USER MANUAL FOR EXPLOSION PROTECTED

image

Contents

1. measurements of the isolation should be performed with the test voltage max 1000 V DC and a test current 1 mA between Neutral and earth conductor Phase and earth conductor Testing between the phase and neutral conductor is not allowed and will get the wrong value because the electronic ballast is connected to the input circuit For successful testing is necessary to disconnect the electronic ballast via NC switch when glass cover is opened e a ei e C ee vg Wiring diagram PSF 236 fafa e sis 36 W T8 1p E G13 G1 SB A 36 W T8 HHI th n E L7 black 1 mm2 LL SMP 07 12 N blue 1 mm2 Isolating switch green yellow 1 5 mm aE eo el blue 1 5 mm HN ea P black 1 5 mm2 LIS es 8 black 1 5 mm2 Li a t S black 1 5 mm2 CITES amp 5 7 gt ern USER MANUAL FOR EXPLOSION PROTECTED tel 049 222 900 FLUORESCENT LIGHT FITTING type PSF 236 fax 049 426 450 S maile tEPEX MEDEX Broj TEPEx RS 041 Datum 06 2014 www tepex hr 8 DIMENSION Se 200 _ Z 1370 a l x ae O Z v KH 6 2 M25 M8 7 J EF E E 800 9 SPARE PART AND ACCESSORIES OZNAKA ZA SKICA OZNAKA ZA NARUDZBU NARUDZBU i Ex e cable gland Diffuser PSF PSF236 20 120 SPU 25 SPU 25 Gasket PSF PSF236 20 130 Internal reflector oy PSF with lamp holder PSF236 20 140 Si Ja f Ceiling mounting PSF 30 110 G13 PSF set A PSF SMP 07 12 wT Pipe mounting PSF 30 120 lt a set El Ballast SMP 07 12 eer PSF PSF
2. product has been developed manufactured and tested according to the existing state of technique accordance with the standards EN 9001 2008 and EN ISO IEC 80079 34 2011 The product is in compliance with the LV Directive 2006 95 EC The product is in compliance with the RoHS Directive 2002 95 EC The product is in compliance with EMC Directive 2004 108 EC 5 DEGREE OF PROTECTION AND DATA Broj TEPEx RS 041 Certificate Marking Category and explosion protection Ambient temperature Mechanical protection Resistance to shock Class of protection Rated voltage Frequency Rated current Power factor Ballast lumen factor BLF End of life EOL Lifetime of ballast Lifetime of lighting source Light source Lampholder Cable entry Through wiring Central interlocking switch no load condition EXA 13 ATEX 0014 C E 2465 Il 2G Ex de mb IIC T4 Gb II 2D Ex tb IIIC T80 C Db 20 C lt Ta lt 50 C IP 66 IK 08 I PE protective earthing 220 240 V 10 50 60 Hz 0 33 A A 0 95 97 5 The electronic ballast type SMP 07 12 fulfills the requirements according to EN 61347 2 3 2011 simulation of the end of life effect of fluorescent lamps 70 000 hours at Tamb 40 C medium 10 000 hours long tube lifetime up to 70 000 hours only on special request fluorescent tube 36W T8 26 mm according to EN 60081 2008 A4 2012 G13 accordance EN 60061 1 2008 A45 2012 Two cable glands
3. 236 20 150 la AYAL MOUNN R e set Socket key SW8 PSF236 20 160 Ring bolt M8 PSF 30 140 PSF Metal cable glands for reinforced cable mounting set 21mm set Terminals 5x2 5mm PSF 30 160 10 INSPECTION MAINTENANCE REPAIR AND OVERHAUL Inspections are carried out in accordance with IEC 60079 17 2007 C 1 2008 general and special conditions of manufacturer and users Regulations and includes supervision of parts on which the explosion protection depends especially the housing diffuser cable gland plugs and seal are without rupture and damage the glands plugs terminals pressure screw intermediate gland screw of the glass cover are fastened with nominal torque All the repairs are performed by the manufacturer or the manufacturer s authorized personal and the original parts must be provided according to the product documentation all in accordance with EN 60079 19 2011 Overhaul and modifications are not allowed If repair or any other procedure are performed on the product by unauthorized person all producer responsibility for the product and the warranty and the manufacturer s declaration of conformity becomes invalid 6 7 gt ern USER MANUAL FOR EXPLOSION PROTECTED tel 049 222 900 FLUORESCENT LIGHT FITTING type PSF 236 fax 049 426 450 S Malle taper Gteper lik Broj TEPEx RS 041 Datum 06 2014 www tepex hr 11 RESPONSIBILITY AND AUTHORIZATION This instruction is the basic info
4. Ex e M25x1 5 for cable diameters 06 15 mm and two Ex e plug in accordance with EN 62444 2013 3 x 2 5 mm max 16 A or looping of the cables entry and exit on one side When the central interlocking switch is in position OPEN internal elements of the lamps are in no load condition electronic control gear head of G13 The interlocking switches power on a flashlight after closing the cover and rotate the lock switch in position CLOSE In case of failure or lack of one of the fluorescent tubes electronic control gear type SMP 07 12 shuts off the power to the malfunctioned fluorescent tubes 2 7 X een USER MANUAL FOR EXPLOSION PROTECTED tel 049 222 900 FLUORESCENT LIGHT FITTING type PSF 236 fax 049 426 450 e fail tEPEXMEPEX Nr Broj TEPEx RS 041 Datum 06 2014 www tepex hr Maximum number of lamps pieces Automatic circuit breaker per one automatic circuit breaker Ip B 10A lp C 10A Ip B 16A lpC 16A 28 Housing SMC polyester plastic reinforced with glass fiber color RAL 7038 Diffuser PC polycarbonate plastic Tightening torque pressure screw 2 5 Nm intermediate gland and plug 3 5 Nm plug in housing 4 Nm screw terminals 0 5 Nm Isolation stripping length of the 9mm connection wires Dimension 1370 x 200 x 130 L x W x H Weight 10 kg 6 TYPE NOMINAL MODEL LAMP NOMINAL LUMINOUS LAMP CODE a TYPE VOLTAGE FLUY lm HOLDER os WEIGHT PSF 236 2x36 W Bw 220 240
5. ING type PSF 236 e mail pore Broj TEPEx RS 041 Datum 06 2014 www tepex hr Replacing of the fluorescent tubes two contacts lamp holder G13 Set both ends of the fluorescent tube in the lamp holder grooves then perform the rotation of the fluorescent tubes in the left or right side Internal reflector with G13 lamp holders and T8 fluorescent tubes is with reflector hinges and reflector lends carriers attached to the base plate at six different sites three on each side Access to terminals is done with a screwdriver in a manner that is necessary to separate the two hinge bracket of the reflector lends on the same side by applying a moderate force with a screwdriver toward the downward direction 4 7 gt Gen USER MANUAL FOR EXPLOSION PROTECTED tel 049 222 900 FLUORESCENT LIGHT FITTING type PSF 236 fax 049 426 450 e mail pore Broj TEPEx RS 041 Datum 06 2014 www tepex hr Gaining access to the terminals is achieved by rotating assembly of the reflector Note it is possible to separate the three hinge reflector lends from the bracket and gain access to the other side of the terminals by rotating assembly of the reflector lends to the other side Closing is done in reverse order of actions by bringing hinge reflector lends back to mount of the reflector lends only by light hand pressure With the commissioning the control
6. V 2 x 3350 0 33 A t0ks t0ks 7 MOUNTING AND INSTALATION Fluorescent lighting fitting comes standard with fluorescent tubes special wrench for open the lid two Ex e cable glands M25 for cable 6 l15mm two Ex e plug M25 and accessories for suspension assembly PSF 30 150 The lamp is designed for indoor and outdoor use Notes for safe installation and assembly gt Check the ambient temperature gt Possibility of installation in hazardous areas 1 2 21 22 gt Checking of cable entry into the fluorescent lighting fitting compromised mechanical protection IP number gt Damage lamps distort explosion protection of the area in which it is installed Opening and closing of the fluorescent light fitting Remove the rubber protection on the central lock switch Turn the central axis 180 to the left marking OPEN with a socket wrench Sliders release transparent cover and the lamp opens When closing follow the orders of operations in reverse When closing pay special attention to the positioning of the seal slot in the cover relative to the housing gt By turning the central lock switch the fluorescent light fitting is in no load state gt The main connections terminals L N gt In the open position the mechanical lock prevents access to the interlocking switches USE MODERATE FORCE WHEN OPENING 3 7 0 0 USER MANUAL FOR EXPLOSION PROTECTED ae FLUORESCENT LIGHT FITT
7. X oo USER MANUAL FOR EXPLOSION PROTECTED a ee FLUORESCENT LIGHT FITTING type PSF 236 fax e mail pore Broj TEPEx RS 041 Datum 06 2014 www tepex hr CONTENT L Manufacturer 1 2 General safety informations 1 j Purpose 2 4 Product compliance 2 5 Degree of protection and technical data 2 6 Type 3 7 Mounting and installation 3 8 Dimensions 6 9 Spare part and accessories 6 10 Inspection maintenance repair and overhaul 6 11 Responsibility and authorization 7 I2 Storage and transport 7 13 Manufacturer s transport 7 14 Marking 7 1 MANUFACTURER TEP Ex d o o Prilaz dr Franje Tu mana 6 HR 49210 ZABOK Tel 385 49 222 900 Web www tepex hr l2 GENERAL SAFETY INFORMATIONS A WARNING The user manual contains basic information about the product Mounting installation usage and maintenance should be carried out under this user manual to provide and ensure safe operation within the nominal characteristics This user manual complement national Regulation and Standards The responsible person shall ensure their implementation Failure off implement this user manual can reduce explosion protection and endanger people property and the environment Any improper and illegal actions as well as non compliance with the provisions of this user manual excludes all responsibility by manufacturer side Before installation commissioning Carefully read all instructions Execute proper training of respon
8. ide housing TErEx e HR 10090 Zagreb aes PSF 236 230 240V 50 60Hz 2x36W T8 G13 IP66 C I12G Ex d e mb IIC T4 Gb gt 12D Ex tb IIIC T80 C Db EXA 13 ATEX 0014 20 C lt Ta lt 50 C MA DAT text on diffuser of the tool A V Ss VARNING POTENTIAL ELECTROSTATIC CHARGING HAZARD CLEAN ONLY WITH A DAMP CLO A gt 7 7
9. rmation about the product It is completed by the corresponding national laws and regulations Production use certification and supervision are determined at the national level a Regulations concerning equipment and protective systems intended for use in potentially explosive atmospheres EU directive 94 9 EC ATEX 94 b Regulations on minimum requirements for safety and health protection of workers and technical inspection of facilities equipment installations and equipment in hazardous areas EU directive 1999 92 EC ATEX 137 The responsible person shall ensure their implementation at the working facility 12 STORAGE AND TRANSPORT Transportation and warehousing of the lamps is only allowed in the original packaging as outlined in a cardboard box 13 MANUFACTURER S WARRANTY The manufacturer provides a warranty on the product for a period of one year under the provisions of this user manual and the law on obligations This statement has the force of Warranty sheet 14 MARKING Explosion protected fluorescent lighting fitting type PSF 236 is marked with marking label on housing of lamp with technical and certification data Ex HR 10090 Zagreb Saa P PSF236 230 240V 50 60Hz 2x36 WT8G13 IP66 I2GExdemb IIC T4 Gb Il 2D Ex tb IIIC T80 C Db EXA 13 ATEX 0014 20 C lt Ta lt 50 C MA DAT OPEN CLOSE label with technical and certification data on internal reflector ins
10. sible personnel Check that the contents of these instructions is fully understandable by the responsible personnel Make sure that all the requirements and national Regulations as well as all special security measures are applied In lack of understanding Contact the manufacturer During operation Ensure that this user manual and other work instructions are available to the responsible staff at all times Check the implementation of these instructions and all other safety user s instructions 1 7 X d 0 0 tel 049 222 900 fax 049 426 450 e mail tepex tepex hr www tepex hr USER MANUAL FOR EXPLOSION PROTECTED FLUORESCENT LIGHT FITTING type PSF 236 3 PURPOSE Explosion proof fluorescent lighting fitting type PSF 236 is intended for use in industrial areas endangered explosive atmosphere in Zones 1 2 and in areas endangered by explosive and flammable mixtures of dust and air in Zones 21 22 accordance with EN 60079 10 1 2 2009 Ex fluorescent light fitting is used as fluorescent lighting fitting with two T8 26mm 36W 2G13 fluorescent lamp in parallel configuration 4 PRODUCT COMPLIANCE The product is in compliance with Regulations concerning equipment and protective systems for use in potentially explosive atmosphere NN br 34 10 The product complies with the ATEX Directive 94 9 EC and standards EN 60079 0 2012 EN 60079 1 2007 EN 60079 7 2007 EN 60079 18 2009 EN 60079 31 2009 The