Home
Windy Boy Grid Tied Inverter Operators Manual Addendum for the
Contents
1. 20 VdcWindStart 0 0 300 400 600 Input Voltage Vdc The operating parameter settings within the Windy Boy are pre programmed by the wind turbine manufacturer or SMA America Operating Scenario Consider the following scenario Parameter Setting Value Units T Start 10 Seconds T Stop 120 Seconds Vdc Start 300 Vdc Vdc Max 400 Vdc Pmax 1000 Watts When the DC input voltage from the wind turbine reaches 300 Volts the inverter will wait 10 seconds If the voltage remains above 300Vdc the Windy Boy will synchronize with the utility and begin exporting power When the DC voltage reaches 350Vdc the Windy Boy will output 500 Watts AC to the utility If the DC voltage reaches 400 Volts the Windy Boy will output 1000 Watts AC If the voltage continues to increase the Windy Boy will continue to output 1000 Watts AC as specified by the lt Pmax gt parameter setting If the wind slows down such that the DC voltage falls below 300 Volts the inverter will continue to operate at zero power output for 120 seconds If the DC voltage increases above 300 Volts the stop timer will reset and the Windy Boy will process power according to the power curve If the DC voltage remains below 300 Volts for 120 seconds the Windy Boy will stop processing power and shut down Typical Installation Diagrams The following drawings are not specific for any wind turbine or installation They are prov
2. AMT Windy Boy Grid Tied Inverter Operators Manual Addendum for the Sunny Boy 1800U 2500U Revision 1 2 Revision History 1 0 October 20 2003 Kent Sheldon Initial Release 1 1 October 22 2003 Kent Sheldon 15A DC Fuse Requirement 1 2 December 11 2003 Kent Sheldon DC Ripple Requirement SMA America 12438 C Loma Rica Drive Grass Valley CA 95945 530 273 4895 Windy Boy Grid Tied Inverter Operators Manual Addendum for the Sunny Boy 1800U 2500U M Table of Contents Table of Contents cis cecorcasncesa ren acess gectuecntuet isi oneni aE EENE EE EaR EESE a ESEESE aeae 2 VIVO Weraroa aE a e E A O AEA E E E E AA da 3 A ON essiri octartate ean dutalen etwas tala entei aeaii 3 Product Limitations and Warnings acc en seusevenice prone nsiiseedsocs nels denewmneunedeseceudaedenaneatiengeueuaeuien 3 Inverter Selection and Specification sis sess seccet aah css scapetssectasas eo hcecuscs ncaa iaddreasieeeciets 3 System Protection Requirements sseeseseeseeseeseeresresstssrststsrertesresresrtsststesesstestesteseesseseese 3 WB 1800U iiriienuisicensis nense irei rnae peen E aE a ESS EE E EEEE TERE EES 3 WB2500U eiieeii e Sister E E EE A E R EEEE EA 4 DC Oyer voltag PROS COIN scssi nenen ai Eaa aa eenst 4 Operating Specifications ceninin inna ei aaa a i aiat 4 WV BB OQ senise terreinen assinei eein EEA ETEEN EAS 4 WB2500U a acatah ceed ash scen cteeeic teehee ul a Ei i aE EAE EEE E
3. E ai aE iE i 5 Power C rye FUNCHUON seir ayesieecctnctaceanendvn sircentnat ase p an an E a aAA EAE Ea ERARE 5 Operating Scenari Ossis aires dodiad 6 Typical Installation Dia eran sisena a aa 6 Ground Fault Protection isrener a is aiaei 7 DC Disconnect Switch sesiis riccirirsaiisneiiisserirssi ie isie isisisi eisein 8 DC Input Purse Reqguitement siesisrisscsisrenentinrsnetiina inania Enae NE AEE a AEE 8 Surge Protection sisie onra eee ee Pen aaa eee eer mene E ep ii 8 Appendiks ieis inesi E a E a EEE ESE ET 8 Contact Ui AG OB ances sb wciteseic tata te excse cuenta seisena E eaa EEEE ESEESE Ea 8 Notice The Windy Boy inverter must be used within the limits shown on the rating label This document is an addendum to be used in conjunction with the Sunny Boy 1800 or 2500 SWR1800U or SWR2500V installation and operations manuals Caution The Windy Boy inverter is designed to operate with wind turbines employing a 3 phase generator and rectifier that produce current and voltage within the allowable operating ranges of the inverter All protective wind turbine input functions over current over voltage over power fault tolerance and recovery turbine mechanical protection etc are the responsibility of the turbine manufacturer or system integrator installer The Windy Boy inverter is a standard inverter designed to be installed only with qualified wind turbines Input protection is the responsibility of the turbine manufacture
4. ca com SMA America Incorporated Version 1 2 Copyright 2003 Page 8 of 8
5. curs causing the inverter to immediately stop processing power When this happens the power that was going to the utility is transferred back into the turbine as speed The wind turbine will quickly increase speed which causes the DC voltage to also increase rapidly This can produce voltage in excess of 2000Vdc if the turbine was fully loaded at the time of an event Exceeding the maximum input voltage will void the inverter warranty Most turbine manufacturers have designed a protection circuit to protect power processing equipment from this condition Operating Specifications Version 1 2 WB1800U Maximum DC Input Voltage 400Vdc DC Operating Range 139 400Vdc line voltage dependent see SB2500U Technical Description Maximum DC Operating Current 12Adc Maximum DC Short Circuit Current 18Adc Nominal AC Output Voltage 120Vac AC Operating Voltage Range 106 132Vac Nominal AC Frequency 60Hz AC Operating Frequency Range 59 3 60 5Hz Maximum AC Output Current 17Aac Maximum AC Output Power 1800Wac AC Output Overcurrent Protection 20A Power Factor Fixed Unity SMA America Incorporated Copyright 2003 Page 4 of 8 M WB2500U Windy Boy Grid Tied Inverter Operators Manual Addendum for the Sunny Boy 1800U 2500U Maximum DC Input Voltage 600Vdc DC Operating Range 204 550Vdc line voltage dependent see SB2500U Technical Description Maximum DC O
6. d Version 1 2 Copyright 2003 Page 7 of 8 Windy Boy Grid Tied Inverter Operators Manual Addendum for the Sunny Boy 1800U 2500U M DC Disconnect Switch A means of disconnect between the wind turbine and the Windy Boy inverter is required by the NEC It must be load break rated for the maximum DC voltage of the system 400Vdc for the WB1800U and 600Vdc for the WB2500U The NEC requires the DC input be grounded This is done on the negative DC input within the inverter through a 1 Amp fused GFDI detection circuit Because of this the negative input may not be switched at the DC disconnect or anywhere else in the input circuit DC Input Fuse Requirement A 15 Amp overcurrent device is required in the DC input circuit for both the WB1800U and the WB2500U This could be either a circuit breaker or fuse rated for DC current and the appropriate maximum DC voltage of the system 400Vdc for the WB1800U and 600Vdc for the WB2500U Surge Protection There are no surge protection devices within the Windy Boy inverter SMA recommends placing appropriate surge protection devices as close to the AC and DC sources as possible We recommend placing the AC surge protector within the AC main panel The DC surge protector should be installed at the turbine in the DC interface enclosure shown in the previous diagrams Appendix Contact Information SMA America 12438 C Loma Rica Drive Grass Valley CA 95945 530 273 4895 www sma ameri
7. delivered to the inverter as DC voltage speed and current torque Most small turbines use an AC alternator and a diode rectifier bridge to convert variable frequency AC from the alternator to DC power The inverter uses a programmed power versus voltage curve to command current from the turbine dependent upon the DC voltage generated by the turbine Each alternator design has an optimum operating point or power curve of speed voltage versus torque current The Windy Boy incorporates a linear power curve that may be programmed by the user to match the characteristics of the specific wind turbine alternator Product Limitations and Warnings The Windy Boy inverter is a standard inverter designed to be installed only with qualified wind turbines Input protection is the responsibility of the turbine manufacturer or system integrator installer Misapplication of the Windy Boy may cause irreparable damage to the inverter and turbine system and will void all product warranties Please contact your turbine manufacturer for detailed system information The Windy Boy inverter is designed to operate with wind turbines employing a 3 phase generator and rectifier that produce current and voltage within the allowable operating ranges of the inverter All protective wind turbine input functions over current over voltage over power fault tolerance and recovery turbine mechanical protection etc are the responsibility of the turbine manufacturer or sys
8. ided as basic reference material showing necessary major components and installation sequence Please contact the specific wind turbine manufacturer for exact installation drawings specific for your wind turbine SMA America Incorporated Version 1 2 Copyright 2003 Page 6 of 8 Windy Boy Grid Tied Inverter Operators Manual Addendum for the Sunny Boy 1800U 2500U M OND NEUTRAL H MAN M EE a OAD a T DAD fa i i 14 Fuse DC INTERFACE Cnternabd OVERCURRENT amp OVERVOLTAGE 2 PROTECTION AC MAIN PANEL Windy Boy 1800U NEUTRAL En h u Le ISA Fuse 1A Fuse DC INTERFACE nternal OVERCURRENT amp OVERVOLTAGE A IEAS PROTECTION AC MAIN PANEL Windy Boy 2500U Ground Fault Protection The Windy Boy inverter is designed to work with a turbine alternator DC rectifier that is ungrounded floating The Windy Boy inverter grounds the negative leg of the DC input with an integrated 1 Amp fused GFDI circuit within the inverter In the event an alternator winding or DC wire becomes shorted to ground the GFDI circuit will trip safely shut down the inverter and display the fault on the user interface display The GFDI circuit is the same as found within the Sunny Boy inverters It is a1 Amp 600Vdc midget class fuse Littlefuse KLKD 001 Replacement fuses must be 600Vdc rated and are available from SMA America SMA America Incorporate
9. perating Current 13Adc Maximum DC Short Circuit Current 18Adc Maximum AC Current 15Aac Nominal AC Output Voltage 240Vac AC Operating Voltage Range 211 264Vac Nominal AC Frequency 60Hz AC Operating Frequency Range 59 3 60 5Hz Maximum AC Output Current 12Aac Maximum AC Output Power 2500Wac AC Output Overcurrent Protection 15A Power Factor Fixed Unity Power Curve Function The Windy Boy controls power to the grid based upon the input DC voltage from the wind turbine This is based upon a linear curve with a start voltage and a maximum operating voltage These parameters may be adjusted and optimized for the specific turbine connected to the Windy Boy When the DC input voltage reaches the start voltage setting the inverter will begin a countdown to start delivering power to the grid This length of time is dependent upon the start timer setting If the DC input voltage remains above the start voltage setting for the prescribed length of time the inverter will synchronize with the grid and begin delivering power As the DC input voltage rises the power delivered to the grid will increase as shown in the chart below SMA America Incorporated Version 1 2 Copyright 2003 Page 5 of 8 Windy Boy Grid Tied Inverter Operators Manual Addendum for the Sunny Boy 1800U 2500U M Windy Boy Power Curve 120 100 VdcWindMax 80 60 Pmax 40
10. r or system integrator installer Misapplication of the Windy Boy may cause irreparable damage to the inverter and turbine system and will void all product warranties Please contact your turbine manufacturer for detailed system information SMA America Incorporated Version 1 2 Copyright 2003 Page 2 of 8 Windy Boy Grid Tied Inverter Operators Manual Addendum for the Sunny Boy 1800U 2500U M Overview The Windy Boy is the first SMA inverter designed for direct connection of a wind turbine generator to the utility grid The Windy Boy is the same physical inverter as the Sunny Boy operating in a special Turbine software mode This document details this operating mode and the requirements for connecting a wind turbine to the Windy Boy inverter Background Historically grid tied wind turbines have charged batteries through a charge controller and used another converter to process power from the battery to the utility grid The dual conversion and inherent losses associated with moving power through a battery resulted in very inefficient delivery of wind power to the utility Overall transfer conversion losses were easily in the 40 50 range This means that 50 of the energy available from the wind turbine was being delivered to the utility The Windy Boy inverter is a single conversion DC to AC inverter which is similar in operation to the Sunny Boy grid tied PV inverter Mechanical power from the turbine is
11. tem integrator installer Inverter Selection and Specification Currently the wind turbine software mode is available with the WB1800U 1800 Watt peak and the WB2500U 2500 Watt peak Windy Boy inverters must be specially ordered from your wind turbine dealer Contact your wind turbine dealer to determine which inverter is optimized for use with their turbines System Protection Requirements WB1800U Maximum Input Voltage 400Vdc Maximum DC Fuse Requirement 15Adc 600Vdc Maximum DC Power 2000Wdc Maximum DC Ripple 5 peak to peak Maximum AC Current Protection 20Aac 120Vac SMA America Incorporated Version 1 2 Copyright 2003 Page 3 of 8 Windy Boy Grid Tied Inverter Operators Manual Addendum for the Sunny Boy 1800U 2500U M WB2500U Maximum Input Voltage 600Vdc Maximum DC Fuse Requirement 15Adc 600Vdc Maximum DC Power 2800Wdc Maximum DC Ripple 5 peak to peak Maximum AC Current Protection 15Aac 240Vac It is the responsibility of the turbine manufacturer and system installer to insure adequate system protection is provided for the Windy Boy inverter DC Over voltage Protection The largest danger to the inverter is from DC over voltage This is the common result of a wind turbine over speed condition The most radical over voltage condition occurs when the inverter is processing power from the turbine and an event most commonly a utility line fault oc
Download Pdf Manuals
Related Search
Related Contents
Network Scanner Tool V3.3 Benutzerhandbuch Medlight 630 Pro Near Infrared Light Therapy Device User Manual Electrolux ESI7321ROK dishwasher Télécharger - Nantes Tourisme Multimedia Recording Adaptor User Manual User Manual Part Three •71+72_SMART BASE_English UK Preliminär utgava Tiptel Snom 820 EPSON PP-100N 運用者ガイド Copyright © All rights reserved.