CC-Link/LT Master Block Model FX2N-64CL
Contents
1. lt CONFIG mode gt ON Master block is operating normally OFF Master block is abnormal Power has been interrupted lt TEST mode gt ON Master block is operating normally OFF Master block is abnormal Power has been interrupted N lt ONLINE mode gt ON Communication speed setting error occurred EEPROM read error sum mismatch occurred Flickering Power supplied for communication is abnormal DIP switch for operation setting was changed during operation OFF Master block is operating normally lt CONFIG mode gt ON Communication speed setting error occurred EEPROM write error occurred Flickering Power supplied for communication is abnormal DIP switch for operation setting was changed during operation OFF Master block is operating normally lt TEST mode gt ON Communication speed setting error occurred Flickering Power supplied for communication is abnormal DIP switch for operation setting was changed during operation OFF Master block is operating normally lt ONLINE mode CONFIG mode gt ON Data link is being executed OFF Data link is stopped L RUN lt TEST mode gt ON Self loop back Test finished normally OFF Self loop back Test finished abnormally LED is OFF while the self loop back Test is being executed lt ONLINE mode gt ON Station number discrepancy when BFM 32 20h to 95 5Fh is edited the station numbers are checked Outside control range station error occurred Flickering Stations are abnormal L ERR OF
2. CLIY4 RiB2 Output signals and load 35 vy DC or less power supply Terminal to connect output signals and load power supply EN61131 2 2007 Programmable controllers Relay output 2 240 V AC or less 2 30 V DC or less DC input Relay output 2 CL1XY4 DR1B2 CL1XY8 DR1B2 CC Link LT Dedicated Power Supply 1 Zone defined in EN61131 2 Separation defined in EN61131 2 for EMC LVD regulation decided depending on condition in industrial setting Zone C Factory mains which is isolated from public mains by dedicated transformers Zone B Dedicated power distribution which is protected by secondary surge protection 300 V or less in the rated voltage is assumed Zone A Local power distribution which is isolated from dedicated power distribution by AC DC converters isolation transformers etc 120 V or less in the rated voltage is assumed 100 120 200 230 240 V AC Terminal block to CL1PSU 2A connect power supply 2 Terminal block connection type 3 250 V AC or less when the unit does not comply with UL or cUL standards e When the following models use the CC Link LT power adapter model CL1PAD1 a power line connecting to the external power supply terminal of the CL1PAD1 must be 30 m 98 5 or less CL2AD4 B CL2DA2 B Associated Manuals CC Link LT Master This manual explains the specifications wiring handling etc of the CC Link LT master block Block Model FX2n 64CL M User s Ma
3. It is important to follow the directions for usage DESIGN PRECAUTIONS e Construct an interlock circuit in the sequence program so that the system works correctly using the communication information when an error in the data link occurs If such an interlock circuit is not provided accidents may be caused by erroneous output or malfunction e When a remote I O unit fails inputs outputs may randomly become ON or OFF therefore build an external monitoring circuit that will monitor any input signals that could cause a serious accident Accident may be caused by erroneous output or malfunction CAUTION e Use the master block without applying any force on the master block and the CC Link LT connection cable Otherwise such cables may break or fail INSTALLATION PRECAUTIONS e Make sure to cut off all phases of the power supply externally before attempting installation work Failure to do so may cause electric shock or damage to the product e Use the product within the generic environment specifications described in PLC main unit manual Hardware Edition Never use the product in areas with excessive dust oily smoke conductive dusts corrosive gas salt air Cl2 H2S SO2 or NO2 flammable gas vibration or impacts or expose it to high temperature condensation or rain and wind If the product is used in such conditions electric shock fire malfunctions deterioration or damage may occur e Install the product securely
4. ON Self loop back Test finished abnormally OFF Self loop back Test finished normally LED is OFF while the self loop back Test is being executed lt ONLINE mode CONFIG mode TEST mode gt ON Data is being sent lt ONLINE mode CONFIG mode TEST mode gt ON Data is being received CC Link LT connection cable connector 24G DB DA 24 V Communication speed Swi SW2 Point mode setting Select the number of I O points per station OFF 4 point mode 4 input points and 4 output points in each station ON _ 16 point mode 16 input points and 16 output points in each station Setting is disabled Make sure that this is OFF during operation Setting is disabled Make sure that this is OFF during operation CONFIG mode OFF ONLINE mode normal operation ON CONFIG mode The information on connected stations is saved in the EEPROM TEST TEST mode 7 ONLINE OFF ONLINE mode normal operation ON TEST mode Self loop back Test Setting is disabled Make sure that this is OFF during operation e Factory default all bits of the DIP switch are set to OFF Test mode is selected when both the CONFIG and TEST modes are set to ON simultaneously Status indicator LEDs D p 2 ie P Sm o Q o b e s z 2 m ONLINE For each setting the status at time of power ON is valid If a setting is changed after the power is turned ON the change is invalid CONF
5. It may cause malfunction due to noise interference e Accommodate the CC Link LT connection cable inside a duct or fix it with clamps If the connection cable is loose or is pulled for movement or carelessness the master block and the connection cable may be damaged or malfunction due to imperfect connection e Correctly wire the master block while confirming the rated voltage and terminal arrangement of the master block It may cause fire or product failure e Hold the connector area when disconnecting the CC Link LT connection cable from the master block If the cable area is pulled the master block or the dedicated cable may be damaged or malfunction STARTING AND MAINTENANCE PRECAUTIONS Do not touch any terminal while the PLC s power is ON It may cause an electric shock or malfunction e Make sure to shut down all phases of the power supply outside the master block before starting cleaning If all phases of the power supply are not shut down the master block may be seriously damaged or malfunction CAUTION e Do not disassemble or modify the master block Doing so may cause fire equipment failures or malfunctions For repair contact your local Mitsubishi Electric representative e The case of the master block is made of resin Do not drop or apply strong impacts to the master block DISPOSAL PRECAUTIONS e Please contact a certified electronic waste disposal company for the environmentally safe recycling
6. and disposal of your device Notification of CE marking This notification does not guarantee that an entire mechanical module produced in accordance with the contents of the notification comply with the following standards Compliance to EMC standards of the entire mechanical module should be checked by the user manufacturer Attention e This product is designed for use in industrial applications Note e Authorized Representative in the European Community Mitsubishi Electric Europe B V Gothaer Str 8 40880 Ratingen Germany Standards with which this product complies Type Programmable Controller Open Type Equipment Models Products manufactured from February 1st 2003 Electromagnetic Compatibility Standards EMC EN61000 6 4 2007 Compliance with all relevant aspects of Generic emission standard Industrial the standard environment e Emission Enclosure port e Emission Low voltage AC mains port e Emission Telecommunications network port Compliance with all relevant aspects of the standard Equipment requirements and tests EMI e Radiated Emission e Conducted Emission EMS e Radiated electromagnetic field e Fast transient burst e Electrostatic discharge e High energy surge e Voltage drops and interruptions Conducted RF e Power frequency magnetic field For more details please contact the local Mitsubishi Electric sales site e Notes for compliance to EMC regulation The FX2N 64CL M must be installed in a shielded
7. be checked by the user manufacturer Attention e This product is designed for use in industrial applications Note e Authorized Representative in the European Community Mitsubishi Electric Europe B V Gothaer Str 8 40880 Ratingen Germany Standards with which this product complies Type Programmable Controller Open Type Equipment Models Products manufactured from February 1st 2003 Electromagnetic Compatibility Standards EMC EN61000 6 4 2007 Compliance with all relevant aspects of Generic emission standard Industrial the standard environment e Emission Enclosure port e Emission Low voltage AC mains port e Emission Telecommunications network port Compliance with all relevant aspects of the standard Equipment requirements and tests EMI e Radiated Emission e Conducted Emission EMS e Radiated electromagnetic field e Fast transient burst e Electrostatic discharge e High energy surge e Voltage drops and interruptions Conducted RF e Power frequency magnetic field For more details please contact the local Mitsubishi Electric sales site e Notes for compliance to EMC regulation The FX2N 64CL M must be installed in a shielded metal control panel e Use the CC Link LT module in Zone A as defined in EN61131 2 The terminal and the wiring for the following table can be used in Zone B ae Terminal that can be Rated load Classification d used in Zone B voltage CL1Y4 R1B1 Temminalto connect sag Ac orless
8. metal control panel e Use the CC Link LT module in Zone A as defined in EN61131 2 The terminal and the wiring for the following table can be used in Zone B ae Terminal that can be Rated load Classification d used in Zone B voltage CL1Y4 R1B1 Temminalto connect sag Ac orless GLIVAR Be iPutsignals and load Soy DG or less power supply Terminal to connect output signals and load power supply EN61131 2 2007 Programmable controllers Relay output 2 240 V AC or less 2 30 V DC or less DC input Relay output 2 CL1XY4 DR1B2 CL1XY8 DR1B2 CC Link LT Dedicated Power Supply 1 Zone defined in EN61131 2 Separation defined in EN61131 2 for EMC LVD regulation decided depending on condition in industrial setting Zone C Factory mains which is isolated from public mains by dedicated transformers Zone B Dedicated power distribution which is protected by secondary surge protection 300 V or less in the rated voltage is assumed Zone A Local power distribution which is isolated from dedicated power distribution by AC DC converters isolation transformers etc 120 V or less in the rated voltage is assumed 100 120 200 230 240 V AC Terminal block to CL1PSU 2A connect power supply 2 Terminal block connection type 3 250 V AC or less when the unit does not comply with UL or cUL standards e When the following models use the CC Link LT power adapter model CL1PAD1 a power line
9. using a DIN rail or mounting screws e When drilling screw holes or wiring make sure that cutting and wiring debris do not enter the ventilation slits Failure to do so may cause fire equipment failures or malfunctions e During installation and wiring works adhere dust proof sheets supplied together with the master block on the sides of the master block so that foreign objects such as cutting chips and wiring chips do not enter the inside Otherwise foreign objects may cause fire failure or malfunction e Be sure to remove the dust proof sheet from the PLC s ventilation port when installation work is completed Failure to do so may cause fire equipment failures or malfunctions WIRING PRECAUTIONS e Make sure to cut off all phases of the power supply externally before attempting installation or wiring work Failure to do so may cause electric shock or damage to the product e CC Link LT network wiring uses the CC Link LT connection cable specified by CC Link Partner Association CLPA and perform wiring in accordance with the specifications described in this manual If any cable other than the connection cable is used or if wiring is performed in a method not conforming to the specifications normal data transmission cannot be assured e Do not bind the CC Link LT connection cable together with major circuits or power cables Keep the connection cable away from major circuits and power cables by 100 mm 3 93 or more
10. C 24 V DC power supply oc a Mass weight 0 15 kg 0 33 Ibs 1 When connected to the FX1N Series PLC up to two FX2N 64CL M units can be connected to the main unit and another two on the extension unit 2 FX2N 64CL M draws 190 mA from the 5 V DC source The total 5 V consumption of all special function blocks connected to the main unit or extension unit must not exceed the 5 V source capacity of the system Refer to the Hardware manual of the PLC 3 For the VCTF cable specifications refer to the FX2N 64CL M USER S MANUAL Detailed Volume 6 External Dimensions 2 4 5 0 18 4 0 16 CCrink LT O POWER O FX2n 64CL M 90 3 55 FX2n 64CL M 80 3 15 0 5 0 02 mounting size 87 3 43 l Unit mm inches This manual confers no industrial property rights or any rights of any other kind nor does it confer any patent licenses Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property rights which may occur as a result of using the contents noted in this manual Warranty Mitsubishi will not be held liable for damage caused by factors found not to be the cause of Mitsubishi opportunity loss or lost profits caused by faults in the Mitsubishi products damage secondary damage accident compensation caused by special factors unpredictable by Mitsubis
11. F Data link is being executed normally lt CONFIG mode gt ON Station number discrepancy when BFM 32 20h to 95 5Fh is edited the station numbers are checked Flickering All stations are abnormal OFF Data link is being executed normally Status indicator LEDs RE a lt TEST mode gt ON Self loop back Test finished abnormally OFF Self loop back Test finished normally LED is OFF while the self loop back Test is being executed lt ONLINE mode CONFIG mode TEST mode gt ON Data is being sent lt ONLINE mode CONFIG mode TEST mode gt ON Data is being received CC Link LT connection cable connector 24G DB DA 24 V Communication speed setting Communication speed SW SW2 Mana L ERR Status indicator LEDs m D a Q O D 2 5 Mbps Setting disabled Point mode setting Select the number of I O points per station 16pts OFF 4 point mode 4 input points and 4 output points 4pts in each station ON 16 point mode 16 input points and 16 output points in each station Setting is disabled Make sure that this is OFF during operation Setting is disabled Make sure that this is OFF during operation CONFIG mode OFF ONLINE mode normal operation ON CONFIG mode The information on connected stations is saved in the EEPROM TEST TEST mode 7 ONLINE OFF ONLINE mode normal operation ON TEST mode Self loop back Test Setting is disabled Make sure that this is OFF during operati
12. IGMODE e BFM 32 20h to 95 5Fh changed value while online will cause a L ERR e If no remote modules are attached during power ON no L ERR shown If a remote module is removed during operation no L ERR will be shown 3 Handling Cautions The master block can be mounted on a DIN rail or directly with screws The installation procedure in each case is described below Use the master block without applying any force on the cable Refer to the FX2N 64CL M USER S MANUAL Detailed Volume 3 1 Mounting direction Do not install the master block on the floor ceiling or horizontally within the cabinet If the master block is installed in such a way its temperature may rise Install the master block vertically on the back wall of the cabinet e Leave a space of 50 mm 1 96 or more between the master block and other equipment or structures Keep the master block away from high voltage cables high voltage equipment and other power equipment as much as possible 3 2 DIN rail mounting Align the upper DIN rail installation groove in the module with the DIN rail and press the module on to the DIN rail When removing the module pull the installation hook downwards and remove the module DIN rail mounting screw pitch When mounting the module on the DIN rail tighten the mounting screws at a pitch of 200 mm 7 87 or less Applicable DIN rail TH35 7 5Fe and TH35 7 5Al 3 3 Direct mounting Fix the master block on t
13. JY997D05401J B MITSUBISHI ELECTRIC JAPANESE ENGLISH PROGRAMMABLE CONTROLLERS MELSEGIF CC Link LT Master Block Model FX2n 64CL M User s Manual Hardware Volume Manual Number JY997D05401 J Revision FX This manual describes the name of each part external dimensions and specifications of the CC Link LT master block for the Mitsubishi FX series Programmable Logic Controller PLC For the design and construction of the CC Link LT system refer to the CC Link LT Master Block Users Manual Effective April 2015 Specifications are subject to change without notice 2002 Mitsubishi Electric Corporation SAFETY PRECAUTIONS These SAFETY PRECAUTIONS are classified into two categories WARNING and CAUTION Procedures which may lead to dangerous conditions or cause death or serious injury if not carried out properly Z WARNING Procedures which may lead to dangerous conditions or cause minor to medium injury or physical damage if not carried out properly Z CAUTION Depending on certain circumstances procedures indicated by Z CAUTION may also be linked to serious ramifications It is important to follow the directions for usage DESIGN PRECAUTIONS e Construct an interlock circuit in the sequence program so that the system works correctly using the communication information when an error in the data link occurs If such an interlock circuit is not provided accidents ma
14. cations Specification Remarks speed Distance between noe No restriction stations Maximum number of modules connected 8 units in 1 drop line Maximum trunk 35 m 100 m 500m Cable length between length 114 9 1640 5 terminating resistors 328 1 No restriction Norestriction Maximum drop 4m 16m 60 m Cable length per line length 49 2 164 0 656 2 KK Trunk length branch line length not included T branch Master station T branch interval connection resistor adapter I O station resistor Remote O station Drop length Remote including branch VO station Remote I O station Remote I O station Distance between stations Remote I O station Trunk line Drop line 5 3 Performance specifications Specification FX1N FX2N FX2NC FX3G F X3GC FX3u FX3uc Series PLC FX2NC CNV IF is required when FX2NC Series PLC is connected FX2NC CNV IF or FX3uc 1PS 5V is required when an FX3GC FX3uc Series PLC is connected FX1N Series Up to 4 1 FX2N Series Up to 8 2 FX2nc Series Up to 3 2 FX3G FX3u Series Up to 8 2 FX3GcC FX3uc Series Up to 5 2 P gt 4 point mode and 16 point mode pF pointmode 16 point mode Connected to FX1N FX3G FX3Gc Series PLC 128 points Connected to FX2N FX2NC FX3U FX3UC Series PLC 256 points including I O points in PLC in each case Number of connectable master blocks Maximum number of link po
15. connecting to the external power supply terminal of the CL1PAD1 must be 30 m 98 5 or less CL2AD4 B CL2DA2 B Associated Manuals This manual explains the specifications CC Link LT Master Block Model FX2n 64CL M User s Manual Detailed Volume 1 Product Outline The CC Link LT master block FX2N 64CL M can be connected to the FX Series PLC By using this master block a CC Link LT system can be constructed with the FX Series PLC as the master station JY997D08501 wiring handling etc of the CC Link LT master block 2 Part Name and Setting 2 64 5 0 18 mounting hole DIP switch for operation setting M4 mounting screw ON OFF Test UE Status indicator LEDs CONFIG ONLINE tepts _4pts 8 7 6 5 4 3 2 1 B RATE FX2n 64CL M Extension cable connected to PLC Extension connector to extension block unit or special function block unit of the PLC Connector for CC Link LT interface Hook for installation to DIN rail ea lt ONLINE mode CONFIG mode TEST mode gt ON Power is being supplied OFF Power is not being supplied lt ONLINE mode gt ON Master block is operating normally OFF Master block is abnormal Power has been interrupted EEPROM read error sum mismatch occurred
16. curred EEPROM read error sum mismatch occurred Flickering Power supplied for communication is abnormal DIP switch for operation setting was changed during operation OFF Master block is operating normally lt CONFIG mode gt ON Communication speed setting error occurred EEPROM write error occurred Flickering Power supplied for communication is abnormal DIP switch for operation setting was changed during operation OFF Master block is operating normally lt TEST mode gt ON Communication speed setting error occurred Flickering Power supplied for communication is abnormal DIP switch for operation setting was changed during operation OFF Master block is operating normally lt ONLINE mode CONFIG mode gt ON Data link is being executed OFF Data link is stopped L RUN lt TEST mode gt ON Self loop back Test finished normally OFF Self loop back Test finished abnormally LED is OFF while the self loop back Test is being executed lt ONLINE mode gt ON Station number discrepancy when BFM 32 20h to 95 5Fh is edited the station numbers are checked Outside control range station error occurred Flickering Stations are abnormal L ERR OFF Data link is being executed normally lt CONFIG mode gt ON Station number discrepancy when BFM 32 20h to 95 5Fh is edited the station numbers are checked Flickering All stations are abnormal OFF Data link is being executed normally Status indicator LEDs lt TEST mode gt
17. er strict quality control However when installing the product where major accidents or losses could occur if the product fails install appropriate backup or failsafe functions in the system MITSUBISHI ELECTRIC CORPORATION HEAD OFFICE TOKYO BUILDING 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN JY997D05401J B MITSUBISHI ELECTRIC JAPANESE ENGLISH PROGRAMMABLE CONTROLLERS MELSEGIF CC Link LT Master Block Model FX2n 64CL M User s Manual Hardware Volume Manual Number JY997D05401 J Revision FX This manual describes the name of each part external dimensions and specifications of the CC Link LT master block for the Mitsubishi FX series Programmable Logic Controller PLC For the design and construction of the CC Link LT system refer to the CC Link LT Master Block Users Manual Effective April 2015 Specifications are subject to change without notice 2002 Mitsubishi Electric Corporation SAFETY PRECAUTIONS These SAFETY PRECAUTIONS are classified into two categories WARNING and CAUTION Procedures which may lead to dangerous conditions or cause death or serious injury if not carried out properly Procedures which may lead to dangerous conditions or cause minor to medium injury or physical damage if not carried out properly Z CAUTION Depending on certain circumstances procedures indicated by Z CAUTION may also be linked to serious ramifications
18. he panel surface by tightening the M4 screws inserted in the two upper and lower mounting holes provided on the master block Install the module so that a clearance of 1 to 2 mm 0 04 to 0 08 is assured for each module M4 height 16 mm 0 63 or more Tightening torque range 0 78 to 1 08 N m 4 Connection of External Equipment Connect the master block to a remote I O unit or power adapter using the connection cable and the dedicated CC Link LT connector The connection order of the CC Link LT connection cable has no relevance to the station No e Make sure to install the master block on one side of the trunk line e In the CC Link LT system terminating resistors should be connected to both ends of the trunk line Connect the terminating resistor on the master block side within 200 mm 7 87 of the master block e For the CC Link LT connection cable point of contact the connection cable connector and terminating resistors refer to the homepage of the CC Link Partner Association CLPA http www cc link org 5 Specifications 5 1 General specifications The general specifications except for the following are the same as the PLC main unit For the general specifications except for the following refer to the PLC main unit manual Specification Dielectric 500 V AC for 1 mi are Between case and PLC grounding t inal Isolation 5 MQ or more by 500 V ermina resistance DC megger 5 2 Network wiring specifi
19. hi damages to products other than Mitsubishi products and to other duties e This product has been manufactured as a general purpose part for general industries and has not been designed or manufactured to be incorporated in a device or system used in purposes related to human life e Before using the product for special purposes such as nuclear power electric power aerospace medicine or passenger movement vehicles consult with Mitsubishi Electric e This product has been manufactured under strict quality control However when installing the product where major accidents or losses could occur if the product fails install appropriate backup or failsafe functions in the system MITSUBISHI ELECTRIC CORPORATION HEAD OFFICE TOKYO BUILDING 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN
20. ifications except for the following are the same as the PLC main unit For the general specifications except for the following refer to the PLC main unit manual Specification 500 V AC for 1 min Between case and PLC grounding t inal Isolation 5 MQ or more by 500 V ermina resistance DC megger 5 2 Network wiring specifications Specification Remarks speed Distance between me 4 No restriction stations Maximum number of modules connected 8 units in 1 drop line Maximum trunk 35m 100 m 500m Cable length between length 114 9 328 1 1640 5 terminating resistors i 4m 16m 60m Cable length per 13 1 52 5 196 10 branch 15m 50m 200 m 656 2 Sum of all drop lines 49 2 164 0 K Trunk length branch line length not included T branch k S T branch interval connection pees Power Remote pened resistor adapter I O station resistor Remote I O station Drop length Remote including branch I O station Remote I O station Remote I O station Distance between stations Remote O station Trunk line Drop line 5 3 Performance specifications tem Specification O O FX1N FX2N FX2NC FX3G F X3GC FX3u FX3uUc Series PLC FX2NC CNV IF is required when FX2NC Series PLC is connected FX2NC CNV IF or FX3uc 1PS 5V is required when an FX3Gc FX3uc Series PLC is connected FX1N Series Up to 4 1 FX2N Series Up to 8 2 FX2nc Series Up t
21. ints Number of link points per station shows the number of link points when composite I O module is used 4 points 8 points 16 points 32 points Control specifications cee ms Mekes sems 78m selectable by DIP switch BITR method Broadcastpolling Interval Timed Response Master Station connection Connected at the end of the trunk line position Communication error detection automatic return to system slave station disconnection and internal loop back diagnosis Dedicated flat cable 0 75 mm x 4 VCTF cable 0 75 mm x 4 3 e High flexible cable 0 75 mm x 4 f 8 points fixed Number of occupied NO points Number of connected remote I O points 190 mA Supplied from PLC via extension connector Voltage 20 4 to 28 8 V DC Supplied from power Current adapter via Link scan time Communication Protocol Communication specifications Connection cable Current consumption inside 5 V DC 24 V DC power supply connector Mass weight 0 15 kg 0 33 Ibs 1 When connected to the FX1N Series PLC up to two FX2N 64CL M units can be connected to the main unit and another two on the extension unit 2 FX2N 64CL M draws 190 mA from the 5 V DC source The total 5 V consumption of all special function blocks connected to the main unit or extension unit must not exceed the 5 V source capacity of the system Refer to the Hardware manual of the PLC 3 For the VCTF cable specificati
22. nual Detailed Volume JY997D08501 1 Product Outline The CC Link LT master block FX2N 64CL M can be connected to the FX Series PLC By using this master block a CC Link LT system can be constructed with the FX Series PLC as the master station 2 Part Name and Setting 2 64 5 0 18 mounting hole DIP switch for operation setting M4 mounting screw ON OFF Test UE Status indicator LEDs CONFIG ONLINE tepts _4pts B RATE 8 7 6 5 4 3 2 1 FX2n 64CL M Extension cable connected to PLC Extension connector to extension block unit or special function block unit of the PLC Connector for CC Link LT interface Hook for installation to DIN rail ea lt ONLINE mode CONFIG mode TEST mode gt ON Power is being supplied OFF Power is not being supplied lt ONLINE mode gt ON Master block is operating normally OFF Master block is abnormal Power has been interrupted EEPROM read error sum mismatch occurred lt CONFIG mode gt ON Master block is operating normally OFF Master block is abnormal Power has been interrupted lt TEST mode gt ON Master block is operating normally OFF Master block is abnormal Power has been interrupted N lt ONLINE mode gt ON Communication speed setting error oc
23. o 3 2 FX3G FX3u Series Up to 8 2 FX3Gc FX3uc Series Up to 5 2 4 point mode and 16 point mode ApplicabIE pomt made selectable by DIP switch point mode 16 point mode Connected to FX1N FX3G FX3Gc Series PLC 128 points Connected to FX2N FX2NC FX3uU FX3UC Series PLC 256 points including I O points in PLC in each case Number of connectable master blocks Maximum number of link points Number of link points per station shows the number of link points when composite I O module is used z5Mbps orm moms fe2skops 22m sems 4 points 8 points 16 points 32 points Control specifications 8 0 ms 14 1 ms 25Mbps t2ms 20m fsekbps 156ms 78ms Link scan time 2 5 Mbps 625 kbps and 156 kbps selectable by DIP switch Protocol Broadcastpolling Interval Timed Response Master Paton connection Connected at the end of the trunk line position Communication error detection automatic return to system slave station disconnection and internal loop back diagnosis e Dedicated flat cable 0 75 mm x 4 VCTF cable 0 75 mm x 4 3 e High flexible cable 0 75 mm x 4 8 points fixed Number of connected remote I O points 190 mA Supplied from PLC via extension connector Voltage 20 4 to 28 8 V DC Supplied from power Current adapter via connector Communication specifications Connection cable Number of occupied I O points Current consumption inside 5 V D
24. on e Factory default all bits of the DIP switch are set to OFF e Test mode is selected when both the CONFIG and TEST modes are set to ON simultaneously e For each setting the status at time of power ON is valid If a setting is changed after the power is turned ON the change is invalid CONFIGMODE e BFM 32 20h to 95 5Fh changed value while online will cause a L ERR e If no remote modules are attached during power ON no L ERR shown If a remote module is removed during operation no L ERR will be shown DIP switch for operation setting 3 Handling Cautions The master block can be mounted on a DIN rail or directly with screws The installation procedure in each case is described below Use the master block without applying any force on the cable Refer to the FX2N 64CL M USER S MANUAL Detailed Volume 3 1 Mounting direction e Do not install the master block on the floor ceiling or horizontally within the cabinet If the master block is installed in such a way its temperature may rise Install the master block vertically on the back wall of the cabinet e Leave a space of 50 mm 1 96 or more between the master block and other equipment or structures Keep the master block away from high voltage cables high voltage equipment and other power equipment as much as possible 3 2 DIN rail mounting Align the upper DIN rail installation groove in the module with the DIN rail and press the module on
25. ons refer to the FX2N 64CL M USER S MANUAL Detailed Volume 6 External Dimensions 4 0 16 CC1ink LT 2 4 5 0 18 0 POWERO FX2n 64CL M 90 3 55 FX2n 64CL M 80 3 15 0 5 0 02 mounting size 87 3 43 l Unit mm inches This manual confers no industrial property rights or any rights of any other kind nor does it confer any patent licenses Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property rights which may occur as a result of using the contents noted in this manual Warranty Mitsubishi will not be held liable for damage caused by factors found not to be the cause of Mitsubishi opportunity loss or lost profits caused by faults in the Mitsubishi products damage secondary damage accident compensation caused by special factors unpredictable by Mitsubishi damages to products other than Mitsubishi products and to other duties e This product has been manufactured as a general purpose part for general industries and has not been designed or manufactured to be incorporated in a device or system used in purposes related to human life e Before using the product for special purposes such as nuclear power electric power aerospace medicine or passenger movement vehicles consult with Mitsubishi Electric e This product has been manufactured und
26. t connection e Correctly wire the master block while confirming the rated voltage and terminal arrangement of the master block It may cause fire or product failure e Hold the connector area when disconnecting the CC Link LT connection cable from the master block If the cable area is pulled the master block or the dedicated cable may be damaged or malfunction STARTING AND MAINTENANCE PRECAUTIONS Do not touch any terminal while the PLC s power is ON It may cause an electric shock or malfunction e Make sure to shut down all phases of the power supply outside the master block before starting cleaning If all phases of the power supply are not shut down the master block may be seriously damaged or malfunction CAUTION e Do not disassemble or modify the master block Doing so may cause fire equipment failures or malfunctions For repair contact your local Mitsubishi Electric representative e The case of the master block is made of resin Do not drop or apply strong impacts to the master block DISPOSAL PRECAUTIONS e Please contact a certified electronic waste disposal company for the environmentally safe recycling and disposal of your device Notification of CE marking This notification does not guarantee that an entire mechanical module produced in accordance with the contents of the notification comply with the following standards Compliance to EMC standards of the entire mechanical module should
27. to the DIN rail When removing the module pull the installation hook downwards and remove the module DIN rail mounting screw pitch When mounting the module on the DIN rail tighten the mounting screws at a pitch of 200 mm 7 87 or less Applicable DIN rail TH35 7 5Fe and TH35 7 5Al 3 3 Direct mounting Fix the master block on the panel surface by tightening the M4 screws inserted in the two upper and lower mounting holes provided on the master block Install the module so that a clearance of 1 to 2 mm 0 04 to 0 08 is assured for each module M4 height 16 mm 0 63 or more Tightening torque range 0 78 to 1 08 N m 4 Connection of External Equipment Connect the master block to a remote I O unit or power adapter using the connection cable and the dedicated CC Link LT connector e The connection order of the CC Link LT connection cable has no relevance to the station No e Make sure to install the master block on one side of the trunk line e In the CC Link LT system terminating resistors should be connected to both ends of the trunk line Connect the terminating resistor on the master block side within 200 mm 7 87 of the master block e For the CC Link LT connection cable point of contact the connection cable connector and terminating resistors refer to the homepage of the CC Link Partner Association CLPA http www cc link org 5 Specifications 5 1 General specifications The general spec
28. upplied together with the master block on the sides of the master block so that foreign objects such as cutting chips and wiring chips do not enter the inside Otherwise foreign objects may cause fire failure or malfunction e Be sure to remove the dust proof sheet from the PLC s ventilation port when installation work is completed Failure to do so may cause fire equipment failures or malfunctions WIRING PRECAUTIONS e Make sure to cut off all phases of the power supply externally before attempting installation or wiring work Failure to do so may cause electric shock or damage to the product e CC Link LT network wiring uses the CC Link LT connection cable specified by CC Link Partner Association CLPA and perform wiring in accordance with the specifications described in this manual If any cable other than the connection cable is used or if wiring is performed in a method not conforming to the specifications normal data transmission cannot be assured e Do not bind the CC Link LT connection cable together with major circuits or power cables Keep the connection cable away from major circuits and power cables by 100 mm 3 93 or more It may cause malfunction due to noise interference e Accommodate the CC Link LT connection cable inside a duct or fix it with clamps If the connection cable is loose or is pulled for movement or carelessness the master block and the connection cable may be damaged or malfunction due to imperfec
29. y be caused by erroneous output or malfunction e When a remote I O unit fails inputs outputs may randomly become ON or OFF therefore build an external monitoring circuit that will monitor any input signals that could cause a serious accident Accident may be caused by erroneous output or malfunction CAUTION e Use the master block without applying any force on the master block and the CC Link LT connection cable Otherwise such cables may break or fail INSTALLATION PRECAUTIONS e Make sure to cut off all phases of the power supply externally before attempting installation work Failure to do so may cause electric shock or damage to the product e Use the product within the generic environment specifications described in PLC main unit manual Hardware Edition Never use the product in areas with excessive dust oily smoke conductive dusts corrosive gas salt air Cl2 H2S SO2 or NO2 flammable gas vibration or impacts or expose it to high temperature condensation or rain and wind If the product is used in such conditions electric shock fire malfunctions deterioration or damage may occur e Install the product securely using a DIN rail or mounting screws e When drilling screw holes or wiring make sure that cutting and wiring debris do not enter the ventilation slits Failure to do so may cause fire equipment failures or malfunctions e During installation and wiring works adhere dust proof sheets s