary to fit baffles to the ASD2 to ensure that the sampled air flow is directed towards the detectors Each baffle is shaped to match a particular model range of detectors and simply clips into position in the slots provided in the transparent lid 4 2 DETECTOR INSTALLATION A pair of Conventional Analogue Addressable Point Detectors are mounted on the display mounting board using the screws provided The detectors can then be wired to either the local terminals in the centre of the detector mounting points then to the loop conventional circuit via the Loop In Loop Out terminals on the main circuit board or directly to the loop zone circuit with the wiring passing through the cut outs on the display mounting board 4 3 WIRING EXAMPLES The following examples show typical installations for conventional and analogue addressable detectors KEY 1 Display Detector Mounting Board 2 Main Circuit Board 3 Ribbon Connector 5 Detector 1 6 Detector 2 7 Terminating Resistor 8 Loop Interface Module 9 Addressable Loop Conventional Circuit 4 3 1 ASD2 WITH CONVENTIONAL DETECTORS Terminating resistor wired across both fault relays so flow fault in either channel w

Download Pdf Manuals

image

Related Search

Related Contents

OWNER`S MANUAL  V7 1 Year Extended Warranty for Product Value up to EUR 3000 / £ 2400  Annexe A.p65 - KNX Association  GEOPOINT LCD  Planning des activités_mars 2015.xlsx  EC2000取説 - ロックダイナミクス株式会社  The RDI Broadband ADCP and Transect User Notes for Logging  Samsung RS7527THCSP - SBS,  NORMA TÉCNICA PARA LA ATENCIÓN AL RECIEN NACIDO  manual genesis 282 352 282 tle 352 tle it gb de fr es  