WALL MOUNTED TYPE FAN COIL UNIT SERVICE MANUAL

image

Contents

1. DXX RR EE BILLY Bm M A RAN SOR 45004 9 9 9 054 X 21 UXXXXKXXXXI XXX XX OOA 16 9 js Bee http splitoff ru tehn doc html Spare parts list FP 51BWA2 A K EM55000240 FP 51BWA5 A K EM55000300 Wall Mounted Type Fan Coil Unit Service Manual No Name of part Part code Quantity No Name of part Part code Quantity 01252013 30565056 D 1 Wall Mounting Frame 1 18 Display Board 1 01252021 30565026 2 Rear Case 2220245401 1 19 Front Panel 200121505 1 3 Sufer Cooler Assy 1126406 1 4 Evaporator Support 24212091 1 20 Screw Cover 24252016 1 5 Cross Flow Fan 10352017 1 21 Guide Louver 10512157 1 6 Ring of Bearing 26152022 1 22 Wire Clamp 71010003 1 7 Bearing cushion 76512203 1 23 Rear Clamp 26112164 1 rubber base 8 Volute tongue 26112163 1 24 Motor MP24AA 1521210801 1 9 Left Axile Bush 10512037 1 25 Motor Clamp 26112161 1 10 Crank 10582070 1 26 Motor FN20J PG 150120874 1 11 Axile Bush 10542008 1 27 Electric Box Cover 1 20122103 1 12 Swing Louver1 10512156 1 28 Covering Plate2 20122075 1 13 Swing Louver2 10
2. Model FP 51BWA3 A K FP 85BWA3 A K FP 51BWA5 A K FP 85BWA5 A K EM55000240 55000250 Product Code 55001430 55001510 55000300 55000310 m h 450 650 High CFM 265 382 m h 383 560 Air flow volume Medium CFM 225 329 m h 323 490 Low CFM 190 288 Cooling W 1500 2400 Capacity Heating W 2250 3600 Type V Ph Hz 220 240V 50Hz Power system Input W 50 60 m h 0 28 0 38 Water flow volume GPM 1 23 1 67 Water system kPa 37 60 Pressure drop 12 2 19 7 Aluminum fin copper tube Coil Operating pressure MPa lt 1 5MPa lt 1 5MPa Type FN20J PG FN20V PG Motor Capacitor uF 1 1 5 Power output 20 20 Sound pressure level dB A 42 50 Connection Water inlet amp outlet inch 1 2 pipe size Condensing water drain mm 15 6 Outline dimension WxDxH mm 845x180x275 940x200x298 Package dimension WxDxH mm 915x255x355 1010x285x380 Net weight kg 11 13 Gross weight kg 14 17 20 GP 365 290 Loading quantity 40 GP 765 595 40 HQ 850 671 Standard wireless remote controller YB1FA Bee http splitoff ru tehn doc html Wall Mounted Type Fan Coil Unit Service Manual Model FP 85BA2 A D Product Code 55001590 1000 High CFM 588 840 Air flow volume Medium CFM 493 720 Low 423 Cooling 5400 Capacity Heating
3. E x B 08 9 C CH Es ue fore gt Ems gt GREE GREE GREE d Enter Cance d Fan Enter Cancel Niro lode Fan pam Function v Timer On Off S Aa v Timer On Off Function v Timer On Off When the Quiet Auto Press Function to go Press Enter cancel to Quiet function is to the setting status deactivate this function activated Fig 25 How to Deactivate the Quiet Auto Quiet Function N NOTE The fan speed is unadjustable when the Quiet function is activated Q When the Auto Quiet function is activated the unit will run into the Quiet status according to the actual indoor ambient temperature and user set temperature In this case the fans speed is adjustable 8 Under the Auto Quiet mode the fan speed can only go down And the Quiet function will quit automatically if the fan speed is adjusted manually The Quiet function is unavailable under the Fan and Dry modes And the default status of the function is Off when the unit is powered on again 5 The Turbo function will be deactivated automatically when the Quiet function is activated 4 13 Debugging When the unit is Off press Function and Timer simultaneously for five seconds to call out the debugging menu after that press Mode to select the desired submenu and then press A or V to set the parameter 4 13 1 Ambien
4. http splitoff ru tehn doc html Wall Mounted Fan Coil Unit Service Manual 1 3 SLEEP SLEEP button Press this button to select Sleep On Sleep Off If power is on Sleep Off is default If the unit is turned off the Sleep function setting will be not retained in memory If Sleep function is on the mark of Sleep will display In this mode the time of timer can be adjusted Under Fan and Auto modes this function is not available 1 4 FAN FAN button Press this button Auto Low Medium High speed can be circularly selected After powered on Auto fan speed is default Under Dehumidify mode Low fan speed is default euet ral Low Medium aq High Note Under the Dry mode the fan speed isn t adjustable low fan speed is default 1 5 CLOCK CLOCK button Press Clock button to set the time of clock When C blinks and displays you can set the time by pressing or button If no button is pressed within 10 seconds the remote will revert back to the normal display Press again to accept the setting If it is set the first time 12 00 is the initial value Note If mark displays on the LCD it means it is the time of clock if not it is the time of timer 1 6 LIGHT LIGHT button Press this button to select LIGHT On Off in the displayer When the LIGHT On is set the mark 2 will be displayed and the indicator light in the displayer will be on When the LIGHT Off is set th
5. Enter Cdncel Fan Mode 1 1 1 1 Mh Timer On off Function v Timer On Off When the Turbo function is not activated Press Function to go to the setting status Press Enter cancel to active the Turbo function See Fig 17 for how to deactivate the Turbo function fw 28 5 Rp 2B I Ez 5 Eni GREE H G GREE Enter Cancel Fan Mode Enter Cincel Fan Mode Enter cancel Fan Mode 1 Function v Time On Off Au v Timer On Off Function Timer On Off AA NOTE When the Turbo function is activated Press Function to go to the setting status Press Enter cancel to deactivate the Turbo function Fig 17 How to Deactivate the Turbo Function The Turbo function is deactivated when the unit is powered on after power failure Under the Dry and Fan modes the Turbo function is unavailable and the symbol no will not appear 8 The Turbo function will be deactivated automatically when the Quiet function is activated The Turbo function will be deactivated automatically when the Fan speed is adjusted 4 9 Save 1 S
6. GREE O a Enter Cance Fan Mode Enter Cance Fan Mode Enter capa A Fan Mode b Function v Timer On Off meli Timer On Off Function v Timer On Off When the Blow function Press Function to go Press Enter cancel is not activated to the setting status to activate the Blow function Fig 22 How to Activate the Blow Function See Fig 23 for how to deactivate the Blow function gt a CU cB Ev x GREE d a wt 3 Enter Cancel Fan Mode i MA G GREE Enter Cancel Fan Mode didi Y Rer SE v Timer On Off Function v Timer On Off When the Blow Press Function to go Press Enter cancel function is activated to the setting status to deactivate the Blow function Fig 23 How to Deactivate the Blow Function 4 12 Quiet There are two options for this function Quiet and Auto Quiet How to activate the Quiet Auto Quiet function Press the Function key to go to the setting state with the symbol or flashing then press A or Y to switch between Quiet and Auto Quiet after that press the Enter Cancel key to make a confirmation How to deactivate the Quiet Auto Quiet func
7. FP 51BA5 B D 2700 EM55001900 550 FP 68BA5 B D 3600 EM55001910 680 FP 85BA5 B D 4200 EM55001920 850 FP 102BA5 B D 5400 EM55001930 1000 2 NOMENCLATURE OF THE UNIT FP a 1 2 3 4 4 6 NO Description Options 1 Fan coil 2 Air flow volume Numberx10 3 Structure type mounted B Wall mounted with water valve BW 4 Front panel code One letter number 5 Design Sequence Arranged by A B C 6 Power code K 220 240V 50Hz D 208 230V 60Hz 3 FUNCTION Function Fan Coil Unit Service Manual for Evaluation Cooling YES Heating YES Dehumidify YES Air Flow YES Auto Swing YES Sleep and Auto YES With Access Control System Optional Central Control Optional For Comfortable Wired Controller Optional Air Conditioning Long Distance Control Optional Timer YES Energy Saving YES Anti Cold Air YES Anti Heat Air YES Waste Heat Blow YES Memory YES Self Diagnosis YES Alarming YES Bce n http splitoff ru tehn doc html Wall Mounted Type Fan Coil Unit Service Manual 4 PRODUCT DATA FP 34BA2 A K FP 51BA2 A K FP 68BA2 A K FP 85BA2 A K FP 34BA3 A K FP 51BA3 A K FP 68BA3 A K FP 85BA3 A K Model FP 34BA4 A K FP 51BA4 A K FP 68BA4 A K FP 85BA4 A K FP 34BA5 A K FP 51BA5 A K FP 68BA5 A K FP 85BA5 A K FP 34BB3 A K FP 51BB3A K FP 68BB3A K FP 85BB3 A K EM55000200 EM550
8. 8500 V Ph Hz 208 230V 60Hz Power system Input 70 m h 0 88 Water flow volume GPM 3 87 Water system kPa 63 Pressure drop Ft WG 20 7 Type Aluminum fin copper tube Coil Operating pressure lt 1 5 FN20W PG Motor Capacitor 1 5 Power output 20 Sound pressure level 49 Water inlet amp outlet 1 2 Connection pipe size Condensing water drain 15 6 Outline dimension WxDxH 940x200x298 Package dimension WxDxH 1010x285x380 Net weight 13 Gross weight 17 290 Loading quantity Standard wireless remote controller http splitoff ru tehn doc html Wall Mounted Fan Coil Unit Service Manual FP 34BA2 B D FP 51BA2 B D FP 68BA2 B D FP 85BA2 B D FP 102BA2 B D Model FP 34BA3 B D FP 51BA3 B D FP 68BA3 B D FP 85BA3 B D FP 102BA3 B D FP 34BA5 B D FP 51BA5 B D FP 68BA5 B D FP 85BA5 B D FP 102BA5 B D EM55000320 EM55000330 EM55000340 EM55000350 EM55000360 Code EM55001760 EM55001800 EM55001770 EM55001780 EM55001790 EM55001890 EM55001900 EM55001910 EM55001920 EM55001930 igh m h 360 550 680 850 1000 i d CFM 212 324 400 500 588 m h 322 413 591 708 840 Air flow volume Medium CFM 189 242 347 416 493 7 m h 282 367 532 616 720 ow CF
9. 1 20012199S 20012202 9 9 3 Evaporator Assy 01126406 1 20 Screw Cover 24252016 1 4 Evaporator Support 24212091 1 21 Guide Louver 10512157 1 5 Cross Flow Fan 10352017 1 22 Wire Clamp 71010003 1 6 Ring of Bearing 26152022 1 23 Rear Clamp 26112164 1 7 Bearing cushion 76512203 1 24 Motor MP24AA 1521210801 1 rubber base 8 Volute tongue 26112163 1 25 Motor Clamp 26112161 1 9 Left Axile Bush 10512037 1 26 Motor FN20J PG 150120874 1 10 Crank 10582070 1 27 Electric Box Cover 1 20122103 1 11 Axile Bush 10542008 1 28 Covering Plate2 20122075 1 12 Swing Louver1 10512156 1 29 Terminal Board 42010262 1 13 Swing Louver2 10512155 1 30 Electric Box 20112082 1 14 Front Case 20012123 1 31 Main PCB Z5P251A 30225043 1 4202300117 15 Filter 1112220401 2 C 16 aer E 30510041 1 20192265 22432230 17 Decorate Piece 2019223601 1 33 43110233 1 20192247 27219900310 34 Power Cable 400220112 1 Note QD is part of FP 34BA2 A K is part of FP 51BA2 A K is part of FP 34BA3 A K is part of FP 51BA3 A K is part of FP 34BA4 A K is part of FP 51BA4 A K is part of FP 34BA5 A K 8 is part of FP 51BA5 A K is part of FP 34BB3 A K 0 is part of FP 51BB3 A K http splitoff ru tehn doc html Wall Mounted Type a Fan Coil Unit Service Manual Model FP 51BWA2 A K EM55000240 FP 51BWA5 A K EM55000300 Exploded Views
10. 68 5 55001650 FP 85 EM55001750 exploded views 3l http splitoff ru tehn doc html Wall Mounted Type Fan Coil Unit Service Manual Spare parts list FP 68BA3 B K EM55001750 FP 68BA2 B K EM55001690 FP 68BA5 B K EM55001650 No Name of part Part code Quantity 20012260 1 Front Panel Assy 20012283 1 20012286 3 2 Filter Sub Assy 1112208901 2 3 Front Case 2690603901 1 4 Screw Cover 24252016 1 5 Rubber Plug Water Tray 76712012 1 6 Surface Cooler Assy 01126656 1 7 Cross Flow Fan 10352019 1 8 Ring of Bearing 76512051 1 9 Rear Case assy 1231221408 1 10 Wall Mounting Frame 01252218 1 11 Volute tongue 26112238 1 12 Air Louver 1 10512116 1 13 Axile Bush 10542036 1 14 Left Axile Bush 10512037 1 15 Guide Louver 10512115 1 16 Crank 10582070 1 17 Stepping Motor 15012086 1 18 Swing Louver2 10512117 1 19 Drainage hose 05230014 1 20 Rear Clamp 26112164 1 21 Motor 1570643301 1 22 Motor Press Plate 26112494 1 23 Electric Box 20112108 1 24 Capacitor 33010020 1 25 Installation Supporting Frame 01806867 1 26 Terminal Board 42010262 1 27 Electric Box Cover 1 20122154 1 28 Shield cover of Electric Box 01592092 1 29 Electric Box Cover 2 20112081 1 30 Electric Box Assy 01397320 1 31 Evaporator Angular 24212100 1 32 Pipe Conn
11. or Y to adjust the time after that press the Timer to finish this setting Finally the time displayed is for the unit On while time for unit Off will not be displayed How to set timer for unit Off When the unit is press the Timer key with the symbol orF flashing and then press A or V to set the time when to stop the unit after that press the Timer key again to finish this setting Before pressing the Timer key to finish the setting for unit Off it is also available to go to set when to start the unit by pressing the Mode key with the symbol flashing and then press A or V to adjust the timer after that press the Timer key again to finish the setting Finally the time displayed is for the unit Off while time for unit On will not be displayed How to cancel the timer When the timer is set press Timer to cancel it and then no time will be displayed on the LCD http splitoff ru tehn doc html E Wall Mounted Type Fan Coil Unit Service Manual See Fig 12 for how to set the timer under the On status of the unit ge cH as Cc T aut Gare Q GREE gt GGI A Fan Mode Enter Cancel A 7 Enter Cancel A Fan Mode gal CU Enter Cance
12. 2 Ex 59 GREE e GREE GREE c Enter Cance Fan Mode Enter Cancel jd Fan Enter Fan Function v Timer On off NT v Timer On Off Function v Timer On Off When the Save Press Function to go Press Enter cancel to function is activated to the setting status deactivate the Save function Fig 19 How to Deactivate the Save Function NOTE QD The Sleep function will be deactivated when the Save function is activated 2 The Save function will be memorized when the unit is powered on again after power failure The initial lower temperature limit under the Save cooling mode is 16 C and the initial upper temperature limit is 30 C under the Save heating mode When the Save function is activated if the set temperature under each mode is higher than the corresponding temperature limit for energy saving then the set temperature will forcibly go to the temperature limit http splitoff ru tehn doc html E Wall Mounted Type Fan Coil Unit Service Manual 4 10 E Heater E heater Function Under the Heat mode the heating efficiency can be improved greatly by activating the auxiliary electric heater How to active the E heater function Under the Heat mode press the Function key to go to the setting state with the symbol Eexe flashing after that press Enter Cance
13. to go to the setting state of the sleep function with the symbol amp flashing after that and then press Enter Cancel to make a confirmation and the symbol will disappear See Fig 14 for how to activate the Sleep function x xx 18 28 d 28 ms Rem sj ee GREE O GREE Enter C A Fa Q T A Fan Mode ier um NI Fan Function Timer On Off an Timer On Off Function v Timer On Off When the Sleep function Press Function to go to Press Enter cancel to is not activated the setting status activate the Sleep function Fig 14 How to Activate the Sleep Function See Fig 15 for how to deactivate the Sleep function x oct gt ea mi 28 foo ue fees fuer uer gt G GREE Enter Cancel d A Fan Mode m z 8 P T 8 gt 8 Function v Timer On Off Ag v Timer On Off Function Timer On Off When the Sleep function Press Function to go to Press Enter cancel to is activated the setting sta
14. EM55000340 FP 85BA2 B D EM55000350 FP 102BA2 B D EM55000360 FP 68BA3 B D EM55001770 FP 85BA3 B D EM55001780 FP 102BA3 B D EM55001790 FP 68BA5 B D EM55001910 FP 85BA5 B D EM55001920 FP 102BA5 B D EM55001930 Exploded Views Bee http splitoff ru tehn doc html Spare parts List Wall Mounted Type Fan Coil Unit Service Manual FP 68BA2 B D EM55000340 FP 85BA2 B D EM55000350 FP 102BA2 B D EM55000360 FP 68BA3 B D EM55001770 FP 85BA3 B D EM55001780 FP 102BA3 B D EM55001790 FP 68BA5 B D EM55001910 FP 85BA5 B D EM55001920 FP 102BA5 B D EM55001930 No Name of part Part code Quantity 2001216801 VG 1 Front Panel Assy 20012260 X 1 20012286 DOQ 2 Filter Sub Assy 1112208901 2 3 Front Case 200122615 0 1 200122715 4 Screw Cover 24252016 1 5 Display Board 30565039 0009090 1 30565038 DOQ 6 Rubber Plug Water Tray 76712012 1 01126648 D 01126649 01126405 3 7 Surface Cooler Sub Assy 01126649 1 01126405 01156558 DOQ 8 Cross Flow Fan 10352019 1 9 Ring of Bearing 26152022 1 10 Rear Case assy 1231221408 1 11 Wall Mounting Frame 01252218 1 12 Helicoid tongue 26112238 1 13 Air Louver 1 10512116 1 14 Axile Bush 10542036 1 15 Left Axile Bush 10512037 1 16 Guide Louver 10512115 1 17 Crank 10582070 1 18 St
15. FP 68BB3 A K Q is part of FP 85BB3 A K http splitoff ru tehn doc html Wall Mounted Type a Fan Coil Unit Service Manual Model FP 85BWA2 A K EM55000250 FP 85BWA5 A K EM55000310 Exploded Views Bee http splitoff ru tehn doc html Spare parts list FP 85BWA2 A K 55000250 FP 85BWAS A K EM55000310 Wall Mounted Type Fan Coil Unit Service Manual Shield cover of No Name of part Part code Quantity No Name of part Part code Quantity 20012283 D 1 Front Panel Assy 20012286 1 18 Stepping Motor 15012086 1 Filter Sub Assy 1112208901 2 19 Air Louver 2 10512117 1 Front Case 20012250 1 20 Drainage hose 05230014 1 Screw Cover 24252016 1 21 Pipe Clamp 26112164 1 30565039 15012113 5 Display Board 30565038 1 22 Fan Motor 15012116 1 6 Rubber Ping 76712012 1 23 Motor Press Plate 26112178 1 Water Tray Evaporator Assy 24212100 1 24 Electric Box 20112108 1 Cross Flow Fan 10352019 1 25 Main Board 30225045 1 Ring of Bearing 26152022 1 26 Transformer 43110237 1 10 Rear Case Assy 12312214 1 27 Terminal Board 42010268 1 11 Wall Mounting Frame 01252218 1 28 Electric Box Cover1 20122128 1 12 Helicoid tongue 26112238 1 29 01592092 1 Electric Box 13 Air Louver 1 10512116 1 30 Electric Box Cover2 20112081 1 14 Axile Bush 1
16. Unit Service Manual Spare parts list FP 51BA3 B K EM55001 730 FP 51BA2 B K EM55001700 FP 51BA5 B K EM55001660 No Name of part Part code Quantity 1 Wall Mounting Frame 01252021 1 2 Rear Case 2220245401 1 3 Surface Cooler Assy 01127669 1 4 Evaporator Support 24212091 1 5 Cross Flow Fan 10352017 1 6 Ring of Bearing 76512051 1 7 Bearing cushion rubber base 76512203 1 8 Volute Tongue 26112163 1 9 Left Axile Bush 10512037 1 10 Crank 10582070 1 11 Axile Bush 10542036 1 12 Swing Louver1 10512156 1 13 Swing Louver2 10512155 1 14 Front Case 2001212301 1 15 Filter Assy 1112220401 2 16 Decorate Piece pho A d 1 20012122 17 Front Panel 20012150 1 20012199 18 Guide Louver 10512157 1 19 Screw Cover 24252016 1 20 Wire Clamp 71010003 1 21 Rear Clamp 26112164 1 22 Stepping Motor 1521212901 1 23 Motor Clamp 26112161 1 24 Motor 15706434 1 25 Electric Box Cover 1 20122103 1 26 Electric Box Cover 2 20122075 1 27 Terminal Board 42010262 1 28 Installation Supporting Frame 01806868 1 29 Capacitor 33010089 1 30 Electric Box 01396952 1 Notes only is part ofFP 51BA3 B K only is part of FP 51BA2 B K only is part of FP 51BA5 B K http splitoff ru tehn doc html E Wall Mounted Type Fan Coil Unit Service Manual Model FP 68BA3 B K EM55001750 FP 68BA2 B K EM55001690
17. any button the mark gg will blink for three times but the air conditioner has no despondence If unlocked the mark will disappear Switch between Fahrenheit and Centigrade When unit is under Off state press MODE and button simultaneously to switch between C and F 5 CHANGING BATTERIES AND NOTICES Slightly to press the place with along the arrowhead direction to push the back cover of wireless remote control As show in figure Take out the old batteries As show in figure S Insert two new AAA1 5V dry batteries and pay attention to the polarity As show in figure Attach the back cover of wireless remote control As show in figure NOTE e When changing the batteries do not use the old or different batteries otherwise it can cause the malfunction of the wireless remote control e f the wireless remote control will not be used for a long time please take them out and don t let the leakage liquid damage the wireless remote control e The operation should be in its receiving range e t should be placed at where is 1m away from the TV set or stereo sound sets e f the wireless remote control can not operate normally please take them out after 30s later and reinsert if they cannot normally run please change them Sketch map for e leakage liquid damage the wireless remote control changing batteries http splitoff ru tehn doc html Wall Moun
18. enne nnn nennen nnn nnn nnn nnn nnn 30 CAD INFINE zESI i 31 MAINTENANCE 34 1 TROUBLESHOOTING baa so coa do a aca Eno ninos Rak es acad 34 2 MAINTENANCE 1 5 nnn nnn anna nnn nnns 35 http splitoff ru tehn doc html E Fan Coil Unit Service Manual PRODUCT 1 PRODUCT Wall Mounted Type Fan Coil Unit Service Manual PRODUCT 1 MODELS LIST Model Name uM o Product Code po Greg Remarks FP 34BA2 A K 2100 EM55000200 360 FP 51BA2 A K 2700 EM55000210 550 FP 68BA2 A K 3600 EM55000220 680 FP 85BA2 A K 4200 EM55000230 850 FP 51BWA2 A K 1500 EM55000240 450 FP 85BWA2 A K 2500 EM55000250 650 FP 34BA2 B K 2300 EM55001710 360 FP 51BA2 B K 2900 EM55001700 550 FP 68BA2 B K 3800 EM55001690 680 FP 85BA2 B K 4800 EM55001680 850 FP 34BA3 A K 2100 EM55001130 360 FP 51BA3 A K 2700 EM55001210 550 FP 68BA3 A K 3600 EM55001290 680 FP 85BA3 A K 4200 EM55001360 850 FP 34BA3 B K 2300 EM55001720 360 FP 51BA3 B K 2900 EM55001730 550 _ FP 68BA3 B K 3800 EM55001750 680 85 4800 55001740 850 FP 51BWA3 A K 1500 EM55001430 450 220 240V FP 85BWA3 A K 2400 EM55001510 650 50Hz FP 34BB3 A K 2100 EM55001180 360 FP 51BB3 A K
19. five seconds to call 5 7 out the debugging menu after that press Mode to select the desired submenu and press A V TR to set the parameter finally press Enter Cancel to save the setting and quit the setting status Anti Cold Hot Air r inaly p g and q g 4 6 Mode Under the Off status of the unit press Mode and Y simultaneously for five seconds to switch the Celsius scale and Fahrenheit scale 3 Installation Instructions f Fig 4 Installation of the Wired Controller No Name 1 2 3 4 5 Installation Box Base Plate Screw M4X25 Front Panel Screw ST2 2X6 5 Fig 4 presents simply how to install the wired controller and please pay special attention to the following instructions 1 Please cut off the power supply for all buried power cords in the installation hole and the whole installation must be done without any live part 2 Pull out the four core twisted pairs in the installation hole and let it go through the rectangular hole on the base plate of the wired controller 3 Fix the base plate on the wall with screws M4X25 4 Let the four core twisted pairs go through the slot of the wired control and then fix the front panel and base plate together 5 Fasten the front panel and base plate with screws ST2 2X6 5 NNOTE Pay special attention to the electric wiring to prevent that the air conditioner goes out of control owi
20. 00210 55000220 55000230 55001130 55001210 55001290 55001360 Product Code 55001140 55001220 55001300 55001370 55000260 55000270 55000280 55000290 55001180 55001260 55001340 55001410 m h 360 550 680 850 High CFM 212 324 400 500 m h 322 413 591 708 Air flow volume Medium CFM 189 242 347 416 m h 282 367 532 616 Low CFM 166 215 312 362 Cooling 2100 2700 3600 4200 Capacity Heating Ww 3150 4050 5400 6300 Power Type V Ph Hz 220 240V 50Hz system Input Ww 50 50 60 60 m h 0 4 0 45 0 6 0 7 Water flow volume Water GPM 1 76 1 98 2 64 3 08 system kPa 13 24 44 45 Pressure drop Ft WG 4 3 7 9 14 5 14 8 Type Aluminum fin copper tube Coil Operating pressure MPa lt 1 5MPa lt 1 5MPa lt 1 5MPa lt 1 5MPa Type FN20J PG FN20V PG Motor Capacitor uF 1 1 1 5 1 5 Power output 20 Sound pressure level dB A 35 40 43 48 Connection Water inlet amp outlet inch 1 2 pipe size Condensing water drain mm 15 6 Outline dimension WxDxH mm 845x180x275 940x200x298 Package dimension WxDxH mm 915x255x355 1010x285x380 Net weight kg 11 13 Gross weight kg 14 17 20 GP 365 290 Loading quantity 40 GP 765 595 40 HQ 850 671 Standard wireless remote controller YB1FA Bee http splitoff ru tehn doc html Wall Mounted Type Fan Coil Unit Service Manual FP 51BWA2 A K FP 85BWA2 A K
21. 0112081 1 30 Electric Box Assy 01397320 1 31 Evaporator Angular 24212100 1 32 Pipe Connection Assembly 06649591 2 33 Blow Molding Drainage Pipe 05230022 1 Notes QD only is part of FP 85BA3 B K only is part of FP 85BA2 B K 3 only is part of FP 85BA5 B K http splitoff ru tehn doc html Wall Mounted Type a Fan Coil Unit Service Manual Model FP 51BWA3 A K EM55001430 exploded views Bee http splitoff ru tehn doc html Spare parts List FP 51BWA3 A K EM55001430 Wall Mounted Type Fan Coil Unit Service Manual No Name of part Part code Quantity 1 Wall Mounting Frame 01252021 1 2 Rear Case 2220245401 1 3 Sufer Cooler Assy 01126407 1 4 Evaporator Support 24212091 1 5 Cross Flow Fan 10454101 1 6 Ring of Bearing 26152022 1 7 Bearing cushion rubber base 76512203 1 8 Volute tongue 26112163 1 9 Left Axile Bush 10512037 1 10 10582070 1 11 Axile Bush 10542036 1 12 Swing Louver1 10512156 1 13 Swing Louver2 10512155 1 14 Front Case 26906038 1 15 Filter 1112220401 2 16 Remote Control YB1FA 305100413 1 17 Decorate Piece 22432230 1 18 Display Board D5183Z 30565007 1 19 Front Panel 20012123 1 20 Screw Cover 24252016 1 21 Guide Louver 10512157 1 22 Wire
22. 0542008 1 31 Tube Sensor 390000592 1 15 Left Axile Bush 10512037 1 32 Ambient Temperature 390000451 1 Sensor 16 Guide Louver 10512115 1 33 Remote Controller 30510041 1 17 crank 10582070 1 34 Power Cord 400220112 1 Note D is part of FP 85BWA2 A K only is part of FP B5BWA5 A K only http splitoff ru tehn doc html Wall Mounted a Fan Coil Unit Service Manual Model FP 34BA2 B D EM55000320 FP 51BA2 B D EM55000330 FP 34BA3 B D EM55001760 FP 51BA3 B D EM55001800 FP 34BA5 B D EM55001890 FP 51BA5 B D EM55001900 Exploded Views Bee http splitoff ru tehn doc html Spare parts list Wall Mounted Type Fan Coil Unit Service Manual FP 34BA2 B D EM55000320 FP 51BA2 B D EM55000330 FP 34BA3 B D EM55001760 FP 51BA3 B D EM55001800 FP 34BA5 B D EM55001890 FP 51BA5 B D EMS55001 900 No Name of part Part code Quantity 01252013 02900 1 Wall Mounting Frame 1 IR 01252021 2 Rear Case 2220245401 1 3 Sufer Cool
23. 13 y It indicates the current fan speed It indicates the memory function is activated that is the unit will back to the previous set status after 14 MEMORY i powered on again 15 It indicates the turbo status 16 It lashes animatedly when the unit is started and the ambient temperature is displayed 17 It indicates the ambient temperature set temperature 18 It indicates the energy saving status 19 It indicates that the auxiliary electric heater can be activated 20 It indicates the blow function is activated 21 999 pie It indicates the timer status 22 QUIET It indicates the quiet operation status including two statuses Quiet and Auto Quiet Note Symbols MASTER and CO2 will not displayed on the LCD of the wired controlled XK26 2 Press Keys 2 1 Name of Press Keys 1 2 3 4 Enter LL d Function v Timer On Off 2 2 Introduction to the Functions of the Press Keys Table 2 Introduction to the Functions of the Press Keys No Press Bottoms Function Description 1 Enter Cancel It is used to select the desired function or cancel the selected function 1 It is used to adjust the running temperature of the indoor unit among16 30 C 2 A 2 It is used to adjust the temperature under the energy saving condition among16 30 C 3 It is used to adjust the timer among 0 5 24 hours 6 v 4 It is used to switch between the mode
24. 2700 EM55001260 550 FP 68BB3 A K 3600 EM55001340 680 FP 85BB3 A K 4200 EM55001410 850 FP 34BA4 A K 2100 EM55001140 360 FP 51BA4 A K 2700 EM55001220 550 FP 68BA4 A K 3600 EM55001300 680 FP 85BA4 A K 4200 EM55001370 850 FP 34BA5 A K 2100 EM55000260 360 FP 51BA5A K 2700 EM55000270 550 FP 68BA5 A K 3600 EM55000280 680 FP 85BA5 A K 4200 EM55000290 850 FP 51BWA5 A K 1500 EM55000300 450 FP 85BWAB A K 2500 EM55000310 650 FP 34BA5 B K 2300 EM55001670 360 51 5 2900 EM55001660 550 FP 68BA5 B K 3800 EM55001650 680 FP 85BA5 B K 4800 EM55001640 850 Bee http splitoff ru tehn doc html Wall Mounted Fan Coil Unit Service Manual FP 85BA2 A D 5400 55001590 1000 FP 34BA2 B D 2100 EM55000320 360 FP 51BA2 B D 2700 55000330 550 208 230V FP 68BA2 B D 3600 EM55000340 680 60Hz FP 85BA2 B D 4200 55000350 850 FP 102BA2 B D 5400 55000360 1000 FP 34BA3 B D 2100 55001760 360 FP 51BA3 B D 2700 EM55001800 550 FP 68BA3 B D 3600 EM55001770 680 209 n me 60Hz I FP 85BA3 B D 4200 EM55001780 850 FP 102BA3 B D 5400 55001790 1000 E FP 34BA5 B D 2100 EM55001890 360 _
25. 510 EM55001670 EM55001660 EM55001650 EM55001640 nee m h 360 550 680 850 450 650 1 3 CFM 212 324 400 500 265 383 mh 322 413 591 708 383 560 Air flow volume Medium CFM 189 243 348 417 225 330 m h 282 367 532 616 328 490 ow CFM 166 216 313 363 193 288 Cooling 2300 2900 3800 4800 1500 2400 Capacity Heating 4050 4850 6000 6900 2250 3600 V Ph Hz 220 240V 50Hz system Input 30 30 40 60 50 60 Water flow 0 43 0 49 0 78 0 9 0 28 0 38 Water volume GPM 1 89 2 16 3 43 3 96 1 23 1 67 system pressure kPa 19 23 49 55 37 60 drop FtWG 6 4 7 7 16 4 18 4 12 2 19 7 Type Aluminum fin copper tube Coil i Operating MPa lt 1 6MPa pressure Type FN6B FN9A FN13G FN23A FN20J PG FN20V PG Motor Capacitor uF 1 1 5 1 1 5 w 6 9 13 22 20 20 output Sound pressure level dB A 35 40 43 48 42 50 Water inlet Connection amp outlet inch 1 2 pipe size Condensing mis 15 6 water drain oo mm 845x180x275 940x200x298 845x180x275 940x200x298 Package dimension mm 915x255x355 1010 285 380 915x255x355 1010 285 380 WxDxH Net weight kg 8 8 10 8 11 13 Gross weight kg 11 8 14 8 14 17 20 GP 365 290 365 290 Loading quantity 40 GP 765 595 765 595 40 HQ 850 671 850 671 Standard wireless remote controller YB1FA X FAN Note 1 The water working temperature is from 7 C 44 6 F to 60 C 140 F 2 The temperature exchange efficiency and enthalpy exchange efficiency are tested under these testing condi
26. 512155 1 29 Terminal Board 42010262 1 14 Front Case 20012123 1 30 Electric Box 20112082 1 15 Filter 1112220401 2 31 Main PCB Z5P251A 30225043 1 16 Remote control 30510041 1 32 Jumping Connector 4202300129 1 YB1FA 20192265 D 33 Transformer 48X26G 43110233 1 17 Decorate Piece 1 20192247 Q 34 Power Cable 400220112 1 Note D is part of FP 51BWA2 A K only 2 is part of FP 51BWA5 A K only http splitoff ru tehn doc html Wall Mounted E Fan Coil Unit Service Manual Model FP 68BA2 A K 55000220 FP 85BA2 A K 55000230 68 EM55001290 85 55001360 68 4 55001300 85 4 55001370 68 5 55000280 FP 85BA5 A K 55000290 FP 68BB3 A K 55001340 FP 85BB3 A K EM55001410 FP 85BA2 A D EM55001590 Exploded Views Bee http splitoff ru tehn doc html Spare parts list Wall Mounted Type Fan Coil Unit Service Manual FP 68BA2 A K EM55000220 FP 85BA2 A K EM55000230 FP 68BA3 A K EM55001290 FP 85BA3 A K EM55001360 FP 68BA4 A K EM55001300 FP 85BA4 A K EM55001370 FP 68BA5 A K EM55000280 FP 85BA5 A K 55000290 FP 68BB3 A K EM55001 340 FP 85BB3 A K EM55001410 FP 85BA2 A D EM55001590 N
27. Clamp 22432230 1 23 Rear Clamp 26112164 1 24 Motor MP24AA 1521212901 1 25 Motor Clamp 26112161 1 26 Motor FN20J PG 150120874 1 27 Electric Box Cover 1 20122103 1 28 Covering Plate2 20122075 1 29 Terminal Board 42010262 1 30 Electric Box 2011208201 1 31 Main PCB Z5P251A 30225043 1 32 Jumping Connector 4202300127 1 33 Transformer 48X26G 43110233 1 34 Power Cable 400220112 1 35 Loop of electromagnetic valve 43007002 1 36 Electromagnetic valve 43007001 1 http splitoff ru tehn doc html Wall Mounted Type Fan Coil Unit Service Manual Model FP 85BWA3 A K EM55001510 exploded views http splitoff ru tehn doc html Spare parts List FP 85BWA3 A K EM55001510 Wall Mounted Fan Coil Unit Service Manual No Name of part Part code Quantity 1 Front Panel Assy 20012260 1 2 Filter Sub Assy 1112208901 2 3 Front Case 26906039 1 4 Screw Cover 24252016 3 5 Display Board 30565038 1 6 Rubber Plug Water Tray 76712012 1 7 Surface Cooler Assy 01126404 1 8 Cross Flow Fan 10454102 1 9 Ring of Bearing 26152022 1 10 Rear Case assy 01516005 1 11 Wall Mounting Frame 01252218 1 12 Helicoid Tongue 26112238 1 13 Air Louver 1 10512116 1 14 Axile Bush 10542036 1 15 Left Axile Bush 10512037 1 16 Guid
28. M 166 215 312 362 423 Cooling Ww 2100 2700 3600 4200 5400 Capacity Heating Ww 3150 4050 5400 6300 8500 Power Type V Ph Hz 208 230V 60Hz system Input Ww 50 60 70 Water flow m h 0 4 0 45 0 64 0 78 0 88 Water volume GPM 1 76 1 98 2 82 3 43 3 87 system kPa 13 24 44 45 63 Pressure drop Ft WG 4 3 7 9 14 5 14 8 20 7 Type Aluminum fin copper tube Coil Operating MPa lt 1 6MPa pressure Type FN20X PG FN20W PG Motor Capacitor uF 1 1 5 Power output 20 Sound pressure level dB A 35 40 43 48 49 Water inlet Connection amp outlet nes in pipe size Condensing 156 water drain Outline dimension WxDxH mm 845x180x275 940x200x298 Package dimension WxDxH mm 915x255x355 1010x285x380 Net weight kg 11 13 Gross weight kg 14 17 20 GP 365 290 Loading quantity 40 GP 765 595 40 HQ 850 671 Standard wireless remote controller YB1FA X FAN Bee http splitoff ru tehn doc html Wall Mounted Fan Coil Unit Service Manual FP 34BA2 B K FP 51BA2 B K FP 68BA2 B K FP 85BA2 B K Model FP 34BA3 B K FP 51BA3 B K FP 68BA3 B K FP 85BA3 B K dro Rer ird d FP 34BA5 B K FP 51BA5 B K FP 68BA5 B K FP 85BA5 B K EM55001710 EM55001700 EM55001690 EM55001680 Code EM55001720 EM55001730 EM55001750 EM55001740 EM55001430 EM55001
29. O GREE Change for Life WALL MOUNTED TYPE FAN COIL gt gt UNIT SERVICE MANUAL 4 GC201208 1 GREE ELECTRIC APPLIANCES INC OF ZHUHAI http splitoff ru tehn doc html CONTENTS PRODUCT EE 2 1 amp LIST 2 2 NOMENCLATURE OF THE UNIT nace 3 we PT 3 4 PRODUCT DATA m E 4 CONTROL 10 1 WIRELESS REMOTE CONTROLLER nnn nnn nnn nnn nnns nnn 10 2 OPERATION OF WIRELESS REMOTE 11 3 OPERATION OF WIRELESS REMOTE nennen 12 4 OPERATION OF WIRELESS REMOTE 13 5 CHANGING BATTERIES AND enhn nnn nnne nnn nnne 13 6 WIRED CONTROLLER OPERATION 14 INSTALLATION 29 1 INSTALLATION THE 29 2 INSTALLATION DIMENSION DIAGRAM cesses enne
30. Off When the E heater Press Function to go to Press Enter cancel to function is activated the setting status dectivate the E Heater function Fig 21 How to Deactivate the E heater Function N NOTE D The E heater function is unavailable under the Cool Dry or Fan mode and the symbol EHEATER will not be displayed on the LCD under those modes 2 When the unit is switched to the Heat mode the default status of the E heater function is On 4 11 Blow Blow Function It is intended to dry the moisture inside the evaporator after the unit is turned on to prevent mould growing there How to activate the Blow function Under the Cool and Dry mode when the Blow function is not activated press the Function key to go to the setting state with the symbol flashing and then press the key Enter Cancel to make a confirmation How to deactivate the Blow function When the unit is On and the Blow function is activated press Function function to go to the setting state with the symbol flashing and then press the Enter Cancel key to deactivate this function http splitoff ru tehn doc html Wall Mounted a Fan Coil Unit Service Manual See Fig 22 for how to activate the Blow function Zl CN 28
31. Off Function On Off When the Swing Press Function to go Press Enter cancel functions is not activated to the setting status to activate the Swing function See Fig 11 for how to deactivate the Swing function GREE O GREE O Mode nter bance an ode Ente Enter Cance Fan m e Function Timer On Off d v Timer On Off Function v Timer On Off When the Swing is Press Function to go Press Enter cancel to activated to the setting status deactivate the Swing function N NOTE If the setting of the swing function is Off the swing angle may change after the unit is powered on again 4 6 Timer Under the or Off status press the Timer key to set the time when to automatically start or stop the unit How to set timer for unit On Under the Off state of the unit press the Timer key with the symbol on in the timer zone flashing and then press A or Y to set when to start the unit after that press the Timer key again to finish this setting Before pressing Timer key to finish the setting for unit On it is also available to go to set when to stop the unit by pressing the Mode key with the symbol flashing and then press A
32. abnormal heat in power supply cord and power plug 2 MAINTENANCE INSTRUCTIONS Forcibly pull the panel for a specific angle from the two ends of the front panel according to the arrow direction Then pull the air filter downwards to remove it See Fig a Mount the healthy filter onto the air filter as shown in Fig b If the air filter cannot be installed please mount the healthy filter on the front case as shown in Fig c Mount the air filter properly along the arrow direction in Fig d and then close the panel cover 2 1 Cleaning and Maintenance Take out the healthy filter before cleaning and reinstall it after cleaning according to the installation instruction Pay special attention to that silver ion filter can t be cleaned with water while active carbon photocatalyst low temperature conversion LTC catalyst formaldehyde eliminator catechin or mite killing filter can but can t with brush or hard things Dry it in the shade or sun after cleaning but not by wiping 2 2 Service Life The healthy filter commonly has its usage lifetime for one year under normal condition As for silver ion filter it is invalid when its surface becomes black green This supplementary instruction is provided for reference to the unit with healthy filter If the graphics provided herein is different from the physical goods the latter one shall prevail The quantity of healthy filters shall be based on the actual delivery p Wall Mounte
33. ave Function 1 This function is intended to save energy through limiting the temperature range under Cool Dry Heat mode 2 The set temperature range for energy saving under the Cool or Dry mode is from the set point to 30 3 The set temperature range for energy saving under the Heat mode is from 16 to the set point 2 How to set the Save function under the Cool mode 1 When the unit is On press Function to go to the setting state of the Save function with the symbol flashing 2 Press the A or V key to adjust the set temperature 3 Press the Enter Cancel key to activate the Save function 3 How to set the Save function under the Heat mode 1 When the unit is press Function to go the setting state of the Save function with the symbol flashing 2 Press Mode to switch to the setting status for heating 3 Press to adjust the set temperature 4 Press Enter Cancel to activate the save function 4 How to deactivate the Save function When the Save function is activated press the Function key to go to the setting state of this function with the symbol flashing after that press the Enter Cancel key to cancel the Save function and the symbol will disappear http splitoff ru tehn doc html Wall Mounted a Fan Coil Unit Servic
34. ay is default Note This function is only available for certain models http splitoff ru tehn doc html Wall Mounted a Fan Coil Unit Service Manual 2 5 TURBO TURBO button In Cool or Heat mode press this button to turn on off the Turbo function Note This function is not available for this model 3 OPERATION OF WIRELESS REMOTE CONTROL Note This is a general remote control it could be used for multiple types functions of air conditioners For some models without the functions specified here we preserve the right to not to inform exclusively 3 1 SWING UP AND DOWN BUTTON Press this button to adjust swing angle which circularly changes as below Sp Eee A OFF 3 AA This is a general use remote control If remote control shows the following three kinds of status that the swing status of main unit will bel 5 217 When the guide louver start to swing and down if turn off the Swing the air guide louver will stop at current position 3I which indicates the guide louver swings up and down between the five positions 3 2 TIMER ON BUTTON Press the TIMER ON button to set the timed On Press once to increase or decrease the minute by 1 minute If pressed and held for 2 seconds the minute will increase or decrease constantly by 1 minute If held constantly for more than 5 seconds the minute will begin to chan
35. d Type Fan Coil Unit Service Manual http splitoff ru tehn doc html Wall Mounted a Fan Coil Unit Service Manual 3 EXPLODED VIEWS AND SPARE PART LISTS Model FP 34BA2 A K EM55000200 FP 51BA2 A K EM55000210 FP 34BA3 A K EM55001130 FP 51BA3 A K EM55001210 FP 34BA4 A K 55001140 FP 51BA4 A K EM55001220 FP 34BA5 A K EM55000260 FP 51BA5 A K EM55000270 FP 34BB3 A K EM55001180 FP 51BB3 A K EM55001260 Exploded Views 15 o XXX Bee http splitoff ru tehn doc html Spare parts list Wall Mounted Type Fan Coil Unit Service Manual No Name of part Part code Quantity No Name of part Part code Quantity 30565056 0 30565007 3 1 Wall Mounting Frame 01252021 1 18 Display Board 30565012 1 30565026 30565037 9 200121505 D 200121225 3 2 Rear Case 2220245401 1 19 Front Panel 200121538
36. diagram requirements 9 Do not use the unit in the immediate surroundings of a laundry a bath a shower or a swimming pool 1 4 Safety Requirements For Electric Appliances 1 The power supply should be used the rated voltage and AC exclusive circuit the power cable diameter should be satisfied 2 Don t drag the power cable emphatically 3 It should be reliably earthed and it should be connected to the special earth device the installation work should be operated by the professional The air switch must have the functions of magnetic tripping and heat tripping in order to protect the short circuit and overloading 4 The min distance from the unit and combustive surface is 1 5m 5 The appliance shall be installed in accordance with national wiring regulations 6 An all pole disconnection switch having a contact separation of at least 3mm in all poles should be connected in fixed wiring Note CD Make sure that the Live wire or Zero line as well as the earth wire in the family power socket can not be wrong connected there should be reliable and no short circuit in the diagram Wrong connection may cause fire 1 5 Earthing requirements 1 Air conditioner is type electric appliance thus please do conduct reliable earthing measure 2 The yellow green two color wire in air conditioner is earthing wire and cannot be used for other propose It cannot be cut off and be fix it by screw otherwise it would cause electric sh
37. e Louver 10512115 1 17 Crank 10582070 18 Motor 15012086 1 19 Air Louver 2 10512117 1 20 Drainage Hose 05230014 1 21 Pipe Clamp 26112164 1 22 Fan Motor 15012116 1 23 Motor Clamp 26112494 1 24 Electric Box 20112108 1 25 Main Board 3022504501 1 26 Transformer 43110237 1 27 Terminal Board 42010268 1 28 Electric Box Cover1 20122154 1 29 Shield Cover of Electric Box 01592092 1 30 Electric Box Cover2 20112081 1 31 Tube Sensor 390000592G 1 32 Temperature Sensor 390000451 1 33 Remote Controller 305100413 1 34 Power Cord 400220112 1 35 Loop of electromagnetic Valve 43007002 1 36 Electromagnetic Valve 43007001 1 http splitoff ru tehn doc html JF00300236 GREE ELECTRIC APPLIANCES INC OF ZHUHAI Add West Jinji Rd Qianshan Zhuhai Guangdong China 519070 Tel 486 756 8522218 Fax 86 756 8669426 E mail gree gree com cn www gree com For continuous improvement in the products Gree reserves the right to modidy the product specification and appearance in this manual without notice and without incurring any obligations http splitoff ru tehn doc html
38. e Manual See Fig 18 for how to activate the Save function ff gt So DD in us CHE ea IC Llc e T f cRee O GREE G GREE Enter Cancel A Fan Mode Enter Cancel A Fan Mode Enter Cancel A Fan Mode Function On Off S s v Timer On Off Function 5 On Off 2 When the Save Press Function to go Press A or Y to function is not activated to the setting status adjust the temperature for cooling Xx bi cu le 5 c mr d G GREE O G Gree O GREE Enter Capz l A Fan Mode Enter Cancel A Fan Mode Enter Cancel A Fan Mode E E Function v Timer On Off Function 6 Timer On Off Function v Timer On Off Press Enter cancel Press A or Y to Press to switch to activate the Save adjust the temperature for to the setting status for function heating heating Fig 18 How to Activate the Saving Function See Fig 19 how to deactivate the Save function 20
39. e mark will disappear and the indicator light will be off 2 OPERATION OF WIRELESS REMOTE CONTROL Note This is a general remote control it could be used for multiple types functions of air conditioners For some models without the functions specified here we preserve the right to not to inform exclusively 2 1 X FAN X FAN button Press this button to turn on off the X FAN function The function is not available for this function 2 2 button Presetting temperature can be decrease the temperature by 1 degree Celsius once press and hold for more than two seconds so that we can change the temperature continuously The minimum and maximum setting range of the temperature is 16 to 30 degree Celsius ON OFF 4 y 2 3 button Press this button increase the temperature by 1 degree Celsius once Press and C hold for more than two seconds so that we can change the temperature continuously The minimum and maximum setting range of the temperature is 16 to 30 degree 2 4 Cran TEMP button Press this button to select the display of either indoor setting temperature or indoor ambient temperature When the indoor unit powered on firstly setting temperature display is default Change status toto display the ambient temperature rured steer If received control signal in 5 seconds the display temp will revert back to setting temperature When unit is off indoor setting temperature displ
40. e unit to the other place please firstly contact with the authorized Maintenance Center in the local area 1 2 Basic Requirements For Installation Position Install in the following place may cause malfunction If it is unavoidable contact with service center please 1 Place where strong heat sources vapors flammable gas or volatile object are emitted 2 Place where high frequency waves are generated by radio equipment welders and medical equipment 3 Place where a lot of salinities such as coast exists 4 Place where the oil machine oil is contained in the air 5 Place where a sulfured gas such as the hot spring zones is generated 6 Other place with special circumstance 1 3 Indoor Unit Installation Position Selection 1 The air inlet and outlet vent should be far away from the obstruction 2 Select a position where the condensing water can be easily drained out 3 Select a location where the children can not reach 4 Select the place that is strong enough to withstand the full weight and vibration of the unit And will not increase the noise 5 Be sure to leave enough space to allow access for routine maintenance The height of the installed location should be 250cm or more from the floor 6 Select a place about 1m or more away from TV set or any other electric appliances 7 Select a place where the filter can be easily taken out 8 Make sure that the unit installation should accord with installation dimension
41. ected with the main board If there are disconnected please insert the ambient temperature sensor and then check whether it can run normally after power on If it still can t run normally please replace the ambient temperature sensor Cooling LED blinks display F1 F1 Aluminum fin copper tube temperature sensor is open or short circuit Please cut off power at first and then check whether the wires of tube temperature sensor have been disconnected with the main board If there are disconnected please insert the tube temperature sensor and then check whether it can run normally after power on If it still can t run normally please replace the tube temperature sensor Running LED blinks displays C5 C5 Malfunction protection of the jumper cap Please cut off power at first and then check whether the cap jumper has been inserted well Running LED blinks displays H6 H6 No motor feed back Please cut off power at first and then restart the unit to check whether it can run normally or not http splitoff ru tehn doc html e Immediately stop all operations and plug out contact the dealer in following situations e There is harsh sound during operation e The terrible odors emitted during operation e Water is leaking in the room e Air switch or protection switch often breaks e Carelessly splash water or something into the unit e There is an
42. ection Assembly 06649591 2 33 Blow Molding Drainage Pipe 05230022 1 Notes D only is part of FP 68BA3 B K only is part of FP 68BA2 B K only is part of FP 68BA5 B K http splitoff ru tehn doc html Wall Mounted Fan Coil Unit Service Manual Spare parts list FP 85BA3 B K EM55001750 FP 85BA2 B K EM55001680 FP 85BA5 B K EM55001640 No Name of part Part code Quantity 20012260 1 1 Front Panel Assy 20012283 2 1 20012286 3 2 Filter Sub Assy 1112208901 2 3 Front Case 2690603901 1 4 Screw Cover 24252016 1 5 Rubber Plug Water Tray 76712012 1 6 Surface Cooler Assy 01127666 1 7 Cross Flow Fan 10352019 1 8 Ring of Bearing 76512051 1 9 Rear Case assy 1231221408 1 10 Wall Mounting Frame 01252218 1 11 Volute tongue 26112238 1 12 Air Louver 1 10512116 1 13 Axile Bush 10542036 1 14 Left Axile Bush 10512037 1 15 Guide Louver 10512115 1 16 Crank 10582070 1 17 Stepping Motor 15012086 1 18 Swing Louver2 10512117 1 19 Drainage hose 05230014 1 20 Rear Clamp 26112164 1 21 Motor 15706433 1 22 Motor Press Plate 26112494 1 23 Electric Box 20112108 1 24 Capacitor 33010020 1 25 Installation Supporting Frame 01806867 1 26 Terminal Board 42010262 1 27 Electric Box Cover 1 20122154 1 28 Shield cover of Electric Box 01592092 1 29 Electric Box Cover 2 2
43. epping Motor 15012086 1 19 Air Louver 2 10512117 1 20 Drainage Hose 05230014 1 21 Pipe Clamp 26112164 1 22 Fan Motor FN20W PG 1501211601 1 23 Motor Press Plate 26112494 1 24 Electric Box 20112108 1 25 Main Board 3022504501 1 26 Transformer 43110237 1 27 Terminal Board 42010268 1 28 Electric Box Cover1 20122154 1 29 Shield cover of Electric Box 01592091 1 30 Electric Box Cover2 20112081 1 31 Tube Sensor 05212423 1 32 Ambient Temperature Sensor 390000592 1 33 Remote ControlYB1FA XFAN 305100413 1 34 Power Cord 4002048712 1 4202300126 DOO 35 Jumping Connector 1 4202300127 Notes only is part of FP 68BA2 B D only is part of FP 85BA2 B D only is part of FP 102BA2 B D only is part of FP 68BA5 B D 9 only is part of FP 102BA5 B D only is part of FP 68BA3 B D only is part of FP 85BA3 B D 8 only is part of FP 102BA3 B D only is part of FP 85BA5 B D http splitoff ru tehn doc html Fan Coil Unit Service Manual Model FP 34BA3 B K EM55001720 FP 34BA2 B K EM55001710 FP 34BA5 B K EM55001670 FP 51BA3 B K EM55001730 FP 51BA2 B K EM55001700 FP 51BA5 B K EM55001660 exploded views 30 MAINTENANCE 48 http splitoff ru tehn d
44. er Assy 01126406 1 4 Evaporator Support 24212091 1 5 Cross Flow Fan 10352017 1 6 Ring of Bearing 26152022 1 7 Bearing cushion rubber base 76512203 1 8 Volute tongue 26112163 1 9 Left Axile Bush 10512037 1 10 Crank 10582070 1 10542008 O2 11 Axile Bush VOOD 1 10542036 9 12 Swing Louver1 10512156 1 13 Swing Louver2 10512155 1 14 Front Case 20012123 1 1112220401 e 15 Filter DOGO 2 1112208503 5X6 16 Remote Control YBIFA XFAN 305100413 1 20192265 020 17 Decorative Board 22432230 1 20192247 X6 18 Display Board 30565056 OO 1 i _ pay 30565007 QO 200121505 0 19 Front Panel 0290 1 200121995 906 20 Screw Cover 24252016 1 21 Guide Louver 10512157 1 22 Wire Clamp 71010003 1 23 Rear Clamp 26112164 1 24 Motor MP24AA 1521212901 1 25 Motor Clamp 26112161 1 26 Motor FN20X PG 15012089 1 27 Electric Box Cover 1 20122103 1 28 Covering Plate2 20122075 1 29 Terminal Board 42010262 1 30 Electric Box 2011208201 1 31 Main Board 30225043 1 4202300117 32 Jumping Connector 4202300125 2X4 1 4202300117 39 33 Transformer 48X26G 43110233 1 34 Power Cord 4002048712 1 Note only is part of FP 34BA2 B D only is part of FP 34BA3 B D 3 only is part of FP 51BA3 B D 4 only is part of FP 51BA2 B D only is part of FP 34BA5 B D http splitoff ru tehn doc html Wall Mounted a Fan Coil Unit Service Manual only is part of FP 51BA5 B D Model FP 68BA2 B D
45. ge in every 10 minutes Press TIMER ON again to accept the setting and ON will show besides the time of clock meaning the setting succeeds Press the TIMER ON again to cancel the setting 3 3 TIMER OFF BUTTON Press the TIMER OFF button to set the timed Off The procedures are similar as above http splitoff ru tehn doc html E Wall Mounted Type Fan Coil Unit Service Manual 4 OPERATION OF WIRELESS REMOTE CONTROL 4 1 Guide for operation General operation DPress SLEEP button to set the sleep state Press TIME ON and TIME OFF button to scheduled the unit ON OFF Press LIGHT button to control on and off the indicator board This function maybe not available for some units 4 2 Guide for operation Optional operation QD After powered on press ON OFF button the unit will start to run Note When it is powered off the guide louver of main unit will close automatically Press MODE button select desired running mode or press COOL or HEAT mode to enter the corresponding operation directly Press or button to set the desired temperature CLOCK TIMER on Press FAN button to set fan speed from AUTO FAN LOW MID and HIGH 5 Press3l button to select SWING mode Seer 4 3 Operation of wireless remote control Press buttons simultaneously to lock or unlock the wireless remote control If it is locked the mark will display when pressing
46. ing suitable Were inlet and outlet vents obstructed Is filter dirty Are the windows and doors clothed Did Fan speed set at low speed Is there any heat sources in the room Wireless remote control is not available The unit is interfered by abnormal or frequent functions switchover occasionally the controller cannot operate At this time you need to pull out of the plug and reinsert it Is it in its receiving range Or obstructed To check the voltage in wireless remote control inside is charged otherwise to replace the batteries Whether the wireless remote control is damaged If water leakage in the room The air humidity is on the high side Condensing water over flowed The connection position of indoor unit drainage pipe is loosed Indoor unit cannot deliver air In HEAT mode when the temperature of indoor heat exchanger is very low that will stop deliver air in order to prevent cool air Within 2min In COOL mode when the temperature of indoor heat exchanger is very high that will stop deliver air in order to prevent heat air Within 2min Moisture on air outlet vent If unit is running under the high humidity for a long time the moisture will be condensed on the air outlet grill and drip off Cooling LED blinks display FO F0 Ambient temperature sensor is open or short circuit Please cut off power at first and then check whether the wires of ambient temperature sensor have been disconn
47. ious state On condition that the Memory function is activated when the wired controller is powered on again the unit with the card inserted in will back to the previous state and the unit with the card drawn out will go to Off status On condition that the Memory function is deactivated the unit will go to the Off state when the wired controller is powered on again NOTE D The card being inserted or not the long distance monitoring is always enabled 2 The displayed symbol 1 indicates that the unit can not be controlled through the keys 4 14 4 Switchover between Celsius and Fahrenheit Scale When the unit is Off it is able to switch the Celsius scale and Fahrenheit scale by pressing Mode and simultaneously for five seconds 4 14 5 Long distance Shield On condition that all functions or the function On Off Mode Temperature or Save is shielded the press on any key of the wired controller or the operation through the wireless controller will be ineffective but with the corresponding symbol flashing For instance if the Mode is shielded then the operation to switch the current mode Cool to Heat would fail 5 Error Display http splitoff ru tehn doc html Wall Mounted Type Fan Coil Unit Service Manual When a system error arises its error code will be displayed in the temperature zone While if several errors
48. ire are not allowed e The electric wiring must be correctly connected wrong connection may cause spare parts malfunction e Tighten the terminal screw in order to prevent loose e After tighten the screw slight pull the wire and confirm whether is it firm or not e f the earth wire is wrong connection that may cause electric shock e The cover plate must be fixed and tighten the connection wire if it is poor installed that the dust moisture may enter in or the connection terminal will be affected by outside force and will cause fire or electric shock Finally wrap with tape Water drainage pipe 3 4 Install the unit e The piping can be lead out from right right rear left left rear 1 When routing the piping and wiring from the left or right side of indoor unit cut off the tailings from the chassis in necessary Show in Fig 7 1 Cut off the tailings 1 when routing the wiring only a 2 Cut off the tailings 1 and tailings 2 when routing both Fig 8 the wiring and piping Fixing hook 2 Take out the piping from body case wrap the piping electric wire water pipe with tape and pull them through the piste piping hole As show in Fig 8 3 Hang the mounting slots of the unit on the upper tabs of the rear panel and check if it is firm enough As show in Fig 9 Fig 9 4 The height of the installed location should be 2 5 m or more from the floor Fig 6 Inlet water side pipe Outlet water side _ Taili
49. l Function Timer On Off L Function v On Off L Function v Timer On Off When the timer is not set Press Timer to go to Press A or W to adjust the setting status the time for unit On J cB 52 CU 8 GREE A Fan G i y Mode Y Enter Cance N Enter Cancel Fan de Function v a On Off Function Timer On Off Function Timer On Off Press Timer to finish Press A or W to Press Mode to switch this setting adjust the time to setting status for unit ON Fig 12 How to Set the Timer See Fig 13 for how to cancel the timer under the status of the unit 2 I dis O GREE Enter Cancel 7 Function Timer On Off Function v x On Off The timer is set when the unit Press Timer to cancel the is turned on setting Fig 13 How to Cancel the Timer Timer Range 0 5 24 hours Each press on will increase or decrease the timer by 0 5 hour And the long time press will increase or decrease the timer by 0 5 hour per 0 3 second s NOTE When the unit is On if the time for unit On and unit Off have been set then onl
50. l to make a confirmation and then the symbol will stop flashing How to deactivate the E heater function When the E heater function is activated press the Function key to go to the setting state of the E heater function with the symbol flashing after that press the Enter Cancel key to deactivate this function and then the symbol will disappear See Fig 20 for how to activate the E heater function ia E cA 22 28 29 Ej ETETE 7 G Enter Cancel A pin pam oe A SER Mode C A uet o Function Timer On Off anh Y Timer On Off Function v Time On Off Press Function to go When the E heater Press Enter cancel to to the setting status function is not activated activate the E Heater function Fig 20 How to Activate the E heater function See Fig 21 for how to deactivate the E heater function che 28 ETETE pue GcRee Q 0 QD Enter Cancel Fan Mode Enter Cancel n Mode Enter Car el oe Mode Function v Timer On Off anys v Timer On Off Function v Timer On
51. l Unit Service Manual 4 14 Other Functions 4 14 1 Lock Lock Function It can lock the keypad and then the press on any other keys will get no response Whatever the unit is On or Off press and simultaneously for five seconds to activate the Lock function and the symbol will appear And then another press on them will deactivate this function and the symbol will disappear The Lock function will be memorized when the unit is powered on again after power failure 4 14 2 Memory Memory Function When the Memory function is activated for the wired controller the unit resume the status before powered off when it is powered on again otherwise the unit will go to the status when it is powered on again How to switch to the Memory function When the unit is press Mode and A simultaneously for five seconds to activate deactivate the Memory function Once the function is activated the symbol will be displayed on the LCD NOTE Please don t cut down the power after the content changes in five seconds or it may fail to save the content 4 14 3 Gate Control When the gate control is effective the unit will work with the card inserted in and will be shut down with the card drawn out When the card is drawn out the unit will be shut down and the symbol will appear when the card is inserted in again the symbol jt will disappear and the unit will run as the prev
52. n the outlet wal j wall of water tray should be adjusted slightly down above oe when installing that is taking the outlet of the water a tray as the center of a circle the included angle SS j between the evaporator and level should be 0 or i Ri ht more that is good for condensing water drainage R E Bal aa R hol 2 Fix the rear panel on the wall with screws Fig 5 Where is pre covered with plastic granula 3 Be sure that the rear panel has been fixed firmly enough to withstand the weight of an adult of 60kg further more the weight should be evenly shared by each screw 3 2 Install the piping hole Outdoor Ake the piping hole 55 in the wall at a slight downward slant to the Indoor outdoor side Wall pipe Insert the piping hole sleeve into the hole to prevent the connection piping and wiring from being damaged when passing through the hole Seal pad 3 3 Install the water drainage pipe M 0 55 1 For well draining the drain hose should be placed at a downward slant 2 Do not wrench or bend the drain hose or flood its end by water As show in Fig 6 Bent 3 When the long drainage hose passing through indoor should wrap the insulation materials Note D When connecting the electric wire if the wire length is not enough please contact with the authorized service shop to buy a exclusive gt lt gt lt Flooded electric wire that is long enough and the joint on the w
53. n v Timer On Off 4 3 Temperature Setting Under the On status press A and to increase or decrease the set temperature A long time press will make the temperature go up or down by 1 per 0 3 seconds Temperature Range 16 C 30 C GREE Enter Cancel A Fan Mode fs Function v Timer On Off NS Fig 8 Temperature Setting http splitoff ru tehn doc html Wall Mounted Type Fan Coil Unit Service Manual 4 5 Swing How to activate the Swing function under the On status of the unit press the Function key to go to the setting status with the symbol q flashing and then press Enter Cancel to make a confirmation and the symbol lt will stop flashing How to deactivate the Swing function under the On status of the unit press the Function key to go to the setting status with the symbol 28 flashing and then press Enter Cancel to deactivate this function and the symbol will disappear See Fig 10 for how to activate the Swing function O E x 28 8 22 C a 08 Ej ea x 6 2 6 5 Enter Cance A o d A xps Mode Enter Cancel Mic Function Timer On Off v Timer On
54. ng items before asking for repair it can save your time and money Phenomenon Troubleshooting Not operate immediately when the air conditioner is restarted Once the air conditioner is stopped it will not operate in approximately 3minutes to protect itself There s unusual smell blowing from the outlet after operation is started Sound of water flow can be heard during the operation The unit has no peculiar smell by itself If has that is due to the smell accumulated in the ambient Solution method Cleaning the filter If problem still has so need to clean air conditioner Please contact with the authorized maintenance center The sound is due to water flowing they are not malfunctions In COOL mode sometimes the mist emitted from the air outlet vent When the indoor temperature and humidity are very high this phenomenon would happen This is caused by the room air is swiftly cooled down After running for a while indoor temperature and humidity will fall down the mist will die away Creaking noise can be heard when start or stop the unit This is caused by the deformation of plastic due to the changes of temperature The unit can not run Has the power been shut down Is power plug loosed Is the circuit protection device tripped off or not Is voltage higher or lower Tested by professionals Is the TIMER correctly used Cooling Heating efficiency is not good Is Temp sett
55. ng to the electromagnetic interference D The signal line and communication line should be separated with the power cord and the connecting wires between indoor and outdoor units should be with a minimal distance of 20cm otherwise the communication would go wrong 2f the air conditioner is installed where it would be affected by electromagnetic interference the signal line and the communication line must be the shielded twisted pairs http splitoff ru tehn doc html E Wall Mounted Type Fan Coil Unit Service Manual 4 Operation Instructions 4 1 On Off e Under the Off status of the unit press On Off to start the unit e Under the On status of the unit press On Off to stop the unit e Fig 5 is the Off status when the unit is powered on Fig 6 show the On status when the unit is powered on S IZ 11 GREE Enter Cancel A Fan Mode Enter Cancel A Fan Mode Function v Timer On Off Function v Timer On Off Fig 5 Off Status Fig 6 Status 4 2 Mode Under the status each press on Mode can change the modes circularly as the following order f i r Cool gt Dry Fan gt Eu wn Bio We MEMORY X GREE Enter Cancel A Fan Mode Functio
56. ng2 Tailing1 Inlet side piping Outlet side piping insulatio Left rear Mounting baord Bee http splitoff ru tehn doc html Wall Mounted Type Fan Coil Unit Service Manual 3 5 Install the connection pipe 1 Align the center of the piping flare with the relevant valve pi Spring washer 2 Screw in the flare nut by hand and then tighten the nut with spanner and torque wrench refer to the following Hex nut diameter Tightening torque N m FCU pipe Connection nut Spring washer Connection pipe FCU pipe d Be sure there is an col interval of 6 7mm when M fitting is completed Before installed the two pipes must be e tightened with the steps of the connection nut Spanner SA Torque wrench 2 Be sure there is an lt Spring washer Washer O ring Connection nut SS interval of 6 7mm when the fitting is completed Nut 7 TRE O ring Washer Spring washer Connection pipe 3 6 Check after installation and test operation 3 6 1 Check after installation Items to be checked Possible malfunction Has it been fixed firmly The unit may drop shake or emit noise Is heat insulation sufficient It may cause condensation and dripping Is water drainage well It may cause condensation and dripping Is the voltage in accordance with the rated
57. o Name of part Part code Quantity No Name of part Part code Quantity 20012283 1 Front Panel Assy 20012260 1 19 Air Louver 2 10512117 1 20012280 20012286 8 20012467 9 Q 2 Filter Sub Assy 1112208901 2 20 Drainage hose 05230014 1 3 Front Case 20012250 21 Pipe Clamp 26112164 1 15012116 0000 4 Screw Cover 24252016 1 22 Fan Motor Do 1 1501211601 9 30565039 0090600 5 Display Board 30565038 1 23 Motor Press Plate 26112178 1 30565038 30565037 0 Q 6 QS 76712012 1 24 Electric Box 20112108 1 7 Evaporator Assy 24212100 1 25 Main Board 30225045 1 8 Cross Flow Fan 10352019 1 26 Transformer 43110237 1 9 Ring of Bearing 26152022 1 27 Terminal Board 42010268 1 Rear Case Assy 12312214 1 28 Electric Box Cover1 20122128 1 11 Wall Mounting Frame 01252218 1 29 possa 01592092 1 12 Helicoid tongue 26112238 1 30 Electric Box Cover2 20112081 1 13 Air Louver 1 10512116 1 31 Tube Sensor 390000592 1 14 Axile Bush 10542008 1 32 temp io M 390000451 1 15 Left Axile Bush 10512037 1 33 Remote Controller 30510041 1 16 Guide Louver 10512115 1 34 Power Cord 400220112 1 17 crank 10582070 1 35 Jumping Connector 4202300120 1 18 Step Motor 15012086 1 D00 op Note D is part of FP 68BA2 A K is part of FP 85BA2 A K 9 is part of FP 68BA3 A K is part of FP 85BA3 A K is part of FP 68BA4 A K is part of FP 85BA4 A K is part of FP 68BA5 A K is part of FP 85BA5 A K 9 is part of FP 85BA2 A D is part of
58. oc html Spare parts list Wall Mounted Type Fan Coil Unit Service Manual FP 34BA3 B K EM55001720 FP 34BA2 B K EM55001710 FP 34BA5 B K EM55001670 No Name of part Part code Quantity 1 Wall Mounting Frame 01252021 1 2 Rear Case 2220245401 1 3 Surface Cooler Assy 01127669 1 4 Evaporator Support 24212091 1 5 Cross Flow Fan 10352017 1 6 Ring of Bearing 76512051 1 7 Bearing cushion rubber base 76512203 1 8 Volute Tongue 26112163 1 9 Left Axile Bush 10512037 1 10 Crank 10582070 1 11 Axile Bush 10542036 1 12 Swing Louver1 10512156 1 13 Swing Louver2 10512155 1 14 Front Case 2001212301 1 15 Filter Assy 1112220401 2 22432230 16 Decorate Piece 20192265 1 20012122 17 Front Panel 20012150 1 20012199 18 Guide Louver 10512157 1 19 Screw Cover 24252016 1 20 Wire Clamp 71010003 1 21 Rear Clamp 26112164 1 22 Stepping Motor 1521212901 1 23 Motor Clamp 26112161 1 24 Motor 15706432 1 25 Electric Box Cover 1 20122103 1 26 Electric Box Cover 2 20122075 1 27 Terminal Board 42010262 1 28 Installation Supporting Frame 01806868 1 29 Capacitor 33010089 1 30 Electric Box 01396952 1 Notes only is part of FP 34BA3 B K only is part of FP 34BA2 B K 9 only is part of FP 34BA5 B K http splitoff ru tehn doc html Wall Mounted Fan Coil
59. occurs at the same time their codes will be displayed circularly Once an error arises please shut down the unit and contact the professional technician See Fig 26 for the communication error Error list Enter Cancel Function v Timer On Off N A Fig 26 Communication Error Error Code Error Description E0 Water pump error E6 Communication error E9 Water overflow protection FO Error of Indoor ambient temperature sensor of return air inlet F1 Temperature sensor error of evaporator F5 Temperature sensor error of wired controller EH Auxiliary electrical heater error C5 Jumper error H6 PG motor error http splitoff ru tehn doc html Wall Mounted Type a Fan Coil Unit Service Manual INSTALLATION Bee http splitoff ru tehn doc html Wall Mounted Fan Coil Unit Service Manual INSTALLATION 1 INSTALLATION OF THE UNIT 1 1 Important Notices 1 The unit installation work must be done by qualified personnel according to the local rules and this manual 2 Before installing please contact with local authorized maintenance center if unit is not installed by the authorized maintenance center the malfunction may not be solved due to discommodious contacts 3 When removing th
60. ock 3 The earth resistance should accord to the National Criterion 4 The user power must offer the reliable earthling terminal Please don t connect the earthing wire with the following place D Tap water pipe 2 Gas pipe S Contamination pipe 4 Other places that professional personnel consider them unreliable 5 The model and rating values for fuses according the silk print on fuse cover or related PCB board http splitoff ru tehn doc html Wall Mounted a Fan Coil Unit Service Manual 2 INSTALLATION DIMENSION DIAGRAM Space to the ceiling 15 Dee nc GemAbove gt Space to the wall Space to the wall Ww 300cm 290 Abov cm Air outlet side Space to the floor The dimensions of the space necessary for correct installation of the appliance including the minimum permissible distances to adjacent structures 4 4 CUIU ECCO http splitoff ru tehn doc html E Wall Mounted Type Fan Coil Unit Service Manual 3 INSTALL THE UNIT 3 1 Install the rear panel 1 Always mount the rear panel horizontally Wal Mark on the middle ofit g Due to the water tray of indoor unit has been T NN adopted the both way drainage desig
61. s of Quiet and Auto Quiet 3 Fan There are four fan speed options High Medium Low and Auto 1 It is used to set the mode of Cool Dry Fan and Heat 4 2 When the Save function is being set it is used to switch between the mode options of Heat and Cool 3 When the Timer is being set it is used to switch between the options of Unit On and Unit 5 Function It is used to switch the functions of Swing Sleep Turbo Save E Heater Blow Quiet etc 7 Timer It is used to set the timer 8 On Off It is used to start stop the indoor unit Under the Off status of the unit press Mode and A simultaneously for five seconds to activate 4 2 MEMORY or deactivate the MEMORY function once this function is activated the unit with power failure will resume the previous set status after powered on again otherwise it will go to the Off status AY Press A and simultaneously for five seconds to go to the lock status in which case the press 2 6 LOCK on any other key will get no response And another press on and for five seconds will quit this status http splitoff ru tehn doc html Wall Mounted a Fan Coil Unit Service Manual Function Timer Ambient Under the Off status of the unit press Function and Timer simultaneously for
62. t Temperature Sensor Under the debugging condition press the Mode to adjust the display to 00 in the temperature zone and press A or to adjust the display in the timer zone for which there are three options e The indoor ambient temperature is the return air temperature 01 displayed e The indoor ambient temperature is the temperature which the wired controller senses 02 displayed e The return air temperature sensor is selected under the Cool Dry or Fan mode The temperature sensor of the wired controller is selected under the Heat mode 03 displayed 4 13 2 Anti Cold Hot Air Function Under the debugging condition press the Mode key to switch the display in the temperature zone to 03 and press A or V to switch the display in the timer zone For the later display there are two options 01 indicating the unit with the anti cold hot air functions and 02 indicting the unit without the anti cold hot air function Please press Enter Cancel to save the setting and quit the setting status otherwise if there is no operation in 20 seconds after the system responds to the last operation on the press button and then the system will quit this setting status and back to the normal Off status with the current setting not saved http splitoff ru tehn doc html Wall Mounted Type Fan Coi
63. ted a Fan Coil Unit Service Manual 6 WIRED CONTROLLER OPERATION OPTIONAL 1 LCD Display 1 1 Symbols on the LCD HOUR onorr Enter Cancel Function v Timer On Off Fig 1 Appearance of the Wired Controller 1 2 Introduction to the Symbols on the LCD 7 HOUR BB 1 020 12 13 14 15 16 17 18 19 16 20 21 22 Fig 2 Symbols on the LCD Table 1 Introduction to the Symbols on the LCD No Symbol Function Description 1 zl It indicates the swing function 2 A It indicates the function of air exchange It is unavailable for this wired controller 3 It indicates the sleeping status 4 It indicates each running mode of the indoor unit AUTO mode It is unavailable for this wired controller 5 x It indicates the Cool mode 6 i It indicates the Dry mode 7 45 It indicates the Fan mode 8 Xx It indicates the Heat mode 9 It indicates the defrosting mode It is unavailable for this wired controller 10 It indicates the gate control status 11 It indicates the locking status http splitoff ru tehn doc html Wall Mounted Fan Coil Unit Service Manual It indicates the shield status It appears when all functions or the function On Off Temp Mode 12 SHIELD Save is shielded through the Long distance monitoring System
64. tion when the Quite Auto Quiet function is activated press the Function key to go to the setting state with the symbol or Quen flashing after that press Enter Cancel to deactivate the Quiet function See Fig 24 for how to activate the Quite Auto Quiet function x ui ch e CH EEN wor 22 Ej z GREE Enter Cancel d Fan o Enter Cancel I rn Mode Enter Cancel re Fan Mode Function Y Timer On Off L a Timer On Off Function v Timer On Off When the Quiet Auto Press Function to go Press A or W to Quiet function is not to the setting status select Quiet or Auto activated Quiet http splitoff ru tehn doc html Wall Mounted Fan Coil Unit Service Manual c e 8 C a sj G oree d Fan Mode b Function On Off Press Enter cancel to activate this function Fig 24 How to Activate the Quiet Auto Quiet Function See Fig 25 for how to activate the Quiet function
65. tions as below 1 Cooling efficiency air 27 C 80 6 F DB 19 5 C 67 1 F WB water temperature in 7 C 44 6 F water out 12 C 53 6 F 2 Heating efficiency air 21 C 69 8 F DB Water temperature 60 C 140 F 3 The operating water pressure of the models above is no more than 1 5MPa Bee http splitoff ru tehn doc html E Fan Coil Unit Service Manual CONTROL 9 CONTROL Fan Coil Unit Service Manual CONTROL 1 WIRELESS REMOTE CONTROLLER Names and functions of wireless remote control Note Be sure that there are no obstructions between receiver and remote controller Don t drop or throw the remote control Don t let any liquid in the remote control and put the remote control directly under the sunlight or any place where it is very hot sex gt 1 1 ON OFF ON OFF button Press ON OFF button to turn on off the unit When the unit is turned off the Timer Sleep function will not be retained in memory but the time will be retained and is still displaying 1 2 MODE MODE button Press this button Auto Cool Dry Fan Heat mode can be selected circularly Under Cool mode the initial value is 24 C 75 F Under Heat mode the initial values 24 75 Auto mode is not available in this mode G O auto COOL 6 6 6 DRY SH FAN XX HEAT CONTROL 10
66. tus deactivate the Sleep function Fig 15 How to Deactivate the Sleep Function NOTE D The default setting for the Sleep function is Off when the unit is powered on again after power failure 2 This function is unavailable under the Fan mode 4 8 Turbo Turbo function It is a function to make the temperature of the conditioned air approach the set value rapidly through high speed running of the fan under either or Heat mode How to active the Turbo function under the Cool or Heat mode when the Turbo function is Off press the Function key to go to the setting status of the Turbo function with the symbol ruo flashing after that press the Enter Cancel key to make a confirmation and then the symbol stops flashing How to deactivate the Turbo function When the unit On and the Turbo function is activated press the Function key to go to the setting state of the Turbo function with the symbol wro flashing after that press the Enter Cancel key to make a confirmation and then the symbol disappear http splitoff ru tehn doc html See Fig 16 for how to activate the Turbo function E Wall Mounted Type Fan Coil Unit Service Manual GREE Enter Cancel A Fan Mo Function Timer On Off eu E Ca fem E ES T Li
67. voltage marked on the It may cause electric malfunction or damage the part nameplate Is the electric wiring and piping connection installed correctly and securely It may cause electric malfunction or damage the part Has the unit been connected to a secure earth connection It may cause electrical leakage Is the power cord specified It may cause electric malfunction or damage the part Is the inlet and outlet been covered It may cause insufficient cooling heating capacity 3 6 2 Test Operation 1 Before test operation 1 Do not switch on power before installation is finished completely 2 Electric wiring must be connected correctly and securely 3 All the impurities such as scraps and thrums must be cleared from the unit 2 Test operation method 1 Switch on power press ON OFF button on the wireless remote control to start the operation 2 Press MODE button to select the COOL HEAT FAN to check whether the operation is normal or not http splitoff ru tehn doc html Wall Mounted Fan Coil Unit Service Manual MAINTENANCE http splitoff ru tehn doc html Wall Mounted Type Fan Coil Unit Service Manual MAINTENANCE 1 TROUBLESHOOTING 1 1 CAUTION Don t attempt to repair the air conditioner by yourself It can cause an electric shock or fire Please check the followi
68. y the time for unit Off will be displayed on the wired controller When the unit is Off if the time for unit On and unit Off have been set then only the timer for unit On will be displayed on the wired controller 2 When the unit is Off the time for unit On starts as soon as the time for unit Off ends When the unit is the time for unit Off starts as soon as the time for unit On ends 4 7 Sleep 1 Sleep Function 1 Under the and Dry Mode when the unit has run for one hour the set temperature will go up by 1 and then another 1 C in another hour then the temperature will not change any more 2 Under the Heat mode when the unit has run for one hour the set temperature will go down by 1 C and then another 1 in another hour and then the temperature will not change any more http splitoff ru tehn doc html Wall Mounted a Fan Coil Unit Service Manual 2 How to activate the Sleep function When the unit is On and the Sleep function is deactivated press the Function key to go to the setting state of the Sleep function with the symbol amp flashing after that press the Enter Cancel key to make a conformation and then the symbol will stop flashing 3 How to deactivate the Sleep function When the unit is On and the Sleep function is activated press Function