BROTHER BRENNAN CENTRE Renewable Energy System User
Contents
1. 24 VDC Series Parallel battery configuration shown as a reference only Other voltage levels and or configurations may be used depending on the application OutBack Flexware DC connections 881 G3 ZI LNdNI IV AC HOT OUT AC NEUTRAL IN AG NEUTRAL OUT BOLVHINID BO OMD ANILA NOUS LEN SV 881 MOVIE LI NNI SV 8 ANNOYS Figure 20 Outback Flexware AC Connections 120 v split phase with Autotransformer Generator Auto Start AGS Mode Auto Generator Start One controller is used to sense the battery voltage and if below a set minimum value it can send a start signal to an Atkinson Generator Start Control Module GSCM Figure 21 located adjacent the Isuzu generator The GSCM will warm up the glow plug turn the crank and ignite the generator If it fails it will try four times before locking out Part of its circuitry checks the frequency of the line voltage from the generator to ensure the motor speed is correct However this feature can cause problems when the generator is used with an Outback inverter as higher harmonics can distort the wave form and instead of seeing the normal 60 Hz the sensor can mistakenly see the second harmonic 120 Hz causing an Generator Hz Shutdown error LED just under Start The way around this is to disable this line frequency checking by the GSCM by setting the Under and Over Frequency Shutdown voltages to 0 volts turning them both off and allowing the Outback
2. There are two voltage settings in the Whisper controller that regulate the voltage delivered to the batteries The regulation on voltage is the voltage above which 100 of the turbine output is dumped into the resistor to protect the batteries from over voltage The regulation off voltage is that below which none of the power is dumped The primary function of the controller is to convert the 48V 3Phase AC output from the turbine to 48 DC for battery storage The controller is connected to the batteries via a key switch Note there must be an electrical load on the turbines either from the brake or the controller batteries at all times or they could spin excessively fast The 48V DC key switches should be turned off if the turbines are not in use as the controllers can drain the batteries Note the brakes should be on if the controller is switched off 3500 3000 5 2500 8 1500 8 1000 amp 500 0 mph 5 10 15 20 25 30 35 40 45 ms 23 45 68 9 0 11 3 13 5 15 8 18 0 20 3 Instantaneous Wind Speed Figure 12 Whisper 500 Output as function of wind speed Diversion Switch The diversion rocker switch is located on the top of the controller Figure 9 to the left of the green and red LEDs Setting the switch to OFF causes all the power produced by the wind turbine to be diverted the Diversion Load and the wind turbines will slow down The Whisper 500 utilizes an external Diversion Load Note The switch may not stop a rapid
3. cone Reattach tail stock Check for cracks in wire Install anemometers Place brakes on and raise towers on calm day Make sure DC key switch is turned on and Whisper controllers are energized Turn off brakes Annual Battery Voltage Check With system fully charged Put turbine brakes on Turn off breakers A D on Inverter DC panel Remove plastic protective battery covers and measure and record individual cell voltages All cells should be about 2 15V and no cell should be more than 0 05V from the mean of all Repeat for each battery bank Summer Rentals Summer rentals may be under the mistaken impression that the power is free therefore there is no reason to conserve This could not be further from reality The batteries are most happy when fully charged Education for all is necessary WattPlot WattPlot rev 4 6 10 is software that is installed on the Centre s laptop and connects to the MATE via a RS232 to USB adaptor WattPlot provides a graphical interface to monitor the power and battery voltage WattPlot communicates with the MATE via a pair of GC ATC 981 wireless RS232 wireless serial port Figure 10 Figure 10 GridConnect ATC 871 Wireless Serial Module The MATE must have it SETUP MATE COMM PC set to ON The MATE communication port does not have internal power so it is wired to battery bank B to provide 9 volts at pins 4 and 7 at the MATE The 12v DC power to the ATC 871 is also provided by the same batterie
4. system to monitor line frequency itself If the Outback system sees an error in line frequency it can shutdown the generator see Atkinson Engineering Application Bulletin EAB 9 July 19 2006 gt a je zi 23 E amp 1 All caties are to be minimally SAWG THHN 2 TBB Terminal Bus Bar S001 SV OL e Worse ean noe i Lo ti potter Ya XID gontrol of Soto 5c Matis Figure 21 Atkinson GSCM for staring the generator When the generator starts it will begin supplying power to both the buildings and the batteries If the buildings are requiring nearly all the generator power then the batteries will not charge However even if the buildings are switched off the charger will only be allowed 20A of current or less if the batteries do not need it Initially the batteries will usually take all the power they can have as they are weak However as the charge progresses their voltage will increase until they reach a recommended preset adsorption voltage of about 55 2V 2 3 volt cell x 24cells At this time the current will begin to drop and the batteries will begin their adsorption cycle for some hours where additional charge is placed in them At the end of the adsorption cycle the generator will automatically shutdown Note the float refloat cycles are not used in this remote off grid installation AGS will initiate a generator start under a number of conditions 1 Load Start If the building load is above 10
5. 6 2 Shock absorber The shock absorber is manufactured by Competition Engineering as a 3 way adjustable front drag racing shock The model number is C2620 and is set to the 90 10 ratio XF This puts maximum damping force into shock extension when the wind turbine is furling The shock slows the rate at which the turbine furls in high winds To set 1 hold shock vertical with rod upward 2 extend compress shock 10 times and then compress fully rotate rod clockwise several times until clicking felt or heard finally set index to XF see http www competitionengineering com catalog images c2600_inst pdf Figure 14 Competition Engineering s 3 way shock absorber model C2620 set to 90 10 Leading Edge Tape The leading edges of the turbine blades should be covered with protective tape The recommended tape is 3M 8607 Polyurethane Protective Tape However this is difficult to obtain but 3M 8671 available from www aviall com seems to be a similar product Outback Inverter Charger System The Outback System consists of four 3600 w DC AC inverter two for each phase of a 120V split phase system In normal operation the inverters take the 48 Volt DC power form the batteries and convert it to 120V 240V split phase that is sent to the buildings As it is a split phase system the load on the phases may become unbalanced so the Outback system has an autotransformer to transfer power form the lightly loaded phase to the more heavily lo
6. BROTHER BRENNAN CENTRE Renewable Energy System User Manual Introduction The renewable energy system at the Brother Brennan Centre consists of four principal components 1 two Whisper 500 wind turbine and controllers 3000 Watt peak power each Figure 1 and Figure 2 and controllers Figure 3 2 three battery packs of 24 cells each Unigy II Figure 4 and Figure 5 3 four Outback inverters chargers 3600 watt each 48 volts VFX3648 Figure 6 4 anda diesel backup generator Figure 7 shows how the above components are interconnected Figure 1 Two Whisper 500 turbines on hill behind Brother Brennan Centre ah Figure 2 Whisper 500 wind turbine TT mn SK CT fi Hi rr OUT BUE EEE EAHA UU EG Ld Figure 3 Charge controllers for wind turbines diversion resistors on top on bottom brake diversion switch and battery key switch The Outback FX inverter charger system and the Whisper wind turbines are relatively independent are only connected through the batteries The wind turbine can only put energy into the batteries while the Outback system and put energy in charging or take it out inverting For charging it must be connected to the generator Inverter D P4 Inverter C P3 Inverter B P2 Inverter A P1 1 Turbine By A Frame 2 Turbine By Outdoor Class Figure 7 Red high voltage AC Orange 48 V DC Green Low voltage Lt Blue 48V AC General Operation Figure 8 MATE displa
7. aded phase There is a breaker on the Outback Flexware AC panel labeled Auto Transformer this should always be ON The Flexware cabinet has two distribution panels the one on the left handles the 120V AC side going to and from the generator and buildings while the right panel handles the 48V DC power coming from the batteries The charger input current is limited to 18 amps which limits the overall charging current to the batteries to about 39 amps per inverter or 156 amps for the four units 7 8 kW In between there are four inverter chargers A D and these communicate with each other over ports 1 4 with port 1 bottom being the master and 2 4 being slaves Control and configuration of the controllers is collected under the MATE and its programming interface On the DC side there are four breakers that disconnect the batteries from the controllers If the system is going to be left dormant for a long period of time longer and a weekend without any wind power then these four breakers should be shut off as the inverters each require about 25 watts 100 watt total of power when in idle mode and can over a period of time drain the battery Also on this panel there is a battery indicator which is only accurate when the generator is not running Also there is a small breaker at the bottom of the panel for 48V DC power not used On the top of the AC panel left side there are 12 breakers with the left most 8 of these are ganged to a mec
8. ange indicating a problem with the tank The seal pressure should be checked each year Table 2 Diesel Fuel Tank Capacity eve Volume eve Volume Level in cm I Level in cm I 1 2 3 4 5 6 7 8 Fuel liters Litres of Fuel in Tank 0 4 8 12 16 20 24 28 32 36 40 44 48 Fuel Level inch Figure 22 Storage Tank Capacity versus Fuel Level Support Contacts Labrador Coastal Gerry amp Chris Skinner gerry labradorcoastal com Labrador Coastal Equipment Newfound Energies 98 Dogberry Hill Road St Philips NL AIM 1C2 Canada Phone 709 895 6626 Toll Free 866 895 6626 Cell 709 689 6626 Fax 709 895 6629 www windspot ca www labradorcoastal com www nfenergies com Unigy Batteries Jeff Lambert 610 682 6361 ext 2848 484 995 2899 Cell JLambert eastpennunigy com SouthWest WindPower Bo Culton gone now SouthWest have stopped the Whisper production support limited bo culton windenergy com Technical Support Representative Southwest WindPower 1801 W Route 66 Flagstaff Az 86001 928 779 9463 ph 928 779 1485 fax Constantines Engine and Performance Performance Engineering C2620 shock replacement 22 Goldstone St John s 709 753 9145 Also http www summitracing com Outback Power Systems 19009 62 Ave NE Arlington WA 98223 www outback com Tech Support 360 618 4363 6 AM 5 PM PST WattPlot Andrew Welch wattplot_info wat
9. e 56 Volt 100 power diverted 28 Whisper controller regulation off voltage 52 Volt 0 power diverted 29 Battery Capacity 5400 Amp hr Whisper Controller Regulation Setpoint 70 a Dumps current to aes resistor bank if T voltage rises above aen a E 60 this voltage for 30 s pema Regulation ON 2 a pi B Regulation OFF a co 55 o 8 50 Resumes charging gt batteries if output voltage fall below this 45 voltage for 30 s 40 0 2 4 6 8 10 12 14 16 18 Full CCW Potentiometer Turns Full CW Figure 18 Whisper 500 regulator setpoint versus potentiometer 6 turns CW default BBC setting is 52 and 56 volt 4 turns CW 0987654321 HUB CATS COMM CABLE 1ST MATE Grounding wire must be removed from DC Negative Bus Bar on shunt when installing a Ground Fault Protective device i EN I SLAVE 3 L 1 HUBIMATE RTS DC POSITIVE GROUND BOX LUG DC NEGATIVE SLAVE 2 HUB MATE RTS DC POSITIVE a GROUND BOX LUG DC NEGATIVE i SLAVE 1 HUBIMATE RTS DC POSITIVE GROUND BOX LUG DC NEGATIVE MASTER HUB MATE RTS DC POSITIVE GROUND BOX LUG DC NEGATIVE p DC NEGATIVE TBB DC BREAKERS AT O CABLING RECOMMENDATIONS e 125 AMP 2 AWG MIN 175 AMP 2 0 MIN 250 AMP 4 0 MIN FLEXWARE DC BUS BAR lil evoe 6 AWG MIN GROUND TBB FOR GROUND WIRES Figure 19
10. ess AC IN button twice 2 and then press OFF and the yellow LED should go out Re Setting AUTO Start If for some reason the generator fails to start after 17 minutes while in AUTO mode it will set a fault flag to prevent any further attempts To clear the fault the operator must manually start and then stop the generator MAN ON then MAN OFF and then switch the generator over to AUTO If the generator needs to start it will display AUTO ON otherwise it will remain displaying AUTO OFF Forced Battery Charge BULK To force a full battery charge cycle known as BULK charge press AC IN left hand side button on the Mate panel two 2 times Then press ON to manually start the generator You may hear a slight click coming from the DC power cabinet After a few minutes the ACin light on the left side of the mate will be solid yellow Press this button two more times until BULK or EQalize Press BULK button Then press START The diesel generator will go through an entire BULK recharge cycle fully charging the batteries Wait for bulk charge stopped to display and the diesel generator should automatically stop The BULK charge cycles has two steps first the batteries are brought up to the ABSORB voltage for two hours and then the voltage is reduced to the FLOAT voltage for one hour Monthly Generator Exercise At 9 30 AM on the first Tuesday of every month the Automatic Generator Start will run the generator for 15 min
11. ger on the side red post of cell 1 has big stamped on plate and the negative black terminal of the charger on the negative terminal black of cell 12 Turn the voltage selector knob fully clockwise to 24V full charge Check everything then turn timer to 1 hour Ventilate well very explosive hydrogen gas may be vented during this recharging Charging current should be 20 40 amps With the charger off remove both cables and put the negative black cable on the negative black post of cell 24 has big stamped on plate Connect the positive red cable of charger to negative black terminal of cell 13 happens to be the same as the of cell 12 Again check and charge for 1 hour Measure voltages on all three batteries if not up to 43 volts repeat process Finally make fine adjustments of individual batteries to balance them to within 0 1 volts Re Connect the battery with highest voltage to inverter Re connect battery with second highest voltage Re connect battery with third highest voltage Energize inverters by throwing four DC circuit breakers A D on right hand panel Reference Voltages Currents and Timers i i Time of Day hrs Figure 17 Typical charge cycle Discharge from 10 to 12am at 49V generator starts charging when battery voltage reaches equalize voltage 55 2 V 16 00 charger current is reduced so this voltage is held for 1 hr 17 00 then charge current is reduced further until vo
12. hanical lockout These are the AC bypass breakers If for instance the batteries failed less than 42 volts and the inverters could not be powered the generator power could not reach the buildings Before starting the generator loosen the lockout using a small wrench and switch all eight bypass breakers allowing the generator power to bypass the inverters and go directly to the buildings The generator power would now also be available in the control shed The other four other breakers on the right providing AC power to the inverters could be left on When switching back to normal mode it would be best to once again turn off the generator first switch back the eight switches and then restart the generator FLEXnet DC Monitor The FLEXnet DC monitor module Figure 15 is located on the left hand side of the DC cabinet It monitors the energy current in amp hr entering and leaving the batteries As the current from the wind turbines passes through Shunt A it causes a small voltage across it Likewise the current coming from or going to the Outback inverter charger passes through Shunt B and is also monitored The total power going into the batteries is the sum of these two sources The module also monitors the battery voltage The state of charge SOC Figure 16 and Table 1 of the batteries is monitored by keeping track of the energy entering the batteries and that being drawn from the batteries Energy withdrawn from the batteries by the inver
13. kW for 10 minutes then the generator will start to avoid a heavy battery drain It will stop again when the load falls below 7 kW Note a load start will not be commenced during Quiet Time 2 Monthly Exercise On the first Tuesday of each month at 9 15 AM the generator will run for 15 minutes This is to burn of carbon or clean out condensation 3 SOC Start When the SOC as monitored by the FLEXnet DC falls below 79 the generator will start until the SOC reaches 93 Note if in Quiet Time the 79 SOC limit will be bypassed until Quiet Time has passed Once a week a full recharge will be called for and the 93 stop limit will be overridden 4 Voltage Start There are three set points for voltage start Upon entering a voltage start sequence the generator will run through a full BULK charge cycle that is the battery voltage will increase to the adsorb set point 54 2Volt and then hold this for 1 hour Note When AGS Aux has been initiated a yellow lamp will illuminate on the AC panel in the battery room to indicate that 12V DC start signal has been sent to the generator Storage Tank The steel fuel tank is 4 in 1 22 m diameter and 12 long The capacity of the tank is approximately 4300 liters of diesel fuel Table 2 and Figure 22 show the volume of fuel remaining in the tank versus the level on the dip stick in inches or cm The tank is double walled with a vacuum seal in the cavity between If the seal fails the pressure will ch
14. ltage is at float voltage 54 V for one hour 17 00 18 00 hrs At 18 00 the generator is shut off l 2 on Ah 10 11 Minimum allowable but not recommended battery voltage 42 Volt Minimum voltage for Inverters shutdown below this voltage 46 Volt Normal voltage of healthy battery not charging no load 51 4 Volt wait 3 days after charging and no load Maximum voltage during adsorb recharge cycle 2 3 x 24 55 2 Volt End of charge voltage 55 2 0 4 54 8 V Float Voltage 52 8 Volt Duration of Adsorb Cycle before generator shutdown 3 hours Note the FN DC will stop the charge cycle if charge parameters are met for 10 minutes green light flashing Maximum AC charge input current 18 amp per charger inverter 145 amps DC Return amps 2 of 5400 110 amps Equalize voltage 55 4 Volts 2 35V x 24 Equalize period 1 hrs 12 13 14 15 16 17 18 19 20 21 Enable FN DC charge termination YES AGS Load start 10 kW AGS Load start delay 10 minutes AGS Load stop 7 kW AGS Load stop delay 10 minutes AGS Port 1 Inv A AGS Enabled yes AGS Control AUTO AGS 24 hr delay volt Start 49 2 V AGS 2 hr delay Start 48 6 V 22 AGS 2 min delay Start 48 Volt minimum recommended battery voltage 2 04 v cell 23 AGS Exercise Day First Tuesday of month 24 AGS Exercise Time 9 15AM 25 AGS Exercise Period 15 minutes 26 Output voltage 120 V AC 27 Whisper controller regulation on voltag
15. ly spinning wind generator however once stopped setting the switch to OFF will keep the generator from spinning in most winds Figure 13 Wind turbine diversion switch and LED LED Indicators e Steady illumination of the Green LED indicates that batteries are being charged by the wind generator e Steady illumination of the Red LED indicates that all available power produced by the wind generator is being diverted to the Diversion Load as a result of operator request The operator may select this mode by setting the Diversion Switch to OFF or through the LCD Display The turbines may turn slowly but will not produce power Thus the diversion switch provides a quick and easy way to shut down the turbines e A flashing Red LED indicates power is being diverted to the diversion load in order to automatically regulate the battery voltage This will happen if the battery voltage rises above 56 volts for more than 30 seconds It will stay in this mode until the battery voltage drops below 52 volts for 30 seconds When this happens the turbines turn at a much reduced speed In normal operation the rocker switch will be ON and the green LED will be lit From time to time the red LED may be blinking typically in high winds with batteries fully charged The operator may place the rocker switch OFF and the green LED will go out and the red LED will be continuously illuminated Turbine Serial Numbers 17293010 1 1729299
16. n a bulk charge As the charging proceeds the battery voltage will increase to 55 4 V After 1 hour at this voltage the charging will cease Wind turbines may stop at 55 2 V STOP will stop the charging AUTO Automatically e Press lt ACIN gt key twice for GEN START CONTROL Start Stop starts and e Press key below AUTO to place generator start control in stops automatic mode generator to e If either the battery SOC or voltage are low the generator will maintain automatically start and control will display AUTO ON battery e Make sure the enable disable switch in generator house will allow voltage state the generator to start if required If the generator fails to start of charge automatically after 3 attempts it will set a fault flag which must be manually cleared Clearing Failure to start e To clear an Auto Start fault you must manually start generator Auto Start generator press lt ACIN gt twice to GEN START CONTROL Fault automatically e Press key below ON display will read MAN ON will set a fault e After running 1 2 minutes press key below OFF The control will be left in MAN OFF manual mode off state Alternatively simply press key below AUTO and the display will read AUTO ON Ifthe generator is not required it will switch to AUTO OFF and automatically shut down the generator Press AUTO to restore AUTO mode If either the battery SOC or voltage are low the generato
17. or class is needed and it very windy the turbines can produce excessive noise preventing effective communication To make a more pleasant environment the diversion rocker switch on the turbine controller could be temporally put on to slow down the turbines and dump the power red light will be solid on Inform the kitchen staff to avoid using the dryer electric heaters to reduce load Light use during Summer or Weekends If the Centre does not have clients over a period of time the diversion switch on the controller could be put on one turbine with the active one providing power to top up and maintain the batteries Winter Shutdown Lay wind generator towers down remove tail pieces and nose cone and blades and wrap generator in waterproof tarp Remove anemometers Turn off Whisper Controller DC Key switch If batteries are not charged run a BULK charge to charge the batteries completely then turn off DC breakers A D providing power to inverters These can run the batteries down over a long period of time Temporary Winter Usage If necessary the system could be turned on DC breakers A D for a few hours of light usage Alternatively the system could be put in Bypass mode to bypass the inverters and run directly on generators Spring Startup Touch up any paint Check and replace return springs if showing cracks Replace nose cone if cracked Check turbine blades for cracks and replace any missing or torn leading edge tape replace nose
18. r will automatically start
19. s When transmitting the yellow transmit led should be flashing once per second indicating it is transmitting data To serial radio GND 9V TDX RDX NC NC NC 9V NC dO 2x9V batteries Figure 11 MATE Communication port connector Note WattPlot activation code is 58Z0H01q09 on centre s desktop PC 040e f03f 0f43 921b 46a0 g and the Mate S N is MA035149 To move WattPlot to another computer you MUST follow the procedure listed in the WattPlot manual Communication Ports The MATE FX Inverters and the FLEXnet DC monitor module all communicate through ports on the 10 port communication HUB The mate is connected to port 00 the FX master L1 inverter on port 01 FX slave L1 is on ports 02 FX slaves L2 are on ports 03 and 04 The FLEXnet DC monitor is on port 05 The AGS start relay is assigned to port 1 that is the FX Inverter A large yellow LED light will illuminate on the AC panel when the generator start relay is energized Whisper Wind Turbine System The two wind turbines have their own controllers that consist of an electrical brake that shorts the 3 phase 48 volt windings on the turbines When shorted the high current leads to high load torque so the turbine generator and the blades can only turn very slowly even in the strongest wind There is also a load dump resistor bank diversion load that automatically takes excess power from the turbine and dumps it to prevent too high a voltage from reaching the batteries
20. ters is removed at 100 factor while energy entering the batteries from the charger or the wind machines comes in at a lower efficiency 94 When the single green led is flashing SOC parameters have been met and battery recharging will cease and a discharge cycle will commence 100 gt 90 80 89 70 79 60 69 50 59 lt 50 blink Figure 16 State of charge SOC indicator lights Table 1 Approximate battery voltage and state of charge State of Volts per 48 Volt battery temperature deg C Comment 5 10 15 20 25 Amp hr 56 56 56 56 56 Regulation on 5421 52 52 52 52 52 Regulation off SOC Stop 93 SOC Start 79 24 hr start 2 hr start 2 minute start Shutdown Manual Battery Re Charging If by accident the battery voltage becomes so low that the inverters cannot be powered up then they will have to be manually recharged with the centre s 24V charger The general procedure is as follows take your time and be very careful l 10 Repeat 4 10 for batteries B and C 12 13 11 14 15 16 17 Place the AC panel in Bypass mode to provide 120V AC or bring in an external 120V generator Turn off DC breakers A D to disconnect the batteries from the inverters Remove plastic covers from batteries Remove terminal wires from batteries remember the wires could be still live and not fused even when disconnected so wrap terminals in electrical tape For battery A place the red terminal of the char
21. tplot com www wattplot com No AC Turning on or Press lt INV gt key once to get to INVERTER CONTROL menu if Power off the display is OFF press key below ON Green light on MATE Inverters above INV should come solid on and display should show ON Normally left Note if generator is running the inverter is bypassed and the ON green light will be off Start Stop Manually e Press lt ACIN gt key twice for GEN START CONTROL Generator START e Press key below ON to start generator Display will read MAN STOP ON Yellow light on panel will illuminate to indicate control Generator signal sent to generator After a few minutes the yellow light on MATE will flash indicating generator running Finally it should go solid yellow Note starting the generator alone will not charge the batteries a BULK charge cycle is also required e Press key below OFF to stop generator Display will read MAN OFF It will take 2 3 minutes for the generator to stop BULK Applies AC e Press lt ACIN gt once and check AC INPUT CONTROL is USE Charge power to If DROP press key below USE Battery charge e Next press lt ACIN gt key one more time to GEN START batteries CONTROL start generator Wait until light above lt ACIN gt is solid yellow e Next Press lt ACIN gt twice more to get to CHARGER CONTROL MODE e Press key below BULK to enter BULK CONTROL e Press key below START to begi
22. utes Monthly Battery Equalize EQ Equalize applies a slightly higher charging voltage for a shorter time Do BULK charging first if necessary On MATE press AC IN four 4 times to get CHARGER MODE CONTROL Press EQ to bring up the EQUALIZE screen START will start charge and STOP will stop it The AC IN status light must be solid yellow Inverter ByPass Mode Before starting generators loosen the bypass mode switch mechanical lockout bar need a 11 32 wrench on the Flexware AC panel left hand side cabinet and switch the four switches under the right side of the plate 1 to off down to disconnect the inverters from the buildings Lights will go out Then switch the four switches on the left side 2 of the plate to on also down to connect the diesel generator directly Start diesel generator and the inverters will now be by passed and the power restored Figure 9 AC Bypass switches under plate do 1 switches first then 2 switches To leave by pass mode switch 2 to off up then switch 1 on also up Excessive Wind Speed During periods of excessive wind speed approaching hurricanes etc it will be better to put the brakes on to reduce the wear and tear on the turbines Note when the wind speed is very high the Whisper controller dumps most of its energy so there is no big loss in having the brakes on Teaching in Meadow If the battery is in a reasonable state of charge and the meadow or outdo
23. ys status and controls generator chargers inverters MATE serial number MA035149 On the MATE there are two LED lights one above the AC IN key yellow and one above the INV key green The yellow LED above the AC IN provides status of the AC from the generator Flashing means generator is running but not connected to Outback system Solid On mean generator running connected and in use Offno generator AC present normal The green LED above the INV key provides status of the inverter and also has three modes Flashing means the inverter is in search or power save mode this mode not used at BBC Solid On means the batteries are supplying power to the buildings normal Off means it is not converting battery power to AC No Power in Buildings If there is no power in buildings it may mean that the inverters are switched off The green light above the INV button on the MATE should be illuminated To check the status of the inverters press the INV button once to get to the INVERTER CONTROL screen It may read Currently OFF If so press the button below ON and the display should change to Currently ON and then press OK The light above the INV key should turn solid green Manual Generator Start Stop Press AC IN button on MATE twice 2 to get GEN START CONTROL and then press ON the diesel generator should start and yellow light should illuminate To manually stop the generator pr
Download Pdf Manuals
Related Search
Related Contents
Eton E1 Dark silver USER`S MANUAL MODEL: 5970-80 MODEL User Guide for the TIMSS International Database Adding Peripherals - Big Fin Scientific Crazy Controllerz Xbox One V5 Controller User Manual.pages PCM Codec Connection to TC1130 12 - Atelier Théâtre Jean Vilar BENDIX TCH-001-036 User's Manual Copyright © All rights reserved.