4: Eltako Powerline, monitor presentation
Contents
1. Eltako Powerline The Ideal supplement to the Eltako Wireless Building System with EnOcean Eltako Powerline Wireless Powerline gateway FPLG14 and Powerline pushbutton gateway PL FTGW Decentralised actuator PL SAM1L with sensor input and decentralised actuator PL SAM2L with sensor inputs Decentralised Venetian blind actuator PL SAM2 with sensor inputs Decentralised universal dimmer actuator with sensor input PL SAMDU Decentralised dimmer actuator PL SAMDR with sensor input and decentralised dimmer actuator PL AMD1OV Decentralised TLZ actuator PL SAMILT with sensor input and decentralised sensor input PL SMI1L Decentralised 8 channel sensor input PL SM8 and Temperature controller PLSAMTEMP for heating and cooling Coupling element PL SW PROF for Software SIENNA Professional Typical connections Technical data Powerline devices The electricity wiring in buildings acts as the Eltako Powerline bus Now you can transmit sensor data and telegrams to actuators over the existing electricity wiring instead of broadcasting wireless telegrams that is the basic difference between the two technologies Eltako ELECTRONICS Wireless Powerline Gateway and Powerline Pushbutton Gateway FPLGI4 Wireless Powerline gateway Bidirectional Standby loss only 0 4 watt Modular device for DIN EN 60715 TH35 rail mounting 2 module 36mm wide 58mm deep This gateway translates wireless and Powerline telegrams i
2. 0 2mm to 1 5 mm Next to them are three wires with wire end sleeves for the two control inputs with internal low voltage Typical connections on page 4 10 Powerline Venetian blind actuator for 1 motor EAN 4010312316689 105 40 pc Recommended retail prices excluding VAT Decentralised Universal Dimmer Actuator with Sensor Input Eitako ELECTRONICS PL SAMDU Powerline universal dimmer actuator 53x43mm 40mm deep for mounting in 58mm switch boxes Power MOSFET up to 300 W Automatic lamp detection Sensor input 230V Standby loss only 0 6 Watt To control and dim at different places Universal dimmer switch for lamps up to 300W dependent on ventilation conditions Dimmable energy saving lamps ESL and dimmable 230V LED lamps additionally dependent on the lamps electronics No minimum load Zero passage switching with soft ON and soft OFF to protect lamps short time control commands switch on off permanent control varies the brightness to the maximum level A interruption of control changes the direction of dimming The brightness level is stored on switch off memory In case of a power failure the switch position and the brightness stage are stored and may be switched on when the power supply is restored Automatic electronic overload protection and overtemperature switch off Two rotary switches are located on the front for address assignment The left rotary switch defines the group address g with 16
3. Alternative LIN NL LJ dre dresse ss Cont Reset GAL CO on esel ANL o O K A a Typical connection PL SAM2L Consumer 1 Consumer 2 PL SAM1L g PL SM1L Typical connection PL SAM2 L N L1 Up N L2 Down Venetian blind switch Venetian blind pushbutton Up I l l l Down l l PL saM2 J enoo Typical connection PL AMD10V PL AMD10V Typical connection PL SM1 Switch an additional consumer L Alternative resse Adress ad Oo SAR PD Fee Conf Rese oO PL SM1L PL SAM1L e g mirror light in bathroom socket in living room outside light Typical connection PL SAMILT Delayed switch off 3 way switch pushbutton z N L Adre adresse dress z q os Cont Reset GSA AWD 0 ORe adresse PL SAM1ILT g PL SM1L e g staircase time switch or circulation pump SAM1LT switches itself and associated actuators off after a preset time Typical connection PL SM8 LIN GND Ton Typical connection PL SAMDU Technical Data Powerline Devices Eftako ELECTRONICS PL SAMDR PL SAMDU PL SAMIL PL SAMILT Agsn0 0 5 mm Agsn0 0 5 mm Agsn0 0 5 mm J 7 N gt N Triac Contact material contact gap SAMDU Power MOSFET Agsn0
4. SAMIL PL SAMIL PL SAM2L PL SAM2L ELECTRONICS Powerline actuator with 1 channel 53x43mm 25mm deep for mounting in 58mm switch boxes Used as impulse switch or relay 1 NO contact not potential free 10 A 250V AC incandescent lamps 2000 watts Sensor input 230V Standby loss only 0 5 watt To control and switch at the same place Two rotary switches are located on the front for address assignment The left rotary switch defines the group address g with 16 alphabetical values from A fo P The right rotary switch defines the element address e with 16 numerical values from 0 to 15 Above it is a slide switch which acts as a configuration switch with positions 0 1 and 2 Position O Sensor input functions as pushbutton impulse switch Position 1 Sensor input functions as NO contact relay Position 2 A change over switch is evaluated as a pushbutton To the left of the rotary switches is a red LED which indicates all activities Next to it is a reset pushbutton and fo the right of that is a service pin For functions please refer to the operating instructions The terminals located above are plug in terminals for conductor cross sections of 0 2 mm to Lomm Typical connections on page 4 10 Powerline actuator 1 channel with sensor input 230V EAN 4010312316665 103 70 pc Powerline actuator with 2 channels 53x43 mm 25mm deep for mounting in 58mm switch boxes Used as impulse switch or relay 1 1 NO contacts not pot
5. low voltage Standby loss only 0 5 watt To control and switch at different places Use only potential free switching elements Internal low voltage applied to the sensor inputs Two rotary switches are located on the front for address assignment The left rotary switch defines the group address g with 16 alphabetical values from A fo P The right rotary switch defines the element address e with 16 numerical values from 0 to 15 Above them is a slide switch which functions as a configuration switch Position O 2 adjacent inputs as direction pushbuttons for UP DOWN or ON OFF Position 1 All sensor inputs function separately as NO contacts Position 2 All sensor inputs function separately as pushbutions To the left of the rotary switches is a red LED which indicates all activities Next to if is a reset pushbutton and fo the right of that is a service pin For functions please refer fo the operating instructions The terminals located above are plug in terminals for conductor cross sections of 0 2mm to lomm The addresses of the 8 inputs can also be freely assigned if necessary using the SIENNA Professional software The socket strip located above this has 9 plug in wires with wire end sleeves 8 control inputs with internal low voltage Typical connections on page 4 10 Powerline sensor inputs 8 channels internal low voltage PL SAMTEMP Powerline temperature controller with display white 50x50mm for moun ting in swit
6. 0 5 mm Spacing of control connections contact Se Test voltage control connections contact Rated switching capacity each contact a 600 VA Incandescent lamp and halogen lamp load 230V I on lt 70A 10ms scan Inductive laod cos 0 6 230V AC up to 150 W inrush current lt 35A SAMDU up to 300W 3mm 3mm w 3 2000 V 2000 V 2000 V 10A 250V AC 5A 250V AC 3 A 250V AC 2000 W 1000 W 650W 650 W 650 W Fluorescent lamp load with KVG in lead lag circuit or non compensated Fluorescent lamp load with KVG 600 VA shunt compensated or with EVG 1000 VA 500 VA 500 VA 250 VA Compact fluorescent lamps with EVG and energy saving lamps up to 150 W Dimmable 230V LED lamps SAMDU up to 300 W Service life at rated load cos 510 or incandescent lamps 500W at 100 h Service life at rated load AK 10 cos 0 6 at 100 h bis 400 W bis 400 W J e gt lt gt 10 10 gt 10 gt 4x10 gt 4x10 gt 4x 10 Max operating cyles 10 h 10 h 10 h 10 h Connection type Plug in terminals Plug in terminals Minimum conductor cross section 0 2 mm Plug in terminals Plug in terminals Plug in terminals 0 2mm 0 2mm 0 2mm 1 5mm 1 5 mm 1 5mm Maximum conductor cross section 1 5 mm Conductor stripping 8 9 mm Type of enclosure terminals IP30 IP20 IP30 IP20 Time on 100 100 100 100 100 Max min temperature at mounting locati
7. 30V EAN 4010312316870 119 60 pc Recommended retail prices excluding VAT Decentralised Dimmer Actuator with Sensor Input and Decentralised Dimmer Actuator 1 10 Volt PL SAMDR PL SAMDR PL AMD10V PL AMD10V Powerline dimmer actuator with 1 channel 53x43mm 25mm deep for mounting in 58mm switch boxes Phase control dimmer for loads up to 300 W at cos phi 1 and 150 W at cos phi 0 6 Electronic universal transformers up to 150W Sensor input 230V Standby loss only 0 5 watt To control and dim at the same place Overload cut off with auto recovery after GO seconds Two rotary switches are located on the front for address assignment The left rotary switch defines the group address g with 16 alphabetical values from A fo P The right rotary switch defines the element address e with 16 numerical values from 0 to 15 Above it is a slide switch which acts as a configuration switch with positions 0 1 and 2 Position 0 Dimmer switch for R and L loads up to 300 W at cos phi 1 and 150 W at cos phi 0 6 Dimming range 10 100 Position 1 Dimmable LED lamps with phase control Dimming range 15 100 Position 2 Dimmer switch for electronic universal transformers up to 150 W Important Please observe the minimum load of universal transformers Dimming range from 30 to 100 Also suitable to control fountain pumps Dimming range 35 100 To the left of the rotary switches is a red LED which indicates all activities Next to it i
8. alphabetical values from A fo P The right rotary switch defines the element address e with 16 numerical values from 0 to 15 Above it is a slide switch which acts as a configuration switch The position AUTO allows the dimming of all types of lamps up to 300 watts The position LCI is a comfort position for LED lamps up to 150 watts which are not being dimmed down enough when set to AUTO Ctrailing phase angle dependent on the construction and must therefore be forced to leading phase angle The position AUTO2 allows the dimming of all types of lamps up to 300 watts Increased minimum brightness compared to AUTO In position LC no inductive wound transformers should be used In addition the maximum number of dimmable LED lamps can be lower than in the AUTO position dependent on the construction Mixing of L loads inductive loads e g wound transformers and C loads capacitive loads e g electronic transformers is not permitted R loads ohmic loads e g 230V incandescent lamps and halogen lamps may be added anytime To the left of the rotary switches is a red LED which indicates all activities Next to it is a reset pushbutton and to the right of that is a service pin For functions please refer fo the operating instructions The terminals located above are plug in terminals for conductor cross sections of 0 2 mm to Comms Le A CCO E O eE AG Powerline universal dimmer actuator PL SAMDU 1 channel with sensor input 2
9. ch systems In addition a floating control contact 3A 250V AC os for direct connection of heaters and coolers Standby loss only 0 5 watt a piel The scope of supply comprises a frame RIE and an intermediate frame ZR65 55 for the Ma E E Design the temperature controller upper part and a bottom part for attachment in 58 mm ia flush mounted boxes In normal mode the current room temperature is indicated in the display as well as icons for present or absent and for heating on or cooling active Press the pushbuttons 4 absent and lt present to activate the associated setpoint In setup mode as described in the user s manual press pushbuttons A and W to display the setpoint and actual temperatures and change the setpoints Control heating or cooling with Powerline actuators PL SAMIL or PL SAM2L EAN 4010312316719 105 40 pc Powerline Temperature controller for PL SAMTEMP heating and cooling EAN 4010312316733 198 90 pc Recommended retail prices excluding VAT Coupling Element PLSW PROF for Software SIENNA Professional Eitako ELECTRONICS PL SW PROF The coupling element with USB cable and 230V power supply unit is included in the scope of supply The software for installation and configuration of the powerline devices PL is available for download under eltako com PL SW PROF is a Windows based program for installing and configuring all PL and SIENNA components and is design
10. ed for electricians Powerline systems can either be installed or configured using a screwdriver or a PC laptop All changes can be made from the PC Existing installations in a building can also be read and detected The bus is coupled using a USB port on the PC Thanks to Powerline technology the nearest electric socket becomes a bus coupler Download in accordance with the included installation instructions from the homepage eltako com en gt Software gt Powerline The operating instructions are available for download at the bottom of the page under Operating Instructions SIENNA Professional System requirements Laptop PC Intel Pentium Ill 366MHz or higher Windows 7 Windows 8 82 Bit and 64 Bi Technical data Echelon Koppelelement PL 20 e Powerline communication on B C tape 5 Kb s acc to FCC CENELEC EN50065 1 Iy and LONWORKS protocol Fused safety socket 230V 50Hz PC coupler USB TI Or 20 Mains plug power supply unit maximum 250 mA at 18V DC voltage USB maximum 50mA at 5V DC voltage Processor type Neuron processor integrated in Powerline Smart Transceiver PL 3120 Temperature range 25 C to 70 C PL SW PROF Software PL SW PROF EAN 4010312316856 333 40 pc Recommended retail prices excluding VAT The software part is not discountable Typical Connections Typical connection PL SAM1L Additional switching point for an existing consumer L 3 way switch pushbutton
11. ensor with confirmation in teaching in mode Up to 80 Powerline sensors or feedbacks can be taught in The function as a universal direction or central pushbutton for a taught in wireless sensor is assigned via slide switch of the PL FIGW The Powerline address is set via rotary switch g and e which should be addressed with the wireless sensor In addition to wireless switches also Eltako wireless sensors such as window contacts and motion detectors can be taught in Also control functions of the GFVS for dimmer switches and roller shutter control is possible The implementation into practical Powerline telegrams fur PL actuators is done automatically Up to 100 different wireless sensor can be taughi in All records and configurations can be accessed via Sienna Professional software and power supply Other functions can then be selected which are not available through the direct teaching in via rotary switch In addition the gateway can be set into the learn and deletion mode so that a manual feaching in can be carried out without direct access to the device The PL FTGW also serves as a relay station for communication between the temperature controller PLSAMTEMP with EnOcean actuators FKS MD1 and FKS E Up to 20 actuators and PL SAMTEMP are managed here Available november 2015 PL FIGW Powerline pushbutton gateway EAN 4010312316986 166 40 pc Recommended retail prices excluding VAT Decentralised Actuator with Sensor Inputs ELltako PL
12. ential free 5A 250V AC incandescent lamps 1000 watts 2 sensor inputs with internal low voltage Standby loss only 0 5 watt To control and switch at the same place Use only potential free switching elements Internal low voltage applied to the sensor inputs Two rotary switches are located on the front for address assignment The left rotary switch defines the group address g with 16 alphabetical values from A fo P The right rotary switch defines the element address e with 16 numerical values from 0 to 15 Above it is a slide switch which acts as a configuration switch with positions 0 1 and 2 Position 0O Sensor inputs function as pushbuttons impulse switches Position 1 Sensor input functions as NC contact relay Position 2 A change over switch is evaluated as a pushbutton To the left of the rotary switches is a red LED which indicates all activities Next to it is a reset pushbutton and to the right of that is a service pin For functions please refer fo the operating instructions The terminals located above are plug in terminals for conductor cross sections of 0 2 mm to 1 5 mm Next to them are three wires with wire end sleeves for the two control inputs with internal low voltage Typical connections on page 4 10 Powerline actuator 2 channels with 2 sensor inputs EAN 4010312316672 105 40 pe Recommended retail prices excluding VAT Venetian Blind Actuator with Sensor Inputs PL SAM2 PL SAM2 P
13. ices excluding VAT Decentralised TLZ Actuator with Sensor Input and Decentralised Sensor Input 230V Eitako ELECTRONICS PL SAMILT Powerline TLZ staircase time switch actuator with 1 channel 53x43 mm 25mm deep for mounting in 58mm switch boxes Off delay settable from 1 minute to 120 minutes 1 NO contact not potential free 10A 250V AC incandescent lamps 2000 watts Sensor input 230 V Standby loss only 0 5 watt To control and switch at the same place Two rotary switches are located on the front for address assignment The left rotary switch defines the group address g with 16 alphabetical values from A fo P The right rotary switch determines the off delay time Above it is a slide switch which acts as a configuration switch with positions 0 1 and 2 Position 0 Pushbutton at sensor input with subsequent switching Position 1 Same as Position O but with switch off early warning Position 2 A change over switch is evaluated as a pushbutton To the left of the rotary switches is a red LED which indicates all activities Next to it is a reset pushbutton and to the right of that is a service pin For functions please refer to the operating instructions The terminals located above are plug in terminals for conductor cross sections of SATA Ve mM Typical connections on page 4 10 Powerline TLZ actuator 1 channel with PL SAMILT sensor input 230V EAN 4010312316702 105 40 pc PL SMI1L Powerline sensor input w
14. ith 1 channel 53x43mm 25mm deep for mounting in 58mm switch boxes Sensor input 230V Standby loss only 0 5 watt To control and switch at different places When pressed the sensor input acts on all actuators with the same address or as a central pushbutton if element address O is used Two rotary switches are located on the front for address assignment The left rotary switch defines the group address g with 16 alphabetical values from A fo P The right rotary switch defines the element address e with 16 numerical values from 0 to 15 Above it is a slide switch which acts as a configuration switch with positions 0 1 and 2 Position O Sensor input with reset function as pushbutton Position 1 Sensor input functions as NO contact Position 2 A change over switch is evaluated as a pushbutton To the left of the rotary switches is a red LED which indicates all activities Next to it is a reset pushbutton and fo the right of that is a service pin For functions please refer fo the operating instructions The terminals located above are plug in terminals for conductor cross sections of 0 2 mm to lomme TYPO EOE EAE PL SMIL Powerline sensor input 230V EAN 4010312316740 99 90 pc Recommended retail prices excluding VAT Decentralised 8 channel Sensor Input and Temperature controller for heating and cooling Powerline sensor input with 8 channels 53x43 mm 25mm deep for mounting in 58mm switch boxes 8 sensor inputs with internal
15. n both directions All Powerline telegrams from the electricity wiring system are automatically translated into RS485 bus telegrams and may also be sent as wireless telegrams by connected FTD14 devices Only wireless and RS485 bus telegrams taught into the FPLG14 are translated into Powerline telegrams and modulated onto the electricity wiring system Up to 120 different addresses Teach in takes place by means of rotary switches on the front of the devices or using the PCT14 as described in the user s manual g A A AUTO LRN AUTO GFVS FTK FBH ZA LRN Z RT Standard setting ex works FPLG14 Wireless Powerline gateway EAN 401031231677 91 60 pc PL FTGW Bidirectional Powerline pushbutton gateway 53x43mm 40mm deep for mounting in 58mm switch boxes supply voltage 230V Power consumption in operation 1 1 Watt Powerline telegrams from the grid taught in into the gateway are automatically transformed and sent into Eltako wireless telegrams Wireless telegrams taught in into the gateway are transformed into powerline telegrams and modulated to the power supply grid By pressing the reset button the PL FTGW will be put into the teaching in mode The rotary switch selects whether wireless or powerline telegrams should be taughi in One being taught powerline sensor is automatically assigned by operating in the learning mode a free radio channel A free wireless channel is automatically assigned to a taught in powerline s
16. on 50 C 20 C 50 C 20 C 50 C 20 C 50 C 20 C 50 C 20 C 0 5W Max parallel capacitance approx length 3 nF 3 nF 3nF onir of local control lead at 230V AC 10m 10m 10m 10m 1 Applies to lamps of max 150W Also transformers electronically C load for SAMDR only up to 150W Generally applies to 230V LED lamps Due fo different lamp electronics switch on off problems and a restriction in the maximum number of lamps however the dimming ranges may be limited depending on the manufacturer in particular when the connected load is very low e g with 5W LEDs The comfort position LC at SAMDU optimizes the dimming range which however results in a maximum capacity of only up to 150W In this comfort position no wound inductive transformers should be dimmed Fluorescent lamps or LV halogen lamps with electronic ballast All actuators with 2 contacts Inductive load cos 0 6 as sum of both contacts 1000 W max A maximum of 2 transformers of the same type EVG electronic ballast units KVG conventional ballast units 8 9 mm 8 9 mm 8 9 mm IP30 IP20 IP30 IP20 IP30 IP20 N Vv wo GH gt Powerline communication in the B C Band 5kb s corresponds to FCC CENELEC EN 50065 1 and LONWORKS protocol Compliance with EN 61000 6 3 EN 61000 6 1 EN 50065 1 and EN 60669
17. owerline Venetian blind actuator for 1 motor 53x43mm 25mm deep for mounting in 58mm switch boxes 1 1 NO contact for motors up to 3A 2 sensor inputs with internal low voltage Standby loss only 0 5 watt To control and switch at the same place Use only potential free switching elements Internal low voltage applied to the sensor inputs The control inputs can be used for a Venetian blind pushbutton or a Venetian blind switch The runtime is preset to 120 seconds This can be changed using the SIENNA Professional installation software Two rotary switches are located on the front for address assignment The left rotary switch defines the group address g with 16 alphabetical values from A fo P The right rotary switch defines the element address e with 16 numerical values from 0 to 15 Above it is a slide switch which acts as a configuration switch with positions 0 1 and 2 Position O Start and stop by pressing Venetian blind pushbutton Auto stop at end Position 1 Comfort switch for Venetian blind slat adjustment Tip briefly to adjust slats gt second same as position O Position 2 Tip pushbutton to operate release to stop Auto stop at end To the left of the rotary switches is a red LED which indicates all activities Next to it is a reset pushbutton and fo the right of that is a service pin For functions please refer to the operating instructions The terminals located above are plug in terminals for conductor cross sections of
18. s a reset pushbutton and to the right of that is a service pin For functions please refer fo the operating instructions The terminals located above are plug in terminals for conductor cross sections of 0 2 mm to Fomm Typical connections on page 4 10 Powerline dimmer actuator 1 channel with sensor input 230V EAN 4010312316696 105 40 pc Powerline dimmer actuator 1 10 V 53x43 mm 25mm deep for mounting in 58mm switch boxes To switch and or dim via a 1 10V interface 1 NO non floating contact 600 VA Standby loss only 0 5 watt To activate and dim at different places Current sink of max 30mA for active and passive electronic ballasts A Powerline sensor input is required for activation Two rotary switches are located on the front for address assignment The left rotary switch defines the group address g with 16 alphabetical values from A fo P The right rotary switch defines the element address e with 16 numerical values from 0 to 15 Above it is a slide switch which has no function here To the left of the rotary switches is a red LED which indicates all activities Next to it is a reset pushbutton and to the right of that is a service pin For functions please refer to the operating instructions The terminals located above are plug in terminals for conductor cross sections of 0 2 mm to Lomm Typical connections on page 4 10 Powerline dimmer actuator 1 10 V EAN 4010312316726 105 40 pc Recommended retail pr
Download Pdf Manuals
Related Search
Related Contents
TG-820 TG-620 - Olympus America Prix des Dévoreurs Configuration and Administration Guide OpenBAT Family Advanced field calibrator and communicator South Shore Furniture 3642027 Instructions / Assembly 10 消耗部品の交換方法 1 CIRCULAIRE n° E.T. 122.682 (AGFisc N° 22/2012) dd Intec 2015 Users Manual microARRANGER Quick Start Guide Copyright © All rights reserved.