Noby-65 Installation Manual Rev.1
Contents
1. 6 Intruder Fire Water Combined Alarm Installation Manual and User Operating Instructions TABLE OF CONTENTS First Power Up Power Supply Unit Input amp Detection Circuits Output amp Alarm Circuits Keyswitch Options Remote Signalling Equipment Technical Specification Connection Diagrams User Operating Instructions For your safety This equipment is to be installed serviced and maintained by a suitably qualified technical person with the requisite knowledge of electrical and fire safety installations The Noby 65 is intended to be permanently connected to the 230VAC house wiring via a 2A fused spur and in accordance with local wiring regulations Part of the internal circuitry operates at 230VAC and presents an electrical shock hazard Do not attempt to open dismantle repair or tamper with this equipment without first disconnecting the 230VAC supply voltage This is Class 1 electrical equipment and must be earthed gt gt o BPP Please read this Installation Manual carefully and retain for future reference Noby 65 Installation Manual amp Operating Instructions Rev 1 Page 1 of 12 FIRST POWER UP We strongly recommend that the Noby 65 is first powered up with all 10K End Of Line resistors fitted at the panel as supplied by the factory In this way you can gain confidence that the panel is operating correctly before introducing detector and sounder circuits Power Up With Battery e T
2. Shipping Weight 4 5 Kg Noby 65 Installation Manual amp Operating Instructions Rev 1 Page 7 of 12 Exit Entry Zone 1 Zone 2 Door Window EOL rl 5 Sab Alm Window Foil teta aj Final Exit Door 5 Sab Water Detectors Fire Smoke Detectors Noby 65 P2 Lid Switch wE OOOO000000000 Entry 0 Ov 0 0 Ov 0 Timer Timer water Sap Panic EX Zone 24 25 o 0 605 10 3605 Keyswitch Connection T 5 5 n DOODO Figure 2 Detection Circuits Wiring Diagram Noby 65 Installation Manual amp Operating Instructions Rev 1 Page 8 of 12 Intruder Siren atl atl 414 F 471 12 Fire JV Diode Sounder _ uS 4 Intruder X Bell 230VAC Power Figure 3 Alarm Outputs Wiring Diagram amp External Keyswitch Figure 4 NobyCode NC 02 Connection External Keyswitch Connection s gt 5 Troe mia 11 Link Solenoid Motorised Water Valve Internal Piezo Buzze
3. conditions Terminal B10 is a 12v supply fused at F1A sharing a common fuse F6 together with the Water Alarm Output Terminal B11 is an open collector npn transistor output switching from 12v to Ov The Noby 65 emits the following Buzzer tones i Exit Time Continous steady tone ii Entry Time Slow pulsing tone 1Hz iii Alarm amp Faults Fast pulsing tone 2Hz It is recommended that the Internal Warning Buzzer or piezo sounder can be heard outside the Final Exit Door so that the keyholder can hear the Exit Time finish and be confident that the Noby 65 is fully armed Following an alarm condition the Buzzer will continue to sound until the keyswitch is turned to OFF Duress Panic Signal B12 A positive going 12V 10mA signal output B12 which latches on receipt of a Duress or Panic alarm condition This output is cleared by performing a System Reset This signal is provided to trigger Remote Signalling Equipment PIR Memory SW Signal B13 A positive going 12V 10mA signal output B13 switching to 12V when the Noby 65 is either Full Set or Part Set This signal can be used to control the latching LED function of PIR detectors connected to Zone 1 or Zone 2 To reset a latched PIR detector i turn the Keyswitch to FULL ii allow the Exit Time to finish iii turn the Keyswitch to OFF The SW signal can also trigger Remote Signalling Equipment to transmit an Open Close signal to a central monitoring station Note Som
4. is not covered by the warranty Noby 65 Installation Manual amp Operating Instructions Rev 1 Page 2 of 12 POWER SUPPLY UNIT The PSU provides a regulated voltage rail of 13 6v nominal 12v with a continuous current rating of 1 5A and a 20 minute rating of 2 0A The PSU is designed to meet the internal standby power requirements of the Noby 65 and also to charge and maintain the 7Ah SLA battery in optimum condition The battery standby time is dependant upon the overall system current drawn including all connected equipment Also it is strongly recommended that the continuous system standby current does not exceed 1 0A because some reserve PSU capacity must be available to recharge the battery following an alarm condition or a prolonged period of 230VAC power loss The Noby 65 enclosure can accommodate one 12v 7Ah SLA battery The PSU is monitored for loss of 230VAC power low battery voltage and a Battery Condition load test is performed every 12hrs PSU faults are indicated by a flashing Power LED and the Fault LED together with an audible pulsing fault tone at the Buzzer output Always ensure that the maximum current drawn in alarm does not exceed the 3 0A battery fuse limit F3 The PSU is monitored for PSU Fault LED Status i 230VAC Absent or Fuse F2 blown Power LED is off after a 10s delay ii 230VAC Restored Power LED flashes memory iii Low Battery Voltage Power LED flashes Fault LED is lit when the voltage l
5. Fused Outputs F1 30VAC Transformer Secondary 2 0 A T2A 20mm Quick Blow F2 Auxillary 12v Supply 500 mA F500mA 20mm Quick Blow F3 Battery ve 3 0 A T3A 20mm Quick Blow F4 Fire Alarm Outputs 1 0 A F1A 20mm Quick Blow F5 Intruder Alarm Output 1 0 A F1A 20mm Quick Blow F6 Water Alarm amp Internal Buzzer 1 0 A F1A 20mm Quick Blow Standby Battery Current 70 mA 9 EOL resistors fitted Low Voltage Monitor 10 0 volts Battery Condition Test Yes 10s load test every 12hrs Detection Circuits Value Unit Comments TT Zone 1 Zone 2 Exit Entry No Detection Circuits 7 Duress Panic Fire Water Sabotage Anti Tamper End Of Line EOL Resistor 10 000 ohms Open Circuit Monitoring R gt 17 000 ohms No Detectors Per Fire Zone 10 based 1000 per detector Fire Circuit Detection Threshold R lt 3000 ohms Alarm Output Circuits Value Unit Comments Intruder Alarm Output SPDT Relay 12v centre contact fuse F5 24Hr Fire Alarm Output 0 gt 12 volts open collector pnp transistor fuse F4 12Hr Fire Alarm Output 0 gt 12 volts open collector pnp transistor fuse F4 Water Alarm Output 12 20 volts open collector npn transistor fuse F6 Internal Buzzer Output 12 20 volts open collector npn transistor fuse F6 Signal Outputs Value Unit Comments Duress Panic Signal 10 mA Ov gt 12volt going signal SW Signal panel SET signal 10 mA Ov gt 12volt ve going signal Dimensions width x height x depth 368 x 275 x 75 mm 1 2mm powder coated steel
6. Perform a System Reset Cleaning Clean external surfaces with a damp cloth and mild detergent Do not use abrasives solvents or polish Noby 65 Installation Manual amp Operating Instructions Rev 1 Page 11 of 12 LED Indications 2 Flashes sec 1 Flash sec Power 230VACOK PSU or Battery Fault 230VAC restored Alarm or First To Alarm or Fault mreny steamy em eem Frat Toa Zone mne Pan Se Norwegian English WATER eue SET ALARM TAMPER PART Noby 65 Installation Manual amp Operating Instructions Rev 1 Page 12 of 12
7. Proceed directly through the Exit Route to the night time living area Zone 2 e Listen for the Exit Tone to stop Note All existing alarm conditions must be clear before attempting to arm the intruder system The Noby 65 will abort the Exit procedure in the event of a system fault or alarm and the buzzer will emit a rapid pulsing tone Perform a System Reset to clear the LEDs and try again Entry Procedure e Open the Final Exit Door A slow pulsing Entry Tone will commence e Proceed immediately to the Noby 65 control panel Do not stray from the Entry Route e Turn the Keyswitch to OFF The Entry Tone will stop Following an Intruder Alarm Turn the Keyswitch to OFF The Siren and Internal Buzzer will silence e Observe and note the red LEDs e Perform a System Reset To clear latched PIR LED indications e Turn the Keyswitch to FULL e Allow the Exit Time to finish e Turn the Keyswitch to OFF System Reset Momentarily turn the Keyswitch to FULL and then to OFF within 2s Observe a 2s LED test Note If the cause of an alarm still persists then the alarm will re trigger immediately following a System Reset To Silence the Alarm e Turn the Keyswitch to FULL for 4 seconds e Turn the Keyswitch to OFF Following a Fire Alarm or Water Alarm CARRY OUT THE PRESCRIBED EMERGENCY PROCEDURE Only when it is safe to continue e Silence the alarm e Observe and note the red LEDs which will identify the cause of the alarm e
8. e PIR detectors require a 10K pull down resistor to be connected from terminal B13 to OV Noby 65 Installation Manual amp Operating Instructions Rev 1 Page 5 of 12 KEYSWITCH OPTIONS Internal Keyswitch The Noby 65 has an internal keyswitch fitted as standard supplied with 4 keys The switch has the following positions i OFF All Intruder circuits are disarmed Other 24 hour circuits remain active ii FULL SET All Intruder circuits are armed Noby 65 is Full Set after the Exit Time iii PART SET Noby 65 is Part Set after the Exit Time with Zone 2 isolated External Keyswitch Connections B14 B15 B16 B17 The Noby 65 can be operated remotely by connecting an external keyswitch to terminals B15 B17 as shown in Figure 3 Note that switching terminal B15 to Ov causes the Noby 65 to Full Set whilst switching terminal B17 to causes the Noby 65 to Part Set Terminal B16 is the Ov connection Terminals B14 and B15 must be linked together for correct operation of the internal keyswitch An attractive alternative to a mechanical keyswitch is the Nobycode NC 02 Remote Keypad Figure 4 The NC 02 is specifically designed to control the Full Set Part Set and System Reset functions of the Noby 65 The 02 keypad also has 2 LEDs to remotely indicate the ON OFF status and the Alarm Fault status of the Noby 65 For additional security it is recommended to remove the two EOL resistors from the Noby 65 terminals and re connect them in the
9. e default mode of operation as supplied from the factory Alternatively the Noby 65 can be configured to give a full local audibles Panic alarm To configure the Panic Option i remove all power from the Noby 65 both battery and 230VAC power supply ii press the Panic Button such that the Panic Circuit is open circuit iii reconnect the power supply to the Noby 65 iv reset the Panic Button v reset the Noby 65 by performing a System Reset Important the Panic option will revert back to Duress in the event of total power loss to the Noby 65 Sabotage Circuit Anti Tamper A07 A08 The Sabotage circuit protects the Noby 65 from criminal interference or accidental damage This is a single circuit and should be routed around all the intruder detection circuits and through all lid switches The Noby 65 is supplied with an internal lid microswitch pre wired and fitted with a series 10Kohm EOL resistor at terminal A08 To insert new sabotage loops First unscrew the wire at terminal 07 and then connect any newly created loops between A07 and the free end of the microswitch wire For typical installations it is recommended to leave the EOL resistor in its original position at terminal A08 Fire Detection Circuit A03 A04 The Noby 65 incorporates a low power 12v 24v invertor which permits the use of industry standard 24v conventional smoke detectors Any combination of conventional optical or ionisation smoke detectors or rate of rise h
10. eat detectors can be connected The total steady state current taken from the Fire Detector terminals A03 amp 04 must not exceed 1mA Typically this equates to a maximum of 10 detectors assuming a rated current of 100uA per detector The Fire Detector Circuit is monitored for open circuit faults Water Alarm Detection Circuit A05 A06 This circuit is intended to accomodate water level float switches for use in flood detection Once triggered the Water Alarm Output can be used to shut off a water solenoid operated valve as shown in Figure 3 Although this circuit is labelled Water it can be used for other purposes e g a 24hr freezer alarm to give a warning of rising freezer temperature Noby 65 Installation Manual amp Operating Instructions Rev 1 Page 4 of 12 OUTPUT amp ALARM CIRCUITS Figure 3 shows the alarm outputs wiring diagram for a typical residential alarm system Intruder Alarm Relay Output B01 B02 B03 B04 The Noby 65 alarm siren output is provided at terminals 01 to BO4 Terminal 01 is Ov and terminals 02 and 04 are a set of make break relay contacts For most installations a Siren will be driven from this relay and for convenience the centre contact is connected to 12v via fuse F5 on the PCB This 12v feed can be diconnected by removing fuse F5 leaving a clean set of voltage free contacts rated at 30V 2 5A This alarm output relay is activated for a preset Siren Time adjustable from 10s to 360
11. ees a circuit resistance of 10kohm Any detection circuit not being used must have its EOL resistor connected at the Noby 65 terminals Auxillary 12v Detector Supply A01 A02 A 12V supply fused at F500mA F2 is provided at terminals A01 amp 02 to supply power for PIRs and other low power electronic detection devices Noby 65 Installation Manual amp Operating Instructions Rev 1 Page 3 of 12 Intruder Detection Circuits A11 A16 There are three intruder circuits Zone 1 Zone 2 and Exit Entry Each detection circuit may comprise any combination of i door or window magnetic contacts ii electronic detectors PIR ultrasonic or doppler microwave iii window foil iv vibration or glass break detectors V pressure mats Zone 1 is the main intruder detection circuit and is armed when the keyswitch is turned to FULL or PART Zone 2 is the secondary intruder detection circuit and is armed only when the keyswitch is turned to FULL Zone 2 is normally used to protect the night time living area in a house such that the occupants can freely move around without causing an alarm whilst the rest of the house is protected in Zone 1 Exit Entry is the area covering the direct path between the Noby 65 and the final exit door This circuit allows the keyholder to safely leave the property within a preset Exit Time On re entering the premises the Entry Tone will start and the keyholder must proceed directly to the Noby 65 panel and tu
12. nal block and switch on 60s Start up Period i All LEDs flash for 60s ii The Buzzer output will make a pulsing sound if connected After Start up i The green Power LED will flash ii The yellow Fault Alarm LED will be lit iii The red Sabotage LED is lit because Noby 65 lid is removed The 60s Start up Period can be prematurely terminated by turning the Keyswitch to FULL for 4s and then back to OFF e Perform a System Reset Momentarily turn the Keyswitch to FULL and then to OFF within 2s Observe a 2 second LED test e After System Reset i The green Power LED is lit 230VAC OK indication ii The yellow Fault Alarm LED is lit iii The red Sabotage LED is lit because Noby 65 lid is removed e Connect the black battery lead to the battery ve terminal e Connect the red battery lead to the battery ve terminal It is normal to see a small spark e Replace the Noby 65 panel lid observe the yellow Fault Alarm LED turn off e Perform a System Reset momentarily turn the Keyswitch to FULL and then to OFF within 2s Observe a 2s LED test e The panel should now be in a quiescent standby state with only the green Power LED lit IMPORTANT TAKE CARE TO CONNECT THE BATTERY CORRECTLY Whilst there is a measure of protection against accidental reverse connection of the battery such action will almost certainly blow fuse F3 and may cause permanent damage to the Noby 65 panel Such damage is identifiable to Noby UK Ltd and
13. r Suppressor Diode K e g 1N4001 12v DC Coil Isolation Relay 230VAC Contacts External Keyswitch Connection External Keyswitch L1L2 LEDS 12v Ov L1 L2 mele oleic nolo e 4 sab SNP E E Noby 65 Installation Manual amp Operating Instructions Rev 1 NOBYCODE NC 02 Page 9 of 12 End Of Line Resistors 10K F4 T2A T2A Timer CQ C 0 60s 10 360s I Sabotage 6 Detector External Keyswitch Connection 01102103104 05106 07 DHAHARA Red E 12v TAhr End Of Line Il Sealed Lead Acid Resistors 10K Black 1 Battery m I Figure 5 Noby 65 PCB Assembly INSTALLATION NOTES Noby 65 Installation Manual amp Operating Instructions Rev 1 Page 10 of 12 Noby 6 USER OPERATING INSTRUCTIONS Exit Procedure Full Set e Check that only the green Power LED is lit e Turn the Keyswitch to FULL SET e All LEDs illuminate for 2 seconds followed by a continuous Exit Tone e Proceed directly to the Final Exit Door Do not stray off the Exit Route e Leave the premises and listen for the Exit Tone to stop Part Set e Check that only the green Power LED is lit e Turn the Keyswitch to PART SET Zone 2 is isolated and the Zone 2 LED will flash slowly e All LEDs illuminate for 2 seconds followed by a continuous Exit Tone e
14. remote keyswitch housing such that any break in the cable will force the Noby 65 to either Full Set or Part Set the intruder system For high security installations it is also recommended to route the Sabotage circuit though the cable and connect through any lid microswitches REMOTE SIGNALLING EQUIPMENT AUTO DIALLER The Noby 65 cabinet can accomodate an Auto Dialler underneath the main circuit board assembly Figure 1 shows a typical Auto Dialler connection diagram The channel numbers may differ according to the signal priorities demanded by the remote central station Also take care to ensure that the Water Alarm channel is programmed to be a negative going input signal External Keyswitch Connection 0000000000000000 prose ETT OV Intruder ES Alarm Channels Remote Signalling Equipment Auto Dialler Figure 1 Auto Dialler Connections Noby 65 Installation Manual amp Operating Instructions Rev 1 Page 6 of 12 Noby 65 TECHNICAL SPECIFICATION Power Supply Unit Value Unit Comments Mains Supply Voltage 230 10 6 volts AC Mains Supply Frequency 50 60 Hz Mains Power Rating 30 VA Nominal Battery Voltage 12 volts Regulated PSU charger voltage 13 6 volts Regulated PSU charger current 20 minute rating 2 0 A e continuous rating 1 5 A
15. rn the keyswitch to OFF Straying off the Exit Entry route into an area protected by Zone 1 or Zone 2 will trigger an immediate alarm condition Electronic detection devices e g PIRs are powered from the Auxillary 12v supply terminals A01 amp A02 fused at 500mA F2 Warning do not to overload this 12v supply As a rough guide each PIR draws 25mA The latching LED function of PIRs can be controlled by connecting the appropriate PIR terminal often called SW Set C or Control to the SW signal appearing at terminal B13 This signal is normally Ov and switches to 12v when the Noby 65 is fully armed i e after the Exit Time period This SW signal can also be used to signal a System Set Open Closed signal for Remote Signalling Equipment Pressure Mats must be connected between the two cores of the detection circuit such that the EOL resistor becomes short circuit in alarm The cable for each circuit may require up to 7 cores 2 cores for the alarm detection circuit 2 cores for the detector supply 1 core for the SW signal and 2 cores for the Sabotage circuit Anti Tamper Any spare cores should be used to stiffen the detector Ov power connection Duress Panic Personal Attack A09 A10 Activating the Duress Panic Circuit will trigger a silent Duress response at signal output B12 A silent Duress alarm is sometimes the preferred option for systems employing Remote Signalling Equipment For personal safety reasons Duress is th
16. s P3 It is recommended to use polarised sirens or bells fitted with a suppressor Fire Alarm Ouput B05 B06 B07 The following two fire sounder outputs are fused at F1A Fuse F4 i the 24hr terminal 05 gives a fire alarm at all times even when the keyswitch is OFF ii the 12hr or SET terminal 07 activates only when the keyswitch is turned to FULL or PART Both terminals are open collector pnp transistor outputs and switch to 12v during a fire alarm condition It is recommended to use polarised sirens or bells fitted with a suppressor Water Alarm Output B08 B09 Terminal 08 is a 12v supply fused at F1A sharing a common fuse F6 together with the Buzzer Output Terminal B09 is an open collector npn transistor output switching from 12v to Ov on detection of a Water Alarm condition This output is suitable for driving a siren bell or sounders Alternatively it is possible to activate a Solenoid Water Valve to disconnect the water supply Note that in most cases a 230VAC isolating relay is required to operate the Solenoid Valve It is recommended to fit a suppressor diode across the relay coil to prevent damage due to high voltage transients as shown in Figure 3 Some relays are supplied with a suppressor fitted internally IMPORTANT DO NOT CONNECT 230VAC DIRECTLY TO THE NOBY 65 TERMINALS Internal Warning Buzzer Output B10 B11 This output is provided at terminals B10 amp B11 for audible indication of warning and fault
17. t 10 0v iv Battery Condition or Fuse F3 blown Power LED flashes Fault LED is lit INPUT amp DETECTION CIRCUITS Figure 2 shows the detector wiring diagram for a typical residential alarm system Detection Circuit Terminal No Description Intruder Zone 1 A13 amp A14 Intruder alarm circuit PIRs and contacts 15 amp 16 Intruder alarm circuit PIRs and contacts Zone 2 Isolated when Part Set Delayed intruder alarm circuit for the Entry Exit route Intruder Exit Entry 11 amp A12 Entry timer adjustable 0 120s Exit timer adjustable 0 120s PIRs and contacts Duress Panic Circuit A09 amp A10 24hr circuit Fire Detectors A03 amp 04 24hr circuit 24v optical amp ionisation smoke or rate of rise heat detctors Water Detectors A05 amp A06 24hr circuit Water float switches sabotage Circuit 07 amp 08 24hr circuit This circuit Includes the Noby 65 lid microswitch Anti Tamper End Of Line Resistors The Noby 65 requires that all detection circuits be terminated with a 10K End Of Line resistor to facilitate open circuit fault monitoring For maximum security the EOL resistors should be connected at the last detection device at the end of each cable run and for this reason it is advised to daisy chain the cable with no T junctions Only one EOL resistor is permitted on each circuit such that in steady state condition the Noby 65 s
18. urn the Keyswitch to the OFF position e Connect the black battery lead to the battery ve terminal e Connect the red battery lead to the battery ve terminal It is normal to see a small spark 60s Start up Period i All LEDs flash for 60s ii The Buzzer output will make a pulsing sound if connected After Start up i The green Power LED flashes ii The yellow Fault Alarm LED is lit iii The red Sabotage LED is lit because Noby 65 lid is removed The 60s Start up Period can be prematurely terminated by turning the Keyswitch to FULL for 4s and then back to OFF e Perform a System Reset Momentarily turn the Keyswitch to FULL and then to OFF within 2s Observe a 2s LED test e After System Reset i The green Power LED is off because the 230VAC is absent ii The yellow Fault Alarm LED is lit iii The red Sabotage LED is lit because Noby 65 lid is removed Connect 230VAC supply to the 230v 50Hz AC screw terminal block e Replace the Noby 65 panel lid observe the yellow Fault Alarm LED turn off e Switch on the 230VAC power and observe the green Power LED flash indicating 230VAC restored e Perform a System Reset momentarily turn the Keyswitch to FULL and then to OFF within 2s Observe a 2s LED test e The panel should now be in a quiescent standby state with only the green Power LED lit Power Up With 230VAC e Turn the Keyswitch to the OFF position e Connect a 230VAC power supply to the 230v 50Hz AC screw termi