Contents

1. EL REFERENCE MEANING Biddle product series CA air curtain CA model Daikin system V for connection within Daikin VRV system multi capacity S M L or XL small medium large or extra large range discharge width 100 150 200 or 250 discharge width in cm heating DK heating within Daikin direct expansion system mounting method free hanging model recessed model cassette model colour White Aluminium non standard colour control panel Biddle control panel included zZzi ioO x ounn m not included Version 5 2 08 12 2010 INTRODUCTION biddle Biddle by Markowei 4 NL 9288 HA Kootstertille Ce Type CAVM150DKFBC Code 1550 230 V 1N 50 Hz 5426 1 1 00 01 Tmax L4 24A DaikinC Imax L2 M 60 kg Imax L3 Medium RA10A Prnotor 0 56 kW Prax Pheating Capacity Index 80 Example of a type plate D COMFORT AIR CURTAIN FOR DIRECT EXPANSION 1 3 5 Type plate The type plate can be found at the left side on the inlet side under the inlet cover It lists the following data e Type full type code of the unit Code unit code of the Biddle electronic controller M weight of the unit e Medium refrigerant e Capacity Index Daikin capacity index U lnae Pmotor maximum load on the electrical system by the unit 1 3 6 Components and acc
2. e the manual of the Biddle CA model Comfort Air Curtain the manuals of the Daikin system components outdoor unit indoor unit operation panel etc Before carrying out any work on this appliance read this man ual and all referred sections in other manuals completely through in the presented order 1 2 2 Marginal symbols In this manual the following marginal symbols are used Note Draws your attention to an important part of the text Read this part of the text carefully Caution If you do not perform this procedure or action correctly you can damage the device So follow the instructions carefully Version 5 2 08 12 2010 INTRODUCTION PICTOGRAM DESCRIPTION Warning You are entering an area which contains live components Accessible to qualified maintenance staff only Caution is urged COMFORT AIR CURTAIN FOR DIRECT EXPANSION Warning If you do not perform this procedure or action cor rectly you can cause bodily injury and or damage So follow the instructions carefully Danger This indicates actions which are not permitted Ignoring this warning can lead to serious damage or accidents which may involve bodily injury The action concerned may only be performed by qualified technical staff when carrying out mainte nance or repair 1 2 3 Pictograms on the device and in the guide The pictograms in tablel refer to possible risks and or dangers You will find these pictogra
3. Check the plug and the power supply The en buttons on the Biddle control panel do not work These buttons have no function Switch the air curtain on with the Daikin operation panel See Sec tion 3 2 The ed e and 7 buttons on the Daikin operation panel do not work These buttons have no function Control the strength of the air curtain with the Biddle control panel See Section 3 3 The air curtain does not work and the LED on the Biddle con trol panel is lit Either the system is switched off or it turned off the air curtain automatically Verify the settings on the Daikin operation panel See Sections 3 2 3 3 en 4 1 The air curtain is discharging unheated air The system turned off the heat ing automatically Verify the settings on the Daikin operation panel See Sections 3 2 3 3 en 4 1 The air curtain is discharging unheated or cold air or does not work and the Daikin operation panel displays amp E e2s The system is working in defrost mode This will take 5 to 10 min utes Wait until defrosting is done Version 5 2 08 12 2010 FAULTS 6 4 SYMPTOM The Biddle control panel display is blank COMFORT AIR CURTAIN FOR DIRECT EXPANSION Faults with specific symptoms EXPLANATION Connected unit has no power supply Faulty connection to control panel Fault in Biddle electronics in the unit ACTI
4. either discharge unheated air or be turned temperature setpoint off depending on the settings see Section 4 1 2 Display on Daikin operation panel example isl Note P To prevent draught problems Biddle recommends to adjust the temperature setpoint to maximum The button om the Biddle control panel has no function The display on this panel always shows the actual room tem perature Version 5 2 08 12 2010 17 OPERATION COMFORT AIR CURTAIN FOR DIRECT EXPANSION 3 4 Messages on the Biddle control panel fault code Lr l LL SERVICE MN D 3 4 1 Dirty filter indicator The number of full triangles indicates the filter s service life the more triangles the longer the service life When the message FILTER appears the filter s maximum life has lapsed you should then clean or replace it For details on the filter indication see the CA model Air Cur tain Manual 3 4 2 Outside air temperature sensor indication If the 2 symbol is displayed on the Biddle control panel then the air curtain setting is turned up by the outside air tempera ture sensor 3 4 3 Faults The message SERVICE indicates that there is a fault Next to it the fault code is displayed Note The fault code will disappear when you press any key The message SERVICE will however remain visible as long as the fault is not corrected If an fault code is displayed without the message SERVICE th
5. mre button on the Daikin operation panel Fan only the air curtain always discharges unheated air Heating the air curtain s heating is automatically con trolled Other modes are not available biddle MANUAL OPERATION 3 2 3 Defrosting When the Daikin operation panel displays the sym 6 qe bol the system is working in defrost mode Then the air cur tain will either discharge unheated air or be turned off depending on the settings see Section 4 1 2 Defrosting is activated automatically by the system when nec essary When the defrosting is done the unit will operate nor mally again 3 3 Air curtain settings 3 3 1 Adjusting settings actual room temperature Adjust the strength of the air curtain using the and buttons on the Biddle control panel The ed e and gt buttons on the Daikin operation panel strength have no function i Note Los p To achieve maximum climate separation with minimum energy consumption Biddle recommends to select the lowest strength at which no draught occurs Display on Biddle control panel example 3 3 2 Adjusting heating Adjust the temperature setpoint with the B buttons on the BS n Daikin operation panel The display on this panel shows the ZIT setpoint ZI IC L Ic The system controls the air curtain s heating automatically The heating is stopped when the setpoint is reached Then 4 the air curtain will
6. Manual Comfort Air Curtain for Direct Expansion Copyright and trademarks All the information and drawings in this manual are the property of Biddle and may not be used other than for the actual operation of the device photocopied duplicated translated and or be brought to the attention of third parties without Biddle s prior written permission The name Biddle is a registered trademark Warranty and Liability Please refer to Biddle s Terms of Sales and Delivery for warranty and liability conditions Biddle excludes liability for consequential loss at all times and under all circumstances Liability for the contents of this manual However much care might have been taken in ensuring the correctness and where necessary completeness of the description of the relevant parts Biddle disclaims all liability for damage resulting from any inaccuracies and or deficiencies in this manual Should you detect any errors or ambiguities in this manual then we would be pleased to hear from you it helps us to improve our documentation even further Biddle retains the right to change the specifications stated in this manual For more information If you have any comments or questions about specific topics relating to this product please do not hesitate to contact Biddle Address for the UK Address for other countries Biddle Air Systems Ltd Biddle bv St Mary s Road PO Box 15 Nuneaton
7. NL 9288 ZG Kootstertille Warwickshire CVI 1 5AU The Netherlands United Kingdom tel 024 7638 4233 tel 31 512 33 55 24 fax 024 7637 3621 fax 31 512 33 55 54 e mail sales biddle air co uk e mail export biddle nl internet www biddle air com internet www biddle info 2 biddle MANUAL Table of contents l Introduction I I About this manual 1 2 How to use this manual 1 2 1 General 1 2 2 Marginal symbols 1 2 3 Pictograms on the device and in the guide 2 4 Related documentation 1 3 About the unit 1 3 1 System operation 1 3 2 Outside air temperature sensor accessory 1 3 3 Limitations 1 3 4 Models and type references 1 3 5 Type plate 1 3 6 Components and accessories 1 4 Safety instructions 1 4 1 Operation 1 4 2 Installation maintenance and service 2 Installation 2 1 General instructions 2 2 Delivery check 2 3 Installation procedure 2 4 Connecting the unit to the power supply 2 5 Connecting the unit to the Daikin system 2 5 1 Connecting the control system 2 5 2 Connecting the refrigerant 2 6 Installing the outside air temperature sensor accessory 2 7 Switching on and testing operation 2 7 1 Switching the system on 2 7 20 Testing operation S0 30 00 00 40 0 0 0 U1 01 N OC RR UCPNKMNM C 3 Operation 16 3 1 General l6 3 2 Switching On and Off l6 3 2 1 Switching the system On and Off l6 3 22 Selecting the operation mode l6 3 2 3 Defrosting 17 3 3 Air curtain settin
8. NUAL INSTALLATION Models with discharge widths 150 200 or 250 l Connect the system controller to the X84 connector located on the top of the air curtain Connect the controller cable from the outdoor unit to FI F2 If applied to your unit Connect the Daikin opera tion panel to PI P2 2 Attach the cable housing supplied to the connector Models with discharge width 100 Remove the cover from the box on the side of the unit Optional Detach the box from the unit Remove the bracket from the unit and from the box Mount the box to the wall at a place of your choice Caution Do not detach the cables between the unit and the box Lead the control cable s into the box through the free cable gland s Connect the system controller to the terminal block Connect the controller cable from the outdoor unit to FI F2 If applied to your unit Connect the Daikin opera tion panel to PI P2 Screw down the cable gland s 6 Put the cover back onto the box 2 5 2 Connecting the refrigerant Attach the pipes as described in the Daikin outdoor unit Installation Manual Attach the pipelines to the protruding pipe ends on the top surface of the unit by means of a soldered joint Version 5 2 08 12 2010 13 INSTALLATION COMFORT AIR CURTAIN FOR DIRECT EXPANSION 2 6 Installing the outside air temperature sensor accessory Attach the outside air temperature
9. ON Check power supply Consult the Faults section in CA model Air Curtain Manual The Daikin operation panel dis play is blank Connected unit has no power supply Faulty connection to control panel Fault in Daikin electronics in the unit Check power supply Consult Installation Manual of control panel Contact the supplier Biddle control panel displays a fault message SERVICE and or E or F plus a digit Biddle electronics signals a fault Consult the Faults section in CA model Air Curtain Manual Daikin operation panel displays an fault message flashing LED and or fault code Daikin electronics in unit or outdoor unit signals a fault Consult the Service Manual of the outdoor unit Contact the supplier Air curtain does not work while Biddle control panel indicates that it is working LED unlit sym bols on display no SERVICE symbol Fault in Biddle electronics transformer fuse or fans in unit Consult the Faults section in CA model Air Curtain Manual Appliance discharges cooled air for a prolonged time and or con densate is forming in the unit Fault in unit Warning This situation can be hazardous and or cause damage Turn the whole system off immediately Contact the supplier biddle Service 7 1 Safety instructions Danger Service on the unit may be performed by qualified tech
10. ain Manual Maintain the Daikin components according to their Serv ice Manuals from Daikin Version 5 2 08 12 2010 21 Faults 6 1 Safety instructions A LS Sis S 6 2 Testing for faults d Danger Work on the unit s interior shall be performed by qualified technical staff only Warning Before opening the unit follow the safety instruc tions in section 1 4 Note No specialist skills are required to perform the tests described below If you suspect a fault then perform the following steps to determine whether there is indeed a fault Determine whether the symptoms are part of normal operations as described in Section 6 3 Determine whether the symptoms are caused by a fault as described in Section 6 4 Set the system to heating mode using the Daikin opera tion panel and set the temperature setpoint to maximum If the appliance discharges no air at all or no hot air after 15 minutes then there is a fault Set the temperature setpoint to minimum If the appliance still discharges hot air after 15 minutes then there is a fault If you have detected a fault and Section 6 4 does not pro vide a solution then contact the supplier 22 biddle MANUAL 6 3 Non fault related symptoms FAULTS SYMPTOM The displays of one or both con trol panels display is blank EXPLANATION The unit connected to the con trol panel has no power supply ACTION
11. all the system in the following predefined order Install Daikin components as described in the relevant manuals outdoor unit if applicable to your system indoor unit s operation panel Version 5 2 08 12 2010 lI INSTALLATION COMFORT AIR CURTAIN FOR DIRECT EXPANSION 2 Install the air curtain unit as described in the Installation chapter in the CA model Air Curtain Manual I Mount the unit 2 Install the control panel 3 Finish the unit 4 Connect the air curtain unit to the power supply see Sec tion 2 4 5 Connect the air curtain unit to the Daikin system see Sec tion 2 5 6 Install the outside air temperature sensor optional see Section 2 6 7 Turn the system on and check that it functions properly see Section 2 7 2 4 Connecting the unit to the power supply Ensure that an earthed grounded power point is available at a maximum of 5 m from the left side of the unit j Warning The unit must be earthed grounded j Warning The wall socket must remain accessible after the installation of the unit to be able to disconnect the unit from the mains when maintenance work is to be performed j Warning Do not switch the unit on off in normal use via the mains use the control pad 2 5 Connecting the unit to the Daikin system 2 5 1 Connecting the control system All models Caution Use a cable with a minimum cross sectional area of 0 75 mm 12 hiddle MA
12. ce with relevant local and national regulations Any used electrical electronic devices must be handed in for processing in compliance with EU regulations By ensuring that this product is disposed of in the correct manner you prevent any damage to human health and or the environment For more information about this subject please contact your sup plier or local government agency Version 5 2 08 12 2010 27 P I Declaration of Conformity b i d d e manufacturer address We declare that the following product product description brand model type Remark CLIMATE SOLUTIONS Biddle BV Markowei 4 9288 HA Kootstertille The Netherlands Comfort Air Curtain Biddle CA with integrated Daikin print suitable for Daikin VRV or CVP R410A system CA V S 100 150 200 250 CA V M 100 150 200 250 CA V L 100 150 200 250 CA V XL 100 150 200 250 The installer is responsible for making the whole heating system comply with the PED directive In accordance with the following Directives 2006 95 EC 2004 108 EC the Low Voltage Directive the Electromagnetic Compatibility Directive Has been designed and manufactured to the following specifications EMC X EN61000 6 2 EN 61000 6 3 LVD EN 60335 1 EN 60335 2 40 2002 Electromagnetic Compatibility EMC Part 6 1 Generic standards Immunity for industrial environments Electromagnetic Compatibility EMC Part 6 3 Generic standards E
13. e fault occurred in your absence and has been resolved in the meantime For details on the fault messages see the CA model Air Cur tain Manual biddle Settings 4 1 Setting on the Daikin operation panel 4 1 1 General On the Daikin operation panel field settings can be per formed as detailed in its Installation Manual The unit models described in this manual have some addi tional settings 4 1 2 Additional field settings 4 2 Settings on the Biddle control panel 4 2 1 General Mope No FIRST DESCRIPTION SECOND CODE NO CODE NO OF SETTING 01 02 03 04 22 3 Air curtain s unheated unheated halted operation default when 23 when not heat 8 is set to ing 01 23 8 Air curtain s halted unheated unheated operation in default defrost mode On the Biddle control panel settings can be performed at the Managers level and at the Installer s level as detailed in the CA model Air Curtain Manual The unit models described in this manual have some addi tional settings Conversely certain functions do not work with these models Version 5 2 08 12 2010 SETTINGS COMFORT AIR CURTAIN FOR DIRECT EXPANSION 4 2 2 Additional functions at the Installer s level No FUNCTION OPTIONS TOUR SETTING 85 Outside air temperature setpoint Pre settable between 9 5 and 31 C PEE default value 0 C If the outside a
14. essories Daikin components The following components are required with an installation outdoor unit optional one or several indoor units e Daikin operation panel materials necessary for connection e g refrigerant pipes cables etc see the outdoor unit s Installation Manual Note The outdoor unit s control system and capacity index must match with those of the air curtain unit Biddle components The following components are delivered separately but always required e Biddle control panel able to control a maximum of 10 units Biddle control cable available in various lengths only with free hanging models set of end panels Accessories The following accessories are available as options outdoor air temperature sensor biddle MANUAL INTRODUCTION wall bracket set Standard or Design threaded rod lining 1 4 Safety instructions 1 4 1 Operation LU Warning Do not put any objects in the inlets and outlets j Warning Do not block the inlets and outlets U Warning The upper surface of the unit becomes hot during operation Caution Water may leak from the unit in exceptional situations Do not place anything under the unit that may suffer damage as a result of any leakage 1 4 2 Installation maintenance and service A v Danger The unit may be opened by qualified technical staff only j Warning Perform the following actions before opening
15. gs 17 3 3 1 Adjusting settings 17 3 3 2 Adjusting heating 17 3 4 Messages on the Biddle control panel 18 3 4 1 Dirty filter indicator 18 3 4 2 Outside air temperature sensor indication 18 3 4 3 Faults 18 Version 5 2 08 12 2010 3 COMFORT AIR CURTAIN FOR DIRECT EXPANSION Settings 4 Setting on the Daikin operation panel 4 1 1 General 4 1 2 Additional field settings 4 2 Settings on the Biddle control panel 42 1 General 4 2 2 Additional functions at the Installer s level 4 03 Non operational functions Maintenance 5 Replacing or cleaning the filter 5 2 Cleaning the unit 5 3 Scheduled maintenance Faults 6 Safety instructions 6 2 Testing for faults 6 3 Non fault related symptoms 6 4 Faults with specific symptoms Service 7 Safety instructions 7 2 Access to the interior of the unit 7 2 1 Opening the unit 7 2 2 Accessing electronics in the unit 7 3 Fuses 7 4 Other service works Dismantling biddle Introduction 1 1 About this manual 1 2 How to use this manual d y This manual relates to the comfort air curtain models CA V which are intended specifically for application within Daikin direct expansion systems This manual contains information and instructions for installa tion operation and maintenance which are specific to these particular unit models 1 2 1 General This manual is a leading It should be read in the written order From this manual references are made to
16. ir temperature falls below this point then the air volume 7 7 below 9 5 C outdoor air setting is increased by one level temperature sensor regulation deactivated 86 Outside air temperature setpoint 2 Pre settable between 9 5 and 31 C a default value 9 5 C If the outside air temperature falls below this point then the air volume 7 7 below 9 5 C outdoor air setting is increased by two levels temperature sensor regulation deactivated 87 Current outside air temperature and The outside air temperature is displayed sensor function test flashing 9 5 C sensor not connected 4 2 3 Non operational functions The outside air temperature reading function no 69 can not be disabled All functions relating to external controls functions nos 60 6 amp 76 cannot be set All functions relating to discharge air temperature func tions nos 5 51 72 amp 74 an be set but have no effect 20 biddle Maintenance 5 Replacing or cleaning the filter See the Maintenance Section in the CA model Air Curtain Manual 5 2 Cleaning the unit You may clean the exterior of the unit with a damp cloth and a domestic cleaner Do not use any solvents Ensure that no water runs into the unit y Warning U Warning Ensure that the connectors on the top surface are kept dry 5 3 Scheduled maintenance Maintain the air curtain unit according to the Mainte nance Section in the CA model Air Curt
17. mission standard for residential commercial and light industrial environments Safety of household and similar electrical appliances Part 1 General requirements Safety of household and similar electrical appliances Part 2 40 Particular requirements for electrical heat pumps air conditioners and dehumidifiers hereby declare that the equipment named above has been designed to comply with the relevant sections of the above referenced specifications The unit complies with all essentials requirements of the directives signed by P Stoelwinder Managing Director 27 10 2010 p
18. ms in the text when risky actions are being discussed The same pictograms will also be found on the device Table l I Pictograms 1 3 About the unit Warning This surface or part can be hot There is a risk of burns on contact 1 2 4 Related documentation Besides this manual the following documents are supplied with this unit Biddle CA model Comfort Air Curtain Manual wiring diagram for installation and service 1 3 1 System operation The air curtain is connected within a Daikin direct expansion system Air discharged by the appliance is heated by the refrig erant biddle MANUAL INTRODUCTION The air curtain is controlled and operated partially by the Daikin system and partially by the Biddle system 1 3 2 Outside air temperature sensor accessory The sensor controls the air curtain in response to outside air temperatures At lower temperatures the unit is set one or two settings higher 1 3 3 Limitations The unit can only be applied within Daikin direct expan sion systems The unit is not suitable for cooling No external controls may be connected to the unit 1 3 4 Models and type references Table l 2 provides an overview of the models that are described in this manual and their corresponding type refer ences Combined the type references constitute the type code for instance CAVMISODKFBC Several combinations are available Table l 2 Type code explained
19. nical staff only Warning Before opening the unit follow the safety instruc tions in section 1 4 7 2 Access to the interior of the unit 7 2 1 Opening the unit See the Service Chapter in the CA model Air Curtain Man ual 7 2 2 Accessing electronics in the unit j Warning Before opening the unit Follow the safety instructions in Section 1 4 All models Remove the inspection panel see CA Model Air Cur tain Manual 2 Biddle electronics are located at O Version 5 2 08 12 2010 25 SERVICE COMFORT AIR CURTAIN FOR DIRECT EXPANSION Models with discharge widths 150 200 or 250 3 Remove cover Daikin electronics are located behind this cover Models with discharge width 100 4 Remove the cover O from the box on the side of the unit Daikin electronics are located behind this cover 7 3 Fuses There are 4 fuses in the unit Their values are indicated near the fuse holders Table 7 1 Locations of fuses LABEL LOCATION F100 on PCB of Biddle electronics FIIO on PCB of Biddle electronics transformer fuse near transformer with unlabelled Biddle electronics FIU on PCB of Daikin electronics 7 4 Other service works See the Service Chapter in the CA model Air Curtain Man ual 26 biddle Dismantling Dismantling the system handling coolant oil and other com ponents should be performed by a qualified engineer in com plian
20. r 2 Set the operation mode to Heating and set the temper ature setpoint to maximum After some time the unit should discharge heated air 3 Set the operation mode to Fan only After some time the unit should discharge unheated air 4 Switch the system Off After some time the unit should turn itself off 5 If you have installed the outdoor air temperature sensor Verify the operation of the sensor with function no 87 in the Installer s Level see Section 4 2 2 Version 5 2 08 12 2010 15 Operation 3 1 General tciclle Biddle control panel lilii Daikin operation panel 3 2 Switching On and Off The air curtain is operated partially from the Daikin operation panel partially from the Biddle control panel Most features on the Daikin operation panel work as described its Operation Manual However several features do not work or operate differently The features on the Biddle control panel work as described below 3 2 1 Switching the system On and Off To switch the system On or Off press the ly button on the Daikin operation panel When the LED next to this button is lit the system is On If the LED is flashing there is a fault The 9 button on the Biddle control panel has no function When the LED on this panel is lit the system has turned off the air curtain 3 2 2 Selecting the operation mode Select the operation mode with the
21. sensor to the outside of the building Note Do not place the sensor in direct sunlight 2 Connect the sensor to the X82 connector on top of the air curtain 3 Attach the cable housing supplied to the connector 2 Switching on and testing operation 2 7 1 Switching the system on o C Check all air curtain connectors Er BEEP unit s power supply control cable s connecting Biddle control panel and control cable s connecting Daikin outdoor unit and unit s control cable s connecting Daikin operation panel and unit s 2 Turn on the power supply and or put the air curtain plug in the socket If the unit is working correctly then the Biddle control panel will display symbols If multiple air curtain units have been attached Turn on the power supply to all air curtain units 2 Reset the Biddle control panel Please refer to the CA model Air Curtain Manual 3 If applicable to your system Turn on the Daikin indoor unit s as described in their Installation Manual 4 Turn on the Daikin outdoor unit as described in its Installa tion Manual display for non operational air curtain 14 biddle MANUAL INSTALLATION 2 7 2 Testing operation 5 Test the system according to the outdoor unit s Installa tion Manual 6 Operate the unit with the Daikin operation panel see Chapter 3 and verify its operation Il Switch the system On The unit should start to dis charge ai
22. the unit l Switch the system Off using the Daikin operation panel 2 Wait until the fans of the air curtain unit have stopped 3 Allow the unit to cool down The heat exchanger can get very hot Moreover the fans may keep on running for a while 4 Disconnect power supply to the Daikin outdoor unit 5 Disconnect power supply to the air curtain unit Caution If the unit is working or just has worked in defrost mode there may be water in the inspection panel Version 5 2 08 12 2010 9 INTRODUCTION COMFORT AIR CURTAIN FOR DIRECT EXPANSION j Warning The fins of the heat exchanger are sharp 10 hiddle Installation 2 1 General instructions Warning Installation may only be carried out by technically S qualified staff Warning Follow the safety instructions in Section 1 4 Caution The unit should be connected in compliance with all local statutory regulations instructions and standards Caution Taking in building dust grit cement powder etc may dam e ec age the unit While such substances are present in the room do not start to use the device cover air intake and discharge openings You may cover the unit with the packaging material 2 2 Delivery check Check the unit and its packaging for correct delivery Immediately report to the supplier any damage caused in transit e Check whether all parts are included 2 3 Installation procedure Inst

Download Pdf Manuals

image

Related Search

Related Contents

Mode d`emploi  Toshiba B-SV4D Printer User Manual  CASHFLOW 130 ACCEPTOR USER GUIDE  Handbuch zur CamControl LITE - bei der HeiTel Digital Video GmbH  TB-FMCL-USB30 Hardware User Manual  D-Link DWL-7700AP Wireless AG Outdoor AP/Bridge  Silverstone LC10-E  Document  03267 - ELASA SA  wally-user-manual with wifi  