End To End Optical Beam Smoke Detector User Guide EN

image

Contents

1. CONTROLLER SETTINGS RECEIVER SETTINGS FIRE TEST DELAY TO FAULT 7 2 Receiver Settings 7 2 1 Receiver Settings Overview VIEW SIGNAL STRENGTH COMPENSATION SET LATCHING MODE i e FOLIAR ao 10907 ILJII 2 00 GF O IJ d fa TO om QA m II SOFTWARE Y Mm Z RX GAIN ico p je 00 HARDWARE 4 J Mm LI RX GAIN IJ p E E 7 3 Controller Settings 7 3 1 Controller Settings Overview d 7x Oh LKB PASSCODE CHANGE amp N SCREEN CONTROLLER i STATUS LED ON m OFF sin SCREEN g 22 7 3 2 Passcode Change Screen This screen allows the user to change the Pass Code used to access the ENGINEERING MENU NOTE The number being altered flashes A partial passcode ie with dashes in it will not be accepted Default Pass Code 1234 4 Change digit 4 O Move between digits Y Save new Pass Code x Abort change 23 7 3 3 Controller Status LED ON OFF Screen This setting controls whether the System Controller Status LED will flash o me Toggle ON or OFF cue ot Vv Confirm setting E Abort change 8 Specification Parameter Operating Range 5 to 120m bt dem Operating Voltage Range 12 to 36V DC 10 ransmitter Current Quiescent Current Controller with 1 or 2 Rece
2. C 16 4 Maintenance and Troubleshooting 4 1 System Maintenance The system will automatically compensate for dust build up by changing the Compensation Level However it is recommended that the Transmitter and Receiver lenses are cleaned periodically with a soft lint free cloth The system should be isolated from the Fire Control Panel before cleaning takes place After cleaning verify that the system is operating normally by following the Alignment procedure and the Fire and Fault Tests described in this User Guide 4 2 Error Codes Corrective Action O o Q o AIM not recognised Refer to manufacturer for further technical assistance Receiver Communications Fault Check wiring between Controller and Receiver E 02 Find not successfully executed Follow Find process Compensation limit reached Clean and re align system Receiver missed too many readings or lost sync Ensure clear line of sight from Transmitter to with the Transmitter Receiver Follow alignment procedure Ensure clear line of sight from Transmitter to Receiver Signal too low at end of alignment Ensure clear line of sight from Transmitter to Receiver Ensure alignment of Transmitter AND Receiver Do not exit whilst alignment status LEDs are still flashing Signal too high at end of alignment Follow alignment procedure again Do not exit whilst alignment status LEDs are still flashing Short circuit detected on communications Check wirin
3. 80m 196 8 262 5 ft 80 100m 262 5 328 1 ft 100 120m 328 1 393 7 ft 9 2 European Approval Information e Complies with EN54 12 for sensitivity levels between 25 and 35 with a maximum delay to fire of 20 seconds 25
4. 6 Alignment Step 1 In alignment mode you are centring the Transmitter beam onto the Receiver and the system is adjusting its power for optimum signal 00 p i E A NOTE 1 Value can be between 2 and 178 A higher value means a better alignment Set Tx power to maximum Signal too 3K Signal too high low Green short long Amber flash View LEDs on Rx or short long flash LCD value No flash wo i Reduce Tx f F power SEE NOTE 1 EJ Tx No flash j ra No flash Proceed to Step 4 11 From Step 3 Adjust one thumbwheel by Step 4 NOTE 1 Value can be between 2 and 178 A higher value means a better alignment 1 4 turn Green flash stop Amber flash stop View LEDs on Rx or LCD value id A Ld a n R G SEE NOTE 1 SEE NOTE 1 a Signal Signal decreased increased Adjust same thumbwheel by 1 4 turn in the opposite direction Green flash stop Adjust same thumbwheel by 1 4 turn in the same direction Release thumb wheel and wait 1 second LED no flash LCD between 2 and 178 Reduce Tx Green short long power flash LCD 180 Green flash stop LCD value increases View LEDs on Rx or LCD value Amber flash stop LCD value decreases Adjust same thumbwheel by 1 8 turn in CI the opposite direction thumb wheel alignment Repeat step 4 for t
5. End To End Optical Beam Smoke Detector User Guide Document Number 0044 047 01 EN Contents 1 Installation 2 Commissioning 3 In Use 4 Maintenance and Troubleshooting 5 Display and Indicators 6 User Menu 7 Engineering Menu 8 Specification 9 Approval Information Page 14 17 18 19 20 24 25 1 Installation 1 1 Mounting and Positioning Transmitter Receiver Clear Lens Black Lens Controller 1 p P P r A IMPORTANT NOTE The infrared beam path MUST be kept clear of obstructions at all times Failure to comply may result in the system initiating a Fire or Fault signal e Check the beam spacing against local regulations Ensure clear line of sight from Receiver to Transmitter e Mount on solid surfaces structural wall or girder and ensure fixing is rigid Position beam as high as possible but with a minimum distance of 30cm from Receiver Transmitter to ceiling For installations complying with UL 268 NFPA 72 the maximum distance of Transmitter and Receiver from the ceiling must be 10 of the distance between floor and ceiling Mount Receiver and Transmitter directly opposite each other Do NOT position where personnel or objects can enter the beam path ZONE 1 ZONE 1 ZONE 2 ZONE 2 SUPPLY SUPPLY 1 2 Wiring Diagram For connection of Receivers to individual zones RECEIVER 1 RECEIVER 2 TRANSMITTER TRANSMITTER OUTPUT OUTPUT S
6. RED every Flashes RED every Closed Closed 10 seconds 10 seconds System Controller Status LED Right hand LED flashes green every 10 seconds 18 6 User Menu 6 1 User Menu Overview The USER MENU allows system settings to be viewed only The USER MENU will timeout 15 minutes after the last key press 4 hd CONTROLLER SOFTWARE VERSION Nm ID V 8 To TL th Ee JTL H 1097607 Lou Z RECEIVED SIGNAL _ a JL S ME ATEN n 8 mm O TL Q THRESHOLD J C n Y B ae E JL QA DELAY TO FIRE H n a am sec E wo mn wy g ID V co nm ass S a DDD ce nm wy g ILS d 19 CONTROLLER LED ON OFF STATUS RECEIVER SOFTWARE VERSION RECEIVER STATUS Refer to Troubleshooting for error codes DELAY TO FAULT 7 Engineering Menu 7 1 Engineering Menu Overview The ENGINEERING MENU allows system settings to be changed The ENGINEERING MENU will timeout 60 minutes after the last key press RECEIVER FIND Y Pe OH or zz 7 LASER TARGETING A i THOS SeRE 0 BEAM ALIGNMENT gt OAL a ZE 0 FIRE THRESHOLD 7x OD OBR 0 DELAY TO FIRE EA OOO ARRE d FLOD FP Ok RY a Y TEONE iE Ef des E RS A a Pe Oh PQA nO 20 Ov d
7. UPPLY SUPPLY 12V to 36V DC A ed 1 RECEIVER 1 RECEIVER 1 RECEIVER 2 RECEIVER 2 FIRE FAULT baw FRE dh FAULT N O COM N C N O COM N C N O COM N C N O COM N C pa esata ELG A NA hA CT see note 1 For connection of both Receivers to one zone ARTETA i RECEIVER 1 RECEIVER 1 RECEIVER 2 RECEIVER 2 FIRE FAULT L FIRE FAULT N O COM N C N O COM N C N O COM N C N O COM N C LEG RE En ae EYES iI PES NINN JOG sg St re r is E EOL EXTERNAL RESET Note 1 This component is the fire resistor Its value is specified by the Fire Control Panel manufacturer For U S installations it is typically a short circuit ALWAYS use a separate 2 core cable for each Receiver head e CAUTION For system monitoring Do not use looped wire under any terminals Break wire run to provide monitoring of connections e Components not supplied e Schottky Diode Typically 60V 1A UL rated for installations conforming to NFPA 72 End Of Line EOL component supplied by Fire Control Panel manufacturer e Fire Resistor not supplied After installation check operation of Fire and Fault connection on Fire Panel 4 1 3 Fitting the Product RECEIVER TRANSMITTER mk TO RECEIVER TO OUTPUT ON 12 to 36V DC OR CONTROLLER SUPPLY ON BOARD CONTROLLER BOARD LED ind
8. g between Controller and Receiver between Controller and Receiver IR signal integrity fault Check there are no strong sources of light near the Receiver or direct sunlight Ambient light fault Check there are no strong sources of light near the Receiver or direct sunlight Power too low fault Check power supply to Controller 17 5 Display and Indicators 5 1 LCD Icon Layout Receiver Latched Number Reset Minutes Compensation Level Degrees amp LED seconds Signal User Fire Setting Strength eN Controller 1 Setting 2 04 of External Reset Fault A OOOH OG gt CED CD O IV System Locked ADDR _ Unlocked ap aD Ga ea ec O Address Setting 52 2 a a a A A TT UE er Mode Bar Graph CY Laser LLC Receiver Beam Delay Fire Controller Find Alignment To Fire Test Settings LASER Fire Delay To Receiver Targeting Threshold Fault Settings 5 2 Receiver Status Indicators The Green and Amber LEDs flash during alignment to indicate alignment status Refer to alignment procedure for further information The Red LED will flash every 10 seconds when a fire is detected during normal operation 5 3 Controller Status Indicators Condition LEFT HAND LED MIDDLE LED FIRE RELAY FAULT RELAY RECEIVER 1 RECEIVER 2 STATE STATE STATUS LED STATUS LED No Flash No Flash Open Fault Trouble Flashes AMBER Flashes AMBER Open Open every 10 seconds every 10 seconds Fire Alarm Flashes
9. he other Y Press tick to accept 12 2 7 Fire and Fault Tests After alignment or maintenance it is recommended that Fire and Fault tests are performed 2 7 1 Remote Fire Test The Remote Fire Test allows the user to perform a Fire Test from the System Controller The Remote Fire Test is acceptable for Fire Authority Acceptance and Routine Maintenance per UL 268 5 oO EY we Oh amp IB 5 R Receiver Fire LED Test The Receiver will signal Fire the System Controller will stay Normal To exit without performing iP QO test press T amp S iz IS EN FEE EEN re Relay Controller Wirin Test The System Controller signals Fire to the Fire Control Panel To exit press either only Completely cover the Receiver taking less than 2 seconds to do so The Controller will indicate Fault after the Fault Delay time 2 7 2 Fault Test Uncover the Receiver The Controller will return to Normal state after approximately 5 seconds 2 7 3 Manual Fire Test Although the Remote Fire Test adequately tests the Fire response of the system it is also possible to perform a Manual Fire Test Slowly half cover the Receiver The Controller will indicate Fire after the Fire Delay Time Uncover the Receiver The Controller will return to Normal state after approximately 5 seconds If Fire Latching Mode is set to On then clear the Fire condition by Ap
10. icator must face downward 2 Commissioning 2 1 Apply Power NOTE One System Controller can be used to control and monitor up to two Receiver heads The symbol in this guide is used to represent the number of the Receiver currently selected 1 or 2 Apply Power to Controller Receiver s amp Transmitter y wo TH L DO A gongs OG OOO AZ om E aman Je un ARO y 3 seconds y e Receivers are not found normal at this stage E z Ha uw eh 9 IL eb e Commissioned System wwe wu Z 8 FREE E IL h e Receivers have been found but not commissioned ee gate 2 8 I I co e Communications fault or no Receiver connected E g H el 2 2 Enter Pass Code to Access Engineering Menu Y To enter PASS CODE SCREEN in USER MENU Default Pass Code 1234 4 Change digit Q O Move between digits Y Accept An incorrect Pass Code will return the display to the Pass Code entry screen A partial passcode ie with dashes in it will not be accepted Three incorrect attempts will lock access for three minutes 2 3 Finding Receivers Perform Find during initial installation or when adding or removing Receivers 00 Ep AONE As each Receiver is Found the relevant HUD me receiver number appears p K here nl Gi OLS El mr 00 This will be the
11. ivers Alarm Current Controller with 1 or 2 Receivers Fault Current Controller with 1 or 2 Receivers 14mA Power Down Reset Time Fire and Fault Relay Contacts FCO 2A 30 Volts DC resistive 10 C to 55 C non condensing EN Pperatng Temperatura 20 C to 55 C non condensing UL Storage Temperature 40 C to 85 C non condensing Receiver Tolerance to Beam Misalignment at 25 sensitivity 2 5 ransmitter Tolerance to Beam Misalignment at 25 sensitivity 0 7 Fire Alarm Thresholds Selectable increments of 1 from 10 to 60 i Major selectable increments are 25 35 and 50 eight Transmitter amp Receiver inc brackets 207g Red Fire one for each Receiver LED Indications Control Unit Amber Fault one for each Receiver Green System OK de Gh FRE Red Fire Green and Amber indication LEDs for LED Indications Receiver single person alignment IP Rating IP54 Relative Humidity Max 93 non condensing CPD Reference UL File S3417 volume 6 Housing Construction Controller Transmitter Receiver UL94 VO PC 24 9 Approval Information 9 1 UL Approval Information UL File Number S3417 All installations should comply with NFPA72 No liability will be accepted for applications not conforming to NFPA regulations Distance pla peli and Receiver 5 10m 16 4 32 8 ft 10 20m 32 8 65 6 ft 20 40m 65 6 131 2 ft 40 60m 131 2 196 8 ft 60
12. number of a Receivers found Press tick to enable Found Receivers Any unused Receiver channels are switched off x To re scan if the number is incorrect 2 4 Select Receiver to be Accessed All Receivers need to be aligned separately The following sections in this User Guide explain how to align individual Receivers d Fr ono lo de 2 5 LASER Targeting The LASER in the Receiver head is used to align the Receiver with the Transmitter The LASER can be activated using the button on the Receiver head whilst in Engineering Menu or via the LASER icon in the ENGINEERING MENU as shown below Move the LASER as close to the Transmitter as possible by moving the Receiver s thumbwheels The system will signal Fault while in this mode 00 A f L PlOnP OAR This LASER TIMEOUT value MIN 1 min HEN MAX 59 mins may be A ERE incremented or A L U SS decremented in 1 min i steps by using g Sis LASER RADIATION AVOID m DIRECT EYE EXPOSURE POWER OUTPUT lt 5mW CLASS Illa LASER Wavelength 630 680 nm E3 HUND 47 Y Countdown Elapsed If it is not possible to see the LASER because of the installation environment for example if there is high ambient light then mechanically align the Receiver by eye so that it is pointing at the Transmitter 10 2
13. plying a voltage between 5V and 40V to the external reset terminal Entering the Pass Code Disconnecting the power to the Controller for more than 20 seconds System will clear latched fire when power is re applied 13 3 In Use 3 1 Settings 3 1 1 Fire Threshold This setting is the threshold at which the Receiver will detect a fire Default factory setting 35 Set for each Receiver 00 go 7x SOM 14 3 1 2 Delay To Fire Screen This setting is the delay the System Controller uses before signalling a FIRE condition to the Fire Control Panel Default factory setting 10 seconds Set for each Receiver 3 1 3 Delay To Fault Screen This setting is the delay the System Controller uses before signalling a FAULT condition to the Fire Control Panel Default factory setting 10 seconds Set for each Receiver 00 J TONLAR 00 E 7 e Oh PIOKREZ 00 15 3 1 4 Set Fire Latching Mode Screen Default factory setting Non Latching Set for each Receiver To clear a latched fire apply 5 40V to the External Reset terminal enter the passcode or power cycle for 20s KLD g 1 t 7x OH LKQ Use OD to scroll between settings in the Receiver Menu Y TO TL QA NON LATCHING j j MODE me E a ICM J QA Z e LATCHING MODE e a