1. AGalletti 8 MAINTENANCE The routine maintenance operations to be performed on S fan heaters mainly regard the heat exchanger It must be cleaned to eliminate dust buildup which tends to obstruct the spaces between the fins resulting in a decrease in the quantity of heat exchanged This job may be done using jets of compressed air If grease has also deposited you can wash the fins taking care not to wet the electric motor and making sure to dry the finned block thoroughly before starting the fan heater It is recommended to carry out these operations at least once a year before the start of the heating season The electric motor requires no maintenance as it is of the closed type with self lubricating bearings Every time you start up the unit after it has been off for a long time make sure no air is trapped in the heat exchanger Special care should be taken when carrying out maintenance work some metal parts may cause injuries wear protective gloves maintenance may be performed exclusively by specialised personnel contact your dealer or installer For safety reasons before carrying out any maintenance or cleaning jobs put the main switch of the unit off to disconnect the power supply If any work needs to be done on a unit that is working with steam it is advisable to shut off the steam by means of the on off valves and allow the fan to run for a few minutes until all the metal parts have cooled down before car
2. 5 The fan heater does not work at all 1 No power supply 2 The motor overload cutout has tripped 3 The main switch is on off 1 Restore the power supply 2 Contact a service engineer 3 Switch on the power supply The fan heater provides inadequate heating 1 An obstacle is obstructing the air intake or outlet 2 The operating speed selected is too low 1 Remove the obstacle 2 Select a higher speed The fan heater leaks water 1 Operation in 4 pole air conditioning mode 2 Leaky plumbing connections 1 Select a lower speed 2 Contact a service centre or your installer AP66000409 01 severamente vietata la riproduzione anche parziale di questo manuale All copying even partial of this manual is strictly forbidden AGalletti 1 Modello RPM Qa PT Qs Tbs2 Hmax Lwa M rpm m h kW kg C m dBA kg 5 12 1400 1150 12 00 20 51 0 3 0 66 19 4 900 700 8 92 15 57 9 3 0 62 19 4 5 22 1400 2600 24 50 40 48 0 3 5 69 25 1 900 1650 18 80 31 53 9 3 5 63 25 1 5 32 1400 4250 39 28 64 47 5 4 5 74 33 7 900 2700 30 19 49 53 2 4 0 65 33 7 5 42 1400 5900 55 40 90 47 9 4 5 77 39 1 900 3750 42 55 69 53 7 4 0 69 39 1 5 52 1400 8800 79 42 130 46 8 5 0 84 49 6 900 5600 61 18 100 52 5 4 0 73 49 6 5 62 900 8100 92 65 151 54 0 5 5 7T 57 8 700 6250 79 34 129 57 7 5 0 71 57 8 2 AP66000409 01 sever
3. VOLTAGE 1 BEFORE STARTING INSTALLATION Carefully read this manual Installation and maintenance may be carried out solely by qualified technicians specifically trained for this type of equipment in conformity with current regulations On receiving the equipment check that it has not undergone any damage during transport 2 INTENDED USE AND OPERATING LIMITS Galletti S p A will not accept any liability for damage or injury caused as a result of installation by non qualified personnel improper use or use in conditions not allowed by the manufacturer failure to perform the maintenance prescribed in this manual use of spare parts other than original factory parts The operating limits are specified at the end of this chapter usage outside the stated limits is to be considered improper When choosing an installation site you should observe the following rules The heating unit should not be placed immediately under a socket do not install the unit in places where inflammable gases are present do not expose the unit directly to sprays of water install the unit on walls or ceilings able to withstand its weight use accessories suited to the purpose and suitable screw anchors Store the unit in its packing container until you are ready to install it to prevent dust from infiltrating inside it Installation maintenance and cleaning jobs may be carried out only with the power supply disconnected If
4. AEROTERMI A VAPORE SERIE S FAN HEATER FOR STEAM OPERATION S SERIES INSTALLAZIONE USO E MANUTENZIONE INSTALLATION USE AND MAINTENANCE COMPANY WITH QUALITY SYSTEM CERTIFIED BY DNV 1 0 9001 2000 T A Galletti AIR C O N D TI O NI NG DICHIARAZIONE DI CONFORMIT La Galletti S p A con sede in via Romagnoli 12 a 40010 Bentivoglio BO Italia dichiara sotto la propria responsabilit che gli aerotermi per alimentazione a vapore S sono conformi a quanto prescritto dalle Direttive CEE 73 23 89 392 91 368 93 44 93 68 89 336 83 97 e successive modifiche Bologna li 30 06 2004 Luigi Galletti Presidente de SIMBOLI DI SICUREZZA A m Leggere attentamente ATTENZIONE PERICOLO il manuale TENSIONE 1 PRIMA DI INIZIARE L INSTALLAZIONE Leggere attentamente questo manuale L installazione e la manutenzione dell apparecchio devono essere effettuati esclusivamente da personale tecnico qualificato per questo tipo dimacchina in conformit alle normative vigenti Al ricevimento dell apparecchio controllarne lo stato verificando che non abbia subito danni dovuti al trasporto 2 UTILIZZO PREVISTO E LIMITI DI FUNZIONAMENTO La Galletti S p A si ritiene sollevata da eventuali responsabilit nei casi in cui l apparecchio sia installato da personale non qualificato venga utilizzato impropriamente o in condizioni non ammesse dal costruttore non venga effettuata la manutenzione previ
5. Installazione errata o non conforme Danni da trasporto e o movimentazione non reclamati all atto della consegna Uso improprio Alimentazione elettrica non prevista dai dati di targa Danni o manipolazioni di personale non autorizzato Atti vandalici e danni da agenti atmosferici Galletti si riserva di contestare la validit della garanzia se da riscontri oggettivi risulti che il prodotto abbia funzionato prima della decorrenza della garanzia Le modalit delle presenti condizioni di garanzia sono valide ed applicabili esclusivamente per il territorio italiano ONLY FOR ITALIAN MARKET SEULEMENT POUR LE MARCH ITALIEN NUR F R DEN ITALIENISCHEN MARKT AGalletti AIR C O N D 40010 Bentivoglio BO Via Romagnoli 12 a Tel 051 8908111 Fax 051 8908122 www galletti it
6. a installazione LWA livello di potenza sonora M peso AP66000409 01 2 AGalletti 3 DESCRIZIONE DELL APPARECCHIO Gli aerotermi per funzionamento a vapore sono principalmente costituiti dai componenti elencati di seguito Mobile di lamiera di acciaio preverniciata completo di angolari in ABS termoresistente Il mobile completo di alette deflettrici orientabili a molla in alluminio poste sulla mandata aria per una distribuzione ottimale dell aria nell ambiente riscaldato dotato di serie di staffe per il fissaggio alle dime di sostegno disponibili in accessorio Batteria di scambio termico realizzata in tubo di rame ed alette in alluminio ad alta conducibilit termica per ottimizzare lo scambio rispetto alle batterie con tubo in ferro tradizionali le circuitazione in parallelo permette un agevole deflusso del vapore condensato evitando colpio di ariete Motori di serie con le seguenti caratteristiche tropicalizzati dotati di protettore termico interno klixon avvolgimenti di classe F grado di protezione 55 Doppia velocit 4 6 poli o 6 8 poli nell esecuzione 400V trifase del tipo stella triangolo Ventilatore assiale con pale a falce bilanciate staticamente inserite in un apposito boccaglio che esalta le prestazioni aerauliche e minimizza il rumore Una griglia anti infortunistica in filo di acciaio elettrozincato sostiene il motore ed fissata al mobile mediante supporti anti vibrant
7. amente vietata la riproduzione anche parziale di questo manuale All copying even partial of this manual is strictly forbidden 6 AGalletti 25 gt 25 B p A A 300 A mm B mm C mm E mm G mm S 12 460 330 500 328 300 5 22 560 430 500 428 400 5 32 660 530 525 528 500 5 42 760 630 515 628 600 5 52 860 730 535 728 700 5 62 960 830 535 828 800 A HO HV 1400 rpm 900 rpm 1400 rpm 900 rpm HV LV HV LV HO LO HO LO m m m m m m m m 12 3 0 7 0 3 0 5 0 3 5 575 5 22 3 5 11 0 3 5 7 5 4 0 7 0 3 5 5 5 5 32 4 5 15 5 4 0 9 5 5 0 12 0 4 0 7 5 42 4 5 19 0 4 0 11 5 5 5 12 0 4 0 8 0 S52 5 0 19 0 4 5 12 0 6 0 12 0 5 5 7 0 5 62 5 5 12 5 6 0 11 0 7 AP66000409 01 severamente vietata la riproduzione anche parziale di questo manuale All copying even partial of this manual is strictly forbidden AGalletti 5 2 350
8. arziale di questo manuale All copying even partial of this manual is strictly forbidden 1 8 CONDIZIONI GENERALI DI GARANZIA AEROTERMI GALLETTI Gli aerotermi Galletti S p A sono garantiti per 24 mesi dalla data di consegna all utilizzatore La garanzia relativa alla riparazione e o sostituzione in forma gratuita dei componenti con vizi o difetti di fabbricazione Galletti vincola la concessione della garanzia alla verifica di vizi o difetti dei componenti attraverso un Centro Assistenza Autorizzato dalla scrivente stessa sul territorio di competenza In conformit con la direttiva 199 44 CE attuata dal Decreto Legislativo N 24 2 Febbraio 2002 la garanzia Galletti applicabile esclusivamente al prodotto non contemplando alcuna parte dell impianto La data di decorrenza della garanzia sar relativa al documento fiscale di accompagnamento In mancanza dello stesso la Galletti si riserva di stabilire la decorrenza dalla data di fabbricazione Scaduti i termini di garanzia i costi relativi ai ricambi ed alla manodopera necessaria per la riparazione sono a carico del cliente Come specificato dai termini di legge DL 199 l obbligo della garanzia all utilizzatore finale a carico del venditore la societ presso la quale ha effettuato l acquisto Galletti attiver le procedure di garanzia su richiesta del venditore La garanzia Galletti non copre Controlli manutenzioni riparazioni dovuti a normale usura
9. bes and aluminium fins assuring higher heat exchange than standard iron tubes exchangers All circuit are in parallel without siphons to drain perfectly the condensed steam All motors are standard equipped with internal thermal protection klixon windings in class protection degree IP55 Two speeds 4 6 poles or 6 8 poles in the 400 3 50 version delta star type Axial fan with statically balanced sickle blades housed in a specially designed compartment that enhances ventilation and reduces noise emissions Safety grille made of electrogalvanised steel wire it supports the motor and is fixed to the cabinet by means of vibration damping supports Main components as shown in figure 2 1 2 3 4 5 6 7 8 9 10 Cabinet side panel Cabinet upper panel Cabinet lower panel Rear panel fan compartment Safety grille fan supporting motor Finned block heat exchanger heat exchanger coil Adjustable louvers Conveyor duct Plastic corner trim on cabinet left and right Wall ceiling mounting brackets 4 DIMENSIONS Figure 3 shows the dimensions of the unit IN Steam inlet connection 1 female gas OUT Condensate drain connection 1 female gas 5 INSTALLATION Remove the fan heater from the packing container and check that no damage has occurred during transport Before starting to install the unit make sure that the installat
10. ella sotto riportata Se il problema non pu essere risolto rivolgetevi al rivenditore o al centro assistenza Problema Causa Soluzione 1 Manca corrente 1 Ridare corrente L aerotermo non 2 E scattato l interruttore 2 Chiedere l intervento funziona affatto salvamotore del servizio assistenza 3 Il sezionatore si trova 3 Dare tensione su arresto 1 E presente un ostacolo 1 Rimuovere l ostacolo vicino all aspirazione o L aerotermo riscalda all uscita dell aria poco 2 E stata selezionata 2 Selezionare la velocit una velocit di pi alta funzionamento troppo bassa 1 Perdita dalle connessioni idrauliche L aerotermo perde 1 Contattare il centro acqua assistenza o l installatore di fiducia AP66000409 01 severamente vietata la riproduzione anche parziale di questo manuale All copying even partial of this manual is strictly forbidden DECLARATION OF CONFORMITY Galletti S p A whose main office is located at 12 a via Romagnoli 40010 Bentivoglio BO Italy hereby declares under its own responsibility that the fan heaters belonging to the AREO S series indoor units for air conditioning systems conform to the specifications of EEC Directives 73 23 89 392 91 368 93 44 93 68 89 336 83 97 and subsequent modifications Bologna 30 06 2004 Luigi Galletti President SAFETY SYMBOLS i MR Carefully read this handbook DANGER
11. i Componenti principali come da figura 2 Mobile di copertura pannello laterale 3 Mobile di copertura pannello inferiore 2 Mobile di copertura pannello superiore 4 Pannello posteriore boccaglio ventilatore 5 Griglia antinfortunistica ventola supporto motore 6 Scambiatore di calore a pacco alettato batteria di scambio termico 7 Alette deflettrici orientabili 8 Convogliatore aria 9 Angolare plastico di chiusura mobile destro e sinistro 10 Staffe di fissaggio a parete soffitto 4 DATI DIMENSIONALI Nella figura 3 sono riportati i dati dimensionali dell apparecchio IN Attacco ingresso 1 1 femmina gas OUT Attacco uscita 1 femmina gas 5 INSTALLAZIONE Estrarre l aerotermo dall imballo e controllarne lo stato verificando che non abbia subito danni dovuti al trasporto Prima di procedere al montaggio dell apparecchio verificare che l altezza di installazione ed il lancio d aria siano conformi alle indicazioni riportate Sul catalogo tecnico in funzione della polarit e del tipo di proiezione dell apparecchio L altezza massima di installazione comunque indicata in figura 4 Perl installazione a parete utilizzare le apposite dime di fissaggio disponibili in accessorio DFP per fissaggio a pareti DFC per fissaggio a colonne DFO orientabile per fissaggio a pareti colonne da 0 a 45 Nel caso in cui non si utilizzino dime di fissaggio originali ve
12. ion height and air range conform to the specifications provided in the technical catalogue according to the number of motor poles and type of air flow vertical or horizontal The maximum installation height is also shown in figure 4 In the case of wall installation use suitable mounting boards available as accessories DFP for wall mounting DFC for mounting on columns Adjustable DFO for mounting on walls columns from 0 to 45 If you do not use the mounting boards supplied by the manufacturer make sure in any case that the unit is adequately spaced from the wall or ceiling at a distance that is at least that shown in figure 5 Use screw anchors of adequate dimensions to support the weight of the unit and make sure that the surface of the installation site is suited to the purpose Using suitable lifting equipment a forklift truck is recommended convey the unit to the installation site and rest it on the floor with the fins facing down The feeding hose should be connected to the upper coupling and the condensate drainage hose to the lower coupling Fig 6 shows an example ofwater connection diagram where the condensate drainage hose atthe unit outlet is provided with a drainage trap a Y filter a condensate drainage aflow indicator and a regulating valve severamente vietata la riproduzione anche parziale di questo manuale All copying even partial of this manual is strictly forbidden LA wise for hydraulic connec
13. la figura 11 9 Collegamento a triangolo alla morsettiera di motori 400 400 V YA velocit alta 10 Collegamento a stella alla morsettiera di motori 400 400 V YA velocit bassa 11 Schema elettrico di collegamento di un motore 400 400 V con selettore stella triangolo Y A Legenda schemi elettrici CST Commutatore stella triangolo accessorio F Fusibile di protezione NON FORNITO IL Interruttore di linea NON FORNITO M Motore 7 VERIFICA FUNZIONALE Controllare la tenuta dei collegamenti idraulici Controllare la stabilit delle staffe di fissaggio se l installazione del tipo a parete il fissaggio con le catene se l installazione stata eseguita a soffitto Controllare che i cablaggi elettrici siano ben saldi Orientare come desiderato le alette deflettrici e dare tensione all apparecchio per verificarne il funzionamento Verificare sempre che verso di rotazione della ventola sia corretto ANTIORARIO guardando l aerotermo da dietro figura 12 AGalletti 8 MANUTENZIONE Le operazioni di manutenzione da eseguirsi periodicamente sugli aerotermi serie AREO riguardano principalmente la batteria di scambio termico che deve essere pulita da residui polverosi tendenti a ostruire i passaggi fra le alette con conseguente diminuzione della quantit di calore scambiata L operazione pu essere eseguita con getti di aria compressa In presenza di depositi grassi si pu procedere al la
14. mm 300 gt N N Il N I N N N N N N N jo N 6 fr a Eu ii ij PE i i S b gt O 7 8 M RPM V PA CA r p min V W A 12 416 1400 900 400 67 46 0 209 0 118 5 22 4 6 1400 900 400 277 1 172 0 61 0 32 5 32 4 6 1400 900 400 394 294 0 85 0 58 5 42 4 6 1400 900 400 703 471 1 49 0 85 5 52 4 6 1400 900 400 1300 860 2 49 1 37 5 62 6 8 900 700 400 540 417 1 18 0 69 AP66000409 01 8 severamente vietata la riproduzione anche parziale di questo manuale All copying even partial of this manual is strictly forbidden AGalletti 9 10 KLIXON KLIXON R S T R S T 11 12A KLIXON L4 13 se L2 4 15 L3 2 o O 6 W2 U2 2 U1 V1 w1 7 D DE 16 5 CST 9 AP66000409 01 severamente vietata la riproduzione anche parziale di questo manuale All copying even partial of this manual is strictly forbidden AGalletti 15 AP66000409 01 10 severamente vietata la riproduzione anche parziale di questo manuale All copying even partial of this manual is strictly forbidden AGalletti 11 AP66000409 01 severamente vietata la riproduzione anche p
15. ono di tipo chiuso asincrono trifase doppia velocit 400 400 V collegamento YA motori del tipo 400 400 V YA sono dotati di klixon interno e la selezione delle velocit avviene per mezzo di un normale commutatore stella triangolo accessorio CST terminali del klixon sono riportati in morsettiera cosicch possa essere utilizzato come protezione in serie alla bobina di un teleruttore Nel caso in cui non si utilizzi il klixon interno per proteggere il motore occorre prevedere un salvamotore tarato ad una corrente del 10 15 maggiore rispetto alla corrente indicata nei dati di targa dell apparecchio Effettuare i collegamenti elettrici in assenza di tensione secondo le nor mative di sicurezza vigenti cablaggi dovranno essere eseguiti esclusivamente da personale qualificato Verificare che la tensione di rete corrisponda a quella indicata sulla targhetta dell apparecchio Seguire scrupolosamente lo schema elettrico a seconda del tipo di installazione Per ogni aerotermo prevedere sulla rete di alimentazione un interruttore IL con contatti di apertura con distanza di almeno 3mm e un fusibile F di protezione adeguato tabella di figura 8 sono indicate le caratteristiche elettriche dei motori dove M Polarit del motore RPM numero di giri del motore V Tensione di alimentazione elettrica PA Potenza elettrica assorbita CA Corrente elettrica assorbita Gli schemi elettrici sono riportati dalla figura 9 al
16. rificare comunque che la distanza dalla parete o dal soffitto non sia inferiore a quanto riportato in figura 5 Utilizzare tasselli di fissaggio adeguati al peso della macchina e verificare che la superficie di fissaggio sia adatta allo scopo Munirsi di un idoneo mezzo di sollevamento consigliato il carrello elevatore per portare l apparecchio nella posizione di installazione appoggiando lo stesso sulla parte delle alette Gli attacchi idraulici non possono avere funzione portante e dunque non possono essere utilizzati per sostenere l apparecchio Il tubo di alimentazione va collegato all attacco superiore quello di scarico della condensa all attacco inferiore In figura 6 riportato un esempio di schema di collegamento idraulico in cui sulla tubazione di scarico condensa in uscita dalla macchina son inseriti un pozzetto di drenaggio un filtro a Y uno scaricatore di condensa un indicatore di passaggio e valvola di intercettazione severamente vietata la riproduzione anche parziale di questo manuale All copying even partial of this manual is strictly forbidden Aereo per i collegamenti idraulici utilizzare una chiave di tenuta per evitare la rotazione del collettore ed il conseguente danneggiamento della batteria di scambio termico figura 7 Una volta installata la macchina aprire e direzionare le alette deflettrici orientabili 6 COLLEGAMENTI ELETTRICI motori standard utilizzati sugli aerotermi serie AREO s
17. rying out any job on the fan heater Stop the fan and disconnect the unit from the power supply before working on it 9 TROUBLESHOOTING If the unit is not working properly before calling a service engineer carry out the checks indicated in the table below If the problem cannot be solved contact the dealer or service centre Problem Cause Solution RPM Motor revolutions Supply voltage Electrical input 3 lt Current absorption The wiring layouts are shown in the figures from 9 to 16 9 Delta connection to terminal block of 400 400 V YA motors high speed 10 Star connection to terminal block of 400 400 V YA motors low speed 11 Wiring diagram showing connection of 400 400 V motor with star delta selector YA Legend of wiring diagrams CST star triangle switch option F Protective fuse NOT SUPPLIED IL Switch NOT SUPPLIED M Motor 7 CHECKS BEFORE STARTUP Check the tightness of the plumbing connections Check the stability of the mounting brackets if the unit is installed on the wall the chains if the unit is ceiling mounted Make sure that the wiring is firmly secured Make sure that air has been eliminated from the heat exchanger Adjust the louvers as desired and switch on the unit to check that it works properly Always make sure that the fan turns in the correct direction ANTI CLOCKWISE viewing the fan heater from the rear figure 12
18. sta dal presente manuale non siano stati utilizzati ricambi originali I limiti di funzionamento sono riportati in fondo al presente capitolo ogni altro uso considerato improprio Nella scelta del luogo di installazione osservare i seguenti punti L apparecchio di riscaldamento non deve essere posto immediatamente sotto una presa di corrente installare l unit in ambienti con presenza di gas infiammabili non esporre l unit direttamente a spruzzi di acqua installare l apparecchio su pareti o soffitti che ne reggano il peso utilizzando accessori dedicati allo scopo e tasselli ad espansione adeguati Conservare l apparecchio nell imballo fino al momento dell installazione in modo da evitare infiltrazioni di polvere al suo interno Eseguire le operazioni di installazione manutenzione e pulizia in assenza di tensione Non modificare i cablaggi elettrici interni o altri particolari dell apparecchio Limiti di funzionamento Fluido termovettore vapore saturo Pressione vapore max 10 bar Temperatura vapore max 180 C Temperatura aria aspirata min 10 C max 40 C Tensione di alimentazione nominale 10 La gamma si compone di 6 modelli le cui caratteristiche sono riassunte in tabella di figura 1 dove RPM numero di giri motore QA portata aria PT potenza termica riscaldamento 1 bar 20 C Qs consumo vapore Tbs2 temperatura uscita aria Hmax altezza massim
19. the unit is installed in a room that is only occasionally used the temperature in the room itself must be kept above 0 C or else antifreeze must be added to the water to prevent it from freezing inside the coil Do not attempt to modify the internal wiring or other parts of the unit Operating limits thermal carrier fluid max steam pressure 10 bar max steam temperature 180 C Air inlet temperature 10 C to 40 C Power supply rated voltage 10 The range comprises 6 models whose features are summarised in the table of figure 1 where RPM number of motor revolutions air flow rate PT heating capacity steam pressure 1 bar 120 C Qs steam consumption Tbs2 Air outlet temperature Hmax maximum installation height LWA sound power level M sound pressure level distance 5m directional factor 2 AP66000409 01 4 AGalletti 3 UNIT DESCRIPTION The fan heater for steam operationare mainly made of the components listed below Prepainted sheet steel cabinet complete with heat proof ABS corner trim The cabinet is complete with adjustable aluminium louvers spring operated placed on the air outlet which allow an optimal distribution of the air within the heated room They are supplied with brackets for suspending the fan heaterto the ceiling or joining it to the mounting board for installation on the wall accessory High conductivity heat exchanger made with copper tu
20. tions use a tightening wrench to avoid the manifold rotation that may damage the heat exchanger figure 7 On completing installation open and direct the louvers 6 ELECTRICAL CONNECTIONS The standard motors installed in AREO fan heaters are of the closed type asynchronous three phase 2 speed motors 400 400 V star delta connection 400 400 V YA motors are equipped internally with a thermal cutout and speeds are selected by means of a normal star delta switch accessory CST The terminals of the cutouts are connected to the terminal block so that they can be used as protection in series with the coil of a contactor If the internal cutout is not used to protect the motor it will be necessary to provide a motor overload cutout set at a current that is 10 1596 higher than the current indicated on the unit rating plate Make the electrical connections with the power supply disconnected in accordance with current safety regulations All the wiring must be done by qualified personnel Check that the mains electricity supply is compatible with the voltage shown on the unit rating plate Scrupulously follow the wiring diagram provided according to the type of installation Each fan heater requires a switch IL on the feeder line with a distance of at least 3 mm between the opening contacts and a suitable safety fuse F The table in figure 8 shows the electrical specifications of the motors where M Number of poles of motor
21. vaggio delle alette avendo cura di non bagnare il motore elettrico e di asciugare bene il pacco alettatoprima di avviare l aerotermo E consigliato eseguire queste operazioni almeno una volta all anno prima dell inizio del periodo di riscaldamento Il motore elettrico non necessita di alcuna manutenzione in quanto di tipo chiuso e con cuscinetti autolubrificanti Ad ogni avviamento seguente una lunga sosta assicurarsi che non sia presente aria nello scambiatore di calore E necessario prestare attenzione durante le operazioni di manutenzione alcune parti metalliche possono provocare ferite dotarsi di guanti protettivi la manutenzione pu essere effettuata solamente da personale specializzato contattare il proprio rivenditore o installatore di fiducia Per motivi di sicurezza prima di compiere qualsiasi manutenzione o pulizia spegnete l apparecchio togliendo tensione dal sezionatore Qualora si debba intervenire su una macchina che sta lavorando con vapore consigliabile interromperne il flusso agendo sulle valvole di sezionamento e lasciare la ventola in moto per qualche minuto in modo da raffreddare tutte le parti metalliche prima di intervenire sull aerotermo Fermare il ventilatore e togliere tensione all apparecchio prima di intervenire sullo stesso 9 RICERCA DEI GUASTI Sel apparecchio non funziona correttamente prima di richiedere l intervento del servizio assistenza eseguite i controlli riportati nella tab