1. Vector Installation amp Commissioning Manual 53 MENU AND CONTROL FUNCTIONS Continued Engineering Options Cont Vector ae SET PANEL Ne PARAMETERS MONITOR DEVICE RESPONSE MAINTENANCE CHECK SET MANAGER ACCESS CODE VIEW DATA CORRUPTION COUNT oa EDIT COMPANY NAME use template EDIT PANEL NAME use template SET NUMBER OF REMOTE PANELS 00 15 28 POWER VECTOR 2 8 YES NO SUPPLY TYPE LE PSU gt LOCAL OR RESPONSE J 5 SYSTEM WIDE MODE SILENCE IF SET KEYPAD YES NO 2 gt LOCAL ALARM gt RESET IF LOCAL alarm S gt LOCAL gt evacuate s gt vesmo LOCAL 9 sence s gt eso gt LOCAL RESET gt YES NO SET NUMBER oriooPps ins OE VIEW FIRMWARE VERSIONS SELECT LOOP 1 4 SELECT 2 8 LOOP POLL DIRECTION DEVICE SET MAINTENANCE THRESHOLD KEYPAD 8 DIGITS SELECT LOOP NUMBER Installation amp Commissioning Manual 2 8 ANALOGUE LEVEL 30 64 MENU TO ESC 2 VIEW COUNT PER SCAN 8 5 SECS ACTIVATE DEVICE OUTPUTS OP100 10 1 000 DEVICES OUTSI
2. 082852 Men ccn uet 35 Connecting the Battery sa i 36 Sounder GCIl cUlls s oam CE ih ang Su h decet deu 37 Remote Relay 5 37 Remote Outputs 1 5 a enne nemen ren nnns 38 CPRO OE AMPLE TRE 39 Sasia eei erre evisos n are 39 Vector Installation amp Commissioning Manual 5 Page NetWorkI g ong ep non Pn tee RE ba vts 40 System Operation RR dob Rina tea nli uterine ase 41 Fire Alarm mE 41 Silencing the Alarm eae a 42 Resetting the 42 MEE 43 aulis 43 Fault u L eel dedi t eo ruit naa a rit ires n cbe aas 44 NICE ID 45 Menu and Control Functions sssssssssssss 46 FUNCUON BUTLONS P 46 Accesso Levels tse shane tet Erbe re Pre LR e ERR ee d nt 47 Menu Flow h Ip a RIEN ERI A 48 XCVACN TIT 50 Disablement Flow Chalrlt emen emen nnn 51 Engineering Options Flow Charts meme 53 COMPUTATION 57 EA teet N
3. Open short circuit on sounder circuit Mains Tall itecto Mains failed Battery fault Battery disconnected max 30s delay or internally faulty Earth fault tee Earth fault Double Resp onse Duplicate address CPU Fault uds CPU failed Network Communications failure Charger PSU failure External only Voltage fault 28 Volts outside spec 22V gt 30V Device Analogue value low Warning Prog switch on SW 2 on DIL switch set to ON Loops Loop quantity fault GPRS modem error Fault from SMS text modem if fitted Vector Installation amp Commissioning Manual 45 MENU AND CONTROL FUNCTIONS General The control panel incorporates facilities to alter the status of the system e g it is possible to isolate parts of the system if there is work in progress or a particular device is faulty and causing unwanted alarms The system can be put into test mode to allow an engineer to activate devices without causing a general alarm and the time and date can be changed e g for British Summer Time These functions are accessible to the user at access level 2 but care should be exercised when utilising the functions as it is possible to disable some or all of the system It is recommended
4. Analogue Addressable Fire Control Panel for Apollo XP95 amp Discovery Protocol V4 1 and above Installation amp Commissioning Manual MV EC 01 Issue 3 0 July 2008 PLEASE READ THIS MANUAL BEFORE HANDLING THE EQUIPMENT AND OBSERVE ALL ADVICE GIVEN IN IT THIS PARTICULARLY APPLIES TO THE PRECAUTIONS NECESSARY TO AVOID E S D Caution Compatibility Software upgrade to V4 1 V4 0 has been introduced to provide the following improvements Support for new printer mechanism Loop polling synchronisation Programmable precinct response Non latching input output units Isolate devices or groups via switch monitor unit Location text with alarm event Revised download program It is recommended that all PCBs are upgraded to V4 1 for compatibility V3 0 files can be uploaded to the new V4 0 download program for editing V4 0 PCBs are not compatible with V3 0 PCBs Vector Installation amp Commissioning Manual CONTENTS Page Introduction rette 6 Product OVverview 8 Installation ote tae emt dator tec eee cte 9 Mounting the skin aE E hem he essa 10 ESD e o lilemEE eL 10 RE E au vented sa Ride apes EAE puede e ater ue eS 11 Mains 11 Connectio
5. US DRE DAR Ra 57 Device 4 4 aadaki oinin 58 Set Loop Parameters Edit loop 61 Set Discovery Device Options r ra mee 63 Loop Set Ancillary Base e 65 Loop Set Programmable 67 Loop Set Default Sounder 68 Loop Set Responses To Remote 68 Set Panel Parameters 5 ee adeb eee 69 PC Configuration oS Mh dosis ned 70 Configuration e bere e BR reuera sad 70 Firmware Flash 76 Technical Specification a rara 78 IDE 78 General x s EE 79 Vector Installation amp Commissioning Manual INTRODUCTION The Vector is a multi loop analogue addressable fire alarm control panel which may be equipped with up to 64 fire zones and 16 non fire zones It has been designed In accordance with European standards EN54 2 and EN54 4 Fire Detection and Alarm systems Control and Indicating Equipment It
6. o 5 Ta swe apa SEE m mie gt 0 ERIT III i Flash Firmware upgrade switch e zm e K M B OUS c o 8 N zo E o 950 n 5 amp o o zLi U4 o Ini nmi o nin o c o 5 o o o o o 5 8 Z gt c gt j gt L _ N c N W z S m o o o o uJ x u c JE o o e o o UECTOR 20 LEDS Vector Installation amp Commissioning Manual 27 ZONE LED BREAKOUT BOARD PCSLA13 a AE gt nS OG Ribbon cable to LED PCB PCSLA12 Vector Installation amp Commissioning Manual gt gt Connect to PCSLA10 11 28 PRINTER CONTROL BOARD PCSLA15 P Connect to PCSLA10 11 9 9 Ribbon cable 8 to printer mechanism we a8 ouo 5 wou 2 a Ribbon cable to LED PCB SETTINGS gt PCSLA12 gt if fitted SWITCHES i 2 ADDRESS SWITCHES FL FLASH PROGRAM MODE CM WATCHDOG INHIBIT NOT USED 1 ADDRESS VALUE 0 1 2 ADDRESS VALUE 0 2 4 ADDRESS VALUE 0 4 Ribbon cable 8
7. COPY TO LOOPS This facility allows copying of a set of parameters common bell operation to a range of other loops for speed of programming Check boxes of desired loops and press ok button to copy Note The Current loop being copied is greyed out DISCOVERY Enter day and night start times at which sensitivity modes are automatically changed Vector Installation amp Commissioning Manual 74 PC CONFIGURATION Continued Network parameters LOOP Select loop 1 4 Set all loops Tick box to give all four loops the same settings RESPONSES TO REMOTE PANELS On the tree the current panel is Marked N A the remote panels are listed Click on plus to expand tree to show the signals which come from the remote panel Evacuate activation of evacuate on remote panel First Alarm a single device in alarm or stage 1 on remote panel Second Alarm Two devices in alarm or stage 2 on remote panel Precinct precinct of remote panel is active Fault a common fault signal from remote panel Expanding the tree of each remote signal displays the status of the available panel out puts when the signal is active Double clicking the status will select between three states continuous pulsing or off for each output The available outputs are Loop sounders all loop sounder devices regardless of local programming Common sounder 1 local sounder cct 1 Common sounder 2 local sounder cct 2 Loop modules
8. The Vector is equipped with up to 64 Fire Zones and 16 Non Fire Zones 65 80 which are used to indicate the location of a device or group of devices on the system Any device which is required to provide an indication must be assigned to one of these zones All devices may be assigned to the Fire Zones 1 64 Non Fire zones are restricted to the following device types only TEM RIO ZMU MAN The Vector may be supplied in increments of 16 32 or 64 zones Vector Installation amp Commissioning Manual 57 CONFIGURATION continued Device configuration Device types operate and are monitored by data bits transmitted to and received from the device The transmitted bits are used to turn on detector LEDs module outputs etc output bits and the received bits are used to identify the device type its address current status etc input bits For a fuller explanation of the data transmission the literature for the relevant device should be con sulted Device types and responses Detectors MAN OPT ION and TEM are general system devices and are assigned to zones 1 to 64 The manual call point MAN has a fast response interrupt facility for rapid operation of sounder outputs The data value returned by the devices is generally as follows Fault Less than 8 Normal Between 8 and 35 Maintenance Between 35 and 45 Pre alarm Between 48 3 and 63 Fire Greater than 64 Output bit operation Bit 0 Switches o
9. and defining the function of each group NOTE For an explanation of group functions and examples of their use in system operation refer to the PC Configuration section Groups are numbered 1 to 32 and are indicated by YES when they are on active and NO when they are off inactive For example if Groups 2 and 4 are on the display would indicate GROUPS YES Press 5 to edit the groups on off The currently selected device is assigned to all groups that are on Text edit To create a text message or to amend an existing message toggle the cursor using the 6 key to the end of the display The display will indicate the text instruction Using the SHIFT or BACK key to position the cursor on the character to be input edited select the key covering the character required and repeatedly press until the correct character appears Press SHIFT to move the cursor to the next position and repeat to selection of the character Continue to select and edit characters until the desired message is displayed Press MENU to return to the first option and continue to edit other addresses if required Press MENU to exit Set input attributes Each device which has input attributes is offered the option latching which can be set as yes or no Non latching is only available for RIO type devices This can be used for interfacing purposes RIO or ZMU Switch monitor types only can be set as Isolator Isolators are inherently non lat
10. Double click and select device from list provided BASE TYPE Double click to select base unit fitted sounder or relay Default is set to remote LED output for detectors OUTPUT RESPONSE Double click to change Silenceable Evacuateable W Non Silenceable Non Evacuateable Non Precinct Common Zonal Groups or Local refer to responses of outputs Select as required DEVICE NAME double click and further click to Enter descriptive text 40 characters ZONE Double left click scroll control to select desired zone 1 80 Note a device must be present before a zone can be specified GROUP ASSIGNMENT Double click to assign de assign the device into one of 32 groups Either as an input output or both to a group INPUT RESPONSES Double click to change attributes 7 Latching Non Latching Isolator Non Isolator Vector Installation amp Commissioning Manual 73 PC CONFIGURATION Continued Ancillary base devices The Apollo range of ancillary base devices sounder and relay bases function by utilizing the remote led output of a detector or beacon to operate them Thus saving addresses used by the loop They are not addressed directly by the system and as such they cannot be auto learnt onto the system The default use of the remote led output of a detector is to illuminate the local remote led In order to utilize these devices it is necessary to allocate them onto the h
11. 3 LOGS ALARM LOG VIEW ENTER 2 2 FAULT LOG P gt DISABLEMENTS sh MANAGER 51 gt VIEW USER LOG 7 5 SET CLOCK Ib ENTER TIME amp DATE 4 4 1005 USING KEYPAD ACTIVATE ENTER SELECT ZONE IN SOUNDER TEST 5 gt MANAGER p TEST s ON OFF 2 8 MODE CODE 2 8 scroll OR ZONAL 0 ALL ZONES i i gt print alarm log 80 PRINT OPTIONS 2 8 print fault log oO print user log ENTER ENGINEERING ENGINEERS OPTIONS CODE 195 print parameters Vector MEMORY ACCESS SWITCH ON CONTINUED ON PAGE 53 Installation amp Commissioning Manual 48 MENU AND CONTROL FUNCTIONS Continued Menu Procedures The following procedures are common to all of the menu options and should be understood before attempting to alter the system status To access the Options Menu the CONTROLS key switch must be in the ON position Press the MENU button on the KEYPAD to display the following SELECT MENU OPTION 1 VIEW ACTIVE FAULTS Use the 2 and 8 keypad buttons to toggle scroll to the required option then press 5 to display the required information At any time pressing MENU again will return you to the menu options or in some cases return you to the last step Depending on the option selected there will be sub menu items which can be accessed by the 5 key or scrolled across to using th
12. All loop rio modules regardless of local programming Remote signal relay local remote relay contact Common fault relay Local fault relay only available for fault signal UPLOADING OR DOWNLOADING VECTOR PANEL FROM PC To download program data to panel a special serial adapter device is required SWP VEC 1 This device provides an opto isolated serial communications between panel and pc Protecting against damage from earth faults or stray voltages This adaptor connects to the vector panel via a special 10 way idc connector and connects to the pc using a cable with a standard rs232 9 pin D connector In computers with no serial port use of an USB to RS 232 adaptor is recommended These devices are readily available complete with serial port emulating software Place the panel to be programmed in the waiting for pc mode via the engineers menu Connect the pc or laptop and then invoke the Read write panel data window SELECT PANEL TYPE to be down loaded this may be panel or repeater panel SELECT PANEL Select the address of the panel which you wish to communicate with COMMS PORT Select which comport you are using on the pc 1 thru 4 Press continue to proceed to the READ or WRITE selection buttons IMPORTANT Before you upload a panel make sure you have saved any data which you have created in the pro gram with an appropriate filename More importantly make sure that you have saved any data in the program prior to downloading the
13. FLT REM SIGNAL FIR COMMON SNDR1 SNDR2 OV 12V 28V 28V C NO NC C NO NC C NO NC NO NC c OOOOOOOOQO OOOOOOOOO OOO Common Fault Relay o p Volts free contacts C Common NO Normally Open NC Normally Closed Remote Signal Isolated by Menu Relay o p Volts free contacts Contacts as above Common Fire on alarm Relay Volts free contacts Contacts as above Common Fire on alarm Relay Volts free contacts Contacts as above SNDR 1 Sounder Circuits 24v Both must be used SNDR 2 12v Voltage Outputs 28v Vector Installation amp Commissioning Manual 21 MAIN PCB continued Terminal Block 4 28V DC 28V DC OO OO OOO 12V Ancillary 12 from the power supply unit Fused on the main at 500mA Output on TB3 for use on ancillary devices PSC Clock input from power supply pcb PSD Data input from power supply pcb 28VDC 28 volt supply from psu to power load Separately fused at full output current 28V NOTE Fuses of lower value may be fitted to provide extra protection to external equipment Vector Installation amp Commissioning Manual 22 MAIN PCB continued Dual in Line Switch Switch 1 In the ON position allows the flash memory to be programmed this disables the cpu and brings on the cpu fault light Switch 2 Program mode switch Wh
14. Fire Alarm signal or an Evacuate command Test Mode Active Indicates system is in the Engineers Test mode with limited operational capabilities Disablement Active Indicates that part of the system is disabled isolated Supply Healthy Indicates that the Mains or Battery supply is present Common Fault Indicates that a fault is present on the system The LCD will show the details Pre Alarm Indicates that a detector has recorded a higher than normal analogue value which could signal an impending fire condition System Fault Indicates that the processor has halted This can only be reset by an engineer Alarm Fault Indicates a fault on the alarm circuit Vector Installation amp Commissioning Manual 16 PANEL INDICATORS CONTINUED Remote Active Indicates that the Remote output relay has been activated Remote Disabled Indicates that the Remote output relay has been isolated for maintenance or testing ARW Auto Reset Warning Indicates processor has automatically re started Must be reset by Reset System Key 9 on keypad More Indicates that there are more events to be interrogated PSU Indicates power supply failure The LCD will show the details Fire Detection Zones Up to 64 indicators zones 1 64 to show which area group of devices has activated in a fire condition Vector Installation amp Commissioning Manual 17 LCD DISPLAY The LCD displays event information status information and the
15. In particular use of BELDEN 8760 1 pair cable is advised Up to 1km of cable may be used over the network For installations exceeding this requirement protocol repeaters may be available please contact the technical dept for further information The CAN bus wiring standard requires the use of 120 ohm termination resistors at the furthest ends of the cabling regardless of its length or the number of nodes fitted Where only one panel is in use the terminating resistors are not required The CAN bus connections are labelled A and B basically all A terminals are connected together and all B terminals are connected together Signal levels around 5 volts would typically be seen when the bus is running Typical CAN bus wiring A B A B A B A B 1208 1208 Up to 1Km Belden 8760 or equivalent Setting up network Each panel in the network must be set with a unique address starting at 0 this is set on the address switches on each panel in turn refer to page 23 for details Each panel has a parameter in the engineering options menu set system parameters option 3 to set the number of remote panels This quantity needs to be set on each panel to represent the number of other panels fitted in the system e g in a network of five panels this figure will be set to 4 in each case Once set correctly the system will be in the quiescent state Net
16. No Refers to time delay If set to no time will expire and function will occur Group assignments 1 Devices Select individual devices and allocate them as inputs and or outputs to the group Ancillary bases must be set for the address before they are available as outputs in groups 2 Zones not available in download program Quick set up utility to insert all addresses in a zone only in the one loop into a group as inputs and or outputs Set the parameter as Add or Remove using scroll button This option can also remove devices from a group by zone This utility works as a off command and cannot be reviewed other than at device level Vector Installation amp Commissioning Manual 66 CONFIGURATION continued Loop Set programmable relays There are four programmable relays available for each loop The common sounder circuits 1 amp 2 which are monitored polarity reversal outputs and the common fire contact and remote signal contact These are clean changeover contacts The remote signal contact has an LED associated with the output on loop one and is intended for connection to remote signalling equipment Select the required relay using the scroll buttons 2 amp 8 1 Common sounder 1 2 Common sounder 2 3 Common fire relay 4 Remote signal relay When selected Option 1 Default assignments will set the relay to function with factory set defaults which is common operation Optio
17. a serial port on your PC Switch the flash Programming switch The first left of the 6 way dil switches Turn power on Panel will have blank or black lined display the cpu fail buzzer will operate and cpu fail led will be lit Run the Fujitsu flash MCU programming software When the window opens the following data must be selected TARGET MICROCONTROLLER MB90F546 g gs CRYSTAL FREQUENCY 4MHz HEX FILE vectVxx M mhx as issued by haes Select com port in the set environment option Click on the full operation button The software will be upgraded as indicated by a progress bar on the PC screen When complete Turn off power to panel Remove the connector from the program ming adapter and switch the flash switch off on the PCB To subsequently program the loop cards Leave the ribbon to the main display disconnected and plug the adapter into the lower programming socket as normally used for downloading in the Multi loop panel Switch on the flash programming switch on the first loop card Then apply power to the panel Vector Installation amp Commissioning Manual 76 FIRMWARE FLASH UPGRADE CONT D To reprogram a panel To subsequently program the loop cards Leave the ribbon to the main display disconnected and plug the adapter into the lower programming socket as normally used for downloading in the Multi loop panel Switch on the flash programming switch on the first loop card The
18. be in the ON position Press the EVACUATE button once The sounders are energised and the common FIRE LED will flash To turn the Evacuate signal off Press the SILENCE button keypad 6 This will be displayed on the LCD and the flashing FIRE LED will change to steady Press RESET keypad 9 Panel buzzer The internal panel buzzer operates whenever an abnormal event is on the system It operates in the following modes Fire Evacuate Fast pulse Fault Slow pulse Disablement Double pulse Silenced Intermittent bleep Monitoring The control panel internal circuitry is fully supervised in accordance with the requirements of EN54 2 1998 and indicates a failure as a fault condition Loop and sounder circuits are monitored for open circuit and short circuit fault conditions Essential fuses are monitored Vector Installation amp Commissioning Manual 43 SYSTEM OPERATION continued Fault conditions When the control panel detects a fault condition one of the following occurs 1 2 The COMMON FAULT led will flash and the LCD will show the details The PRE ALARM led will flash This indicates that a detector has recorded a higher than normal analogue value which could signal a possible fault with that detector or an impending fire condition The LCD will show the details The SYSTEM FAULT led will flash indicating that the processor has halted This can only be reset by an engineer The ALARM FAULT led illumi
19. necessary If it is required to edit the current configuration e g if a device type is changed added or removed or needs to be allocated to a different zone then it can be achieved via the panel keypad controls as follows In the Menu option select 7 for Engineering options Enter the engineering code and ensure that the Program Mode switch is ON Toggle 2 8 to option 3 Set panel Parameters and then to option 1 Edit loop devices The display should now be showing ADD 001 TYPERIO ZONEOO1 GROUPS By using the 4 6 keys each word group can be addressed ADD Address enter a number 001 through to 126 TYPE Toggle 2 8 to enter the type of device which is expected at this address RIO ION ZMU OPT MAN SDR ZONE Toggle 2 8 to enter 1 80 This is the zone in which the device resides Zones 65 80 are Non Fire zones and have no associated fire LED indication GROUPS Toggle 2 8 to switch group on then 4 6 to move to next group see Group Edit To be allocated on the system a device must be included in one of the zones or groups TEXT A 40 character text message may be input via the keypad for display during fire or fault conditions see Text Edit Vector Installation amp Commissioning Manual 61 CONFIGURATION continued Group edit Group editing consists of assigning the currently selected device to a group by turning any or all of the 32 available groups on or off
20. panel When you download to the panel the current panel parameters will be uploaded and you will be of fered a dialog box to save the file with an alternative name for safety backup purposes It is a good idea to do this in case there is a problem with the new panel configuration Vector Installation amp Commissioning Manual 75 FIRMWARE FLASH UPGRADE Flash programming software The control panel operating software firmware can be updated This may be required if new fea tures or software corrections have been applied The version of software currently loaded in the panel is shown when the option is selected in the set panel options menu in the engineers options The version is shown in square brackets 3 0 for each loop fitted to the panel 3 0 being the first Multi loop version of vector code Included on the CD is a copy of a Fujitsu programming utility which enables the possibility to upgrade the firmware of the control panel Install the software by following the directions of the install program To reprogram a panel NOTE Panel configuration parameters will be corrupted by the reprogramming process Make sure you have downloaded a copy of the panel Config data and saved it to disc as a backup Power down the control panel first to reprogram the main display PCB Remove the ribbon cable connector at the right hand end of the main display circuit PCSLA7 Insert the connector from the download adapter Connect to
21. power supply and battery unit Input terminals are provided in the control panel on the main pcb for the 28V supply charger and battery fault conditions The clock and data lines must be maintained For connections see the Terminal Block 4 diagram In the event of remote supply failure the LCD shows Power Supply Fault CPU reset The CPU Reset pushbutton on the main pcb is provided to manually restart the system following the failure of the software to execute a command The effect is the same as disconnecting and reconnecting power to the panel Checking the system Any fault conditions indicated at this stage should be investigated and cleared before putting the System into operation Check that the system operates in accordance with the operation described in the following pages Clear ARW On initial power up of the control panel an ARW Automatic Reset Warning indication is present This must be cleared by operating the RESET switch on the front panel If ARW warnings occur during normal system operation there may be interference or a software problem Vector Installation amp Commissioning Manual 39 NETWORKING The Vector utilises CAN controller area networking Protocol to provide a fast reliable network of up to 16 control panels Also repeater panels printers and other devices may utilize the same bus over 1 000 devices can be used on same twisted pair A twisted screened pair data type cable is recommended
22. the wiring must be carried out before the control panel and any devices are connected Vector Installation amp Commissioning Manual 14 PANEL CONTROLS Logo Badge CONTROLS EVACUATE ALARM SLENCE RESOUND ALARMS ACTIVE RESET SYSTEM CONTROLS MUTE BUZZER Key switch Activate Controls This key switch is normally in the OFF position with the key withdrawn and stored where it can be accessed by authorised personnel in the event of an alarm or fault In the OFF position with the exception of the mute buzzer button on the keypad and button 5 if a fire is present to allow viewing of device text none of the other functions are operable even though the system is completely operational If the keyswitch is turned to the ON position then the keypad becomes fully functional NOTE It is not possible to withdraw the key in the ON position Key lock This allows authorised engineering personnel access to the inside of the control unit WARNING The power to the alarm unit should be isolated before gaining access The voltages in this unit are high enough to cause severe injury Vector Installation amp Commissioning Manual 15 PANEL INDICATORS TEST MODE DISABLEMENTS ACTIVE ACTIVE SUPPLY p c c CC D lt gt c lt gt FIRE SYSTEM ALARM REMOTE REMOTE ARW MORE PSU ALARM FAULT FAULT ACTIVE DISABLED Fire Indicates the presence of a
23. with the correct configuration program For further details see the section on PC Configuration Set Loop Parameters For details see the section on Panel Configuration Set Panel Parameters 1 Edit Company Name Using the template around the keyboard to be found under the main cover the displayed company name can be altered 2 Edit Panel Name Using the template enter the Panel name 3 Set number of remote panels Using the 2 8 toggle input the number of remote panels 4 Set power supply type can be set to No if a non Vector type PSU is in use This option will inhibit the comms data monitoring the PSD amp PSC inputs may then be used for Charger Fault and Battery Fault inputs switched ve from other PSU types 5 Set common response mode local or system wide Sounders amp outputs can be set to Common Response i e to any fire This option allows the response to be contained locally i e just in one panel or System Wide i e from all panels in the network 6 Keypad Options 1 Silence if local alarm Set to No silence button will silence all fires on network Set to Yes local panel fires only 2 Reset if local alarm Set to No reset button will reset all fires on network Set to Yes local panel fires only 3 Local evacuate No will disable Evacuate button input on the panel 4 Local silence No will disable silence button on the panel Installation amp Commissioni
24. ADDRESS EDIT LOOP 4 6 ZONE 2 8 gt SET LOOP Cs ipe PARAMETERS SELECT LOOP SESS Y SET INPUT LATCHING Y N b Device 6 gt isorATOR ATTRIBUTES DAY NIGHT 00 00 00 00 SET DISCOVERY JE SENSITIVITY MODE 1 5 Br DEVICE POLLING LED XP95 QETIONS LED YES NO LED LOCAL ADD TYPE MI EP RELAY COMMON SET OUTPUT SORA SIL NSIL 5 E gt Device _ s common EVAC NEVAC RESPONSES GROUPS PRECINCT ATTRIBUTES NORMAL SET GROUP GROUPS 1 32 2 STAGE s PARAMETERS s Comsoaz gt s COINCIDENCE TIME DELAY ISOLATOR DELAY RESPONSES ADDRESSES ASSIGNMENTS s 1 126 ZONES DEFAULTS e SIGNALS ON SET ZONES 1 64 SDR2 OFF L ZONES 65 80 25 common NONFIRE GROUPS PULSING SET DEFAULT 8 5 sour s 28 gt PULSING RESPONSE Q SET RESPONSES TO REMOTE PANELS 5 2 8 LOOP SOUNDERS EVACUATE OFF COMMON SOUNDER 1 2nd ALARM FROM PANEL PULSING COMMON SOUNDER 2 1st ALARM PANEL 01 CONTINUOUS LOOP MODULES PRECINCT 15 REMOTE SIGNAL RELAY FAULT
25. ADDRESS VALUE 0 8 to FIRE TEXT Note address only required in stand alone mode GPRS modem if fitted ENABLE SWITCHES SYS SYSTEM WIDE PRINTING ON OFF FLT FAULT PRINTING ON OFF Vector Installation amp Commissioning Manual 29 POWER SUPPLY MODULE PSUXLKEN54 3A Mains Input Fuse Mains Supply Input 1 12V Ancillary 12 volt to the main PCB unit Fused on the Main PCB at 500mA Output on TB3 Main for use on ancillary devices 2 Clock output from power supply PCB to main PCB 3 Data output from power supply PCB to main PCB 4 5 27 volt supply from PSU to power load Separately fused at full output current 6 7 The Voltage output is factory adjusted to 27 6 volts 0 2 volts off load and with the batteries dis connected The power supply is temperature compensated in line with battery manufacturers rec ommendations For details of the battery connections see page 36 Vector Installation amp Commissioning Manual 30 POWER SUPPLY MODULE Testing and maintenance Disconnect the mains supply The Common Fault LED and the PSU LED will show and the internal buzzer will sound The LCD will indicate MAINS FAIL Mute the buzzer by pressing the bottom right hand key on the key pad mute buzzer There will be no indication on the LCD panel Reconnect the mains all Fault LEDs will extinguish NOTE The Battery Charger circuit will disconnect the batteries at 19 volts to protect the
26. DE THRESHOLD TEST COMPLETE 54 MENU AND CONTROL FUNCTIONS Continued Engineering options Cont This option requires the operator to input a security code 195 in order to access all engineering options The program mode switch must be in the ON position on the display board and also on the loop cards as required 1 Vector Auto learn loop devices This facility is provided to enable an engineer to configure the System with the minimum of effort The entire contents of the loop are read in by the control panel and placed in the memory for subsequent editing or downloading to the PC program NOTE Before auto learning takes place it is important that the placement of components and the addressing of them on the loop has been completed Auto learning can only take place once the control panel has been initialised if this option is selected during initialisation a warning message is displayed and auto learn is halted until initialisation is completed An option is provided either to learn the complete loop and overwrite all the previous data or just learn new or removed devices without affecting the rest of the programming As a default all auto learned devices are placed in zone 1 The device zone designations may be altered at the next step by selecting the edit loop devices option Connect to PC This is to allow access to the processor software for initial configuration of the system updates or modifications by a PC equipped
27. LODP M DIL SWITCH APDLLO E P C INTERFACE PROTOCOL TPCSLAZ 55 3 UL D4 ADJUST DISPLAY CONTRAST DISPLAY Adjustments Contrast The display contrast should be adjusted for convenient viewing in the light available Buzzer volume The buzzer volume should be adjusted to suit requirements It should be noted however that on the minimum setting the buzzer is muted Connections Terminal block 1 Keyswitch connections With the keyswitch in the ON position these terminals are shorted to gether Vector Installation amp Commissioning Manual 19 MAIN PCB continued Terminal Block 2 LOOP 1 LOOP OUT LOOP IN INPUTS OUTPUTS 28V O P 28V CAN NET A E S R SC Lo m o Ro LT RR AM F _ B OOOOOOOOOOOOOOOOOOOOO Loop Out Connections for loop one Connections should be as shown Loop In on Page 29 Inputs switched ve A Alert Pulsed sounders latching input E Evacuate Continuous sounders latching input S Silence Remote R Reset Remote P Precinct class change Sounder activation non latching input Outputs Grounded when o p CF R Common Fire CF LT Common Fault RS Reset PA Pre alarm o p RE M Remote o p SC F Common Fire silenced by system silence 28V o p Paralleled o p fused at 1 amp CAN Comms Link NET i Vector Installation amp Commissioning Manual 20 MAIN PCB continued Terminal Block 3 COMMON
28. OTE The Main PCB should be removed before any knockouts Always ensure that if a knockout is removed the hole is filled with a good quality cable gland Any unused knockouts must be securely blanked off AJOJ OOOO Knockouts should be removed with a sharp tap at the rim of the knock out using flat 6mm broad bladed screwdriver Use of excessive force will damage the enclosure around the knockout Vector Installation amp Commissioning Manual 12 Fixing the cabinet If the Main PCB hasn t already been removed then remove the wires from TB4 Page 22 then remove it from back box by unscrewing 4 in number M4 cross headed screws from the circuit board supports Place circuit board and screws in a safe position Secure cabinet to the wall using the four indented holes in the back box Ensure that the box is mounted in a convenient location where it may be easily operated and serviced and where it is away from possible sources of vibration or shock Loop4 Loop3 Loop2 Main PCB PSU Loop 1 P 4 p PS7 12 PS7 12 7Ah 12v SLA 7 12v SLA External cables should be glanded via pre formed knockouts at the top and rear of the box as provided The enclosure should be cleaned of swarf etc prior to re fitting of the printed circuit board Replace the four cross head screws in the Main PCB and reconn
29. as are necessary to ensure that any appropriate information about this product is made available by you to anyone concerned with its use This equipment is designed to be operated from 220 240V AC mains supplies and is of Class construction As such it must be connected to a protective earthing conductor in the fixed wiring of the installation Failure to ensure that all conductive accessible parts of this equipment are adequately bonded to the protective earth will render the equipment unsafe This equipment must only be installed and maintained by a suitably skilled and technically competent person THIS ITEM IS A PIECE OF CLASS 1 EQUIPMENT AND MUST BE EARTHED General The control panel is a micro processor controlled analogue addressable fire alarm control system comprising of one circuit board plus add on modular circuit boards The enclosure consists of back box and hinged removable lid Constructed of 1 2mm 18swg zintec mild steel and powder coated in textured light grey The enclosure is designed to give protection to IP30 level These panels are designed to comply with the requirements of BS EN 54 part 2 1998 but include integral facilities to enable connection to older systems which may not comply with current standards Installation of the panel should only be carried out by qualified personnel The electronic components within the panel can be damaged by static charge Suitable precautions must be taken when handling c
30. be tested simultaneously if required It has a real time clock with back up utilising a smart cap rather than a battery thus eliminating battery life issues The Vector incorporates a very fast auto learn sequence only learning selected parts of the loop and if required can unlearn devices from the system It supports the new Apollo ancillary base sounders and relays local zonal or common operation A device monitoring mode allows activation of the device outputs and control of the loop polling direction Also there is a selectable maintenance scanning threshold The Vector has genuine peer to peer 16 panel networking utilising reliable CAN bus technology with response settings to evacuate 1st alarm 2nd alarm precinct and fault signals with programmable responses for loop sounders panel sounder circuits remote relays and loop modules This manual is intended as a complete guide to the installation commissioning and operation of the Vector fire alarm control panel A separate User s Manual is supplied with the control panel which in addition to explaining the operation of the panel incorporates a log book and details of the user s responsibilities for testing and maintaining the system It is intended that the User s Manual forms part of the documentation package passed to the customer on completion Vector Installation amp Commissioning Manual INTRODUCTION continued It is assumed that users of this manual are competent fir
31. ching and so this selection will not be available if Isolator is set as Yes Vector Installation amp Commissioning Manual 62 CONFIGURATION continued Set Discovery Device Options Apollo Discovery protocol devices have extra features as compared to XP95 devices These may be utilised via this menu The Vector panel supports the following functions 1 Device sensitivity mode settings 2 Selection of Day Night mode sensitivity changing 3 Device LED polling indication refer to Apollo Discovery literature for more details 1 Loop Set Day Night Times Set the times at which the devices can switch from one sensitivity setting to another This is a blanket time setting which applies to all devices simultaneously DAY STARTS 00 00 NIGHT STARTS 00 00 Use the scroll buttons 2 amp 8 to edit the time values as required 2 Set Device Sensitivity Initially the screen shows ALL DEVICES DAY NIGHT This is an opportunity to set all devices to the same setting Edit the values using the scroll buttons Scrolling the devices field will subsequently offer each device address on the loop in turn Only applicable devices are offered for adjustment Scrolling the day amp night fields offers the values 1 to 5 These being the Discovery mode options sensitivity and also XP95 If the device selected is not Discovery the setting should be left as XP95 otherwise a Device Type error may be shown If a Discove
32. clude FP200 Firetuff Firecel MICC Pyro or any other cable complying with BS 6387 categories C W Z Cabling Suitable cables should be brought into the cabinet using the knockouts provided The screen or drain wire of loop circuits should be bonded to earth at one location only and should be continuous throughout the circuit Drain wires should be terminated in the cabinet as near as possible to the entry point Mains wiring The mains supply to the fire alarm panel should be hard wired using suitable three core cable no less than 0 75bmm and more than 2 5mm or a suitable three conductor system that meets the appropriate national wiring regulations The panel should be fed from an isolating switched fused spur supplied directly from the Main Distribution Board fused at 3A This should be secure from unauthorised operation and be marked FIRE ALARM DO NOT SWITCH The mains supply must be exclusive to the fire panel As an alternative to a switched fused spur a double pole isolating device may be used see diagram providing it meets the appropriate national wiring regulations 21 0mm 2 5mm Main Fire Alarm Distribution Control Panel Board Vector Installation amp Commissioning Manual 11 INSTALLATION Continued Planning the cable layout in the panel The detector and sounder circuit cabling is classed as extra low voltage and must be segregated away from mains voltages N
33. dy The buzzer tone changes to an intermittent bleep The LCD continues to show the event information OQ O N NOTE If another device is activated the sounders re energised and the new event information is displayed If there are multiple events on the system the information for each event may be viewed by using the toggle function with keypad buttons 2 8 The MORE LED is illuminated if there are other events The LCD shows the total number of events Resounding the alarm If having silenced the sounders it is necessary to reactivate them e g because there are personnel still within the building press the SILENCE RESOUND ALARMS keypad button again Resetting the system To restore the system to normal operation after a fire alarm it is necessary to reset the control panel by pressing the RESET button Key 9 on keypad All the LEDs illuminate for 3 4 seconds lamptest function following which the panel reverts to its normal mode NOTE 1 It is not possible to reset the system until the alarms have been silenced 2 The system will not reset if the cause of the alarm is still present i e broken glass in call point or smoke heat in the vicinity of a detector Vector Installation amp Commissioning Manual 42 SYSTEM OPERATION continued Evacuate The EVACUATE button keypad 3 may be operated at any time to activate the alarm sounders except in Engineering Menu mode The CONTROLS keyswitch must
34. e 4 and 6 keypad buttons When satisfied with the data obtained press MENU to return to the initial screen Vector Installation amp Commissioning Manual 49 MENU AND CONTROL FUNCTIONS Continued Key to menu 1 View active faults This option provides a method of viewing faults on the system when there are active fire events present 2 View active disablements This option allows the user to identify parts of the system that have been isolated 3 View Clear event logs This option allows the Alarm log and the Event log to be inspected and if required can be cleared 4 Set disablements This option allows remote outputs sounders loop and zones to be disabled and also enabled manually or automatically at a preset time and date An optional managers code can be used to allow access to this function 5 Set clock Allows the time and date to be entered via the keypad 6 Activate test mode Allows zones to be tested individually or all together With or without sounder An optional managers code can be used to allow access to this function T Print options If a printer is installed various reports may be printed Print Alarm Log Print Fault Log Print User Log Print Device Parameters Printouts may be selected for any panel loop on the entire network of panels if desired NOTE Each loop printout must be separately selected 8 Engineering options This option requires a security code to be entered before a
35. e alarm engineers with experience of fire alarm installation and the relevant standards It is recommended that the manual is read and understood before attempting to commission or configure the control panel The system should be thoroughly tested following commissioning and prior to handover to confirm that it operates in accordance with the specification and applicable legislation Vector Installation amp Commissioning Manual PRODUCT OVERVIEW The control panel is a multi loop up to 64 zone analogue addressable unit with integral power supply and space for a standby batteries It has two sounder circuits per loop auxiliary volt free contacts and various remote inputs and outputs The control panel comprises a sheet steel enclosure suitable for wall mounting with a hinged lockable front access door It can be semi recessed if required by using a suitable flushing bezel Cable entry is via the top or rear of the cabinet 20mm knockouts are provided in the top and in the rear Separate keys fit the door lock and the control enable key switch A 2 x 40 character backlit LCD is fitted to display event information function and configuration menus Alarm and status information is provided by LED indicators There is a 12 button keypad which controls the system and allows access to the function and configuration options The control panel operates with the Apollo protocol and supports the XP95 and Discovery detection devices The full range o
36. e it is possible to select conflicting requirements which affect one output Take care with assignments Vector Installation amp Commissioning Manual 68 CONFIGURATION continued Set panel parameters 1 Edit company name A 40 character display message can be set here using the text entry template on the keypad Press menu to exit 2 Edit panel name A 14 character name may be given to the panel for identity purposes Use text entry template to edit Press menu to exit 3 Set number of remote panels In a network system the quantity of other panels must be entered to all panels for integrity monitoring purposes Use scroll buttons to edit the quantity Press menu to exit Set power supply type Is the standard Vector power supply being used or an alternative Unticking this box removes the standard data based monitoring function of the power supply input and converts the PSD and PSC inputs into switched negative battery and charger fault inputs from alternative power supplies Set common response mode Scroll 2 amp 8 to edit 1 Local panel only 2 System wide In a network system this setting determines if common as applied to output device responses is restricted to the local panel or activated from all panels in the network Set keypad options This option specifies in a network if this panel has the ability to silence and or reset alarms on other panels If set to YES then the silence and or reset wil
37. e operable and limited menu functions available Level 3 An access code must be entered to gain access to the configuration and advanced options An additional access code must be entered in order to set the Disablements and to activate the Test Mode Level 4 Configuration software Download facilities are available for off site programming NOTE Amending the system configuration can have serious effects on the operation of the equipment and should only be undertaken by a competent person who has information concerning the devices installed and the specified operational requirements The system should be fully tested after any alterations to the configuration program Level 2 options menu View active faults View active disablements View Clear event Logs Set disablements Set Clock Activate test mode Print options Engineer options Sl v DA tup cr Vector Installation amp Commissioning Manual 47 MENU AND CONTROL FUNCTIONS Continued Menu flow chart YES TOGGLE 2 amp 8 NO EXIT VIEW ACTIVE FAULTS key 5 To view FAULTS VIEW ACTIVE SELECT DISABLEMENTS LOOP 5 view DISABLEMENTS VIEW CLEAR EVENT 28 1 VIEW
38. e required operation is achieved by assigning the devices in the relevant zones and the applicable sounders to a group set to Normal If additional functions are required such as generating a general alarm when a call point or two or more devices are active additional groups are set to the appropriate mode and programmed to provide the required result Vector Installation amp Commissioning Manual 72 PC CONFIGURATION Continued Explanation of program parameters and their use COMPANY NAME Enter the desired company name message up to 40 characters Displayed on all panels in the network No OF PANELS IN THE NETWORK Scroll to the desired value The quantity is stored in all panels to allow checking of network integrity LOOPS Quantity of loops fitted in the panel For info only PANEL NAMES Enter the desired panel identifiers 14 characters If no identifier is used the pan els will revert to displaying panel number as derived from the address setting switches 0 to 15 CURRENT PANEL Select the panel 0 thru 15 These numbers refer to panel address set switches IMPORTANT please be aware of which panel you are defining the parameters of CURRENT LOOP Select the loop 1 thru 4 INSTALLED This indicates whether the device is assigned on the system or not Unassigned devices can be programmed into the panel memory for future on site assignation To assign a device allocate it to a zone and or a group DEVICE TYPE
39. ect the cables in 4 Locate the white jumper lead and connect to the batteries as per the drawing on page 31 Locate the two battery connections from the PSU board and connect to the batteries Carefully place the batteries as indicated in the drawing above Ensuring that the terminals are kept well clear of the PCB support pillars Vector Installation amp Commissioning Manual 13 INSTALLATION Continued Mains connections Do not connect the mains supply to the panel until you fully conversant with the layout and features of the equipment A rating plate is fitted in the bottom right hand corner of the panel describing the nature of the supply permitted The incoming mains supply should be brought into the panel in the bottom right hand corner via the knockout provided A suitable cable gland must be used to secure the outer sheath of the cable used The earth must first be connected to the primary earth stud peg marked with a symbol using the ring provided Sufficient earth lead should be left to allow Live and Neutral connections to be accidentally pulled from terminal block while leaving earth connection intact Secondary earths may be connected to the brass earthing block L N Earth Terminal Mains Input Mains Connection to Vector Field devices Sensors call points and input output devices are supplied with full installation instructions Warning High voltage testing of
40. en ON allows the engineer access to the memory Switch 3 S These four switches are used for network addressing These Switch 6 represent a Binary value with switch 3 as the least significant bit and switch 6 as the most significant bit ie switch 3 1 4 2 5 4 8 Panel addresses range from 0 15 NOTE Each panel on the network must occupy a different panel address Repeater panels and printers use the same address but are recognised as different types and may therefore occupy the same address values Panel addresses may be contiguous i e not in numerical sequence gaps are permitted If a network error is present the following message is shown on the LCD display NETWORK ERROR PANELS FOUND 1L34 From this display it is possible to determine the network status The signifies a missing panel a number shows address present L signifies the address location of the currently viewed panel This information must be compared to the known system setup Vector Installation amp Commissioning Manual 23 MAIN PCB continued TEST EVACUATE LAMPS ALARM SILENCE Keypad RESOUND ALARMS 7 RESET SYSTEM MUTE MENU BUZZER All the numbered keys are digits in their own right but also have the following additional finctions Test button for lamps panel sounder and LCD Scroll up Generate full alarm evacuate Scroll left Select to view option Toggle silence resound alarm Scroll down System r
41. ery 58000 600 Part numbers are correct at time of publication For further devices not listed please contact our technical support department Device address Each device on the system excluding short circuit isolators must have a unique address in the range 1 to 126 Detectors are addressed by means of the XPERT address card which is either supplied blank for on site configuration or pre configured to simply slot into the appropriate device Controllers and Input Output modules are addressed by means of the DIL switch Devices do not have to be addressed in the order in which they are wired An error message will appear on the LCD display to indicate duplicate addresses Vector Installation amp Commissioning Manual 33 COMMISSIONING continued Loop wiring The loop wiring should be tested in accordance with the requirements of BS 5839 Part 1 before connecting devices When the detector bases and other field devices have been connected the loop should be checked for continuity and earth faults using a multimeter only To measure the continuity it is necessary to link the L1 IN and L1 OUT terminals in each isolator NOTE Unlike other XP95 devices isolators are polarity sensitive and must be connected correctly Measure the resistance of the loop and ensure that it does not exceed 50 ohms Check there are no earth faults present When the loop wiring checks have been satisfactorily completed reinstate the isolators and co
42. es described in this manual before attempting to create or edit a configuration program It is assumed that users of the PC Configuration program are experienced fire alarm system engineers with basic computer skills It is recommended that the configuration program is copied from the CD on which it is supplied to the machine s hard disc using the installation routing SETUP EXE Configuration options On new project there are basically two ways of loading the required configuration data into the panel If the initialisation procedures described previously are carried out the program from the panel can be read into the configuration program and edited as required e g group assignments etc by using the Read panel data option This method ensures that the device information is correct i e the device type programmed for each address matches the installed device Preferably a configuration file can be created via the PC program and downloaded to the on board processor If this method is chosen the programmer must ensure that the device details entered into the program match the installation Newly created or edited files can be saved to disk for record purposes and the data can be subsequently retrieved for editing To retrieve a file from disk select Load an existing project file option and follow the on screen prompts The Create a new project option is selected to display the client data and the edit screen where a conf
43. eset Access to menu Bottom right Mute internal buzzer CJ UJ 0 JC Vector Installation amp Commissioning Manual 24 LOOP PCSLA11 Loop Card 2 off programmable conventional sounder circuits f Detection Loop out in Discovery amp XP95 devices Program write protect switch LOOP N LOOP DUT Flash Firmware upgrade switch Sounders fused at 500mA NC NO COMMON FERE C SIGNAL NC C REMOTE PGSL 01 sss 3 LOOP CARD i 00000000 99 5 01000000000 cI 00000 in 2 x clean changeover contacts programmable Max 500mA 50 un fused Installation amp Commissioning Manual Vector 25 LOOP POWER PCB PCSLA10 To CAN Network Download socket for panel 53333 0000 o a 1 o q 8 28v dc supply input 9 9 o Q Connectors for Loop power fuse 2 amps loop cards Up to 3 loops only o Ribbon to 15 66 display PCB Loop No Sequence ss play 5 5 5 2 J 5 m a B N gt o N 9 0 9 E o a o oa uz O Loop volts adjustment factory set Vector Installation amp Commissioning Manual 26 ZONE EXPANSION LEDs PCB PCSLA12 Ribbon cable to PCSLA13 red stripe to top
44. f detectors sounder controllers modules conventional zone monitors etc can be incorporated into the system In addition to the 64 fire zones there are further options which have special functions enabling auxiliary devices to be configured for alternative operation also 32 groups are provided per loop for cause and effects configuration Plus additional 26 panel wide combo groups A Z It is possible to power the panel from a remote power supply if required and input terminals are provided to facilitate the remote supply input and also to monitor the unit for mains and battery failure An integral 5 amp power supply and expansion box to allow space for 17Ah batteries is also available Access to the panel functions and configuration options is at different levels enabling restricted access to certain functions At the user level it is possible to disable parts of the system set the time and date put the system into walktest mode and view the system status Advanced options include configuration maintenance checks and fault finding mode The control panel incorporates an auto learn feature which enables the system devices to be recognised on initial power up Configuration of the system operation can be achieved via the panel controls or by downloading data created in a PC software program An optional Thermal Printer is available which can be either mounted on the panel lid or supplied as a stand alone unit The printer is netwo
45. iguration program is created or edited before being saved and or downloaded Finally the configuration file can be printed as a hard copy record of the system program Vector Installation amp Commissioning Manual 70 PC CONFIGURATION Continued Before creating or editing a configuration file it is important to understand the available options and the program system limitations The following paragraphs describe the basic functions of the program and how they affect the system operation when downloaded to the on board micro processor The programmer should also be in possession of the device information i e address type location etc and understand the specified operation The available device types and their function are described in the configuration section earlier in this manual but are outlined again here for clarification The device types are Sensors i e lonisation ION Optical OPT and Temperature TEM Manual Call Point MAN Sounder module Addressable sounder Beacon SDR Input output module RIO Zone Monitor ZMU NOTE The device type assigned to each address must match the installed device type Assigning devices to zones Devices which are to be indicated zonally by the panel i e sensors call points zone modules and input modules must be assigned to a zone in the range 1 to 64 SDR device types sounders can be assigned to a zone in the range 1 to 64 Sounders assigned to a specific zone opera
46. ing With careful planning and forethought at the installation stage reasonably complex operating modes can be achieved Groups are used to link devices so that for instance the activation of a device in any one of several zones can activate common sounders or turn on a particular output Groups spanning several loops can be created using the Combo A Z option Each group has options in the way it operates i e Normal Coincidence or 2 stage Basically the selection has the following effect Normal The activation of any input device in the group will operate sounders outputs in the group Other sounders i e those not in the group are silent or pulsed depending on the default ring mode Coincidence The activation of two or more devices the group is necessary to operate sounders outputs in the group 2 stage The activation of a single input device in the group causes sounders only in the group to pulse and the activation of a subsequent device causes the sounders to go steady ISOLATOR Devices in this group will be disabled by an active isolator device Devices may be assigned to one or more groups to achieve the required operation Sounders and output modules can be assigned to zones and groups or just groups depending on the required operation Input devices are always assigned to a zone irrespective of any groups they may also be assigned to Example 2 In the example above if each floor comprises say four zones th
47. ion The temperature should be in the range 5 to 35 and the humidity should not exceed 95 ESD precaution Electronic components are vulnerable to damage by Electrostatic Discharges ESD ESD wrist strap suitably grounded should be worn at all times when handling pcbs These wrist straps are designed to prevent the build up of static charges not only within a persons body but on many other materials ESD damage is not always evident immediately faults can manifest themselves at anytime in the future All pcbs should be stored in static shielded bags silvered for safe keeping when not mounted in the control panel Do not use black or pink bags and never allow pcbs to come in contact with bubble wrap or expanded polystyrene packing chips Static shielded bags and disposable wrist straps are available from the manufacturer All system wiring should be installed to meet BS 5839 Pt 1 2002 and BS 7671 Wiring Regulations Other national standards of installation should be used where applicable Vector Installation amp Commissioning Manual 10 INSTALLATION Continued Cable types and limitations To comply with EMC Electro Magnetic Compatibility regulations and to reduce the risk of electrical interference in the system wiring we recommend the use of screened cables throughout the installation Acceptable commonly available screened cables which can be used on both the sounder and detector circuits in
48. ircuit boards Never insert or remove boards or components or connect cables with the mains power on or batteries connected Vector Installation amp Commissioning Manual INSTALLATION Continued Equipment guarantee This equipment is not guaranteed unless the complete system is installed and commissioned in accordance with the laid down national standards by an approved and competent person or organisation This product has been manufactured in conformance with the requirements of all applicable EU Council Directives Mounting the cabinet The installation of fire detection and alarm systems should be carried out in accordance with current IEE wiring regulations and in line with B S 5839 British Standard codes of practice for fire alarm installations The installation should be carried out by suitably qualified and experienced technicians Care should be taken with regards to avoiding the close proximity of high voltage cables or areas likely to induce electrical interference Earth links should be maintained on all system cables and grounded in the control panel Any junction boxes used should be clearly labelled FIRE ALARM Any ancillary devices e g door retaining magnets must be powered from a separate power Source Any coils or solenoids used in the system must be suppressed to avoid damage to the control equipment The site chosen for the location of the panel should be clean and dry and not subject to shock or vibrat
49. l 59 CONFIGURATION continued ZMU Zone monitor unit This device monitors a zone of conventional fire detection devices and requires a 24V DC supply Data value Normal 16 Fault 4 open and short circuit Fire 64 Output bit operation BitO Resets the zone Bit 1 Activates remote test facility Bit2 Increases zone current to allow illumination of device LEDs Input bit operation Mirrors the operation of the output bits to aid in identifying the status of the output bits In engineer s test mode these devices respond as standard devices ZMU Switch monitor unit This device has a monitored input which can be activated by a switch or key switch This input can be designated as an Isolator in the input attributes setting This will isolate any devices in cluded in the group which has been set as Isolation group type Only one isolation group can be specified across the panel These groups which can be Set separately for each loop are automatically linked and are activated by any device specified as an isolator on any loop Vector Installation amp Commissioning Manual 60 CONFIGURATION continued Set loop parameters Edit loop devices The loop configuration options enable device types to be edited devices to be assigned to zones and groups and location text to be programmed The data stored during the initialisation procedure may be accurate in which case further configuration may not be
50. l be cleared Vector Installation amp Commissioning Manual 77 TECHNICAL SPECIFICATION Electrical Specification Mains supply fuse 3 15 Amp F3 15A H250V Replace only with similar type Power supply rating 3 amps total inc battery charge 28V 2V Maximum ripple 250 millivolts Battery type Two 12 volt sealed lead acid 7Ah maximum Battery charge voltage 27 6 vdc nominal Temperature compensated Battery charge current 0 7A max Max current drawn from batteries 3 Amps With mains power source disconnected Dedicated sounder outputs 24V fused at 500mA 2 per loop 1 6 Amp total load over all circuits Fault relay contact rating 30 Vdc 1 Amp maximum for each Maximum ratings not to be exceeded Remote fire relay contact rating 30 Vdc 1 Amp maximum for each Maximum ratings not to be exceeded Terminal capacity 0 5 mm to 2 5 mm solid or stranded wire Number of devices per loop 126 Dependant on type Number of sounders per circuit Dependant on type and current consumption Sounder circuit end of line 4K7 5 14 Watt resistor Supplied in terminals Number of sounder outputs 2 per loop SIL AL FLT RST Switched max resistance 100 Ohms Vector FP200 or equivalent maximum capacitance 1pF maximum inductance 1 millihenry Installation amp Commissioning Manual Cable g
51. l only function if there is an alarm locally If set to NO then the panel can silence or reset any alarm on any panel This is to provide the possibility of providing a silence or reset command from an originating panel only LOCAL EVACUATE SILENCE and RESET buttons When set to NO the buttons operate system wide When set to YES buttons operate locally only Set number of loops Set quantity of loops expected in the panel An incorrect quantity will show a system fault Vector Installation amp Commissioning Manual 69 PC CONFIGURATION The Vector PC Configuration program enables a system to be programmed via a PC to operate in accordance with specific requirements and includes options for zonal sounder operation 2 stage and coincidence functions selective output device operation etc The program also enables device types to be programmed devices to be assigned to zones and device location text to be entered In addition devices can be assigned to groups Configuration files are created via the PC program and downloaded to the on board processor This program will affect the way that the panel functions and could result in a system operation that does not comply with British Standards and or the specification The fact that there are no faults indicated does not necessarily infer compliance Therefore persons using this program should be in possession of the full system information and should be familiar with the procedur
52. lands must be used 78 TECHNICAL SPECIFICATION continued General Specification VECTOR Enclosure Steel IP 30 Dimensions H x W x Dmm 310 x 460 x 85 mm Weight 6 22 Kg 1 loop 6 5Kg 4 loop Temperature 0 to 45 C Cable Entries 20mm knockouts 14 x top 6 x top rear 4 x bottom Number of Fire Zones 16 32 or 64 Number of Loops Up to 4 loops Loop Current 500 mA max per loop Protocols Apollo S90 XP95 Discovery Explorer Open Collector Outputs Auxiliary Supply Output 6 x 30V Dc 100mA max 2x28V DC 1 Amp Vector Installation amp Commissioning Manual 79
53. llowing entry 195 Allows the system to automatically learn new devices To connect to a PC set loop parameter including Discovery options day night mode sensitivity polling LED cause and effect group options relay programming sounder responses and network responses To set panel parameters company name panel name number of groups number of panels To monitor individually the device response change loop poll direction and activate the device outputs To perform a maintenance check set a threshold and list all devices within this threshold To set Management access code to restrict access to the Set Disablements option and the Activate Test Mode facility Vector Installation amp Commissioning Manual 50 MENU AND CONTROL FUNCTIONS Continued 4 Set Disablements MENU SET DISABLEMENTS ENTER MANAGER CODE SET REMOTE TOGGLE CONTACTS 1 REMOTE SIGNAL DISABLEMENTS COMMON FIRE COMMON FAULT TOGGLE EN DIS TOGGLE 5 ISO DE ISO scroll 2 8 TOGGL SET ZONES gt SELECT ZONE 0 EN DIS 5 gt DEVICES Toy A 001 A126 TOGGLE 1 4 DISABLEMENT 5 2 8 scroll EN DIS SET AUTO ENABLE TIMERS DEVICES EDIT TIME amp DATE OUTPUTS SET AUTO ENABLE TIME ON OFF 2 8 TO CONFIRM Vector Installation amp Commissioning Manual 51 MENU AND CONTROL FUNCTIONS Continued Set Disableme
54. m from a full discharge after the mains supply has failed When the mains supply is restored the relay energises and the batteries are reconnected to the charger It is recommended that a discharge test be carried out on a regular basis perhaps by switching the mains supply off and checking that the battery supply will sustain power for the required period Any further detailed tests should be carried out with the approval of the battery manufacturers Vector Installation amp Commissioning Manual 31 COMMISSIONING General When the control panel is installed and the wiring is complete the system can be commissioned The commissioning procedure comprises two main elements i connecting the external wiring circuits and powering the panel ii configuring the system for the required operation Field devices The control panel operates with the Apollo XP95 protocol and accepts a range of Apollo field devices Field devices should be connected to the loop circuit in accordance with the instructions supplied with them ensuring that where necessary a 24V DC supply is available and monitoring resistors are fitted The following chart is a brief overview of the supported devices and relevant type codes NO C po Vector Installation amp Commissioning Manual 32 COMMISSIONING continued Analogue ionisation smoke detector Discovery 58000 500 Analogue optical smoke detector Discov
55. mperature compensation A thermistor lead is provided This should be placed adjacent or taped to one of the power supply batteries for reference BATTERY CONNECTION DETAIL Starting the panel on battery power It is not possible to start the panel without the mains supply e g during commissioning if the supply is not yet available The mains supply must be cycled to override the battery cut off func tion to allow the panel to power up A Mains fault is indicated and the buzzer pulses The buzzer can be silenced by pressing the mute buzzer key on the key pad The fault clears automatically when the supply is restored Vector Installation amp Commissioning Manual 36 COMMISSIONING continued Sounder circuits The two sounder circuits are connected as follows Remove the 4 7 resistor from the sounder circuit terminals on the main PCB and fit to the last device on each circuit Circuits are fused at 1A each NOTE To comply with BS 5839 Part 1 at least 2 circuits should be utilised COMMON FIRE SNDR1 SNDR2 OV 12V 28V 28V NO NC Sounder circuit connection detail Remote relay contacts Four sets of voltfree changeover relay contacts are available for remote signalling or control func tions Common Fire Energises on a fire alarm and de energises on Reset x2 Remote Signal Energises on a fire alarm and de energises on Reset Can be isolated for system testi
56. n 2 Signals NOTE defines default setting Responses can be defined for EVACUATE ON Off or Pulse COMMON FIRE ON Off or Pulse ALERT On Off or PULSE PRECINCT ON Off or Pulse COMMON FAULT On OFF or Pulse SILENCE ON Off Option 3 Zones 1 16 On continuous Off or Pulsing for each zone Option 4 Zones 17 32 Option 5 Zones 33 48 Option 6 Zones 49 64 Option 7 Zones 65 80 non fire indicating zones Option 8 Groups 001 016 On Off or Pulsing for each group Option 9 Groups 017 032 Vector Installation amp Commissioning Manual 67 CONFIGURATION continued Loop Set default sounder response This option informs sounders and loop sounders how to react when not in the active fire group The choice is Pulsing or Off Loop Set responses to remote panels This effectively programs the network interaction between control panels Each loop must be set up according to requirements The signals available from each panel 00 16 are EVACUATE 2ND ALARM 1ST ALARM PRECINCT FAULT The responses can be set for each of the following outputs Loop Sounders en bloc Off Continuous Pulsing Common Sounder 1 Off Continuous Pulsing Common Sounder 2 Off Continuous Pulsing Loop Modules RIO en bloc Off Continuous Pulsing Remote Signal Relay Off Continuous Pulsing The settings should be checked for every loop on all panels in a network PLEASE NOTE With many options availabl
57. n alarm LED Bit 1 Activates the device self test Bit 2 Switches on output for remote LED Input bit operation Mirrors the operation of the output bits to aid in identifying the status of the output bits Vector Installation amp Commissioning Manual 58 CONFIGURATION continued SDR Sounder control module loop powered sounder The sounder module provides a single monitored sounder output and requires a 24V DC supply and a 10K end of line resistor Up to 30 loop powered sounders can be installed and do not require an additional power supply Loop sounders are single point devices Data values Normal 16 Fault 4 open and short circuit or power supply fault if monitored Output bit operation Bit 0 Activates sounder output in continuous mode Bit 1 Activates sounder output in pulse mode Bit 2 Not used Input bit operation Mirrors the operation of the output bits to aid in identifying the status of the output bits Operation SDR devices must be programmed to the specific zone area where they are to be fitted This al lows the software to activate sounders in the zone of fire first in the event of an alarm Thus provid ing full compliance to B S 5839 requirements SDR device responses must be set up in the Set Output Device Responses option The response can be zonal common default or groups Zonal will be continuous for the zone of fire and pulsing or off for other zones depending on default sounder mode Commo
58. n apply power to the panel Run the Fujitsu flash MCU programming software When the window opens the following data must be selected TARGET MICROCONTROLLER MB90F546 g gs CRYSTAL FREQUENCY 4MHz HEX FILE vectVxx S mhx as issued by haes Run the same sequence for each loop in turn powering down between and selecting the flash switch on for the required loop only before invoking the program Panel will be programmed with latest software version when finished close down program and dis connect leads etc Restore the panel to normal operation by switching off the flashprog switch Make sure to reconnect finally the ribbon cable between the PCSLA7 and the loop cards below Then it is necessary to restore factory defaults in the eeprom memory to prevent erroneous data caused by any parameter changes that may have occurred This is done by holding down button 2 on the panel keypad during a restart Make sure that all 4 loops if fitted are initialized Then re download the control panel from the back up file you made before starting NOTE occasionally the download software may be updated and if new parameters are needed an import facility will be provided to enable conversion of existing panel parameters to any new require ments Please check with supplier if in doubt During initialization you will be asked to confirm the number of loops and the qty of remote panels will be reset to zero and any power supply and device setting wil
59. n is for any fire Groups will depend on group programming applied Additionally the SDR response to silence or evacuate may be set SlL ence default or N on SlL ence as required Response to precinct input may also be set Default setting is ON ALM devices respond to Evacuate Silence and Precinct in the same manner as the panel sounder circuits RIO Input output modules Single input output devices Data values Normal 16 NOTE No other data is returned from this module type Output bit operation Bit O Activates relay output 1 Input bit operation X Bit O Logic level inputs RIO devices should be programmed to the specific zone area where they are fitted RIO devices must be set up in the Set Output Device option The same response settings as sounders are available The default settings are common operation non silence and non evacuate RIO devices can be used in Non Fire zones 65 80 to provide indications of other system activities If a module input is activated and the device is in zones 65 to 80 There is no fire response i e no sounders operated but the SYSTEM FAULT LED is illuminated and the buzzer sounds until the input is cleared The display will show Device Fault RIO devices can be set to be non latching This is useful for interfacing with remote equipment This applies to the input side only RIO devices can be set as isolator input Vector Installation amp Commissioning Manua
60. nates to indicate a fault on the alarm circuit The PSU led when lit indicates a power supply failure The LCD will show the details For each of the above or combination of them the internal buzzer pulses slow pulse The LCD will display the event information e g NO RESPONSE ZONE 001 01 OF 01 PE MAN ADD 003 18 20 23 03 The fault message is normally self explanatory for instance in the above example the message is NO RESPONSE indicating that the panel cannot communicate with the device A003 which could indicate that it had been removed The fault condition can be accepted by pressing the SILENCE key 6 To view the text description of the device press keypad 5 The flashing LEDs go steady and the buzzer tone changes to an intermittent bleep The panel automatically returns to normal operation when the fault condition clears however certain faults e g SYSTEM FAULT require the CPU to be reset Vector Installation amp Commissioning Manual 44 SYSTEM OPERATION continued Fault messages The following events are detected and reported Message Fault Condition No response Device removed Type error Device fault wrong device type installed Loop open circuit Loop circuit open Loop short circuit Loop circuit short Power supply fault PSU failed Sounder short open
61. ng Common Fault De energises on any fault condition and stays de energised until the fault is cleared ie failsafe NOTE Fault relay is normally energised when the system is healthy Vector Installation amp Commissioning Manual 37 COMMISSIONING continued Remote outputs The remote output terminals provide a switched OV supply in conjunction with system events and can be used for control and or signalling purposes The load applied to any remote output should not exceed 100mA The following outputs are available and are switched on when the relevant event occurs CFR Common fire switched off when Reset is pressed CFLT Common fault switched off when fault clears RS Reset 8 second pulse when Reset is pressed PA Pre alarm switched off when condition clears REM Remote signal switched off when Reset is pressed SCF Common fire switched off when Silence is pressed Remote inputs The remote inputs provide control functions from remote switches and are energised by applying OV 28v via a switch or relay contact Remote input connection detail L L PRECINCT SOUNDERS LOOP OUT LOOP IN INPUTS OUTPUTS 28V O P 0V O P A E S R P CF CF RE SC LT RS M F OOOOOOOOOO Vector Installation amp Commissioning Manual 38 COMMISSIONING continued Remote power supply If required the supply to the control panel can be derived from a remote
62. ng Manual 55 MENU AND CONTROL FUNCTIONS Continued Engineering options Cont Keypad options 5 Local reset No will disable reset button on the panel 7 Set number of loops This must be set to correct quantity of loops in the panel A fault is annunciated if this is not correct 8 View loop Firmware versions Select to view software version No for each loop 5 Monitor device response Once the device is selected then the direction of polling can be altered by the 4 6 toggle Then the 3 bit outputs can be checked 6 This is a device maintenance check where the maintenance threshold can be set perhaps for servicing purposes then anything outside of this limit is displayed on the LCD 7 Set management access code Allows the setting of an access code to restrict access to Disablements and the Test mode functions If set to 000 it is ignored 8 View data corruption count This facility gives some indication of the integrity of the loop wiring Initially select the loop to be scanned E g select loop number 1 A display is given thus VIEW LOOP 1 CORRUPTION COUNT 000 CORRUPTED RESPONSES PER SCAN It is necessary to wait for a short time period about 10 seconds for the measurement to be updated The number is the quantity of data errors and corrupted returns given from the loop A high number may indicate that the wiring should be checked for earth faults or potential interference from high voltage sources It i
63. nnect the circuit as indicated in the figure below LOOP OUT LOOP IN Pg OO LOOP CIRCUIT CONNECTION DETAIL Vector Installation amp Commissioning Manual 34 COMMISSIONING continued Powering the panel It is recommended that following the connection of the loop circuit the panel is powered up and tested before proceeding with the connection of the sounders remote outputs and auxiliaries When the panel is first powered up the panel must be initialised or a configuration program downloaded The loop is scanned and the devices are identified Each device is displayed showing its address and type and the zone as unassigned allowing the operator to allocate each device to the required zone see Initialisation Mains connection Ensure that the incoming mains supply is fully isolated Remove the fuse from the mains terminal block and connect the incoming live neutral and earth wires to the L N and Primary Earthing Stud Switch on the supply do not replace the fuse at this stage Vector Installation amp Commissioning Manual 35 COMMISSIONING continued Connecting the battery Prepare to connect the battery as indicated in the figure below do not connect the battery at this stage NOTE There is a 30 second default delay on the indication of a battery fault when the battery is disconnected Similarly when the battery is reconnected the fault continues to be indicated for 30 seconds The power supply has te
64. ns e bete ee m eas et bee ae ne A 14 Field DEVICES ENT u Sopa 14 Panel Controls nos suyunu u edet oda ee 15 Pan l IndICalors oet eR 16 ECD DISDIaV u ya an Eie etu ka sapaska id 18 Main PR CEN EH PRESTON 19 Terminal Block Wis steko accorto oodd eb tb dede 19 Terminal BlOCK 2 5 entra ee he et eo uer edet ehem time De tA wa ysi woa ee Ras 20 BIOCK tute Dci oe biete tag ay e 21 Terminal Block oec m ee te Q 22 ERR TUNI 23 AREE TR D E a DL UL UT 24 Loop ai 0 zr 25 Loop Power trente kayak Resin intem 26 Zone Expansion LEDs PCB n rr 27 Zone LED Breakout ens 28 Printer Control Board mener 29 Power Supply Module n eae es oe rU eher e 30 Commissiohilid asc natn ea bob dde a on cta met edt 32 Field D VI68 uu us ERI iine unb 32 Device Address ay aa deh deeds 33 LOOP P baa aie 34 Powering the Panel y Enero RE REP repaid 35
65. nts 1 Remote Contacts can be disabled or enabled for test purposes This applies to the signal relay the common fire common fault or the loop module relays 2 Sounders can be disabled if required and enabled again 3 The Loop can be isolated on this option 4 Any selected zone can be disabled or enabled 5 Any of up to 126 devices on the loop can be disabled or enabled 6 Timers can be set for devices or outputs to be re enabled automatically at a specified time and date with this option 7 All disablements on whatever device or line can be cleared simultaneously NOTE From software version 4 1 onwards a group of devices can be disabled by activating a special input loop device specified as an isolator in the input attributes of the device This isolator will disable all devices contained within a group which has been specified as an isolation group Only one isolation group can exist on any loop Isolator groups are linked automatically No COMBO can be used Vector Installation amp Commissioning Manual 52 MENU AND CONTROL FUNCTIONS Continued Engineering Options TOGGLE 2 8 CONTINUED ON NEXT PAGE PROGRAM ENTER ENGINEERING MODE SWITCH lt SECURITY CODE lt OPTIONS MENU ON 195 OVERWRITE 5 AUTO LEARN gt 5 5 LOOP SELECT Q EDIT NEW DEVICES LOOP E EJ 2 s UPDATE NEW REMOVED CONNECT TO DEVICES ONLY PC
66. ollo range of ancillary base devices sounder and relay bases function by utilising the remote led output of a detector or beacon to operate them thus saving addresses used by the loop They are not addressed directly by the system and as such cannot be auto learnt The default use of the remote led output of a detector is to illuminate the local remote led In order to utilize these devices it is necessary to allocate them on to the hosting device A unit selected as a sounder will respond to evacuate and silence as required If set as a relay it will remain activated until the panel is reset The devices have 7 possible modes of operation LOCAL Operated by the host device in alarm only ZONAL Activated by any alarm in the same zone COMMON Activated by any alarm NONE This applies when no ancillary base device is fitted N SIL Silenceable non silenceable N EVAC Evacuateable non evacuateable PRECINCT Precinct non precinct Set output device responses Output devices type SDR and RIO need to be instructed how to respond in the case of alarm There are 4 options common default local zonal or groups Common will activate with any alarm local responds only if the detector attached is in alarm zonal responds to alarms in the assigned zone groups will respond to cause and effect group programming only Also whether a device is silenced or responds to evacuate is set here SDR devices are set to respond to SIL silence EVAC evac
67. option menus It has two lines of text each with 40 characters and is backlit when there is an active event on the system or the menu options are accessed In the normal operating mode the backlight is off and the top line displays a default text message or user defined text The second line displays the current time and date e g VECTOR MULTI LOOP SYSTEM NORMAL 9 36 15 03 04 When an event occurs the backlight is activated and the LCD shows the event details e g FIRE PANEL 01 ZONE 01 CARETAKERS OFFICE The display shows the event type i e Fire the zone that the activated device is in i e zone 1 the device location text and the number of events i e 1 Pressing button 5 reveals the address number of the activated device i e 002 and the device type i e manual call point NOTE Fault conditions on the system are suppressed when Fire events are present The SYSTEM FAULT LED is illuminated and faults can be viewed if required the View Active Faults option when button 5 is pressed The bottom line displays a text message describing the device location In the engineering mode menu options are displayed as follows SELECT MENU OPTION 5 SET CLOCK The Keypad is used to navigate through the menu options and select functions as described in the operating manual Vector Installation amp Commissioning Manual 18 TB 1 TB 2 TB 3 ADJUST INTERNAL BUZZER VOLUME SINGLE
68. osting device A unit selected as a sounder will respond to evacuate and silence as required if set as a relay it will remain activated until the panel is reset The devices have 3 possible modes of operation local operated by the host de vice in alarm only Zonal activated by any alarm in the same zone Common activated by any alarm Miscellaneous options SILENCE ONLY IN ALARM Check box only if you require that the panel cannot silence fire events that happen elsewhere on the network RESET ONLY IN ALARM Check box only if you require that the panel cannot reset fire events that happen elsewhere on the network LOCAL SILENCE Tick to restrict silence to local panel LOCAL RESET Tick to restrict silence to local panel LOCAL EVACUATE Tick to restrict evacuate to local panel DEFAULT RING MODE specify action for non active sounders Pulsing or off VECTOR SUPPLY Check box if intelligent vector type psu is installed default If unchecked psd and psc inputs become switched neg power supply fault inputs psd charger fault psc battery fault PROGRAMMABLE RELAY RESPONSES Set the responses of the selected panel s on board relay circuits to local alarms The yes setting activates the circuit for the given alarm Note The alarms zone is set as default to yes to provide common sounder ringing Switch this to no to allow any other selection to function When no is selected the default ring mode will apply
69. rk based and can be set for either local panel or complete System based printing Up to 16 printers may be incorporated into any Vector network system providing complete flexibility of printing options Vector Installation amp Commissioning Manual INSTALLATION Safety Suppliers of articles for use at work are required under section 6 of the Health and Safety at Work Act 1974 to ensure as reasonably as is practical that the article will be safe and without risk to health when properly used An article is not regarded as properly used if it is used without regard to any relevant information or advice relating to its use made available by the supplier It is assumed that the system of which this control panel is a part has been designed by a competent fire alarm system designer in accordance with BS 5839 Part 1 1988 and with regard to BS EN 54 parts 2 and 4 in the case of control equipment and power supplies Design drawings should be provided to clearly show the position of any field devices and ancillary equipment This product should be installed commissioned and maintained by or under the supervision of competent persons according to good engineering practice and i IEE regulations for the electrical equipment in buildings ii Codes of Practice iii Statutory requirements iv Any instructions specifically advised by the manufacturer xx According to the provisions of the Act you are therefore requested to take such steps
70. ry mode is set the panel will check for a Discovery type device If Discovery devices are fitted and the mode is left as XP95 the devices will be set to 3 standard mode and no error will be flagged Sensitivity setting is an optional requirement Summary of Discovery modes mode DEVICE TYPE lonisation 0 45 Y 0 7 Y 5 secs 30 secs 5 secs 30 secs 5 secs Heat TEM A1R A2 A2S CR CS 90 4 2 M 61 2 1 M 1 1 M 2 8 M A1 20 secs optical 20 secs 20 secs heat CO ION 30 PPM 45 PPM 45 PPM 60 PPM 75 PPM 60 secs 30 secs 60 secs 30 secs 30 secs Optical OPT 1 4 M 1 4 M 2 1 M 2 1 M 2 8 M 5 secs 30 secs 5 secs 30 secs 5 secs Warning Sensitivity modes may change the response time to fire and should only be used un der the supervision of trained fire detection specialists Refer to detector manufacturer for further advice and information Vector Installation amp Commissioning Manual 63 CONFIGURATION continued Set Discovery Device Options cont d 3 Set Polling Indicator Discovery devices have an option to allow the indicating LED to flash whilst the device is polled by the system This is often used as a confidence check that the system is operating Setting this option to YES will cause all Discovery devices on the loop to flash whilst polling Vector Installation amp Commissioning Manual 64 CONFIGURATION continued Loop Set ancillary base units The Ap
71. s natural for any system to have a few data errors The panel will report bad responses as a fault if there is excessive noise Vector Installation amp Commissioning Manual 56 CONFIGURATION Following the initialisation procedure the control panel has basic functionality i e if a detector or call point is activated the alarm is annunciated and the sounder circuits are energised For the system to function in any other way it must be configured for the required operation This configuration is also known as cause and effect i e the action in the event of a particular occurrence is specified The cause and effect capability of the panel is quite powerful and provides sufficient flexibility to enable the system to be configured for the required operation in most cases Where there are special requirements which cannot be met by the standard features it is possible for the software to be customised to satisfy a particular project The supplier should be consulted in such circumstances Of the configuration options available full editing may be carried out via the panel control switches Configuration editing including assigning devices to groups etc can also be carried out via the PC software program which is used to download a program directly to the panel To provide a better understanding of how the system may be configured the various device types and their operation is explained in more detail in the following paragraphs Zones
72. te according to output response settings All other sounders are either silent or pulsed depending on the default ringing mode which is selected in the edit screen Input output modules RIO can be assigned to a zone in the range 1 to 64 or to non fire indicating zones 65 80 I O modules assigned to a specific zone turn their output on according to output response settings When a device is assigned to zones 65 80 there is no fire response and no sounders are activated a text message is displayed and the SYSTEM FAULT LED is illuminated Vector Installation amp Commissioning Manual 71 PC CONFIGURATION Continued Example 1 In a multi storey building the sounders are required to operate continuously on the floor where the activation occurs and intermittently elsewhere Assuming each floor comprises one zone only the sounder modules addressable sounders on the floor are assigned to that zone the output response to zonal and the default ringing mode is set to Pulsed When a device is activated the associated sounders operate continuously and all others are pulsed If however each floor comprises more than one zone the above method is not suitable as only the sounders associated with the activated zone will sound continuously In this case it is necessary to assign devices to a Group or Groups Assigning devices to groups The program is fully flexible as there are thirty two groups available in each loop for programm
73. that before attempting to enter the options menu the features are fully understood and the operator is familiar with the controls used to navigate the menus and select options Function buttons Four of the keypad buttons are used as function buttons when the options menu is invoked Most of the panel functions including configuration are controlled by these buttons which have the following functions MENU The Menu button is used to initially invoke the options menu Press once to enter the Menu and press again to Exit 2 and 8 The 2 and 8 buttons are used to toggle select the Menu options Once having selected an option then to escape the Menu button should be pushed again 5 The 5 button on the keypad is pressed when the option selected needs to be viewed 4 and 6 The 4 and 6 buttons are used to position the cursor along a full display line in order to adjust various options available Vector Installation amp Commissioning Manual 46 MENU AND CONTROL FUNCTIONS Continued Access levels To prevent unauthorised operation of the panel controls and functions access is restricted in accordance with the requirements of EN54 2 The following access levels apply Level 1 Full restrictions The internal buzzer MUTE only is available at this level Note Button 5 View Text and Scroll buttons 2 amp 8 are available if an alarm is present Level 2 CONTROL keyswitch ON The control switches ar
74. uate and PRECINCT ON by default RIO devices are set as NSIL non silence NEVAC non evacuate by default These responses must be checked for all output devices if operation other than common alarms is required Loop Set group parameters Each loop has 32 cause and effect groups Loop 1 groups 1 32 Loop 2 groups 33 64 Loop 3 groups 65 96 Loop 4 groups 97 128 Each group is restricted to the loop it is on but can be linked to groups on other loops using the combo Up to 26 combos are available A group can only have combo associated to it Each group can have a delay timer up to 300 seconds these will function separately from the combo so it is possible to have 2 groups sharing a combo with different delays for each group Select group option Use scroll buttons to select the desired group No Group attributes 1 Activation Normal 1 device 2 stage 1st 2nd alarms Coincidence 1 device 2 Group combo Local group is self contained A Z Tag which links groups Be aware combos are panel wide Vector Installation amp Commissioning Manual 65 CONFIGURATION continued Group attributes 3 Delay Time 0 300 seconds 4 Pre Delay Response Off Continuous Pulsing Evacuate NOTE If delay is set to 0 only output response will be available in menu 5A Post Delay Response Off Continuous Pulsing Evacuate 5B Output Response Off Continuous Pulsing Evacuate if no delay set 6 Halt on Silence Yes
75. unders operate in accordance with the programmed configuration This is normally a general evacuation continuous alarm throughout the building but may be an alert intermittent signal or alarm in certain parts of the building only 2 The common FIRE LED flashes on the front panel 3 The relevant zone LED flashes 1 64 4 The LCD illuminates and shows the event information 5 The internal buzzer pulses rapidly 6 The remote contacts operate and signal the fire brigade if this has been configured in the system 7 Remote control functions are initiated in accordance with the program e g doors closed ventilation shutdown etc 8 Event details are printed assuming a printer is fitted The actions to be taken in the event of a fire alarm should be fully documented and implemented immediately upon hearing the alarm After the event note the event details i e the activated zone and the device details if not already determined Vector Installation amp Commissioning Manual 41 SYSTEM OPERATION continued Silencing the alarm Before the alarm sounders can be silenced the CONTROLS keyswitch must be set to the ON position by inserting the key and turning it clockwise a quarter of a turn With the controls enabled press the SILENCE RESOUND ALARMS keypad button once The alarm sounders on the system are silenced The LCD will illuminate to indicate the current status The flashing common fire and zone LEDs change to stea
76. utilises the latest surface mount technology with a flash programmable 16 bit Micro controller for easier software updates It operates with the Apollo XP95 and Discovery protocols and supports the Apollo range of field devices Two internal sounder circuits are provided per loop and additional sounder circuits can be connected to loop wired modules The control panel is programmable via the keypad controls or via a PC allowing the configuration to be created off site and downloaded In addition to the requirements of EN54 2 the control panel has the following facilities Test Condition to allow the automatic resetting of zones in alarm for testing purposes EN54 2 Section 10 option with requirements Fire Alarm Devices to enable an audible warning to be sounded throughout a premises upon the detection of a fire condition or the operation of a manual call point 54 2 Section 7 8 option with requirements In addition to the requirements of EN54 2 all control panels have voltage free relay contacts for fire and local fire which operate upon fire condition These are to be used for local control and signalling The Vector has individually isolatable panel contacts via the menu with an Auto enablement feature and the option to remove all disablements The menu is comprehensive yet easy to use allowing electrical isolation of the loop via the keyboard The menu includes an enhanced test mode with or without sounders allowing all zones to
77. work diagnostics As each panel operates on a peer to peer basis i e independently All panels monitor each other Each panel sends a regular ident pulse which is monitored by all others If an error is present it will be annunciated on all panels A fault message is given if a panel is lost or if a panel is seen on the network which is not expected Also the integrity of the message packets received is constantly monitored If data corruption is occurring perhaps due to cabling faults this will be annunciated as a network message error along with the number relating to the panel affected Note due to display restrictions panels 10 to 15 are indicated by letters A210 11 C212 D 13 E 14 F 15 This indication may also be given if there are two identical addresses on the network To clear the fault check all address settings or cable integrity Vector Installation amp Commissioning Manual 40 SYSTEM OPERATION Fire alarm During normal operation the only active indication on the control panel is the green Supply Healthy LED The LCD shows the system normal message and the time date and company name if utilised The backlight is off The control keyswitch should be in the OFF position and the key should be removed and stored in a secure place readily available when required If a manual call point is activated or an automatic detector senses smoke or heat a fire alarm signal is generated and the following occurs 1 The alarm so