Home
        SattTop®
         Contents
1.      Built in solenoid valves eliminate the  need for solenoid valve cabinets     CE approved        Configuration overview    Host control system  RS485G    PC with PCDoc    SattTop   STC  SattTop PS2 SattTop OP2  power supply g          SattTop Trunk cable    SattTop junction box SattTop connection box SattBus    ajil       SattTop SattTop nt a  valve box I O box F   le    SattTop Trunk    Field units cable branch SattTop Valve units       Data concentrator  SattTop STC is the link between the Dimensions  SattTop STC host control system and the SattTop All dimensions are given in mm   system  It has the following major    functions    e A data concentrating function which  collects the current values of  variables and parameters from  SattTop field units thereby allowing a  host control system to read and  change the values of the variables    e A SattBus supervising function      initiating SattBus communication      establishing token passing      supervising SattBus communication    collecting data from field units      distributing data to field units           xev  1 2 3 4 5 6 7 8  ver    o ae    The SattTop STC communication  hardware comprises a RS485G  interface for serial line communication  to host control system  with a selectable  baud rate between 2400 and 9600           Operator s panel   SattTop OP2          OOO    QOOO  O00           1 0     SattTop OP2 has the following major   functions    e  An operator function to examine and  change variables and parame
2.  0 86 g  0 17 g rms  Humidity  Amplitude Max  0 45 mm  Cyclic IEC 68 2 30    Life test  25   55  C  5 cycles   Spectra 10 20 Hz  5 0 x 10   g2 Hz  Operating IEC 68 2 3   oe 20   500 Hz   3 dB octave   40  C  96h  93   R H    cceleration Max  3 1 g  0 61 g rms      Amplitude Ma En Protection class IP 67    Technical data for Valve Top Unit  SattTop LKT S    Compressed air Solenoid valves  Pressure Max  1 MPa  10 bar   Available voltage 24 V DC   Particle size Max  0 01 mm  Power consumption Max  4 W   Oil content Max  0 08 ppm  Optional function Manually operated   Dew point of compr  air Min  10  C below amb  temp  Protection Not earthed   Water content Max  7 5 g kg air  Materials  Connection R 1 8   BSP   OD 10 mm tube  Black plastic parts Reinforced PA 6  polyamide   ID 6 mm tube  Red plastic parts POM  polyacetal     Position sensors Activating stem for  Type Hall element sensors  SMP EC valve Acid resistant steel AISI 316     Signal output On off digital  Seals for SMP valve stem EPDM rubber   Supply voltage 8 30 V DC  Other seals EPDM  NBR  nitrile   SEBS  Supply current Max  25 mA   Thermo plastic elastomer    Output PNP open collector  Electronic parts IP67 protected    max  100 mA     Technical data for Valve box  SattTop VB1 and VB2    Power supply  Trunk Cable  Sensitivity to electrical interference  Voltage 20 to 32 V DC  max  36 V DC  Burst test trunk cable IEC 801 4 2 kV Level 3  Supply current  electr   35 mA  no output load  Burst test feedback cable IEC 801 4
3.  1 kV Level 3  Total current 45 mA  one solenoid activ    Electrostatic discharges IEC 801 2 8 kV   Air supply Input  feedback   Pressure Max  1 MPa  10 Bar   Supply voltage to sensors 19 to 24 V DC  Particle size Max  0 01 mm  Max  feeding current con   Oil content Max  0 08 ppm  tinuous 15 mA    Dew point of compr  air   Min  10   C below amb  temp  ae ea eta 60 mA    Input voltage level ON 15 to 30 V          Water content Max  7 5 g   kg air     Air inlet connection Quick coupling     8 3 mm   Camozzi 5053 1 8   or comp    Input voltage level OFF Oto5V    Number of outputs 1or2 Feedback cable Max  1m    Nominal orifice 1 2mm  QNn 45 l min    Air outlet connection Quick coupling   Camozzi 5450 6 4   or comp          Technical data for I O box  SattTop I O  Power supply  Trunk Cable     Voltage   Supply current   Total current  Inputs    Input impedance  24 V AC DC  48 V AC DC   110 V AC DC  220 V AC DC    20 to 32 V DC  max  36 V DC   35 mA no output load   55 mA  two relays activated       typical      Allowed input voltage DC    24 V AC DC  48 V AC DC       30 V to  30 V max      60 V to  60 V max     Allowed input voltage AC    24 V AC DC  48 V AC DC  110 V AC DC  220 V AC DC    Technical data for power supply  SattTop PS2    Parallell serial  connection    Mains voltage  Mains voltage range    Output voltage  Fuse    Ripple and noise  Input regulation  Load regulation   0   100    Over current protect   Over voltage protect   Gavanic isolation  Input   output  Input   
4.  EN 55022 B conducted   VDE 0871 B     IEC 801 2  4 and 5  EN 61000 4 2   4 and 5 as of Jan 1 st  1997      IP20  1 1 kg       Tin coated Cu 7 x 0 31  PVC insulation  Tin coated Cu 7 x 0 67  PVC insulation    PVC 9 7 mm shealth        Ak ED ED  FADED    Regional Center Sweden  Vasteras  Sweden   Phone   46  0  21 34 20 00  Fax   46  0  21 13 78 45       Internet   www abb com    Regional Center Americas  Wickliffe  OH  USA   Phone   1  440  585 8500  Fax   1  440  585 8756    Regional Center Germany  Mannheim  Germany  Phone   49  0  1805 266776  Fax   49  0  1805 776329  Email  Marketing Control Products de abb com    00000  AE Andersson Grafiska AB  Printed in Sweden 2000     Specifications subject to change without notice   Printed in Sweden     2000 ABB Automation Products AB  All rights to trademarks reside with their respective owners     493 0488 11  0005 v  5 1    
5.  units to the trunk cable    The T connector is to be used on  single valves  For valve clusters     see  the SattTop junction box    The T connector consists of the  SattTop drop cable and a T piece   enclosed in a moulded plastic cover   This  together with gaskets  provides a  watertight seal when the two halves of  the connector are clamped and screwed  together        The T connector is not to be installed  where there is a risk of direct exposure  to high pressure washing    The four exposed leads of the trunk  cable are pressed into the slots of the  T piece to ensure correct connection    The SattTop drop cable length is  either 0 4  2 or 3 metres  A screw  connector is used at the SattTop EU end  to provide an easy to install  watertight  connection     SattTop termination plug       A SattTop termination plug is used to  terminate the SattBus  The SattBus  must be terminated at both ends    Using a termination plug instead of a  permanent bus termination makes it  easier to rearrange the bus system and  move the termination     SattTop connection box       The SattTop connection box is used for  cable joining  branching and trunk end  termination    The box has five watertight cable  entries and a 6 way screw terminal  block    A 100 Q resistor is supplied for use  when the connection box is used for  SattBus termination     Dimensions  All dimensions are given in mm       210               Hole pattern             h       Technical data for Data concentrator  SattT
6. OQ        oO   a      gt    is m  S   S          z w   fi  o              See the SattTop User   s Manual for  detailed instructions     Power supply   The Electronic Unit  SattTop EU  the  components inside the box  feedback  sensors and solenoid valves  are  powered from the SattTop trunk cable     Dimensions  All dimensions are given in mm        107                                              Applications   SattTop VB can be used in three  different ways  Either an object error  alarm based on one output and two  feedbacks to and from one object        Or an object error alarm based on two  outputs and two feedbacks to and from  one object        Or an object error alarm based on two  outputs and two feedbacks to and from  two objects     SattTop EU    I O box  SattTop I O       SattTop I O is a relay module in the  SattTop system for remote control   The box is equipped with the  Electronic Unit  SattTop EU   SattTop I O has the following major  functions      Two relay contact outputs  250 V  2 A     Four versions of optocoupled inputs     with two 24 V AC or DC     with two 48 V AC or DC     with two 110 V AC  or    with two 220 V AC     Detachable screw terminal blocks    LED indicators  Five LEDs are visible through the box  cover  In A  In B  Out A and Out B show  the status of the inputs outputs    The flashing RUN LED indicates that  power is applied and the microprocessor  is in run mode     Connections to the trunk cable  and the process   A function block diag
7. The SattTop System is a distributed I O  system with unique functionality  leading to cost savings during  installation and in a reduced  commissioning time  It has open  communication to a number of major  PLC DCS manufacturer   s products    The SattTop system provides data  communication facilities and local  interface units for control of valves   motors  control panels etc    A Data Concentrator  SattTop STC   connects the I O system to the host  control system via a Serial link     SsattTop     Distributed I O    The Operator   s Panel  SattTop OP2   can be used to configure and supervise  the field units    The Configuration and  Documentation tool  SattTop PCDoc  is  used to facilitate the configuration and  documentation work for the  programmer    The following SattTop field units are  available       Valve Top Unit  SattTop LKT S     Valve box  SattTop VB      I O box  SattTop I O     Each field unit is equipped with an  Electronic Unit  SattTop EU    The field units are connected via a  SattTop trunk cable  a four core cable  with two wires for communication and  two for power supply    SattTop OP2 and STC are also  connected to the trunk cable        SattTop has the following main features        Lower installation costs     Up to 120 units on one bus       Open communication to major PLC   s     CE      Easy maintenance       Built in feedback functions      Less PLC programming which saves  memory capacity in the PLC system    e   PC based configuration tool   
8. als are compared and an alarm  signal is produced if a deviation is  detected  i e  an object error alarm     Power supply  SattTop PS2          ln  1       a  i    i    T    tat      hy E     The power supply  SattTop PS2 can  supply up to 120 SattTop field units in a  loop  Its output voltage  32 V DC  is  connected to the trunk cable through a  SattTop connection box or a screw  terminal    SattTop PS2 can operate from any  normal mains supply  115 230 V AC      Dimensions  All dimensions are given in mm           SS  SIMS             Hole pattern             257       _ gt           SattTop Accessories    The SattTop Accessories below are  required to construct a complete  SattTop system     SattTop trunk cable       The SattTop trunk cable is specially  designed and manufactured for the  SattTop system    The cable  which consists of four  wires in twin pairs  serves two  functions  The thin pair of leads  green  and yellow  are for SattBus  communication  The thick pair  blue  and grey  supplies the power to the  SattTop EUs  Both pairs are twisted to  reduce interference     Cable stripping tool       To make a connection between the  SattTop trunk and drop cables  the outer  insulation of the trunk cable must be  removed  The cable stripping tool  enables this to be carried out quickly  and without damage to the inner wires   The stripping tool can be set to cut  around and along the cable     SattTop T connector       A SattTop T connector connects the  SattTop field
9. chassis  Output   chassis    Max  27 V rms   Max  53 V rms   Max  132 V rms   Max  264 V rms     Not allowed   115 230 V AC  47 5 to 63 Hz     85 to 132 VAC  115 V  or  170 to 264 V AC  230 V      32 V DC  7 6 A     Located on the primary side   6 3 A 250 V slow      400 mVp p  Max  0 8     Max  0 9   Constant current limiting   12 A   Output shutdown     3000 V AC  1 min    3000 V AC  1 min    500 V AC  1 min      Technical data for SattTop trunk cable    4 wire cable  Cable       2x 2 5 mm    2 x 0 5 mm   Unshielded twisted pair  min  3 turns m    Outputs  Number of outputs  Continuous voltage  Continuous current  Control break load    2  Relay type    Max  250 V AC or DC    Max  2 A    Max  50 W  DC   1250 VA  AC     Nominal detecting threshold    24 V AC  24 V DC  48 V AC DC  110 VAC  220 V AC    ON  gt  15V  ON   gt  14V  ON   gt  34V OFF   ON  gt  79V OFF   ON   gt  164 V OFF     OFF   OFF     Signal delay due to input    filter    20 ms  typical      Sensitivity to electrical interference    Burst test trunk cable  Electrostatic discharges    Inrush current    Hold up time   Temperature  Operation  Storage   Relative humidity   Power dissipation   Safety    EMC  Emission  Immunity    Protection class  Weight    Conductor 0 5  Conductor 2 5    IEC 801 4  IEC 801 2    2 kV Level 3  8 kV       Max  15 A  115 VAC  and  max  30 A  230 AC      Min  20 ms      0 to  50  C      20 to  85  C   Max  90   non condensing   Max  40 W    IEC 950  EN 60950  UL1950   C UL1950  CSA    
10. ion and  documentation tool   SattTop PCDoc       SattTop PCDoc is a configuration and  documentation program designed to run  on a PC  It is delivered on a 3 5  disk  together with a SattBus PC board    SattTop PCDoc is used to create  edit   back up  verify  transmit and print a  SattTop configuration    A total configuration includes the  SattTop STC  all SattTop EU and an  additional project description    The link between SattTop PCDoc and  the SattBus network is an ABB standard  SattBus PC board  This board uses a  half size I O channel slot in your PC     Valve boxes  SattTop VB1  and VB2       SattTop VB is an electro pneumatic   remote controlled module  There are   two versions  VB1 with one solenoid   valve and VB2 with two solenoid   valves  Both versions are equipped with   the Electronic Unit  SattTop EU   SattTop VB has the following major   functions      Outputs with quick release air outlet  connectors    e Two current sinking inputs  24 VDC     type 1  in accordance with IEC TC 65       Sensor type input is current sourcing      PNP type             Inputs are not galvanically separated  from power line      Detachable screw terminal blocks     LED indicators   Three LEDs are visible through the box  cover  Out A and Out B show the status  of the solenoid valves  The flashing  RUN LED indicates that power is  applied and the microprocessor is in run  mode     Connections to the trunk cable  and the process   A function block diagram is shown  below     a   
11. ll valves        SattTop LKT S has the following   features       Up to 120 units can be supplied from  one trunk cable and one air tube      Open and closed valve positions are  indicated locally by two LEDs and a  visual valve stem extension  and can  be remotely supervised via SattBus  from SattTop OP2  PC with PCDoc or  a host control system       Two Hall type proximity switches  generate the feedback signals      The Valve Top units can be combined  with Valve box units  SattTop VB and  I O units  SattTop I O  on the same  trunk cable for control of other types  of valves  motors  etc       Assembly  adjustment  service  and  dismantling are simple procedures  requiring only standard tools      Protection class is IP 67     There are seven versions of SattTop  LKT S to be used with different valve    types   All units are equipped with the    Electronic Unit  SattTop EU     Dimensions  All dimensions are given in mm          Max  178    110                Cutaway view   Valve top unit LKT S for SRC  SMP SC   SMP BC and ARC valves is shown  below     OH          S  z NI      97 N                1    D N   as N   yl oi   apa   et    gt  ME    Des     77772  hae    1 Quad ring between base and actuator  2 Base with solenoid valve es  3 Housing with screws  4 Frame with Hall element sensors  5 Activator stem extension  6 O ring between housing and stem  7 SattTop EU  8 Drop cable connector  male  9 O ring between housing and base  10 Retainer for stem             Configurat
12. llen Bradley  Siemens     Screened multi core   Max  1000 m      0 to  55       25 to  70   C    10 to 95   non condensing   IP 20    Fulfils Electro Magnetic  Compatibility  EMC  directive  89 336 EEC     Technical data for Operator   s panel  SattTop OP2    Display  amp  Keyboard 4 x 40 characters  26 keys  Temperature  Power supply 24 V DC  20 to 32 V DC   Operating  0 to  50  C   Power consumption 8 W  24 V DC   Storage  25 to  70  C     Communication SattBus connector  Attachable Relative humidity 10 to 95   non condensing   4 pole screw terminal  Protection class Front IP 65  mounted in panel    SattBus channel Other sides IP 20     Transfer rate 62 5 kbits s  Electrical environment IEC 801 4      l l 2 kV  other 1 kV   Cable Unshielded twisted pair POM ETE RY  min  3 turns m  IEC 801 2  8 kV     Characterist  impedance 80 150 Q  Mounting panel aperture 205 x 205mm  1 mm     Area  gt 0 20 mm   AWG 24   Cable length Max  1000 m        Technical data  common for SattTop LKT S  SattTop VB and SattTop I O    Temperature Transportation l g  Operating IEC 68 2 1 2  5 to  55  C Spectra st 2 is o 3 3 ge ae  Storage IEC 68 2 1 2    25 to ee Point 3  16Hz  10x103 g  Zi   Temperature change IEC 68 2 14  25to 70  C Point 4  40Hz  1 0x10   oe  Hz     Vibrations IEC 68 2 36 Point 5  80Hz  1 0x10  95  Hz   Functional test Point 6  200Hz  10x108 g  Hz    Spectra 10 20 Hz  4 0 x 104 g2 Hz  Acceleration Max  2 6 g  0 52 g rms     20 500 Hz   3 dB octave  pinputnde Meee  Acceleration Max 
13. op STC    Power supply  Power consumption  Memory backup    Communication    SattBus channel    Transfer rate  Cable    Characterist  impedance  Area  Cable length    24 V DC  20 to 32 V DC    5 W  24 V DC      The configuration is retained at  power down  capacitor back   up  for at least 24 hours   SattBus connector  Attachable  4 pole screw terminal    Serial channel RS485G    and RS422   25 pole D sub  connector  Canon      62 5 kbits s     Unshielded twisted pair   min  3 turns metre     80 150 Q    gt 0 20 mm2  AWG 24   Max  1000 m     Serial channel  Baud rate    Fixed parity    Cable   Cable length  Temperature   Operating   Storage    Relative humidity    Protection class       Fixed parameters    Electrical environment    SattTop junction box  The SattTop junction box is similar to  the connections box and used to connect  SattTop field units in valve clusters   There are three types of junction  boxes  for either 3  6 or 20 junctions  A  drop cable  2 metres  is used to connect  a SattTop field unit to the junction box           Dimensions   All dimensions are given in mm      210 280 400    D     a H g       o  8    D 0 g          60 60 100               Hole pattern    O  45 45 170 a                     NOTE  The first measure applies for a  junction box for 3 valves  the second for    a junction box for 6 valves  and the third  for a junction box for 20 valves     148 218 370    9600  4800 and 2400 baud   8 data bits  1 stop bit     Odd  COMLI  Modbus    Even  A
14. ram is shown  below  The inputs and outputs are  sourced externally     SattTop   drop cable  SattTop EU       See the SattTop User   s Manual for  detailed instructions     Power supply   The Electronic Unit  SattTop EU and  components on the PC board  relays and  LEDs  are powered from the SattTop  trunk cable     Dimensions  All dimensions are given in mm     150                      oO  ae     Hole pattern  net     a mee         Applications   SattTop I O can be used in four different  ways  Either an object error alarm based  on one output and two feedbacks to and  from one object        lt    _   _                   Or an object error alarm based on two  outputs and two feedbacks to and from  one object     SattTop EU    Or an object error alarm based on two  outputs and two feedbacks to and from  two objects     SattTop EU    Or a no object error alarm with two  separate outputs and two separate    inputs     Object 1   lt   Object2  SattTop EU    gt  Object 3  Object 4    a    Electronic Unit  SattTop EU       Each field unit includes a SattTop EU   which is mounted on the side of the unit   SattTop EU transmits and receives the  variables and parameters via SattBus  It  controls signals for the solenoid valves  and monitors the feedback signals  indicating the conditions of the valves     LED indicators   Two LEDs  A and B  normally indicate  the status of the feedback signals  but  also provide error indication under fault  conditions  The control and feedback  sign
15. ters in  SattBus modules such as SattTop  LKT S  SattTop VB  SattTop I O or  other field devices using SattTop EU       Displaying variables parameters in  the SattTop units       Changing variables parameters in the  SattTop units     The SattTop OP2 communicates with  the field units via SattTop trunk cable     Dimensions  All dimensions are given in mm     So             ef       Se  che  SS          CR     OLLA                 Keyboard and display   SattTop OP2 is equipped with a 4 x 40   character display and a 26 key  membrane keyboard    Plastic covered slots on the membrane  keyboard allow labels to be fitted above  the function keys    The SattTop OP2 is an operator  interface which includes a configuration  tool to configurate the SattTop field  units and the data concentrator function  in the SattTop STC unit    Most of the SattTop OP2 function  setup can also be performed by using the  Configuration and Documentation tool   SattTop PCDoc     Operator interface   The operator can at any time display the  variables and parameters stored in a  SattTop field unit  At this access level  some variables can be examined and  changed but parameters can only be  examined  The variables in the SattTop  modules are stored in RAM        Valve Top Unit   SattTop LKT S    The Valve Top Unit  SattTop LKT S  is  an electro pneumatic remote controlled  module  It can be mounted on the LKM  valve types SRC  ARC  SMP SC EC   BC TO and on the actuator type  LKLA T for butterfly and ba
    