Product Specification and User`s Manual PDF
Contents
1. AA ee 1 80 50 Allowable current o 0 10 20 30 40 90 60 Ambient temperature C a lt PRODUCTEXPLANATION 4 2 Wiring a Single phase 25A 70A 112 3 4 5 6 7 8 9 10 11112118 14 15 16 17 PCB Power 220V TIC 4 20mA Sensor C KI C R S Main Power Check the voltage of provided power is same as the voltage of the machine and the rated current is not exceeding proper capacity of load current Then provide the power l It is o ed that you do not use a machine at over 70 of the rated current 12 4 PRODUCTEXPLANATION 4 2 Wiring b Single phase More than 90A A Type 11 2 3 4 5 6 7 8 9 10 11 12 13 1411516 17 4 20mA PCB Power Main Power 220V S TIC NIG Sensor Check the voltage of provided power is same asthe voltage of the machine and the rated current is not exceeding proper capacity of load current Then provide the power It is jecommended that you do not use a machine at over 70 of the rated current N 13 a lt PRODUCTEXPLANATION 4 2 Wiring c Single Phase More than 90A Type B 11 2 3 4 5 6 7 8 9 10 11 12119 1415 16 17 PCB Power 220V 4 20mA ERE Sensor R S Main Power Check the voltage of provided power is same as the voltage of the machine and the rated current is MO exceeding proper capacity of load current Then provide the powe It is recommended hat you do not use a machine at over 7096 of the rated
2. amp Is the limit over current flows the unit notify the abnormal status and does not allow the output OC lamp Red lamp on It is recommended to adjust O C value should be 1 1 times than load ampere 26 ST Green 5 1 Notices During Operation 1 Please watch out power supply terminals otherwise electric shock will cause 2 Do not touch any of components in the unit because of high temperature Especially watch out not to put your finger orany stick in the cooling fan which tumstoo fast and cause you any ham 3 Do not operate ortum on the unit without load which results in over voltage and damages transformer in unit 4 Use only shield cable when wiring control terminal block 5 Must not allow more than DC 5V or DC 20MA asinput signal 6 Installation Circumstances D Mount this unit in the place where it ventilates well 2 Do not operate the machine where there is a risk of infla mma bility explosive ne ss corrosion or humidity 7 Ground type 1 grounding or special type 3 grounding in the exterior box of the machine to prevent electric shock 8 Checkthat voltage of provided powerissame asthe voltage of the machine and the rated curment is not exceeding proper capacity of load cument Then provide the power It is recommended that you do not use a machine at over 70 of the rated current condition 9 FUSE D To prevent fire and to protect the machine use a fast acting fuse which is designated by our c
3. curren 14 a lt PRODUCTEXPLANATION 4 2 Wiring e 3 Phase all models WW ANAMAAAAINI Heater Check the voltage of provided power is same as the voltage of the machine and the rated current is not exceeding proper capacity of load current Then provide the power It is recommence that you do not use a machine at over 70 of the rated current 15 a PRODUCTEXPLANATION 4 3 Control Terminal Arrangement 1 2 3 4 5 6 7 8 9 oh 1 1213 14 15f1617 c I Pun Stop a Lo O h 950V PCB M Auto OFF Reset ATX RTX Al E S larm NS gt FG Hanua CH di Only Single Phase Note Please referto the control input wiring diagram which is attached to the inside of the front panel or outside of case to connect correct wires 1 The main power must be cut off to connect wires 2 To prevent malfunctions by noise use the twist shield cable for control input wiring FIELD GROUND and SIGNAL GROUND must be operated A 3 Install wiring of the control input part far from the other power lines Shield cable usage example Danger Warning Notice Danger Waming This symbol is displayed when there is risk of death or severe injuries Notice This symbol is displayed when there isa risk of property damage KE PRODUCTEXPLANATION 4 4 System Block Diagram a Single Phase 220V 380V 440V 50Hz 60Hz RUN STOP AUTO MANUAL o TT O EXT POTENTIO METER 10K Processor
4. if is a feed back type of product display message varies from minimum to maximum current voltage or power against full input signal according to adjusting output volume Example When it is SPP2 040 1 220V 40A CURRENT FEEDBACK display message shows you from OA to 40A according to adjusting output volume 24 PRODUCTEXPLANATION 4 6 Display Message 3 On adjusting SOFT volume voo 1 SOFT volume cai come QNG NO The display shows SOFT START time by second But not shown in three phase model SOFT Adjust YES Adjust SOFT volume Note SOFT volume adjusting is only possible while the 27 DIP switch is ON see page 7 Actual Cument C YO Use SOFT Volume to adjust soft Start time 0 30sec This setting time applies to soft up down also On the adjusting soft volume display FND shows you 0 30 sec Then you can select required time by turning volume switch left and right Note SOFT volume adjusting is only possible while the 2nd DIP switch is ON see page 7 25 PRODUCTEXPLANATION 4 6 Display Message On adjusting O C over current volume O C volume 245 NO O C Adjust YES MM Adjust LI LI c volume 245 On selecting OC Over Current Volume FND shows O max maximum amperage will be shown For example OC volume is selected as 40 amp over current more than 52 amp 40amp X 1 3V normally 1 3 times of maximum
5. precise inspections When a problem occursin the PCB UNIT please contact ourcompany s A S Department Danger Warning Notice Danger Waming This symbol is displayed when there is risk of death or se no us injury Notice When the product is used incomectly it could cause property damage 29 Pio aaa A The main power must be tumed off to operate periodic inspection There isa risk of defect electric shock or fire Penodic Inspection Please operate the periodic inspection the following items once every 6 months to maintain the best condition and functions of the machine 1 Cleaning Dust may come from the outside When there is dust such as iron powder insulation is worse and causes infenonty of operation So please clean the attached materials Remove the dust on the components using a soft brush or air 2 Components fa stening condition Check the screw fastening condition of each connection part The screw could be loosened with time Fastened screw could cause damage by heat so it could cause control insta bility or defects So periodic inspection is necessary to keep the normal condition 3 Wiring condition check Must check abnormality or modification of insulating covering of input and output wires A of the machine When there isabnoma lity please change the part 4 Other check items Must check the fastening and connection condition of connector and terminalsin the machine Da
6. x SUM is used for only Protocol is 1 Table 6 General Command Host Client e Client Host Response message construction Pm B Bytes 2 f e 0 0 0 2 f 0 0 Ed me KE um x M E VM t SUM is used for only Protocol is 1 77 BO ser on 50 os or om Kama e o Soo Ceo E Refer to Code Table Table 7 General Command Client gt Host e Explanation Of DATA Sphere DATA sphere is composed of total 6Bytes Each ASCII code becomes actual DATA For the Alarm status please refer to Alarm Code Table in 8Page PARANA 4 2 2 Alarm Status Signal Ver 2 00 LINE FUSE FAULT DATA REMARK Status Table 8 Alarm Status Signal Fault 0 Normal 1 Abnormal Example FUSE Abnormal Over Temp O T Over Current O C Transmitting DATA 15 Binary digit of 15is 1111 Head Office 15 Naeri Jinryang Gyungsan City Gyungbook Korea VER 4 00 060606CB TEL 82 53 857 4478 A S 82 53 857 4471 FAX 82 53 857 4474 Suwon Office 302 Sungshin Technopark 509 7 Maetan 3Dong Yeongtong Gu Suwon City Kuoungki Do Korea TEL 82 31 211 4478 A ENT FAX 82 31 212 4478 PARA Home Page www paratec co kr E mail paratec paratec co kr
7. DIGITAL POWET REGULATOR DER Series USER S MANUAL ABOUT PRODUCTS amp SERVICES We appreciate your purchasing our Digital Power Regulator To avoid any trouble and for your sa fety please read this manual carefully before usage Preface Charged Services Please read the manual in advance asa service charge will be imposed forany service request on a product without defects A defect because a userdoesn t follow the instructions in the manual A defect caused by not following rating cument capacity or using When a defect abnormal voltage or power A defect caused by using components that ourcompany doesn t designate occurs due to mishandling or improper repair on EOD P A defect caused by repair work of non specialists Altemation of fuse and consumption goods e A defect caused by natural calamities Term of guarantee of this product is 1 year from the purchase date Product installation environments Install this product vertically to activate ventilation and do not use it in oraround flammable explosive comosive and humid environments Symbol explanation This symbol marks the parts where there is danger Notice forelectric shock of electric shock Power must be tumed off for maintenance orrepair of the product Notice This symbol indicates risk of death or senous injury Waming When the product is used incorrectly it could Danger cause property damage To prevent malfunc
8. RODUCTEXPLANATION 4 6 Display Message a Main Message on FND Window TRANSFORMER COUPLED LOAD RESISTIVE LOAD r1 El OVER CURRENT gE e OVER TEMPERATURE HEAT FAILURE OR ALARM MESSAGE FOR ABNORMAL STATUS OF POWER SYSTEM FUSE FAILURE PARTIAL LOAD FAILURE OPTION MAXIMUM 6 LOADS FOR SINGLE PHASE n FF SCR FAILURE MAIN POWER CUT OFF 21 NM PRODUCTEXPLANATION b Display to Each Optional Function Standard Type Display Current Unit A Current Feedback Type Display Current Unit A 1 Voltage Feedback Type LI Display Voltage Unit V Power Feedback Type Display Power Unit Kw RMS current value is displayed for Phase Angle control and Average current value is displayed for Zero Crossing control N 22 a lt PRODUCTEXPLANATION 4 6 Display Message c Display Example D While initial starting Example Single Phase 220V 400A display Message Type of product a P D Single Phase 220V HDD eem Type of Loads m FF Tansformer MODE Actual Cunent d y 5 Display actual cument A 23 PRODUCTEXPLANATION 4 6 Display Message 2 On adjusting OUTPUT power volume OUTPUT Adjust Display of output Ex 50 of max rated current Adjust OUTPUT volume cai con PHS OUTPUT Volume is used when selecting maximum output FND shows figures 0 100 set up the figure you require by turning volume left and right When
9. amp ON i 5 Seana SE 1234 K Please read carefully this user s manual before operation A And consult an expert when you have any question related to this unit Wrong usage or operation may cause bad effect on the system and worker 2 CONTROL BOARD EXPLANATION 2 2 CONTROL Volume Operation related terms Il RESET RESTART On Alarming status OUT PUT select maximum output PARA SOFT Time for Soft Start 8 Soft UP DOWN OC Over Current prevention function Current Value D Use RESET Button when you re start the unit on the status of wa ming operation or alarm operation OUTPUT Volume isused when selecting maximum output FND shows figures 0 100 set up the figure you require by tuming volume left and right After setting up the figure you want just push RESET BUTION to complete selection 3 Use SOFT Volume to adjust soft Start time 0 30sec This setting time appliesto soft up down also On the adjusting soft volume display FND shows you 0 30 sec Then you can select required time by tuming volume switch left and right After setting up the figure you want just push RESET BUTION to complete selection 4 On selecting OC Over Current Volume FND shows O max maximum amperage will be shown Forexample OC volume is selected as40 amp overcurrent more than 52 amp 40amp X 1 3 normally 1 3 times of maximum amp is the limit over current flows the unit notify the abnormal status and doesno
10. ds with LF OXOA SUM Protocol is standard protocol added by check sum as an error check code a Standard Protocol Frame 0x02 0 127 Refer to each Command Table 2 Standard Protocol Frame b Standard Protocol SUM Frame ka pee 127 Refer to each Command Check Sum Lu pe Table 3 Standard Protocol SUM Frame Check Sum indicates 1Byte as sixteenmo digit 2Digits 2Bytes among ASCII code added by 1 byte from the character next to Frame to the just before of Error Code PARA NI Ver 2 00 4 1 COMMUNICATION COMMAND General Commands to notify the error in machinery are as below 4 1 1 General Command NF Requesting Alarm Status of Machinery Host gt Client No No Transmitting data data Host gt Host Client INE LL _ s Amperage and Host gt EJ Alarm Status of Machinery AN Requesting only Current Amperage only Current Amperage Host gt Host gt Client E s Voltage and Host a Alarm Status of Machinery VN Requesting only Current Voltage 09090900 only Current Voltage Host gt Host gt Client AAA command signal Mio gt Host Table 4 General Command 4 1 2 Error Response era 2 6 ppp Table 5 Error Response SUM is used for only Protocol is 1 PARAAN Ver 2 00 4 2 Command Signal 4 2 1 General Command D Reguiring current ampere value and alarm status e Host Client ves 2 me NM B nas
11. essage 5 Operation 5 b 27 5 1 Notices during operation 5 2 Wiring Control Terminal block ARE PARA Mantena aa ee E 29 T inspection 2 59 T 30 EM IDENTIFICATION 1 1 Identification Code e CODE S SINGE PHASE P PHASE ANGLE P P TYPE T THREE PHASE Z ZERO CROSSING X X TYPE 5 RATED CURRENT 6 FEEDBACK OPTION 25A 800A I CURRENT FEEDBACK OVER 800A PLEASE V VOLTAGE FEEDBACK CONSULT US W POWER FEEDBACK CUSTOMER S REQUIREMENT Note Identification code is attached to the outer side of the unit Please make sure this unit is the same as what you ordered by referring to identification code PARA ENT Republic of Korea 82 53 857 4478 Product Power Regulator seria No 36007 PARASME Power Rating 110A 220V 60Hz C Input Firing Mode Zero Crossing Made In Korea Fuse SIBA 20 282 04 125A Any otherfuse invalidates warranty H page www paratec cokr mail paratec paratec co kr A S O53 857 447O Must preserve notices during handling the machine to ensure safety EN CONTROL BOARD EXPLANATION a Normal operation Normal output and Normal status PILOT Green Lamp Blinking PARA 5 2 a SS CK KSDUSH n DIGITAL gt ITYRISTOI I OC b Warning Operation Normal output but attention is needed Lamps are blinking c Alarm Operation Abnormal status and output is off Operation related terms Lamps turn on FILET Operating status lamp PICOT Red L
12. lt 9 o Control Q O ALARM O Q O O 220V POWER O O o PHASE Control Signal 4 20 MA Temperature Controller Heater 4 PRODUCTEXPLANATION 4 4 System Block Diagram b Three Phase 220V 380V 440V 50Hz 60Hz RUN STOP AUTO MANUAL O o EXT POTENTIO METER 10K Processor To Control Q O Current ALARM O DO 220V POWER Control Signal 4 20 MA Temperature Controller Heater Le Y n E a lt PRODUCTEXPLANATION 4 5 Dimension a Sngle Phase W D D VEL b N et Front View Side View Front View Side View Models for less than 70 A Models for more than 90 A W H W1 H1 Not Type A ei Bolt 7 25 40 55 70 108 195 150 185 Terminal Block SOL T30 BUS BAR fe pe ais mo oc ao ape eo fam on am 160 2007 250 520 BUS BAR er es a oo as lel ae a wn oe 400 500 BUS BAR a so o Ju Dimensions of the upper products could be changed without pre notification for improving functions The sizes for A and B please refer to page 12 and 13 A 19 a lt PRODUCTEXPLANATION 4 5 Dimension b Three Phase Model Mounting H WI Terminal 25 40 55 70 5 AO 55 70 eek QU 110 130 160 BUS BAR Dimensions of the upper products could be changed without pre notification for improving functions 20 a lt P
13. must not be mounted on a surface of flammable material 4 Live parts may need to be accessible a statement requiring the fitting of a residual current opened circuit breaker 6 Disassembly or remodeling of the machine 1 Never change components voluntarily with the exception of changes of fuse or thyristor 2 Our company can not guarantee operation of the machine when the volume of the machine or component is altered voluntarily When a problem occurs please contact our company s A S Department 7 Check and repair 1 Before checking the machine cut off the power and beware of electric shock 2 Check fastening condition of bolts and nuts of terminal parts 3 When bolts of terminal are loose it could generate heat so wiring can be damaged or fire can occur Check this condition periodically 8 This manual could be revised without notification for improvements of functions of the machine 9 Responsibilities and guarantee 1 Must preserve notices for handling maintenance and repair of the machine 2 Our company is not responsible for damage which occurs due to not following these instructions Must preserve notices during handling the machine to ensure safety NOTIC ES FOR SAFETY 10 Cleaning 1 Do not spray water directly at the product A fire and electric shock will be occurred 2 Please unplug the product 3 Do not use chemical liquid Discoloration will be occurred 4 Appropriate decontamination is carried ou
14. ndition of communication are as below COM P Select Protocol Standard Protocol Standard Protocol Check sum 19200bps BAUD Baud Rates 1 9600bps 0 2400bps NONE No Parity PTRY Parity Bit EVEN Even Parity Odd parity x O O x x O x x O gt lt SBIT Stop Bit 1 bit 2bits DLEN Data Length bits 8bits ADDR 0 127 MW Address RPTM Response Time EE Time RTPM 10msec Table 1 Communication Parameter O x PARAAN Ver 2 00 3 2 Selection Guide 3 2 1 Baud Rates Selection Speed of Comm N Fr la f n 1 ng ums amp P E P l i E la Aika TM T mp aa D Baud Rate DIP S W e a PUN Ls pH KANA TE did DN N IA PEROSA Address DIP S W Fig 3 DIP Switch Selection Select 1 Baud Rate DIP Switch in Fig 3 as below o a o EN Fig 4 Selecting Baud Rate 3 2 2 Selection ADD for DPR Select 2 ADD DIP Switch in Fig 3 as below Example Selecting address 1 Refer to Fig 5 Fig 5 Address Selection EX Selected as ADD 1 PARA NI Ver 2 00 3 2 3 RS 485 COMMUNICATION PORT 11213 415 6 7 8 9 1011 1213 14 15 16 17 eo Pun Stop A 4 uto OFF Reset ATK RTX 4 20mA Manual ON 3 RS 485 Connection Port Fig 6 RS 485 Communication Port 4 Standard Protocol Standard Protocol Communication is accomplished by ASCII and known by fixed command There are two protocols selected by parameter Standard Protocol is 0 and starts with STX 0x02 and en
15. nger Warning Notice Danger Waming This symbol is displayed when there is risk of death or se no us injury Notice When the product is used incorrectly it could cause property damage 30 DIGITAL power USER S MANUAL REGULATOR COMMUNICATION MANUAL DPR Series Appendix PARANA Ver 2 00 Contents 1 Summary of communication 2 Wiring Diagram 3 Communication parameter 3 1 Contents of parameter 3 2 Selecting Guide 3 2 1 Baud Rates Selection 3 2 2 Selecting ADD for DPR 3 2 3 RS485 Communication Port 4 Standard Protocol 4 1 Communication Command 4 1 1 General Command 4 1 2 Error Repose 4 2 Command Signal 4 2 1 General Command 4 2 2 Alarm Status Signal PARAS Ver 2 00 1 Summary of Communication Fig 1 Connection to DPR DPR Series is operated by Half Duplex method controlled by RS485 And maximum 31 units of DPR series can be connected to supervisory system for communication through adopting prepared Protocol 2 Wiring Diagram Wiring between supervisory system and power controller is as below Multi access is available to maximum 31 units Connect resistance 200 2 1 4W at the end of the each terminal Master DPR DPR Resistance 12000 1 4W Resistance 2000 1 4W __ SHIELD type 3 grounding type 3 grounding Fig 2 Wiring Diagram PARAAN Ver 2 00 3 Communication Parameter 3 1 Contents of Parameter Parameters to select co
16. of current rating Voltage feedback D to 0854955 Power feedback 0 to 98 95 of the voltage rating X 0 to 100 of current rating Non Feedback 0 to 98 of the voltage rating of the voltage rating e Zero Crossing Control 0 to 100 of voltage rating In case of Three Phase Applicable Load e Resistive load or inductive load transformer primary side control For Zero Crossing Control only resistive load can be used Allowable Ambient Temperature e Performance guarantee range 0 to 50 C e Operating guarantee range COR Cooling Method e Current rating of 70A or less Natural convection e Current rating of 90A 25A or more Fan Cooling as standard Insulation Resistance Over DC 500V 200M9 between power terminal and case Mounting Method Vertical Method b Characteristics B Input output characteristics SAA a EE pr SA p Pt Tt IR Current Feedback Power Feedback Output 9 10 11 12 13 14 15 16 17 18 19 20 Input signal mA B Gradient setting characteristics Set value 20 100 00 E l 400 1907 aa 800 1040 1200 1360 1520 1600 1840 2000 Input signal mA B Ambient temperature and allowable current 110 100 Current rating E grimiirbrrigefatre rin rre ran re rro rre ra ero rre rae ra nre ere rie anre nre rre rente ris rere rn erm ere rer eret F 1 H i i 1 1 T a i 1 i I PA
17. ompany Referto the product label 2 Must tum off the main powerto exchange the fuse 10 Disassembly or remodeling of the machine D Never change components voluntarily with the exception of changes of fuse or thyristor 2 Ourcompany can not guarantee operation of the machine when the volume of the machine orcomponent is altered voluntarily When a problem occurs please contact ourcompany s A S Department 11 Check and repair 1 Before checking the machine cut off the powerand beware of electric shock 2 Check fastening condition of bolts and nuts of terminal parts 3 When bolts of terminal are loose it could generate heat so wiring can be damaged orfire can occur Checkthis condition periodically 27 KEN OPERATION 1 4 20mA Auto Mode 2 4 20mA Outer Power Volume x Dip SW3 ON for Outer Power Volume C NU COM 3 Relay Switch ON OFF 4 Manual Only 0 QU Manual ON Reset 5 Reset Alarm Wiring 28 EN s FUSE Exc hange A fuse designated by ourcompany must be used Check that the fuse is fastened correctly after it is changed 1 The main power must be tumed off to change the fuse SCR Exchange An SRC designated by ourcompany must be used 1 The main power must be tumed off to change the SCR element Check that the SCR is fastened correctly after changing it PCB UNIT The main power must be tumed off to check PCB UNIT PCB UNIT is manufactured through our company s
18. t allow the output OC lamp Red lamp on Time Soft Start Soft UP DOWN And consult an expert when you have any question related to this unit f Please read carefully this users manual before operation Wrong usage or operation may cause bad effect on the system and worker CONTROL MODE SELECTION 3 1 Phase Angle Control Front Control Part A Function to SW1 ON OFF ON KSDOSH ED 29 34 5 KSDOSH A Note Please make sure SW2 is on when it is transformer coupled load CONTROL MODE SELECTION 3 2 Zero Crossing Control A mode ETE 73 1 4 Lj 4 5 ON KSDOSH 2 3 4 5 D 16 mode KSD05H Thi 3 4 5 L q E 32 mode KSD05H Thi 3 4 5 L q poo OF 2 or 3 OFF 4 Option O O1 ON 2 oro 3 OF 4 Option _ 1 or 2 ON 3 or 4 option 01 ON lo 3 or 4 Option CONTROLMODE SELECTION F 64 mode IT 10 4 PRODUCTEXPLANATION 4 1 Technical Data a General Specifications Voltage Rating 200 220 240VAC or 380 400 440VAC Frequency 50 60Hz Auto selectable Current Rating 25A 40A 55A 70A 90A 110A 130A 160A 200A 250A 320A 400A 500A 570A 800A 1100A all based on an ambient temperature of 50 C Input Signal 4 to 20mADC Output Range e Phase Angle Control Current feedback l to DV to SV 0 to 100
19. t if hazardous material is split onto or into the equipment 5 Cleaning and decontamination necessary as a safeguard when laboratory heating equipment and any accessories are maintained required and transferred 11 Protection against electric shock 1 The hazardous live parts are supplied from a circuit protected by a residual current operated circuit breaker which interrupts the supply at a differential current of 30mA or less or the installation such a circuit breaker 2 Conveyor belts muffles etc which are conductive are connected to the protective conductor terminal 3 Please express clearly the necessary method to be carried for protection and method for protection on where operator or other personnel can be contacted such as rechargeable part or terminal connected to conductive circuit ex Isolation tools isolation cable 12 A S Request A S Department TEL 053 857 4470 4471 FAX 053 857 4474 mail paratec paratec co kr Must preserve notices during handling the machine to ensure safety PAGE l Identifying Label _ _ __r 5 1 1 Coding 2 Control Board Explanation rr C C 7 6 3 Control Mode Selection p 8 4 Product Explanation v q 11 4 1 Technical Data 4 2 Wiring 4 3 Control Terminal Arrangement 4 4 System Block Diagram 4 5 Dimensions 4 6 Display M
20. tion you must operate grounding To prevent electric shock or noise from the outside Grounding NOTIC ES FOR SAFETY 1 Install 1 Before installing this machine install main power circuit breaker NFB and Magnetic switch on the outside of the main body for safety 2 If after transport or storage in humid conditions equipment could fail to meet all the safety requirement the install instruction shall 4 hour of operation to dry out the equipment and restore it to normal condition 2 Ground type 1 grounding or special type 3 grounding in the exterior box of the machine to prevent electric shock 3 Check that voltage of provided power is same as the voltage of the machine and the rated current is not exceeding proper capacity of load current Then provide the power It is recommended that you do not use a machine at over 70 of the rated current condition 4 Fuse 1 To prevent fire and to protect the machine use a fast acting fuse which is designated by our company Refer to the product label 2 Must turn off the main power to exchange the fuse 3 The fuse used must be of the specified rating current voltage type in order to prevent a fire hazard o Environments 1 Adjust ventilation and temperature so that temperature inside the control panel is not over 45 C 2 Do not operate the machine where there is a risk of inflammability explosiveness corrosion or humidity RH 7096 below at 40 C 3 The equipment