Home
        USER`S MANUAL - Mitsubishi Heavy Industries
         Contents
1.                        Heating                      Radiator  _  Floor  _  Fan convector          Cooling       Other L_  Floor L  Fan convector     Not available       External heat source  Solar  _  Gas  _  Oil  _  Wood  _  Pellets  _  Electricity                                  Accessories  Tank heater  _  MH RG 10  _  ESV22 28  _  VCC22 28  __  ACK22 28    Settings                                                                      Fill in the difference from default settings        Menu Number Menu Type Description Setting                      Date Signed                   This appliance is not intended for use by persons  including children  with reduced physical  sensory or mental capabilities  or lack of  experience and knowledge  unless they have been given supervision or instruction concerning use of the appliance by a person  responsible for their safety    Children should be supervised to ensure that they do not play with the appliance     Information about the installation       Product information    Hydrolution is a complete modern heat pump system that  offers effective technical energy saving and reduced carbon  dioxide emissions  Heat production is safe and economical  with integrated hot water heater  immersion heater  circulation  pump and climate system in the indoor unit     The heat is retrieved from the outdoor air through outdoor unit   where the refrigerant circulated in a closed piping system transfers  the heat from the heat source  outdoor air  
2.             Silent mode time          7 7  N  Return               Return             8 6  N  Return    8 5 2  U      Max time for HW             8 5 3  U      Return          23    Control    Main menus    Menu 1 0  N  Hot water temp     The current hot water temperature in the vessel is shown here     Figure on left shows the one in the middle and right one in  brackets shows the one on the bottom     Menu 2 0  N  Supply temp     The current supply temperature for the heating system is shown  here with the calculated supply temperature in brackets     Menu 3 0  N  Supply temp  2    The current supply temperature for heating system 2 is shown  here with the calculated supply temperature in brackets     Menu 4 0  N  Outdoor temp   The current outdoor air temperature is displayed here   Menu 5 0  N  Heat pump    The outdoor operation data are shown in the sub menus to this  menu     The following text appears in the display           Text Means   Off Shown when there is no compressor demand  and none of the following apply    On Shown during normal operation with the com   pressor    Initiates Shown while the compressor is running        Com  problem  Shown in the event of temporary communica   tion problems                    Defrosting Shown during defrost    Oil return Shown when the compressor is rotated to be  lubricated    Protection Shown when the compressor is in some form  of protection or during a start delay of 30 minu   tes    Shutdown Shown in the event of an alar
3.     6 0  N  Room temperature       6 1  U  Room compensation       6 2  U  Heating system       6 3  N  Room temp  setpoint       6 4  U  Room temp avg  1min       6 5  U  Room integrator time                6 6  N  Return          5 16  N  Return       5 14 2  U  Inverter temp Tho IP          5 14 3  U  Return          22     Requires accessory and activation in menu 9 3 6     7 0  N  Clock  7 1  N  Date       7 2  N  Time       7 3 0  U  Temp set back    7 3 1  U      Set back time    8 0  N  Other adjustments    8 1 0  N  Display settings    N    Control      Menu type          7 4 0  U  Extra hot water    U      Set back temp             Heating system         Return         XHW Monday    8 2 0  N  Op  mode settings      Language         Display contrast         Light intensity                 8 1 3  N            Return             7 5 0  U  Vacation set back      XHW Tuesday         XHW Wednesday         XHW Thursday         XHW Friday         XHW Saturday         XHW Sunday    8 3 0  U  Current limiter            Stop temp  heating         Start temp  cooling         Hysteresis            Return         Fuse size            Return         Vacation begins       7 6 0  N  Silent mode      Vacation ends         Heating system         Offset heating curve         HW off         Return    8 5 0  U  Period settings      Max  electric power         Current phase 1            Current phase 2         Current phase 3         Transform  ratio EBV         Return         Period time
4.    Wait one day between settings so as to stabilise the       temperatures     Comfort setting heating    Setting with diagrams    The diagram shows the relation between the outdoor temperature  in the area and the target supply water temperature of the heating  system  This is set under menu 2 1 2     Heating curve     Limitations   which are not in the diagrams  can be set in the control system   s  permitted min and max temperatures   See menu 2 1 4 and 2 3 as  well as 3 3 and 3 4     Heating curve offset  2    HEATING CURVE                                                 151413 12 11 10   g 8     T 7  o    n l        2 6  E   5    Te ae j  a    a            43     E    5 Ze a      A A A A ua  10 0   10  20  30  40   C   5     Outdoor temperature   OFFSET HEAT CURVE    Heating curve offset 0  HEATING CURVE                                              70 151413 12 11 10 9   2   2   g   o   2        2    gt    2   2        77     5   10 0   10   20   30  40   C   5     Outdoor temperature   OFFSET HEAT CURVE    Heating curve offset  2  HEATING CURVE      C                                           2  70 151413 12 11 10 9  o  2  3  2  fi  g  o  Q  E     fo  2  2  a  2  3   7    5  10 0   10   20   30  40   C   5      Outdoor temperature    OFFSET HEAT CURVE    11    Comfort setting heating    Readjusting the default settings   If the room temperature does not reach the target  readjustment  may be necessary    Cold weather conditions    m When the room temperature is too low 
5.    is found  cut off the power  and stop the operation    Then consult your dealer     If you use it as it stands  it may lead to  failure  electric shock or fire        One of the causes of poor cooling Q  or poor heating may be refrigerant  leakage  Please consult your dealer     If the repair requires additional refrigerant   determine the service with the service staff   The refrigerant of air conditioner is not toxic   Normally the refrigerant does not leak  But if  it leaks and contacts fire such as fan heater   space heater or cooking heater  it may  produce toxic chemicals     Do not insert fingers or sticks even if S  air blower does not operate     It may suddenly operate and cause injuries        Safety precautions    A CAUTION    Do not use for particular purpose such S  as the storage of food  animals and  plants  precision apparatus and arts etc     Storage goods may degrade        Do not operate the button with wet Qy  hand  S    It may cause electric shock     G       When a burning appliance is used    together with the unit  ventilate frequently     If ventilation is not sufficient  it may cause  oxygen deficiency accident        Do not place a burning appliance where  the airflow from the unit is directly     blown in case fan coil is used     It may cause the imperfect combustion of the  equipment        Make sure that the unit installation  foundation is not damaged due to long   term use    If it is left to stand  the unit may fall down causing  injury  
6.   Also check the water heater safety valve regularly  The  appearance and location of the safety valve differs between  different installations  Contact your installer for information     Pressure gauge in indoor unit    The working range of the heating system is normally 0 5     1 5  bar when the system is closed  Check this on the pressure  gauge  BPS      Emptying the hot water heater    The water heater is of the coil type and is drained using the  siphon principle  This can be done either via the drain valve on  the incoming cold water pipe or by inserting a hose into the  cold water connection     Emptying the vessel    Contact your installer if the vessel in indoor unit needs  emptying     Maintenance of outdoor unit    Outdoor unit is equipped with control and monitoring  equipment  however some exterior maintenance is still  necessary     Make regular checks throughout the year that the inlet grille is  not clogged by leaves  snow or anything else  During the cold  months of the year  check to make sure that there isn   t a build up  of ice or frost under outdoor unit  Strong wind combined with  heavy snowfall can block the intake and exhaust air grilles   Make sure that there is no snow on the grilles    Also check that the condensation water drain under outdoor unit  is not blocked    If necessary the outer casing can be cleaned using a damp  cloth  Care must be exercised so that the heat pump is not  scratched when cleaning  Avoid spraying water into the grilles  
7.   Display settings   Settings concerning language and menu type are set in the sub   menus to this menu    Menu 8 1 1  N  Menu type   The menu type is chosen here     N  Normal  covers the normal user   s needs     U  Extended  shows all menus except the service menus      S  Service  shows all menus  returns to normal menu level  30 minutes after the last button was pressed        NOTE    Incorrect settings in the service menus can damage the    property and or heat pump        Setting range  N  U  S    Menu 8 1 2  N  Language    Language settings are made here     Menu 8 1 3  U  Display contrast  The display   s contrast is set here     Setting range  0     31    Menu 8 1 4  U  Light intensity    The light intensity in idle mode is set here  Idle mode starts 30  minutes after the last button was pushed     Setting range  0 off  1 low  2 average     Menu 8 1 5  N  Return  Return to menu 8 1 0     Menu 8 2 0  N  Op  mode settings   Settings regarding auto mode can be made in the sub menus to  this menu    Menu 8 2 1  N  Allow add  heat   You can choose at which operating mode the electric heater is  to be permitted to produce hot water and heat when needed   Setting range  Off  Heating  Heating   Cooling  Cooling    Default values  Heating    Menu 8 2 2  N  Add  heat mode    Selected if electric heater only is to be used to produce hot  water and heat     Setting range  Off  On    32    Menu 8 2 3  U  Stop temp  heating  The average outdoor air temperature at which the heat p
8.   Do not lean on the unit     It may overturn or fall if it is placed on  unstable surface and if may cause injury           Do not wash the unit with water  nor  place a vase with water on the unit     It may cause electric shock or ignition              Do not install the unit where the airflow S  is directly blown to animals and plants     They may suffer from adverse effect        Before cleaning  make sure to stop Q  operation and cut off the power     The fan inside rotates at high speeds        Make sure to use proper size of fuse  S    Using steel wire or copper wire may  lead to failure or fire        Do not store a flammable spray etc  near S  the unit  nor blow directly to the unit     It may lead to fire        Before maintenance  make sure to  gt   stop operation and cut off the power     The fan inside rotates at high speeds        Safety precautions       When the unit isn   t used for a long  e  term  cut off the power     The accumulation of dirt may lead to heat  generation or fire  But  before resuming  the operation  turn on the unit for six hours  beforehand to save harmless     Do not place any object around the Q  outdoor unit  nor allow fallen leaves to   pile up    Fallen leaves may induce insects and worms  in them  and they may lead to failure  ignition  or smoking by touching electric components        Do not place any other electric appliances S  or household goods below or around the  air conditioner     Dripping from the unit may lead to failure
9.   Key lock  Language setting       Comfort setting heating  General       Operating status       Changing the room temperature manually  Default Heating curve setting          Readjusting the default settings  Heating system 2       Vacation set back       Silent mode       Comfort setting with room sensor       Comfort setting cooling  General       Cooling operated from the outdoor sensor in operating  mode AutoC       Comfort setting hot water  Available volume       Prioritizing       Extra Hot Water       Maintenance  Checking the safety valves in indoor unit  Pressure gauge in indoor unit       Emptying the hot water heater          Emptying the vessel  Maintenance of outdoor unit       Saving tips       Dealing with comfort disruption       Operating mode    Add  heat only          Emergency mode       Alarm indications  What happens in the event of an alarm   Recommended actions       Resetting alarms       NNN    O O O O Ooo    13    13    14  14  15    19  19  19    Table of Contents    Control  Display       Menu types       Menu management       Menu tree       Main menus       1 0  N  Hot water temp        2 0  N  Supply temp        3 0  N  Supply temp  2       4 0  N  Outdoor temp        5 0  N  Heat pump       6 0  N  Room temperature       7 0  N  Clock       8 0  N  Other adjustments       Checklist  Checks before commissioning    Safety precautions    HN SAFETY PRECAUTIONS    m Please read these    SAFETY PRECAUTIONS     before starting to use this product a
10.   U  Hot gas Tho D   This menu shows the hotgas temperature in the heat pump   Menu 5 9  U  Liquid line temp    This menu shows the liquid line temperature in the heat pump   Menu 5 10  U  Condensor out   max    Shows the current and max  allowed temperature after the  condenser     Menu 5 11  U  HP    The current high pressure and corresponding temperature  during heating are shown here  During cooling  the actual low  pressure and corresponding temperature are shown     Menu 5 12  U  LP LPT   The current low pressure is shown here   Menu 5 13  U  Fan speed   No function     Menu 5 14 0  U  CompFreq act set    The actual and set point value for the compressor frequency  are shown here     Menu 5 14 1  U  OU current CT   The present phase current to outdoor unit is shown here   Menu 5 14 2  U  Inverter temp Tho IP   The current inverter temperature is shown here    Menu 5 14 3  U  Return   Return to menu 5 14 0     29    Control    Menu 5 16  N  Return    Return to menu 5 0     30    6 0  N  Room temperature        Requires accessory and activation in menu 9 3 6   Menu 6 1  U  Room compensation    A factor is selected here that determines how much the  calculated supply temperature is affected by the difference  between the room temperature and the set room temperature  A  higher value gives a greater change     Setting range  0    10 0    Menu 6 2  U  Heating system    You select here whether the room sensor is valid for heating  system    menu 2 0  and or heating system 2  
11.   U  Max supply temp        2 2 2  N  Cooling curve       2 2 3 0  U  Own cooling curve    2 2 3 1  U  Supply temp at  20       2 2 4  U  Min supply cooling       2 2 3 2  U  Supply temp at  40          2 2 3 3  U  Return          2 2 5  U  Circ pump speed cool          2 2 6  N  Return          2 4  U  External adjustment       2 5  U  Supply Return temp        2 6  U  Degree minutes       2 7  N  Return          21    Control    3 0  N  Supply temp  2  3 1  N  Offset heating Tot 2       3 2  N  Heating curve 2       3 3  U  Min supply temp  2       3 4  U  Max supply temp  2       3 5  U  External adjust  2       3 6 0  U  Own heating curve 2    3 6 1  U  Supply temp at  20    4 0  N  Outdoor temp   4 1  N  Outdoor avg  temp        4 2  U  Outdoor filter time       4 3  U  Outdoor avg  1min           4 4  N  Return          3 7  U  Supply Return temp 2    3 6 2  U  Supply temp at  20          3 6 4  U  Supply t  at buckl                3 6 3  U  Buckling temperature          3 6 5  U  Return             3 8  N  Return       5 0  N  Heat pump  5 1  N  Number of starts       5 2  N  Run time compressor       5 3  U  Time to start       5 4  U  Outdoor temp  Tho A       5 5  U  Heat Ex Tho R1       5 6  U  Heat Ex Tho R2       U  Suction temp  Tho S       5 8  U  Hot gas Tho D             5 9  U  Liquid line temp        5 10  U  Condensor out   max       5 11  U  HP                 5 12  U  LPLPT  5 13  U  Fan speed       5 14 0  U  CompFreq act set    5 14 1  U  OU current CT
12.   the fan  may rotate suddenly causing injuries     Do not strain the remote control S  cord     A part of core wire may be cut off causing  electric leakage              Do not use water heater etc  near the  indoor unit or remote control     If a Vapor generating appliance is used near  them  it may lead to water drop causing  electric leakage or short circuit     Do not use the unit where powder or S  fiber is floating     Fine powder or fiber passing through the air  filter may stagnate inside the unit and lead  to electric leak or short circuit     Do not place objects under the unit S  which must avoid being exposed to  water     Over 80 percent humidity or the clogging of  drain pipe may damage them through dew  dropping              u PRECAUTIONS FOR RELOCATION OR REPAIRING  A CAUTION    Never perform any modification  Q  Contact your dealer for repairing     Improper repairing may lead to water  leakage  electric shock or fire  Normally  the refrigerant does not leak  But if it leaks  and contacts fire such as fan heater  space  heater or cooking heater  it may produce  toxic chemicals  When repairing refrigerant  leakage  determine the service with the  service staff that the repair has been finished  without fault        If it is required to relocation and reinstall    the unit  consult your dealer or a specialist     Improper installation of air conditioning unit  may cause water leakage  electric shock  and or fire        Before repairing or checking indoor a  un
13.  2    The present supply and return temperatures for heating system  2 are shown here  Return temperature is shown in brackets     Menu 3 8  N  Return    Return to menu 3 0     4 0  N  Outdoor temp     Menu 4 1  N  Outdoor avg  temp     This menu shows the average outdoor temperature according  to the set value in menu 4 2  factory setting  24h      Menu 4 2  U  Outdoor filter time    Here you select during how long the average temperature in  menu 4 1 is calculated     Setting range  1 min  10 min  1h  2h  4h  6h  12h  24h    Menu 4 3  U  Outdoor avg  1min   Shows the average outdoor temperature over the last minute   Menu 4 4  N  Return    Return to menu 4 0     Control    5 0  N  Heat pump    Menu 5 1  N  Number of starts   The accumulated number of starts with the compressor in  outdoor unit is shown here    Menu 5 2  N  Run time compressor    The accumulated time that the compressor has been used in  outdoor unit is shown here     Menu 5 3  U  Time to start    Time until the compressor start in outdoor unit is shown in this  menu     Menu 5 4  U  Outdoor temp  Tho A    This menu shows the outdoor air temperature that the heat  pump measures     Menu 5 5  U  Heat Ex Tho R1    This menu shows the evaporator temperature in the heat pump  at sensor Tho R1     Menu 5 6  U  Heat Ex Tho R2    This menu shows the evaporator temperature in the heat pump  at sensor Tho R2     Menu 5 7  U  Suction temp  Tho S   This menu shows the suction gas temperature in the heat pump   Menu 5 8
14.  HMS140VA  HMS140V gt                                                  MT300  Hot water volume   450   400 122 min  m  350   gt     162 min  E 300       gt   5 250  R  3  2 200  2   150   100   50   0     50 53 56 59 62 65    Stop temp HW    C                          MT500  Hot water volume  1600 102  min  1400  S 1200 122 min    1000  Z 142 min    800  5 162 min  i     600  ap Limi  a 24    min    400  n  200                                        Stop temp  HW   C      These graphs are based on the following conditions    Inlet water temperature   15  C  Outlet water temperature   40  C  Outdoor air temperature   7  C    Hot water Supply is unlimited in case 8    min at the condition as  the capacity is bigger than hot water supply     Prioritizing   When the water temperature in the tank drops  heat pump  operation shifts to hot water production  In case there is  demand for both hot water and heating cooling for long time   operation mode is periodically switched between hot water and    heating cooling  For details  see menu 1 0 Hot water temp and  8 5 0 Period settings     14    Extra Hot Water    In all    Extra hot water    functions  the temperature of the hot  water increases temporarily  The temperature is first increased  to an adjustable level by the compressor  menu 1 5  and then  the electric heater is energized until the water temperature  reaches the stop temperature  menu 1 4      Temporary    Extra hot water    is activated manually  whilst time  based ext
15.  If the cooling system is set to    On    in menu 9 3 3 and the  outdoor temperature is greater or equivalent to the set start  temperature for cooling in menu 8 2 4  cooling starts     Cooling stops when the outdoor temperature drops below the  set value minus the set value in menu 8 2 5     The calculated supply water temperature is determined from the  selected cooling curve in menu 2 2 2 and the offset for cooling  curve  menu 2 2 1  Limitations  which are not in the diagram   are included in the control system   s permitted min temperature     DA  Sn                                        Calculated supply water temperature  S    0 20 30 40   C  Outdoor temperature    Comfort setting cooling    13    Comfort setting hot water    Comfort setting hot water    The integrated water heater is a coil model and is heated by  circulating water  which is heated by the heat pump    During    normal    consumption it is enough to run the heat  pump to supply the different tapping points of the house with  hot water  The temperature of the hot water in the water heater  then varies between the set values    Under section 1 0  N  Hot water temp  on page 25 there is a  complete description of menu settings for hot water  temperatures     Available volume   lt HMA100V  HMA100VM gt     Hot water volume                                           600  8 l min  500  S  o  g 209 12     min  z  5 16 2  min  2 300  3   gt   Q    200  nN  100  0  50 53 56 59 62 65    Stop temp  HW    C       lt
16.  low    is displayed    Menu 8 3 6  U  Transform  ratio EBV    The transfer value must be defined depending on the current  transformers used for the PCB     Setting range  100     1250    Menu 8 3 7  U  Return  Return to menu 8 3 0   Menu 8 5 0  U  Period settings    Time periods for heating and hot water production are set in  the sub menus for this menu     Menu 8 5 1  U  Period time    You can set the length of cycle time for hot water production  and heating in case there is demand for both     Setting range  5     60 min    Menu 8 5 2  U  Max time for HW    Here you select operation period for hot water of the period  time   8 5 1     Setting range  0     60 min    Menu 8 5 3  U  Return  Return to menu 8 5 0   Menu 8 6  N  Return    Return to menu 8 0     Control    33    Control    Checklist  Checks before commissioning                                                                                                                                                                                                                                                                                           Hot water Notes Checked  Non return valve Is it installed in right direction    Safety valve Is it installed in cold water line    Mixer valve Is it installed in right direction    Heating Notes Checked  System volume Tank  2tSystem 2  Total 64  Safety valve Is FL2 installed    Expansion vessel Total system volume x 5  ormore     Internal heater Permitted prohibited  Menu 8 2 
17.  or  contamination        Do not touch the aluminum fin  S  Otherwise it may lead to injuries        Do not clean the inside of the indoor  unit by yourself  Make sure to consult Q  your dealer or user inquiry counter  specified by our company    If you select incorrect detergent or improper  method  resin parts may be damaged and  lead to water leakage  If the detergent is  dropped on the electric component or motor   it may lead to failure  smoking or ignition        Do not place objects on the outdoor unit  S  nor mount on it     It may lead to injuries resulting from  dropping or falling        During the operation or maintenance  SO  do not use an unstable footrest     It may lead to injuries resulting from falling        During thunderstorm  stop the WA  operation and turn off the switch     A lightning strike may lead to failure        After several seasons of operating  Q  inspections and maintenances are  required except routine care and cleaning     Accumulated dirt or dust inside the indoor  unit may cause odor  water leakage through  the clogging of water discharging pipe for  dehumidification  Specialized information  and skills are required for inspections and  maintenances  Therefore contact your  dealer           Do not use with inlet outlet grilles or S  other panel removed     Otherwise  it may lead to injuries     Do not operate or stop the unit by S  using the power supply switch   It may lead to fire or water leakage     If auto restart is set effectively
18.  reduced physical  sensory or  mental capabilities or lack of experience  and knowledge if they have been given  supervision or instruction concerning  use of the appliance in a safe way and  understand the hazards involved  Children  shall not play with the appliance  Cleaning  and user maintenance shall not be made  by children without supervision    This in accordance to applicable parts of  the low voltage directive 2006 95 EC  LVD   HMS140VA  HMS140V and its relevant  outdoor unit and tanks are also intended  for use by experts or trained users in    shops  hotels  light industry  on farms and  in similar environments  This in accordance  to applicable parts of the machinery  directive 2006 42 EC    CE marking is applicable to the area of  50 Hz power supply    The emission sound pressure level from  each Indoor and Outdoor unit is under  70 dB A         INSTALLATION PRECAUTIONS   A DANGER  Make sure to have the installation Q  done by your dealer or a specialist          If you install by yourself and the unit is not  properly installed  water leakage  electric  shock  fire and injuries caused by the drop  of the unit may occur                 The preventive measures that the    density of leaked refrigerant does not        exceed the limit is necessary in case of  installing the unit in a small room     The leakage of refrigerant may cause oxygen  deficiency accident  Consult your dealer for the  measures     A CAUTION    Make sure to perform grounding D  work        D
19.  the    Heating curve     value is increased in menu 2 1 2 by one increment     m When the room temperature is too high  the    Heating  curve    value is decreased in menu 2 1 2 by one increment     Warm weather conditions    m Ifthe room temperature is low  increase the    Heating curve  offset    setting by one step clockwise     m Ifthe room temperature is high  reduce the    Heating curve  offset    setting by one step anti clockwise     Heating system 2    If the heating system has two different type of emitter like  radiator and under floor heating  it is possible to set two  different calculated supply temperature  System 1 for higher  supply temperature can be set in menu 2 1 0  and system 2 for  lower supply temperature can be set in menu 3 0     Vacation set back    When you are away from home for a long time  it is possible to  set the target supply water temperature for heating lower than  usual to save energy consumption  Also  it is possible to cancel  hot water operation during the period     For details  see menu 7 5 0 Vacation set back     Silent mode    If you like to reduce noise from outdoor unit  it is possible to do  by reducing the compressor speed and fan speed in outdoor unit     For details  see menu 7 6 0 Silent mode     12    Comfort setting with room sensor  If MH RG10 is installed  operation mode is chosen not only by  outdoor temperature but also by room temperature     Upper limit of the outdoor temperature to operate in Heating  mode can be s
20.  the heat from the water and release the heat  to the outdoor air  the heat pump can cool instead if necessary     Indoor unit determines when outdoor unit is to work and not to  work  using the collated data from the temperature sensor  In  the event of extra heat demands  indoor unit can connect additional  heat source in the form of the internal immersion heater  or any  connected external heat source     Front panel  indoor unit    Front panel  indoor unit    Addition  heat symbol Hot water symbol  If the electrical addition is connected   Hot water charging in progress      T    Electrical step 1    A    Temporary Extra hot water operation in     IT    Electrical step 2 progress      I II    Electrical step 1 2    B    Time based Extra hot water operation in     TIT    Electrical step 3 progress  e g  periodic   Compressor symbol Circulation pump symbol      Compressor is operational     A    Heating mode     B    Cooling mode         Circulation pump in operation     With two circulation pumps  requires ESV  22 accessory   the operating pump is also  indicated    Operating status  Button pressing  the change does not  need to be confirmed with the enter  button     Current operating mode  shown in display   Further button press  changes operating mode  Press the  enter button to return to the normal  display mode           Heating system symbol            WI Heating in progress             Description of current display  For information about the various operating param
21. 1   External heat Source ha  gt  Type__ Setting  Menu 9 2 8   Heating system 2 ka  Cooling Notes Checked  Pipe system  condensation insulation  Reversing valve  ON12  Is it installed in right direction    Refrigerant system Notes Checked  Pipe length  within 12m  sm  Height difference  within 7m      m  Test pressurization 41 5 bar  Leak tracing  End pressure Evacuation  1 bar or lower for one hour  Electrical installation Notes Checked  Property   s main fuse 3 1 phase____A  Group fuse 3 1 phase____A  Current limiter current sensor Is it installed properly if the power supply is 3 phase    Accessories Notes Checked  External circulation pump Yes No  Buffer vessel Yes No Volume 4  Relief valve Yes No  Room sensor ANO DE E  Setting  Menu 9 3 5  9 3 6  6 2                                   34       MEMO    35    36    MEMO    A MITSUBISHI HEAVY INDUSTRIES  LTD     AIR CONDITIONING  amp  REFRIGERATION SYSTEMS    3 1  Asahi  Nishibiwajima cho  Kiyosu  Aichi  452 8561  Japan  http   www mhi co jp    MITSUBISHI HEAVY INDUSTRIES AIR CONDITIONING EUROPE  LTD   7 Roundwood Avenue  Stockley Park  Uxbridge  Middlesex  UB11 1AX  United Kingdom  Tel   44 20 7025 2750  Fax   44 20 7025 2751    http   www mhiae com    
22. Menu 7 4 1     7 4 7  U  XHW Monday     XHW Sunday    Here you select the period for respective days when extra hot  water should be activated  Hours and minutes for both start and  stop are shown  Equal values mean that extra hot water is not  activated  Time can be set past midnight     Setting range  00 00     23 45   Menu 7 4 8  U  Return   Return to menu 7 4 0    Menu 7 5 0  U  Vacation set back    Holiday settings are made in the sub menus to this menu   When the holiday function is active  the calculated supply line  temperature is reduced according to the setting and hot water  charging can be switched off    When the holiday function is deactivated  the heat pump operates  hot water for an hour  before periodic extra hot water is activated   even if periodic extra hot water is activated in menu 1 7      Note  The holiday setting does not deactivate cooling     Control    Menu 7 5 1  U  Vacation begins    The start date for holiday changing is set here  The date is  changed by pressing the enter button  The holiday change starts  applying at 00 00 on the selected date     Same date in menu 7 5 1 and 7 5 2 deactivates the holiday function   Menu 7 5 2  U  Vacation ends    The end date for holiday changing is set here  The date is  changed by pressing the enter button  The holiday change stops  applying at 23 59 on the selected date     Same date in menu 7 5 1 and 7 5 2 deactivates the holiday function   Menu 7 5 3  U  Heating system    The heating system to apply the v
23. USER   S MANUAL  MITSUBISHI HEAVY INDUSTRIES LTD     Air to Water Heat Pump  Hydrolution  HM        HMA100V  HMA100VM   FDCW71VNX A FDCW100VNX A  HMS140VA  HMS140V   FDCW140VNX A                                        MITSUBIS  Hydrolution                                 _            o a  fi ua          S    us    lt  aa aa    uu uu           uu                                                                                  N m 7   A    1 or  i Xy N m Bae m my 7       a Aa aa   SRR I   st           S 5     b   gt     o  n   aj  a                 a       S    RAS 9        SEN       _      I      lt  MITSU               E s BI     n a           lt        AVY INDUSTRIES  LTD  AAN      uu uu H ES LTD  Se  Z           A lydrolution uu  Ca AILI    RAOR                 tiiin  LUIS       CTT    TUPLE                                                                   4  O A  C     English   Original instruction    This heat pump complies with EMC Directive 2004 108 EC   LV Directive 2006 95 EC  and  parts of Machinery Directive 2006 42 EC  HMS140VA  HMS140V    and its relevant outdoor unit and tanks only    CE marking is applicable to the area of 50 Hz power supply  P S A 0 1 2 B 7 3 3 C    Safety percautions       General       Installation data       Information about the installation  Product information       Features of Hydrolution       Principle of operation Hydrolution       Front panel  indoor unit       How to use the front panel       Menu types       Quick movement        
24. acation set back is selected  here  If heating system 2 is present the menu can be set to    Off         System 1        System 2    or    System 1 2     In other cases only     Off    and    System 1    can be selected     Setting range  Off  System 1  System 2  System 1 2   Menu 7 5 4  U  Offset heating curve   How much the heating curve is to be offset during the holiday  period is set here     If the relevant heating system has a room sensor  the change is  given in degrees     Setting range   10    10   Menu 7 5 5  U  HW off   You can choose if hot water operation is cancelled during the  holiday period   Setting range  No  Yes    Menu 7 5 6  U  Return  Return to menu 7 5 0   Menu 7 6 0  N  Silent mode    Setting is made in the sub menu of this menu if Silent mode is  activated on a certain period     When the silent mode is activated  maximum compressor speed  and fan speed in outdoor unit is reduced in order to make the  noise smaller     Take note that the capacity is reduced by around 30  during silent mode     It is valid in heating mode only   Menu 7 6 1  N  Silent mode time    Here you select the period when the silent mode should be  activated  Hours and minutes for both start and stop are shown   Equal values mean that the silent mode is not activated  Time  can be set past midnight     Setting range  00 00 23 45  Menu 7 6 2  N  Return  Return to Menu 7 6 0  Menu 7 7  N  Return    Return to menu 7 0     31    Control    8 0  N  Other adjustments    Menu 8 1 0  N
25. any blown circuit and  main fuses        Possible earth circuit breaker tripped     Reset the earth circuit breaker  if the earth  circuit breaker trips repeatedly  call an    electrician        Switch  SF1  set to mode 0     Set the switch to 1        Large hot water demand     Wait a few hours and check if the hot water  temperature rises        Too low start temperature setting on the  control system     Adjust the start temperature setting in menu  1 2        Low room temperature     Possible earth circuit breaker tripped     Reset the earth circuit breaker  if the earth  circuit breaker trips repeatedly  call an  electrician        Heat pump and immersion heater do not heat     Check and replace any blown circuit and  main fuses        Incorrect setting of    Heating curve  offset     and or    Cooling curve  offset        Adjust the settings    Check menu 2 1 1  2 1 2 for heating system 1  3 1  3 2 for heating system 2  2 1 1  2 2 2 for cooling system       Stop temp heating setting is too low     Adjust the setting  Check menu 8 2 3       Circuit or main MCB tripped     Check and replace blown fuses        Heat pump in incorrect operating mode    Hot  water    or    Cooling        Change operating mode to    Auto    or     Au   toC           The current limiter has restricted the current  because many power consumers are being  used in the property     Switch off one several of the power consu   mers        High room temperature     Incorrect setting of    Heating curv
26. ay be heard from  a stopped indoor unit        The air conditioning system   Outdoor unit does not restart during the first 3 minutes after stopping operation  This is because a  cannot start operating again   circuit for protecting the compressor is activated  the fan is operating during this period    immediately after stopping        The outdoor unit discharges   Water or steam is discharge during defrosting operation which removes frost built up on the surface of  water or steam during the heat exchanger in the outdoor unit in heating mode   heating operation        The outdoor unit fan is not   The fan speed is automatically controlled according to the ambient temperature  It may be stopped in  running even when the high ambient temperature in case of heating  and in low ambient temperature in case of cooling  Also   system is in operation  the fan is stopped during defrosting operation    KESSI The fan will suddenly begin to operate even if it is stopped  Do not insert finger and or stick        Hissing sounds are heard These sounds are generated when the refrigerant valve inside the air conditioning system is activated   when the operation is  stopped or during defrost  operation                 Operating mode    Add  heat only       In the event of malfunctions that cause a low indoor temperature   you can normally activate    Add  heat only    in indoor unit  which  means that heating only occurs with the immersion heater     Activate the mode by holding in the opera
27. e   10    10  Menu 2 1 2  N  Heating curve    The selected heating curve is shown here  At value 0  the  function    Own heat curve    is activated  see menu 2 1 3 0     Setting range  0     20    Menu 2 1 3 0  U  Own heating curve    Here you can select your own curve definition  This is an  individual linear curve with one break point  You select a break  point and the associated temperatures     Note  The    Heating curve    in menu 2 1 2 must be set to 0 to  activate this function     Menu 2 1 3 1  U  Supply temp at  20    The supply temperature at an outdoor air temperature of   20   C is selected here     Setting range  0     80    C      Limited by menu 2 3 Max supply temp   Menu 2 1 3 2  U  Supply temp at  20    The supply temperature at an outdoor air temperature of  20   C  is selected here     Setting range  0     80    C      Limited by menu 2 3 Max supply temp   Menu 2 1 3 3  U  Buckling temperature    Here you select at what outside air temperature the break point  shall occur     Setting range   15    15   C    Menu 2 1 3 4  U  Supply t  at buckl     You set the calculated supply temperature for the break point  here     Setting range  0     80    C      Limited by menu 2 3 Max supply temp   Menu 2 1 3 5  U  Return  Return to menu 2 1 3 0     26    Menu 2 1 4  U  Min supply heating    The set minimum level for the supply temperature to the  heating system is shown here     The calculated flow temperature never drops below the set  level irrespective of the outd
28. e  offset     and or    Cooling curve  offset        Adjust the settings    Check menu 2 1 1  2 1 2 for heating system 1  3 1 3 2  2 1 1  2 2 2 for cooling system    for heating system 2       Heat pump in incorrect operating mode     Change operating mode to    AutoC           Start temp cooling setting is too high     Adjust the setting  Check menu 8 2 4        Heat load is too high     Remove the excess heat load        The compressor does not start     Minimum time between compressor starts  alternatively time after power switch on not  being achieved     Wait 30 minutes and check if the compressor  starts        Alarm tripped     See section    Alarms           Alarm cannot be reset     Activate operating mode    Add  heat only           Panel gone out           Check and replace any blown circuit andmain  fuses        Check that the circuit breaker to the indoor  unit is not off              Set switch  SF1  to standby     AS             17    Dealing with comfort disruption    The phenomena mentioned below is not malfunction        The air conditioning system   Sounds of rustling or gurgling may be heard when the operation is started  when the compressor is       sounds as if water is activated deactivated during operation  or when the operation is stopped  These are the sounds of the  draining from it  refrigerant flowing through the system   Sounds of rustling or These sounds can be heard when the air conditioning system is performing automatic control     gurgling m
29. e when the heat pump stops hot water charging  is set here     Setting range  30     60   C    Menu 1 4  U  Stop temperature XHW    The desired temperature during extra hot water is set here   Setting range  40     65   C    Menu 1 5  U  Heat pump stop XHW    The desired stop temperature during extra hot water for the  heat pump is set here     Setting range  40     60   C    Menu 1 6  U  Max heat p  time XHW    Here you select the maximum amount of time the heat pump  can charge hot water for during extra hot water     Setting range  0     60 min    Menu 1 7  U  Interval XHW    Periodic time based extra hot water is selected here     Extra hot water is shut off at the value    Off     Extra hot water  is started when the value is confirmed     Setting range  0     90 days    Menu 1 8  U  Next XHW action    Time to the next periodic Extra hot water operation is shown  here     Menu 1 9  U  HW run time    Shows how long hot water charging with the compressor has  been in progress  accumulated      Menu 1 12  N  Return    Return to menu 1 0     Control    25    Control    2 0  N  Supply temp     Menu 2 1 0  N  Heating settings  Heating settings are made in the sub menus for this menu   Menu 2 1 1  N  Offset heating Total    The selected heating curve offset is shown here     The total offset of the heat curve is also shown here  It  includeschedule  outer compensation and any room control     Note  The value is changed using the    Heating curve offset     knob     Setting rang
30. et in menu 8 2 3 Stop temp Heating    Lower limit of the outdoor temperature to operate in Cooling  mode can be set in menu 8 2 4 Start temp Cooling    Target room temperature can be adjusted by turning the knob  on MH RG1O  and it is displayed in menu 6 3     For details  see instruction manual for MH RG10  The below  figure shows an example of mode transition     NOTE    Mode transition wouldn t happen even if MH RG10 is  installed in case Heating or Cooling mode is chosen              Choose Auto or AutoC in case room sensor is used                    A  Qo Hot water production Cooling  3  i  D Target 8            __                     room temp    2  63     E Heatin     8 I  8  a 1  ji  l  gt   Stop temp Start temp  Heating  8 2 3  Cooling  8 2 4     Outdoor temperature    Mode transition  in case AutoC is chosen        MH RG10    Comfort setting cooling  General    In the default setting  cooling operation is not allowed  In order  to activate  change the setting on the menu 9 3 3 Cooling  system to    On        NOTE    The climate system must manage cooling operation        Setting must be made by the installer when    commissioning the system     Settings must be made by the installer when commissioning  the system     If a room sensor is connected  it starts and stops cooling based  on both the room and the outdoor temperature  The lowest  calculated supply water temperature is set in menu 2 2 4     Cooling operated from the outdoor sensor in  operating mode AutoC   
31. eter  modes  see the different sections regarding    comfort settings           Information symbols    1 0 Menu number         Extra hot water  KHW     Extra hot water operation starts with this  button  The operation is cancelled when  the button is pressed again    The change does not need to be  confirmed with the Enter button         2 Key lock activated                Plus button      Scroll forward in the menu system     Increase the value of the selected parameter  See the section    Control     General       Menu 1 0  Pressing the button takes you directly to  menu 1 0                   Minus button          Offset heating curve    Turning clockwise     offsets the Heating  curve  When the knob is turned   menu 2 0 is shown on the display and   the value for the calculated supply  temperature changes    For details  see Default Heating curve setting       Scroll back in the menu system     Reduce the value of the selected parameter  See the section    Control     General              Enter button      Entering lower layer in the menu system     Parameter change activated            Parameter change confirmed       Switch       See the section    Control     General       1            Normal mode  All control functions connected   Status lamp       0 Shutdown s    During normal operation  the status lamp    lights green  In the event of an alarm  it  lights red          AS  Emergency mode   Only the circulation pump and  electric heater  electrical step 2   are operati
32. he  operating mode     Add  heat only     can be activated to  resume a normal temperature level in the house  This is  most easily carried out by holding the    Operating mode     button in for 7 seconds     NOTE    Recurring alarms mean that there is a fault in the  installation     Contact your installer     19    Control    Control    Display    Operating symbols    Menu number    Value of the current parameter       A Hil AB Hl        lt  5 QO m  Sion    C    Hot water temp     a   z  Menu N    Key lock       13 43             Clock    Menu types    Control is classified into different menu types depending on    how    deep    into the controls you need to go     Normal  NJ  The settings you as a customer  often need   Extended  U   Shows all detailed menus except    the service menus     Menu management    20    The Plus button is used to move forward to the  next menu on the current menu level and to  increase the value of the parameter in menus  where this is possible     The Minus button is used to move back to the  previous menu on the current menu level and to  decrease the value of the parameter in menus  where this is possible     The Enter button is used to select submenus of the  current menu  to permit parameters to be changed  and to confirm any changes to parameters  When  the menu number ends with a zero this indicates  that there is a submenu     Changing parameters    In order to change a parameter  value      1     2     Access the reguired menu     Pres
33. it  be sure to turn off    Indoor unit  power supply breaker        It can result in electric shock or injury due   to rotation of indoor unit fan if you perform  check or repair with the    Indoor unit power  supply breaker    turned on        Place the panels removed for Q  repairing or checking on the stable  spot     Otherwise  dropping or falling may lead to  injury     Safety precautions    General    General    Hydrolution is a system for heating  cooling and producing hot water for small houses  The system consists of an outdoor nuit  which  utilises the energy in the outdoor air and sends it to the indoor unit  which takes care of the regulation and heat distribution in the house   In order to get the greatest benefit from the system Hydrolution you should read through the User s Manual     Hydrolution is a quality system offering a long service life and reliable operation     NOTE    Do not vent R410A into the atmosphere  R410A is a fluorinated greenhouse gas  covered by the Kyoto Protocol with a Global       Warming Potential GWP    1975     Installation data    Completed by the installation engineer when the installation is installed    Installation data and installation check list on page 34 must  be filled in by the installer in order for the warranty to apply        The Serial number  must always be stated in all correspondence with MHI        Indoor unit  Outdoor unit                 Installation date  Check list  page 34  filled in    Installation engineers  
34. ling     Heat pump is used for cooling only if electric heater use is  allowed  Otherwise  it is used for both cooling and hot water     The circulation pump is in operation the entire time   5  Hot water   Only hot water is produced    Only the compressor is operational   6  Add  Heat only    Heat pump is not operational  The function is activated   deactivated by pressing in the    operating mode button    for  7 seconds       To use the cooling functions  the system must be designed to  withstand low temperatures and cooling must be activated in  menu 9 3 3     Changing the room temperature manually    If you want to temporarily or permanently increase or lower  the indoor temperature  turn the    Offset heating curve    knob    clockwise to increase or anticlockwise to lower  One line  approximately represents   degree change in room temperature     NOTE    An increase in the room temperature may be inhibited  by the radiator or underfloor heating thermostats  if so       these must be set at 0     Default Heating curve setting    The basic heating is set using menu 2 1 2 and with the    Heating  curve offset    knob    If the room temperature does not reach the target  readjustment  may be necessary     If you do not know the correct settings  use the basic data from  the automatic heating control system diagram on the right     Heating curve  Bo lar        Menu 2 1 2 Heating curve Offset heating curve    Heating curve offset for system 2 can be made in menu 3 1    NOTE 
35. m  tariff B or  Operating mode Addition only    Stopped Shown when the outdoor temperature is outsi     de the compressor   s working range  too high  or too low temperature               Menu 6 0  N  Room temperature    The room temperature is shown here and the set room temperature  in brackets  The factor for the room sensor and heating system to  control are set in the sub menus to this menu     Menu 7 0  N  Clock    The date and time are set in the submenus of this menu   Different temperature reductions and increases at selected  times are also set from this menu     Menu 8 0  N  Other adjustments    The menu type  language  operating mode settings and load  monitor reading are set in the sub menus to this menu     24       NOTE  These settings should only be made by persons  with the necessary expertise      N  Normal  covers the normal user   s needs      U  Extended  shows all menus except the service menus     1 0  N  Hot water temp     Menu 1 1  N  Max HW Period time    The time of the hot water period and the time for the whole  period are shown here  Whole period is shown in brackets   Shown for both hot water charging and heating when  necessary     Time for Heating  Max   when heating is in progress   Time for Hot water  Max   if hot water charging is in progress     Menu 1 2  N  Start temperature HW    The temperature when the heat pump starts hot water charging  is set here     Setting range  25     55   C    Menu 1 3  N  Stop temperature HW    The temperatur
36. menu 3 0      Setting range  Off  System 1  System 2  System 1 2    Menu 6 3  N  Room temp  setpoint   The desired room temperature is shown here    Setting range  10     30   C   Menu 6 4  U  Room temp avg  1min   Shows the average room temperature over the last minute   Menu 6 5  U  Room integrator time    Select the integration time for room control here     Setting range  0    120    Menu 6 6  N  Return    Return to menu 6 0     7 0  N  Clock    Menu 7 1  N  Date   The current date is set here    Menu 7 2  N  Time   Here the current time is set    Menu 7 3 0  U  Temp set back    Settings  e g  for night reduction can be selected in the  submenus to this menu     Menu 7 3 1  U  Set back time    The time for the set back operation  e g  night reduction is  chosen here     Menu 7 3 2  U  Set back temp       Changes of the heat curve during set back operation period  e g   the night reduction is set here    Setting range   10     10   Default value  0   Menu 7 3 3  U  Heating system    The heating system to apply the set back operation is selected  here  If heating system 2 is present the menu can be set to     Off        System 1        System 2    or    System 1 2     In other  cases only    Off    and    System 1    can be selected        Setting range  Off  System 1  System 2  System 1 2  Menu 7 3 4  U  Return   Return to menu 7 3 0    Menu 7 4 0  U  Extra hot water    Settings are made in the sub menus of this menu when extra  hot water is required on a specific day     
37. nd comes     Comfort setting hot water   Maintenance    Maintenance    Hydrolution requires minimal maintenance after commissioning   Hydrolution contains many components and is why monitoring  functions are integrated to help you     If something abnormal occurs  a message appears about  malfunctions in the form of different    alarm    texts in display     Checking the safety valves in indoor unit    Indoor unit has been equipped with a safety valve for the water  heater as well as a safety valve for the climate system by the  installer     For HT30  a safety relief valve is supplied with tank unit and  the valve is installed to water pipe by installer     The climate system   s safety valve   lt HMA100V  HMA100VM gt         lt HMS140VA  HMS140V gt   MT300       MT500       15    Maintenance    The climate system   s safety valve  FL2  must be completely  sealed  Checks must be carried out regularly as follows     m Open the valve     m Check that water flows through the valve  If this does not  happen  replace the safety valve     m Close the valve again     m The heating system may need to be refilled after checking  the safety valve  see the section    Filling the heating  system        Hot water heater safety valve    The water heater   s safety valve sometimes releases a little  water after hot water usage  This is because the cold water   which enters the heater to replace the hot water  expands when  heated causing the pressure to rise and the safety valve to open   
38. nd use  the product appropriately according to the  instructions     m The precautions provided here are classified  into    a DANGER    and    a CAUTION      The    a DANGER    sections describe  potentially hazardous situations that may  lead to serious outcomes such as death  and sericus injuries if the product is  mishandled  Note  however  that depending  on the situation  the items listed in the      A CAUTION    sections do also have the  potential of causing serious outcomes   Both warnings and cautions provide you  important information related to safety    please make sure to observe them     m The symbols used throughout the main  text of this manual have the following  meaning    A marks mean danger  alarm  and   A caution  The specified prohibited item   is described in the triangle  The left  mark means    Shock hazard alarm          lt  gt  O marks mean prohibited items  The   Y specified prohibited item is described  in the circle or in the vicinage    aes  marks mean compulsory action or    instruction  The specified prohibited  item is described in the circle  The  left mark means    Earth is needed       m After you have read the manual  always  store it where other users can refer to at  any time  If a new owner takes over the  system  make sure to pass this manual   This heat pump complies with EMC  Directive 2004 108 EC     This appliance is designed for use in a  home environment and can be used by  children aged from 8 years and above and  persons with
39. not need to be    acknowledged when the cause has disappeared      m Existing alarms that require corrective action by you or the    installer     Recommended actions    1  Read off which alarm has occurred from the heat pump   s    display       Asacustomer you can rectify certain alarms  See the table    below for relevant actions  If the alarm is not rectified  or is  not included in the table  turn off the switch  SF1  to 0 and  contact your installer        Alarm text on the display    Alarm description    Check remedy before installers service  technicians are called       LP ALARM Tripped low pressure sensor  Check that the thermostats for the radiators   under floor systems are not closed   HP ALARM Tripped high pressure sensor  Check that the thermostats for the radiators     under floor systems are not closed        OU power failure   OU Com  error    cut    Outdoor unit not powered   Communication    Check that any circuit breakers to the outdoor  unit are not off           Display not lit       Check and replace any blown circuit and  main fuses        Check that the circuit breaker to the indoor  unit is not off    Check that the switch  SF1  is in normal posi   tion  1                  Resetting alarms    No harm in resetting an alarm  If the cause of the alarm remains   the alarm recurs        When an alarm has been triggered  it can be reset by switching  indoor unit off and on using the switch  SF1      When the alarm cannot be reset using the switch  SF1   t
40. o not connect grounding wire to any  gas pipe  water pipe  conductor rods or  telephones  Incomplete grounding may  cause electric shock through leakage of  electricity        Make sure to mount a leakage breaker  d     Otherwise electric shock may occur     Please consult your dealer or a specialist for the  mounting        Do not mount where flammable gas Q  leakage can happen  LY    If leaked gas stagnates in the unit  the gas  may cause fire        Make sure to layout the drain pipe so rt  that the water is completely drained  2 d    Otherwise  water may leak and wet  household goods        ns OPERATION PRECAUTIONS  A DANGER    Do not expose yourself directly to SO  radiator or any other heating device  for a long time     It may cause low temperture burn injury        Do not set water temperature too S  high when under floor heating  application is used     It may cause low temperature burn injury        Do not expose yourself directly to S  cooled air flow for a long time or  cool too much     It may be cause of deconditioning or health  disorder        Do not insert fingers or sticks into S  the air inlet or outlet grilles     It may cause injuries because of the fan  rotating at high speed        If the unit has been submerged under BD  water due to a natural disaster such as  flood or typhoon  consult your dealer before  using it again    If you use it as it stands  it may lead to  failure  electric shock or fire        If any abnormal symptom  scorched Q  flavor etc
41. onal                                How to use the front panel    All the most common settings are made from the panel such as  comfort etc  that you expect from the heat pump system to  fulfil     In order to make full use of it  certain basic settings must have  been made  see page 11  and the installation in general is carried  out according to the instructions     Menu 1 0  the temperature in the water heater  is  normally shown on the display     MD The plus and minus buttons and the enter button are     used to scroll through the menu system as well as to  change the set value in some menus         Q    Menu types  Menu 8 1 1     Control is classified into different menu types depending on  how    deep    into the controls you need to go     E Normal  N   The settings you as a customer  often need   m Extended  U   Shows all detailed menus except    the service menus     Quick movement    To quickly return to the main menu from a sub menu  press  the following button  D    Key lock    A key lock can be activated in the main menus by simultaneously    pressing the Jd and the eC buttons  The key symbol will    then be shown on the display  T  The same procedure is used to deactivate the key lock     Language setting  Menu 8 1 2     Language used in the display can be chosen in menu 8 1 2     Front panel  indoor unit    Comfort setting heating    Comfort setting heating  General    The indoor temperature depends on several factors     m Sunlight and heat emissions from peo
42. oor temperature  heating curve or  its offset heating curve     Setting range  20     65   C    Menu 2 1 5  U  Circ pump speed heat    The speed of the circulation pump during space heating is  selected here     Setting range  1     100    Menu 2 1 6  N  Return   Return to menu 2 1 0    Menu 2 2 0  N  Cooling settings   Cooling settings are made in the sub menus for this menu   Menu 2 2 1  N  Offset cooling Total    The selected cooling curve offset is changed here     The total offset of the cooling curve is also shown here  It  includes schedule  outer compensation and any room control     Setting range   10     10    Menu 2 2 2  N  Cooling curve    The selected cooling curve is shown here  At value 0  the  function    Own cooling curve    is activated  see menu 2 2 3 0     Setting range  0     3    Menu 2 2 3 0  U  Own cooling curve    Here you can select your own curve definition     Note  The cooling curve in menu 2 2 2 must be set to 0 to  activate this function     Menu 2 2 3 1  U  Supply temp at  20    The supply temperature at an outdoor air temperature of  20   C  is selected here     Setting range  0     25    C      Limited by menu 2 2 4 Min supply cooling   Menu 2 2 3 2  U  Supply temp at  40    The supply temperature at an outdoor air temperature of  40   C  is selected here     Setting range  0     25    C      Limited by menu 2 2 4 Min supply cooling   Menu 2 2 3 3  U  Return    Return to menu 2 2 3 0     Menu 2 2 4  N  Min supply cooling    The set minimum le
43. or the sides so that water penetrates into outdoor unit  Prevent    16    outdoor unit coming into contact with alkaline cleaning agents     AAWARNING     Rotating fan       Saving tips    Your Hydrolution produces heat and hot water according to  your needs  It also attempts to carry out all requirements with  all available    aids    from the control settings made     The indoor temperature is naturally affected by the energy  consumption  Therefore  take care not to set a temperature  higher than necessary     Other known factors that affect the energy consumption are   for example  hot water consumption and the insulation level of  the house  as well as the level of comfort you require     Also remember     m Open the thermostat valves completely  except in the  rooms that are to be kept cooler for various reasons  e g   bedrooms      Thermostat valves in the radiators and floor loops can  negatively affect the energy consumption  They slow the flow  in the heating system  which the heat pump wants to  compensate with increased temperatures  It then works harder  and consumes more electrical energy     Dealing with comfort disruption    Use the following list to find and remedy any heating or hot    water problems     Dealing with comfort disruption       Symptom    Cause    Action       Low hot water temperature or a lack of hot  water    Circuit or main MCB tripped     Check and replace blown fuses        Heat pump and immersion heater do not heat     Check and replace 
44. ple and household  machines are normally sufficient to keep the house warm  during the warmer parts of the year     m When it gets colder outside  the heating system must be  started  The colder it is outside  the warmer radiators and  under floor heating systems must be     Controlling heat production    Normally  the heat pump heats the water  heating medium  to  the temperature required at a certain outdoor temperature  This  occurs automatically on the basis of the collected temperature  values from the outdoor sensor and sensors on the lines to the  radiators  supply water sensors   Extra accessories such as room  sensors  can influence the temperature     In order to operate the system properly  the correct settings  must be made on the heat pump first  see the section    Default  Heating curve setting        The outdoor sensor  mounted on an exterior wall of the house   senses variations in the outdoor temperature early on  sends the  information to the heat pump control computer and heating  operation is started  It does not have to be cold inside the house  before the control system is activated  As soon as the  temperature drops outside  the temperature of the water to the  radiators  supply temp   inside the house is increased  automatically     The heat pumps flow temperature  menu 2 0  will hover around  the theoretical required value  which is in brackets on the  display    Temperature of the heating system   The temperature of the heating system in relation to 
45. pply Return temp     The current supply and return line temperatures are shown  here  Return temperature is shown in brackets     Control    Menu 2 6  U  Degree minutes    Current value for number of degree minutes  In addition  this  value can be changed to accelerate the start of heating production  or cooling     Setting range   32000     32000    Menu 2 7  N  Return    Return to menu 2 0     27    Control    3 0  N  Supply temp  2    Menu 3 1  N  Offset heating Tot 2    The heating curve offset 2 is selected here     The total offset of heat curve 2 is also shown here  It includes  schedule  outer compensation and any room control     Setting range   10     10    Menu 3 2  N  Heating curve 2  The selected heating curve is shown here  At value 0  the  function    Own heat curve 2    is activated  see menu 3 6 0     Setting range  0     20    Menu 3 3  U  Min supply temp  2  The set minimum level for the supply temperature for heating  system 2 is shown here     The calculated flow temperature never drops below the set  level irrespective of the outdoor temperature  heating curve or  its offset     Setting range  10     65   C    Menu 3 4  U  Max supply temp  2  The set maximum level for the supply temperature for heating  system 2 is shown here     The calculated flow temperature never exceeds the set level  irrespective of the outdoor temperature  heating curve or its  offset     Setting range  10     65   C    Menu 3 5  U  External adjust  2    Connecting an external con
46. ra hot water is activated using the settings made in the  control computer     When     m    A    appears above the     icon  temporary extra hot water  is active     m    B    appears above the  4 icon  time based extra hot water  is active     NOTE       Extra hot water    usually means that the electric heater  is activated regardless of Allow add heat setting  menu       8 2 1  and therefore increases the electrical  consumption        Extra hot water    can be activated in three different  ways     1  Periodic time based extra hot water    Interval between extra hot water operation is selected  in menu 1 7  Menu 1 8 shows when the next extra hot  water operation is due     The increased temperature is maintained by the  electric heater for one hour     2  Schedule time based extra hot water    The start and stop times for the day of the week when  the extra hot water operation is required are set in the  sub menus to menu 7 4 0     The increased temperature is maintained by the  electric heater for the selected period     3  Temporary extra hot water    Extra hot water operation starts when Extra hot water  button is pressed  and it is kept for 3 hours  The  operation is cancelled when the button is pressed  again during the period    The increased temperature is maintained by the  electric heater until the period of time has expired     NOTE    Heat pump will not start until Extra hot water       period finishes  It may cause insufficient hot    water supply if big dema
47. s    button  the numerical value starts to flash       Increase or decrease using     or     buttons   h  ine OY    Confirm by pressing button       Menu 1 0 is automatically displayed again 30 minutes    after the last button is pressed     Example    Changing the heating curve  menu 2 1     1     2     3     The starting point is menu 1 0     Press     button to move to menu 2 0          Press   button to move to menu 2 1   h        Press    button to change the value        Change the value by pressing     or 6 buttons     Confirm the selected value by pressing    button     Press     button to access menu 1 0     Menu tree    1 0  N  Hot water temp   1 1  N  Max HW Peroid time       1 2  N  Start temperature HW       1 3  N  Stop temperature HW       1 4  U  Stop temperature XHW       1 5  U  Heat pump stop XHW       1 6  U  Max heat p  time XHW       1 7  U  Interval XHW       1 8  U  Next XHW action       1 9  U  HW run time          1 12  N  Return          2 0  N  Supply temp     2 1 0  N  Heating settings    2 1 1  N  Offset heating Total       2 2 0  N  Cooling settings    2 1 2  N  Heating curve       2 1 3 0  U  Own heating curve    2 1 3 1  U  Supply temp at  20    Control       2 1 4  U  Min supply heating    2 1 3 2  U  Supply temp at  20          2 1 3 4  U  Supply t  at buckl                 2 1 3 3  U  Buckling temperature          2 1 3 5  U  Return          2 1 5  U  Circ pump speed heat       2 1 6  N  Return       2 2 1  N  Offset cooling Total       2 3
48. tact  for example  a room thermostat   accessory  or a timer allows you to temporarily or periodically  raise or lower the room temperature  When the external contact  is closed  the heating curve offset or the cooling curve offset is  changed by the number of steps shown here     If room control is active there is a degree change to the set  room temperature     Setting range   10     10    Menu 3 6 0  U  Own heating curve 2    Here you can select your own curve definition  This is an  individual linear curve with one break point  You select a break  point and the associated temperatures    Note  The heating curve in menu 3 2 must be set to 0 to  activate this function     28    Menu 3 6 1  U  Supply temp at  20    The supply temperature at an outdoor air temperature of   20   C is selected here     Setting range  0     80    C      Limited by menu 3 4 Max supply temp  2   Menu 3 6 2  U  Supply temp at  20    The supply temperature at an outdoor air temperature of  20   C  is selected here     Setting range  0     80    C      Limited by menu 3 4 Max supply temp  2   Menu 3 6 3  U  Buckling temperature    Here you select at what outside air temperature the break point  shall occur     Setting range   15    15   C    Menu 3 6 4  U  Supply t  at buckl    You set the calculated supply temperature for the break point  here     Setting range  0     80    C      Limited by menu 3 4 Max supply temp  2   Menu 3 6 5  U  Return   Return to menu 3 6 0    Menu 3 7  U  Supply Return temp
49. the  outdoor temperature can be determined by you by selecting a    heat curve and by using the    Offset heating curve    knob on the  heat pump   s front panel     Operating status  The    Operating mode    button is used to set the required  operating mode     The change does not need to be confirmed with the  enter button     The current operating mode is shown on the front panel display  when the button is pressed and the mode changes when you  continue to press the button     The display returns to the normal display mode once the enter  button is pressed     The electric heater is only used for anti freeze if it is deactivated  in the menu system for all operating modes     There are different operating modes to choose     10    1     Auto       Indoor unit automatically selects the operating mode by  taking the outdoor temperature into account  This means  that the operating mode switches between  Heating  and     Hot water        The circulation pump is permitted to operate when there is  a need     2     AutoC        Indoor unit selects operating mode automatically  cooling  can also be selected now  by the outdoor temperature  This  means that the operating mode switches between    39 66       Heating        Cooling    and    Hot water        The circulation pump is permitted to operate when there is  a need     3  Heating  Only heating and hot water mode     The circulation pump is in operation the entire time   Electirc heater is energized if necessary     4  Coo
50. ting mode button    for 7 seconds     Note that this is only a temporary solution  as heating with the  immersion heater does not make any savings     Emergency mode    Emergency mode is activated by setting the switch to    ASV    It is used when the control system and thereby operating mode      Add  heat only    do not function as they should  Emergency   mode is activated by setting switch  SF1  to    ASV    The following applies in emergency mode    m The front panel is not lit and the control computer in  indoor unit is not connected    m  Outdoor unit is off and only the circulation pump and  immersion heater in indoor unit are active    m An electrical step of 4 kW is connected  The immersion  heater is controlled by a separate thermostat  BT30      m The automatic heating control system is not operational  so  manual shunt operation is required  Call installer     18    Alarm indications    There are many monitoring functions integrated in Hydrolution   To alert you to any malfunctions  the control computer  transmits alarm signals that can be read from the front panel  display     What happens in the event of an alarm     The background lighting in the display starts flashing and  the status lamp lights red     Some alarms change operating mode to    Add  heat only      and reduce the supply temperature to the minimum  permitted temperature to notify you that something is  wrong     Alarm indications    Different types of alarms    m Alarms with automatic reset  do 
51. to indoor unit     This eliminates the need for holes and coils in the ground     Features of Hydrolution   m Optimal annual heating factor thanks to the inverter  controlled compressor    m Outdoor unit with compact dimensions     m Speed controlled system pump that supplies the heat pump  with suitable system flow     m Optimized operating costs  The speed of the compressor is  adjusted according to the demand     m Integrated coil water heater in indoor unit     m Integrated clock for scheduling extra hot water and  temperature lowering increasing the supply water temperature     m Prepared for control of two heating systems   m Integrated active cooling function     m Possible to connect external heat sources     Information about the installation    Principle of operation Hydrolution                                                                         7  Function    Hydrolution is a system that can produce heating  hot water  and cooling     The principle during heating can be simplified as follows     1  The refrigerant in outdoor unit takes the heat from the  outdoor air and is compressed to higher temperature by the  compressor     2  The hot refrigerant  now in gas state  is routed into indoor unit     The refrigerant releases the heat for further distribution in  the system     4  The refrigerant  now in liquid state  is routed back to  outdoor unit and the process is repeated     By reversing the entire process  and thereby the refrigerant in  outdoor unit takes
52. ump  in  auto mode  is to stop heat production     When the average outdoor air temperature falls below Stop  temp  heating     Hysteresis  menu 8 2 5  heating starts again     Setting range  1     43   C    Menu 8 2 4  U  Start temp  cooling    The average outdoor air temperature at which the heat pump  in  autoC mode  is to start cooling     When the average outdoor temperature exceed it  cooling  starts     When the average outdoor air temperature falls below Start  temp  cooling     Hysteresis  menu 8 2 5  cooling stops     Setting range  10     43    C      Operable temperature range is 15     43   C   Menu 8 2 5  U  Hysteresis    See menu 8 2 3 and menu 8 2 4  Also affects control with room  sensor     Setting range  1 0     10 0    Menu 8 2 6  N  Return  Return to menu 8 2 0     Menu 8 3 0  U  Current limiter   Settings and readings regarding the load monitor are set in the  sub menus to this menu    Menu 8 3 1  U  Fuse size   The setting selected on the PCB  AA22  switch  R24  is shown  here    Menu 8 3 2  U  Max  electric power   The setting selected on the PCB  AA22  switch  R25  is shown  here    Menu 8 3 3  U  Current phase 1   Measured current from phase 1 shown here  If the value falls  below 2 8 A    low    is displayed    Menu 8 3 4  U  Current phase 2   Measured current from phase 2 shown here  If the value falls  below 2 8 A    low    is displayed    Menu 8 3 5  U  Current phase 3   Measured current from phase 3 shown here  If the value falls  below 2 8 A   
53. vel for the supply temperature to the  cooling system is shown here    The calculated flow temperature never drops below the set  level irrespective of the outdoor temperature  cooling curve or  its offset                             HMA100   HMS140VA   HMS140V  Setting range    C  7 25 7 25 7 25     Default value    C  10 18   18        1 It is necessary to adjust the value for fancoil application   Recommended value is 10      2 Do not set the value lower than 18  C  It may cause water  leak and damage your property or the product itself     Menu 2 2 5  N  Circ pump speed cool  The speed of the circulation pump during cooling is selected  here     Setting range  1     100    Menu 2 2 6  N  Return   Return to menu 2 2 0    Menu 2 3  U  Max supply temp    The set maximum level for the supply temperature to the  heating system is shown here     The calculated flow temperature never exceeds the set level  irrespective of the outdoor temperature  heating curve or offset  heating curve     Setting range  25     65   C    Menu 2 4  U  External adjustment    Connecting an external contact  for example  a room thermostat   accessory  or a timer allows you to temporarily or periodically  raise or lower the room temperature  When the external contact  is closed  the heating curve offset or cooling curve offset is  changed by the number of steps shown here     If room control is active there is a degree change to the set  room temperature     Setting range   10    10    Menu 2 5  U  Su
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
SBS Aero  OPERATORS MANUAL - Great Plains Manufacturing  secadora    instruction manual bedienungsanleitung manuel d'utilisation  Philips MCM1120    Brookstone 741507 User's Manual  manuel_riviera_&_bar&_791& a  Manuel de l'utilisateur User Manual    Copyright © All rights reserved. 
   Failed to retrieve file