1. Fresh cold air inlet p Server Server Server Note Motorized damper see Fig 1a 2 FAM 6000 I 400 3 N 50 Hz AIR MODULE FAM 6000 Fig 4 DN Fig 5a FAM 6000 I 1950 rear air inlet 100 Ln o o T air inlet x side view e FAM 6000 I WO E o inf 5 a oo 2 tn Y FAM 6000 400 3 N 50 Hz Fig 5b FAM 6000 I Fan and motorized grille Fig 5c FAM 6000 air filters and pre filter 4 FAM 6000 I 400 3 N 50 Hz Premise Before installing the machine we recommend to read the instruction reported on page 0 of this manual Use conditions The air inlet module FAM 6000 I is a standalone unit that draws cold fresh air from outdoor to achieves a freecooling effect that removes the heat produced in the technological room The warm air will be expelled outdoor Installation and connections The module is located in the proximity of a wall Fig 1 2 3 The air intake is via duct by the customer The expulsion of the air can occur in two ways with a motorized damper Fig 1 1a 3 by extractor FAM 6000 E Fig 2 2a For the wiring see Fig 7 Note Use a differential switch class B 300 mA To install the machine it is mandatory to use suitable Protective
2. Equipment as wear appropriate Q work clothes wear protective gloves amp wear Safety shoes Description of FAM 6000 1 The module is made by a steel box see Fig 4 stove varnished that includes a EC Centrifugal fan directly coupled to a variable speed motor with different air flows and head pressure see TAB 1 This motor is equipped with internal thermal relay with automatic reset that intervenes in case of electrical electronic control thermal overload or mechanical troubles b Microprocessor control device c Optimization of Air flow through continuous speed regulator 0 10 VDC d Direct cooling with outside air e Structure in sandwich panels class AO A1 f Pocket high capacity filter preceded by a metal prefilter FAM 6000 400 3 N 50 Hz 5 TAB 1 TECHNICAL CHARACTERISTICS FAM 6000 1 400 3 N 50 Hz earth Characteristics Unit of measure Value Air flow at 21 C density 1 2 kg m mi h 6000 nominal ESP External Static Pressure Pa 200 Cooling capacity kw 24 9 Electronically controlled Fan EC Fan n 1 Electric Supply VAC 10 EN 60204 1 V Ph Hz 400 3 N 50 Max Operative Power input kw 1 51 Min Electric absorption 0 1 Max Electric absorption FLA A 4 0 Dimensions W x D x H mm 750x750x1950 Weight kg 220 Limits of use 20 50 Cooling capacity refers to the following conditions Outdoor Temp 12 C and Indoor Tem
3. ag 9 Standard spare parts Pag 5 Use conditions Pag 9 Disposal Pag 5 Installation and connections Last Cover Conformity Declaration Note 1 The technical characteristics of FAM could be changed by the Manufacturer without notice To size the electrical cables and for service interventions it is necessary to follow this Service Manual annexed to the machine Note 2 All activities as Installation Start up Adjustment and Maintenance must be done by skilled workers or as choice by Service of Manufacturer or by there representatives FAN AIR MODULE FAM 6000 1 Using outdoor air for cooling of technological rooms Distributes the environment air in UNDER or DISPLACEMENT version see figures below Fig 1 FAM 6000 1 UNDER version Air distribution with overpressure motorized damper Fig 1a Motorized 000 Fresh cold ee e P air inlet Server Server Server gt FAM 6000 1 400 3 N 50 Hz 1 Fig 2 FAM 6000 UNDER version Air distribution with FAM 6000 E FAM 6000 1 Fresh cold A P d air inlet Server Server Server FAM 6000 E Fig 3 FAM 6000 1 DISPLACEMENT version Air distribution with overpressure motorized damper FAM 6000 1
4. cMMA Vg G A CONprroY FAN AIR MODULE FAM 6000 400 3 N 50 Hz Operating and Service Manual MEE VADE IN ITALY PRESENTATION This service manual gives all information requested for the knowledge the correct use and the cor rect maintenance of all devices described in this Extraction Air Device In case of no observance of the Manual s contents the Manufacturer will stop any guarantee on the damaged product In case of very difficult maintenance or revision it is recommended to request the direct inter vention of the Manufacturer that is however always at disposal for any suggestion finalized to the solution of the problem WARRANTY All our products are quaranteed for 12 months after purchase s date The reparations under warran ty do not change the warranty period The warranty concerns defects of materials that compromise the function of product reducing the efficiency or cancelling the effect of the device The warranty is recognised if the fault is reported within 2 days after the appearance The warranty does not include faults provoked by 1 physical chemical characteristics of the ambient in which the device operates 2 not correct application of our instructions reported in this manual 3 storage conditions non in accordance with this manual 4 reparations carry out by not authorised service personnel And than the warranty is also not applicable if 5 the Serial Number is
5. itions openings of cabinet produce air by pass and amperage modifications 2 Extraordinary Maintenance Where fan shows to high absorption or to high noise intervene with expert personnel as indicate on Note 2 page 1 Standard Spare Part for FAM 6000 I EC Fan Air filter Air metallic prefilter Motorized damper Electronic control Before requesting spares check any reference stamped on the component Disposal Disassembly Scrapping User according to CE guidelines or to own country regulations is responsible of disposal of the whole machi ne or also part of it In case of scrapping the entire machine or parts of it you should take all safety precautions necessary to avoid the risks associated with the decommissioning of industrial machinery This operation must be done following all safety precautions specially during the following phases Disassembly of machine from the operative site Transportation and movement Disassembly Separation of single components Separation of materials and their recycling or disposal it is mandatory to apply the National and Regional Rules regarding disposal of solid industrial waste amp ATTENTION Disposal of components and materials In case of scrapping according to local regulations the customer must use special cautions regarding the disposal of PVC ELECTRICAL CABLES STEEL IMPORTANT NOTICE Toxic or corrosive substances are not present in
6. nabling the fan 100 ON Note OFF FAM s Ventilator is off ON FAM s Ventilator is on 0 OFF AT 3K t AT Indoor Temp Outdoor Temp K FAM 6000 1 400 3 N 50 Hz 7 Fig 10 100 0 Fig 11 100 0 Fig 12 100 0 8 Management of n 1 FAM 6000 1 Combined action with other Conditioners AC A Modulating control ON f OFF Ecco Indoor Temp t I gt Set Point SP1 P 1 2 Proportional Band B1 SEQUENTIALLY management of FAM 6000 1 Combined action with other Air Conditioners AC A l OFF t H Set Point SP1 Indoor Temp 1 2 Proportional Band B1 A PARALLEL management of FAM 6000 1 Combined action with other Conditioners AC A L ON Es i 4 I I l Indoor Temp t t gt Set Point SP1 1 2 Proportional Band B1 1 FAM 6000 I 400 3 N 50 Hz Shut off Open the power switch QS see electrical diagram inside the machine Maintenance IMPORTANT it is strongly forbidden to access to the interior part of FAM when the fan is running Wear appropriate Do not approach Q work clothes Wear protective gloves Wear safety shoes AS ihe hot surfaces 1 Ordinary maintenance and Control Check every 6 months at least the fan electrical absorption to compare with data of TAB 1 Note This control must be done without changing the FAM running cond
7. not readable 6 the Customer has not complied to all obligations with the Manufacturer updated to the service intervention WARRANTY EXCLUSIONS The warranty is void in case of 1 error handling of the operator 2 damage due to uncorrected service operation 3 replacement of not original spare parts 4 the operator did not follow the information indicated in this manual Also damages due to negligence neglect bad and inappropriate use of the machine exclude the war ranty The elimination of safety devices will cause autornatically the void of warranty and of any responsibility from the Manufacturer LEGISLATION REFERENCES The machines object of this Service Manual have been made in accordance with EU Directives reported in the rear page of this Manual Climatel Padova e iy Gut di Giuseppe Giraldo de TCR a Ca pF Index Pag 0 Presentation Pag 5 Description of FAM 6000 I Pag 0 Warranty Pag 6 TAB 1 Technical characteristics Pag 0 Exclusion of warranty Pag 6 Functional diagram Pag 0 Normative References Pag 6 Electrical Diagram Pag 1 FAM 6000 I module Pag 7 EC Fan with digital control Pag 1 Air distribution Pag 7 Startup Pag 2 Air distribution Pag 7 Management of FAM 6000 I Pag 3 Fan Air Module FAM 6000 1 Pag 8 Management of FAM 6000 I Pag 3 Illustrative figures Pag 9 Shut off Pag 4 Illustrative figures Pag 9 Ordinary and extraordinary Maintenance Pad 5 Premise P
8. p 24 C Fig 6 Functional diagram LEGEND 1 Fan 2 Electrical panel Air filter metal prefilter Damper 3 4 5 Noise absorption partitions at Par SS Fig 7 Electrical Diagram for FAM 6000 I Note Use a differential switch Class B 300 mA See Diagram inside the electrical panel of the machine FAM 6000 I 400 3 N 50 Hz Variable speed fan with digital control The module FAM 6000 I is equipped with a special high efficiency fan which allows to contain significantly con sumption and energy costs operation making it even more convenient to the Freecooling effect it produces EC fans electronically commutated DC motors have the additional advantage of being adjustable thus allo wing the following benefits according to the actual demands of the individual user Control of the air flow Control of available static pressure Optimization of sound output Optimization of power consumption Fig 8 Electrical diagram of Fan speed Regulator Rpm max 1400 1 10 VDC External control 1 10 VDC Start up After connecting FAM module in accordance with electric diagram inside the machine start the FAM closing the power switch QS see electrical diagram Adjust the fan speed by applying a signal between 1 and 10 VDC depending on the needs of the environment as well as the pressure drop of the outdoor air intake and of the expulsion air module Fig 9 Management of FAM 6000 1 E
9. this machine FAM 6000 400 3 N 50 Hz 9 CONFORMITY DECLARATION C OF MANUFACTURE IN ACCORDANCE WITH DIRECTIVE 2006 42 CE Manufacture Climatel di Giuseppe Giraldo Registered operating seat Via B Cristofori n 1 35020 Vigorovea PD OBJECT OF DECLARATION Space for customized label DECLARES The machine in your possession was made in accordance to the following EU Directives Directive machine 2006 42 CE Directive low tension 2006 96 CE Directive electromagnetic compatibility 2004 108 CE The person authorized to produce this technical documentation is Giuseppe Giraldo Via B Cristofori n 1 35020 Vigorovea PD Climatel di Giuseppe Giraldo Giuseppe Giraldo Legal representative Climatel Freecooling Ei www climatelfreecooling com
Download Pdf Manuals
Related Search
Related Contents
ENGLISH De la textualité numérique : l`hypertexte et la “ fin ” du livre Philips 9000 series Smart LED TV 60PFL9607S Upgrade to Kaspersky Anti-Virus 2016 (3 user) at Fry`s Installation Guide Directive Personnel enseignant – Modalités de calcul du salaire en Capno True MiMI Plugin User Guide - NCIBI - National Center for Integrative Sangean Digital Table-Top Radio Copyright © All rights reserved.