PRO75D 100A MID User manual
Contents
1. EN 50470 1 2006 Electricity metering equipment a c part 1 General requirements tests and test conditions Metering equipment class indexes A B and C EN 50470 3 2006 gt Electricity metering equipment a c part 3 Particular requirements Static meters for actve energy Class indexes A B and C Valid until June 11 2020 The results are recorded in the following annex test report 70965037 TDT 6335 10 KEMA Quality B Ne Amhem J r s ir APA ir P J J G Nabuurs Certificati Managing Director The investgation reported here does nat conter any right to use an approbation mark granted by KEMA ci publication of this certificate and adjoining reports is allowed This certificate a issued provided that KEMA not assumes ary lability KEMA Nedestand 8 V Utrechtseweg 310 6812 AA Arnhem The Netherlands F O Box 9095 6900 ET Amham The Nethertands 7431 0106 3 56 2215 F431 0175 4 426211 CSMGheme com awwkera com Irade register Amber Expenence you can trust DMMetering R 2011 5 PRO75D 100A MID User manual 0018 MID conformitity certificate Declaration of Conformity We Inepro Metering BV Of inepro Metering BV Pond weg 7 2153 PK Nieuw Vennep The Netherlands Ensure and declare that the apparatus PRO 75A PRO 75D PRO 75D Modbus With the measurement range 230V 10 100 A 50 or 60Hz 1600imp kWh are in conformity with the type as described in the EC type examination certificate 63
2. PRO75D 100A MID DIN rail single phase two wire energy meter User manual Version 1 12 DMMetering L oan y MNS UCONN S e E E 3 2 TO WO e E E A E EET 4 r MID Cero cate sra 5 4 MID conformitity ae gales i a a ee ee ee eee 6 GE COC ate mataran 7 6 Performance cnt ares 8 FSGS CAMO Son idos iaa 8 A a A Po o E E 8 J 1D 6 0 0 0 y OPA UA O aednateteces dindecenesadezand 9 PO DIMEN ION AMA e o oe 10 1D A pis lalo y PA e o A 10 E nn E E E E RA 11 12 1 COn UNP A O sanar arar 11 122 Reverse A O anar E A 11 12 3 Reading the meter evocan a 11 1244 PUSS OUUTE E E E E E 11 O TROUDICS AOON E IE T A EEA 12 14 EC SUDDO oaa iii 15 pmmMetering 2011 2 PRO75D 100A MID User manual 0018 1 Safety instructions Information for your own safety This manual does not contain all of the safety measures for operation of this meter because special operating conditions local code requirements or local regulations may necessitate further measures However it does contain information which must be adhered to for your own personal safety and to avoid material damage This information is highlighted by a warning triangle with an exclamation mark or a lightning bolt depending on the degree of actual or potential danger Caution This means hazard of electric shock and failure to take the necessary safety precautions Warning This means that failure to observe the instruction can result in death serious injury or co
3. e Do not touch the meter s connection clamps directly with your bare hands with metal blank wire or other conducting material as you will risk an electric shock that could cause possible injury serious injury or death e Make sure the protection covers are replaced after installation Maintenance and repair of the meter should only be carried out by qualified personnel e Never break any seals if present on this meter to open the front cover as this might influence the functionality or accuracy of the meter and will void all warranty e Do not drop or allow physical impact to the meter as there are high precision components inside that may break and affect the meter measurement negatively pmmMetering 2011 3 PRO75D 100A MID User manual 0018 e All clamps should be properly tightened e Make sure the wires fit properly in the connection clamps e If the wires are too thin it will cause a bad contact which can spark causing damage to the meter and its surroundings Exclusion of liability We have checked the contents of this manual and every effort has been made to ensure that the descriptions are as accurate as possible However deviations from the description cannot be completely ruled out so that no liability can be accepted for any errors or omissions in the information given The data in this manual are checked regularly and the necessary corrections will be included in subsequent editions If you have any suggestions ple
4. 35 10 and satisfy the appropriate requirements of the Directive 2004 22 EC June 11 2010 ES f Apice Daan van der Vaart 6 DMMeterisg R 2011 PRO75D 100A MID User manual 0018 5 CE certificate Inepro Supote s Deciaradon of Gonrformity The basis for the critena hes been found in intamational documentation particularly in 150 IEG Guide 22 1982 Informa on on manufacturers Declaration af Conformiy wath standards or other DMMetering 2011 We Inepro Metering BV ero les Pit Niouw Vennep The Netherlands declare under our sole responsibility that the products PRO T5D PRO75D MODBUS Single phase DIN rail Watt Hour Meter to which this declaration relates in confonmity with the following European harmonized and published standards af date of this declarationc IEC EN 50470 Following the provisions of the Directives if applicable BH 2004 22 EG These conclusions are based on the test reports done by KEMA with report numbers 6335 10 with Notified Body number 0344 Nieuw Vennep 2010 June 11 Place and date of issue f s PRO75D 100A MID User manual 0018 6 Performance criteria Operating humidity Storage humidity Operating temperature Storage temperature International standard Accuracy class Protection against penetration of dust and water Insulating encased meter of protective class 7 Specifications Meter type Nominal voltage Un Operationa
5. al as that will cause an electric shock and possibly cause injury serious injury or even death Turn off and if possible lock all sources supplying the energy meter and the equipment that is connected to it before opening the protection cover and working on it Turn off and lock all power supply to the energy meter and the equipment to which it is installed before opening the protection cover to prevent the hazard of electric shock AN Maintenance or repair should only be performed by qualified personnel familiar with applicable codes and regulations Use insulated tools to maintain or repair the meter Make sure the protection cover is in place after maintenance or repair The case is sealed failure to observe this instruction can result in damage to the meter DMMeteriasg R 2011 A PRO75D 100A MID User manual 0018 Problem The power supply indicator L1 is off The consumption LED is not flashing PULSE LED DMMetering Q 2011 Possible cause The meter is not connected to a power source Li and N are not connected correctly There is no 230V AC between the N and one of the L connections when power is supplied to the meter There is no 400V AC between the L connections when power is supplied to the meter is no load to the There connected meter The load on the line is very low There is a fault inside the meter f 3 Check solution Are the fuses or and surg
6. ase do not hesitate to contact us Subject to technical modifications without notice Copyright Copyright Inepro Metering June 2011 All rights Reserved It is prohibited to pass on or copy this document or to use or disclose its contents without express permission of Inepro Metering BV Any duplication is a violation of the law and subject to criminal and civil penalties All rights reserved particularly for pending or approved patent awards or registered trademarks Registered trademarks DMMetering is a registered trademark of Inepro Metering BV member of the Inepro Group Other names appearing in this manual may be trademarks of third parties and are property of their respectful owners 2 Foreword Thank you for purchasing this energy meter Inepro has a wide product range of devices We have introduced a large number of energy meters on the market suitable for 110V AC to 400V AC 50 or 60Hz Besides the normal energy meters we also developed our own pre paid meters with chip card chip card re loaders and a complete PC management control system For more information on other products please contact our sales department at sales ineprometering com or visit our website at www ineprometering com Although we produce this device according to international standards and our quality inspection is very accurate it s still possible that this device shows a defect or failure for which we do apologize Under normal conditions your product
7. e protection defect Make sure the wires are connected properly and tighten the screws if possible Check if there is 230V AC voltage between N and one of the L connections with a volt meter Check if there is 400V AC volt between N and one of the L connections with a voltage meter If the checks above don t solve the problem please contact technical support for a meter replacement Connect a load to the meter Check with an Ohm meter if the load value is very low If the checks above don t solve the problem please contact technical support for a meter replacement PRO75D 100A MID User manual 0018 Problem The register doesn t count No pulse output The pulse output rate is wrong DMMetering 2011 Possible cause There is almost no load connected to the meter iS a the Maybe there fault inside meter The pulse output is not supplied with DC power The pulse output is not connected correctly iS a the there inside Maybe fault meter iS a the there inside Maybe fault meter 14 Check solution Check if the consumption LED is flashing 160 flashes of the LED at 1600 pulses per kWh equals 0 1kWh and should be clearly visible on the display Please contact technical support for a meter replacement Check the external voltage source Ui is 5 27V DC with a voltage meter Check if the connection is correct the 5 27V DC should be connec
8. eter can be installed indoor or outdoor enclosed in a meter box which is sufficiently protected in accordance with local codes and regulations To prevent tampering an enclosure with a lock or a similar device can be used The meter has to be installed against a fire resistant wall The meter has to be installed in a well ventilated and dry place The meter has to be installed in a protective box if the meter is exposed to dust or other contaminants The meter can be installed and used after being tested and can be sealed afterwards The device can be installed on a 35mm DIN rail The meter should be installed on a location where the meter can be read easily DMMeteriasg R 2011 10 PRO75D 100A MID User manual 0018 e In case the meter is installed in an area with frequent surges for example due to thunderstorms welding machines inverters etc the meter is required to be protected with a Surge Protection Device e The black pins closing the protection covers are made as placeholders please use these accordingly e The device should be sealed immediately after installing it in order to prevent tampering e Connection of the wires should be done in accordance with the connection diagram as shown below HM H 1 2 Phase line IN OUT L 3 4 Neutral line IN OUT N 5and6 Test pulse output contact 12 Operation 12 1 Consumption indication There is a red LED with the text 1600imp kWh above it on the front panel which indica
9. gy meter and the equipment that is connected to it before working on it Always use a properly rated voltage sensing device to confirm that power is off Fs The installation should be performed by qualified personnel familiar with applicable codes and regulations Use insulated tools to install the device A fuse thermal cut off or single pole circuit breaker should be fitted on the supply line and not on the neutral line The connecting wire connecting the device to the outside circuit should be sized in accordance with local regulations for the maximum amount of the current breaker or other overcurrent protection devices used in the circuit An external switch or a circuit breaker should be installed on the supply wires which will be used to disconnect the meter and the device supplying energy It is recommended that this switch or circuit breaker is placed near the meter because that is more convenient for the operator The switch or circuit breaker should comply with the specifications of the building s electrical design and all local regulations An external fuse or thermal cut off used as an overcurrent protection device for the meter must be installed on the supply side wires It s recommended that this protection device is also placed near the meter for the convenience of the operator The overcurrent protection device Should comply with the specifications of the building s electrical design and all local regulations This m
10. l voltage Insulation capabilities AC voltage withstand Impulse voltage withstand Basic current Ib Maximum rated current Imax Operational current range Over current withstand Operational frequency range Internal power consumption Test output flash rate Pulse output rate Data save 8 Basic errors 0 05Ib Cos 1 0 1Ib Coso 0 5L Cos 0 8C 0 1Ib Imax Cos 1 0 2Ib Imax Coso 0 5L Cosp 0 8C DMMetering R 2011 ate cee lt 75 lt 95 10 C 40 C 30 C 70 C EN50470 3 1 IP51 II PRO75D 100A MID 230 400 AC 3 161 299V AC 4KV for 1 minute 6KV 1 2uS waveform 10A 100A 0 4 Ib Imax 30Imax for 0 01s 50Hz or 60 Hz 10 lt 2W 10VA 1600imp kWh 1600imp kWh The data can be stored for more than 10 years without power 11 5 1 5 11 5 11 0 1 0 1 0 PRO75D 100A MID User manual 0018 9 Description 0UNWS Material Front panel Cover Base DMMetering 2011 Lay ion OOO J Ts P 7 O EN Front panel Cover Base Security wire PC flame resistant plastic ABS flame resistant plastic ABS flame resistant plastic agn PRO75D 100A MID User manual 0018 10 Dimensions Height 130 mm Height without protection cover 100 mm Width 76 mm Depth 65 mm Size of the connection clamp 10 x 8 mm Weight 0 2 Kg net 11 Installation A CAUTION Turn off and if possible lock all sources supplying the ener
11. nsiderable material damage A will result in death serious injury or considerable material damage Qualified personnel Installation and operation of the device described in this manual may only be performed by qualified personnel Only people that are authorized to install connect and use this device who have the proper knowledge about labeling and grounding electrical equipment and circuits and can do so in accordance with local safety regulations are considered qualified personnel in this manual Use for the intended purpose This device may only be used for the application cases specified in the catalog and the user manual and only in connection with devices and components recommended and approved by Inepro Metering B V Proper handling The prerequisites for perfect reliable operation of the product are proper transport storage installation and connection as well as proper operation and maintenance During its operation certain parts of the meter might carry dangerous voltages Only use insulated tools suitable for the voltages this meter is used for Do not connect while the circuit is connected to a power or current source Only place the meter in a dry environment Do not mount the meter in an explosive area or exposed to dust mildew and or insects Make sure the used wires are suitable for the maximum current of this meter Make sure the AC wires are connected correctly before activating the current voltage to the meter
12. should give you years of trouble free operation In case there is a problem with the energy meter you should contact your distributor immediately Most of our energy meters are sealed with a special seal Once this seal is broken there is no possibility to claim any warranty Therefore NEVER open an energy meter or break the seal of the device The warranty period is 3 years after production and only valid for production faults DMMetering R 2011 4 PRO75D 100A MID User manual 0018 3 MID certificate CERTIFICATE EC Type examination certificate 6335 10 Manufacturer inepro Metering BY Contact person D van der Vaart Address P O Box 92 2450 AB Leimuiden Country The Netherlands instrument Electronic single phase two wire energy meter Direct commected Mark Type PRO 75A PRO 75D PRO 75D MODBUS Register Mechanical LCD LCD Accuracy Class 4B Measurement range 230V 10 100 A 50 or 60 Hz 1600 imp kWh Temperature range gt 10 40 C Use Indoor Protection Class AED Environmental class M1 E2 Registry method bidirectional method with always positive register the mater always counts the energy of the measuring point as received energy irrespective of the real energy direction The energy meter meets the requirements of Directive 2004 22 EC of the European parliament and the council of 31 March 2004 on measuring instruments Certification was based on compliance with the following harmonised standards
13. ted to the collector connection pin 6 and the signal wire S to the emitter connection pin 5 Please contact technical support for a meter replacement Please contact technical support for a meter replacement PRO75D 100A MID User manual 0018 14 Technical support For questions about one of our products please contact Your local Inepro Metering distributor Email support ineprometering com www ineprometering com DMMeteriasg R 2011 Se PRO75D 100A MID User manual 0018 This page is left blank on purpose DMMeteriasg R 2011 aG PRO75D 100A MID User manual 0018 This page is left blank on purpose RoHS COMPLIANT E 2002 95 EC DMMeteriasg R 2011 e lt PRO75D 100A MID User manual 0018
14. tes the power consumption measured by the meter When power is consumed the LED will flash The faster the LED flashes the more power is consumed For this meter the LED flashes 1600 times per kWh 12 2 Reverse indication A red LED with the text Reverse above it will lighten when the meter load current flow is running in reverse direction 12 3 Reading the meter The energy meter is equipped with 5 2 LCD display which is used to in record consumption and can t be reset to zero without breaking the seal The reading accuracy is 1 100 kWh 12 4 Pulse output The energy meter is equipped with a pulse output which which is optically isolated from the inside circuit It generates pulses in proportion to the measured consumption for purpose of remote reading or accuracy testing The pulse output is a polarity dependent open collector transistor output requiring an external voltage source for correct operation For this external voltage source the voltage Ui should be 5 27V DC and the maximum input current Imax is 27mMA DC To connect the impulse output connect 5 27V DC to connector 6 collector and the signal wire S to connector 5 emitter DMMeteriasg R 2011 di PRO75D 100A MID User manual 0018 A miw 5 5 emitter 6 collector 13 Troubleshooting A CAUTION During repair and maintenance do not touch the meter connecting clamps directly with your bare hands with metal blank wire or other conducting materi