1. AXP1620 Installation and Use 6806800E23L AXP1620 Shelf Description Figure 2 7 Upper Front FTM Front View 2 3 Power Entry Modules PEMs The PEM is a Field Replaceable Unit FRU and can be replaced while the system is on but the power for the PEM being replaced PEM A or PEM B must be shut down at the external source Replacement can take place in under 30 minutes by a trained service person For important information on removing power before replacing a PEM refer to Recommended Power Off Procedures on page 86 and Power Entry Module PEM on page 87 The PEMs are accessible from the rear of the shelf and connect to the power entry module connectors on the backplane A removable plastic housing covers the power feeds and returns to prevent accidental shorting The PEM also features an injector ejector handle that provides the hot swap mechanism for signalling the state of the PEM prior to removal Each PEM powers two separate power domains A and B and each domain supports two 80A power rails to supply power to the AdvancedTCA slots AXP1620 Installation and Use 6806800E23L 63 AXP1620 Shelf Description The PEMs are hot swappable and will not cause a fault when one is removed for replacement Two PEMs are required to support 2N 1 redundancy If your system is configured for redundant operation using two power feeds they operate in load sharing where the total load is equal to or less than what on
2. 00 c cece ete c cence ee enn e ence enneees 109 5 12 2 1 PEM Upgrade Sample Output 0c cece eee eee eee eens 110 5 12 3 Shelf Manager Firmware Upgrade cece e cece e teen eee eeeeeeneees 111 5 12 3 1 Establishing Network Connectivity to the SAM eee eee ees 112 5 12 3 2 Update ShM Firmware onthe SAM cee cence eee e ne eee ees 113 6 FRU installation 2 er ees 115 Deli OVEIVICW an none ee ae an ee 115 6 2 Installing RTMs Blades and SAMS 0 cece cece cece e een ene e tent ee ene nennen 115 6 2 1 Module Installation and Removal 00 cece cece eee e eee ee ee ee nee nen 116 6 2 1 1 Installing the RTM 0 cece cece cece cence ene eee ee eneees 116 6 2 1 2 Removingthe RTM ccc cece cece cece eee e eee essen nenn 121 AXP1620 Installation and Use 6806800E23L 5 Contents 6 2 2 Node Blade Installation and Removal 00 c cece eee eect ence nee eens 123 6 2 2 1 Installing the Node Blade eee eee eect e eee t nee eee 123 6 2 2 2 Removing the Node Blade ccc eee eee eee eee n ee nnn 126 6 2 3 Installing and Removing the Shelf Management Alarm Module 127 6 2 3 1 Non Powered System cc ccc cece cence teen e nee e eens eens 128 6 2 3 2 Powered System cece cece cece ee ence eee teen een nenne nenn 129 5 3 Unused Slots sense en 131 6 4 Installing Power Entry Modules 0 cece cece
3. NOTICE There is one earth ground located at the back of the shelf There are three ESD bonding points two on the front and one on the back of the shelf AXP1620 Installation and Use 6806800E23L 97 AXP1620 Shelf Installation 5 4 Installing the Shelf The AXP1620 can be mounted in a 23 EIA or 600mm ETSI frame using front mounting brackets Using rear mounting brackets is recommended for all frame types when installed in a Central Office Environment Front or rear mounting brackets are not shipped with this product For assistance with the acquisition or design of mounting brackets for your particular application please contact your Artesyn representative Do not mount a single shelf at the top of the rack A top heavy rack can tip causing damage to equipment and injury to personnel Do not use the FTM handles or PEM handles for lifting the shelf Make sure you have the appropriate equipment to safely lift and mount the shelf securely To avoid personal injury or damage to the equipment use two persons for the installation procedure 5 4 1 23 EIA Rack Cabinet Installation Front mounting brackets are required to attach the shelf to an EIA 23 frame 1 Locate the standard mounting hole and slot locations on the front mounting flanges on the AXP1620 shelf 2 Fasten the mounting brackets to the back side of the front chassis flanges using M6 screws x 12mm at each of the 5 locations 3 Be sure to mo
4. cece eee c ccc cc e nee cece cece eee neeeneeeenetenes 82 A AXP 1IGZ0 Operations ssc cicccnccccccs nennen 85 4 1 2OVENIEW ne een 85 4 2 Recommended Power On Procedures cece cece e cee eee ence eee ee eeeeeee nenne 85 4 3 Recommended Power Off Procedures 0c cece cece c eet eet eee nee eee eens 86 4 4 Emergency Power Off Procedures cece ccc e ete c ene teen nee e eee esse nenne 86 4 5 Power Entry Module PEM 00 e cece cece cece teen een ence e ete eee eeeneeees 87 4 3 1 DEscriplion 2 n ohne een 87 4 5 2 PMC Eirevitiyaransn ee sep 88 4 6 Fan TrayiModules crne see ee ee nee 89 4 6 1 DESeriplionensenksr ears ates enlskne nee ES E EEREN ASS 89 4 6 2 Cooling Budget 0 cee cece eee e eee eee tee nennen nenn 90 4 63 IPMECireuityv een ne ee bare 90 4 7 AirFilter Maintenance 2c2eeeseeseeeseneseeesneeseeseneeseesenesseesseesnnnenee 91 4 8 CleaningtheAlrFilter ame reeds eabethiaebeveo serenaded terde ES 91 4 8 1 Storing the Filter sia dsiecese Pace aiankia als cecineinte ri ernt Gis Mig gle ware nr 92 4 AXP1620 Installation and Use 6806800E23L Contents 5 AXP1620 Shelf Installation ua 93 9 1 MOVEIWIOW eretti tiene lene anecuce pre Dia AE E E EEE E ann 93 5 2 Shelf Physical Characteristics 0 cece ccc ene ene e ene ence been ences 93 5 3 Installation Prerequisites ccc eee nen eee tenet ene nennen 94 5 3 1 Equipment You Will Need 0 ieee ence ee
5. Covering unused slots This section provides information how to cover empty slots Installing power components This section provides information about how to install and remove Power Entry Modules Installing fan trays This section provides information about how to install and remove upper and lower fan trays Installing an air filter This section provides information about how to install and remove an air filter Installing cable management This section provides information about to install the cables of the system secure 6 2 Installing RTMs Blades and SAMs The following sections provide the information needed to install RTMs AdvancedTCA blades and SAMs Installation Sequence of RTMs and AdvancedTCA Blades If you are going to install an RTM and an AdvancedTCA blade you have to regard the following sequence First install the RTM then install the matching AdvancedTCA blade Otherwise the blades and RTMs will be damaged AXP1620 Installation and Use 6806800E23L 115 FRU Installation 6 2 1 6 2 1 1 116 Module Installation and Removal The RTM can be installed into a powered or nonpowered system RTM Damage Installing the RTM with other blades than the ones designed for it may damage the RTM and the front blade Only install the RTM with the correct front blade Damage of Circuits Electrostatic discharge and incorrect RTM installation and removal can damage circuits or shorte
6. This is the normal upgrade sequence 3 Upgrading the FPGA firmware on the SAM AXP1620 Installation and Use 6806800E23L 111 AXP1620 Shelf Installation 5 12 3 1 112 4 The startup logic following the root file system upgrade automatically detects the need to upgrade the FPGA If an upgrade is necessary the startup logic loads the FPGA and automatically reboots the ShM again If this occurs you should note a delay of approximately 5 8 minutes while this download occurs Updating the default U boot environment variable configuration The upgrade procedure preserves all U boot environment variables No special procedures are necessary Start the following sequence of operations with the backup Shelf Manager Establishing Network Connectivity to the SAM The list below outlines the different actions required to enable and use the front panel Ethernet interface on a SAM If the upgrade is being performed over the backplane Ethernet interfaces from one of the hub boards skip these steps 1 2 Login to the SAM front panel serial console using the id root and password root Set the environment variable that defines the IP address allocated for the SAM s front panel Ethernet interface setenv ipladdr W X Y z substituting your address ifconfig ethl W X Y Z If your file server for Artesyn files is on a different subnet route add default gw W X Y z you will need to do this each time you reboot If you
7. amp Base Interface Diebe J10 J10 J10 istribution Zones amp Shelf Mangement Slot Backplane Slot ID Logical Slots SAMA PEMA Shelf Management Power Entry Alarm Module Module SAM B Upper FTM Lower FTM PEMB Shelf Management Fan Tray Fan Tray Power Entry Alarm Module Module Module Module 1 6 Operating Systems The AXP1620 comes installed with the following software e Wind River PNE LE e Enhanced Basic Blade Services BBS For more information contact your Artesyn sales representative for other software products for your configuration 48 AXP1620 Installation and Use 6806800E23L Platform Architecture 1 7 Remote Management and Maintenance The AXP1620 supports remote critical management and maintenance procedures This eliminates the need for on site maintenance personnel to handle routine maintenance tasks A standard Telnet connection for remote access to networked functionality provides the ability to e Upgrade IPMI firmware flashed on the SAMs PEMs FTMs node and hub blades e Upgrade BIOS e Access in service application software upgrades e Access IPMI event logs for performance monitoring e Access custom designed in functionality or event logs AXP1620 Installation and Use 6806800E23L 49 Platform Architecture eee EEE 50 AXP1620 Installation and Use 6806800E23L Chapter 2 AXP1620 Shelf Description NL 2 1 2
8. 100 and follow these steps This procedure assumes that the PEMs are preinstalled in the shelf AXP1620 Installation and Use 6806800E23L 103 AXP1620 Shelf Installation Procedure Have the following tools on hand before you begin these steps standard Phillips screwdriver nut driver torque wrench multimeter and lug kit 1 Locate the target power input cable s terminals at the branch circuit or power distribution unit Open the external circuit breakers that provide DC feed power to the PEM 2 Lock and tagout the circuit breakers on the branch circuit or power distribution unit Cables may or may not be preinstalled at the branch circuit or power distribution unit If the DC power cables are not connected to the branch circuit or power distribution unit connect the power cables to the PEMs before connecting the DC power cables to the external power source If the DC power cables are connected to the branch circuit or power distribution unit a qualified service person must confirm that the power to the cables is terminated off before continuing the steps to attach the cables to the PEMs In either case use a Multimeter to check the PEM end of the terminals to confirm there is no power present 3 Using the appropriate tool carefully remove the plastic covering over the terminal blocks 4 Confirm that there is no power to the PEM lug bolts Using a multimeter measure between the two lugs and then measu
9. 1000BASE BX to the fabric interface of a PICMG 3 1 compliant blade Figure 1 1 Fabric Option 1 2 and 3 Logical Slots 1 3 5 7 9 11 13 1 5 4 6 8 10 12 14 16 2 Update Channels 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Physical Slots The fabric interface switch is also extended outside the AXP1620 shelf through eight external connectors on the RTM 1 4 3 IPMINetwork The Intelligent Platform Management Interface IPMI is based on a redundant radial topology Redundant IPMI networks are supported by the Shelf Management Alarm Module SAM to manage the shelf resources 46 AXP1620 Installation and Use 6806800E23L Platform Architecture 1 4 4 1 5 The SAM is the center of the IPMI network hubs are the center of the Base Interface network The SAM connects to all slots in the shelf and monitors and reports on the content of the AXP1620 The SAM collects environmental data from sensors within the shelf and can assist high availability software to determine when a failover is necessary due to hardware removal or environmental changes such as an over temp condition The SAMs contain the Shelf Management Controller ShMC which polls all devices resident to the shelf and collects the FRU data records for all the components The SAM also manages non IPMI devices for the shelf and performs environmental monitoring of the temperature and voltage Using the PICMG 3 0 standard
10. 6806800E23L Safety Notes Injuries or Short Circuits Blade or Power Supply In case the ORing diodes of the blade fail the blade may trigger a short circuit between input line A and input line B so that line A remains powered even if it is disconnected from the power supply circuit and vice versa To avoid damage or injuries always check that there is no more voltage on the line that has been disconnected before continuing your work Expansion System Overload To avoid an overload of the system check the total power consumption of all components installed see the technical specification of the respective components Ensure that any individual output current of any source stays within its acceptable limits see the technical specification of the respective source Loss of Safety Compliance Using of Additional Plug in Blades By using additional plug in blades it may be possible that the system may be no more compliant to safety and EMC regulations The system integrator has to ensure that the compliancy is guaranteed Exchanging PEMs Personal Injury through Electric Shock and Burning Touching the PEM power input terminals with metallic objects on your hands wrists or hanging from your neck may lead to serious injuries like burns or amputations Do not wear any metallic attire or commodity on your hands wrists or hanging from your neck when working at the power input terminals or power input cables Be extremely careful wh
11. 7 5 2 7 5 2 1 Shelf Management Alarm Module Redundancy Control The ShMM 1500R supports redundant operation with automatic switchover using a redundant ShMM 1500R In a configuration where two ShMM 1500Rs are present one acts as the active shelf manager and the other as a standby Both ShMM 1500Rs monitor each other and either can trigger a switchover if necessary The ShMM 1500R provides a number of hardware redundancy signals on the CN1 connector The HRI is implemented using the FPGA device Hardware Redundancy Interface The hardware redundancy signals of the ShMM 1500R are implemented as follows e Cross connected ShMM 1500R present input PRES_R and output PRES_L e Cross connected ShMM 1500R status 0 input SHMM_STATUSO_R and output SHMM_STATUSO_L e Cross connected redundant ShMM 1500R status 1 input SHMM_STATUS1_R and output SHMM_STATUS1_L e Active output ACTIVE that can be used on the ShMM 1500R carrier to enable interfaces that must be exclusively driven by the active ShMM 1500R e Bi color status LED Note that the ACTIVE signal is intended for use ona carrier and is not connected directly to the peer ShMM through the backplane The cross connected ShMM 1500R status signals are asynchronous serial bit streams that are transmitted to the peer ShMM by the FPGA and communicate the following information Health status Switchover Requests PRES_R state Active state watchdog timer status parity and other T
12. Engineer Federal Communications Commission Field Replaceable Unit High Availability am gt HS Hot Swap ID Identifier IEC International Electric Code IEEE Institute of Electrical and Electronics Engineers IPM Intelligent Platform Management IPMB Intelligent Platform Management Bus IPMC Intelligent Platform Management Controller Intelligent Platform Management Interface Mezzanine Management Controller Network Equipment Building System National Electric Code OEM Original Equipment Manufacturer PCI Peripheral Component Interconnect PEM Power Entry Module 14 AXP1620 Installation and Use 6806800E23L About this Manual Abbreviation Definition PICMG PCI Industrial Computer Manufacturers Group RMCP Remote Management Control Protocol RoHS Restriction of Certain Hazardous Substances RTM Rear Transition Module SAM Shelf Management Alarm Module SCSI Small Computer System Interface SELV Safety Extra Low Voltage ShM Shelf Manager ShMC Shelf Management Controller SNMP Simple Network Management Protocol TNV 2 Telecom Network Voltages without overvoltage TPE Twisted Pair Ethernet UL Underwriters Laboratories VCCI Voluntary Control Council for Interference WEEE Waste from Electrical and Electronic Equipment Conventions The following table describes the conventions used throughout this manual Notation Description 0x000
13. FTM Upper FTM Lower FTM Upper FTM FTM 2 FTM 1 FTM 2 FTM 1 AXP1620 Installation and Use 6806800E23L 53 AXP1620 Shelf Description 2 3 2 4 2 5 54 Enclosure The AXP1620 shelf consists of a formed 13U sheet metal card cage with structure and support for the backplane PEMs FTMs SAMs and 16 card slots Figure 2 1 on page 52 provides a front view of the shelf The enclosure mounts in a 600mm x 600mm ETSI frame relay rack or optional EIA 23 rack Mounting holes for bezel brackets are provided which allows the use of power supply or card cage customer designed bezels See Appendix A Related Specifications for details on the physical characteristics of the enclosure Power Consumption The following table shows the total power requirements for the shelf Power consumption breakdown is shown in the next table Table 2 1 AXP1620 Shelf Power Requirements Amps per Fan Maximum Total Watts AXP1620 Shelf without AdvancedTCA 850 Watts assumes the shelf is configured Blades with 2 SAMs 2 PEMs and all FTMs running at full speed Shelf Ground Configuration The AXP1620shelf was tested in the default configuration of logic ground and shelf ground connected and does not connect 48VDC Return with Shelf Ground The Centellis 4620 platform has been tested in the default configuration and complies with safety and regulatory standards As a compliant AdvancedTCA shelf the AXP1620 allows system integrators at the
14. RS 232 Serial Interface The SAM provides an RS 232 interface on the face plate connector using an RJ 45 connector The connector is routed to the serial port of the shelf manager mezzanine The default baud rate is 9600 8 N 1 Pin assignments for this connector are Table 7 1 RJ 45 Serial Port Connector Signal Direction DSR Input DCD Input DTR Output GND RXD Input TXD Output CTS Input RTS Output AXP1620 Installation and Use 6806800E23L Shelf Management Alarm Module 7 4 3 7 4 4 The SAM provides an RS 232 interface on the alarm display panel at the front of the chassis utilizing a mini D 9pin connector The connector is routed to the second serial port of the shelf manager The baud rate is 115200 8 N 1 and cannot be changed Pin assignments for this connector are Table 7 2 Alarm Display Panel ADP Serial Port Connector Pin Signal Direction 1 No Connect RXD Input TXD Output N gt w No Connect SigGnd No Connect No Connect 5 6 7 8 No Connect to No Connect Master Only I C Bus The SAM provides a number of I C devices using the master only I C bus of the shelf manager mezzanine The master only IC bus is used internally on the mezzanine for the real time clock and EEPROM devices Additional I C devices connected to the bus on the SAM are used for the following functions e System hardware monitoring and control e GPIO extension
15. SAM They share signals across the AdvancedTCA backplane that allow them to coordinate their redundant operations The SAM provides access to the IPMCs for the Power Entry Module PEM and the two fan trays through the IPMB The SAMs use IPM Sentry Shelf Manager software for system management Refer to SAM Software on page 163 for further information The SAM also provides these operations for the AXP1620 shelf e Control for the activation deactivation of AdvancedTCA blades e Handles E Keying e Control of Power Management e Monitoring of overall system and blade level health e Logging for critical system events AXP1620 Installation and Use 6806800E23L 143 Shelf Management Alarm Module 7 2 144 e Support for the Command Line Interface CLI to access shelf information for Shelf blade population List of sensors and sensor values Sensor threshold settings System events Shelf health e Control of chassis cooling management fan levels For additional information on the above operations and the Command Line Interface refer to the AXP 1440 AXP1620 Subsystem IPMI Programmer s Reference guide and the Pigeon Point Shelf Manager External Interface Reference Release 2 5 3 respectively Features The SAM is based on the Pigeon Point Systems ShMM 1500R and Freescale MPC8343 System On a Chip SOC The following lists the features of the SAM e High density small 92 mm x 50 8 mm form factor e Fully compliant with
16. SAM refer to Chapter 7 Shelf Management Alarm Module on page 143 AXP1620 Installation and Use 6806800E23L 127 FRU Installation eee TI The following figure shows the face plate of the SAM 1500R shelf management alarm module Figure 6 1 SAM 1500R O O o 2o 2 0 ie 0 O D O CONSLOE Damage of Circuits Electrostatic discharge and incorrect blade installation and removal can damage circuits or shorten their life Before touching the blade or electronic components make sure that you are working in an ESD safe environment 6 2 3 1 Non Powered System This section describes the installation procedure for the SAM in non powered systems 128 AXP1620 Installation and Use 6806800E23L FRU Installation 6 2 3 2 Installation Procedure To install a SAM in a non powered shelf proceed as follows 1 2 5 Put on an ESD wrist strap Connect the strap to the shelf by attaching the front or rear ESD jack Insert the module into the shelf by placing the top and bottom edges of the module in the card guides of the shelf Ensure that the guiding module of shelf and board are aligned properly The alignment pin facilitates the insertion and prevents bent pins Slide the module into the shelf and rotate the ejector handle upward until it snaps into place Screw in the captive screw hand tigh
17. Shelf AIlOW 244s s c4 septa tied ee ea 80 Figure 3 3 Planning Checklist 1 2 4 2 ee ea ss 82 Figure 3 4 Planning Checklist 2 see een u eee ead Hee eee 83 Figure 5 1 Rack Mounting Dimensions 0 eee eee eee eee eee e nee n een eeeees 95 Figure 5 2 Shelf Airflow Diagram 0 cece cece e eee e eee e eet n cence ee en eens 96 Figure 5 3 Placement of Grounding LUG 0 cece cece cece tee eee e eee eeeennenes 100 Figure 5 4 DC Power Connection Detail cee cece eee ee eee ene e een eeaes 102 Figure 6 1 SAM T500R ee 128 Figure 6 2 Upper Rear FTM Ejector Handles and LEDs 0 ce eee eee eee eee ene 136 Figure 6 3 Lower Front FTM Ejector Handles and LEDs eee eee e eee eens 138 Figure 6 4 Position of the Fan Filter 2 0 0 ccc ccc eee eee eee nee eee eneenes 141 Figure 7 1 Block Diagram Of SAM 0 cece ccc een ence e eee eee e ee eeneeees 146 Figure 7 2 SAM Face Plate cs ccct5 peta ea k EEE oraaa eee geet ee ends 147 Figure 7 3 SAM HRI Interconnection 1 0 cece cece cece eee ne en en 156 Figure 7 4 Interhub Slot and Shelf Manager Connectivity 0 eee eee eee eee 158 AXP1620 Installation and Use 6806800E23L 9 List of Figures m 10 AXP1620 Installation and Use 6806800E23L List of Tables ee Table 2 1 AXP1620 Shelf Power Requirements 0 eee eee cece e eee eee e een e neta enae 54 Table 2 2 Slot Connector Description 0 cece cece
18. Zone Locations ona Blade cece cece nee eee e eee e eee e teenies 60 2 7 Fan Tray Modules FTMs cece cece cece cence eee cence nee e nent eenneeeneeanes 62 2 8 Power Entry Modules PEMs 0 0 0 cece cece e eee e eee n eee e eee nennen 63 2 9 Stationary Boards aus td wees caleba yee eke etal EEEE ies Iahes en 66 AXP1620 Installation and Use 6806800E23L 3 Contents 2 10 Standard Compliances 0 cece ccc cence nent rererere rrene e seen nenne 67 2 11 WEEECompliance u ee en 69 3 Site PRepahatiOM sas cicccsawaocinsctrneaaariew rear 71 3 1 OVERVIEW ee ih tienes re Re SA 71 3 2 Site Planning Considerations 0 cece ccc ene nee eee n eee n eee eeennees 71 3 2 1 Receiving and Unpacking the SysteM 00 cece eee nunnur errenneren 71 3 2 2 Site and Installation Planning 00 cc cece cece eee eee een ee ee een 73 3 2 3 Requirements 2 whee eee daw eda a eee bs 73 3 2 3 1 Environmental Requirements cece eee eee ee een een eeee 73 3 2 3 2 Power Requirements cc cece eee eee eect E 76 3 2 4 Dimensions and Weight cece ccc cece eee e ence eee ernennen 77 3 2 5 MOUNTING Options iori reL NEEESE REENE ERAS EREE 78 3 2 6 Airflow Requirements ccc cece eee eee e ene ence eee ee seen 79 3 2 7 Acoustic Noise Control cece cece eee e rence nee e ence en en en enene nen 81 3 3 Site Planning Checklists 0
19. are not field replaceable e Backplane e Upper Fan Interconnect board provides power and signaling from the backplane to the FTM distribution board e FTM distribution board provides the signal and power connections to the upper fan tray modules from the backplane e Alarm Display Panel ADP contains the shelf FRU SEEPROMs telco alarm indicators and serial console ports for the SAM The following table shows the ADP telco alarm indicators Table 2 9 ADP LED Status Indicators Alarm Display Panel LED LED Color State State Condition Critical alarm CRT Red On Active Major alarm MAJ Red On Active Minor Alarm MIN Yellow On Active Power PWR Green On Power Present AXP1620 Installation and Use 6806800E23L AXP1620 Shelf Description 2 10 Standard Compliances The Centellis 4620 AdvancedTCA platform complies with the safety and regulatory standards as shipped from the factory It is possible to use this product with other components that produce a system not in compliance with system guidelines Since Artesyn Embedded Technologies cannot anticipate what equipment may be used with this enclosure or how it may be used the responsibility for designing a system that conforms overall to the safety requirements EMI RFI emission limits and other applicable standards rests entirely with the system integrator and installer Table 2 10 Standard Compliances PICMG3 0 R1 0 Defines mechanics board dimensions power
20. distribution PICMC1 5 1 power and data connectors and system management UL 60950 1 Safety Requirements legal EN 60950 1 IEC 60950 1 CAN CSA C22 2 No 60950 1 CISPR 22 EMC requirements legal on system level CISPR 24 predefined Artesyn Embedded Technologies system EN 55022 EN 55024 EN 300386 FCC Part 15 Industry Canada ICES 003 NEBS Standard GR 63 CORE Environmental Requirements NEBS Standard GR 1089 CORE ETSI EN 300 019 series ETSI ETS 300 753 ETSI EN 300 132 2 Power requirements Directive 2011 65 EU The product has been designed to meet the directive on the Restriction of the use of certain Hazardous Substances in electrical and electronic equipment RoHS AXP1620 Installation and Use 6806800E23L 67 AXP1620 Shelf Description To fulfill the requirements of Telcordia GR 1089 R4 14 use Shielded Twisted Pair STP cables Vly Sf grounded at both ends to connect to the Ethernet ports The following figure contains the Declaration of Conformity for AXP1620 Figure 2 10 Declaration of Conformity EC Declaration of Conformity According to EN 17050 1 2004 Manufacturer s Name Artesyn Embedded Technologies Embedded Computing Manufacturer s Address Zhongshan General Carton Box Factory Co Ltd No 62 Qi Guan Road West Shiqi District 528400 Zhongshan City Guangdong PRC Declares that the following product in accordance with the requirements of 2004 108 EC 2006 95 EC 2011 65 EU a
21. e eee ene eee n ene een nennen 131 6 4 1 Tools You Will Need 0 2 eee cece eee ne ene nee e eee e ee eneeneees 132 6 4 2 Replacing the PEM u nennen nee ounces 132 6 5 Upper and Lower Fan Tray Modules 2c cece cece eee ence eect teen een rennen 135 6 5 1 Removing the Upper FTM 0 cece eee ence cece eee e eee eee eee nennen 136 6 5 2 Installing the Upper FIM eee e cece eee cent ene nee e ete e ee en ences 137 6 5 3 Removing the Lower FTM 0 cece eee eee e tenn nee e eee ee eneeneees 138 6 5 4 Installing the Lower FTM cece cece e cece eee tenet nee e eee eeeeneeeeees 139 6 6 Replacing the Fan Filter 0 cece cece cece e een ene eee e ene eeeeeeenes 139 7 Shelf Management Alarm Module ccc ccc cece ccc cece eee e ee ns ns n sn n nn nenne 143 1 0 SOVEIVieWie re een 143 1 22 Featutesa een ae 144 7 3 SAM Diagram and Face Plate Layout 0 cece eee eee e nen e ene nennen 146 7 4 Functional Description ccc cece cece cece e eee e teen eee n scene eeeaeennes 147 7 4 1 IPMB Connectivity nn aa aba 148 1 4 2 RS 232 Serial MPCMACE con sien ela 0 een EEEE EE EA 148 7 4 3 Master OnlyI2CBus 0222222eseneeeeneeereneenenenenennenenenen nennen 149 7 4 4 Shelt FRU SEEPROM u 20 a 149 71 45 SAMILEDS u rinine een ea een 150 TASA HOLSWaBLED nee pe a a 150 7 4 5 2 SAM ADP Status LEDS 2c enseeeeeneeneeenenenen nennen nenn 151 7
22. eine Erdung durchf hren m ssen da hier ein hoher Ableitstrom vorhanden sein kann AXP1620 Installation and Use 6806800E23L 35 Sicherheitshinweise Hoher Ableitstrom kann zu Verletzungen f hren Stellen Sie deshalb vor Anschluss des Systems an ein Telekommunikationsnetz unbedingt eine Erdungsverbindung her Besch digung des Systems Falsche Jumper Einstellungen k nnen dazu f hren dass das System nicht mehr funktioniert ndern Sie deshalb nie die Einstellungen der Jumper Board und RTM Installation 36 Besch digung des Boards Ber hren Sie das Board oder elektrische Komponenten in einem nicht ESD gesch tzten Bereich kann dies zu einer Besch digung des Boards f hren Bevor Sie Boards oder elektronische Komponenten ber hren vergewissern Sie sich dass Sie in einem ESD gesch tzten Bereich arbeiten Reihenfolge bei der Installation von RTMs und AdvancedTCA Boards Die folgende Reihenfolge mu bei der Installation von RTMs und AdvancedTCA Boards eingehalten werden Installieren Sie zuerst das RTM und erst danach das passende AdvancedTCA Board Ansonsten k nnen RTM oder Board besch digt werden Besch digung des Boards oder Systems Wird ein Board in den falschen Steckplatz im System gesteckt k nnen sowohl das Board als auch das System besch digt werden Installieren Sie Boards deshalb ausschlie lich in daf r vorgesehene Steckpl tze Besch digung des RTMs oder Boards Wird das RTM ausgebaut w hrend die Pa
23. for one PEM is shown below upgradepem peml tmp pem1620 img Upgrading upgradefw I dev i2c5 0x66 tmp pem1620 img BMR AVR firmware upgrade utility Pigeon Point Systems c 2004 Upgrade interface IPMB device dev i2c5 options 0x66 Firmware upgrade image tmp pem1620 img Preparing Master AVR for programming OK Programming 39703 bytes to Master AVR at 000000 100 Preparing Slave AVR for programming OK Programming 7008 bytes to Slave AVR at 000000 100 upgradefw returned 0 bin upgradepem Upgrade complete Verify firmware version clia ipmc v 0x66 Pigeon Point Shelf Manager Command Line Interpreter 66 Entity Oxa 0x60 Maximum FRU device ID 0x01 PICMG Version 2 1 Hot Swap State M4 Active Previous M3 Activation In Process Last State Change Cause Normal State Change 0x0 Device ID 0x01 Revision 0 Firmware 1 03 ver 1 0 3 IPMI ver 1 5 Manufacturer ID 0000al Product ID 005e Auxiliary Rev 00000018 Device ID String PEM1620 Global Initialization Oxc Power State Notification Oxc Device Capabilities 0x29 Controller provides Device SDRs Supported features 0x29 Sensor Device FRU Inventory Device IPMB Event Generator AXP1620 Installation and Use 6806800E23L AXP1620 Shelf Installation 5 12 3 Shelf Manager Firmware Upgrade There are three files which contain the ShM firmware sentry shmm1500 kernel sentry shmm1500 rfs and
24. fters da die Zentrifugalkr fte noch wirken und somit die Handhabung erschweren k nnen AXP1620 Installation and Use 6806800E23L Sicherheitshinweise Verkabelung Kabelf hrung Verletzungsgefahr Ver ndern Sie nie die von Artesyn ausgelieferte Verkabelung des Systems Stellen Sie sicher dass die Verkabelung schon existierenden Kabelf hrungen folgt und bestehende oder hnliche Befestigungen verwendet berpr fen Sie nach der Erweiterung der Verkabelung ob das System ordnungsgem arbeitet Reduzieren Sie die Verletzungsgefahr indem Sie Kabel so verlegen dass niemand dar ber stolpern kann Verletzungsgefahr durch Stromschlag Durch das Ber hren von Kontakten und Kabeln w hrend des Betriebs k nnen Sie einen elektrischen Schlag bekommen Schlie en Sie in jedem Fall aus dass Personen durch einen elektrischen Schlag verletzt werden k nnen indem Sie sicherstellen dass Kontakte und Kabel des Systems w hrend des Betriebs nicht ber hrt werden k nnen Falls Sie Fragen bez glich der Verkabelung haben wenden Sie sich an die f r Sie zust ndige Gesch ftsstelle von Artesyn Besch digung der Kabel Werden Kabel geknickt kann das Kabel besch digt werden und der Datentransfer nicht mehr stattfinden Stellen Sie sicher dass Kabel nicht geknickt werden RJ 45 Stecker Besch digung des Systems Bei den RJ 45 Steckern die sich auf den Boards befinden handelt es sich entweder um Twisted Pair Ethernet TPE oder um E1
25. is calculated using the following algorithm S1 72 77 Tiniet AXP1620 Installation and Use 6806800E23L 153 Shelf Management Alarm Module 154 Using the above algorithm at 40 C ambient the cooling algorithm adjusts the fan speeds to maintain a deltaT rise in temperature at 15 C Table 7 7 Cooling Budget Ambient Temperature Temperature Rise Delta T 20 C Delta T 15 C 55 C Delta T 10 C The values for 1 S2 T1 and T2 are configurable In abnormal operating conditions that is when a blade thermal sensor is approaching or crossed its upper non critical threshold the SAM automatically adjusts the fan speeds to a point where all the blade thermal sensors are just below their upper non critical threshold minus a user configurable offset The dynamic minimum fan level is not used Each fan tray has six fan units and each fan unit has an inlet and outlet fan Fan speeds for all level settings are summarized in the next table Fan Level Speed in RPMs 1 1800 Inlet 1100 Outlet 10 10 2600 Inlet 1500 Outlet 10 2 3200 Inlet 2000 Outlet 8 0 30 3900 Inlet 2400 Outlet 8 40 4500 Inlet 2900 Outlet 5 50 5100 Inlet 3300 Outlet 5 60 5800 Inlet 3700 Outlet 5 70 6400 Inlet 4200 Outlet 5 5 8 7000 Inlet 4500 Outlet 5 9 7600 Inlet 5000 Outlet 5 8000 Inlet 5200 Outlet 5 0 0 AXP1620 Installation and Use 6806800E23L
26. is installed When fillers are used both the front and RTM filler must be in place Filler blades are available from Artesyn Installing Power Entry Modules The AXP1620 shelf supports two Power Entry Modules PEMs Since the shelf is equipped with a redundant power distribution system the removal of a single PEM does not interrupt system operation PEMs are accessible from the rear of the shelf Each PEM has EMI gaskets on all sides of the module that provide EMI shielding The following instructions describe how to replace a power entry module For further information on power entry modules refer to Power Entry Modules PEMs on page 63 AXP1620 Installation and Use 6806800E23L 131 FRU Installation 6 4 1 6 4 2 Tools You Will Need e Multimeter e Standard 2 Phillips head screwdriver e 7 16 Torque wrench e Nut driver torque nut to 50 in Ibs e AXP1620 DC Power Installation Kit PN 6706822A01 shipped with AXP1620 Replacing the PEM When replacing a PEM make sure you have a replacement PEM available Replacement can take place in under 30 minutes by a qualified service person PEMs are accessible from the rear of the shelf Replacing one PEM is done while the other PEM is in operation Having the PEM located in the shelf is critical to maintaining proper airflow and cooling of the shelf Steps in which a PEM is removed from a slot and reinserted should be completed within 3 minutes to maintain the shelf within sa
27. komplexes Produkt mit vielf ltigen Einsatzm glichkeiten handelt k nnen wir die Vollst ndigkeit der im Handbuch enthaltenen Informationen nicht garantieren Falls Sie weitere Informationen ben tigen sollten wenden Sie sich bitte an die f r Sie zust ndige Gesch ftsstelle von Artesyn Das System erf llt die f r die Industrie geforderten Sicherheitsvorschriften und darf ausschlie lich f r Anwendungen in der Telekommunikationsindustrie im Zusammenhang mit Industriesteuerungen und in der Entwicklung verwendet werden Es darf nicht in sicherheitskritischen Anwendungen lebenserhaltenden Ger ten oder in Flugzeugen verwendet werden Einbau Wartung und Betrieb d rfen nur von durch Artesyn Embedded Technologies ausgebildetem oder im Bereich Elektronik oder Elektrotechnik qualifiziertem Personal durchgef hrt werden Die in diesem Handbuch enthaltenen Informationen dienen ausschlie lich dazu das Wissen von Fachpersonal zu erg nzen k nnen dieses jedoch nicht ersetzen Halten Sie sich von stromf hrenden Leitungen innerhalb des Systems fern Entfernen Sie auf keinen Fall die Systemabdeckung Nur werksseitig zugelassenes Wartungspersonal oder anderweitig qualifiziertes Wartungspersonal darf die Systemabdeckung entfernen um Systemkomponenten zu ersetzen oder andere Anpassungen vorzunehmen Installieren Sie keine Ersatzteile oder f hren Sie keine unerlaubten Ver nderungen am System durch sonst verf llt die Garantie Wenden Sie sich f r
28. reach Are racks with sufficient space to install the system available Is suitable equipment available to lift the system into the rack al Ww Isthere enough space to run a system console terminal Isthe cable long enough to reach the system 6 Are the inlet and outlet of the fans and therefore the airflow not blocked Requirements Before and during system installation and operation you always have to ensure that the requirements listed in the following sections are met Environmental Requirements To ensure proper function of the system make sure that the environment in which the system is to be used fulfills the environmental requirements AXP1620 Installation and Use 6806800E23L 73 Site Preparation The environmental values must be tested and proven in the planned system configuration that is the delivered system and other third party products you want to integrate ly e Operating temperatures refer to the temperature of the air circulating at the air intake of the d system and not to component temperatures Some of the climatic values may exceed the specification of some system components for example hard disks As Artesyn cannot guarantee the functionality of third party products that are handled or operated out of their specifications the environmental conditions may be limited to the specifications of these components The following table lists the environmental requirements Table 3 1 Environmental C
29. the Active Shelf Manager specified by the IP address supplied in the command The Standby Shelf Manager floating RCMP address will be the exclusive OR of the least significant bit of that address If the IP address assigned with the set Lanconfig is odd the Standby Shelf Manager floating RCMP IP address will be 1 less than the active If the RCMP IP address for the Active Shelf Manager is even then the RCMP IP address for the Standby Shelf Manager will be greater by 1 For information on configuration of additional characteristics of the RMCP interface like subnet address and so on refer to Pigeon Point Shelf Manager External Interface Reference Switchover Signals A switchover takes place when the Standby SAM determines that the Active SAM is no longer operational The signs of this are The REMOTE_HEALTHY or REMOTE_PRESENT changes to FALSE This indicates that the peer SAM is no longer healthy or present e The TCP connection between the Active and the Standby SAMS closes The keep alive time out parameter for this connection is set to 1 second to recognize a malfunction of the Active SAM as quickly as possible In this case the Standby SAM waits for 3 seconds and then checks the state of the REMOTE_HEALTHY to make sure the connection is broken due to a failure of the Active SAM and not due to a communication failure If the Standby SAM detects that the Active SAM is still healthy it doesn t perform the switchover but instead reboots itse
30. the Restriction of Hazardous Substances RoHS directive e Ointerfaces available on a Tyco 220 pin 0 5 mm Free Height receptacle e 64 or 128 MBytes of DDR SDRAM with Error Correcting Code ECC support 266 or 400 MHz PowerPC superscalar RISC core with MMU and caches 32K 32K with parity e 32 or 64 MBytes of Flash e Hardware support for a reliable upgrade of software images in Flash e Dual IPMB with IPMB buffer controls for hot insertion and removal onto a live backplane e Dual serial interface at RS232 or CMOS levels one port with modem control AXP1620 Installation and Use 6806800E23L Shelf Management Alarm Module e Dual 10 100Mbit Ethernet using the integrated 802 3 controllers buffered by external onboard PHY layer devices e FPGA device on the PCI bus used to implement IPMB 0 the Shelf Manager oriented interfaces for hardware redundancy hot swap and carrier ID plus the ATCA Watchdog and a high speed serial interface for an alternate software redundancy interface between peer SOMM 1500Rs Three general purpose I C interfaces one with limitations for access to on carrier devices such as hardware monitors and the Telco Alarm interface e RTC backed by on carrier battery User SEEPROM e External interrupt inputs e User GPIO e SPI interface as an extension interface for on carrier devices PCl interface as an extension interface for on carrier devices e On carrier PLD interface e JTAG interface for softw
31. the air filter replacement must be cleaned out vacuumed from the fan tray prior to re installing the fan tray into the chassis 140 AXP1620 Installation and Use 6806800E23L FRU Installation Figure 6 4 Position of the Fan Filter 5 Lower the vane assembly and rotate the filter bracket into place 6 Reinstall the lower FTM using the procedure described in Installing the Lower FTM AXP1620 Installation and Use 6806800E23L 141 FRU Installation m 142 AXP1620 Installation and Use 6806800E23L Chapter 7 Shelf Management Alarm Module ee 7 1 Overview This chapter describes the AdvancedTCA Shelf Management Alarm Module hereafter known as the SAM which consists of the Shelf Management Controller SAMC and the Shelf Management Mezzanine Module ShMM which installs on the carrier blade Two SAMs are installed into two dedicated shelf manager slots located at the bottom rear of the AXP1620 16 Slot Shelf The SAM is hot swappable and the connectors are accessible through the face plate You will find the following information in this chapter e Features SAM Diagram and Face Plate Layout e Functional Description Hardware Monitoring and Control e Telco Alarm Functionality Hot Swap Interface Power SAM Software The SAM supports redundant operation by automatic switchover between two SAMs When two SAMs are present in a shelf one acts as the Active SAM and the other acts as a Standby
32. their trade name and is put on the European Union market after 13 August 2005 places a clearly identifiable mark on the equipment and that this mark signifies that equipment is to be reprocessed or recycled using authorized recyclers and processes This minimizes the disposal of unsorted municipal waste achieves a high level of separate collection of WEEE and ensures the environmentally sound disposal of electrical and electronic equipment placed on the market after 13 August 2005 To dispose of equipment marked with the WEEE symbol Artesyn Embedded Technologies has contracted with certified companies that can reprocess this equipment per European Union requirements Please visit the Artesyn web site or contact your Artesyn representative to find out who to contact and how to dispose of the equipment AXP1620 Installation and Use 6806800E23L 69 AXP1620 Shelf Description a 70 AXP1620 Installation and Use 6806800E23L Chapter 3 Site Preparation eee 3 1 Overview The following sections help you to prepare system installation Section Gives Information On Site Planning Considerations This section includes information on unpacking and inspecting the system requirements technical data and other information you need to know before you start system installation Site Planning Checklists This section provides checklists for site preparation 3 2 3 2 1 Site Planning Considerations This section provides
33. to notify any person of such revision or changes Electronic versions of this material may be read online downloaded for personal use or referenced in another document as a URL to an Artesyn website The text itself may not be published commercially in print or electronic form edited translated or otherwise altered without the permission of Artesyn It is possible that this publication may contain reference to or information about Artesyn products machines and programs programming or services that are not available in your country Such references or information must not be construed to mean that Artesyn intends to announce such Artesyn products programming or services in your country Limited and Restricted Rights Legend If the documentation contained herein is supplied directly or indirectly to the U S Government the following notice shall apply unless otherwise agreed to in writing by Artesyn Use duplication or disclosure by the Government is subject to restrictions as set forth in subparagraph b 3 of the Rights in Technical Data clause at DFARS 252 227 7013 Nov 1995 and of the Rights in Noncommercial Computer Software and Documentation clause at DFARS 252 227 7014 Jun 1995 Contact Address Artesyn Embedded Technologies Artesyn Embedded Technologies Marketing Communications Lilienthalstr 17 19 2900 S Diablo Way Suite 190 85579 Neubiberg Munich Tempe Arizona 85282 Germany Contents ee About thisiManial
34. to operate with commercial grade components 70 C ambient temperature typical Table 4 2 Cooling Budget Ambient Temperature Temperature Rise Delta T 20 C Delta T 15 C Delta T 10 C The following guidelines can assist in determining the cause of the cooling failure Also refer to Environmental Requirements on page 73 for important information regarding ambient temperature requirements during servicing e Ifa cooling failure occurs the failure may be caused by a failed fan or possibly a clogged filter Check the filter first before replacing the FTM see Air Filter Maintenance on page 91 For further information of nonrecoverable temperature events refer to the FRU Information chapter in the AXP1620 Subsystem IPMI Programmer s Reference IPMC Circuitry Preprogrammed FRU and SDR information reside on the FTMs and is accessible from the SAM through the I C bus FRU information can be found in the AXP1620 Subsystem IPMI Programmer s Reference listed in Appendix A Related Documentation AXP1620 Installation and Use 6806800E23L AXP1620 Operations 4 7 4 8 Air Filter Maintenance Air filters should be cleaned every 90 days or sooner depending on the conditions of the Central Office Environment Because Central Offices vary in physical location and cleanliness check your air filters every week after you first install your system In a dusty environment a filter may need cleaning more often than a f
35. your AXP1620 1 Verify that all shelf modules and associated data and control cables are properly configured and installed Make sure that all empty or unused slots contain an approved filler panel 2 Enable DC power at each external source branch circuit or power distribution unit 3 Verify that the shelf configuration s current loads do not exceed 200W slot for front side blades 25W slot for RTMs across the operating range of the equipment 4 Push the circuit breakers to the ON position They are located on the front of each PEM AXP1620 Installation and Use 6806800E23L 85 AXP1620 Operations 4 3 Recommended Power Off Procedures Procedure Follow these steps to shut down your AXP1620 1 Shut down all software operations and the operating system For shelves with independently running segments each segment must be shut down 2 Turn each circuit breaker on the front of PEM A and PEM B to the OFF position Step 2 removes the input power from the slots in the AXP1620 shelf only It does not remove power to the PEMs To remove power to these components refer to the next step 4 4 3 Disable the DC power at each of the external sources branch circuit or power distribution unit for both PEM A and PEM B 4 This completely removes power from the shelf and its subassemblies Emergency Power Off Procedures Procedure Read this caution and follow the next steps if it is necessary to remove power du
36. 00000 Typical notation for hexadecimal numbers digits are 0 through F for example used for addresses and offsets 0b0000 Same for binary numbers digits are 0 and 1 bold Used to emphasize a word Screen Used for on screen output and code related elements or commands in body text Courier Bold Used to characterize user input and to separate it from system output AXP1620 Installation and Use 6806800E23L 15 About this Manual Notation Description Reference Used for references and for table and figure descriptions File gt Exit Notation for selecting a submenu lt text gt Notation for variables and keys text Notation for software buttons to click on the screen and parameter description Repeated item for example node 1 node 2 node 12 Omission of information from example command that is not necessary at the time being Ranges for example 0 4 means one of the integers 0 1 2 3 and 4 used in registers l Logical OR A Ee Indicates a hazardous situation which ifnot avoided A could result in death or serious injury Pettesitettitstittstetttrittttstettrrsi test tested URN HUREN NENNEN NINO III AXKHUKKUNKKUKKKUNKKUKKKUNKKHUKKUUKKANKKANKKHAKKEN Indicates a hazardous situation which if not avoided may result in minor or moderate injury KRKICHUI ICH EICH ICH IN MCKRA AARNE NR NLICHEH LICH MICH ICH MMAR JOU 2 6 8 2 2 8 5 2 2 6 3 2 2 8 9 OOOO OOOO OOOO IG KAXAAKAAAKAAXKAAXKAAKKAAKKA
37. 163 A Related Documentation eaten ei Neds a ee 167 A 1 Artesyn Embedded Technologies Embedded Computing Documentation 167 A 2 Related Specifications 0 cece ce ccc eee e erent nen eee n een ee ee ne seen nenne nen 168 AXP1620 Installation and Use 6806800E23L 7 Contents m 8 AXP1620 Installation and Use 6806800E23L List of Figures ee Figure 1 1 Fabric Option 1 2 and3 1 0 eee cece eee srera diid katiae it 46 Figure 1 2 Location of Zones 1 2 aNd 3 2 1 eee eee eee eee eee een nee n ee aees 48 Figure 2 1 Front Shelf VieW u ner se eek 52 Figure 2 2 Rear Shelf View nee eeciee td eats 53 Figure 2 3 Backplane Power Segments 2 0 se cece cee n eect ete tn eee eneees 56 Figure 2 4 Blade Slot Connectivity 0 cece cece eee eee e tenet nee ee neeeees 61 Figure 2 5 Hub Slot Connectivity 22 0 ccc eee eee eee eee been ene en eeeees 61 Figure 2 6 Lower Fan Tray Module Front View cece cece ence eee cence aces 62 Figure 2 7 Upper Front FTM Front View 1 00 0 cece cece cece eee ee eens 63 Figure 2 8 PEM Backplane Connectivity cece cece eee eee e eee cent ences 64 Figure 2 9 PEM View with Detail 0 cece cece cece eee teen ence nee neeeees 65 Figure 2 10 Declaration of Conformity cece cece eee eee eee teen tence neneees 68 Figure 3 1 Rack Mounting Dimensions 0 eee eee eee tenet eee ene nee neeaees 79 Figure 3 2
38. 1_ 2 and SAM2_J2 SAM A and B 2 PEM1_ 1 PEM A and B 2 FTM2_ 1 Lower Fan 1 FTM Interconnect 1 Table 2 4 Slot Hardware Addressing for J10 58 AXP1620 Installation and Use 6806800E23L Table 2 4 Slot Hardware Addressing for J10 continued AXP1620 Shelf Description Slot HA7 HA6 HA5 HA4 HA3 HA2 HA1 HAO Gnd Open Gnd Open Gnd Physical Slot Fan 1 Site Type 04h Gnd Gnd Open Gnd Open Fan 2 04h Gnd Gnd Open Gnd AXP1620 Installation and Use 6806800E23L 59 AXP1620 Shelf Description Table 2 6 SAM and PEM Hardware Addressing Physical HW Site Slot Address Type HA7 HA6 HA5 HA4 HA3 HA2 HA1 HAO Gnd Open Open Gnd SAM 1 1 03h Gnd Open SAM 2 2 03h Open Gnd 2 6 5 Zone Locations on a Blade The backplane provides dual star Base Interface and dual star Fabric Interface connections at each slot with segmented power four power segments provided by the dual PEMs e Zone 1 provides the system management and power interfaces such as redundant 48VDC power and IPMB e Zone 2 the data transport interface provides the Base and Fabric interfaces Update Channels and clock synchronization through the ZD connectors per front side blade e Zone 3 provides the direct interconnect for user designated I O NOTICE Rear Transition Modules connec
39. 2 Overview The AXP1620 Shelf supports 16 AdvancedTCA blade slots of which 14 are I O node slots that can be populated with task CPU processor blades network processor blades or any other blade designed for a specific application and two slots for the system controller and switching blades There are slot locations below the AdvancedTCA slots in the rear of the shelf for the two SAMs shelf management alarm modules All slots comply with PICMG 3 0 for power distribution and form factor and use the PICMG 3 1 for Ethernet and Dual Star interface The shelf s other components include two Power Entry Modules PEMs one upper Fan Tray Module FTM one lower FTM and front and rear cable management trays Platform Features The AXP1620 includes the following features e 16 slot card cage with 16 rear transition module RTM slots e Two Shelf Management Alarm Modules SAMs e Upto two PICMG 3 0 compliant System Controller and Switching blades e Two DC hot swappable 2N 1 redundant Power Entry Modules PEMs e Fan Trays Modules FTMs one upper tray and one lower tray e Front access service and installation of blades and lower fan tray e Rear access service and installation of RTMs SAMs upper FTM and PEMs e Cable management front and rear e Alarm Display Panel ADP for telco alarms located on the front of the chassis e Filler panels for front and rear slots AXP1620 Installation and Use 6806800E23L 51 AXP1620 Shelf Descripti
40. 5 ManagementandControl 22220 esseeeeeeeeenneeeeneneeeenersernernenenn 151 7 5 1 Hardware Monitoring and Control 2 eee e cece eee eee eee een e nennen 151 Tkl Voltage Sensors seen an 152 7 5 1 2 Temperature Monitoring 0 ccc eee eee ee eee eee 152 7 5 1 3 Fan Speed and Control cece cece cence cere e eee ee ene nenn 152 7 9 2 Red ndaney Control nee ne Rep 155 6 AXP1620 Installation and Use 6806800E23L Contents 7 5 2 1 Hardware Redundancy Interface 0 cece cece ene eee eee nenn 155 75 2 2 AR PROtOCOl wis atau ern es 156 7 3 2 3 Ethernet Signals cis es tenes ne iNET ESA 157 7 5 2 4 Configuring Front Panel Network Interface 02 cece eee eee eee 159 7 5 2 5 Configuring RMCP Network Interface 2 cece cence eee eee nee 160 7 53 SWIECHOVED SIGNS x04 u enter An ee weaes 160 7 6 Telco Alarm Functionality 0 ccc cece cece eee rreren e eee eeeneeanes 161 7 6 1 Telco Alarm Cutoff Push Button 0 cece cece cece eee e ee ee ee eenees 161 7 6 2 TelcoAlarMLEDS 0 cece cece eee cee EE nen e enn cence nnenenetenes 161 7 6 3 Telco Alarm Interface 0 0 ccc cece cece cence nee e ne ee ne eeneeneneennes 162 7 1 HOtSwWapntertace Jains ningun aied eran caer say Sens E E deiner newness 163 1 8 POWER gcc tie ond cen bh naphtha hen Saka a hee ee eae MRS ash ae 163 7 9 SAMSOftWw re 2 meer ie ehr 163 LIT URS IS ee nen rare
41. 6806800E23L 23 Safety Notes Damage of RTM and Front Blade Removing the RTM from the system while the playload of the front blade is powered up may damage the front blade and RTM Whenever removing the RTM from the system you have to power down the playload of the front blade first RTM Malfunctioning Incorrect RTM installation and removal can result in RTM malfunctioning When plugging the RTM in or removing it do not press on the face plate but use the handles RTM Damage Installing the RTM with other blades than the ones designed for it may damage the RTM and the front blade Only install the RTM with the correct front blade Data Loss Removing the RTM with the system power on and the blue LED on the front blade still flashing causes data loss Before removing the RTM from a powered system power down the slot by opening the lower handle of the front blade and wait until the blue LED is permanently ON Blade Malfunctioning Incorrect blade installation and removal can result in blade malfunctioning Make sure that the blade is connected to the system backplane through all assembled connectors and that power is available on all zone 1 power pins Operation System Overheating Cooling vents Inproper cooling can lead to blade and system damage 24 AXP1620 Installation and Use 6806800E23L Safety Notes To ensure proper cooling and undisturbed airflow through the system always operate the system in a horizontal positi
42. 7 47 2008 Image Type PowerPC Linux Firmware uncompressed Data Size 212992 Bytes 208 00 kB 0 20 MB Load Address 0xF0000000 Entry Point 0x00000000 164 AXP1620 Installation and Use 6806800E23L Shelf Management Alarm Module dev mtdblock7 Image Name Created Image Type Data Size Load Address Entry Point Linux 2 4 25 Thu Mar 27 21 33 51 2008 PowerPC Linux Kernel Image 793096 Bytes 774 51 kB 0x00000000 0x00000000 gzip compressed 0 76 MB dev mtdblock9 Image Name Created Image Type Data Size Load Address Entry Point sentry shmm1500 RFS Ramdisk Imag Thu Mar 27 21 41 21 2008 PowerPC Linux RAMDisk Image 5429028 Bytes 5301 79 kB 0x00000000 0x00000000 gzip compressed 5 18 MB From the sample output it is possible to see the compilation dates of the U Boot RFS and Kernel images for both the active and nonactive firmware banks Compilation times will never be identical for all three images but should be relatively close to each other AXP1620 Installation and Use 6806800E23L 165 Shelf Management Alarm Module u 166 AXP1620 Installation and Use 6806800E23L Related Documentation a A 1 Artesyn Embedded Technologies Embedded Computing Documentation The publications listed below are referenced in this manual You can obtain electronic copies of Artesyn Embedded Technologies Embedded Computing publications by contacting your local Artesyn sales of
43. AKKAXKAAXKAAKKAAXKAAKK Indicates a property damage message XXXXXXXXXXXXXKXXXXXXXXKXXXXXXXXXXXXXXXXXXXXXXXXXX XXXXXXXXXXXXXXXXXXXXXXXXXKXXXXXXXAXXXXXXXXXXXXXXXXX XXXXXXKXXXXXXXXKXXXXXXXXKXXXXXXXXXXXXXXXXXXXXXXXX p y 0000000000000000 000000000000 No danger encountered Pay attention to important 200000000000000000000000000000000000000000XXXXXXX i nfo rm ati on 16 AXP1620 Installation and Use 6806800E23L About this Manual Summary of Changes Order No 6806800E23A June 2008 Description First Release 6806800E23B 6806800E23C 6806800E23D January 2009 February 2010 November 2010 Added a step in the section Replacing the PEM on page 132 to add the input power terminal block cover removal instruction to the procedure Updated FTM IPMC Firmware Upgrade on page 106 Updated Table Hot Swap Interface Pin Out on page 162 and Table Dimensions and Weight of System and Components on page 77 Updated Declaration of Conformity changed Centellis 4620 to AXP1620 6806800E23E March 2011 Updated Upper and Lower Fan Tray Modules 6806800E23F 6806800E23G 6806800E23H 6806800E23 March 2012 December 2012 May 2013 May 2014 Updated Figure 7 1 Updated section Ethernet Signals on page 157 Added a Notice in System Installation on page 21 Systeminstallation on page 33 Updated EMC on page 20 andEMV on page 32 Updated Standard Compliances on page 67 Updated Receiving
44. AXP1620 Installation and Use P N 6806800E23L September 2014 eee Copyright 2014 Artesyn Embedded Technologies Inc All rights reserved Trademarks Artesyn Embedded Technologies Artesyn and the Artesyn Embedded Technologies logo are trademarks and service marks of Artesyn Embedded Technologies Inc 2014 Artesyn Embedded Technologies Inc All other product or service names are the property of their respective owners Intel is a trademark or registered trademark of Intel Corporation or its subsidiaries in the United States and other countries Java and all other Java based marks are trademarks or registered trademarks of Oracle America Inc in the U S and other countries Microsoft Windows and Windows Me are registered trademarks of Microsoft Corporation and Windows XP is a trademark of Microsoft Corporation PICMG CompactPCI AdvancedTCA and the PICMG CompactPCI and AdvancedTCA logos are registered trademarks of the PCI Industrial Computer Manufacturers Group UNIX is a registered trademark of The Open Group in the United States and other countries Notice While reasonable efforts have been made to assure the accuracy of this document Artesyn assumes no liability resulting from any omissions in this document or from the use of the information obtained therein Artesyn reserves the right to revise this document and to make changes from time to time in the content hereof without obligation of Artesyn
45. AXP1620 Installation and Use 6806800E23L 6 2 1 2 FRU Installation The blue LEDs on both the front blade and the RTM start flashing This indicates that the front blade is informing the shelf manager about its desire to power up the payload of both the front blade and the RTM 11 Tighten the two face plate screws on the front blade 12 Wait until the blue LEDs on both the front blade and the RTM are OFF Switched off blue LEDs indicate that the payload of the respective blade or RTM has become active 13 Plug interface cable into face plate connectors if applicable Removing the RTM Removal Procedure The following procedure describes the removal of the RTM It assumes that your system is powered If your system is unpowered you can disregard the blue LED and thus skip the respective step In this case it is a purely mechanical procedure Damage of RTM and Front Blade Removing the RTM from the system while the payload of the front blade is powered up may damage the front blade and RTM Whenever removing the RTM from the system you have to power down the payload of the front blade first AXP1620 Installation and Use 6806800E23L 121 FRU Installation 1 Unlatch the lower handle outward by squeezing the lever and the latch together and turning the handle outward only enough to unlatch the handle from the face plate that means until you feel a resistance Do not rotate the handle fully outwards The blue L
46. BD data An identical copy of the bit stream is also sent on the redundant ShMM 1500R status signal This information is used by the FPGA to ensure that only one of the two connected ShMM 1500Rs goes into active mode at a time Figure 7 3 on page 156 shows the HRI of the ShMM 1500R As shown in the figure the ShMM 1500R HRI incorporates a hot swap buffer IDT QuickSwitch which isolates the interface from the peer ShMM prior to FPGA configuration or when the ShMM 1500R is powered down The QuickSwitch device is guaranteed to be disabled open when unpowered and does not have a low impedance path from any of the signal pins AXP1620 Installation and Use 6806800E23L 155 Shelf Management Alarm Module to the power or ground rails Hence the device prevents an unpowered ShMM 1500R from loading down the HRI of the peer ShMM 1500R It also prevents a carrier from detecting the ACTIVE output as a zero that is active during aShMM 1500R power cycle or aShMM 1500R power supply failure The FPGA device contains a built in CRC error checker for detecting soft errors in the configuration data When a CRC error is detected the signal LATCH_CRC_ERROR is set active by the ShMM 1500R CRC error detection circuit which immediately sets the ShMM_STATUS 0 1 _L and ACTIVE signals high The peer SOMM 1500R if it is not already active upon detecting the loss of the status serial bit streams becomes the active ShMM 1500R Figure 7 3 SAM HRI Interconnectio
47. Blades RTMs und Systeme gem derin Ihrem Land g ltigen Gesetzgebung und den Empfehlungen des Herstellers 42 AXP1620 Installation and Use 6806800E23L Chapter 1 Platform Architecture a 1 1 1 2 1 3 Description The versatile highly available AXP1620 is designed as an open standard platform on which to run applications in the Telecom Central Office environments The AXP1620 combines existing PICMG standards featuring high speed serial data fabrics These standards serve to streamline the architecture by eliminating the overhead of bridging increasing payload and eliminating the need for system and non system slot blades This is accomplished by using the Intelligent Platform Management Interface IPMI and dual Ethernet star network which allows for communication between all node blades using Ethernet The AXP1620 is a high availability platform with special locations for Shelf Management Alarm Module SAMs and sixteen 8U x 280mm slots sixteen 8U x 70mm rear transition modules Fan Tray Modules FTMs and Power Entry Modules PEMs PICMG Compliance The AXP1620 is designed to be compliant with PCI Industrial Computers Manufacturer s Group PICMG specifications 3 0 and 3 1 and also provides support for PICMG 1 5 1 IPMI bus for system management Shelf Topology Topology refers to the shape of a network or the network s physical layout The way that different nodes in a network are connected to each other and how t
48. D blinks Wait until the blue LED is switched OFF The switched off blue LED indicates that the board is activated Removal Procedure To remove a SAM from a powered shelf proceed as follows 1 2 3 Put on an ESD wrist strap Connect the strap to the shelf by attaching the front or rear ESD jack Unfasten the captive screw at the upper left hand corner of the face plate until the module is detached from the shelf The blue LED blinks indicating that the module power down process is ongoing AXP1620 Installation and Use 6806800E23L FRU Installation 6 3 6 4 5 Wait until the blue LED is illuminated permanently NOTICE Data Loss Removing the module with the blue LED still blinking causes data loss Wait until the blue LED is permanently illuminated before removing the module 6 Unlock ejector handle by pressing the handle and pull down The SAM should start to move out of the chassis Do not force it If the SAM does not move it means the captive screw is not fully unscrewed Unscrew until loose and rotate the ejector handle down 7 Remove the module from the shelf Unused Slots All unused node or hub slots must be covered with filler blades These filler blades ensure a consistent airflow per slot whether or not the neighboring slot contains an AdvancedTCA blade There are filler blades sized for the front and for the RTM slots An unused slot can not contain a front filler when an AdvancedTCA RTM
49. DC Power Connection Detail 6806800E23L nd Use AXP1620 Installation a 102 AXP1620 Shelf Installation 5 8 Power Cable Termination Custom lugs are used with large gauge wires for up to 80 AMPs DC 4 AWG when connecting to the PEM These are shipped with the product The lugs are angled to allow the cables to be dressed below the cable management tray thus protecting the circuit breakers from accidental tripping Terminating this lug is identical to terminating standard lugs To minimize shorting of the terminals the lugs must be insulated according to the following illustration Heat shrink should be placed as close to the hole as possible 0 15 apart The heat shrink tube should be cut approximately at a 30 angle 5 9 Connecting the Cables to the PEM In a redundant configuration each PEM must be connected to a separate DC power source The 2 separate inputs on a single PEM should be connected to the DC same source Power is introduced to each PEM s terminal block on the front of the module power input cable and return cable The lugs provide secure contact for the cable and prevent the power cables from rotating A plastic housing covers the power feeds and returns and is attached with one screw Refer to Figure 5 4 on page 102 for detail To cable a dual breaker DC system read all cautions and warnings properly ground the equipment by following the procedure in Grounding the Shelf on page
50. DP This push button activates the alarm cutoff ACO state When ACO is activated the active alarm LED blinks and all of the alarm relays are deactivated This button does not clear alarms Refer to Figure 7 2 on page 147 for the location of the alarm cutoff push button switch 7 6 2 Telco Alarm LEDs These LEDs are used to indicate the presence of the critical major and minor alarms When a LED is lit the respective alarm is active A blinking LED signals an alarm cut off state which is initiated by pressing the alarm cut off button when an alarm is active AXP1620 Installation and Use 6806800E23L 161 Shelf Management Alarm Module 7 6 3 Telco Alarm Interface The SAM provides a front panel alarm connector which is a standard DB 15 connector with the following pin assignments Table 7 10 Hot Swap Interface Pin Out Pin Description 1 Minor Alarm Reset Minor Alarm Reset Major Alarm Reset Major Alarm Reset Critical Alarm NO Critical Alarm NC Critical Alarm COM Minor Alarm NO Minor Alarm NC 10 Minor Alarm COM 2 3 4 5 N 11 Major Alarm NO 14 Pwr Alarm NO 15 Pwr Alarm COM 162 AXP1620 Installation and Use 6806800E23L 7 7 7 8 7 9 7 9 1 Shelf Management Alarm Module Hot Swap Interface The SAM provides a hot swap interface allowing the SAM to be replaced without powering down the shelf The hot swap interface is implemented
51. ED blinks indicating that the shelf manager is informed about the desire of the blade to power down the payload of both the front blade and the RTM and the power down process is ongoing NOTICE Data Loss Removing the RTM with the system power on and the blue LED on the front blade still flashing causes data loss Before removing the RTM from a powered system power down the slot by opening the lower handle of the front blade and wait until the blue LED is permanently ON 2 Wait until the blue LEDs on both the front blade and the RTM are permanently ON A permanently switched ON LED indicates that the payload of respective blade or RTM has been powered down 122 AXP1620 Installation and Use 6806800E23L 6 2 2 6 2 2 1 FRU Installation 3 Unlatch the upper handle and rotate both handles fully outward 4 Remove interface cables from face plate connectors if applicable 5 Loosen the two RTM face plate screws 6 Remove the RTM from the slot Node Blade Installation and Removal The blade is fully compatible to the AdvancedTCA standard and is designed to be used in AdvancedTCA shelves The blade can be installed in any AdvancedTCA node slot Damage of Circuits Electrostatic discharge and incorrect blade installation and removal can damage circuits or shorten their life Before touching the blade or electronic components make sure that you are working in an ESD safe environment Blade Malfunctioning Incorre
52. EM s circuit breakers to the OFF position The PEMs remain powered until the 48VDC power to each PEM is removed Make sure you disconnect the power at the external source before removing the PEM from the shelf AXP1620 Installation and Use 6806800E23L 87 AXP1620 Operations 4 5 2 88 Power is introduced to the PEM using a DC power cable attached to the terminal blocks on the front of the module power input cable and return cable The terminal block consists of a dual stud connection which prevents the power cables from rotating and provides secure contacts for the cable lug There is a plastic cover that protects the cable connections The DC power inputs must only be attached to approved Telephone Network Voltage TNV or Safety Extra Low Voltage SELV branch circuits Branch circuits must comply with all requirements called for in these safety standards IEC 60950 EN 60950 CAN CSA C22 2 No 60950 Attaching inputs to non TNV SELV approved power sources will cause the system to fail compliance with safety regulations IPMC Circuitry Each PEM is capable of monitoring voltage and circuit breaker status The PEMs are loaded with the AdvancedTCA IPMC firmware Preprogrammed FRU and Sensor Data Record SDR information reside on the PEM and is accessible from the SAM through the IPMB ports of the PEM In addition the IPMC monitoring functions include digital inputs to detect circuit breaker trips voltage sensors to detec
53. EMC regulatory markings Grounding To ensure the system is properly grounded each of the system s parts must contact the EMI gasket The system contains gaskets at the shelf and module level The shelf is also fitted with ESD contacts Please take care for proper ESD protection of the operator This is a Class A product based on the standard of the Voluntary Control Council for Interference by Information Technology Interference VCCI If this equipment is used in a domestic environment radio disturbance may arise When such trouble occurs the user may be required to take corrective actions The equipment is suitable for installation ina Common Bonding Network CBN or Isolated Bonding Network IBN AXP1620 Installation and Use 6806800E23L Safety Notes System Installation System Damage To avoid system damage verify that the system environment meets the environmental and power requirements given in this manual before installing the system Before you begin to set up and cable your new system consider these guidelines e Restricted access area Install the system only in a restricted access area e Installation codes This unit must be installed in accordance with the National Electrical Code Articles 110 16 110 17 and 110 18 and the Canadian Electrical Code Section 12 a e Overcurrent protection A readily accessible listed branch circuit overcurrent protective device must be incorporated into the building wiring For
54. Geb udes haben Ein Primary Protector wie in GR 1089 CORE beschrieben ist keine ausreichende Absicherung um die Geb ude internen Schnittstellen mit Leitungen au erhalb des Geb udes zu verbinden Besch digung des Systems Verschmutzungen k nnen das System besch digen Betreiben Sie das System an einem ersch tterungsfreien Ort an dem weder Staub Rauch noch elektrostatische Entladungen auftreten Stellen Sie au erdem sicher dass die klimatischen Bedingungen die in diesem Handbuch spezifiziert sind eingehalten werden und genug Raum f r die Luftzirkulation vorhanden ist Verletzungsgefahr und Besch digung des Systems Das System ist an eine TNV 2 Spannungsquelle angeschlossen Diese Spannung kann gef hrlich sein Stellen Sie sicher dass die externe Spannungsversorgung den entsprechenden Sicherheitsstandards entspricht System berhitzung Unzureichende K hlung kann zu einer Besch digung der Boards f hren Um eine ausreichende K hlung sicherzustellen betreiben Sie das System nur aufrecht Sorgen Sie au erdem daf r dass ein aureichender Mindestabstand mindestens 6 cm vor den L ftungsschlitzen an der Vorder und R ckseite des Systems freigehalten wird Genaue Informationen finden Sie im Kapitel Site Planning Considerations on page 71 34 AXP1620 Installation and Use 6806800E23L Sicherheitshinweise Verletzungsgefahr und Besch digung des Systems Wenn die Gewichte im Schaltschrank ungleich verteilt sind kann d
55. Guidelines It is important to have sufficient open space at the front and rear of the shelf when installed in arack or cabinet Depending on whether the enclosure has solid or vented doors will determine the recommended open space required Follow these guidelines for positioning the shelf to allow for the optimal open space for the shelf air inlet and shelf air exhaust Do not obstruct the ventilation openings at the top sides and back of the shelf Figure5 1 Rack Mounting Dimensions Cabinet Door 3 5mm Air Outlet toDoor at Back Side 25mm Thick of Rear Door Door 2X 13U Shelf Side View 3mm to Door Air Inlet gt 75mm 42mm k 550mm Inside Door to Door 600mm Deep Cabinet gt AXP1620 Installation and Use 6806800E23L 95 AXP1620 Shelf Installation Figure 5 2 Shelf Airflow Diagram Upper FTM Outlet Plenum Chassis DE gt Exhaust Air Flow RTM i 4 4 4 4 i i Chassis 1 Chassis 1 Front i Rear 1 1 i 1 1 1 1 I H Room au gt y Ambient Se nee KR Air Flow gt Exhaust Lower Front Air Intake Lower FTMs 5 3 3 Mounting Options and Stabilization telecommunication equipment For increased stability we recommend that the rack is extended The AXP1620 is designed to be mounted in an equipment rack while maintaining conforma
56. Handbuch beschrieben sind eingehalten werden Verletzungen oder Kurzschl sse Blade oder Stromversorgung Falls die ORing Dioden des Blades durchbrennen kann das Blade einen Kurzschluss zwischen den Eingangsleitungen A und B verursachen In diesem Fall ist Leitung A immer noch unter Spannung auch wenn sie vom Versorgungskreislauf getrennt ist und umgekehrt Pr fen Sie deshalb immer ob die Leitung spannunggsfrei ist bevor Sie Ihre Arbeit fortsetzen um Sch den oder Verletzungen zu vermeiden Ausbau Erweiterung System berlastung Verhindern Sie eine System berlastung indem Sie die gesamte aufgenomme Leistung aller eingebauten Komponenten also z B der installierten Blades und Laufwerke siehe die technischen Daten der entsprechenden Komponente berpr fen Stellen Sie sicher dass der Ausgangsstrom jedes Verbrauchers innerhalb der zul ssigen Grenzwerte liegt Verlust der Sicherheitszulassung Verwendung zus tzlicher Module Wenn Sie zus tzliche Module und Boards verwenden ist es m glich dass das System nicht mehr den g ltigen Sicherheits und EMV Normen entspricht Der Systemintegrator muss die Einhaltung der g ltigen Normen sicherstellen AXP1620 Installation and Use 6806800E23L 39 Sicherheitshinweise Austausch von PEMs Verletzungsgefahr durch Stromschlag und Verbrennungen Ber hren metallische Gegenst nde an H nden Handgelenken oder am Hals die Input Terminals der PEMs kann dies zu extremen Verletzungen
57. T1 J1 Stecker Beachten Sie dass ein versehentliches Anschlie en einer E1 T1 J1 Leitung an einen TPE Stecker Ihr System zerst ren kann e Kennzeichnen Sie deshalb TPE Anschl sse in der N he Ihres Arbeitsplatzes deutlich als Netzwerkanschl sse e Stellen Sie sicher dass die L nge eines mit Ihrem Systems verbundenen TPE Kabels 100 m nicht berschreitet AXP1620 Installation and Use 6806800E23L 41 Sicherheitshinweise e Das System darf ber die TPE Stecker nur mit einem Sicherheits Kleinspannungs Stromkreis SELV verbunden werden e Bei Fragen wenden Sie sich an Ihren Systemverwalter Laser Verletzungsgefahr Einige Boards die in verschiedenen Systemkonfigurationen verwendet werden sind Laserprodukte der Klasse 1 Verwenden Sie diese anders als in der Dokumentation beschrieben kann dies zu gef hrlicher Strahlung f hren Einge RTMs sind Laserprodukte der Klasse 1 Verwenden Sie diese anders als in der Dokumentation beschrieben kann dies zu gef hrlicher Strahlung f hren Batterieaustausch Besch digung der Boards Ein unsachgem er Austausch von Batterien kann zu gef hrlichen Explosionen und Besch digung der Boards f hren Verwenden Sie deshalb nur den Batterietyp der auch bereits eingesetzt wurde und befolgen Sie die entsprechende Anleitung im Installationshandbuch des jeweiligen Boards Entsorgen sie alte Batterien entsprechend der in Ihrem Land g ltigen Richtlinien Umweltschutz Umweltschutz Entsorgen Sie alte
58. Wartung oder Reparatur bitte an die f r Sie zust ndige Gesch ftsstelle von Artesyn Embedded Technologies So stellen Sie sicher dass alle sicherheitsrelevanten Aspekte beachtet werden AXP1620 Installation and Use 6806800E23L 31 Sicherheitshinweise Allgemein EMV 32 Verletzungsgefahr An der R ckseite des Systems befinden sich spitze Stifte an denen Sie sich verletzen k nnen Seien Sie vorsichtig im Umgang mit dem System Das Produkt wurde getestet und erf llt die f r digitale Ger te der Klasse A g ltigen Grenzwerte gem den FCGRichtlinien Abschnitt 15 bzw EN 55022 Klasse A Diese Grenzwerte sollen einen angemessenen Schutz vor St rstrahlung beim Betrieb des Produkts in Gesch fts Gewerbe sowie Industriebereichen gew hrleisten Das Produkt arbeitet im Hochfrequenzbereich und erzeugt St rstrahlung Bei unsachgem em Einbau und anderem als in diesem Handbuch beschriebenen Betrieb k nnen St rungen im Hochfrequenzbereich auftreten Benutzen Sie zum Anschlie en von Peripherieger ten ausschlie lich abgeschirmte Kabel So stellen Sie sicher dass ausreichend Schutz vor St rstrahlung vorhanden ist Die Blades m ssen mit der Frontblende installiert und alle freien Steckpl tze m ssen mit Blindblenden abgedeckt sein Ein AXP1620 das als Ersatzteil Austauschchassis oder unkonfiguriertes System ausgeliefert wird enth lt keine Platzhalter Boards Es liegt in der Kundenverantwortung sicherzustellen dass alle le
59. akers that provide DC feed power to the PEM you are replacing 7 Confirm whether the power to the PEM lug bolts is correct Using a multimeter measure between the two lugs Ensure that the voltage is of the correct polarity 8 Close the breakers on the PEM Ensure that the IS LED turns green 6 5 Upper and Lower Fan Tray Modules To prevent system damage the operator must replace the fans within the recommended service interval shown in the following table to prevent a decline in shelf operability Make sure the replacement FTM is available for exchange and ready to install Service Interval for 1 FTM Temperature Range Not recommended 40 55 C Four hours 40 C maximum AXP1620 Installation and Use 6806800E23L 135 FRU Installation When a FTM is taken out of operation the system manager will compensate for the loss by increasing the speed of the remaining fans as needed Please read the following caution before replacing any of the FTMs Fans may continue to rotate after power is removed Be careful to keep fingers away from the bottom of the FTM enclosure 6 5 1 Removing the Upper FTM Removal Procedure Follow these steps and refer to the figures to remove the upper fan tray module from the shelf 1 Loosen the retention screw to the chassis before loosening the ejector handle screw Figure 6 2 Upper Rear FTM Ejector Handles and LEDs 2 Pull the ejector handle o
60. an un 13 Safety Notes air 19 Sicherheits himili u a 31 1 Platform Architecture 00000 nenne 43 1 1 D amp scripti n een eae IREKE ee beeen eee 43 1 2 PICMG Compliance u ne ee ee ee la wea rented 43 1 3 Shelf Topology 2 cece sense ea nn 43 1 4 Network Descriptions un en vinci yale eaeesekker 44 LA Baselntert ce un ae ee i E OE ates 44 1 4 2 Fabricinterfae ns bie id eee tae thee baw deere erie EEES 45 1 4 3 IPMI Network n ee ee he Falle nina ehren 46 1 4 4 Update Channel Interface 0 ccc cece cece eee nen e eee nee eens 47 1 5 Backplane and Component Connectivity ccc cee cence teen ene ene eeeennes 47 LE Operating Systems ansehe air 48 1 7 Remote Management and Maintenance 0 cece cece eee eee tenet nennen 49 2 AXP1620 Shell Description aaa sn ag a tiwesaduinweeewtebesewrsvae 51 2 1 OVENIEW ae 51 2 2 Platformi Features msn rnr e nenie EEE EE EEE E ne pn 51 2 3 EMClOSUPE u coe dedt a aae aE RAE a er datas 54 24 Power Consumplon urn 54 2 5 Shelf Ground Configuration 0 0 c cece cece cence ene nee e ence nee sen ene nen 54 2 6 Backplane weve denen decades eher ei ne weed oe 55 2 6 1 Functional Layout 0 cece eee een cence ene eee E ER 55 2 62 E Keyind scence gues tdass ooo eee RFs Rene pea ee eee tangas se PRR eher 56 2 6 3 Shelf FRU Information u een dae 57 2 6 4 Backplane Slot Connectors eee eee ene ence eee eee en nennen 57 2 6 5
61. and Unpacking the System on page 71 Mounting Options on page 78 Connecting the Cables to the PEM on page 103 Accessing the System on page 105 Installing the Upper FTM on page 137 and Installing the Lower FTM on page 139 Re branded to Artesyn template Updated Figure Declaration of Conformity on page 68 Updated the sections Grounding the Shelf on page 100 RS 232 Serial Interface on page 148 and Ethernet Signals on page 157 Added new sections Configuring Front Panel Network Interface on page 159 and Configuring RMCP Network Interface on page 160 Updated Figure 7 4 on page 158 6806800E23K August 2014 Added Installation procedure and modified Removal procedure under the section Replacing the PEM on page 132 6806800E23L September 2014 Updated the section Grounding the Shelf on page 100 AXP1620 Installation and Use 6806800E23L 17 About this Manual m 18 AXP1620 Installation and Use 6806800E23L Safety Notes General This section provides warnings that precede potentially dangerous procedures throughout this manual Instructions contained in the warnings must be followed during all phases of operation service and repair of this equipment You should also employ all other safety precautions necessary for the operation of the equipment in your operating environment Failure to comply with these precautions or with specific warnings elsewhere in this manual could result in personal injury or damage to t
62. appropriate AWG rating of the overcurrent protection device see NEC Table 310 16 and other national regulations e The protective bonding conductor depends on your power distribution topology Make sure that you use an appropriate protective bonding conductor regarding the rating of the branch circuit protection e Install the system safely Make sure that cables and cords are out of the way Make sure that the set up is comfortable for users System Damage WARNING The intra building port s of the equipment or subassembly is suitable for connection to intra building or unexposed wiring or cabling only The intra building port s of the equipment or subassembly MUST NOT be metallically connected to interfaces that connect to the OSP or its wiring These interfaces are designed for use as intra building interfaces only Type 2 or Type 4 ports as described in GR 1089 and require isolation from the exposed OSP cabling The addition of Primary Protectors is not sufficient protection in order to connect these interfaces metallically to OSP wiring System Damage Environmental contamination can impair system operation Locate the system in a stable area free of excess movement and jarring and free of dust smoke and electrostatic discharge ESD Make sure that the temperature does not exceed the operating temperature given in the environmental requirements in this manual and allow room for proper air flow for cooling AXP1620 Installation an
63. are debug and manufacturing AXP1620 Installation and Use 6806800E23L 145 Shelf Management Alarm Module 7 3 SAM Diagram and Face Plate Layout Figure 7 1 shows a block diagram of the overall SAM architecture and Figure 7 2 on page 147 shows the face plate layout Figure 7 1 Block Diagram of SAM HS 12VA Dual f Voltage and Carrier ID 5 hotswap Power Supplies Temperature PROM 12VB controllers Monitoring P 12C 3 o 12C 2 Console oe XFMR Handle rot Switch RS232 Base 2 XFMR Four port Ethernet XFMR SAMM 1500R Switch SER Ethernet SPI RJ45 Redundancy Interface Ethernet Inter Pal SAM Telco Telco Link AEM GPIOs Alarm Alarm High Speed Cross SAM gt Sena un DB15 IPMB link lt Fan Full FPGA S peed 20 GPIOs K gt LEDs IPMB 0 a N RS232 So gt DB9 ADP Telco Alarm Cutoff The SAM has these interfaces e Four 10 100Base T Ethernet links One link to each system controller and switching blade 2 One link to the redundant SAM Onelink to the face plate 146 AXP1620 Installation and Use 6806800E23L Shelf Management Al
64. arm Module e One Ethernet link failover management status signals and one IPMB branch or segment to the other SAM e Radial IPMB links for up to 20 modules 16 blades 2 fan trays and 2 PEMs e Face plate interfaces that include 10 100Base T Ethernet RS232 serial console and Telco alarm interface with connector e Interface to ADP panel for Telco Alarm indicators and serial console port The SAM provides the face plate LEDs listed in the following table More detail on the LEDs is provided in the following sections Figure 7 2 SAM Face Plate Io To O O 26 O o9 ol 0 O CONSLOE 7 4 Functional Description The SAM has a high density 220 pin socket for the shelf management mezzanine ShMM device and front panel connectors for the serial console Ethernet and Telco alarm signals of the mezzanine The dual IPMB interface from the mezzanine is connected to the dual IPMBs in the backplane AXP1620 Installation and Use 6806800E23L 147 Shelf Management Alarm Module 7 4 1 7 4 2 148 The SAM includes several on board devices that enable different aspects of shelf management based on the shelf management mezzanine These facilities include I Gbased hardware monitoring control and GPIO expander devices IPMB Connectivity The IPMB is a dual radial topology Each IPMC in the shelf connects to both SAMs for a redundant IPMB
65. as System ausschalten Besch digung des Systems Luftfilter Verunreinigungen in der Luft k nnen den Luftfilter verschmutzen und so die Luftzufuhr des Systems beeintr chtigen Das kann zur berhitzung des Systems und zu Sch den an Systemteilen f hren Um einen reibungslosen Luftstrom durch das System zu gew hrleisten sollten Sie den Luftfilter sp testens alle sechs Monate austauschen Artesyn empfiehlt die L fter alle 90 Tage auszutauschen Wie h ufig Sie die Filter austauschen m ssen h ngt von der Umgebung ab in der das System betrieben wird Da die Verh ltnisse in Vermittlungsstellen sehr unterschiedlich sein k nnen sollten Sie die Luftfilter nach der Erstinstallation des Systems jede Woche kontrollieren In einer staubigen Umgebung muss ein Filter gegebenenfalls fter gereinigt AXP1620 Installation and Use 6806800E23L Sicherheitshinweise werden als in einer sauberen Umgebung Pr fen Sie den Filter regelm ig bis Sie eine Vorstellung davon haben wie oft der Filter gereinigt werden muss Erstellen Sie aufgrund Ihrer Beobachtungen einen Reinigungsplan und protokollieren Sie jede Reinigung oder jeden Austausch des Filters Uberhitzung des Systems Wenn Sie die Geschwindigkeit der L fter reduzieren steigt die Systemtemperatur an Kontrollieren Sie deshalb st ndig die Temperatur im System wenn Sie die Geschwindigkeit der L fter reduziert haben Stellen Sie w hrend des Betriebs sicher dass die Bedingungen die im
66. bled SAM to Hub 192 168 24 101 192 168 24 100 ETH1 24 Enabled Table 7 9 Shelf Manager Dynamic Network IP Interfaces Function IP Active SAM IP Backup SAM Ethernet Device Default State RMCP 192 168 24 11 192 168 24 10 ETH1 24 1 Enabled The IP addresses defined in Table 7 9 are relative to active standby SAM When active standby switchover takes place the addresses are re assigned to the appropriate physical SAMs Addresses ending in 1 are always associated with the active SAM Addresses ending in 0 are always associated with the standby 7 5 2 4 Configuring Front Panel Network Interface To set front panel Ethernet and make it permanent over power cycle set the following U boot environment variables This may be done in Linux or U Boot If done in U Boot saveenv must be executed to save the environment variables setenv ipladdr lt IP address gt setenv gatewayip lt gateway IP gt setenv enable_front_panel_ethernet y Saveenv AXP1620 Installation and Use 6806800E23L 159 Shelf Management Alarm Module 7 5 2 5 7 5 3 160 Configuring RMCP Network Interface To change the RCMP network address that is associated with the Active and Standby Shelf managers from the default values use the following clia command on the Active Shelf Manager where xxx xxx xxx xxx indicates a sample IP address clia setlanconfig 1 3 xxx xxx xxx xxx This will set the floating RCMP IP address associated with
67. ch other or to other conductors Using the appropriate tool loosen the chassis retention screws on each side of the PEM Open the ejector handles completely You will see the PEM disconnect from the backplane Pull the module straight out from the rail guides Installation Procedure To install a PEM follow these steps 1 2 Ensure that the PEM breakers are in the off position Insert the new PEM closing the ejector handles AXP1620 Installation and Use 6806800E23L FRU Installation 3 Using the appropriate tool tighten the chassis retention screws on each side of the PEM 4 Using the appropriate tool carefully remove the terminal block cover plastic covering over the terminal block The terminal block cover is attached to the terminal block by two tabs with slots in the cover that insert into embossments in the terminal block wall To remove the cover press the upper wall of the terminal block wall downward and slip a flat bladed screwdriver between the cover and the terminal block wall and pry the cover tab up to relieve it from the embossment in the terminal block wall Once the upper cover tab is free from the terminal block embossment the cover should rotate downward and free itself from the lower embossment 5 Install the DC power cables to the dual lug bolts on the PEM 6 Locate the target power input cable s terminals at the branch circuit or power distribution unit Close the external circuit bre
68. connects the backplane to the FTM distribution board The FTMs are powered from 48VDC from the backplane The lower FTM receives its signal and power connections from the AdvancedTCA backplane Only the lower FTM has an air filter frame and filter in the module The FTMs have variable speed fan control which is dependent on the temperature readings in the shelf Airflow rates can vary depending on the fan speed and payload Fan speed levels are controlled from the SAM through the IPM shelf management software The fan speed levels change automatically based on temperature sensors For more information refer to Fan Speed and Control on page 152 The FTM has an ejector handle that interfaces with a mechanical switch to signal the software for hot swap The handle and captive screws lock the FTM securely into the shelf Each FTM is equipped with three status LEDs on the face plate For removal and installation procedures for the FTMs refer to Chapter 6 FRU Installation In the event of a Fan Filter Out of Service alarm first check the fan filters only on the lower FTMs to make sure the airflow is not obstructed For information on the maintenance of air filters see Air Filter Maintenance on page 91 AXP1620 Installation and Use 6806800E23L 89 AXP1620 Operations 4 6 2 4 6 3 90 Cooling Budget The shelf cooling is designed to operate with the following temperature rises across the shelf This allows cards with these dissipations
69. ct blade installation and removal can result in blade malfunctioning When plugging the blade in or removing it do not press on the face plate but use the handles Installing the Node Blade To install the blade into an AdvancedTCA shelf proceed as follows AXP1620 Installation and Use 6806800E23L 123 FRU Installation 124 Installation Procedure The following procedure describes the installation of the blade It assumes that your system is powered If your system is unpowered you can disregard the blue LED and thus skip the respective step In this case it is a purely mechanical installation 1 Ensure that the top and bottom ejector handles are in the outward position by squeezing the lever and the latch together 2 Insert blade into the shelf by placing the top and bottom edges of the blade in the card guides of the shelf Ensure that the guiding module of shelf and blade are aligned properly 3 Apply equal and steady pressure to the blade to carefully slide the blade into the shelf until you feel resistance Continue to gently push the blade until the blade connectors engage 4 Squeeze the lever and the latch together and hook the lower and the upper handle into the shelf rail recesses AXP1620 Installation and Use 6806800E23L FRU Installation 5 Fully insert the blade and lock it to the shelf by squeezing the lever and the latch together and turning the handles towards the face plate If your
70. d Use 6806800E23L Global Initialization Oxc Power State Notification Oxc Device Capabilities 0x29 Controller does not provide Device SDRs Supported features 0x00 PEM IPMC Firmware Upgrade There is a single IPMC firmware image common to the two PEMs in the AXP1620 The PEM IPMCs are assigned IPMB addresses 0x66 and 0x68 The file containing the firmware image is pem1620 img As upgrades are released Artesyn will supply the current version of this file The upgrade process described here uses a script named upgradepem which is supplied on shelf managers starting with build 4 1 0 3 Upgrade Process Steps Follow these steps to upgrade the PEM firmware 1 Copy the pem1620 img file to the tmp directory on the active Shelf Manager The tmp directory on the shelf manager is mounted to ram this copy of the file will be deleted on the next reset of the shelf manager If you want to save the file to flash copy it to the var nvdata directories on both shelf managers 2 Execute the following command to upgrade one PEM upgradepem pem1 tmp pem1620 img 3 After a successful upgrade the upgradepenm script displays the current firmware level reported by the device as shown in PEM Upgrade Sample Output on page 110 109 AXP1620 Shelf Installation 5 12 2 1 110 4 Repeat this command to upgrade the other PEM upgradepem pem2 tmp pem1620 img PEM Upgrade Sample Output The sample output for this command
71. d Use 6806800E23L 21 Safety Notes 22 Personal Injury or System Damage The system is supplied by a TNV2 voltage This voltage is considered hazardous Make sure that the power supply meets the local safety standards System Overheating Inproper cooling leads to blade damage To ensure proper cooling always operate the system in a horizontal position Furthermore keep clear at least 6 cm adjacent to the cooling vents on the chassis front and back side For detailed information refer to Site Planning Considerations on page 71 Personal or System Damage Unstable system installation in a rack can cause the rack to topple over Therefore if your system is the only one in the rack make sure to mount the system in the lowest part of the rack If other systems are installed in one rack start with the heaviest component at the bottom If the rack is equipped with stabilizing devices make sure that they are installed and extended so that the rack is secure Then proceed to mount or service the system Personal Injury or System Damage When pulling the system out of the rack it can fall down and cause injuries Pull out the system cautiously Personal Injury or System Damage The system is heavy and if you carry it on your own you can hurt your back To prevent injury keep your back straight and have two people lift the system or use additional lifting equipment System Damage During the course of handling shipping and assembly
72. dry dark environment High temperature humidity and ultraviolet light adversely affect the filter media foam Foam also degrades when exposed to solvents and sulfates such as engine exhaust Controlling relative humidity between 40 80 and temperature between 4 4 C 32 2 C 40 F 90 F yields an acceptable environment Covering the filters with dark plastic keeps the foam dry and protects it from ultraviolet light Purchase enough to keep adequate inventory for no more than a few months filters could degrade under long term storage conditions AXP1620 Installation and Use 6806800E23L AXP1620 Shelf Installation A 5 1 Overview This chapter discusses mounting and installation options for the AXP1620 shelf The topics covered are e Installation Prerequisites e Installing the Shelf e DCPower Cable e Connecting the Cables to the PEM e Grounding the Shelf e Shelf Ground Configuration e Powering Up the System Accessing the System Upgrading Firmware 5 2 Shelf Physical Characteristics The following table provides the dimensions and weight of an equipped and unequipped shelf and rack mounting requirements Table 5 1 AXP1620 16 Slot Shelf Physical Characteristics Characteristics Specifications Size 22 56 inches 57 3 cm high 13U 19 50 inches 49 52 cm wide 21 06 inches 53 5 cm with mounting flanges 21 51 inches 54 64 cm deep with cable trays Weight Approximately 93 8 Ibs 42 5 kg base in
73. e 6806800E23L Shelf Management Alarm Module 7 4 5 2 15 7 5 1 SAM ADP Status LEDs Status is shown using an LED on the SAM face plate and ADP The illumination state of the LED is normally controlled by the GPIO on the SAM The following tables describe the LED states Table 7 5 SAM LED Status Indicators SAM Face Plate LED LED Color State State Condition IS In Service Active power good OOS Out of Service Failed HS How Swap Blue On Remove OK Table 7 6 ADP LED Status Indicators Alarm Display Panel LED LED Color State State Condition Critical alarm CRT Active Major alarm MAJ Active Minor Alarm MIN Yellow Active Power PWR Green On Power Present Management and Control This section gives a general description of the role of the on board I C devices and how management control and redundancy is handled by the SAM Detailed information on sensors can be found in the AXP1620 Subsystem IPMI Programmer s Reference Hardware Monitoring and Control The hardware monitoring and control functions implemented by the AXP1620 are provided by the on board I Cbased devices AXP1620 Installation and Use 6806800E23L 151 Shelf Management Alarm Module 7 5 1 1 7 5 1 2 7 5 1 3 152 Voltage Sensors On board sensors provide the following power supply voltages All voltage sensors are implemented using the ADM1024 device on the master only I C bus System management softwa
74. e een nent nennen 94 5 3 2 Rack Cabinet Cooling Guidelines 0 cc cece eee e eee entee nee n erreren 95 5 3 3 Mounting Options and Stabilization 0 cece cece cent e nee neee eens 96 5 3 4 Weight Distribution Within a Rack 0 ccc cece cece ene ene tenes 97 5 3 5 Electrostatic Discharge ESD and Safety Procedures cee cence ence ees 97 5 4 Installing the Shelf u a dee oe hee Gua an seus tad DI ln 98 5 4 1 23 ElARack Cabinet 0 cece ence ene erent ernennen en er ene nen 98 5 4 2 600mm ETSI Rack Cabinet 0 ccc cece eee eee eee ene een eenneees 99 5 5 Grounding the Shelf 0 cece cece ene eee eee e een e eens nennen 100 5 6 Shelf Ground Configuration 0 cece eee eee eee ene e teen ene cence enees 100 5 7 IDE Power Cable ur ee Den Ra 101 5 8 Power Cable Termination 0 ccc cece ence eee eee nen ene e ene eee e ne en eed 103 5 9 Connecting the Cables to the PEM 0 eee cece eee een ene een nent ne nenn 103 5 10 Powering Up the System cece cence eee n een eee n ene tenet ene eens 105 5 11 Accessing thesystem wee nie Henne ak en ek 105 5 12 Upgrading Firmware 22222essseeeeesneeeeeeeseneseenenneseesnenenee nennen 106 5 12 1 FTM IPMC Firmware Upgrade 0 ccc cee cece cence teen ne eee eneteneees 106 5 12 1 1 FTM Upgrade Sample Output 0 cece eee runnner erenneren 107 5 12 2 PEMIPMC Firmware Upgrade
75. e face plate but use the handles Removal Procedure The following procedure describes how to remove the blade from a system It assumes that the system is powered If the system is unpowered you can disregards the blue LED and thus skip the respective step In that case it is a purely mechanical procedure 1 Unlatch the lower handle by squeezing the lever and the latch together and turning the handle outward only enough to unlatch the handle from the face plate Do not rotate the handle fully outward The blue LED blinks indicating that the blade power down process is ongoing AXP1620 Installation and Use 6806800E23L FRU Installation 6 2 3 2 Wait until the blue LED is illuminated permanently then unlatch the upper handle and rotate both handles fully outward If the LED continues to blink a possible reason may be that upper layer software rejects the blade extraction request NOTICE Data Loss Removing the blade with the blue LED still blinking causes data loss Wait until the blue LED is permanently illuminated before removing the blade 3 Remove face plate cables if applicable 4 Unfasten the screws of face plate until the blade is detached from shelf 5 Remove the blade from the shelf Installing and Removing the Shelf Management Alarm Module The following sections describe the installation and removal procedures for the shelf management alarm module SAM 1500R For a detailed description of the
76. e oe P7 Ambient gt Deo RR Loe Air Flow Sa r Exhaust Lower Front Air Intake Lower FTMs The Cooling subsystem is compliant to CP TA B 4 The cooling system provides for greater than 40 CFM for the front blade and 5 0 CFM for the RTM The actual cooling performance depends on the slot population and the heat sink design of installed blades and should be validated based on the used configuration 80 AXP1620 Installation and Use 6806800E23L Site Preparation The cooling subsystem is designed to provide 31 1 CFM in the front and presence of any single cooling failure ly The distance to other equipment must be sufficient to avoid an overheating of the system N 7 If you install the system into a closed frame ensure that the air inlet and outlet are kept free 3 2 7 Acoustic Noise Control The system can generate a lot of acoustic noise This system has a built in noise control due to the fan speed control If the system is installed in an environment where the noise may be harmful to personnel being exposed to the noise during extended time periods additional protective measures should be considered AXP1620 Installation and Use 6806800E23L 81 Site Preparation 3 3 Site Planning Checklists The following table lists the tasks which you have to perform as plan the installation of the system Figure 3 3 Planning Checklist 1 Determine where to install the system and ensure that the required installation too
77. e power feed can provide Figure 2 8 PEM Backplane Connectivity Seated SAMA SAM B HA1 Logic_GND Shelf_GND IPMB_A IPMB_B Backplane Power Entry Module 48v 48v_RTN Front Panel 8 ATCA 8 ATCA FTM FTM SAMA SAMB Slots Slots 64 AXP1620 Installation and Use 6806800E23L AXP1620 Shelf Description Each of the PEMS are equipped with two rocker type circuit breakers three status LEDs hot swap ejector handle and a plastic cover that protects the dual stud terminal block The rear of the PEM has two output connectors that mate with the backplane Figure 2 9 PEM View with Detail D 1 48 VDC RTN 48 VDC RTN 48 VDC 48 VDC Table 2 8 PEM LED Status Indicators Power LED State Condition In Service Off no service Blink PEM activating Glow Steady service available Out of Service OOS Off service available Blink Deactivation requested Glow Steady no service Hot Swap HS Blue Off PEM is not ready to be removed Blink Deactivation requested Glow Steady PEM is ready to remove AXP1620 Installation and Use 6806800E23L 65 AXP1620 Shelf Description 2 9 66 Stationary Boards There are four stationary boards in the shelf which are completely passive and
78. e shelf connect the other end of the wire to a reliable earth ground Use the torque setting required by the connector supplier The 2 hole lug prevents rotation of the lug and ensures a permanent bonding of ground to the shelf The dual hole mount accepts 1 4 20 screws Use Panduit LCC2 14AW Q 2 hole lug or equivalent Figure 5 3 Placement of Grounding Lug Back of Shelf Shelf Ground Configuration The AXP1620 shelf was tested in the default configuration of logic ground and shelf ground connected and does not connect 48VDC Return with Shelf Ground The system has been tested in the default configuration and complies with safety and regulatory standards As a compliant AdvancedTCA shelf the AXP1620 allows system integrator at their own discretion to remove the mechanism which connects Logic Ground to Shelf Ground and install the mechanism that connects 48VDC Return to Shelf Ground If the system integrator exercises the option of removing the connections from Logic Ground to Shelf Ground and or adds the connection between 48VDC Return and Shelf Ground the responsibility for maintaining compliance to CSA C US VDE safety requirements and EMI RFI emission limits rests entirely with the system integrator and installer AXP1620 Installation and Use 6806800E23L AXP1620 Shelf Installation 5 7 DC Power Cable Power is introduced to the shelf through redundant DC PEMs The recommended power cable is an 4 AWG gauge that meets the
79. ejector latches This will signal the switch to deactivate the hot swap signal Watch for the blue LED to go solid and steady signaling that it is ready to remove AXP1620 Installation and Use 6806800E23L 133 FRU Installation 134 5 Using the appropriate tool carefully remove the terminal block cover plastic covering over the terminal block The terminal block cover is attached to the terminal block by two tabs with slots in the cover that insert into embossments in the terminal block wall To remove the cover press the upper wall of the terminal block wall downward and slip a flat bladed screwdriver between the cover and the terminal block wall and pry the cover tab up to relieve it from the embossment in the terminal block wall Once the upper cover tab is free from the terminal block embossment the cover should rotate downward and free itself from the lower embossment If the multimeter indicates there is still power present and power cannot be removed from the terminals the entire shelf must be powered down to perform the PEM replacement 6 g Confirm that there is no power to the PEM lug bolts Using a multimeter measure between the two lugs and then measure between the chassis ground and each lug If the DC potential is 3 0 VDC or less then power is not present Remove the DC power cables from the dual lug bolts on the PEM you are replacing being careful to place the two cables so they cannot short to ea
80. en you use electrically conductive tools near the PEMs Short Circuits or Personal Injury Ensure that the power feeds you plan to remove or attach are powered off and cannot be switched on while you are working AXP1620 Installation and Use 6806800E23L 27 Safety Notes Short Circuit and Electric Shock To avoid short circuits and electric shock the power lugs must not be energized before removing the screws It is essential to ensure that the power lugs are not energized before loosening the screws Be careful with the used tools in order to prevent a short circuit PEM Damage Applying reversal power causes damage to the electrolytic capacitors of the filter Therefore only switch on the breakers if no red light is visible Exchanging Fans Cabling 28 Personal Injury Rotating Fans Inserting tools or fingers into operational fans may cause injuries Fans become exposed when the fan tray is pulled Keep clear of the fans as long as they are rotating When the fan is removed extreme care should be taken while handling the fan itself The centrifugal forces will make the unit difficult to handle Personal Injury The cabling should follow existing cable paths using existing or similar cable fastenings Never change the system s cabling as delivered by Artesyn Check proper function of the system after cabling extensions To avoid injuries always ensure that cables are securely installed so that nobody can trip over them P
81. er 497 x 573 x 544 93 8 Ibs PEM 164x 73x 155 3 7 Ibs Upper Fan Tray Module 491x87x227 9 3 Ibs Lower Fan Tray Module 491 x 119x331 16 5 Ibs Shelf Management Alarm Module SAM 1 75x3x6 25 0 45 Ibs AXP1620 Installation and Use 6806800E23L 77 Site Preparation 3 2 5 78 Grounding To ensure the system is properly grounded each of the system s parts contact the EMI gasket The system contains gaskets at the shelf and module level The shelf is also fitted with ESD contacts Please take care for proper ESD protection of the operator Mounting Options You can simply operate the system on your desk or you can install it in a standard 23 rack During the course of handling shipping and assembly pins shrouds and mounting screws fans and other items can become loose or damaged Do not operate a damaged shelf this can cause damage to devices that interfere with it Do not remove shipping frame stiffeners until positioning is complete and all bolts are fully tightened Mounting without frame stiffeners may cause warping of the chassis Always lift the chassis from the bottom base of the chassis Do not lift chassis at the internal card cage Lifting at internal card cage may cause warping of the chassis and prevent proper insertion of blades products Do not lift chassis at the front upper fan tray or top front of chassis Lifting at these points may cause warping of the chassis and prevent proper EMI sealing or da
82. er Schaltschrank umkippen Bauen Sie das System deshalb ganz unten im Schrank ein wenn es das einzige System im Schrank ist Wenn mehrere Systeme in einen Schrank eingebaut werden sollen plazieren Sie das schwerste System ganz unten und die leichteren weiter oben Falls der Schaltschrank mit Kippsicherungen ausgestattet ist stellen Sie sicher dass diese auch installiert und ausgefahren sind um einen sicheren Stand des Schranks zu gew hrleisten Beginnen Sie erst danach mit dem Einbau oder der Wartung des Systems Verletzungsgefahr oder Besch digung des Systems Das System kann beim Herausziehen herunterfallen und Verletzungen verursachen Ziehen Sie das System vorsichtig heraus damit es nicht herunterfallt Verletzungsgefahr oder Besch digung des Systems Das System ist schwer und wenn Sie es alleine tragen kann dies zu R ckensch den f hren Heben Sie deshalb das System nur zu zweit und halten Sie beim Heben Ihren R cken gerade oder benutzen Sie zus tzliche Hilfsmittel Besch digung des Systems W hrend des Transportes und Zusammenbaus des Systems k nnen sich Teile wie zum Beispiel Schrauben Blenden Stecker oder L fter l sen oder besch digt werden Nehmen Sie das System nicht in Betrieb wenn Teile besch digt sind Dies k nnte zu Besch digungen an anderen Teilen f hren Hoher Ableitstrom Dieser Aufkleber befindet sich in der N he der Schuzleiter auf der R ckseite des Systems und warnt dass Sie vor der Inbetriebnahme
83. eren Steckpl tze mit Boards RTMs oder zugelassenen Platzhalter Boards belegt sind um die Sicherheits und EMCVorschriften zu erf llen Erdung Um eine korrekte Erdung des Systems zu gew hrleisten befinden sich sowohl am System als auch an den einzelnen Modulen Dichtungen Stellen Sie sicher dass alle Systemteile die EMI Dichtung ber hren Am System befinden sich auch ESD Kontakte Stellen Sie sicher dass jede Person die mit dem System arbeitet mit ESD Schutz zum Beispiel ESD B ndern ausger stet ist AXP1620 Installation and Use 6806800E23L Sicherheitshinweise Das Produkt ist eine Einrichtung der Klasse Agem dem Standard des Voluntary Control Council for Interference von Information Technology Interference VCCI Wird das Produkt in Wohngegenden betrieben k nnen St rungen im Hochfrequenzbereich auftreten In einem solchen Fall ist der Benutzer verpflichtet entsprechende Gegenma nahmen zu ergreifen Das Produkt ist f r den Einsatz in Netzwerken mit gemeinsamem Potentialausgleich oder mit isoliertem Potentialausgleich geeignet Systeminstallation Besch digung des Systems Bevor Sie das System installieren berpr fen Sie ob die im Handbuch beschriebenen Anforderungen erf llt werden Beachten Sie folgende allgemeinen Sicherheitshinweise vor der Installation und Verkabelung des Systems e Bereich mit eingeschr nkter Zugang Installieren Sie das System nur in Bereichen mit eingeschr nkter Zugang e In
84. ersonal Injury through Electric Shock Touching contacts and cables during system operation can cause injuries through electric shock To avoid electric shock make sure that contacts and cables of the system cannot be touched while the system is operating If in doubt concerning cabling ask your local Artesyn representative AXP1620 Installation and Use 6806800E23L Safety Notes Cable Damage Folding the fiber cable damages the cable and inhibits the data transmission Therefore make sure you do not fold the cable RJ 45 Connector Laser Battery System Damage RJ 45 connectors on blades are either twisted pair Ethernet TPE or E1 T1 J1 network interfaces Connecting an E1 T1 1 line to an Ethernet connector may damage your system Make sure that TPE connectors near your working area are clearly marked as network connectors e Verify that the length of an electric cable connected to a TPE bushing does not exceed 100 m Make sure the TPE bushing of the system is connected only to safety extra low voltage circuits SELV circuits e Ifin doubt ask your system administrator Personal Injury Some variants of the blades in the system are Class 1 laser products The use of controls or adjustments or performance of procedures other than those specified herein may result in hazardous radiation exposure Some variants of the RTM are a Class 1 laser product The use of controls or adjustments or performance of procedures othe
85. ew hrleistet ist berhitzung des Systems L ftungsschlitze Unzureichende L ftung kann Sch den an Boards und am System verursachen AXP1620 Installation and Use 6806800E23L 37 Sicherheitshinweise 38 Um eine ausreichende L ftung zu gew hrleisten stellen Sie sicher dass das System w hrend des Betriebs stets waagerecht steht und dass ein Freiraum von mindestens 60 mm an der R ckseite des Systems vorhanden ist Halten Sie die L ftungsschlitze an der Oberseite und der R ckseite des Systems frei Halten Sie die Frischluftzufuhr ffnung an der unteren Vorderseite des Systems v llig frei und stellen Sie sicher dass sich die Frischluft nicht mit der Abluft von anderen Systemen mischt Um eine ungest rte Luftzirkulation zu gew hrleisten stellen Sie sicher dass alle Steckpl tze mit Boards oder Platzhaltern belegt sind Besch digung des Systems Durch hohe Luftfeuchtigkeit k nnen Kurzschl sse entstehen Betreiben Sie das System nur innerhalb der angegebenen Grenzwerte f r die relative Luftfeuchtigkeit und Temperatur Stellen Sie vor dem Einschalten des Stroms sicher dass sich auf dem System und auf den Boards kein Kondensat befindet und starten Sie das System nicht unter 0 C Stromschlaggefahr Das System besitzt vier 48V bis 60V DC Anschl sse Alle Anschl sse m ssen vom System entfernt werden um das System spannungsfrei zu schalten Um eine Verletzungsgefahr zu minimieren entfernen Sie die Anschl sse wenn Sie d
86. fe operating temperatures Read all cautions and warnings and ensure the equipment is properly grounded by reviewing the procedure in Grounding the Shelf on page 96 and follow these steps The PEM has multiple power sources This procedure should be followed precisely to ensure the PEM is isolated from all power sources before removing the PEM from the shelf or removing the plastic terminal block lug cover This procedure assumes that the redundant PEMs are powered on in the shelf 132 AXP1620 Installation and Use 6806800E23L FRU Installation Removal Procedure To remove a PEM refer to this figure and follow the steps O O 48 VDC RTN Q O 48 VDC RTN 48 VDC 48 VDC 1 Turn off both breakers located on the PEM To turn off the breakers you need to use a tool small screwdriver which can be inserted into the opening of the protective covers which are assembled over top of these breakers When the breaker is turned to the OFF position the red part of the breaker switch will be exposed 2 Locate the target power input cable s terminals at the branch circuit or power distribution unit Open the external circuit breakers that provide DC feed power to the PEM you are replacing 3 Lock and tagout the circuit breakers on the branch circuit or power distribution unit 4 Open the
87. fice For released products you can also visit our Web site for the latest copies of our product documentation 1 Goto www artesyn com computing support product technical documentation php 2 Under FILTER OPTIONS click the Document types drop down list box to select the type of document you are looking for 3 Inthe Search text box type the product name and click GO Table A 1 Artesyn Embedded Technologies Embedded Computing Publications Document Title Publication Number Centellis 4620 Release 1 0 Document Collection 6806800648 AXP 1440 AXP1620 Subsystem IPMI Programmer s Reference 6806800G38 Centellis 4620 Release Notes 6806800E79 ATCA F120 Installation and Use 6806800D06 ATCA F120 Control through IPMI Programmer s Reference 6806800D18 RTM ATCA F120 Installation and Use 6806800D07 RTM ATCA F120 Control through IPMI Programmer s Reference 6806800D17 Pigeon Point Shelf Manager User Guide Release 2 5 3 6806800G49 Pigeon Point Shelf Manager External Interface Reference Release 6806800G50 2 5 3 AXP1620 Installation and Use 6806800E23L 167 Related Documentation A 2 168 Related Specifications For additional information refer to the following table for related specifications As an additional help a source for the listed document is provided Please note that while these sources have been verified the information is subject to change without notice Table A 2 Related Specifica
88. for various purposes Shelf FRU SEEPROM The SAM provides access to the SEEPROMS on the Alarm Display Panel ADP through the master only I C Information stored on the ADP contains Artesyn OEM records that enable the SAM to self configure for the AXP1620 shelf AXP1620 Installation and Use 6806800E23L 149 Shelf Management Alarm Module 7 4 5 SAM LEDs The SAM provides the LEDs listed in the following table More detail on the LEDs is provided in the following sections Also refer to Figure 7 2 on page 147 for SAM face plate LED locations and to Figure 2 1 on page 52 for the ADP teleco LED locations Table 7 3 SAM LEDs LED Type Location Teleco Critical alarm CRIT Alarm Display Panel Major alarm MAJ Minor alarm MIN In Service In Service IS SAM face plate Out of Service Out of Service OOS SAM face plate Hot Swap Hot swap ready HS SAM face plate 7 4 5 1 Hot Swap LED The SAM provides a blue hot swap LED This LED indicates when it is safe to remove the SAM from a live shelf Table 7 4 Hot Swap LED States off The SAM is not ready to be removed disconnected from the shelf Blue The SAM is ready to be removed disconnected from the shelf Long blink The SAM is activating itself Short blink Deactivation has been requested The software running on the shelf manager mezzanine is responsible for turning the LED on off using the GPIOs on the ShMC 150 AXP1620 Installation and Us
89. he equipment Artesyn intends to provide all necessary information to install and handle the product in this manual Because of the complexity of this product and its various uses we do not guarantee that the given information is complete If you need additional information ask your Artesyn representative The product has been designed to meet the standard industrial safety requirements It must only be used in its specific area of office telecommunication industry industrial control and development It must not be used in safety critical components life supporting devices or on aircraft Only personnel trained by Artesyn or persons qualified in electronics or electrical engineering are authorized to install remove or maintain the product The information given in this manual is meant to complete the knowledge of a specialist and must not be used as replacement for qualified personnel Keep away from live circuits inside the equipment Operating personnel must not remove equipment covers Only factory authorized service personnel or other qualified service personnel may remove equipment covers for internal subassembly or component replacement or any internal adjustment Do not install substitute parts or perform any unauthorized modification of the equipment or the warranty may be voided Contact your local Artesyn representative for service and repair to make sure that all safety features are maintained Danger of Injuries At the syste
90. he flash bank that is currently not active is programmed with the new images the processor is reset and the newly programmed flash bank is selected If the new firmware fails to load or execute properly the Shelf Manager automatically resets and reverts to the previous flash bank Selection of the bank to be used for booting is not a configurable option at run time The following text shows sample output obtained by running imls at the Shelf Manager Linux prompt Note that the first three images listed reflect the currently active flash bank contents and the next set of three images is contained within the other flash bank imls dev mtdblock3 Image Name U Boot 1 1 4 for shmm1500 board Created Fri Jun 6 14 51 44 2008 Image Type PowerPC Linux Firmware uncompressed Data Size 212992 Bytes 208 00 kB 0 20 MB Load Address 0xF0000000 Entry Point 0x00000000 dev mtdblock2 Image Name Linux 2 4 25 Created Fri Jun 6 14 59 00 2008 Image Type PowerPC Linux Kernel Image gzip compressed Data Size 793193 Bytes 774 60 kB 0 76 MB Load Address 0x00000000 Entry Point 0x00000000 dev mtdblock4 Image Name shelfman 4 0 0 build 21 Created Fri Jun 6 15 07 27 2008 Image Type PowerPC Linux RAMDisk Image gzip compressed Data Size 5398657 Bytes 5272 13 kB 5 15 MB Load Address 0x00000000 Entry Point 0x00000000 dev mtdblock8 Image Name U Boot 1 1 4 for shmm1500 board Created Thu Mar 27 21 2
91. hey communicate are determined by the network s topology The backplane of the AXP1620 uses a dual star topology that supports two independent networks The dual star uses a point to point configuration with redundancy added for reliability All devices on a star network are connected to a central connection point hub Nodes communicate across the network by passing data through the hub slot which on the AXP1620 contains a switching function that forwards packets to the appropriate port based on the packet s address Switching hubs support traditional Ethernet 10 Mbps Fast Ethernet 100 Mbps and Gigabit Ethernet 1000 Mbps ports AXP1620 Installation and Use 6806800E23L 43 Platform Architecture eee O 1 4 Network Descriptions This section describes the operational aspects of each of the shelf s network designs based on the Base and Fabric interfaces Zone 3 1 4 1 Base Interface NOTICE The blade slots are numbered physically from 01 to 16 going left to right along the front of the shelf Each slot also has a logical slot number that defines it for backplane connectivity logical slot numbers are not shown on the shelf Please note that the slots will be referred to by their physical slot location 44 AXP1620 Installation and Use 6806800E23L Platform Architecture The base hub slots physical slots 1 and 16 have four pairs of 1000Base T signals to node slots which form the dual star topology fabr
92. ic Each of the node slots support two base channel interface signals that connect to each hub slot In turn the channel 1 base interface of each hub slot is connected to the SAM Each of the hub slots support a total of 16 base channels The hub slots require connectors P23 and P24 The base node slots require only connector P23 1 4 2 Fabric Interface The fabric interface supports point to point connections between AdvancedTCA blades In the AXP1620 these fabric connections are configured in a dual star topology that runs back to the hub slots The AXP1620 system has one two or four channel slots These channels are aggregated at the hub slots into the dual star topology In this configuration all node slots support one fabric channel to each of the two hub slots The fabric channels are located on connector P20 of the node slots and connectors P20 P21 P22 and P23 of the hub slots The implementation of the interface is indicated by the level of PICMG compliance a blade or hub is designed to The AXP1620 supports the PICMG 3 1 fabric standard to allow for several configuration options that can provide greater bandwidth to certain slots in the shelf The fabric interface switch supports PICMG 3 1 Option 1 1 0Gbps Option 2 2 0Gbps and Option 3 4 0Gbps The following figure shows the AXP1620 shelf update channel connectivity AXP1620 Installation and Use 6806800E23L 45 Platform Architecture A PICMG 3 1 compliant hub provides
93. icable Installation Procedure without Installed Front Blade The following procedure describes the installation of the RTM 1 Locate the slot the RTM is to be installed into the shelf s rear which must be the same as that of the front blade 2 Ensure that the top and the bottom handles of the RTM are in an outward position by squeezing the lever and the latch together 3 Insertthe RTM into the shelf by placing the top and bottom edges in the card guides of the slot 4 Slide the RTM into the slot 5 Apply equal and steady pressure to the RTM to carefully slide the RTM into the shelf until you feel resistance Continue to gently push the RTM until the RTM connectors engage AXP1620 Installation and Use 6806800E23L 119 FRU Installation 6 Squeeze the lever and the latch together and hook the lower and the upper handle into the shelf rail recesses 7 Fully insert the RTM and lock it to the shelf by pressing the two components of the lower and the upper handles together and turning the handles toward the face plate 8 Tighten both face plate screws on the RTM 9 Insert the front blade from the system s front into the same slot as the RTM As soonas the front blade is connected to the backplane the blue hot swap LEDs of both the front blade and the RTM are illuminated permanently This indicates that the IPMC of the front blade and the MMC of the RTM are powered up 10 Close the handles of the front blade 120
94. ilter in a cleaner environment Check the filters frequently until you have a good idea of how often it needs cleaning Based on your findings establish a regular cleaning schedule and keep a log to record the date of each filter cleaning or replacement Air filters should also be checked occasionally to make sure they are not obstructed or damaged Visually inspect filters for tears or rips Do not reinstall a torn filter as it will be ineffective in trapping particulates and will interrupt air flow distribution To maintain safety certification use only Artesyn approved fan filters You can order replacement fan filters part number RAF1620 by contacting your Artesyn sales representative For replacement procedures refer to Replacing the Fan Filter on page 139 Cleaning the Air Filter To ensure the AXP1620 shelf operates properly routine filter maintenance is required as discussed in Air Filter Maintenance Maintenance includes cleaning replacing and properly storing the air filters Filter cleaning frequency depends on the environment the system is subjected to The shelf filter requires routine cleaning to ensure effective filtration and airflow To prevent air contamination from polluting the air filter and possibly obstructing the air intake of the system the air filter should be replaced according to the schedule you have established based on your Central Office Environment as discussed in Air Filter Maintenance Remove and inspec
95. information to prepare the site and the shelf for installation Receiving and Unpacking the System Carefully inspect the system and all components delivered together with it Personal Injury or System Damage The system is heavy and if you carry it on your own you can hurt your back To prevent injury keep your back straight and have two people lift the system or use additional lifting equipment Personal or System Damage Unstable system installation in a rack can cause the rack to topple over Therefore if your system is the only one in the rack make sure to mount the system in the lowest part of the rack If other systems are installed in one rack start with the heaviest component at the bottom If the rack is equipped with stabilizing devices make sure that they are installed and extended so that the rack is secure Then proceed to mount or service the system Do not tilt the system forward or backward when removing it from the system package as the FRU ejector handles at the bottom could be damaged AXP1620 Installation and Use 6806800E23L 71 Site Preparation 72 Damage of Circuits Electrostatic discharge and incorrect RTM installation and removal can damage circuits or shorten their life Before touching the RTM or electronic components make sure that you are working in an ESD safe environment Shipment Inspection To inspect the shipment perform the following steps 1 Verify that you have rece
96. ir own discretion to remove the mechanism which connects Logic Ground to Shelf Ground and install the mechanism that connects 48VDC Return to Shelf Ground If the system integrator exercises the option of removing the connections from Logic Ground to Shelf Ground and or adds the connection between 48VDC Return and Shelf Ground the responsibility for maintaining compliance to CSA C US VDE safety requirements and EMI RFI emission limits rests entirely with the system integrator and installer AXP1620 Installation and Use 6806800E23L AXP1620 Shelf Description 2 6 Backplane The shelf backplane supports 2 hub slots 14 node slots and two SAMs This AdvancedTCA backplane provides the IPMB and I C bus interface signals from the shelf manager to all AdvancedTCA blades and the other FRUs The backplane provides signal routing for fail over signals between active SAM and standby SAM The power connectors for the power entry modules are located on the backplane The backplane is not a Field Replaceable Unit FRU 2 6 1 Functional Layout The backplane provides dual star base interface and dual star fabric interface connections at each blade slot with segmented power five power segments provided by the dual Power Entry Modules PEMs AXP1620 Installation and Use 6806800E23L 55 AXP1620 Shelf Description The blade slots are numbered physically from 1 to 16 going left to right along the front of the shelf Numbers on slots 1 and 16 desig
97. ived all items of your shipment Compare the shipment thoroughly with the delivery note 2 Visually inspect the shelf to ensure that all of the connector pins are straight shrouds are properly seated screws are tight and so on Check the rails for proper alignment Check that the air filter is properly installed Check that the cable connections are secure and properly fitted Check the EMI gaskets for damage N DD WN A W Check the items listed above for damage and report any damage or differences to the customer service at www artesyn com computing 8 Tighten loose screws before proceeding AXP1620 Installation and Use 6806800E23L Site Preparation WY 3 2 2 3 2 3 3 2 3 1 9 Remove the desiccant bags delivered together with the system and dispose of them according to your country s legislation 10 Do not remove shipping frame stiffeners until positioning is complete and all bolts are fully tightened Mounting without frame stiffeners may cause warping of the chassis The system is thoroughly inspected before shipment If any damage occurred during transportation or any items are missing please contact our customer s service immediately Site and Installation Planning To plan basic site and installation requirements you have to consider the following issues 1 Is adequate power for the AXP1620 system available Can the system be positioned in a way that 48 to 60V DC power source is easy to
98. le The fan filter housing is kept in place by 2 tabs located on the inner left side in front of the stationary metal frame Air filters should be checked occasionally to make sure they are not obstructed or damaged Visually inspect filters for tears or rips Do not reinstall a torn filter as it will be ineffective in trapping particulates and will interrupt air flow distribution To maintain safety certification use only Artesyn approved fan filters You can order replacement fan filters part number RAF1620 by contacting your Artesyn sales representative For detailed information on filter maintenance and cleaning see Air Filter Maintenance on page 91 AXP1620 Installation and Use 6806800E23L 139 FRU Installation Replacement Procedure To replace the fan filter for a lower FTM refer to Removing the Lower FTM and follow these steps to replace a fan filter Please have your replacement fan filter available before starting this procedure 1 With the FTM removed and placed on a solid surface position the FTM with the front facing you 2 Using your fingers rotate the filter frame away from the housing using the two tabs on the right and left sides of the filter frame 3 Rotate the vane assembly out of the way to expose the lower portion of the air filter 4 Insert the replacement fan filter by positioning the filter onto the velcro edges and form into place NOTICE Any particulates that fall into the fan tray module during
99. lf After the reboot it makes a second attempt to initialize as a backup and will continue until either it succeeds in establishing the connection with the Active SAM or it detects that the Active SAM is no longer healthy If it detects that it isn t healthy it will initialize as the Active SAM AXP1620 Installation and Use 6806800E23L Shelf Management Alarm Module When the Active SAM receives a switchover command from the Standby SAM and agrees to switchover it closes the TCP connection clears the LOCAL_HEALTHY bit and exits the program which indicates the switchover to the Standby SAM If the Standby SAM decides that a switchover should take place it closes the TCP connection and exits this function Activate callbacks are called for all facilities and the SAM starts to work in active mode with no backup At this moment the SAM sets the LOCAL_SWITCHOVER bit requesting the hardware to recognize it as the Active SAM In response the hardware must set the ACTIVE bit When the formerly active SAM restarts it successfully establishes the connection with the current SAM and starts to operate in the backup mode 7 6 Telco Alarm Functionality The SAM provides Telco alarm functionality with the following components e Telco alarm cutoff push button e DB15 Telco alarm contacts e Telco alarm LEDs 7 6 1 Telco Alarm Cutoff Push Button The SAM provides a Telco alarm cutoff function with the front panel push button switch located on the A
100. ls and equipment are available Control the available installation tools and equipment Ensure that enough space is available Determine the needed power Plan the cable management Ensure proper cooling Schedule the arrival of system FOU UO Consider consulting of Artesyn services 82 AXP1620 Installation and Use 6806800E23L Site Preparation Figure 3 4 Planning Checklist 2 Issue Entry General site review FoF ioe CC S SYA aiiin Coo eh Installation date Loo Site address Loo y Oe Companyname DO Eh Special Instructions CT Operational days Lo ae CO u Coo k Path to the installation area clear SY ene C Eh cas PT ac E AXP1620 Installation and Use 6806800E23L 83 Site Preparation m 84 AXP1620 Installation and Use 6806800E23L AXP1620 Operations eee 4 1 Overview This chapter provides the basic operating procedures for the AXP1620 For software specific information or information regarding the operation of third party or add on components please refer to the software or hardware product s vendor documentation You can refer to Appendix A Related Documentation for a collection of supporting manuals This chapter covers the following topics Recommended Power On Procedures e Recommended Power Off Procedures Emergency Power Off Procedures Power Entry Module PEM e Fan Tray Modules e Air Filter Maintenance 4 2 Recommended Power On Procedures Procedure Follow these steps to power on
101. m 90 194 F the service personnel may touch the components the cables must be isolated and the hot surface icon must be attached The cables must be approved to be used in this temperature range 3 2 3 2 Power Requirements Make sure that a suitable 48VDC or 60VDC power source is within reach of the system Two power entry modules PEMs can be installed in the system The shelf may require up to 125 amps DC through 2 80 amp feeds The required cable size for 80 amps is 4 AWG wire Personal or System Damage The system may be supplied by a TNV 2 voltage This voltage is considered hazardous Make sure that the power supply unit meets the local safety standards 76 AXP1620 Installation and Use 6806800E23L Site Preparation Table 3 3 System Power Requirements Feature Value Rated voltage 40VDC to 60VDC SELV 60VDC to 72VDC TNV 2 Input current 125A Operating voltage range 40 0 to 72VDC When installing additional blades or modules make sure that the power consumption of all ly So installed modules does not exceed the system s maximum power dissipation 3 2 4 Dimensions and Weight The table below lists the dimensions and weight of the shelf and system components The maximum weight of the system must not exceed 208 lbs S 4 Table 3 4 Dimensions and Weight of System and Components Dimensions Component WxHxDinmm Weight Shelf including two fans two PEMs air filt
102. m s rear there are sharp pins which can cause injuries Be careful when handling the system AXP1620 Installation and Use 6806800E23L 19 Safety Notes EMC 20 The product has been tested and found to comply with the limits for a Class A digital device in this system pursuant to part 15 of the FCC Rules EN 55022 Class A respectively These limits are designed to provide reasonable protection against harmful interference when the product is operated in a commercial business or industrial environment The product generates and uses radio frequency energy and if not installed properly and used in accordance with this user s documentation may cause harmful interference to radio communications Operating the product in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense To ensure EMC protection use only shielded cables when connecting peripherals to assure that appropriate radio frequency emissions compliance is maintained Installed blades must have the face plates installed and all vacant slots in the shelf must be covered An AXP1620 thatis shipped as a spare replacement chassis or an unconfigured system will not have filler panels installed It is the responsibility of the customer to ensure that all open slots are filled with payload blades rear transition modules RTMs or approved filler panels in order to be compliant with the safety
103. m the shelf 1 Using a Phillips screwdriver loosen the two chassis retention screws Figure 6 3 Lower Front FTM Ejector Handles and LEDs 2 Open the ejector handle and wait for the Blue LED to go solid and steady This indicates that the FTM is ready to be removed 3 Open the ejector handle to a full open position 4 Using the ejector handle on the front of the FTM slowly pull the FTM out of the shelf while supporting the bottom of the module with the palm of your hand The module is heavy hold it securely 138 AXP1620 Installation and Use 6806800E23L FRU Installation 6 5 4 Installing the Lower FTM Installation Procedure Have the correct FTM available and follow these steps to install the upper fan tray module 1 While supporting the FTM align the FTM carefully into the fan slot in the shelf and slowly slide the FTM until the ejector handles engage fully close the handles The FTM is connected when the assembly is firmly seated in the upper backplane connector and the hot swap handle moves to the closed position 2 Hand tighten both chassis retention screws at the same time to secure the FTM Hand tool tighten both chassis retention screws alternating back and forth until hand tight The recommended torque settings is 5 inch pounds When the blue LED turns off the fan is operating 6 6 Replacing the Fan Filter Your replacement fan filter consists of a filter media for the lower Fan Tray Modu
104. mage to the fan tray AXP1620 Installation and Use 6806800E23L Site Preparation You have to keep in mind the following conditions when installing the system into a 600 mm 23 62 inch deep rack The physical dimensions in the figure below are in millimeters Figure3 1 Rack Mounting Dimensions Cabinet Door 3 5mm _ gt Air Outlet to Door at Back Side 25mm Thick __ of Rear Door Door 2X 13U Shelf Side View al 3mm to Door Air Inlet gt 75mm 42mm ii 550mm Inside Door to Door 600mm Deep Cabinet 3 2 6 Airflow Requirements The AXP1620 provides fault tolerant cooling to front mounted AdvancedTCA blades and to rear transition modules based on one front and one rear maintainable intelligent fan trays with six fans per tray AXP1620 Installation and Use 6806800E23L 79 Site Preparation Fan trays are mounted in the shelf top and bottom The figure below shows the general airflow for the system Figure 3 2 Shelf Airflow Upper FTM Outlet Plenum SO er mm Chassis Fa seen eee eee eeneee ened epee gt Exhaust semm Hamann Air Flow i ra i i 2 H Ir ra T I H 1 1 i 1 H ry 1 i i 1 H ry 1 I 1 i a nh 1 H 1 ru 4 1 1 1 Chassis 1 i R A Chassis 4 Front ot Rear 1 ot i io 1 1 1 4 I 1 1 1 1 H I 1 1 i 1 1 i 1 1 i 1 i 1 i ROOM sanma gt b
105. n F_ShMM_STATUS 0 4 a KK ShMM 1500R A F ShMM STATUS 1 ShMM 1500R B _ShMIM PRES GND N ShMM 1500R A buffer ShMM 1500R B buffer The HRI also includes 13 test points for in service monitoring of the hardware redundancy signals and for out of service diagnostics enabling the ShMM 1500R to isolate failures on the HRI to a single carrier SHMM 1500R pair 7 5 2 2 HRI Protocol In the redundant configuration the two ShMM 1500R boards communicate through the HRI by exchanging data packets The HRI continues to be operational in case of a single interconnection failure and is able to detect a double failure The HRI has a redundant communication path using four signals In the case of a single wire permanent failure the signal gets stuck high low or breaks data packets continue to be transmitted through the redundant communication path A short between two of these four signals is considered a double failure 156 AXP1620 Installation and Use 6806800E23L Shelf Management Alarm Module 7 5 2 3 Ethernet Signals The ShMM1500R provides two 100BaseT Ethernet ports identified within the Linux environment as ethO and eth1 The eth0 port is cross connected to the ethO port on the other SAM to provide a dedicated high speed inter SAM link for the exchange of status and configuration details The eth1 port is connected to an Ethernet switch a Broadcom BCM5325E which in turn connec
106. n their life Before touching the RTM or electronic components make sure that you are working in an ESD safe environment Installing the RTM You can install the RTM into a system if the front blade is already installed or if itis not installed If the front blade is already installed its payload has to be powered down first Installation Procedure with Installed Front Blade The following procedure describes the installation of the RTM It assumes that your system is powered If your system is unpowered you can disregard the blue LED and thus skip the respective step In this case it is a purely mechanical installation 1 Locate the slot the RTM is to be installed into the shelf s rear which must be the same as that of the front blade 2 Open the lower handle of the front blade in order to power down its payload The blue LED on the front blade starts to flash This indicates that the front blade is informing the shelf manager about its desire to power down its payload 3 Wait until the blue LED on the front blade is ON This indicates that the front blade s payload is powered down AXP1620 Installation and Use 6806800E23L FRU Installation 4 Ensure that the top and the bottom handles of the RTM are in an outward position by squeezing the lever and the latch together N Lever 5 Insert the RTM into the shelf by placing the top and bottom edges in the card guides of the slot 6 Slide the RTM into the slot 7 A
107. nate the hub slots Each slot also has a logical slot number that defines it for backplane connectivity logical slot numbers are not shown on the shelf The backplane functional layout is shown in the following figure Figure 2 3 Backplane Power Segments Power Segments lt Physical Logical ATCA P Blade Slots Power Segments Lower FTM Lower Rear 2 6 2 E Keying The AXP1620 supports the shelf management infrastructure with a process called E Keying E Keying replaces the mechanical connector keying method used in earlier backplane designs E Keying prevents damage to blades prevents misoperation and verifies fabric compatibility 56 AXP1620 Installation and Use 6806800E23L 2 6 3 2 6 4 AXP1620 Shelf Description E Keying entries are present as FRU information in the shelf FRU and all blades present in the shelf The E Keying entries describe the Base Interface Fabric Interface Update Channel Interface as implemented by the shelf and blades E keying allows blades that support different PICMG 3 standards to be used in the same shelf More detailed information suchas connectivity and requirements for E Keying can be found in PICMG 3 0 R1 0 AdvancedTCA Specification and the AXP1620 Subsystem IPMI Programmer s Reference listed in Appendix A Related Documentation Shelf FRU Information The SEEPROMs are located on the Alarm Display Panel ADP the FRU information for
108. nce securely mounted to the floor or if using stabilizing devices make sure they are installed and to the NEBS 24 deep lineup and the ETSI 600mm deep lineup standards for 96 AXP1620 Installation and Use 6806800E23L 5 3 4 5 3 5 Use ESD protection AXP1620 Shelf Installation Weight Distribution Within a Rack To avoid personal injury or damage to the equipment plan your installation so that within the limitations of equipment and cabling The weight of the equipment is evenly distributed in the rack The heaviest units are mounted nearer the bottom of the rack Uneven mechanical loading of the rack may cause toppling Electrostatic Discharge ESD and Safety Procedures Artesyn strongly recommends that you use an antistatic wrist strap and a conductive foam pad when installing or upgrading a shelf Electronic components such as disk drives computer boards and memory modules can be extremely sensitive to electrostatic discharge ESD After removing the component from its protective wrapper or from the shelf place the component flat on a grounded static free surface and in the case of a blade component side up Do not slide the component over any surface If an ESD station is not available you can avoid damage resulting from ESD by wearing an antistatic wrist strap available at electronics stores that is attached to an active electrical ground Note that a shelf may not be grounded if it is unplugged
109. nd their amending directives Product ATCA 16 Slot Shelf Model Name Number AXP1620 AXP1620 GB AXP1620 R10 HJP CENT 4620 R10 01 CENT 4620 R10 02 CENT 4620 R10 02 HJP has been designed and manufactured to the following specifications EN55022 2006 A1 2007 Class A EN55024 1998 A1 2001 A2 2003 ETSI EN 300 386 V1 5 1 2010 10 IEC 60950 1 2005 2nd Edition EN60950 1 2006 A11 2009 2011 65 EU RoHS Directive As manufacturer we hereby declare that the product named above has been designed to comply with the rele vant sections of the above referenced specifications This product complies with the essential health and safety requirements of the above specified directives We have an internal production control system that ensures compliance between the manufactured products and the technical documentation es 05 20 2014 Tom Tuttle Manager Product Testing Services Date MM DD YYYY 68 AXP1620 Installation and Use 6806800E23L AXP1620 Shelf Description 2 11 WEEE Compliance To satisfy the requirements for marking electrical and electronic equipment in accordance with article 11 2 of Directive 2002 96 EC Waste from Electrical and Electronic Equipment WEEE Artesyn Embedded Technologies includes a e crossed out bin symbol on all standard and noncustom chassis product This a marking fulfills the requirement set out by WEEE that a producer of an electrical or electronic appliance that bears
110. nector ccc eee cece eee eee e eee 149 Table 7 3 SAM LEDS u Sato aa Wao era ee EE E REEE ERNAS 150 Table 7 4 HOt SWap LED States us 2002 0 eds ad 150 Table 7 5 SAM LED Status Indicators 0 0 0 eee een ene e tence nee eee nennen 151 Table 7 6 ADP LED Status Indicators 0 cece cece e eee n een e eet e ee een eens 151 Table 7 7 Cooling B dget 55 2205 una ne ee Ge eee aed whee es 154 Table 7 8 Shelf Manager Static Network IP Interfaces cece eee e ence cent nee nee 159 Table 7 9 Shelf Manager Dynamic Network IP Interfaces 2 seen eee eee ee ences 159 Table 7 10 Hot Swap Interface Pin Out cece cece cece eee ene e nen nee eee n anaes 162 Table A 1 Artesyn Embedded Technologies Embedded Computing Publications 167 Table A 2 Related Specifications cece ccc eee nen nent nee n ene e ee nennen 168 AXP1620 Installation and Use 6806800E23L 11 List of Tables a 12 AXP1620 Installation and Use 6806800E23L About this Manual Overview of Contents This Installation and Use manual is organized as follows Sicherheitshinweise Platform Architecture AXP1620 Shelf Description Chapter Description About this Manual Lists all conventions and abbreviations used in this manual and outlines the revision history Safety Notes Describes the safety information which has to be regarded Translation of the chapter Safety Notes to German Describes the system architec
111. nee eee eee nent ee en eens 57 Table 2 3 Backplane COMNneCtGMs osse i dseriasn awe oon chaise ed sea Lak u weeks 58 Table 2 4 Slot Hardware Addressing for J10 cece cece cece e eee eee rererere 58 Table 2 5 Fan Tray Module Hardware Addressing 2 cee e cece eee e eee e ene nennen nen 59 Table 2 6 SAM and PEM Hardware Addressing 0 cece eect eee cette eee en eee eeneeaee 60 Table 2 7 FIM LED Status Indicators 1 0 0 eee cece cect eee e E nent nee n enn EEA 62 Table 2 8 PEM LED Status INGiCatols un ee es 65 Table 2 9 ADP LED Status Indicators 0 cece cece een een cence nent been eee eeae 66 Table 2 10 Standard Eompli nces ue nae nee am en str e 67 Table 3 1 Environmental Conditions 0 e cece eee ee eee nee ene eect neeneeeees 74 Table 3 2 Critical Temperature Limits 0 0 cece eee eee e eee n ence eee neeaee 75 Table 3 3 System Power Requirements nee 77 Table 3 4 Dimensions and Weight of System and Components 0e eee e eee ence eens 77 Table 4 1 PEM IPMB Addresses 002 ec cece ence tniii ei ce te eect ne en nanenn nenn 88 Table 4 2 Cooling B dget 4 eriei 21 AG As tee Oe FAs dats see eeeey Meh abas tas 90 Table 5 1 AXP1620 16 Slot Shelf Physical Characteristics 0c cece cence eee cence eeees 93 Table 7 1 RJ 45 Serial Port Connector 2 2 0 2 02 e eee eee eee ene eect e eee nennen 148 Table 7 2 Alarm Display Panel ADP Serial Port Con
112. nslation Cet appareil est con u pour permettre le raccordement du conducteur reli la terre du circuit d alimentation c c au conducteur de terre de l appareil Pour ce raccordement toutes les conditions suivantes doivent tre respect es e Ce mat riel doit tre raccord directement au conducteur de la prise de terre du circuit d alimentation c c ou a une tresse de mise a la masse reli e a une barre omnibus de terre laquelle est raccord e a l lectrode de terre du circuit d alimentation c c e Les appareils dont les conducteurs de terre respectifs sont raccord s au conducteur de terre du m me circuit d alimentation c c doivent tre install s a proximit les uns des autres p ex dans des armoires adjacentes et a proximit de la prise de terre du circuit d alimentation c c Le circuit d alimentation c c ne doit comporter aucune autre prise de terre e Lasource d alimentation du circuit c c doit tre situ e dans la m me piece que le mat riel ne doit y avoir aucun dispositif de commutation ou de sectionnement entre le point de raccordement au conducteur de la source d alimentation c c et le point de raccordement a la prise de terre System Overheating If you reduce the fan speed the system temperature will rise Constantly control the system temperature once you have reduced the fan speed While operating the system ensure that the environmental and power requirements are met 26 AXP1620 Installation and Use
113. ogram these images into flash and then reset to execute the new images rupgrade_tool s v d a hook erase The hook erase argument is optional and is normally not used This directs the upgrade procedure to avoid preserving the customer specific configuration files etc shelfman conf and etc shelfman conf sam1500 Normally these files should be preserved across an upgrade but on occasion when Artesyn makes a change to the format of the configuration options you may be instructed to use this option In this case you need to re enter the configuration by editing these files following the upgrade The files are copied to flash memory and the system should reboot in a couple of minutes When the system is restarted the bootup logic automatically determines if the SAM1500 FPGA needs to be loaded to a new firmware revision If so an additional upgrade and reboot takes place and takes an additional 5 8 minutes The SAM should now be running the new firmware The process can now be repeated with the other Shelf Manager AXP1620 Installation and Use 6806800E23L 113 AXP1620 Shelf Installation eee EEE 114 AXP1620 Installation and Use 6806800E23L FRU Installation ee 6 1 Overview The following chapters help you to start up and maintain the system Installing RTMs blades and SAMs This section provides information about how to install and remove RTMs AdvancedTCA blades and shelf management alarm modules
114. on The following figure shows the location of each of the components in the AXP1620 Figure2 1 Front Shelf View Alarm Display Panel o we a 9 ae ae O 6 6 6 6 ACTB ACTB PWRMIN MAJ CRT ACO AAN Management Tray je Je Je Je le oe je eo le Je je Je le oe FanTray 52 AXP1620 Installation and Use 6806800E23L AXP1620 Shelf Description Figure 2 2 Rear Shelf View FanTray O Backplane 1 O O Cable Management Tray on F on Qoss Qoss or on OFF e La le e 5 je Sie Sa e C e ye RC amp Som 1 if 22h 02 av a we amp E O a we PEM 1 Circuit Breakers SAM1 SAM2 ircuit Breakers PEM2 Earth Ground FEED B2 B4 FEED B1 B3 FEED A2 A4 FEED A1 A3 Phy Slots Phy Slots Phy Slots Phy Slots 9 to 16 1t08 9 to 16 1to8 Lower
115. on and keep clear at least 60 mm at the back of the system Do not obstruct the ventilation openings at the top and back of the system Keep the fresh air intake at the bottom front side of the chassis completely clear and ensure that fresh air supply is not mixed with hot exhaust from other devices To ensure proper air flow within the system make sure that all slots are populated with either filler blades blades or dummy blades Product Damage High humidity and condensation on blade surfaces causes short circuits Do not operate the system outside the specified environmental limits Make sure the system is completely dry and there is no moisture on any surface before applying power Do not start the system below 0 C Injury Caution this unit has four 48V to 60V DC feeds All must be disconnected to de energize the system To reduce the risk of injury disconnect the feeds when removing power from the system System Damage Air Filter Air contamination can pollute the air filter and obstruct the air intake of the system which may cause system overheating and component damage To guarantee proper airflow through the system the air filter has to be replaced at least every six months Artesyn Embedded Technologies recommends to replace the air filter every 90 days Filter replacement frequency depends on the environment the system is subjected to Because central offices vary in physical location and cleanliness check your air filters e
116. onditions Temperature 5 C 41 F to 40 C 104 F normal operation according to NEBS standard GR 63 CORE 5 C 23 F to 55 C 131 F exceptional operation according to NEBS standard GR 63 CORE Non Operating packed state 40 C 40 F to 70 C 158 F Temp change Relative humidity 0 25 C min according to NEBS standard GR 63 CORE 5 to 90 non condensing according to Artesyn internal environmental requirements 0 25 C min 5 to 95 non condensing according to Artesyn internal environmental requirements Shock Vibration tested in target platform Half sine 11 ms 30 m s 0 1g from 5 Hz to 100 Hz and back to 5 Hz ata rate of 0 1 octave minute Blade level packaging Half sine 6 ms at 180 m s 5 20 Hz at 0 01 g Hz 20 200 Hz at 3 0 dB octave Random 5 20 Hz at 1m2 s Random 20 200 Hz at 3 dB octave Free fall 74 300mm 11 8 in packaged 25mm 1 in unpackaged per GR 63 CORE fully populated system AXP1620 Installation and Use 6806800E23L Site Preparation Table 3 1 Environmental Conditions continued Feature Operating Non Operating packed state ETSI ETS 300 753 October 1997 Telecommunication equipment rooms attended 7 2 bel Measurement of declared A weight sound power level All values are applicable to normal operating conditions 23 C NEBS GR 63 CORE Issue 3 Telecommunication equipment rooms a
117. pins shrouds and mounting screws fans and other items can become loose or damaged Do not operate a damaged shelf this can cause damage to devices that interface with it AXP1620 Installation and Use 6806800E23L Safety Notes Electrical Hazard The caution label on the system s rear near the grounding studs shows that you have to create an earth connection because there may be a high leakage current which is considered as hazardous High leakage current can cause injuries Therefore it is essential that you create an earth connection before connecting the PEM to a telecommuncation network System Damage Wrong jumper settings can make the shelf in operable Therefore never change the settings of the jumpers Blade and RTM Installation Damage of Circuits Electrostatic discharge and incorrect RTM or blade installation and removal can damage circuits or shorten their life Before touching the RTM blade or electronic components make sure that you are working in an ESD safe environment Installation Sequence of RTMs and AdvancedTCA Blades If you are going to install an RTM and an AdvancedTCA blade you have to regard the following sequence First install the RTM then install the matching AdvancedTCA blade Otherwise the blades and RTMs will be damaged Blade or System Damage Installing a blade in the wrong slot causes blade or system damage Only install blades in the designated slots AXP1620 Installation and Use
118. pply equal and steady pressure to the RTM to carefully slide the RTM into the shelf until you feel resistance Continue to gently push the RTM until the RTM connectors engage 8 Squeeze the lever and the latch together and hook the lower and the upper handle into the shelf rail recesses AXP1620 Installation and Use 6806800E23L 117 FRU Installation 9 Fully insert the RTM and lock it to the shelf by pressing the two components of the lower and the upper handles together and turning the handles toward the face plate If your shelf is powered as soon as the RTM is connected to the front blade the blue LED is illuminated and will remain illuminated until both the lower handle of the RTM and the lower handle of the front blade are closed 10 Close the lower handle of the front blade in order to power up the payload of both the front blade and the RTM The blue LEDs of both the front blade and the RTM start to flash This indicates that the front blade is informing the shelf manager about its desire to power up the payload of both the front blade and the RTM 11 Tighten both face plate screws on the RTM 12 Wait until the blue LEDs of both the front blade and the RTM are OFF 118 AXP1620 Installation and Use 6806800E23L FRU Installation A switched OFF blue LED indicates that the payload of the respective blade or RTM has been powered up and is active 13 Plug interface cable into face plate connectors if appl
119. r than those specified herein may result in hazardous radiation exposure Blade Damage Wrong battery installation may result in hazardous explosion and blade damage AXP1620 Installation and Use 6806800E23L 29 Safety Notes Always use the same type of battery as is installed and make sure the battery is installed as described in the user manual of the blade Always dispose of old batteries according to your country s legislation Environment Environmental Always dispose of used blades system components and RTMs according to your country s legislation and manufacturer s instructions 30 AXP1620 Installation and Use 6806800E23L Sicherheitshinweise ese Dieses Kapitel enth lt Hinweise die potentiell gef hrlichen Prozeduren innerhalb dieses Handbuchs vorrangestellt sind Beachten Sie unbedingt in allen Phasen des Betriebs der Wartung und der Reparatur des Systems die Anweisungen die diesen Hinweisen enthalten sind Sie sollten au erdem alle anderen Vorsichtsma nahmen treffen die f r den Betrieb des Systems innerhalb Ihrer Betriebsumgebung notwendig sind Wenn Sie diese Vorsichtsma nahmen oder Sicherheitshinweise die an anderer Stelle diese Handbuchs enthalten sind nicht beachten kann das Verletzungen oder Sch den am System zur Folge haben Artesyn ist darauf bedacht alle notwendigen Informationen zum Einbau und zum Umgang mit dem System in diesem Handbuch bereit zu stellen Da es sich jedoch bei dem System um ein
120. re between the chassis ground and each lug If the DC potential is 3 0VDC or less then power is not present 5 Attach the DC power cables input and return to the dual lug bolts on each PEM 6 Using a torque wrench tighten the nuts with a recommended torque setting of 35 5 to 38 5 inch pounds Make sure all DC leads are fastened securely 7 Replace the plastic cover over the terminal blocks 8 Verify that the circuit breakers are in the ON position 104 AXP1620 Installation and Use 6806800E23L AXP1620 Shelf Installation 9 Break the tagout or lockout seals on the branch circuit or power distribution unit 10 Apply power by closing the branch circuit or power distribution unit The OOS indicator LED will glow solid red and the other LEDs will go dark The OOS will not go dark and the IS indicator LED will not illuminate until the external power circuit breakers are closed 11 Verify that all FRU LEDs illuminate and the PEM s IS LED is green and the OOS LED is dark 5 10 Powering Up the System With the installation cabled up you are ready to apply power to the system Cover all open module slots and put all approved filler panels in place before turning on power This is necessary to properly cool the chassis and to avoid electrical shock and other possible hazards Slot covers and panels must remain in place during system operation Procedure Follow these steps to power up the system 1 Push the PEM circ
121. re running on the SAM is responsible for reacting to an event when an interrupt is triggered by the ADM1024 device Temperature Monitoring An on board temperature sensor is available on the SAM This sensor is implemented through the ADM1024 Fan Speed and Control All fan speed and fan voltage sensors are exposed on the active SAM The FTMs have 110 fan speed settings The SAM uses a proprietary cooling algorithm to automatically adjust the fan speed to cool the chassis based on sensor data from the blades as well as inlet and outlet sensors on the FTMs The minimum fan speed is 1 In normal operating conditions the cooling algorithm adjusts the fan speed based on the ambient air temperature as measured at the inlet fans to maintain a deltaT value calculated to be the rise in airtemperature measured at the inlet and outlet fan sensors based on the inlet air temperature value The lower the ambient temperature the higher the rise in temperature allowed AXP1620 Installation and Use 6806800E23L Shelf Management Alarm Module The deltaT set point is calculated as follows Set Point A S1 l gt T1 T2 Inlet Air Temperature For ambient air temperatures at or below 25 C default T1 the deltaT set point is set to 20 C default S1 For ambient air temperatures at or above 55 C default T2 the deltaT set point is set to 10 C default S2 For ambient air temperatures between T1 and T2 the deltaT set point
122. ring an emergency situation Following this procedure will result in a loss of data and may cause damage to chassis components in a running platform Use this method only when normal shutdown procedures cannot be followed 86 AXP1620 Installation and Use 6806800E23L AXP1620 Operations 4 5 4 5 1 1 Turn each circuit breaker on the front of PEM A and PEM B to the OFF position 2 Disable the DC power at the external sources branch circuit or power distribution unit for PEM A and PEM B Power Entry Module PEM This section discusses the operations of the Power Entry Module for the AXP1620 configurations Description The AXP1620 has PICMG 3 0 compliant dual PEMs and is rated for nominal 48VDC to 60VDC The PEMs plug directly into the midplane and deliver power to the backplane Each input is rated for 80 amps The two 80 amp feeds each power eight AdvancedTCA slots and the upper and lower FTMs Each PEM also generates a separate 1 2V for redundant powering of the SAMs This voltage is distributed to each of these modules across the backplane Power conversion for the SAMs and PEMs consists of two 66 watt 48VDC to 12VDC converters which distribute dual power busses of 12VDC to separate parts of the system The 12VDC outputs are provided on the backplane connector to the rest of the shelf Power is redundant through the secondary PEM Removing power to these components cannot be accomplished by turning the P
123. sentry shmm1500 u boot bin All files should be loaded onto both ShMs using the procedures described here These files also contain firmware to be loaded into the SAM1500 FPGA The SAM1500 FPGA will be programmed automatically if necessary by the process As upgrades are released Artesyn will supply the current version of these files Shelf Manager Upgrade Steps The upgrade process involves the following steps 1 Preserving and restoring configuration settings Normally any configuration settings you have saved in etc shelfman conf and etc shelfman conf sam1500 are preserved during the upgrade procedure if you are starting with a version of shelfman that is at revision PPS 2 5 2 or higher so you do not need to save and restore unique settings saved in these files Occasionally however a firmware upgrade presents a change in the options presented in these configuration files If this is the case you are asked to note any changes to settings you have made to these files and to perform the upgrade in a way that overwrites these configuration files You then need to edit these text files reapplying your changes NOTICE If you are starting from an earlier version of shelfman prior to PPS 2 5 2 your configuration files will not be preserved across an upgrade and you will need to restore any special configuration settings by editing the conf files after the upgrade 2 Upgrading the U boot kernel and root file system images
124. shelf is powered as soon as the blade is connected to the backplane power pins the blue LED is illuminated When the blade is completely installed the blue LED starts to blink This indicates that the blade announces its presence to the shelf management controller If an RTM is connected to the front blade make sure that the handles of both the RTM and the front blade are closed in order to power up the blade s payload 6 Wait until the blue LED is switched off then tighten the face plate screws which secure the blade to the shelf AXP1620 Installation and Use 6806800E23L 125 FRU Installation u 6 2 2 2 126 The switched off blue LED indicates that the blade s payload has been powered up and that the blade is active 7 Connect cables to the face plate if applicable After the blade has been inserted you have to ensure that a boot image is either present on the ATCA F120 or on the blade s hard disk Removing the Node Blade This section describes how to remove the blade from an AdvancedTCA system Damage of Circuits Electrostatic discharge and incorrect blade installation and removal can damage circuits or shorten their life Before touching the blade or electronic components make sure that you are working in an ESD safe environment Blade Malfunctioning Incorrect blade installation and removal can result in blade malfunctioning When plugging the blade in or removing it do not press on th
125. specifications for this shelf There are four lugs for each PEM Two are straight and the other two are custom offset lugs The end that connects to the external DC power source should be equipped with an 8mm terminal Always check with your local building authorities for wire sizing requirements for your environment The installation must comply with the 1993 National Electric Code NEC and other applicable codes The DC power inputs must only be attached to approved Telephone Network Voltage TNV or SELV Safety Extra Low Voltage branch circuits Branch circuits must comply with all requirements called for in these safety standards IEC 60950 EN 60950 CAN CSA C22 2 No 60950 Attaching inputs to non TNV SELV approved power sources will cause the system to fail compliance with safety regulations The ground wire must be connected to a reliable earth ground connection to comply with Class 1 Equipment requirements Multiple power sources are present Service only by qualified service personnel Mehrfache Energiequellen Handhabung nur durch geschultes Personal Des sources multiples de pouvoir sont pr sentes L entretien de cet quipement doit tre effectu par du personnel de service qualifi Earth Ground PE GND Primary Earth Ground Input power 48VDC nominal to 60VDC Return 48VDC RETURN AXP1620 Installation and Use 6806800E23L 101 AXP1620 Shelf Installation Figure 5 4
126. stallationsrichtlinien Dieses System muss gem folgender Richtlinien installiert werden National Electrical Code Artikel 110 16 110 17 und 110 18 und Canadian Electrical Code Abschnitt 12 a e Uberstrom Schutzeinrichtung Eine leicht zug ngliche Trennvorrichtung muss in der Geb udeverkabelung eingebaut sein Einen angemessenen AWG American Wire Gauge amerikanische Norm f r Drahtquerschnitte Wert der berstrom Schutzeinrichtung k nnen Sie der NEC National Electrical Code Tabelle 310 16 oder anderen nationalen Regelwerken entnehmen e Der Erdungsleiter ist abh ngig von der Spannungsverteilungstopologie innerhalb Ihrer Anlage Stellen Sie sicher dass Sie einen angemessenen Erdungsleiter gem der Auslegung des Zugangsleitungsschutzes verwenden e Bauen Sie das System sicher ein Stellen Sie sicher dass Kabel und Leitungen nicht im Weg sind e Stellen Sie sicher dass der Systemaufbau anwenderfreundlich ist AXP1620 Installation and Use 6806800E23L 33 Sicherheitshinweise Besch digung des Systems Die Geb ude internen Schnittstellen intra building ports per GR 1089 CORE der Ger te oder Baugruppen sind nur f r geb udeinterne Verkabelung vorgesehen Die Schnittstellen sind als Typ 2 oder Typ 4 definiert wie in GR 1089 Core beschrieben und erfordern eine Isolation zu Leitungen au erhalb des Geb udes Die Geb ude internen Schnittstellen d rfen keine elektrisch leitende Verbindung zu Leitungen au erhalb des
127. t Removal Procedure To remove a SAM from a non powered shelf proceed as follows 1 2 5 Put on an ESD wrist strap Connect the strap to the shelf by attaching the front or rear ESD jack Unfasten the captive screw at the upper left hand corner of the face plate until the board is detached from the shelf Unlock ejector handle by pressing the handle and pull down The SAM should start to move out of the chassis Do not force it If the SAM does not move it means the captive screw is not fully unscrewed Unscrew until loose and rotate the ejector handle down Remove the module from the shelf Powered System This section describes the installation and removal procedures for a SAM in powered systems AXP1620 Installation and Use 6806800E23L 129 FRU Installation 130 Installation Procedure To install a SAM in a powered shelf proceed as follows 1 2 3 Put on an ESD wrist strap Connect the strap to the shelf by attaching the front or rear ESD jack Insert the module into the shelf by placing the top and bottom edges of the board in the card guides of the shelf Ensure that the guiding module of shelf and board are aligned properly The alignment pin facilitates the insertion and prevents bent pins Slide the module into the shelf and rotate the ejector handle upward until it snaps into place Wait until the blue LED is illuminated Screw in the captive screw hand tight The blue LE
128. t backplane voltages current sensors to detect current to the backplane and on board circuitry to detect failures on the PEM The PEMs are managed by the Sentry Shelf Management software Refer to the AXP1620 Subsystem IPMI Programmer s Reference guide listed in Appendix A Related Documentation for more information Table 4 1 PEM IPMB Addresses IPMB Address 0x66 Description PEMB 0x68 Figure 2 3 on page 56 provides a conceptual view of the connections between the PEMs backplane FTMs and SAMs AXP1620 Installation and Use 6806800E23L AXP1620 Operations 4 6 4 6 1 Fan Tray Modules This section discusses the operation of the Fan Tray Modules FTMs of the AXP1620 Description The FTMs are loaded with AdvancedTCA IPMC firmware The fans are controlled as a group through the IPMI based interfaces IPMB to the SAM The IPMI interface is used for reporting faults events and status The shelf manager software performs management of the FTM through the IPMB bus The IPMC circuit provides temperature sensors for monitoring the temperatures of the FTM board components and for monitoring the inlet and outlet air temperature of the shelf For further information refer to the AXP1620 Subsystem IPMI Programmer s Reference guide listed in Appendix A Related Documentation The upper FTM receives its signal and power connections from the backplane through a FTM distribution board A fan interconnect board
129. t directly with the connectors on the front side blade and do not make the connection through the backplane 60 AXP1620 Installation and Use 6806800E23L AXP1620 Shelf Description Figure 2 4 Blade Slot Connectivity Figure2 5 Hub Slot Connectivity AXP1620 Installation and Use 6806800E23L 61 AXP1620 Shelf Description 2 7 62 Fan Tray Modules FTMs The AXP1620 supports 2 fan trays in a push pull configuration Each fan tray contains 6 dual counter rotating fans The lower fan tray is accessible from the front of the chassis and contains the replaceable air filter The upper fan tray is located in the rear of the chassis The FTM has a ejector handle which signals the IPM Sentry software for hot swap If your system is not running high availability software behavior of the LED may be indeterminate The face plate of the upper and lower FTMs has the following indicators Table 2 7 FTM LED Status Indicators FTM LED LED Color State Condition In Service IS Off no service Blink FTM activating Glow Steady service available Out of Service OOS and Red default Off service available Failure Blink Deactivation requested Glow Steady no service Hot Swap H S Blue Off FTM is not ready to be removed Blink Deactivation requested Glow Steady FTM is ready to remove Figure 2 6 Lower Fan Tray Module Front View OCOC i sees COOOX X
130. t the filter for tears or damage before cleaning it If the filter is torn or damaged discard the filter and replace it with a new one Refer to Replacing the Fan Filter on page 139 if you need help If the filter is undamaged proceed to clean it There are several methods for cleaning the air filter 1 Vacuum clean A few passes of a vacuum cleaner can remove accumulated dust and dirt AXP1620 Installation and Use 6806800E23L 91 AXP1620 Operations 2 Oil free compressor air Point the compressed air nozzle in the opposite direction of the filter s operating airflow blow from the filter s exhaust side toward the intake side 3 Cold water rinse Collected dirt is washed away using a standard hose nozzle with plain water Ensure the filter is completely dry before returning to service 4 Immersion in warm soapy water Dip the filter in a solution of warm water and mild detergent Then rinse the filter in clear water and let stand until completely dry before returning to service Before returning a filter to service visually inspect it for tears or rips that may have occurred during cleaning Do not reinstall a torn filter as it will be ineffective in trapping particulates and will interrupt air flow distribution You may order replacement fan filters part number RAF1620 by contacting your Artesyn sales representative 4 8 1 92 Storing the Filter The ideal storage condition for the air filter is a cool
131. tegrated platform Base platform 2 shelf managers 2 PEMs 1 upper FTM 1 lower FTM no payload blades AXP1620 Installation and Use 6806800E23L 93 AXP1620 Shelf Installation Table 5 1 AXP1620 16 Slot Shelf Physical Characteristics continued Characteristics Specifications Rack Mounting Per ETSI 600mm x 600mm ETSI frame on integrated front frame mounting ears Frame mounting brackets are required for a 23 EIA frame Rear mounting brackets are recommended in both instances for Central Office Environment Each shelf requires 13U of space and effectively takes up 13U when mounted in a rack Three shelves can fit in a 40U telecom rack which leaves 1U remaining Cable management trays are available for the front and the rear of the shelf 5 3 Installation Prerequisites This section describes the prerequisites required for installation 5 3 1 Equipment You Will Need You will need the following to install the AXP1620 16 slot shelf into an approved EIA 23 or 600mm x 600mm ETSI frame e Torque wrench e Nut driver with 7 16mm socket e Multimeter e Phillips head screwdriver 1 e Front mounting brackets for an EIA 23 frame shipped with your AXP1620 e AdvancedTCA PEM Service Kit PN 6706808A01 shipped with your AXP1620 e Right angle Cable Lug Kit PN 6706808A01 shipped with your AXP1620 94 AXP1620 Installation and Use 6806800E23L AXP1620 Shelf Installation 5 3 2 Rack Cabinet Cooling
132. the PEM is contained in FRU 0 This information is accessed by using the standard IPMI FRU commands over the IPMC Refer to the AXP1620 Subsystem IPMI Programmer s Reference listed in Appendix A Related Documentation The SAM queries all IPMCs during system startup to determine whether they are a source of shelf FRU information and then uses that information to complete initialization The information is cached as FRU 254 on the active ShMC 0x20 The information in the SEEPROM is only needed when the SAMs are first inserted or when the shelf is powered on for the first time The redundancy feature provides the shelf specific information should one SEEPROM be nonfunctional Backplane Slot Connectors The following table provides a summary of what resides on each of the slot connectors Table 2 2 Slot Connector Description Connector Slots 1 and 16 Physical Switches Slots 2 15 Physical Node Power IPMB Hardware Address Power IPMB Hardware Address Base N A Fabric and Base Base Fabric N A P20 Clocks Update Fabric Clocks Update Fabric AXP1620 Installation and Use 6806800E23L 57 AXP1620 Shelf Description The following table provides connector specific information for the backplane slots Table 2 3 Backplane Connectors EN Slots 1 through 16 16 Slots 1 and 16 2 Slots 1 and 16 2 Slots 1 through 16 16 Slots 1 and 16 2 Slots 1 through 16 16 SAM1_ 1 and SAM2_ 1 SAM A and B 2 SAM
133. the SAM is able to power off and reset slots for hot swap capability Update Channel Interface The update channel interface consists of 10 differential pairs on the P20 connector The physical layer and protocol used on this interface is application specific Backplane and Component Connectivity The blade connectivity on the AXP1620 backplane is divided among three zones each with the following characteristics e Zone 1 provides redundant radial IPMI to all blade slots and redundant 48 VDC to all blade slots e Zone 2 the data transport interface provides the dual star configuration for the base interface dual star configuration for the fabric interface update channel routing for all blade slots and three redundant bussed telecom clock signals to all blade slots e Zone 3 provides the PICMG 3 0 defined open area that is application specific NOTICE Rear Transition Modules connect directly with the connectors on the front side blade and do not make the connection through the backplane AXP1620 Installation and Use 6806800E23L 47 Platform Architecture Figure 1 2 Location of Zones 1 2 and 3 Physical sali 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 RTM Zone 3 lt vO Interface M as ag oa Om f E ES lt 5 lt 2 Synch Clock z Zone 2 lt Update Chnl Fabric
134. tions Document Title and Source IEEE http standards ieee org catalog Publication Number IEEE Standard for Local Area Networks Carrier Sense Multiple IEEE 802 3 Access with Collision Detection CSMA CD Access Method and March 2002 Physical Layer Specifications Institute of Electrical and Electronics Engineers Inc IEEE Amendment 1 Media Access Control parameters Physical IEEE 802 3ae Layers and Management Parameters for 10Gb s Operation August 2002 PCI Industrial Manufacturers Group PICMG http www picmg com PICMG 3 0 AdvancedTCA Base Specification Revision 1 0 PICMG 3 0R 1 0 December 30 2002 PICMG 3 0 AdvancedTCA Serial Interconnect Specification R2 0 PICMG 3 0 R2 0 PICMG 3 1 AdvancedTCA Ethernet Fibre Channel Revision 1 0 PICMG 3 1 R1 0 January 22 2003 PICMG 3 0 ECN 3 0 1 0 001 January 21 2004 ECN 3 0 1 0 001 AXP1620 Installation and Use 6806800E23L A mS YN Z wm E ou F EMBEDDED TECHNOLOGIES Artesyn Embedded Technologies Artesyn and the Artesyn Embedded Technologies logo are trademarks and service marks of Artesyn Embedded Technologies Inc All other product or service names are the property of their respective owners 2014 Artesyn Embedded Technologies Inc
135. ts to the base ports of the two hub slots and to the front panel RJ45 Ethernet connector The port utilization of the switch is e TP port 1 to Local hub slot e TP port 2 to Remote hub slot TP port 3 to Front panel RJ45 e TPport 4 to ShMM1500R e TPport 5 is not used e Mil portis not used AXP1620 Installation and Use 6806800E23L 157 Shelf Management Alarm Module The default state of the Ethernet switch is not to forward packets between ports The correct switch configuration for normal operation is to allow ingress from ports 1 2 and 3 to port4 and to allow egress from port 4 to ports 1 2 and 3 With the exception of routing a port to itself all other routes are blocked Figure 7 4 _Interhub Slot and Shelf Manager Connectivity Front Front Panel Panel A A SAM A SAM B ShMM 1500 lt gt ShMM 1500 ETHO ETH1 ETH1 Port 4 Port 4 Ethernet Ethernet 2 Port2 Switch Switch E Port 1 Port 2 Port 3 Port 2 Port 1 A t t A Hub Slot 1 Hub Slot 1 158 AXP1620 Installation and Use 6806800E23L Shelf Management Alarm Module The default configuration of Ethernet channels is depicted inTable 7 8 and Table 7 9 Table 7 8 Shelf Manager Static Network IP Interfaces Function IP Active SAM IP Backup SAM Ethernet Device 192 168 25 101 192 168 25 100 ETHO Front Panel R 45 0 0 0 0 0 0 0 0 ETH1 Disa
136. ttended 78 dB Measurement of declared A weight sound power level All values are applicable to normal operating conditions 27 C ly e The ambient temperature around the shelf and the air inlet temperature must not exceed nr 55 C 131 F The AXP1620 system regulates the fan speed based on the temperature sensors present in the system The fan speed is adjusted to the lowest speed which still keeps the evaluated temperature readings below or at their respective upper non critical threshold Hence the fan speed depends on the ambient temperature blade design temperature threshold settings and system configuration To guarantee proper blade operation you have to make sure that the temperatures at the locations specified in the following are not exceeded If not stated otherwise the temperatures should be measured by placing a sensor exactly at the given locations Table 3 2 Critical Temperature Limits Component Temperature Limit Air inlet system s front 55 C 131 F Air outlet system s rear 70 C 158 F AXP1620 Installation and Use 6806800E23L 75 Site Preparation Table 3 2 Critical Temperature Limits continued Component Temperature Limit Power entry module lug plastic washer 70 C 158 F gt 70 C 158 F and maximum 90 C 194 F the cables must be isolated and must be approved to be used in this temperature range gt 70 C 158 F and maximu
137. ture Provides an overview of the features of the system and lists the standard compliances Site Preparation AXP1620 Operations AXP1620 Shelf Installation FRU Installation Provides site planning considerations and checklists describes the requirements and conditions Describes basic operating procedures Describes mounting and installation options Describes how to install and replace blades modules power components fans and air filter Shelf Management Alarm Module Describes the shelf management alarm module Related Documentation Abbreviations Lists related documentation and specifications This document uses the following abbreviations Abbreviation Definition AdvancedTCA Advanced Telecom Computing Architecture AMC AdvancedTCA Mezzanine Card ANSI American National Standards Institute ARP Address Resolution Protocol ARTM AdvancedTCA Rear Transition Module ATCA Advanced Telecommunications Computing Architecture AXP1620 Installation and Use 6806800E23L 13 About this Manual Abbreviation Definition American Wire Gauge BBS Basic Blade Services Comit International Sp cial des Perturbations Radio lectriques co Central Office EMC Electromagnetic Compatibility EMI Electromagnetic Interference EMV Elektromagnetische Vertraeglichkeit EN European Norm ESD Electrostatic Discharge European Telecommunication Standards Institute Field Application
138. uit breakers to the ON position 2 Verify that all FRU LEDs illuminate and the PEM s In Service LED is green The system executes its normal start up routine and is then ready to use 5 11 Accessing the System You can access your system using the SAM shelf manager The SAM 1500 direct serial console connector back of chassis is an RJ45 connector on the SAM face plate This connector is configured as DTE The indirect serial console connector front of chassis located on the ADP is a 9 pin micro D subconnector For default user name and password contact your Artesyn s sales representative AXP1620 Installation and Use 6806800E23L 105 AXP1620 Shelf Installation 5 12 5 12 1 106 Custom cables are required for these connectors Refer to RS 232 Serial Interface on page 148 for pin assignments Upgrading Firmware Upgrading firmware on the AXP1620 shelf involves the following components e PMC firmware on the two Fan Tray Modules FTMs e PMC firmware on the two Power Entry Modules PEMs e Shelf Manager firmware including an FPGA image on the two SAMs FTM IPMC Firmware Upgrade There is a single IPMC firmware image common to the two FTMs in the AXP1620 The FTM IPMCs are assigned IPMB addresses 0x56 and 0x58 Different upgrade image variants are generated as part of the release but only one file is required for the normal field upgrade process This file is tm1620_hpml1fw img As upgrades are released Artes
139. unt the shelf with metal screws or bolts that give a good electrical connection between the screws or bolts and the mounting surface 98 AXP1620 Installation and Use 6806800E23L AXP1620 Shelf Installation 4 Tighten all screws using a torque setting of 35 5 to 38 5 inch pounds Failure to observe proper grounding practices may cause a variety of noise electrostatic discharge and RFI Radio Frequency Interference problems 5 4 2 600mm ETSI Rack Cabinet Installation The shelf mounts directly from the integrated flange on the front of the shelf 1 Locate the standard mounting hole and slot locations on the front integrated mounting flanges on the AXP1620 shelf 2 Fasten the mounting brackets to the back side of the front chassis flanges using M6 screws x 12mm at each of the 5 locations 3 Be sure to mount the shelf with metal screws or bolts that give a good electrical connection between the screws or bolts and the mounting surface 4 Tighten all screws using a torque setting of 35 5 to 38 5 inch pounds NOTICE Failure to observe proper grounding practices may cause a variety of noise electrostatic discharge and RFI Radio Frequency Interference problems AXP1620 Installation and Use 6806800E23L 99 AXP1620 Shelf Installation 5 9 5 6 100 Grounding the Shelf Use a 2 AWG wire with a 2 hole copper lug and connect directly to the earth ground point located on the right side of the back of th
140. use the Uboot environment variable gatewayip the route is set automatically at reboot setenv gatewayip W X Y X If the local subnet is not a class C subnet you may need to also execute the command ifconfig ethl netmask toalterthe netmask used by the ethernet interface If you use the Uboot environment variable netmask1 this subnet mask is set automatically at bootup setenv netmask1 netmask Ping the file server containing the Artesyn files You should get a response if the Ethernet cable is connected Set the environment variable that keeps the front panel Ethernet interface enabled following a reboot setenv enable_front_panel_ethernet y AXP1620 Installation and Use 6806800E23L AXP1620 Shelf Installation 5 12 3 2 Update ShM Firmware on the SAM This step involves programming of the U boot Linux kernel and root file system into flash on the ShMM1500 on the SAM 1 Copy the three required firmware image files listed below to the tmp directory on the ShM e sentry shmm1500 u boot bin e sentry shmm1500 kernel e sentry shmm1500 rts One way of doing this is scp acctname fileserver_ip dirname sentry shmm1500 tmp where acctname is the login account for the user on the linux file server fileserver_ip is the IP address of the file server dirname is the relative directory name from the login home for the location of the images Verify that the files were copied to tmp Execute the command to pr
141. using the shelf manager mezzanine CPLD device The interface is composed of three components e Injector Ejector handle switch e Presence signal indicating that the SAM is fully seated in its backplane connector e HS LED to indicate safe to remove state Power The SAM uses dual 12V power feeds one from each PEM Hot swap circuitry ensures correct operation when a SAM is inserted into or removed from a live system SAM Software The software that runs on the shelf manager is described in detail in the Pigeon Point Systems IPM Sentry Shelf Manager User Guide which provides an introduction to shelf management the shelf manager and the shelf management mezzanine Also available is the Pigeon Point Systems IPM Sentry Shelf External Interface Reference which describes the command line web SNMP Simple Network Management Protocol and RMCP Remote Management Control Protocol interfaces Refer to Appendix A Related Documentation for more information on these publications imls Utility A utility called imls is available on the SAM It can be used to list all firmware images present in flash Note that the Shelf Manager flash is divided into two banks Each bank contains a set of three separate firmware images e U Boot e RFS e Kernel images AXP1620 Installation and Use 6806800E23L 163 Shelf Management Alarm Module When the rupgrade_tool utility is used to perform a reliable firmware upgrade operation on the Shelf Manager t
142. utput The sample output for these commands for one FTM is shown below AXP1620 Installation and Use 6806800E23L 107 AXP1620 Shelf Installation upgradeftm upper tmp ftm1620_hpmlfw img Upgrading ipmitool_v0 9 H 192 168 24 11 t 0x58 U openhpi P openhpi hpm upgrade var nvdata ftm1620_hpm1fw img PICMG HPM 1 Upgrade Agent 0 4 Validating firmware image integrity OK Performing preparation stage OK Target Product ID z195 Target Manufacturer ID 161 Performing upgrade stage Upgrading H8S ATCA F W with Version Major 1 Minor 8 Aux 000 000 000 000 Firmware size 171840 Writing firmware 100 completed Firmware upgrade procedure successful ipmitool returned 0 Activating ipmitool_v0 9 H 192 168 24 11 t0x56 U openhpi P openhpi hpm activate PICMG HPM 1 Upgrade Agent 0 4 ipmitool returned 0 bin upgradeftm Upgrade and activate complete Verify firmware version clia ipmc v 0x56 Pigeon Point Shelf Manager Command Line Interpreter 58 Entity Oxle 0x60 Maximum FRU device ID 0x00 Hot Swap State M4 Active Previous M3 Activation In Process Last State Change Cause Normal State Change 0 0 Device ID 0x00 Revision 0 Firmware 0 00 ver 0 0 0 IPMI ver 0 0 Manufacturer ID 000000 Product ID 0000 Auxiliary Rev 00000000 Device ID String FTM1620 108 AXP1620 Installation and Use 6806800E23L AXP1620 Shelf Installation 5 12 2 AXP1620 Installation an
143. utward to a slightly open position to disengage the hot swap switch Watch for the Blue LED to blink When the blinking stops and the LED remains a solid blue the FTM is ready to be removed 136 AXP1620 Installation and Use 6806800E23L FRU Installation 3 Open the ejector handle to a full open position 4 Using the handle on the front of the FTM slowly pull the FTM out of the shelf while supporting the bottom of the module with the palm of your hand The module is heavy hold it securely 6 5 2 Installing the Upper FTM Installation Procedure Have the correct FTM available and follow these steps to install the upper fan tray module 1 While supporting the FTM align the FTM carefully into the fan slot in the shelf and slowly slide the FTM until the ejector handles engage fully close the handles The FTM is connected when the assembly is firmly seated in the upper backplane connector and the hot swap handle moves to the closed position 2 Hand tighten both chassis retention screws at the same time to secure the FTM Hand tool tighten both chassis retention screws alternating back and forth until hand tight The recommended torque settings is 5 inch pounds When the blue LED turns off the fan is operating AXP1620 Installation and Use 6806800E23L 137 FRU Installation 6 5 3 Removing the Lower FTM Removal Procedure Follow these steps and refer to the figure to remove the lower front fan tray module fro
144. very week after you first install your system In a dusty environment a filter may need cleaning more often than a filter in a cleaner environment Check the filters frequently until you have a good idea of how often it needs cleaning Based on your findings establish a regular cleaning schedule and keep a log to record the date of each filter cleaning or replacement AXP1620 Installation and Use 6806800E23L 25 Safety Notes This equipment is designed to permit the connection of the earthed conductor of the DC supply circuit to the earthing conductor at the equipment If this connection is made all of the following conditions must be met e This equipment shall be connected directly to the DC supply system earthing electrode conductor or to a bonding jumper from an earthing terminal bar or bus to which the DC supply system earthing electrode conductor is connected e This equipment shall be located in the same immediate area such as adjacent cabinets as any other equipment that has a connection between the earthed conductor of the same DC supply circuit and the earthing conductor and also the point of earthing of the DC system The DC system shall not be earthed elsewhere e The DC supply source shall be located within the same premises as this equipment e Switching or disconnecting devices shall not be in the earthed circuit conductor between the DC source and the point of connection of the earthing electrode conductor French tra
145. wie zum Beispiel Verbrennungen oder Amputationen f hren Tragen Sie bei der Arbeit mit dem System keine metallischen Gegenst nde an Ihren H nden oder Armen und lassen sie keine metallischen Gegenst nde um Ihren Hals h ngen Seien Sie extrem vorsichtig mit elektrisch leitenden Gegenst nden in der N he der PEMs Kurzschlu und Gefahr durch Stromschlag Um einen elektrischen Schlag zu vermeiden berzeugen Sie sich dass vor dem Austausch des PEMs die Stromzufuhr unterbrochen ist und w hrend des Austausches unterbrochen bleibt Kurzschlu und Gefahr durch Stromschlag Um Kurzschl sse und elektrischen Schlag zu vermeiden berzeugen Sie sich dass vor dem L sen der Schrauben die Stromzufuhr unterbrochen ist und w hrend des Austausches unterbrochen bleibt Vermeiden Sie Kurzschl sse indem Sie sehr vorsichtig mit dem Werkzeug umgehen Besch digung der Spannungsversorgungseinheit Wir die Spannungsversorgungseinheit verkehrt angeschlossen werden die Elektrolytkondensatoren der Filter besch digt Schalten Sie die Unterbrecher deshalb nur wenn das rote Licht nicht sichtbar ist L fteraustausch 40 Verletzungsgefahr Rotierende L fterschaufeln Sie k nnen verletzt werden wenn Sie Werkzeuge oder Finger in laufende L fter einf hren Wenn Sie die L fterschublade aus dem Chassis ziehen wird die Abdeckung der L fterschaufeln freigelegt Ber hren Sie die L fterschaufeln nicht Seien Sie vorsichtig nach dem Herausziehen des L
146. yload des dazugeh rigen AdvancedTCA Boards noch nicht heruntergefahren ist kann dies zu Besch digungen am Board oder RTM f hren Fahren Sie deshalb die Payload des AdvancedTCA Blades immer herunter bevor Sie das dazugeh rige RTM aus dem System entfernen AXP1620 Installation and Use 6806800E23L Sicherheitshinweise Betrieb Besch digung des RTMs Fehlerhafte Installation kann zu einer Besch digung des RTMs f hren Verwenden Sie die Handles um das RTM zu installieren deinstallieren Auf diese Weise vermeiden Sie dass die Frontblende oder die Platine deformiert oder zerst rt werden Besch digung des RTMs oder Boards Das System wird besch digt wenn die RTMs nicht zu den von vorne in dem System installierten Boards passen Stellen Sie deshalb sicher dass Boards und RTMs die von vorne bzw von hinten in den gleichen Steckplatz des Systems eingebaut werden stets zueinander passen Datenverlust Das Entfernen eines RTMs w hrend des Systembetriebs und blinkender blauer LED des Front Boards f hrt zu Datenverlust Vor dem Entfernen des RTMs im laufenden Systembetrieb schalten Sie das entsprechende Board ab indem Sie die Griffe des Boards ffnen Warten Sie bis die blaue LED dauerhaft leuchtet Fehlfunktion Unsachgem er Ein und Ausbau von Boards kann zu einer Fehlfunktion des Boards f hren Vergewissern Sie sich dass das Board ber alle Stecker an die AdvancedTCA Backplane angeschlossen und die Stromversorgung g
147. yn will supply the current version of this file The upgrade process described here uses a script named upgradeftm which is supplied on shelf managers starting with build 4 1 0 3 AXP1620 Installation and Use 6806800E23L AXP1620 Shelf Installation Upgrade Process Steps Follow these steps to upgrade the FTM firmware 1 Copy the tm1620_hpm1 fw img file to the tmp directory on the active Shelf Manager The tmp directory on the shelf manager is mounted to ram this copy of the file will be deleted on the next reset of the shelf manager If you want to save the file to flash copy it to the var nvdata directories on both shelf managers 2 Execute the following command to upgrade the upper FTM ipmitool_v0 9 H 192 168 24 11 t 0x56 U openhpi P openhpi hpm update tmp ftm1620_hpmifw img ipmitool_v0 9 H 192 168 24 11 t 0x56 U openhpi P openhpi hpm activate 3 Repeat the command to upgrade the lower FTM ipmitool_v0 9 H 192 168 24 11 t 0x56 U openhpi P openhpi hpm update tmp ftm1620_hpm1fw img ipmitool_v0 9 H 192 168 24 11 t 0x56 U openhpi P openhpi hpm activate 4 After a successful upgrade the upgrade ftm script displays the current firmware level reported by the device as shown in FTM Upgrade Sample Output on page 107 5 If necessary it is possible to revert to the previous firmware version using a command of the form upgradeftm upper lower rollback 5 12 1 1 FTM Upgrade Sample O