Wet Alarm Valve - Spira Fire Protection
Contents
1. 31 HAYES AVE GUELPH ONTARIO N1E5V6 PHONE 519 823 1150 FAX 519 822 7752 OPERATING INSTRUCTIONS FOR MANUAL amp AUTOMATIC WET ALARM VALVE SPRINKLER SYSTEM ca SEE DIAGRAM ON BACK OF THIS SHEET MAIN CONTROL VALVE NORMALLY OPEN 3 MAIN DRAIN VALVE NORMALLY CLOSED 3 PRESSURE PUMP INTAKE CONTROL VALVE NORMALLY CLOSED FOR MANUAL MODEL AND OPEN FOR AUTOMATIC MODEL 4 PRESSURE PUMP DISCHARGE CONTROL VALVE NORMALLY CLOSED FOR MANUAL MODEL AND OPEN FOR AUTOMATIC MODEL 5 PRESSURE PUMP SWITCH NORMALLY OFF FOR MANUAL MODEL AND NORMALLY ON FOR AUTOMATIC MODEL 6 ALARM TEST VALVE NORMALLY CLOSED 7 ALARM SHUT OFF VALVE NORMALLY OPEN IF INSTALLED INSTRUCTIONS FOR TESTING SYSTEM A NOTIFY FIRE DEPARTMENT SECURITY COMPANY PERSONNEL AND ALL OCCUPANTS THAT A TEST IS GOING TO BE CONDUCTED B TO TEST ALARM OPERATION ONLY OPEN ALARM TEST VALVE 6 UNTIL ALARM IS ACTIVATED RETURN VALVE TO CLOSED POSITION C TO TRIP TEST ALARM VALVE SHUT OFF PUMP SWITCH 5 IF AUTOMATIC MODEL OPEN MAIN DRAIN VALVE 2 OR THE INSPECTORS TEST VALVE AT END OF THE SYSTEM AND WAIT FOR ALARMS TO SOUND D CLOSE MAIN DRAIN VALVE OR INSPECTORS TEST VALVE ALARMS SHOULD SHUT OFF WHEN VALVE IS CLOSED E PRESSURIZE SYSTEM SEE BELOW INSTRUCTIONS FOR DRAINING SYSTEM A NOTIFY FIRE DEPARTMENT SECURITY COMPANY AND ALL PERSONNEL B SHUT OFF PUMP SWITCH 5 IF AUTOMATIC MODEL C CLOSE MAIN SHUT OFF VALVE 1 D OPEN MAIN DRAIN VALVE
2. 2 E OPEN THE INSPECTORS TEST VALVE AT THE END OF THE SYSTEM INSTRUCTIONS FOR RE FILLING SYSTEM A CLOSE THE INSPECTORS TEST VALVE AT THE END OF THE SYSTEM B CLOSE THE MAIN DRAIN VALVE 2 C OPEN THE MAIN SHUT OFF VALVE 1 INSTRUCTIONS FOR PRESSURIZING SYSTEM D OPEN PRESSURE PUMP CONTROL VALVES 3 amp 4 E TURN ON PRESSURE PUMP SWITCH 5 AUTOMATIC MODEL ALLOW SYSTEM PRESSURE UPPER GAUGE TO RISE TO 125 PSI OR 50 PSI ABOVE THE LOWER GAUGE PRESSURE THE PUMP SHOULD STOP AUTOMATICALLY WHEN THE PRESSURE SWITCH IS SATISFIED MANUAL MODEL ALLOW SYSTEM PRESSURE UPPER GAUGE TO RISE TO 125 PSI OR 50 PSI ABOVE THE LOWER GAUGE PRESSURE TURN OFF PRESSURE PUMP SWITCH 5 AND CLOSE PRESSURE PUMP CONTROL VALVES 3 amp 4 F DOUBLE CHECK THAT VALVES 1 7 ARE IN THEIR NORMAL POSITION F NOTIFY FIRE DEPARTMENT SECURITY COMPANY PERSONNEL AND ALL OCCUPANTS THAT THE SYSTEM IS ON FOR ANNUAL INSPECTIONS RENOVATIONS AND 24 HOUR EMERGENCY SERVICE CALL 519 823 1150 SPIRA rir protection LTD HE 31 HAYES AVE GUELPH ONTARIO N1E 5V6 PHONE 519 823 1150 FAX 519 822 7752 ALARH FET ii m 2 PE EN i FOR ANNUAL INSPECTIONS RENOVATIONS AND 24 HOUR EMERGENCY SERVICE CALL 519 823 1150
Download Pdf Manuals
Related Search
Related Contents
LUCM and LUCMT Multifunction Control Unit User Guide 03/2008 Samsung CE282DN دليل المستخدم MANUEL D`UTILISATION weBoost Drive 4G-X 470510 User Manual User Manual - Documents and Support Copyright © All rights reserved.
Failed to retrieve file