Home
        Instruction Manual for VB3 i VB5 series
         Contents
1.                                                                                                                                                                                                                           dy  O  A  J00  FWD          O O  167 0  180  0       B V5 series 11 55KW       247 9          260  0       VB3 V5 VB5 series inverter     Unit  mm                                                                                                                                                                                                                       THINGET                                  7 mos                            The details of the dimension                  Unit  mm     13    VB3 V5 V BS series inverter    1  a    L    7  4011    BE     V54015  Wd     V54018      D   V542    V5     V 4000         ae     V54045    V5     V54055         1 5  Choose fittings     gt  Braking Resistor    1 5 18 5KW series inverters have braking unit inside  not include VB5 21P5  If you have the requirements of power  consumption braking  choose braking resistor  unit according to table 1 1  22KW and above inverters need to connect    braking unit  The braking resistor connection method is shown as below            Brake Resistor    Figure 1 1 Wiring of inverter and brake units    Each power level inverter is corresponding to the following connection method                                                                                                               
2.                       a    Preset freq enabled Run at preset    frequence f      N    Low pnort  go                     y Common    operaton f    Fig  3 1 Running state of V3       Except    Jog running     other 4 kinds running modes can be enabled by multi freguency setting method  Besides     PLC    99 66 99 66    running        multi speed running      common running    can be used as traverse frequency     3 2  Use the keyboard    3 2 1  Keyboard layout    Start  speed  stop  brake  running parameter setting and control of the peripheral can be performed by inverter   s operation  29    V5 series inverter    panel and control terminals  operation panel is shown in Fig 3 2                                         VB3 0 4 0 75KW VB5 OPU 01 V5 OPU 03   C 06061 rmn C nnn  0 O0 OQ I  JL AL ILI JLILILI                                           saa THINGET  n THINGET                                                                         JOG    FWD REV                                   Vt N     MENU    ENTER  ESC DATA   gt  gt     y STOP  RESET                                              Fig  3 2 Illustration of operation panel    3 2 2  Keyboard function    There are 8 keys and 1 analog potentiometer on operation panel and the functions are shown in the following table     Key Name    In operate panel control mode  press this key to run forward    In operate panel control mode  press this key to stop running or return to normal state  Stop Reset uu  when inverter is in error s
3.      Frequency setup  0  Multi i G 1 7   1  Frequency is decide by P0 01       Ten s place of LED  Operating direction selection  0  Run forward   1  Run reverse   2  Decided by operating instructions    Hundred s place of LED  Acc Dec time selection    With the unit s place  ten s place and hundred s place of LED  P8 01   P8 14 defined the running frequency  direction and  Acc Dec time of PLC     Unit s place of LED    0  Multi frequency i  i 1 7  defined by P3 26   P3 32   1  Frequency is set by P0 01   Ten s place of LED  Operating direction selection    84    V5 series inverter    0  Run forward   1  Runreverse   2  Decided by operating instructions  Hundred s place of LED  Acc Dec time selection  0  Acc Dec time 1   1  Acc Dec time 2   2  Acc Dec time 3   3  Acc Dec time 4   4  Acc Dec time 5   5  Acc Dec time 6   6  Acc Dec time 7    4 2 10 Traverse and measure function parameters  Group P9     Traverse operation is widely used in textile and chemical fiber industry  The typical application 1s shown in Fig  5 37   Traverse operation process  First  the drive accelerates to the preset frequency of traverse operation  F6 02  within the Acc  time and then waits for certain time  F6 03   The drive transits to the central frequency within Acc Dec time  and at last the  drive traverse according to the preset traverse amplitude  F6 04   jitter frequency  F6 05   traverse cycle  F6 06  and rising  time of traverse operation  F6 07  until it receives a stopping command and stops
4.      Table 1 1 Braking resistor selection    Braking unit Braking resistor    spe   No  Braking resistor  O    Braking power CW     300 400  200 500    200 500    Built in 100 500       VB3 V5 VBS5 series inverter    EE LIE a  L1   mi       5  Dp 9 p 9    BRU 4045 9600  13 6 9600       Operate panel SONS seat    me panel Suitable Typ Mounting dimension  mm   V5 OPU 01 a 62 75  V5 OPU 03 11 55 71 131       Operation panel extension cable       The frequency inverter will be attached with 0 3m extension cable when out of factory  Besides  we also provide 0 5m  1 0m  1 5m    extension cable     Cable type Length  m        15    VB3 V5 VBS5 series inverter    2 Installation and Wiring    2 1  Installation environment    2 1 1  Environment requirement     gt  Ambient tempeature  It is required to be within the range of  10  C 40  C  The inverter should be derated when the  temperature over 40  C  at the same time ventilation and heat dissipation should be enhanced    Far away from the location with direct sunlight  dust  floating fiber or metal powder    Mount in the location free of corrosive gas and combustible gas    Mount in the location free of condensing  dry bulb and the humidity should less then 95 RH    Mount in the location where vibration less than 5 9m s  0 6G    Far away from electramagnetism interfere source and other electric instruments sensitive with electramagnetism  interfere     VN V V Vv    2 1 2  Mounting location and space     gt  Mount the inverter vertical
5.     Hz    Fi Stopping signal    F3         Phase 1   Phase 2    Phase 2  Operating time Remnant time    Ay   Acc time of stagel A    Acc time of stage2 Az  Acc time of stage3    d  1 Dec time of stage  Fl Freguency of stage  F2 Frequency of stage2 F3 Frequency of stage3    Fig 4 44 PLC start mode 1    Ten   s place of LED  Save at power off   0  Notsaving  The inverter does not save the PLC operating status after power off and restart to operate in first stage    1  Save  Save the operating parameters of PLC operation after power off  including the operating stage  operating frequency  and operating time  The inverter will continue to operate in the mode defined by the ten   s place    Thousand s placeof LED  PLC running time   0  second   1  minute   This unit only valid for the definition of PLC running time  The unit of Acc Dec time durning PLC is running is set by P0 16   Notes  1  This stage 1s invalid when the PLC running time 1s set as 0      2  You can control pause  invalidation  run and others for the PLC process via terminals  refer to group P4 for details      mm  swixwm O  Rem m x      mum   Operating ts  Ranger 00000    mm  swew  Remi e   U   mu  Op  n  nszanl     a OA   MA  esos  sugas O TONU   mm  sugas SSS Rages monn    mum   Operating tie ofstges  Ranger O a   mm  swssm           Rem U e    Wo    M O   o   mu  swowm                    TO ON M   men   Operating tmeofsge6   Rangs 00009                         w  m m T   0    mu   Operating tes  Regn 0   M     
6.     REV           1173  1 111                      FWD REY ALM     HZ Y A  o       5 e      5600    THINGET                   THINGET    THINGET                      V uL   C  MENU    ENTER                                                                         FWD     REV  A                                                         l Power on and Stop status  display running status   FigA initialize  display Fig B the stop parameters Fig  C display the running  the dynamic picture parameters    Fig  3   4 Display during initialize  STOP and RUN  2  Parameters displayed in running status    When the inverter receive the running command  it starts to enter running status and operation panel will display running  monitor parameters  the default parameter is output frequency  b 00 monitor parameter  as shown in Fig 3 4 B  the unit  indicator on the top right indicates the unit of this parameter   Press cS key can display parameter in running status circularly  defined by function code P3 41 and P3 42  While  displaying  press jkjk key to shift to the default parameter b 00  that 1s output frequency  Otherwise  the operation panel    will display the last monitor parameter constantly   3  Alarm information    When then inverter detects a fault signal  the panel will display fault code  the code will flash to catch your attention as  ENTER    shown in Fig 3 5  Press      key to view the relative fault parameters in stopping status  and then press  FT to shift to       fault code dis
7.     Upon unpacking  please confirm that  Check whether the model and the rated values on the nameplate of the inverter are in  accordance with your order  Check if there is any damage occurred during transportation  pleases contact us or the    distributor if you find any missing or damage of the products     In order to use this product correctly  the user who uses the product for the first time must read this manual carefully and    pay close attention to the safety precautions     Please keep this manual properly  hand it to the terminal user and lay it on the place where the operators can read it easily     O Safty Precautions       Confirmations Upon Delivery    Never install an inverter that is damaged or missing components  Doing so can result in injury     Installation    Always hold the bottom of the inverter when carrying it  If the inverter 1s held by the front cover  the main body  of the inverter may fall  possible resulting in injury    Attach the inverter to metal or other noncombustible materials  Fire can result if the inverter is attached to a  combustible material    Install a cooling fan or other cooling device when installing more than one inverter in the same enclosure so that    the temperature of the air entering the inverters is below 45 C  Overheating can result in fires or other accidents     Always turn off the input power _   A before wiring  Otherwise  an electric shock or fire may occur   Wiring must be operated by an authorized person qualified
8.    AINE       VB3 VB5 V  gt  freguency inverter    User manual    Xinje Electronic Co  Ltd   No  INV C 01 20081130 204    2   INDE    VB3 VB5 V5  Series Inverter    User Manual       Table of Contents    Preface    Safty Precautions    Product Introductions    Installation and Wiring    Operation Descriptions    Function Parameters    Fault Diagnosis and Disposal    Maintenance    Communication Protocol    VB3 VBS5 V5 series inverter    This manual includes the basic caution items that you should obey to ensure your personal safety  as well as to protect the  product and the connected equipments  These items are highlighted in the manual by a warning triangle  Please comply    with the essential electric operation  rules that are not indicated in this manual     Installing Precautions      Please comply with these items  incorrect operation may cause the system error working even abnormal        More serious would cause possession loss        Correct Applications      The device and its components can only be used in the applications described in the catalog and the       technical manuals  can only be connected with devices or components from other manufacturers which     gt     have been approved or recommended by Xinje   The products will run normally in the condition of been transported  stored  configured and installed    correctly  been operated and maintained as recommended        Xinje Electronic Co   Ltd    Copyright reserved  Without written authority  please do not
9.    Run forward reverse  dead time  Highest  frequency  Basic  frequency    em  A    Minm    i Factory setting   Change  unit  1    l    0 01HZ 50 00HZ    0 1s 0 1s    X    0 01 Hz 50 00Hz    X    0 01 Hz 50 00Hz    IV Inverter rated X  voltage  2 095    25 00Hz    0 1     1    0 1K  1           oS          V5 series inverter        leton   1  S curve Ace Dec    P0 14 Low speed time of S   10 026    50 0  CAcc Dec time  0 126 20 0   ramp PO 14 PO 15 lt 90        P0 15 Linear time of S   10 0     80 0   CAcc Dec time  0 1  60 0   ramp PO 14 PO 15 lt 90     m e o  1  minute   POI      Acti           060E   O    Poig       Deetiel          01   6000        01   100   O      P0 19 High frequency limit   Low frequency limit     highest 0 01 Hz 50 00Hz X  output frequency P0 06    P0 20 Low frequency limit   0 00Hz     high frequency limit 0 01 Hz 0 00Hz  X    P0 21 Running mode of   0  running at low frequency limit 1  low freguency limit 1  stop    P0 22 V F curve setting 0  constant torque curve 1 X   1  torque reducing curve 1  1 2   order     2  torque reducing curve 2  1 7   order     3  torque reducing curve 3  2 0   order     4  multi segment V F curve    P0 23 V F frequency value   0 00    P0O 25 0 01 Hz 0 00Hz X  P1   P0 24 V F voltage value   0    P0 26 0 0 0  X  Vi  2  2          1   P  V   P0 27 P0 25   P0 07 basic running  P3 frequency  V3    2  Reference frequency parameter  Group P1     X  X  X    Group P1  reference frequency parameter    Minmum Factory setting Chan
10.   2  3  1   8   2 format  no parity check  1 stop bit  8 data bits  2 stop bits  no parity check   4  5  1   8   1 format  even  1 stop bit  8 data bits  1 stop bit  even    6  1   8   1 format  no parity check  1 stop bit  8 data bits  1 stop bit  no parity check   Hundred s place of LED   undefined    Notes when choose Modbus RTU communication mode  you should select digital format 3 6     P3 10 Local address Ranges 07 248    This parameter is used for identify the inverter s address in serial communication     0 1s the broadcast address  If take inverter as a slave  1t will receive the command with 0 as broadcast address and will not  answer the PC   248 1s the address with inverter as a host  If take inverter as host and set P3 10 as 248  it can send broadcast command to  other inverters to realize multi machine     Time threshod for judging    P3 11 Ranges 0 0   1000 0S 0 0S  communication status       When serial port failed and the duration over the reference value  the inverter will judge it as communication fault   When set the value as 0  the inverter will not detect the serial communication port and this function disabled     P3 12 Host PC response delay Ranges 0 1000ms    It refers to time from inverter s serial port receiving and executing the command of host PC to returning response to it     Reference proportion of  P3 13 Ranges 0 01 1 00 1 00  communication frequency    This parameter 1s used for setting the proportion coefficient according to frequency settin
11.   24    P3 42 Display parameters select   0000    FFFF 0000 Lo   42       V5 series inverter    Unit s place  b 25 b   28  Ten s place  b 29    b 32  Hundred s place  b 33    b 36  Thousan   s place  b 37    b 40  Display parameters   0000    4040  selection 3 Ten s place  uni   s pladce   stop  displaved parameter selection  Thousan   s place  hundred s place      run displaved parameter selection    Display    coefficient without unit  JOG REV shift control   0  select JOG to start jog    mode 1  select REV start reverse       5  Function parameters of terminal  Group P4        Group P4  Function Parameters of Teriminal    Minmum Factory Change  Parameter Name Range  setting    P4 00 Function selection of   0  Control terminal free  input terminal X1     Multi step speed  control terminal 1  2  Multi step speed control  terminal 2  3  Multi step speed control  terminal 3  4  Exteral terminal for  forward jog operation  5  Exteral terminal for  reverse jog operation    Acc Dec time terminal 1    Acc Dec time terminal 2    Acc Dec time terminal 3    3 wire operation control  10  Coast to stop  FRS   11  External stop command  12  DC injection braking  command DB  13   Inverter running  prohibit  14   Frequency ramp  up  UP   15  Freguency ramp down   DOWN   16  Acc Dec prohibit  17  Reset signal   clear  fault   18  External fault signal  normally open input          V5 series inverter eee series inverter    P4 08    P4 09 UP DN   rate 0 01    99 99Hz s    P4 10    input term
12.   External pulse reference   13  RS485    VI     External pulse reference   14  VI c  CI Increase Decrease key reference  Digital setting P0 02  15  VI CI    Increase Decrease key reference   Digital setting P0 02  16  MAX  VI  CD   17  MIN  VL  CD   18  MAX  VI  CI  PLUSE    19  MIN  VI  CI  PLUSE    20  VI  Clis active  VI is priority    Parameter initialization Range  LED unit s place 0 2   locking up LED ten s place 0 2    LED uni   s place  0  All the parameters are allowed modifying   1  Only P3 01 can be modified   2  Only P0 02 and P3 01 can be modified   LED ten s place  0  Disabled  1  Restore to factory setting    2  Clear fault record  Notes  1  The factory setting of P3 01 is 0 and allow all the parameters to be modified  After modifying this parameter   please set it as 0 if you want to modify other parameters  Also    you can set protective grade      2  P3 01 will be changed to 0 automatically after restoring to factory setting     Parameter copy Range  0 1 2    0  Disabled   1  Parameter up load  Up load the parameters from inverter to remote opration panel    2s Parameter download  Down load the parameters from remote operation panel to inverter   Note   This function is still in developing     Auto energy saving function Ranges 0 1    0  Disabled  1  Enabled  Inverter can regulate output voltage through detecting load current to achieve energy saving when the motor running    without load or with light load  Auto energy saving 1s suitable for the applicatio
13.   Max    freguency 20KHz     preset counting value   P4 23 9999 1  arriving   Mid counting value   0 P4 22 1  P4 23 E   arriving    Overload pre alarm   20     200  1    P4 21 0 1KHz 10 0KHz    P4 22          130   P4 24    detection level        m    un  A  c  un    Delay time of over load   0 0   20 0s  P4 25       pre alarm    6  Protective function parameters  Group P5     Group P5  Protective function parameters    Minmum Change  Parameter Name Range Factory setting  unit  P5 00 Motor overload protection   0  Inverter locking output 1 X  mode selection 1  Disabled  P5 01 Motor s overload   20   120  1 100  x  protection coefficient    P5 02 Protection of over load at   0  Disabled l 1 X  P5 03 Over voltage point at stall 380V  120   150  1   P5 04 Auto current limiting   110     200  1  150  X    46       V5 series inverter    Frequeny decrease rate   0 00    99 99 Hz s 0 01 Hz s 10 00Hz s  when current limiting    Auto current limiting   0  Disabled in constant speed   1  selection 1  Enabled in constant speed  Note  Enabled at Acc Dec  setting of the restart after   0  Disabled 1  power off 1  Enabled M  Holding time of restart 0 1s  after power off  mo  Auto reset times of fault 0   10 1  0   No auto reset  function  Note  overload and  0 1s    overheat have no recovery    function     P5 10 Auto reset interval of fault 0 5    20 0s oas       CE    7  Fault recording parameter  Group P6   Group P6  Fault recording parameter    P6 00 Previous fault record Previous faul
14.   P4 23 are the additional definition of No 12 13 functions in table 4 6     Preset counting value arriving  It defines after X1 receives the relay or OC  bi direction open collector output terminal  will  output a signal     For example  as shown in Fig  4 28  when the eighth pulse signal 1s received by terminal Xi  OC outputs an indicating signal  and F7 33 8 at this time     Mid counting value arriving  When Xi receives the number of pulse F7 34  OC or the relay will output a signal which will  last until preset counting value arrives     As shown in Fig  4 28  when Xi receives the 5th pulse  the realy outputs an indication signal  It lasts until X1 receives the  8th pulse  At this time  P4 23 5  The mid counting value will be disabled if it is bigger than preset counting value     X1 Input 1 2 3 4 5 5 T a 9    OC Output i    Relay Output        Fig 4   28 Preset counting value arriving and Mid counting value arriving    Overload pre alarm detection level Range  20   200    130            PADS     Overload pre alarm delay time Ranges 0 0   20 0S   55    If output current over the detecting level set by P4 24 continuously   Actual detecting current level     P4 24 X inverter s rated  current   Bi direction open collector will output available signal after the delay time set by P4 25 refer to Fig 4 29 and  P4 11 for details      Output current          F4 24 detection level        P425 time      P425tme  Time       Overload pre alarm active    U       i 1    enable          
15.   Ta i Ts   T6    T   LJ LI Li LI LI LA LM   PLC cycle completion indication So00ms  Sea    PLC phase completion mdic ation  Fig 4 40 Simple PLC diagram  In Fig 4 40  a  a7  d  d are the Acc Dec time of different stages and they are set by Acc Dec time parameters P0 17 P0 18    and P3 14   P3 2  Fj F   TT  are the running frequency and running time and they are set by P8 01    P8 14   Range LED    Unit s place   0 3  Ten s places 0 1       L i lecti  Simple PLC operation mode selection Hundred s place  0 1     Thousand s places 0 1       Unit s place of LED  PLC operation mode selection  0  Disabled     1  Stop after operating for one cycle  As shown in Fig 4 41  If inverter stop after single cycle operation  running command  should be give once again to start the inverter          F6   Simple PLC operation Fi  d  F2 aj i NFZ  ao  Fs   PN  Fi   A TR   d    o T   ds as   E  E   tA F f i            Fa f i      L Ix  123  Ta  Ta c Ts T6  17 1    RUN command     ODO    Fig  4 41 PLC stop mode after single cycle of operation    2  Holding at the final value after single cycle of operation  As shown in Fig 4 42  Inverter will keep the running frequency   direction of the last setting automatically after single cycle 1s completed  then it will stop with the reference Dec time if stop    82    V5 series inverter    command is input       Fi   us aj i  r l TR 73 ds    Mag i       INEJ i           i1  Tai 13  T4 i Ts   T6   T3      RUN c     omman d    Fig  4 42 PLC holding mode after 
16.   You should set PO 05 0 0s  P0 200 5Hz  PO 17 lt 0 5S  PO 183 lt 0 5S  P0 20     2 0Hz  P2 0122 0Hz   This function is usually used in the control process of continuous to and for control  If swift turn     around is needed  reduce the Acc Dec time and increasethe lower limit of frequency start frequency   P0 17 lt 0 5S  P0 18 lt 0 5S   P0 20Z2 0Hz  P2 01 22 0Hz       PB 02 Inverter type select range  0  1    0  G type  normal   used in normal situation    1  P type  wind machine water pump   used in wind machine  water pump and other small load situation  Under this mode   power will improve   time  if the machine power is 2 2K W  under P type mode  the power will be 3 7K W  Please note P0 22  should be set as 3     0  before power on  if the pointis short  run theinverter immediately     1  before power on  if the pointis short  run theinverter after cut off the point and connectit again     4 2 13  Factory setting  Group PF     OO  00    V5 series inverter    This parameter can be protect against unauthorized personnel to view or modify function parameters   If user s password don t need  you can set 0000 as its value       ENTER      If usre s password is needed  input four figures as password  then po IS to confirm  the password will be valid    immediately     MENU    Modification Press key to validate password  with correct password you can enter parameter editing status  After       selecting PF 01  PF 01 0000     input new password and press to confirm  then the pas
17.  3 12 Procedures of starting the driver for the first time    36    4 Function Parameters    V5 series inverter       4 1  Function parameter table         O           X        66 sk       Parameters can be changed while running  Parameters can not be changed while running  Parameters can only be read  user can not changed    1  Basic running parameters  Group P0     Group P0  Basic running parameters       Parameter    P0 00    P0 01    P0 02    P0 03    P0 04    P0 05    P0 06    P0 07    P0 08    P0 09  P0 10    PO 11    PO 12  PO 13    Control mode   0  V F control  1  open loop vector control    setting   0  Analog potentiometer 1n the    selection    Freguency            mode panel  1  Increase Decrease key  2  digit setting 1  via keys on the  panel  3  digit setting 2  via terminal  UP DOWN    digit setting 3  via serial port    VI analog input  VI GND      CI analog input  CI GND      Pulse input  PULSE     Combined setting mode  refer  to P3 00     Running frequency   PO 19  in digit mode High frequency limit     P0 20 low  frequency limit   command   0    Running Running frequency via    selection operation panel control  1  Teminal control   2    Unit s place   0   l  jog reverse via panel    serial port control    Running direction    setting jog forward via panel    Ten s place     0  permit reverse       1  prohibit reverse    voltage    for torque boost freguencyPO 07  1  automatical    Carrier freguency 1 0K    14 0K  Acc Dec direction se   0  linear Acc Dec 
18.  BITO  stop indicate  0  Stop  1  Run 1  Run  BIT1  1  low I  m 0  normal  BIT2  RAM eis eer indicate l  forward  0  reverse  BIT3 poete rere Ree       BIT3 jog indicate 1  jog   none        00000 jog  0  none  Monitor inverter s BIT4 close ails lop contactor  Y eei pene control selection  1  close loop  0  none   status BIT5 traverse mode a Gein ka A   BITS traverse mode running flag  1  traverse  0  mone 1  traverse  0  none    03H  n BIT6 PLC running   BIT6 PLC running flag  1  PLC running   0  no 1  PLC running   0  no  BIT7 Multi  tma sa k EA running flag of terminals  1  Multi speed  0  none  BIT8 Common running   BIT8 Common running flag  1  common running  0  no 1  common running  0  no  BIT9 Main na s Ganda TI from communication interface  1  yes   BIT10    BIT10 Analog input from main frequency  1  yess 0  MO input from main frequency  1  yes  0  no  BI111 porn P TT command from communication interface  1  yes  0  no  BIT12 Password   BIT12 Password protection for parameters  1  yes  0  no 00000000  for parameters  1  yes  0  no    2102H Read inverter  s reference frequency             Read data from  function  code  03H     Write data to    Bit3  X4    210CH    GGnnH     GG  Group No  of Inverter responses to the data  function code nn  No  CWhen use Modbus address  the nn must be turned into hex   function code     GGnnH       GG  Group No  of Data be wrote in the inverter  function    code  06H     function code nn  No   When use Modbus address  the nn must be tu
19.  Feedback  corresponds to   corresponds to  min reference   min reference    nun max    mun max  reference     reference reference reference   1  Positive regulation feedback  2  Negative regulation feedback    Fig  4 36 reference and feedback curve    P7 10 Proportional gain KP Ranges 0 000 9 999    P7 11 Integral gain KI Ranges 0 000 9 999  P7 12 Sampling cycle T Range  0 01   10 00S    The bigger the proportion gain KP  the quicker the response  while too bigger of it may lead to surge easily        As only with proportiaon gian KP  deviation can not be eliminated  integral gain KI can be used to to form PI control to  eliminate the deviation  The bigger of the Ki  the quicker the response of changing deviation  while too big of the K1 may lead  to surge easily    sampling cycle T 1s the sampling cycle of feedback value PI regulator calculate once in every sampling clcle  the longer the    cycle   the slower the response     ras Ranges 8020006 2006     The max deviation value of close loop reference is shown in Fig 4 37  if the feedback value is within this range  PI regulator will stop    operation  This function 1s useful to improve accuracy and stability of the system     V5 series inverter    Reference     Feedback Value    4    m  FEE CENE PO AA A Oa 4    Output frequency                           Limits of deviation Preset frequency  Ime  Output frequency i  Tine T          Time PA ii  Holding time of preset frequency  Fig 4 37 Limits of deviation Fig 4 38  close loo
20.  MEE 15  PAY y D E                                                               16  2 3  Wiring OF main CIFCUIE terminals  e                                                                                16  Pos MR S I RP m k                               e 16  223 2  Terminal assienment and description s easi sex Oed eG ad tie aru Ernst 17  2 4  Basic ur M Rl PR                                                                                   18  2 5  Setting and wiring OF control CIECUIL     asiste te t   bI VERE poh  nka kos KS anka v ka 18  2 5    Position and function of terminals and jumpers on control panel                       esssessessseseeeene nennen nnne nnne 18  245 2  Description or terminals on control patiel iiseossobsoesat ime d insu gusce oar enixe lob o ad ks is En cu eoa Se use EO NK nn 20  2 5 3  Analog input output terminal WIriNg           cccccecccccscccccceccecceecccceeeeeeseseeesseseeeaaeaeeeeeeeeeeeeeeeeeeeeeeeseeeeeeessssseseeeaaeeeeeeeeeeeeeeeeeeeees 22  2 5 4  Connection of communication terminals           ccccccccccecceeseseeenseneseeeeeeeeeeeeeeeeeeeeeeeeeeeeseeeeeeeeaeseeeeeeeeeeeeeeeeeeeeeeeeeeseeeeeeeeeesaaas 23  2 6  Mounting guide according with EMC requirement        sssssssssssssssosseeccssssssssseecossssssssseecssssssessesecessssssssscccccsssesssseccesssssssseeesss 24  PA ors nre Ge  SE o a mE 24  20 2 Local wirmno and SS TOM NEN 23  JOPERATUNGINSINUGTIONOS ciii aditnr EFI EU RES pinu Z RK o nu k SERLO UM I EFIE END IS CES DNE 27  3 
21.  a slave to communicate with the marter  such as PLC and PC  which has the same communicatin  port and protocol  also  user can use a inverter as the master to communicate with several inverters produced by our  company via RS485 port to realize multi machine linkage  Besides  you can connect the RS485 port to remote keyboard to  realize remote operation     This inverter support MODBUS RTU  the following 1s the particular instruction for the inverter s communication protocol     7 2  Instruction of communication protocal  7 2 1  Communicating mode    Inverter as a slave    R5232    232 455  Adapter  R5455    R5232    252 455  Adapter    Or Master  PC                  ingle master and multi slave ingle master and multi slave    Fig 7   1 Networking diagram of inverter    Multi device linkage       Fig 7 2 Networking diagram of multi device linkage  7 2 2  Communication modes    The inverter can be used as both master and slave in RS485 net  If 1t 1s used as a master  1t can control other inverters made  by our company to realize multi machine linkage If it is used as a slave  PC or PLC can be set as a master to control it  The  concrete communication modes are shown below     1   1  The inverter 1s a slave in the network  It communicates in    point to point  mode  The inverter will not response    to the command sent by the master via broadcast address     95    V5 series inverter     2  The inverter is a master in the network  the slave will not response to the command sent
22.  by the inverter via broadcast  address     3  Users can set the inverter s current address  baud rate and data format by using the inverter s keypad or through the  serialcommunication port      4  The drive can report the current fault information when polled by the master     7 2 3  Mode of communication port    RS485  asynchronous  semi duplex  Default  Ibit of start bit  8 bits of data bit  1 bit of stop bit  9600bps  See Group P3 09    P3 12 for parameter settings     7 3 Modbus RTU communication protocol    7 3 1  Structure     1   5   2 format  None   t    1  iss       St Stop  m 1 2 3 4 5 6 i top   POE  bat bit bit     1   58   1 format    Odd     t   T Stor  bit       5   1 format  Even     sta   E i m       S  2 mi H o   2 3 d J o i Even top  bit bit     1   8   1 format  None     Start   A     Stop  i 1 P  3 4 6 T    oF  bit bit    7 3 2  Communication information             Star  bit   1       1  RTU mode     07 i 00 N 8 bit data  N cB  Max t bit    Keep the time no signal  gt  10ms       96    V5 series inverter    2  Communication address     00H  broadcast for all the inverters  broadcast    01H  communicate with the inverter addressed 01   OFH  communicate with the inverter addressed 15  10H  communicate with the inverter addressed 16    By parity of reasoning             max can reach 254  FEH   3  Function code and Data     03H  Read data from registers  can read several registers with the numbers less than 31 and only can read the data in the  same group 
23.  control panel jumper position    1 5KW VB   series single phase inverter jumper position    19    VB3 V5 V BS series inverter       Fig 2   4  b  control panel jumper position  1 5 3 7KW VB   series three phase inverter jumper position       Fig 2   4  c  control panel jumper position    5 5   7 5KW  VBS5 series three phase inverter jumper position       Fig 2   4  d  control panel jumper position    11 55KW V5 series inverter jumper position       Fig 2   4 Ce  control panel jumper position  The position of terminals and jumpers on control panel are shown in Fig  2 4  the function descriptions of terminals are shown in  Table 2 3 and the function descriptions of jumpers and their setting method are shown in Table2 2  Before running the inverter   make sure terminals wiring and jumpers setting have been done  more than 1 mn    cables are recommended to use     Table 2 2 Function of jumpers    1   2 connect  External power supply  Pulse output terminal    2    3 connect      Inverter s internal   External power supply    DO power selection       24V power supply    20    Analog output    terminal AO output    CI current voltage    VB3 V5 VBS5 series inverter          2 connect   4 20mA   AO    terminal outputs current signal    2   3 connect  0 10V  AO terminal  outputs voltage signal  1   2 connect   V side  0   10V voltage    signal    input modes selection  2    3 connect   I side  4 20mA       current signal    2 5 2 Description of terminals on control panel    1  Functio
24.  copy  transfer or use this document and its content  Anyone who disobeys this    should take responsibility for the loss     Obligation Declare  We have checked and confirmed that the contents in this manual were compatible with the hardware and software described   Since mistakes are hard to avoid  we cannot promise total accordant  This manual is subject to change without notices   2010 01    VB3 VBS5 V5 series inverter       PREFACE NE naan sact ea cea E E E 1  SAFETY PRECAUTIONS sicace asi ceacuaestanstansascnenensehubustssuswassssasaeatunens deuensdsnpasensauiseuaysesunwasedaateviensansneeus 2  1 PRODUCT INS ERUC NON  sta  i av  nt  itnn  sralsrn  ri tecesneaneussenstwunscuauauucaniectanassncecusdsewecancanaueceticsaunacaseanes 6  1 1  Product OV OR VICW PIT ETE DE 6  1 2  Product technical specilica 100  ssssis   ci I                 7  1 3  Produ  tappe  rancs  s isi  asp  s     sk  si k  sok vn K va nn van   9  FA Product dlIMENSIOM si   eska   da a sa sa sana  n   ov   a  ov 11  1 5  Choose DNES  k   v  nok                                                                                                        13  2 INSTALLATION AND VVIRING  s s   i neb  nns cio kn VENEREM xi in   i sin fo ik non nn nn CENE ES ES 15  2 1  Installaton environ eT Essenis                                                                    15  Zeb o EnIFoBIIC BE TOUT CRIT os ois o Ro A 15  251 2  Mounting location and SPACE ERN RR                       15  Zele NO AMT ai ECIHOVIBIP osn o o
25.  in Fig 4 5 as  3   where the changing rate of output frequency increases for 0    Linear time of S ramp is shown in Fig 4 5 as  2   where the changing rate of output frequency is constant    High speed time of S ramp is shown in Fig 4 5 as  D  where the changing rate of output frequency increases from 0  High  speed time   100      P0 14     P0 15    Notes S ramp Acc Dec mode is suitable for the start stop of elevator  conveying belt  conveying load and so on     P0 16 Acc Dec time unit Ranges  0 1    This function defines Acc Dec time unit   0  second   1  minute   Notes  1  This function is active for all the process of Acc Dec except jog running    2  Select second as time unit is recommended     Acc time 1s the time taken for the motor to accelerate from 0 Hz to upper limit of frequency  as t  in Fig 4 6  Dec time 1s the  time taken for the motor to decelerate from upper limit of frequency to 0 Hz  as t  in Fig 4 6     oT    V5 series inverter    Output frequency    Upper imit  of frequency         4            lt    h t2    Fig 4 6 Acc Dec time    Note   1 This series inverter defines seven kinds of Acc Dec time  Here only defines Acc Dec time 1  Acc Dec time 2 7 are  defined in P3 14 P3 25      2 Minute and second as the time unit of Acc Dec time 1 7 can be selected via P0 09 and the default unit is second     Upper limit of frequency Ranges lower limit of frequency max output frequency 50 00Hz  Lower limit of frequency Ranges 0 00Hz upper limit of frequency 0 00HZ    
26.  in electrical work  Otherwise  an electric shock or  fire may occur     Make sure to ground the ground terminals  Otherwise  an electric shock or fire may occur     Always check the operation of any emergency stop circuits after they are wired  Otherwise  possibly result in    injury   user responsibility for the wiring     Never touch the output terminal directly by your hands or let the output terminals to come into contact with the  inverter case  Never short the output terminals  Otherwise  an electric short or ground short may occur    Never touch the internal circuit or the zero component until power off and the charge indicator is off as    there may still be high voltage inside the AC motor dirver        VB3 V5 VBS5 series inverter    Confirm that the voltage of the main AC power supply satisfies the rated voltage of the Inverter  Injury and fire    may occur if the voltage is not right     Do not perform voltage withstand tests on the Inverter  Otherwise  semiconductor elements and other devices    can be damaged    Connect braking resistors  Braking Resistor Units  and Braking Units as shown in the I O wiring examples   Otherwise  a fire may occur    Tighten all terminal screws to the specified tightening torque    Otherwise  a fire may occur    Do not connect AC power to output terminals U  V  and W   The interior parts of the Inverter will be damaged if voltage is applied to the output terminals    Do not connect phase advancing capacitors or LC RC noise filters 
27.  inverter      Derate according to basic frequency setting    When the basic frequency 1s lower than the reference frequency  please consider duration for the motor so as to avoid    motor s damage caused by overheating    gt  Running at frequency above 50Hz    If running at frequency above 50Hz  besides the increment of vibration and noise  the ranges of running speed of motor    shaft and mechanical device have to be guaranteed  Be sure to make an enquiry first    gt   Theelectro thermal protective value of motor    If the applicable motor is selected as per requirements  the inverter can perform the thermal protection to the motor  If the  ratings of applied motor are not in compliance with the inverter  be sure to adjust the protective value or adopt other    protective measures to guarantee the safe running of motor    gt  Altitude and derate    When the altitude 1s higher than 1000m  the cooling effect of inverter 1s deteriorated because of the rareness of air  deration  must be considered  shown in Fig 0 2 which indicates the relationship between the altitude and rated current of frequency    inverter     lo ut  100     tts       1000 2000 3000 4000   mi    Fig  0 2 The relationship between the altitude and rated    current of freguency inverter    VB3 V5 VBS5 series inverter     gt   Aboutprotection classes    The protection class of V5 F5 series inverter IP20 is reached in the case of status display unit or keyboard     O Note For Scrap       When you scrap the inver
28.  inverter     You can select the command channels via parameter P0 03 or via multi function input terminal  P4 00  P4 07 function 23   24      Warning  The user must debug the system after changing the command channel to make sure it can meet the system    requirement  otherwise device damage and physical injury will happen   3 1 2  Frequency setting channel    In common operating mode  there are 8 channels to set the frequency     keyboard analog potentiometer   Uu and  57  keys on the keyboard     Operation panel function code     Terminals UPIDOWN     Serial port     Analog VI     Analog CI     Pulse terminal  PULSE       Combination    oO   1 QN tn RA U LUH       3 1 3  Running state    There are two running state  stopping and running   Stopping state  After the inverter is switched on and initialized  If no operating command is executed  then the inverter  enters stopping state     Running states The inverter enters running state after it receive the running command     3 1 4  Running modes    V5 inverter has 5 kinds of running modes which can be sequenced according to the priority  Jog running Close loop  running   PLC running Multi step speed running Simple running  as shown in Fig  3 1     0  Jog running    28    V5 series inverter    When the inverter is in the stopping state  it will running according to jog frequency  refer to P3 06 P3 08 for details    after receiving jog running command  e g after pressing ELE key    1  Close loop    If the close loop running fu
29.  min reference    Pmax  Frequency corresponding to  max reference    The relationship between PULSE and reference frequency is shown below            Arm hone   1  Positive  2  Negative  A  gt  Reference Arun  Min reference Pr  n   Frequency corresponding to  of PULSE Amax   Max reference min reference    Pmax  Frequency corresponding to  max reference    60    V5 series inverter    4 2 3  Starting and braking parameters  Group P2     0  Start from the starting frequency   Inverter starts at the starting frequency  P2 01  within the holding time of starting frequency  P2 02     1  Brake first and then start   Brake with DC braking current  P2 03  within braking time  P2 04  and then start at starting freguency    2  Start on the fly   When P2 00 is set to 2  it 1s suitable for repowering after instantaneous power off or restarting after external fault  As shown  in Fig 4 9     AC supply    Off On    Motor speed s       Inverter output  frequency       Fig 4 9 Start on the fly    Notes  1  Starting mode 0  It is recommended in general application or when the inverter drives synchromous motor    2  Starting mode 1  It 1s suitable for starting the motor that is running in forward or reverse with small inertial load   and it 1s not recommended for big inertial load    3  Starting mode 2  It is suitable for starting the motor that is in free stop or for restarting after instantaneous power  off       P201   Starting frequency Range  0 20 20 00Hz 0 50 Hz         me   Holding time o
30.  parameter group by four figures  The parameter values are in hex    which should be changed to binary ones according to the sequency of monitor parameters when using The relationship  between four figures and parameters are shown in Fig  4 17         b 25     b 28  b 33   b 36    b 37     b 40   Fig 4   17 Display parameters selection 2   Refer to P73 for b 09     b 40    Note  A  Thousand s place  B  Hundred s place     C  Ten s place  D  Unit s place  Display parameters 3 Ranges 0000 4040 0001    Ten s place  unit s place  used to set stop status    Thousand s place  hundred s place  used to set running status  Example  When you want to let the inverter display current value in running status and display DC injucetion bus voltage    value  you can set P3 43 0304  You can also press the key cE  view other monitor parameters     Display coefficient without unit Ranges 0 1  60 0 1 0    P3 44  It is used to set proportion value between display value and output frequency of monitor parameter b 14     Display value of b 14   Output frequency of inverter X P3 44    mas   JOGIREV stitt contror mode   Ranges OL    P3 45 is used to select the usage of JOG REV key in the panel  the references are shown below   0  select to JOG  1  selectto REV    4 2 5  Function parameters of terminal  Group P4     P4 00 Function selection of input terminal X1 Ranges 0737  Function selection of input terminal X2 Ranges 0737      RO   Function selection of input terminal X3 Ranges 0737    Function sel
31.  reference    14  V1  CI Increase Decrease key    reference  Digital setting  15  VI  CI     Increase Decrease key    reference  Digital setting   16  MAX  VI  CD   17  MIN  VI  CD   18  MAX  VI  CI  PULSE    19  MIN  VI  CI  PULSE    20  VI  CI none zero 1s valid  VI       priority    Group P3  Auxiliary running parameters    V5 series inverter    P3 01 Parameter initialization Unit s place     locking up 0  All parameters are allowed    modifying  1  Only P3 01 can be modified  2 Only P0 02 and P3 01 can be  modified  Ten s place   0  disabled  1  Restore to factory setting  2  Clear fault record   P3 02 Parameter copy 0 disabled  1  parameter upload    2 parameter download       Note Function is still in developing  P3 03 Auto energy saving   0  disabled  s  P3 04 AVR function 0  disabled  1  enable all the time  2  Disabled in Dec process  P3 05 Gain slip   0    15026    P3 06 Jog operating IM  010   5000Hz    10   50 00Hz     00Hz   01Hz 5      500Hz      P3 09 Communication LED unit s place  baud rate selection  0  1200BPS   1  2400BPS   2  4800BPS  3  9600BPS  4  19200BPS  5  38400BPS       config    LED ten s place  data format  0  1   7   2 foramt  no parity check  1  1   7   1 format  Odd     1   7   1 format  Even      1   8   2 format  None      1   8    1 format  Even    2  3  4  1   8   1 format  Odd  5  6      1   8   1 format  None   When use Modbus RTU  communication mode   please select  data mode 3   6     LED hundred s place     undefined    P3 10 Local ad
32.  reference of 10V corresponds to the    synchronized speed of the motor s max output frequency     P7 02 Feedback channel selection Range  0 6    0  VI  0   10V   1  CI   2  VI 4CI   3  VI   CI   4  Min  VL CI   5  Max  VL CI     P7 04 Feedback filter Ranges 0 01 50 00S    79    V5 series inverter    Both the external reference signal and feedback signal have interferences  while these can be filtered by setting the time constant  of filter  P7 03 and P7 04   the longer the filter time  the better the immunity capability  but the slower the response  on the    contrary  the shorter the filter time   the worse the immunity capability  but the quicker the response     P7 05 Set reference in digital mode Ranges 0 00   10 00V 0 00V    If P7 01 Q the value set by P7 05 will be as the reference of close loop control system  Therefore  you can modify the value of    P7 05 to change if via operation keyboard or serial port     Feedback value corresponding to min  P7 07 Ranges 0 0   100 0    0 096  reference    P7 08 Range  min reference  100 0 96  100 0     Feedback value corresponding to max  P7 09 Range  0 0    100 0    100 0   reference    P7 06     P7 09 define the relationship curve of analog close loop reference and expecting feedback The reference value 1s       the percentage of real value of feedback corresponding to benchmark value  10V or 20mA   as shown in Fig 4 36              Feedback Feedback  corresponds to r corresponds to    max reference   max reference  Feedback  
33.  too low Select a high power inverter    Sudden change of load Check and reduce the change of load    Over current during Prolong Acc Dec time  constant speed Check the load  Check AC supply voltage  Select a high power inverter      gt  duminej     TooshorAcetime 0 Prolong Ace time  90    acceleration  The rotating motor restarts after stop Set as    start on fly    function       Too short Dec time Prolong Dec time    Over voltage durning Oo  The load generates energy or the load inertial 1s    deceleration Connect suitable braking kit    too big       Abnormal input voltage Check input voltage  Over voltage  l Too short Acc Dec time Prolong Acc Dec time  Durning constant    Abnormal change of input voltage Install input reactor  speed operation  Too big the load inertial Connect suitable braking kit    Inverter    s control  power supply over Abnormal input voltage Check input power or ask for service    voltage    Vent obstructed Clean the vent  Over temperature Improve condition and decrease carrier freguency  Inverter overheat  Fan does not work Change the fan    Ask for help       IGBT module 1s abnormal    Inverter overload Too short Acc time    Prolong Acc time    V5 series inverter    Reduce DC injection braking current and prolong braking    DC injection braking current is too big       time    Set  start of fly  function    Adjust V F curve and torque boost value    V F curve 1s not suitable    Low AC supply voltage Check AC supply voltage    Common motor has oper
34.  will coast to stop and it is prohibited  to restart  This function 1s mainly used in application with requirements of safety protection    14 15  Frequency ramp up  UP  Frequency ramp down DOWN  The terminal can be used to increase or decrease the  frequency  Its function is the same with operating keys on the panel  which enables remote control  This terminal 1s enabled  when P0 01 3  Increase or decrease rate is determined by P4 09    16  Acc Dec prohibit  The terminal can make the motor operate at present speed without being influenced by external  signal  except stopping command     Note  Disabled in normal dec to stop    17  Reset signal  The inverter can be reset via this terminal when the inverter has a fault  The function of this terminal 1s the same  with that of Cue panel    18  External fault signal normally open input  The fault signal of external equipment can be input via the terminal  which    is convenient for the inverter to monitor the external equipment  Once the inverter receives the fault signal  1t will display     SE 13   Refer to Fig 4 20     19 21  Frequency selector 1  Different ON OFF combination of terminals 19  20 and 21 can select reference frequency as  shown in Table 4 4  The inverter will be active this function and P0 01 later     Table 4 4 Frequency selector    Frequency selector 3 Frequency selector 2 Frequency selector 1 Frequency selector     o   Mem   ON isting       om       O r DO in  Lo  mem  or  ox  p as    PULSE  Combination settin
35.  within Dec time     The central frequency is actually the preset frequency of simple operation  except PLC  traverse operation  jog    multi step  speed operation or PLC operations     Traverse operating function is disabled automatically in Jog operation or close loop operation process     If PLC operation and traverse operation start at the same time  the traverse operation 1s disabled when the drive transits  from one PLC operating stage to another stage  The drive will accelerate to the preset frequency of PLC operation and then  start traverse operation  The drive will decelerate to stop within the Dec time set in PLC operating stage            Operating  freq   Hz  Traverse operation       Upper limit of 4 amplitude Aw Fset  P9  04   frequency PH um Fa i    4  dk 07  gt  GG a  Central Frequency Pset  77 7  NC ius je    IN us   Ni         Lower limit of Aw al 4 4     freguency PL O a y f a      7    TC    TT   Jitter      freq  AW  P9 05    Waiting time   P9 03 i    Preset frequency           t  Decelerate  m       to Acc tim     according  Traverse to Dec time  Run   operating  cycle  command           stop  command    Fig 4   45 Traverse operation    85    V5 series inverter    P9 00 Traverse operation selection Ranges 0 1 HEINE    0  Disabled  1  Enabled    P9 01 Traverse operation control mode Ranges 00 11    Unit s place of LED  start mode   0  Auto modeThe inverter will running at preset frequency  P9 02  for certain time  P9 03   and then enter the traverse  oper
36. 0    50 00Hz 1 00Hz    P4 15 FDT2 Cfrequency  level Ranges 0 00 upper limit of frequency 10 00Hz  P4 16 FDT2 lag Ranges 0 00   50 00Hz 1 00Hz    P4 13     P4 14 1s the additional definition of No 2 function in Fig 4 6  P4 15     P4 16 is the additional definition of No 3  function in Fig 4 6  The both have the same usage and the following take P4 13   P4 14 as an example to introduce  When  the output frequency over a certain frequency FDT1 level   indication signal will be output until the output frequency fall to  the value which is lower than the certain frequency  FDTI level     FDTI lag   as shown in Fig  4 27        Output frequency    FDTI level        4    Tune       Fig 4 27 FDT level    P4 17 Analog output selection  AO  Ranges 0 7 DEBER  P4 18 Analog output gain  AO  Ranges 0 50 2 00 1 00       Table 4 7 Output terminals     0m       Fem O  O  e   omme   s OOOO O    PID feedback 0 10V    JR Jj O o o99w       V5 series inverter    As to the analog output of AO  you can adjust the output gain to change the measuring range or calibrate the meter   P4 19 AO output mode Ranges 0  1    0  4    20mA  1  0  10V    P4 20 DO output terminal Range  0 7    Refer to Table 4 7 for function selection of DO output terminal     P4 21 DO max pulse output frequency Range  0 1 20 0  max 20K     This parameter defines the max output frequency of DO terminal       PA2   Preset counting value arriving Ranges P4 23  9999 foo    P423   Mid counting value arriving Ranges 0 P4 22 pO    P4 22
37. 0   150    140     220V  110 130    120       0  Prohitit  1  Permit       During deceleration  the motor   s decelerate rate may be lower than that of inverter   s output frequency due to the load inertia   At this time  the motor will feedback the energy to the drive  resulting in the voltage rise on the inverter s DC bus  If no    measures taken  the inverter will trip due to over voltage     During the deceleration  the inverter detects the bus voltage and compares it with the over voltage point at stall defined by  P5 03  If the bus voltage exceeds the stall overvoltage point  the inverter will stop reducing its output frequency  When the    bus voltage becomes lower than the point  the deceleration continues  as shown in Fig 4 31     76    V5 series inverter    Over voltaze  pomt at stall    i or  Time  Output T  1  frequency  E        Time    Fig  4 31 Over voltage function      P504   Auto current limiting threshold Range  110 200    150         P505   Frequeny decrease rate when current limiting Ranges 0 00  99 99Hz   S 10 00Hz S    P506   Auto current limiting selection Ranges  0 1    Auto current limiting function is used to limit the load current smaller than the value defined by P0 54 in real time        Therefore the inverter will not trip due to surge over current  This function is especially useful for the applications with big    load inertia or big change of load     Auto current limiting threshold  P5 04  defines the threshold of auto current limiting  The 
38. 0  Simple PLC Pause  running finished   11  PLC is finished after  one cycle running  12 Specified counting  value arriving   13  Mid counting value  arriving   14  Inverter Ready running  finished  RDY     15  Inverter fault   16   Start frenquence  running time   17   Start DC injection  braking time   18  Stop braking time   19  High and lower limits  of traverse operating  frequency    20  set running time arrive       0 01 Hz 5 00Hz  0 00    50 00HZz    0 00     upper limit of of    freguency    eee CSV SS series inverter series inverter    0 01Hz 10 00Hz UN    FDTI lag 0 00 50 00Hz 0 01Hz 1 00Hz LAN    FDT2  frequency  level       0 00   upper limit of of    frequency    0 01Hz 10 00Hz LINE    FDT2 lag 0 00 50 00Hz 0 01Hz 1 00Hz oOo    Analog output CAO        0  Output frequency  0       1  Output current  0    2    times of rated current     2  Output voltage  0    1 2 1    V5 series inverter    nverter s rated voltage       Bus voltage  0   800V      PID reference     PID feedback     VI  0   10V      CI 0   10V 4   20mA   Analog output CAO  gain   0 50    2 00 0 01       P4 18         c        setup    P4 19 AO output mode           i    P4 20 DO output terminal 0  Output freguency  0      upper limit of of  frequency    1  Output current  0    2  times motor rated current   2  Output voltage  0    1 2  inverter s rated voltage      Bus voltage  0   800V      PID reference     PID feedback     VI  0   10V      CI 0   10V 4   20mA    DO max pulse oupt   0 1K   20 0K 
39. 1  R  n the TINY COCO Nas rr                                                              27  3 1 1  Command channel for inverter TUDDITIS us  sosslsio  in ch p IR ERES E EUERT OE Rad Fs be Fe o o r noo kn dno 27    VB3 VBS5 V5 seires inverter    SOAM Frequency setting INIRE NERONE RR m u                                        21  Sls  RUA Md DID SEC palace skon qM dora dM NUMERI M PIE ADEM tao MB E MSS 27  Eed Runnin IR dS ONU mE 27  3 2  se t   ndn ip e                                                                             M   28  Set  Res DOG   VOU asto on dis into cute uit in stt vence fra Marcas E eM EM ed sen Son 28  si i SEC TMI E TO Eline cou n   nr A A AO non pbi ME 29  3 2 3  Fuention description of LED and indicator                   oooooooovnvnv   n   nn nn ene oo o eee en 30  Sud Display of the operation pane h  t o r ees oni 30  32225 ale VO et One Procedir  snes  ko os nt nn s r rn rot o r  32   D 5 SOUT OUND xs aa AE EE E AE E A AEE SE E E N OAO A OAE A EA EE E EA 34  J l  Checking belore starine UI DS n  nst oo dust oma sn ion tn idol a a a aE ESEE EE EEEE an fra kr  s 34  32389 Startup he inverter Tor ihe irst TINE sennen a AAEE OAOE 34  4 FUNCTION PARAMETERS        sssssssssssssssssssssssssssssessssesssseesssseeessneeessseessasesssauesssseeseneeseneeerenses 36  4 1  Function parameter CAD Cs sissstsiskss  ss    il z  skok kod   koko fa od io v  d kan vo   ak   no Tana Aon Konad anai 36  4 2  Parameter NESCTIJNIOM i    iss s   n  mi   ak   s ak  si ak 
40. 2  to set the frequency via serial port    5  VI analog input  VI    GND    The reference frequency 1s set by analog voltage input via terminal VI  the input voltage range is DC 0 10V  The  corresponding relationship between frequency and VI is decided by parameters P1 00 P1 05    6  CI analog input  CI    GND    The reference requency is set by analog voltage current of terminal CI and the input range is DC  0   10V  if jumper JP3 is  placed on  V  side    DC 4 20mA  if jumper JP3 is placed on    A    side   Then corresponding relationship between  frequency and CI input is decided by parameter P1 06 P1 10    7  Pulse input  PLUSE    The referency frequency 1s set by pulse input via pulse terminal  can only be input via terminal X6   The corresponding  relationship between frequency and PLUSE input 1s decided by parameters P1 11 P1 15    8  Combination    Please refer to P3 00  to set the reference frequency via combination of channels     Range  Upper limit of of frequncy   lower limit of    Digital frequency setting       frequency    When the reference frequency is set in digital mode  P0 01 1 2 3 4   The setting of P0 02 is the inverter s initial frequency    value     Methods of inputting operating  commands    0  Panel control    STOP    Input operating commands via panel start or stop the inverter by pressing   EE and on the panel    1  Terminal control   Input operating commands via externals such as FWD  REV  X1 X6 to start or stop the inverter    2  Serial port con
41. 5  the inverter will output indicate signals  This function is mainly used in pre alarm    5  Inverter under voltage locking CLU    While inverter is in running process  if the DC injection bus voltage is lower than  the limit value   E 11  will be displayed in LED and indicate signal will be output    6  External fault stop CEXT    An indicate signal will be output if inverter outputs trigging signal caused by external fault   7  Output frequency arrive upper limit  FH    An indicate signal will be output if reference frequency gt upper limit of  frequency and the running frequency arrives the upper limit of frequency    8  Output frequency arrive lower limit CFL    An indicate signal will be output if reference frequency     lower limit of  frequency and the running frequency 1s lower than low limit of frequency    9  Inverter zero speed running  The output frequency of inverter is 0   while the terminal will output indicate signal when  inverter is in running status    10  Simple PLC Pause running finished  An indicate signal  single pulse signal  500ms width  will be output if the present  stage of PLC operation 1s finised    11  PLC is finished after one cycle running  An indicate signal  single pulse signal  500ms width  will be output if one  cycle running of simple PLC 1s finished    12  Specified counting value arriving   13  Mid counting value arriving   12 13 refer to P4 22 P4 23 for function instruction    14  Inverter Ready running finished CRDY   If RDY signal i
42. AA ENESE ooo osie   ch 87  5 FAULT DIAGNOSIS AND COUNTERMEASUREG         ssssssssssssssssssssssesesssesesssessssesssaeeseaeeeseaes 88  5 1  Fault diagnosis and couniermeASUTS   i i  ssisk2ossi  c  a  cozko b d  a ad c   ocakaval br  na 88  5 2  Fault PECOTOS  NEN E TT E T UI 90  RM grnlida  i e P                      M                        90  O MAINTENANCE saasa EA AEEA 91  0 1  Dira cur  c                                                                              lona 91  O  TeT  BOUT He THATHUO HOO a sade Bec ca rete caus ET E UL ONDE lyse etu cn DOES Male oa Roo A CUPIT E eed U bU taint sels E dU CU Db E QUE 91  0 2  Periodical care and M  mienan  e s   ss5  iii laku ka   oko ko nak    NANANA AAN ARE AAA v   kov 91  O 2  I Periodical Caf Gore Skin u vnoci A Ta ustne nan nt nn 91  6 2 Per modica Bt  ie 91    VB3 VBS5 V5 series inverter    0 3  Warranty of the inverter MRRRR                                          92  T COMMUNICATION PROTOCOL s   siii   i   is ad sv    d  ai   s   svu    za        ouai a lu isla caos sas ce cu eo uzn 125i ss ivi ulica  93  7 1  Overview of communication protocol           ssssssssssssssssooososooossso soon soon 93  7 2  Instruction of communication protocal           sssssssosssososssoonooooooo sos sos esee e 93  Jade Lo CC OC AO HOC ecco ght sos ces tU Ui wean ets o En MEER NI 93  7 2 2  Communication MOU6S  sles  sazacieda RR                         m 93  75253  Mode ot communicaltOB POLL  xasonso cepta scoop ett etin sS xa I GR ERRE
43. ER n Z A ro non ona 94  7 3 Modbus RTU communication protocol                               c eeeeec ss ooo ooooKe 94  fio S PIS REIP RE r 94  T 2  Communication norma 10M oc eec apad ona lo o kos ls rot don s OA dS TRUE 94  fa s tommuncadidot Doble e AEE A E E o rn 96    iii    VB3 VB5 V5 AAAS Mia    Preface    Essential introduction for this manual       Thank you for purchasing Xinje inverter  this manual should be read and understood before attempting relevant operations   1  Purpose of this manual    This manual offers guidance and introductions about how to use and maintains the inverter correctly  including functions     usages  installation  maintenance  etc     2  Qualified personnel  This manual is intent for the following personnel    gt  Inverter installation personnel     Project technical personnel electric engineer  electrician      gt  Design personnel    The above personnel should read and understand this manual carefully before operating and debugging     3  Validity of this manual    This manual may only be used for inverters made by Xinje     4  Electronic Documents   In addition to our written manuals  we offer electronic documentations of our products by the following ways    gt  User CD   There are software  user manual and application tip of relevant products     gt  Website    Please visit www xinje com to obtain all variable electronic documents     VB3 V5 VBS5 series inverter    Safety Precautions    Essential introduction about product operation   
44. IC SHOCK DUAL  SUPPLY DISCONNECT MAINS AND  LOADSHARING BEFORE SERVICE                                  OQO O00 O0 QO                                           C 2 C 2 5 LUE A             V5 series 11 18 5KW V5 series 22 55KW          O O        O                                                                                                                                                                                                                       o o o 0 0 o  6000 0080 5 0  UUU 9 6090     UU U     THiNGET  Z THINGET A  ZA n    a V     C  MENU    ENTER de MENU    ENTER  ESC DATA i D ESC    DATA m    p gt      Fo   E      gt   m Rev A  AJ a STOP E   a   v gm A  A   Y   fr S   amp           B        A ral 000600000000 m  00000000000  6966666666  696696966906 e         s  S A          P                                                                                                                                                                                                                                                                                                                                                                      11    VB3 V5 VBS5 series inverter    1 4  Product dimension  B VB3 series 0 4 0 75KW CUnit  mm                  rr  mi    rr  E    B  VB5 series 1 5 3 7KW  Unit  mm     The details of the dimension     mu       41 P5  o           VBS 2P2   VB5   VBS43P7      B VBS series 5 5 7 5KW                                                         
45. It defines the time of a complete traverse operation cycle including rising and falling processes     P9 07 Rising time of trangle wave Range  0 098 096 50 096    Running time of traverse rising stage     P9 06 X P9 07 s   Time of falling stage    P9 06X  1   P9 07   s   Refer Fig 4   45    for introduction    Notes Youcan select S curve Acc Dec mode along with traverse so as to make the traverse operating more smoothly     P9 08 Reference length Ranges 0 000  65 535km 0 000 km   P9 09 Actual length Range  0 000  65 535km 0 000 km   P9 10 Times of length Ranges 0 001    30 000    correction coefficient of  P9 11 Ranges 0 001 1 000  length    P9 12 Perimeter of shaft Range  0 01  100 00 cm  10 00 cm   P9 13 Number of pulses per revolution Range  17 9999    This group of parameters are used for fixed length control        The drive inputs counting pulses via terminals  X6  defined as function 35   and calculate length according to the number of  pulses per revolution  P9 13  and perimeter of shaft  P9 12      Calculated length     Number of pulses number of pulses per revolution X perimeter of shaft    86    V5 series inverter    The calculated length can be corrected through times of length  P9 10  and correction coefficient of length  P9 11   and the  corrected length is the actual length    Actual length    calculated length X correction coefficient of length   correcting coefficient of length   When actual length P9 09    preset length P9 08   the inverter will send out a S
46. Ranges  Lower mimit of frequency mode 0  running with lower limit of frequency NA  1  stop    P0 19 and PO 20 define the upper and lower frequency of frequencies respectively  as shown in Fig 4 2 as FH and FL        When the actual frequency 1s lower than the lower limit of frequency  inverter will accelerate with the accelerate time which  you have set  and then after reaching the lower limit of frequency  inverter will running with the lower limit of frequency if the    running mode is 0 and it will decelerate output frequency continuously until OHz with the running mode 1s 1     V F curve setting Ranges 0 4      mmo V F frequency value F1 Ranges 0 00  P0 25 00H    P924   V F voltage valueV1 Range  0  P0 26    V F frequency value F2 Ranges P0 23   P0 27 0 00Hz    V F voltage value V2 Ranges  P0 24   P0 28  P0 27 V F frequency value F3 Ranges P0 25   P0 07 basic running frequency 0 00Hz    P0 28 V F voltage value V3 Range  P0 26   100 096       This group of parameters defines the flexible V F setting modes of this inverter to satisfy the requirement of different loads   Four fixed curves and one user defined curve can be selected according to P0 22   PO 22 0  V F curve is constant torque curve  as shown in Fig 4 7 as curve 0   PO 22   1  V F cuve is 1 2 order torque reducing curve  as shown in Fig  4 7 as curve 1   PO 22 2  V Feuve is 1 7 order torque reducing curve  as shown in Fig 4 7 as curve 2   PO 22   3  V Fcuve is 2 0 order torque reducing curve  as shown in Fig 4 7 
47. TOP command to stop  When the inverter  restarts  it needs to clear the actual length  P9 09  or modify actual length  P9 09  lt  Reference length  P9 08   otherwise the    inverter will not start        Note   1 The actual length  terminal Xi 1s defined as function 36  can be cleared by multi function input terminal  The  actual length can be calculated only after this terminal 1s disconnected     2  Actual length  P9 09  will be saved after power off automatically     3  Function of stopping at fixed length 1s disabled if P9 08 I set as 0  but the calculated length 1s still effective     4 2 11  Vector control parameters CGroup PA     PA 00 Motor auto turning Ranges 0 1 DE    0  Noturning  1  Static turning    Dependent on  PA 01 Rated voltage of motor Ranges 0     400V  inverter s model  Dependent on  PA 02 Rated current of motor Ranges 0 01    500 00A  inverter s model  Dependent on  PA 03 Rated frequency of motor Range  1    99Hz  inverter s model  Dependent on  PA 04 Rated speed of motor Range  17 9999 r min  inverter s model  Dependent on  PA 05 Polarity of motor Ranges 27 48  inverter s model    Dependent on  PA 06 Stator inductance of motor Ranges 0 1  5000 0mH  inverter s model  Dependent on  PA 07 Rotor inductance of motor Ranges 0 1  5000 0mH  inverter s model  Dependent on  PA 08 Exciting inductance of motor Ranges 0 1    5000 0mH  inverter s model  Dependent on  PA 09 Stator resistance of motor Range  0 001    50 000    inverter   s model  Dependent on  PA 10 Ro
48. Time    Fig 4 29 Overload pre alarm       gs    V5 series inverter    4 2 6  Protective function parameters  Group P5       P590   Motor overload protection mode selection Ranges 0 1 EE    This parameter defines the protection mode when overload or overheat occurs   0  Inverter locking output  When overload or overheat occurs  inverter will lock output and the motor will coast to stop   1  Disabled  Motor will be without overload protection and inverter will do the overload protection for the motor  Cautions to    using     P5 01 Motor s overload protection coefficient Ranges 20      120    100       This parmeter 1s used to set sensitivity of thermal relay protection from inverter to overload  When the output current value  of load motor can not match the rated current of the inverter  correct thermal protection can be realized by setting this  parameter  as shown in F1g 4 30     Use the following coefficient to calculate     Wlotor rated current   PS OLE X 100    Inverter s rated output current  Time     P5 01  50     P5 01  10096  1 minute L  XIX    Curent       55      110  150   G   105  1207    P     Fig 4 30 Thermal relay protection    Note   When one inverter run with multi motors  inverter s thermal relay protection will be disabled  Therefore  please install    thermal relay in the wire end of each motor to protect motor more efficiently     Protection   Protection of over load at stall     over load at stall Range  0 1    Over voltage point at stall Range  380V  12
49. and be grounded by shielding layer  Motor cable should use 4 core cable  one of the    cores should be grounded near the inverter and another point should be connected to the motor s cover      Don t put the strong and weak electricity cables in parallel or bundle these cables together  Other devices should  also be away from the inverter  The devices wire should be away from the I O of the inverter  The signal cables    and power cables should be shielded cables  Devices with strong electric field and magnetic field should be away        1 The equipment and the signal cables should be as far away as possible from the inverter  The signal cables  should be shielded and the shielding layer should be grounded  The signal cables should be located far away  from the input output cables of the inverter  If the signal cables must cross over the power cables  they should be  placed at right angle to one another    456  2  Install high frequency noise filter  ferrite common mode choke  at the input and output of the inverter to    and orthogonal from the inverter     2 6 2  Local wiring and grounding     1  The cable connected inverter and motor  cables from U  V  W points  should not parallel with power supply calbe  R  S   T or L  N terminal input wire   The distance should be more than 30cm     2  Inverter s output cables from U  V  W terminals 1s recommend to put in metal tube or slot     3  Control signal cables should be shield and the shield layer should be connected with inve
50. as curve 3   To achieve best energy saving effect  you can select 1 2 or 3 V F curves according to the actual loads such as fans and    pumps     58    V5 series inverter       Output  Voltage  Vimax eT g R dd RE EGR R TT TEE TT TOT EU RR ST d  F    V    3  Output  Frequency Hz  wt i  QO      Fp  Vmax    Max output voltage P0 08  Fy   Basic running frequency P0 07  Fig 4 7 V F curve  Voltage Z  100  f  V  t  V2 d  Vil 1  er Output  Vb    Frequency Hz    F1    Vl1 V3  voltage of sections 1 3   Fl  F3  frequency of sections 1 3    F2 F3 Fb    Fig  4 8 User defined V F curve    When P0 22 is set to 4  you can define V F curve via modifying  V1  F1   V2  F2    V3  F3  to satisfy the special load  requirement  as shown in Fig 4 8  Torque boost is suitable for user defined V F curve In Fig 4 8   Vb  Torque boost  P0 09  X VI    4 2 2  Parameters of reference frequency  Group P1       Poo   Time constant of analog filter Range  0 01    30 00s          It 1s the constant time of the filter that 1s for internal sample picking by inverter when reference frequency is set by external  analog channel  When the wire is too long or the interference is serious which can lead to reference frequency becomes  wavy  you can increase filter time to improve the situation  The bigger the time constant 1s  the higher the immunity level   but the response time 1s prolonged with the increase of the time constant  That 1s  the smaller the time constant is  the shorter       the response time  but the l
51. ated with heavy load   Select motor with frequency conversion if it requires to       Molorovedoad at low speed for a long time operate for a long time    Unsuitable motor   s overload protection l l  l Set motor   s overload protection coefficient correctly  coefficient    The motor is blocked or the load is too big Check load    Too low AC supply voltage Check AC supply voltage    Instant over current of inverter Refer to countermeasure of over current    Short circuit among 3 phase output or    mE Rewiring  line to ground short circuit  Vent is obstructed or fan is damaged Clean the vent or change the fan    Over temperature Reduce environment temperature  IGBT protection Wires or connectors of control board are loose Check and rewiring    Current waveform distorted due to output phase M  i Check wiring  OSS    Auxiliary power is damaged and inverter                Seek factory or agent for service       voltage is low    Abnormal control board Seek factory or agent for service    Emergency stop for peripheral equipment l  Peripheral equipment Break external fault terminal after dealing with the  terminal close   fault external fault    Wires or connectors of control board are loose Check and rewiring  Current  Auxiliary powe is damaged Seek factory or agent for service  detection circuit  Hall sensor is damaged Seek factory or agent for service  has fault  Amplifying circuit is abnormal Seek factory or agent for service    key to reset  or seek service    RS485 Serial por
52. ation    1  Manual mode If the multi function terminal  Xi 1s set to No 25 function  1s enabled  the inverter will enter traverse  mode  If the terminal 1s disabled  the drive will end traverse operation and operate at the pre traverse frequency  P9 02    Ten s place of LED  Traverse operating amplitude    0  Variable amplitude  Traverse operating amplitude AW changes with the central frequency and the change rate is defined  by P9 04   1  Fixed amplitude Traverse operating amplitude AW 1s decided by max frequency and P9 04       Pe   Pre traverse frequency Ranges 0 00   650 00Hz 0 00Hz       Waiting time before pre traverse frequency Ranges 0 0   6000 0s    P9 02 is used to set running frequency before inverter enter traverse state   If you select auto start mode  P9 03 is used to set the holding time with pre traverse frequency before the inverter enter    traverse state  1f you select manual start mode  P9 03 is disabled  Refer to Fig  4    45 for introduction     P9 04 Traverse operating amplitude Range  0 050 096 0 096    Variable amplitude  Aw     Central frequency X P9 04  Fixed amplitude  Aw     Max operting frequency P0 06 X P9 04    Prompt  The traverse frequency will be limit by upper lower limit of frequency  and the traverse operation will not work    abnormally with unsuitable setup     Jitter frequency Range  0 050 096 0 096    As shown in Fig4 45  there 1s no jitter frequency if P9 05 1s set to 0     P9 06 Traverse operating cycle Ranges 0 1   999 9s 10 0s    
53. ation  Normally  lifetime is     93    V5 series inverter    Table 6 2 Lifetime of inverter components    Cooling fan    Electrolytic capacitors 4 5 year  Print circuit boare  Fuse 10 year    The usage conditions of the above components are shown below    1  Environmental temperature 30 C as average    2  Load coefficient  below 80     3  Running time   below 12 hour per day     6 3  Warranty of the inverter    Xinje electronic Co  Ltd will offer warranty service in the case of the following situations     1  The warranty clause 1s only confined to the inverter     2  We will take the responsibility of 15 months defects liability period for any faults or damages under the normal  operation conditions  After15 months  maintenance will be charged     3  Even within 15 months  maintenance would be charged under the following conditions    Inverter is damaged due to incorrect operation  which are not in compliance with    User Manual     Inverter is damaged due to fire  flood  abnormal voltage and so on    Inverter is damaged due to wiring fault    Inverter is damaged due to the improper use of drive functions      4  Service fee will be charged according to the actual costs  If there are any maintenance contracts  the contract prevail     94    V5 series inverter    7 Communication Protocol       7 1  Overview of communication protocol    These series inverter supply RS485 communication port and adopt MODBUS startded communication protocol  Therefore   the inverter can be set as
54. cal inertia    2  Dec to stop DC injection braking    After receiving the stopping command  the inverter reduces its output frequency according to Dec time and then start to DC    injection braking after the output frequency reaching the initial frequency of braking at stop as in P2 06     DC injection braking initial frequency at  i Ranges 0 0 15 00Hz  stop    P2 07 DC injection braking time at stop Range  0 0 60 0S  P2 08 injection braking current at stop Range  0 80        P2 08 refers to the set of DC injection braking current at stop which is the percentage value of inverter s rated current  There       is no DC injection braking when the braking time is 0 0  as shown in Fig 4 12     4 2 4  Auxiliary running parameters CGroup P3       P390   Combination of frequency setting Ranges  07 20 PO    When P0 01  Frequency setting mode  is set to 8  combination of frequency setting can be set through this parameter   0  VI CI  1  VI   CI    External pulse reference   VI   Increase Decrease key reference    External pulse reference     VI     Increase Decrease key reference      External pulse reference   CI      RS485   VI Increase Decrease key reference    2   3   4   5  External pulse reference     CI   6   7  RS485    VI    Increase Decrease key reference  8      RS485 ClI Increase Decrease key reference    V5 series inverter    9  RS485   Cl Increase Decrease key reference   10  RS485 CI   External pulse reference   11  RS485   CI    External pulse reference   12  RS485  VI 
55. called positive    characteristic  On the contrary  if the motor speed is required to decrease when the reference value increases  this control    characteristic 1s called negative characteristic     The two close loop characteristic can be set by P7 14  as shown in Fig4 35     Anticipant feedback    Speed Positive    CPP ERO ee Pe Pe ee ee          i  Negative    4m     Reference   Close loop reference       10V    Fig 4 34 Reference and Fig 4 35 Close loop adjustment  anticipant feedback characteristic diagram    After conforming the system  the procedure of setting close loop parameters 1s shown below    1  Confirm the close loop reference and feedback channel  P7 01  P7 02       2  The relationship between close loop reference and feedback value  P7 06 P 7 09  should be defined for close loop    control      3  If reference and required motor s speed is opposite  please set close loop characteristic as negative to confirm close loop    adjustment characteristic  P7 14   1   as shown in Fig4 35    4  Set the function of close loop preset frequency  P7 16    P7 17       5  Set close loop filter time  sampling cycle T  limits of deviation and gain coefficient  P7 03  P7 04  P7 12  P7 13      P7 00 Close loop function selection Range  0 1    0  Close loop control is disabled  1  PI close loop control is enabled    P7 01 Reference channel selection Range  0  1 2    0  Digit input  1  VI  0   10V     2  CI  0 10V voltage or 4 20mA current reference  for speed close loop  analog
56. cation  6    VB3 V5 VBS5 series inverter    220V    Over loading Ability 150 Rated Current for 1 minutes  180  Rated Current for 1 second  Rated Voltage Frequency single phase 220V 50 60Hz    AC voltage permit fluctuate range Voltage   20     20   Voltage Unbalance Rate   lt 3     Frequency fluctuate Range Frequency   5        380V    um ss E pm e pe  fff  eo em  s  n    output   Rated 4 5 ER 0 Es 0 ES ES  current  A     Rated AC 380  voltage  V     frequency range Hz  0   500  Overload Ability 150  Rated Current for 1 minute  180  Rated Current for 1 second    Rated voltage Three phase 380V  50Hz 60Hz   Frequency  AC voltage fluctuate range Voltage   20     20   Voltage Unbalance Rate   lt 3     Frequency fluctuate range   Frequency   5     Power Capacity  KVA        Common characteristics  Environment Application environment In door  free from direct sunlight  dust  corrosive gas  oil mist     steam  water drop etc     Elevation Lower than 1000m   The inverter should be derated when the    elevation is higher than 1000m      Ambient Temperature    10 C      400    Storage Temperature    20          60 C    Structure Protect Configuration IP20 In the state of  state display units  or  keyboard          VB3 V5 VBS5 series inverter    l Optimized space voltage vector SVPWM modulation  Modulation mode    SVPWM control  dead zone compensation for optimized low frequency     MN Digital Setting  max frequencyx 0  01    Frequency precision  Analog Setting  max frequencyx 0 2     Ma
57. cient of 0 001     1 000 0 001 1 000  length    P9 12 Perimeter of shaft 0 01    100 00cm 10 00cm lO      P9 13 Number of pulses per   1    9999 1 1  revolution    11 Vector control parameters   Group PA        Group PA  Vector Control Parameters    PA 00 Motor auto tune 0  No tune   mm og op or or  PA 01 Rated voltage of motor 0   400V F     PA 02 Rated current of motor 0 01    500 00A 0 01 A Dependent   PA 03 Rated freguency of motor      99Hz Dependent  O    PA 04 Rated rotated speed of motor 1     9999 r min 1r min ad   PA 05 Polarity of motor 2   48 Dependent   PA 06 Stator inductance of motor 0 1    5000 0mH 0 1mH Dependent on   PA 07 Rotor inductance of motor 0 1    5000 0mH 0 1mH Dependent  s pee r po   PA 08 Exciting induction of motor 0 1    5000 0mH 0 1mH ee       V5 series inverter    PA 09 Stator resistance of motor 0 001     50 000    0 001    a   PA 10 Rotor resistance of motor 0 001     50 000    0 001    S   PA 11 Over current protection   0   15   ui coefficient of torque ERN  PA 12 Percentage adjustment   50   120   uli coefficient of speed deviation mm    PA 13 Integral adjustment coefficient   100   500   mur  Reva  ee  emm OH  b ema pw              Ti   ma  mea v   i    12 Specail Application function parameters  Group PB               A  a                      00      N N    Group PB  Specail Application function parameters    PB 00 Jog frequency source 0   4    P3 06    Panel potentiometer    P0 02    VI    CI  PB 01 selection of  forward   reverse dea
58. ctor output terminal OC Range  07 20       P4 11 Relay output selector Ranges  0720    Bi direction oper collector output terminal OC  the options of this parameter are shown in Table 4 6     Table 4 6 Functions of output terminals      Setting       EA a Fumtons O O  Inverter running  RUN  11 PLC is finished after one cycle running   Frequency arriving signal FAR  12 Specified counting value arriving  3    Mid counting value arriving  Frequency detection threshold  FDT1  1  HN Frequency detection threshold  FDT2  14 Inverter Ready running finished  RDY      l  2  3  5  T    5  Inverter under voltage locking  LU  16 Start frenquence running time  7    External fault stop CEXT  1       Start DC injection braking time    V5 series inverter      Stop braking time  I Output frequency arrive upper limit  FH  18  l mE High and lower limits of traverse operating frequency  Output frequency arrive lower limit CFL  19    Instructions of the functions shown in Tabel 4 6        0  Inverter running CRUN    Inverter is in the running status and the terminal outputs indication signal    1  Frequency arriving signal CFAR    Refer to P4 12 for function instruction    2  Frequency detection threshold CFDT1    Refer to P4 11  P4 12 for function instruction    3  Frequency detection threshold CFDT2    Refer to P4 13 P4 14 for function instruction    4  Overload pre alarm COL    If the output current is higher than the value defined by P4 24 and the time is longer than the  value defined by P4 2
59. d time 0  Dead time 1s enabled  Min 0 15   l   dead time can be set to  0   P0 05 0 0S   P0 20   0 5Hz is  needed   PB 02 Inverter type select 0  G type normal   1  P type wind machine water pump   power increases 1 level   Note  set as 1  P0 22 must set to 3   PB 03 Short the run point   0  after inverter is power on  run  before power on  set the   immediately  run mode 1  after inverter is power on  cut off  the point and connect again to run    13  Factory setting  Group PF        Group PP  Factory Setting    Minmum  Parameter Name Range v Factory setting   Change  uni    PF 01 User s password   0  With no password protection mE  0001    9999  passwor protection       5     V5 series inverter    OE p E CNN       PF 03    PF 10 Reversed    14  B   Monitor function parameters    B   Monitor function parameters    Minmum Factory   Change  Code Name Description  unit setting    v   owpuneaueney   Prsewoupurnequney foom   Po  es   Retence sede   Pennine tauuensy foom   P  em   owpuvotase   vaia ae ofpe oupa  v lO  em   ouipatcunen   vaid se opreso cum A   oo  m Bevora  mempcewmee O OTO I   bos   Module temperate   ir Temperate otras Joe       Deas   Motor overload speed   Present moror overoaa speed  m Ol  Pear open me   one conti opening tine siene   1mo                    Dem opa ea suras   Dl app ma   s          O O oo  e ro piv  Vestmdrmpavi Jow   pooo  Des   kop   terase ch fov   Po  en stra puise input   at vor pl fms OTO  Dur veno rea on   merere da       Des ene r vona
60. dress 0    248  0  broadcast address  248  inverter as the host address    41       V5 series inverter    ontrol PLC 0 0  Detection disabled    P3 12 Delay for responding to   0    1000ms 1 5ms  P3 13 Reference proportion of   0 01    1 00 0 01  Ej NNNM    P3 26 Multi freguency   Lower limit frequency     upper limit of 0 01Hz 5 00Hz  nandi a nd EN   P3 27 Multi frequency 2 Lower limit frequency     upper limit of 0 01Hz 10 00Hz  ee eee   P3 28 Multi freguency 3 Lower limit frequency     upper limit of 0 01Hz 20 00Hz   P3 29 Multi freguency 4 Lower limit frequency     upper limit of 0 01 Hz 30 00Hz   P3 30 Multi frequency 5 Lower limit frequency     upper limit of 0 01 Hz 40 00Hz      E   P3 31 Multi frequency 6 Lower limit frequency     upper limit of 0 01 Hz 45 00Hz   P3 32 Multi freguency 7 Lower limit frequency     upper limit of 0 01Hz 50 00Hz    P3 33 Jump freguency I 0 00     500 00Hz 0 01 Hz 0 00Hz x    P3 34 Range of jump frequency   0 00   30 00Hz 0 01Hz 0 00Hz X    1  P3 35 Jump freguency 2 0 00     500 00Hz 0 01 Hz 0 00Hz X    P3 36 Range of jump frequency   0 00   30 00Hz 0 01 Hz 0 00Hz X  2    P3 37 Jump freguency 3 0 00 500 00Hz 0 01Hz 0 00Hz    P3 38 Range of jump frequency   0 00 30 00Hz 0 01Hz 0 00Hz  3    P3 39  65 535K hour 0 001K 0 000K  ug c  P3 40 02205 535K hot 0 001K 0 000K    P3 41 Display parameters   0000   FFFF 1 0000  selection 1 Uni   s place  b 09 b   12  Ten s place  b 13   b    16  Hundre   s place  b 17 b   20  Thousan   s place  b 21    b  
61. e   muento display 0   5 select position 4     amp     next parameter    Fig  3 8 Parameter editing    In the third level menu  the parameter can t be changed if none digit of the parameter 1s flashing  the possible reasons are    1  The setting of this parameter can not be changed  such as the actural detected parameters or recorded parameters     2  This parameters can only be changed in stopping state and can not be changed in running state     3  Parameters have been protected  If P 3 01 1s set to 1 or 2  the setting of all the parameters can not be changed by wrong  operation  If you really want to change the setting  first set P3 01 to 0    3  Jog   When the inverter in stop state  press JOG key and holde it  the panel will display start output frequency and the frequency  will ramp to 5Hz  then releasing the JOG key  the frequency will drop to OHz and the inverter will stop        Dispaly Press Release  Ready  tatus JoG Hold on JOG  Key Operation         gt  e      inem  TP Display zlat     Display sia   Output frequency s    4 Ouiput frequency  prset running ramp to 5Hz drop to 0 Hz  frequency frequency    Fig  3 9 Jog Operation    4  Setting user s password    Setting PF 01 as    2345    and let it as user s password  The bold digit indicates flashing digit     LED   50 00   0000 0 0 0 5   20 05      cB E  Dm  operation m    Parameters User s First  the Move the hern    displayed in password lowest dizit cursor to the       9  2   stopping  valid  enter start to flas
62. e 380V    Grounding          RST   Three phase AC 380V input       U  V  W    Three phase AC output    Generatrix   and      Three phase 380V      PIL PB  jBrkigresstr o      PE Grounding             O    V5 series P   P     U  V  W  P  L3  U  V  W  PE  R  S  T  U  V  W  Pl  PB  PE       18    VB3 V5 VBS5 series inverter    2 4  Basic running wiring    three phase braker  three phase     4  a OR  LI  11             i u     power supply p       A        8  L  I  La V oO M    di  gt    PEG    SEE   At  eroundmg  speeds    11 Te    speeds 1  ai braking resistor  free stap      n Z2  error rese       FB I            z  samy cm          error   Ls i T    error relay outpu         0 X6 ob A   forward 1  Tc     reverse A 1  FWD D 10V  4 20m  cutput  Rey so 1 VA   KT GND 0   DO o igh speed pulse output    open circuit  collector    OC 0 open circuit collector    A oo Rogi communication    UROK        Note     1  P  terminal is only used in 5 5K W and larger inverters     2  L  N terminals are suitable for 220V single phase inverters     3  L1  L2  L3 terminals are suitable for VB5 series 1 5 3 7KW three phase types     4  VBS series 1 5   3 7KW three phase has no digital input X5  analog input Vi and digital output DO    5  VB3 VB5 series single phase have no X4 X6  VI  AO  DO  OC  P   P   PB     2 5  Setting and wiring of control circuit    2 5 1 Position and function of terminals and jumpers on control panel    0 4  0 75KW     VB3 series inverter jumper position       Fig 2   4  a 
63. ection of input terminal X4 Ranges 0737    Function selection of input terminal X6 Ranges 0737    P4 06 Function selection of input terminal X7 Ranges 0737    P4 07 Function selection of input terminal X8 Ranges 0737    P4 04 Function selection of input terminal X5 Ranges 0737       Multi function input terminals X1 X8 support various functions which you can select freely to satisfy your  requirement  You can define the function of X1     X8 by setting the value of P4 00     P4 07  refer to Table 4 1 for  details  Among these terminals  X7 corresponds to FWD and X8 corresponds to REV        Table 4 1 Multi function selection    Sc      67    V5 series inverter    E Control terminal leave unused  Multi step speed control terminal 1  Multi step speed control terminal 2    Control mode selector 1  Control mode selector 2    Acc Dec time terminal 3 Close loop disabled    3 Multi step speed control terminal 3    4 Exteral terminal for forward jog operation  5 Exteral terminal for reverse jog operation    Acc Dec time terminal 1    10 Coast to stop  FRS  PLC disabled  11 External stop command Reset PLC stopping status    12 DC injection braking command DB Frequency reference is input via CI  13 Inverter running prohibit Counter s trig signal input    14 Frequency ramp up CUP  Counter s zero cleaning signal input    15 Frequency ramp down  DOWN  External interrupt input  16 Acc Dec prohibit Pulse frequency input  only valid for X6   17 Reset signal  clear fault  Autual length cleari
64. eld layer should be hung in the air and the other terminal should    be connected with the inverter s grounding terminal E  the cable length should be less than 50m     B Before layout operation  make sure the power supply of inverter is cut off  all the LED on the operate panel is black out    and delay for more than 10 minutes     B Wiring work can be performed after the voltage between internal electrolesis capacity         and           is below DC36V     Wiring work can only be done by trained and professional personnel     B Before power on  please check if the power supply voltage 1s consistent with the inverter voltage level  otherwise    device damage  human injuries and deaths may occur     2 3  Wiring of main circuit terminals    2 3 1  Wiring diagram             Circuit Breaker V5  AC 1  RCL  U         Power A A   S V f      9 TCN  We    E lom  PB P           me     Brake Resistor    Fig  2 3 Wiring of main circuit    2 3 2  Terminal assignment and description    17    VB3 V5 VBS5 series inverter    Bee       Fig  A PEL NUW Fig  B       PEE    L1 L2 L3           Fig  C c Fig  D  a TS TT Be  Fig  E Fig  F Ld RA RA  E S T PlP P  U V W PE  Fig  G    The relationship between main circuit terminals and inverter types     Main circuit I O terminals are shown in table 2 1     220V    Table2 1 main circuit I O terminals      Single phase AC 220V input  VB3  VBS series    Single phase 220V     U V  W   Three phase AC output                 000000000  VBS series  Three phas
65. elow     CI current      3    V5 E  t luV TE      O A E  m T  or 4 20m       0 e      GND CI voltage  ground the proximal PE i  point of shield cable    j 1  JP3    Fig  2 7 CI terminals    wiring    3  Wiring for analog ouput terminal AO  Analog output terminal AO can display various physical quantities when connecting external analog meter  output voltage    0 10V  output current 4 20mA  wiring is shown in Fig 2 8     23    VB3 V 5 V BS series inverter    analog meter       analog voltage current    Fig  2 8 Analog output wiring  Note      1  When using analog input  you can connect filter capacitor or common mode inductor between VI and GND  or CI and  GND      2  Because analog input signal 1s easily interfered by outside  the shield cable is required  the cable length must be short  and the shield layer must be grounded well     2 5 4  Connection of communication terminals    The communication port of this inverter is standard RS485 port    With the following wiring methods  you can buildup control system of one host with one slave or one host with several  slaves  Also  you can realize the functions such as real time monitor  remote control  high level automation and others for  the inveter with the host  PC or PLC  software       Connection of inverter s RS485 port and the host     host  RS485 R5232 converter       RESSYDEM       css   terminal terminal    Shield    i description  name    i ji JV power   PEN    i supply      45V        receive data   RXD     HEV 1    F
66. er is used for setting PI threshold and hysteresis of zero frequency operation     If you set the frequency as 0 Hz  PI threshold of zero frequency operation will be disabled     Actual setting frequency 7        E Fb Original setting frequency    Fa  zero frequency operation    Fb  Patzero frequency hysteresis  Fig 4 39 zero frequency hysteresis  As shown in Fig 4 39    Start process     81    V5 series inverter    After start command is set out  the motor will start and accelerate to the frequency in the Acc time until the setting frequency  reach or exceeds the certain value Fb     Stop process     The inverter will not stop immediatelyif the setting frequency is lower than Fb  only when the setting frequency reach Fa   the inverter will stop output     Fa points to zero frequency threshold which 1s defined by P7 18  the value among Fb Fa point to zero frequency hysteresis  which is defined by P7 19     This function can enable the inverter to enter domant state so as to save energy  besides  the inverter will not start at the    threshold of zero frequency operation if the hysteresis 1s set properly   4 2 9  Simple PLC operation parameters   Group P8     simple PLC function can enable the inverter to change its operating frequency and directions automatically to satisfy the  manufacturing requirements  as shown in Fig4 40     Fe  Simple PLC operati   id  F2   maple operation as    VE   ap EA Fs  as  Fi  HA   Nd  F   ias F      3x43  amp  ds          Fa   3    Ti  T2   Ts 
67. er records the codes of latest 6 fault and operating parameters of last 1 fault which can be help for finding  the possible reason of faults  All of these fault informations are saved in group P6  Please refer operation methord of    keyboard to enter group P6     5 3  Fault reset    Once the fault occurs  select one of the following operations to restart the inverter   ST       STOP   1  When fault code displayed in the operation panel  press  Ed key after you confirm the inverter can be reset    2  After setting one terminal among X1     X8 as external RESET input  P4 00     P4 07 17   connect it with COM terminal  and then disconnect them      3  Cut off the power supply     1  Please make sure you know the reason of the fault and get rid of it before resetting  otherwise the inverter may be  damaged permanently     2  If the inverter can not be reset or fault reoccurred after resetting   please check the reason as the inverter may be  damaged by resetting continuously      3  Delay 5 minutes to reset when overload and overheat protection are enabled     92    V5 series inverter    6 Maintenance       6 1  Maintenance    Environment effections such as ambient temperature  humidity  fog  internal component aging and other factors will give rise to the occurrence    of potential faults  Therefore  it is necessary to conduct daily check and routine maintenance to the inverters     6 1 1  Routine maintenance    Please confirm the following items when start the inverter    1  I
68. every time    06H  Write data into the register    08H  Diagnosis    10H  write several data to register     1  Function code 03H  read register  For example  Read data from address2104H  Output current      RTU Mode     Function code 03H 03H    21H  Register address Byte No  02H  04H    00H 00H  Register No  Dada  01H 00H    CRC CHECK Low CRC CHECK Low B8H  CRC CHECK High CRC CHECK High 44H     2  Function code 06H  Write to register  For example  01H  write function code P0 02   50 00HZ        RTU Mode     00H 00H  Register address Register address  02H 02H  13H 13H  Data Data  88H 88H  CRC CHECK Low 25H CRC CHECK Low 25H  CRC CHECK High 5CH CRC CHECK High 5CH     3  Command mode  08H Diagnosis       This command is used for testing that if the communication between the client device  master  and inverter slave  1s  normal Inverter will sent the data to control device   RTU mode        V5 series inverter    CRC CHECK Low CRC CHECK Low  CRC CHECK High CRC CHECK High     4  function code 10H  write several data in the register       Note  V5 VB5 inverters only support one pack of data write   For example  write P0 06   50 00Hz in inverter address 01H     RTU mode     Inquiry information format Reply information format    Register address Register address    Register quantity Register quantity    Byte quantity    Data    CRC CHECK Low CRC CHECK Low    CRC CHECK High CRC CHECK High       5  Verify code    RTU mode  Double bytes with hex   CRC field 1s the binary value has two b
69. f LED  Acc Dec time selection  0  Acc Dec time 1  1  Acc Dec time 2  2  Acc Dec time 3  3  Acc Dec time 4  4  Acc Dec time 5  5  Acc Dec time 6  6  Acc Dec time 7    P8 02 Operating time in stage 1 0 1  P8 04 Operating time in stage 2   10 0  P8 06 Operating time in stage 3 i 10 0  P8 08 Operating time in stage 4   10 0  P8 10 Operating time in stage 5 0 1  P8 12 Operating time in stage 6 i  P8 14 Operating time in stage 7 0 1       S       m     gt                em                        10  Traverse and measure function parameters  Group 9     Group P9  Traverse and measure function parameters    P9 00 Traverse function selection 0  Disabled mE       Enabled    X  Traverse operation control   00   11 X    mode Unit s place of LED  Start mode       0  Auto mode    49    V5 series inverter    1  Manual mode  Ten s place of LED  Amplitude control  0  Variable amplitude    1  Fixed amplitude    P9 02 Predtavere negu    ney 0 00    500 00Hz 0 01Hz 0 00Hz lO      Waiting time before pre   P9 03 0 0   3600 0s 0 1s 0 0s  traverse frequency    P9 04 Traverse operating amplitude   0 0    50 026  01     004     O       P9 05 Jitter frequency 0 0   50 0  0 1  0 0    with reference to P9 04     P9 07 Rising time of trangle wave 0 0    98 026 0 126 50 0    with    P9 08 Reference length 0 000     65 535 km  0 001km 0 000km lO    P9 09 Actual length 0 0   65 535km 0 001km 0 000km   Saving at power off      P9 10 Times of length 0 001    30 000 0 001 1 000 ET o     P9 11 correction coeffi
70. f starting frequency Ranges 0 0   30 0S 00S    Starting frequency points to the initial frequency when inverter starts  as shown in Fig 4 10 as Fs  Holding time of starting    frequency points to the holding time while inverter is running at the starting frequency  as shown in Fig 4 10 as t     Note  Starting frequency 1s not stricted by the lower limit of frequency         Frequency Hz    Fmax    Starting  Frequency    Fs    ti Starting Time    Fig 4 10 Starting frequency and starting time      P8   DC injection braking current at start Range  0  80    0            PAM   DC injection braking time at start Ranges 0 0  60 0S   ws    When P2 00 is setto 1  P2 03 and P2 04 are active  as shown in Fig  4 11    61    V5 series inverter    DC injection braking current at start is a percentage value of inverter s rated current  There is no DC injection braking when  the braking time is 0 00s     Output Frequency       Time    Draking    energy    Output Voltage   Effective value        i DC injection    braking time    Runnin g f 5                                              nou      Command    Fig 4 11 Starting mode 1    t OITLITL HELL    Fig  4 12 Dec to stop DC injection braking    0  Dec to stop   After receiving the stopping command  the inverter reduces its output frequency within its Dec time and stops when the  frequency becomes 0    1  Coast to stop   After receiving the stopping command  the inverter stops output power immediately and the motor stops according to  mechani
71. f there is abnormal noise and vibration with th motor    2  Ifthe inverter and motor heat unusually     3  If the environment temperature is too high    4  If the value of load amperometer is as usual      5  If the fan of inverter can operate normally     6 2  Periodical care and maintenance    6 2 1 Periodical care       Before check and maintenance the inverter  please make sure that the inverter is power off  monitor has no display content    and the indication lamp of main circuit power is off  The checked contents are shown in Tabel 6 1     Table 6 1 periodical maintenance    Main circuit terminals  control  EN If the screws are loose Tighten the screws with screw drivers  circuit terminals  Use dry compressed air with 4   6kgcm   Heatsink If there 1s dust  pressure    Use dry compressed air with 4   6kgcm   Power component If there 1s dust 2 P    pressure  Aluminium electrolytic capacitors If 1t has changed color   particular smell or bubble Change aluminium electrolytic capacitors       TN Use dry compressed air with 4   6kgcm   PCB print circuit board If there is dust  pressure    There is abnormal noise  vibration  or if it has run for  Cooling fan Change cooling fan  more than 20 000 hours     6 2 2  Periodical maintenance    To make the inverter work normally for long time  periodical care and maintenance for inverter s internal electronic  component should be done  The electronic component s lifetime depends largely on their application environment and    preserv
72. g   refer to P3 01     22  Terminal control mode is forcibly enabled  When this terminal is enabled  the running mode will be turn to terminal       control   23724  Control mode selection  Control mode can be selected via ON OFF combination of terminals  The inverter will be  active this function and P0 03 later     Table 4 5 Control mode    Hold the control mode    Terminal control mode  Serial port control mode    25  Start traverse operation  When the traverse operation is as    manual     the traverse function will be enabled if this       terminal 1s enabled  see Group P9 for details    26  Reset traverse operation  No matter the traverse operation is    Manual    or    Auto     close loop this terminal will clear  all the memorized information of traverse operation  Disconncet this terminal can restart traverse operation  Refer to P9 for  parameters instruction     27  Close loop disabled  The terminal can be used to flexible switching the close loop operation and low level operation     70    V5 series inverter    and the setting of start stop control  direction  Acc Dec time mode in low level operation    Notes Switching between close loop operation and low level operation can be realized only when close loop 1s enabled   P7 00    1     28  Pause the PLC operation  The terminal is used to realize pause control  when this terminal is enabled  the inverter will  run in 0 Hz and PLC will not accumulate time  when this terminal 1s disabled  inverter will start with auto 
73. g 4   19 Wire of multi step    Fig 4 20 External device fault input    P3 06 P3 08     4 5  External terminals control jog operation JOGP JOGR  When choose terminal control  P0 03 1   JOGP is used as  forward jog operation  JOGR is used as reverse jog operation  Jog operating frequency and jog Acc Dec time are defined in    65 8  Acc Dec time selection    Table 4 3 Acc Dec time selection  OFF OFF OFF  OFF OFF    OFF    OFF       Acc time 5  Dec time 5  OFF    Acc time 7  Dec time 7  Through the ON OFF combination of Dec time terminal  you can select dec time 1 7     9  3 wire operation control  refer to functional instruction of P4 08   10 Coast to stop CFRS    this function has the same meaning as the description in P2 05  while here it is achieved by  terminal controlling which is convenient for remote control     11 External stop command  this command is valid for all the running channels and it can stop the inverter according to the  setting mode in P2 05     69    V5 series inverter    12  DC injection braking command DB  the terminal can be used to perform DC injection braking to the motor that is running  so as to realize the emergent stop and accurate location of the motor  Initial braking frequency  braking time and braking current  are defined by P2 06 P2 08  Braking time 1s the greater value between P2 07 and the effective continuous time defined by this  control terminal    13  Inverter running prohibit  When the terminal is enabled  the inverter that is operating
74. g command which 1s receiving by       inverter through RS485  the actual running frequency equivalent to this parameter multiply the frequency value receiving  through RS485     This parameter can also set running frequency proportion of several inverters in multimachine linkage mode     Ace  Acc tme     Dec ime  Dec ine 6  koef 7  Dec ine 7    Seven kinds of Acc Dec time can be defined  and the inverter   s Acc Dec time 1 7 can be selected by different combination of  control terminals  Please refer to the introductions of P4 00 P4 05 for the definitions of terminals used to select Acc Dec time   also  you can refer to Acc Dec time defined in P0 17 and P0 18        Dec time 4 Range  0 1 6000 0   w      Acc time 5 Ranges 0 1 6000 0    65    V5 series inverter    Multi frequency 1 Ranges lower limit of frequency   upper limit of frequency     50Hz         Multi frequency 2 Ranges lower limit of frequency   upper limit of frequency 10 00Hz    Ranges lower limit of frequency   upper limit of frequency   50 00Hz           These frequencies will be used in multi step speed operation and simple PLC operation  please refer to the instructions of  P4 00 P4 05 and P8              Range of jump frequency 3 Ranges 0 00   30 00Hz 0 00Hz    P3 33 P3 38 define the functions that will let output frequency of the inverter avoid resonant point of mechnical load  The    reference frequency of the inverter can do jump operation in the certain range of some jump frequency point  as shown in    F
75. ge   ener eds dv      I    b 16      Display present counter   Display present counter value       value    Note s The corresponding relationship of monitor parameter input output terminals and their status display are shown    b 17  b 40    below          shows disabled  lamp off   f         shows enabled Clamp on     Status of X5 input terminal Status of X4 input terminal  Status of X6 input terminal     Status of X3 input terminal    Status of FWD input terminal     Status of X2 input terminal    Status of REV input nat Status of XI input terminal              l  Upper half stands for  Lower halfeind Ipr mum mmm mm the status of input terminal  the status of output terminal 7        Status of OC output s     Status of relay output terminal    V5 series inverter    53    V5 series inverter    4 2  Parameter description    4 2 1  Basic operating function parameters  Group P0     P0 00 Control mode selection Range  0   1    0  V F control    1  Open loop vector control  P0 01 Reference fregunce selection Ranges  17 8 EET    0  Panelanalog potentiometer setting    1  Ey   M keys on the panel  You can set the reference frequency via Ely  HA cv  on the panel     2  Keyboard digital   Initial frequency 1s the value of PO 02  to set the reference frequency via keyboard by modifying the value of PO 02    3  Terminal UP DOWN   Initial frequency is the value of P0 02  to set the frequency via terminal UP DOWN    4s Serial port  remote control    Initial frequency 1s the value of P0 0
76. ge  Parameter Name Setting range  unit  P1 00 Time constant of   0 01    30 00s 0 01s 0 20s  analog filter  P1 01 VI Gain of reference   0 01    9 99 0 01 1 00  frequency selsector    P1 02 m  iefremeeotVI   G00 Pi4 0 01V 0 00V           P1 03 Frequency 0 00 high frequency limit 0 01Hz 0 00Hz  corresponding to  min reference of VI    P1 04 Maxweferenecof VI   Pi04esT0300V 0 01V 10 00V       3    P1 05 Frequency 0 00   high frequency limit 0 01Hz 50 00Hz  corresponding to  max reference of VI   P1 06 Gain of reference   0 01  9 99 0 01 1 00  frequency selector of  CI    38       V5 series inverter    P1 07 Min referenceof CE  0400 P   DO 0 01V 0 00V Lx     Frequency 0 00   high frequency limit 0 01Hz 0 00Hz  corresponding to  min reference of CI    P1 09 Max reference of   P1 07  10 00V 0 01V 10 00V  s A ot  Freguency 0 00     high frequency limit 0 01Hz 50 00Hz  corresponding to  max reference of CI wm ts  Max input pulse   0 1   20 0K 0 1K 10 0K  freguency of    Min reference of   0 0    P1 14 0 1K 0 1K  PULSE  Max reference of PULSE     Freguency 0 00     high frequency limit 0 01 Hz 0 00Hz  corresponding to   min reference   PULSE    Max reference P1 12  Min reference of PULSE      0 1K 10 0K  PULSE P1 11  Max input frequency     Freguency 0 00     high frequency limit 0 01Hz 50 00Hz  corresponding  max reference  PULSE  P1 16 Input mode of CI 0  4   20mA  mI ee 0    c  tlt    3  Starting and Braking Prameters  Group P2        Group P2  Starting and Braking Prameters    Mi
77. h highest digit  running or fault user s password and increase to   check status  a    ENTER PM     DATA  Press the key to Increase to Move to the Increase to Move to the  enter the edit status      4  third dieit  3  second digit       Fig  3 10 Input user   s password    34    V5 series inverter    5  Inquiry fault parameters     QE I um E  Dipy  E03   Paoi Bie    poz  kae  pa  eae    parameter    displed    utput frequency  Key   i    operation    Poruneter    4 Parameter  15  OTI    Pen pa 03  Emon   bao    temperature      a of module ra bus voltage output voltage  NUUS 388                         EE    Fig  3 11 Inquiry operation in fault status    preset frequency   gt     output current           Note     1  You can press ce key to inquire P6 function parameter group in the status of parameters displayed in fault  the range  of the parameters is P6 01   P6 06  when you pressi key  parameter No  will firstly displayed and the parameter value  will be displayed automatically in one second      2 While inquiring  You can press EB key to back to fault parameter displayed status     6  Setting freuqnecy via nm and U     Suppose that the parameters at stop is displaying  P0 01   1  the operation mode is shown below      1 Freguency adjustment adopt integral mode      2 When pressing A    digital of ten s place starts to increase  as the same  when it carries from ten s place to hundred s place  the digital of         the digital increases from unit  place of LED  then it ca
78. he bigger the stator 1s  the higher the boost  voltage        P0 09 i   Inverter s output current  Boost Voltage   100  x  Motors Rated Voltage           2 X Inverter s rated current    Carrier frequency Range s 1 0K  14 0K    Carrier frequency will effects the motor s noise and heat waste The relationship among carier frequency  motor noise  leak    current  and dist are shown below     Comer frequency Decrease Increase       V5 series inverter    Notes  1  In order to achieve better performances  the ratio of carrierfrequency to the maximum running frequency of the  inverter should be less than 36      2  When the carrier frequency is low  the current display value may has error     0  LinearAcc Dec mode   Output frequency increases or decreases according to a constant rate as shown in Fig  4 4   1  S ramp Acc Dec mode   Output frequency increases or decreases according to a S shape curve  as shown in Fig 4 5     Frequency  Upper limit      AREA      of frequency      Time              Fig 4 4 Linear Acc Dec  4 Freguency  g    Upper limit   veter rtt y  of frequency  D i    D  e i  11    i 1 i i        ae   T          Fig 4 5 S shape curve    P0 14 Low speed time of S ramp Range  10 096   50 096 CAcc Dec time   P0 14  P0 15 9096 20 096       P0 15 Linear time of S ramp Range  10 0  80 0   Acc Dec time   P0 14 P0 15 lt 90  60 0     P0 14 and P0 15 are only active when Acc Dcc mode is S ramp Acc Eec mode  P0 13  1  and P0 14 P0 15  lt  90     Low speed time of S ramp is shown
79. he devices  wiring environment  safety distance  grounding method and other    factors The noise contains the following types  electrostatic induction  circuit transmit  space transmit  electro magnetic    Space    induction and so on     Circuit Electromagnetic    Electrostatic    transmission transmission induction    induction       Path 1 Path d 8       Leakage current Power supply   D NS Motor Power Inverter  grounding circuit transmission  cable cable radiatio  RF RF n  Path 2 Path 3        2  Essential countermeasure for suppressing noise    25    VB3 V5 VBS5 series inverter    Table 2 5 solution for control noise    Noise transmit  Solution  path    When the external equipment forms a loop with the inverter  the equipment may operate incorrectly caused by    leakage current of inverter grounding cable  The problem can be solved if the equipment is not grounded     If the external equipment shares the same AC supply with the inverter  the inverter s noise may be transmitted  along its input power supply cables  which may cause interference to other external equipments  Take the  following actions to solve this problem  Install noise filter at the input side of the inverter  and use an isolation    transformer or power filter to prevent the noise from disturbing the external equipment     prevent the RF interfere of power lines      3  Motor cables should be placed in a tube thicker than 2mm or buried in a cement slot  Power cables should be  placed inside a metal tube 
80. ig  2 9 RS485  RS485 232  RS232 cable connection     gt  More than one inverters can be connected through RS485 with the PLC or PC  as the host  as shown in Fig 2 10  Also   you can select one inveter as host and the other inverters as slaves  as shown in Fig 2 11 Because with increasing of the    inverter s quantities  the communication system will be interfered easier  the following wiring is recommended        Fig  2 10 Connection of PLC and inverters    24    VB3 V5 VBS5 series inverter     Inverters and motors are all grounded well        Fig  2 11 Connection of several inverters     Inverters and motors are all grounded well     If the communication 1s still failed with the above connection methods  you can adopt the following measures    1  Use separate power supply for PLC or isolate the power supply      2  Use magnetism ring for the cable and reduce the inverter s carrier frequency     2 6  Mounting guide according with EMC requirement    As the inverter s output wave is PWM  electromagnetic noise will be inevitably generated while it 1s working To reduce the  inverter s disturbance for the external devices  this chapter introduces the mounting method in the following aspects   control the noise  local wiring  grounding  leak current  usage of power supply filter     2 6 1  Control the noise    1  Noise type  The noise made by inverter may affect the neaby equipments and the effection is related to inveter s control system     antinoise and anti jamming ability of t
81. ig  6 15  you can define three ranges of jump frequency at most     A Reference Frequency    After Regulating                                 1i a      Jump Dette trier brentmh ie brachii Lowa  Range of jump frequency 3  Frequency 3 Jemen nd  be        U  VV  Jump   j 1 A  oo ojo oni slaninou mimis aiani seins Range of jump frequency i  Frequency 3                          ay ie  Jump peten Range of jump frequency          a  Fre guency 3 m vana   i at  i    F i Reference Frequency    Fig 4 15 Jump frequency and range       Accumulate running time Ranges 0  65 535K hour DEBE    Acculate running time to reach the reference time  P3 39   the inverter will output signal  refer to function instruction of  P4 08 P4 09     P3 40 refers to the accumulating running time from factory till now       Ba   Display parameters selection 1 Ranges 0000  gt  FFFF 0000    P3 41 controls that if the monitor parameters b 09     b 24 can be displayed in parameter group by four figures  The  parameter values are in hex which should be changed to binary ones according to the sequence of monitor parameters when  using  The relationship between four figures and parameters are shown in Fig 4 16     fal al ele      hra    framed    Fig 4   16 Display parameters selection 1       Note  A  Thousand   s place  B  Hundred   s place     V5 series inverter    C  Ten s place  D  Unit s place    Display parameters  Ranges 0000   FFFF 0000  selection 2    P3 42 controls that if b 25     b 40 can be displayed in
82. in Control Digital Setting  0 01Hz        Freguency resolution  Function Analog Setting  max frequencyx0 1     Start freguency 0 40Hz    20 00Hz  Auto torque boost  manual torque boost 0 1      30 0     Five modes  constant torgue V F curve  1 V F curve mode by user and 3 kinds of    torgue derating modes  2nd power  1 7th power  1 2nd power   Two modes  linear Acc Dec  S curve Acc Dec  seven kinds of Acc Dec time    Accelerate Decelerate curve ME     Maximum 6000 minutes  and unit minute or second  1s selectable     Initial frequency of DC braking  0    15 00Hz  DC braking Braking time  0    60 0 s  Braking current  0    8096    Power consumption braking   Power consumption unit inside  can be connected with external braking resistor    Range of jog freguendy  0 1 Hz     50 00Hz  Acc Dec time of jog operation 0 1      og  60 0s    Internal PI Be able to form close loop control system easily    Multi step Multi step speed running can be realized by internal PLC or control terminals    speed running    Textile wobble frequency Adjustable preset frequency and center frequency    Auto voltage regulation When the power system voltage changes  maintain the constant of output voltage     AVR   Wall mounted or install inside cabinet       Installation    2  General Specification    VB3 V5 VBS5 series inverter      V F curve is optimized automatically according to the load condition to realize  Auto energy saving running  energy saving operation    Auto current limiting running curre
83. inal X2    input terminal X3    input terminal X4    input terminal X5    input terminal X6    input terminal X7 FWD       input terminal X8 REV    Operation mode selection    collector output terminal    19  Frequency selector 1    20  Frequency selector 2    21  Frequency selector 3    22  Terminal control mode   is forcibly enabled   23  Control mode selector 1   24  Control mode selector 2   25  Start traverse operation   26   Reset the traverse   operation status   27  Close loop disabled   28   Pause the PLC   operation   29  PLC disabled   30  Reset PLC stopping   status   31  Frequency reference 1s   input via CI   32  Counter   s trig signal   input   33 4 Counter s zero    cleaning signal input   34  External interrupt input   35  Pulse frequency input  Conly valid for X6    36  Actual length clearing       input    2 wire control mode 1    2 wire control mode 2      3 wire control mode 1         3 wire control mode 2    0  Inverter running  RUN       Frequency arriving    signal  FAR        0 01 1 00Hz s    P4 11  P4 12    P4 13    P4 14  P4 15    P4 16  P4 17    Detecting range of    freguency arrive  FAR        FDTI  frequency  level       2  Frequency detection  threshold CFDTI    3  Frequency detection  threshold  FDT2    4   Overload pre   alarm  OL    5  Inverter under voltage  locking  LU    6   External fault  stop CEXT     7  Output frequency arrive    upper limit of CFH     8  Output frequency arrive  lower limit CFL    9  Inverter zero speed  running   1
84. ing parameters    Forward running indicator  inverter outputs positive phase  the  t ill f fi i the i        motor will run forward after connecting to the inverter If FWD and REV indicators all light on    it means that the inverter are under DC    Reverse running indicator  inverter outputs negative phase The braking status    motor will run reverse after connecting to the inverter    un       o       G  O     o  c    vm  un  Bg  G       un    This indicator will light on when the inverter has fault     Display function       3 2 4  Display of the operation panel    The inverter s operation panel can display four paraters in stopping  editing  fault alarming and running   1  Parameters displayed in stopping status    When the inverter stops operation  operation panel displays monitor parameters in stopping status  the normally content is  setting frequency  b 01 monitor parameter   As shown in Fig 3 4 the unit indicator on the top right indicates the unit of this  parameter    Pressing  a key can display other monitor parameters in stopping status circularly  the first seven monitor parameters  in B group are fault displayed value and the other monitor parameters can be defined by function code P3 41 and P3 42   please refer to Chapter 5 for details  Press in display status can shift to b 01 which can set frequency  otherwise    the panel will display the last monitor parameter constantly     3l    V5 series inverter             Hz Y A  o O o    FWD REY  o       A  e    WD 
85. input signal and reference frequency    36  Autual length clearing input  If this terminal is enabled  the autual length parameter P9 09 will be cleared to zero     P4 08 FWD REV operation mode selection Range  073  oo      This parameter defineds four operaion modes via which external terminals can control inverter      s  pepe bl     FWD  1   Forward   s REV  eem  em  Ip    Fig 4 21 2 wire operation mode 1    0  2 wire control mode 1       1  2 wire control mode 2    DE   ES s  rs    5 FWD  INN L   Forward i     REV       Fig 4 22 2 wire operation mode 2    2s 3 wire control mode 1  SB1  Stop button  SB2  Forward button  SB3  Reverse button    7     V5 series inverter    VS  SB2 m  SBI A  SB3 bus    COM    Fig  4 23 3 wire operation mode 1    X1 1s the multi function input terminal of X1 X6 here you should define its function as No 9    3 wire control mode        3  3 wire control mode 2  SBI  Stop button  SB2  Running button    n o   tnt       XI    K2 EH Reverse       5 COMI    Fig 4 24 3 wire control mode 2    X1 is the multi function input terminal of X1 X6  here you should define its function as No 9    3 wire control mode      Notes When the inverter stops due to fault  it will start immediately if the terminal control mode and terminal FWD REV  are enabled and the fault is cleared     P4 09 UP DOWN speed rate Ranges 0 01    99 99Hz s 1 00 Hz s    This parameter defines the change rate of reference frequency that is changed by UP DOWN     P4 10 Bi direction open colle
86. ly under general condition        Themounting space and distance are shown in Fig  2 1     gt  When several inverters are mounted up and down  air diversion plate should be fixed in the middle as shown in Fig  2   2        VS    100   m 4 Air diverting    T plate    VS  Fig  2 1 Mounting Space Fig 2 2 Mounting of Multi Inverters    2 1 3  Mounting and removing       Removing  Romove the four screws on the cover with phillips screwdriver     Mounting  Allign the mounting holes and then fix the screws     VB3 V5 VBS5 series inverter    2 2  Wiring   N   B Wiring after power off for at least 10 minutes  otherwise  an electronic short may occur    B Donotconnect AC power to output terminals U  V and W    B Both the inverter and the motor should be safety grounded as there is leakage current inside the inverter  The diameter  of grounding copper cable must be more than 3 5mm     grounding resistor must be less than 10ohm    B Withstand voltage test of the inverter has been done in the factory  users would better not do it again    B Do not install electromagnetic contactor  absorption capacitor or other resistance capacitance absorption devices  as  shown in Fig2 3    B In order to make the input over current protection and power off maintenance easily  the inverters should connect  power supply via braker    B The connection cable of relay I O circuit  X1 X6  FWD  REV  OC  DO  should select the twisted pair or shield cable    with diameter over 0 75 mm     One terminal of the shi
87. n with steady load and speed     AVR funciton Ranges 0 1 2    AV R function points to regulating voltage automatically When the input voltage of inverter fluctuates  AVR function can    keep it steady    In Dec to stop process  if AVR is disabled  the Dec time is short and the running current is big  if AVR is enabled  the motor  decelerates steadily  the running current 1s small and the Dec time 1s prolonged    0  Disabled   1  Enabled   2  Disabled in Dec process    Gain of slip compensation Range  0 150    0       This function can make suitable regulation for inverter   s output frequency according to the load changes  and control the  63    V5 series inverter    speed at a certain value with dynamic compensation for slip frequency of asynchronism motor  If use auto torque boost    function in addition  better low speed moment characteristic can be get  As shown in Fig 4 13     Slip Compensation 100    A Output current      150  5 Ad  gt        1    100  EE S ae c  Before Shp   3 Slip C        1 Ship Compensation  Compensation WE      HRLE IARIGASEZHIXGZARARZZAJEZSRXSRIRIERSZARRZHSRARALARIASZIRGGXG IEEE    1  4 i     507               Motor Speed    i i  A    i      Fig 4 13 Slip Compensation      P306     Jog operating frequency Ranges 0 10    50 00Hz 5 00Hz       P3 07 Acc time of jog operation Ranges 0 1  60 0S   5805  P3 08 Dec time of jog operation Ranges 0 1  60 0S   505    Jog operating frequency has the highest priority  No matter what status the inverter 1s in  o
88. nce there 1s a jog operating  command input  the inverter will run into jog operating frequency within Acc Dec time of jog operation  as shown in Fig 4   14    Acc time of jog operation means the time needed for inverter from 0 Hz to upper limit of frequency  Dec time of jog    operation means the time needed for inverter from upper limit of frequency to 0 Hz            i Dec time of jog operation  Jog Operating       55555555 pe  Frequency Acc time of d Jog           Frequency      a 3 Jog   J    atl        Ms Operating        en     SMS Operating   Signal i   Signal    Fig 4 14 Jog operation    Note  1  Jog operation can be controlled by panel  terminal and serial port      2  If jog operation command has been canceled  the inverter will stop according to Dec to time     Communication  Ranges 000   155  configuration    You can change baud rate  digital format and communication mode by setting unit s place  ten s place and hundred s place  of P3 09   Unit s place of LED  Set baud rate  the values are shown below     0  1200BPS  1  2400BPS  2  4800BPS  3  9600BPS  4  19200BPS    V5 series inverter    5  38400BPS  Ten   s place of LED  Set digital format  the values are show below   0  1   7   2 format  no parity check  1 stop bit   7 data bits  2 stop bits  no parity check   1   7   1 format  odd  1 stop bit  7 data bits  1 stop bits  odd  1   7   1 format  even  1 stop bit  7 data bits  1 stop bit  even    1   8   1 format  odd  1 stop bit  8 data bits  1 stop bit  odd    l
89. nction code copy among frequency inverters by remote keyboard    Over current protection  over voltage protection  under voltage protection  over  Protection Function l  heat protection  over load protection    Optional parts Braking parts  operation panel installation seat  operation panel extension cable       1 3  Product appearance   VB3 series 0 4 0 75KW    VB3 V5 V BS series inverter                                                                                           LED ADIIT  5 i n i 4 bits LED display  We    fle Buttons                                                                Control   4                      terminals    Analog potentiometer                                                                                                                                                                                                                                                                                              El  al     ssl i  Power 4   i  terminals   ET A  al li   sl A  Ek  Mounting hole  VBS series 1 5KW 3 7KW VBS series 5 5KW 7 5KW       VB3 V5 V BS series inverter                                                                                                       O ey  000000  cann  JILILILI  THINGET C3  ENT JOG STOP    DATA   REV p  ENT JOG  DATA REV                            A WARNING      STORED CHARGE DO NOT TOUCH  UNTIL 10 MIN  AFTER DISCO   NNECT   ON     DO NOT CONNECT AC POWER TO  OUTPUT TERMINALS OF    U VW         RISK OF ELECTR
90. nction is enabled  P7 00 1   the inverter will enter the close loop running modes  that 1s  it  will perform PI adjust according to the reference and feedback value  refer to parameters in group P7   PI adjuster  output 1s the essential command of inverter s output frequency  Close loop running can be disabled by multi function  terminal  No 27 function  and the inverter will be in a running mode with lower priority    2  PLC running  If PLC function is enabled  Uni   s place of P8 00 1s set to a non zero value   the inverter will enter PLC running mode  and running in the pre defined running mode  refer to parameter description in group P8   PLC running can be  disabled by multi function terminal  No 29 funcition  and the inverter will select a running mode with low priority    3  Multi speed running  Select Multi frequency 1   7  P3 26     P3 32  to realize multi speed running by no zero combination of multi function  terminal  No 1  2 and 3 functions    4  Common running    Common running is actually the open loop running mode       so       lt 3   gt  C    High priority           Closeloop setting  ctive  F5 00 gt 0 7       N    A b      Terminal for disabling    N   Close loop   s  close oop operation   operation      i   M   M      M        V  enabled           PLC setting active            N Y p ni for disabling  N   PLC operation      PLC enabled     ren           MLLLILLILLLILDLLLLILIRLLELLELLLLLLI       E                                         M      M             
91. ng input    Introductions of the functions shown in Table4 1   17 3  Multi step speed control terminals  Up to 7 speed reference can be set by different ON OFF  open close        combination of the function terminals  at the same time  you can select corresponding Acc Dec time     Table 4 2 On Off combination of function terminals     x    x       mm   Aem O    Multi step frequency 4 Acc Dec time 4  Multi step frequency 5 Acc Dec time 5  Multi step frequency 6 Acc Dec time 6  Multi step frequency 7 Acc Dec time 7       The above frequencies can be used in multi step speed running and simple PLC running  this manual take multi step speed    running as an example     68    The definition of X1  X2 and X3 are shown below     V5 series inverter    P4 00 1  P4 01 2  P4 03   3  X1  X2 and X3 can be used to achieve multi step speed operation  as shown in Fig 4 18   A Output Frequency    Speed 7  speed        SpeedS       i   Speed 4         Speed3         Pd     Speed     3   Common      M Speed     operatmz   ONE      n      t0     1          frequency  pet     i      BAR     i  Dr   i  speed    command      Al m          a    Fig 4 18 Multi step speed operation    In Fig 4 19 terminal control is selected  the operating direction is controlled by K   Kg In Fig 4 18  Common operating  frequency or 1 7 multi step frequency can be controlled by different combination of K   Ky  K3     Circuit Breaker    RB   KM  Power AS V  4 i  W  STIT  PE  K  V  K2  K3 FWD A  COM REV     COM       Fi
92. nmum Factory setting   Change  Parameter Name Range    P2 00 Starting mode 0  Start from the starting  frequency  1    Brake first and then start  from the starting frequency  2  Start on the aaa             P2 01 Starting frequency  020   2000Hz   0 01Hz 0 50Hz EE      P2 02 Holding time of starting   0 0   30 0s 0 1s 0 0s  ei  om   mq om  P2 03 injection braking   0 0    80 026 0 126  mom om om om  P2 04 DC injection braking time   0 0   60 0s   0  Dec to stop  P2 05 Stopping mode 1  Coast to stop 1 X   2  Dec to stop  DC braking   ma ion br  ne iat  ootd To       39    O    39       V5 series inverter    P2 07 DC injection  waiting time at stop    braking   0 0    60 0s    braking   0 0    80 024       P2 08 DC injection  current at stop    4  Auxiliary running parameters  Group P3        P3 00    40    Name    Combination    frequency input    Range    of   0  VI CI    1  VI   CI   2  External pulse reference   VI    Increase Decrease key reference   3  External pulse reference     VI      Increase Decrease key reference   4  External pulse reference   CI   5  External pulse reference    CI   6  RS485  VI   Increase Decrease  key reference   7  RS485     VI     Increase Decrease  Key reference   8  RS485   CI   Inerease Decrease  key reference   9  RS485     CI     Increase Decrease  key reference   10  RS485   CI   External pulse  reference   11  RS485     CI     External pulse  reference   12  RS485   VI   External pulse  reference   13  RS485     VI     External pulse 
93. ns of CN1 terminal are shown as bel    Tabl    Termina  Name  1 Mark    Inverter  Relay output  TB   Multi function  terminal  relay output terminals    2  Control circuit terminals CN2    VB3 series single phase 0 4   0 75KW    VBS series single phase 1 5KW    VBS series three phase 1 5   3 7KW    VBS series three phase 5 5   7 5KW    V5 series 11    55KW    ow in Table 2 3     e 2 3 Function of CN1 on control panel    Function Description Specification    Inverter TA TC  normal close   Multifunctional relay output   TA TB  normal open  terminals  Please refer to  Contact Capacity    terminal function parameters  AC250V 2A  COS   1   P4 11 and description of output   AC250V 1A  COS   0 4   terminals DC30V 1A       A B xl x2 AJ FWDREVTIDVLI COM  COCOKOOKOOIKOKCOOD  COM CITIO0V El x2 AZ FAN REY A B  SERE BABA  A B kl ke ka 14 AG FWD REY      Z4Y COM AU CI 10V GHD    SBRERERREBEBB LB    A Al ka ko FRO REY IO AJ VI 10Y    SISA II             B az 14 46 COM OC GHD CI GHD PE    x T A x v al   d T            B COM  2 14 26 COM OC GHD CI GHI PE    Fig  2 5 Terminals on control panel    21    VB3 V5 VB5 series inverter  3  CN2 terminals  function description are shown as below     Table 2 4 CN2 terminals  function description    Name Terminal Function Description Specification    x Positive terminal of   RS485  E differential signal standard RS485 port  please use  Communication RS485 port   F      Negative terminal of RS485 twisted cable or shielded cable  differential signal    Mul
94. nt is limited automatically to avoid trip caused by overcurrent  Fix length control The frequency inverter will stop running when reaching the fixed length    Communication With RS485 port  support Modbus RTU protocol  Be with master slave multi   function devices linkage function  Operation panel setting  control terminals setting  serial port setting  three modes    Running command channel  are exchangeable     Keyboard analog potentiometer setting   4 E2 keys setting  function code    Operating l digital setting  serial port setting  UP DOWN terminal setting  analog voltage     Freguency setting channel mE  function setting  analog current setting  pulse setting  combination setting  different setting    modes can be selected    1  Forward Reverse running command  6 channels programmable digital input  can  Digital input channel  set 35 kinds of function  X6 support 0 20KHz pulse output    Analog input channel 2 channels analog input    4   20mA and 0    10V can be selected    1 channel analog output    0    10V  be able to output setting frequency  output  Analog output channel  frequency    Digital  pulse output 1 channel programmable open collector output  1 channel relay output  1 channel    channel 0 20K Hz pulse output    LED Display Can display setting frequency  output voltage  output current and other parameters     Display output frequency  output current  output voltage and other physical  External meter Display 7  Operation panel quantities    Parameter Copy Fu
95. o P4 08 for details Input resistance  R 2KQ  terminal SEV Reverse  instruction about 2 wire and 3  Highest input frequency 200Hz  running wire control function    Multifunction  X1  input    Multifunction  X2  input Z          Multi function digital input  Multifunction          mE X3 terminals  refer to input terminals     Multifunction input input 3 m      function description in terminals     terminal Multifunction    X4   function parameters P4   input 4 l         common terminal  COM   Multifunction  X5    input 5  Multifunction  X6 l  input 6   24V power  Offer  24V power supply  Power supply 24V      supply  negative terminal  COM   22    C  I  I  O       Input voltage range  9 30V    Al X4  FWD  REV N Close   is enabled  COM         VB3 V5 VBS5 series inverter     10V power  Offer  10V power supply  10V Max output current 50mA  supply  negative terminal  GND      10V    power supply  Reference ground of analog signal    GND  common  and 10V power supply o    o   COM is isolated with GND inside    terminal l  inverter     24V power  COM  supply common  Digital signal I O common terminal       terminal       2 5 3  Analog input output terminal wiring    1  VI terminal voltage signal input  wiring is shown as below     V5     10V  I preneenom X4 yy  0  HUV     o L      GND  ground the proximal PE    point of shield cable    Fig  2 6 VI terminal wiring diagram    2  CI terminal analog input  jumper select voltage input 0 10V  or current input 4 20mA   wiring is shown as b
96. ok kava k  n n  d V 52  4 2 1  Basic operating function parameters  Group PO              oo oooovnnovnnnnoon noo ne rr 52  4 2 2  Parameters of reference frequency  Group P1     nennen nn 57  4 2 3  Starting and braking parameters  Group P2     enne nn 59  4 2 4  Auxiliary running parameters  Group P3     noo oo nu 61  4 2 5  Function parameters of terminal  Group P4  ou    cesescesssscessscccesscscesssccessecconssescesseecesseescesssecesscecesseeeceseeecesseecessees ons 66  4 2 6  Protective function parameters  Group P3  sesoccerissonsniasatansaveiesewosnastivavsnenddiommssassdcassiacesvunbsliocaimadsatwnssventeamseduscatissenantes 74  4 2 7  Fault recording parameters  Group P6            esses RR RR RR sette RR 76  4 2 8 Close loop control parameters  Group P                       oooooooonvnnnnnn n   en re ee rr T1  4 2 9  Simple PLC operation parameters   Group P8   ieccccecccsccccsscccesscecesseeccsseeccssseecesseecesssecessseeeescecesssecesseeeesseeceseecestseeess 80  4 2 10 Traverse and measure function parameters  Group P9   essessssesssesssssressresserrssrresertessressresssrressreesrressresssrrsserresrresseeessres 83  4 2  1  Vector control parameters  Group PA            sccesccerercseereverscverccvenetsevenconetevstevsnsessssecesascossscsenessenencenenconeneseeseveanevencesens 85  4 2 12  Specail application function parameters  Group PB    eee eene enne nennen nnne nenne seen nennen nennen ens 86  d 2 13  Factory seting  Group PE  snanar drano RNa EEEE R E ERE 
97. ower the immunity level     Gain of reference frequency selector of VI    P1 01  P1 02    P1 03    P1 04    Range  0 00 P1 04 0 00V    Ranges 0 00 upper limit of frequency 0 00Hz    Ranges P1 04 10 00V 10 00V    Ranges 0 00 upper limit of frequency 50 00Hz    Min reference of VI   Frequency corresponding to min reference of  VI   Max reference of VI    Frequency corresponding to max reference of    Ranges OOI 999  dm  Range  0 00  P1 09 0 00V    Gain of reference freguency selector of CI    Min reference of CI    Freguency according to min reference of CI    Range  P1 07    10 00V 10 00V  Range  0 00 upper limit of frequency 50 00Hz    59    Max frequency of CI    Ranges 0 00 upper limit of frequency 0 00Hz       Frequency according to max reference of CI    V5 series inverter    Max input pulse frequency of PULSE Ranges 0 1  20 0K  Min reference of PULSE Ranges 0 0 P1 14    Ref  Amplify Set  selection PL OL P1 06 frequency  P   n1 curve       The relationship between VI and preset frequency is shown below         Reference Frequency       Arain Amax Arun Amax   1  Positive  2  Negative   amp    Reference of VI Arum  Min reference Prin   Frequency corresponding to  max   Max reference min reference    Pmax  Frequency corresponding to  max reference    The relationship between CI and reference frequency is shown below        Aun Amax Amm    max   1  Positive  2  Negative   amp    Reference of CI Armin  Min reference Proin  gt  Frequency corresponding to  Amax     Max reference
98. p preset frequency    P7 14 Close loop adjustment characteristic Range  0 1    0  Positive When the reference increases  it will be enabled when the motor speed increase     Note  Define the relationship of reference and speed     P7 15 Integral adjustment selection Range  0 1    0  Stop integral adjustment selection when the frequency reaches upper limit or lower limits    1  NegativeWhen the reference increases  it will be enabled when the motor speed reduces    1  Continue the integral adjustment selection when the frequency reaches high limit or lower limits    For the system need quick response  cancel the continuouse integral adjustment is recommended     P7 16 Close loop preset frequency Range  0   upper limit of frequency 0 00Hz       P7 17 Holding time of close loop preset frequency Ranges 0 0   250 0S     MS o    This function can make the close loop adjustment enter stable stage quickly     When the close loop starts  the frequency will accelerate to the preset value set by P7 16 according to Acc time and the inverter  will running with this freuquency in the holding time set by P7 17  then running according to close lood character  as shown in  Fig4 38     Notes If the function of close loop preset frequency is not needed  you can set the preset frequency and holding time as 0     P7 18 PI Threshold of zero frequency operation Ranges 0 00   500 0Hz 0 01Hz       P7 19 PI hysteresis of zero frequency operation Ranges 0 00   500 0Hz 0 01Hz    The two function paramet
99. play     If you want to view fault information  press to view P6 parameter in editing status After you finding out and solve  the default  the inverter can be reset by key in operation panel or control terminals or communication command  The  fault code will not disappear until the fault 1s cleared    Notes For some serious default such as over current  over voltage etc  please do not reset the inverter to rerun before    confirming that the default is cleared  otherwise the inverter may be damaged                                                           Fig 3   5 Alarming display status  4  Editing status    This status can be entered by pressing fag key in stopping  running or fault alarming status if there is a user   s password   you should input correct password  refer to P0 00 and Fig 3 9 for details   This status can be displayed in three level menu   they are  code gruop  gt  code No      code parameter  you can enter the sub menu by pressing Ein code parameter status     MENU JN  press Em to save parameter and press    to exit without saving     32    V5 series inverter      First level menu Second level menu Third level rnenu  MENUWU ESC ENTER DATA ENTER DATA    Oooo000    k       MENU ESC MENU ESC  Parameters displayed in I  stoppinz status   parameters displayed in l  runninz status  or fault alarming displayed    Fig  3   6 Editing status  3 2 5  Panel operation procedure    The following shows how to do various operation by operation panel   1  Parameter Displa
100. range of it is a percentage of the    inverter s rated current     Frequency decrease rate when current limiting  P5 05  defines the rate of output frequency when the inverter is in auto    current limiting status     If the decrease rate 1s set too small  auto current limiting status may not be switched and overload fault may occur  If it 1s set  too big  the frequency will change too sharply and thus the inverter may be in generating status for long time  which may    result in overvoltage protection     Auto current limiting function is always enabled in Acc or Dec process  Whether it 1s enabled in constant speed operating    process 1s decided by auto current limiting selection  P5 06    P5 06   0  Auto current limiting function 1s disabled in constant speed operating process     F5 06    1  Auto current limiting function is enabled in constant speed operating process     In auto current limiting process  the inverter s output frequency may change  therefore  when the inverter s output frequency    is required to be stable  this function is not recommended     P5 07 Setting of restart after power off Range  0 1 EE       P5 08 Holding time of restart after power off Ranges 0 0   10 0S   95S    P5 07    0  Restart after instantaneous power off is disabled   P5 07   1  Restart after instanteaneous power off is enabled     If instantaneous powe off  E 11 displayed in inverter s LED  occurs when inverter is in running status  after repowering  it       will detect speed automa
101. re and   speed   0  Stop integral adjustment selection when the   1 X   frequency reaches high limit or lower limits  P7 16 Close loop preset frequency 0    upper limit of of frequency 0 01 Hz 0 00Hz lO o   P7 17 Holding time of close loop 0 0 250 0s 0 1s X    Threhold of zero freguency   0 00    500 00Hz   P7 18 l 0 01 Hz 0 01 Hz X  operation  Hysteresis of zero frequency   P7 19 l 0 00 500 00Hz 0 01 Hz 0 01Hz X  operation    9  Simple PLC operation parameters  Group P8        P7 15 frequency reaches upper limit or lower limits    Integral adjustment selection    1  Continue the integral adjustment selection when the       Group P8  Simple PLC operation parameters    P8 00 Simple PLC operation   0000   1113  mode selection Uni   s place  mode selection   0  Disabled  1  Stop after single cycle of operation  2  Holding at the final value after single cycle of  operation  3  Operate continuously  Ten s place   PLC restarting mode after stopping   48       V5 series inverter    0  Run again from stage 1  1  Continue to run from the stopping stage    Hundred s place     Save at power off    0  Not saving   1  Save the time and frequency at power off  Thousand s place  Selecting the unit of time  0 second    1 minute    P8 01 Stage 1 setup 000   621  Unit s place of LED  frequency setup  0  Multii  1   1   7   1  Frequency is decide by P0 01  Ten s place of LED  Operating direction selection  0  Run forward  1  Run reverse  2  Decided by operating instructions  Hundre   s place o
102. rned into hex     function code     Take the following as examples     Read function code P1 02    01H  03H  01H  02H  00H  01H  CRC1  CRC2  Read the reference frequency of inverter    01H  03H  21H  02H  00H  01H  CRC1  CRC2  Write function code P1 02  the write value is 1   01H  06H  01H  02H  00H  01H  CRC1  CRC2  Running command        99    V5 series inverter    01H  06H  20H  00H  00H  01H  CRCI  CRC2    Definition of fault code     Fault code    01H Fault function code  Inverter can not find   03H  06H  08H     Fault data address  Inverter can not find data address    03H Fault data  data over the limit       Note  The parameter address must in hex format  as the function codes of parameters are in decimal system  so you must let  them turn to hex For example  the Modbus address of function code P2 11 1s 020BH     100       SLIR E    FOSS TH  REPA T   BES  IE JG 1H 88 pal JT c D   Gill ser Mr pd 7 c PVR   HZ  214072   Hii   86 510 85134136   IE     86 510 85111290          Xinje Electronic Co   Ltd    4th Floor Building 7 Orignality Industry park   Liyuan Development Zone  Wuxi City   Jiangsu Province  China 214072   Tel  86 510 85134136   Fax  86 510 85111290    
103. rries from unit s place to ten s place  the  hundred s place starts to increase  so does the digital of thousand s place  If you release  A  and press it again  the digital  will restart to increase from the unit s place of LED      3 When pressing  7    the digital decreases from uni   s place of LED  then it borrow from ten s place   the digital of ten s  place starts to decrease  So does the digital in hundred place and thousand s place If you realse Lv key and press it again     it will restart to descrease from the unit   s place of LED     7  Lock the panel    If the panel is unlocked  press key for five seconds can lock the panel   8  Unlock the panel    If the panel is locked  press EE key for five seconds can unlock the panel     3 3  Start up  3 3 1  Checking before starting up  Please wire the inverter according to    Wiring      in this manual     3 3 2  Start up the inverter for the first time    After checking the wiring and AC power  switch on the AC power supply to electrify the inverter  The inverter s panel will  display dynamic screen and then the contactor closes  When the LED displays preset frequency  the initialization of this  inverter is completed  The procedure IS shown as Fig    35    V5 series inverter       Wing according to section 2 4            Connection is correct     Y    Input voltaze  ds correct            Display dynamic Image      Y N        Contractor closes         isplay  x ireguency setu      Y    Start up Start up fails         Fig 
104. s output  it means the drive has no fault  its DC bus voltage is  normal and it can receive starting command    15  Inverter fault  If there is fault with inverter  indicate signal will be output    16  Start frenquence running time   17  Start DC injection braking time   18  Stop braking time   19  Upper and lower limits of traverse operating frequency An indicate signal will be output if the traverse operating  frequency calculated by central frequency is higher than upper limit of frequency  P0 19  or lower than the lower limit of  frequency  F0 20   as shown in Fig  4 25           Upper limit of frequency             5 n0 coo eee          oco oe    Lower limit of frequency                                    E    Upper and lower frquency  of traverse operating    Fig 4 25 Upper and lower limits of traverse operating frequency    73    V5 series inverter    20  Set running time arriving  When the accumulating time  P3 40  arrive the reference time  P3 39   an indication signal  will be output     P4 12 Detecting range of frequency arrive CFAR  Range  0 00  50 00Hz     5H      This parameter is the additional definition of No  1 function in Table4 6  As shown in Fig 4 26  when the output frequency  of inverter is within the detecting range of reference frequency  pulse signal will be output     Output    Reference  Prequency    Time       Fig 4 26 Frequency arriving signal    P4 13 FDT1 Cfreqeuncy  level Range  0 00 upper limit of frequency 10 00Hz  P4 14 FDT1 lag Ranges 0 0
105. should be derated due to  the worsening radiating effect  If low speed constant torque long term running 1s required  then a special variable frequency  motor is needed      gt  Motor insulation    When using the V5 F5 series inverter  make sure to confirm the insulation of the motor which will be used to avoid device  damage  Besides  do the periodic check for the insulation condition of the motor located in the bad environment to    guarantee the system can operate safely    gt  Negative torque load    If in the case of improving load  negative torque may occur  Braking units should be connected with the inverter  or over    current and over voltage fault may happen     VB3 V5 V BS series inverter     gt  Mechanical resonance point of load    The inverter may encounter the mechanical resonance point of load within certain output frequency range  Jump    frequencies have to be set to avoid it       Capacitor and resistor    Because the inverter output pulse wave  capacitor and resistors shouldn t be connected with the output terminals of the  inverter  or the inverter may trip or components may be damaged  Besides  don t connect switch components such as air  switch and contactor with the output terminals 1s recommended  as shown in Fig 0 1 If switch components need to be    connected with the output terminals  make sure output current of the inverter 1s zero when switch 1s acting      INVERTER       Fig 0 1 Capacitor 1s prohibited to be connected with    output terminals of
106. single cycle  ra Fe  F gt    F7 F gt   AE  2 f   1 F   3 i P    d  j   1 j   j   EL    Fs i G R  i Fs  i DM  Fy N         F1 i 13  fi ii  fi i i     EY      ifd  PLC operation   i i i f   i i i     i         h c    i               lt         d       anae ees     nen       nen        zan 0 neem     au f a                               AAA      A                         A        4 AA           4    45                      O                                   RUN command    STOP command    Fig  4 43 PLC operate continuously mode    3  Operate continuously  As in Fig 4 43  inverter start next cycle automatically after operating for one cycle  it will stop  until stop command is input    Ten   s place    Restarting mode after stopping   0  Run again for stage 1   1  Continue to run from the stopping stage   Hundred   s place    Save at power off   0  Not saving   1  Save the time and frequency at power off   Thousand   s place  Selecting the unit of time   0  second   1  minute   Ten   s place of LED  PLC restarting mode after stopping   0  Run again from stage 1  Inverter will start to run from stage 1 if the stop is caused by stop command  fault or power off   1  Continue to run from the stopping stage  For the stop caused by stop command or fault  inverter will recorc the time in  current phase automatically  then restart to enter this stage with the same frequency and run continuously in the rest time  as  shown in Fig 4 44     83    V5 series inverter         Output  frequency
107. speed and PLC  continue to run  Refer to group P  for instructions    29  PLC disabled  This terminal can be used to flexible switching the PLC operation and low level operation    Note  The switching between PLC operation and low level operation only when PLC 1s running  the unit s place of P8 00 1s  not to 0     30  Reset PLC stopping status  When PLC is in stopping status  the enabled terminal can clear PLC running stage  running    time  running frequency and other informations of PLC stopping memory  Refer to P8 for instructions     31  Frequency reference is input via CI  Frequency reference is input via CI forcibly when the terminal is enabled  and it  will involute when the terminal 1s disabled     32  Counter s trig signal input  This terminal is used to input pulse signal to the internal counter of the inverter  The  highest pulse frequency is 200Hz  The present counting value can be saved at power off  See P4 22 and P4 23 for details   33  Counter s zero cleaning signal input It is used to clear the counter to zero in conjunction with terminal 43    34  Externalinterrupt input A fter receiving external interrupt input signal  inverter will lock output and running in 0 Hz   once the interrupt input signal release  the inverter will start on the fly and continue the PLC operation    35  Pulse frequency input Conly valid for X6   This terminal can receive pulse signal as reference frequency  please refer  to P1 11 P1 15 for the relationship between pulse frequency of 
108. sword will be valid    immediately  The password for super user 1s    2644        Software version is set by factory and it can not be modified by user     V5 series inverter    5 Fault Diagnosis and Countermeasures       5 1  Fault diagnosis and countermeasurs    When fault occurs  the function code and its contents will be shown in LED display  the protection function starts  the inverter  stops outputting and the fault relay contact point is activated Before seeking services  the subscriber may conduct the self   check according to the prompt given in this section  analyze the fault causes  and find out the solutions If the fault belongs to  the causes described in the broken line box  please seek the service by contacting the inverter agent or directly contacting our    corporationl   Table 5 1 Fault content and countermeasures    Fault Code Fault Type Possible reason of fault countermeasure  Too heavy the load and too short the Acc time Prolong the Acc time  V F curve 1s not suitable Adjust V F curve    Over current  fure The rotating motor restarts after stop Set as  start on fly  function  during  acceleration Adjust the value of manual torque boost or change it as  Too large the value of torque boost  auto torque    Inverter power is too low Select a high power inverter  Too short Dec time Prolong the Dec time               Over current     during  The load generates energy or the load inertial is    Connect suitable braking kit    deceleration       Inverter power is
109. t communication error x    Improper setting of alarm parameter Modify the setting of P3 09    P3 12  Host PC does not work Check host PC  check the wiring    STOP  RESET       Communication error    Press key to reset or install power filter at the input    Severe disturbance  System disturbance    side of the inverter    W R error of DSP in main control board Press keys to reset or seek service    91       V5 series inverter    E   PROM Press  W R error of control parameter  W R error    E DC brake overcurrent  Set wrong current Set wrong current of DC brake     DC brake Decrease the brake current      Main circuit lack  Lack of phase when input current  momentary    OP    E key to reset or seek service       Check the reason and reset  voltage the power off  power supply point loose  power    E 24 l Check the power supply  electromagnetic  supply voltage fluctuates serious and make the  j UN Ask the factory  contacter action error  main circuit contacter open  Input power supply lack of phase  momenta  Lack of phase when dd   uer i A Y  ower off  power su oint loose  power  E 30 31   inverter running or A   EU i Check the reason then reset    supply voltage fluctuates serious and make the    stop       voltage between phases unbalance  SUM Panel communication  Operate panel and CPU board connection is not Uninstall the operate panel and install again  ask  error good  the control circuit of inverter is not good  the factory for help  5 2  Fault records    This series invert
110. t record      P6 01 Output frequency of   Output frequency of previous fault  previous fault record  P6 02 Setting frequency of   Setting frequency of previous fault  previous fault record  P6 03 Output current of previous l  Output current of previous fault  fault  P6 04 Output voltage of previous  Output voltage of previous fault  fault  P6 05 DC injectiong bus voltage   DC injectiong bus voltage  of previous fault previous fault  P6 06 Module temperature of   Module temperature of previous  previous fault fault                     8  Close loop control parameters  Group P7        Group P7  Close loop control parameters    P7 00   Disabled  Close loop function selection    Enabled  P7 01 Reference channel selection   Digit input    VI 0 10V        47    V5 series inverter    P7 02 Feedback channel selection 0  VI 0 10V  1 1  1  Analog reference by CI  2  VICI  3  VI CI  4  Min  VI  CI   5  Max  VI  CI      ms  tn o E  o   mo  Rune           ocos m  ok  o I  mas   stereo i de  om maw        Oo  mos   ine one ms  e  o I    P7 07 Feedback value corresponding   0 0    100 096 0 1926 0 0   to min reference    P7 08 Min reference P7 06 100 0  100   o    P7 09 Feedback value corresponding   0 0    100 026 0 1926 100 0   to max reference    Pu  messer  3559 Fr  we o  Fu meus     escas              Tim  om o      P7 13 Limits of deviation 0 0   20 0  a   20  Jo      P7 14 Close loop adjustment   0 Forward 1 X  characteristic 1 Reverse   Note  relationship between reference temperatu
111. tate   Program Exit Enter or exit programming state    P3 45   0  jog running  Jog Reverse run  P3 45   1  reverse running    Increase Increase data or function code  Decrease Decrease data or function code    T In editing state  press this key to select the bit to be changed  in other state  press this  uit  key to see the monitor parameters   Save switch In program state  press this key to enter the next menu or saving the parameters     Analog potentiometer When P0 01   0  adjust analog potentiometer to change the inverter s output frequency        30    V5 series inverter    3 2 3  Fucntion description of LED and indicator    The operation panel consists of 4 bits 8 segments LED  3 unit indicators and 3 state indicators  The three unit indicators  have 6 different combinations and each combination corresponds to one type of unit while settting parameters The    relationship between the combination of the indicators and the unit are shown in Fig 3 3     Hz r Hz  O Hz       He rU Hz i    AS O  2101 AS O4 As 04 AS     oS  tho Selo Pele ola fy le fs e    no A y Hz m z    unit e On O Of    Fig  3   3 Unit represted by combination of the indicators    3 state indicators locate above the LED display on the operate panel  From left to right are  forward indicator FWD  reverse    indicator REV  alarm indicator ALM  The functions of these indicators are shown in Table3 1    Table 3 1 Functions of status indicators    LED display Display inverter s current status parameters and sett
112. ter  please pay attention to   Explosion risk of capacitor  The capacitors in the main circuits may explode when they are burned   Waste gas when plastic parts are burned  Poisonous gas may be generated when front panel 1s burned     Dispose method  Please dispose as industrial rubbish     VB3 V 5 V BS series inverter    1 Product Instruction       1 1  Product overview   V3 F5 series inverter is produced by Thinget Co   Ltd with high performance  easy operating and low noise  It is a  innovative product with a series advanced and practical running and control functions such as practical PI  flexible input  and output terminals  parameter modification online  fixed length control  traverse operation  RS485 control  bus mastering     It provides OEM customers with high integrated  reliable  cost effective solution     Name Designation Rules  3P7    FT Max Suitable Motor s Capacity  011  11KW    1P5  1 5KW  Inverter Series Voltage Level And so on  V5  VVVF vector control 2  220V  P  Stands for radix Point     VB5  VVVF vector control 4  380V  VB3  VVVF control  mini type     B means black cover     VB3 only has 220V level types  V5 VBS5 series frequency inverter has 220V and 380V voltage levels  Suitable motor  capability is from 0 4KW to 55KW   Please note 220V level types have no vector control    Rated capacity  KVA    Rated output current  A    Suitable motor  KW     220V  single phase    14 0    Three pahse       1 2  Product technical specification    1  Technical specifi
113. ter s PE terminal  then ground  the point near the inverter     4  The grounding cable of inverter s PE terminal should be connected to ground directly It can t connect to other devices   grounding cables     5  Don t put the signal cables in parallel with the power cables  R  S  T or L  N with U  V  W  or bundle these cables   together  at least 20   60 cm distance shoule be kept  related with power current   If the signal cables and power cables    needed to be intersected  they should be vertical to each other  as shown in Fig2 12    Power supply or motor cable    Signal control cable    Fig  2 12 Wiring requirement of system     6  The weak electricity grounding cable such as control signal and sensors should be separated with strong electricity    grounding cable     26    VB3 V5 VBS5 series inverter     7  Do not connect other devices to inverter s power input terminals  R  S  T or L N      27    V5 series inverter    3 Operating Instructions       3 1  Run the inverter    3 1 1  Command channel for inverter running    We can control the inverter s START  STOP  JOG and other running actions by three command channels     1  Operation panel    Control b   Mm and    2  Control terminals  Use FWD  REV  COM to form 2 wire control  or use one terminal of X1 X6 and FWD  REV to form 3 wire control   3  Serial port       JOG  KW keys on the operation panel  default setting        The operations such as START  STOP can be controlled by other devices which can communicate with the
114. ti function     digital output    E  optical coupling isolation output             Open collector terminal  Refer to output terminals     Multifunction output    l I        voltage range 9 30V  output terminal function description of terminal    terminal max output current 50mA    function parameters P4 10 for details   usage please refer to P4 10   common terminals  COM   Multi function digital output terminal  Open collector   Refer to output terminals    function Output frequency range  Decided  Pulse output terminal pulse output description of terminal function by function code P4 21  highest  terminal parameters P4 20  P4 21 for details  20KHz     common terminals  COM     Input voltage range  O 10V  input  Analog input  analog voltage input  V resistance  47K    reference ground  GND   accuracy  1 1000    Analog     current voltage     input  Input voltage range  0 10V  input          voltage and current are selected by resistance  47K      Analog input    CI jumper JP3 and the default is Input current range  4 20mA  input    current  resistance  500            reference ground  GND  accuracy  1 1000  Analog voltage current ouput     Analog input  They are selected by jumper JP2  Analog output Voltage output range  0 10V  and the default 1s voltage which can  AO IN Current output range  4 20mA  indicate 7 values   reference    Analog output  ground  GND     EWD Forward    Forware reverse digital command   Optical coupling isolation input  Running control running Refer t
115. tically and then restart after the reference holding time  set by P5 08  During the holding time of  restart  the inverter will not start even if you input running command  while if you input stop command  the inverter will    stop detecting and restarting       P509   Auto reset times of fault Ranges 0 10 0         P510   Autoreset interval of fault Range  0 5 20 0S   ses        When the inverter is in running process  it may occur fault and stop output by accident for overload fluctuating To avoid the    pause of the device  you can use auto reset times of fault  In the reseting process  inverter will restart with detecting function   If the inverter can not reset to running successfully in the reference times  fault protection will be enabled and output will  be stopped     Note   1  When use this function  make sure that it is permissible by device and there is no substantiality fault with inverter     TI    V5 series inverter     2  This function is disabled with the fault protection caused by overload and overheat     4 2 7  Fault recording parameters CGroup P6     P6 11 6 latest fault record Ranges 0 23    0  no fault  17 17  E 01    E 17 fault  referto chapter 5 for fault types       PO Setting frequency of previous fault Ranges  0 upper limit of frequency    Peas   DCinjectiong bus voltage of previous fault   Raw OA    4 2 8 Close loop control parameters  Group P7     Output frequency of previous fault Ranges 0    upper limit of frequency po       Analog feedback con
116. to the output circuits  The Inverter may be  damaged or internal parts burnt if these devices are connected    Do not connect electromagnetism switch  electromagnetism contactor to output circuit  When the inverter 1s  running with load  the electromagnetism switch and electromagnetism contactor will generate inrush current  which will cause inverter s over current protection     Do not disassemble the whole front cover as disassembling the top front while wiring 1s ok  Otherwise  inverter       internal parts may be damaged         Maintenance and Inspection    Do not touch the inverter terminals  as they may carry high voltage    Otherwise  an electric short may occur    Make sure to have protective cover  Always have the protective cover in place when power 1s being supplied to  the Inverter  When attaching the cover  please with the power turns off    Otherwise  an electric short may occur    Maintenance  inspection  must be performed only by authorized personnel     Otherwise  an electric short may occur     A CMOS IC 1s used in the control board  Handle the control board and CMOS IC carefully  The CMOS IC can  be destroyed by static electricity if touched directly     2  Do not change the wiring  or remove connectors or the Digital Operator  during operation        Otherwise  The devices may be damaged     O Usage Precautions        gt  Constant torque low speed running    When the inverter outputs to a common motor at low speed for a long term  the output rated torque 
117. tor resistance of motor Ranges 0 001    50 000 Q  inverter s model    PA 01   PA 10 are set as motor parameters which have default setting dependent on inverter   s modle by the factory  you can          reset these parameters according to the motor parameters of yours  PA 01 PA 10 are used for vector control  which should       be input correctly so as to realize the expecting effect     Over current protection coefficient of  PA 11 Range  0 15  torque    In vector control  this parameter is used to control torque current to avoid over current  0   15 correspond to50  200      PA 12 Percentage adjustment coefficient of speed dev Range  507   120    87    V5 series inverter    deviation       Integral adjustment coefficient of speed  PA 13 Ranges 100 500    In vector control  PA 12 PA 13 are used for control motor speed Adjust the two parameters can realize better effect for motor    speed control     PA 14 Vector torque boost Ranges 100 150    In vector control  this parameter is used for boosting motor s output torque  You can increase this parameter to boost motor s    output torque in the place with too heavy load     4 2 12  Specail application function parameters  Group PB     PB 00 Jog frequency source Ranges 0 4    0  P3 06   1  Panel potentiometer  2  P0 02   3  VI   4  CI    PB 01 selection of forward  reverse dead time Ranges 0 1    0  Dead time is enabled  According to the value set by P0 05 with the minimum value 0 1S   1  Dead time can be set to 0  no dead time 
118. trol   To start or stop the inverter via RS485 port    Notes The control modes can be controlled by modifying P0 03  while please be careful to use this method during    operating     54    V5 series inverter    The unit s place of this parameter is active with panel control mode to operate jog   Unit s place of LED    0  Jog forward in panel control mode   1  Jog reversein panel control mode  Ten s place of LED    0  Reverserunning is permissible     1  Reverse running is prohibit  The inverter will stop output when reverse command is input       P905   Run forward reverse dead time Ranges 0 0 120 0s   94s    It is the transition time at zero frequency time when the inverter switching its running direction  as shown in Fig 4 1 as t     Output Frequency       Fig  4 1 Run forward reverse dead time    P0 06 Max output frequency Ranges 50 00Hz 500 0Hz 50 00Hz  P0 07 Basic running frequency Ranges 1 00Hz 500 00Hz 50 00Hz  P0 08 Max output voltage Ranges 1  480V    The max output frequency 1s the highest permissible frequency of the inverter  as shown in Fig 4 2   Basic running frequency is the lowest frequency when the inverter output the highest voltage and it is usually rated  frequency of the motor  as shown in Fig4 2 as FB        The max output voltage 1s the relevant output voltage when the inverter output basic running frequency and it 1s usually    rated voltage of the motor  as shown in Fig 4 2 as Vmax     Output Voltage  may         HO P u skoro iii l   oa             O
119. trol system  Reference pressure is input via VI  and feedback value  4  20mA  of pressure sensor is input to inverter via CI  Also  there    is an internal PI adjustor to form analog close loop control system  as shown in Fig4 32        Circuit breaker Vs  A S Output            R U                 7m  Power r S V     MI     4     Pee Pressure  i  eh  E    OT wW g  r i sensor  i Il    E            Forward Reverse J TFWD   1 29     command    Reference   RT  10V  13KY    1 Vi    p     9GND       Fig 4 32 Analog feedback control system with internal PI    Principle diagram of inverter s internal PI is shown below      lt i     i      Reference A aif  Close loop     Close loop  adjustment CAT adjustment i   output   P7 06 P7 08    characteristie      Integral   4    eee HUSA gain KI   P7 11   Feedback  adjustment     P7 07 P7 09     Fig  4 33 PI block diagram    Close loop reference  feedback  limits of deviation  proportional and integral parameters which are as same as common PI    78    V5 series inverter    adjustment are defined in P7 01   P7 11  The relationship between reference and feedback are shown in Fig4 34  thereinto     10V corresponds to 100  of reference and 20mA corresponds to 100  of feedback     The aim of reference adjustment and feedback adjustment is to confirm the corresponding relationship and dimension of    unification  as shown in Fig 4 33     If the motor s speed is required to increases with the reference speed  this kind of control characteristic 1s 
120. utput    Frequency       FL FBFH Fmax  Fig  4   2 Characteristic parameter    FH  FL are defined by P0 19 and P0 20 as upper limit of of frequency and lower limit of frequency     T                               In order to compensate the torgue drop at low freguency  the inverter can be boost the output voltage so as to boost the    torque  the torque boost of constant torque curve and square torque curve are shown in Fig  4 3 as a  b     55    V5 series inverter    Output  Frequency       Fz FB  Vb  Manual torque boost voltage Vmax I Max output voltage    Fz  Cut off frequency for torque boost FB  Basic running frequency     a  Torque boost of constant torque curve         Output Voltage    Output    Frequency    Fz F      Vb   Manual torque boost voltage Vmax   Max output voltage       i as    Fr   Cut off frequency of torque boost FB  Basic runninz frequency   b  Torque boost of square torque curve    Fig  4   3 Torque boost    Cut off frequency of torque boost Range  0 00Hz     Basic running frequency 25 00Hz    This function defines the cut off frequency of torque boost  as shown in Fig  4 3 as Fz  Then cut off frequency 1s suitable for  any V F curve defined by P0 02     Torque boost mode Ranges 0 1    0  Manual torque boost    Torque boost voltage 1s defined by parameter P0 09  The boost voltage 1s fixed while motor will be easily magnetism  saturation with light load    1  Auto torque boost   Torque boost voltage will change with the motor stator s current changes  T
121. y    Press cS key to display monitor parameters in b group First display the parameter No  then shift to display parameter    value automatically in one second The shift method is shown below in Fig 4 7        ius  Set Output Output  freguency voltage current  Output freguency  LU b      Button  operation    ls ls    Generatrix    Set length voltage     E    Fig  3 7 Setting the parameters in running status  1 State parameter can only display seven parameters from b 00 to b 06 with factory setting  you can view other status  parameters by changeing P3 41 and P3 42     ENTER        2  When you want to view status monitor parameter  press  Rn can shift to default monitor parameter display  status  The default monitor parameter in stopping states is setting frequency and in running states is output frequency     2  Function parameter    Take the following as an example  reset function parameter P3 06 from     5 00Hz to 8 50Hz     33    V5 series inverter          Display ENTER ENTER  ES nn O m EE EB          Parameter Enter nelect Confirm Select Confirm Modify  key   displayed editing function parameter parameter parameter parameter   operation   in stopping status to parameter group to enter P3 06 enter level 3 select   status display P3   level 2 menu menu position    level 1    mn 0500       wu  ENTER    PR  XE DATA EMENN 57           Exit Back to saving the Modify Modify Modify  level 1 menu modified value  parameter parameter parameter   back to level 2 value value t   valu
122. ytes  16 bits   it 1s added to the message after calculating  when added  the first 1s  low byte and the second is high byte  therefore  the last byte of the sended message is high byte  Then the receiving device  cauculate CRC which has received message again and compared it with the value in CRC field If the two values are not the  same  the device will take this message as fault and abandond it without any responses  and then receive next frame data     Please refer to MODBUS protocol instruction for calculate method of CRC verification     7 3 3 Communication parameter    Parameter address  Internal reference  GGnnH GG stands for parameter group  nn stands for parameter No   parameters    0001H  Running command  Forward   0002H  Forward command  0003H  Reverse command   2000H    Command to  inverter   06H     0009H    og stop command  000AH  Fault reset command       98    att        2001H Set ee command via port    21 021000000 Read inverter    s fault   Readinverter   s fault parameter 00000000       2103H Read inverter  s output frequency  2104H Read inverter  s output current    2105H Read inverter  s bus voltage  2106H Read inverter  s output voltage    2107H Read motor    s speed    2108H Read module temperature    2109H Read analog input via VI    210AH Read analog input via CI  210BH Read inverter   s software version    I O terminal status  Bit0  XI  Bitl  X2  Bit2  X3    V5 series inverter    0  no    RI inverter  s status    BITO   map io         indicate  0   
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
MAXI SKY440 - Medicaleshop.com  11/1(日)よりBOOK EXPRES…  Supplément Haut-Rhin Sud - secteur de Mulhouse  DGC5 - INTEC Controls  COMO VERIFICAR LA PRESIÓN DEL SISTEMA DE AIRE  Digital Signage Technology Guide  VCB-3385P VCB-3380P VCB-3380P-UK  Micro Motion® Masse Abfüll- Auswerteelektronik mit Modbus  User GUide - GN ReSound  Ficha en Pdf - Abejon Informatica    Copyright © All rights reserved. 
   Failed to retrieve file