Home
        INSTALLATION MANUAL
         Contents
1.          Be sure only trained and qualified service personnel to  install  repair or service the equipment    Improper installation  repair  and maintenance may result in  electric shocks  short circuit  leaks  fire or other damage to  the equipment     Install according to this installation instructions strictly   If installation is defective  it will cause water leakage   electrical shock fire     When installing the unit in a small room  take measures  against to keep refrigerant concentration from exceeding  allowable safety limits in the event of refrigerant leakage   Contact the place of purchase for more information   Excessive refrigerant in a closed ambient can lead to oxygen  deficiency     Use the attached accessories parts and specified parts  for installation    otherwise  it will cause the set to fall  water leakage   electrical shock fire     Install at a strong and firm location which is able to  withstand the set  s weight    lf the strength is not enough or installation is not properly  done  the set will drop to cause injury     The appliance must be installed 2 5m above floor   The appliance shall not be installed in the laundry     Before obtaining access to terminals  all supply circuits  must be disconnected     The appliance must be positioned so that the plug is  accessible     The enclosure of the appliance shall be marked by word   or by symbols  with the direction of the fluid flow     For electrical work  follow the local national wiring  standard
2.   oo        B  For 18000 60000   Fig 5 9  Q NOTE    This chart is based on 36000 type  So  a little differences  may exist on the outlook and functions from yours         n case of air return from back please refer to the following     205  300    Back panel layout     For 18000 48000     Fig 5 10    m Inthe above figure  double point line means the dimensions of  air inlet box     mM Please explain clearly when ordering if customers need air inlet  box  And note it is below air inlet or back air inlet     installation manual    5    75 Main body  800          40  Fig  5 11 e apent  Electric control box   Gas sideoF   Connecting point of  refrigerant pipe   Liquid sideoG   A Dust proof net  Connecting point of drain pipe W 40 NI  Additional purchase   tina hole 470 Canvas air passage  Entrances and exits for communicatio Ceiling hole  Additional purchase   lines of indoor and outdoor units Panel 500 sant   Additional purchase   300 Main body  800  Fixing screw  Connecting point of  refrigerant pipe   Gas sideoF   Fig 5 11a    Connecting point of  refrigerant pipe     Liquid side  G        Filter net  Connecting point of drain pipe M 459    S    Additional purchase     Ceiling hole 470 Canvas duct  Eling Note TU Additional purchase  Panel 500 eae    Air inlet plank    Additional purchase     125 Plank inside      For air delivery from outside   Co     For 48000 II  60000     Note  Fig 5 11         Use for slim duct A3  series  Fig  6 1 Ta       Use for high static pressure duc
3.   regulation and this installation instructions  An  independent circuit and single outlet must be used    lf electrical circuit capacity is not enough or defect in  electrical work  it will cause electrical shock fire     Use the specified cable and connect tightly and clamp  the cable so that no external force will be acted on the  terminal    lf connection or fixing is not perfect  it will cause heat up or  fire at the connection     Wiring routing must be properly arranged so that control  board cover is fixed properly    lf control board cover is not fixed perfectly  it will cause  heat up at connection point of terminal  fire or electrical  shock     If the supply cord is damaged  it must be replaced by the  manufacture or its service agent or similarly qualifued  person in order to avoid a hazard     An all pole disconnection swith having a contact  separation of at least 3mm in all poles should be  connected in fixed wrong     When carrying out piping connection  take care not to let  air substances go into refrigeration cycle    Otherwise  it will cause lower capacity  abnormal high  pressure in the refrigeration cycle  explosion and injury     Do not modify the length of the power supply cord or use  of extension cord  and do not share the single outlet with  other electrical appliances    Otherwise  it will cause fire or electrical shock     Carry out the specified installation work after taking into  account strong winds  typhoons or earthquakes   Improper install
4.  1 meter away from  televisions or radios in order to prevent image  interference or noise    Depending on the radio waves  a distance of 1 meter may not  be sufficient enough to eliminate the noise     The appliance is not intended for use by young children  or infirm persons without supervision     Don t install the air conditioner in the following locations     There is petrolatum existing     There is salty air surrounding  near the coast      There is caustic gas  the sulfide  for example  existing in  the air  near a hot spring      The Volt vibrates violently  in the factories     In buses or cabinets    In kitchen where it is full of oil gas    There is strong electromagnetic wave existing   There are inflammable materials or gas     There is acid or alkaline liquid evaporating     Other special conditions     installation manual    2    INSTALLATION INFORMATION       To install properly  please read this    installation manual    at  first     The air conditioner must be installed by qualified persons     When installing the indoor unit or its tubing  please follow  this manual as strictly as possible     If the air conditioner is installed on a metal part of the  building  it must be electrically insulated according to the  relevant standards to electrical appliances     When all the installation work is finished  please turn on  the power only after a thorough check     Regret for no further announcement if there is any change  of this manual caused by product impr
5.  In laying or embedding the screw bolts     R4         Blade shape  Slide insertion   insertion  Fig  5 9     Steel bar  Embedding screw bolt   Pipe hanging and embedding  screw bolt  Fig  5 4    FOR ORIGINAL CONCRETE BRICKS    Install the hanging hook with expansible bolt into the  concrete deep to 45 50mm to prevent loose     Fig 5 5    STEEL ROOF BEAM STRUCTRUE    Install and use directly the supporting angle steel     Hanging screw bolt       Hanging  bolts angle steel    Fig  5 6    2 Overhanging the indoor unit    E      Overhang the indoor unit onto the hanging screw bolts with  block     m Position the indoor unit in a flat level by using the level  indicator unless it may cause leakage         Screw nut          Washer  Overhang part           Hanging  screw bolt    Fig 5 7    3 Installing the dust proof net and canvas air passage    E install the dust proof net according to the installation manual     M Install the canvas air passage underneath the dust proof net     4 Pipe Connection    m The static pressure in the outside of the unit is 39 2Pa   maximum 98Pa   the length of the air pipe attached is  determined by this parameter     5 The positioning of ceiling hole and indoor unit and hanging  screw bolts    Air outlet Hanging Screw  bolt          Main body   A        4 M10 Site  configuration    Ceiling hole  D     For 18000 60000     Fig 5 8    r Hanging Screw bolt  Distance between bolts  B    Air outlet 4 M10  Site prepared     Main body   A       400 640  A  
6.  the outdoor unit   Then fasten the nuts at the repair points     Bend the connecting pipe of small wall thickness     Cut out a desired concave at the bending part of the  insulating pipe   e Then expose the pipe cover it with tapes after bending        To prevent collapsing of deforming  please bend the pipe  at its biggest radius     e Use bender to get a small radius pipes     NOTE    The bending angle should not exceed 90       Bending position is preferably in the middle of the bendable  pipe  The larger the bending radius the better it is     Do not bend the pipe more than three times     Be sure to use the same insulating materials when you buy  the brass pipe   More than 9mm thick     Locate The Pipe    Drill a hole in the wall  suitable just for the size of the wall  conduit   then set on the fittings such as the wall conduit and its  cover     Bind the connecting pipe and the cables together tightly with  binding tapes    Pass the bound connecting pipe through the wall conduct from  outside  Be careful of the pipe allocation to do on damage to  the tubing     Connect the pipes  Refer to  How to Connect the  pipes    for details     Expel the air with a vacuum pump  Refer to  How to  expel the air with a vacuum pump  for details     open the stop values of the outdoor unit to make the  refrigerant pipe connecting the indoor unit with the  outdoor unit in fluent flow     Check the leakage  Check all the joints with the leak  detector or soap water     Cover the joint
7. 1 The power connection for the air conditioner has to be  done at the main power distribution  The distribution has  to be of a low impedance  normally the required  impedance reaches at a 32 A fusing point     2 No other equipment has to be connected with this power  line     3 For detailed installation acceptance please refer to your  power supplier  if restrictions do apply for products like  washing machines  air conditioners or electrical ovens     4 For power details of the air conditioner refer to the rating  plate of the product     5 For any question contact your local dealer     11 1 Connect the cable    m Dissemble the bolts from the cover  If there isn t a cover on  the outdoor unit  disassemble the bolts from the maintenance  board  and pull it in the direction of the arrow to remove the  protection board      refer to Fig  11 1     mM Connect the connective cables to the terminals as identified  with their respective mached numbers on the terminal block  of indoor and outdoor units     m Re install the cover or the protection board     11 2 The Specification of Power   refer to Table 11 1     11 3 Wiring figure   refer to Fig  11 2   Fig  11 5        Protection board    Fig 11 1    Q NOTE    All the pictures in this manual are for explanation purpose only     They may be slightly different from the air conditioner you  purchased depend on model  The actual shape shall prevail     installation manual    14    12  TEST OPERATION    1 The test operation must be car
8. INSTALLATION MANUAL       DUCT TYPE    Thank you very much for purchasing our air conditioner   Before using your air conditioner   please read this manual carefully and keep it for future reference     CONTENTS PAGE    PRECAUTIONS   INSTALLATION INFORMATION  ATTACHED FITTINGS   INSPECTING AND HANDLING THE UNIT   INDOOR UNIT INSTALLATION  OUTDOOR UNIT INSTALLATION    INSTALL THE CONNECTING PIPE  REFRIGERANT PIPE CONNECTION  CONNECT THE DRAIN PIPE  CONNTROL   WIRING   TEST       1  PRECAUTIONS            Be sure to be in conformity with the local  national and  international laws and regulations    M Read  PRECAUTIONS  carefully before installation    Mm The following precautions include important safty items   Observe them and never forget      E Keep this manual with the owner s manual in a handy place    for future reference        The safty precautions listed here are divided into two categories  In  either case  important safty information is listed which must be read  carefully        who WARNING L  Failure to observe a warning may result in death   ik CAUTION    Failure to observe a caution may result in injury or damage  to the equipment        After completing the installation  make sure that the unit operates  properly during the start up operation  Please instruct the customer  on how to operate the unit and keep it maintained Also  inform  customers that they should store this installation manual along with  the owner s manual for future reference           WARNING
9. ND HANDLING THE UNIT      At delivery  the package should be checked and any damage should  be reported immediately to the carrier claims agent     When handling the unit  take into account the following     1 Ld Fragile  handle the unit with care     ttl Keep the unit upright in order to avoid compressor    damage    2 Choose on before hand the path along which the unit is to be  brought in    3 Move this unit as originally package as possible    4 When lifting the unit   always use protectors to prevent belt  damage and pay attention to the position of the unit   s centre of  gravity     5  INDOOR UNIT INSTALLATION    5 1 Installation place   refer to Fig 5 1 for specification      The indoor unit should be installed in a location that meets  the following reauirements     e There is enough room for installation and maintenance        The ceiling is horizontal  and its structure can endure the  weight of the indoor unit        The outlet and the inlet are not impeded  and the influence  of external air is the least        The air flow can reach throughout the room   e The connecting pipe and drainpipe could be extracted out  easily     e There is no direct radiation from heaters     ik CAUTION    Keep indoor unit  outdoor unit  power supply wiring and  transmission wiring at least 1 meter away from televisions  and radios  This is to prevent image interference and  noise in those electrical appliances   Noise may be  generated depending on the conditions under which the  el
10. ation work may result in the equipment falling  and causing accidents     installation manual    1    If the refrigerant leaks during installation  ventilate the  area immediately    Toxic gas may be produced if the refrigerant comes into the  place contacting with fire     The temperature of refrigerant circuit will be high  please    keep the interconnection cable away from the copper tube     After completing the installation work  check that the  refrigerant does not leak   Toxic gas may be produced if the refrigerant leaks into the  room and comes into contact with a source of fire  such as a  fan heater  stove or cooker        CAUTION    Ground the air conditioner    Do not connect the ground wire to gas or water pipes   lightning rod or a telephone ground wire Incomplete  grounding may result in electric shocks     Be sure to install an earth leakage breaker   Failure to install an earth leakage breaker may result in  electric shocks     Connect the outdoor unit wires   then connect the indoor  unit wires    You are not allow to connect the air conditioner with the  power source until wiring and piping the air conditioner is  done     While following the instructions in this installation  manual  install drain piping in order to ensure proper  drainage and insulate piping in order to prevent  condensation    Improper drain piping may result in water leakage and  property damage     Install the indoor and outdoor units  power supply wiring  and connecting wires at least
11. de of the fix board of the waist shaped hole on the  hook of the main body         Tighten the other side of the board with screw to the outside  frame     E Cut off the surplus part of the board with pliers     mM Bend the top of the broken end     Q NOTE    when hanging up the outside frame with the fix board of  waist shaped hole and the belt  stick the outside frame  tightly to the ceiling and fix it     Hook          Waist shaped hole  fixed board    Outside frame    s oS f Bend    Fig 5 21    6 Install the inner frame on the outside frame  the inverse  sequence of unloading the inner frame      Q NOTE    Connect the remote control receiver with the indoor unit  signal wires and fix it         For 18000 60000     Fig 5 22        Reverse side     Air pa  sage    Outside frame        Inside frame  Air inlet     For 18000 48000 I    Fig 5 23    7 Install remote controller     6  OUTDOOR UNIT INSTALLATION    6 1 Installation Place    E The outdoor unit should be installed in the location that  meets the following requiements        There is enough room for installation and maintenance        The air outlet and the air inlet are not impeded  and can  not be reached by strong wind        It must be a dry and well ventilating place     e The support is flat and horizontal and can stand the  weight of the outdoor unit  And will no additional noise or  vibration        Fig 6 2  e Your neighborhood will not feel uncomfortable with the  noise or expelled air        Itis easy to ins
12. ectric wave is generated  even if 1 meter is kept         N    CCa       Fig 5 1    installation manual    4    NOTE    Notes Before Installation  Identify the correct transporting route     Move the air conditioner in its original package as possible as  you can     If the unit should be installed on the metal part of the  building  electric insulation is necessary and make sure that it  comply with the relevant technical standard of electric  equipment     5 2 Install hanging screw bolts    1 Installing   10 hanging screw bolts   4 bolts    a Please refer to the following figure for the hanging screw  bolts distance   5 Please install with 010 hanging screw bolts    if The handling to the ceiling varies from the constructions     consult the construction person for the specific condition     e The size of the ceiling to be handled       Do keep the  ceiling flat  Consolidate the roof beam for possible  vibration     e Cut off the roof beam     e Strengthen the place that has been cut off  and consolida   tethe roof beam     E After the selection of installation location  position the refriger   ant pipes  drain pipes  indoor  amp  outdoor wires to the connection  places before hanging up the machine     E The installation of hanging screw bolts     WOODEN CONSTRUCTION    Put the square timber traversely overthe roof beam  then install  the hanging screw bolts     Timber over the beam       Q Roof beam  Ceiling         Hanging screw bolts    Fig 5 2    NEW CONCRETE BRICKS   
13. een set    before leaving the factory   anyone  can   t modify it except the  maintenance person        10 2 Network address set       IL    Every air conditioner in network has only one network address  to distinguish each other  Address code of air conditioner in  LAN is set by code switches S1  amp  S2 on the Main Control Board    of the indoor unit  and the set range is 0 63     Toggle switch set Network    address  code    00 15    16 31  32 47    WIRING    CAUTION    The appliance shall be installed in accordance with nat   ioanl wiring regualtions    The air conditioner should use separate power supply  with rated voltage     The external power supply to the air conditioner should  have ground wiring  which is linked to the ground wiring  of the indoor and outdoor unit     The wiring work should be done by qualified persons  according to circuit drawing     An all pole disconnection device which has at least 3mm  speparation distance in all pole and a residual current  device RCD  with the rating of above 10mA shall be  incorporated in the fixed wiring according to the national  rule     installation manual    13    Be sure to locate the power wiring and the signal wring  well to avoid cross disturbance     Do not turn on the power until you have checked carefully  after wiring     Q NOTE    Remark per EMC Directive 89 336 EEC   For to prevent flicker impressions during the start of the  compressor  technical process     following installation  conditions do apply     
14. hased depend on model   The actual shape shall prevail     7  INSTALL THE CONNECTING PIPE    Check whether the height drop between the indoor unit and  outdoor unit  the length of refrigerant pipe  and the number of  the bends meet the following requirements     Table 7 1  JEJEJE   ih a EALA al el et leiro    Jadelle pee    When outdoor FF 12   12   12   20   20  20 12  unit is bottom    The number of bends ae Less than 10    installation manual    10    The outdoor unit is factory charged with refrigerant   Some systems require additional charging of regrigerant  depending on pipe lengths  The additional refrigerant to  be cahrged can be calculated from the following formule     Table 7 2    D mm   R g  26 35 29 53   12 7  L m     Added Refrigerant When 11g mx L 5   30g mx L 5   60g mx L 5     Over 5m One way    Do not let air  dust  or other impurities fall in the pipe system  during the time of installation      The connecting pipe should not be installed until the indoor and  outdoor units have been fixed already      Keep the connecting pipe dry  and do not let moisture in during  installation      Please record the quantity added and store it carefully for  future maintenance        7 1 The Procedure of Connecting Pipes    z    CAUTION    All field piping must be provided by a licensed  refrigeration technician and must comply with the  relevant local and national codes     Do not let air  dust  or other impurities fall in the pipe  system during the time of installatio
15. manual    12    8 3 Insulation    E Be sure to with insulating materials cover all the exposed parts  of the flare pipe joints and refrigerant pipe on the liquid side  and the gas side  Ensure that there is no gap between them     a Incomplete insulation may cause water condensation     9  CONNECT THE DRAIN PIPE    1 Install indoor unit drain pipe    The outlet has PTI screw bread  Please use sealing materials  and pipe sheath fitting  when connecting PVC pipes     e The drain pipe of indoor unit must be heat insulated  or it  will condense dew  as well as the connections of the  indoor unit     e Hard PVC binder must be used for pipe connection  and  make sure there is no leakage     e With the connection part to the indoor unit  please be  noted not to impose pressure on the side of indoor unit    pipes     e When the declivity of the drain pipe downwards is over  1 100  there should not be any winding     e The total length of the drain pipe when pulled out  traversely shall not exceed 20m  when the pipe is over  long  a prop stand must be installed to prevent winding     e Refer to the figures on the right for the installation of the  pipes       ee oe oe eet a   lt r            rode       Insulating      Downward declivity  material lower than 1 100       Fig 9 1  Bend X  7a Scape  Fig 9 2  Put as deep as possible   about 10cm   Downward declivity  lower than 1 100 VP30 Fig  9 3  2 Drainage test  a Check whether the drainpipe is unhindered  a New built house should have 
16. mporary buttons works well   g  Whether the drainage is normal   h  Whether there is vibration or abnormal noise during  operation      Whether the air conditioner heats well in the case of the  HEATING COOLING type     e 2  The outdoor unit  a  Whether there is vibration or abnormal noise during  operation   b  Whether the generated wind  noise  or condensed of by  the air conditioner have influenced your neighborhood   c  Whether any of the refrigerant is leaked        rr CAUTION    A protection feature prevents the air conditioner from being  activated for approximately 3 minutes when it is restarted  immediately after shut off     m  The Specification of Power       E Table 11 1    18000 24000Btu h 30000 48000Btu h 36000 60000Btu h        with 1 Phase Outdoor Unit     with 1 Phase Outdoor Unit     with 3 Phase Outdoor Unit     1 PHASE    FREQUENCY AND VOLT 220 240V    50HZ 220 240V    50HZ    INDOOR OUTDOOR CONNECTING WIRING 3 core shielded wire   WEAK ELECTRIC SIGNAL   mm   3x0 5             PHASE 1 PHASE                220 240V   50Hz            3 core shielded wire  3x0 5    3 core shielded wire  3x0 5        rt CAUTION    A disconnection device having an air gap contact separation in all active conductors should be incorporated  in the fixed wiring according to the National Wiring Regulation   The power cord type designation is HO7RN F     installation manual    15    E Fig 11 2    Power supply    220 240V  50Hz  1 phase    Power supply  220 240V  50Hz    sy Circuit b
17. n     The connecting pipe should not be installed until the  indoor and outdoor units have been fixed already     Keep the connecting pipe dry  and do not let moisture in  during installation     Execute heat insulation work completely on both sides  of the gas piping and the liquid piping  Otherwise  this  can sometimes result in water leakage     1 Measure the necessary length of the connecting  pipe  and make it by the following way     E Connect the indoor unit at first  then the outdoor unit       Bend the tubing in proper way  Do not harm to them   Bend the pipe with thumb    ATV    min radius 100mm Fig  7 4   e Daub the surfaces of the flare pipe and the joint nuts  with frozen oil and wrench it for 3 4 rounds with hands  before fasten the flare nuts  Refer to chart 16     Use frozen oil       Fig 7 2    e Be sure to use two wrenches simultaneously when you  connect or disconnect the pipes            Make the ends  straight  Fig 7 3    The stop valve of the outdoor unit should be closed absolutely   as original state  Every time you connect it first loosen the nuts  at the part of stop valve  then connect the flare pipe  immediately  in 5 minutes   If the nuts have been loosened for  a long time  dusts and other impurities may enter the pipe  system and may cause malfunction later So please expel the air  out of the pipe with refrigerant before connection     Expel the air refer to the    Expel The Aijr    after connecting the  refrigerant pipe with the indoor unit and
18. n onthe vacuum pump  At the beginning of pumping   loosen the maintenance terminator nut of stop valve B a  little to check whether the air comes in  the sound of the  pump changes  and the indicator of compound meter  turns below zero   Then fasten the nut     installation manual    11      When the pumping has finished  close the Lo lever of the  manifold valve completely and turn off the vacuum pump   When you have pumped for over 15 minutes  please  confirm that the indicator of multimeter is on  1 0X10  Pa    76cmHg     e Loosen and remove the quadrangle cover of stop valves  Aand B to open stop valve A andB completely  then  fasten them       Disassemble the charge hose from the repair mouth of  stop valve A  and fasten the nut     Manifold valve  Multi meter   Pressure meter        Hi lever  Charge hose    Z acuum pump    Lo lever    Fig  8 3    dk CAUTION    All the stop valves should be opened before test  operation  Each air conditioner has two stop valves of  different sizes on the side of the outdoor unit which  operate as Lo stop value  respectively  Refer to Fig  8 4     Flare nut       Valve body    Valve stern    Fig  8 4    8 2 Check the Leakage    heck all the joints with the leak detector or soap water   See Fig 8 5  as a reference illustration     in the chart   A      L0 stop valve   B      Hi stop valve   C D  Joints of the connecting pipe to the indoor unit     Check point of indoor unit D C        Check point of outdoor unit    Fig 8 5    installation 
19. ovement        INSTALLATION ORDER    M Select the location       Install the indoor unit    M Install the outdoor unit    m Install the connecting pipe    m Connect the drain pipe    E Wiring       E Test operation     3  ATTACHED FITTINGS    Please check whether the following fittings are of full scope  If there are some spare fittings   please restore them carefully     NAME QUANTITY USAGE                1  Pipe insulating material  Heat resisting     2  Drain elbow To connect drain    To connect drain    4  Signal receiver display board Receive Signal    a Never throw or beat the controller  Mounting screw B   T2 9x10 C H    5  Remote controller  6  Frame  7  Mounting screw ST2 9 X 10 C H     8  Alkaline dry batteries  AM4        10  Owner s manual    Cautions on remote controller installation     a Before installation  operate the remote controller to determine its location in a  reception range       Keep the remote controller at least 1m apart from the nearest TV set or stereo  equipment   it is necessary to prevent image disturbances or noise interferences          a Do not install the remote controller in a place exposed to direct sunlight or close to a  heating source  such as a stove  Remote controller  holder  a Note that the positive and negative poles are right positions when loading batteries  Remote  controller  m   This manual is subject to changes due to technological improvement without further Fig 3 1  notices     installation manual    3    4  INSPECTING A
20. pen two of the three directions 895   590   333   355   302   313   862   M N P   refer to Fig 6 5   220   e24   a06   290   sso   asa   500       puim Buoys    R22  624   366   396   340   354 Fig 6 2    940 376   400   340   360   1245  Fig 6 1       v NOTE       All the pictures in this manual are for explanation purpose  only  They may be slightly different from the air conditioner  you purchased depend on model  The actual shape shall  prevail        installation manual    9        Wall or obstacle        Fig 6 5    NOTE    All the pictures in this manual are for explanation purpose only   They may be slightly different from the air conditioner you  purchased depend on model   The actual shape shall prevail     6 2 Moving and installation      Since the gravity center of the unit is not at its physical  center  so please be careful when lifting it with a sling        Never hold the inlet of the outdoor unit to prevent it from  deforming      Do not touch the fan with hands or other objects       Do not lean it more than 45  and do not lay it sidelong      Make concrete foundation accoding to the sepecif ications of    the outdoor units   refer to Fig 6 6        Fasten the feet of this unit with bolts firmly to prevent it from  collapsing in case of earthquake or strong wind  refer to  Fig 6 6            Fix with bolt    Fig 6 6      NOTE    All the pictures in this manual are for explanation purpose only   They may be slightly different from the air conditioner you  purc
21. reaker 1 phase    Power wiring  indoor     Communication Bus Circuit breaker    Outdoor  Unit    CENTRAL CONTROL  MONITOR CCM  COMPUTER       For 18000 60000Btu h  with 1 Phase outdoor unit     E Fig 11 3    Power supply    220 240V  50Hz  1 phase    Power supply  380 415V  50Hz    sy Circuit breaker 3 phase    Power wiring  indoor     a Circuit breaker  Communication Bus    Indoor  Unit Outdoor  Unit    CENTRAL CONTROL  MONITOR CCM  COMPUTER       For 36000 60000Btu h  with 3 Phase outdoor unit     ri CAUTION    The wiring diagram of the air conditioner are shown as follows  When wiring  please choose the  corresponding figure or it may cause damage     installation manual    16    E Fig 10 4    INDOOR UNIT    Power Supply  3 core shielded able to CCM 1 Phase 220 240       3x0 5 mm   3 core cable 3x1  0 me     3 core shielded cable   3x0  5 mm      Power Supply    1 Phase 20 240V    3 core cable 3 x2  5mm      OUTDOOR UNIT       For 18000 60000Btu h  with 1 Phase outdoor unit     E Fig 10 5    INDOOR UNIT    ta  Power Supply  3 core shied ed cable to CCM 1 Phase 20 240V       3x0  5 mm2   3 core cable 3x1  0 mm        3 core shielded cable     3x0 5 mm      Power Supply  3 Phase 380 415V    6 core cable 5x2  5 nm        OUTDOOR UNIT       For 36000 60000Btu h  with 3 Phase outdoor unit     installation manual    17    
22. ried out after the entire  installation has been completed     2 Please confirm the following points before the test operation     e The indoor unit and outdoor unit are installed properly   e Tubing and wiring are correctly completed       The refrigerant pipe system is leakage checked    e The drainage is unimpeded    e The heating insulation works well    e The ground wiring is connected correctly     e The length of the tubing and the added stow capacity of  the refrigerant have been recorded     e The power voltage fits the rated voltage of the air  conditioner     e There is no obstacle at the outlet and inlet of the outdoor  and indoor units        The gas side and liquid side stop valves are both opened   e The air conditioner is pre heated by turning on the power     3 According to the user s requirement  install the remote  controller frame where the remote controller s signal can  reach the indoor unit smoothly     4 Test operation      Set the air conditioner under the mode of  COOLING  with the    remote controller  and check the following points  If there is  any malfunction  please resolve it according to the chapter   Troubleshooting  in the  Owner s Manual      e 1  The indoor unit  a  Whether the switch on the remote controller works well   b  Whether the buttons on the remote controller works  well   c  Whether the air flow louver moves normally   d  Whether the room temperature is adjusted well   e  Whether the indicator lights normally   f  Whether the te
23. s of the connecting pipe with the  soundproof   insulating sheath  fittings   and bind it  well with the tapes to prevent leakage        8  REFRIGERANT PIPE CONNECTION    8 1 Expel The Air    1 Flaring    e Cuta pipe with a pipe cutter   refer to Fig  8 1     OXXX  90   Lean crude burr  A      A  y 11      Insert a flare nut into a pipe and flare the pipe     Fig 8 1       2 Fasten the nut    e Put the connecting tubing at the proper position   wrench the nuts with hands then fasten it with  a wrench   refer to Fig 8 2        Fig 8 2    ri CAUTION    Too large torque will harm the bellmouthing and too small will  cause leakage  Please determine the torque according to  Table 8 1     Table 8 1  Flare dimensin A    Pipe E onin torque min  mm  max Flare shape  14 2 17 2 N m  204  144   176 kgf cm          mo  pi  1      20   R  184 l   i      32 7 39 9 Nm  09 5  333 407 kgf cm  49 5 60 3 Nm    prer  504 616 kgf cm     2 0  5 4  61 8 75 4 N m  A  630 770 kgf cm   97 2 118 6N m  AE  990   1210 kgf cm  22 9   23 3    3 Expel the air with a vacuum pump Refer to Fig 8 3      Please refer to its manual for the way of using manifold  valve     e Loosen and remove the maintenance nuts of stop valves  A and B  and connect the charge hose of the manifold  valve with the maintenance terminator of stop valve A    Be sure that stop valves A and B are both closed     e Connect the joint of the charge hose with the vacuum  pump     e Open the Lo lever of the manifold valve completely       Tur
24. t  MHB  series    E When using a back air installation  please refer to the following       P 250xL       Back panel layout     For 48000 II 60000     installation manual    6    Table 5 1 mm      Move A B    B    F G H   J K M m n Refrigerant    18000 Btu h R410A  24000 Btu h iia  30000 Btu h     36000 Btu h   48000 I Btu h               Q NOTE    The dimension of 24000Btu h and 30000Btu h 3 PHASE are the same  The dimension of 30000Btu h and 36000Btu h 1 PHASE are the same       Table 5 2 mm    Refrigerant    I   ro oo pef 2 Pee fat  60000 Btu h Cy oy ay gy a e ea e e a a a       5 3 Install the main body                     d Main body  Main body Distance between bolts M  Distance between bolts i h  oint of ili it Connecting point of  ili iii  sor banal pe i n re ferigerantpipe   ji Throttle part  H Il ili   Gas sidedF    Throttle part  Gas sidedF  A  K    Sa  jai Electric control box  Electric contro  box Connecting point of  Connecting point of refrigerant pipe  A emj  refrigerant pipe  Liquid sidedG  Se z  t   e     Liquid sideG  T      Dust proof net Connecting point of drain pipe pe    Dust proof net    i  gt  aai A D A ST Ny  Additional purchase   CONRRHES POETS AN oS N  Additional purchase  Entrances  and exits for  communigation Pe Canvas air passage  I ceiling hole   Canvas air passage limes of indoor and outdoor units Ceiling hole JN YAdditional purchase   Entrances and exits for communication   Ceiling ho  Additional purchase  Panel  lines of indoor and outdoor 
25. tall the connecting pipes or cables     e Determine the air outlet direction where the discharged air  is not blocked     e There is no danger of fire due to leakage of inflammable  gas     e The piping length between the outdoor unit and the indoor  unit may not exceed the allowable piping length     e Inthe case that the installation place is exposed to strong  wind such as a seaside  make sure the fan operating  properly by putting the unit lengthwise along the wall or  using a dust or shield  refer to Fig 6 1     e If possible  do not install the unit where it is exposed to  direct sunlight     e  f necessary  install a blind that does not interfere with the  air flow     e During the heating mode  the water drained off the  outdoor unit   The condensate should be well drained away  by the drain hole to an appropriate place  so as not to  interfere other people     e Select the position where it will not be subject to snow  drifts  accumulation of leaves or other seasonal debris  If  unavoidable  please cover it with a shelter        e Locate the outdoor unit as close to the indoor unit as    possible  Fig 6 4   e If possible  please remove the obstacles nearby to prevent  the performance from being impeded by too little of air Table 6 1 mm  circulation     e The minimum distance between the outdoor unit and  0  n  3 ee  obstacles described in the installation chart does not    B C D E F H  mean that the same is applicable to the situation of an 24  airtight room  Leave o
26. this test done before paving the    ceiling     e Remove the test cover and stow water of about 2000ml  to the water receiver through the stow tube  Refer to  Fig 9 4     Water to the receiver  Test cover through the stow tube        Take 36000Btu h type as example   Fig 9 4    3 Drain Elbow Installation Cooling Only Type  Without     Fit the seal into the drain joint  then insert the drain joint into the  base pan hole of outdoor  rotate 90   to securely assemble them   Connect the drain joint with an extension drain hose  Locally  purchased   in case of the condensate draining off the outdoor  unit during the heating mode     Seal  Seal Drain joint The base pan hole  of outdoor unit  The base pan Drain  of outdoor unit joint  Fig 9 5    All the pictures in this manual are for explanation purpose only   They may be slightly different from the air conditioner you  purchased depend on model  The actual shape shall prevail     10  CONTROL    e The capacity of the system and the network address of  the air conditioner can be set by the switches on the  Main Control Board of the indoor unit     e After the setting  be sure to cut down the main power  supply switch  then turn it on again       Setting would be invalid without disconnecting the  power     10 1 Horsepower code set    The capacity of the indoor unit has been set before  leaving the factory according to the below table     Horsepower code       POWER_S             ENC1 ar ha Capacity Btu h     Note  The capacity has b
27. units Panel  Additional purchase    Additional purchase    For 18000 60000   For 19000 00990   Fig 5 13 Fig 5 14  5 4 Panel installation  i Inside f  1 Unload inner frame  aside frame  Knob  M Slide the knob  release the buckle from the outside frame hole   then unload the inner frame  _  2 Hang the outside frame on the main body with face down   4  places at 4 corners    E Hang the belt on the hook of the main body  Fig 5 15    installation manual    7    Q NOTE    The signal wire of the remote control receiver must be  drawn out through the canvas air passage     Hook  Gallus  Outside  P   frame    Fig 5 16         Main body    Canvas air passage       Waist shaped hole  fixed board    Ceiling     For 18000 60000            Main body Hook    Canvas air passage    Waist shaped hole Belt      fixed board    a Outside    vA frame  cans    Fig 5 17    Ceiling    Outside frame     For 18000 48000 I      3 Fix the outside frame and the canvas air passage with screws     E Screw must be fixed on from the bottom to the top     it i Canvas air passage    Screw  Ceiling    4 Hang up the outside frame until it sticks to the ceiling tightly     Fig 5 18    Main body         Canvas air passage    Ceiling     For 18000 60000  Fig 5 19           Main body    Air pa sage    Canvas air passage    Ceiling Outside frame     For 18000 48000 I      installation manual    8       5 Fix the main body and the outside frame with the fix board of    waist shape hole  in two places      E Hang one si
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
Pfister 0X8-340A Installation Guide  pmi14v-f112-...-io-... handbuch  IAN 87797 - Lidl Service Website  DataSheet SDS1000CFL Series Digital  2010年9月期 第1四半期決算短信(PDF:322KB)  Titre II. - Orthèses et Prothèses externes  BBP33 - manuel  取扱説明書    Copyright © All rights reserved. 
   Failed to retrieve file