Home
        Kobold DOR Series Paddle Wheel Flow Meter Manual
         Contents
1.                                                                                                                                                         22    a or          pipe ID  mm        Calculate K factor   pulses   litre   using the above graph and the metric constant of 1273 2  as follows      Pulses   litre   1273 2 x  A  from graph  pipe ID   mm     Example    a      K factor for 100mm pipe  1  from graph 100mm ID  A    24 0    2  pulses litre    1273 2 x 24 0  10000   3 056 p litre    K factor for m    multiply by 1000 eg  K   3056 p m   K factor for megalitres   multiply by 1000000 eg  K   3056000 p megalitre    NOTE   K factors for Reed Switch output option are 1 3 the standard factors of voltage  pulse output     page 13    4 4 Calculating K factors   US gallons         7 6 7                               7 5 4                               7 4                                 7 3 4                               7 2      7 1 4 Pipe ID 19 5      amp  above  A    6 86      7 0                                                       A                                                                                         6 9                                                                                                               6 8        1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20  pipe ID  inches                 Calculate K factor   pulses   gallon   using the above graph and the volumetric  constant of 24 51 as follows      Pulses   US gal    24 51 x  A 
2.         24Vdc  external  power       Troubleshooting 15      Display shows model number at all times        example    The instrument has not been fully programmed after power up  enter the program mode  amp   enter program parameters  be sure to exit the program mode before the 4 minute no data  entry time out or the instrument will revert back to model number display       Display ghosting under external power    The LCD display will    ghost    when the instrument is powered from an external 24Vdc  power supply  this is corrected by including two   watt resistors  1 2K  amp  3 3K  on the  input power source as shown below       Scaleable pulse output counts on after flow has stopped     The scaled pulse output has exceeded its output limit of 8Hz  Allow the memory buffer to  catch up or increase the pulse value   number of litres etc  per pulse   clause 4 5  p12        Display shows random characters   The instrument may have taken an electrical    hit     press the processor reset button  p70      Cut from manual for increased security    16 Declaration of Conformance    7  Declaration of Conformance  We  KOBOLD Messring GmbH  Hofheim Ts  Germany  declare under our sole    responsibility that the product     Battery Totaliser Model  ZOD Z1    to which this declaration relates is in conformity with the standards noted below     Optional for Equipment intended for use in Potentially Explosive Atmospheres     ATEX Directive 94 9 EC    EN 50014  1997   Amds  1  amp  2 Intrins
3.       Loop load specification   R    V     10    0 02    where   V   loop voltage  R   max  load Q             Powering via 4 20mA loop    Positive referenced      Flow High flow alarm  Input B Low flow alarm    Optional wiring  When wired in this manner the one loop  power supply  limited to 24Vdc  may be  used to also power active flow sensors   scaled pulse  amp  alarm outputs at terminals  7 13 8 14 8   or multiple RT s if required           Elow  4 20mA output  InputA  4 20mA output   4   OV  ground  not used   8 24Vdc in not used A  Pulse output  OV  ground  8    sonjooo       Wiring requirements   Use multi core screened twisted pair instrument cable   0 25     0 5mm2  for electrical connection between the ZOD Z3 and any remote  flowmeter or receiving instrument  The screen needs to be earthed to the signal ground of the receiving instrument only to protect the transmitted signal from mutual  inductive interference     Instrument cabling should not be run in a common conduit or parallel with power and high inductive load carrying cables  power surges 8 power line frequencies may  induce erroneous noise transients onto the signal  Run instrument cables in a separate conduit or with other instrument cables     11 Installation    Pulse 8 Alarm Outputs    Current Sinking outputs   NPN    Current sinking derives its name from the fact that it    sinks current from a load     When activated the current flows from the load  into the appropriate output  7 13  amp  14      Driv
4.      Ground screen at  OV  5  D  8 24Vdc in not used 9    Pulse output  OV  ground  8    2  Voltage Pulse  8 pulse wires      03 High flow alarm    O Flow g  o 2  All DIP swithes off InputB Lowflow alarm    ol Flow  4 20mA output   12   N           TG input A  4 20mA output   Pa  OV  ground  not used   a dat  gt   lt  Ground screen at  0V  5      SE Na EJ  E    Pulse output  OV  ground  81    3  Coil   Turbine  amp  paddle style flowmeters     minimum 15mV p p      All DIP switches off  position switch 1 O3 High flow alarm  14  ON if unit is effected by line noise  x 02 a 14  aq OP Low flow alarm        O C13 Elow  4 20mA output  02   N D Input A  4 20mA output    OV  ground  not used     8 24Vdc in not used   9    Pulse output  OV  ground  8       9 Installation    3 2 Flowmeter connections   powered sensors      for l S  installations refer to l S  supplement      4  Hall effect   5 24Vdc open collector      DIP SW2   sn up  is on        e Flow High flow alarm  Ground old Ki B KA Wi    Signal out J LI L at terminal 5        Flow  4  20mA output    OV ground m JE sa  Input A        Hall effect  _ Vac supply     4 20mA output        OV  ground  not used   8 24Vac in not used   9    Pulse output  OV  ground  8    5  Namur   inductive proximity switch   DIP SW3  pull down  is on    3    ge Flow High flow alarm  N  n Input B Low flow alarm  Ol Flow      4 20mA output  N at 2  Input A  A 20mA output  41    OV  ground  not used   8 24Vdc in not used   9   Pulse output  OV  ground 
5.     Flow                      IMPORTANT    Fix 1N4004 electrical surge  suppression diode supplied  across solenoid valve coil    band to   side                    Installation 11    Two Stage Control  using relays 1  amp  2                         Network Relay 2 high  Relay 1 low          Flow Batch status  Input not used   OV  ground  not used   8 24Vdc in Run inhibit 9      No flow alarm  OV  ground  ES                         Flow        gt       a          IMPORTANT    See notation on 1N4004 diode  When the solenoid valve coil is de energized  it generates its own voltage sending a    surge spike    through the circuit   Depending on the coil size and the number of amp turns it contains  this   generated voltage can be very high  Installing the diode will suppress this     spike    and protect sensitive components of the electronic instrument     Relay Control Logic    i     complete    ENERGISED     ENERGISED    Relay 1 LOW FLOW                  OFF          ENERGISED     ENERGISED    Relay 2 HIGH FLOW             OFF    Start delay  gt  gt  a Start delay  gt          Pre stop        1 4 sec         ENERGISED  Batch  amp  network    status   NPN   output       OFF        Batch  amp  network status  end of batch    occurs 1 4 seconds after relay 1 is off     12 Programming    4  PROGRAM PARAMETERS    4 1 PIN No  Program Protection   Any user defined PIN number other than 0000 will engage the program protection feature   failure to input the correct PIN number will deny 
6.     Terminal layout    Wiring of analog output  Wiring of flowmeter inputs  Wiring of pulse outputs  Wiring to external supplies  Wiring requirements    14  16  17  11  12    12    12  11  12    18  18    10  8  9  11  10  10    Manufactured and sold by     Kobold Messring GmbH  Nordring 22 24  D 65719 Hofheim  Tel    49 0 6192 2990  Fax   49 0 6192 23398  E Mail  info de kobold com  Internet  www kobold com    Version  KO2 1010    22 Declaration of Conformance    9  Declaration of Conformance    We  KOBOLD Messring GmbH  Hofheim Ts  Germany  declare under our sole  responsibility that the product        Flow Rate Totaliser Model  ZOD Z5    Universal Mount Series  to which this declaration relates is in conformity with the standards noted below     Optional for Equipment intended for use in Potentially Explosive Atmospheres     ATEX Directive 94 9 EC Z5 FLOW RATE TOTALISER    with backlighting  amp  flow alarms    EN 50014  1997   Amds  1  amp  2 Intrinsically Safe Electronics  1 S       Optional  mds ntrinsically Safe Electronics  I S   ptiona INSTRUCTION MANUAL    EN 50020  2002 Intrinsically Safe Electronics  1 S       Optional    EN 60529  DIN VDE 0470 1 1992 11  I P  Ingress Protection Classifications    EN 61326 1  2006 10  Electrical equipment for control  instrumentation technology and laboratory use     EMC  requirements  Industrial area     EN 61010 1  2002 08   Safety requirements for electrical equipment for measurement  control  and laboratory  use       2008 35 
7.    May be link configured for PNP to drive compatible logic circuits     NPN PNP solid state alarm or non scaleable pulse output    terminal 7    5000hz max    1A maximum drive capability     NPN open collector  0 1A dc resistive load max   page 16      Eg  Pulses litre  gallon  lb etc  Programmable range is 0 001   9999999 999 with a floating decimal point during K factor entry     Selectable Ltr  gal  m3  kgs  los  maximum 8 digits of batch    Count UP or count DOWN selectable at program level     AOC enabled disabled selection at programming level  page 13      Batch size limits can be set at programming level  page 13    Run key can be inhibited from an external source  page 16      A two wire loop system can link up to 9 individual batch  controllers with one common flowmeter to provide an economical  multi source dispense interlocked batching system  page 18      A  IP66   67 high impact glass reinforced Polyamide enclosure   B  3 x M20 or 2  NPT female conduit entries    C  125mm diameter  5     x 61mm deep  2 5     x 400g  0 91b     D  Temperature range from  20  C to  80  C    4  F to  176  F      3    4    Introduction    1 3 Overview  The ZOD B1 is a dc powered high speed batch controller specifically designed for liquid  batching using a flowmeter with a pulse or frequency output     ZOD B1 is push button programmable with PIN protection and an internal battery is provided  allowing pre programming without applying power  The large LCD provides batch quantity in  
8.    Use of a good quality DC power supply   Select A Press to reset totaliser  Select  A  is recommended  Avoid using low cost response  sec  deadband  0 9     digital switch mode power packs     PROGRAM PROGRAM    loop wiring   repeater pulse output       Ma re A Number of excitation poles  NOP  si koki A  of poles   1 32   for each revolution of the primary of poles   1 32      a   i    a PAR E The NPN pulse output is isolated PROGRAM measuring elements  see page 2   PROGRAM  1    from the loop powered circuit   YA    and will support up to 30Vdc and O     E  drive to 100mA     Run mode   display defaulis Run mode   display defaults      savde to input frequency  Hz   to input frequency  Hz   Digits  supply Press A to show Hz for 20mA  flash when in alarm condition   Press A to show Hz set point        
9.   A self generating pulse output which produces a strong 1 5 volt voltage spike of  approximately 10 micro second duration with no dependence on rotor speed     peteeneecnesecensenenaeseesesensesecaeseeansenssaeeneaens Screen    z   dw   O  A  Pos          m  Yellow              Green           Square Wave Pulse  Hall sensor   also applies to non magnetic  amp  QP Hall outputs    An NPN open collector transistor pulse output produced by a solid state Hall Effect device     This three wire device requires 5 24vdc and produces an NPN square wave output  20mA  max  sink   pulse width is 2 75 mSec  The Hall output requires a pull up resistor  these are  generally incorporated in most receiving instruments  For  QP  Quadrature pulse output  refer details page 9     O a Screen     5 24vdc supply    j i T L signal output       Red       White     Ov ground         Black       Page 9  3 5 Quadrature outputs  DOR series flow meters supplied with the QP option produce two NPN open collector pulse  outputs from two Hall Effect sensors  The outputs are     phase offset     in their timing so that  external electronics are able to differentiate  These outputs may be used to assure output  signal integrity or to measure bi directional flow       CU eee eee Screen    Red   Vdc               White   output 1       Blue   output 2          Black    OV       3 6 Bi directional flow   The DOR flow transducer is capable of accurately measuring flow in both directions without  modification  Meter
10.   Inhibit the integration  amp  registration of    apparent flow    which at times may be encountered on mobile  installations where the movement of the vehicle or dead heading a pulsating pump may cause spurious flow  signals which are not attributed to actual flow     3  Inhibit the integration  amp  registration of flow at input frequencies below what is considered the minimum accurate  flow rate of the primary flow element  flowmeter      Caution  If the low frequency cut off is set to any value other than 0 0Hz then the integration  of rate and total will cease at frequencies on or below the set value  HERTZ      2 5 Inhibit total  see wiring schematic page 18   With the remote    inhibit total  switch closed the ZOD Z3 with display flow rate but at the same time will inhibit the  resettable  amp  accumulative totalising functions     2 6 Keypad function matrix    PROGRAM    ES  ATA  rom   an  NON  E  NEERA    N  QQ    Displays Accumulative Total when pressed    refer clause 2 1 for options      Toggles between Rate 8 resettable  Total displays     Resets the resettable total display to zero  when it is being displayed     1  Pressing the Prog  8 Rate Total keys for 5    seconds enters you into the program mode     2  Displays model 8 software revision No     No function    No function    3  INSTALLATION    3 1 Remote Mounting       Operation 6    No function    No function    No function    1  Each press steps you through each  level of the program chart   2  Holding fo
11.   LINK 7A  select SPO or REP pulse O  output   see clause 4 8  o LINKS 13  amp  14  67 SPO  scaled pulse  SER  select NPN or PNP  REP  repeater pulse  style alarm outputs  TA  e  Inhibit total  switch B    clause 2 5  Flow input  EN conditioning DIP  3 A switches  I   ae  REMOTE KEYS  real OOOO    NPN PNP  LINK 7B Q  o  Select NPN or PNP    style pulse output use momentary    action switches    SWITCH 3   ON engages 8200 pull down resister a  SWITCH 2   ON engages 1 meg Q pull up resister reset            program      lt     SWITCH 1   ON engages 0 01uf capacitor to accum  total   suppress reed switch bounce rate   total      lt     19 Rate dampening                                                                Response curve  to 99  of actual  flow rate                                                                               Response curve  to 90  of actual  flow rate                                        RESPONSE TIME seconds                                                                                            9 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95  ZOD Z3 DAMPENING VALUE             Rate dampening value verses time to reach new reading   for an instantaneous change in actual flow rate       Dual flow inputs    Dual flow inputs 20    When externally powered at terminals 5 8 6 the ZOD Z3 provides a dual flow input feature which can be  configured for one of three available functions of A B  A B or A B  ratio      The dual flow inputs are referred
12.   linear      Linearity     Repeatability     Max pressure     Temperature range     Material  Body   Rotor   Rotor shaft   Bearing     Seals     Electronics    Output frequency at max  velocity     Supply voltage     Electronic features   Wiring  standard      Transmission distance   Cable entry  terminal box      Protection Class     Straight piping requirement     Weight     page 3    0 3   10 m s equates to approx O 25   49 000 l s in  DN40 to DN2500 pipes  0 15   10 m s when using the  linearisation function of electronic type Z3     1 5  with well est  flow profile     1  of f  s  at factory conditions and optimal straight  runs    80 bar     40    100  C standard  see max  allowable medium  temperature table for other options and restrictions    stainless steel 1 4404  316L    PVDF or PEEK  depending on model   stainless steel 1 4404  316L   graphite PTFE   FPM  standard    15    200  C    EPR  ethylene propylene rubber    20    120  C  for  ketones only    PTFE encapsulated FPM   20    200  C  NBR  Nitril    65    125  C    220   240 Hz  hall effect and voltage output    73   80 Hz  reed switch output     see electrical output specifications and electronics  comparison table in the data sheet    see electronics comparison table in the data sheet  5 core  screened cable  length 3 meters    1 000 meters maximum  without integrated electronics  M20x1 5  standard   1 2    NPT adapter  optional     IP68  cable connection    IP66 67  all other electrical connections     Min
13.  14          High flow relay 2        Low flow relay 1       7B  0 0 0  lt        Set jumper IMPORTANT  NPN PNP to NPN For solenoid valve coils fix a 1N4004 electrical surge    suppression diode across the coil  refer page 10     7 5 Current Sourcing outputs   PNP     Current sourcing gets its name from the fact that it    sources current to a load     When activated the  current flows from the output  7 13  amp  14  into the load  When wired as below the output voltage pulse  is the supply voltage of the load  The load would normally have an internal pull down resistor on its    input as shown   A H PNP  lt     Set jumper s   no NPN to PNP    13 14  High flow relay 2  Low flow relay 1    5   OV  ground   S       8 24Vdc in  Alarm output  0V  ground     7B  o o o           Set jumper  NPN PNP to PNP    ARE       4H       Do not tie 0 volts of the   logic input to O volts of   the ZOD B1 when wired  in PNP configuration    18 Networking Networking  continued  19    8  CONTROLLER NETWORKING Multi point batching    Flowmeter    ZOD B1 has a unique networking feature which allows up to 9 individual batch controllers to  be networked together with each being connected to one common flowmeter  see opposite      Typical applications are where one liquid is being dispensed to a number of individual outlets  or a number of different liquids are to be batched via one common flowmeter  In either  application each batch controller is wired to the same flowmeter but controls its own proce
14.  2  Voltage Pulse  8 pulse wires           Relay 2  high   Relay 1  low     All flow DIP swithes off    Batch status        OV  ground    8 24Vdc in        3  Coil   Turbine     paddle style flowmeters      Factory set  do not change          All flow DIP switches off  position switch 1    ON if unit is effected by line noise  Relay 2  high     Relay 1  low   Batch status    Not used  Not used    Network  loop        OV  ground    8 24Vdc in          3 2 Flowmeter connections   powered sensors      4  Hall Effect  open collector            Flow input DIP SW2 is on  loop           Signal out T LI L    a  Fon A    Vdc supply  OV  ground      8 24Vdc in    5  Namur  inductive proximity switch             Network    Flow input DIP SW3 is on  loop         Input A  an NAMUR i    n Inductive Proximity     OV  ground    8 24Vdc in    Pulse output    NOTE   Limit supply to 8 5Vdc  through an approved barrier for  intrinsically safe NAMUR proximities    6  Current modulated pulse    4mA to 20mA pulse amplitude             Flow input DIP switches off  Network    NOTE   Position a 1000  14W loop    Resistor across terminals 3  amp  5        Flow  Input A    Coil with pre amp  current modulated  OV  ground    8 24Vdc in    Pulse output    Network          Installation    Factory set  do not change  Relay 2  high   Relay 1  low     Batch status          Factory set  do not change  Relay 2  high   Relay 1  low    Batch status    Not used  Not used     OV  ground           Factory set  do no
15.  7 x 0 3mm  0 5mm   should be used for electrical PROGRAM key for 3 seconds to  connection between the flowmeter and remote instrumentation  Belden   number 9363 or similar   The cable drain enter program mode   or screen should be terminated on a DC COMMON or a specifically assigned shield termination at the readout    instrument end only in order to protect the transmitted signal from mutual inductive interference  IMPORTANT  tape Press B key to select function   off  amp  isolate the shield at the flowmeter end of the cable       b  F I converter p Divider p Flow switch   The cable should not be run in a common conduit or parallel with power and high inductive load carrying cables as   power surges may induce erroneous noise transients onto the transmitted pulse signal or cause damage to the   electronics  Run the cable in a separate conduit or with low energy instrument cables only                 PROGRAM PROGRAM PROGRAM    loop wiring    The loop powered milliamp output is generally               analog  4 to 20mA  or may be programmed in    Position Pm Select A  gt  Position  field for status switching between 4  amp  20mA for decimal point divider factor decimal point  either divided pulse or flow switch output          GND PROGRAM PROGRAM PROGRAM          MIZI  PA 2   fl    d     D Selectfull A  gt  Selectfow A  scale frequency  Hz  Switch point  Hz      PROGRAM PROGRAM    FI  A PERSE   rus  24Vdc  supply COH Run mode   display defaults  to a totaliser  divided value 
16.  8       Ground screen  at terminal 5               NAMUR  e Inductive Proximity          NOTE   Limit supply to 8 5Vdc  through an approved barrier for  intrinsically safe NAMUR proximities    6  Current modulated pulse   4mA to 20mA pulse amplitude      DIP switches off  NOTE  Position a 1000  14W  Resistor across terminals 3  amp  5                     o 3 Flow High flow alarm  4 INPULB Low flow alarm  Ground screen OG Flow  4 20mA output   at terminal 5 N fit A 4 20mA    Coil with pre amp   B  4 20mA output  current modulated   A  0V od not used   8 24Vdc in not used 9    Pulse output  OV  ground  8    Installation 10    3 3 Wiring connections  for l S  installations refer to I S  supplement      External DC powering   required for powered flow sensors  flow alarms or pulse outputs  amp  dual flow inputs     Flow High flow alarm  InputB Low flow alarm    Es  E Flow  4 20mA output         CAUTION    Avoid using low cost  digital switch mode    8 24Vdc    Input A      regulated supply a  4 20mMA output        OV  ground  not used power packs          6   8 24Vdc in not used   9      Pulse output  OV  ground  8    Powering via 4 20mA loop    Negative referenced    High flow alarm    Input B Low flow alarm      Signal out JUL      Negative    effect      Yde supply __ _J____     Flow  4 20mA output  InputA  4 20mA mall v             Pulse output  OV  ground  8    Shows powering of a Hall Effect  device using the loop power  source if required                Optional wiring i 
17.  EN 13463 1  2009  Non electrical equipment for use in potentially explosive atmospheres    When fitted with an integral EX ia certified instrument such as the ZOD Z3 or ZOD Z1  in combination with a  Reed Switch only output  the product also complies with     94 9 EC  ATEX Directive    page 15    Certificate about acknowledgement of quality assurance production  Certificate number  BVS 12 ATEX ZQS E110  Certification body  DEKRA EXAM GmbH  notified body No 0158    SIRA 06 ATEX M348   Only when equipped with integral ZOD Z3 or ZOD Z1 options  Issued by Sira Certification     United Kingdom    EN 13980 2002  Potentially Explosive Atmospheres     Application of Quality Systems    94 9 EC Articles IV and VII  ATEX Directive    H  Peters M  Wenzel  General Manager Proxy Holder    Hofheim  12  Nov  2013    11  Declaration of Conformance    We  KOBOLD Messring GmbH  Hofheim Ts  Germany  declare under our sole responsibility that  the product        Batch Controller Model  ZOD B1K    to which this declaration relates is in conformity with the standards noted below  Universal Mount Series    EN 60529  DIN VDE 0470 1 1992 11  I P  Ingress Protection Classifications    EN 61326 1  2006 10 BATCH CONTROUER Model ZOD BIK    Electrical equipment for control  instrumentation technology and laboratory use     EMC  requirements  Industrial area   INSTRUCTION MANUAL    EN 61010 1  2002 08    Safety requirements for electrical equipment for measurement  control  and laboratory use  2008 35 EC W
18.  L hr  the alarm will not  switch off until the flow increases above    BAND XX  HIGH 105 L hr     L22 DUAL INPUTS REQUIRED Y N  DUAL Y   N         L23 ENTER NUMBER PULSES PER  Ltr m3 kg gal Ib  unit  FOR INPUT B  00000 001   9999999 9    NO       L24 SET DUAL INPUT FUNCTION    A B A B A B       program return    17 Programming    6 4    Program detail record Pencil your program details here    mo n  0 0 0 00  10 000    mo Mon  10 00  10 000  mo 300  10 00  10 000  cl yes C no  RCF   Units     Sec   Min    Hr   Day     yes    no  L11 pulse value      L12   Non linear correction     yes  _  no       baaa    frequency 1  Power mode    Ultrasave  L  Standby   Continuous  L14   Analog output     yes     no    zero set point  L16   span set point    LI    no        lt    D  Ma    Alarm outputs          low set point         percentage    3S      low deadband           high set point      high deadband Yo  L22   Dual flow inputs     yes  _  no  L23   K factor for B input   K   L24   dual input function LI A B L  A B     A B    Your back up 4 digit PIN number is 1820    Terminal designation 18    l  TERMINAL DESIGNATION    Terminal Terminal  High fl   14  Terminals 1  2  amp  5 replicate l Flow S  terminals 3  4  amp  5 for dual 2   input B Low flow alarm  13  flow inputs 3   Flow  4 20mA output  12  4    input A  4 20mA output  11  5   OV  ground  not used  10  6    8 24Vdc in not used   9  7   Pulse output  OV  ground    8    Terminal layout   links  amp  remote switch inputs     
19.  Terminal layout  Troubleshooting     w  Wiring connections  Wiring practice    14     17    11    12  11    13    14  11    12  12    10    15    8 11    10            Universal Mount Series    OBOLD  O    ZOD Z3 FLOW RATE TOTAUSER    INSTRUCTION MANUAL       Software version    16 12 04  27 04 07        Press  amp  hold Program key to show  instrument model  amp  software version    Replacement Batteries     KOBOLD supplied batteries      Non l S  battery  KOBOLD P No  1312007    A    l S  battery  Kobold P No  1412028    Warning   KOBOLD  Intrinsically safe battery  assembly only is approved  for ZOD Z3 mounted in a  hazardous area     Suitable non l S  batteries also available from      R S Components Farnell Components  Stock No  596 602 Order code 206 532       3 6V x 2 4Ah AA    Lithium Thionyl Chloride    non   rechargeable cell    TABLE OF CONTENTS    INTRODUCTION   1 1 Model number designation   1 2 Specifications   1 3 Overview   1 4 LCD displays   OPERATION   2 1 Accumulative total display   2 2 Resettable total display   2 3 Rate display   2 4 Low frequency cut off   2 9 Inhibit total function   2 6 Keypad function matrix   INSTALLATION   3 1 Mounting   wall   surface mount    pipe mount    panel mount   3 2 Flowmeter connections   unpowered sensors    powered sensors   3 3 Wiring connections   external powering    4 20mA loop powering    wiring requirements    pulse outputs    alarm outputs    remote switches   PROGRAM PARAMETERS   4 1 PIN number program protect
20.  Total   The batch value is displayed in all normal operational modes     2 5 Accumulative Total   Accumulative total can be reset in the program mode   The accumulative total is displayed momentarily by pressing the ACCUM TOTAL key     2 6 TNB display   Total number of batches     ZOD B1 will accumulate the total number of  individual completed batches  Reset of TNB is simultaneous with the resetting of the  Accumulative total in program mode  To view the TNB value simultaneously press  amp  hold the  two top right hand keys   Prog   amp  Accum Tot      2 7 Keypad functions      KEY FUNCTION IN OPERATING MODE FUNCTION IN PROGRAM MODE    1  Enters  amp  Exits the batch set mode   2  May be pressed during batching to show  batch pre set value  this action will not No function  interfere with the batch process   Selects the digit to be Increments the selected digit  Indexed   digit will flash     selected digit will be flashing      Pressing PROG  amp  STOP keys for 5 sec   gives entry to the program mode    1  Resets the batch to the last pre set value   2  Resets individual digits to zero when No function  in the BATCH SET mode   1  Displays Unit ID number followed by the  Accumulative Total as the key is held  No functi  2  Displays total number of batches   press O TUNCUON  Accum  Total 8 Prog  keys at the same time     1  Pressing PROGRAM 8 STOP keys for 5    Pressing PROGRAM  amp  ACCUM TOTAL keys   Seconds gives entry to the program mode     displays the Total Number of 
21.  YN O cC L cl i  nfo g OS ES   Z  O OSO O yB S  Oy XA VOS  OOo fH   onto             canada o       EI TOO a P                 i       0o D  2535  oc    Ty EO  e roncrrrcrcrcrrrrrrrrrrcner no   an oO     Q c5G58a  a  gt  b DELL      kai  k      P 120398  L    lt  SaS DO D  aa D Co HERE DHS  O L pei os  2yg  S   pos OLSON 20005527  D ES pir BAJZra3  a  jo 50C53 Too avo  O 253538 22092       ng     gt On ESO  x copo acZdyod  i  Ge 00H S O  0US QV Ec dD  E  7   CS    CO ZE ope te  Os        ILLES  OnsaraZszlce    page 8    3 3 Instrument cable installation requirements   Use twisted multi core low capacitance shielded instrument cable  22 AWG   7x 0 3  stranded  for electrical connection between the flow meter and the remote instrumentation   The screen should be earthed at the readout instrument end only to protect the transmitted  signal from mutual inductive interference     The cable should not be run in a common conduit or parallel with power and high inductive  load carrying cables as power surges may induce erroneous noise transients onto the  transmitted pulse signal  Run the cable in separate conduit or with other low energy  instrument cables      3 4 Pulse output selection   standard outputs     The standard flowmeter has two independent pulse output signals that are linearly  proportional to volumetric flow rate  Pulse transmission can be up to 1000 metres  3300 ft     An optional I S  Reed Switch output is available  see page 7      Voltage pulse  pulse wire  output
22.  a normal condition as the circuit dissipates the excess input voltage        Supplement 21    Remove a  batterv Relay board plugs inte  16  amp  20 pin sockets    Relay control output board with two SPCO relays shown with a ZOD Z3   N O contacts are rated to 5A  amp  the N C contacts 3A max      Relay board held by    Y   battery cradle clips       FI 420 Universal pulse  processor board    INSTRUCTION MANUAL SUPPLEMENT    WOW  ye ki go PWE  A Mr to   gt  SPAN 4 20 w    a Zn  i  ie    fie 4       IMFI420 0212    Introduction 1    Specifications  Programming On board programming via three tactile push buttons   Display 4 digit  seven segment LCD with 4 levels of contrast adjustment   Input frequency  Hall Effect  amp  Coil   1 0   9999 Hz   frequencies below 1hz are not registered      Reed Switch   1 0   80 0 Hz   frequencies below 1hz are not registered    Input sensor types Reed switch  Hall Effect  pulse wire or reluctance coil  turbine meter      Milliamp outputs    Pulse repeater output  Maximum loop powered voltage    1  Analog 4   20mA   600Q maximum drive capability   28Vac    2  Modulated between 4 and 20mA  divided pulse  amp  flow switch    Isolated NPN square wave  30Vdc x 100mA maximum load   28Vdc   absolute maximum  reverse polarity protected      Accuracy     0 3  of span    Response Programmable 1 9 seconds    Full scale limit 20mA internally limited  over range defaults to OmA     Temperature range  10  C    80  C    Processor 8 bit processing via 256 step 
23.  flow goes above the set point   2  Deadband  a bANa  or Reset Differential  provides  a buffer zone about the alarm set point in order to  L d bANd avoid alarm output    chattering     on 8 off when the  flow rate is hovering on or about an alarm set point   XXXXXX The   deadband applies above the Low set point and  HI   FL below the High set point  Deadband is set as a    O percentage of each set point   Eg  5  deadband at a low alarm set point of  100 L hr will cause a low alarm when the  flow drops to 100 L hr  the alarm will not  H d bANd switch off until the flow increases above  105 L hr   N   YES No  ENd Prog  YES  Saves settings  amp  exits program  5 2 Program detail record    User selected PIN No    Engineering units   K factor  scale factor    Decimal for reset Total L  0 C  0 0 C  0 00  10 000  Decimal for Accum  total      0 L  0 0 L  0 00  10 000    L  0 L  0 0    0 00  10 000    Decimal for Rate    Units    Sec    Min   Hr   Day    Set at   Deadband    Set at   Deadband Yo    Time base for Rate  Rate response   Low frequency cut off  Scaled pulse output  Low flow alarm       High flow alarm    Your back up 4 digit PIN number is 1820       gl    LI    i BE  E ki    jo   El    Index    ALPHABETICAL INDEX    Accumulative total    Battery    Backlighting the LCD display    DC power  Decimal point  Displays  Display priority    Engineering units  External DC powering    Flow alarms  Flowmeter connections  Flow rate    Installation    Input signals    Keypad functio
24.  from graph  pipe ID   inches     Example    b      K factor for 10  pipe  1  from graph 10  ID  A    7 01    2  pulses gal    24 51 x 7 01  100   1 718 p gal    NOTE   K factors for Reed Switch output option are 1 3 the standard factors of voltage pulse output     page 14   5 0 Declaration of Conformance   We  KOBOLD Messring GmbH  Hofheim Ts  Germany  declare under our sole responsibility that the product   Bi Directional Insertion Flow Transducer Model  DOR   to which this declaration relates is in conformity with the standards noted below    97 23 EC Pressure Equipment Directive   Pressure Accessory     Insertion Flowmeter     No CE Marking    Article 3  Paragraph 3  Diagram 9  Piping  Group II Liquids  Article 3  Paragraph 3  Diagram 8  Piping  Group   Liquids     with the following restrictions    Connection Nominal Size Maximum Pressure Rating  For Group   Liquids    1 5     40 mm  50 bar   2     50 mm  40 bar  2002 96 EC Waste Electrical 4 Electronic Equipment  WEEE   2002 95 EC Restriction of Hazardous Substances  RoHS     Also the following EEC guidelines are fulfilled   2004 108 EC EMC Directive     Electromagnetic Compatibility Directive    When fitted with an optional Reed Switch ONLY pulse output  which is classified as a simple apparatus  and  when installed in accordance with Hazardous Area standards by a competent professional the product also  complies with     EN 60079 11  2011     Section 5 7  Equipment protected by Intrinsic Safety     Simple Apparatus   
25.  if the battery is removed     Environments   The instrument is weatherproof to IP66 67  Nema 4X  standards  constructed in ADC12 aluminum alloy with  Stainless screws 8 FKM O ring seals  The instrument suits harsh indoor and outdoor environments  amp  conforms to  EMC directive 89 336 EEC Electro Magnetic Compatibility     Features  PIN Protection  NPN scaleable pulse output  Low frequency cut off  display priority  amp  large backlit digital display   backlighting enabled under external DC power only      Installation   Specifically engineered to be directly mounted on a variety of flowmeters  wall or surface mounted  pipe or panel  mounted  Various mounting kits are available  The instrument can be self powered or may be powered by an  external dc supply or two wire loop powered     1 4 LCD displays  Full LCD display test feature illuminates all  Ltr display segments and script text displays for 5    seconds when entering the program mode   l o  l o  l o  l    l o  l o  bs Resetable Total This large 6 digit display can  m a l E rl See a be programmed for up to 3 decimal places     AA  gt  a LI a a E A E a   po A Accumulative Total The 8 digit display can    be programmed for up to 3 decimal places   Reset is only possible when in the program  mode which can be PIN protected for security            l   l Rate display Rate is displayed with a flashing  l followed by up to 5 digits of rate  these are          time base of either SEC   min   hr or dAy      R   programmable for
26.  kit   ERS ZOD 1522002 stainless steel 2  pipe mount kit   ERS ZOD 1522011 DRT series cooling fin kit for flowmeters with integral instruments  ERS ZOD 1522005 DOR  amp  Turbine stem adaptor   metric  M16 to M20    ERS ZOD 1522006 DOR 8 Turbine stem adaptor   USA  M16 to 1 2  NPT    ERS ZOD 1323006 DOR 42 stem  100mm effective height  threaded M16 male      ERS ZOD1323011 DOR 52 stem  350mm effective height  threaded M16 male    ERS ZOD 1322071 3 4  BSPF fixed stem for Turbine flowmeters   3 4  BSPF to M16    ERS ZOD        132822101 1  NPTF universal swivel stem for Turbine flowmeters   3 4  BSPF to M16      ERS ZOD 1334001 DC switch mode DIN mount power supply   100 240Vac input  ERS ZOD 1412063 Relay contol output board with two SPCO relays       3 Introduction  1 2 Specifications    Display      Signal Input      Battery power      External power    Memory      Pulse output      Analog output      8 digit alpha numeric LCD characters 9mm   0 35      high with second line sub script text   8 digits totalising  5 digits rate  Programmable 0 3 decimal places for all displays     Universal pulse frequency input compatible with Reed switch  Hall effect  Namur proximity  detectors  Pulse wire  voltage  current  amp  Coil  15mV P P min   Max  input frequency 10Khz     Minimum input frequency for rate display is 0 1hz with low frequency cut off feature enabled   0 3hz when disabled  amp  0 7hz if the non linearity feature is enabled  Totals have no  minimum     Battery life expec
27.  pulse amplitude      DIP switches off  NOTE  Position a 1000  14W           Resistor across terminals 3  amp  5  OV  ground   Remote reset  03  Fa m2 fa    Coil with pre amp B d1  current modulated A  OV  ground        6    8 24Vdc in    12 Installation    3 3 Wiring connections    External DC powering   required for powered flow sensors  display backlighting or pulse outputs     CAUTION    Avoid using low cost digital  switch mode power packs     OV  ground   Remote reset    Flow  Input   OV  ground      8 24Vdc in    A Pulse output    8 24Vdc  regulated supply       EN  2   3  a  5  6    Note   Powering the instrument from an external DC source will cause the  backlighting feature to turn on  if this is not desirable at all times then install a  power isolation switch in series with the DC power source as shown     Remote reset  Terminals 1  amp  2 cater for the connection of a remote reset switch  this will reset the 6 digit resettable totaliser display but does  not effect the 8 digit Accumulative totaliser  The remote switch needs to have a momentary contact action only     Remote reset switch    AJO as a    Remote reset switch is to have a  momentary action     normally open        Wiring requirements   Use multi core screened twisted pair instrument cable   0 25     0 5mm2  for electrical connection  between the RT and any remote flowmeter or receiving instrument  The screen needs to be earthed to the signal ground of the  receiving instrument only to protect the tran
28.  switches     OV  ground  ES     Feessseossoesosesssossseseseosooesosesssossoessseosoossesessoossoossseosoeesesesososesessseesooeesosesssosssosssoosoeesesesssossoossscosoeesesesssosssossscososesesesssossoessssesooee    Flowmeter       Reference information 20    9  REFERENCE INFORMATION    9            Program detail          Pencil your program details here          seconds           seconds                O   inhibit network function     9 2 Error messages  ZOD B1 has a series of error messages which are scrolled  across the LCD display when ever an error condition exists     NO POWER    NO INPUT    BATCH VALUE EXCEEDS  BATCH LIMIT    PRE STOP EXCEEDS  BATCH VALUE    WAIT    9     Go    No power indicates that the instrument is on battery power  only and needs to be supplied with an external power source  in order to operate     No input  missing pulse detection  indicates that no pulses  were received at the controller input within the time out period  at any stage of the batch cycle    see clause 4 9      The new batch value will not be accepted because it  exceeds the maximum batch limit value    see clause 4 10      The new batch value will not be accepted as it is less than  the pre stop value   clause 4 7     This message will show if the RUN button is pressed whilst  the controller is in the process of assessing the degree of  overrun from the previous batch when AOC is enabled      1 Back up PIN number   see clause 4 1      Cut from manual for increased security  Yo
29.  the instrument runs on 3 6Vdc  the  battery icon illuminates when the battery output falls below 3 1Vdc  at this point the  instrument will continue to operate for a short period but the battery should be change as  soon as possible  batteries are readily available from all major electronic component  suppliers  see page 2 for details      External power   Regulated 8 24Vdc x 50mA minimum    Memory   All programmed  amp  accumulated data is stored permanently in non volatile memory   Pulse output  NPN transistor  scaleable  5Khz max  100mA maximum drive capability    IP66   67 aluminum alloy with 0 3  magnesium  6  is maximum for mine sites    3 x M16 x 1 5 female conduit entries     A   B   C  114mm  4 5     wide x 96mm  3 8     high x 62mm deep  2 5     x 480g  11b    D  Temperature range from  20  C to  80  C    4  F to  176  F      Physical      Configuring  PIN protected data entry     K factor range     scale factor   Eg  Pulses litre  gallon  lb etc  Programmable range is 0 001  99 999 999  with a floating decimal point during K factor entry     Engineering units   Selectable Ltr  gal  m3  kgs  lbs  total    sec   min   hr or  day  rate      6 Introduction    1 3 Overview   The instrument will display Flow Rate  Resettable Total and an Accumulated Total in engineering units as  programmed by the user  Simple flow chart programming prompts you through the programming set up greatly  reducing the need to refer to the instruction manual  All user program data is retained
30.  to as    INPUT A    at terminals 3 8 4 and  INPUT B    at terminals 1  amp  2     Function A B  Both inputs are added together and displayed as one for Rate  Resettable  amp  Accumulative Totals     Displays Rate  Reset Total  Accum  Total  Outputs Scaled Pulse  Alarms  Analog Output  Function A B      The total of A B flow rates displayed as one rate     The total of A B totals displayed as one total     The total of A B accum totals displayed as one total       Scaled pulse value is relative to the totalised values     Alarms are taken relative to the displayed rate     4 20mA output is proportional to the displayed rate     Input B is subtracted from input A  the resultant is displayed as one for Rate  Resettable  amp  Accumulative Totals     Displays Rate  Reset Total  Accum  Total  Outputs Scaled Pulse  Alarms  Analog Output  Function A B      The difference of A B flow rates displayed as one rate    The difference of A B totals displayed as one total     The difference of A B accum tot  displayed as one total       Scaled pulse value is relative to the totalised values     Alarms are taken relative to the displayed rate     4 20mA output is proportional to the displayed rate     Input A is divided by input B  the resultant is displayed as an instantaneous Ratio  Resettable 4 Accumulative  Totals are independently displayed for both A     B inputs     Displays    Outputs    Rate    Reset Total input A  Reset Total input B  Accum  Total input A  Accum  Total input B    S
31.  up to 3    floating    decimal  IM CO Imin A dis  NOE a Time bases of units  SEC  amp  units  dAy are  displayed to the left of the digital display whilst  LEI le    units  min  amp   hr are to the right of the rate  digits as shown     Backlighting The LCD backlight feature will  only work from an external dc power source in  the range of 8 24Vdc     M     IO  JAY 943        Operation 7    2  OPERATION    2 1 Accumulative Total  Accumulative total can be reset in the program mode  The accumulative total is displayed by pressing the  ACCUM TOTAL key     2 2 Resettable Total  The resettable total display remains visible at all times  amp  may be reset at any time by pressing the reset button for  1 2 seconds     2 3 Rate display The second line display toggles between Rate  amp  Accumulative Total as the appropriate keys  are pressed  The instrument will default out of the rate mode after 1 minute when under battery power  this is to  conserve the battery as the unit draws more current when it needs to calculate rate  Under external power the  instrument will remain on Rate or Accumulative Total as they are selected     When rate is displayed the leading three alpha characters on the left of the display    flash     the time base for rate  eg  rate  SEC  rate  dAy   amp  rate  min  or rate  hr to the left of the rate digits  Decimal points float to provide good  resolution  amp  rangeability     _Lltr SEC o   SEL cr A   bet   litres second  w    litres   second      The minim
32. Batches   TNB   2  Steps you through the program ladder   3  Holding for 3 secs  fast tracks to end prog     1  Starts a batch    2  Resumes a batch if paused    Pauses a batch during batching       D0000Y0       6 Installation Installation 7    3 1 Mounting  3 1 Mounting          Integral meter      Vertical pipe mount  mounts         order Pipe mount kit P No  APM  comprising two brackets   screws and worm drive clamps     Panel mount    Horizontal R  pipe mount E    Surface mount footprint   use 4 screws supplied               doooeoeeeanencnCCCoCCSS           Wall mount usina optional   3 Conduit entries have an integral a  bracket set   a ANY jen a moulded seal  to remove break Cuta 106 5mm  4 2      96mm  3 8        i i 18mm seal out using suitable lever diameter hole in panel    di  eg  screwdriver or rod      8 Installation    3 2 Flowmeter connections  un powered sensors      Flow input switch functions                                             Factory set network default settings  do not change    3 Switch 1   ON engages 0 01uf capacitor to suppress reed switch bounce  Flow    Input Switch 2   ON engages 1 meg Q pull up resister    Switch 3   ON engages 8200 pull down resister    Factory set  do not change    1  Reed switch  200hz max      Relay 2  high   Flow DIP switches 1 4 2 are on    Relay 1  low   Batch status    Not used  Not used    Network  loop        ground    8 24Vdc in           on  gt     Ground screen at  OV  5          Factory set  do not change   
33. CUM  TOTAL STOP BAT LOW HIGH RATE    Lanp hy al al  OJI      LOW HIGH    LILI  T ss    TOTAL    ACCUM  TOTAL       Full LCD display test feature illuminates all  display segments and script text displays for 5  seconds when entering the program mode     Up to 8 digits of Batch quantity programmable  for up to 3 decimal places  English prompts  clearly show the status of the batch        An 5 digit TNB display shows the Total  number of batches dispensed since last reset    reset of TNB and Accumulative Total is only  possible whilst in the program mode       The 8 digit Accumulative Total display can be  programmed for up to 3 decimal places  Reset  is only possible when in the program mode  which can be PIN protected for security     Operation 5  2  OPERATION    2 1 Batch set   Pressing the Batch set key allows the user to enter a batch value by  using the arrowed keys to select the appropriate digits and change their value  Pressing  Batch set again enters  amp  confirms that the new batch value has been entered     2 2 Run   Press RESET then RUN to start the batch  If there are no interruptions the  batch controller will automatically stop the batch once the batch value has been reached     2 3 Stop   Pressing the STOP key at any time during the batch will cause the batcher to  go into a    PAUSED     state and the output relays will be turned off  At this point the user can  resume batching by pressing the RUN key or abort the batch by pressing the RESET key     2 4 Batch
34. EC Waste Electrical  amp  Electronic Equipment  WEEE     Also the following EEC guidelines are fulfilled     2004 108EC EMC Directive  2006 95 EC Low Voltage Directive    ALE Ya   I  Hofheim  17  Sep  2010    H  Peters M  Wenzel  General Manager Proxy Holder          K01 1110    Software issue    ED    Press  amp  hold Program key to show  instrument software version    Replacement Batteries     battery  P No  1312007    O    R S Components Farnell Components  Stock No  596 602 Order code 206 532    3 6V x 2 4Ah AA    Lithium Thionyl Chloride       non   rechargeable cell       TABLE OF CONTENTS    INTRODUCTION   1 1 Order Details   1 2 Specifications   1 3 Overview   1 4 LCD displays   OPERATION   2 1 Accumulative total display   2 2 Resettable total display   2 3 Rate display   2 4 Keypad function matrix   INSTALLATION   3 1 Remote mounting   Surface mount footprint    wall   surface mount    panel mount    pipe mount    facia protector option   3 2 Flowmeter connections   unpowered sensors    powered sensors   3 3 Wiring connections   external powering    remote reset    wiring requirements    scaled pulse output   PROGRAM PARAMETERS   4 1 PIN number program protection   4 2 Resetting accumulative total   4 3 Engineering units   4 4 K factor  flow input scale factor    4 6 Rate response   4 7 Low frequency cut off  refer clause 2 4 page 5    PROGRAMMING   5 1 Programming ladder chart   5 2 Program detail record    PANEL MOUNT DRILL TEMPLATE  Supplement    Declaration of Co
35. K03 1213  Manufactured and sold by     Kobold Messring GmbH  Nordring 22 24  D 65719 Hofheim  Tel    49 0 6192 2990  Fax   49 0 6192 23398       BI DIRECTIONAL INSERTION FLOW TRANSDUCER  Model DOR    INSTRUCTION MANUAL          BIL    A  Air ot  or  Mo           IMPORTANT INFORMATION    Thank you for purchasing a Kobold Insertion Flowmeter  It is important that you  read this manual to gain a full understanding of the capability and operational  aspects of the equipment you are about to install     This information is provided only to assist in the installation of the product and  does not diminish your obligation to read the manual     1  Select a location that meets the requirements as illustrated on the guideline  sheet  please see the data sheet order codes   An ideal installation would provide  for 25 diameters of straight pipe upstream from the meter and 10 diameters  downstream     You will also need to know the pipe internal diameter  NB  and pipe wall thickness  for calculation of the insertion depth   refer page 5   Non ideal installations may  require in situ calibration  refer to the factory for details      2  After screwing the flowmeter in place ensure the flow alignment mark located  on the top positioning collar of the meter aligns with the flow in the pipe  refer  page 5   This ensures the paddle is correctly aligned to the flow    Note  the meter is bi directional so a flow direction arrow is not provided     3  Calculate and adjust the height of the flowme
36. OR 52 stem  350mm effective height  threaded M16 male      Relay contol output board with two SPCO relays    DOM series cooling fin kit for flowmeters with integral instruments    1 2 Specifications    Display      Functions      Configuration      Signal Input      Power requirement      Battery      Control outputs      Alarm   pulse output      Batch status output      K factor range      Engineering units    Count direction      Automatic overrun    compensation    Batch limiting    Run inhibit input      Network I O      Physical      Introduction    8 digit aloha numeric LCD characters 9mm   0 35      high with  second line sub script text  8 digits totalising  3 programmable  decimal points  5 digits for Total number of batches     Batch total  Accumulated total  amp  Total number of batches  TNB      Flow chart entry of data with scrolling English text prompts  User  selectable 4 digit PIN number set up protection  Programmable  decimal points and K factors  All programmed data and batch  status are EPROM protected in the event of a power failure     Universal pulse frequency input compatible with Reed switch   Hall effect  Namur proximity detectors  Pulse wire  voltage   current  amp  Coil  15mV P P min   Max  input frequency 10Khz   Regulated 12 24Vdc x 50mA  add switched current      3 6Vdc lithium battery annunciates a power loss  amp  preserves  batch settings  amp  progress at time of power loss     Two independent NPN open collectors  1A dc resistive load max  
37. ORT  10       ESTOPN  PAUSE NL Y  TO RESUME       16 Secondary I O    7  SECONDARY I O    7 1 Batch Status Output   A solid state NPN output signal is switched on at terminal 12 when a batch is started  the  signal remains on until the batch cycle is completely finished or the batch is stopped and  aborted using the STOP 8 RESET keys     The output is used to notify other control equipment when ZOD B1 is in operation or is  paused  by pressing STOP  or inhibited through an input at terminal 9  RUN inhibit   the  signal remains on under all three conditions  The signal can also be used to inhibit  lock out   other equipment whilst the controller is in use          Batch status        Flow  refer 7 4   input   OV  ground   6   8 24Vdc in Run Inhibit  9       No flow alarm Alarm output  OV  ground  8 H T   refer 7 4  amp  7 5  FON Run inhibit  input      closed   inhibit RUN      7 2 Alarm Output   An NPN PNP selectable solid state output signal  ferminal 7  is activated when the missing  pulse detection feature detects a no flow condition  refer 4 9   NPN PNP selection is to be in  accordance with the connection options on the following page  17      7 3 Run Inhibit Input  The RUN inhibit feature enables ZOD B1 to interlock with other devices within the system or  process when ZOD B1 is in use     When a contact is made across the Run inhibit input at terminal 9  a batch cannot be started  and at the same time an    ENGAGED     prompt will show on the LCD display  If the inhibi
38. Pulse Width Modulation   Resolution 62uA  frequencies above 99 99 Hz are processed as whole numbers      Program protection    Overview    All programmed  amp  accumulated data is stored in non volatile memory     The FI 420 is a non volatile field programmable pulse converter which may be set to function as either a frequency  to current converter  F I   a pulse divider or a single point flow rate alarm device for high or low flow rate detection   The instrument also has an NPN pulse output which mirrors input pulse frequency  this two wire signal may be  used for remote totalisation and or rate indication     The instrument is specifically designed to fit within the terminal housing of any of the propriety flowmeters or may  be adapted to other styles of meters including Turbine and Insertion Paddle wheel flowmeters     In all three functions  the output signal remains as a milliamp signal as follows     Function 1   frequency to current   F I    4   20mA proportional to flow rate  spanned as desired   Function 2   frequency divider  divider range 1 9999  output is 4mA  pulse low  and 20ma  pulse high   25hz max   Function 3   frequency  flow rate  alarm  output is 4mA  no alarm condition  and 20ma  flow rate alarm condition      Calibration   The philosophy behind the processor board rests on the origin of the flow input signal being expressed in terms of  frequency rather than K factor  scale factor  however  in order to derive the relevant frequency the user must work  f
39. S    5 1 Analog Output  loop powered     The loop powered 4 20mA output can be spanned anywhere within the flow meter range  Testing the current loop  is available during programming when 4mA will output at programming level L15 and 20mA will output at level L16   page 16      Note  If using the Rate Conversion Factor  RCF  the span for 20mA must be set in relation to the  total units  not the rate units     5 2 Flow Alarms  The ZOD Z3 must be externally powered as per page 10   Two flow alarm FET  transistor   outputs may be programmed for Low  amp  High flow alarms     5 3 Flow Alarm Deadband   Alarms are NPN PNP link selectable  An adjustable deadband  reset differential  provides a trip buffer zone about  the set point in order to overcome alarm    chattering    when the flow rate is fluctuating close to the alarm set point   Deadband is entered as   of each set point value  refer to page 16 for an example      5 4 Dual Flow Inputs  see also page 20 for complete description   When externally powered at terminals 5  amp  6 the ZOD Z3 accepts inputs from two sources  input A  amp  input B   a  separate scaling factor is entered for the second flow input  the instrument is then programmed for one of the dual  input functions of A B  A B or A B  ratio     A B Both inputs are added and displayed as one for Rate  amp  Totals    A B Input B is subtracted from input A  amp  the difference is displayed for both Rate  amp  Totals    A B Totalises A 8 B separately  amp  Rate is a fu
40. S gallons      Declaration of Conformance    page 1    PAGE    w 0 w    ODIO       oDVvooons           Page 2    1 1 Model no  designation  Please see the data sheet    1 2 Overview   Kobold insertion flow transducers provide a cost effective and simple means of measuring  the flow of a wide range of low viscosity liquids  Installation is quick and inexpensive for  pipe diameters ranging from 40mm to 900mm  1 5 36   and up to 2500mm  100   nominal  bore for the Hot tap capable model DOR 52     The flowmeter has a linear measuring range of 0 3 10 0 metres sec   1 33 ft sec     Minimum detectable flow velocity is 0 15 m sec   0 5 ft sec    When used in conjunction with  the ZOD Z3 flow rate totaliser NLC feature the linear flow range is extended down to 0 15  m sec   0 5 ft sec   with an improved linearity     The flowmeter is constructed from 316 L  1 4404  stainless steel enabling use in many  applications for metering water and low viscosity chemicals     Two independent pulse outputs are standard  amp  can directly input to a wide range of  ancillary instruments  PLC   s and computers  Both pulse outputs have a high level of  immunity to electrical interference  Options include a reed switch     1 3 Operating principle   Flow passes through a pipe causing the rotor to spin  Magnets installed in the rotor pass by  pulse sensors within the transducer body  amp  inturn this produces frequency outputs  proportional to flow rate     1 4 Specifications    Velocity measuring range
41. aste Electrical  amp  Electronic Equipment  WEEE     Also the following EWG guidelines are fulfilled     2004 108EC EMC Directive  2006 95 EC Low Voltage Directive  Hofheim  8  Nov  2010 PE  H  Peters M  Wenzel  General Manager Proxy Holder    Manufactured and sold by   Kobold Messring GmbH  Nordring 22 24  D 65719 Hofheim  Tel    49 0 6192 2990  Fax   49 0 6192 23398          KO1 1110    Software versions    n IONES  AAA    Replacement Battery     P No  ERS ZOD 1312007    3 6V x 2 4Ah AA    Lithium Thionyl Chloride      non   rechargeable cell    R S Components  Stock No  596 602       Farnell Components  Order code 206 532    Table of contents    1    10     INTRODUCTION    1 1 Model number designation   1 2 Specifications   1 8 Overview   1 4 LCD displays   OPERATION   2 1 Batch Set   2 2 Batch RUN   2 3 Batch STOP   2 4 Batch Total   2 5 Accumulative total   2 6 Total Number of Batches   TNB     2 1 Keypad function matrix   INSTALLATION   3 1 Mounting   integral mount   wall mount    pipe mount     panel mount   3 2 Flowmeter connections   unpowered sensors    powered sensors   3 3 Wiring connections   external powering      remote switches     wiring requirements     single stage control     two stage control     relay control logic     status  amp  relay connections  PROGRAM PARAMETERS    4 1 PIN number protection   4 2 Resetting accumulative total   4 3 Engineering units   4 4 K factor  scale factor    4 5 Decimal points   4 6 Count direction   4 7 Start delay  amp  Pr
42. bile  installations where the movement of the vehicle or dead heading a pulsating pump may cause spurious flow  signals which are not attributed to actual flow     3  Inhibit the integration  amp  registration of flow at input frequencies below what is considered the minimum  accurate flow rate of the primary flow element  flowmeter      Caution  If the low frequency cut off is set to any value other than 0 0Hz then the integration  of rate and total will cease at frequencies on or below the set frequency value     Programming 15    4 8 Display priority The large digits at the top of the display can be programmed to show either flow rate or  resettable total  When flow rate is selected at the top display the rate key can be used to cycle between rate    reset total  amp  accumulate total  in this mode the instrument will default from rate to reset  amp  accumulative totals after  1 minute  external power must be applied if required to display rate at top display continuously     4 9 1 Flow Alarms  The RT must be externally powered as per page 12   Two flow alarm FET  transistor   outputs may be programmed for Low  amp  High flow alarms  An optional plug in alarm board is available having dual  SPDT 5 amp electro mechanical contacts     4 9 2 Flow Alarm Deadband   An adjustable deadband  reset differential  provides a trip buffer zone about the set point in order to overcome  alarm    chattering    when the flow rate is fluctuating close to the alarm set point  Deadband is ent
43. ble gland entry at base  amp  rear of the enclosure      Overall 85mm diameter x 45mm deep x 175g  0 4Ib          B  C  D  Operating temperature  20  C    80  C    4  F    176  F      Accumulated  amp  Resettable totals  pre amplifier pulse output  amp  a  scaleable pulse output  Low battery indication     Flow chart entry of data with English text prompts    User selectable 4 digit PIN number program protection   Programmable engineering units  decimal points and K factors   All programmed data protected with the battery     Entered as pulses   litre  gallon   b etc  Programmable range is  0 001 9 999 999 999 with a floating decimal point during K factor   scale factor  entry     Entered as engineering units pulse  Range is 0 1 9999 9  units pulse     Selectable Ltr  Gal  m3  kgs  Ibs  MLtr  amp  Mgal or no units of display     A Introduction    1 3 Overview   The ZOD Z1 series instruments are specifically designed for computing     displaying totals  from flowmeters with pulse or frequency outputs  They are battery powered or can be  powered by an external 8 24Vdc regulated or l S  certified supply     The instrument will display Resettable Total and an Accumulated Total in engineering units as  programmed by the user  Simple PIN protected flow chart programming with English prompts  guide you through the programming routine greatly reducing the need to refer to the manual     Special Features   Standard   PIN Protection  Amplified non scaled repeater or scaleable pulse out
44. caled Pulse      Alarms    Analog Output      The resultant Ratio between A B flow rates displayed as an instantaneous    Ratio       The total of input A     The total of input B     The Accumulative total of input A     The Accumulative total of input B       The scaled pulse output relates to input A     Alarms are taken relative to the displayed ratio     4 20mA output is proportional to the displayed ratio     Note  The alarm and analog outputs for the A B function are set in the initial stages of programming in  relation to rate units eg  setting the analog output range to 4mA   00 000 litres min and 20mA   10 000  litres min  the analog output will be proportional to the ratio rate display of 0 000 10 000  eg  4mA    0 000 and 20mA   10 000    The same set up analogy applies to the alarm settings     Declaration of Conformance 21    di    Declaration of Conformance  We  KOBOLD Messring GmbH  Hofheim Ts  Germany  declare under our sole  responsibility that the product     Flow Rate Totaliser Model  ZOD Z3K    to which this declaration relates is in conformity with the standards noted below     Optional for Equipment intended for use in Potentially Explosive Atmospheres   ATEX Directive 94 9 EC    EN 50014  1997   Amds  1 4 2 Intrinsically Safe Electronics  1 S       Optional  EN 50020  2002 Intrinsically Safe Electronics  1 S       Optional    EN 60529  DIN VDE 0470 1 1992 11  I P  Ingress Protection Classifications    EN 61326 1  2006 10  Electrical equipment for contr
45. e stop   4 8 Automatic overrun compensation   AOC    4 9 Missing pulse detection   no flow alarm output  4 10 Batch limiting   4 11 Controller network ID number    PROGRAMMING FLOW CHART  BATCH OPERATING PROCEDURE    SECONDARY I O    7 1 Batch status output   7 2 No flow alarm output   71 3 Run inhibit input   7 4 Solid state output logics   NPN selection    TS Solid state output logics   PNP selection      BATCH CONTROLLER NETWORKING    REFERENCE INFORMATION    9 1 Program detail record  9 2 Error messages  9 3 Back up PIN number    ALPHABETICAL INDEX    Eh KON    a d   O OA oo    2 Introduction    1 1 Model number designation  Order Details  Example  ZOD B1KS1F300   Electrical    Housing Type connection  Supply Voltage  Cable gland    1   KS   universal mount   3x cable entry   F3   8   24 VDC    standard  M20 Battery    2   3 x cable entry   F1      110 VAC   KM      integral mount   1 2  NPT 8   24 VDC 0   without    R 2x  Relay  PP   panel mount 0    FO    220 VAC   for ZOD    IP20  screw terminal 8   24 VDC B1K      order only when retrofitting a pulse meter  only possible with ZOD B1PP       Mechan   ical  protect   ion    0      without    S    silicone  bezel boot       Part No  ACCESSORIES FOR ABOVE SERIES  Model  ERS ZOD        stainless steel wall mount kit    stainless steel 2  pipe mount kit    DOR  amp  Turbine stem adaptor   metric  M16 to M20    DOR  amp  Turbine stem adaptor   USA  M16 to 1 2  NPT   DOR 42 stem  100mm effective height  threaded M16 male    D
46. er than 40 hz        ON DIP switches  OO  183  de bounce    D in the ON position    40 hz max                 gnd   Vdc   l  gnd                      Coil input from  turbines or paddle    DIP switch 1 in  the ON position   5 Khz max       Vdc tI L  gnd           and       twisted pair    A  WO  TO       Voltage pulse  input  pulse wire     DIP switch 1 in  the ON position   2 Khz max       Vdc    L  gnd        Screen grounded at  amphenol shroud or  terminal box and  terminal 3 at ZOD Z1           gnd       yellow  N  aster  gt   5   a B    Installation 9    3 2 Flowmeter connections   powered sensors          Namur proximity       NOTE   Voltage not to exceed 13 4 Vdc            through an approved barrier if when using input  an intrinsically safe NAMUR proximity in a       hazardous area   EEx la 11C    Typically DIP switch 2 in  these proximity s are limited to 8 2 Vdc the ON position    250 hz max      gnd   Vdc   l  gnd                   NAMUR  Inductive Proximity        8 24Vdc  external  power    Ground screen at 3            Hall effect input    NPN open collector      DIP switch 1 in  the ON position     Vdc    L  gnd       NOTE  For an input    gt 800hz position a Ya   watt resistor across  terminals 1     4   12Vdc  1Meg Q    24Vdc  2Meg Q              gnd          EL          1        Hall 8 24Vdc  effect external  power            Modulated current  pulse input  4 20mA     All DIP switches  to be in the OFF  position     Vdc       gnd    NOTE  Position a 100 oh
47. ered as   of each  set point value  refer to page 17 for an example      Programming 16    5 1    Return to top    ISSUE 1 0    AccESSED    if PIN protected       hold Program  amp  Reset keys for    Prog  k  press Frog  key 5 secs to access program mode    to step through  program levels          Nu Pin    rESEt  ACCUM TOTAL   XxXxxxxxx    Ltr gal m3 Ibs kgs  none   Eng unit    S   FAct  00000 001   99999 999    0 0 0 0 00 0 000    dEc tot    PEr SEC   min   hr  dAy     001   999  rESPonSE    if incorrect  PIN No  is entered    rEAdonLY                   4          Read only                              S factor  K  factor  is the number of pulses   unit volume  or unit mass eg  20 465 pulses   litre  gallon  kg etc     0 0 0 0 00 0 000    0 0 0 0 00 0 000  dEc rAtE                            Response to change in rate  see rate dampening 4 6            Low frequency cut off is generally set to 0 0Hz  disabled  for  most applications other than those described at clause 2 4             PuLSE The scaleable pulse output is set as the number of litres   Out 0001 0 gallons etc per output pulse  see clause 4 8         totAL rAtE    toP diSP    Continued over    Assign resettable total or rate to the large LCD top display   see display priority 4 8        of program page    Programming 17    Return to top          of program  XXXXXX Optional alarm outputs  Lo   FLo 1  Low flow alarm  Lo Flo  occurs when the flow  falls below the set point  High flow alarm  Hi Flo   occurs when the
48. es are made  after 4 minutes     14 Programming    5  PROGRAMMING FLOW CH    V3 1 HOLD 3 2 1    TESTING DISPLAY 88888888    PROGRAM MODE ENTERED    if PIN protected    ENTER PIN    PIN       press Prog  key  to step through  program levels                                     CHANGE PIN No  Y   N  NUPIN Y N    YES NO                RESET ACCUM TOTALS Y N  RESET Y   N    SET ENGINEERING UNITS  ENG UNIT Ltr gal m3 Ibs kgs  none     ENTER NUMBER PULSES PER  Ltr m3 kg gal Ib  unit   K 0000 001   999999 999  SET DECIMAL POINTS    DPt TOTAL 0 0 0 0 00 0 000  DPt ACCUM TOTAL O 0 0 0 00 0 00    SET COUNT DIRECTION  COUNT DN   UP    START DELAY   RELAY 2  DELAY 000   999 seconds            PRE STOP VALUE   RELAY 2    PRE 000   999    AUTOMATIC OVERRUN COMPENSATION    AICOMP Y  N    continued             ART    CE    hold Program  amp  Stop    6 keys for 5 secs to C stop    enter the program    if incorrect  PIN No  is entered    INVALID PIN VIEW  EXISTING PROGRAM  DETAILS ONLY         gt  K factor  scale factor  is the number of  pulses per unit volume or unit mass  eg  20 465 pulses   litre  gallon  kg etc        SET MISSING PULSE TIME OUT  T OUT 00   99 seconds    SET BATCH LIMIT  XXXXXXXX    NETWORK OPERATION  N   WORK Y N    YES NO    SET UNIT ID No   ID No  X    See page 13                                NO YES      Exit program  mode    BATCH OPERATING PROCEDURE    TO REPEAT  BATCH    Operating 15    fentcu SEN TO CHANGE  A BATCH  ENTER BATCH A   QTY  XXXXXXXX  AIDA  UM  O  TO AB
49. ets   screws and worm drive clamps        seo HAAR e G    Optional facia protector  3mm clear  polycarbonate plate with access port  for keys  Order P No  1306067       Horizontal  pipe mount                      10 Installation    3 2 Flowmeter connections   unpowered sensors    DIP switch functions      Switch 3   ON engages 8200 pull down resister    Input Switch 2   ON engages 1 meg    pull up resister    Switch 1   ON engages 0 01uf capacitor to suppress reed switch bounce       1  Reed switch    DIP switch 1  amp  2 are on 2    Flow  Input       ae  gt   Ground screen at  OV  5      6  8 24Vdc in    2  Voltage Pulse    Flow  Input       3  Coil  Turbine 8  paddle style flowmeters     minimum 15mV p p      All DIP switches off  position switch 1  OV  ground     ON if unit is effected by line noise   Remote reset    03   a  d1    OV  ground      8 24Vdc in    Pulse output       Installation 11    3 2 Flowmeter connections   powered sensors    4  Hall effect  5 24Vac open collector    DIP SW2  pull up  is on     OV  ground   Remote reset      Signal out J U L A   ti  pos OW    OV ground   ime Input    Vdc supply m  OV  ground    8 24Vdc in    Ground screen       5  Namur  inductive proximity switch   DIP SW3  pull down  is on        Ground screen    LF 3    O Flow  at terminal 5 As Input  NAMUR    Inductive Proximity    NOTE   Limit supply to 8 5Vdc  through an approved barrier for  intrinsically safe NAMUR proximities                6  Current modulated pulse  4mA to 20mA
50. fficient time for the  battery change to take place  Changing the battery whilst flow is taking place could cause loss  of the programmed detail  It is advisable to record program details prior to battery change       The battery can last 7 10 years depending on application  amp  environment     2 5 Processor reset button   Should the instrument be corrupted by an electrical hit the processor can be reset by pressing  the black re boot button located above the red DIP switch block on the input interface board   refer page 10   This procedure does not effect totals or programmed data     6 Installation 7    3  INSTALLATION    Surface mount footprint               3 1 Mounting    Integral meter mounting    Use only the 4  special length  self tapping  screws supplied    If using the cable gland  supplied carefully drill a  12 5mm  72     hole at  the underside or from    Noe the inside rear of  housing       Cable diameter range  is 2 9 6 4mm  Z8 4              Panel mounting             APM adaptor pipe  mount kit is suitable  for vertical or  horizontal pipes       If using the cable gland supplied   carefully drill a 12 5mm  72     hole at  bottom or rear of housing as shown  on housing footprint detail on page 7          Cut a 75mm   3     dia  hole in  panel  Existing O ring seals  against panel face       8 Installation    3 2 Flowmeter connections  un powered sensors             Reed switch input Note  DIP switch 3 is to be    OFF for reed switch input  frequencies great
51. frequencies may induce erroneous noise  transients onto the signal  Run instrument cables in a dedicated low energy  low voltage conduit     Installation 11  3 3 Wiring connections   pulse outputs    Current Sinking outputs   NPN    Current sinking derives its name from the fact that it    sinks current from a load     The current flows from  the load into the appropriate output  terminal 5      Driving a logic input The output voltage pulse is typically the internal voltage of the load   The load would normally have an internal pull up resistor on its input     Driving a coil               The NPN style of output is to be used when driving a coil  The coil load is  obtained by dividing the coil voltage by coil impediance   Q    is expressed in amps  amp  is not to exceed  0 1A  The coil voltage is connected across  8 must match  the ZOD Z1 supply voltage 8 the output  5        m FA TIT J1 in the  NPN position    scaleable iJ  non scaled freq   pulse output ai pulse output    8hz max     5Khz max                  NPN output pulse       8 24Vdc external power    Current Sourcing outputs   PNP     Current sourcing gets its name from the fact that it    sources current to a load     The current flows from the  output  terminal 5  into the load  When wired as below the output voltage pulse is the supply voltage of  the load  The load would normally have an internal pull down resistor on its input     J1 in the PNP              position    scaleable iJ  nonscaled freq   pulse outp
52. gnal Inputs      Powering      Pulse output      Physical      Configuration    Functions      Configuration      K factor range      Pulse output range      Engineering units      Introduction 3    5 digit resettable LCD totaliser 7 5mm   0 3     high with second  line 8 digit accumulative total display  amp  text 3 6mm   0 15     high   3 programmable decimal points with both display lines     Universal pulse frequency input compatible with Reed switch    Hall effect  Coil sine  20mV P P min    Voltage or current pulse  amp   Namur proximity detectors  Maximum input frequency is 5Khz for  coils  2 5Khz for Hall effect  amp  current pulse inputs  2Khz for voltage  pulse devices  amp  500Hz for a Namur proximity sensor     3 6Vdc Ultra Lithium battery or l S  battery pack supplied  life  expectancy can be up to 7 10 years  Battery life reduces when  connected with a coil input from turbine flowmeters  The ZOD Z1  may also be externally powered from a regulated 8 24Vdc supply   see page 14 for special instructions regarding ghosting      Scaleable or non scaleable NPN PNP selectable field effect output  Transistor  Non scaleable pulse is particularly suitable for pre   amplifying pick off coil inputs from turbine meters   5Khz  Max       The scaleable pulse output has a fixed pulse width of 60ms and  therefore has a frequency limit of 8hz   Both pulse outputs have a  50mA maximum drive capability    A  IP66 67 high impact  glass reinforced Polyamide enclosure     Self drill ca
53. he count down mode will show with a minus sign in front of the overrun value     4 7 Start Delay  amp  Pre Stop   Relay 2 can be programmed to turn on a time period after the run signal is given then turn off  again a preset number of litres  gallons etc  before the end of the batch  These operational  features provide greater control over the dynamics of the batching process through soft start  and or soft stop or phasing of the control valves and or pump control     The Start Delay can be set from 0 seconds   no delay   to 999 seconds  The pre stop range  is O  no pre stop  to 999 units of measure   litres or gallons etc       Programming 13    4 8 Automatic Overrun Compensation  AOC     Most batching applications will have an inherent end of batch overrun due mainly to the  response time of the process valve  Overrun can be compensated by closing the valve  slightly before the batch value is reached so that the exact batch value is achieved by the  time that the system comes to rest     ZOD B1 has an Automatic Overrun Compensation feature which when enabled will assess  the degree of overrun on previous batches and automatically alters the close timing of the  process valve so that the exact batch value is reached  This feature should not be enabled  on batch processes which are subject to erratic or inconsistent flow conditions     4 9 Missing Pulse Detection   When a value other than 00 seconds is set at Time Out   T   OUT   in the program mode   ZOD B1 will monitor for 
54. hing display   Tohave the accum  total display latch when key is pressed simply press  amp  hold the ACCUM  TOTAL key for 10 seconds  the display will then latch each time the key is pressed  Holding the accumulative total  key again for 10 seconds will revert this key function back to a momentary action     2 2 Resettable Total  also see page 18 for remote reset feature    The display toggles between Rate  amp  Total when the RATE TOTAL key is pressed     Pressing the RESET key whilst displaying total will cause the total to reset to Zero     2 3 Rate display  When rate is displayed the leading three alpha characters on the left of the display    flash     the time base for rate  eg  rate  SEC  rate  MIN  rate  HR  or rate  DAY  Decimal points float to provide good resolution  amp  rangeability     Ltr   SEC      litres   second         The minimum input frequency for rate display is 0 3hz reducing to 0 1hz If the low frequency cut off is set to 0 1Hz   see below   amp  0 7Hz with NLC enabled     2 4 Low frequency cut off  The low frequency cut off is most commonly set to 0 0Hz  disabled  other than to     1  To display rate for input frequencies below 0 3hz  for example setting the cut off at 0 1Hz the rate will continue  to display for input frequencies as low as 0 1Hz  one pulse every 10 seconds   such conditions often apply to  flowmeters with low resolution pulse outputs  low frequency  or flowmeters with a high operational turndown   maximum to minimum flow rate      2
55. hreaded weld on fitting  threadolet  or service saddle   Wrap the threads of the flowmeter with PTFE tape or sealing compound 8 screw the unit  into the installed fitting     page 5    2 3 Height adjustment calculation  Calculate the adjustment height A for DOR 42  or AA for the DOR 52  as follows     A  for DOR 42   175mm  6 9     B C D   AA  for DOR 52   420mm  16 5    B C D     Where     B   Distance between the top of the pipe 8 the top of the hex adaptor   C   Pipe wall thickness   D   Insertion depth   pipe ID   8     ALIGNMENT SLOT TO  PARRALLEL PIPE    Examples of insertion depth D      For 40mm pipe ID  D  5 0mm   For 50mm pipe ID  D  6 25 mm   For 100mm pipe ID  D  12 5 mm   For 400mm pipe ID  D  50 0 mm              Tum the height adjustment nuts  1  as required so that the distance between the top of the  hex adaptor  2  and the top of the positioning collar  3  equals your calculated distance A   for DOR 42  or AA for model DOR 52  Retighten the height adjustment nuts  1      2 4 Flow direction orientation  The unit is bi directional however the paddle must be aligned with the direction of flow     Using a 2mm hex key  Allen key   unlock the locking screw located on the positioning collar   3  then insert the hex key  as a lever  in the body rotating hole located above the collar   turn the body until the alignment slot is parallel with the direction of pipe  Retighten the  locking screw     page      page 6    ELECTRICAL CONNECTIONS      see page 9 for QP output
56. hz  52 43hz  524hz or 5243hz followed by the input frequency  at which the flow alarm is to change status  next the deadband is set as a percentage of the frequency switch point   Deadband provides a variable trip buffer zone about the set point in order to overcome alarm    chattering    when the  flow is fluctuating close to the set point  Deadband is expressed as 0 9  of the set point  hz   The final setting  covers the number of poles  NOP  of magnetic flux associated with the primary measuring elements  for example  an Oval PD flowmeter may typically have 1  2 or 4 magnetic poles per revolution  a Turbine flowmeter may have  from 5 to 20 turbine blades  this feature compensates for any inherent cyclic variations in the flux density field of  each pole which could otherwise produce an unstable output  Setting the NOP  or multiples of the NOP for even  better stability  enables the processor to average the input readings thereby maximizing accuracy and repeatability     In run mode the LCD defaults to display the flowmeter input frequency which is used during alarm set point checks     Frequency divider A limited divider range of 1 9999 suits most smaller capacity flowmeters having a high  resolution pulse output generally in excess of 100 pulses per litre  gallon etc  often in situations where the output is  used for totalising  Other applications can include dosing control signals or general output frequency reduction   Programming simply requires the setting of the appr
57. ically Safe Electronics  1 S       Optional    EN 50020  2002 Intrinsically Safe Electronics  1 S       Optional    EN 60529  DIN VDE 0470 1    I P  Ingress Protection Classifications    EN 61326 1  2006 10    Electrical equipment for control  instrumentation technology and laboratory use     EMC    requirements  Industrial area     EN 61010 1  2002 08    Safety requirements for electrical equipment for measurement  control  and laboratory    USE        2008 35 EC Waste Electrical  amp  Electronic Equipment  WEEE   Also the following EEC guidelines are fulfilled     2004 108EC EMC Directive  2006 95 EC Low Voltage Directive    General Manager    Hofheim  18  Oct  2010    8  ALPHABETICAL INDEX    Accumulative total    Battery condition indicator  Battery replacement    Battery jumper     D  DC power  powering    Decimal points    Displays     El Engineering units  External DC powering      F   Flowmeter connections     1  Input signal    Interface board  Installation     K  Keypad functions  K factor  scale factor     LCD display     M  Model number designation  Mounting options    0 11    12     14     N  NPN pulse output     o  Operation    Overview  amp  Options     P  PIN number protection  PNP pulse output  Processor reset button  Programming  Program detail record  Pulse output     R  Resettable total    Index    Resetting accumulative total 5     Resetting the processor     s  Scale factor  K factor     Scaleable pulse output    Specifications    Terminal designation   
58. imum  10xd  upstream   5xd  downstream   Optimal  25xd  upstream   10xd  downstream      approx   without electronics    1 6 kg  DOR 4   2 5 kg  DOR 5     page 4  2 0 INSTALLATION    2 1 Meter location   Choose an appropriate section of horizontal or vertical pipe as per the guidelines below   With vertical pipe installations the media should be pumped up through the pipe past the  flow sensor so that any entrained air will pass freely     The DOR flow sensor requires a fully developed turbulent flow profile to ensure maximum  measurement accuracy and repeatability  This can be achieved by installing the DOR in a  straight run of pipe  We recommend at least 10 but ideally 25 straight pipe diameters  upstream  amp  at least 5 but ideally 10 pipe diameters downstream of the flowmeter  Major  obstructions such as pumps  valves or strainers will require longer straight runs before and  after the flowmeter        Major obstructions such as  pumps valves reducers or strainers    to be kept well outside the straight  run pipe sections    10 pipe dia  minimum  25 pipe dia  prefered        5 pipe dia  min   10 pipe dia  prefered       2 2 Meter installation  amp  orientation   Cut a 40mm diameter hole  1 6   on either the 2  10 or 12 o   clock positions of the pipe  If  there is any likelihood of air entrainment in a horizontal pipe do not locate the flow  transducer in the 12 o clock position     mon mi an    Other positions    around the pipe are  acceptable       Install a female t
59. ing a logic input                    The output voltage pulse is typically the internal voltage of the load  The load would normally  have an internal pull up resistor on its input as shown     Driving a coil               The NPN style of output is to be used when diving a coil  The coil load is obtained by dividing the coil  voltage by coil impediance   Q    is expressed in amps  amp  is not to exceed 0 1A  The coil voltage is connected across  amp  must  match the ZOD Z3 supply voltage  amp  the output  7 13  amp  14           LAS scaled pulse PNP Set jumper s   REP repeater pulse A A NEN  lt        to NPN    TA 13 14  High flow alarm  Low flow alarm     OV  ground    8 24Vac in  Pulse output  OV  ground     7B  0 ojo   set jumper i                      E  8       NPN PNP to NPN     ee a ea O    tase er oe Se er es SS ee aaa Ss ae a a a Y SS a Se ee SS Sa a    Current Sourcing outputs   PNP     Current sourcing gets its name from the fact that it    sources current to a load     When activated the current flows from the output   7 13  amp  14  into the load  When wired as below the output voltage pulse is the supply voltage of the load  The load would  normally have an internal pull down resistor on its input as shown     LAS scaled pulse PNP D Set jumper s   REP repeater pulse Jo  Lo  NPN to PNP    TA 13 14    High flow alarm   Low flow alarm   5   OV  ground   Ss        8 24Vdc in  Pulse output  OV  ground               Do not tie O volts of the   l logic input to O volt
60. ion   4 2 Resetting accumulative total   43 Engineering units   4 4 K factor  flow input scale factor    4 5 Rate conversion factor   4 6 Rate dampening   see response graph page 19     4 7 Low frequency cut off  refer clause 2 4 page 5    4 8 Pulse outputs   scaleable or non scaleable     49 Non linearity correction   NLC  Linearisation   4 10 Presetting battery power levels    ADDITIONAL PROGRAM PARAMETERS    9 1 Analog output   9 2 Flow alarms   9 3 Flow alarm deadband   9 4 Dual flow inputs   PROGRAMMING   6 1 Program levels 1 7  Program levels 8 13   6 2 Program levels 14 24   6 3 Program detail record    TERMINAL LAYOUT  SELECTION LINKS  amp  REMOTE SWITCHES  DECLARATION OF CONFORMANCE    ALPHABETICAL INDEX    A B    Po    Ooo ooo    Introduction 2    1 1 Model number designation    Electrical  connection     Housing Type Cable gland Supply Voltage Mechanical  protection       KS   universal mount   1   3 x cable entry   F3   8   24 VDC      standard  M20 Battery 0   without 0   without  F1    110 VAC   ZOD  2   3 x cable entry 8   24 R    2 x Relay  Z3      KM      integral mount 1 2  NPT VDC  for ZOD Z3K     F0       220 VAC   PP   panel mount 8   24 S      IP20  02    screw terminal   VDC E      EExia IIB T4   silicone    bezel boot       Yorder only when retrofitting a pulse meter  only possible with ZOD Z3PP     Donk possbk with ZOD Z3K   Optons  R  and  E  cannotbe com binned    Part No  ACCESSORIES FOR ABOVE SERIES       ERS ZOD 1522001 stainless steel wall mount
61. l cause the large 5 digit total to reset to zero  The reset function is  possible at any time during counting     2 2 Accumulative Total   There are 8 digits in the accumulative total display  these can only be reset in the program  mode or can be protected by enabling the PIN protection feature at the front end of program  mode     2 3 Keypad functions  Resets the 8 digit accumulative    total display to zero  Resets internal K factor   scale factor  to zero    Resets the 5 digit resettable  total display to zero     1  Pressing the Program  amp  Reset keys for 5 1  Each press steps you through each level of  seconds enters you into the program mode  the program chart   2  Holding for 3 seconds fast tracks to the END    2  Displays model  amp  software revision No  of the program from any program level     Selects the digit to be set  the selected digit  will be    flashing     indicating that it can be  incremented     No function    Increments the selected digit each time    No function that it is pressed        2 4 Battery replacement   The instrument draws very little power and will run for many years  without the need to  replace the battery  A battery condition indicator on the LCD display will appear when the  battery is low  if the low battery is not replaced the programmed detail  amp  totals will be lost     When changing the battery a small capacitor within the instrument will maintain the  programmed detail  amp  totals in memory for up to 10 seconds providing su
62. loss of flowmeter input signal at all times when either of the control  relays 1 8 2 are energised  If no pulses are received within the time out period   0 99 sec     the controller will de energise both control relays and scroll a    NO INPUT    message across  the LCD display  at the same time it will turn on the    no flow alarm    output at terminal 7   see  page 17 for flow alarm connection detail      At    NO INPUT     the user must acknowledge the alarm condition by pressing the STOP key  once  the operator then has the option of continuing the batch by pressing the RUN key or   aborting the batch by pressing the RESET key which will return the controller to the original  batch set value     4 10 Batch Limit   To avoid entering excessive batch quantities  a maximum batch limit can be set at the  program level  ZOD B1 will not accept a batch value which exceeds the batch limit  on  rejecting an excessive batch value the controller will scroll the message    BATCH VALUE  EXCEEDS BATCH LIMIT    and default to the batch limit on entry  batch set      4 11 Controller networking ID number   Each controller can be given a networking ID number in the range of 1 9  Allocating an ID  number other than 0 is only necessary when a number of controllers are to be networked  together for interlocking purposes   see page 18 for Controller Networking    Setting the ID  number to zero inhibits this function     Note   The instrument defaults out of the program mode if no program entri
63. m   Ya watt resistor across  terminals 1 8 3 as shown        gnd                      Coil with pre amp B    current modulated  A     8 24Vdc  RECTO si exte rnal    Ground screen at 3 power        10    Installation    3 3 Wiring connections    Terminal designation    I P Flow input pulse signal    Vref  Flow input  coils  amp  voltage type inputs    gnd GND Flowinput  pulse type inputs      Ef O P Output pulse  J1  amp J3 selectable      1  2  3  4  Vdc  Vdc External power    8 24Vdc  see P14   5  6  gnd GND External power    Interface board layout    Battery jumper  battery engaged           Processor  reset button      battery isolated  o  F O    ol P O            Input DIP   switches   1   1MO pull up resistor   2   8200 pull down resistor   3   0 01uf de bounce  amp  noise capacitor    limits max  input freq  to 40hz     Output jumpers   J1 NPN PNP selection   J3 Output pulse selection   F O non scaled frequency  P O scaleable pulse    Wiring practice    Use multi core screened twisted pair instrument cable   0 5mm      for electrical connection  between the instrument and any remote flowmeter or receiving instrument  The screen needs to  be earthed to the signal ground or the receiving instrument  this is to protect the transmitted  signal from mutual inductive interference  Do not earth the screen at both ends of the cable     Instrument cabling is not be run in a common conduit or parallel with power and high inductive  load carrying cables  power surges 8 power line 
64. m view remain functional     4 5 Pulse output   The pulse output is NPN PNP link selectable via jumper J1  It is also selected at jumper J3 to  act as a non scaled pre amplified pulse output or scaleable pulse output  maximum load is  50mA     Non scaled pulse output    The un scaled repeater pulse output represents one pulse out for each input pulse from the  primary measuring element  flowmeter   This output acts as an input signal pre amplifier  particularly suitable for pick up coil inputs up to 5Khz  The duty cycle of the output adopts the  duty cycle of the input  The ZOD Z1 needs to be externally powered for this feature to operate   see page 11      Scaleable pulse output     The fully scaleable pulse output is programmable as the number of litres   gallons etc  per  output pulse Eg  0 1 litres pulse  10 litres pulse  100 gallons pulse  Range is 0 1   9999 9  Eng  unit pulse  The ZOD Z1 needs to be externally powered for this feature to operate   p11          The scaleable pulse output is suitable only for remote integration due to the spasmodic nature  of its output frequency  it is limited to 8hz  Should the potential incidence of this output exceed  8hz it can continue to count after flow has stopped until such time as the processor buffer has  completed integration  Most scaleable pulse output requirements are low frequency due to  down scaling and therefore not effected by the buffer count effect     Programming 13    9  PROGRAMMING FLOW CHART              hold P
65. n No s press 8  hold program key         Replacement Batteries     Non l S  battery  P No  1312007    3 6V x 2 4Ah AA    Lithium Thionyl Chloride      non   rechargeable cell    R S Components Farnell Components  Stock No  596 602 Order code 206 532       TABLE OF CONTENTS    1  INTRODUCTION  1 1 Model number designation  1 2 Specifications  1 3 Overview  1 4 LCD displays  2  OPERATION  2 1 Resettable total  2 2 Accumulative total  2 3 Keypad function matrix  2 4 Battery replacement  2 5 Processor reset button  3  INSTALLATION  3 1 Mounting   integral meter mounting    panel mounting    wall   surface mounting    pipe mounting  3 2 Flowmeter connections   un powered sensors    powered sensors  3 3 Wiring connections   Terminal designation    Interface board layout    Wiring practice    NPN pulse output    PNP pulse output  4  PROGRAM PARAMETERS  4 1 PIN number protection  4 2 Resetting accumulative total  4 3 Engineering units  4 4 K factor  scale factor   4 5 Pulse output  5  PROGRAMMING FLOW CHART  5 1 Program detail record  6  TROUBLESHOOTING  7  Declaration of Conformance  8  ALPHABETICAL INDEX    Page 1    E KON    ooo O1 Ol    14    16    17    2    1     Introduction    INTRODUCTION    Housing Type Electrical connection  Supply Voltage Mechanical  Cable gland protection    KS   universal mount   standard   KM    integral mount     order only when retrofitting a pulse meter    0   cable gland supplied   suits 3   6 mm   cables       1 2 Specifications    Display      Si
66. n factor is the number needed  to convert to the required rate unit  some  examples are     Total unit           Cubic metres   Litres   1000 000  US Barrels USgal   42 000  Imp  gallons Litres   4 546       continued           N program return    15 Programming    6 1 Program levels 8   13    L8 SET RATE DAMPENING  DAMP 00 99 RATE    L10 OUTPUT PULSE REQUIRED Y   N  PULSE Y   N    YES NO        L11 ENTER No  OF gal   litres etc  PER OUTPUT PULSE    OP XXXX X    L12 NON LINEAR CORRECTION  NLC Y  N    YES NO    OF 0000 0  set output freq  at point 0   000000 000  set K factor at point 0      1F 0000 0  set output freq  at point 1   000000 000  set K factor at point 1      10 points from OF up to 9F    9F 0000 0  set output freq  at point 9   000000 000  set K factor at point 9                       L13 CHANGE POWER MODE Y N  CHANGE Y   N  applicable under battery only     YES NO    1  ULTRA POWER SAVE  2  STANDBY  3  CONTINUOUS    refer clause 4 10                L9 SET LOW FREQUENCY CUT OFF  HERTZ 0 0   9 9          Low frequency cut off    The low frequency cut off is generally set to  0 0Hz  disabled  for most applications other  than those described at clause 2 4 on page 5    Non linear correction  NLC       overrides K factor set at L4      1  Any number up to 10 frequency points of non   linearity can be programmed with point OF being  the pulse output frequency at the lowest flow rate     2  If any frequency point is set to zero Hz then  all remaining NLC points up to p
67. nction of A B to give instantaneous ratio   Note     When using A 8 B inputs the functions of Scaled Pulse output  Alarm set points    and the Analog output are relevant to resultant computation between A 8 B    The analog output of  function A B can be used as an input for ratio control     6     PROGRAMMING    6 1 Program levels 1 7    V3 2 HOLD 3 2 1    TESTING DISPLAY 88888888 tt    PROGRAM MODE ENTERED    if PIN protected    ENTER PIN    L1     CHANGE PIN No  Y N  NUPIN Y  N    YES NO    L2 RESET ACCUM TOTAL Y N  RESET Y   N    L3 SET ENGINEERING UNITS    ENG UNIT Ltr gal m3 Ibs kgs  none     press Prog  key  to step through  program levels    L4 ENTER NUMBER PULSES PER         Ltr m3 kg gal Ib  unit of measure     0000000 001   9999999 999    L6 RATE CONVERSION Y N  RATECON Y  N                          L7 SET TIME BASE FOR RATE    Ltr gal etc   SEC MIN HR or DAY          NO  Saves  amp  exits program      YES    YES              Programming 14    eS  you    hold Program  amp  Rate  keys for 5 secs to  enter the program    if incorrect  PIN No  is entered    INVALID PIN VIEW  EXISTING PROGRAM  DETAILS ONLY    Mit ia  gt  K factor  scale factor  is the number of    pulses per unit volume or unit mass  eg  20 465 pulses   litre  gallon  kg etc     R 0000 001   9999 999       WARNING on rate conversion factor  RCF     This feature need only be programmed when  the total  amp  rate engineering units are to be  different  eg  m3 for total and litres for rate    The conversio
68. nformance    O O oO  amp     NNNN    15  16    20    22    4 Introduction Introduction 5    1 1 Order Details    Housing Type Electrical connection  Supply Voltage Mechanical  Cable gland protection    1 2 Specifications       KS n es ak moun 0   without Display   Large backlit 6 digit numeric display with LCD characters 17mm   0 67      high  second line  2   3 x cable gland entry 1 2    NPT F3   8   24 Voc  0   without se ae a i ap dat ee a  standard  3   3 x cable gland entry M16 R 2xRelays   P  display of 8 digits x 7mm high totalising plus 5 digits of rate indication  Programmable 0 3 decimal  KM      integral mount protection plate   f Il displ     order only when retrofitting a pulse meter places tor all displays     Signal Input  Universal pulse frequency input compatible with Reed switch  Hall effect  Namur proximity  detectors  voltage  current  amp  Coil  15mV P P min   Max  input frequency 5Khz     Minimum input frequency for rate display is 0 1hz with low frequency cut off feature  enabled  totals have no minimum input frequency when low frequency cut off is set to zero     Battery power  The unit draws about 70UA under battery  life expectancy is generally 3 years  Battery life  reduces when rate is more often displayed  amp  there is no external power connected   Rate  display defaults to total display 1 minute after pressing the rate key in order to conserve  battery power   reverse polarity protected     Battery condition is continuously monitored internally 
69. ns  K factor  scale factor     LCD displays    Low frequency cut off    Model number designation  Mounting options    Operation    Overview    15  12    17  11  15    8  13    10     14     14     11      P   PIN number protection    Programming  Program detail record  Pulse output    Rate response  Rate display   Rate time base  Remote reset input  Resettable total    Resetting accumulative total    Scale factor  K factor   Scaled pulse output  Specifications    Wiring of flowmeter inputs  Wiring of pulse output  Wiring to external power  Wiring requirements    14  16  14  15    16  13    14  15  7  15  7  15    12    14  15    13  5    10  11    13  12  12       89 6 mm          Panel mount template 19         3 53         PANNEL CUT OUT   71mm high x 83mm wide    2 8    x 3 3         Tapping    Drill  amp  tap 4 x M4 holes where indicated   Tapping drills   3 4mm  1 8    or  30 drill     Clearance drills    Clearance drills   4 7mm  3 16    or  13 drill      gt                        68 0 mm    2 68            20 Supplement    8  Instruction manual supplement  for    ELECTRONICS ZOD Z3  ZOD Z5  amp  ZOD B1 WITH  OPTIONAL RELAY OUTPUT BOARD                1  Overview   The Relay Control Output boards are an option for the flow rate totalisers and batch controller  they have two  electro mechanical SPCO relays instead of the solid state outputs of either instrument  The relays will switch  higher loads  5 amps max   to that of the solid state relays and provide electrical is
70. oad would normally    have an internal pull up resistor on its input as shown     Driving a coil               The coil load is obtained by dividing the coil voltage by coil impediance   Q    is expressed in amps  amp  is  not to exceed 0 1A  The coil voltage is connected across  amp  must match the RT supply voltage  amp  the output  7 13  amp  14      14 Programming    4  PROGRAM PARAMETERS    Note  The instrument defaults out of the program mode if no programming entries are made after 4 minutes     4 1 PIN No  Program Protection   Any user defined PIN number other than 0000 will engage the program protection feature  failure to input the  correct PIN number will deny the ability to change any of the program parameters but will allow the user to step  through and view the existing program parameters     Only one PIN number may be set but this can be changed at any time after gaining access through PIN entry   A second back up PIN number is installed at the factory should the programmed PIN be lost or forgotten    refer bottom of page 16 for the back up PIN No       4 2 Resetting Accumulated Total  Resetting the accumulated total can only be done in the program mode     4 3 Engineering Units  Select from available Engineering units to right of the display  refer clause 1 4   for other engineering units set  display to show no engineering units  amp  program a suitable K factor     4 4 K factor  scale factor   Enter K factor at S Fact  up to 5 whole numbers  amp  3 decimal n
71. oint 9F will  automatically assume the last entered NLC  K factor and the program will advance to the   next level  This feature simplifies programming   when not all points of correction are used     3  Linear interpolation is used between frequency    points  except above the last entered frequency  where the last entered NLC K factor is applied     continued                      _   _   _   _  gt  p gt      eg program return e    Programming 16    6 2 Program levels 14 24    L14 ANALOG OUTPUT REQUIRED Y N  4 20mA Y  N    YES NO    L15 ENTER FLOW RATE AT 4mA    TIP  holding the prog  key for 3 sec s  fast tracks to the END of the program       XXXXX XXX LOW        L16 ENTER FLOW RATE AT 20mA    XXXXX  XXX HIGH            L17 ALARM OUTPUTS REQUIRED Y N  ALARMS Y  N Alarm outputs    YES NO 1  Low flow alarm occurs when the flow falls  below the set point  High flow alarm occurs    when the flow goes above the set point   XXXXX XXX LOW 2  Deadband  Reset Differential   provides a    buffer zone about the alarm set point in order  to avoid alarm output    chattering     on  amp  off    L19 ENTER LOW ALARM DEADBAND   when the flow rate is hovering about an alarm    set point   BAND XX  LOW    The   deadband applies above the Low set  point and below the High set point  Deadband    L20 ENTER FLOW RATE HIGH ALARM is setas a percentage of each set point     XXXXX XXX HIGH    Eg  5  deadband at a low alarm set point of  100 L hr will cause a low alarm when the      flow drops to 100
72. ol  instrumentation technology and laboratory use     EMC  requirements  Industrial area     EN 61010 1  2002 08  Safety requirements for electrical equipment for measurement  control  and laboratory  use        2008 35 EC Waste Electrical  amp  Electronic Equipment  WEEE     Also the following EEC guidelines are fulfilled     2004 108EC EMC Directive  2006 95 EC Low Voltage Directive    AE VO    J    Hofheim  18  Oct  2010    H  Peters M  Wenzel  General Manager Proxy Holder    8     5     ALPHABETICAL INDEX    Accumulative total  Alarm deadband  Alarm outputs  Analog output    Battery power levels    DC power  Decimal point  Displays   Dual flow inputs    Engineering units  External DC powering    Flowmeter connections  Flow rate    Inhibit totals  Installation  Input signals    Keypad functions  K factor  scale factor     LCD displays  Loop powering  Link selectors  for outputs     Low frequency cut off    Model number designation  Mounting options    11     13     12     13  13  13    13    10  14    20    12  10    14    10  18    N     22 Index    Non linear correction    o  Operation    P     Output selector links    Overview    PIN number protection    Presetting battery power levels 13    Programming  Program detail record  Pulse outputs    Rate conversion factor  Rate dampening   Rate display   Rate time base  Remote switch inputs  Resettable total    Resetting accumulative total    Scale factor  K factor   Scaled pulse output  Specifications    Terminal designation
73. olation between the switched  output and the instruments circuitry  This option cannot be used in Intrinsically Safe environs     Once plugged into the 16 pin socket  ZOD Z3  amp  ZOD B1  or 20 pin socket  ZOD Z5   the solid state outputs at  terminals 13  amp  14 then cannot be used  the installer must make his control terminations at the relay board  terminals marked NO  normally open   C  common   amp  NC  normally closed   DC  amp  AC voltages may be switched  at these terminals  generally the active is switched      2  Installing relay board  First check  and set if necessary  the positions of the flow input DIP switches adjacent terminals 1 4 on the    instrument PC board  see pages 9 10 in the relevant instrument instruction manual for setting options      As the relay control output board requires external DC power  12 24Vdc at terminals 5  amp  6  the instrument  battery is no longer required  With no external power applied remove the battery to enable the relay board to be  plugged into place using the battery cradle as the retaining mechanism  apply slight pressure to the board as you  spread the battery cradle clips to embrace the relay PC board  The assembly is now ready to be wired     3  Operation  The relay board has a voltage dropping circuit which limits the relay coil drive voltage to 12Vdc irrespective of the    external supply to the instrument  When the external supply exceeds 12Vdc the largest component of this circuit  will become hot to touch  this is
74. opriate divisor number  between 0001  amp  9999   The divided  pulse output is limited to 25hz  The output is current modulated between 4mA and 20mA     In run mode the LCD defaults to function as an output totaliser  amp  may be reset at any time     Operation 3                    LCD contrast has 4  settings  0 3  Press A  for best contrast     KA      GND  E GE    YA    PROGRAM       Touch key matrix    Displays set function Press  amp  hold to enter program  Adjusts LCD contrast Selects digit to be set  Shows set point  divide factor or resets total   Changes value of selected digit       Touch key operation  The 3 touch keys need to be operated slowly with deliberate action as the processor cyclic routine is some what  slow  amp  at times may miss a sharp key action  this is not to be interpreted as an intermittent fault     Testing output with a multimeter   Wire in accordance with the diagram shown  Test output in proportion to frequency input for the 16mA span   4 20mA   16mA span  20mA being full scale  FS  range   for example  if 100hz were to produce 20mA then 50hz  should produce 12mA  25hz should produce 8mA  amp  10hz 5 6mA                         NOTE   Include a 250 load  resistor in circuit to protect  output from overload     K VA    GND  x ieee    YA                       JD      D        PROGRAM    4 Analog output Programming 5    Programming chart       Electrical connections Press  amp  hold PROGRAM  Twisted pair low capacitance shielded instrument cable
75. put     NPN PNP selectable pulse output    Optional   Display backlighting  needs external dc power for this option to illuminate      Intrinsic Safety Certification to IECex scheme and ATEX directive     Environments   The ZOD Z1 series is designed to suit harsh indoor and outdoor industrial and marine  environments  The robust housing is weatherproof to IP676   IP67 standards  UV resistant   glass reinforced Polyamide with stainless steel screws  amp  FKM O ring seals     Installation   Specifically engineered to be directly mounted on a variety of flowmeters  wall  surface or pipe  mounted in the field or control room  Various mounting kits are available  The instrument is  self powered using one 3 6Vdc lithium battery or I S  battery pack  the pulse output option  requires 8 24Vdc     1 4 LCD display    Full LCD display test feature illuminates all  characters and script text displays for 5  seconds when entering the program mode     The 5 digit Total display is front panel  resettable and can be programmed for  up to 3 decimal places     Engineering units are selected during  the initial programming routine        Battery condition indicator shows only  when battery is low  battery life can last  up to 7 10 years     The 8 digit Accumulative Total display  can be programmed for up to 3 decimal  places  Reset is only possible when in  the program mode which can be PIN  protected for security     Operation 5  2  OPERATION    2 1 Resettable Total  Pressing the RESET key wil
76. r 3 seconds fast tracks to the end  of the program from any program level     Selects the digit to be set  the selected digit  will be    flashing     indicating that it can be  incremented     Increments the selected digit each time  that it is pressed        Surface mount footprint 426mm    N Z     use 4 screws supplied   i       Wall mount using optional 3  bracket set  ERS ZOD 1522001        96 mm  3 8     i    7 Installation    3 1 Remote Mounting  continued            Vertical pipe mount      order Pipe mount kit PANO  ERS ZOD   152202 comprising two brackets   screws and worm drive clamps     Panel mount    Horizontal Po  pipe mount   1           Conduit entries have an integral  moulded seal  to remove break  seal out using suitable lever    eg  screwdriver or rod      Cut a 106 5mm  4 2       diameter hole in panel    Installation 8    3 2 Flowmeter connections   unpowered sensors    for l S  installations refer to l S  supplement            Flow input A 8 B switch functions           Gen Flow Terminals 1  28 5 replicate terminals 3  4  amp  5 for dual flow inputs  Ny 1 Input B Switch 1   ON engages 0 01uf capacitor to suppress reed switch bounce  guns Flow Switch 2   ON engages 1 meg Q pull up resister   NE  4 nputA Switch 3   ON engages 8200 pull down resister       1  Reed switch  200hz max      DIP switch 1 4 2 are on    gan Flow High flow alarm  Ny 1 Input B Low flow alarm    Flow  4 20mA output  InputA   _4 20mA output           3     ground  not used  Pani  gt
77. rogram  amp  Reset Cros   keys for 5 seconds to  enter the program mode    if PIN  protected       press Program key to advance  through each program level  Use  arrowed keys to enter parameters       if incorrect  PIN No  is entered    Note  The ZOD Z1 will  default out of the  program mode if no  entries are made  within 4 mins       __  View program  details only      wo    l p K factor  scale factor  is the  number of pulses per unit  volume or unit mass eg    20 465 pulses litre  gal  kg etc     NO       Important  record program details overleaf             14 Programming flow chart    5 1 Program detail record  If not powered for more than 10 seconds the programmed detail  amp  Accumulated Total will    be lost from the processor memory  it is advisable to record your programmed detail  below  Specific instructions on changing the battery without loss of program detail are  given at clause 2 4  page 5     Pencil your program details here    po 0001 0    Factory default settings       6  TROUBLESHOOTING      No display   Check position of the battery jumper J2   see interface board layout page 10    amp  check  battery contact connections  Replace battery       Display ghosting under external power    The LCD display will    ghost    when the instrument is powered from an external 24Vdc  power supply  this is corrected by including two   watt resistors  1 2K  amp  3 3K  on the  input power source as shown below        omy ZOD Z1     Vdc tI Ll  gnd    3           gnd    
78. rom the flowmeters known K factor  these are in most cases available from the respective flowmeters calibration  sheet or given as a nominal with some inferential style flowmeters such as insertion paddle wheel meters     Some programming examples for each function are shown below     Programming examples      30 litres   hr 23 47 hz  282 or 2816   23 47 hz        Flowmeter K factor from calibration report or established tests        Flow rate for 20mA full scale output  no decimal position above 99 9 hz           Minimum divisor depends on acceptable error levels by the user        2 Configuration  Input configurations    The processor board is produced in two configurations  the most common is supplied fitted with a loop powered  Hall Effect pick up  this model is typically supplied with positive displacement flowmeters  The second configuration  board does not have a Hall Effect device but has the facility to accept either a reed switch  coil or pulse wire input  via hard wire solder pad connection  Unless otherwise requested at time of order placement the unit is pre   programmed at the factory to produce 20mA at the maximum flow rate of the associated flowmeter     Function configuration    Frequency to current   F I  Produces 4   20mA analog output proportional to flow rate  Programming requires  the setting of a decimal point for frequency resolution eg  1 000hz  10 00hz  100hz or 1000hz followed by the full  scale frequency to produce 20mA output then finally a respon
79. rsion feature is available  amp  is explained at level 6 in the program chart  page 14   When enabled the  analog output under rate conversion needs to be programmed in relation to the    TOTAL    engineering units     4 6 Rate dampening   Dampening is available to smooth out fluctuating flow input signals in order to provide a stable rate display  amp   analog output  Most input signal are reasonably stable and need only a low setting value of 40 to 70   see  response graph on page 19      4 7 Low frequency cut off This feature is explained in clause 2 4   page 5       4 8 Pulse Outputs  for this feature the ZOD Z3 must be externally powered as per page 10   The pulse output  is link selectable as a scaleable pulse or non scaled repeater pulse  amp  NPN  current sinking  or PNP  current  sourcing  style pulse capable of switching up to 1 amp  Pulse scaling  when selected  is set as the number of litres    gallons etc  per output pulse Eg  0 1 litres pulse  10 litres pulse  100 gallons pulse  Range is 0 1   9999 9  Eng unit pulse  The totalising display visually slows to two updates sec  if the scaled pulse output is selected   The pulse width  pulse duration 1 1  automatically adjusts to the output frequency defaulting to a maximum pulse  width of 300 milliseconds at frequencies below 1 66hz  To calculate pulse width at higher frequencies use  1000     hz x 2    pulse width in milliseconds     4 9 Non Linearity Correction  NLC    Linearisation  Linearisation enables the inst
80. rument to correct for known inaccuracies in a flowmeter thereby improving the overall  accuracy and in many cases increasing the effective flow range  turndown  of the flowmeter  Refer to program  level L12  page 15 for setting NLC points  NLC can be used without external power however  battery life is  reduced according to usage     13 Programming    4 10 Presetting battery power levels   When the instrument is operated under battery power only a special    Power Mode  program option will appear at  level 13 within the programming routine  A choice of three battery power modes enable maximisation of the  battery life according to operational requirements     Ultra Power Save  Typically selected if reading the register infrequently  The display scrolls a  Prompt    PRESS ANY KEY     when a key is pressed display wakes up for  4 minutes then returns to sleep mode  greatly extending the battery life     otandby   Display becomes active whenever a key is pressed or product flows  through the flowmeter  Display returns to sleep mode    after 4 minutes of  no flow input or key actions  prompt then returns to    PRESS ANY KEY        Continuous  Display is active at all times resulting in reduced battery life  Display  reverts from Rate to Total after 4 minutes to reduce battery draw         In sleep mode  and programming mode  flow is always continually totalised     When the battery voltage is low a battery low indicator will appear on the display   J  ADDITIONAL PROGRAM PARAMETER
81. s      3 0    DIT k ALALLAAN LLANTA 3    2 5 Hot tap installation       Yellow  Green                      REED SWITCH  OUTPUT               al F Wo De  o sla 8 T g    Wy  amp  To Q          s   3 a  as 3     2 SE 2  5  g 22 8  L L  gt  ol O  5 we o  5  Ows5     WO  gt   Q O5  gt   Gs 622 or S   gt     IS  Et TE     agi 5  2 si 2  lt  Ss  gt   sone     A AME     N              oo    q  SMES m     ole E  D  D          KOBOLD  OQ Lock          ALO          sensor and high temperature output options    Terminal box option  terminal connections    Conductor color coding also applies to the Non magnetic  Positioning  collar                             bang  2     Do v   o D    P   Shs E  O a ko  O  JAN  lt  D 7 23068    os  Q o2 HL 8  35  x     n 05    e n oo  aj  ocg    os OF  Y  lt            58 7 W ep      2    E Ss5x  3 Mo    1  22D Qu De  D  Q O Lo   lt  2 28    2S SCS G  ws Na e O  gt T o  a  Oy    en B pLa  gt  cos  A A oc Oo OL  s  O BULLE LL x A 12 258 Eg 522  p   f    2 EZEKZEZ s   532   lt  SP OL wew   Ye   E Pop c N 2s ROET a gfo  Lo  O q pa oS amp  o gt   n   oN u a     lt    fe f   E 5    lt   ey 3 Sd  E   SA fo  sheas N GOTTODE LSDESE Vw  AY 500  aw go o ANZ O a W uNnNSo230   2 0  D D     5 su X O WoJ20ES2 lt  p    ou jo     o YSsuU Ro S5SLeD  a  T 2 O x to ZoaLlis SD      gt  an f      DEBOBEZNEOOQ          gt  8  0    3 2  Fz OF wy a  DOocr     a      O  eD   ZEDZ 6 E Q O     ONE BL otis 38  O          O 2 Oo  oO ao as oq YE    0  SUE 9 2 OS we D  D    gt  Clo co 
82. s fitted with the QP output option  quadrature pulse output  may be  interfaced with the Pulse Discriminator Module  PD2   The PD2 accepts the Quadrature  pulse inputs  amp  from these will discriminate between forward  amp  reverse flow  Two individual   amp  proportional pulse outputs can then be sent to appropriate totalising registers or an Z3  add and subtract flow rate totaliser     It is important to note that the Quadrature Pulse option has the same pulse resolution   pulses unit volume  as a standard flowmeter for both forward  amp  reverse outputs     Flowmeter with QP outputs    5 24Vdc maximum    Forward flow Sig     Output signals    Reverse flow Sig     page 10    3 7 Voltage Pulse Connection to family instruments                     Flow instruments or a       terminal box can be  directly mounted to the  flowmeter using ST4  for  DOR 42  or ST5  DOR   52  mounting stem kits      Note  For other output styles see  receiving instrument manual    Z3 8  B1 SERIES  INSTRUMENTS         I  E B3  Allflow DIP    C12  switches in the  LITI OFF position   OV  ground     ZO       Screen    Z1 TOTALISER            DIP switch 1 in  the ON position   2 Khz max      yellow       The flowmeter cable should  not be run with other high  energy cables   clause 3 3             page 11  4 0 K     FACTORS  calibration factors for meter      The K factor  pulses   litre  gallon etc   will vary in relation to the bore size of the pipe in  which the flowmeter is installed     The K fac
83. s of   7B  gt  Set jumper the RT when wired in  NPN PNP to PNP PNP configuration    Programming 12    4  PROGRAM PARAMETERS    Note  The ZOD Z3 defaults out of the program mode if no programming entries are made after 4 minutes     4 1 PIN No  Program Protection   Any user defined PIN number other than 0000 will engage the program protection feature  failure to input the  correct PIN number will deny the ability to change any of the program parameters but will allow the user to step  through and view the existing program parameters     Only one PIN number may be set but this can be changed at any time after gaining access through PIN entry   A second back up PIN number is installed at the factory should the programmed PIN be lost or forgotten    refer bottom of page 17 for the back up PIN No       4 2 Resetting Accumulated Total  Resetting the accumulated total can only be done at level 2  L2  in the program mode     4 3 Engineering Units  refer clause 1 4    select from available Engineering units to right of the display  For other engineering units set display to show no  engineering units  amp  program a suitable K factor     4 4 K factor  scale factor    Enter K factor starting with the most significant number  up to 7 whole numbers  amp  3 decimal numbers can be  entered  Trailing decimal numbers move into view as digits to the right are progressively selected  any significant  digits which may move from view remain functional     4 5 Rate conversion factor  A rate conve
84. se time in seconds  The response time is used to  smooth out fluctuating flow rate in order to provide a stable current output  Most input signals are reasonably stable  and only need a low setting value of 1 to 3 seconds  9 sec  is maximum   these are step changes to the analog  output signal  for example a response setting of 2 seconds would cause the processor to update the output every 2  seconds  The final setting covers the number of poles  NOP  of magnetic flux associated with the primary  measuring elements  for example an Oval PD flowmeter may typically have 1  2 or 4 magnetic poles per revolution   a Turbine flowmeter may have from 5 to 20 turbine blades  this feature compensates for any inherent cyclic  variations in the flux density field of each pole which could otherwise produce an unstable output  Setting the NOP   or multiples of the NOP for even better stability  enables the processor to average the input readings thereby  maximizing accuracy and repeatability of the output     The span adjustment  20m4  is preset at the factory and should have no need to be adjusted there after   In run mode the LCD defaults to display the flowmeter input frequency which is used during calibration     Frequency  flow rate  alarm Output is current modulated between 4mA  no alarm condition  and 20ma  flow rate  alarm condition  when the input frequency reaches the alarm set point frequency  Programming requires the setting  of a decimal point for frequency resolution eg  5 243
85. selected engineering units  batch status and has scrolling English prompts to make   programming easy     Two independent output relays  the second with programmable start delay and pre stop   enable pump and valve control or 2 stage flow phasing at the start and end of each batch   Precise batching is aided by Automatic Overrun Compensation which  when enabled   automatically manages variations in system time lags which could otherwise lead to    discrepancies in dispensed quantity     Safety features includes for an alarm output and automatic cessation of batching if no flow  input is detected and programmable batch limiting protects against setting an oversize batch  quantity  Scrolling messages on the LCD annunciate any alarm fault conditions     Control features include batch count up or down  remote operational switch interface  run  inhibit interlock and batch status output  The ZOD B1 is capable of networking with up to 9  batch controllers using one common flowmeter     Environments  The ZOD B1 is designed to suit harsh indoor and outdoor industrial environments  amp  conforms  to EMC directives  The housing is weatherproof to IP66 67  Nema 4X  standards  UV  resistant  robust glass re enforced plastic with stainless steel screws  amp  FKM O ring seals     ZOD B1 can be mounted on a variety of flowmeters or as a stand alone instrument for wall   surface  pipe or panel mount  Various mounting kits are available     1 4 LCD displays    PAVIA ZN VAN AN ZN Y AN    RUN AC
86. smitted signal from mutual inductive interference     Instrument cabling should not be run in a common conduit or parallel with power and high inductive load carrying cables  power  surges  amp  power line frequencies may induce erroneous noise transients onto the signal  Run instrument cables in a separate  conduit or with other instrument cables     Installation 13    3 3 Wiring connections  continued    Pulse  amp  Alarm Output  for this feature the instrument must be externally powered as per page 12     The scaled pulse output is in the form of an NPN  current sinking  style pulse capable of switching up to 100mA    Current sinking derives its name from the fact that it    sinks current from a load     When activated the current flows from the load    into the appropriate output  terminals 7  13  amp  14      Pulse scaling is set as the number of litres   gallons etc  per output pulse Eg  0 1 litres pulse  10 litres pulse  100 gallons pulse   Range is 0 1   9999 9 Eng unit pulse     The pulse width  pulse duration  of the output pulse automatically mirrors the cyclic width of the incoming pulse  for example    5HZ input frequency would produce a scaled pulse output with a duration  lt 200ms  for 100Hz input the output pulse duration  would be  lt 10ms      E    5   OV  ground     cabana                 gt   8 24Vdc Low flow alarm   1  A Pulse out High flow alarm  1  g  Driving a logic input     The output voltage pulse is typically the internal voltage of the load  The l
87. ss  control valve     Networking takes place when any one controller is started  at this point the flowmeter input   count  is restricted to the controller in use  all other controllers will not count and their start  function will be inhibited and an    ENGAGED    will scroll across the LCD display showing the  ID number of the controller in use        Batch entries can be made whilst individual batch controllers are inhibited  locked out  but  they cannot be started until the controller in operation has completed its batch cycle     eee deeds       TER OE ey OI OR TRO ja  E    For the network feature to work the network DIP switches must be set as shown  amp  each  batch controller MUST be programmed with an individual ID number other than 0  zero         Network loop wiring              ZOD B1 1 ZOD B1 3 Multi product batching                         0 A3  Network High relay 2 0_23  Network High relay 2  NA 2  DIP switch my kl    eee  D1  settings Low relay 1 D1  settings Low relay 1             Product 2       ee ee    Flow Batch status  input DIP  switches     OV  ground  8      Flow Batch status  input DIP  switches    Alarm output  OV  ground  EA                  ZOD B1 2 ZOD B1 4                            03  Network High relay 2  14 C13  Network High relay 2  14   a joi ewitche    AA 14 On 2 DIP switch 919a 14   D1  settings Low relay 1 D1  settings Low relay 1    Flow Batch status  input DIP  switches    Alarm output  OV  ground  ES    Flow Batch status  input DIP 
88. standards include  EN 61326  immunity in industrial locations    EN 62326   emissions in industrial locations    EN 60529  degrees of protection   IP        Installation   specifically engineered to be directly mounted on a variety of flowmeters  wall or surface mounted  pipe or panel  mounted  Various mounting kits are available  The instrument can be self powered or may be powered by an  external dc supply or two wire loop powered     1 4 LCD displays    Full LCD display test feature illuminates all display   N VIN VN VIN VIN VIN VA segments and script text displays for 5 seconds when    RUN ACCUM  TOTAL STOP BAT LOW HIGH RATE entering the program mode     Rate display has flashing SEC  MIN  HR or DAY followed  by up to 5 digits of rate programmable for up to 3    floating     decimal places     The 8 digit Total display is push button or remote  resettable and can be programmed for up to 3 decimal  places     pann The 8 digit Accumulative Total display can be  L       aJ  L AL AN gal programmed for up to 3 decimal places  Reset is only    E al J  k   ja Ji possible when in the program mode which can be PIN  ACCUM TOTAL protected for security        5 Operation    2  OPERATION    2 1 Accumulative Total  Accumulative total can be reset at L2 in the program mode  The accumulative total can be displayed momentarily  or continuously through use of the front panel ACCUM TOTAL key     Momentary display   Accumulative total is displayed only whilst the key is held pressed     Latc
89. t  contact is made whilst a batch is running the batch will be paused  When the run function is  inhibited it is still possible to enter a new batch quantity or review the accumulated totals but  it will not allow the operator to RUN or re start the batch until the inhibit input is released     An example of this feature in practice is where a batch should not be allowed to RUN whilst a  valve at another location is open     Solid state output logics 17    7 4 Current Sinking outputs   NPN     Current sinking derives its name from the fact that it    sinks current from a load     When activated the  current flows from the load into the appropriate output   terminals 7  12  13  amp  14    NPN is the factory  default configuration for the outputs  Refer to pages 10  amp  11 for wiring control outputs     Driving a logic input The output voltage pulse is typically the internal voltage of the load   The load would normally have an internal pull up resistor on its input as shown     Driving a coil               The NPN style of output is to be used when driving a coil  The coil load is  obtained by dividing the coil voltage by coil impediance   Q    is expressed in amps  amp  is not to exceed  100mA at terminals 7 8 12 or 1A at terminals 13  amp  14  The coil voltage is connected across 8 must  match the ZOD B1 supply voltage  amp  the appropriate output   terminals 7  12  13 8 14       L spo  no flow alarm  a 0I PNP Set jumper s   O REP repeater pulse A A NPN  lt  to NPN    TA 13
90. t change    Relay 2  high   Relay 1  low   Batch status    Not used  Not used  Inhibit input a     OV  ground  8           9    10 Installation  3 3 Wiring connections    Powering 8 Remote switches  remote keys      use momentary contact    Network loop Relay 2 high  Relay 1 low    Flow Batch status  Input not used   11     OV  ground  not used   8 24Vdc in Run inhibit 9      No flow alarm  OV  ground  sp    Remote keys    spe  Ne             clit  Reg Vdc    cm STOP    15  16  17  18  19     remote switches only        m RUN    Wiring requirements   Use multi core screened twisted pair instrument cable  0 25 0 5mm       for  electrical connection between the ZOD B1 and any flowmeter or remote switch input  The screen needs to be  grounded at  OV  terminal 8   this is to protect the transmitted signal from mutual inductive interference     Instrument cabling should not be run in a common conduit or parallel with power or high inductive load cables   Power surges  amp  power line frequencies may induce erroneous noise transients onto the signal  Run instrument    cables in a separate conduit or with other instrument cables     Single Stage Control  use relay 1 or 2  relay 2 has pre stop programming capability      Network Relay 2 high  Relay 1 low    Flow Batch status  Input not used   11   OV  ground  not used     8 24Vdc in Run inhibit 9    No flow alarm  OV  ground  a                                  ke    A n e e e A A A A A ee y    Ma Mu Mu Mu Mu Mu Mu amu Mu Mu e Mu e Mu
91. tancy can be up to 5 10 years when programmed with the unique      Ultra Power Save    sleep cycle  Battery life reduces when connected with a coil input from  turbine flowmeters  Rate display defaults to total display 4 minutes after pressing the rate  key in order to conserve battery power   reverse polarity protected    Regulated 8 24Vdc x 150mA or 4 20mA loop powered     All programmed  amp  accumulated data is stored permanently in non volatile memory     NPN PNP transistor  scaleable  50hz max   or non scaleable   5000hz max    1A maximum  drive capability     Two wire loop powered  12 28Vdc into 100 9000 loop load  accuracy    0 25  FS  key  entry programming of Zero  amp  Span     Alarm outputs  Two NPN PNP selectable FET  transistors  programmable low 8 high flow alarm with    Physical      Configuring      K factor range      adjustable deadband  reset differential   Maximum drive 100mA resistive load  24Vdc max     A  IP66   67 high impact glass reinforced Polyamide enclosure   B  3 x M20 or 2  NPT female conduit entries    C  125mm diameter  5    x 64mm deep  2 5   x 400g  0 9lb     D  Temperature range from  20  C to  80  C    4  F to  1 6  F      PIN protected data entry with scrolling English text prompts     Eg  Pulses litre  gallon  lb etc  Programmable range is 0 001  9999999 999 with a floating  decimal point during K factor entry     Engineering units   Selectable Ltr  gal  m3  kgs  Ibs  total    sec min hr or day  rate      Rate conversion  Enables the ra
92. te to be displayed in different engineering units to that of the totals    Battery modes      eg  totals in barrels  oil   amp  rate in US gallons     Ultra power save  standby or continuous display selectable     Dual Input option  Programmable for computations of A B  A B  or A B  ratio      Introduction 4    1 3 Overview  The ZOD Z3 is specifically designed for computing  displaying and transmitting totals and flowrate from flowmeters  with pulse or frequency outputs     The instrument will display Flow Rate  Resettable Total and an Accumulated Total in engineering units as  programmed by the user  Simple flow chart programming with scrolling English prompts guide you through the  programming routine greatly reducing the need to refer to the instruction manual  All user program data is retained  if the battery is removed     Environments   The ZOD Z3 is weatherproof to IP66 67  Nema 4X  standards  UV resistant glass reinforced Polyamide with  Stainless screws  amp  FKM O ring seals  The instrument suits harsh indoor and outdoor environments  amp  conforms  to EMC directive 89 336 EEC Electro Magnetic Compatibility     Features   10 point Linearisation  PIN Protection  NPN PNP selectable autoranging pulse outputs  scaled or un scaled   Low  frequency cut off  Battery conservation mode  4 20mA output  High   Low flow alarms with adjustable deadbands   Dual inputs  Optional l S  certification to ATEX directive  for conforming standards refer to l S  supplement     Conforming 
93. ter  refer page 5      4  Electrical Installation depends on the model you have purchased    If the dualpulse is fitted or supplied with a receiving instrument such as a totaliser  or rate totaliser please refer to the appropriate manual and page 10 of this  manual  For pulse output meters  select the appropriate output and wire to your  receiving device   refer pages 7 to 9      5  Calculate the flowmeter K  scale  factor to suit the installation  For ideal  installations refer to page 11 or 12 or 13 of the flowmeter Manual  For non ideal  installations the K factor may be calculated by performing an in situ calibration   Enter the appropriate K factor into your receiving instrument     CONTENTS  1 0 INTRODUCTION  1 1 Model number designation  1 2 Overview  1 3 Operating principal  1 4 Specifications  2 0 INSTALLATION  2 1 Meter location  2 2 Meter installation  amp  orientation  2 3 Height adjustment  2 4 Flow direction orientation  2 5 Hot tap installations  3 0 ELECTRICAL CONNECTIONS  3 1 Standard outputs  3 2 Optional Reed switch output  30 Instrument cable installation requirements  3 4 Pulse output selection   standard outputs    3 5 QP Quadrature pulse output option  3 6 Bi directional flow using QP option  3 7 Connection to family instruments  4 0 K     FACTOR  calibration factor for meter      5 0    K factors for common pipe ID sizes  lt 575mm  K factors for large pipe ID  gt 460mm   Calculating K factors   metric units     litres or M3    Calculating K factors   U
94. the ability to change any of the program  parameters but will allow the user to step through and view the existing program parameters     Only one PIN number may be set but this can be changed at any time after gaining access  through PIN entry  A second back up PIN number is installed at the factory should the  programmed PIN be lost or forgotten    refer bottom of page 19 for the back up PIN No       4 2 Resetting Accumulated Total  amp  Total Number of Batches   TNB     Resetting the Accumulated Total 8 Total Number of Batches  TNB  is done at    RESET  ACCUMULATIVE TOTALS     in the program mode  Both Accumulated Total  amp  TNB are reset  if you select YES at this program level     4 3 Engineering Units   refer clause 1 4     Select from available Engineering units to right of the display  No engineering units denote  NIL set allowing the user to set up the instrument with other units of measure which are not  available on the ZOD B1 LCD display     4 4 K factor   scale factor     Enter K factor starting with the most significant number  up to 7 prime numbers  amp  3 decimal  numbers can be entered  Trailing decimal numbers move into view as digits to the right are  progressively selected  any significant digits which may move from view remain functional     4 5 Decimal Points  Up to three decimals points can be selected for Batch Total or Accumulative Total     4 6 Count Direction  B1 can be programmed to count DOWN from a preset quantity or UP from zero   Overruns in t
95. tors and formula shown are a result of factory testing using smooth bore piping  under ideal conditions  Variations to the given K factors may occur when using rough bore  piping or inadequate flow conditioning on either side of the flow transducer  refer clause  2 1   In these instances on site calibration may be used to determine the K factor     4 1 Flow transducer K  factors for common pipe sizes  Pipe detail K factors   standard K factors for voltage 8 square wave outputs    NB  ID   40  Schedule 40 pipe     40 Schedule 80 pipe     80       For other pipe sizes below 610mm  24   not listed above  use the graphs and apply the  formula on the following pages   12 8 13     4 2 K factors for large pipes 460mm ID  18   and above use     Pulses per litre   28647   pipe ID     mm   Pulses per M  28647000   pipe ID   mm     Pulses per US gallon 168 14   pipe ID   inches   Pulses per Imp  gallon   201 94   pipe ID   inches        NOTE   K factors for Reed Switch output option are 1 3 the standard factors of voltage  pulse output     page 12    4 3 Calculating K factors  litres or m            25                  24 5 y                24    Pipe ID 450mm  amp  above  A    22 5   A  23 5                                                                                                                                                                                                                                                      23         See          example a          22 5       
96. um input frequency for rate display is 0 25hz reducing to 0 1hz If the low frequency cut off is set to  0 1Hz   see clause 4 7       2 4 Keypad function matrix    Displays Accumulative Total No function  when pressed     Increments the selected digit each time    No function that it is pressed     Resets the accumulative total    Resets the resettable total display to  zero when pressed for 1 2 seconds  display to zero     1  Pressing the Prog   amp  Reset keys for 5  PROGRAM seconds enters you into the program mode  Each press steps you through each  level of the program     2  Displays model  amp  software revision No     Selects the digit to be set  the selected digit  will be    flashing     indicating that it can be  incremented     Displays flow rate when pressed       8    3     Installation    INSTALLATION  3 1 Remote Mounting  Surface mount footprint    use 4 x M3 screws  supplied       Wall mount bracket en  Optional  P No  AWM          6 5 x 19mm 42 6 mm  l  t   sou HARARE tro LI   1 67        meri    la 96 mm  38                       Panel mount options    Cut a 71mm x 83mm   2 8 x 3 3      opening in panel     Drill 4 holes to take  M4 screws on a  68 0 x 89 6mm pitch    2 68    x 3 53            See panel mount tem    Mount using 4 x M4 nuts   amp  washers  tap panel or  use rear case as shown       3 x M16 conduit entries    30mm pitch    Installation 9    3 1 Remote Mounting  continued       Pipe mount      order Pipe mount kit P No  APM  comprising two brack
97. umbers can be entered using the arrowed keys     4 6 Rate response   Adjustable response  rate dampening  is available to smooth out fluctuating flow input signals in order to provide  a Stable rate display  Most input signal are reasonably stable and need only a low setting value of 001 to 004  The  response number  ranged 001 999  represents the number of pulse intervals  duration between each pulse  that  the processor averages and displays the rate as calculated     As a general rule it would be best to apply a response number which is a multiple of the number of pulses a meter  produces for each cycle of its primary measuring element  for example a rotating element may produce 4 pulses  per revolution so 004  008  012 or 016 would be ideal response settings whereas a turbine meters with high  resolution pulse outputs would require response settings like 050  100  200 or in some cases involving high  frequency pulse outputs eg  500hz  the response number would be set to say 999     4 7 Low frequency cut off  The low frequency cut off is most commonly set to 0 0Hz  disabled  other than to     1  To display rate for input frequencies below 0 25hz  for example setting the cut off at 0 1Hz the rate will  continue to display for input frequencies as low as 0 1Hz  one pulse every 10 seconds   such conditions often  apply to flowmeters with low frequency pulse outputs     2  Inhibit the integration  amp  registration of    apparent flow    which at times may be encountered on mo
98. ur back up 4 digit PIN number is 0502    10     E    ALPHABETICAL INDEX    Accumulative total 5  Alarm output 16  Automatic Overrun Comp  13  Batch RUN 5  Batch SET 5  Batch STOP 5  Batch total 5  Batch limit 13  Batch operating procedure 15  Batch status 16  Back up PIN number 20  Battery 4  Controller ID number 13  Controller networking 18  19  Count direction 12  Decimal points 12  Engineering units 3  12  End of batch  batch status  11  16  amp  17  Error messages 20  External DC powering 10  Flow alarm output 18  Flowmeter connections 8  9  ID numbering 13  Inhibit input 16  Keypad functions 5  K factor  scale factor  12  14    Index    LCD display     M  Model number designation  Missing pulse detection  Mounting options     N  Networking   o  Operation    Overrun compensation  Overview     P  PIN number protection  Pre stop  Programming  Program detail record  Programming flow chart     R  Relay control logic  Remote operating keys    Resetting totals  Run inhibit input     s  Scale factor  K factor   Single stage control  Specifications  Start delay    Total Number of Batches  Two stage control    Wiring connections  Wiring requirements    18     12     12     10     21    12  12  13  20  14    11  10  12    16    11  10    KO1 1010    Manufactured and sold by   Kobold Messring GmbH  Nordring 22 24  D 65719 Hofheim  Tel    49 0 6192 2990  Fax   49 0 6192 23398       Universal Mount Series    ZOD ZI BATTERY TOTAUSER    INSTRUCTION MANUAL       To review software versio
99. ut pulse output    8hz max     5Khz max                        PNP output pulse      50mA max   8 24Vdc      external power        load     12 Programming    4  PROGRAM PARAMETERS    4 1 PIN No  Program Protection   The option exists to protect the programmed detail  amp  Accum  Total with a user selected four  digit PIN No    0000 represents no PIN protection     f activated the user must input the correct  PIN No   failure to do so will deny access to change any of the program parameters or reset  the Accumulative Total but will allow the user to step through and view the program details     Only one PIN number may be set but this can be changed at any time after gaining access  through PIN entry  A second back up PIN number is installed at the factory should the  programmed PIN be lost or forgotten   refer page 14 for the back up PIN No       4 2 Resetting Accumulated Total  Resetting the accumulated total can only be done within the program mode     4 3 Engineering Units  refer clause 1 4     Select from available Eng  units to right of the display  The ZOD Z1 can display in engineering  units not available on the LCD display by programming to    no eng  units    and a suitable K   factor     4 4 K factor  scale factor    Enter K factor starting with the most significant number  up to 8 prime numbers  amp  3 decimal  numbers can be entered  Trailing decimal numbers move into view as digits to the right are  progressively selected  any significant digits which may move fro
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
  2727 - Candide  TELSTRA 4G PRE-PAID WI-FI  取扱説明書 家庭用バイオ式生ごみ処理機    Samsung S5610 2.4" 91g Grey  取扱説明書  Procolor Pro-Screen  Trust iZZi  OpenStage 40 T HiPath 4000    Copyright © All rights reserved. 
   Failed to retrieve file