Contents
1. 1 008 shutter 1bit 22 Rocker A left COMB OBJ3 C T DPT 18 001 scene 1byte 23 Rocker A left COMB OBJ4 C T DPT 1 010 sequence 1bit 24 Rocker A left COMB OBJ5 C T DPT 5 001 percentage 1byte 25 Rocker A left COMB OBJ6 C 1 001 threshold 0 255 1bit 26 Rocker A left COMB 7 T DPT 1 008 string 14bytes 1bit 27 Rocker A left COMB OBJ8 18 001 switching 1byte 28 Rocker A left COMB OBJ9 C T DPT 1 010 shutter 1bit Guangzhou Hedong Electronic Co Ltd HDL www hdlchina com 38 43 Panel controlle PV2 HDL KNX EIB BUS 29 Rocker A left COMB OBJ10 switching T DPT 5 001 1byte These communication objects used for control of multiple objects at the same time You can set different objects NO Object name Function Flags Data type 20 Rocker A right COMB OBJ1 C T DPT 1 001 switching 1bit 21 Rocker A right COMB OBJ2 C T DPT 1 008 shutter 1bit 22 Rocker A right COMB OBJ3 C T DPT 18 001 scene 1byte 23 Rocker A right COMB OBJ4 C T DPT 1 010 sequence 1bit 24 Rocker A right COMB OBJ5 C T DPT 5 001 percentage 1byte 25 Rocker A right COMB OBJ6 C T DPT 1 001 switching 1bit 26 Rocker A right COMB OBJ7 C T DPT 1 008 shutter bit 27 Rocker A right COMB OBJ8 C T DPT 18 001 scene 1byte 28 Rocker A right COMB OBJ9 C T DPT 1 010 sequence 1bit 29 Rocker A right COMB OBJ10 C T DPT 5 001 percentage 1byte Th
2. 38 5 Applications rem 40 Guangzhou Hedong Electronic Co Ltd HDL www hdichina com 2 43 HDL KNX EIB BUS Panel controlle PV2 1 Product introduction HDL KNX EIB series Panel controller PV2 are developed by HDL Using KNX EIB BUS communication with other KNX devices Database need to be downloaded to the Panel controller by using the ETS2 V1 3 vd2 ETS 3 0 vd3 ETS4 The document describes how to use the product Our products use standard according to EMC electrical safety environmental conditions This product has the accept function of infrared remote control So through infrared remote control can be reach the aim of control directly The panels are can be use as Switch Dimmer Shutter control Flexible control Scene control Sequence control Percentage control Threshold control Combination control String 14bytes controller Button Lock Button Trigger Other Controlled equipments The rights and the copyright to this manual are exclusively the property of HDL Guangzhou Hedong Electronic Co Ltd HDL www hdlchina com 3 43 HDL KNX EIB BUS 1 1 Product Function M P01 2 M P02 2 M P04 2 Panel controlle PV2 For M P01 2 M P02 2 M P03 2 M P04 2 require The manual take M P04 2 for example The following functions can be
3. wake Vid det Siding i ES Pu m I 21 Rocker A left long Switching Toggle 1 bit W T U 1 bit DPT_Switch Low 122 Rocker right short Switching Toggle 1 bit W T U 1 bit DPT_Switch Low 23 Rocker right long Switching Toggle 1 bit W T U 1 bit DPT_Switch Low NO Object name Function Flags Data type 20 Rocker A left short 21 Rocker A left long Switching C W T U DPT 1 001 22 Rocker A right short ON Toggle ibit 23 Rocker A right short These communication objects used for switching other switch device Send telegram value 1 for ON send telegram value 0 for OFF Tips Rocker A set up different work mode will have different function but the same object number Other rockers are same to rocker A Guangzhou Hedong Electronic Co Ltd HDL www hdlchina com 34 43 HDL KNX EIB BUS Panel controlle PV2 4 3 Objects Dimming controller 220 Rocker A left short Switching 1 1 bit C W T U 1 bit DPT_Switch Low 21 Rocker A left long Dimming 4 bit C W T U 3 bit controll Low 2022 Rocker right short Switching Toggle 1 bit E W T U 1 bit DPT Switch Low mzs Rocker A right long Dimming 4 bit G W T U 3 bit controll Low NO Object name Function Flags Data type 20 Rocker A left short Switching Toggle W T U DPT 1 001 1bit 21 Rocker A left long Dimming C W T U DPT 3 007 4bit 22 Rocker A right short Switching
4. 1 telegram value 1 is start Stop with 0 telegram value 0 is stop gt Reaction on left long button This parameter determines the work mode of the rocker A s left short button The left long button is same to the left short button Options Invalid Toggle Start 1 Stop 0 Start with 1 Stop with 0 The left long button is same to the left short button The right button s setting is same as left button Long button time after Options 0 2s 60s Set the time of long button If pressing the button longer the time is long button The default time is 1s Ifyou select double buttons mode Rock A s setting as follows Double buttons mode rocker A must set the same targets but you can set the different states of the targets Reaction on short button This parameter determines the work mode of the rocker A s short button Options Invalid Left start with 1 Right stop with 0 Left stop with 0 Right start with 1 Left start with 1 Right start with 1 Left stop with 0 Right stop with 0 Invalid rocker A is invalid Left toggle Right toggle Left and right are all toggle Left start with 1 Right stop with 0 Left button telegram value is Right button telegram value is 0 Guangzhou Hedong Electronic Co Ltd HDL www hdlchina com 26 43 HDL KNX EIB BUS Panel controlle PV2 Left stop with 0 Right start with 1 Left button telegram value is 0 Right button tele
5. 255 gt Threshold on right long 0 255 Delay on right short button 0 255s Delay on right long button 0 2553 Long button time after 1s LED status According to object status Fig10 Threshold controller window Threshold value type Option 1 byte threshold 2 bytes threshold Threshold on left short button 0 255 Set the light level of left short button Options 0 255 When select 2 bytes threshold that the option s range is O 65535 Threshold on left long button Set the light level of left long button Guangzhou Hedong Electronic Co Ltd HDL www hdlchina com 29 43 HDL KNX EIB BUS Panel controlle PV2 Options 0 255 When select 2 bytes threshold that the option s range is 0 65535 Delay on left short button 0 255S Set the delay time of left short button after press The delay time range is 0 255S Options 0 255S Delay on left long button 0 255S Set the delay time of left long button after press The delay time range is 0 255S Options 0 255S The right button s setting is same as left button gt Long button time after Set long button time the default time is 1s Options 0 2S 60S LED status Set the status of LED Options Flashing Always ON Always OFF According to object status Flashing when pressing the button LED will flashing Always ON LED s status always ON Always OFF LED s status always OFF According to object
6. T WV Low NO Object name Function Flags Data type 0 General Heartbeat telegram C T DPT 5 001 1byte 1 General Change LED brightness CWT This communication object is used to change LED brightness function NO Object name Function Flags Data type Guangzhou Hedong Electronic Co Ltd HDL www hdichina com 33 43 HDL KNX EIB BUS Panel controlle PV2 2 General Infrared C W T U 1 003 active inactive 1bit This communication object used to enable or disable the infrared function if receive the value 1 and the infrared function is enabled if receive the value O and the infrared function is disabled NO Object name Function Flags Data type 3 General Lock buttons C W T U DPT 1 003 1bit This communication object used to lock the button if receive the value O and all buttons locked if receive the value 1 and all buttons is unlocked NO Object name Function Flags Data type 4 11 General Trigger left orright C W T U DPT 1 008 of rocker N 1bit These communication objects used to trigger the button If receive the value 1 and the single button triggered if receive the value O and the button not triggered It is only can get a short operation when using the remote trigger button objects Long operate is impossible 4 2 Objects Switch controller Priorit Heartbeat telegram
7. delay for operation left button YES If you select yes will appears some parameter as follows gt Delay for left button ves Delay for switch ON of left short button D 255s Delay for switch OFF of left short button 0 255s 0 Delay for switch ON of left long button 0 255s 0 mM Delay for switch OFF of left long button 0 255s 0 lt Set the delay time for button delay operation The delay time range is 0 255S gt Reaction on right short button gt Reaction on right long button gt Delay for right button Right button 5 setting as same as left button gt Long button time after Set long button time the default time is 1s Options 0 2S 60S LED status Set the status of LED Options Flashing Always ON Always OFF According to object status Flashing when pressing the button LED will flashing Guangzhou Hedong Electronic Co Ltd HDL www hdichina com 13 43 HDL KNX EIB BUS Panel controlle PV2 Always ON LED s status always ON Always OFF LED s status always OFF According to object status LED s status is same to the object s status Ifyou select double buttons mode Rock A s setting as follows Double buttons mode rocker A must set the same control targets but you can set the different states for the buttons gt Reaction on short button This parameter determines the work mode of the rocker A s short button Options Invalid Left to
8. on left short button Set the light level of left short button Options 0 0 100 255 Percentage on left long button Set the light level of left long button Options 0 0 100 255 Delay on left short button 0 255S Set the delay time of left short button after press The delay time range is 0 255S Options 0 255S Delay on left long button 0 255S Set the delay time of left long button after press The delay time range is 0 255S Options 0 255S The right button s setting is same as left button gt Long button time after Set long button time the default time is 1s Options 0 2S 60S LED status Guangzhou Hedong Electronic Co Ltd HDL www hdlchina com 28 43 HDL KNX EIB BUS Panel controlle PV2 Set the status of LED Options Flashing Always ON Always OFF According to object status Flashing when pressing the button LED will flashing Always ON LED s status always ON Always OFF LED s status always OFF According to object status LED s status is same to the object s status 3 2 8 Button mode Threshold controller L 1 1 5 04 2 General Rocker A Rocker Rocker B Rocker C Rocker work mode Threshold controller Rocker D Threshold value type byte threshold gt Threshold on left short button D 255 0 gt Threshold on left long button 0 255 0 Delay on left short button 0 255s 0 Delay on left long button D 255s gt Threshold on right short button D
9. setting time it is long button Options 0 2S 60S Guangzhou Hedong Electronic Co Ltd HDL www hdlchina com 31 43 HDL KNX EIB BUS Panel controlle PV2 LED status Set the status of LED Options Flashing Always ON Always OFF According to object status Flashing when pressing the button LED will flashing Always ON LED s status always ON Always OFF LED s status always OFF According to object status LED s status is same to the object s status 3 2 10 Button mode Combination controller L il 1 5 04 2 General Rocker A Rocker A Rocker B T Racker C Rocker work mode Combination controller Rocker D LED status Flashing Left button Left button object type 1 nvalid Left button object type 2 nvalid Left button object type 3 nvalid Left button object type 4 nvalid Left button object type 5 nvalid Left button object type 6 nvalid Left button object type 7 nvalid Left button object type 8 nvalid Left button object type 3 Invalid Noct Fig12 Combination controller window LED status Set the status of LED Options Flashing Always ON Always OFF Flashing when pressing the button LED will flashing Always ON LED s status always ON Always OFF LED s status always OFF Left button Guangzhou Hedong Electronic Co Ltd HDL www hdlchina com 32 43 HDL KNX EIB BUS Panel controlle PV2 lt Left button of object1 5 Invalid Switch controller Shutter contro
10. status LED s status is same to the object s status Guangzhou Hedong Electronic Co Ltd HDL www hdlchina com 30 43 HDL KNX EIB BUS Panel controlle PV2 3 2 9 Button mode String 14 bytes controller 1 1 5 04 2 General Rocker A Rocker Rocker B m Rocker C Rocker work mode String 14bytes controller Bache String on left short button Hello gt String on left long button Hello Delay on left short button 0 255s 0 Delay on left long 0 2555 0 gt String on right short button Hello String on right long button Hello Delay on right short 0 2552 0 Delay on right long button 0 255s 0 Long button time after 15 LED status According to object status OK JI Default J Fig11 14 bytes value controller window String on left short button Short press left button can sends the value to the bus The value type is string Max lenoth is 14bytes String on left long button Long press left button can sends the value to the bus The value type is string Max length is 14bytes Delay on left short button 0 255S Set the delay time after press short button The delay time range is 0 255S Options 0 255S Delay on left long button 0 255S Set the delay time after press long button The delay time range is 0 255S Options 0 255S The right button s setting is same as left button gt Long button time after Press button more than the
11. Decrease Stop Long press left button to Decrease Stop Stepping gt Toggle Stop Long press left button to Toggle Stop Moving gt UP Long press left button to up Moving gt Down Long press left button to down Moving gt Toggle Long press left button to toggle Press Moving gt UP Release Call short button Long press left button to move up Release to call short button Press Moving gt Down Release Call short button Long press left button to move down Release to call short button Press Moving gt Toggle Release Call short button Long press left button to move toggle Release to call short button Right button s setting as same as left button gt Long button time after Set long button time the default time is 1s Options 0 2S 60S e select double buttons mode Rock A s setting as follows Guangzhou Hedong Electronic Co Ltd HDL www hdlchina com 20 43 HDL KNX EIB BUS Panel controlle PV2 Double buttons mode rocker A must set the same control targets but you can set the different states of the button gt Reaction on short button This parameter determines the work mode of the rocker A s short button Options Invalid Left Decrease Stop Right Increase Stop Left Increase Stop Right Decrease Stop Invalid button invalid Left Decrease Stop Right Increase Stop Left short button to Decrease Stop Right short button to Increase Stop Left Increase Stop Right Decrease Stop Left
12. HDL KNX EIB BUS Panel controlle PV2 E ON OFF I BEDROOM I Panel Controller PV2 DDEL M PO 1 2 M PD212 M PO3 2 Guangzhou Hedong Electronic Co Ltd HDL Guangzhou Hedong Electronic Co Ltd HDL 1 43 HDL KNX EIB BUS Panel controlle PV2 HDL KNX EIB BUS Intelligent Installation Systems Product Manual Contents 1 Product INIOGUCIION skins 3 Tol Product FUNCHION 4 2 Hardware u u ua 5 2 1 Technical data uuu ua ee Gh 5 2 2 Dimension 7 2 3 WITI QUdIaQralfl 7 2 4 Maintenance and Cautions 8 3 i n eee 9 31 Function parameter 9 3 2 Function parameter Rocker 11 3 2 1 Rockers Mode Switch controller 12 3 2 2 Rocker s mode Dimming 15 3 2 3 Rockers mode Shutter 19 3 2 4 Rockers mode Flexible controller 22 3 2 5 Roc
13. N P04 2 General Rocker Rocker B Rocker Rocker D Rocker A Rocker work mode Switch controller gt Reaction on left short button Reaction on left long button gt Delay for left button No gt Reaction on right short button Toagle gt Reaction on right long button Invalid gt Delay for right button No Long button time after 1s LED status According to object status OK Default Fig3 Switch controller parameter windows Rocker A work mode Set the rocker A s work mode Options Single button mode Double buttons mode Single button mode rocker A divided into left button and right button The left button and the right button are independent If you select single button mode Rock A s setting as follows gt Reaction on left short button This parameter determines the work mode of the rocker A s left short button Options Invalid Toggle ON OFF Toggle Left short button is toggle ON Left short button is on OFF Left short button is off gt Reaction on left long button Guangzhou Hedong Electronic Co Ltd HDL www hdlchina com 12 43 HDL KNX EIB BUS Panel controlle PV2 This parameter determines the work mode of the rocker A s left long button Options Invalid Toggle ON OFF Toggle Left long button is toggle ON Left long button is on OFF Left long button is off gt Delay for left button Options NO YES NO there is not
14. ON Release ON Press OFF Release OFF Press OFF Release OFF Press ON Release OFF Press OFF Release ON Toggle the left button is toggle Pressz ON Press left button is ON Guangzhou Hedong Electronic Co Ltd HDL www hdlchina com 22 43 HDL KNX EIB BUS Panel controlle PV2 Press ON Release ON Press and release left button are all on Press OFF Press left button is OFF Release OFF release left button is off Press OFF Release OFF Press and release left button are all off Press ON Release OFF Press left button is on release is off Press OFF Release ON Press and release left button are all off Operation of the right The right button s setting is same as left button 3 2 5 Rocker s mode Scene controller 1 1 5 04 2 General Rocker A Rocker Rocker B ee Rocker al Rocker work mode Scene controller Call scene number of the left Scene 01 Call scene number of the right Scene NO 02 Long button operation as Invalid Delay operation for left short button D 255s 0 Delay operation for right short button 0 256s 0 Long button time after 15 LED status According to object status OK Cancel Default Fig7 Scene controller window Call scene number of the left Call the scene number of left button Options Scene NO 01 Scene NO 64 Call scene number
15. Pay attention to damp proof quakeproof and dustproof Avoid rain other liquids or caustic gas Please contact professional maintenance staff or HDL service center for repair or fix Remove the dust regularly and do not wipe the unit with the volatile liquids like alcohol gasoline etc If damaged by damp or liquid turn off it immediately Regularly check the circuitry and other related circuit or cables and replace the disqualified circuitry on time For security each circuit to connect an MCB or fuse Installation location should be well ventilated pay attention to moisture shock dust proof Guangzhou Hedong Electronic Co Ltd HDL www hdlchina com 8 43 HDL KNX EIB BUS Panel controlle PV2 3 Software HDL KNX EIB Panel type is M P04 2 The Interface and the functions Apply parameters please overview the following description of the paragraph 31 Function parameter General 1 1 5 EK P04 2 Rocker B SAT Rocker C Heartbeat telegram 1 65535s 0 invalid Rocker D Brightness of the buttons Level 100 Change buttons Led brightness via EIB Enable Led brightness automatic darker Enable Led automatic darker after delay 3 255s 5 Led automatic darker brightness Level 01 Active infrared function via bus Enable Infrared default active status Active Lock the buttons via EIB Enable Enable buttons triggered via EIB Enable Fig1 General parameter window Th
16. Toggle C W T U DPT 1 001 1bit 23 Rocker Aright long Dimming C W T U DPT 3 007 4bit These communication objects used for switch or dimming the device Rock short button for switching Rocker long button for dimming 4 4 Objects Shutter controller Number Name Object Function Length W T Ul Data Type Priority D General Heartbeat telegram 1 bit C T 1 bit DPT Enable Low ES ERES ee dee CUu EE LM a 2021 Rocker A left long Move for shutter 1 bit C W T WV 1 bit DPT UpDovn Low 222 Rocker right s Adjust for shutter 1 bit T V Low 0223 Rocker right long Move for shutter 1 bit Cos W T U 1 bit DPT UpDown Low NO Object name Function Flags Data type 20 Rocker A left short Adjust for shutter C W T U DPT 1 007 1bit 21 Rocker A left long Move for shutter C W T U DPT 1 008 1bit 22 Rocker A right short Adjust for shutter C W T U DPT 1 007 1bit 23 Rocker A right long Move for shutter C W T U DPT 1 008 1bit These communication objects used for Adjust and Move for the shutter Send the telegram value 1 to adjust or move or send telegram value 0 to stop adjust or stop moving Guangzhou Hedong Electronic Co Ltd HDL www hdichina com 35 43 HDL KNX EIB BUS Panel controlle PV2 4 5 Objects Flexible controller Number Hame Object Function Ds Lengt
17. am 1 bit C T 1 bit DPT_Enable Low 8820 Rocker A Threshold 2bytes 2 Byte G W T V 2 byte unsigne Low NO Object name Function Flags Data type 20 Rocker A Threshold ibytes C W T U DPT 5 004 1byte 20 Rocker A Threshold 2byte W T U DPT 7 001 1byte This communication object used for threshold control 4 10 Objects string 14 byte value Number Name bject Function Die Length W T Data Type Priority mjo General Heartbeat telegram 1 bit C T 1 bit DPT Enable Low 0420 Rocker A String ldbytes 14 Byte E Y T V Character string Low NO Object name Function Flags Data type Guangzhou Hedong Electronic Co Ltd HDL www hdlchina com 37 43 HDL KNX EIB BUS Panel controlle PV2 Rocker A String 14 byte value C W T U DPT 16 000 14byte This communication object used for control 14 bytes string value According to the set and send corresponding string variables 4 11 Objects Combination controller Number 20 20 m21 22 23 las 26 127 2028 29 42130 131 32 33 2034 135 36 38 39 General Rocker A left Rocker A left Rocker A left Rocker A left Rocker A left Rocker A left Rocker A left Rocker A left Rocker A left Rocker A left Rocker A right Rocker A right Rocker A right Rocker A right Rocker A right Rocker A right Rocker A right Rocker A ri
18. art Low 23 Rocker A right long Sequence 1 bit C W T U 1 bit DPT Start Low NO Object name Function Flags Data type 20 Rocker A left short Sequence C W T U DPT 1 010 1bit 21 Rocker A left long Sequence C W T U DPT 1 010 1bit 22 Rocker A right short Sequence C W T U DPT 1 010 Guangzhou Hedong Electronic Co Ltd HDL www hdlchina com 36 43 HDL KNX EIB BUS Panel controlle PV2 1bit 23 Rocker A right long Sequence C W T U DPT 1 010 1bit These communication objects used for start and stop sequence Send the telegram value 1 to start one sequence and send the telegram value 0 to stop on sequence 4 8 Objects Percentage controller Number Name Object Function D Length C R W T U Data Type Priority mjo General Heartbeat telegram 1 bit C T 1 bit DPT_Enable Low 220 Rocker Percentage 1 Byte Co W T U 8 bit unsigned Low NO Object name Function Flags Data type 20 Rocker A Percentage C W T U DPT 5 001 1byte This communication object used for control some device eg Absolute dimming the brightness 4 9 Objects Threshold 1byte Number Name bject Function D Length ER T Data Type Priority mjo General Heartbeat telegram 1 bit GC T 1 bit DPT Enable Low 20 Rocker Threshold 1byte 1 Byte T V Low Number Name bject Function DU Length Y T Data Type Priority General Heartbeat telegr
19. ble Can t lock the buttons via EIB Enable Can lock the buttons via EIB Enable buttons triggered via EIB Options Disable Enable Disable Can t trigger these buttons via EIB Enable Can trigger these buttons via EIB Guangzhou Hedong Electronic Co Ltd HDL www hdlchina com 10 43 HDL KNX EIB BUS Panel controlle PV2 3 2 Function parameter Rocker L 1 1 5 04 2 General Rocker Rocker B Rocker C Rocker D Rocker A Rocker work mode Switch controller Rocker operation mode Single button mode gt Reaction on left short button Toggle Reaction on left long button Toggle gt Delay for left button gt on right short button Toggle gt Reaction on right long button Invalid gt Delay for right button No Long button time after 1s LED status According to object status Fig2 Rocker A parameter window This page is setting functions about Rocker A Rocker A work mode The Rocker N work mode can be selected with the following parameter Options Switch controller Dimming controller Shutter controller Flexible controller Scene controller Sequence controller Percentage controller Threshold controller String 14bytes controller Combination controller Guangzhou Hedong Electronic Co Ltd HDL www hdlchina com 11 43 HDL KNX EIB BUS Panel controlle PV2 3 2 1 Rocker s Mode Switch controller L 1 1 5
20. button and can set different control targets Ifyou select single button mode Rock A s setting as follows gt Reaction on left short button This parameter determines the work mode of the rocker A s left short button Options Invalid Stepping gt Increase Stop Stepping gt Decrease Stop Stepping gt Toggle Stop Moving gt UP Moving gt Down Moving gt Toggle Invalid Short press left button is invalid Stepping gt Increase Stop Short press left button to increase stop Guangzhou Hedong Electronic Co Ltd HDL www hdichina com 19 43 HDL KNX EIB BUS Panel controlle PV2 Stepping gt Decrease Stop Short press left button to Decrease Stop Stepping gt Toggle Stop Short press left button to toggle stop Moving gt UP Short press left button to up Moving gt Down Short press left button to down Moving gt Toggle Short press left button to toggle gt Reaction on left long button This parameter determines the work mode of the rocker A s left long button Options Invalid Stepping gt Increase Stop Stepping gt Decrease Stop Stepping gt Toggle Stop Moving gt UP Moving gt Down Moving gt Toggle Press Moving gt UP Release Call short button Press Moving gt Down Release Call short button Press Moving gt Toggle Release Call short button Invalid Long press left button is invalid Stepping gt Increase Stop Long press left button to Increase Stop Stepping gt
21. deline and low voltage guideline Guangzhou Hedong Electronic Co Ltd HDL www hdlchina com 5 43 HDL KNX EIB BUS Panel controlle PV2 Pollutant Comply with ROHS Application table Max number of communication objects 230 Max number of group addresses 254 Max number of associations 254 Note The programming requires the EIB Software Tools ETS2 V1 3 or ETS3 0 or ETS4 Guangzhou Hedong Electronic Co Ltd HDL www hdlchina com 6 43 HDL KNX EIB BUS Panel controlle PV2 2 2 Dimension drawings Side M P04 2 2 3 Wiring diagram Proarammina L M P01 2 48 Lock or unlock r Proarammina KNX EIB BUS M P02 2 48 AER Programming Keep pressing these both buttons for 2s will enter programming mode Programming Lock or unlock keep pressing these both buttons together for 2s will lock or unlock the Lock or unlock panel Proarammina M P04 2 48 N A B C D Order from top to bottom Guangzhou Hedong Electronic Co Ltd HDL www hdlchina com 7 43 HDL KNX EIB BUS Panel controlle PV2 2 4Maintenance and Cautions Please read this user manual carefully before any operation Don close to the interfering devices The site should be ventilated with good cooling environment
22. e window can set the panel s base parameters Heartbeat telegram 1 65535s 0 invalid The range of the parameter is 0 to 65535s Zero is disable the function other parameter enable this function The parameter set to nonzero Device will send a telegram data cyclically when time out Send the value alternately between 0 and 1 Brightness of the buttons Set the LED s brightness of the button The LED level setting range is 00 Level100 Options Level 00 Level100 Change buttons LED brightness via bus If choose the Enable other devices on the bus can send telegram to change the LED brightness of the buttons Guangzhou Hedong Electronic Co Ltd HDL www hdichina com 9 43 HDL KNX EIB BUS Panel controlle PV2 If choose the Disable the LED brightness of the buttons can t changed by other KNX EIB devices Options Disable Enable LED brightness automatic darker It s energy saving mode If enable LED brightness will automatic become darker after a set delay Options Disable Enable Active infrared function via bus Whether activate the infrared function via bus Options Disable Enable Disable you can t activate infrared function via bus Enable you can activate infrared function via bus Infrared default active status Options Inactive active Inactive infrared default status is inactive active infrared default status is active Lock the buttons via EIB Options Disable Enable Disa
23. ese communication objects used for control of multiple objects at the same time You can set different objects Other rockers are same to rocker A Guangzhou Hedong Electronic Co Ltd HDL www hdlchina com 39 43 HDL KNX EIB BUS 5 Application 5 1 Program functions diagram Program _ Start Guangzhou Hedong Electronic Co Ltd HDL General Function 1 Panel controlle PV2 Switch controller Dimming controller Shutter controller Flexible controller Scene controller Sequence controller Percentage controller Combination controller String 14bytes Ly di controller pi gt Yes gt No 3el gt Yes No Y gt es lt gt Yes w No He gt Yes No t lt gt VYes gt No Yes No Yel gt yes No www hdlchina com Signal output 40 43 HDL KNX EIB BUS Panel controlle PV2 Guangzhou Hedong Electronic Co Ltd HDL www hdlchina com 41 43 HDL KNX EIB BUS Panel controlle PV2 Guangzhou Hedong Electronic Co Ltd HDL www hdlchina com 42 43 HDL KNX EIB BUS Panel controlle PV2 Guangzhou Hedong Electronic Co Ltd HDL www hdichina com 43 43
24. ggle Right toggle Left ON Right OFF Left OFF Right ON Left ON Right ON Left OFF Right OFF Left toggle Right toggle Left and right are all toggle Left ON RightzOFF left button is on right button is off Left OFF Right ON left button is off right button is on Left ON Right ON left and right buttons are all on Left OFF Right OFF left and right buttons are all off Reaction on long button This parameter determines the work mode of the rocker A s long button Options Invalid Left toggle Right toggle Left ON Right OFF Left OFF Right ON Left ON Right ON Left OFF Right OFF Left toggle Right toggle Left and right buttons are all toggles Left ON RightzOFF left button is on right button is off Left OFF Right ON left button is off right button is on Left ON Right ON left and right buttons are all on Left OFF Right OFF left and right buttons are all off Guangzhou Hedong Electronic Co Ltd HDL www hdlchina com 14 43 HDL KNX EIB BUS gt Delay for button Options NO YES NO there is not delay when operation button YES If you select yes will appears some parameter as follows Panel controlle PV2 gt Long button time after Set long button time the default time is 1s Options 0 2S 60S LED status Set the status of LED Options Flashing Always ON Always OFF According to object status Flashing when pressing the button LED will flashing Always ON LED s status alwa
25. ght Rocker A right Rocker A right Object Function 0825 Length Heartbeat telegram 1 bit COMB OBJ1 switching 1 bit COMB OBJ2 shutter 1 bit COMB scene 1 Byte COMB OBJ4 sequence 1 bit COMB 5 percen 1 Byte COMB OBJ6 thresh 1 Byte COMB OBJT String 14 Byte COMB OBJ switching 1 bit COMB shutter 1 bit COMB OBJ10 shutter 1 bit COMB OBJ1 switching 1 bit COMB OBJ2 shutter 1 bit COMB scene 1 Byte COMB OBJ4 scene 1 Byte COMB 5 scene 1 Byte COMB OBJ6 sequence 1 bit COMB OBJT percen 1 Byte COMB OBJ8 sequence 1 bit COMB percen 1 Byte COMB OBJ10 sequence a 00 C CG C G G G C C CO CG C G CG G C CO O I I I 1 1 1 1 1 I 1 1 m I 1 I I I I I I I I I I 3 63 I I I I I I I I I I I Data Priority 1 bit DPT_Enable Low 1 bit DPT_Switch Low 1 bit DPT_UpDown Low Low 1 bit DPT_Start Low 8 bit unsigned Low Low Character string Low 1 bit DPT Switch Low 1 bit DPT_UpDown Low 1 bit DPT UpDown Low 1 bit DPT Switch Low 1 bit DPT UpDown Low Low Low Low 1 bit DPT Start Low 8 bit unsigned Low 1 bit DPT Start Low 8 bit unsigned Low 1 bit DPT Start NO Object name Function Flags Data type 20 Rocker A left COMB OBJ1 C T DPT 1 001 switching 1bit 21 Rocker A left COMB OBJ2
26. gram value is 1 Left start with 1 Right start with 1 Left button telegram value is 1 Right button telegram value is 1 Left stop with 0 Right stop with 0 Left button telegram value is 0 Right button telegram value is 0 gt Reaction on short button The setting is same to the short button gt Long button time after Set long button time the default time is 1s Options 0 2S 60S LED status Set the status of LED Options Flashing Always ON Always OFF According to object status Flashing when pressing the button LED will flashing Always ON LED s status always ON Always OFF LED s status always OFF According to object status LED s status is same to the object s status Guangzhou Hedong Electronic Co Ltd HDL www hdlchina com 27 43 HDL KNX EIB BUS Panel controlle PV2 3 2 7 Button mode Percentage controller L 1 1 5 04 2 Coe Rocker A Rocker Rocker B Rocker C Rocker D Rocker work mode Percentage on left short button 100 255 gt Percentage on left long button 00 Delay on left short button 0 255s 0 Delay on left long button 0 255s 0 gt Percentage on right long button 100 255 gt Percentage on right long button 0 0 Delay on right short button 0 255s 0 Delay on right long button 0 255s 0 Long button time after 15 LED status According to object status Cancel Default Fig9 Percentage controller window Percentage
27. h C Y T Data Type Priority mjo General Heartbeat telegram 1 bit T 1 bit DPT Enable Low 2020 Rocker A left Flexible 1 bit W T U 1 bit DPT_Switch Low 21 Rocker A right Flexible 1 bit C W T U 1 bit DPT Svitch Low NO Object name Function Flags Data type 20 Rocker A left Flexible C W T U DPT 1 001 1bit 21 Rocker A right Flexible C W T U DPT 1 001 1bit These communication objects used for flexible control some device 4 6 Objects Scene controller Number Name Object Function Die Length C E W T Data Type Priority mjo General Heartbeat telegram 1 bit C T 1 bit DPT Enable Low cezo Rocker A short Call scene 1 Byte Low NO Object name Function Flags Data type 20 Rocker A short Call scene C W T U DPT 18 001 1byte 21 Rocker A long Scene dimming C W T U DPT 3 007 4bit These communication objects used for Call and Scene dimming Call scene NO is 1 to 64 and the value is 0 to 63 The Scene dimming is 4bits value 4 7 Objects Sequence controller Name Object Function U Data Type 080 General O O O 9 Heartbeat telegram bit DPT Enable Low p m 5 al gt lir lise iw Priority _ c et a 20 Rocker A left short Sequence 1 bit E T V Low G21 Rocker A left long Sequence 1 bit gt W T U 1 bit DPT Start Low 22 Rocker right short Sequence 1 bit W T U 1 bit DPT St
28. hort button Options Invalid Toggle ON OFF Toggle Left short button is toggle ON Left short button is on OFF Left short button is off gt Reaction on left long button This parameter determines the work mode of the rocker A s left long button Options Invalid Dim gt Brighter Dim gt Darker Dim gt Brighter Darker Dim gt Brighter Long press left button to increase light brightness Dim gt Darker Long press left button to decrease light brightness Dim gt Brighter Darker Long press left button to increase light brightness then long press left button again to decrease light brightness gt Delay for switch ON of left short button 0 255s Set the delay time for switch ON after press left short button The delay time range is 0 255S Options 0 255 gt Delay for switch OFF of left short button 0 255s Set the delay time for switch OFF after press left short button The delay time range is 0 255S Guangzhou Hedong Electronic Co Ltd HDL www hdlchina com 16 43 HDL KNX EIB BUS Panel controlle PV2 Options 0 255 gt Reaction on right short button gt Reaction on right long button gt Delay for switch ON of right short button 0 255s gt Delay for switch OFF of right short button 0 255s Right button s setting as same as left button gt Long button time after Set long button time the default time is 1s Options 0 2S 60S Ifyou select double buttons mode Rock A s sett
29. ing as follows Double buttons mode rocker A must set the same control targets but you can set the different states of the button gt Reaction on short button This parameter determines the work mode of the rocker A s short button Options Left toggle Right toggle Left ON Right OFF Left OFF Right ON Left ON Right ON Left OFF Right OFF Left toggle Right toggle Left and right buttons are all toggles Left ON RightzOFF left button is on right button is off Left OFF Right ON left button is off right button is on Left ON Right ON left and right buttons are all on Left OFF Right OFF left and right buttons are all off gt Reaction on long button This parameter determines the work mode of the rocker A s long button Options Left Dim toggle Right DIM toggle Left Brighter Right Darker Left Darker Right Bright Left Bright Right Bright Left Darker Right Darker Left Dim toggle Right DIM toggle long press left and right are all toggles Guangzhou Hedong Electronic Co Ltd HDL www hdlchina com 17 43 HDL KNX EIB BUS Panel controlle PV2 Left Brighter Right Darker long press left button to increase light brightness long press right button to decrease light brightness Left Darker Right Bright long press left button to decrease light brightness long press right button to increase light brightness Left Bright Right Bright long press left and right buttons are all to increase ligh
30. kers mode Scene 23 3 2 6 Rockers mode Sequence 25 3 2 7 Button mode Percentage 28 3 2 8 Button mode Threshold controller 29 3 2 9 Button mode String 14 bytes 31 3 2 10 Button mode Combination controller 32 4 Communication objects description J 33 4 1 Objects General ccrscsssis ES HERES Sua EP VIS E 33 4 2 Objects Switch controlle 34 4 3 Objects Dimming controlle 35 4 4 Objects Shutter controller 35 4 5 Objects Flexible 36 4 6 Objects Scene controller 36 4 7 Objects Sequence 36 4 8 Objects Percentage 37 4 9 Objects Threshold 1byte 37 4 10 Objects string 14 byte value 37 4 11 Objects Combination controller
31. ller Scene controller Sequence controller Percentage controller Threshold controller 14byte value controller string This mode is that left button can control several objects if set some these items and when press short button that can send several control telegram simultaneously Maximum control object number of each button is 5 The right button s setting is same as left button 4 Communication objects description In this section will introduce the communication objects The objects will show by setting the function enable Note In following sections the NZA B C D 41 Objects General Number Name bject Function Description Length CIDE T U Data Type Prio a General Heartbeat telegram T 1 bit DPT Enable 281 General Change button Led br 1 Byte C W T U 6 bit unsigned Low 282 General Infrared active inac 1 bit C WT U 1 bit DPT_Enable Low General Lock buttons 1 bit WT U 1 bit DPT_Enable Low General Trigger left of Rock A 1 bit G Y T W Low T s General Trigger right of Rock A 1 bit G f T V Low mje General Trigger left of Rock B 1 bit D f T W Low 1 Trigger right of Rock B 1 bit T V Low mjs General Trigger left of Rock C 1 bit C T U Low 29 General Trigger right of Rock 1 bit T T WV Low 210 General Trigger left of Rock D 1 bit C T WV Low m i General Trigger right of Rock D 1 bit
32. ode Set LED s mode Options Show via object status Always on Always off Show via object status the LED s status shows the object s status Always on the LED is always on Always off the LED is always off 3 2 6 Rocker s mode Sequence controller L 1 1 5 04 2 General Rocker A Rocker A Rocker B Rocker Rocker work mode Rocker D Rocker operation mode Double buttons mode gt Reaction on short button Left Start with 1 Right Stop with D gt Reaction on long button Invalid Long button time after 15 LED status According to object status o _J Cancel JI Default Fig8 Sequence controller window Rocker A operation mode Options single button mode Double buttons mode Single button mode rocker A divided into left button and right button can set different targets e Ifyou select single button mode Rock A s setting as follows Reaction on left short button This parameter determines the work mode of the rocker A s left short button Options Invalid Toggle Start with 1 Stop with 0 Guangzhou Hedong Electronic Co Ltd HDL www hdlchina com 25 43 HDL KNX EIB BUS Panel controlle PV2 Start with 1 Stop with 0 Invalid rocker A s left short button is invalid Toggle Start with 1 Stop with 0 rocker A s left short button is a toggle telegram value 1 is start telegram value 0 is stop Start with
33. of the right Call the scene number of right button Guangzhou Hedong Electronic Co Ltd HDL www hdichina com 23 43 HDL KNX EIB BUS Panel controlle PV2 Options Scene NO 01 Scene NO 64 Long time button operation as Set the button s functions when long button press Options Invalid Scene dimming Scene saving Dimming and Saving Scene dimming Options Left Brighter Right Darker Left Darker Right Brighter Left Brighter Right Darker left button press to increase light brightness right button press to decrease light brightness Left Darker Right Brighter left button press to decrease light brightness right button press to increase light brightness Scene saving Long button to saving the scene and the scene number is 1 64 Dimming and Saving Dimming and saving together Long press button for dimming UP DOWN Long release button for stop dimming and scene save Delay operation for left short button 0 255S Set the delay time of left short button after press The delay time range is 0 255S Options 0 255S Delay operation for right short button 0 255S Set the delay time of right short button after press The delay time range is 0 255S Options 0 255S Long button time after Set long button time the default time is 1s Options 0 2 60S Guangzhou Hedong Electronic Co Ltd HDL www hdlchina com 24 43 HDL KNX EIB BUS Panel controlle PV2 LED of the operation m
34. set individually for each control channel 1 Switch control 2 Dimming control 3 Shutter control 4 Flexible control 5 Scene control 6 Sequence control 7 Percentage control 8 Combination control 9 String control 10 Button Lock 11 Button Trigger 12 Night mode Setup 13 Infrared remote control 14 Remote trigger control Guangzhou Hedong Electronic Co Ltd HDL www hdlchina com 4 43 HDL KNX EIB BUS Panel controlle PV2 2 Hardware The technical properties of HDL KNX EIB Panel controller as the following sections 2 1 Technical data Panel type and buttons Type of Device M P01 2 M P02 2 M P03 2 M P04 2 Number of button 1 2 3 4 Power supply Operating voltage supply by the bus 21 30 V DC Current consumption EIB KNX operate lt 15 mA Connections EIB KNX Bus Connection Terminal 0 8 mm single core Operating and display Push first and last button Programming mode Temperature range Operation 5 45 Storage 25 55 Transport 25 C 70 C Environment conditions humidity max 95 Non condensing Appearance design Dimensions H x W x D 86 x 86 x41 Weight unit kg 0 26 Installation Standard GI Box 86x86 Mounting position The wall Material and Colour Glass and plastic Black or White Standard and Safety Certificated LVD Standard EN60669 2 1 EN60669 1 EMC Standard EN50090 2 2 CE mark In accordance with the EMC gui
35. short button to Increase Stop Right short button to Decrease Stop gt Reaction on long button This parameter determines the work mode of the rocker A s long button Options Invalid Left UP RightZDOWN Left DOWN Right UP Left UP DOWN Right UP DOWN Invalid Long press is invalid Left UP RightZDOWN Left long button to UP Right long button to down LeftZDOWN Right UP Left long button to down Right long button to up LeftZUP DOWN Right UP DOWN Left long button or Right long button UP DOWN gt Long button time after Set long button time the default time is 1s Options 0 2S 60S LED status Set the status of LED Options Flashing Always ON Guangzhou Hedong Electronic Co Ltd HDL www hdlchina com 21 43 HDL KNX EIB BUS Panel controlle PV2 Always OFF According to object status Flashing when pressing the button LED will flashing Always ON LED s status always ON Always OFF LED s status always OFF According to object status LED s status is same to the object s status 3 2 4 Rocker s mode Flexible controller L 1 1 5 W P04 2 General Rocker A Rocker A Rocker B Rocker C Rocker A work mode Flexible controller Rocker D Operation of the left Toggle Operation of the right Toagle LED status According to object status Cancel Default Fig6 Flexible controller window Operation of the left Options Invalid Toggle Press ON Release ON Press
36. t brightness Left Darker Right Darker long press left and right buttons are all to decrease light brightness gt Delay for switch ON of short button 0 255s Set the delay time for switch ON after press left short button The delay time range is 0 255s Options 0 255s gt Long button time after Set long button time the default time is 1s Options 0 2S 60S LED status Set the status of LED Options Flashing Always ON Always OFF According to object status Flashing when pressing the button LED will flashing Always ON LED s status always ON Always OFF LED s status always OFF According to object status LED s status is same to the object s status Guangzhou Hedong Electronic Co Ltd HDL www hdlchina com 18 43 HDL KNX EIB BUS Panel controlle PV2 3 2 3 Rocker s mode Shutter controller L 1 1 5 K P04 2 General Rocker A Rocker Rocker B Rocker C Rocker work mode Shutter controller Rocker D Rocker short button Double buttons mode Reaction on short button Left Decrease Stop Right Increase Stop gt Reaction on long button Left UP Right DO WN Long button time after 15 LED status According to object status Cancel Default Fig5 Shutter controller parameter window Rocker A short button Set the rocker A s operation mode Options Single button mode Double buttons mode Single button mode rocker A divided into left button and right
37. ys ON Always OFF LED s status always OFF According to object status LED s status is same to the object s status 3 2 2 Rocker s mode Dimming controller 1 1 5 EN P04 2 General Rocker A Rocker Rocker B Rocker C Rocker D Fig4 Dimming controller parameter windows Rocker work mode Rocker operation mode Reaction on left short button gt Reaction on left long button Delay for switch ON of left short button D 255s Delay for switch OFF of left short button D 2553 Reaction on right short button gt Reaction on right long button Delay for switch ON of right short button D 255s Delay for switch OFF of right short 0 2555 Dimming steps Long button time after LED status Dimming controller Single button mode Toggle Dim gt Brighter D arker 0 0 Toggle Dim gt Brighter D arker 0 0 Step1 100 us According to object status OK Cancel Default Rocker A operation mode Guangzhou Hedong Electronic Co Ltd HDL www hdlchina com 15 43 HDL KNX EIB BUS Panel controlle PV2 Set the rocker A s operation mode Options Single button mode Double buttons mode Single button mode rocker A divided into left button and right button and can be set different control targets e Ifyou select single button mode Rock A s setting as follows Reaction on left short button This parameter determines the work mode of the rocker A s left s