SERVICE CHECKER TYPEⅢ INSTRUCTION MANUAL - Klíma
Contents
1. 19 2 4 Switching on the power supply of Checker TYPE 3 21 Chapter 3 Starting up and ending of TYPE 3 software 23 3 1 Starting up of TYPE 3 software 23 3 2 Setting of customer data 24 3 3 Setting of SS data 25 3 4 Setting of RS 232C port 26 3 5 Ending of TYPE 3 software 27 Chapter 4 Recording of operation data 279 4 1 Displaying of operation data 29 4 1 1 Selection of customer data and others 29 4 1 2 Displaying of network map 33 4 1 3 Inputting of detailed data 3 4 1 4 Displaying of operation data 39 4 2 Setting of recording 41 4 2 1 Setting of periodical recording in case of DIT NET connection and PCB connection
2. 41 4 2 2 Setting of periodical recording in case of only sensor input only 45 4 2 3 Setting of trigger recording 47 4 3 Centralized operation 49 Chapter 5 Playing jpqQjaeQhharCmoo DG_Vv X X _ Q Q Seqqq 51 5 1 Playing of operation data 51 5 2 Playing of network map 54 5 3 CSV output 56 5 4 Data transfer 58 List of applicable models SpecificationS 62 Introduction Thank you for purchasing our Service Checker TYPE II This Instruction Manual explains operation methods on how to use the Service Checker TYPE M and the TYPE 3 software Read carefully the Manual before using correctly the Service Checker TYPE I andthe TYPE 3 software If improper handling of the Service Checker TYPE II and the TYPE 3 software is made without observing correctly the notes specified in the Manual it may cause acciden
3. Periodic Recording Setting D aikin Industries Ltd DIII NET 1_ DIII NET m 1 Red interval 5 7 Second 2 Red stop method Manual Auto record time 30 minutes 3 Record system select possible to select more than one System No Expected record file size a E System 1 DKB 210KB Set completed F1 Total of expected record file size Free disk area If the free disk area is more than 2 GB values may not be corect 4 Sensor input setting Cancel Esc No recording Recording system selection System 1 x Sensor input setting F2 The window of Periodical record setting Procedures Set the 1 Recording interval the 2 Recording end method and the 3 Recording system selection Select the time intervals recording in the hard disk of the personal computer 5 10 20 30 60 120 180 300 600 seconds Since less time intervals need more recording data area for the hard disk the initially set value of 20 seconds is recommended When recording for a long time more than 2 3 days it is recommended that the recording interval should be 120 to 300 seconds The recording interval is an interval recorded in the hard disk of the personal computer The operation data taken in from each air conditioner may be recorded at intervals of several minutes in case of indoor units If recording interval is set at 5 seconds in the PCB connection it may not take
4. id001 Daikin Industries Ltd No data control Select customer Fa n New customer F3 Edit cust data F4 Delete customer ra Cancel Esc 29 Chapter 4 Recording of operation data In case of recording operation data after inputting customer data for a new customer press the New customer F3 and display proceeds to the Input customer data window Proceed to In case of recording operation data for a previously input customer press the Settlement customer F2 by placing the cursor in the customer name and display proceeds to the Network map selection window Proceed to In case of recording operation data for a previously input customer after changing customer data press the Edit customer data F4 by placing the cursor in the customer name and display proceeds to the Input customer data window Proceed to In case of recording only operation data without customer management press the Record only F1 and display proceeds to the Access Method selection Proceed to In case of Record only be careful to note that operation data are overwritten every time 2 In case of recording customer data by the Record only in the DIT NET connection input customer data as much as possible since an air conditioner will be set to restart standby every time When deleting a customer data press the Delete customer F9 When returning to the Main menu press the Cancel ESC 3 In
5. wm Checker Type 3 Software Function F Edit E Option 0 Window Ww S Main Menu Play F2 Data transfer F3 Customer data F4 SS data F5 END F12 Ver1 01 Press F1 to F5 or F12 Key The window of the Customer Selection is displayed below Press the Select customer F2 to display the window of the Network Map Selection Customer Selection 1 Customer selection id001 Daikin Industries Ltd No data control id002 Ex21 3 The window of the Network Map Selection is displayed below By placing the cursor in the target name of the network map press the OK F1 button to proceed the window of the Network Map Display Network Map Selection D aikin Industries Ltd Office DII NET 4 7 98 OK F1 New F2 Edit map name F3 Delete F9 Cancel Esc 54 Chapter 5 Playing of operation data 4 The window of the Network Map Display is displayed below Network Map Display D aikin Industries Ltd DIII NET 1 DIII NET dN NC S E E 8 8 8 8 8 8 8 8 eee ese eee S 014 020 010 019 026 011 009 018 CO C C C C C C Ti Map mode a Display mode F4 Record mode F5 Cancel Esc Down F2 Detail data input F6 Central operation F7 Update map F8 Screen prt F9 UP F1 Down F2 The window is scrolled upward and downward respectively Detail data input F6 The detail data of an
6. Chapter 2 Connection to air conditioner 2 3 Sensor connection Features of sensor connection In case of air conditioners not conforming to the DIIT NET and the PCB connection it becomes possible to measure temperature and pressure by connecting the optional sensor kit Parts Number 999107T Six temperature points and two pressure points are possible to measure Among these points two measurement points of temperature can be monitored as a signal of DC 0 5V or DC 0 1V via measuring instrument by shifting the switch Possible to use in combination with either the DII NET connection or the PCB connection Procedures 1 Connect the sensors of a sensor kit to the Sensor connector at the front side of the Checker TYPE 3 WARNING When measuring current and voltage be sure to input a signal of 0 5VDC or 0 1VDC via measuring instrument to A and V terminals Do not connect these terminals to directly an object to be measured current or voltage or add more than 5VDC to these terminals since fatal injury to human bodies by electric shock or fires and failures of air conditioning systems may be caused Tht Th2 Th3 Th HP LP amp G9 Cable of sensor kit Th1 Connect air temperature thermistor for outdoor Th1 white Connect pipe temperature thermistor Th2 white Connect discharge pipe temperature thermistors Th3 red Since the discharge E pipe temperature thermistors differs from other thermistors in a co
7. Clips Used for making up the DII NET connection Refer to 3 of the Preparation 2 TYPE 3 Power Unit 220V Parts Number 999142T 1 AC adapter TIT ow WARNING Be sure to charge the battery by using the optional charger to prevent accidents such as fires and bursting out 3 Battery charger 3 TYPE 3 Software English Parts Number 999143T Floppy disc 4 Instruction Manual English version for the Service Checker TYPE 3 Parts Number 999144T this Manual Prepare the following 1 Personal computer with the following specifications CPU Pentium 75MHz or above Memory 16MB or larger Hard Disk Empty space of more than 20MB RS 232C 19200 bps or higher Windows95 English version 2 If the Checker TYPE 3 is connected to DII NET terminal for VRV system air conditioners for building make up DII NET connecting cables as follows Procedures Prepare the following signal wires Discharged in the O below When connecting to an outdoor unit it is appropriate for the signal wires to have 2 m in length When connecting to an indoor unit or wiring indoor from the outdoor unit it is possible to lengthen the signal wires within the limits of the DII NET length For control signal wiring use vinyl cords or cables with two core and sheathed as follow Vinyl cabtyre cylindrical cord VCTF JISC3306 Vinyl insulated vinyl sheathed cable for control CVV JISC3401 Vinyl insulated vinyl sheathed cylindr
8. RSXY5G 10G Y1 YAL Heat Recovery RSEY8G 10G Y1 VRV H seri Cooling Only RSX5H 10H Y1 lis Heat Pump RSXY5H 10H V1 YAL TAL RSX5K 10K Y1 TAL VRV K series Heat Pump _ RSXY5K 10K Y1 YAL TAL Heat Recovery RSEY8K 10K Y1 Cooling Only _ RX16 30K Y1 YAL C unit VRV plus series Heat Pump _ RXY16 30K Y1 YAL L unit Heat Recovery REY16 30K Y1 R unit a use Super Multi 2MK58FVIN 3MK75FV1N fer DII DIN NET connection PCB PCB connection 1 Connect to a functional unit 2 Optional M5 RA cable is required 6 Specifications WE Specifications of Service Checker TYPE IL tem Specifications External dimensions 180 width x 150 depth x 45 height mm excluding projecting sections Weight Approx 700g 9VDC 300mA outside Use an AC adapter or battery off TYPE3 newer supny Power 220V Approx 1 2W ean at Approx 8 hours after complete charging when using a battery attached to Battery drive time TYPE3 Power 220V Temperature and 10 to 55 C 10 to 35 C for AC adapter 95 RH or less no condensation humidity conditions RS 232C interface Asynchronous 19200bps D sub 25 pin female straight connection to a personal computer Temperature at 6 points one point for discharge pipe pressure at 2 Sensor input section points high pressure and low pressure Two out of the 6 points can be switched to receive voltage signals O to 5VDC or 0 t
9. Setting of customer data The TYPE 3 software manages the operation data of every customer For that reason be sure to input customer ID If the Record only without customer data management is used in the DII NET connection since restart standby is applied every time at the side of an air conditioner input customer data as much as possible Note Other than input from the following step of Customer data menu the input of customer data is possible by selecting the Record F1 of the Main menu Procedures Press the Customer data F4 in the Main menu to display the window of the Customer selection wm Checker Type 3 Software Customer Selection 1 Customer selection E Customer ID Customer name Record only F1 id001 Daikin Industries Ltd No data control Select customer Fa New customer F3 cust data F4 Deere customer Fa Cancel Esc Function F Edit E Option 0 Window fw Play F2 Data transfer F3 Customer data F4 SS data F5 END F12 Ver1 01 2 55 Corbet eelscton Press F1 to F5 or F12 Key When customer data are newly input press the New customer F3 to display the next window of the Input customer data When the current customer data need to be changed select the customer by cursor then press the Edit customer data F4 to display the next window of the Input customer data When customer data ne
10. for the record time the operation data for 30 minutes before and after trigger are recorded If set to a value higher than 60 minutes the record time before trigger setting will be set to 60 minutes and that after trigger will be set to the value The interval of recording to the hard disk of the personal computer is fixed 10 seconds 2 1 Trigger System 1 only is possible to set trigger recording in the TYPE 3 software record Select a System each outdoor unit recording trigger a ee Chapter 4 Recording of operation data 1 Record time before and after trigger system By placing the cursor in the System No to press the F12 key Recording selection or No recording is shifted The left side of system recording trigger is marked The Trigger conditions can set two groups the Trigger condition 1 and the Trigger condition 2 If either group is met to trigger conditions trigger will start recording Within a group when all the conditions are met to trigger conditions trigger 2 2 Trigger will start recording conditions In the window example of the previous page by the Trigger conditions 1 setting the Thermo ON is ON and trigger is started if Error code shows error state but no other items are related to When clicking with the mouse a column of the Trigger conditions 1 or the Trigger conditions 2 in the right side of the Data item since the selection items OFF ON Neglect are displa
11. 3 Software Network map data will be collected System will be on standby for restarting and aircondi toners on OUI NET will stop for several minutes OF Yes F1 If the restart standby is allowed press the Yes F1 Notes 1 When pressing the Yes F1 air conditioners on the DII NET are set to restart standby making the thermostat switched off for several minutes 2 If using the previous network data by customer management no such message in the window will be displayed again from the second time Then air conditioners on the DII NET are automatically searched for several minutes Network Map Display Daikin Industries Ltd DIII NET 1 DIII NET Ip Fi i Display mode F4 Record mode F5 Cancel Esc Detail data input F6 Central operation en Update map F8 Screen prt F9 Down EZ Note When the wiring change button on the PCB is not pressed after adding or removing an outdoor unit an indoor unit and BS unit and changing PCB the network map may not be displayed In such a case press the wiring change button f the restart standby is not allowed press the No ESC to return to the previous stage and monitor every outdoor unit by PCB connection 33 Chapter 4 Recording of operation data This is the window the Network Map Display Network Map Display Daikin Industries Ltd DIII NET 1_ DIII NET Up F1 Map modera Display mode F4
12. D aikin Industries Ltd Serisor 1 5 nsor input only o Megha Display mode F4 Record mode F5 Cancel Esc Dawn FZ Period rcd set F6 Period rcd start F7 Trig rcd set F8 Trig inspt start F9 The window of the Periodical record setting Periodic Recording Setting D aikin Industries Ltd Sensor 1 Sensor input only 1 Red interval 5 7 Second 2 Red stop method Manual J 3 Expected record file size 12 KB Free disk area If the free disk area is more than 2 GB values may not be corect 4 Measurement data item Set completed F1 Vv Thi Int Item fTM M Th2 item Th M Th3 Item Th ik o Ma Cancel Esc M HP item HP M LP Item LP TA Item f CoN COW ovf Fullscale Unit Oe TY litm eow C OV joy Full scale Unit Procedures 1 Set the 1 Recording interval and the 2 Recording end method Refer to of the 4 2 1 Setting of periodical recording in case of DII NET connection and PCB connection Not setting of the 3 Recording system selection Set the 4 Setting of sensor input Refer to of the 4 2 1 Setting of periodical recording in case of DII NET connection and PCB connection 3 When completing to set the above press the Setting complete F1 to return to the window of the Network Map Display 4 When starting the periodical recording press the Periodical record start F7 in the window of the Network M
13. Input each item of the 2 Detail data input The items are as follows po tem ieseription Installation site name Input fora memo Model No Input for a memo Since the automatic type identification in the DIT NET connection and the model name of the PCB connection input by following the window of the Access Method Selection in the 4 1 1 Selecting of customer data and Model name others are roughly designated model name select here the model name in detail After selected model name can be edited In case of an indoor unit input model name since there are no selection items Centralized address Input for a memo In case of the DIZ NET connection address is automatically taken in In Rute address the window of the Network Map Display the icons are displayed in order of auto addresses lt Not to possible to change In case of the DIIT NET connection AIRNET address is automatically AIRNET address taken in This address is set to an indoor unit by remote controller Not to possible to change After one set of data for an air conditioner are completed to input press the Save F1 237 Chapter 4 Recording of operation data Notes By selecting another air conditioner with the 1 Airconditioner selection to input necessary data press the Save F1 In case of replacing PCB of an air conditioner auto addresses in the network are changed If in the DII NET connection a PCB of an air conditio
14. after this are overwitten No F3 While not overwriting this operation data the next operation data are successively being transferred Cancel ESC Data transfer is stopped Same operation data already exists Current operation data Customer ID fidoo System Mo Daikin Industries Ltd Record start time 4 16 98 11 43 00 System 1 Customer name Network map name DI NET 1 File size Overwrite the following new operation data Customer ID fidoo System Mo System 1 Daikin Industries Ltd Record start time 14 16798 17 43 00 Network map name DII NET 1 File size Yes F1 es to all FZ No F3 D If the customer data with the same title already exists the following window is displayed The functions of the buttons are same as the above C Customer name Current customer data Customer ID fig Customer name L aikin Industries Ltd Ovenarite the following new customer data Customer ID fidoo Customer name Oakin Industries Ltd 2 Transfer only customer data Same as the 1 Transferring operation data and customer data other than selecting the Customer data at the upper left in the window 3 After ending the data input press the Cancel ESC 59 Chapter 5 Playing of operation data 60 Chapter 5 Playing of operation data List of Applicable Models pType Model DIII PCB Cooling Only RSX8G 10G Y1 YAL VRV G series Heat Pump
15. data display is shown below Uperation Data Display D akin Industnes Lid DIN NE 1 1 DIN NE ISystem 1YRY Y_PLUS L_C IN 40 1 Themostat_ON Su OFF A 1 1 Restart_stand hy S1 NFF A 1 FrrarendelSystera 117 7 1 Frrar_endelln 14 811 1 Amhenttenn AP Te 90 1 Healexchanger_le 47 1 C 100 1 Diszh _pipe_temp 13 0 C 11 0 1 Diszh _pipe_temp 13 0 C 12 0 1 Suction_pipe_ten 47 5 C 13 0 1 DiLtemp NV 47 5C 14 0 1 Dil temp fSTD 47 5C zj 4 gt i i On reproduce pericd red data 4 16 9811 44 20 11 44 00 11 44 30 11 45 30 0 1 X Larcel Esc Grapa Suror noverent Let r5 r rc Searsh ra Screen prt ra Fas Fi Ned ra Netn FZ Tord ra X Refer to the 4 1 4 Displaying of operation data regarding detailed display When clicking the mouse on a graph the data at the time are displayed in the right list The following buttons function to a graph Expansion F 1 A graph is displayed by shortening the display time of the graph Reduction F2 A graph is displayed by lengthening the display time of the graph Return F3 A graph is moved to the left in the window Forward F4 A graph is moved to the right in the window Left F5 The cursor on a graph is moved to the left in the window Right F6 The cursor on a graph is moved to the right in the window Print screen F9 Screen is printed 4 The maximum and minimum analog data and error code can be searc
16. there are items updating at intervals of several minutes Full scale When graphing analog data full scale corresponds to a 100 value 39 Chapter 4 Recording of operation data Notes 1 2 Eight items per an air conditioner for analog data and digital data are displayed respectively By placing the cursor in a data item to be displayed and pressing the F12 key the data item is marked at the leftend by and its graph is displayed in the left side of the window at the same time In case of ending a graph displayed by a data item place the cursor in the data item on the list at the right in the window and press the F12 key In the PCB connection the data item with Retry does not show Retrying but shows to have retried before On the data item of an indoor unit connected to the PCB Internal and external transmission error shows the state that due to an indoor unit s error signal transmission between an indoor unit and an outdoor unit cannot be performed Indoor unit error shows the error state that it is impossible for an indoor unit to switch thermostat ON System error shows that the overall system between an indoor unit and an outdoor unit is error Error between remote controllers shows the error state between an indoor unit and a remote controller Because of not covering all of model classification in the TYPE 3 software small horse power models may display the items of not existing sen
17. this window of the Input customer data input customer data Customer ID fidoo Customer name Daikin Industries Ltd O00000 Section fo save FT Person in charge POO O Address Poo Telephone P Cancel Esc Fax Po Remarks Be sure to input the Customer ID with alphanumeric letters to identify customers Input the Customer name as much as possible to display in the windows of the Selection of operation data and others Use as memos items other than Customer ID and Customer name When ending press the Record F1 button and display proceeds to the Network map selection window Proceed to When returning to previous state input waiting state without saving press the Cancel ESC button 30 Chapter 4 Recording of operation data This is the window of the Network map selection Hetwork Map Selection D aikin Industries Ltd Map name Access method Modelname Date 427798 E Difice DIN NET OK F1 New F2 Edit map name F3 Delete F9 Cancel Esc Notes 1 For one customer multiple network maps can be managed 2 On the unit of network map 1 In case of the DII NET connection construct by every object or even if the objects are same construct separately each network map for both sides divided by DII NET expansion adapter DTA109A1 2 In case of the PCB connection construct a network map for each outdoor unit In case of being same network map fo
18. unit with average data 3 There are some models of air conditioners which cannot display indoor units by the PCB connection 4 The system displayed at the upper left in the window denotes a unit of an outdoor unit In the VRV PLUS one system is constructed by the overall system including the function units The DILZ NET connection can take in the data of multiple systems at the same time The Central column in the window indicates Centralized address input by the Detail data input while the Installation site column indicates Installation site input by the Detail data input In the DII NET connection the AIRNET address automatically taken in by the TYPE 3 software is displayed in the AIRNET column in the window 2 When the number of systems or air conditioners is too much to display in one window press the Up F1 or the Down F2 at the left below side of the window to scroll the window 34 Chapter 4 Recording of operation data 3 In the group of buttons displayed at the bottom of the window by shifting a mode with the upper 3 buttons the bottom 4 buttons can execute each function A Map mode F3 Map mode F3 Detail data input F6 In case of inputting detailed data such as types installation sites press this button Proceed to the 4 1 3 Inputting of detailed data Centralized control F7 In case of DII NET connection the centralized control of indoor uni
19. 41T and serial connector conversion cable conditioner for Attached to the Checker TYPE 3 building 1 TYPE 2 spare 999113T Use to drive the Service Checker TYPE II battery 1 Attached to the TYPE 3 Power 100V 1 They can be used as optional or spare items for the Service Checker TYPE2 Product name Service Checker Part number 999118T Please follow Daikin s purchasing procedure Pentium is a registered trademark of Intel Corporation Other product names mentioned above are trademarks or registered trademarks of respective companies The above prices do not include consumption tax The above specifications are valid as of April 1998 and they may be modified for improvement without any advance notice For any inquiries please contact the following division DAIKIN INDUSTRIES LTD Engineering amp Information Sect Planning Dept After Sales Service Div Umeda Center Bldg 2 4 12 Nakazaki Nishi Kita Ku Osaka 530 Japan Phone 006 374 9373 FAX 06 373 4382 63 2952
20. Checker Type3 Removal Are you sure you want to completely remove Daikin ServiceChecker Type3 and all of its components After completing the deletion of the TYPE 3 software the following message is displayed in the picture as shown below Press the OK button For safety reasons this procedure will not allow to delete operation data and customers information In case of deleting completely all the data including the operation data and customer data delete by following the next ei Daikin ServiceChecker Type3 Removal Start up the Explorer Since the operation data and customer data are normally located under the folder of c Program Files Checker3 delete all the folders under c Program Files Checker3 14 Chapter 1 Installing of TYPE 3 software Chapter 2 Connection to air conditioner WARNING When using outdoor the Service Checker TYPE 3 be sure to protect it from rain so that it becomes free from the danger of electric shock and fires When leaving the Checker for a long time as it is take proper measures against leak current and rain water which may cause fires Be sure to connect AC adapter and the Charger to AC 220V The connecting method between the Checker TYPE 3 and Daikin s air conditioning systems consists of three DII NET connection PCB connection and Sensor connection Select an appropriate one depending on their advantages 2 1 DIL NET connection Features of
21. DAIKIN SERVICE CHECKER TYPEM INSTRUCTION MANUAL Corresponding to Ver 101 Wiffle oe ett z a F e il mg a ee seia X l a a i lt ET i 4 F Issued by Maintenance Sales Dep After Sales Service Div DAIKIN INDUSTRIES LTD 980423 DAIKIN INDUSTRIES LTD Introduction Outline of the Manual 3 Confirming of packaged items 4 Preparation 6 Name of each part T Chapter 1 Installing of TYPE 3 software 1 1 Installing of TYPE 3 software 9 1 2 Deleting of TYPE 3 software 13 Chapter 2 Connection to air conditioner 15 2 1 DII NET connection 15 2 2 PCB connection 17 2 2 1 PCB connection to VRV system air conditioner for building 17 2 2 2 PCB connection to room air conditioner and Super Multi 18 2 3 Sensor connectiOn
22. DII NET connection Possible to monitor simultaneously the operation data of multiple outdoor and indoor units on the DII NET by connecting to VRV system air conditioners for building and chillers conforming to the DII NET in internal and external data transmission Units conforming to the DII NET are shown in the List of applicable units at the end of this Manual Note The range exceeding the limits of the DII NET expansion adapter DTA109A1 is not possible to monitor To connect to the DII NET terminals F1 F2 located on the PCB of an outdoor unit or an indoor unit Note In case of an indoor unit connect the end of the indoor unit not so as to create sub branching When the Service Checker TYPE 3 is connected to the DII NET for the first time be careful to note that air conditioners on the DII NET will be set to restart standby for several minutes In performing customer management unless PCBs are replaced or the number of air conditioners has changed the air conditioners will not be set to the standby state from the second time on by utilizing the previously recorded data of network map The intervals of monitoring operation data are different depending on data items Besides be careful to note that the operation data of an indoor unit are monitored at intervals of several minutes If the length of a connecting cable for the DIL NET is within the limits of the DII NET it is possible to lengthen the cable Not poss
23. F4 Vertical scroll bar Digital data graph display Horizonta scroll bar Possible to jump to another air conditioner in the same system 1 miele data graph display upper left in the window Time and percentage ratio 20 to 100 to full scale are indicated in the horizontal axis and in the vertical axis respectively Since full scale is located at the end of the right side of data item list in the window see by moving the horizontal scroll bar to the right When at100 full scale value is indicated The number and color of a graph coincide with those of atthe left end in the data item in the window Eight items per an air conditioner can be displayed 2 Digital data ON OFF graph display left bottom in the window In case of ON blue bar is displayed The number of a graph coincides with that of the left end in the data item in the window Eight items per an air conditioner can be displayed 3 Present value display of each item list at the right side in the window Item of list CieScription O left end Data in a graph corresponds to colored From left Successive number Distinction and number of indoor and outdoor Data item unit and item name are displayed Operation data are displayed Data In case of DIL NET connection updating of operation data of an indoor unit is at intervals of several minutes The time of data updated is displayed Update time In case of D NET connection
24. F6 Ope mode Cooling I In this window air conditioners possible to make centralized operation displayed in order of centralized address by icons The icons are displayed with colors changed according to the state of an air conditioner Error state Operating state Stopped state 49 Chapter 4 Recording of operation data Procedures Make centralized operation by placing the cursor at the icon of target air conditioner and pressing the buttons at the bottom in the window and inputting figures Column Up F1 Move upward in the window Down F2 Move downward in the window Operation F3 Command air conditioner to operate Command air conditioner to stop Set temperature with a range of 0 35 C Up F5 PFS X Even if an air conditioner with the maximum temperature rating of 25 C D F6 is set to 35 C with A F5 the display is returned to 25 C in 2 3 seconds Cooling F7 ssue cool mode command to air conditioner Heating F8 ssue heat mode command to air conditioner Fan F9 ssue fan mode command to air conditioner f error occurs display error code Same statement as remote controller is displayed with red characters in the right side in the window Under Center Control Not possible to operate from Checker Under Forced Stop Not possible to operate from Checker other than stop Under Centralized Control If other centralized instrument has prohibited the operations of indoor units Ri ee fr
25. PE 3 software Note In case of shifting Th5 to A or Th6 to V by using the switch of the Checker TYPE 3 shift at a window before the window of Display of network map otherwise operation data will not be correctly recorded 2 Set the sensor block to air conditioning systems When measuring current and voltage be sure to input a voltage signal of 0 5VDC or 0 1VDC via the measuring instrument to the sensor connectors of the Checker TYPE J 20 Chapter 2 Connection to air conditioner 2 4 Switching on the power supply of Checker TYPE 3 Procedures AM Connect the RS 232C cable attached to the Checker TYPE 3 to the RS 232C connector of the Checker TYPE 3 and the Serial connector of a personal computer RS 232C connector Power Supply connector Connect the AC adapter attached to the TYPE 3 Power Supply 220V or a battery to the Power Supply connector of the Checker TYPE 3 CAUTION Be sure to use the AC adapter attached to the TYPE 3 Power Supply 220V or a battery to prevent accidents such as fires 3 Turn on the Power Switch of the Checker TYPY 3 The red lamp of the Power Switch lights When the Checker TYPE 3 is normally operating the green lamp flashes Power Switch Operation Lamp lll _ Fai ml TFI Thi Tha Th3 Tih HF il LP i camela Ge mi ot oa A 3 H _ 21 Chapter 2 Connection to air conditioner 22 Chapter 2 Connection to air conditioner C
26. Record mode F5 Cancel Esc Down F2 1 Detail data input F6 Central operation F7 Update map F8 Screen prt F9 1 This is the picture of the Network Map Display The window displays outdoor units and indoor units in order of each auto address by using icons The colors of the icons are changed depending on the state of an air conditioner Error state Red In case of Super EX21 if any of outdoor units are not normal all of outdoor units and function units are displayed Red Transmission error Purple Chillers and Energio exceeding the range of the DII NET expansion adapter are displayed Purple even if they are normally operating Indoor unit operating state Green Outdoor unit thermostat ON state X Excluding Super Multi and room air conditioners Indoor unit not operating state Outdoor unit thermostat OFF state ite When air conditioners connected to the DII NET exist but their types have White not been identified automatically this color icon is displayed while identifying the types automatically for a few minutes Notes 1 Be careful to note that Super Multi and room air conditioners connected to the PCB cannot be correctly displayed in distinguishing between an indoor unit and an outdoor unit If nine or more indoor units are connected by using an expanding adapter fo indoor units be careful to note that the display of operation data on the units is limited to on one indoor
27. air conditioner designated by cursor are displayed Print screen F9 Screen is printed Cancel ESC Return to the window of the Network Map Selection 55 Chapter 5 Playing of operation data 5 3 CSV output The data of CSV format possible to be read into by a commercial integrated software are output Procedures Press the Play F2 in the Main Menu to display the window of the Customer Data Selection wm Checker Type 3 Software Function F Edit E Option 0 Window Ww SU Main Menu Data transfer F3 Customer data F4 SS data F5 END F12 Verl 01 Press F1 to F5 or F12 Key The window of the Customer Data Selection is displayed below Press the CSV data output F3 to display the window of the Save with file name Customer Data Selection Customer Customer nar Map name System N Model name Ac Re Record start tine id001 Daikin Industri DIN NET 1 System 1 VAY PLUSII Dil Pe 4 16 98 11 43 00 id001 Daikin Industri DIII NET 1 System 2 VRV K DII Pe 4 16 98 11 43 00 Daikin Industri DIII NET 1 System 2 VRV K DII Tri 4 16 98 14 19 40 Daikin Industri DIII NET 1 System 1 AxY10K DII Pe 4 16 98 12 25 20 EX21 DIII NET 1 System 1 YAY_PLUS I DII Pe 4 16 98 14 07 25 EX21 DIII NET 1 System 2 VRV K DII Pe 4 16 98 14 07 25 EX21 DIII NET 1 System 1 VAY _PLUS I DII Tri 4 16 98 14 08 00 3 The window of the Save with file name is displayed below Select the Saving site to
28. ame and the Folder name directory name can be changed The unit of data transfer consists of two 1 Operation data and Customer data and 2 only Customer data X The data of network map are included in the customer data 1 Transferring operation data and customer data A In case of transferring data from the hard disk of a personal computer to a floppy disk or MO 1 Select the Operation data at the left side in the window before selecting the transferring operation data in the list below 2 Select the destination of transfer by using the Drive name and the Folder name directory name at the right side in the window 3 Pressing the gt F1 to transfer the operation data and customer data 58 Chapter 5 Playing of operation data B In case of transferring data from a floppy disk or MO of a personal computer to the hard disk 1 Select the Operation data at the upper left in the window 2 After setting the floppy disk or the MO to the personal computer select the source of transfer by using the Drive name and the Folder name directory name at the right side in the window 3 By using the list below the Folder name select the operation data 4 Pressing the lt F2 to transfer the operation data and customer data C If the operation data with the same title already exists the following window is displayed Yes F1 Only this operation data is overwitten Overwrite all F2 All the operation data
29. ap Display to display the Periodical recording in red at the upper left in the window Also the indication of the button is changed to the Periodical record end F7 a 5 Chapter 4 Recording of operation data Network Map Display D aikin Industries Ltd Sensor 1 Sensor input only System 1 EEE Period Ried Ua Ely Map mode F3 Display mode F4 Record mode F5 Cancel Esc j Period rcd set F6 Period rcd end F7 Trig rcd set F8 Trig inspt start co When ending manually the periodical recording press the Periodical record end F7 If in the Recording end method of 1 the Automatic is set recording data is automatically ended after pre set recording time 46 Chapter 4 Recording of operation data 4 2 3 Setting of trigger recording System 1 only is possible to set trigger recording in the TYPE 3 software The Trigger recording is a method which records before and after meeting trigger conditions a combination of digital values ON OFF of operation data Notes 1 Since air conditioners conforming to the DII NET in the internal and external transmission method will take maximum several minutes for data transfer intervals triggering may be delayed several minutes even if actual changes are taken place in an air conditioner Depending on a combination of trigger conditions triggering may not occur because of time deviation between the changes of an air conditioner and its da
30. arting up and ending of TYPE 3 software on the starting up and ending of the TYPE 3 software and the setting of customer data and others After connecting the Service Checker TYPE II to the air conditioner and the personal computer operation data and network map linking between an indoor unit and an outdoor unit can be displayed by following the procedures of the Chapter 4 Recording of operation data Also following the procedures of the 4 2 Setting of recording it is possible to record data after setting to record them into the hard disc of the personal computer When recording operation data and network map are recorded while in playing the operation data and network map are played by following the procedures of the 5 1 Playing of operation data and the 5 2 Playing of network map respectively Confirming of packaged items The Service Checker TYPE II consists of five standard items packaged as follows Check up the contents in the package See optional items in the Specification at the end of the Manual 1 Service Checker TYPE 3 Parts Number 999135T 1 Service Checker TYPE 3 2 Cable for VRV system air conditioner for building Used for PCB connection to VRV system air conditioners for building 3 Serial connector conversion cable Used when connecting M5 RA cable to the Service Checker TYPE 3 4 RS 232C cable D sub 25 pin male D sub 9 pin female straight 5
31. completed by pressing the OK button Daikin ServiceChecker Types Setup 12 Chapter 1 Installing of TYPE 3 software 1 2 Deleting of TYPE 3 software When deleting the TYPE 3 software English follow the procedures described below Procedures In the Windows 95 initial window of the personal computer press the Start button before selecting the Control panel on the Setting in the pull down menu My Computer e 32btODBC Accessibility Add New Add Remove i ptions Hardware rogram A a 8 Fonts Keyboard Modems REI Passwords Printers Regional Settings Sets up programs and creates shortcuts A 3 Select the Daikin Service Checker Type 3 before pressing the Adding and deleting button in the right below in the window Add Remove Programs Properties EAE Install Uninstall Windows Setup Startup Disk To install a new program from a floppy disk or CD ROM drive click Install The following software can be automatically removed by Windows To remove a program or to modify its installed components select it from the list and click Add Remove Daikin ServiceChecker Type Visual Basic 5 0 Enterprise Editon 13 Chapter 1 Installing of TYPE 3 software 4 If the following message is displayed in the window as shown below select the Yes button After the picture of confirming the deletion of DataCtrl dll is displayed select the Delete button Daikin Service
32. cording the operation data of a selected system for the Record time before and after trigger set by the trigger recording is automatically ended 48 Chapter 4 Recording of operation data 4 3 Centralized operation In the DII NET connection the centralized operation of indoor units can be made from the Service Checker TYPE II If no centralized control equipment on the DII NET is provided set centralized address After connecting the Checker TYPE 3 to the DII NET and setting customer data by the TYPE 3 software display the window of the Network Map Display To set in this window centralized address to each indoor unit by using a remote controller centralized operation will become possible From the next time the centralized operation can be performed without setting the centralized address by using both customer data obtained this time and the network map without setting of centralized adress The window of the Centralized operation is displayed by pressing the button of the Centralized operation F7 after selecting the Map mode F3 in the window of the Network Map Dis alle y Network Map Display D aikin Industries Ltd DII NET 1 DIII NET System 2 jown F2 Detail data input F6 Central operation en Update map F8 Screen prt F9 The window of the Centralized operation BEE Ope Fa Temp Up F5 Cool F7 Heat Fa Fan F9 Emar eade Down rafi Stop Fa E c C
33. d it for you open 9 Chapter 1 Installing of TYPE 3 software 3 Insert the floppy disc of the Checker TYPE 3 software 1 2 into the floppy disk drive of the personal computer before selecting the 3 5 inch FD ers reseed My Computer 71x Oe ay Sl cel fee a File name Setup exe Fedw Fosae N cama _ Press the OK button My Computer My Computer Inbox re ed Recycle Bin mon Copying initialization files e These files will be removed if setup is cancelled 5 The 4 soft Doea 7 RANNASSA A Type the name of a program folder or document and Ss Windows will open it for you Open fs Setup exe r TS a 10 Chapter 1 Installing of TYPE 3 software After the message is displayed in the screen as shown below remove from the floppy disk drive the floppy disc of the Checker TYPE 3 software 1 2 and insert the disc of the software 2 2 before pressing the OK button My Computer a Recycle Bin EN Please insert the disk labeled Set Up TH Thes Disk 2 into drive A Set Up The i Microsoft Network After the message is displayed in the window as shown below press the OK button Daikin ServiceChecker Types Setup A Daikin ServiceChecker Type3 Setup ea Welcome to the Daikin ServiceChecker Type3 installation program Prrd Setup cannot install system files or update shared files if they are in use Before proceeding we recommend that you close an
34. ding mode F5 pS Recordingmode F5 Periodical record Periodical record Trigger record Trigger inspection setting F6 start F7 setting F8 start F9 The method of recording operation data consists of two one is the Periodical recording which records successively for a constant time and another is the Trigger recording which records before and after meeting trigger conditions conditions of digital data ON OFF The TYPE 3 software can set separately the method Periodical record start Periodical record Trigger inspection start Meeting trigger conditions time Trigger record Periodical record setting F6 By proceeding the window of Periodical recording setting the periodical recording is set Proceed to the sections of 4 2 1 and 4 2 2 for periodical record setting Periodical record start F7 By pressing this button periodical record is started to indicate Periodical recording in red at the upper left in the window The indication of the button is changed to Periodical record end F7 Pressing the button again the periodical record is ended Trigger record setting F8 By proceeding to the window of Trigger record setting trigger record is set Proceed to the 4 2 3 Setting of trigger record Trigger inspection start F9 By pressing this button trigger inspection is started to indicate Trigger inspecting in red at the upper left in the window When meeting trigge
35. e section of 2 3 Sensor connection otherwise proceed to the section of 2 4 Switching on of the Checker TYPE 3 16 Chapter 2 Connection to air conditioner 2 2 PCB connection Features of PCB connection To connect normally to service ports on the PCB of an outdoor unit Depending on the type of an air conditioner the state of an indoor unit is also possible to monitor In case of a room air conditioner the PCB is connected to an indoor unit In case of VRV PLUS the PCB is connected to a function unit L C unit or R unit Connect separately a cooling plus unit Refer to applicable units possible to make the PCB connection in the List of applicable units at the end of this Manual Depending on the type of an air conditioner the items of operation data possible to monitor are different Monitoring the operation data of an outdoor unit is at intervals of minimum 5 seconds but those of indoor units conforming to the DII NET are at intervals of several minutes Depending on the air conditioner type the cables to be used are different There are three kinds of cables as follow 1 In case of VRV system air conditioner for building use cable for VRV system air conditioner for building supplied with the Checker TYPE 3 as standard accessory 2 In case of room air conditioner or Super Multi use optional M5 RA cable Parts Number 999140T Not possible to use in combination with the DIIT NET connection but Sensor conn
36. e type of an air conditioner so selection is not necessary PCB connection Possible to use only PCB connection or in combination with Sensor input Same method as the conventional Service Checkers Select a type of an air conditioner Access Method Selection D aikin Industnes Ltd 1 Network nap nane Poo sornection 1 2 Sooctess method t DRET ie PCB conection Typical model selection cancel Esc VEGAS rG g WWE SEY JR WWE FSP PoK New WAV EE Sey Sk TOF a Sensor input only Select this when monitoring by an optional sensor kit the temperature and pressure of an air conditioner in not conformity with DIIT NET or PCB connection 3 If the selection is OK press the O K F1 Proceed to the window of the Network Map Display Refer to 4 1 2 Network map display When returning to the previous stage press the Cancel ESC 32 Chapter 4 Recording of operation data 4 1 2 Displaying of network map If time setting of the personal computer is made after the window of the Network Map Display the order of data to be recorded is changed resulting in not recording data correctly Do not make time setting of the personal computer after the window of the Network Map Display X lt When the Checker TYPE 3 is connected to the DII NET for the first time air conditioners on the DII NET will be set to restart standby for several minutes displaying the following message Checker Type
37. ecker TYPE 3 AC adapter or battery is connected 9VDC Use AC adapter or battery e attached to the Checker TYPE 3 Power switch When switching on the red lamp is lit Operating lamp When the Checker TYPE 3 is normally operated the green lamp is flashed When using cables for Super Multi or room air conditioner this connector is Serial Connector used for connecting the attached serial connector conversion cable to the Checker TYPES When making PCB connection to VRV system air conditioner for building Parallel connector this connector is used for connecting the cable of VRV system air conditioner for building to the Checker TYPES This connector is used for connecting the optional sensor kit Parts Number 999107T This terminal is for connecting the connecting cable for the DIT NET prepared in 3 the section of the Preparation Sensor connector DII NET terminal Chapter 1 Installing of TYPE 3 software 1 1 Installing of TYPE 3 software When the Service Checker TYPE II is newly purchased or the version up of the TYPE 3 software English is made install the new version of TYPE 3 software into the personal computer Procedures In the Windows 95 initial picture in the personal computer press the Start button before selecting the Executing by designating a file name el 14 2 doc WordPad Press the Reference button e Type the name of a program folder or document an
38. ection 2 2 1 PCB connection to VRV system air conditioner for building Procedures 1 Connect the cable for VRV system air conditioner for building attached to the TYPE Checker 3 to the Parallel connector at the right side of the Checker TYPE 3 Parallel connector Then connect another side of the cable to the Service ports on the PCB of an outdoor unit Notes 1 Normally connect to a white connector 2 Since the old types of VRV system air conditioners for building such as G series are equipped with two service ports white and blue colors on the PCB if so connect to the two service ports In case of VRV PLUS connect to the function units L C unit or R unit By this connection the operation data of the function units an outdoor unit excluding a cooling plus unit and an indoor unit can be monitored 17 Chapter 2 Connection to air conditioner 2 2 2 PCB connection to Room air conditioner and Super Multi air conditioner Procedures Connect the serial connector conversion cable attached to the Checker TYPE 3 to the Serial connector at the right side of the Checker TYPE 3 Serial connector Then connect another side of the cable to the optional cable for M5 RA Parts Number 999140T 3 Then connect another side of M5 RA cable both to an indoor unit for a room air conditioner and to the Service ports on the PCB of an outdoor unit for Super Multi air conditioner respectively 18
39. ed to be deleted press the Delete customer F9 24 Chapter3 Starting up and ending of TYPE 3 software Customer ID fidoo a Customer name Daikin Industries Lid O a Section ooo Save F1 a Person in change O Address Po Telephone Po Cancel Esc Fax FO Remarks 1 3 Be sure to input the Customer ID with alphanumeric letters to identify customers Input the Customer name as much as possible to display in the windows of the Selection of operation data and others 6 Other items are only for memos When ending press the Record F1 button When returning to previous state input waiting state without recording press the Cancel ESC button Setting of SS data Procedures Press the SS data F5 in the window of the Main menu to display the window of the Input SS data wm Checker Type 3 Software Function F Edit E Option 0 Window w SS Data Input SS name SS address Save F1 SS tel No Customer data F4 55 fax No Cancel Esc SS data F5 SS contact x Add F5 END F12 Delete F6 Ver1 01 i ecor Play F2 Data transfer F3 Press F1 to F5 or F12 Key Input each item Other than the item of In charge of use as memos Input the name of the Person in charge of SS before pressing the Add F5 button When deleting select the name to be deleted by cursor before pressing the Delete F6 After completing the input press t
40. essing time of a personal computer differs depending on the model of an air conditioner and its capability respectively note that the above time is only an estimation 57 Chapter 5 Playing of operation data 5 4 Data transfer To exchange customer data and operation data data transfer to a floppy disk and MO is possible Note In case of exchanging data between personal computers copy the data to a folder directory installed the TYPE 3 software in the section of the 1 1 Installing TYPE 3 software Procedures 1 Press the Data transfer F3 in the Main Menu to display the window of the Data Transfer wm Checker Type 3 Software Function F Edit E Option 0 Window fa i Record F1 ee eee EENEN E eee ered Play F2 Data transfer F3 Customer data F4 SS data F5 END F12 Ver1 01 The window of the Data Transfer is displayed below Data Transfer Checker Type 3 Software Designate source or destination of transfer Drive name x Operation data Customer data Folder name csv id C d3data gt Dail Jaikin Industri DIIIL NET 1 Syster alkin tri D Suste DIII NET 1 DIII NET 1 DIIN NET 1 Company C Company C Syster The left in the window is a site on the hard disk of a personal computer installed the TYPE 3 software fixed The right in the window is a destination of transfer The Drive n
41. hapter 3 Starting up and ending of TYPE 3 software 3 1 Starting up of TYPE 3 software Note If connection to an air conditioner is made by PCB connection method end other software before starting up the TYPE 3 software since the processing time of the TYPE 3 software will take longer Procedures In the Windows 95 initial window in the personal computer press the Start button before selecting the Program P in the window Select the Checker TYPE 3 software b mE Microsoft Visual Basic 5 0 gt A StartUp gt KE MS DOS Prompt Q Windows Explorer Data transfer F3 Customer data F4 SS data F5 END F12 Verl 01 Press F1 to F5 or F12 Key Record F1 Press when recording Refer to Chapter 4 Recording of operation data Play F2 Press when seeing recorded operation data Refer to 5 1 Play of operation data Data transfer F3 Recorded operation data and customer data are transferred to a 23 Chapter3 Starting up and ending of TYPE 3 software 3 2 floppy disk or MO Refer to 5 4 Data transfer Customer data F4 Customer data are input and edited Be sure to input customer ID Recorded network map data are possible to see here Refer to 3 2 Setting of customer data and 5 2 Play of network map LSS data F5 SS data are normally input Refer to 3 3 Setting of SS data LEND F12 The TYPE 3 software is ended Refer to 3 5 Ending of TYPE 3 software
42. he Record F1 button When returning without recording press the Cancel ESC 25 Chapter3 Starting up and ending of TYPE 3 software 3 4 Setting of RS 232C port The personal computer is equipped with the setting of RS 232C ports COM1 COM2 COM3 and COM4 In case of using a laptop personal computer use the serial connector initially COM1 fixed on the back side If changing the ports change by pressing the Communication port T in the menu of the Option W Checker Type 3 Software Function F Edit E GRRE Window w Communication Port I _ V COMTO Play F2 Data transfer F3 Customer data F4 SS data F5 END F12 Press F1 to F5 or F12 Key 26 Chapter3 Starting up and ending of TYPE 3 software 3 5 Ending of TYPE 3 software 1 When ending the TYPE 3 software press the End F12 button in the window of the Main menu wm Checker Type 3 Software Function F Edit E Option 0 Window w a Main Menu Data transfer F3 Customer data F4 SS data F5 END F12 Yerl 01 Press F1 to F5 or F12 Key 2 In case of ending the TYPE 3 software after recording and playing it is necessary to repeat several times pressing the Cancel ESC to return to the window of the Main menu In this case by pressing the x utton in the extreme upper right of the window the TYPE 3 software will end at once Operation Data Display D aikin Industries L
43. hed X Digital data cannot be searched Press the Search F7 button by placing the cursor in data item to be searched in the list at the right in the window 1 In case of analog data Operation Data Search 15 O 1 Inverter_frequency ie lo min Search from top a Ti mar pie Search next F2 Masimum value C Minimum value Cancel Esc Input the conditions at the left in the window Search from the top F1 Searching is made from the top of operation data Search next F2 Searching is made in the direction from a cursor position on a graph to time lapse Cancel ESC Returning to the window of the Operation Data Display 52 Chapter 5 Playing of operation data 2 In case of error code Operation Data Search 6 O 1 Errorcode Error code will be searched Search next F2 3 Cancel Esc Data with error code is searched Search from the top F1 Searching is made from the top of operation data Search next F2 Searching is made in the direction from a cursor position on a graph to time lapse Cancel ESC Returning to the window of the Operation Data Display 6 Press the Cancel ESC button to return to the window of the Customer Data Selection 53 Chapter 5 Playing of operation data 5 2 Playing network map The network map is played from customer data Procedures M Press the Customer data F4 in the Main Menu to display the window of the Customer Selection
44. ible to use in combination with PCB connection but Sensor connection 15 Chapter 2 Connection to air conditioner Procedures 4 Screw tightly the clip free end of DII NET connection cable made up by following the item 3 of the Preparation at DII NET terminals F1 F2 of the Checker TYPE 3 If an air conditioner side is first connected and the resultant short circuit should occur it may cause the failures of the air conditioner Tht Th2 Tha Tha CHI TE oo b amp DII NET terminals D Connect the clipped side of the DII NET connection cable to the air conditioner WARNING Be sure to connect the clipped side to the transmission terminal board F1 F2 of the air conditioner outdoor unit or indoor unit If wrongly connected to power terminals of centralized equipment and the like it may cause fatal injuries by electrical shock to human bodies and failures of equipment CAUTIONS 1 In case of connecting to an indoor unit connect the end of the indoor unit in consideration of not creating sub branching If sub branching is created communication errors may happen Do not need to correspond F1 F2 of the transmission terminal board of the air conditioner to F1 F2 of the Checker TYPE 3 like F1 F1 or F2 F2 respectively Connect the clip attached side of the DII NET connection cable to the transmission terminal board F1 F2 of the air conditioner If sensor connection is needed proceed to th
45. ical cable for control CVS JISC3401 Vinyl insulated vinyl sheathed cylindrical cable VVR JISC3342 600V vinyl cabtyre cable VCT JISC3312 Polyethylene insulated vinyl sheathed cable CPEV See Note Instrumentation cable with mesh and shielding MVVS See Note Note If a shield wire is used be sure to ground either end of the wire Cautions 1 Do not use multiple cored wires with 3 cores or more Use wires with a cross section of 0 75mm 1 25mm Do not make wires packed in control signal wiring Do not make long distance wiring by having signal wires packed with tapes tie laps and the like Wire the signal wires away from power lines to prevent the effects of electric noise Since Daikin s air conditioners and related products will generate much lower electric noises it allows to have a distance of minimum 50mm between the power lines and the control signal wires Attach the accessory clip for the Service Checker TYPE 3 to one end of the above signal wire Note When using the control signal wire connect the clip attached side of the wire to an air conditioner and the other side to the Service Checker TYPE 3 respectively Name of each part RS 232C connector Power supply connector Power switch Serial Connector Operating lamp DAIKIN p senvice cne CKER TYPE m DII NET terminal Parallel connector Sensor connector A personal computer is connected by using RS 232C cable Use RS 232C cable attached to the Ch
46. ig cond disp F2 EX21 DIII NET 1 System 2 VRV K DII Pe 4 16 98 14 07 25 EX21 DIII NET 1 Ope data disp F1 System 1 VAV_PLUS I DIL Tri 4 16 98 14 08 00 CS data output F3 Delete F3 PELE Cancel Esc Place the cursor in the target operation data Operation data display F1 The operation data are displayed Proceed to Trigger condition display F2 In case of operation data recorded by the Trigger recording the setting of the trigger recording at that time is displayed Trigger Condition Display D aikin Industries Ltd DIII NET 1 DIII NET 1 Record time minutes 2 Trigger condition 2 1 Trigger record system one system only System No System2 32KB Free disk area i KB If the free disk area is more than 2 GB values may not be correct 2 2 Trigger condition Close Esc IGNORED IGNORED IGNORED IGNORED IGNORED IGNORED IGNORED IGNORED 5 0 1 Restart_stand bi IGNORED IGNORED 6 0 1 Error_code ERROR IGNORED 70 1 Compressor2 STD IGNORED IGNORED IGKINREN IGMIOBEN 2 0 1 Heating 3 0 1 Cooling 4 0 1 Thermostat_ON CSV data output F3 The data of CSV format possible to be read by commercial integrated software are output Proceed the 5 3 CSV output 51 Chapter 5 Playing of operation data Delete F9 The operation data are deleted Cancel ESC The return to the Main Menu is made 3 The window of the Operation
47. in all the data at intervals of 5 seconds Normally set at intervals of 10 to 20 seconds Set a recording stop method as follows Manual In the window of the Network Map Display continue to Recording record until pressing the Periodical record stop F7 button end method Automatic Recording of operation data ends automatically after arriving at a pre set recording time Input a recording time with a minute unit In the DII NET connection it is possible to set Recording or No recording for every system each outdoor unit Multiple selection is possible By placing the cursor in the System No to press the F12 key Recording or No recording is shifted The left side of system recording is marked O 1 Recording interval Recording system selection Since the Total of expected record file size KB and the Free hard disk area KB are displayed confirm if the free area is enough in recording the data Be careful to note that if the free hard disk area of the personal computer is more than 2 GB values may not be correct 42 Chapter 4 Recording of operation data Set the 4 Setting of sensor input Select the Recording or No recording and also the System when recording When recording further press the Sensor input setting F2 Set the Measurement data item by following the window below Periodic Recording Setting D aikin Industries Ltd DIII NET 1 DIII NET System 1 Sens
48. input the File name and press the Save button J csv i a data_Iu0 cew data_lu02 csv data_lu03 cev Ja data_lud cay data_Iu05 csy data Oulll cev Save jni File name Save as type csv Files cev Cancel 56 Chapter 5 Playing of operation data 4 While outputting CSV the following window is displayed CSV data is being output Notes 1 In the CSV file one file per an air conditioner is output In case of one outdoor unit and eight indoor units one CSV file for the outdoor unit and eight CSV files for the eight indoor units are output respectively If the size of CSV file has become bigger because of being recorded for a long time and resultantly the integrated application software can not read in by one file the file may be automatically divided into multiple files X Estimated time in CSV data processing In the DIT NET connection if one outdoor unit and eight indoor units are periodically recorded at intervals of 5 seconds for 3 8 days the file size of the operation data will be approximately 32MB To output the operation data with CSV data it will take approximately 1 5 hours to store the CSV data in the hard disk The CSV file size for the outdoor unit and the indoor units becomes approximately 29MB and 5MB Also it will take approximately 15 minutes to open the CSV data of the above outdoor units by the Excel integrated application software Since the size of CSV file and proc
49. ner is replaced after making a network map once the detail data for air conditioners will be deviated by reason of managing the detail data for each air conditioner in order of auto address To correct the deviation move the detail data in accordance with the following procedures Auto address and Airnet address are not related to since they are automatically identified To correct the deviation move the detail data in accordance with the following procedures an example of transfer the detail data of In3 to In7 1 Select the In7 by the 1 Airconditioner selection in the window of the Detail data input Detail Data Input Daikin Industries Ltd DIII B2T 1 DIII NET Syst 1 Airconditioner selection 2 Detail data input Save FI Install site name Office Model No feB945 ee pee Ryk List display F2 Centralized address Cancel Esc Auto address Ajimet address 2 Press the List diSplay F2 to display the window of Detail Data List Display Detail Data List Display D aikin Industries Ltd DIII NET 1 DIII NET Tnstal ste Model No Office E VRV K In Ceiling_Mc 1 00 In Ceiling_Mc 1 01 Copy F1 In Ceiling_Mc 1 02 In Ceiling_Mc 1 03 In Ceiling_Mc 1 04 In Ceiling_M 1 05 In Ceiling_Mc 1 06 In Ceiling_Mc 1 07 Cancel Esc In Ceiling_Mc In Ceiling_Mc In Ceiling_Mc In Ceiling Mc 4 b 3 By placing the cursor at the transferring In3 and pres
50. nverting resistance value to temperature value method be sure to use the thermistor Th3 Th4 Connect pipe temperature thermistor Th4 blue HP Connect high pressure sensor HP blue Do not connect HP since HP differs from LP in a converting resistance value to pressure value method OPO Connect low pressure sensor LP red Do not connect LP since LP differs from HP in a converting resistance value to pressure value method om Connect air temperature thermistor for indoor Th1 white To make Th5 valid place the upper switch in Th5 side A and Th5 are not possible to use simultaneously Using optional cable A red connect to measuring instrument To make A valid place the upper switch in A side A and Th5 are not possible to use a simultaneously The conversion of a voltage signal from measuring instrument into current is set by periodical recording in the 4 2 Setting of records of the TYPE 3 software Connect air temperature thermistor for indoor Th4 blue To make Th6 valid Te place the upper switch in Th6 side V and Th6 are not possible to use simultaneously 19 Chapter 2 Connection to air conditioner Using optional cable V blue connect to measuring instrument To make V valid place the upper switch in V side V and Th6 are not possible to use simultaneously The conversion of a voltage signal from measuring instrument into voltage value is set by periodical recording in the 4 2 Setting of records of TY
51. o 1VDC W Standard configuration Part 1 Service Checker TYPE M 2 Cable for VRV system air conditioner for building 3 Serial connector conversion cable Use when connecting Checker TYPE 3 999135T M5 RA cable to the Service Checker TYPE 3 4 RS 232C cable for personal computers D sub 25 pin male D sub 9 pin female straight 5 Bag worm like clip 1 AC adapter Input 220VAC 50Hz Output 9VDC 500mA Outside 999142T Temperature condition 10 to 35 C 2 Battery Ni Cd battery 3 Charger 220VAC input 50 60Hz Complete charging approx 16 hours TYPE 3 Software English 999143T Compatible with English version Windows95 TYPE 3 Instruction 999144T Instruction manual of TYPE 3 software English Manual English E Optional Items Part Use when connecting to a Super Multi or room air conditioners via M5 RA cable 1 999140T PCB connection No need to purchase this cable if customers have TYPE2 Expansion kit 999112T Discharge pipe temperature thermistor 30 to 150 C 1pc Outdoor air distribution pipe temperature thermistor 30 to 70 C 3pcs TYPE 3 Power 220V 1 Sensor kit 1 999107T Indoor air temperature thermistor 10 to 50 C 3pcs High pressure sensor 0 to 30kg cm G 1 set Low pressure sensor 0 to 10kg cm G 1 set 2 ue W Spare parts Part TYPE3 cable for A set of cable for VRV system air conditioners for building VRV system air 9991
52. om a remote controller at hand this ight side in poet ihe window sign Is displayed on each indoor unit The indoor units are not possible to operate other than stop Under Operation Shift Control In case of wiring multiple indoor units to one handy remote controller or connecting an operation shift controller to outdoor units this sign is displayed when selecting an indoor unit impossible to shift operation mode When ending this window press the Cancel ESC button 50 Chapter 4 Recording of operation data Chapter 5 Playing of operation data 5 1 Playing of operation data Procedures Press the Play F2 in the Main Menu to display the window of the Customer Data Selection wm Checker Type 3 Software iaf x Function F Edit E Option 0 Window Ww B oes Data transfer F3 Customer data F4 55 data F5 END F12 Ver1 01 PesFloFsaFi2ky The window of the Customer Data Selection is displayed below Customer Data Selection Customer Customer nam Map name System N Model name Ac Re Record start tme id001 Daikin Industri DIIIL NET 1 System 1 YRY_PLU sil DII Pe 4716 98 11 43 00 id001 Daikin Industri DIII NET 1 System 2 VRV K DIl Pe 4 16 98 11 43 00 id001 Daikin Industri DIII NET 1 System 2 VRV K DII Tri 4 16 98 14 19 40 id001 Daikin Industri DIII NET 1 System 1 AxY10K DII Pe 4 16 98 12 25 20 id002 Ex21 DIII NET 1 System 1 YAY_PLUS I DII Pe 4 16 98 14 07 25 Tr
53. or a room air conditioner to monitor as well as the conventional TYPE 1 and TYPE 2 or by connecting the optional kit of sensors The contents of the Manual are subject to change without notice No part of this publication may be transmitted in any form without the prior permission of the publisher We shall not have any responsibilities and liabilities on the results arising from operating the Service Checker TYPE M The contents of this Manual are valid as of April 25 1998 and they may be modified for improvement without any advance notice Outline of the Manual Firstly read carefully the section of Introduction Then confirm the contents of the packaged items by following the procedures of Confirming of packaged items Then make up a connecting cable for DII NET and prepare for a personal computer by following the procedures of Preparation Install the TYPE 3 software English into the personal computer by following the procedures of Chapter 1 Installing of TYPE 3 software Perform this installing at the time of purchasing the Service Checker TYPE II and every version up of the TYPE 3 software Refer to the 1 2 Deleting of TYPE 3 software when the TYPE 3 software needs to be deleted from the computer 3 Refer to the Chapter 2 Connection to air conditioner on the connecting between an air conditioner and the Service Checker TYPE II and the personal computer 4 Refer to the Chapter 3 St
54. or in Free disk area i Ifthe free disk area is more than 2 GB values may not be correct 4 Measurement data item Set completed F1 Mihi item Tht M Th2 Item Tho M Th3 Item Th Aoo Ma Cancel Esc M HP item HP M LP Item LP EEEn E a Unit CV tem 08 Cow oyf fulsa unt In case of shifting Th5 to A or Th6 to V by using the switch of the Checker TYPE 3 shift at a window before the window of Display of network map otherwise operation data will not be correctly recorded Set the following items Item Description for setting Th3 1 Click with the mouse the Check box at the left of sensor connectors to be used HP 2 Input the Item name for recording data 1 Click with the mouse the Check box at the left of sensor connectors to be used 2 Input the Item name for recording data 3 If the switch of the Checker TYPE 3 is positioned at A or V set further the items located at the right side in the window Select the range of voltage signals with 0 5VDC or 0 1VDC Input a value at O V in the item of 0 V Input a value at full scale 5V or 1V in the item of Full scale Input unit in the item of Unit Unit Example of 0 5V Value at Full scale Value at OV OV 5V Voltage signal V Horizontal axis voltage signals from measuring instrument vertical axis recording values corresponding to voltage signals When completing to se
55. r conditions to start trigger recording the indication of trigger recording is displayed The indication of the button is changed to Trigger inspection end F7 Pressing the button again the trigger record is ended Network Map Display D aikin Industries Ltd DIII NET 1_ DIII NET Up F1 Map mode F3 Display mode F4 Record mode F5 Cancel Esc DownlF2 Period rcd set F6 Period rcd end F Trig rcd set F8 Trig rcd end F9 36 Chapter 4 Recording of operation data 4 1 3 Inputting of detailed data The window of the Detail data input is displayed below Detail Data Input Daikin Industries Ltd DIN NET 1 DIIN NET Syst 1 Airconditioner selection E 2 Detail data input saakt Office Install site name Model Mo Ees Model name Pei O Centralized address Auto address joo eE Aimet address joo sd When pressing the button of the Detail data input F6 after selecting the Map mode F3 in the window of the Network Map Display the window of the Detail data input is displayed to enable to input the detail data of a system pointed with cursor every outdoor unit Use detail data as memos Incase of recording only operation data the detail data input is unnecessary Procedures In the 1 Airconditioner selection select an air conditioner for inputting detail data The order of the in1 in2 is for the order of auto address
56. r a customer with operation data recorded previously press the O K F1 by placing the cursor in the corresponding network map Proceed to the window of the Network Map Display Refer to 4 1 2 Network Map Display In case of being different network maps for DIT NET connected objects different DII NET expansion adapter different PCB connected outdoor units for a customer with operation data recorded previously press the New F2 and proceed to the Access Method Selection window Proceed to In case of changing the name of network map press the Edit map name F3 and proceed to the Access Method Selection window Proceed to When deleting a network map press the Delete customer F9 When returning to the previous stage press the Cancel ESC button 31 Chapter 4 Recording of operation data This is the window of the Access Method Selection Access Method Selection D aikin Industries Ltd_ 1 Network map name DIN NET OK F1 2 Access method DINI NET PCB connection Typical model selection Cancel Esc Sensor input only an 1 Be sure to input the 1 Network map name 2 Select the 2 Access method DII NET Possible to use only DIL NET connection or in combination with Sensor input Possible to use air conditioners conforming to the DII NET in internal and external transmission method Possible to identify and select automatically th
57. sing the Copy F1 button the detail data of the In3 are transferred to the In7 4 Press the Cancel ESC to return to the window of the Detail data input After completing to input press the Cancel ESC to return to the window of the Network map display 38 Chapter 4 Recording of operation data 4 1 4 Displaying of operation data The window of the Operation Data Display is displayed below The operation data for a system are displayed by pressing the button of the Operation Data Display F6 after selecting the Display mode F4 in the window of the Network Map Display One window is displayed per one system Analog data graph display Present value for each data item Uperation Data Display U aikin Industnes Ltd DIN NE 1 1 DIIN NEISsstem 1YH Y_PLUS L_C INY O08 Tata tern ate 7 1 0 1 Ventilation OFF fz 2 0 1 Healing OV 3 0 1 Coolng OFF 4 0 1 Themostat_OM SA OFF R 1 1 Restart_stand b S NFF RNA1 Frrar endelsen 111 7 NA Frrar rna 4 ad R 1 1 Amhent Fenn AF Te i 90 1 Healexchangsr_le 47 1 C 1 100 1 Diszh_pipe_temp 13 0C 11 0 1 Diszh _pipe_temp 13 0 C 120 1 Suction_ppe_ten 47 5 C 13 0 1 DiLtemp NY 47 5C 140 1 0il temp 5TD 47 5C x 4 On reproduce pericd ed data 4 16 98 11 44 20 145 30 o x Carcel Esc Cursor noverrent lst r5 r aj s SNET Screen prt raj 11 44 30 Grapa Cap iT y Med F2 fletn Fo 1 Fowd
58. sors and actuators Neglect this and refer to the Service Manual in detail 4 Press the Cancel ESC to return to the window of the Network Map Display 40 Chapter 4 Recording of operation data 4 2 Setting of recording The method of recording operation data consists of two one is the Periodical recording which records successively for a constant time and another is the Trigger recording which records before and after meeting trigger conditions conditions of digital data ON OFF The TYPE 3 software can set separately the method Sensor input can be set only in the periodical recording Periodical record start Periodical record 4 2 1 4 2 2 Trigger inspection start Meeting trigger conditions Time Trigger record 4 2 3 4 2 1 Setting of periodical recording in case of DIT NET connection and PCB connection The window of the Periodical record setting is displayed by pressing the button of the Periodical record setting F6 after selecting the Recording mode F5 in the the window of the Network Map Display Network Map Display D aikin Industries Ltd DIII NFET 1_ DIII NET Be eee eee Install site o System 2 1 04 0021 05 001 11 06 f 006 Up F1 Menken Display mode F4 Record mode F5 Cancel Esc Period PCd set F6 Period rcd start F7 Trig rcd set F8 Trig inspt start F9 4 Chapter 4 Recording of operation data
59. t the above press the Setting complete F1 to return to the window of the Periodical record setting 43 Chapter 4 Recording of operation data 3 Press the Setting complete F1 in the window of the Periodical recording Setting to return to the Network Map Display 4 When starting the Periodical record press the Periodical record start F7 in the window of the Network Map Display to display the Periodical recording in red at the upper left in the window Also the indication of the button is changed to the Periodical record end F7 Network Map Display Daikin Industries Ltd DIII NET 1 DIII NET S a a a a a a a A 00s fi or a A aA a a A A a oor a a eee aes ee ee ee ee ee E a Up F1 Map mode F3 Display mode F4 Record mode F5 Cancel Esc Dawn FZ Period rcd set F6 Period rcd end F Trig rcd set F8 Trig inspt start F9 When ending manually the Periodical record press the Periodical record end F7 If in the Recording end method of the Automatic is set recording data is automatically ended after pre set recording time 44 Chapter 4 Recording of operation data 4 2 2 Setting of periodical recording in case of sensor input only The window of the Periodical record setting is displayed by pressing the button of the Periodical record setting F6 after selecting the Recording mode F5 in the window of the Network Network Map Display
60. ta transfer The window of the Trigger record setting is displayed by pressing the button of the Trigger record setting F8 after selecting the Recording mode F5 in the window of the Network Map Display Network Map Display D aikin Industries Ltd UI NET 1 DIII NET Up F1 Map mode F3 Display mode F4 Record mye 5 Cancel Esc ovr FZ Period rcd set 6 Period rcd start F7 Trig rcd set F8 Trig inspt start F9 The window of Trigger record setting Trigger Record Setting D aikin Industries Ltd DIII NET 1 DIII NET 1 Red time bef aft tria 20 minutes lf set to a value higher than 60 minutes the record time 5 before trigger setting will be set to 60 minutes pooo o 1 2 1 Trigger record system selection 1 system only System No Expected record file size System 1 Set completed F1 KB If the free disk area is more than 2 GB values may not be corect 2 2 Trigger conditions setting Free disk area Cancel Esc 4 0 1 Thermostat_ON 5 O 1 Restart_stand by 6 0 1 Error_code 7 0 1 Compressor2 STD IGNORED IGNORED IGNOREN IGKINBEN Procedures 1 Set the 1 Record time before and after trigger and the 2 Trigger setting When the trigger conditions are met in the window of the 2 2 Trigger conditions setting set a time by minute unit to determine the recording time before and after trigger If setting 30 minutes
61. td DIN NCT 1 DINI NCT System 2 YNY K fi E 39 doc I Checker Type 2Soft Example f the display of operation data 27 Chapter3 Starting up and ending of TYPE 3 software 3 Also by selecting the End X of the menu of Function F located in the extreme upper left of the window the TYPE 3 software will end at once W Checker Type 3 Software Function F 28 Chapter3 Starting up and ending of TYPE 3 software Chapter 4 Recording of operation data The TYPE 3 software manages data by the hierarchy structure of customer network map operation data Network map Operation data system 1 Mar 23 System 2 Mar 23 System 1 Feb 11 Pe system 1 Apr 2 DII NET for E building A customer PCB EXII kK for E building B customer 4 1 Displaying of operation data 4 1 1 Selecting of customer data and others Procedures Press the Record F1 in the Main menu to display the window of the Customer selection wm Checker Type 3 Software Function F Edit E Option 0 Window w Data transfer F3 Customer data F4 SS data F5 END F12 Ver1 01 Fress F1 to F5 or F12 Key In this window of the Customer selection input customer related data Recording data only without relating to customers is also possible Customer Selection 1 Customer selection Customer ID Customer name Record only F1
62. ts is possible Proceed to the 4 3 Centralized control Update map F8 If the number of air conditioners has changed or PCBs are replaced in the DI NET connection press this button to search the data of network map Notes When pressing the Yes F1 air conditioners on the DII NET are set to standby for restart making the thermostat switched off for several minutes Print screen F9 Press this button to print the screen of network map B Display mode F4 pf Displaymode F4y Joo Display operation data F6 By proceeding to the window of Display operation data system operation data are displayed Proceed to the 4 1 4 Displaying of operation data Note In case of the DIL NET connection after all icons of the system to be seen have become colors other than white display the operation data Start D I data recording F7 Do not press the button since this function is not used Note If pressing this button the indication is changed to End DIdata recording F7 If so press again to return to Start DI data recording F7 Display number of units F8 The number of connected outdoor units and indoor units is displayed Note In the PCB connection the number of units of Super Multi and room air conditioners is not correctly displayed Number of Units Display D aikin Industries Ltd DIII NET 1 DIII NET 235 Chapter 4 Recording of operation data C Recor
63. ts to human bodies or failures of air conditioning systems Utilize fully the Manual with keeping it carefully in a proper place adjacent to the Service Checker TYPE IM Notes on safety Notes in the Manual of which negligence to observe may cause fatal or serious injuries to human bodies are headed WARNING On the other hand notes in the Manual of which negligence to observe may cause failures of the air conditioning systems are headed CAUTION The Service Checker TYPE II has been developed for enhancing customer service capabilities of Daikin s air conditioners It is a personal computer monitored device which is connected to an air conditioner and reads out operation data by temperature sensors pressure sensors several kinds of solenoid valves operating modes etc We have been developing and selling the conventional checkers of TYPE 1 and TYPE 2 Our newly developed Service Checker TYPE II conforms to the DII NET which is widely being applied to internal and external data transmission for Daikin s VRV system air conditioner for building and has come to allow to monitor simultaneously multiple outdoor and indoor units by connecting to a single air conditioner limited to VRV system air conditioners conforming to the DII NET The Service Checker TYPE II is possible to measure six temperature measurement points and two pressure measurement points by PCB Connection connecting to an outdoor unit an indoor unit f
64. y applications you may be running Exit Setup If the destination to be installed is the same place as a folder directory displayed in the window press the icon button displayed in the upper left window If the destination to be installed needs to be changed change by pressing the Directory change button Daikin ServiceChecker Type3 Setup Daikin ServiceChecker Type3 Setup E Daikin ServiceChecker Type3 Setup Begin the installation by clicking the button below a Daikin ServiceChecker Type3 Setup Destination File Click this button to install Daikin ServiceChecker Type3 software to the pela i specified destination directory C Program Files Checker3 checker3 exe Directory E Program Files Checker3 Change Directory Exit Setup 11 Chapter 1 Installing of TYPE 3 software Q If the message is displayed in the picture as shown below press the Yes button to stop installing and delete the old version of the software by following the procedures of the 1 2 Deleting of TYPE 3 software before re installing by starting from the procedures of the above 0 Daikin ServiceChecker Types Setup 2 Daikin ServiceChecker Type3 Setup Destination File C Program Files Checker3 checker3 exe Daikin ServiceChecker Type3 Setup N Setup is about to replace a pre existing file s This may cause loss n of data for an existing applicatio Cancel setup If the following message is displayed the installing is
65. yed select applicable ones Since the Total of expected record file size KB at the right side of 2 1 Trigger record system selection window and the Free hard disk area KB at the bottom of the window are displayed confirm if the free area is enough in recording the data However be careful to note that if the free hard disk area of the personal computer is more than 2 GB values may not be correct Press the Setting complete F1 to return to the Network Map Display 3 When starting the trigger record inspection press the Trigger inspection start F9 in the window of the Network Map Display to display the Trigger inspecting in red at the upper left in the window Also the indication of the button is changed to the Trigger inspection end F9 When trigger conditions are met to start trigger recording the red characters at the upper left in the window are changed to the Trigger recording and also the indication of the button is changed to the Trigger record end F9Q Network Map Display D aikin Industries Ltd DIII NET 1 DIII NET Up F1 Map mode F3 Display mode F4 Record mode F5 Cancel Esc Davn rz Period rcd set F6 Period rcd end F7 Trig rcd set F8 Trig rcd end F9 4 When ending manually the Trigger inspecting or the Trigger recording press the Trigger inspection end F9 button or the Trigger record end F9 button After starting trigger recording and re