1. Parameters Parameter Description Roller blind master uae a zE RE EEE Seiected D MMN N mm Not selected N Not changeable D EA Ea Ea a Operation mode E 3 fe F t s 4 t s Simultaneously Sequentially Cal Je i a H E E E Eea 2s J ed ad Reverse Up time a 2 2 Bt L 005 Seconds ra a a a E E E E E E E Pr Operation mode The setting determines whether the roller blinds are started simultaneously or sequentially With the setting Sequentially the roller blinds start and stop suc cessively at 1 second intervals This time interval is also observed in connection with change of direction or tilting blind Reverse Up time This time interval does not affect the set roll time Roll time The roll time determines for how long the roller blinds must run This roll time overrides the roll time set in the Decentral up down roller blind control Reverse Up time The Reverse Up time determines the time in seconds for which the roller blinds must run in the opposite direction after expiry of the roll time Applies to tilting blinds Note The Controller only executes the Reversing function in decentral roller blind controls in which the option adjustment of Tilting blinds has been activat ed 62 2002 Carlo
2. Alarm signal delay With this setting you can determine the time which is to elapse from the alarm siren is activated till the alarm signal is activated The value can lie between 0 and 10 min 2002 Carlo Gavazzi Industri A S All rights reserved 47 G 3800 X015 Configuration Software October 2002 Time characteristics Passive detector IN Passive detector OUT Manual armouring IN Manual armouring OUT Alarm siren glar_ta Alarm signal PMan_TBur t th be The above illustration shows the normal sequence of an alarm as well as early acknowledgement and the switching of the system back into the alert state through the Manual Armouring option t When the Master Generator is switched on the alarm system becomes alert through activation once of the Manual Armouring function tz An alarm contact is activated eg by the opening of a secured port Since the armouring delay Try in this example has not yet elapsed nothing happens at first ts After elapse of the armouring delay Try the alarm is started ie both the channel of the alarm contact and that of the Manual Armouring start to flash ty After elapse of the de armouring delay Tav the Master Generator activates the alarm siren ts After elapse of the siren time Ta the alarm siren channel is deactivated The flashing of the alarm contact and the Manual Armouring output continues
3. With this setting you determine the time to elapse after switching on of the alarm siren till the alarm signal is activated The value can lie between 0 and 10 min 2002 Carlo Gavazzi Industri A S All rights reserved 41 G 3800 X015 Configuration Software October 2002 Time characteristics Passive detector IN Passive detector OUT Reset IN Reset OUT Siren Tm Alarm signal t h t t f te ae The above illustration shows the normal sequence and reset of an alarm t When power supply is connected the system becomes alert after elapse of the set reset delay Tr indicat ed by reset of the reset output to After a short delay approx 3 s after the occurence of a fire activation of the Passive detector the alarm is started This takes place by the alarm siren flashing and by output of the Passive detector channel whereby the alarm source is indicated ts The channel generator activates the alarm signal channel after elapse of the set alarm signal delay Tu t4 By activation of the reset button the alarm siren and the alarm source indication are reset although the alarm source Passive detector is activated as before The reason is that the Master Generator ignores all alarm sources during the reset delay ts By removing the smoke from the smoke detector the Passive detector opens again and deactivates the alarm channel ts After elapse of the res
4. consequently transmitted on the Dupline bus an alarm is started Reset This object makes it possible to include a button to reset the alarm and restart the R i system __ If a contact is activated during reset a new alarm is started after elapse of the reset delay Note This object must be configured in order to achieve correct function of the smoke alarm system The siren indicates that an alarm has occurred The channel configured with this object can be used to output the alarm on any output modules It usually activates a relay output through which a siren is switched Alarm siren gt Note The alarm output basically flashes When an alarm occurs a channel configured with this object is activated for 10 s and can thus be used to activate a telephone or GSM modem Alarm signal gt 2002 Carlo Gavazzi Industri A S All rights reserved 39 G 3800 X015 Configuration Software October 2002 Parameters Parameter Description Passive detector Channel function Disable address Passive detector Io C Active detector at C Reset C Alarm siren Alarm signal Disable address Enter an address A1 P8 or a flag W1 Z8 whose activation 1 signal will leave out the Passive detector function of the monitoring system whereby it cannot trig ger off any further alarms Active detector Channel function Disable address Passive detector bs Active detector ae Reset C Alarm siren
5. No of channels For selection of the number of channels desired in the system The minimum is 8 the maximum is 128 in one Dupline network Auto start Dupline on short circuit In case of a short circuit on Dupline the Generator shuts down the Dupline signal Under default conditions power off followed by power on needs to be performed to reset the Generator after removal of the short cir cuit However if the Auto start Dupline on short circuit box is checked then the Generator will automatically start up the Dupline signal after removal of the short circuit Enable automatic update of realtime status upon Config download and System power up If this box is checked the Generator will automatically set the correct status for realtime channels according to the switch time settings provided that the actual Day of the week matches the internal Day of the week of the Generator Also the Generator will only scan the switch times ON or OFF for that same day Enable Automatic Daylight saving Central European Time standard If this box is checked the Generator will automatically change the time settings 2 times per year according to the European standard for daylight savings Enable RTC Powerline Autocalibration Selecting Auto calibrate will enable the internal Realtime clock to adjust its internal calibration against the Mains supply frequency In most countries the Mains supply frequency is very accurate and in that case an improved acc
6. Analog sensor Analog signal out A3 Temperature sensor put and switching channel for the relay of the heating valve Real time clock Timer for night A4 setback 2002 Carlo Gavazzi Industri A S All rights reserved 29 G 3800 X015 Configuration Software 2 3 2 Motion detector Description Parameters Function Includes motion detectors or similar input modules in the Dupline system October 2002 Application Control of lamps and integration in the intruder alarm system Off time adjustable from 00 h 00 min 00 s to 99 h 59 min 59 s Variable number of movement impulses helps to avoid false alarms in the intruder alarm Select with mouse Motion detector The object Motion detector makes it possible to include Dupline Passive Infrared Detector PIR eg G8910 1127 and conventional motion detectors which are connected to the Dupline bus via binary inputs The PIR detector can have an off time defined and be integrated in the intruder alarm system Thereby it becomes possible avoid false alarms by setting the number of impulses which must be detected within a 10 s time window before the alarm starts Note If you want a PIR detector to generate the off time indepedently the object Push button function should be used The off time of G8910 1127 can be operated through DIP switches Configuration window of Motion detector Use in
7. Counter No of values O16 Multiplexer delay o Counter range Counter ranges With this setting made under lt Edit gt lt Counter And Mux Analog Setup gt you select the range of counter values Depending on the range a coresponding number of channel groups beginning by B are reserved Reserved groups None counter operation switched off 0 99 B C 0 9999 B D 0 999999 B E 0 99999999 B F Application Example Task On a camping site 64 current values are to be detected and used on a PC for the issue of invoices Solution The counter modules G4420 7401 are built into the local power cabinets Four Dupline energy counters supply one G4420 7401 with the corresponding impulses The Master Generator is configured for Counter setup through entry of the counter ranges A data entry software avail able through a DDE interface reads out the values via the DDEServer and resets the counter value when a new guest arrives The voltage of the individual power outlet is turned on from the PC through a relay module software DP Camp Free channels are used for this purpose The applied Master Generator can of course also perform additional automation functions Object Function Channel In outputs Counter input Detection of B1 F8 impulses from energy counter Relay output Switching power G1 N8 outlets Configuration of Master Generator Counter ra
8. Disable address Enter an address A1 P8 or a flag W1 Z8 whose activation 1 signal will leave out the Passive detector function of the monitoring system whereby it cannot trigger off any further alarms 2002 Carlo Gavazzi Industri A S All rights reserved 35 G 3800 X015 Configuration Software October 2002 On delay Enter a time value in seconds 0 255 for which the alarm signal is delayed upon activation of the alarm contact Acknowledge No configuration possibilities Reset No configuration possibilities Lamp test No configuration possibilities Alarm siren Channel function Siren time C Passive detector C Active detector o2 Minutes C Acknowledge C Reset Lamptest Alarm siren Operation mode Standard a L Siren time This setting determines for how long the alarm output is to remain activated in the case of alarm The value can be between 0 and 60 min Note With the Minus key the time can be set to an indefinite time This is indi cated by Time characteristics Operation mode Standard Passive detector IN Passive detector OUT Acknowledgement Reset Alarm siren t t t 4 PMan_TISA_1a 36 2002 Carlo Gavazzi Industri A S All rights reserved G 3800 X015 Configuration Software October 2002 The above illustration shows the normal sequence and reset of an alarm
9. est address number eg B7 has priority over A5 will be applied e The master function cannot affect channels with advanced functions eg alarm channels or analog sen sors e A master function cannot activate another master function Parameters Configuration window of Master function In this example a real time clock is included and the option Enter Switch times mm a ch mol B A f AAO x 2 Tum On B 0 X x X x x xX x Tum Ot C X XX X X X x Xx X Do not change D X X O O x X Not changeable E IIE l El El i Tooge swi ggle switch F XX XX gt lt xX lt x Pindar Include Realtime G fe f x f fe et fe H x Enter Switch times ot l wal weal Wr C1 d d Switch time Switch time Days of week Hour Minute Hour Minute MT WTF SS H al a a a a a a a e n J A E E p il a Te is a Pee al CU CSU a S S a S L 22 2002 Carlo Gavazzi Industri A S All rights reserved G 3800 X015 Configuration Software October 2002 Parameter Description Address matrix Mark the addresses to be switched on by the master function with 1 and the addresses to be switched off with O Addresses marked with x are not affected Addresses which are automatically marked with a red line cannot be controlled by a master function eg master func tions roller blind controls etc Toggle switch If this function is selected the master function w
10. None 12 2002 Carlo Gavazzi Industri A S All rights reserved G 3800 X015 Configuration Software October 2002 2 2 2 The push button function e Function Monostable Ea e Application Connection of push button switches and contacts for load switching e Also Normally Closed function e Select with mouse Push button or short cut key 0 Zero Description The push button function the most simple object of the Dupline Master Generator makes it possible to connect any type of push button switch and contact to the Dupline bus With this function outputs can indi rectly be controlled with logic functions In this function the output follows the input signal the output is activated as long as the input signal is ON inverted in Normally Closed function Parameters Configuration window of push button function Basic Channel Operation JV Inverted function Parameter Description Inverted function When this function is selected the output signal is inverted This means that the output is activated as long as the input has not been set Time characteristics Normally Open Normally Closed OUT OUT t g 7 7 t 4 ty t3 PManTTast_1a t ty t3 PManTTast_2a The output follows the input upon a short delay In the Normally closed function the output function is the opposite of the input function 2002 Carlo Gavazzi Industri A S A
11. a DK DK DK DK DK DK DK DK DK DK DK DK DK DK DX DK Time to Data Clear oS ov Seconds Connected to Gen time 13 Parameter Description Clear data upon loss of radio communication Per default the substations maintain the last received Dupline output data no matter how long time has passed since the last telegram was received from the central master generator If Clear data upon loss of radio communication is checked then the output data will be cleared when the time out defined in Time to Data clear has run out Time to Data clear Defines the time out when Clear data upon loss of radio modem communica tion is selected 78 2002 Carlo Gavazzi Industri A S All rights reserved
12. object switches off The room temperature reaches the lower limit value again and the object switches on The Disable Address channel or flag is activated for example through a toggle switch Although the upper limit value is reached the object does not switch the channel on because the Disable address is active The temperature sensor switching channel does not switch off until the Disable address is deactivated 28 2002 Carlo Gavazzi Industri A S All rights reserved G 3800 X015 Configuration Software October 2002 Application Example Task A heating element is to keep the room temperature between 19 C and 21 C during daytime At night the temperature must be lowered by 4 C A temperature sensor located in the room is coded for address A2 and displays the tempera ture on a Touchscreen Solution Since the analog sensor value on A2 is already needed for displaying the temperature we assign the temperature sensor object and consequently the relay controlled by the heating element to address A3 For the night setback we assign a real time clock to A4 with the desired switching times The real time clock serves as an additional address for enabling the second pair of limit values Object Function Channel In outputs Temperature sensor Temperature A2 Relay output Heating valve A3 Configuration of Controller Analog sensor Transmission of A2 Temperature sensor analog value
13. 4520213324 It can be selected if an event based SMS message shall be sent out to all the telephone numbers on the list simultaneously or if it shall be sent to the telephone numbers one by one until an acknowledge is received The acknowledge is done by sending either a request or just an empty SMS message to the Generator 4 2 Event based SMS messages TE EB HB Ea F_ u bl ee il Me Description Intruder alamfromhal Jv SMS by On SMS by Off 2002 Carlo Gavazzi Industri A S All rights reserved 73 G 3800 X015 Configuration Software October 2002 If the SMS by ON box is checked the Generator will send an SMS with the time and date the identifying text the description text for the channel and the status whenever E1 becomes active The recipient of the SMS will see the following message in the display of the GSM phone 14 10 From 99999999 Test application 2001 01 31 03 36 E1 Intruder alarm from Hall On Answer If more dial out phone numbers have been defined an acknowledgement can be sent to the Generator by sending an empty SMS message back The Generator will then stop sending messages to the following phone numbers SMS messages for AnaLink channels contain the actual AnaLink value 4 3 SMS Control commands and Requests for Dupline data Commands for control or triggering of channel functions can be sent to the Generator vi messages Also it is poss
14. Alarm signal Disable address Enter an address A1 P8 or a flag W1 Z8 whose activation 1 signal will leave out the Active detector function of the monitoring system whereby it cannot trig ger off any further alarms Reset Channel function Reset delay Passive detector C Active detector fo Minutes Reset Alarm siren Alarm signal Reset delay The delay after which the system becomes alert or an alarm is suppressed upon activation of the reset button This function can be used to ensure that the mea suring chambers are completely emptied of smoke This time is also used in connection with downloading of the software and switch ing on of the channel generator 40 2002 Carlo Gavazzi Industri A S All rights reserved G 3800 X015 Configuration Software October 2002 Parameter Description Alarm siren Channel function Siren time Passive detector C Active detector jos Minutes Reset Alarm siren Alarm signal Siren time With this setting you determine the duration of the activation of the alarm output upon the occurence of an alarm The value can lie between 0 and 60 min The entered value is automatically adopted by the Common Siren Alarm signal Channel function C Passive detector C Active detector Reset C Alarm siren Alarm signal Alarm signal delay s Minutes Alarm signal delay
15. Counter amp Mux Analog Setup gt you select how many modules should be addressed The number depends on the number of applied modules and their in output channels From 0 to 16 addresses can be selected The value 0 switches the multiplex operation out Multiplex delay With this setting made under lt Edit gt lt Counter amp Mux Analog Setup gt you select how fast the Master Generator may scan the multiplex addresses This setting only has an effect when multiplex transmission has been activated at least 1 multiplex channel selected Since some of the Dupline Multiplex modules need a large part of their capacity for internal processing their response time is reduced This can be balanced by a longer delay The Master Generator then waits for the corresponding number of cycles between the scans 2002 Carlo Gavazzi Industri A S All rights reserved 67 G 3800 X015 Configuration Software October 2002 3 Logic Setup 3 1 Introduction The preceding chapters have illustrated the simplicity of configuring channels with the pre defined objects Praxis hower is not always so simple for example when the outdoor lamps must be controlled in relation to the time of day or the roller blinds in relation to light or weather or conditions The Master Generator offers a splendid tool for solving these tasks the logic functions with which any rela tion can be established between the individual channels The logic funct
16. Intruder alarm Off Time Hour Minute Seconds foo fos foo I Use in Intruder alarm No of Pulses foo2 Parameter Description Off time The time for which the channel remains activated 00 00 00 to 99 59 59 after a motion impulse has occured Each additional impulse will start the off time again When entering an off time of 00 00 00 the Master Generator generates a short output signal indpendently of the duration of the input signal Click in the check box in order to include the channel in the intruder alarm sys tem A signal from this channel will then also start the intruder alarm see chapter 2 4 5 Number of pulses The value entered here 1 255 determines how many impulses the motion detector may generate within 10 s before the alarm starts When an impulse is detected the Master Generator checks whether the number of impulses during the past 10 s has exceeded the set number If this is the case an alarm is generated in the connected intruder alarm system This setting thus reduces the risk of false alarms Note Since the signal output takes place subsequently an additional impulse is always needed This means that when the number of impulses is set to 3 the alarm will go off at the fourth signal The set off time has no influence on the alarm 30 2002 Carlo Gavazzi Industri A S All rights reserved G 3800 X015 Configuration Software October 2002 Time characteristics In the following
17. Substations Modem Turmatround Time 0100 a Milliseconds Substation Max Responce Time jor Seconds AM SA AN SA AN AN AN SA SN AN E E SNM M 7 3 Select groups for exchange of Mux analog AE AE SSO SE SE SE SO SE S0 E E SE IM M SA 7 AE SE SE SE SE SO GE GE SE GE E E SE M M A0 AE AY AD S0 AE AD SE S0 SE S0 E E bE M M S0 AE AY AD S0 AE S0 SE S0 SE S0 E E bE M M S0 Parameter File Edit Select Tools 1 2 3 A M MM B W a amp Ce ae D me me me E M M M F MMM G Afo Afo Afo H aA a a Afo Ao Afo a Ce cee me Aal Me ij a a Afo Afo Me K fo Afo Afo iE Me Me Me M Afo Afo Afo N fo Afo Afo 0 fo Afo fo P fo fo fo Connected to ID Number 1 via Com 1 Gen time 13 50 Date 11 13 2002 F C D M KL MEE M M N GH F lH r op Description Modem turn around time Defines the time delay the Master Generator uses when changing between receiving and transmitting This can be used to adapt to individual radio modem types which may have different requirements for this parameter The default val ue of 100 ms will work in most cases Substation max response time Defines the time the central master generator will wait for an answer from a sub station If the master generator does not receive an answer within this time it continues to the next substation The default time is 1 s which is fine for most applications but longer time may be needed if r
18. Triggering 70 3 3 3 Using flags 71 3 3 4 Internal processing of the logic setups 71 3 4 Notes and Documentation 71 4 GSM Modem functions only valid for G38001015 72 4 1 SMS Setup 72 4 2 Event based SMS messages 73 4 3 SMS Control commands and Requests for Dupline data 74 5 Radio Modem driver 76 5 1 General 76 5 2 Setup of Radio Modem Central 77 5 3 Setup of Radio Modem Substation 78 2002 Carlo Gavazzi Industri A S All rights reserved G 3800 X015 Configuration Software October 2002 2002 Carlo Gavazzi Industri A S All rights reserved 3 G 3800 X015 Configuration Software October 2002 1 Introduction The G38xx15 program has been designed for configuration of the G3800X015 master generator All functions in the generator are represented by graphic symbols To each channel function are related parameters and comments which can be edited locally in the PC and transferred to the master generator through RS232 Likewise data from the master generator can be uploaded and edited 1 1 Start up 1 1 1 Hardware requirements e The program operates under Windows 95 98 2000 xp and NT and requires at least 486 processor with 8 Mbytes Ram or higher A free serial port Com1 or Com2 5 Mbytes hard disk for installation Screen resolution of 800 x 600 pixels 256 colours or higher Mouse or other pointing tool desirable but not necessary 1 1 2 Installation Insert disk 1 in the A drive and run the program
19. deacti vated disable address has been entered Manual armouring thus partly enables alarms Upon activation of manual armouring the armouring delay begins to run During this time the channel generator ignores activated alarm contacts If subsequently an enabled alarm contact is activated this channel begins to flash and triggers off an alarm through the siren after elapse of the de armouring delay To acknowledge the alarm press the manual armouring key once To restart the alarm system press twice This object makes it possible to include a switch to activate the alarm system The function is similar to that of the manual armour ing only in door lock armouring the disable addresses entered at the alarm contacts are ignored This means that the switch per forms total enabling Upon activation of the switch the armouring delay begins to run During this time the channel generator ignores activated alarm contacts If subsequently an alarm contact is activated this channel like manual armouring begins to flash and triggers off an alarm through the siren after elapse of the de armouring delay The alarm is acknowledged by switching off the door lock armour ing The system becomes alert by renewed switching on This object can be used as an alternative to door lock armouring The mode of operation is identical since this object also performs total enabling of all also disabled alarm contacts The object awaits an impulse
20. from the code lock to make the alarm system alert An additional impulse is needed in order to acknow ledge an occuring alarm see manual armouring The alarm siren indicates that an alarm has occured The channel configured for this object can be used to output the alarm on differ ent output modules It usually activates a relay output through which a siren is switched The configuration also allows the alarm output to flash and makes it possible to determine additional channels which also flash When an alarm occurs a channel configured with this object is activated for 10 s and can thereby be used to activate a telephone modem or a GSM modem 2002 Carlo Gavazzi Industri A S All rights reserved 45 G 3800 X015 Configuration Software October 2002 Parameters Parameter Description Passive detector Channel function Disable address Passive detector laa Active detector Manual armouring Door lock armouring Code Lock armouring Alarm siren Alarm signal Disable address Enter an address A1 P8 or a flag W1 Z8 whose activation 1 signal will leave out the Passive detector function of the monitoring system whereby it cannot trigger off any further alarms Active detector Channel function Disable address Passive detector fs Active detector a Manual armouring Door lock armouring Code Loc
21. in the operation mode Standard ti When all contacts are in off position the Master Generator alerts the alarm system automatically upon loading of the application to After elapse of on delay Tev the Master Generator activates the alarm siren and causes the output of the source channel to flash ts By activation of the acknowledgement button the Master Generator switches the alarm siren off provided that the siren time has not elapsed and transfers the alarm source indication into a continuous signal t4 By activation of the reset button the alarm source indication turns off and the system is alert again Operation mode Auto reset Passitve detector IN Passive detector OUT Acknowledgement Alarm siren PMan_TISA_2a Lt 460 tbt t The above illustration shows the normal sequence and reset of an alarm in the operation mode Auto reset ti to ts ta ts te tz ts When all contacts are in off position the Master Generator alerts the alarm system automatically upon loading of the application If a contact is subsequently activated initially nothing will happen because of entered on delay Tev After elapse of on delay Tev the Master Generator activates the alarm siren and causes the output of the source channel to flash After elapse of the siren time T and reset of the alarm contact the Master Generator switches the alarm siren off Acknowledgement dea
22. izo a3 Scaled nalink value 22 2 Digital Status On In general the operation of sensors depends on the purpose of using the values Showing data on PC Touchscreen or Text display In this case the parameters Control output and Alternative input should not be activated because in that case the analog value will only be transmitted and not displayed Finally the measuring range should be con figured with minimum and maximum values eg 30 C and 60 C Hint In this operating mode limit values can be set It is also possible to use the switching commands of this channel as input in logic functions without activating the parameter Control output Switching an electrical load by means of the sensor For this purpose the parameter Control output must be activated in order to output the set limit values This output function causes a switching command on this channel and thereby an output eg relay on the same address The sensor is to be configured as follows 1 Enter the measuring range of the sensor stated directly on the sensor or in the user manual e g 30 C and 60 C 2 Enter the switching range at which the object switches on or off Standard setting gives the threshold value Off lt Limit and On gt Limit This means that the channel switches off when the analog value drops below the first entered value and the channel switches on when the analog value exceeds the
23. mouse button The channel is thereby assigned a symbol indicating the selected channel function Click on the symbol with the left mouse button and the parameters which can be set for that particular channel function can be viewed in the properties window The arrow keys can also be used to select channel function in the pop up menu Furthermore channel func tion can be selected by clicking on different letters To see how to select functions by clicking on letters select the General information menu under Help Tool tip When the cursor is positioned on a channel button a bar appears indicating channel number describing channel type and showing the user defined channel description T S as chee RG B INN 2002 Carlo Gavazzi Industri A S All rights reserved 9 G 3800 X015 Configuration Software October 2002 1 3 Basic Setup x General description Demo Project for Smart House Garlo Gavazzi Ocktober 2002 No Channels fize x JV Auto start Dupline on Shortcircuit r Enable automatic Update of Realtime status upon Config Download and system Power Up Vv Enable Automatic Daylight saving Central European Time standard J Enable RTC Powerline Autocalibration Syncronize Time to Thursday 17 oktober 2002 12 57 General description The text window is for entering general information eg name of user date of configuration reference to docu mentation etc
24. reserved G 3800 X015 Configuration Software October 2002 2 3 Special objects 2 3 1 Analog sensors e Function Transmission and output of analog values from temperature light and other sen sors to perform switching functions e Application Display of analog AnaLink values on text display touchscreen load switching for example heating elements lamps roller blinds in relation to temperature or outdoor light etc Readout at any time of analog values in relation to external values Up to two switching ranges can be defined on each channel Disabling of switching operations through an additional channel or flag Select with mouse Analog Sensor Description The objects of the analog sensors offer the possibility of integrating analog measuring devices in Dupline and processing their values It is possible to select among four types of sensor functions Measuring sensor General sensor object with which all the other sensor types can be integrated the following sensors such as the light sensor are indicated by different icons and the measuring ranges are partly pre defined Since all sensors operate in the same way their functions are illustrated by means of the general measuring sensor Light sensor This pre defined object for the light sensor DLUX operates in the same way as the measuring sensor but has a different icon and the preset measuring range of 0 1 to 100 000 Lux Wind sensor This s
25. second entered value But this is rarely the case More often and in particular in heating control systems the heating element is to switch on when the temperature drops below set value and switch off when set value is exceeded The invert ed output function needed for this purpose is selected with the parameter Invert limits which changes the entered values into On lt Limit and Off gt Limit Select the values appearing in the window in order to control the temperature of a room within the range of 19 C and 21 C 3 If you want to add night setback to your heating control system select the option Enable Limit 2 to enter a second pair of limit values and specify a channel or flag in the field Enabled by address eg address A3 configured for the real time clock function Hint These limits can also be inverted by clicking Invert limits 4 The entire analog signal output can be disabled through a channel or a flag by entering a Disable address When the Disable address is switched on the sensor object switches neither On nor Off 5 Finally the analog values can also in this case be provided by another channel By clicking in the field Alternative input and entering an address in the field Measuring channel an analog value can generate a random number of outputs 26 2002 Carlo Gavazzi Industri A S All rights reserved G 3800 X015 Configuration Software October 2002 The fo
26. stopped and the Reverse delay Tu starts After elapse of the Reverse delay Ty the motor rolls in the down direction After elapse of the roll time TL the motor is stopped In order to reach the end of the roll time the activa tion of the Down button must last longer than the Reverse Up time Ty 2002 Carlo Gavazzi Industri A S All rights reserved 59 G 3800 X015 Configuration Software October 2002 Application Example Task Control of several roller blinds as well as a roof window in a building The system should include groupwise control for two different floors as well as master control of all roller blinds together To protect the roller blinds a wind sensor and a rain sensor are installed The roller blinds are to roll down by rain and up by wind and wind has priority The roof window is to close by rain Solution The roller blinds as well as the roof window are activated through Dupline roller blind control modules For the group wise and the master control roller blind master controls are used The address of the wind sensor is marked directly in the roller blind controls as priority address The down channel of the master control is activated through logic setup via the address of the rain sensor Further details can be found in chapter 2 5 2 Object Function Channel In outputs Push button inputs Local activation A1 B4 C1 D4 Push button inputs Group wise B5 6 Master D5 6 D7 8 B
27. the Manual Armouring function on F1 in the input range or through the Code Lock Armouring function at the entrance door Disabling of floors is performed with two switches 2002 Carlo Gavazzi Industri A S All rights reserved 49 G 3800 X015 Configuration Software October 2002 2 4 6 The Water Alarm e Function Water alarm system including Passive detector Active detector Reset Siren and Alarm signal se e Application Wiring of water indicators eg the water stop sensor to an alarm system e Select with mouse Water alarm or short cut key W Description The purpose of the Water Alarm is an alarm system consisting of water sensors integrated as Passive or Active detector The wiring makes it possible to replace conventional fire alarm systems Water detectors are generally included in the system through the objects Passive detector or Active detec tor The alarm system is automatically alert after elapse of the Reset delay set with the reset object when the Configuration software has been downloaded or the Master Generator has been switched on The Reset output switches on within this time An alarm is triggered off when one or several alarm contacts are activated for more than 10 s The system steps through the activated alarm contacts as alarm indication as well as the alarm output approx every second The alarm siren flashes with a pulse pause ratio of approx 3 s 57 s By subsequen
28. valid for G38001015 4 1 SMS Setup The G38001015 Master Generator has a built in GSM Modem which enables Monitoring and control of Dupline signals via SMS messages to from mobile GSM telephones There are 3 different ways to use SMS messaging e The Master Generator can be programmed to send out event based SMS messages The event can be a channel switching ON or OFF or it can be an analog signal crossing a set point e Requests for status of digital or analog data can be sent and answered via SMS messages e Status of digital channels can be controlled by sending commands via SMS messages In order to make use of the GSM modem the following is required e A SIM card with the pin code 9090 needs to be inserted into the slot in the front of G38001015 The pin code can be changed by inserting the SIM card in a mobile phone and making use of the setting possi bilities in the mobile phone The SIM card must be a 3V type e A GSM antenna needs to be connected to the FME connector on G38001015 If the unit is installed in a metal enclosure the antenna must be installed outside the enclosure and connected to the Master Gene rator via a cable an antenna of this type is available with type number ANT1 An LED in the front of G38001015 indicates the status of the GSM modem By emitting different blink pat terns the LED indicates connecting SIMcard missing No network found No response from modem SMS sent and SMS received See a
29. 02 Parameters Processing of analog values As opposed to the counter values it is not only possible to visualize the analog multiplex values through the Modbus communication interface but also to change them There are basically two possibilities of value pro cessing 1 Representing the values in visualization software or operator panel eg on a PC with the Dupline Web Server 2 Through communication programmes eg the Dupline DDEServer an open software interface to for example Microsoft Office applications Simultaneous operation with transmission of multiplex analog values If both multiplex modes are used care should be taken to avoid address overlap The transmission channels of the analog modules must be set so that they do not overlap the channels of the counter value transmis sion Read the preceding chapter 2 6 1 Multiplexer Transmission of counter values Working with test unit GTU8 GTU8 makes it easy to read out and simulate analog values of this format operation mode Analog BCD In the case of simulation care should be taken that both the bit Signal available and the validity bit have been set see above Parameter Description Multiplexer Counter and Mux Analog Setu x Transmisison of analog values Counter range Counter No of values 0 9989 aa foie Multiplexer count Multiplexer delay Multiplex channels With this setting made under lt Edit gt lt
30. Gavazzi Industri A S All rights reserved G 3800 X015 Configuration Software October 2002 Time characteristics Up button central Down button central Up channel roller blind 1 Down channel roller blind 1 t Up channel roller blind 2 t e t z t 6 G 4 b t t The above illustration is based on a roller blind master application with sequential operation mode and a Reverse Up time Tr th to ts ta ts te tz The button for the up direction is activated The up channel of the first motor is activated In the operation mode Sequential the Controller switches the up channel of the second motor on after a time delay of 1 s Before elapse fo the master roll time the Down button is actuated whereby the roller blind is forced in the opposite direction The motors stop one by one and the Reverse delay Tu set for the decentral roller blind object begins After elapse of the Reverse delay Tu the first motor starts in the opposite direction while the second motor is activated after a delay of 1 s After the end of the roll time TL the Reverse delay Tu is postponed due to the subsequent Reversing Based on the set Reverse Up time Tr the roller blinds again run in the opposite direction in order to tilt the blinds After elapse of the Reverse Up time Tr the motor of the first roller blind stops Application example A detailed example is described in connectio
31. HH o m m EF P amp aaa Connected to ID Number 32 via Com 1 Gen time 16 02 Date 10 17 2002 Counter and Mux analog Setup Communication Setup Setup of holiday period The holiday setup is active when the current date falls within any of the set time intervals Basic setup of the SMS messaging functions facilitated by the built in GSM modem Basic setup of the multiplex functions required when Counter Modules and Multiplexed Analog Modules are used Configuration of the communication functions available for the two RS 232 ports and the RS485 port of the Generator 2002 Carlo Gavazzi Industri A S All rights reserved G 3800 X015 Configuration Software October 2002 1 2 3 Select menu G38xx15 finn x15 olx File Edit Select Tools Help EE osh 8 A Serial port gt Deutsch E EE 2 fa Dansk B a pen m eal Se l etiw C E Aa Aa A A A A el Me TET oe a aada z5 9 p 9 9 9 E A a a aaa M m U F Ga G amp Q amp Q R 2 ae cx aH Aw M M p H Aaaa Ea M LU l 7 7 7 a J fom Knee LHRRAA AH M if n N Hi 0 my it M P iH amp aaa Oo Connected to ID Number 32 via Com 1 Gen time 16 04 Date 10 17 2002 Menu Item Explanation Language Select between 3 languages By using the Select new menu other languages can be inserted in the 3 language menu Serial port Selection of C
32. In this way it is avoided that non resettable channel activa tions appear An SMS OFF command to these channels may not ensure that the channel output is turned off since the output of the channel is also controlled by transmission on the channel All other channel types cannot be controlled via SMS 2002 Carlo Gavazzi Industri A S All rights reserved 75 G 3800 X015 Configuration Software October 2002 5 Radio Modem driver 5 1 General The Master Generator has a built in driver for control of an external Radio Modem which can be used to cre ate wireless links where no cable is available in parts of an installation One Master Generator must be defined as the central MGEN and up to 32 Master Generators can be defined as remote MGEN s The central MGEN is continuously polling and updating the Dupline data from all remote MGEN s via the radio modem network and in this way it makes the entire system operate as one big Dupline network Apart from increased reaction time depending on the number of remote MGEN s the system will operate as if it was one Master Generator connected to all the I O modules with cable The Master Generator supports the Radio Modem type 2ASxE and all 3AS types from the Finnish manufacturer SATEL www satel fi These are not supplied by Carlo Gavazzi but are available with local support worldwide Find below an application diagram for the Radio Modem option Note Analink modules cannot be used with Rad
33. J 0 plin Installationbus Configuration Software G3800 X015 User Manual Preliminary Data December 2002 G 3800 X015 Configuration Software October 2002 Table of Contents 1 Introduction 4 1 1 Start up 4 1 1 1 Hardware requirements 4 1 1 2 Installation 4 1 1 3 Start up of program 4 1 2 Functions in the main window 5 1 2 1 File menu 5 1 2 2 Edit menu 6 1 2 3 Select menu T7 1 2 4 Tools menu 7 1 2 5 Help menu 8 1 2 6 Configuration of channel functions 9 1 3 Basic Setup 10 2 Objects 11 2 1 General 11 2 2 Standard objects 12 2 2 1 Blank channel no function 12 2 2 2 The push button function 13 2 2 3 The toggle switch function 15 2 2 4 Timer Recycler 17 2 2 5 Real time clock 20 2 2 6 Master function 22 2 3 Special objects 25 2 3 1 Analog sensors 25 2 3 2 Motion detector 30 2 4 Alarm functions 33 2 4 1 Overview 33 2 4 2 General features 33 2 4 3 ISA Alarm 34 2 4 4 The Smoke Alarm 39 2 4 5 The Intruder Alarm 44 2 4 6 The Water Alarm 50 2 4 7 Common Siren 55 2 5 Roller blind control 56 2 5 1 Decentralized roller blind up down function 56 2 5 2 Roller blind master 61 2 6 Counter and Multiplexer 64 2 6 1 Multiplexer transmission of counter values 64 2 6 2 Multiplexer transmission of analog values 66 3 Logic Setup 68 3 1 Introduction 68 3 2 The dialog logic functions 68 3 2 1 Setup 68 3 3 Application 69 3 3 1 Setups and Functions 69 3 3 2 Inversion and Edge
34. Manual armouring Alarm siren Also in this case the motion detector activates the output module for the lighting directly on address A1 If the alarm system is activated via the manual armouring the Master Generator generates an alarm within 10 s after the third impulse Additional details about the intruder alarm can be found in chapter 2 4 5 Tip If you want to use the Sabotage protection Normally closed function of the G 8910 1127 you should configure the object Push button function for the normally closed function and use the increase of signal transmission time function provided by the module In order to include the detector with sabotage protection in an intruder alarm system you must use the object Active detector of the intruder alarm system in stead of the Push button function 32 2002 Carlo Gavazzi Industri A S All rights reserved G 3800 X015 Configuration Software October 2002 2 4 Alarm functions 2 4 1 Overview This chapter will assist you in using the four different Dupline alarm systems 1 ISA alarm chapter 2 4 3 This general alarm system develped acc to ISA specifications is very flexible and has formed the basis of the development of the other alarms systems Application areas include temperature and level control as well as plants requiring ordinary alarm functions 2 Smoke alarm chapter 2 4 4 The primary purpose of this alarm system is the connection of the Dupline smoke de
35. Setup exe This will guide you through the installation pro cess After installation the program can be started by clicking G38xx15 1 1 3 Start up of program When G38xx15 is started two windows will open Gati015 finns Pel File Edit Select Tools Help lees 3 4 5 6 ie 8 AMAWAAAAA HREABBEBEBEABE CHE AAA AA CHER HEEB HE E Fea a yag G Hee ARASH a22 E cacc e J E E a k m eee eee LO Em a l a M M m M M N m M M M M 0 Hy al PHA aaa Oo Connected to ID Number 32 via Com 1 Gen time 16 13 Date 1017 2002 ix Basic set up x General description No Channels fiz x JV Auto start Dupline on Shortcircuit r Enable automatic Update of Realtime status upon Config Download and system Power Up Vv Enable Automatic Daylight saving Central European Time standard I Enable RTC Powerline Autocalibration Syncronize Time to Thursday 17 oktober 2002 16 13 To the left the main window showing the 128 channels available in Dupline and the menus To the right the properties window which for each function shows the parameters related to this particular function 2002 Carlo Gavazzi Industri A S All rights reserved G 3800 X015 Configuration Software October 2002 1 2 Functions in the main window 1 2 1 File menu File Edit Select Tools Help New Ctrl N 5 Open Ctrl 0 Save Ctrl 5 we i Save As Ctrl 4
36. Setups and Functions 3 3 1 1 Creating Setups Navigating For jumbing between the individual fields press the Tab key forward or the Alt and Tab keys backwards Adding All fields in a logic setup must be filled in ie all 4 components must be available Any number of setups can be selected and gaps are allowed To add a function place the cursor in any field in the row Depending on the component press a letter or number key Changing Changes are made in the same way as additions place the cursor in the field Function and overwrite the old value with the new value Deleting The entire logic row can be deleted by placing the cursor in the field Function and press the Delete key or the space bar 3 3 1 2 Mode of operation The in and outputs can be channel addresses A1 to P8 or flags W1 to Z8 Depending on the inputs or logic setup result of the function the output is set in each bus cycle max all 134 ms This means that the output assumes the value O when the setup is not ful filled and the value 1 when the setup is fulfilled The three logic functions correspond to the mathematical functions AND OR and XOR exclusive of OR AND The output is always 1 when both inputs are 1 OR The output is always 1 when one or both inputs are 1 XOR The output is 1 when only one of the two inputs are 1 2002 Carlo Gavazzi Industri A S All rights reser
37. Write Generator Ctr w Aa Read Generator Ctri R m P L2 Print 1 finn x15 Z 2 finn2 x15 Ao 3 All_Types x15 4 All_Types x15 we Exit Alt x H 4 4 4 4 4 4 4 4 4 4 5 a E z S tg H 4 a ts H ts H H H te H lt 4 4 4 t S T OCE A eE A 4 4 4 4 4 F af ag af Ci Connected to ID Number 32 via Com 1 Gen time 15 58 Date 10 17 2002 The file menu contains the usual functions Menu Item Explanation New Spat Save Save AS Write Generator Read Generator Print The following options are available Print out of Address Listing Master Channels Real time Channels or Logic Settings SMS Setup Exit 2002 Carlo Gavazzi Industri A S All rights reserved 5 G 3800 X015 Configuration Software October 2002 1 2 2 Edit menu Menu Item Explanation Basic Setup Basic setup of the G3800X015 generator Logic Setup Configuration of logic functions Holiday Setup SMS only valid for G38001015 G38xx15 finn x15 ol xj File Edit Select Tools Help Basic set up Ctrl B 8 A Logic set up Ctrl L Holiday Set up Ctrl H B sms Setup Ctrl M ic Counter and Mux Analog Setup D Communication Setup a p o 9 9 9 ECS eae eae Be m M U E H a aul g a E c HE FN a M M Bp HaeanAa a A M LU l l paaa a J amp KR M dal i N
38. act does not trigger off an alarm Subsequent acuation of the Reset button switches the alarm contact off and releases the alarm system If the Reset button is actuated before the Acknowledgement button the system will also switch off the alarm output but the alarm contacts will continue to flash A new alarm is caused by renewed activation of an alarm contact In the operation mode Auto reset the alarm system is restarted after acknowledgement and with alarm con tacts in off position The status of the alarm contacts can easily be displayed eg on a panel This only requires that the output channels are coded for the same addresses as the alarm contacts The functionality of the lamps can then be tested by means of the object Lamp test For giving out alarms the object Common siren can also be used Further details can be found in chapter 2 4 7 The various ISA objects are selected under Function Passive detector o Normally open input This object makes it possible to include j Passive detectors When the contact is activated and a 1 Signal consequently transmitted on the Dupline bus an alarm is started Active detector 1 Normally closed input This object makes it possible to include j 4 active detectors When the contact is activated and a 0 Signal consequently transmitted on the Dupline bus an alarm is started This object makes it possible to include acknowledgement buttons Upon a
39. address fields Version 1 10 Connected to ID Number 32 via Com 1 Skovgaard Dupline R amp D Gentime 16 18 Date 10 17 2002 Menu item Explanation General information You can call the Help menu at any time by pressing F1 About program Shows the opening screen G38xx15 New x15 File Edit Select Tools Help 3 General Information lee A m J P m About program 8 2002 Carlo Gavazzi Industri A S All rights reserved G 3800 X015 Configuration Software October 2002 1 2 6 Configuration of channel functions G38xx15 finn x15 OE x File Edit Select Tools Help 1 2 3 4 5 6 7 8 A j mae a ae z E 2 Ao Be A Copy Ctrl C ss Paste Gtr Aal C lt 2 Blank B Lo D Ea Push button 0 E Me ee switch F Ye F g imer T a Real time R 19 G Fasl Master function M H oa Analog Sensor A Motion Detector LU Thermostat e J Night Setback K iff L 154 alarm 4 L Ep Smokealarm 5 M E Intruderalarm I SIL wateralarm wW N in Common siren o Rollerblind Master P H Rollerblind Up Down d Connected to ID Number 32 via Com 1 Gen time 16 06 Date 10 17 2002 When the basic settings have been made under Basic Setup the functions of the remaining channels to be used are defined as follows Activate one of the channels then click on the right mouse button for pop up menu Click on the desired channel function with the left
40. annels configured above chapter 2 5 1 are included in the Roller blind mas ter by marking them in the channel matrix The roll time set for the Roller blind master applies to all indiviual controls and overrides their roll times Enter ing a Reverse Up Time allows automatic adjustment of tilting blinds at the end of a cycle After elapse of the set roll time the Controller switches the motor in the opposite direction for the set Reverse Up time The Roller blind master offers two operation modes for starting the motors 1 Simultaneous All motors are started simultaneously 2 Sequential All motors starting with the lowest address are started at 1 sec intervals Thereby current peaks are avoided Address configuration The Roller blind master can only be configured for an uneven address number This means that the Up chan nel must lie on an uneven eg A1 B5 or P7 and the Down channel must lie on an even address eg A2 B6 or P8 Operation The Up and Down buttons configured for the addresses of the Roller blind master allows very simple opera tion e By pressing a direction key once all selected motors roll until end position is reached or the roll time has elapsed e By pressing the same direction key once more the set roll time starts again Thus it cannot be stopped e By pressing the other direction key the motors stop shortly decentrally set Reverse Up time and run in the opposite direction until the end positi
41. aster Generator e The flags are not stored upon voltage failure at the Master Generator e Flags basically operate in the same way as the Push button function ie the value of the flags changes immediately with the result of the logic setup Only edge triggering is not possible with flags Application If a channel is to be related to more than two other channels flags help to organize the setup The following example illustrates how channels A1 A2 and A3 are organized and assigned to B1 Output Input 1 Function Input 2 w1 A1 AND A2 B1 w1 AND A3 In most objects in the matrix eg the decentral roller blind Up Down function flags can be used in stead of channels In this way it is possible to have priority control functions which are related to several channel sta tuses Note Flags used in this way may only be used once in the logic function 3 3 4 Internal processing of the logic setups The Master Generator processes the setups from block 1 to block 8 and within each block from top to bot tom 3 4 Notes and Documentation For later documentation of the logic setups it is useful to add comments in the field Notes When the logic setups are later printed out the notes appear next to the individual rows so that each individual function is commented on 2002 Carlo Gavazzi Industri A S All rights reserved 71 G 3800 X015 Configuration Software October 2002 4 GSM Modem functions only
42. aturday S Sunday If H is activated the clock also switches on holidays In this case the corre sponding days must be entered under lt Edit gt lt Holiday setup gt Time characteristics OUT PMan_TReal_1a 20 2002 Carlo Gavazzi Industri A S All rights reserved G 3800 X015 Configuration Software October 2002 c Application Example 4 The real time clock activates the channel at the pre defined time without affecting the input channel 2 By activation of the input the output switches off directly 3 By activating the input once more the output switches on again 4 At the set Switch off time the input is always deactivated 5 The output can always be activated againg through the output Task A lamp is to be switched on and off by means of a switch Solution Use for example the universal input module to provide the input signal and configure one of the inputs for address A1 Assign the same address to one of the outputs of a relay module Finally configure channel A1 in the Master Generator as a toggle switching function Object Function Channel In outputs Relay output Outdoor lamp Al Switch Light switch Al Configuration of Master Generator Toggle switch function Light control Al 2002 Carlo Gavazzi Industri A S All rights reserved 21 G 3800 X015 Configuration Software October 2002 2 2 6 Master
43. configured intruder alarm system This means that in an armoured alarm system with no time delay set an alarm is released when the input is activated Time characteristics OUT t PMan_TToggle_1a The first triggering of the input switches the output on the second triggering switches the output off again 2002 Carlo Gavazzi Industri A S All rights reserved 15 G 3800 X015 Configuration Software October 2002 Application Example Task A lamp is to be switched on and off by means of a conventional switch Solution Use for example the universal input module to provide the input signal and configure one of the inputs for address A1 Assign the same address to one of the outputs of a relay module Finally configure channel A1 in the Master Generator as switching function Object Function Channel In outputs Relay output Lamp Al Switch Light switch Al Configuration of Master Generator Toggle switch function Light control A1 16 2002 Carlo Gavazzi Industri A S All rights reserved G 3800 X015 Configuration Software October 2002 2 2 4 Timer Recycler Description Parameters Function Timer or Recycler Application Switching with on or off delay or recycler Activation by signal or impulse Activation by additional channel or flag Select with mouse Timer or short cut key T PEAN L F This object makes it possibl
44. ctivates the Normally open output and the system at once brings itself in the alert state again As ty to In spite of the acknowledgement of the alarm the flashing source indication changes to continuous operation because the alarm source is still activated at this point of time Since the siren time has not yet elapsed the alarm siren turns off Only when the alarm source switches off is the source indication also reset and the alarm system in the alert state again 2002 Carlo Gavazzi Industri A S All rights reserved 37 G 3800 X015 Configuration Software October 2002 Application Example Task In a chemical factory eight laboratories are to be provided with alarm switches Upon activation of an alarm button the fire staff of the factory is informed via a siren When the fire staff has acknowledged the alarm they go to the lab where the alarm was started Solution The alarm switches are coded for channels A1 to A8 The source of the alarm is indicated on a panel whose LED is activated via a mimic display The addresses correspond to those of the alarm contacts The fire staff uses a button coded for address B1 to acknowledge the alarms The alarm is reset through a reset button coded for address B2 The alarm is sounded by means of a horn activated through a relay output of DSM 8 coded for address B4 Object Function Channel In outputs Alarm switch Alarm contact A1 A8 Push button input Acknowledge
45. ctor function of the monitoring system whereby it cannot trig ger off any further alarms Reset Channel function Reset delay Passive detector C Active detector joz Minutes Reset Alarm siren Alarm signal Reset delay The delay after which the system becomes alert or is to remain switched off upon activation of the reset button The reset delay can be from 2 and 10 min 2002 Carlo Gavazzi Industri A S All rights reserved 51 G 3800 X015 Configuration Software October 2002 Parameter Description Alarm siren Channel function Siren time Passive detector Active detector Jos Minutes Reset Alarm siren Alarm signal Siren time With this setting you determine the duration of the activation of the alarm output upon the occurence of an alarm The value can lie between O and 60 min The entered value is automatically adopted by the Common Siren Alarm signal Channel function Alarm signal delay Passive detector C Active detector Joz Minutes Alarm signal delay With this setting you determine the time to elapse after switching on of the alarm siren till the alarm signal is activated The value can lie between 0 and 10 min 52 2002 Carlo Gavazzi Industri A S All rights reserved G 3800 X015 Configuration Software October 2002 Time characteristics Passive detector IN Alarm s
46. ctuation of an acknowledgement button the alarm output is reset and the alarm source indication prepared for the resetting changing from flashing to continuous operation Acknowledgement an T GP Note This object must always be configured This object is only needed in the operation mode Standard and SH makes it possible to include a button for resetting the alarm and restarting the system This requires prior acknowledgement of the alarm Reset T 34 2002 Carlo Gavazzi Industri A S All rights reserved G 3800 X015 Configuration Software October 2002 Parameters If a contact is activated during resetting the system triggers off a new alarm When this object is configured the operation mode Standard is automatically selected Lamp test L This object makes it possible to test the function of lamps indicating the status of isa the alarm contacts All alarm channels are activated upon actuation of the lamp test button Alarm siren 5 The alarm siren indicates the occurence of an alarm The channel configured for isa this object can be used for alarm output on a random number of output modules It usually activates a relay output switching a siren Parameter Description Operation mode Standard This setting means that activation of the alarm system takes place upon prior release by the reset button This entails that the object Reset must be config ured Auto reset With th
47. e and deleted again by the Delete key Off lt Limit These are the switching limits of the sensor object If the option Invert limits is On gt Limit not selected the limit values appear as described ie if the values 17 0 and or 20 0 are entered the channel switches off when the actual value is below 17 0 On lt Limit and switches on when the actual value is above 20 0 Off gt Limit When the limit values are inverted the sensor switches on when the actual value is below 17 0 and switches off when the actual value is above 20 0 This setting is typical for a heating control system The limit values are only active when the address enabling a second pair of limit values is not switched on Note The entry of each value must be confirmed with the Enter key Enable limit 2 This option is selected in order to enter a second pair of limit values for instance for night setback Off lt Limit The second pair of limit values makes it possible to enable a different switching On gt Limit operation through a different address Enabled by address If Enabled by or address is activated the second pair of limit values will apply in stead of the first On lt Limit pair Off gt Limit The second pair of limit values can also be inverted by the Invert limits option Note The entry of each value must be confirmed with the Enter key Enabled by address When the selected channel or flag is
48. e to select between two modes of operation timer and recycler In both modes an input coded to the channel of the timer starts the functions but the input can also be activated by a differ ent channel or flag Timer with on delay or off delay The timer allows the setting of an on delay and or an off delay When an input coded to this channel is acti vated the on delay starts After elapse of this delay the Off time starts The Off time stops after the set time if the input is released before expiry of the set time If the input is not released the output remains activated Recycler If the recycler is activated by an input the recycler continuously generates a square wave signal The output is activated after the set on delay period and de activated after the set off delay period This process is repeated as long as the input or the additional trigger is ON Depending on the options selected under Timer function a number of parameters can be selected for Timer and Recycler Timer with on delay or off delay Configuration window for timer with on or off delay Timer function On Delay On Ott delay Hour Minute Seconds Recycler oo fos oo V Activation by pulse Off Time Enabled by address Hour Minute Seconds jar fo fio foo Parameter Description Timer function Select the option On Off delay in order to use the Timer function Activation by pulse Select this optio
49. ensor object is intended for the integration of a wind meter anemometer but requires a conversion module Apart from that this object operates like the measuring sensor Temperature sensor This object also operates in the same way as the measuring sensor but has its own icon for easy recognition General information Channels for analog transmission operate in the same way as other switching channels For example they cannot be switched with switches that operate on the same channel This means that an additional channel is needed when for example a sensor only is to be switched manually and only at a certain time Furthermore analog values cannot be processed by means of flags In stead it is possible to configure any number of analog sensors so that they relate to the same source value 2002 Carlo Gavazzi Industri A S All rights reserved 25 G 3800 X015 Configuration Software October 2002 Parameters Configuration window of the analog sensor function Function Disable address C Measuring device Light sensor we C Wind Senesor Temperature Sensor ee JV Invert Limits Sensor Input Flange JV Altemative input Min Max Measuring Channel f 30 0 60 0 On lt Limit Off gt Limit When the Configuration Software has been connected to the master the fi 9 0 A 0 J Enable Limit 2 actual values are shown SMS by On SMS by Off On lt Limit Off gt Limit Enabled by address iso
50. epeater stations are used on the radio modems No of substations Defines the number of substations connected via radio modem to the central master generator Important Note The master generators configured as Radio modem substa tion must be given the ID numbers from 1 and onwards Example When No of substations are set to 3 then the 3 master generators configured as radio modem substation must be given the ID numbers 1 2 and 3 respectively Select groups for ex change of Mux analog If multiplexed analog I O s are used in the radio modem system then it is neces sary to define which channel group pairs are used for this purpose This is sim ply done by selecting the relevant check boxes It is only possible upon prior setup of Multiplex count under the menu Counters and Mux Analog Setup 2002 Carlo Gavazzi Industri A S All rights reserved 77 G 3800 X015 Configuration Software October 2002 5 3 Setup of Radio Modem Substation Parameter Radio Modem Substation Pcs News File Edit Select Tools Help 2 3 4 5 6 7 8 X X X X X X X pa ema oma mea ua uai omal 5 x 4 _ Communication Set up xj H ID Number R5485 Baudrate P for 56700 Baud bd MG Com2 operation MG Com2 Baudrate Radio Modem Substation x 9600 Baud ea m Radio Modem SubStation settings y J Clear data upon loss of Radiocommunication sel TO E Ps ee pe Su tay Tel O te
51. er Generator Data is transferred on two consecutive address groups C D E F G H I J D L M N and O P The channels can be set individially to the applied modules and can thus not be reserved by the Master Generator Also when the number is limited to 16 because only four channels have been reserved 112 values can actual ly be processed This is possible because up to 7 analog channels receive the same binary address but sub sequently transmit the values to different channel groups See above Note The reserved addresses must not be used for other purposes eg to output switch commands Module configuration Transmission of analog values requires correct setting of the analog modules Apart from the setting of the transmission channels it is also necessary to assign a binary address to each module Details can be found in the datasheets Data format Within the two channel groups in this case C and D the value 1957 is generated continuously Value in hundreds Value in tens Single digit value Value in thousands o Q D T amp T D 72 Value valid D5 D6 D7 D8 Signal available means that an input module continuously provides the value Value valid indicates that the value is valid An 0 stands for a positive value An 1 stands for a negative value 66 2002 Carlo Gavazzi Industri A S All rights reserved G 3800 X015 Configuration Software October 20
52. es JV ISA alarm o2 Minutes Channel function Here you select one or several alarm systems whose alarm will also activate this siren Siren time Here you enter the max time for which this siren is to remain activated The value can lie between 0 min and 60 min Application Example Task In a commercial building different alarm systems smoke water ISA and Intruder are to acti vate the siren mounted outside Solution The alarm systems described in the previous examples are used The relay for the outdoor siren is configured for address 11 The siren time of each connected alarm is configured 2002 Carlo Gavazzi Industri A S All rights reserved 55 G 3800 X015 Configuration Software October 2002 2 5 Roller blind control 2 5 1 Decentralized roller blind up down function Description Function Up Down control of roller blind motors Application Control of motors for roller blinds sun blinds and roof windows through Dupline modules G 3430 4249 Run time and Switch time individually adjustable Tilted blinds for sun blinds and priority control for example for wind sensor The decentralized roller blind up down control makes it possible to run Dupline roller blind control modules for roller blind and sun blind motors By organizing the up and down channels the Master Generator ensures undisturbed operation by preventing both directions from being activated at the same time and ensuring that the dela
53. ess is dynamic and lasts only two bus cycles it is necessary to select an output channel capable of processing impulses eg channels with toggle switch function timer function or master function A push button function can also be generated with this setup but it should be noted that in this case the out put will only be active for one cycle Example of a logic setup Output Input 1 Function Input 2 A1 E1 AND E2 70 2002 Carlo Gavazzi Industri A S All rights reserved G 3800 X015 Configuration Software October 2002 Time characteristics gt gt t E2 l l gt t Al 7 t PMan_003 t A jan_003a Two conditions must be fulfilled AND E1 must be active and E2 must trigger on leading edge This only takes place at t1 the dotted line to the left If the signal on E1 goes Off dotted line to the right output A will also be reset It is assumed that the channel set as output A is configured for a toggle switch function for example This function only needs one impulse to execute the switching function A push button function would release again immediately 3 3 3 Using flags Dupline offer flags with which the intermediate results of logic setups can be stored in order to be used in other setups Characteristics e The flags are on the channels W1 8 X1 8 Y1 8 and Z1 8 e The flags are initialized for zero upon voltage application at the M
54. et delay the system becomes alert again and the reset output is reset 42 2002 Carlo Gavazzi Industri A S All rights reserved G 3800 X015 Configuration Software October 2002 Application Example Task In a residential building eight rooms are to be equipped with smoke detectors When an alarm occurs a siren switches on and the fire authorities are notified Solution The alarm channels of the smoke detector are assigned to channels C1 to C8 The alarm source is indicated on a panel whose LED is activated by mimic display The addresses corre spond to those of the alarm contacts The alarm is sounded through a horn which is activated through address D2 of a relay module The alarm is reset again by a push button on address B1 2002 Carlo Gavazzi Industri A S All rights reserved 43 G 3800 X015 Configuration Software October 2002 2 4 5 The Intruder Alarm e Function Intruder alarm system including Passive Active detector contacts Toggle switch o functions Motion detectors Manual and Door lock Armouring Code lock Armouring Alarm siren and Alarm signal e Application Wiring of intruder detector contacts to an alarm system e Select with mouse Intruder alarm or short cut key I Description The purpose of the Intruder Alarm is an alarm system consisting of various contacts integrated as Passive or Active detectors The wiring makes it possible to replace conventional intruder alarm syste
55. figure IN is the input channel of the motion detector or the contact while OUT is the out put signal of the same channel In addtion the object Motion detector has been integrated in the intruder alarm system whose alarm siren can also be seen in the below diagram The number of impulses has been set to 3 OUT Alarm siren tp tpo tps i tp4 PMan_TMotion_1a tpi te2 tes and tps are the points of time at which the motion detector generates a signal The impulse duration depends on the characteristics of the detector Ty is the set off time retriggered by the impulses tps and tp and therefore only begins after elapse of the third impulse The alarm will not start until after the fourth impulse tps and only when the time elapse between tp and te is less than 10 s 2002 Carlo Gavazzi Industri A S All rights reserved 31 G 3800 X015 Configuration Software October 2002 Application Example Task A floor lighting is to switch on automatically for 5 minutes with PIR sensor G 8910 1127 and also serve as intruder alarm when the house is empty Solution G 8910 1127 must be connected to the Dupline bus and given an address here A1 In this example increase of the signal transmission time through the DIP switch is to be switched out Configure both the object Motion detector and an output channel of a relay module for address A1 and additional objects needed for the intruder alarm
56. function Ei Si S Bg e Function Simultaneous on and off switching of multiple toggle switch functions real time clocks etc upon activation of input Integrated real time clock with four switch times e Application Simultaneous off on on switching of multiple loads calling lighting scenes in connection with dimmers e Select with mouse Master function or short cut key M Bistable master function Description The master function allows simultaneous activation of a random number of channels configured for suitable objects When the master function is activated an on signal is generated on the channels configured for switching on Likewise an off signal is generated on channels configured for switching off The objects configured for these channels thus determine the behaviour of the outputs Note the following characteristics of the master function e A master function has priority over the individual functions at the time of activation ie it is not possible to activate the individual channels as long as the master function is on Upon reset of the master function the decentral functions are accepted again e It is to be noted in particular in connection with real time clocks that only one master command can apply at a time When several master functions are activated at the same time only the one with the high
57. he addresses of the alarm contacts The object Alarm signal makes it possible to control a telephone or GSM modem because of the short mes sage on this channel For alarm purposes the object Common Siren can also be used Details can be found in the chapter describ ing The alarm siren Common siren The various Intruder alarm objects are selected under Channel function Passive detector This object makes it possible to control windows doors etc with Passive de a z tector If the contact is activated and a 1 Signal consequently transmitted on the Dupline bus an alarm is started Active detector 1 This object makes it possible to control windows doors etc with Active de z tector When the contact is activated and a 0 Signal consequently transmitted on the Dupline bus an alarm is started Toggle switch function Use in Intruder alarm See the chapter describing the Toggle Switch function Motion detector The motion detector can also be integrated in the intruder alarm See the chapter describing the Motion detector Mo 44 2002 Carlo Gavazzi Industri A S All rights reserved G 3800 X015 Configuration Software October 2002 Manual armouring Door lock armouring Code lock armouring Alarm siren Alarm signal This object makes it possible to include a push button to enable and reset the alarm The object only enables the alarm contacts for which no or a
58. hroom fan A2 Configuration of Master Generator Toggle switch function Light control A1 Fan control A2 Timer By use of the additional trigger A1 the timer starts when the light is switched on 2002 Carlo Gavazzi Industri A S All rights reserved 19 G 3800 X015 Configuration Software October 2002 2 2 5 Real time clock J Function Real time clock with week and holiday planner Application Time controlled switching on and off of loads Also applicable as switching function Holiday setting can be performed centrally for all clocks Select with mouse Real time or short cut key R Description The real time clock enables on and off switching of loads in relation to the internal time setting of the Master Generator It is possible to pre define up to four switch on and switch off times for each clock on freely selectable weekdays and holidays Parameters Configuration window of real time clock function Switch on Switch off Days of week Hour Minute Hour Minute MT WTF S S H jos joo h3 joo MMO Cae a ae fia f3 fig fo MMV hie hs fa fis fo CCrrrrr a al CU AU a a a E Parameter Description Switch on time Time at which the channel is to switch on Switch off time Time at which the channel is to switch off Days of week Day s on which the switching time indicated to the left applies M Monday T Tuesday W Wednesday T Thursday F Friday S S
59. ible to send an SMS to the Generator with request for channel status The Generator will then answer by sending back an SMS with the requested data The format of the SMS commands and requests are shown in the example below With passport option Controlling command Example Password Channel argument 1234 F4 on 1234 f4 on 1234 Alarm reset on Request Command Example Password Channel 1234 F3 alt 1234 F37 1234 Siren With passport option Controlling command Example Channel argument F4 on Alarm reset on Request Command Example Channel F3 alt F3 Siren NB When using controlling commands on a channel which is also configured to send a mes sage when changing status the message will also be sent to the GSM phone Not all channel types can be controlled 74 2002 Carlo Gavazzi Industri A S All rights reserved G 3800 X015 Configuration Software October 2002 As it can be seen it is possible to use either the channel reference directly eg F4 or to use the descriptive text defined for that channel The only channel types whose outputs are actually controlled directly ON or OFF by the SMS command are the Toggle and Realtime channels For Push button Timer Master Roller Blind Alarm Reset and Acknow ledge channels an SMS ON command will initiate a pulse on the channel and thereby be able to trigger a function eg a Master function or logic function
60. ignal co t Passive detector OUT on t Reset IN TE Reset OUT Siren a fi tet u te The above illustration shows the normal sequence and reset of an alarm t When power supply is connected the system becomes alert after elapse of the set reset delay Tr indicat ed by reset of the reset output to An alarm contact is activated This starts the switch on delay Tev which can run for 3 11 s depending on the number of channels ts Upon elapse of the switch on delay Tev the Master Generator causes the output of the activated contact as well as the alarm siren to flash The alarm siren is then switched on for approx 3 s and switched off for approx 57 s t4 Upon elapse of the alarm signal delay Tw the alarm signal is briefly activated ts Activation of the reset button starts the reset delay and the siren is switched off 2002 Carlo Gavazzi Industri A S All rights reserved 53 G 3800 X015 Configuration Software October 2002 Application Example Task Solution In a residential building eight rooms are to be protected against water damage When an alarm occurs a siren switches on and the house owner is informed by means of an SMS message The room in question should be recognizable on a panel The alarm channels of the water stop sensors are assigned to channels G1 to G8 The alarm source is indicated on a panel whose LED is activated by a mimic display The addres
61. ill toggle between the selected output status and the inverted output status whenever the input is activated Include Real time A real time clock is included to time control the master function The field Enter Switch times appears Enter Switch times Click here to open or close a matrix in which to enter switch times Real time clock Normally the real time clock for time control of the master function behaves in the same way as the object Real time clock See chapter 2 2 5 Real time clock for further details Unlike a separate real time clock the built in real time clock only generates one switching impulse This is particularly important to bear in mind when the master function is to control push button functions since the switch signal may be of very short duration As a Flip Flop Master The real time function operates both ON switching and OFF switching This enables simultaneous ON and OFF switching of multiple channels The channels marked with 1 switch on when the master is activated and switch off upon deactivation The channels marked with 0 behave in the opposite way Tip Entire address groups can be changed by clicking on the right mouse button Time characteristics without toggle function selected IN OUT i Toggle switch Piai Bee sree y a ag e eer function outputs t Push button t t t t4 PMan_twasterta function The master function rema
62. inary inputs for Priority control E1 E2 wind rain sensors Relay outputs Motors A1 B4 Configuration of Master Generator Decentralized Roller blind roof A1 B4 Roller Blind Up Down window control C1 D4 Roller Blind Master Group wise con B5 6 trol ground floor Roller Blind Master Group wise con D5 6 trol 1st floor Roller Blind Master Master control D7 8 Push button function Connection of E1 E2 With the logic setup below the rain sensor activates all roller blinds in the Down direction through the master function If the wind sensor channel is set the command of the decentralized up down control is not executed priority control at each decentral roller blind object Output Input 1 Function Input 2 D8 E2 AND E2 60 2002 Carlo Gavazzi Industri A S All rights reserved G 3800 X015 Configuration Software October 2002 2 5 2 Roller blind master Description Function Group wise or master control of decentralized roller blinds Application Group wise or master control of motors for roller blinds Roll time with priority over individual roll times adjustable Simultaneous or sequential roller blind start selectable Reverse Up time for tilting blinds when end position reached Enter with mouse Roller blind master This object enables group wise and master control of for example roller blinds sun blinds and roof windows The decentralized roller blind ch
63. ins active until the input is switched off In the above example the outputs switch on and in the case of a push button function remain on until the master function switches off again 2002 Carlo Gavazzi Industri A S All rights reserved 23 G 3800 X015 Configuration Software October 2002 Application Example Task The master function is to control four lamps and two dimmers in a building Master on Switches all lamps on and sets dimmer at 100 Master off Switches all lamps off and sets dimmer at 0 Lighting scene for living room lighting scene 6 factory setting 85 is to be called by both dimmers Solution Three push buttons are configured on addresses A1 to A3 to initiate the master function for calling the lighting scene The channels of the dimmer are coded for B1 to B8 and configured as push button functions Object Function Channel In outputs Push button input Master on Al Push button input Master off A2 Push button input Push button for call A3 ing lighting scene 6 Dimmer channels Channels for calling B1 B4 lighting scenes B5 B8 Relay outputs Lamps C1 04 Configuration of Master Generator Master function Master on Al Master function Master off A2 Master function Calling lighting A3 scene Push button function Dimmer channels B1 B4 1 4 B5 B8 Toggle switch function Lamps C1 04 24 2002 Carlo Gavazzi Industri A S All rights
64. io Modems Satel Shiney he RN Fanmi Tae Hl Che Aewe The Radio Modem must be connected to the COM2 of the Master Generator For serial cable pin connections please refer to the Master Generator datasheet The baud rate selected for COM2 must correspond to the baudrate used by the radio modems and the other master generators in the network The central MGEN must be defined for Radio Modem central function for COM2 while the remote MGEN s must be defined as Radio modem substation The central MGEN can be configured for the usual intelligent functions and it can also be connected via COM1 or the RS485 port to a PLC or PC The remote MGEN s however cannot be configured for any intelligent function They will simply operate as Radio Modem inter faces The system can handle all types of digital analog incl multiplexed and counter values except for Analink values The configuration of the Radio Modem function is performed in the menu Edit under Com munication setup 76 2002 Carlo Gavazzi Industri A S All rights reserved G 3800 X015 Configuration Software October 2002 5 2 Setup of Radio Modem Central Parameter Radio Modem Central x TE Ix ID Number i R5485 Baudrate 56700 Baud x MG Com2 operation MG Com2 Baudrate Radio Modem Central x 9600 Baud x m Radio Modem Central settings No of
65. ions are described in the following chapter 3 2 The dialog logic functions 3 2 1 Setup The processing of logic functions takes place in the Dialog Logic Setup Dialog Menu Logic setup Logic setup Configuration window of the Logic funtions Logic block number Output Input 1 Function Input 2 HALL F1 only on when both is on Each logic block always shows eight setups The individual blocks are selected by pressing the correspond ing block numbers The selected block is marked by a small bar below the box Each setup consists of two inputs interconnected by an operand eg AND The result of the setup True or False is then assigned to the output The components are summarized in the following table 68 2002 Carlo Gavazzi Industri A S All rights reserved G 3800 X015 Configuration Software October 2002 Designation Values Description Abb Output A1 P8 Channel or flag whose status is to be changed A W1 Z8 Input 1 A1 P8 Channel or flag causing the first part of the E1 W1 Z8 conditions for the change in output status Function AND OR XOR The logic operand connection the two inputs Fkt Input 2 A1 P8 Channel or flag causing the second part of the E2 W1 Z8 conditions for the change in output status 1 This abbreviation is used in the following to designate the various components 3 3 Application 3 3 1
66. is setting the system activates itself automatically upon acknowledge ment when all passive and active detectors are in their normal position in which they do not trigger off alarms Note Operation mode can be selected for any object of the ISA alarm but applies to the entire system If the object Reset is selected to include a reset button the system assumes that the operation mode Standard is to be select ed Simultaneously the option operation mode is deactivated and can only be re activated by unclicking the object Reset If Auto reset is selected the system prevents configuration of the Reset object Passive detector Channel function Disable address Passive detector Active detector as C Acknowledge On Delay C Reset 005 Seconds C Lamptest Alarm siren Operation mode Standard ad Disable address Enter an address A1 P8 or a flag W1 Z8 whose activation 1 signal will leave out the Passive detector function of the monitoring system whereby it cannot trigger off any further alarms On delay Enter a time value in seconds 0 255 for which the alarm signal is delayed upon activation of the alarm contact Active detector Channel function Disable address Passive detector Active detector as Acknowledge On Delay C Reset 012 Seconds Lamptest Alarm siren Operation mode Standard
67. k armouring Alarm siren Alarm signal Disable address Enter an address A1 P8 or a flag W1 Z8 whose activation 1 signal will leave out the Active detector function of the monitoring system whereby it cannot trig ger off any further alarms Manual armouring abate ela g Channel function Armouring delay e1OCK A Ing Passive detector Active detector 180 Seconds Manual armouring sp neg Des armouring time Door lock armouring Code Lock armouring h20 Seconds C Alarm siren Alarm signal Armouring delay Here you can determine the delay with which after activation of the Manual armouring function the system becomes alert De armouring delay With this setting you determine how many seconds are to elapse from an alarm has occured till the alarm siren is to be activated This also allows early acknow ledgement of the alarm or prevents an alarm output on the siren for example in order to make it possible to enter a building 46 2002 Carlo Gavazzi Industri A S All rights reserved G 3800 X015 Configuration Software October 2002 Parameter Description Alarm siren Channel function Siren time C Passive detector o2 Minutes C Active detector Manual armouring IV Flash when Alarm Door lock armouring Code Lock armouring amaren Flash Interval Alarm signal Joz Seconds Flashing Channels Siren time With this setting you determine how long the ala
68. l to one output channel The flexible way of controlling several motors centrally or group wise is to use the Roller blind master func tion Further details are found in chapter 2 5 2 2002 Carlo Gavazzi Industri A S All rights reserved 57 G 3800 X015 Configuration Software October 2002 Parameters Parameter Description Roller blind control Decentralized Up Down Roll time Priority 020 Up 5 d gees C Down Reverse Delay Address 0500 Milliseconds ps IV Tilting Blinds Roll time Insert the times Seconds for which the motor is to run in each direction The value must be within 0 and 255 s The selected time interval should ensure that the roller blinds can reach the end positions in both directions where an end position contact must switch the motor off Intermediate values allows shadow for example But it should be ensured that the roller blind is in one of the end positions before start The entered roll time is overwritten by the roll time of the master Reverse delay Enter the delay time milliseconds before the roller blind changes direction The value should lie between 500 and 2000 ms Tilting blinds This option allows adjustment of tilting blinds The function stops within the first three seconds after the key is released The tilting blinds option must be activated if you want to define for how long the roller blinds must run in the opposite directi
69. ll rights reserved 13 G 3800 X015 Configuration Software October 2002 Application Example Task A lamp is to be switched on and off by means of a switch Solution Use for example the universal input module to provide the input signal and configure one of the inputs for address A1 Assign the same address to one of the outputs of a relay module Finally configure channel A1 in the Master Generator as push button function Object Function Channel In outputs Relay output Lamp Al Switch Light switch Al Configuration of Master Generator Push button function Light control A1 14 2002 Carlo Gavazzi Industri A S All rights reserved G 3800 X015 Configuration Software October 2002 2 2 3 The toggle switch function e Function Bistable Flip Flop pea e Application Connection of switches and contacts for load switching e e Can be used in intruder alarm systems Select with mouse Toggle switch or short cut key F Description The toggle switch function makes it possible to simulate the operation of a toggle switch Pressing the switch once activates the output pressing the switch once more de activates the output again Parameters Configuration window of the toggle switch function Basic Channel Operation JV Use in Intruder alarm Parameter Description Intruder alarm When this function is selected the input is used in a
70. llowing table gives an overview of all parameters Parameter Description Function Select the function of an ordinary measuring sensor light sensor wind or tempe rature sensor Basically all functions operate in the same way Disable address When the channel or flag entered here is activated all switching operations of the sensor are disabled The value can be overwritten at any time and deleted by the Delete key Control output This entry is needed in order to use the sensor to activate a relay coded to the same address If the analog value is to be displayed on this channel for instance on a Touch screen then this option must not be selected Invert limits This option inverts the switching function in relation to the limit values Alternative input When selecting this option the analog value is provided by another channel The channel to provide the alternative analog value is entered in the field Measuring channel Sensor input range The upper and lower limit values of the sensor For example the lower value could be 30 C while the upper value could be 60 C Note The entry of each value must be confirmed with the Enter key Measuring channel If the sensor providing the value is coded for another channel this source chan nel is entered here For this purpose the option Alternative input must be acti vated The value can be overwritten at any tim
71. ment B1 Push button input Reset B2 Push button input Lamp test B3 Semiconductor output LED for source in A1 A8 cation on a panel Relay output Alarm siren B4 Configuration of Master Generator ISA alarm Alarm sources A1 A8 Passive detector ISA alarm Alarm B1 Acknowledgement acknowledgement ISA alarm Reset Alarm reset B2 ISA alarm Lamp test Activation of all B3 LEDs on the panel ISA alarm Alarm siren Alarm sounding B4 38 2002 Carlo Gavazzi Industri A S All rights reserved G 3800 X015 Configuration Software October 2002 2 4 4 The Smoke Alarm e Function Fire alarm system including Passive detector Active detector Reset Alarm Siren AD and Alarm signal e Application Wiring of smoke fire indicators to an alarm system e Select with mouse Smoke alarm or short cut key S Description The purpose of the Smoke Alarm is an alarm system consisting of smoke and fire indicators integrated as Passive or Active detectors The wiring makes it possible to replace conventional fire alarm systems Smoke detectors are generally included in the system through the objects Passive detector or Active detector The alarm system is automatically alert after elapse of the Reset delay set with the Reset object when the Configuration software has been downloaded or the Master Generator has been switched on The Reset output switches on wi
72. ms Apart from the contacts represented by their own objects Passive and Active dectector it is also possible to include toggle switch functions and motion detectors which have already been configured This is done directly when setting the parameters for these objects A system which is enabled will then start an alarm when one or several alarm contacts have been activated The channel for the activated alarm channels as alarm source indication as well as the alarm output start to flash after the set time delay By subsequent activation of the Manual armouring the Door lock armouring or Code lock armouring the Master Generator switches the channel out of the system and switches the alarm output off If an alarm is not acknowledged before elapse of the alarm signal delay the system automatically becomes alert again Note Configuration of the objects Manual armouring Door lock armouring or Code lock armouring is absolutely necessary to ensure correct function It is not necessary to use the objects Manual armouring or Code lock armouring but it is possible to have an operation mode in addition to or in stead of the Manual armouring By use of two objects an alarm must necessarily be acknowledged with the object which is also used to alert the system The status of the alarm detectors can be shown in a simple way on a panel All that is needed for this purpose is that the output channels are coded to t
73. n to start the timer by means of a short impulse eg through a push button switch On delay Enter the time 0 s to 99 h 59 min 59 s which must pass before the channel is activated Off time Enter the time 0 s to 99 h 59 min 59 s for which the channel should be activat ed 2002 Carlo Gavazzi Industri A S All rights reserved 17 G 3800 X015 Configuration Software October 2002 Parameter Description Enabled by address Entering of an additional channel A1 P8 or flag W1 Z8 which will also enable the timer function To prevent locking the channel assigned to the timer itself must not be used If the additional signal is an impulse select the option Activation by pulse Recycler Configuration window for recycler Timer function C On Off delay Recycler Enabled by address On Time Hour Minute Seconds foo fos foo Off Time Hour Minute Seconds fe fo fe Parameter Description Timer function To select the Recycler function select Recycler On time Entering of the time 1 s to 99 h 59 min 69 s for which the output is On during recycling Off time Entering of the time 0 s to 99 h 59 min 59 s for which the output is Off during recycling Enabled by address Entering of an additional channel or flag which will also enable the recycler To pre vent locking the channel assigned to the recycler itself must no
74. n with the decentralized up down roller blind function 2002 Carlo Gavazzi Industri A S All rights reserved 63 G 3800 X015 Configuration Software October 2002 2 6 Counter and Multiplexer 2 6 1 Multiplexer transmission of counter values Description e Function Object for detection of max 128 counter values e Application Registration of energy and operating hours with counter module G 4420 7401 e Configuration through the option Counter and Mux Analog Setup in the edit menu Counter and Mux Analog Setu x Counter range Counter No of values 0 9999 x foie Multiplexer count Multiplexer delay The counter channels with the sum sign are for transmission of counter values This multiplex transmission of up to 128 counter values is dedicated to the use of the counter module G 4420 7401 The range of values to be transmitted can be selected in the Basic setup through the option Counter range Depending on the range of values a corresponding number of address groups are reserved whereby the Multiplex system is started Hint The reserved addresses must not be used for other purposes eg to output switch commands There are no further configuration possibilities in the Configuration software addressing of the channels as well as transmission and saving of data is carried out automatically by the Master Generator Module configuration Detection of the counter values req
75. nge Channels for B1 F8 counter values Toggle switch function Switches for power G1 N8 2002 Carlo Gavazzi Industri A S All rights reserved 65 G 3800 X015 Configuration Software October 2002 2 6 2 Multiplexer transmission of analog values Description e Function Object for detection of max 112 analog values Mi e Application Fast transmission of multiplexed analog values through Dupline analog modules e Configuration under the option Multiplexer channels in the Basic setup The original multiplexing of analog values makes it possible ot read and write Dupline multiplex analog val ues As opposed to AnaLink transmission with analog sensors two addresses are needed in stead of one which allows transmission of accurate analog values The transmission speed is also higher A full analog val ue needs one bus cycle at best AnaLink values need 256 cycles While for the transmission of counter values see chapter 2 6 1 only input modules are available various Dupline output modules are available for multiplex analog values The output modules have the output ranges 0 20 mA 4 20 mA and 0 10 V In connection with the configuration of the multiplexer in the Basic setup Options Multiplexer Count and Mul tiplexer delay the Configuration software automatically reserves four channels A1 A4 for addressing the modules The addressing on these channels is performed automatically by the Mast
76. not active the first pair of limit values will apply when it is active the second pair will apply The value can be overwritten at any time and deleted by the Delete key 2002 Carlo Gavazzi Industri A S All rights reserved 27 G 3800 X015 Configuration Software October 2002 Time characteristics Sensor for display of measuring values In this application the displayed value follows the actual value after a short delay Note Upon switch on of the sensor or the Dupline bus the actual sensor value is only reached after a time elapse of 30 s This time is needed by the system to calculate the value accurately Sensor as switching channel The time characteristics of the sensors are here illustrated by the example of a temperature sensor the upper curve shows the room temperature the curve in the middle shows the Disable address and the lower curve shows temperature sensor as switching channel Room temperature Value for Off gt Limit Value for On lt Limit t Disable address t Temperature sensor 2 E 2 t tt it Gi th to ts ta ts te The room temperature drops to the value entered for On gt Limit eg 21 C Since no Disable Address is entered the object Temperature sensor switches the channel on The temperature reaches the value entered for Off lt Limit eg 17 C Since a Disable Address is still not entered the channel assigned to the Temperature sensor
77. om 1 Com 2 Com 3 or Com 4 port for connection of the G3800X015 Generator 1 2 4 Tools menu Generator firmware In this menu it is possible to download a new firmware file to the Generator New firmware files are typically made available when new features are added to the Generator Three steps need to be carried out 1 Browse to select the desired firmware file 2 Activate the Download button 3 Activate the program button 2002 Carlo Gavazzi Industri A S All rights reserved 7 G 3800 X015 Configuration Software October 2002 1 2 5 Help menu File Edit 3l am 5 m General information F Inorder to call Help on the objects or their configuration position the cursor on the desired object and press F1 By clicking on an address field with the right mouse button the selection of Functions opens G The desired Function is selected with the left mouse button 4 click on the selected function with the left mouse button opens the configuration Properties window for that particular Function H Often used functions can also be entered via the keyboard The functions main window must be activated accordingly click on Title bar The Following letters are used O zero Push button F Toggle switch Flip Flop if Timer channel R Real time channel M Master function 5 Smoke alarm I Intruder alarm wW Water alarm 4 154 alarm The arrow keys are used to move between the
78. on after expiry of the roll time Address By activation of the entered channel address the roller blind runs in the selected direction for the entered roll time As long as the indicated priority channel is set input signals on the roller blind channels are ignored Note The priority channel also overrides the master control Priority A channel or flag can be entered by which the up or down direction of the roller blinds is given priority 58 2002 Carlo Gavazzi Industri A S All rights reserved G 3800 X015 Configuration Software October 2002 Time characteristics Up button Down button Up channel Down channel pD_1a PMan_TRollerU The above illustration is based on a roller blind application with adjustment of tilting blinds Reverse Up time Ty of 3s ti to ts ti ts te tz The button for the up direction is activated Since the impulse is shorter than the Reverse Up time Tv 3 s the motor stops when the button is released The up direction is activated again Since the impulse this time is longer than the Reverse Up time Ty the roller master control attempts to switch the channel on for the total roll time An additional actuation in the same direction stops the motor Now the button for the up direction is activated again and the motor consequently started in the up direction By activation of the button for the down direction the motor is
79. on is reached or the set roll time has elapsed e After elapse of the Down time the motors run in the Up direction provided that a Reverse Up time has been entered and the Tilting blinds function has been activated at the decentral roller blind control e During the master command all motors can also be actuated through their individual decentral roller blind control channels All functions of the decentral roller blind control are available Stop reversal of direction adjustment of tilting blinds Automation of master command Surely many methods of automatic operation of roller blinds exist Not only wind and rain sensors but also light sensors and clock timers increase comfort through automatic functions Such functions should if not configured as priority address usually be made by means of Logic setup where primarily edge triggering is to be used which prevents continuous signals and allows permanent con trol by the operator Further details can be found in the chapter describing the logic setup Hint Please be aware that in the application of clock timers in particular only one master command can be executed at a time When several master commands are activated at the same time the Controller only exe cutes the command with the highest address number eg H3 H4 before F7 F8 2002 Carlo Gavazzi Industri A S All rights reserved 61 G 3800 X015 Configuration Software October 2002
80. ponse from a called number is entered Otherwise the next number will be called Acknowledge Either a request a command or an empty SMS password must be included if user password is selected Message Identifying text Optional SMS identifier text that will be included in the SMS messages sent by the Generator Erase SMS on Slmcard during Power Up Check this box to erase old unread SMS messages on the SimCard during System power Up This is to prevent out dated messages from interfering Check Dial in Numbers Check this box to activate the Dial In number protection Any received SMS message contains the original phone number This number must exist in the Dial In numbers list before any command is accepted by the Master Generator when this option is selected Allowed Dial in Numbers Enter the phone numbers which are allowed to send control and read com mands to the Generator The country code must be included in the numbers e g 4520213324 Use Password Check this box to activate the Password protection Any received SMS mes sage will then be checked for the correct password before any command is accepted by the Mastergenerator Dial in Password Type in a password with 4 characters to be used in case Use Password is selected Dial Out Phone Numbers Up to 4 telephone numbers where the SMS messages shall be sent to can be entered The country code must be included in the numbers e g
81. ppendix for further information about the LED indications In order to set up the basic SMS functions select SMS Setup in the Edit menu Parameters Parameter Description sms Setup x Dial Dut Phone Numbers 452021 3324 Simultaneously X Max User Responce Time 01 Minutes One by One to acknowledge A ioe Gana er Max User Responce Time Test application o2 Minutes JV Erase SMS on Simcard during Power Up rm Dial in Security options IV Check Dial in numbers IV Use Password Allowed Dial In Numbers Dial In Password _ Searching for GSM modem CLET PT y am ray 72 2002 Carlo Gavazzi Industri A S All rights reserved G 3800 X015 Configuration Software October 2002 Parameter Description Dial Out Phone Numbers Up to 4 telephone numbers to which the SMS messages shall be sent can be entered The country code must be included in the numbers e g 4520213324 It can be selected if an event based SMS message shall be sent out to all the telephone numbers on the list simultaneously or if it shall be sent to the tele phone numbers one by one until an acknowledgement is received Acknowl edgement is performed by sending either a request or just an empty SMS mes sage to the Generator Max User Response time Only valid when one by one to acknowledge is selected Here the maximum time the Generator shall wait for a res
82. rm output is to remain activated when an alarm occurs The value can lie between 0 and 60 min The system becomes alert again when the siren time has elapsed and no alarm contact is activated any more A value entered here is automatically adopted by the Common siren Flash when Alarm By ticking off this checkbox the option Flashing Channels allows you to select which channels are to flash in case of alarm as well as their flash interval see below The alarm siren channel is thereby constantly switched on Note The options Flash Interval and Flashing Channels only appear when the option Flash when Alarm has been selected Flash Interval Here you can enter the switch on off time span of the flashing alarm signals The option Flash when Alarm must be switches on The value can lie between 0 and 60 s Please note that flash intervals below 2 seconds may turn out inaccurately because of the cycle time When the value 0 is entered flashing takes place at the fastest possible rate Flashing Channels By mouse click on this option an address matrix appears in which you can select the channels which are to flash upon an alarm This option is only available when the option Flash when Alarm has been selected Alarm signal Channel function Passive detector C Active detector Manual armouring Door lock armouring Code Lock armouring Alarm siren Alarm signal Alarm signal delay j2 Minutes
83. s pressed for less than three seconds the motor stops when the key is no longer pressed e If the direction key is pressed for more than three seconds the motor runs to the end position or for the duration of the run time Here it is also possible to stop the motor by pressing the key once more or let it run in the opposite direction by pressing the other direction key The Tilted blinds function makes it possible to activate the sun blinds shortly so that in stead of causing up or down movenment it changes the position of the tilting blinds Automating the roller blind control Surely many methods of automatic operation of roller blinds exist Not only wind and rain sensors but also light sensors and clock timers increase comfort through automatic functions Such functions should if not configured as priority address usually be made by means of Logic setup where primarily edge triggering is to be used which prevents continuous signals and allows permanent opera tor control Further details can be found in the chapter on Logic Setup 56 2002 Carlo Gavazzi Industri A S All rights reserved G 3800 X015 Configuration Software October 2002 Connection of several motors Simultaneous activation of several motors can be achieved by 1 connecting all motors to separate outputs and 2 assigning the same address to all up channels as well as all down channels We strongly advise against connecting two or more motors in paralle
84. ses cor respond to those of the alarm contacts The alarm is sounded through a horn which is activated through address D2 of a relay module The alarm is reset again by a pushbutton on address H1 54 2002 Carlo Gavazzi Industri A S All rights reserved G 3800 X015 Configuration Software October 2002 2 4 7 Common Siren e Function Common output of ISA Smoke Intruder and Water alarm rama e Application Output of several alarms on one siren in addition to or in replacement of alarm system specific sirens e Select with mouse Common Siren Description The Common Siren offers the possibility of transmitting the alarms of all alarm systems on one channel The alarm of the siren output behaves in the same way as the individual alarm sirens If several alarms are on they are indicated wtih the following priority 1 Smoke alarm 2 Intruder alarm 3 Water alarm 4 ISA alarm The operation of the common siren is independent of whether a siren was configured in the individual alarm system Note The signal time entered in the Common siren is automatically adopted by the individual sirens This also applies to reversed function If an alarm has been acknowledged or reset the Master Generator also resets the signal of the common siren Parameters Parameter Description Common siren Channel function Siren time JV Smokealarm fio Minutes JV Intruderalarm Minutes JV Wateralarm Jos Minut
85. t activation of the reset key the Master Generator resets the stepping through of the alarm contacts and the alarm output If contacts are still activated another alarm is triggered off after elapse of the reset delay Note Configuration of the object Reset is absolutely necessary to ensure correct function The status of the alarm contacts can be shown in a simple way on a panel All that is needed for this purpose is that the output channels are coded to the addresses of the alarm contacts The object Alarm signal makes it possible to control a telephone or GSM modem because of the short mes sage on this channel For alarm purposes the object Common Siren can also be used Details can be found in the chapter describ ing the alarm siren Common siren The various fire alarm objects are selected under Channel function Passive detector Normally open input This object makes it possible to include 3 passive detectors When the contact is activated and a 1 Signal consequently transmitted on the Dupline bus an alarm is started Active detector 1 Normally closed input This object makes it possible to include active detectors When the contact is activated and a 0 Signal consequently transmitted on the Dupline bus an alarm is started Reset p This object makes it possible to include a button to reset the alarm and restart the se system s Ifa contact is activated during reset a new alarm is s
86. t be used Time characteristics Timer with on or off delay OUT PMan_TTimer_ta t G t t te G The on delay te starts shortly after the input signal at time t After elapse of the delay the On time ty starts After elapse of the On time ts the output switches off again To achieve this the input must be reset before time ts 18 2002 Carlo Gavazzi Industri A S All rights reserved G 3800 X015 Configuration Software October 2002 Recycler OUT t t tz tz t PMan_TTimer_2a The impulse is generated shortly after the input has switched on at time t A pulse cycle consists of the On time te and the Off time ta When the input is switched off the pulse cycle also ends Application Example Task A fan in a bathroom is to start 5 min after the light has been switched on and run for 10 min Solution The lighting is activated by a push button connected to a sensor module for example a univer sal input module and configured for address A1 as a toggle switch function An output of a relay module is assigned the same address and activates the lighting A second channel A2 is configured as Timer and activated by the above mentioned push button An additional channel of the output module is also assigned the address A2 and activates the fan Object Function Channel In outputs Relay output Bathroom light A1 Switch Light switch A1 Relay output Bat
87. tarted after elapse of the Reset delay Note This object must be configured in order to achieve correct function of the water alarm system Alarm siren ra The alarm siren indicates the occurrence of an alarm The channel configured se for this object can be used for alarm output on any output modules It usually activates a relay output switching a siren In case of alarm this output flashes with an on time of approx 3 s and an off time of approx 57 s Alarm signal When an alarm occurs a channel configured for this object is activated for 10 Ja s and can thus be used to activate a telephone or GSM modem 50 2002 Carlo Gavazzi Industri A S All rights reserved G 3800 X015 Configuration Software October 2002 Parameters Parameter Description Passive detector Channel function Passive detector C Active detector C Reset Alarm siren Alarm signal Disable address _ Disable address Enter an address A1 P8 or a flag W1 Z8 whose activation 1 signal will leave out the Passive detector function of the monitoring system whereby it cannot trig ger off any further alarms Active detector Channel function Passive detector Active detector Reset Alarm siren Alarm signal Disable address Disable address Enter an address A1 P8 or a flag W1 Z8 whose activation 1 signal will leave out the Active dete
88. tector Of course other smoke detectors can also be used if they provide a Normally closed or Normally open contact In this case the connection to the Dupline system can take place through a digital input 3 Intruder alarm chapter 2 4 5 This system provides objects which allow monitoring of input signals for the intruder alarm The inputs can be either floating or non floating contacts connected to the system through digital Dupline inputs 4 Water alarm chapter 2 4 6 The Water alarm was developed as a separate system intended for the connection of water stop sensors The alarm systems differ in the following ways In the armouring manual door lock In the type of alarm resetting Acknowledgement Reset In the way of alarming and In the time characteristics 2 4 2 General features 2 4 2 1 In output on one channel The alarm systems benefit more than any objects fromt he capability of Dupline to differ between in and out puts on the same channel Split I O Thereby it is possible to use a Normally open contact to reset the system and subsequently switch it in and out alternately The user should therefore not be surprised when a channel is activated without an input being activated or a channel is not activated although an input is activated 2 4 2 2 Master functions Alarm objects can generally not be affected by master functions 2002 Carlo Gavazzi Industri A S All rights reserved 33 G 3800 X015 Configura
89. thin this time An alarm is triggered off when one or several alarm contacts are activated for more than 10 s The channel for the activated alarm contacts alarm source indication as well as the alarm output start to flash approx every second By subsequent activation of the reset key the Master Generator switches the channel out of the sys tem If contacts are still activated another alarm is triggered off after elapse of the reset delay Note Configuration of the object Reset is absolutely necessary to ensure correct function The status of the alarm contacts can be shown in a simple way on a panel All that is needed for this purpose is that the output channels are coded to the addresses of the alarm contacts The object Alarm signal makes it possible to control a telephone or GSM modem because of the short mes sage on this channel For alarm purposes the object Common Siren can also be used Details can be found in the section describ ing The alarm siren Common siren The various smoke alarm objects are set under Channel function Passive detector a Normally open input This object makes it possible to include db passive detectors When the contact is activated and a 1 Signal consequently transmitted on the Dupline bus an alarm is started Active detector 1 Normally closed input This object makes it possible to include A active detectors When the contact is activated and a 0 Signal
90. tion Software October 2002 2 4 3 ISA Alarm e Function General alarm system with inclusion of Passive detector Active detector a Acknowledgement Reset Lamp test and Alarm siren isA e Application Monitoring of contacts and other alarm sources e Select with mouse ISA alarm or short cut key A Description The purpose of the ISA Alarm is to serve as a general alarm system acc to the ISA specifications The system supports two operation modes 1 Standard An alarm is reset Reset and switched on again manually by push button 2 Auto reset An alarm is reset and switched on again automatically after acknowledgement and removal of the cause of alarm Normal position of the alarm contacts Alarm contacts are generally included in the system through the objects Passive detector and Active detector The alarm system is switched on for the first time after downloading of the application when all alarm contacts are in off position or the Reset button is activated The alarm is released when one or several alarm contacts are activated The system actuates the activated alarm contact approx every second and switches the alarm output on for the set duration When the Acknowledgement button has been actuated in the Standard operation mode the alarm contacts switch from flashing to continuous operation and the alarm output is switched off At this point of time renewed actuation of an alarm cont
91. ts After elapse of the alarm signal delay Tm set at the object Alarm signal the channel is briefly activated At the same time the alarm contact is continuously switched off and the Manual Armouring output continuously switched on 48 2002 Carlo Gavazzi Industri A S All rights reserved G 3800 X015 Configuration Software October 2002 tz Activation of the Manual Armouring will acknowledge the alarm and the Manual Armouring output will be reset ts Activating the Manual Armouring once more will bring the system back into the alert state after the armouring delay Trv Application Example Task Solution In a residential building eight rooms are to be equipped with window and door contacts All light switches as well as two motion detectors are to be included in the system When an alarm occurs a siren switches on and the police is informed via a telephone modem A panel shows the source of the alarm The system should moreover make it possible to disable the alarm contacts on each floor The alarm contacts are grouped room wise switched in series Each room is assigned to a NO contact within the range E1 E8 The source of the alarm is shown on a panel whose LED is acitvated via a mimic display The addresses correspond to those of the alarm contacts The alarm is sounded through a horn which is activated via a relay on address F3 The alarm can be brought into the alert state as well as acknowledged through
92. uires correct setting of the counter module G 4420 7401 Apart from the setting the counter range it is also necessary to assign an address to each module through rotary switch Data format A description of the used data format can be found in the user manual of the counter module G 4420 7401 Counter value output Access to and output of the stored counter values is only done through the Modbus communication interface of the Master Generator There are basically 3 possibilities of continued processing 1 Representing the values in visualization software or operator panel eg on a PC with the Dupline Web Server 2 Through communication programmes eg the Dupline DDEServer an open software interface to for example Microsoft Office applications 3 Individual reset of counter values Simultaneous operation with Multiplex Analog Value Transmisison If transmission of counter and analog values is needed care should be taken to avoid address overlap The transmission channels of the analog modules must be set so that they do not overlap the channels of the counter value transmission Read the following chapter 2 6 2 Multiplexer Transmission of analog values 64 2002 Carlo Gavazzi Industri A S All rights reserved G 3800 X015 Configuration Software October 2002 Parameters Parameter Description Multiplexer Detection of counter values Counter range 0 9999 Multiplexer count
93. uracy on the Realtime clock can be achieved Syncronize Time to PC date and Time If this button is activated when the Generator is connected to the PC then the PC date and time will be trans ferred to the realtime clock of the Generator 10 2002 Carlo Gavazzi Industri A S All rights reserved G 3800 X015 Configuration Software October 2002 2 Objects 2 1 General The objects are the specific functions of the G 3800 X015 The functions are assigned to channels and the associated parameters determines the operation of the channels 2002 Carlo Gavazzi Industri A S All rights reserved 11 G 3800 X015 Configuration Software October 2002 2 2 Standard objects 2 2 1 Blank channel no function Description Parameters e Function None e Application Activation of output channels through master functions or logic setups e Insert with mouse Blank channel The use of blank channels in Dupline is based on the circumstance that in and output are independent of each other Since this object does not fulfill a function between in and output an input on the address con figured as blank function will be ineffective At the same time it is possible to control the channel and consequently the functions coded for the address either through the master function See chapter 2 2 6 or as output of logic setups See chapter 3 In addition a blank channel can be used as a monostable flag
94. ved 69 G 3800 X015 Configuration Software October 2002 The following tables summarize the results of the logic setups Example If in the XOR function both input 1 E1 and input 2 E2 have the value 1 the output A will assume the value 0 3 3 2 Inversion and Edge Triggering A special feature of the logic functions is the possibility of inverting the output e When a minus is added in front of the value the input value and consequently the output are inverted ie if the input had the value 0 it gets the value 1 and vice versa e Adding a slash in front of the address leads to triggering on leading edge e Adding a backslash in front of the address leads to triggering on trailing edge This change in ouput does not affect the input channels or flags 3 3 2 1 Inversion Inversion can be applied to both channels and flags The output can be of any type Example of a logic setup Output Input 1 Function Input 2 A1 E1 AND E2 Time characteristics gt t A1 o Output A is only active when input E1 is active and input E2 is not active range between the dotted lines The internal processing in the Master Generator inverts the value of E2 before it is output ie sees it as active 3 3 2 2 Example of Edge Triggering Edge triggering can only be used on channels A1 to P8 Since the proc
95. y time is observed The up channel generally overrides the down channel ie if both are activated at the same time the Master Generator will execute the up command Address configuration The roller blind control can only be configured for an uneven channel number This means that the up channel must have an uneven address number assigned to it and the down channel must have an even address num ber assigned to it This reflects the address coding of the roller blind modules Here the up channel must also have an uneven output assigned to it while the down channel must have an even output channel addressed to it Note When in spite of correct address configuration the motor runs in the opposite direction the corre sponding connecting cables of the motor are reversed In this case correct connection must be ensured the channels must under no circumstances be reversed Operation The up and down buttons configured for the addresses of the roller blind control allow very simple operation e By pressing the direction key once the motor runs to the end position or for the duration of the roll time e By pressing the same direction key once more the motor stops e By pressing in the opposite direction the motor stops shortly and runs in the opposite direction until it reaches end position or for the duration of the roll time When the option Tilted blinds is selected the following options are available e If the direction key i